Vous êtes sur la page 1sur 464

EDSG281001

[50Hz]
RXS, RKS, RZR series

EDSG281001

Part 1 SkyAir Inverter Series ....................................................... 1


1. External Appearance...............................................................................3
2. Model Name, Power Supply and Nomenclature .....................................4
2.1 Model Name and Power Supply...............................................................4
2.2 Nomenclature ...........................................................................................5

3. Functions.................................................................................................6
3.1 Indoor Unit................................................................................................6
3.2 Outdoor Unit .............................................................................................7

4. Specifications ..........................................................................................8
5. Dimensions and Service Space ............................................................25
5.1
5.2
5.3
5.4
5.5

Indoor Unit..............................................................................................25
Wired Remote Controller........................................................................39
Wireless Remote Controller ...................................................................41
Outdoor Unit ...........................................................................................43
Installation Service Space ......................................................................49

6. Piping Diagrams....................................................................................55
6.1 Indoor Unit..............................................................................................55
6.2 Indoor Unit + Outdoor Unit .....................................................................57
6.3 Outdoor Unit ...........................................................................................62

7. Wiring Diagrams....................................................................................66
7.1 Indoor Unit..............................................................................................66
7.2 Outdoor Unit ...........................................................................................72
7.3 Field Wiring ............................................................................................80

8. Electric Characteristics..........................................................................81
8.1 RXS50FAVMA / RXS60FVMA / RXS71FVMA
RKS25AVMG / RKS35AVMG / RKS50AVMG / RKS60AVMG ..............81
8.2 RZR71KUV1 / RZR100KUV1 / RZR125KUV1 / RZR140KUV1 .............82
8.3 RZR100HUY1 / RZR125HUY1 / RZR140HUY1 ....................................84

9. Capacity Tables ....................................................................................86


9.1 Capacity Tables......................................................................................86
9.2 Capacity Correction Factor by the Length of Refrigerant Piping ............95

10.Operation Limits ....................................................................................97


11.Fan Performance ..................................................................................99
11.1 FBQ-B ....................................................................................................99
11.2 FBQ-D ..................................................................................................100

12.Air Velocity and Temperature Distributions.........................................102


12.1 FFQ ......................................................................................................102
12.2 FHQ......................................................................................................104

13.Sound Level ........................................................................................106


13.1 Overall Sound Level .............................................................................106
13.2 Octave Band Level ...............................................................................108

Part 2 Installation of Indoor / Outdoor Unit.............................. 113


1. Centre of Gravity .................................................................................114
2. Installation of Indoor Unit ....................................................................117
2.1 FCQ71KVEA / FCQ100KVEA / FCQ125KVEA / FCQ140KVEA..........117
2.2 FFQ25BV1B / FFQ35BV1B / FFQ50BV1B / FFQ60BV1B...................142
2.3 FHQ35BVV1B / FHQ50BVV1B / FHQ60BVV1B / FHQ71BVV1B /
FHQ100BVV1B / FHQ125BVV1B ........................................................165
Table of Contents

EDSG281001

2.4 FBQ50BV1A / FBQ60BV1A / FBQ71BV1A..........................................190


2.5 FBQ71DV1 / FBQ100DV1 / FBQ125DV1 / FBQ140DV1.....................211

3. Installation of Outdoor Unit..................................................................238


3.1
3.2
3.3
3.4

RKS25AVMG / RKS35AVMG ..............................................................238


RXS50FAVMA / RXS60FVMA / RKS50AVMG / RKS60AVMG ..........246
RXS71FVMA ........................................................................................254
RZR71KUV1 / RZR100KUV1 / RZR125KUV1 / RZR140KUV1
RZR100HUY1 / RZR125HUY1 / RZR140HUY1 ..................................262

Part 3 Detail Information of Options ........................................ 279


1. Accessories.........................................................................................281
1.1 Indoor Unit............................................................................................281
1.2 Outdoor Unit .........................................................................................284

2. Remote Controller ...............................................................................285


2.1 BRC1C61 Wired Remote Controller ................................................285
2.2 BRC1D61 Wired Remote Controller with
Weekly Schedule Timer .......................................................................289
2.3 BRC1E61 Navigation Remote Controller (Wired Type)...................297
2.4 Wireless Remote Controller .................................................................336

3. FCQ.....................................................................................................338
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
3.11
3.12
3.13
3.14
3.15
3.16

BYCP125K-W1 Decoration Panel ...................................................338


KDBH55K160F Sealing Member of Air Discharge Outlet................343
KDBP55H160FA Panel Spacer .......................................................347
KDDP55K160(K) Fresh Air Intake Kit (Chamber Type)...................350
KDDP55X160 Fresh Air Intake Kit (Direct Installation Type)...........355
KAFP556H80 / KAFP556H160, KAFP557H80 / KAFP557H160
High Efficiency Filter (Including Chamber) ......................................358
KAFP552H80 / KAFP552H160, KAFP553H80 / KAFP553H160
Replacement High Efficiency Filter..................................................361
KDDFP55H160 High Efficiency Filter Chamber ..............................362
KAFP551K160 Replacement Long-life Filter ...................................365
KAFP55H160 Ultra Long-life Filter Unit (Including Chamber) .........366
KAFP55H160H Replacement Ultra Long-life Filter..........................369
KKSJ55K160 Chamber Connection Kit ...........................................370
KDJP55H80 / KDJP55H160 Branch Duct Chamber........................371
KDTP55K80 / KDTP55K160 Insulation Kit for High Humidity..........374
KRP1H98 Installation Box for Adaptor PCB ....................................376
KRCS01-4B Remote Sensor (for Indoor Temperature)...................381

4. FFQ .....................................................................................................385
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8

BYFQ60B8W1 Decoration Panel.....................................................385


KDBH44BA60 Sealing Member of Air Discharge Outlet..................388
KDBQ44BA60A Panel Spacer.........................................................390
KAFQ441BA60 Replacement Long-life Filter ..................................393
KDDQ44XA60 Fresh Air Intake Kit (Direct Installation Type) ..........394
DTA112BA51 Interface Adaptor for SkyAir Series ..........................396
KRP1BA101 Installation Box for Adaptor PCB ................................398
KRCS01-1B Remote Sensor (for Indoor Temperature)...................403

5. FHQ.....................................................................................................407
5.1 KDU50N60VE / KDU50N125VE Drain-up Kit..................................407
5.2 KAF501DA56 / KAF501DA80 / KAF501DA112 / KAF501DA160
Replacement Long-life Filter............................................................412
ii

Table of Contents

EDSG281001

5.3 KHFP5MA35 / KHFP5MA63 / KHFP5MA160


L-type Piping Kit (for Upward Direction) ..........................................413
5.4 KRP1CA93 Installation Box for Adaptor PCB..................................414
5.5 KRCS01-1B Remote Sensor (for Indoor Temperature)...................416
5.6 DTA112BA51 Interface Adaptor for SkyAir Series ..........................420
5.7 KJB212AA / KJB311AA Electrical Box with Earth Terminal ............422

6. FBQ.....................................................................................................424
6.1 KTBJ25K56W / KTBJ25K80W (T) (F) / KTBJ25K160W(T) (F)
Service Access Panel ......................................................................424
6.2 KDAJ25K56A / KDAJ25K71A / KDAJ25K140A
Air Discharge Adaptor......................................................................427
6.3 KAF372AA80 / KAF372AA160 / KAF373AA80 / KAF373AA160
High Efficiency Filter ........................................................................429
6.4 KDDF37AA80 / KDDF37AA160 High Efficiency Filter Chamber .....430
6.5 KAF371AA80 / KAF371AA160 Long Life Filter ...............................433
6.6 KAF375AA80 / KAF375AA160 Long Life Filter Chamber Kit ..........434
6.7 KRP4A96 Mounting Plate for Adaptor PCB.....................................437
6.8 KRCS01-4B Remote Sensor (for Indoor Temperature)...................440
6.9 DTA112BA51 Interface Adaptor for SkyAir Series ..........................444

7. Outdoor Unit........................................................................................446
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8

Table of Contents

KPW937A4 Air Direction Adjustment Grille .....................................446


KPW945A4 Air Direction Adjustment Grille .....................................447
KKP937A4 Drain Plug .....................................................................448
KKP945A4 Drain Plug .....................................................................449
KKPJ5F180 Central Drain Plug .......................................................450
K-KYZP15C Wire Fixture for Preventing Overturning......................451
KPT-60B160 Fixture for Preventing Overturning .............................453
KRP58M51 Demand Adaptor ..........................................................455

iii

EDSG281001

iv

Table of Contents

EDSG281001

Part 1
SkyAir Inverter Series
Model series
Class

25

35

50

60

FCQ
FFQ
Indoor
unit

25B

FHQ

100

125

140

71K

100K

125K

140K

35B

50B

60B

35BV

50BV

60BV

71BV

50B

60B

71B

FBQ-B
FBQ-D

71D

RXS
Outdoor
unit

71

RKS

25A

RZR

35A

50FA

60F

50A

60A

100BV 125BV

100D

125D

140D

71F

71KU

100KU 125KU 140KU


100HU 125HU 140HU

1. External Appearance...............................................................................3
2. Model Name, Power Supply and Nomenclature .....................................4
2.1 Model Name and Power Supply...............................................................4
2.2 Nomenclature ...........................................................................................5

3. Functions.................................................................................................6
3.1 Indoor Unit................................................................................................6
3.2 Outdoor Unit .............................................................................................7

4. Specifications ..........................................................................................8
5. Dimensions and Service Space ............................................................25
5.1
5.2
5.3
5.4
5.5

Indoor Unit..............................................................................................25
Wired Remote Controller........................................................................39
Wireless Remote Controller ...................................................................41
Outdoor Unit ...........................................................................................43
Installation Service Space ......................................................................49

6. Piping Diagrams....................................................................................55
6.1 Indoor Unit..............................................................................................55
6.2 Indoor Unit + Outdoor Unit .....................................................................57
6.3 Outdoor Unit ...........................................................................................62

7. Wiring Diagrams....................................................................................66
7.1 Indoor Unit..............................................................................................66
7.2 Outdoor Unit ...........................................................................................72
SkyAir RXS, RKS, RZR Series

EDSG281001

7.3 Field Wiring ............................................................................................80

8. Electric Characteristics..........................................................................81
8.1 RXS50FAVMA / RXS60FVMA / RXS71FVMA
RKS25AVMG / RKS35AVMG / RKS50AVMG / RKS60AVMG ..............81
8.2 RZR71KUV1 / RZR100KUV1 / RZR125KUV1 / RZR140KUV1 .............82
8.3 RZR100HUY1 / RZR125HUY1 / RZR140HUY1 ....................................84

9. Capacity Tables ....................................................................................86


9.1 Capacity Tables......................................................................................86
9.2 Capacity Correction Factor by the Length of Refrigerant Piping ............95

10.Operation Limits ....................................................................................97


11.Fan Performance ..................................................................................99
11.1 FBQ-B ....................................................................................................99
11.2 FBQ-D ..................................................................................................100

12.Air Velocity and Temperature Distributions.........................................102


12.1 FFQ ......................................................................................................102
12.2 FHQ......................................................................................................104

13.Sound Level ........................................................................................106


13.1 Overall Sound Level .............................................................................106
13.2 Octave Band Level ...............................................................................108

SkyAir RXS, RKS, RZR Series

EDSG281001

External Appearance

1. External Appearance

Indoor Unit

FCQ

FFQ

FHQ

FBQ50~71B

FBQ71~140D

Remote Controller
Wired Type

BRC1C61

BRC1D61

Wireless Type

BRC1E61

Outdoor Unit

RKS25AVMG / RKS35AVMG

RXS50FAVMA / RXS60FVMA
RKS50AVMG / RKS60AVMG

RXS71FVMA

RZR71KUV1

RZR100~140KUV1

RZR100~140HUY1

SkyAir RXS, RKS, RZR Series

Model Name, Power Supply and Nomenclature

EDSG281001

2. Model Name, Power Supply and Nomenclature


2.1

Model Name and Power Supply


Indoor unit
FCQ71KVEA

Notes:

Outdoor unit

Power supply

RZR71KUV1

FCQ100KVEA

RZR100KUV1

FCQ125KVEA

RZR125KUV1

FCQ140KVEA

RZR140KUV1

FCQ100KVEA

RZR100HUY1

FCQ125KVEA

RZR125HUY1

FCQ140KVEA

RZR140HUY1

FFQ25BV1B

RKS25AVMG

FFQ35BV1B

RKS35AVMG

FFQ50BV1B

RKS50AVMG

FFQ60BV1B

RKS60AVMG

FHQ35BVV1B

RKS35AVMG

FHQ50BVV1B

RKS50AVMG

FHQ60BVV1B

RKS60AVMG

FHQ71BVV1B

RZR71KUV1

FHQ100BVV1B

RZR100KUV1

FHQ125BVV1B

RZR125KUV1

FHQ100BVV1B

RZR100HUY1

FHQ125BVV1B

RZR125HUY1

FBQ50BV1A

RXS50FAVMA

FBQ60BV1A

RXS60FVMA

FBQ71BV1A

RXS71FVMA

FBQ71DV1

RZR71KUV1

FBQ100DV1

RZR100KUV1

FBQ125DV1

RZR125KUV1

FBQ140DV1

RZR140KUV1

FBQ100DV1

RZR100HUY1

FBQ125DV1

RZR125HUY1

FBQ140DV1

RZR140HUY1

1 phase, 220-240V, 50Hz

3 phase, 380-415V, 50Hz

1 phase, 220-240V, 50Hz /


220-230V, 60Hz

1 phase, 220-240V, 50Hz /


220-230V, 60Hz

1 phase, 220-240V, 50Hz

3 phase, 380-415V, 50Hz


1 phase, 220-240V, 50Hz /
220-230V, 60Hz

1 phase, 220-240V, 50Hz

3 phase, 380-415V, 50Hz

1. : New Model or Changed Model


2. Power Supply Intake : Outdoor Unit

SkyAir RXS, RKS, RZR Series

EDSG281001

2.2

Model Name, Power Supply and Nomenclature

Nomenclature

Indoor Unit

FB

50

V1

For Australia
Power Supply Symbol
VE : 1 phase, 220-240V, 50Hz / 220V, 60Hz
V1 : 1 phase, 220-240V, 50Hz
Indicates Major Design Category
Capacity Indication
Refrigerant : R-410A
FC : Ceiling Mounted Cassette Type
FF
: Compact Multi Flow Ceiling Mounted Cassette Type
FH : Ceiling Suspended Type
FB-B : Ceiling Mounted Built-in Type
FB-D : Duct Connection Middle and High Static Pressure Type

Outdoor Unit

60

VM

A
For Australia
Power Supply Symbol
VM : 1 phase, 220-240V, 50Hz / 220-230V, 60Hz
Indicates Major Design Category
Capacity Indication
Refrigerant : R-410A, Inverter (High grade model)
X : Inverter Heat Pump
K : Inverter Cooling Only
Outdoor Unit for Pair Use

RZ

100

KU

V1
Power Supply Symbol
V1 : 1 phase, 220-240V, 50Hz
Y1 : 3 phase, 380-415V, 50Hz
Indicates Major Design Category
Capacity Indication
Refrigerant : R-410A, Cooling Only
Outdoor Unit for Inverter

SkyAir RXS, RKS, RZR Series

Functions

EDSG281001

3. Functions
3.1

Indoor Unit

Items

Control

FCQ

FFQ

FHQ35~60

FHQ71~125

FBQ50~71B

Auto swing

Features

Swing pattern selection

Switchable fan speed

Program Dry

High ceiling application

{ (*1)

{ (*1)

High fan speed mode

Wired type

Wireless type

Year-round cooling applicable

Timer selector

Mould resistant treatment for filter

Mould-proofing drain pan

Drain pump mechanism

Pre-charged for up to 10 m

Pre-charged for up to 30 m

Long-life filter

Filter sign

Ceiling soiling prevention

Two selectable
thermo-sensors

Mould
prevention

Work &
servicing

Control
features

Option
Others

FBQ71~140D

Low gas pressure detection

Emergency operation

Self-diagnosis function

Auto-restart

Control by 2 remote controllers

Control by 1 remote controller

External command control

Central remote control

Interlock control

Ultra long life filter

High-efficiency filter

Fresh air intake kit

PE fin for outdoor unit

Notes:

{ : Functions exist.

: No functions
*1 : Installable on max. 3.5 m high ceiling

SkyAir RXS, RKS, RZR Series

EDSG281001

3.2

Functions

Outdoor Unit
Functions

RKS25AVMG
RKS35AVMG
RKS50AVMG
RKS60AVMG

RZR71KUV1
RZR100KUV1 / RZR125KUV1 / RZR140KUV1
RZR100HUY1 / RZR125HUY1 / RZR140HUY1

Inverter Control
(For Comfortable Air Conditioning)

Night time Quiet Operation


Function for cooling

10~46CDB

5~46CDB

Items

Control
Operation
Range

Wide Operation Range

Notes:

Cooling

{ : Functions exist.

: No functions

Functions

RXS50FAVMA
RXS60FVMA
RXS71FVMA

Inverter Control
(For Comfortable Air Conditioning)

Night time Quiet Operation


Function for cooling

Items

Control

Operation
Range

Wide Operation Range

Notes:

Cooling

10~46CDB

Heating

15~18CWB

{ : Functions exist.

: No functions

SkyAir RXS, RKS, RZR Series

Specifications

EDSG281001

4. Specifications
FCQ (Ceiling mounted cassette type round flow)
Model

Indoor unit
Outdoor unit

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

Fan

HWD
Type
Rowsstagesfin pitch
Face area
Model
Type
Motor output
Air flow rate (H/L)

Sound level (H/L) *5


Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)

Decoration
panel (option)
Outdoor unit
Colour
Dimensions

W
m/min
cfm
dB(A)
kg
mm
mm
mm

mm
kg

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air flow rate
Cooling
Sound level *5
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Drawing No.

mm

kW
W
m/min
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FCQ100KVEA
RZR100KUV1
V1: 1 phase, 220-240V, 50Hz
10.0 (5.0-11.2)
34,100 (17,100-38,200)
8,600 (4,300-9,600)
FCQ100KVEA

298840840
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2121.2
0.535
QTS48C15M
Turbo fan
120
32/20
1,129/706
43/32
24
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC7F632F
BYCP125K-W1
Fresh white
50950950
Resin net (with mould resistance)
5.5
RZR100KUV1
Ivory white
1,170900320
Cross fin coil (Louver fins and Hi-XSL tubes)
1521.4
1.027
JT100G-VD@T3
Hermetically sealed scroll type
1.8
Propeller
70+70
95
49
45
92
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
2.4 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065827A

*1. The above data are based on the following conditions.


Cooling

Piping length

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m
(Horizontal)

*2.
*3.
*4.
*5.

Wired *4
Wireless

Model
Colour
Dimensions HWD
Air filter
Mass (weight)

Notes:

mm

FCQ71KVEA
RZR71KUV1
V1: 1 phase, 220-240V, 50Hz
7.1 (3.2-8.0)
24,200 (10,900-27,300)
6,100 (2,800-6,900)
FCQ71KVEA

256840840
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2101.2
0.446
QTS48C15M
Turbo fan
56
21/13.5
741/476
35/28
21
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC7F632F
BYCP125K-W1
Fresh white
50950950
Resin net (with mould resistance)
5.5
RZR71KUV1
Ivory white
770900320
Cross fin coil (Louver fins and Hi-XSL tubes)
1341.4
0.67
2YC63FXD#D
Hermetically sealed swing type
1.5
Propeller
70
52
48
47
61
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
1.75 (charged for 30m)
Refer to the name plate of compressor.
0.75
C : 3D065827A

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
Wire for remote controller : Field supplied.
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RXS, RKS, RZR Series

EDSG281001

Specifications

FCQ (Ceiling mounted cassette type round flow)


Model

Indoor unit
Outdoor unit

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

Fan

HWD
Type
Rowsstagesfin pitch
Face area
Model
Type
Motor output
Air flow rate (H/L)

Sound level (H/L) *5


Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)

Decoration
panel (option)

W
m/min
cfm
dB(A)
kg
mm
mm
mm

Wired *4
Wireless

Model
Colour
Dimensions HWD
Air filter
Mass (weight)

mm
kg

Outdoor unit
Colour
Dimensions

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air flow rate
Cooling
Sound level *5
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Drawing No.

Notes:

mm

mm

kW
W
m/min
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FCQ125KVEA
RZR125KUV1
V1: 1 phase, 220-240V, 50Hz
12.5 (5.7-14.0)
42,700 (19,400-47,800)
10,800 (4,900-12,000)
FCQ125KVEA

298840840
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2121.2
0.535
QTS48C15M
Turbo fan
120
33/22.5
1,164/794
44/34
24
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC7F632F
BYCP125K-W1
Fresh white
50950950
Resin net (with mould resistance)
5.5
RZR125KUV1
Ivory white
1,170900320
Cross fin coil (Waffle fins and Hi-XSL tubes)
2521.4
1.01
JT100G-VD@T3
Hermetically sealed scroll type
2.4
Propeller
70+70
95
50
45
97
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
3.7 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065827A

FCQ140KVEA
RZR140KUV1
V1: 1 phase, 220-240V, 50Hz
14.0 (6.2-15.4)
47,800 (21,200-52,500)
12,000 (5,300-13,200)
FCQ140KVEA

298840840
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2121.2
0.535
QTS48C15M
Turbo fan
120
33/22.5
1,164/794
44/36
24
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC7F632F
BYCP125K-W1
Fresh white
50950950
Resin net (with mould resistance)
5.5
RZR140KUV1
Ivory white
1,170900320
Cross fin coil (Waffle fins and Hi-XSL tubes)
2521.4
1.01
JT100G-VD@T3
Hermetically sealed scroll type
3.1
Propeller
70+70
95
50
46
97
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
3.7 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065827A

*1. The above data are based on the following conditions.


Cooling

Piping length

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m
(Horizontal)

*2.
*3.
*4.
*5.

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
Wire for remote controller : Field supplied.
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RXS, RKS, RZR Series

Specifications

EDSG281001

FCQ (Ceiling mounted cassette type round flow)


Model

Indoor unit
Outdoor unit

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

Fan

HWD
Type
Rowsstagesfin pitch
Face area
Model
Type
Motor output
Air flow rate (H/L)

Sound level (H/L) *5


Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)

Decoration
panel (option)
Outdoor unit
Colour
Dimensions

W
m/min
cfm
dB(A)
kg
mm
mm
mm

mm
kg

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air flow rate
Cooling
Sound level *5
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Drawing No.

mm

kW
W
m/min
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FCQ125KVEA
RZR125HUY1
3 phase, 380-415V, 50Hz
12.5 (5.7-14.0)
42,700 (19,400-47,800)
10,800 (4,900-12,000)
FCQ125KVEA

298840840
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2121.2
0.535
QTS48C15M
Turbo fan
120
33/22.5
1,164/794
44/34
24
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC7F632F
BYCP125K-W1
Fresh white
50950950
Resin net (with mould resistance)
5.5
RZR125HUY1
Ivory white
1,345900320
Cross fin coil (Waffle fins and Hi-XSL tubes)
2601.4
1.153
JT1G-VDYR@T
Hermetically sealed scroll type
2.3
Propeller
70+70
100
50
45
104
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
4.3 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065827A

*1. The above data are based on the following conditions.


Cooling

Piping length

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m
(Horizontal)

*2.
*3.
*4.
*5.

10

Wired *4
Wireless

Model
Colour
Dimensions HWD
Air filter
Mass (weight)

Notes:

mm

FCQ100KVEA
RZR100HUY1
3 phase, 380-415V, 50Hz
10.0 (5.0-11.2)
34,100 (17,100-38,200)
8,600 (4,300-9,600)
FCQ100KVEA

298840840
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2121.2
0.535
QTS48C15M
Turbo fan
120
32/20
1,129/706
43/32
24
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC7F632F
BYCP125K-W1
Fresh white
50950950
Resin net (with mould resistance)
5.5
RZR100HUY1
Ivory white
1,345900320
Cross fin coil (Louver fins and Hi-XSL tubes)
1601.4
1.172
JT1G-VDYR@T
Hermetically sealed scroll type
1.6
Propeller
70+70
100
49
45
94
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
3.9 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065827A

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
Wire for remote controller : Field supplied.
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RXS, RKS, RZR Series

EDSG281001

Specifications

FCQ (Ceiling mounted cassette type round flow)


Model

Indoor unit
Outdoor unit

FCQ140KVEA
RZR140HUY1
3 phase, 380-415V, 50Hz
14.0 (6.2-15.4)
47,800 (21,200-52,500)
12,000 (5,300-13,200)
FCQ140KVEA

298840840
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2121.2
0.535
QTS48C15M
Turbo fan
120
33/22.5
1,164/794
44/36
24
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC7F632F
BYCP125K-W1
Fresh white
50950950
Resin net (with mould resistance)
5.5
RZR140HUY1
Ivory white
1,345900320
Cross fin coil (Waffle fins and Hi-XSL tubes)
2601.4
1.153
JT1G-VDYR@T
Hermetically sealed scroll type
2.8
Propeller
70+70
100
50
46
104
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
4.3 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065827A

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

Fan

HWD
Type
Rowsstagesfin pitch
Face area
Model
Type
Motor output
Air flow rate (H/L)

Sound level (H/L) *5


Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)

Decoration
panel (option)

W
m/min
cfm
dB(A)
kg
mm
mm
mm

Wired *4
Wireless

Model
Colour
Dimensions HWD
Air filter
Mass (weight)

mm
kg

Outdoor unit
Colour
Dimensions

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air flow rate
Cooling
Sound level *5
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Drawing No.

Notes:

mm

mm

kW
W
m/min
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

*1. The above data are based on the following conditions.


Cooling

Piping length

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m
(Horizontal)

*2.
*3.
*4.
*5.

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
Wire for remote controller : Field supplied.
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RXS, RKS, RZR Series

11

Specifications

EDSG281001

FFQ (Compact multi flow ceiling mounted cassette type)


Model

Indoor unit
Outdoor unit

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1
Indoor unit
Colour
Dimensions
Coil

Fan

HWD
Type
RowsStagesFin pitch
Face area
Type
Motor output
Air flow rate (H/L)

Sound level (H/L) *3


Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)

Decoration
panel (option)

W
m/min
cfm
dB(A)
kg
mm
mm
mm

mm
kg

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Fan
Motor output
Air flow rate (H/L)
Cooling
Sound level *3
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. Piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. Oil
Charge
Drawing No.

Notes:

Wired *2
Wireless

Model
Colour
Dimentions HWD
Air filter
Mass (weight)

Outdoor unit
Colour
Dimentions

mm

mm

kW
W
m/min
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FFQ25BV1B
RKS25AVMG
VM: 1 phase, 220-240V, 50Hz/220-230V, 60Hz
2.5 (1.2-3.0)
8,550 (4,100-10,250)
2,150 (1,030-2,580)
FFQ25BV1B

286575575
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2101.5
0.269
Turbo fan
55
9.0/6.5
317/229
29.5/24.5
17.5
6.4 (Flare)
9.5 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7E531W
BYFQ60B8W1
White (RAL 9010)
55700700
Removable/washable/mildew proof/long life
2.7
RKS25AVMG
Ivory white
550765285
Cross fin coil (Waffle fins and Hi-XD tubes)
2241.4
0.425
1YC23NXD#A
Hermetically sealed swing type
0.6
Propeller
23
33.5/23.4
46

34
6.4 (Flare)
9.5 (Flare)
18.0 (Hole)
Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
20
15
R-410A
1.0 (charged for 10m)
Refer to the name plate of compressor.
0.375

FFQ35BV1B
RKS35AVMG
VM: 1 phase, 220-240V, 50Hz/220-230V, 60Hz
3.4 (1.2-3.7)
11,600 (4,100-12,600)
2,920 (1,030-3,180)
FFQ35BV1B

286575575
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2101.5
0.269
Turbo fan
55
10.0/6.5
353/229
32/25
17.5
6.4 (Flare)
9.5 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7E531W
BYFQ60B8W1
White (RAL 9010)
55700700
Removable/washable/mildew proof/long life
2.7
RKS35AVMG
Ivory white
550765285
Cross fin coil (Waffle fins and Hi-XD tubes)
2241.4
0.425
1YC23NXD#A
Hermetically sealed swing type
0.6
Propeller
23
33.5/23.4
47

34
6.4 (Flare)
9.5 (Flare)
18.0 (Hole)
Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
20
15
R-410A
1.0 (charged for 10m)
Refer to the name plate of compressor.
0.375

*1. The above data are based on the following conditions.


Cooling

Piping length

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB

7.5m
(Horizontal)

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

*2. Wire for remote controller : field supplied.


*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

12

SkyAir RXS, RKS, RZR Series

EDSG281001

Specifications

FFQ (Compact multi flow ceiling mounted cassette type)


Model

Indoor unit
Outdoor unit

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1
Indoor unit
Colour
Dimensions
Coil

Fan

HWD
Type
RowsStagesFin pitch
Face area
Type
Motor output
Air flow rate (H/L)

Sound level (H/L) *3


Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controlle (option)

Decoration
panel (option)

m
W
m/min
cfm
dB(A)
kg
mm
mm
mm

Wired *2
Wireless

Model
Colour
Dimentions HWD
Air filter
Mass (weight)

mm
kg

Outdoor unit
Colour
Dimentions

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Fan
Motor output
Air flow rate (HH/H/L)
Cooling
Sound level *3
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. Piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. Oil
Charge
Drawing No.

Notes:

mm

mm

kW
W
m/min
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FFQ50BV1B
RKS50AVMG
VM: 1 phase, 220-240V, 50Hz/220-230V, 60Hz
4.7 (1.7-5.6)
16,000 (5,800-19,100)
4,040 (1,460-4,820)
FFQ50BV1B

286575575
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2101.5
0.269
Turbo fan
55
12.0/8.0
423/282
36/27
17.5
6.4 (Flare)
12.7 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7E531W
BYFQ60B8W1
White (RAL 9010)
55700700
Removable/washable/mildew proof/long life
2.7
RKS50AVMG
Ivory white
735825300
Cross fin coil (Waffle fins and Hi-XA tubes)
2321.8
0.595
2YC36BXD#A
Hermetically sealed swing type
1.1
Propeller
53
50.9/48.9/41.7
47

47
6.4 (Flare)
12.7 (Flare)
18.0 (Hole)
Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
30
20
R-410A
1.5 (charged for 10m)
Refer to the name plate of compressor.
0.65

FFQ60BV1B
RKS60AVMG
VM: 1 phase, 220-240V, 50Hz/220-230V, 60Hz
5.8 (1.7-6.0)
19,800 (5,800-20,500)
4,990 (1,460-5,160)
FFQ60BV1B

286575575
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2101.5
0.269
Turbo fan
55
15.0/10.0
529/353
41/32
17.5
6.4 (Flare)
12.7 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7E531W
BYFQ60B8W1
White (RAL 9010)
55700700
Removable/washable/mildew proof/long life
2.7
RKS60AVMG
Ivory white
735825300
Cross fin coil (Waffle fins and Hi-XA tubes)
2321.8
0.595
2YC36BXD#A
Hermetically sealed swing type
1.1
Propeller
53
54.2/50.9/45.0
49

47
6.4 (Flare)
12.7 (Flare)
18.0 (Hole)
Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
30
20
R-410A
1.5 (charged for 10m)
Refer to the name plate of compressor.
0.65

*1. The above data are based on the following conditions.


Cooling

Piping length

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB

7.5m
(Horizontal)

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

*2. Wire for remote controller : field supplied.


*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RXS, RKS, RZR Series

13

Specifications

EDSG281001

FHQ (Ceiling suspended type)


Model

Indoor unit
Outdoor unit

FHQ35BVV1B
RKS35AVMG
VM: 1 phase, 220-240V, 50Hz/220-230V, 60Hz
3.4 (1.2-3.7)
11,600 (4,100-12,600)
2,920 (1,030-3,180)
FHQ35BVV1B
White
195960680
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2121.75
0.182
Sirocco fan
62
13/10
458/353
37/32
Removable/washable/mildew proof
24
6.4 (Flare)
9.5 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7EA66
RKS35AVMG
Ivory white
550765285
Cross fin coil (Waffle fins and Hi-XD tubes)
2241.4
0.425
1YC23NXD#A
Hermetically sealed swing type
0.6
Propeller
23
33.5/23.4
47

34
6.4 (Flare)
9.5 (Flare)
18.0 (hole)
Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
20
15
R-410A
1.0 (charged for 10m)
Refer to the name plate of compressor.
0.375
C: 3D061270

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1
Indoor unit
Colour
Dimensions
Coil

Fan

HWD
Type
Rowsstagesfin pitch
Face area
Type
Motor output
Air flow rate (H/L)

Sound level (H/L) *3


Air filter
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)
Outdoor unit
Colour
Dimentions

m
W
m/min
cfm
dB(A)
kg
mm
mm
mm

Wired *2
Wireless

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Fan
Motor output
Air flow rate (H/L)
Cooling
Sound level *3
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. Piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. Oil
Charge
Drawing No.

Notes:

mm

mm

kW
W
m/min
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

*1. The above data are based on the following conditions.


Cooling

Piping length

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB

7.5m
(Horizontal)

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

*2. Wire for remote controller : field supplied.


*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

14

SkyAir RXS, RKS, RZR Series

EDSG281001

Specifications

FHQ (Ceiling suspended type)


Model

Indoor unit
Outdoor unit

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1
Indoor unit
Colour
Dimensions
Coil

Fan

HWD
Type
Rowsstagesfin pitch
Face area
Type
Motor output
Air flow rate (H/L)

Sound level (H/L) *3


Air filter
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)

m
W
m/min
cfm
dB(A)
kg
mm
mm
mm

Wired *2
Wireless

Outdoor unit
Colour
Dimentions

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Fan
Motor output
Air flow rate (HH/H/L)
Cooling
Sound level *3
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. Piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. Oil
Charge
Drawing No.

Notes:

mm

mm

kW
W
m/min
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FHQ50BVV1B
RKS50AVMG
VM: 1 phase, 220-240V, 50Hz/220-230V, 60Hz
5.0 (1.7-5.6)
17,100 (5,800-19,100)
4,300 (1,460-4,820)
FHQ50BVV1B
White
195960680
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3121.75
0.182
Sirocco fan
62
13/10
458/353
38/33
Removable/washable
25
6.4 (Flare)
12.7 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7EA66
RKS50AVMG
Ivory white
735825300
Cross fin coil (Waffle fins and Hi-XA tubes)
2321.8
0.595
2YC36BXD#A
Hermetically sealed swing type
1.1
Propeller
53
50.9/48.9/41.7
47

47
6.4 (Flare)
12.7 (Flare)
18.0 (Hole)
Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
30
20
R-410A
1.5 (charged for 10m)
Refer to the name plate of compressor.
0.65
C: 3D061271

FHQ60BVV1B
RKS60AVMG
VM: 1 phase, 220-240V, 50Hz/220-230V, 60Hz
5.7 (1.7-6.0)
19,400 (5,800-20,500)
4,900 (1,460-5,160)
FHQ60BVV1B
White
1951,160680
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2121.75
0.233
Sirocco fan
62
17/13
600/458
39/33
Removable/washable
27
6.4 (Flare)
12.7 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7EA66
RKS60AVMG
Ivory white
735825300
Cross fin coil (Waffle fins and Hi-XA tubes)
2321.8
0.595
2YC36BXD#A
Hermetically sealed swing type
1.1
Propeller
53
54.2/50.9/45.0
49

47
6.4 (Flare)
12.7 (Flare)
18.0 (Hole)
Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
30
20
R-410A
1.5 (charged for 10m)
Refer to the name plate of compressor.
0.65
C: 3D061272

*1. The above data are based on the following conditions.


Cooling

Piping length

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB

7.5m
(Horizontal)

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

*2. Wire for remote controller : field supplied.


*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RXS, RKS, RZR Series

15

Specifications

EDSG281001

FHQ (Ceiling suspended type)


Model

Indoor unit
Outdoor unit

FHQ71BVV1B
RZR71KUV1
V1: 1 phase, 220-240V, 50Hz
7.1 (3.2-8.0)
24,200 (10,900-27,300)
6,100 (2,800-6,900)
FHQ71BVV1B
White
1951,160680
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3121.75
0.233
Sirocco fan
62
17/14
600/494
39/35

27
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7EA66
RZR71KUV1
Ivory white
770900320
Cross fin coil (Louver fins and Hi-XSL tubes)
1341.4
0.67
2YC63FXD#D
Hermetically sealed swing type
1.7
Propeller
70
52
48
47
61
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
1.75 (charged for 30m)
Refer to the name plate of compressor.
0.75
C : 3D065808A

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

Fan

HWD
Type
Rowsstagesfin pitch
Face area
Type
Motor output
Air flow rate (H/L)

Sound level (H/L) *5


Air Filter
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)

W
m/min
cfm
dB(A)

Wired *4
Wireless

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air flow rate
Cooling
Sound level *5
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Drawing No.

mm

kW
W
m/min
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

*1. The above data are based on the following conditions.


Cooling

Piping length

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m
(Horizontal)

*2.
*3.
*4.
*5.

16

kg
mm
mm
mm

Outdoor Unit
Colour
Dimensions

Notes:

mm

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
Wire for remote controller : Field supplied.
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RXS, RKS, RZR Series

EDSG281001

Specifications

FHQ (Ceiling suspended type)


Model

Indoor unit
Outdoor unit

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

Fan

HWD
Type
Rowsstagesfin pitch
Face area
Type
Motor output
Air flow rate (H/L)

Sound level (H/L) *5


Air filter
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)

m
W
m/min
cfm
dB(A)
kg
mm
mm
mm

Wired *4
Wireless

Outdoor unit
Colour
Dimensions

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air flow rate
Cooling
Sound level *5
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Drawing No.

Notes:

mm

mm

kW
W
m/min
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FHQ100BVV1B
RZR100KUV1
V1: 1 phase, 220-240V, 50Hz
10.0 (5.0-11.2)
34,100 (17,100-38,200)
8,600 (4,300-9,600)
FHQ100BVV1B
White
1951,400680
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3121.75
0.293
Sirocco fan
130
24/20
847/706
42/37
Resin net (with mould resistance)
32
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7EA66
RZR100KUV1
Ivory white
1,170900320
Cross fin coil (Louver fins and Hi-XSL tubes)
1521.4
1.027
JT100G-VD@T3
Hermetically sealed scroll type
2.1
Propeller
70+70
95
49
45
92
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
2.4 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065808A

FHQ125BVV1B
RZR125KUV1
V1: 1 phase, 220-240V, 50Hz
12.5 (5.7-14.0)
42,700 (19,400-47,800)
10,800 (4,900-12,000)
FHQ125BVV1B
White
1951,590680
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3121.75
0.341
Sirocco fan
130
30/25
1,059/883
44/39
Resin net (with mould resistance)
35
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7EA66
RZR125KUV1
Ivory white
1,170900320
Cross fin coil (Waffle fins and Hi-XSL tubes)
2521.4
1.01
JT100G-VD@T3
Hermetically sealed scroll type
2.6
Propeller
70+70
95
50
45
97
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
3.7 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065808A

*1. The above data are based on the following conditions.


Cooling

Piping length

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m
(Horizontal)

*2.
*3.
*4.
*5.

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
Wire for remote controller : Field supplied.
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RXS, RKS, RZR Series

17

Specifications

EDSG281001

FHQ (Ceiling suspended type)


Model

Indoor unit
Outdoor unit

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1 *2
Indoor unit
Colour
Dimensions
Coil

Fan

HWD
Type
Rowsstagesfin pitch
Face area
Type
Motor output
Air flow rate (H/L)

Sound level (H/L) *5


Air filter
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)

W
m/min
cfm
dB(A)

Wired *4
Wireless

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air flow rate
Cooling
Sound level *5
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Drawing No.

mm

kW
W
m/min
dB(A)
dB(A)
kg
mm
mm
mm
%
m
m
kg
L

FHQ125BVV1B
RZR125HUY1
3 phase, 380-415V, 50Hz
12.5 (5.7-14.0)
42,700 (19,400-47,800)
10,800 (4,900-12,000)
FHQ125BVV1B
White
1951,590680
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3121.75
0.341
Sirocco fan
130
30/25
1,059/883
44/39
Resin net (with mould resistance)
35
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7EA66
RZR125HUY1
Ivory white
1,345900320
Cross fin coil (Waffle fins and Hi-XSL tubes)
2601.4
1.153
JT1G-VDYR@T
Hermetically sealed scroll type
2.6
Propeller
70+70
100
50
45
104
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
4.3 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065808A

*1. The above data are based on the following conditions.


Cooling

Piping length

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m
(Horizontal)

*2.
*3.
*4.
*5.

18

kg
mm
mm
mm

Outdoor unit
Colour
Dimensions

Notes:

mm

FHQ100BVV1B
RZR100HUY1
3 phase, 380-415V, 50Hz
10.0 (5.0-11.2)
34,100 (17,100-38,200)
8,600 (4,300-9,600)
FHQ100BVV1B
White
1951,400680
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3121.75
0.293
Sirocco fan
130
24/20
847/706
42/37
Resin net (with mould resistance)
32
9.5 (Flare)
15.9 (Flare)
VP20 (I.D.20 O.D.26)
BRC1C61
BRC7EA66
RZR100HUY1
Ivory white
1,345900320
Cross fin coil (Louver fins and Hi-XSL tubes)
1601.4
1.172
JT1G-VDYR@T
Hermetically sealed scroll type
2.1
Propeller
70+70
100
49
45
94
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *3
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
3.9 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065808A

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
Wire for remote controller : Field supplied.
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RXS, RKS, RZR Series

EDSG281001

Specifications

FBQ (Ceiling mounted built-in type)


Model

Indoor unit
Outdoor unit

Power supply
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h

Cooling capacity *1

Heating capacity *1
Indoor unit
External static
pressure *4
Dimensions
Coil

Fan

FBQ50BV1A
RXS50FAVMA
VM: 1 phase, 220-240V, 50Hz/220-230V, 60Hz
5.0 (1.7-5.6)
17,100 (5,800-19,100)
4,300 (1,460-4,820)
6.0 (1.7-7.0)
20,500 (5,800-23,700)
5,160 (1,460-6,020)
FBQ50BV1A

FBQ60BV1A
RXS60FVMA
VM: 1 phase, 220-240V, 50Hz/220-230V, 60Hz
5.7 (1.7-7.0)
19,400 (5,800-23,900)
4,900 (1,460-6,020)
7.0 (1.7-8.0)
23,900 (5,800-27,300)
6,020 (1,460-6,880)
FBQ60BV1A

High-Standard-Low

Pa

88-49-20

88-49-20

HWD
Type
Rowsstagesfin pitch
Face area
Type
Motor output

mm

W
m/min

300700800
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3141.75
0.132
Sirocco fan
85
13/9
459/318
14/10
494/353
33/29

34
6.4 (Flare)
12.7 (Flare)
VP25 (I.D.25 O.D.32)
BRC1C61
BRC4C62
RXS50FAVMA
Ivory white
735825300
Cross fin coil (Waffle fins and Hi-XA tubes)
2321.8
0.595
2YC36BXD#A
Hermetically sealed swing type
1.1
Propeller
53
50.9/48.9/41.7

3001,000800
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2141.75
0.220
Sirocco fan
110
18/13
635/459
19/14
671/494
34/30

41
6.4 (Flare)
12.7 (Flare)
VP25 (I.D.25 O.D.32)
BRC1C61
BRC4C62
RXS60FVMA
Ivory white
735825300
Cross fin coil (Waffle fins and Hi-XA tubes)
2321.8
0.595
2YC36BXD#A
Hermetically sealed swing type
1.1
Propeller
53
54.2/50.9/45.0

m/min

/45.0/45.0

/46.3/46.3

dB(A)
dB(A)
kg
mm
mm
mm

47/48

48
6.4 (Flare)
12.7 (Flare)
18.0 (Hole)
Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
30
20
R-410A
1.5 (charged for 10m)
Refer to the name plate of compressor.
0.65
C: 3D055515

49/49

48
6.4 (Flare)
12.7 (Flare)
18.0 (Hole)
Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
30
20
R-410A
1.5 (charged for 10m)
Refer to the name plate of compressor.
0.65
C: 3D055516

Air flow
rate (H/L)

Cooling
Heating

Sound level (H/L) *3


Air filter
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)

W
m/min
cfm
m/min
cfm
dB(A)
kg
mm
mm
mm

Wired *2
Wireless

Outdoor unit
Colour
Dimentions

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air flow
Cooling
rate
(HH/H/L) Heating
Cooling / heating
Sound level *3
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. Piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. Oil
Charge
Drawing No.

Notes:

mm

kW

%
m
m
kg
L

*1. The above data are based on the following conditions.


Cooling
Indoor : 27CDB, 19.0CWB
Outdoor : 35CDB

Heating
Indoor : 20CDB
Outdoor : 7CDB, 6CWB

Conversion formulae
Piping length
7.5m
(Horizontal)

kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

*2. Wire for remote controller : field supplied.


*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

*4. Initial setting is Standard.

SkyAir RXS, RKS, RZR Series

19

Specifications

EDSG281001

FBQ (Ceiling mounted built-in type)


Model

Indoor unit
Outdoor unit

FBQ71BV1A
RXS71FVMA
VM: 1 phase, 220-240V, 50Hz/220-230V, 60Hz
6.7 (2.3-8.0)
22,900 (7,900-27,300)
5,800 (1,980-6,900)
8.2 (2.3-10.0)
28,000 (7,900-34,100)
7,050 (1,980-8,600)
FBQ71BV1A

Power supply
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h

Cooling capacity *1

Heating capacity *1
Indoor unit
External static
pressure *4
Dimensions
Coil

Fan

High-Standard-Low

Pa

88-49-20

HWD
Type
Rowsstagesfin pitch
Face area
Type
Motor output

mm

W
m/min

3001,000800
Cross fin coil (Multi louver fins and Hi-XSL tubes)
2141.75
0.220
Sirocco fan
110
18/13
635/459
19/14
671/494
34/30

41
6.4 (Flare)
15.9 (Flare)
VP25 (I.D.25 O.D.32)
BRC1C61
BRC4C62
RXS71FVMA
Ivory white
770900320
Cross fin coil (Waffle fins and Hi-XSL tubes)
2341.4
0.641
2YC36BXD#A
Hermetically sealed swing type
1.92
Propeller
66
57.1/54.5/46.0

m/min

/52.5/52.5

dB(A)
dB(A)
kg
mm
mm
mm

52/52

71
6.4 (Flare)
15.9 (Flare)
26.0 (Hole)
Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
30
20
R-410A
2.3 (charged for 10m)
Refer to the name plate of compressor.
0.75
C: 3D054918

Air flow
rate (H/L)

Cooling
Heating

Sound level (H/L) *3


Air filter
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Remote controller (option)
Outdoor unit
Colour
Dimentions

W
m/min
cfm
m/min
cfm
dB(A)
kg
mm
mm
mm

Wired *2
Wireless

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air flow
Cooling
rate
(HH/H/L) Heating
Cooling / heating
Sound level *3
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. Piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. Oil
Charge
Drawing No.

Notes:

mm

kW

%
m
m
kg
L

*1. The above data are based on the following conditions.


Cooling
Indoor : 27CDB, 19.0CWB
Outdoor : 35CDB

Heating
Indoor : 20CDB
Outdoor : 7CDB, 6CWB

Conversion formulae
Piping length

kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

7.5m
(Horizontal)

*2. Wire for remote controller : field supplied.


*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

*4. Initial setting is Standard.

20

SkyAir RXS, RKS, RZR Series

EDSG281001

Specifications

FBQ (Duct connection middle and high static pressure type)


Model

Indoor unit
Outdoor unit

FBQ71DV1
RZR71KUV1
V1: 1 phase, 220-240V, 50Hz
7.1 (3.2-8.0)
24,200 (10,900-27,300)
6,100 (2,800-6,900)
FBQ71DV1

3001,000700
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3161.75
0.249
Sirocco fan
350
18/15
635/530
37/32
*3
36
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC4C62
RZR71KUV1
Ivory white
770900320
Cross fin coil (Louver fins and Hi-XSL tubes)
1341.4
0.67
2YC36FXD#D
Hermetically sealed swing type
1.5
Propeller
70

FBQ100DV1
RZR100KUV1
V1: 1 phase, 220-240V, 50Hz
10.0 (5.0-11.2)
34,100 (17,100-38,200)
8,600 (4,300-9,600)
FBQ100DV1

3001,400700
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3161.75
0.383
Sirocco fan
350
32/23
1,130/812
38/33
*3
46
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC4C62
RZR100KUV1
Ivory white
1,170900320
Cross fin coil (Louver fins and Hi-XSL tubes)
1521.4
1.027
JT100G-VD@T3
Hermetically sealed scroll type
1.8
Propeller
70+70

m/min

52

95

dB(A)
dB(A)
kg
mm
mm
mm

48
47
61
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *4
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
1.75 (charged for 30m)
Refer to the name plate of compressor.
0.75
C: 3D065826A

49
45
92
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *4
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
2.4 (charged for 30m)
Refer to the name plate of compressor.
1.2
C: 3D065826A

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1 *2
Indoor unit
Colour
Dimensions

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Type
Motor output
Fan
Air flow
rate (H/L) Cooling
Sound level (H/L) *6
Air filter
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Wired *5
Remote controller (option)
Wireless
Outdoor unit
Colour
Dimentions
HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air flow
Cooling
rate
Cooling
Sound level *6
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. Piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. Oil
Charge
Drawing No.

Notes:

mm

m
W
m/min
cfm
dB(A)
kg
mm
mm
mm

mm

kW

%
m
m
kg
L

*1. The above data based on the conditions shown in the table below.
Mark

Cooling

Piping length

(1)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m
(Horizontal)

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

*2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
*3. Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its colorimetric method (gravity method) 50% or more.

*4. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
*5. Wire for remote controller : Field supplied.
*6. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RXS, RKS, RZR Series

21

Specifications

EDSG281001

FBQ (Duct connection middle and high static pressure type)


Model

Indoor unit
Outdoor unit

FBQ125DV1
RZR125KUV1
V1: 1 phase, 220-240V, 50Hz
12.5 (5.7-14.0)
42,700 (19,400-47,800)
10,800 (4,900-12,000)
FBQ125DV1

3001,400700
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3161.75
0.383
Sirocco fan
350
39/28
1,377/988
40/36
*3
46
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC4C62
RZR125KUV1
Ivory white
1,170900320
Cross fin coil (Waffle fins and Hi-XSL tubes)
2521.4
1.01
JT100G-VD@T3
Hermetically sealed scroll type
2.4
Propeller
70+70

FBQ140DV1
RZR140KUV1
V1: 1 phase, 220-240V, 50Hz
14.0 (6.25-15.4)
47,800 (21,300-52,500)
12,000 (5,400-13,200)
FBQ140DV1

3001,400700
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3161.75
0.383
Sirocco fan
350
39/28
1,377/988
40/36
*3
46
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC4C62
RZR140KUV1
Ivory white
1,170900320
Cross fin coil (Waffle fins and Hi-XSL tubes)
2521.4
1.01
JT100G-VD@T3
Hermetically sealed scroll type
2.9
Propeller
70+70

m/min

95

95

dB(A)
dB(A)
kg
mm
mm
mm

50
45
97
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *4
High pressure switch. Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
3.7 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065826A

50
46
97
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *4
High pressure switch. Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
3.7 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065826A

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1 *2
Indoor unit
Colour
Dimensions

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Type
Motor output
Fan
Air flow
rate (H/L) Cooling
Sound level (H/L) *6
Air filter
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Wired *5
Remote controller (option)
Wireless
Outdoor unit
Colour
Dimensions
HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air Flow Cooling
Rate
Cooling
Sound level *6
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity control method
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Drawing No.

Notes:

mm

m
W
m/min
cfm
dB(A)
kg
mm
mm
mm

mm

kW

%
m
m
kg
L

*1. The above data based on the conditions shown in the table below.
Mark

Cooling

Piping length

(1)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m
(Horizontal)

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

*2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
*3. Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its colorimetric method (gravity method) 50% or more.

*4. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
*5. Wire for remote controller : Field supplied.
*6. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

22

SkyAir RXS, RKS, RZR Series

EDSG281001

Specifications

FBQ (Duct connection middle and high static pressure type)


Model

Indoor unit
Outdoor unit

FBQ100DV1
RZR100HUY1
3 phase, 380-415V, 50Hz
10.0 (5.0-11.2)
34,100 (17,100-38,200)
8,600 (4,300-9,600)
FBQ100DV1

3001,400700
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3161.75
0.383
Sirocco fan
350
32/23
1,130/812
38/33
*3
46
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC4C62
RZR100HUY1
Ivory white
1,345900320
Cross fin coil (Louver fins and Hi-XSL tubes)
1601.4
1.172
JT1G-VDYR@T
Hermetically sealed scroll type
1.6
Propeller
70+70

FBQ125DV1
RZR125HUY1
3 phase, 380-415V, 50Hz
12.5 (5.7-14.0)
42,700 (19,400-47,800)
10,800 (4,900-12,000)
FBQ125DV1

3001,400700
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3161.75
0.383
Sirocco fan
350
39/28
1,377/988
40/36
*3
46
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC4C62
RZR125HUY1
Ivory white
1,345900320
Cross fin coil (Waffle fins and Hi-XSL tubes)
2601.4
1.153
JT1G-VDYR@T
Hermetically sealed scroll type
2.3
Propeller
70+70

m/min

100

100

dB(A)
dB(A)
kg
mm
mm
mm

49
45
94
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *4
High pressure switch. Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
3.9 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065826A

50
45
104
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *4
High pressure switch. Fuse.
Compressor revolution speed control (Inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
4.3 (charged for 30m)
Refer to the name plate of compressor.
1.2
C : 3D065826A

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1 *2
Indoor unit
Colour
Dimensions

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Type
Motor output
Fan
Air flow
rate (H/L) Cooling
Sound level (H/L) *6
Air filter
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Wired *5
Remote controller (option)
Wireless
Outdoor unit
Colour
Dimensions
HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air Flow Cooling
Rate
Cooling
Sound level *6
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity control method
Refrigerant control
Max. length
Ref. piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. oil
Charge
Drawing No.

Notes:

mm

m
W
m/min
cfm
dB(A)
kg
mm
mm
mm

mm

kW

%
m
m
kg
L

*1. The above data based on the conditions shown in the table below.
Mark

Cooling

Piping length

(1)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m
(Horizontal)

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

*2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
*3. Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its colorimetric method (gravity method) 50% or more.

*4. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
*5. Wire for remote controller : Field supplied.
*6. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RXS, RKS, RZR Series

23

Specifications

EDSG281001

FBQ (Duct connection middle and high static pressure type)


Model

Indoor unit
Outdoor unit

FBQ140DV1
RZR140HUY1
3 phase, 380-415V, 50Hz
14.0 (6.25-15.4)
47,800 (21,300-52,500)
12,000 (5,400-13,200)
FBQ140DV1

3001,400700
Cross fin coil (Multi louver fins and Hi-XSL tubes)
3161.75
0.383
Sirocco fan
350
39/28
1,377/988
40/36
*3
46
9.5 (Flare)
15.9 (Flare)
I.D.25 O.D.32
BRC1C61
BRC4C62
RZR140HUY1
Ivory white
1,345900320
Cross fin coil (Waffle fins and Hi-XSL tubes)
2601.4
1.153
JT1G-VDYR@T
Hermetically sealed scroll type
2.8
Propeller
70+70

m/min

100

dB(A)
dB(A)
kg
mm
mm
mm

50
46
104
9.5 (Flare)
15.9 (Flare)
26.0 (Hole) *4
High pressure switch. Fuse.
Compressor revolution speed control (inverter system)
Electronic expansion valve
50 (equivalent length 70m)
30
R-410A
4.3 (charged for 30m)
Refer to the name plate of compressor.
1.2
C: 3D065826A

Power supply
kW
Btu/h
kcal/h

Cooling capacity *1 *2
Indoor unit
Colour
Dimensions

HWD
Type
Coil
Rowsstagesfin pitch
Face area
Type
Motor output
Fan
Air flow
rate (H/L) Cooling
Sound level (H/L) *6
Air filter
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Wired *5
Remote controller (option)
Wireless
Outdoor unit
Colour
Dimentions
HWD
Type
Coil
Rowsstagesfin pitch
Face area
Model
Comp.
Type
Motor output
Type
Motor output
Fan
Air flow
Cooling
rate
Cooling
Sound level *6
Night quiet mode
Mass (weight)
Liquid
Piping
Gas
connections
Drain
Safety devices
Capacity step
Refrigerant control
Max. length
Ref. Piping
Max. height difference
Model
Refrigerant
Charge (factory charge)
Model
Ref. Oil
Charge
Drawing No.

Notes:

mm

m
W
m/min
cfm
dB(A)
kg
mm
mm
mm

mm

kW

%
m
m
kg
L

*1. The above data based on the conditions shown in the table below.
Mark

Cooling

Piping length

(1)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m
(Horizontal)

Conversion formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3

*2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
*3. Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its colorimetric method (gravity method) 50% or more.

*4. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
*5. Wire for remote controller : Field supplied.
*6. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

24

SkyAir RXS, RKS, RZR Series

EDSG281001

Dimensions and Service Space

5. Dimensions and Service Space


5.1

Indoor Unit

5.1.1

FCQ

SkyAir RXS, RKS, RZR Series

3D058460B

Unit (mm)

FCQ71KVEA

25

Dimensions and Service Space

EDSG281001

26

3D058469B

Unit (mm)

FCQ100KVEA / FCQ125KVEA / FCQ140KVEA

SkyAir RXS, RKS, RZR Series

260
25

750
ADJUSTABLE (0~545)

62.5

196

575

A ARROW VIEW

700

211

172

700
1

62.5

PIPE CONNECTION
SIDE

DRAIN CONNECTION
SIDE

NOTE) 2.

145
183
285

45 OR LESS

62.5

320

45 OR LESS
NOTE) 4.

575

A
NOTE) 1. STICKING LOCATION FOR MANUFACTURE'S LABEL
MANUFACTURE'S LABEL FOR INDOOR UNIT : ON THE BELL MOUTH INSIDE
SUCTION GRILLE
MANUFACTURE'S LABEL FOR DECORATION PANEL : ON THE INNER FRAME
INSIDE SUCTION GRILLE
2. IN CASE OF USING WIRELESS REMOTE CONTROLLER, THIS POSITION WILL
BE A SIGNAL RECEIVER.
REFER TO THE DRAWING OF WIRELESS REMOTE CONTROLLER IN DETAIL. DECORATION PANEL
3. WHEN THE TEMPERATURE AND HUMIDITY IN THE CEILING EXCEED 30C
BYFQ60BW1 WHITE Ral 9010
AND RH 80% OR THE FRESH AIR IS INDUCTED INTO THE CEILING OR THE
UNIT CONTINUES 24 HOUR OPERATION, AN ADDITIONAL INSULATION
(THICKNESS 10mm OR MORE OF GLASSWOOL OR POLYETHYLENE FORM)
IS REQUIRED.
4. THOUGH THE INSTALLATION IS ACCEPTABLE UP TO MAXIMUM OF 660mm
SQUARE CEILING OPENING, KEEP THE CLEARANCE OF 45mm OR LESS
BETWEEN THE MAIN UNIT AND THE CEILING OPENING SO THAT THE PANEL
OVERLAP ALLOWANCE CAN BE ENSURED.

SUSPENTION BOLT
4-M8~M10

205

533 (SUSPENTION POSITION)


5

62.5

585~660 (CEILING OPENING SPACE)


(180)

SkyAir RXS, RKS, RZR Series

55
30

295 OR MORE

150

89
DRAIN HOSE (ACCESSORY)
SUCTION GRILLE
AIR DISCHARGE GRILL
REMOTE CONTROL CODE
AND CONTROL WIRING CONNECTION
4 POWER SUPPLY CONNECTION
3 DRAIN PIPE CONNECTION
2 GAS PIPE CONNECTION
1 LIQUID PIPE CONNECTION
PART NAME
ITEM

8
7
6
5

1500mm OR MORE *

1500mm
OR MORE *

3D039003B

VP20 (O.D. 26)


9.5 (FLARE CONNECTION)
6.4 (FLARE CONNECTION)
REMARK

I.D. 25 (OUTLET)

* WHEN THE DISCHARGE GRILL IS CLOSEOUT,


THE REQUIRED SPACE IS 200mm OR MORE.

1500mm
OR MORE *

CEILING

OUTDOOR AIR INTAKE


(DIRECT CONNECTION)
B ARROW VIEW

100

210

REQUIRED SPACE
1500mm OR MORE *

4-M4 HOLE

89

Unit (mm)

5.1.2

1500 OR MORE
(REQUIRED SPACE)
FROM THE FLOOR SIDE
2500 OR MORE
FOR HEIGHT INSTALLATION

585~660 (CEILING OPENING SPACE)


300 OR LESS 533 (SUSPENTION POSITION)
320

EDSG281001
Dimensions and Service Space

FFQ

FFQ25BV1B / FFQ35BV1B

27

260
25

62.5

196

575

A ARROW VIEW

211

172

700
1

62.5

PIPE CONNECTION
SIDE

DRAIN CONNECTION
SIDE

NOTE) 2.

45 OR LESS

62.5

320

45 OR LESS
NOTE) 4.

575

533 (SUSPENTION POSITION)


5

62.5

585~660 (CEILING OPENING SPACE)


(180)

700

145
183
285

A
NOTE) 1. STICKING LOCATION FOR MANUFACTURE'S LABEL
MANUFACTURE'S LABEL FOR INDOOR UNIT : ON THE BELL MOUTH INSIDE
SUCTION GRILLE
MANUFACTURE'S LABEL FOR DECORATION PANEL : ON THE INNER FRAME
INSIDE SUCTION GRILLE
2. IN CASE OF USING WIRELESS REMOTE CONTROLLER, THIS POSITION WILL
BE A SIGNAL RECEIVER.
REFER TO THE DRAWING OF WIRELESS REMOTE CONTROLLER IN DETAIL. DECORATION PANEL
3. WHEN THE TEMPERATURE AND HUMIDITY IN THE CEILING EXCEED 30C
BYFQ60BW1 WHITE Ral 9010
AND RH 80% OR THE FRESH AIR IS INDUCTED INTO THE CEILING OR THE
UNIT CONTINUES 24 HOUR OPERATION, AN ADDITIONAL INSULATION
(THICKNESS 10mm OR MORE OF GLASSWOOL OR POLYETHYLENE FORM)
IS REQUIRED.
4. THOUGH THE INSTALLATION IS ACCEPTABLE UP TO MAXIMUM OF 660mm
SQUARE CEILING OPENING, KEEP THE CLEARANCE OF 45mm OR LESS
BETWEEN THE MAIN UNIT AND THE CEILING OPENING SO THAT THE PANEL
OVERLAP ALLOWANCE CAN BE ENSURED.

SUSPENTION BOLT
4-M8~M10

205

750
ADJUSTABLE (0~545)

55
30

295 OR MORE

28
1500 OR MORE
(REQUIRED SPACE)
FROM THE FLOOR SIDE
2500 OR MORE
FOR HEIGHT INSTALLATION

585~660 (CEILING OPENING SPACE)


300 OR LESS 533 (SUSPENTION POSITION)
320

150

89
DRAIN HOSE (ACCESSORY)
SUCTION GRILLE
AIR DISCHARGE GRILL
REMOTE CONTROL CODE
AND CONTROL WIRING CONNECTION
4 POWER SUPPLY CONNECTION
3 DRAIN PIPE CONNECTION
2 GAS PIPE CONNECTION
1 LIQUID PIPE CONNECTION
PART NAME
ITEM

8
7
6
5

1500mm OR MORE *

1500mm
OR MORE *

3D039005B

VP20 (O.D. 26)


12.7 (FLARE CONNECTION)
6.4 (FLARE CONNECTION)
REMARK

I.D. 25 (OUTLET)

* WHEN THE DISCHARGE GRILL IS CLOSEOUT,


THE REQUIRED SPACE IS 200mm OR MORE.

1500mm
OR MORE *

CEILING

OUTDOOR AIR INTAKE


(DIRECT CONNECTION)
B ARROW VIEW

100

210

REQUIRED SPACE
1500mm OR MORE *

4-M4 HOLE

89

Unit (mm)

Dimensions and Service Space


EDSG281001

FFQ50BV1B / FFQ60BV1B

SkyAir RXS, RKS, RZR Series

EDSG281001

5.1.3

Dimensions and Service Space

FHQ

SkyAir RXS, RKS, RZR Series

3D037996A

Unit (mm)

FHQ35BVV1B

29

155

Obstacle

55

Floor side

Drain pipe
connection VP20
(For left piping)

30 or more
(Service space)

16

The front

960

(Hanging position)

920

17

127

142

170

105

13

4-M8 ~ M10

18

90
58

85

160

(Note.2)

Brand name plate

30 or more
(Service space)

10

36
192

135

40

105

Note) 1. Location of unit's Name plate : Bottom of fan housing inside the suction grille.
2. In case of using wireless remote controller, this position will be a signal
receiver. Refer to the drawing of wireless remote controller in detail.
3. The remote control code is the standard <about 3m outside the machine> attached.
(0.5mm2 2 wicks O.D. 5.4)
(It is not attached to VRV.)

For height installaion

80

(Required space)

80

From the floor side 2500 or more

680

300 or more
(Required space)

210
Hanging bolt

195

11

45

50

65

145

100
60
36
26

Upward drain pipe connection


Upward gas pipe connection
Upward liquid pipe connection

16
17
18

3D027536D

Slit hole
Hole of wall for taking out in piping back
15

Slit hole
Right side drain pipe connection
14

Slit hole
Left back drain pipe connection
Left side drain pipe connection

Right side pipe connection


12
13

Slit hole

Upward piping and wiring connection opening lid


11

M4
Suspention bracket
8

Backward piping and wiring connection opening lid

VP 20
Earth terminal (Inside the electric components box)
7

6.4 flare
Drain pipe connection
6

10

12.7 flare
4

Description

Liquid pipe connection

Air filter
3

Name

Gas pipe connection

Air suction grille


2

105

65

Position : Hole of wall


for taking out in piping back
(View from the front)

60

(Required space)

Air discharge grille

14

Number

55

80

15

(View from the front)

Position slit hole for taking out in piping back

60

12
115 60
5

170

40

260
300

90

102
225

(Hanging position)

275

185
275

135

30
155

Unit (mm)

Dimensions and Service Space


EDSG281001

FHQ50BVV1B

SkyAir RXS, RKS, RZR Series

Obstacle
Floor side

55

Drain pipe
connection VP20
(For left piping)

30 or more
(Service space)

80

18 17

The front

1160

1120
(Hanging position)

Note) 1. Location of unit's Name plate: Bottom of fan housing inside the suction grille.
2. In case of using wireless remote controller, this position will be a signal receiver.
Refer to the drawing of wireless remote controller in detail.
3. The remote control code is the standard <about 3m outside the machine> attached.
(0.5mm2 2wicks O. D. 5.4)
(It is not attached to VRV.)

13

5
(Required space)

For height installaion


From the floor side 2500 or more
155

680

300 or more
(Required space)

Hanging bolt
4-M8~M10

195
300

80
170

105

127

65

80

14

15

65
3D037994A

Slit hole
Slit hole
Slit hole
Slit hole
100
60
36
26

12.7 flare
6.4 flare
VP20
M4

Description

Position : Hole of wall


for taking out in piping back
(View from the front)

105

145 60

Name
Air discharge grille
Air suction grille
Air filter
Gas pipe connection
Liquid pipe connection
Drain pipe connection
Earth terminal (Inside the electric components box)
Suspention bracket
Backward piping and wiring connection opening lid
Upward piping and wiring connection opening lid
Right side pipe connection
Left back drain pipe connection
Left side drain pipe connection
Right side drain pipe connection
Hole of wall for taking out in piping back
Upward drain pipe connection
Upward gas pipe connection
Upward liquid pipe connection

55

Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

11

45

Brand name plate


(Note. 2)

30 or more
(Services pace)

60

12

Position slit hole for taking out in piping back


(View from the front)

50

36

85
102
160
185
192
10

135

Unit (mm)

115 60
5
135 (Required space)

170
105
90
16 142
58

40

210
260
(Hanging position)
275

90

40

275

155

SkyAir RXS, RKS, RZR Series


225

EDSG281001
Dimensions and Service Space

FHQ60BVV1B

31

155

(Required space)

13

Obstacle

55

Floor side

4-M8 ~ M10

Drain pipe
connection VP20
(For left piping)

30 or more
(Service space)

80

The front

1160

(Hanging position)

1120

18 17 16

105

80

90

170

127

142
58

85

185

(Note.2)

Brand name plate

30 or more
(Service space)

10

36
192

135

40

105

50

11

45

65

145

Upward piping and wiring connection opening lid


Right side pipe connection
Left back drain pipe connection

11
12

18

Upward liquid pipe connection

3D027538F

26

36

60
Upward drain pipe connection
16

Upward gas pipe connection

100
Hole of wall for taking out in piping back
15

17

Slit hole
Right side drain pipe connection
14

Slit hole

Slit hole

Backward piping and wiring connection opening lid


9
10

Left side drain pipe connection

Suspention bracket
8

13

Slit hole

Earth terminal (Inside the electric components box)


7

M4

VP20

9.5 flare
Drain pipe connection

Liquid pipe connection


6

15.9 flare
Gas pipe connection
5

Description

Air filter

Name

Air suction grille

Air discharge grille

14

65

Position : Hole of wall


for taking out in piping back
(View from the front)

105

60

(Required space)

Number

55

80

15

Position slit hole for taking out in piping back


(View from the front)

60

12

40

170

90

210

For height installaion

Note) 1. Location of unit's Name plate : Bottom of fan housing inside the suction grille.
2. In case of using wireless remote controller, this position will be a signal
receiver. Refer to the drawing of wireless remote controller in detail.
3. The remote control code is the standard <about 3m outside the machine> attached.
2
(0.5mm 2 wicks O.D. 5.4)
(It is not attached to VRV.)

From the floor side 2500 or more

680

300 or more
(Required space)

(Hanging position)

Hanging bolt

195
300

160
275

260
275

102
225

155

115 60
135

32
5

Unit (mm)

Dimensions and Service Space


EDSG281001

FHQ71BVV1B

SkyAir RXS, RKS, RZR Series

155

13

Obstacle

55

680

Floor side

300 or more

Drain pipe
connection VP20
(For left piping)

(Service space)

30 or more

80

The front

1400

(Hanging position)

1360

18 17

16

105

80

170

127

142

90

102
185

(Service space)

30 or more

10

(Note.2)

36
192

Brand name plate

85

58
135
40

105

11

65

145

100
60
36

Upward drain pipe connection


Upward gas pipe connection

16

18

26

Slit hole

Hole of wall for taking out in piping back


15

Upward liquid pipe connection

Slit hole

Right side drain pipe connection


14

Slit hole

Left back drain pipe connection


12

Left side drain pipe connection

Right side pipe connection


11

13

Slit hole

Backward piping and wiring connection opening lid


Upward piping and wiring connection opening lid

3D044893A

M4

Suspention bracket
8
9

VP20

Earth terminal (Inside the electric components box)


7

10

9.5 flare

15.9 flare

Drain pipe connection

17

115 60

Description

Gas pipe connection

Name

Liquid pipe connection

Air filter
4

135

Position:Hole of wall
for taking out in piping back
(View from the front)

105

60

Unit (mm)

65
5

Air suction grille


3

14

80

15

Position slit hole for taking out in piping back


(View from the front)

Air discharge grille

55

60

Number

45

50

12

(Required space)

170

40

210

(Required space)

(Required space)

For height installaion

Note) 1. Location of unit's Name plate : Bottom of fan housing inside the suction grille.
2. In case of using wireless remote controller, this position will be a signal
receiver. Refer to the drawing of wireless remote controller in detail.
3.The remote control code is the standard <about 3m outside the machine> attached.
(0.5mm2wicksO.D. 5.4)
(It is not attached to VRV.)

From the floor side 2500 or more

90

260

Hanging bolt
4-M8 ~ M10

195
300

155

(Hanging position)

275

160
275

SkyAir RXS, RKS, RZR Series


225

EDSG281001
Dimensions and Service Space

FHQ100BVV1B

33

13

(Required space)

Obstacle

55

680

Floor side

Drain pipe
connection VP20
(For left piping)

30 or more
(Service space)

80

Note) 1. Location of unit's Name plate : Bottom of fan housing inside the suction grille.
2. In case of using wireless remote controller, this position will be a signal
receiver. Refer to the drawing of wireless remote controller in detail.
3.The remote control code is the standard <about 3m outside the machine> attached.
(0.5mm2wicksO.D. 5.4)
(It is attached to VRV.)

For height installaion

155

From the floor side 2500 or more

210

Hanging bolt
4-M8 ~ M10

195

1550

The front

1590

(Hanging position)

18 17

16

105

80

170

127

142

90

30 or more
(Service space)

10

185

(Note.2)

Brand name plate

85

135

14

15

Air filter

65

145

60
36
26

Upward gas pipe connection


Upward liquid pipe connection

17
18

16

Upward drain pipe connection

100

Slit hole

Right side drain pipe connection


14

Hole of wall for taking out in piping back

Slit hole

Left side drain pipe connection


13

15

Slit hole

Left back drain pipe connection

Right side pipe connection


11
12

Backward piping and wiring connection opening lid


Upward piping and wiring connection opening lid

9
10

3D044894B

M4

Slit hole

VP20

Earth terminal (Inside the electric components box)


7

Suspention bracket

9.5 flare

Drain pipe connection

15.9 flare

115 60

Description

Liquid pipe connection

Name

Position : Hole of wall


for taking out in piping back
(View from the front)

105

60

Gas pipe connection

Air suction grille

Air discharge grille

80

3
4

Position slit hole for taking out in piping back


(View from the front)

55

60

Number

11

45

50

40

36
192

58

12

(Required space)

105

135

170

40

260

300

300 or more
(Required space)

(Hanging position)

275

160
275

90

102
225

65

34
155

Unit (mm)

Dimensions and Service Space


EDSG281001

FHQ125BVV1B

SkyAir RXS, RKS, RZR Series

EDSG281001

5.1.4

Dimensions and Service Space

FBQ-B

SkyAir RXS, RKS, RZR Series

3D053083

Unit (mm)

FBQ50BV1A

35

250
208
150

300
245
215
150
135

300
SERVICE
SPACE
NOTE) 2

5 150=750
785

1000
760
65

A VIEW

60
50
SUSPENSION BOLT

57
SERVICE SPACE
300 OR MORE

2
45

25

46

440
315

800

10

25

FBQ60 12.7 (FLARE CONNECTION)


FBQ71 15.9 (FLARE CONNECTION)

NOTE) 1. LOCATION OF UNIT'S NAME PLATE: FAN HOSING SURFACE.


2. IF THE CEILING IS NOT REMOVABLE, A 300mm SERVICE SPACE
MUST BE KEPT BETWEEN THE UNIT AND THE CEILING.
3. MOUNT THE AIR FILTER AT THE SUCTION SIDE.
SELECT ITS COLORIMETHOD (GRAVITY METHOD)
50% OR MORE.
4. PIPE SPECIFICATION

27
6 120=720

856
833

135 120

160
228
67
150
200

630
(SUSPENSION POSITION)

195

11 65=715
2 65=130

145

3 65=195

160P. C. D.
125
(KNOCK HOLE)

600

3D053084A

VP25 (O. D. 32, I. D. 25)


NOTE) 4.
6.4 FLARE CONNECTION
DESCRIPTION

VP25 (O. D. 32, I. D. 25)

600 600

B VIEW

FRESH AIR INTAKE POSITION

INSPECTION HOLE
SWITCH BOX
SUCTION FLANGE
DISCHARGE FLANGE
DRAIN HOLE
POWER WIRING PORT
INTERUNIT WIRING PORT
DRAIN PIPE CONNETION
GAS PIPE CONNECTION
LIQUID PIPE CONNECTION
NAME

6-M5HOLE
(CIRCUMFERENCE)

10
9
8
7
6
5
4
3
2
1
NUMBER

12 65=780
1050
(SUSPENSION POSITION)

36
100

Unit (mm)

Dimensions and Service Space


EDSG281001

FBQ60BV1A / FBQ71BV1A

SkyAir RXS, RKS, RZR Series

EDSG281001

5.1.5

Dimensions and Service Space

FBQ-D

SkyAir RXS, RKS, RZR Series

3D060775C

Unit (mm)

FBQ71DV1

37

Dimensions and Service Space

EDSG281001

38

3D060776C

Unit (mm)

FBQ100DV1 / FBQ125DV1 / FBQ140DV1

SkyAir RXS, RKS, RZR Series

EDSG281001

5.2

Dimensions and Service Space

Wired Remote Controller

BRC1C61

Unit (mm)

3D028952

BRC1D61
Unit (mm)
NOTE) 1. REMOTE CONTROLLER CORD AND STAPLE ARE NOT ATTACHED.
THEY ARE FIELD SUPPLIED PARTS.
SPECIFICATIONS OF CORD
REMOTE CONTROLLER DIMENSIONS

SIZE
TOTAL
LENGTH

FOR AUSTRALIA
FOR OTHER COUNTRIES
SHIELD WIRE
VINYL CORD WITH SHEATH OR CABLE
(INSULATED THICKNESS: 1mm OR MORE) (INSULATED THICKNESS: 1mm OR MORE)
0.75 ~ 1.25mm2
500m

38

84

120

42

TYPE

120

18

17

CORD OUTLET HOLE

23 28
46
INSTALLATION METHOD
A EXPOSED BODY, EXPOSED CORD

B EXPOSED BODY, EMBEDDED CORD


C EXPOSED BODY, EMBEDDED CORD
17
CONDUIT
REMOTE CONTROLLER
REMOTE CONTROLLER

REMOTE CONTROLLER

(
17

0~5
BETWEEN REMOTE
CONTROLLER AND
CONTROL BOX

117

STAPLE

17

THROUGH HOLE
(12 ~ 16)

CONTROL BOX
3D048117

SkyAir RXS, RKS, RZR Series

39

Dimensions and Service Space

EDSG281001

BRC1E61

Unit (mm)

3D064037

40

SkyAir RXS, RKS, RZR Series

EDSG281001

5.3

Dimensions and Service Space

Wireless Remote Controller

BRC7F632F (for FCQ)

Unit (mm)

3D052918C

BRC7E531W (for FFQ)


REMOTE CONTROLLER DIMENSIONS

Unit (mm)

RECEIVER INSTALLATION PROCEDURE

TRANSMITTING PART

157

DRAIN PIPING SIDE

REFRIGERANT PIPING SIDE

RECEIVER

62

17.5

REMOTE CONTROLLER HOLDER


INSTALLATION PROCEDURE
<INSTALLATION TO WALL SURFACE>
LIQUID CRYSTAL
REMOTE CONTROLLER
(WIRELESS)

RECEIVER DETAIL

DECORATION PANEL
(BYFQ60BW1)
(BYFQ60B7W1)
(BYFQ60B8W1)

REMOTE CONTROLLER
HOLDER

3D038937A

SkyAir RXS, RKS, RZR Series

41

Dimensions and Service Space

EDSG281001

BRC7EA66 (for FHQ)


Unit (mm)
REMOTE CONTROLLER DIMENSIONS
TRANSMITTING PART

157

RECEIVER INSTALLATION PROCEDURE


RECEIVER

17.5

62

REMOTE CONTROLLER HOLDER


INSTALLATION PROCEDURE
< INSTALLATION TO WALL SURFACE >

RECEIVER DETAIL

LIQUID CRYSTAL
REMOTE CONTROLLER
(WIRELESS)
REMOTE CONTROLLER
HOLDER

3D028963B

BRC4C62 (for FBQ)


Unit (mm)

RECEIVER DETAIL

157

120

REMOTE CONTROLLER DIMENSIONS


TRANSMITTING PART

62

17.5

18

0.5
35

2 5 9 Slot

REMOTE CONTROLLER HOLDER


INSTALLATION PROCEDURE
< INSTALLATION TO WALL SURFACE >

Switch box
(Field Supplied
parts)

Service space for ceiling installation


more than 90
(Service space)

REMOTE CONTROLLER
HOLDER

NOTE Do not install more than 3 receivers in the vicinity of


one another.
With 4 or more units, there is always the possibility
of malfunction.

42

72
83.5

P1 P2

LIQUID CRYSTAL
REMOTE CONTROLLER
(WIRELESS)

106
(Ceiling Opening)

70

49
(Ceiling Opening)
3D007898B

SkyAir RXS, RKS, RZR Series

EDSG281001

5.4

Dimensions and Service Space

Outdoor Unit

SkyAir RXS, RKS, RZR Series

3D059795E

Unit (mm)

RKS25AVMG / RKS35AVMG

43

Dimensions and Service Space

EDSG281001

44

3D051657P

Unit (mm)

RXS50FAVMA / RXS60FVMA
RKS50AVMG / RKS60AVMG

SkyAir RXS, RKS, RZR Series

EDSG281001

Dimensions and Service Space

SkyAir RXS, RKS, RZR Series

3D054589C

Unit (mm)

RXS71FVMA

45

Dimensions and Service Space

EDSG281001

3D065759
REMARK
ITEM

PART NAME

Unit (mm)

RZR71KUV1

46

SkyAir RXS, RKS, RZR Series

EDSG281001

Dimensions and Service Space

SkyAir RXS, RKS, RZR Series

3D065775A

Unit (mm)

RZR100KUV1 / RZR125KUV1 / RZR140KUV1

47

Dimensions and Service Space

EDSG281001

48

3D065788A

Unit (mm)

RZR100HUY1 / RZR125HUY1 / RZR140HUY1

SkyAir RXS, RKS, RZR Series

EDSG281001

5.5

Dimensions and Service Space

Installation Service Space

RZR71KUV1

3D046687C

SkyAir RXS, RKS, RZR Series

49

Dimensions and Service Space

EDSG281001

3D046687C

50

SkyAir RXS, RKS, RZR Series

EDSG281001

Dimensions and Service Space

3D046687C

SkyAir RXS, RKS, RZR Series

51

Dimensions and Service Space

EDSG281001

RZR100KUV1 / RZR125KUV1 / RZR140KUV1


RZR100HUY1 / RZR125HUY1 / RZR140HUY1

3D058489C

52

SkyAir RXS, RKS, RZR Series

EDSG281001

Dimensions and Service Space

3D058489C

SkyAir RXS, RKS, RZR Series

53

Dimensions and Service Space

EDSG281001

3D058489C

54

SkyAir RXS, RKS, RZR Series

EDSG281001

Piping Diagrams

6. Piping Diagrams
6.1

Indoor Unit

FFQ25BV1B / FFQ35BV1B / FFQ50BV1B / FFQ60BV1B

4D039335

FHQ35BVV1B / FHQ50BVV1B / FHQ60BVV1B / FHQ71BVV1B / FHQ100BVV1B / FHQ125BVV1B

C : 4D037995H

SkyAir RXS, RKS, RZR Series

55

Piping Diagrams

EDSG281001

FBQ50BV1A / FBQ60BV1A / FBQ71BV1A

4D053090A

56

SkyAir RXS, RKS, RZR Series

EDSG281001

6.2

Piping Diagrams

Indoor Unit + Outdoor Unit

1
3D065423

FCQ71KVEA / FHQ71BVV1B / FBQ71DV1 + RZR71KUV1

SkyAir RXS, RKS, RZR Series

57

Piping Diagrams

EDSG281001

3D065422A

FCQ100KVEA / FHQ100BVV1B / FBQ100DV1 + RZR100KUV1

58

SkyAir RXS, RKS, RZR Series

EDSG281001

Piping Diagrams

1
3D065869A

FCQ125KVEA / FHQ125BVV1B / FBQ125DV1 + RZR125KUV1


FCQ140KVEA / FBQ140DV1 + RZR140KUV1

SkyAir RXS, RKS, RZR Series

59

Piping Diagrams

EDSG281001

3D065421B

FCQ100KVEA / FHQ100BVV1B / FBQ100DV1 + RZR100HUY1

60

SkyAir RXS, RKS, RZR Series

EDSG281001

Piping Diagrams

1
3D065843B

FCQ125KVEA / FHQ125BVV1B / FBQ125DV1 + RZR125HUY1


FCQ140KVEA / FBQ140DV1 + RZR140HUY1

SkyAir RXS, RKS, RZR Series

61

Piping Diagrams

6.3

EDSG281001

Outdoor Unit

3D047318G

RKS25AVMG / RKS35AVMG

62

SkyAir RXS, RKS, RZR Series

EDSG281001

Piping Diagrams

1
3D051636N

RKS50AVMG / RKS60AVMG

SkyAir RXS, RKS, RZR Series

63

Piping Diagrams

EDSG281001

3D051637Q

RXS50FAVMA / RXS60FVMA

64

SkyAir RXS, RKS, RZR Series

EDSG281001

Piping Diagrams

1
3D054593F

RXS71FVMA

SkyAir RXS, RKS, RZR Series

65

INDOOR UNIT
PRINTED CIRCUIT BOARD
PRINTED CIRCUIT BOARD
(HUMIDITY SENSOR UNIT)
C1
CAPACITOR
HAP LIGHT EMITTING DIODE
(SERVICE MONITOR GREEN)
K1R
MAGNETIC RELAY
KPR MAGNETIC RELAY (M1P)
M1F
MOTOR (INDOOR FAN)
M1P MOTOR (DRAIN PUMP)
M1S MOTOR (SWING FLAP)
R1T
THERMISTOR (AIR)
R2T
THERMISTOR (COIL)
R3T
THERMISTOR PTC
S1L
FLOAT SWITCH
SS1
SELECTOR SWITCH
(EMERGENCY)
V1R
DIODE BRIDGE
X1M TERMINAL STRIP
X2M TERMINAL STRIP
Z1C
FERRITE CORE
Z1F
NOISE FILTER
PS
POWER SUPPLY CIRCUIT
RC
SIGNAL RECEIVER CIRCUIT
TC
SIGNAL TRANSMISSION CIRCUIT
RECEIVER/DISPLAY UNIT (ATTACHED TO
WIRELESS REMOTE CONTROLLER)
A3P
PRINTED CIRCUIT BOARD
A4P
PRINTED CIRCUIT BOARD
BS1
PUSH BUTTON (ON/OFF)
H1P
LIGHT EMITTING DIODE
(ON-RED)
H2P
LIGHT EMITTING DIODE
(TIMER-GREEN)
H3P
LIGHT EMITTING DIODE
(FILTER SIGN-RED)
H4P
LIGHT EMITTING DIODE
(DEFROST-ORANGE)
SELECTOR SWITCH
SS1
(MAIN/SUB)
SELECTOR SWITCH
SS2
(WIRELESS ADDRESS SET)
CONNECTOR FOR OPTIONAL PARTS
X24A CONNECTOR (WIRELESS
REMOTE CONTROLLER)
X33A CONNECTOR
(ADAPTOR FOR WIRING)
X35A CONNECTOR (GROUP CONTROL
ADAPTOR)
WIRED REMOTE CONTROLLER
THERMISTOR (AIR)
R1T
SELECTOR SWITCH (MAIN/SUB)
SS1

A1P
A2P

WHT
RED

2
3

CONTROL BOX

X35A X33A

A1P

A2P

X2M

X27A

A2P

CN1 R1T

X16A

X25A
YLW
YLW

Z1F K1R

RC TC

KPR

M
~
M1P

+
PS

X15A
X24A
SS1 NOTE) 3

X35A
NOTE) 3

HAP

100~140-CLASS

N=1

X36A

X33A
NOTE) 3

X30A

NORM. EMG.

X18A

MS
M1F 3~

Z1C

X20A

- C1

R3T
t V1R+

S1L

YLW
ORG
BLU
BLK

M1S

MSW

X1M
F2
F1
P2
P1

X24A
NOTE) 3

A1P
SS2

SS1

A4P
H1P
H2P BS1
H3P
H4P

MS
3~
71-CLASS

M1F

WHT

Z1C

X20A
N=1

NOTE) 2
CENTRAL REMOTE
CONTROLLER
P2
P1 R1T WIRED REMOTE
CONTROLLER
SS1

X1A
X1A
RECEIVER/DISPLAY UNIT

X2A

A3P

3D058379A

NOTES)
1.
: TERMINAL
,
: CONNECTOR
: FIELD WIRING
2. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION
MANUAL.
3. X24A, X33A, X35A ARE CONNECTED WHEN THE OPTIONAL ACCESSORIES ARE BEING USED.
4. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING DATA AND CATALOGS,
ETC. BEFORE CONNECTING.
5. CONFIRM THE METHOD OF SETTING THE SELECTOR SWITCH (SS1, SS2) BY INSTALLATION MANUAL AND ENGINEERING DATA, ETC.
6. SYMBOLS SHOWS AS FOLLOWS: RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW GRN : GREEN ORG : ORANGE BRN : BROWN
PNK : PINK GRY : GRAY BLU : BLUE
7. SHOWS ONLY IN CASE OF PROTECTED PIPES.
USE H07RN-F IN CASE OF NO PROTECTION.

X1M

X24A

REMOTE CONTROLLER

INDOOR UNIT INDOOR UNIT


(MASTER)
(SLAVE)
X2M
X2M
1
1
2
2
3
3

IN CASE OF SIMULTANEOUS
OPERATION SYSTEM

H05VV-U4G2.5
NOTE) 7
GRN/YLW

BLK

X2M

A1P

WHT
ORG
BRN
BLU

TO OUTDOOR
UNIT

TO OUTDOOR UNIT

R2T

RED

66
WHT
ORG
BRN
BLU

7.1

RED

GRN

Wiring Diagrams
EDSG281001

7. Wiring Diagrams
Indoor Unit

FCQ71KVEA / FCQ100KVEA / FCQ125KVEA / FCQ140KVEA

SkyAir RXS, RKS, RZR Series

EDSG281001

Wiring Diagrams

1
3D064844

FFQ25BV1B / FFQ35BV1B / FFQ50BV1B / FFQ60BV1B

SkyAir RXS, RKS, RZR Series

67

X15A
X25A
X33A
X35A
X40A
X60A
X61A

A3P
A4P
BS1
H1P
H2P
H3P
H4P
SS1
SS2

PRINTED CIRCUIT BOARD


PRINTED CIRCUIT BOARD
PUSH BUTTON (ON/OFF)
LIGHT EMITTING DIODE (ON-RED)
LIGHT EMITTING DIODE (TIMER-GREEN)
LIGHT EMITTING DIODE (FILTER SIGN-RED)
LIGHT EMITTING DIODE (DEFROST-ORANGE)
SELECTOR SWITCH (MAIN/SUB)
SELECTOR SWITCH (WIRELESS ADDRESS SET)
CONNECTOR FOR OPTIONAL PARTS
CONNECTOR (FLOAT SWITCH)
CONNECTOR (DRAIN PUMP)
CONNECTOR (ADAPTOR FOR WIRING)
CONNECTOR (GROUP CONTROL ADAPTOR)
CONNECTOR (ON/OFF INPUT FROM OUTSIDE)
CONNECTOR
(INTERFACE ADAPTOR FOR SKY AIR SERIES)

WIRELESS REMOTE CONTROLLER


(RECEIVER/DISPLAY UNIT)

PRINTED CIRCUIT BOARD


CAPACITOR (M1F)
FUSE (F5A 250V)
LIGHT EMITTING DIODE (SERVICE MONITOR GREEN)
MAGNETIC RELAY (M1S)
MAGNETIC RELAY (M1P)
MOTOR (INDOOR FAN)
MOTOR (SWING FLAP)
THERMO SWITCH (M1F EMBEDDED)
THERMISTOR (AIR)
THERMISTOR (COIL-1)
THERMISTOR (COIL-2)
LIMIT SWITCH (SWING FLAP)
TRANSFORMER (220-240V/22V)
PHASE CONTROL CIRCUIT
TERMINAL BLOCK
TERMINAL BLOCK
SIGNAL RECEIVER CIRCUIT
SIGNAL TRANSMISSION CIRCUIT
WIRED REMOTE CONTROLLER
THERMISTOR (AIR)
SELECTOR SWITCH (MAIN/SUB)
X1M X2M

C1 T1R

X2M

A1P

X2M
F1U
1 BLK
2 WHT
3 RED

: CONNECTOR

X40A

X27A

A1P

RC

X60A

X61A

TC

X19A

t
X17A

X33A

X25A NOTE) 6

X35A HAP

X20A

X15A

X14A

KAR X29A

V1TR

S1Q

MSW
~
M1S

M1F

NOTE) 6

BLK
BLK

BLK

RED

M
~

Q1M

X1M
SS1
P2
P2
X24A
P1 R1T
P1
NOTE)4 X5A
WIRED REMOTE
CONTROLLER
GRY
PRP
BLU
C1
X26A

: CONNECTER COLOUR FOR PRINTED CIRCUIT BOARD.

: CONNECTER COLOUR FOR COMPONENTS.

: CONNECTER DISCRIMINATION COLOUR FOR COMPONENTS.

X10A T1R X11A

YLW

WHT

YLW

R3T

KPR

X18A

R2T

3D037842D

2.
: FIELD WIRING
3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED
INSTALLATION MANUAL.
4. X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED.
5. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING MATERIALS AND
CATALOGS, ETC. BEFORE CONNECTING.
6. IN CASE INSTALLING THE DRAIN PUMP(M1P), REMOVE THE JUMPER CONNECTOR OF X15A AND EXECUTE THE ADDITIONAL
WIRING FOR FLOAT SWITCH AND DRAIN PUMP.
7. SYMBOLS SHOW AS FOLLOWS: RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW PRP : PURPLE GRY : GRAY BLU : BLUE

NOTES)
1.
: TERMINAL

CONTROL BOX

A1P

1
2
3

TO OUTDOOR UNIT

H05VV-U4G2.5
A3P
A4P
SS1
H1P
REMOTE
H2PBS1
CONTROLLER
SS2
H3P
X24A X2A
H4P
NOTE) 4
X1A X1A
RECEIVER/DISPLAY UNIT

X2M

1
2
3

INDOOR UNIT INDOOR UNIT


(MASTER)
(SLAVE)

IN CASE OF SIMULTANEOUS
OPERATION SYSTEM
TO OUTDOOR UNIT

R1T

YLW
WHT

68

R1T
SS1

A1P
C1
F1U
HAP
KAR
KPR
M1F
M1S
Q1M
R1T
R2T
R3T
S1Q
T1R
V1TR
X1M
X2M
RC
TC

Wiring Diagrams
EDSG281001

FHQ35BVV1B / FHQ50BVV1B / FHQ60BVV1B

SkyAir RXS, RKS, RZR Series

SkyAir RXS, RKS, RZR Series

H1P
CAPACITOR (M1F)
LIGHT EMITTING DIODE
(SERVICE MONITOR GREEN) H2P

SELECTOR SWITCH
(MAIN/SUB)

MOTOR (SWING FLAP) H4P


THERMO SWITCH (M1F EMBEDDED)

THERMISTOR (AIR)

THERMISTOR (COIL)

LIMIT SWITCH (SWING FLAP) SS2

TRANSFORMER (220-240V/22V)

M1S

Q1M

R1T

R2T

S1Q

T1R

SELECTOR SWITCH
(WIRELESS ADDRESS SET)

TERMINAL BLOCK
X25A CONNECTOR (DRAIN PUMP)
SIGNAL RECEIVER CIRCUIT X33A CONNECTOR
(ADAPTOR FOR WIRING)
SIGNAL TRANSMISSION CIRCUIT

2.

TO OUTDOOR UNIT

X61A
X40A
X60A

X2M

CONTROL BOX

T1R

C1

X1M

X35A X24A

A1P

X15A X33A X25A

X2A

SS2

SS1

X1A

X1A

A3P

H05VV-U4G2.5

A2P
H1P
BS1
H2P
H3P
H4P

X40A

X27A

A1P

RC

X60A

X61A

R1T

TC

X19A

R2T

X25A

KPR

X33A

X5A

X15A

X14A

KAR X29A

X20A

X26A

X24A
NOTE)4

V1TR

X35A HAP

T1R X11A
t

NOTE)6

X10A

X18A

C1

SS1
P2
P1

R1T

S1Q

~
M1S

MSW

M1F

3D043825B

Q1M

WIRED REMOTE
CONTROLLER

NOTE)6

BLK

BLK

BLK

RED

GRY
PRP
BLU

P1

P2

X1M

3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH
THE ATTACHED INSTALLATION MANUAL.
4. X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED.
5. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM,
CONFIRM ENGINEERING MATERIALS AND CATALOGS, ETC. BEFORE CONNECTING.
6. IN CASE INSTALLING THE DRAIN PUMP (M1P), REMOVE THE JUMPER CONNECTOR OF X15A AND EXECUTE THE ADDITIONAL
WIRING FOR FLOAT SWITCH AND DRAIN PUMP.
7. SYMBOLS SHOW AS FOLLOWS: RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW PRP : PURPLE GRY : GRAY BLU : BLUE

RECEIVER/DISPLAY UNIT

A1P

REMOTE
CONTROLLER
X24A
NOTE)4

X2M

: FIELD WIRING

X2M

IN CASE OF SIMULTANEOUS
OPERATION SYSTEM
INDOOR UNIT INDOOR UNIT TO OUTDOOR X2M
(MASTER) (SLAVE)
1 BLK
UNIT
2 WHT
1
1
3 RED
2
2

SS1 SELECTOR SWITCH (MAIN/SUB) X40A CONNECTOR


(ON/OFF INPUT FROM OUTSIDE) NOTES)
WIRELESS REMOTE CONTROLLER
(RECEIVER/DISPLAY UNIT)
X60A CONNECTOR
: TERMINAL
1.
A2P PRINTED CIRCUIT BOARD X61A (INTERFACE ADAPTOR
,
: CONNECTOR
FOR SKY AIR SERIES)
A3P PRINTED CIRCUIT BOARD

TC
WIRED REMOTE CONTROLLER X35A CONNECTOR
(GROUP CONTROL ADAPTOR)
R1T THERMISTOR (AIR)

RC

X2M

V1TR PHASE CONTROL CIRCUIT CONNECTOR FOR OPTIONAL PARTS


X1M TERMINAL BLOCK
X15A CONNECTOR (FLOAT SWITCH)

SS1

LIGHT EMITTING DIODE


(DEFROST-ORANGE)

MOTOR (INDOOR FAN)

LIGHT EMITTING DIODE


(FILTER SIGN-RED)

M1F

KPR

MAGNETIC RELAY (M1S)


MAGNETIC RELAY (M1P) H3P

LIGHT EMITTING DIODE


(TIMER-GREEN)

LIGHT EMITTING DIODE


(ON-RED)

PUSH BUTTON (ON/OFF)

KAR

HAP

PRINTED CIRCUIT BOARD BS1

C1

YLW
WHT

A1P

EDSG281001
Wiring Diagrams

FHQ71BVV1B / FHQ100BVV1B / FHQ125BVV1B

69

CAPACITOR (M1F)

FUSE (250V, 5A, B )

LIGHT EMITTING DIODE

F1U

HAP

MAGNETIC RELAY (M1P)

MOTOR (INDOOR FAN)

MOTOR (DRAIN PUMP)

THERMO SWITCH (M1F EMBEDDED)

THERMISTOR (AIR)

THERMISTOR (LIQUID)

THERMISTOR (COIL)

SELECTOR SWITCH

KPR

M1F

M1P

Q1M

R1T

R2T

R3T

SS1

TRANSFORMER

T1R

TERMINAL STRIP

SIGNAL RECEIVER CIRCUIT

SIGNAL TRANSMISSION CIRCUIT

X2M

RC

TC

SELECTOR SWITCH (MAIN/SUB)

SS1

(INTERFACE ADAPTOR

FOR SKYAIR SERIES)

CONNECTOR

X61A

(GROUP CONTROL ADAPTOR)

CONNECTOR

(ADAPTOR FOR WIRING)

CONNECTOR

X60A

X35A

X33A

CONNECTOR FOR OPTIONAL PARTS

THERMISTOR (AIR)

R1T

WIRED REMOTE CONTROLLER

TERMINAL STRIP

X1M

(220-240V/22V)

FLOAT SWITCH

S1L

(EMERGENCY)

MAGNETIC RELAY (M1F)

K1R~4R

(SERVICE MONITOR GREEN)

PRINTED CIRCUIT BOARD

C1

X35A
X60A
X33A
X61A
C1

RED

X1M

T1R

X2M

CONTROL BOX

SS1 NOTE) 7

A1P

WHT

BLK

F1U

X27A

RC

X60A

X61A

INDOOR UNIT

TC

X18A

X33A

X25A WHT

KPR

X35A HAP

M
~
M1P

X10A T1R X11A


t

X19A

SS1

X17A

A1P
X1M
P2
P1

WIRED REMOTE
CONTROLLER
(OPTIONAL PARTS)
SS1
P2
P1 R1T

FH

K1R

X15A

FC

FL
FM

K3R

RED

GRY

BLK

BLU

S1L

M1F WHT
M
C1
~
YLW
Q1M

X21A NOTE) 7 NOTE) 7


ORG
FLL

X5A

K2R

K4R

NORM. EMG.

R3T

3D052779B

NOTES) 1.
: TERMINAL
,
: CONNECTOR
2.
: FIELD WIRING
3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN
ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
4. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM,
CONFIRM ENGINEERING MATERIALS AND CATALOGS, ETC. BEFORE CONNECTING.
5. SYMBOLS SHOW AS FOLLOWS : RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW
GRN : GREEN GRY : GRAY BLU : BLUE ORG : ORANGE
6. CONFIRM THE METHOD OF SETTING THE SELECTOR SWITCH (SS1) BY INSTALLATION
MANUAL AND ENGINEERING MATERIALS, ETC.
7. GROUND THE SHIELD OF THE REMOTE CONTROLLER CORD TO THE INDOOR UNIT.

H05VV-U4G2.5

TO OUTDOOR UNIT

X2M

R2T

R1T

GRN/YLW

70

A1P

Wiring Diagrams
EDSG281001

FBQ50BV1A / FBQ60BV1A / FBQ71BV1A

SkyAir RXS, RKS, RZR Series

EDSG281001

Wiring Diagrams

1
3D066031A

FBQ71DV1 / FBQ100DV1 / FBQ125DV1 / FBQ140DV1

SkyAir RXS, RKS, RZR Series

71

Wiring Diagrams

7.2

EDSG281001

Outdoor Unit

3D046707M

RKS25AVMG / RKS35AVMG

72

SkyAir RXS, RKS, RZR Series

EDSG281001

Wiring Diagrams

1
3D050981L

RKS50AVMG / RKS60AVMG

SkyAir RXS, RKS, RZR Series

73

Wiring Diagrams

EDSG281001

3P193830

RXS50FAVMA

74

SkyAir RXS, RKS, RZR Series

EDSG281001

Wiring Diagrams

1
3P177229B

RXS60FVMA

SkyAir RXS, RKS, RZR Series

75

Wiring Diagrams

EDSG281001

3D053931J

RXS71FVMA

76

SkyAir RXS, RKS, RZR Series

EDSG281001

Wiring Diagrams

1
3D065772A

RZR71KUV1

SkyAir RXS, RKS, RZR Series

77

Wiring Diagrams

EDSG281001

3D065771A

RZR100KUV1 / RZR125KUV1 / RZR140KUV1

78

SkyAir RXS, RKS, RZR Series

EDSG281001

Wiring Diagrams

1
3D065770

RZR100HUY1 / RZR125HUY1 / RZR140HUY1

SkyAir RXS, RKS, RZR Series

79

Wiring Diagrams

7.3

EDSG281001

Field Wiring

RZR71KUV1 / RZR100KUV1 / RZR125KUV1 / RZR140KUV1

C : 4D067292

80

SkyAir RXS, RKS, RZR Series

EDSG281001

Electric Characteristics

8. Electric Characteristics
8.1

RXS50FAVMA / RXS60FVMA / RXS71FVMA


RKS25AVMG / RKS35AVMG / RKS50AVMG / RKS60AVMG
REPRESENTATIVE UNIT
COMBINATION

POWER SUPPLY

COMP

INDOOR UNIT

OUTDOOR UNIT

Hz-Volts

VOLTAGE
RANGE

MCA

MFA

RHz

FFQ25BV1B

RKS25AVMG

50 - 220
50 - 230
50 - 240

MAX.50Hz 264V
MIN.50Hz 198V

9.75

10

55

50 - 220
50 - 230
50 - 240

MAX.50Hz 264V
MIN.50Hz 198V

FFQ35BV1B

FHQ35BVV1B

FFQ50BV1B

FHQ50BVV1B

FBQ50BV1A

FFQ60BV1B

FHQ60BVV1B

FBQ60BV1A

FBQ71BV1A

RKS35AVMG

RKS35AVMG

RKS50AVMG

RKS50AVMG

RXS50FAVMA

RKS60AVMG

RKS60AVMG

RXS60FVMA

RXS71FVMA

IFM

FLA

FLA

23

0.16

55

0.6

23

0.16

55

0.6

23

0.22

62

0.6

53

0.32

55

0.7

53

0.32

62

0.6

53

0.19

85

0.7

53

0.39

55

0.7

53

0.39

62

0.6

53

0.39

85

0.8

66

0.40

110

0.8

3.7
3.5
3.4
4.8
9.75

10

79

4.6
4.4
4.5

50 - 220
50 - 230
50 - 240

MAX.50Hz 264V
MIN.50Hz 198V

50 - 220
50 - 230
50 - 240

MAX.50Hz 264V
MIN.50Hz 198V

50 - 220
50 - 230
50 - 240

MAX.50Hz 264V
MIN.50Hz 198V

50 - 220
50 - 230
50 - 240

MAX.50Hz 264V
MIN.50Hz 198V

50 - 220
50 - 230
50 - 240

MAX.50Hz 264V
MIN.50Hz 198V

50 - 220
50 - 230
50 - 240

MAX.50Hz 264V
MIN.50Hz 198V

50 - 220
50 - 230
50 - 240

MAX.50Hz 264V
MIN.50Hz 198V

50 - 220
50 - 230
50 - 240

MAX.50Hz 264V
MIN.50Hz 198V

SYMBOLS:
MCA : MIN. CIRCUIT AMPS (A)
MFA : MAX. FUSE AMPS (A)
RLA : RATED LOAD AMPS (A)
OFM : OUTDOOR FAN MOTOR
IFM : INDOOR FAN MOTOR
FLA : FULL LOAD AMPS (A)
W
: FAN MOTOR RATED OUTPUT (W)
RHz : RATED OPERATING FREQUENCY (Hz)

RLA

OFM

9.75

10

76

4.3
4.1
7.1

19.75

20

71

6.8
6.5
7.6

19.75

20

76

7.2
6.9
8.9

19.75

20

77

8.4
8.1
9.2

19.75

20

83

8.8
8.4
8.8

19.75

20

87

8.4
8.1
10.0

19.75

20

86

9.6
9.2
11.6

19.75

20

61

11.1
10.6

NOTES:
1. RLA is based on the following conditions.
Indoor temp. 27CDB/19CWB
Outdoor temp. 35CDB.
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.

3D054913E
3D055934D
3D040400E
3D054945F
C : 3D054944C
3D055935E
3D054946C
3D054947B

SkyAir RXS, RKS, RZR Series

81

Electric Characteristics

8.2

EDSG281001

RZR71KUV1 / RZR100KUV1 / RZR125KUV1 / RZR140KUV1

4D066509

82

SkyAir RXS, RKS, RZR Series

EDSG281001

Electric Characteristics

C : 3D066073

SkyAir RXS, RKS, RZR Series

83

Electric Characteristics

8.3

EDSG281001

RZR100HUY1 / RZR125HUY1 / RZR140HUY1

4D066511

84

SkyAir RXS, RKS, RZR Series

EDSG281001

Electric Characteristics

C : 3D066073

SkyAir RXS, RKS, RZR Series

85

Capacity Tables

EDSG281001

9. Capacity Tables
9.1

Capacity Tables

FFQ25BV1B + RKS25AVMG

3D055938C

FFQ35BV1B + RKS35AVMG

3D055939C

86

SkyAir RXS, RKS, RZR Series

EDSG281001

Capacity Tables

FFQ50BV1B + RKS50AVMG

3D055942C

FFQ60BV1B + RKS60AVMG

3D055943C

SkyAir RXS, RKS, RZR Series

87

Capacity Tables

EDSG281001

FHQ35BVV1B + RKS35AVMG

COOLING
INDOOR
EWB EDB
C
C
20
14.0
22
16.0
25
18.0
27
19.0
30
22.0
32
24.0

50Hz 220 - 240V

TC
3.48
3.64
3.80
3.87
4.11
4.27

20
SHC
2.76
2.72
2.87
3.05
2.95
2.88

PI
0.81
0.81
0.81
0.82
0.82
0.83

Symbols
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total capacity
SHC : Sensible heat capacity
PI
: Power input

TC
3.33
3.48
3.64
3.72
3.95
4.11

AFR
BF
25
SHC
2.69
2.65
2.81
2.99
2.90
2.83

13
0.20

PI
0.88
0.89
0.89
0.89
0.90
0.91

OUTDOOR TEMPERATURE (CDB)


30
32
TC
SHC
PI
TC
SHC
PI
3.17 2.61 0.96 3.10 2.58 0.99
3.32 2.58 0.97 3.26 2.55 1.00
3.48 2.74 0.97 3.42 2.72 1.00
3.56 2.93 0.97 3.49 2.90 1.00
3.79 2.84 0.98 3.73 2.82 1.01
3.95 2.78 0.98 3.89 2.76 1.02

TC
3.01
3.17
3.32
3.40
3.63
3.79

35
SHC
2.54
2.51
2.68
2.87
2.79
2.73

PI
1.04
1.04
1.05
1.05
1.06
1.06

TC
2.85
3.01
3.16
3.24
3.48
3.63

40
SHC
2.47
2.44
2.61
2.80
2.73
2.68

PI
1.12
1.12
1.13
1.13
1.13
1.14

NOTES:
1. Capacities are based on the following conditions.
(1) Corresponding refrigerant piping length : 7.5m
(2) Level difference
: 0m
2.
shows nominal (rated) capacities and power input.

(m/min.)
(C)
(C)
(kW)
(kW)
(kW)

3D054891B

FHQ50BVV1B + RKS50AVMG

COOLING

50Hz 230V

AFR
BF

INDOOR
EWB EDB
C
C
20
14.0
22
16.0
25
18.0
27
19.0
30
22.0
32
24.0

20
SHC
3.71
3.64
3.80
4.00
3.85
3.74

25
SHC
3.59
3.53
3.70
3.90
3.76
3.66

TC
5.12
5.35
5.58
5.70
6.04
6.27

PI
1.32
1.33
1.33
1.34
1.35
1.36

Symbols
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total capacity
SHC : Sensible heat capacity
PI
: Power input

TC
4.89
5.12
5.35
5.47
5.81
6.04

(m/min.)
(C)
(C)
(kW)
(kW)
(kW)

13
0.10

PI
1.45
1.45
1.46
1.47
1.48
1.48

OUTDOOR TEMPERATURE (CDB)


30
32
TC
SHC
PI
TC
SHC
PI
4.66 3.47 1.57 4.56 3.43 1.62
4.89 3.42 1.58 4.79 3.38 1.63
5.12 3.59 1.59 5.02 3.55 1.64
5.23 3.80 1.59 5.14 3.76 1.64
5.58 3.67 1.60 5.49 3.64 1.66
5.81 3.58 1.61 5.72 3.55 1.66

TC
4.42
4.65
4.88
5.00
5.35
5.58

35
SHC
3.36
3.31
3.49
3.70
3.58
3.50

PI
1.70
1.71
1.72
1.72
1.73
1.74

TC
4.19
4.42
4.65
4.77
5.11
5.34

40
SHC
3.24
3.20
3.39
3.60
3.50
3.42

PI
1.83
1.84
1.84
1.85
1.86
1.87

NOTES:
1. Capacities are based on the following conditions.
(1) Corresponding refrigerant piping length : 7.5m
(2) Level difference
: 0m
2.
shows nominal (rated) capacities and power input.

3D055285B

88

SkyAir RXS, RKS, RZR Series

EDSG281001

Capacity Tables

FHQ60BVV1B + RKS60AVMG

COOLING

50Hz 230V

AFR
BF

INDOOR
EWB EDB
C
C
20
14.0
22
16.0
25
18.0
27
19.0
30
22.0
32
24.0

20
SHC
4.25
4.18
4.36
4.59
4.42
4.30

25
SHC
4.12
4.05
4.25
4.48
4.32
4.21

TC
5.84
6.10
6.36
6.50
6.89
7.15

PI
1.53
1.54
1.55
1.56
1.57
1.58

Symbols
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total capacity
SHC : Sensible heat capacity
PI
: Power input

TC
5.57
5.84
6.10
6.23
6.62
6.89

17
0.20

PI
1.68
1.69
1.70
1.70
1.72
1.73

OUTDOOR TEMPERATURE (CDB)


30
32
TC
SHC
PI
TC
SHC
PI
5.31 3.98 1.83 5.20 3.93 1.89
5.57 3.93 1.84 5.47 3.88 1.90
5.83 4.13 1.85 5.73 4.08 1.91
5.97 4.36 1.85 5.86 4.32 1.91
6.36 4.22 1.87 6.25 4.18 1.92
6.62 4.12 1.87 6.52 4.08 1.93

TC
5.04
5.31
5.57
5.70
6.09
6.36

35
SHC
3.85
3.80
4.01
4.25
4.12
4.03

PI
1.98
1.99
2.00
2.00
2.01
2.02

TC
4.78
5.04
5.30
5.43
5.83
6.09

40
SHC
3.72
3.68
3.90
4.14
4.03
3.94

PI
2.13
2.13
2.14
2.15
2.16
2.17

NOTES:
1. Capacities are based on the following conditions.
(1) Corresponding refrigerant piping length : 7.5m
(2) Level difference
: 0m
2.
shows nominal (rated) capacities and power input.

(m/min.)
(C)
(C)
(kW)
(kW)
(kW)

3D055286B

FBQ50BV1A + RXS50FAVMA

COOLING
INDOOR
EWB EDB
C
C
20
14.0
22
16.0
25
18.0
27
19.0
30
22.0
32
24.0

HEATING
INDOOR
EDB
C
15.0
20.0
22.0
24.0
25.0
27.0

50Hz 220 - 240V / 60Hz 220 - 230V

TC
5.12
5.35
5.58
5.70
6.04
6.27

20
SHC
3.65
3.59
3.73
3.91
3.77
3.66

PI
1.52
1.53
1.54
1.54
1.55
1.56

TC
4.89
5.12
5.35
5.47
5.81
6.04

25
SHC
3.53
3.47
3.63
3.81
3.67
3.58

PI
1.67
1.67
1.68
1.69
1.70
1.71

TC
4.04
3.83
3.75
3.67
3.62
3.54

PI
1.63
1.68
1.69
1.71
1.72
1.74

AFR

OUTDOOR TEMPERATURE (CWB)


-5
0
6
TC
PI
TC
PI
TC
PI
4.72 1.71 5.39 1.79 6.21 1.89
4.51 1.76 5.19 1.83 6.00 1.93
4.43 1.77 5.10 1.85 5.92 1.95
4.34 1.79 5.02 1.87 5.83 1.96
4.30 1.80 4.98 1.88 5.79 1.97
4.22 1.82 4.90 1.90 5.71 1.99

Symbols
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total capacity
SHC : Sensible heat capacity
PI
: Power input

(m/min.)
(C)
(C)
(kW)
(kW)
(kW)

13
0.15

OUTDOOR TEMPERATURE (CDB)


30
32
TC
SHC
PI
TC
SHC
PI
4.66 3.41 1.81 4.56 3.36 1.87
4.89 3.36 1.82 4.79 3.32 1.88
5.12 3.52 1.83 5.02 3.48 1.89
5.23 3.71 1.83 5.14 3.67 1.89
5.58 3.59 1.85 5.49 3.55 1.91
5.81 3.49 1.86 5.72 3.46 1.91

50Hz 220 - 240V / 60Hz 220 - 230V


-10

AFR
BF

TC
4.42
4.65
4.88
5.00
5.35
5.58

35
SHC
3.29
3.25
3.42
3.61
3.50
3.41

PI
1.96
1.97
1.98
1.98
1.99
2.00

TC
4.19
4.42
4.65
4.77
5.11
5.34

40
SHC
3.18
3.14
3.32
3.51
3.41
3.33

PI
2.10
2.11
2.12
2.13
2.14
2.15

14

10
TC
6.75
6.54
6.46
6.38
6.33
6.25

PI
1.95
1.99
2.01
2.03
2.04
2.05
NOTES:
1. Capacities are based on the following conditions.
(1) Corresponding refrigerant piping length : 7.5m
(2) Level difference
: 0m
2.
shows nominal (rated) capacities and power input.

C : 3D055273A

SkyAir RXS, RKS, RZR Series

89

Capacity Tables

EDSG281001

FBQ60BV1A + RXS60FVMA

COOLING
INDOOR
EWB EDB
C
C
20
14.0
22
16.0
25
18.0
27
19.0
30
22.0
32
24.0

HEATING
INDOOR
EDB
C
15.0
20.0
22.0
24.0
25.0
27.0

50Hz 220 - 240V / 60Hz 220 - 230V

TC
5.84
6.10
6.36
6.50
6.89
7.15

20
SHC
4.42
4.34
4.56
4.82
4.65
4.53

PI
1.71
1.72
1.73
1.74
1.75
1.76

TC
5.57
5.84
6.10
6.23
6.62
6.89

25
SHC
4.28
4.22
4.44
4.71
4.55
4.44

PI
1.88
1.89
1.90
1.90
1.92
1.92

TC
4.71
4.47
4.37
4.28
4.23
4.13

PI
1.91
1.96
1.98
2.00
2.01
2.03

AFR

OUTDOOR TEMPERATURE (CWB)


-5
0
6
TC
PI
TC
PI
TC
PI
5.50 2.00 6.29 2.10 7.24 2.21
5.26 2.06 6.05 2.15 7.00 2.26
5.16 2.08 5.95 2.17 6.90 2.28
5.07 2.10 5.86 2.19 6.81 2.30
5.02 2.11 5.81 2.20 6.76 2.31
4.92 2.13 5.71 2.22 6.66 2.33

Symbols
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total capacity
SHC : Sensible heat capacity
PI
: Power input

18
0.15

OUTDOOR TEMPERATURE (CDB)


30
32
TC
SHC
PI
TC
SHC
PI
5.31 4.16 2.04 5.20 4.10 2.11
5.57 4.09 2.05 5.47 4.05 2.12
5.83 4.33 2.06 5.73 4.29 2.13
5.97 4.60 2.07 5.86 4.56 2.13
6.36 4.46 2.08 6.25 4.42 2.15
6.62 4.36 2.09 6.52 4.32 2.16

50Hz 220 - 240V / 60Hz 220 - 230V


-10

AFR
BF

TC
5.04
5.31
5.57
5.70
6.09
6.36

35
SHC
4.03
3.97
4.22
4.49
4.36
4.27

PI
2.21
2.22
2.23
2.23
2.24
2.25

TC
4.78
5.04
5.30
5.43
5.83
6.09

40
SHC
3.90
3.86
4.11
4.39
4.27
4.18

PI
2.37
2.38
2.39
2.39
2.41
2.42

19

10
TC
7.87
7.63
7.54
7.44
7.39
7.09

PI
2.28
2.33
2.35
2.38
2.39
2.41
NOTES:
1. Capacities are based on the following conditions.
(1) Corresponding refrigerant piping length : 7.5m
(2) Level difference
: 0m
2.
shows nominal (rated) capacities and power input.

(m/min.)
(C)
(C)
(kW)
(kW)
(kW)

3D055274A

FBQ71BV1A + RXS71FVMA

COOLING
INDOOR
EWB EDB
C
C
20
14.0
22
16.0
25
18.0
27
19.0
30
22.0
32
24.0

HEATING
INDOOR
EDB
C
15.0
20.0
22.0
24.0
25.0
27.0

50Hz 220 - 240V / 60Hz 220 - 230V

TC
6.86
7.17
7.48
7.64
8.10
8.41

20
SHC
5.00
4.91
5.13
5.40
5.20
5.06

PI
1.97
1.98
1.99
2.00
2.02
2.03

TC
6.55
6.86
7.17
7.32
7.79
8.10

25
SHC
4.84
4.77
4.99
5.27
5.08
4.95

PI
2.16
2.17
2.18
2.19
2.21
2.22

TC
5.52
5.24
5.12
5.01
4.95
4.84

PI
2.26
2.32
2.34
2.37
2.38
2.40

AFR

OUTDOOR TEMPERATURE (CWB)


-5
0
6
TC
PI
TC
PI
TC
PI
6.45 2.37 7.37 2.48 8.48 2.61
6.16 2.43 7.09 2.54 8.20 2.67
6.05 2.45 6.98 2.56 8.09 2.69
5.94 2.48 6.86 2.59 7.82 2.71
5.88 2.49 6.81 2.60 7.57 2.71
5.77 2.51 6.69 2.62 7.09 2.71

Symbols
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total capacity
SHC : Sensible heat capacity
PI
: Power input

(m/min.)
(C)
(C)
(kW)
(kW)
(kW)

18
0.11

OUTDOOR TEMPERATURE (CDB)


30
32
TC
SHC
PI
TC
SHC
PI
6.24 4.69 2.35 6.12 4.62 2.43
6.55 4.62 2.36 6.42 4.56 2.44
6.86 4.86 2.37 6.73 4.80 2.45
7.01 5.13 2.38 6.89 5.08 2.46
7.47 4.97 2.40 7.35 4.92 2.47
7.78 4.85 2.41 7.66 4.80 2.48

50Hz 220 - 240V / 60Hz 220 - 230V


-10

AFR
BF

TC
5.93
6.24
6.55
6.70
7.16
7.47

35
SHC
4.53
4.47
4.72
5.00
4.85
4.74

PI
2.54
2.55
2.56
2.57
2.59
2.60

TC
5.62
5.93
6.23
6.39
6.85
7.16

40
SHC
4.38
4.33
4.59
4.87
4.74
4.64

PI
2.73
2.74
2.75
2.76
2.78
2.79

19

10
TC
9.22
8.80
8.31
7.82
7.57
7.09

PI
2.70
2.75
2.75
2.76
2.76
2.76
NOTES:
1. Capacities are based on the following conditions.
(1) Corresponding refrigerant piping length : 7.5m
(2) Level difference
: 0m
2.
shows nominal (rated) capacities and power input.

3D055275A

90

SkyAir RXS, RKS, RZR Series

EDSG281001

Capacity Tables

1
3D066512A

FCQ71KVEA / FHQ71BVV1B / FBQ71DV1 + RZR71KUV1

SkyAir RXS, RKS, RZR Series

91

Capacity Tables

EDSG281001

3D066761

FCQ100KVEA / FHQ100BVV1B / FBQ100DV1 + RZR100KUV1


FCQ100KVEA / FHQ100BVV1B / FBQ100DV1 + RZR100HUY1

92

SkyAir RXS, RKS, RZR Series

EDSG281001

Capacity Tables

1
3D066513A

FCQ125KVEA / FHQ125BVV1B / FBQ125DV1 + RZR125KUV1


FCQ125KVEA / FHQ125BVV1B / FBQ125DV1 + RZR125HUY1

SkyAir RXS, RKS, RZR Series

93

Capacity Tables

EDSG281001

3D066762

FCQ140KVEA / FBQ140DV1 + RZR140KUV1


FCQ140KVEA / FBQ140DV1 + RZR140HUY1

94

SkyAir RXS, RKS, RZR Series

EDSG281001

9.2

Capacity Tables

Capacity Correction Factor by the Length of Refrigerant Piping

RKS25AVMG / RKS35AVMG / RKS50AVMG / RKS60AVMG


RXS50FAVMA / RXS60FVMA / RXS71FVMA
The capacity of the unit has to be corrected in accordance with the length of refrigerant piping.
(The distance between the indoor unit and the outdoor unit)
RXS60, 71:Heating(96.1%)
RXS50:Heating(93.6%)

(%)

Capacity correction factor

100
95
90
RKS25,35:Cooling(94.6%)

85
RXS,RKS60, 71:Cooling(85.9%)

80
RXS,RKS50:Cooling(90.4%)

75
70
05

10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 (m)
Length of refrigerant piping (Total length)

Notes:

1. line: Correction factor for Cooling Capacity,


line: Correction factor for Heating Capacity
2. The correction factor remains the same whether the outdoor unit is to be installed above or below
the indoor unit.
3. You cannot extend the refrigerant piping exceeding the limit shown in the above table.

SkyAir RXS, RKS, RZR Series

95

Capacity Tables

EDSG281001

RZR71KUV1 / RZR100KUV1 / RZR125KUV1 / RZR140KUV1


RZR100HUY1 / RZR125HUY1 / RZR140HUY1

3D067382

96

SkyAir RXS, RKS, RZR Series

EDSG281001

Operation Limits

10. Operation Limits

RXS50FAVMA / RXS60FVMA / RXS71FVMA

3D054069G

RKS25AVMG / RKS35AVMG / RKS50AVMG / RKS60AVMG

4D050467J
4D054070J

SkyAir RXS, RKS, RZR Series

97

Operation Limits

EDSG281001

RZR71KUV1 / RZR100KUV1 / RZR125KUV1 / RZR140KUV1


RZR100HUY1 / RZR125HUY1 / RZR140HUY1

4D066510

98

SkyAir RXS, RKS, RZR Series

EDSG281001

Fan Performance

11. Fan Performance

11.1 FBQ-B
FBQ50BV1A

3D053085

FBQ60BV1A / FBQ71BV1A

50Hz
(mmH2O)(Pa)
150
15

(mmH2O)
15
HIGH (HIGH ESP)

10

100

L P)
NA ES
ER GH
T
I
EX (H
F E
O R
IT SU
M S
LI E
R PR
PE IC
P
T
U TA
S

10

LOW
HIGH (LOW ESP)
5

50

NAL
TER ESP)
F EX
IT O E (HIGH
IM
L
R
ER
SU
LOW IC PRES
T
STA

NOTE) 1. THE REMOTE CONTROLLER CAN BE USED TO SWITCH


BETWEEN "HIGH" AND "LOW" .
2. THE AIR FLOW IS SET TO "STANDARD" BEFORE LEAVING THE FACTORY.
IT IS POSSIBLE TO SWITCH BETWEEN "STANDARD ESP" AND "HIGH ESP"
BY FIELD SETUP OF REMOTE CONTROLLER.

HIGH (STANDARD ESP)


0

0
14

(mmH2O) (Pa)

16
AIR FLOW (m3/min)

18

20

21

(mmH2O)

3D053086A

SkyAir RXS, RKS, RZR Series

99

Fan Performance

EDSG281001

11.2 FBQ-D
FBQ71DV1

3D060745A

FBQ100DV1

3D060746A

100

SkyAir RXS, RKS, RZR Series

EDSG281001

Fan Performance

FBQ125DV1 / FBQ140DV1

3D060747A

SkyAir RXS, RKS, RZR Series

101

Air Velocity and Temperature Distributions

EDSG281001

12. Air Velocity and Temperature Distributions


12.1 FFQ
FFQ25BV1B (Cooling)

FFQ35BV1B (Cooling)

102

SkyAir RXS, RKS, RZR Series

EDSG281001

Air Velocity and Temperature Distributions

FFQ50BV1B (Cooling)

FFQ60BV1B (Cooling)

SkyAir RXS, RKS, RZR Series

103

Air Velocity and Temperature Distributions

EDSG281001

12.2 FHQ
FHQ35BVV1B / FHQ50BVV1B (Cooling)

FHQ60BVV1B / FHQ71BVV1B (Cooling)

104

SkyAir RXS, RKS, RZR Series

EDSG281001

Air Velocity and Temperature Distributions

FHQ100BVV1B (Cooling)

FHQ125BVV1B (Cooling)

SkyAir RXS, RKS, RZR Series

105

Sound Level

EDSG281001

13. Sound Level


13.1 Overall Sound Level
13.1.1 Indoor Unit
dB(A)
Model

220-240V, 50Hz
H

FCQ71KVEA

35

28

FCQ100KVEA

43

32

FCQ125KVEA

44

34

FCQ140KVEA

44

36

Measuring location

4D058461

Model

230V, 50Hz
H

FFQ25BV1B

29.5

24.5

FFQ35BV1B

32

25

FFQ50BV1B

36

27

FFQ60BV1B

41

32

FHQ35BVV1B

37

32

FHQ50BVV1B

38

33

FHQ60BVV1B

39

33

FHQ71BVV1B

39

35

Measuring location

4D040176A

4D028281B

FHQ100BVV1B

42

37

FHQ125BVV1B

44

39

FBQ50BV1A

33

29

FBQ60BV1A

34

30

FBQ71BV1A

34

30

Model

220-240V, 50Hz
H

FBQ71DV1

37

32

FBQ100DV1

38

33

FBQ125DV1

40

36

4D053092A

Measuring location

4D067285

FBQ140DV1

Note:

106

40

36

Operation sound is measured in an anechoic chamber.


Sound level will vary depending on a range of factors such as the construction (acoustic absorption
coefficient) of the particular room in which the equipments installed.

SkyAir RXS, RKS, RZR Series

EDSG281001

Sound Level

13.1.2 Outdoor Unit

dB(A)
Model

RXS50FAVMA

220-240V, 50Hz/
220-230V, 60Hz
Cooling

Heating

47

48

Measuring location

1m

RXS60FVMA

49

49

RXS71FVMA

52

52

Model

220-240V, 50Hz/
220-230V, 60Hz

3D054590D

Measuring location

Cooling
RKS25AVMG

46

RKS35AVMG

47

RKS50AVMG

47

1m

4D047727H

RKS60AVMG
Model

RZR71KUV1

49
220-240V, 50Hz
Cooling

Measuring location

48

4D066602

RZR100KUV1

49

RZR125KUV1

50

RZR140KUV1

50

Model

Note:

380-415V, 50Hz
Cooling

RZR100HUY1

49

RZR125HUY1

50

RZR140HUY1

50

4D066603

Measuring Location

4D066604

Operation sound is measured in an anechoic chamber.


Sound level will vary depending on a range of factors such as the construction (acoustic absorption
coefficient) of the particular room in which the equipments installed.

SkyAir RXS, RKS, RZR Series

107

Sound Level

EDSG281001

13.2 Octave Band Level


13.2.1 Indoor Unit
FCQ71KVEA

FCQ100KVEA

70

NC-50

HI

50
NC-40
40
NC-30

LOW

30
NC-20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63

125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

NC-60
60

NC-50

50

HI

NC-40
40
NC-30
LOW

30
NC-20
20

APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63

125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

NC-60
60

NC-50

FFQ25BV1B

HI

50
NC-40
40
NC-30

LOW

30
NC-20
20

APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63

125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

4D058463

4D058462

4D058461

FCQ140KVEA

OCTAVE BAND SOUND PRESSURE LEVEL


dB (0dB=0.0002 bar)

NC-60
60

20

FCQ125KVEA

70

OCTAVE BAND SOUND PRESSURE LEVEL


dB (0dB=0.0002 bar)

OCTAVE BAND SOUND PRESSURE LEVEL


dB (0dB=0.0002 bar)

70

FFQ35BV1B

OCTAVE BAND SOUND PRESSURE LEVEL


dB (0dB=0.0002 bar)

70
NC-60
60

NC-50

HI

50
NC-40
40
NC-30

LOW

30
NC-20
20

APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63

125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

4D058464

FFQ50BV1B

4D040176A

FFQ60BV1B

4D040178A

FHQ50BVV1B

108

FHQ35BVV1B

4D040179A

FHQ60BVV1B

4D028281B

4D040177A

4D028280B

FHQ71BVV1B

4D037997A

4D028355B

SkyAir RXS, RKS, RZR Series

EDSG281001

Sound Level

FHQ125BVV1B

FHQ100BVV1B

NC-50
50
NC-40
HI

40

LOW

NC-30
30
NC-20
APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63

125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

OCTAVE BAND SOUND PRESSURE LEVEL


dB (0dB=0.0002 bar)

OCTAVE BAND SOUND PRESSURE LEVEL


dB (0dB=0.0002 bar)

NC-60
60

20

FBQ50BV1A

70

70

NC-60
60

NC-50
50
HI

NC-40
40

LOW
NC-30
30
NC-20
20

APPROXIMATE
THRESHOLD HEARING
FOR CONTINUOUS
NOISE
63

125
250
500 1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

4D028284B

4D028283B

FBQ71DV1

FBQ60BV1A / FBQ71BV1A

4D053091

FBQ100DV1

4D067285

4D053092A

4D067286

FBQ125DV1 / FBQ140DV1

4D067287

13.2.2 Outdoor Unit


RXS50FAVMA (Cooling)

RXS50FAVMA (Heating)

3D027645R

SkyAir RXS, RKS, RZR Series

RXS60FVMA (Cooling)

3D027645R

3D035059J

109

Sound Level

EDSG281001

RXS71FVMA (Cooling)

RXS60FVMA (Heating)

3D035059J

3D054590D

RKS35AVMG

RKS25AVMG

RZR125KUV1

4D027648G

RZR100KUV1

4D066603

4D066602

4D040949H

RZR140KUV1

RZR100HUY1

70

60

50

40

30

20

63

250
500
1000 2000 4000
125
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

4D066789

70

OCTAVE BAND SOUND PRESSURE LEVEL


dB(0dB=0.0002 bar)

OCTAVE BAND SOUND PRESSURE LEVEL


dB(0dB=0.0002 bar)

70

OCTAVE BAND SOUND PRESSURE LEVEL


dB(0dB=0.0002 bar)

RKS50AVMG

RZR71KUV1

RKS60AVMG

3D054590D

4D047728H

4D047727H

110

RXS71FVMA (Heating)

60

50

40

30

20

63

250
500
1000 2000 4000
125
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

4D066790

60

50

40

30

20

63

125
250
500
1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

4D066604

SkyAir RXS, RKS, RZR Series

EDSG281001

Sound Level

RZR125HUY1

RZR140HUY1

OCTAVE BAND SOUND PRESSURE LEVEL


dB(0dB=0.0002 bar)

70

60

50

40

30

20

63

125
250
500
1000 2000 4000
OCTAVE BAND CENTER FREQUENCY (Hz)

8000

4D066791

SkyAir RXS, RKS, RZR Series

4D066792

111

Sound Level

112

EDSG281001

SkyAir RXS, RKS, RZR Series

EDSG281001

Part 2
Installation of
Indoor / Outdoor Unit
1. Centre of Gravity .................................................................................114
2. Installation of Indoor Unit ....................................................................117
2.1 FCQ71KVEA / FCQ100KVEA / FCQ125KVEA / FCQ140KVEA..........117
2.2 FFQ25BV1B / FFQ35BV1B / FFQ50BV1B / FFQ60BV1B...................142
2.3 FHQ35BVV1B / FHQ50BVV1B / FHQ60BVV1B / FHQ71BVV1B /
FHQ100BVV1B / FHQ125BVV1B ........................................................165
2.4 FBQ50BV1A / FBQ60BV1A / FBQ71BV1A..........................................190
2.5 FBQ71DV1 / FBQ100DV1 / FBQ125DV1 / FBQ140DV1.....................211

3. Installation of Outdoor Unit..................................................................238


3.1
3.2
3.3
3.4

Installation of Indoor / Outdoor Unit

RKS25AVMG / RKS35AVMG ..............................................................238


RXS50FAVMA / RXS60FVMA / RKS50AVMG / RKS60AVMG ..........246
RXS71FVMA ........................................................................................254
RZR71KUV1 / RZR100KUV1 / RZR125KUV1 / RZR140KUV1
RZR100HUY1 / RZR125HUY1 / RZR140HUY1 ..................................262

113

Centre of Gravity

EDSG281001

1. Centre of Gravity
RKS25AVMG / RKS35AVMG
Unit (mm)

4D056351N

RXS50FAVMA / RXS60FVMA
RKS50AVMG / RKS60AVMG
Unit (mm)

4D051638P

114

Installation of Indoor / Outdoor Unit

EDSG281001

Centre of Gravity

RXS71FVMA
Unit (mm)

4D053630D

RZR71KUV1
Unit (mm)

4D064948

Installation of Indoor / Outdoor Unit

115

Centre of Gravity

EDSG281001

RZR100KUV1 / RZR125KUV1 / RZR140KUV1


Unit (mm)

4D058487B

RZR100HUY1 / RZR125HUY1 / RZR140HUY1


Unit (mm)

4D061670A

116

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

2. Installation of Indoor Unit


2.1

FCQ71KVEA / FCQ100KVEA / FCQ125KVEA / FCQ140KVEA

2.1.1

Names and Functions of Parts

2
j

m
c

g
f
h
b

a
b
c
d
e
f
g
h
i
j
k
l

Indoor unit
Outdoor unit
Remote controller
Depending on the system configuration, the remote
controller is not provided.
Inlet air
Discharge air
Air outlet
Air flow flap (at air outlet)
Refrigerant piping, connection electric wire
Drain pipe
Model name (model name plate)
(Inside of suction grille)
Drain pumping out device(built-in)
Condensate removed from the room during cooling.
Air filter (suction grille)
3P177429-3F

Installation of Indoor / Outdoor Unit

117

Installation of Indoor Unit

2.1.2

EDSG281001

Installation
FCQ71KVEA
FCQ100KVEA
FCQ125KVEA
FCQ140KVEA

SPLIT SYSTEM
Air Conditioners

Installation manual

CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

SAFETY CONSIDERATIONS ........................................................................................1


BEFORE INSTALLATION ..............................................................................................3
SELECTING INSTALLATION SITE................................................................................5
PREPARATIONS BEFORE INSTALLATION .................................................................7
INDOOR UNIT INSTALLATION .....................................................................................8
REFRIGERANT PIPING WORK ..................................................................................10
DRAIN PIPING WORK .................................................................................................12
ELECTRIC WIRING WORK .........................................................................................15
WIRING EXAMPLE ......................................................................................................17
INSTALLATION OF THE DECORATION PANEL .......................................................... 19
FIELD SETTING...........................................................................................................19
TEST OPERATION ......................................................................................................21

1. SAFETY CONSIDERATIONS
Please read these SAFETY CONSIDERATIONS carefully before installing air conditioning equipment and
be sure to install it correctly. After completing installation, conduct a trial operation to check for faults and
explain to the customer how to operate the air conditioner and take care of it with the aid of the operation manual. Ask the customer to store the installation manual along with the operation manual for future reference.
This air conditioner is classified under appliances not accessible to the general public.
Meaning of WARNING and CAUTION notices.
WARNING .........Failure to follow these instructions properly may result in personal injury or loss of life.
CAUTION ..........Failure to observe these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances.

WARNING
Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage,
electric shocks or fire.
Install the air conditioner in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shocks or fire.
Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.
Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
A foundation of insufficient strength may result in the equipment falling and causing injury.
Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit falling and causing accidents.

1
C : 3P177351-2D

118

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried
out by qualified personnel according to local laws and regulations and this installation manual.
An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.
Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal
connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or fire.
When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the
wires so that the terminal box lid can be securely fastened.
Improper positioning of the terminal box lid may result in electric shocks, fire or overheating terminals.
If refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into contact with fire.
After completing installation, check for refrigerant gas leakage.
Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source
of fire, such as a fan heater, stove or cooker.
Be sure to switch off the unit before touching any electrical parts.
Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead.
Imperfect earthing may result in electric shocks.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks or fire.

CAUTION
While following the instructions in this installation manual, install drain piping to ensure proper drainage and
insulate piping to prevent condensation.
Improper drain piping may result in indoor water leakage and property damage.
Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televisions
or radios to prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 1 meter may not be sufficient to eliminate noise.)
Remote controller (wireless kit) transmitting distance can be shorter than expected in rooms with electronic
fluorescent lamps (inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as possible.
Do not install the air conditioner in the following locations:
1. Where there is a high concentration of mineral oil spray or vapour (e.g. a kitchen).
Plastic parts will deteriorate, parts may fall off and water leakage could result.
2. Where corrosive gas, such as sulphurous acid gas, is produced.
Corroding of copper pipes or soldered parts may result in refrigerant leakage.
3. Near machinery emitting electromagnetic radiation.
Electromagnetic radiation may disturb the operation of the control system and result in a malfunction of
the unit.
4. Where flammable gas may leak, where there is carbon fibre or ignitable dust suspensions in the air, or
where volatile flammables such as paint thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.

2
3P177351-2D

Installation of Indoor / Outdoor Unit

119

Installation of Indoor Unit

EDSG281001

2. BEFORE INSTALLATION
Do not exert pressure on the resin parts when opening the unit or when moving it after opening
Be sure to check the type of R410A refrigerant to be used before doing any work. (Using an incorrect
refrigerant will prevent normal operation of the unit.)
When opening the unit or moving it after opening, be sure to lift it by holding on to the lifting lugs without
exerting any pressure on other parts, especially, drain piping, and other resin parts.
Decide upon a line of transport.
Leave the unit inside its packaging while moving, until reaching the installation site. Use a sling of soft material, where unpacking is unavoidable or protective plates together with a rope when lifting, to avoid damage
or scratches to the unit.
Refer to the installation manual of the outdoor unit for items not described in this manual.
Do not dispose of any parts necessary for installation until the installation is complete.

1. PRECAUTIONS

Be sure to read this manual before installing the indoor unit.


When selecting installation site, refer to the paper pattern.
This unit is suitable for installation in a household, commercial and light industrial environment.
Do not install or operate the unit in rooms mentioned below.
Laden with mineral oil, or filled with oil vapor or spray like in kitchens. (Plastic parts may deteriorate.)
Where corrosive gas like sulfurous gas exists. (Copper tubing and brazed spots may corrode.)
Where volatile flammable gas like thinner or gasoline is used.
Where machines can generate electromagnetic waves. (Control system may malfunction.)
Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates
greatly such as that in factories. Also in vehicles or vessels.

2. ACCESSORIES
Check the following accessories are included with your unit.
Name

(1) Drain hose

(2) Metal clamp

Quantity

1 pc.

1 pc.

(3) Washer for


hanger
bracket
8 pcs.

(4) Clamp

(5) Paper pattern for


installation

(6) Screw (M4)

6 pcs.

1 pc.

4 pcs.

Also used as pack- For paper pattern


for installation
ing material
Shape

Name
Quantity

(7) Washer
fixing plate
4 pcs.

Insulation for
fitting
1 each

Sealing pad
1 each

1 pc.

Installation guide
1 pc.

1 pc.
(Other)

(10) Large
(8) for gas
pipe

(13) Small

(11) Medium-1
Shape

(14)

(15)

Installation
manual
Operation
manual

(9) for liquid


pipe
(12) Medium-2

3
3P177351-2D

120

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

3. OPTIONAL ACCESSORIES
The optional decoration panel and remote controller are required for this indoor unit. (Refer to Table 1, 2)
(However, the remote controller is not required for the slave unit of a simultaneous operation system.)
Table 1
Unit model

Optional decoration panel


BYCP125K-W1
Color : Fresh White

FCQ71100125140KVEA

These are two types of remote controllers: wired and wireless. Select a remote controller from Table 2
according to customer request and install in an appropriate place.
Table 2
Remote controller
Wired type
Wireless type

BRC1C61 / BRC1D61
BRC7F632F

NOTE
If you wish to use a remote controller that is not listed in Table 2 on page 4, select a suitable remote controller after consulting catalogs and technical materials.

FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND
CHECK AFTER INSTALLATION IS FINISHED.
1. Items to be checked after completion of work
Items to be checked
Are the indoor unit and outdoor unit fixed
firmly?
Is the outdoor unit fully installed?
Is the gas leak test finished?
Is the unit fully insulated?
Does drainage flow smoothly?
Does the power supply voltage correspond
to that shown on the name plate?
Are wiring and piping correct?
Is the unit safely grounded?
Is wiring size according to specifications?
Is something blocking the air outlet or inlet
of either the indoor or outdoor units?
Are refrigerant piping length and additional
refrigerant charge noted down?

If not properly done, what is likely to occur

Check

The unit may drop, vibrate or make noise.


The unit may malfunction or the components burn out.
It may result in insufficient cooling.
Condensate water may drip.
Condensate water may drip.
The unit may malfunction or the components burn out.
The unit may malfunction or the components burn out.
It may result in electric shock.
The unit may malfunction or the components burn out.
It may result in insufficient cooling.
The refrigerant charge in the system is not
clear.

2. Items to be checked at time of delivery


* Also review the 1. SAFETY CONSIDERATIONS
Items to be checked

Check

Are the terminal box lid, air filter, suction grille attached?
Did you explain about operations while showing the instruction manual to your customer?
Did you hand the instruction manual over to your customer?

4
C : 3P177351-2D

Installation of Indoor / Outdoor Unit

121

Installation of Indoor Unit

EDSG281001

Points for explanation about operations


The items with
WARNING and
CAUTION marks in the instruction manual are the items pertaining to possibilities for bodily injury and material damage in addition to the general usage of
the product. Accordingly, it is necessary that you make a full explanation about the described contents and also ask your customers to read the instruction manual.

4. NOTE TO THE INSTALLER


Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating different
functions, and adjusting the temperature) by having them carry out operations themselves while looking at the
manual.

3. SELECTING INSTALLATION SITE


Hold the unit by the 4 lifting lugs when opening the box and moving it, and do not exert pressure on to any
other part piping (refrigerant, drain, etc.) or plastic parts.
If the temperature or humidity inside the ceiling might rise above 30C or RH 80%, respectively, use the highhumidity kit (sold separately) or add extra insulation to the main unit body.
Use glass wool or polyethylene foam as insulation and make sure it is at least 10mm thick and fits inside the
ceiling opening.
The direction this product blows can be selected. However, a separately sold shut-off material kit is
needed in order to make the unit blow in two, three, or four (corner shut-off) directions.
(1) Select an installation location with the customers approval which matches the following conditions.
A location from which cool (warm) air will reach the whole room.
A location with no objects blocking the air passage.
A location where drainage can be done with no problem.
A location strong enough to support the weight of the indoor unit.
Locations where the wall is not significantly tilted.
A location which leaves enough room for installation and service work.
A location where there is no risk of flammable gas leaking.
A location where the length of the indoor-outdoor piping is no longer than the tolerated length (see the
installation manual that came with the outdoor unit for details).
[Space required for installation]

*1500

*1500

Air
discharge
At least 1800mm
from the floor.

Air Air
inlet discharge

1500

1500
*1500

Floor surface
Fig. 1
Model
FCQ71KVEA
FCQ100125140KVEA

*1500
Fig. 2

H
256
298

5
C : 3P177351-2D

122

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

CAUTION
The indoor and outdoor units and the power supply wiring and remote controller cord must be installed
at least 1m away from any televisions or radios. This is to prevent interference with picture and sound
reception. (Interference may occur even at 1m away depending on the reception quality.)
If installing the wireless kit, the distance of the signal sent from the remote controller might be shorter if
there are fluorescent lights which are electrically started (such as with inverters, rapid starters, etc.) in
the room. The indoor unit should be installed as far away from fluorescent lights as possible.

(2) Ceiling height


This product can be installed in ceilings up to 3.5m high (4.2m high for the 100, 125, and 140).
If the ceiling height is 2.7m (3.2m for the 100,125, and 140) or more, field settings will have to be made with
the remote controller. See 11. FIELD SETTING for details.
(3) Air direction
The air direction shown in Fig. 3 is an example.
Select the appropriate number of directions according to the shape of the room and the location of the unit.
(Field settings have to be made using the remote controller and the outlet vents have to be shut off if two,
three, or four (corner shut-off) directions are selected. See the shut-off materials (sold separately) installation manual for details.)
(4) Use eyebolts for installation. Check if the location for the installation is strong enough to support the weight
of the unit, reinforce it if necessary, and install using eyebolts. (The spacing of the installation is shown on
the paper pattern for installation (5).)

All-round air

Pipes

Pipes

Pipes

Pipes

[Air direction]

Four air direction Three air direction Two air direction


Fig. 3

6
3P177351-2D

Installation of Indoor / Outdoor Unit

123

Installation of Indoor Unit

EDSG281001

4. PREPARATIONS BEFORE INSTALLATION


Refrigerant
piping
Hanger
bracket

Suspension
bolt (4)

False
ceiling

710(Suspension bolt pitch)


840 (Indoor unit)
860 910 (Ceiling opening)
950 (Decoration panel)

View as seen from A


Fig. 5

125 130

860 910 (Ceiling opening)


840 (Indoor unit)
780 (Suspension bolt pitch)

950 (Decoration panel)

(1) Relation of ceiling opening to unit and suspension bolt position.

A
Fig. 4

910
(Dimension inside frame)

840

Installation is possible when ceiling opening dimensions is as follows


When installing the unit within the frame for fixing false ceiling.

860
(Opening dimension inside
the flame for ceiling)

Frame
False
ceiling

20

840
910
(Dimension inside frame)

20
860 *910
(Ceiling opening dimension) (Ceiling-panel
overlapping dimension)
Fig. 7

Fig. 6

NOTE
Installation is possible with a ceiling dimension of 910mm (marked with *). However, to achieve a ceilingpanel overlapping dimension of 20mm, the spacing between the ceiling and the unit should be 35mm or
less. If the spacing between ceiling and the unit is over 35mm, attach ceiling material to
part or recover
the ceiling.

Ceiling material
35

35
Fig. 8

7
3P177351-2D

124

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

(2) Make the ceiling opening needed for installation where applicable. (For existing ceilings)
Refer to the paper pattern for installation (5) for ceiling opening dimensions.
Create the ceiling opening required for installation. From the side of the opening to the casing outlet,
implement the refrigerant and drain piping and wiring for remote controller (unnecessary for wireless
type) and indoor-outdoor unit casing outlet. Refer to 6. REFRIGERANT PIPING WORK, 7. DRAIN
PIPING WORK and 8. ELECTRIC WIRING WORK.
After making an opening in the ceiling, it may be necessary to reinforce ceiling beams to keep the ceiling
level and to prevent it from vibrating. Consult the builder for details.

<installation example>
Ceiling slab
Anchor
Long nut or turn-buckle
Suspension bolt

50 100

(3) Install the suspension bolts.


(Use either a M8~M10 size bolt)
Use a hole-in anchor for existing ceilings, and
a sunken insert, sunken anchor or other field
supplied parts for new ceilings to reinforce
the ceiling to bear the weight of the unit.
Adjust clearance (50 100mm) from the
ceiling before proceeding further.

False ceiling
Fig. 9

NOTE
All the above parts are field supplied.

5. INDOOR UNIT INSTALLATION


Installing optional accessories (except for the decoration panel) before installing the indoor unit is
easier. However, for existing ceilings, install fresh air inlet component kit and branch duct before
installing the unit.
As for the parts to be used for installation work, be sure to use the provided accessories and specified parts
designated by our company.
(1) For new ceilings
(1-1)Install the indoor unit temporarily.
Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using a nut and
washer (3) from the upper and lower sides of the hanger bracket.
The washer fixing plate (7) will prevent the washer from falling.

Field supply
Washer (3) (accessory)
Insert
Hanger bracket
Tighten
(double nuts)
[Securing the hanger bracket]
Fig. 10

Washer fixing plate (7)


(accessory)
[Securing the washer]
Fig. 11

(1-2)Refer to the paper pattern for installation (5) for ceiling opening dimension.
Consult the builder or carpenter for details.
The center of the ceiling opening is indicated on the paper pattern for installation.
The center of the unit is indicated on the triangular mark to the unit bottom and on the paper pattern for
installation.
Fix the paper pattern to the unit with screws (6) (4).
Ceiling height is shown on the side of the paper pattern for installation (5). Adjust the height of the unit
according to this indication.

8
3P177351-2D

Installation of Indoor / Outdoor Unit

125

Installation of Indoor Unit

EDSG281001

Please perform one of the following, as the shape of the paper pattern for installation differs according to the model.

Center of
ceiling opening

Center of main unit


Center mark of
main unit

Paper pattern for


installation (5)

Screw (6)
(accessory)

Screw (6)
(accessory)
Fig. 12

[Installation of paper pattern for installation]


<Ceiling work>
(1-3)Adjust the unit to the right position for installation.
(Refer to 4. PREPARATIONS BEFORE INSTALLATION-(1).)
Using the Installation guide (15) allows you to check the positions from the underside of the unit to the
lower ceiling surface.

Apply the short


side of the
cut-out section.

Lower ceiling
surface

Underside of
the unit

Installation guide (15)


(accessory)
(1-4)Check the unit is horizontally level.
The indoor unit is equipped with a built-in drain pump and float
switch. Verify that it is level by using a level or a water-filled
vinyl tube.
CAUTION
If the unit is tilted against condensate flow, the float switch may
malfunction and cause water to drip.
(1-5)Remove the washer fixing plate (7) used for preventing the
washer from falling and tighten the upper nut.
(1-6)Remove the paper pattern for installation (5).

Level

Vinyl tube

[Maintaining horizontality]

Fig. 13
(2) For existing ceilings
(2-1)Install the indoor unit temporarily.
Perform step (1-1) in (1) For new ceilings.
(2-2)Adjust the height and position of the unit.
(Refer to 4. PREPARATIONS BEFORE INSTALLATION-(1) and (1-3) in (1) For new ceilings.)
(2-3)Perform steps (1-4), (1-5) in (1) For new ceilings.

9
3P177351-2D

126

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

6. REFRIGERANT PIPING WORK


For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.
Execute heat insulation work completely on both sides of the gas piping and the liquid piping. Otherwise, a
water leakage can result sometimes.
(When using a heat pump, the temperature of the gas piping can reach up to approximately 120C, so use
insulation which is sufficiently resistant.)
Also, in cases where the temperature and humidity of the refrigerant piping sections might exceed 30C or
RH80%, reinforce the refrigerant insulation. (20mm or thicker) Condensate may form on the surface of the
insulating material.
Be sure to check the type of R410A refrigerant to be used before doing any work. (Using an incorrect refrigerant will prevent normal operation of the unit.)

CAUTION
Use a pipe cutter and flare suitable for the type of refrigerant.
Apply ester oil or ether oil around the flare section before connecting.
To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end or cover
it with tape.
Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit, such
as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.

Do not mix air or other gas with the specified refrigerant in the refrigeration cycle.
Ventilate the room if refrigerant gas leaks during the work.
The outdoor unit is charged with refrigerant.
Be sure to use both a spanner and torque wrench together, as shown in the
drawing, when connecting or disconnecting pipes to/from the unit.
(Refer to Fig. 14)
Refer to Table 3 for the dimensions of flare nut spaces.

Torque wrench

Spanner
Pipe union
Flare nut
Fig. 14

When connecting the flare nut, apply ester oil or ether oil to the flare
section (only inside), and spin 3-4 times before screwing in.
(Refer to Fig. 15)
Keep all the screw mounting resin parts (e.g., piping presser
plates) away from oil.
If oil adheres, the strength of the screw mounting resin parts may
drop.

Coat the flare section (only inside)


with ester or ether oil.

Fig. 15

CAUTION
Over-tightening the flare nut may break it and/or cause the
refrigerant to leak.
NOTE
Use the flare nut included with the unit main body.
Table 3

9.5 (3/8)

32.7 39.9 Nm

12.8 13.2

15.9 (5/8)

61.8 75.4 Nm

19.3 19.7

Flare
452

Flare dimensions
A (mm)

R0.4-0.8

Tightening torque

902

Pipe size

Refer to Table 3 to determine the proper tightening torque.

10
C : 3P177351-2D

Installation of Indoor / Outdoor Unit

127

Installation of Indoor Unit

EDSG281001

Not recommendable but in case of emergency


You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may
follow the installation method mentioned below.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque
suddenly increases. From that position, further tighten the flare nut the angle shown below:
Pipe size
9.5 (3/8)
15.9 (5/8)

Further tightening angle


60 to 90 degrees
30 to 60 degrees

Recommended arm length of tool


Approx. 200mm
Approx. 300mm

After the work is finished, make sure to check that there is no gas leak.
Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas
leakage by thoroughly studying the following figure and using the attached heat insulating materials for
fitting (8) and (9). (Fasten both ends with the clamps (4).) (Refer to Fig. 16)
Wrap the sealing pad (11) only around the insulation for the joints on the gas piping side. (Refer to Fig. 16)

Gas Piping Insulation Procedure


Insulation for fitting (8)
(accessory)
Flare nut connection

Piping insulation
material (main unit)

Wrap over from the


base of the unit to
the top of the flare
nut connection.

Attach to base

Turn seams up

Main unit
Piping insulation
material
(Field supply)

Clamp (4) (accessory)


Tighten the part other
than the piping insulation
material.

Sealing pad
medium-1 (11)
(accessory)

Liquid Piping Insulation Procedure


Insulation for fitting (9)
(accessory)
Flare nut connection
Turn seams up

Piping insulation
material (main unit)

Wrap the
insulator around
the part from the
root.

Attach to base

Liquid piping

Main unit
Piping insulation
material
(Field supply)

Clamp (4) (accessory)


Tighten the part other
than the piping insulation
material.

Gas piping

Sealing pad
medium-2 (12)
(accessory)

Screw mounting part


of piping presser plate
(2 locations)
Fig. 16

CAUTION
For local insulation, be sure to insulate local piping all the way into the pipe connections inside the machine.
Exposed piping may cause condensation or burns on contact.
CAUTION
CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING
Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filler metal
(BCuP-2: JIS Z 3264/B-Cu93P-710/795: ISO 3677) which does not require flux.
(Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based
flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the
refrigerant oil.)

11
3P177351-2D

128

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Before brazing local refrigerant piping, nitrogen gas shall be blown through the piping to expel air from the piping.
If you brazing is done without nitrogen gas blowing, a large amount of oxide film develops inside the piping, and
could cause system malfunction.
When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution or
while inserting nitrogen into the refrigerant piping. Once this is done, connect the indoor unit with a flared
or a flanged connection.
Nitrogen should be set to 0.02MPa with a pressure-reducing valve if brazing while inserting nitrogen into
the piping. (Refer to Fig. 17)

Pressure-reducing valve
Refrigerant piping

Taping
Part to be
Hands valve
brazed
Nitrogen

Nitrogen

Fig. 17

7. DRAIN PIPING WORK


(1) Rig drain piping
As for drain work, perform piping in such a manner that water can be drained properly.
Employ a pipe with either the same diameter or with the diameter larger (excluding the raising section) than
that of the connecting pipe (PVC pipe, nominal diameter 25mm, outside diameter 32mm).
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets from
forming.
If the drain pipe cannot be sufficiently set on a slope, execute the drain raising piping.
To keep the drain pipe from sagging, space hanging wires every 1 to 1.5m.

Hanger bracket

11.5m 1/100 gradient or more

GOOD

WRONG

Fig. 18-1

Fig. 18-2

CAUTION
Water pooling in the drainage piping can cause the drain to clog.
Use the attached drain hose (1) and Metal clamp (2).
Insert the drain hose into the drain socket up to the base, and tighten the Metal clamp securely within the
portion of a white tape of the hose-inserted tip. Tighten the Metal clamp until the screw head is less than
4mm from the hose.
Wrap the attached sealing pad (10) over the Metal clamp and drain hose to insulate.
Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water leakage due to dew condensation.
Indoor drain pipe
Drain socket

Metal
clamp (2)

Metal
clamp (2)
(accessory)

Large sealing pad (10)


(accessory)

Drain hose (1)


Tape (White)
Fig. 19

Fig. 20

4mm

12
3P177351-2D

Installation of Indoor / Outdoor Unit

129

Installation of Indoor Unit

EDSG281001

<PRECAUTIONS FOR DRAIN RAISING PIPING>


Install the drain raising pipes at a height of less than 675mm.
The drain pump of this unit has a high delivery flow rate. Therefore, the higher the drain raising height is, the
lower the sound of draining will be. For this reason, a minimum drain raising height of 300mm is recommended.
Install the drain raising pipes at a right angle to the indoor unit and no more than 300mm from the unit.

To prevent air bubbles in the


drain hose part, keep it level or
slightly tilted up. Any bubbles in
the hose might cause the unit
to make noise due to backflow
when the drain pump stops.

Drain raising pipe

850

Level or
tilted
slightly up

Hanger bracket

175

Ceiling slab
300mm
1 1.5m

Drain hose (1)


(accessory)

Adjustable
( 675)

Raising section
Drain hose (accessory) (1)

Metal clamp
(accessory) (2)

Fig. 21

NOTE
To ensure no excessive pressure is applied to the included drain hose (1), do not bend or twist when installing. (This may cause leakage.)
If converging multiple drain pipes, install according to the procedure shown below.

0 675mm

Central drain pipe


The drain pipe should have a downward
slope of at least 1/100 to prevent
air pockets from forming.
Fig. 22

Water accumulating in the drain


piping can cause the drain to clog.

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
(2) After piping work is finished, check if drainage flows smoothly.
WHEN ELECTRIC WIRING WORK IS FINISHED
Add approximately 1000cc of water slowly from the air outlet and check drainage flow.
Check drainage flow during COOL running, explained under 12. TEST OPERATION.
Refer to the figure on the following after checking the draining of water, and mount the thermal insulation
material for drainage (14) and thermal insulate the drain socket.

Thermal insulation
material for drainage (14)
(accessory)

Thermal insulation
material for drainage (14)
(accessory)

Sealing pad (Large) (10)


Be sure to lay the sealing
material on (14).

Make sure that there


is no clearance.

WHEN ELECTRIC WIRING WORK IS NOT FINISHED


CAUTION
Electrical wiring work should be done by a certified electrician.
If someone who does not have the proper qualifications performs the work, perform the following after the
test run is complete.

13
3P177351-2D

130

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Remove the terminal box lid. Connect the single phase power supply (SINGLE PHASE 50Hz 240V) to connections No.1 and No.2 on the terminal block for wiring the units. Do not connect to No.3 of the terminal
block for wiring the units. (The drain pump will not operate.) Connect the ground wire firmly. When carrying
out wiring work around the terminal box, make sure none of the connectors come undone. Be sure to attach
the terminal box lid before turning on the power.
Put approximately 1000cc of water into the drain pan through the blow-off mouth on the left-hand side of the
drain socket. Make sure not to pour water over the drain pump or any electric parts including those of the
drain pump.
When the power is turned on, the drain pump will operate and you can check the draining of water through
the transparent part of the drain socket. (The drain pump will stop automatically in 10 minutes.)
After checking the draining of water, mount the thermal insulation material for drainage (14) and thermal
insulate the drain socket.
After confirming drainage (Fig.23, Fig.24), turn off the power and remove the power supply.
Attach the terminal box lid as before.

Drain sockets

At least
100mm

(Check the
drainage now.)

Plastic watering can


(Tube should be
about 100mm long.)

Drain pump
location

Service drain outlet (with rubber plug)


(Use this outlet to drain water from
the drain pan.)

<Adding water through air discharge outlet>


[Method of adding water]

Fig. 23

Inter-unit wiring
terminal block

Power supply
single phase 240V
Ground
3 2 1
wire
1

Terminal box lid

Fig. 24

14
3P177351-2D

Installation of Indoor / Outdoor Unit

131

Installation of Indoor Unit

EDSG281001

CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.

8. ELECTRIC WIRING WORK

All field supplied parts and materials and electric works must conform to local codes.
Use copper wire only.
For electric wiring work, refer to also WIRING DIAGRAM attached to the unit body.
For remote controller wiring details, refer to the installation manual attached to the remote controller.
All wiring must be performed by an authorized electrician.
A circuit breaker capable of shutting down power supply to the entire system must be installed.
Refer to the installation manual attached to the outdoor unit for the size of power supply electric wire connected to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
Be sure to ground the air conditioner.
Do not connect the ground wire to gas pipes, plumbing pipes, lightning rods, or telephone ground wires.
Gas pipes: might cause explosions or fire if gas leaks.
Plumbing: no grounding effect if hard vinyl piping is used.
Telephone ground wires or lightning rods: might cause abnormally high electric potential in the ground
during lighting storms.
Specifications for field wire
The remote control cord should be procured locally. Refer to the Table 4 when preparing one.
Table 4
Wire
Wiring the units
Remote controller cord

H05VV U4G (NOTE 1)


Vinyl cord with sheath or cable NOTE 2 (2 wire)

Size (mm )
2.5
0.75 1.25

Length

Max. 500m *

*This will be the total extended length in the system when doing group control.
NOTE
1. Shows only in case of protected pipes. Use H07RN-F in case of no protection.
2. Vinyl cord with sheath or cable (Insulated thickness : 1mm or more)
Connection of wiring between units, ground wire and for the remote controller cord (Refer to Fig. 25)
Wiring the units and ground wire
Remove the terminal box lid and connect wires of matching number to the terminal block for wiring the units
(4 P) inside. And connect the ground wire to the ground terminal. In doing this, pull the wires inside through
the hole and fix the wires securely with the included clamp (4).
Remote controller cords (not neccessary for slave unit of simultaneous operation system)
Remove the terminal box lid and pull the wires inside through the hole and connect to the terminal block for
remote controller (4 P). (no polarity) Securely fix the remote controller cord with the included clamp (4).
After connection, attach sealing pad (13).
Be sure to attach it to prevent the infiltration of water from the outside.

15
3P177351-2D

132

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Wiring
through-holes

Inter-unit wiring
Ground wire

Remote controller cord


(weak electric)

Remote
controller

Transmission
wiring

P1 P2 F1 F2

Approximately Sheaths
7mm
Peel back
the sheath
on the power 70 90mm
line and twist. Length of
sheath to
peel back
Inter-unit wiring
terminal block (4P)

10 15mm
Clamp (4)
Cut off any excess
material after
tightening.

Remote
controller
wiring
Wiring
through-holes

Clamping position

(Length of sheath to peel back)


10~15mm

Cut off any


excess
material after
tightening the
inter-unit wiring
and ground
Ground terminal wire together.
3 2 1
3

80~100mm

Remote
controller
wiring terminal
block
(P1 P2)
Terminal box lid

Clamp (4)

Ground
wire

Secure the ground wire


and inter-unit wiring with
both edges aligned.
Ground wire

Inter-unit
wiring sheath

<<Inter-unit wiring (strong electric) / ground wire>>

Electrical Wiring
Diagram Nameplate
(Inside of terminal box lid)

Fig. 25

Observe the notes mentioned below when wiring to the terminal block for wiring the units.
CAUTION
When clamping wiring, use the included clamping material to prevent outside pressure being exerted on the
wiring connections and clamp firmly. When doing the wiring, make sure the wiring is neat and does not
cause the terminal box lid to stick up, then close the cover firmly.
When attaching the terminal box lid, make sure you do not pinch any wires.
After all the wiring connections are done, fill in any gaps in the through holes with putty or insulation (procured locally) to prevent small animals and insects from entering the unit from outside. (If any do get in, they
could cause short circuits in the terminal box.)
Outside the machine, separate the weak wiring (remote controller cord) and strong wiring (interunit,
ground, and other power wiring) at least 50 mm so that they do not pass through the same place together.
Proximity may cause electrical interference, malfunctions, and breakage.

16
C : 3P177351-2D

Installation of Indoor / Outdoor Unit

133

Installation of Indoor Unit

EDSG281001

Processing method of wiring through-holes


Inter-unit wiring,
ground wire, or remote
controller cord

Wiring through-holes

Sealing pad (Small) (13)


Putty or thermal
insulation material
(procured locally)
Use a round crimp-style terminal with insulation sleeve for connection to the terminal block for wiring the
units.

Attach insulation sleeve

Round crimp-style terminal


Fig. 26

Electric wire

When none are available, follow the instructions below.


Do not connect wires of different gauge to the same power supply terminal.

Connect wires of the


same gauge to both
side.

Do not connect wires


of the same gauge to
one side.

Do not connect wires


of different gauges.

Fig. 27
(Looseness in the connection may cause overheating.)
In wiring, make certain that prescribed wires are used, carry out complete connections, and fix the wires so
that outside forces are not applied to the terminals.
Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the
head of the screw might be damaged, and the screw will not be properly tightened.
If the terminal screw are tightened too hard, screws might be damaged.
Refer to the table below for the tightening torque of the terminal screws.
Tightening torque (Nm)
Terminal block for remote controller

0.79 to 0.97

Terminal block for wiring the units

1.18 to 1.44

9. WIRING EXAMPLE
For the wiring of outdoor units, refer to the installation manual attached to the outdoor units.
Confirm the system type.
Pair type: 1 remote controller controls 1 indoor unit. (standard system) (Refer to Fig. 28)
Group control: 1 remote controller controls up to 16 indoor units. (All indoor units operate according to the
remote controller) (Refer to Fig. 29)
2 remote controllers control: 2 remote controllers control 1 indoor unit. (Refer to Fig. 30)
17
3P177351-2D

134

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Pair type

Group control

Main power supply

Main power supply

Main switch
Fuse

Main power supply

Main power supply

Main switch
Fuse

Main switch
Fuse

Main switch
Fuse

Outdoor unit

Outdoor unit

Outdoor unit

Outdoor unit

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

P1 P2

Indoor unit

Indoor unit

Remote controller
(Optional accessory)
Fig. 28

1 2 3
P1 P2

Indoor unit
P1 P 2

P1 P2

1 2 3

1 2 3
P1 P2

P1 P2

Indoor unit

Remote controller
(Optional accessory)
Fig. 29

2 remote controllers control


Main power supply
Main switch
Fuse
Outdoor unit
1 2 3

1 2 3
P1 P2

Indoor unit
P1 P2

P1 P2

Remote
controller

Remote
controller
(Slave)
(Optional accessories) Fig. 30
NOTE
1. All transmission wiring except for the remote controller wires is polarized and must match the terminal symbol.
2. In case of group control, perform the remote controller wiring to the master unit when connecting to the
simultaneous operation system. (wiring to the slave unit is unnecessary)
3. For group control remote controller, choose the remote controller that suits the indoor unit which has the
most functions (as attached swing flap)

18
C : 3P177351-2D

Installation of Indoor / Outdoor Unit

135

Installation of Indoor Unit

EDSG281001

10. INSTALLATION OF THE DECORATION PANEL


Caution:
With a wireless remote controller, field setting and test operation cannot be performed without attaching the decoration panel.
<If performing a test run without attaching the decoration panel, read 11. FIELD SETTING and 12. TEST
OPERATION first.>
Refer to the installation manual attached to the decoration panel.
After installing the decoration panel, ensure that there is no space between the unit body and decoration
panel.

11. FIELD SETTING


CAUTION
When performing field setting or test operation without attaching the decoration panel, do not
touch the drain pump. This may cause electric shock.
Check that the outdoor unit has been wired properly.
Make sure the terminal box lids are closed on the indoor and outdoor units.
Field setting must be made from the remote controller and in accordance with installation conditions.
Setting can be made by changing the Mode No., FIRST CODE NO. and SECOND CODE NO..
For setting procedures and instructions, see Field settings provided with the remote controller.

11-1 Setting ceiling height


Select the SECOND CODE NO. that corresponds to the ceiling height Table 5.
(SECOND CODE NO. is factory set to 01.)
Table 5
FCQ - KVEA
100125
71 type
140 type
Standard All
Ceiling round outlet
height (m) High ceiling 1
High ceiling 2

2.7

3.2

2.7 - 3
3 - 3.5

3.2 - 3.6
3.6 - 4.2

Mode No.
Note) 1

FIRST
CODE NO.

SECOND
CODE NO.
01

13 (23)

02
03

Note:
1. Mode No. setting is done in a batch for the group. To make or confirm settings for an individual unit, set
the internal mode number in parentheses.
2. The figure of the ceiling height is for the all round outlet. For the settings for four-direction (part of corner
closed off), three-direction and two-direction outlets, see the installation manual and technical guide supplied with the separately sold closure material kit.

11-2 Setting of air direction


See the installation manual included with the sealing material of air discharge outlet kit, sold separately and
technical guide, for ceiling height settings for two and three-direction air discharge. (The SECOND CODE
NO. is factory set to 01 (all round outlet) before shipping.)

11-3 Settings for Mounting Options


When installing an option sold separately, refer to the installation manual provided to the option.

19
C : 3P177351-2D

136

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

11-4 Setting air filter sign


Remote controllers are equipped with liquid crystal display air filter signs to display the time to clean air filters.
Change the SECOND CODE NO. according to Table 6 depending on the amount of dirt or dust in the
room.
(SECOND CODE NO. is factory set to 01 for filter contamination-light.)

Table 6
Spacing time of display air filter
sign (long life type)

Setting
Air filter contaminationlight
Air filter contaminationheavy
No Display

Mode No.

FIRST CODE
NO.

Approx. 2500 hrs

SECOND
CODE NO.
01

10 (20)

Approx. 1250 hrs

0
02
3

Note:
1. Mode No. setting is done in a batch for the group. To make or confirm settings for an individual unit, set
the internal mode number in parentheses.
2. Make settings for No Display in cases where no cleaning display is required, e.g., at the time of regular
maintenance servicing.
The air conditioner is provided with a long life filter as a standard accessory. Explain to the customer the
necessity of cleaning the filter periodically along with the set time for filter cleaning for the prevention of
clogging.
When using wireless remote controllers
When using wireless remote controllers, wireless remote controller address setting is necessary. Refer to
the installation manual attached to the wireless remote controller for setting instructions.

11-5 When implementing group control


When using as a pair unit, you may start/stop (group) control up to 16 unit with the remote controller.
In this case, all the indoor units in the group will operate in accordance with the group control remote controller.
Select a remote controller which matches as many of the functions (swing flap, etc) in the group as possible.

Outdoor unit 1
Indoor unit 1

Outdoor unit 2

Indoor unit 2

Outdoor unit 3

Indoor unit 3

Group control remote controller


Fig. 31
Wiring Method
(1) Remove the terminal box lid. (See 8. ELECTRIC WIRING WORK.)
(2) Cross-wire the terminal block for remote controller (P1, P2) inside the terminal box. (There is no
polarity.) (Refer to Fig. 29 and Table 4)

11-6 Control by 2 Remote Controllers (Controlling 1 indoor unit by 2 remote controllers)


When using 2 remote controllers, one must be set to MAIN and the other to SUB.
MAIN/SUB CHANGEOVER
(1) Insert a
screwdriver into the recess between the upper and lower part of remote controller and, working from the 2 positions, pry off the upper part. (The remote controller PC board is attached to the upper
part of remote controller.) (Refer to Fig. 32)
(2) Turn the main/sub changeover switch on one of the two remote controller PC boards to S. (Leave the
switch of the other remote controller set to M.) (Refer to Fig. 33)

20
3P177351-2D

Installation of Indoor / Outdoor Unit

137

Installation of Indoor Unit

EDSG281001

Upper part of
remote controller

Lower part of
remote controller

Insert the screwdriver here


and gently work off the
upper part of remote controller.

Fig. 32

S
M

(Factory setting)
(Only one remote
controller needs
to be changed if
factory settings
have remained
untoched.)

Remote
controller
PC board

S
M

Fig. 33

Wiring Method (See 8. ELECTRIC WIRING WORK.)


(3) Remove the terminal box lid.
(4) Add remote controller 2 (slave) to the terminal block for remote controller (P1, P2) in the terminal
box. (There is no polarity.) (Refer to Fig. 30 and Table 4)

12. TEST OPERATION


CAUTION
When performing field setting or test operation without attaching the decoration panel, do not
touch the drain pump. This may cause electric shock.
Refer to the section of FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED. .
After finishing the construction of refrigerant piping, drain piping, and electric wiring, conduct test operation
accordingly to protect the unit.
Check that the outdoor unit has been wired properly.
Check that the terminal box lid of the indoor unit is closed and that the outer plate and piping cover of the
outdoor unit are closed as well.
Clean the decoration panel and interior of the indoor unit on completion of refrigerant piping, drain piping,
and electric wiring work.
Refer to the installation manual provided to the outdoor unit, and perform the test operation of the air conditioner.
If the decoration panel is mounted at the time of test operation, check the operation of the swing flap of the
decoration panel.
If the interior finishing work has been still on the way on completion of test operation, explain to the customer not to operate the air conditioner for the protection of the indoor unit until the interior finishing work
is completed.
If the air conditioner is operated, substances generated from the paint and glue of the interior finishing will
contaminate the indoor unit, thus resulting in water splashing or leakage.
If an error occurs and the air conditioner does not operate, refer to the following troubleshooting information.
On completion of test operation, press the INSPECTION/TEST OPERATION button to set the air conditioner to
mode and check that the error code is set to 00 (=normal).
If the error code is other than 00, refer to the following troubleshooting information.
The air conditioner will return to normal run mode if the INSPECTION/TEST OPERATION button is pressed
four times.
Perform the trial operation of the air conditioner after mounting the decoration panel if the wireless remote
controller is used.

Mode change
Normal operation
Once
(4 s min.)

Once

Field settings

Four times
Once
On
ce
Fo
ur
tim
es

Test run

Inspection

21
3P177351-2D

138

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

PRECAUTIONS
1. Refer to the diagnoses below if the unit does not operate properly.
2. After completing the test run, press the INSPECTION/TEST OPERATION button once to put the unit in
inspection mode, and make sure the malfunction code is 00. (=normal)
If the code reads anything other than 00, refer to the malfunction diagnoses below.
NOTE
If a malfunction is preventing operation, refer to the malfunction diagnoses below.

12-1 Cautions for servicing


With the power on. Troubles can be monitored on the remote controller.
If the air conditioner does not operate normally after installing the air conditioner.
a malfunction shown in the table below may happened.
Remote controller display

No display

88*
88 flashing

Malfunction
Power supply trouble or Open phase connection
Wrong wiring between indoor and outdoor unit
Indoor PC board faulty
Wrong remote controller conection wiring
Remote controller faulty
Fuse faulty
Indoor PC board faulty
Wrong wiring between indoor and outdoor unit
Wrong wiring between indoor and outdoor unit

*After turning on the power, the maximum is 90 seconds, although it will only display 88. This is not a
problem, and it will be set for 90 seconds.
Trouble shooting with the display on the liquid crystal display remote controller.
1. With the wired remote controller. (NOTE 1)
When the operation stops due to trouble, operation lamp flashed, and
and the Malfunction code are
indicated on the liquid crystal display. In such a case, diagnose the fault contents by referring to the table
on the Malfunction code list it case of group control, the unit No. is displayed so that the indoor unit no with
the trouble can be recognized. (NOTE 2)
2. With the wireless remote controller.
(Refer also to the operation manual attached to the wireless remote controller)
When the operation stops due to trouble. the display on the indoor unit flashes. In such a case, diagnose
the fault contents with the table on the Malfunction code list looking for the Malfunction code which can be
found by following procedures. (NOTE 2)
(1) Press the INSPECTION /TEST OPERATION button,
is displayed and 0 flashes.
(2) Press the PROGRAMMING TIME button and find the unit No. which stopped due to trouble.
Number of beeps 3 short beeps Perform all the following operations
1 short beep
Perform (3) and (6)
1 long beep
No trouble
(3) Press the OPERATION MODE SELECTOR button and upper figure of the Malfunction code flashes.
(4) Continue pressing the PROGRAMMING TIME button unit it makes 2 short beeps and find the upper code.
(5) Press the OPERATION MODE SELECTOR button and lower figure of the Malfunction code flashes.
(6) Continue pressing the PROGRAMMING TIME button unit it makes a long beep and find the lower code.
A long beep indicate the Malfunction code.
NOTE
1. In case wired remote controller. Press the INSPECTION /TEST OPERATION button on remote controller,

starts flashing and changes the inspection mode.


2. Keep down the ON/OFF button for 5 seconds or longer in the inspection mode and the above trouble history disappears, after the trouble code goes on and off twice, followed by the code 00(normal).
The display changes from the inspection mode to the normal mode.
Caution:
Check the items in 2. Items to be checked at time of delivery on page 4 after a test operation.

22
3P177351-2D

Installation of Indoor / Outdoor Unit

139

Installation of Indoor Unit

EDSG281001

12-2 Malfunction code list


For places where the Malfunction code is left blank, the
indication is not displayed. Though the system
continues operating, be sure to inspect the system and make repairs as necessary.
Depending on the type of indoor or outdoor unit, the Malfunction code may or may not be displayed.
Code
A0
A1
A3
A6
AF
AH
AJ
C4
C9
CC
CJ
E0
E1
E3
E4
E5
E7
E9
F3
H3
H4
H7
H9
JA
JC
J1
J2
J3
J5
J6
J7
J8
J9

Malfunction/Remarks
Safety device operates
Indoor units PC board faulty
Drain water level abnormal
Indoor fan motor overloaded, overcurrent or locked
Humidifier faulty
Air cleaner faulty
Only the air cleaner does not function.
Type set improper
Capacity data is wrongly preset. Or there is nothing programmed in the data hold IC.
Sensor for heat exchanger temperature is fault
Sensor for suction air temperature is fault
Humidity sensor abnormal
Sensor for remote controller is fault
The remote controller thermistor does not function, but the system thermo run is
possible.
Action of safety device (outdoor unit)
Outdoor units PC board faulty
High pressure abnormal (outdoor unit)
Low pressure abnormal (outdoor unit)
Compressor motor lock malfunction
Outdoor fan motor lock malfunction
Outdoor fan instantaneous overcurrent malfunction
Electronic expansion valve faulty (outdoor unit)
Discharge pipe temperature abnormal (outdoor unit)
High pressure switch faulty (outdoor unit)
Low pressure switch faulty (outdoor unit)
Outdoor motor position signal malfunction
Outdoor air thermistor faulty (outdoor unit)
Equipment operation in response to errors will vary according to model.
Discharge pipe pressure sensor faulty (outdoor unit)
Suction pipe pressure sensor faulty (outdoor unit)
Pressure sensor system error (batch) (outdoor unit)
Power sensor system error (outdoor unit)
Discharge pipe thermistor faulty (outdoor unit)
Equipment operation in response to errors will vary according to model.
Suction pipe thermistor faulty (outdoor unit)
Heat exchanger thermistor faulty (outdoor unit)
Equipment operation in response to errors will vary according to model.
Heat exchanger thermistor faulty (outdoor unit)
Equipment operation in response to errors will vary according to model.
Liquid piping temperature sensor system error (outdoor unit)
Intake temperature sensor error (outdoor unit)

23
3P177351-2D

140

Installation of Indoor / Outdoor Unit

EDSG281001

L1
L4
L5
L8
L9
LC
P1
P3
P4
PJ
U0
U1
U2
U4
UF
U5
U8
UA
UC
UJ

Installation of Indoor Unit

Inverter system error (outdoor unit)


Overheated heat-radiating fin (outdoor unit)
Inverter cooling defect.
Instantaneous overcurrent (outdoor unit)
Possible earth fault or short circuit in the compressor motor.
Electric thermal (outdoor unit)
Possible electrical overload in the compressor or cut line in the compressor motor.
Stall prevention (outdoor unit)
Compressor possibly locked.
Transmission malfunction between the outdoor control units inverters (outdoor unit)
Open-phase (outdoor unit)
P-board temperature sensor malfunction (outdoor unit)
Heat-radiating fin temperature sensor malfunction (outdoor unit)
Type set improper (outdoor unit)
Capacity data is wrongly preset. Or there is nothing programmed in the data hold IC.
Suction pipe temperature abnormal
Reverse phase
Reverse two phase of the L1,L2and L3 leads.
Power source voltage malfunction (outdoor unit)
Includes the defect in 52C.
Transmission error (indoor unit outdoor unit)
Wrong wiring between indoor and outdoor units or malfunction of the PC board
mounted on the indoor and the outdoor units.
Transmission error (indoor unit remote controller)
Transmission is improper between the indoor unit and the remote controller.
Malfunction in transmission between main and sub remote controls.
(Malfunction in sub remote controller.)
Miss setting for multi system
Setting is wrong for selector switch of multi-system. (see switch SS2 on the main
units PC board)
Central control address overlapping
Peripheral equipment transmission fault

24
3P177351-2D

Installation of Indoor / Outdoor Unit

141

Installation of Indoor Unit

EDSG281001

2.2

FFQ25BV1B / FFQ35BV1B / FFQ50BV1B / FFQ60BV1B

2.2.1

Names and Functions of Parts

e
d

h
f
g

b
d
c

c
d
e
f
g
h
i
j
k

Indoor unit
Outdoor unit
The external appearance of the outdoor
unit varies depending on its capacity
class. The outdoor unit shown in the figure is for reference to indicate features.
Contact your Daikin Dealer and verify
which outdoor unit you have.
Remote controller
Depending on the system configuration,
the remote controller is not provided.
Inlet air
Discharged air
Air outlet
Air flow flap (at air outlet)
Refrigerant piping, connection electric wire
Drain pipe
Air inlet
The built-in air filter removes dust and dirt.
Drain pumping out device (built-in)
Drains water removed from the room during cooling.
Ground wire
Wire to ground from the outdoor unit to prevent electrical shocks.
3P184442-4D

142

Installation of Indoor / Outdoor Unit

EDSG281001

2.2.2

Installation of Indoor Unit

Installation
FFQ25BV1B
FFQ35BV1B
FFQ50BV1B
FFQ60BV1B

SPLIT SYSTEM Air Conditioners

Installation manual

2
CONTENTS

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

SAFETY PRECAUTIONS .......................................................................................... 1


BEFORE INSTALLATION ........................................................................................... 2
SELECTING INSTALLATION SITE ............................................................................ 5
PREPARATIONS BEFORE INSTALLATION.............................................................. 6
INDOOR UNIT INSTALLATION .................................................................................. 7
REFRIGERANT PIPING WORK ................................................................................. 9
DRAIN PIPING WORK.............................................................................................. 11
WIRING EXAMPLE ................................................................................................... 14
ELECTRIC WIRING WORK ...................................................................................... 15
INSTALLATION OF THE DECORATION PANEL..................................................... 17
FIELD SETTINGS ..................................................................................................... 18
TEST OPERATION ................................................................................................... 19

1. SAFETY PRECAUTIONS
Please read these SAFETY PRECAUTIONS carefully before installing air conditioning equipment and be
sure to install it correctly.
After completing installation, conduct a trial operation to check for faults and explain to the customer how to
operate the air conditioner and take care of it with the aid of the operation manual. Ask the customer to store
the installation manual along with the operation manual for future reference.
This air conditioner comes under the term appliances not accessible to the general public.
Meaning of WARNING and CAUTION notices.
WARNING ........ Failure to follow these instructions properly may result in personal injury or loss of life.
CAUTION ......... Failure to observe these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances.

WARNING
Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage,
electric shocks or fire.
Install the air conditioner in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shocks or fire.
Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.
Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
A foundation of insufficient strength may result in the equipment falling and causing injury.
Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit falling and causing accidents.
Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried
out by qualified personnel according to local laws and regulations and this installation manual.
An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.
Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or fire.
English

1
3P184443-4D

Installation of Indoor / Outdoor Unit

143

Installation of Indoor Unit

EDSG281001

When wiring the power supply and connecting the wiring between the indoor and outdoor units, position
the wires so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric shocks, fire or overheating terminals.
If refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into contact with fire.
After completing installation, check for refrigerant gas leakage.
Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source
of fire, such as a fan heater, stove or cooker.
Be sure to switch off the unit before touching any electrical parts.
Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead.
Imperfect earthing may result in electric shocks or fire.
A high surge current from lightning or other sources may cause damage to the air conditioner.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks or fire.

CAUTION
While following the instructions in this installation manual, install drain piping to ensure proper drainage and
insulate piping to prevent condensation.
Improper drain piping may result in indoor water leakage and property damage.
Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televisions or radios to prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 1 meter may not be sufficient to eliminate
noise.)
Remote controller (wireless kit) transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps (inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as possible.
Do not install the air conditioner in the following locations:
1. Where there is a high concentration of mineral oil spray or vapour (e.g. a kitchen).
Plastic parts will deteriorate, parts may fall off and water leakage could result.
2. Where corrosive gas, such as sulphurous acid gas, is produced.
Corroding of copper pipes or soldered parts may result in refrigerant leakage.
3. Near machinery emitting electromagnetic radiation.
Electromagnetic radiation may disturb the operation of the control system and result in a malfunction of
the unit.
4. Where flammable gas may leak, where there is carbon fibre or ignitable dust suspensions in the air, or
where volatile flammables such as paint thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.
The air conditioner is not intended for use in a potentially explosive atmosphere.

2. BEFORE INSTALLATION
Do not exert pressure on the resin parts when opening the unit or when moving it after opening
Be sure to check the type of R410A refrigerant to be used before doing any work. (Using an incorrect
refrigerant will prevent normal operation of the unit.)
When opening the unit or moving it after opening, be sure to lift it by holding on to the lifting lugs without
exerting any pressure on other parts, especially, drain piping, and other resin parts.
Decide upon a line of transport.
Leave the unit inside its packaging while moving, until reaching the installation site. Use a sling of soft
material, where unpacking is unavoidable or protective plates together with a rope when lifting, to avoid
damage or scratches to the unit.
Especially, do not unfasten packing case(top) guarding the control box until suspending the unit.
Refer to the installation manual of the outdoor unit for items not described in this manual.
Do not dispose of any parts necessary for installation until the installation is complete.

English
3P184443-4D

144

Installation of Indoor / Outdoor Unit

EDSG281001

2-1

Installation of Indoor Unit

PRECAUTIONS

2-2

Be sure to read this manual before installing the indoor unit.


When selecting installation site, refer to the paper pattern.
This unit is suitable for installation in a household, commercial and light industrial environment.
Do not install or operate the unit in rooms mentioned below.
Laden with mineral oil, or filled with oil vapor or spray like in kitchens. (Plastic parts may deteriorate.)
Where corrosive gas like sulfurous gas exists. (Copper tubing and brazed spots may corrode.)
Where volatile flammable gas like thinner or gasoline is used.
Where machines can generate electromagnetic waves. (Control system may malfunction.)
Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates
greatly such as that in factories. Also in vehicles or vessels.

ACCESSORIES

Check the following accessories are included with your unit.

Name

(1)Drain hose

(2)Metal clamp

(3)Washer for
hanger bracket

Quantity

1 pc.

1 pc.

8 pcs.

(4)Clamp
(Big)
6 pcs.

(5)Paper pattern
for installation

(Small)
1 pc.

1 pc.
Also used as
packing material

Shape

Name

(6)Screws
(M5)

Quantity

4 pcs.

(7)Washer
Insulation for fitting
fixing plate
4 pcs.

For paper pattern


for installation

Sealing pad

1 each.

1 each.

(8)For gas pipe

(12)Sealing
material
2 pcs.

(10)Large

Operation
manual
Installation
manual

Shape
(11)Small

(9)For liquid pipe

2-3

(Other)

OPTIONAL ACCESSORIES

The optional decoration panel and remote controller are required for this indoor unit.(Refer to Table 1, 2)
Table 1
Unit model

Optional decoration panel


BYFQ60BW1
Color : White

FFQ25355060BV1B

These are two types of remote controllers: wired and wireless. Select a remote controller from Table 2
according to customer request and install in an appropriate place.
Table 2
Remote controller type
Wired type
Wireless type

Cooling only type

Heat Pump type


BRC1C61

BRC7E531W

BRC7E530W

NOTE
If you wish to use a remote controller that is not listed in Table 2 on page 3, select a suitable remote controller after consulting catalogs and technical materials .
English

3
3P184443-4D

Installation of Indoor / Outdoor Unit

145

Installation of Indoor Unit

EDSG281001

FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND
CHECK AFTER INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
Items to be checked
If not properly done, what is likely to occur
Are the indoor and outdoor unit fixed firmly? The units may drop, vibrate or make noise.
The unit may malfunction or the compoIs the outdoor unit fully installed?
nents burn out.
Is the gas leak test finished?
It may result in insufficient cooling.
Is the unit fully insulated?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond The unit may malfunction or the compoto that shown on the name plate?
nents burn out.
The unit may malfunction or the compoAre wiring and piping correct?
nents burn out.
Is the unit safely grounded?
Dangerous at electric leakage.
The unit may malfunction or the compoIs wiring size according to specifications?
nents burn out.
Is something blocking the air outlet or inlet
It may result in insufficient cooling.
of either the indoor or outdoor units?
Are refrigerant piping length and additional The refrigerant charge in the system is not
refrigerant charge noted down?
clear.

Check

b. Items to be checked at time of delivery

Also review the SAFETY PRECAUTIONS


Items to be checked
Are the control box lid, air filter, suction grille attached?
Did you explain about operations while showing the instruction manual to your customer?
Did you hand the instruction manual over to your customer?

Check

c. Points for explanation about operations


The items with
WARNING and
CAUTION marks in the instruction manual are the items pertaining to possibilities for bodily injury and material damage in addition to the general usage of
the product. Accordingly, it is necessary that you make a full explanation about the described contents
and also ask your customers to read the instruction manual.

2-4

NOTE TO THE INSTALLER

Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating different functions, and adjusting the temperature) by having them carry out operations themselves while looking at the manual.

English
3P184443-4D

146

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

3. SELECTING INSTALLATION SITE


Hold the unit by the 4 lifting lugs when opening the box and moving it, and do not exert pressure on to any
other part piping (refrigerant, drain, etc.) or plastic parts.
If the temperature or humidity inside the ceiling might rise above 30C or RH 80%, respectively, use the
high-humidity kit (sold separately) or add extra insulation to the main unit body.
Use glass wool or polyethylene foam as insulation and make sure it is at least 10mm thick and fits inside the
ceiling opening.
The direction this product blows can be selected. However, a separately sold shut-off material kit is
needed in order to make the unit blow in two, three, or four (corner shut-off) directions.
(1) Select an installation location with the customers approval which matches the following conditions.
A location from which cool (warm) air will reach the whole room.
A location with no objects blocking the air passage.
A location where drainage can be done with no problem.
A location strong enough to support the weight of the indoor unit.
Locations where the wall is not significantly tilted.
A location which leaves enough room for installation and service work.
A location where there is no risk of flammable gas leaking.
A location where the length of the indoor-outdoor piping is no longer than the tolerated length (see the
installation manual that came with the outdoor unit for details).

[Space required for installation] (mm)


>

>

* 1500

Air
outlet

* 1500

1500

2500

>

>

>

For installation
in high places

* 1500

Air
Air outlet
inlet

>

* 1500

>

* 1500

Fig. 1

>

* 1500

Fig. 2

NOTE
Leave 200 mm or more space where marked with the *, on sides where the air outlet is closed.
Model

FFQ25355060

285 (Confirm the space of 295 or more)

CAUTION
Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the
noise.)
(2) Air flow direction
The air direction shown is an example.
Select the appropriate number of directions according to the shape of the room and the location of the
unit. (Field settings have to be made using the remote controller and the outlet vents have to be shut off if
two, three, or four (corner shut-off) directions are selected. See the shut-off materials (sold separately)
installation manual for details.)

English

5
3P184443-4D

Installation of Indoor / Outdoor Unit

147

Installation of Indoor Unit

EDSG281001

[Air flow direction] (Example)


Piping

Piping

Air outlet in
4 directions

Piping

Air outlet in
3 directions

Air outlet in
2 directions

(3) Use suspension bolts for installation. Check whether the ceiling is strong enough to support the
weight of the unit or not. If there is a risk, reinforce the ceiling before installing the unit.
(Installation pitch is maked on the paper pattern for installation. Refer to it to check for points requiring
reinforcing.)

4. PREPARATIONS BEFORE INSTALLATION


(1) Relation of ceiling opening to unit and suspension bolt position.

Suspension
bolt ( 4)

533 (Suspension bolt pitch)


575 (indoor unit)
585-660 (Ceiling opening)
700 (Decoration panel)

(Ceiling opening dimension)


585 *660
Hanger
bracket

False
ceiling

20

20

(Ceiling-panel overlapping dimension)


View as seen from A
Fig. 3
Fig. 4

(180)

700 (Decoration panel)


585-660 (Ceiling opening)
575 (indoor unit)
533 (Suspension bolt pitch)

Refrigerant
piping

(mm)

A
NOTE
Installation is possible with a ceiling dimension of 660 mm (marked with *). However, to achieve a ceilingpanel overlapping dimension of 20 mm, the spacing between the ceiling and the unit should be 45 mm or
less. If the spacing between ceiling and the unit is over 45 mm, attach ceiling material to
part or
recover the ceiling.

False
ceiling

False
ceiling

Ceiling material
< 45

< 45

(mm)
Fig. 5

(2) Make the ceiling opening needed for installation where applicable. (For existing ceilings)
Refer to the paper pattern for installation (5) for ceiling opening dimensions.
Create the ceiling opening required for installation. From the side of the opening to the casing outlet,implement the refrigerant and drain piping and wiring for remote controller (unnecessary for wireless type) and wiring between units. Refer to each PIPING or WIRING section.
After making an opening in the ceiling, it may be necessary to reinforce ceiling beams to keep the ceiling level and to prevent it from vibrating. Consult the builder for details.

English
3P184443-4D

148

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

(3) Install the suspension bolts.


(Use either a M8 ~ M10 size bolt)
Use a hole-in anchor for existing ceilings, and
a sunken insert, sunken anchor or other field
supplied parts for new ceilings to reinforce
the ceiling to bear the weight of the unit.
Adjust clearance (50 100 mm) from the
ceiling before proceeding further.

<installation example>
Ceiling slab
Anchor
Long nut or turn-buckle
Suspension bolt
False ceiling

NOTE
All the above parts are field supplied.

(mm)

Fig. 6

5. INDOOR UNIT INSTALLATION


Installing optional accessories (except for the decoration panel) before installing the indoor unit is
easier. However, for existing ceilings, install fresh air inlet component kit and branch duct before
installing the unit.
As for the parts to be used for installation work, be sure to use the provided accessories and specified parts
designated by our company.
(1) For new ceilings
(1-1) Install the indoor unit temporarily.
Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using a nut and
washer (3) from the upper and lower sides of the hanger bracket.
The washer fixing plate (7) will prevent the washer from falling.

Washer (3) (accessory)


Hanger bracket

Insert

Tighten
(double nuts)

Nut
(Field supplied)

Washer fixing plate (7)


(accessory)

[Securing the hanger bracket]

[Securing the washer]

Fig. 7

Fig. 8

(1-2) Refer to the paper pattern for installation (5) for ceilling opening dimension.
Consult the builder or carpenter for details.
The center of the ceiling opening is indicated on the paper pattern for installation.
The center of the unit is indicated on the paper pattern for installation.
Fix the paper pattern to the unit with screws (6) (4).
Ceiling height is shown on the side of the paper pattern for installation (5). Adjust the height of the
unit according to this indication.
Please perform one of the following, as the shape of the paper pattern for installation differs
according to the model.
Paper pattern for installation (5)
(accessory)

Screws (6)
(accessory)
Screws (6)
(accessory) [Installation of paper pattern for installation]
Fig. 9
English

7
3P184443-4D

Installation of Indoor / Outdoor Unit

149

Installation of Indoor Unit

EDSG281001

<Ceiling work>
(1-3) Adjust the unit to the right position for installation.
(Refer to 4.PREPARATIONS BEFORE INSTALLATION-(1).)
(1-4) Check the unit is horizontally level.
The indoor unit is equipped with a built-in drain pump and float switch. Verify that it is level by using
a water level or a waterfilled vinyl tube.
CAUTION
If the unit is tilted against condensate flow, the float
switch may malfunction and cause water to drip.
(1-5) Remove the washer fixing plate (7) used for preventing the washer from falling and tighten the
upper nut.
(1-6) Remove the paper pattern for installation (5).

Water level

Vinyl tube

[Maintaining horizontality]
(2) For existing ceilings
Fig. 10
(2-1) Install the indoor unit temporarily.
Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using a nut and
washer (3) from the upper and lower sides of hanger bracket. The washer fixing plate (7) will prevent the washer from falling.

Washer (3) (accessory)


Hanger bracket
Insert
Nut
(Field supplied)

Tighten
(double nuts)
[Securing the hanger bracket]
Fig. 11

Washer fixing plate (7)


(accessory)
[Securing the washer]
Fig. 12

(2-2) Adjust the height and position of the unit.


(Refer to 4.PREPARATIONS BEFORE INSTALLATION-(1).)
(2-3) Perform steps (1-4), (1-5) in (1) For new ceilings.

English
3P184443-4D

150

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

6. REFRIGERANT PIPING WORK


<For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.>
<Execute heat insulation work completely on both sides of the gas piping and the liquid piping.
Otherwise, a water leakage can result sometimes.>
(When using a heat pump, the temperature of the gas piping can reach up to approximately 120 C, so use
insulation which is sufficiently resistant.)
<Also, in cases where the temperature and humidity of the refrigerant piping sections might exceed
30 C or RH80%, reinforce the refrigerant insulation. (20 mm or thicker) Condensation may form on
the surface of the insulating material.>
<Before refrigerant piping work, check which type of refrigerant is used. Proper operation is not possible if the types of refrigerant are not the same.>

CAUTION
Use a pipe cutter and flare suitable for the type of refrigerant.
Apply ester oil or ether oil around the flare portions before connectiong.
To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end
or cover it with tape.
Do not allow anything other than the designated refrigerant to get mixed into the refrigerant
circuit, such as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room
thoroughly right away.
The outdoor unit is charged with refrigerant.
Be sure to use both a spanner and torque wrench together, as
shown in the drawing, when connecting or disconnecting pipes to/
from the unit. (Refer to Fig. 13)
Refer to Table 3 for the dimensions of flare nut spaces.
When connecting the flare nut, coat the flare section (only inside)
with ester oil or ether oil, rotate three or four times first,
then screw in. (Refer to Fig. 14)

Torque wrench

Spanner
Piping union

CAUTION

Flare nut

Over-tightening may damage the flare and cause a


refrigerant leakage.

Apply ester oil or


ether oil only inside

NOTE
Use the flare nut included with the unit main body.
Table 3
Pipe size

Tightening torque

6.4(1/4")

14.2 - 17.2 Nm
(144 - 175 kgfcm)
32.7 - 39.9 Nm
(333 - 407 kgfcm)

9.5(3/8")
12.7(1/2")

49.5 - 60.3 Nm
(505 - 615 kgfcm)

Fig. 13

Fig. 14

Flare dimensions
A (mm)

Flare

8.7-9.1
12.8-13.2
16.2 - 16.6

Refer to Table 3 to determine the proper tightening torque.

English

9
C : 3P184443-4D

Installation of Indoor / Outdoor Unit

151

Installation of Indoor Unit

EDSG281001

Not recommendable but in case of emergency


You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may follow the installation method mentioned below.
After the work is finished, make sure to check that there is no gas leak.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque suddenly increases. From that position, further tighten the flare nut the angle shown below:
Pipe size
6.4 (1/4")
9.5 (3/8")
12.7 (1/2")

Further tightening angle


60 90 degrees
60 90 degrees
30 60 degrees

Recommended arm length of tool


Approx. 150mm
Approx. 200mm
Approx. 250mm

CAUTION
CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING
Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filler metal
(BCuP-2: JIS Z 3264/B-Cu93P-710/795: ISO 3677) which does not require flux.
(Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based
flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the
refrigerant oil.)
Before brazing local refrigerant piping, nitrogen gas shall be blown through the piping to expel air from the
piping.
If your brazing is done without nitrogen gas blowing, a large amount of oxide film develops inside the piping, and could cause system malfunction.
When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution or
while inserting nitrogen into the refrigerant piping. Once this is done, connect the indoor unit with a flared
or a flanged connection.
Nitrogen should be set to 0.02 MPa (0.2 kg/cm2) with a pressure-reducing valve if brazing while inserting
nitrogen into the piping. (Refer to Fig.15)

Taping

Refrigerant piping

Pressure-reducing valve
Part to be
brazed

hands valve

Nitrogen

Nitrogen
Fig. 15

Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas
leakage by thoroughly studying the following figure and using the attached heat insulating materials for fitting (8) and (9). (Fasten both ends with the clamps (4).)
(Refer to Fig. 16)
Wrap the sealing pad (11) only around the insulation for the joints on the gas piping side.
(Refer to Fig. 16)

10

English
3P184443-4D

152

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Small sealing pad


(accessory) (11)
(Wrap the piping union
with the sealing pad.)
Clamp (4)
(Big 4)
(accessory)

Liquid piping

Insulation for fitting


(accessory) (9)
(for liquid pipe)
Insulation for fitting (accessory) (8)
(for gas pipe)
Gas piping

Fig. 16
CAUTION
Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.

7. DRAIN PIPING WORK


(1) Carry out the drain piping
Lay pipes so as to ensure that drainage can occur with problems.
Employ a pipe with either the same diameter or with the diameter larger (excluding the raising section)
than that of the connecting pipe (PVC pipe, nominal diameter 20 mm, outside diameter 26 mm).
keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets from
forming.
If the drain hose cannot be sufficiently set on a slope, refer to PRECAUTIONS FOR DRAIN RAISING PIPING on page 12.
To keep the drain hose from sagging, space hanger bracket every 1 to 1.5 m.

Hanger bracket
GOOD

1/100
gradient or more

WRONG

WRONG

Fig. 17

Fig. 18

CAUTION
Water pooling in the drainage piping can cause the drain to clog.
Use the attached drain hose (1) and metal clamp (2).
Insert the drain hose into the drain socket up to the base, and tighten the clamp securely within the portion
of a gray tape of the hose-inserted tip. Tighten the clamp until the screw head is less than 4 mm from the
hose.
Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water
leakage due to dew condensation.
Indoor drain pipe
Drain socket
Wrap the attached sealing pad (10) over the metal clamp (2) and drain hose to insulate.

English

11
3P184443-4D

Installation of Indoor / Outdoor Unit

153

Installation of Indoor Unit

EDSG281001

Metal clamp (2)


(accessory)

Metal clamp (2)


(accessory)

Large sealing pad (10)


(accessory)

Drain hose (1)


(accessory)

Tape (Gray)

4mm

Fig. 19

Fig. 20

<PRECAUTIONS FOR DRAIN RAISING PIPING>


Install the drain raising pipes at a height of less than 545 mm.
Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit.

Drain hose (1)


(accessory)
300

Drain hose (accessory)(1)

Adjustable
( 545)

1-1.5m

Metal clamp (2)


(accessory)

750

To prevent air bubbles in the


drain hose part, keep it level or
slightly tilted up. Any bubbles in
the hose might cause the unit to
make noise due to backflow
when the drain pump stops.

Hanger bracket

Ceiling slab

205

Level or
tilted
slightly up

(mm)

Drain raising pipe


Raising section

Fig. 21

NOTE
To ensure no excessive pressure is applied to the included drain hose (1), do not bend or twist when
installing. (This may cause leakage.)
If converging multiple drain pipes, install according to the procedure shown below.

0 545mm

Central drain pipe


The drain pipe should have a downward
slope of at least 1/100 to prevent
air pockets from forming.
Fig. 22

Water accumulating in the drain


piping can cause the drain to clog.

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
(2) After piping work is finished, check if drainage flows smoothly.
Add approximately 1000 cc of water slowly from the air outlet and check drainage flow.
WHEN ELECTRIC WIRING WORK IS FINISHED
Check drainage flow during cooling operation, explained in HOW TO TEST OPERATION on page 19.
WHEN ELECTRIC WIRING WORK IS NOT FINISHED
CAUTION
Electrical wiring work should be done by a certified electrician.
If someone who does not have the proper qualifications performs the work, perform the following after the
test run is complete.
Remove the control box lid. Connect the single phase power supply (SINGLE PHASE 50Hz 220-240V) to connections No.1 and No.2 on the power supply terminal block. Do not connect to No.3 of the power supply terminal block. (The drain pump will not operate.) When carrying out wiring work around the control box, make sure
none of the connectors come undone. Be sure to attach the control box lid before turning on the power.
After confirming drainage (Fig.23, Fig.24), turn off the power and remove the power supply.
Attach the control box lid as before.
12

English
3P184443-4D

154

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Drain sockets
(Check the drainage now.)
Drain pump
location

2
100

(mm)
Plastic container
for pouring
(Tube should be
about 100 mm long.)

Service drain outlet (with rubber plug)


(Use this outlet to drain water from
the drain pan)
<Adding water through air outlet>
[Method of adding water]
Fig. 23

Control
box lid

Remove the
control box lid
(take off 2 screws)

Power supply
terminal block

No.3
No.1 No.2

Ground
Single phase
power supply
(50Hz 220-240V)

Fig. 24

CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage
might enter the indoor unit through the drain pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.

English

13
3P184443-4D

Installation of Indoor / Outdoor Unit

155

Installation of Indoor Unit

EDSG281001

8. WIRING EXAMPLE
For the wiring of outdoor units, refer to the installation manual attached to the outdoor units.
Confirm the system type.
Pair type: 1 remote controller controls 1 indoor unit. (standard system) (Refer to Fig. 25)
Group control: 1 remote controller controls up to 16 indoor units. (All indoor units operate according to
the remote controller) (Refer to Fig. 27)
2 remote controllers control: 2 remote controllers control 1 indoor unit. (Refer to Fig. 28)

Pair type
Main power supply
Main switch
Fuse
Outdoor unit
1 2 3

1 2 3
P1 P2

Indoor unit
P1 P2

Remote controller
(Optional accessories)

Fig. 25

Group control

2 remote controllers control

Main power supply

Main power supply

Main power supply

Main power supply

Main switch
Fuse

Main switch
Fuse

Main switch
Fuse

Main switch
Fuse

Outdoor unit

Outdoor unit

Outdoor unit

Outdoor unit

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3
P1 P2

1 2 3
P1 P2

Indoor unit

Indoor unit
P1 P2

Remote controller
(Optional accessories)

Fig. 27

1 2 3
P1 P2

Indoor unit

P1 P2

Indoor unit
Remote
controller 1 P P
(Optional
accessories)
1

P1 P2

Fig. 28

Remote
controller 2
(Optional
accessories)

NOTE
1. All transmission wiring except for the remote controller wires is polarized and must match the terminal
symbol.
2. In case a shielding wire is to be used, connect a shielded portion with the
of a remote controller terminal board.(Also, connect the ground for the remote control to a grounded metal part.)
3. For group control remote controller, choose the remote controller that suits the indoor unit which has the
most functions (as attached swing flap)

14

English
C : 3P184443-4D

156

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

9. ELECTRIC WIRING WORK

All field supplied parts and materials and electric works must conform to local codes.
Use copper wire only.
For electric wiring work, refer to also Wiring diagram label attached to the Control box lid.
For remote controller wiring details, refer to the installation manual attached to the remote controller.
All wiring must be performed by an authorized electrician.
A circuit breaker capable of shutting down power supply to the entire system must be installed.
Refer to the installation manual attached to the outdoor unit for the size of power supply electric wire connected to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
Be sure to ground the air conditioner.
Do not connect the ground wire to gas and water pipes, lightning rods, or telephone ground wires.
Gas pipes : might cause explosions or fire if gas leaks.
Water pipes : no grounding effect if hard vinyl piping is used.
Telephone ground wires or lightning rods : might cause abnormally high electric potential in the ground
during lighting storms.

Specifications for field wire


The remote controller cord should be procured locally. Refer to the Table 4 when preparing one.
Table 4
Wire
Wiring between units

Size(mm2)

Length(m)

2.5

0.75-1.25

Max.500 *

2.0

H05VV-U4G(NOTE 1)

Remote controller cord

Vinyl cord with sheath or cable (2 wire) (NOTE 2)

Wiring to ground terminal

Ground wire conform to local codes

*This will be the total extended length in the system when doing group control.
NOTE
1. Shows only in case of protected pipes. Use H07RN-F in case of no protection.
2. Asian market : Vinyl cord with sheath or cable (Insulated thickness : 1mm or more)
For Australian regular : Shield wire (Insulated thickness : 1mm or more)
CAUTION
Arrange the wires and fix a lid firmly so that the lid does not float during wiring work.
Do not clamp remote controller cords together with wiring between units together. Doing so may cause
malfunction.
Remote controller cords and wiring between units should be located at least 50 mm from other electric
wires. Not following this guideline may result in malfunction due to electrical noise.
Connection of wiring between units, ground wire and for the remote control cord (Refer to Fig. 29)
Wiring between units and ground wire
Remove the control box lid and connect wires of matching number to the power supply terminal block
(4P)inside. And connect the ground wire to the terminal block. In doing this, pull the wires inside through
the hole and fix the wires securely with the included clamp (4).
Give enough slack to the wires between the clamp (4) and power supply terminal block. (Use Fig. 30 as a
guide and allow at least 80mm for removing the sheath.)
Remove the control box lid and pull the wires inside through the hole and connect to the terminal block for
remote controller (6P). (no polarity) Securely fix the remote controller cord with the included clamp (4).
Give enough slack to the wires between the clamp (4) and the terminal block for the remote controller.
After connection, attach sealing material (12)
Be sure to attach it to prevent the infiltration of water as well as any insects and other small creatures from
the outside. Otherwise a short circuit may occur inside the control box.

English

15
3P184443-4D

Installation of Indoor / Outdoor Unit

157

Installation of Indoor Unit

EDSG281001

Wiring Remote controller cord

Remote controller cord

Ground the shield part of shielded wire.


Refer to Note 2 in "8. WIRING EXAMPLE"

Note

Terminal block for


remote controller (6P)
15
10~
mm

control box lid

After clamping
Clamp(4)(small)
(accessory)
to wire sheath,
Clamp(4)
clamp the wire
(accessory) sheath with
(Big)
Clamp(4) Clamp(4)(Big)
(Small)
to clamp
material.
Be sure to clamp
wire sheath.
After securing the
Clamp
clamp (4) to clamp
material
material, cut off
any extra material

Wiring diagram label


(Back side of control box lid)

Remove the
control box lid
(take off 2
screws)

Wiring between units


Outdoor
unit

Note

Indoor
unit

(Wiring between units)


How to connect power
supply terminal block
(4P) with ground wire

10~15mm

Wiring between
units
Clamp(4)
(Big)

Power supply
terminal block

(accessory) Be sure to clamp

Clamp
material

wire sheath.
After securing the
clamp (4) to clamp material,
cut off any extra material

Fig. 29

Note)
Be sure to attach it to prevent the infiltration of water
as well as any insects and other small creatures from
the outside. Otherwise a short circuit may occur
inside the control box.
(accessory)
Sealing material (12)

Sealing
material(12)

Attach completely to
hole of wiring without
leaving any space

(accessory)

Wiring

(Outside)

Wiring to
outside

(Inside)

[How to attach sealing materials]

Observe the notes mentioned below when wiring to the power supply terminal block.
Tightening torque for the terminal blocks.
Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the
head of the screw might be damaged, and the screw will not be properly tightened.
If the terminal screws are tightened too hard, screws might be damaged.
Refer to the table below for the tightening torque of the terminal screws.
Terminal block for remote controller (6P)
Power supply terminal block (4P)

16

Tightening torque (Nm)


0.79 - 0.97
1.18 - 1.44

English
3P184443-4D

158

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Precautions to be taken for power supply wiring


Use a round crimp-style terminal for connection to the power supply terminal block. In case it cannot be
used due to unavoidable reasons, be sure to observe the following instructions.
Be sure to peel off the sheath of wiring between units more than 80 mm.
(Refer to Fig. 30)
In wiring, make certain that prescribed wires are used, carry out complete connections, and fix the wires
so that external forces are not applied to the terminals.

Attach insulation sleeve


Round crimp-style terminal
Wiring between units
e

or

mm
80

Fig. 30

m
or

When none are available, follow the instructions below.


Do not connect wires of different gauge to the same power supply terminal.

Connect wires of the


same gauge to both
side.

Do not connect wires


of the same gauge to
one side.

Do not connect wires


of different gauges.

(Looseness in the connection may cause overheating.)


CAUTION
When clamping wiring, use the included clamping material to prevent outside pressure being exerted on the
wiring connections and clamp firmly. When doing the wiring, make sure the wiring is neat and does not
cause the control box lid to stick up, then close the cover firmly.
When attaching the control box lid, make sure you do not pinch any wires.
After all the wiring connections are done, fill in any gaps in the through holes with putty or insulation (procured locally) to prevent small animals and insects from entering the unit from outside. (If any do get in,
they could cause short circuits in the control box.)
Outside the machine, separate the weak wiring (remote controller cord) and strong wiring (interunit,
ground, and other power wiring) at least 50 mm so that they do not pass through the same place together.
Proximity may cause electrical interference, malfunctions, and breakage.

10. INSTALLATION OF THE DECORATION PANEL


Caution:
With a wireless remote controller, field setting and test operation cannot be performed without
attaching the decoration panel.
<Read 12. TEST OPERATION before making a test run without attaching the decorated panels.>
Refer to the installation manual attached to the decoration panel.
After installing the decoration panel, ensure that there is no space between the unit body and decoration panel.

English

17
3P184443-4D

Installation of Indoor / Outdoor Unit

159

Installation of Indoor Unit

EDSG281001

11. FIELD SETTINGS


CAUTION
When performing field setting or test operation without attaching the decoration panel, do not
touch the drain pump. This may cause electric shock.
(1) Make sure the control box lids are closed on the indoor and outdoor units.
(2) Field settings must be made from the remote controller and in accordance with installation conditions.
Setting can be made by changing the Mode No., FIRST CODE NO. and SECOND CODE NO..
The Field Settings included with the remote control lists the order of the settings and method of operation.

11-1 Setting air outlet direction


For changing air outlet direction (2 or 3 directions), refer to the optional installation manual of the sealing
member of air discharge outlet kit or the service manual.
(SECOND CODE NO. is factory set to 01 for air outlet in 4 directions.)

11-2 Setting for options


For settings for options, see the installation instructions provided with the option.

11-3 Setting air filter sign


Remote controllers are equiped with liquid crystal display air filer signs to display the time to clean air filters.
Change the SECOND CODE NO. according to Table 5 depending on the amount of dirt or dust in the
room.
(SECOND CODE NO. is factory set to 01 for air filter contamination-light.)
Table5
Setting
Air filter contamination-light
Air filter contamination-heavy

Spacing time of display air


filter sign (long life type)
Approx. 2500 hrs
Approx. 1250 hrs

Mode No.

FIRST CODE
NO.

10 (20)

SECOND
CODE NO.
01
02

When using wireless remote controllers


When using wireless remote controllers, wireless remote controller address setting is necessary. Refer to
the installation manual attached to the wireless remote controller for setting instructions.

11-4 When implementing group control


When using as a pair unit, you may control up to 16 unit with the remote controller.
In this case, all the indoor units in the group will operate in accordance with the group control remote controller.
Select a remote controller which matches as many of the functions (swing flap, etc) in the group as possible.
Outdoor unit 1
Indoor unit 1

Outdoor unit 2

Indoor unit 2

Outdoor unit 3

Indoor unit 3

Group control remote controller

Wiring Method (See 9. ELECTRIC WIRING WORK on page 15.)


(1) Remove the control box lid.
(2) Cross-wire the remote control terminal block (P1 P2) inside the control box. (There is no polarity.)
(Refer to Fig. 27 on page 14 and Table 4 on page 15)

11-5 Two remote Controllers (Controlling 1 indoor unit by 2 remote controllers)


When using 2 remote controllers, one must be set to MAIN and the other to SUB.
18

English
3P184443-4D

160

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

MAIN/SUB CHANGEOVER
(1) Insert a
screwdriver into the recess between the upper and lower part of remote controller and, working from the 2 positions, pry off the upper part. (The remote controller PC board is attached to the upper
part of remote controller.) (Refer to Fig. 31)
(2) Turn the main/sub changeover switch on one of the two remote controller PC boards to S. (Leave the
switch of the other remote controller set to M.) (Refer to Fig. 32)
Fig. 31

Upper part of
remote controller

Insert the screwdriver


here and gently work
off the upper part of
remote controller.

Fig. 32

Lower part of
remote controller

(Factory setting)

S
M

(Only one remote


controller needs S
to be changed if M
factory settings
have remained
untouched.)

Remote
controller
PC board

Wiring Method (See 9. ELECTRIC WIRING WORK on page15. )


(3) Remove the control box lid.
(4) Add remote controller 2 to the remote control terminal block (P1, P2) in the control box.
(There is no polarity.) (Refer to Fig. 28 on page 14 and Table 4 on page 15)

12. TEST OPERATION


CAUTION
When performing field setting or test operation without attaching the decoration panel, do not
touch the drain pump. This may cause electric shock.
Refer to the section of FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED on page 4.
After finishing the construction of refrigerant piping, drain piping, and electric wiring, conduct test operation accordingly to protect the unit.

12-1 HOW TO TEST OPERATION


1. Open the gas side stop valve.
2. Open the liquid side stop valve.
3. Electrify for 6 hours.
4. Set to cooling operation with the remote controller and start operation by pressing ON/OFF button (
).
5. Press INSPECTION/TEST OPERATION button (
) 4 times (2 times for wireless remote controller) and
operate at Test Operation mode for 3 minutes.
6. Press AIR FLOW DIRECTION ADJUST button (
) to make sure the unit is in operation.
7. Press INSPECTION/TEST OPERATION button (
) and operate normally.
8. Confirm function of unit according to the operation manual.
9. If the decoration panel has not been installed, turn off the power after the test operation.
PRECAUTIONS
1. Refer to 12-2 HOW TO DIAGNOSE FOR MALFUNCTION if the unit does not operate properly.
2. After completing the test run, press the INSPECTION/TEST OPERATION button once to put the unit in
inspection mode, and make sure the malfunction code is 00. (=normal)
If the code reads anything other than 00, refer to 12-2 HOW TO DIAGNOSE FOR MALFUNCTION.
NOTE
If a malfunction is preventing operation, refer to the malfunction diagnoses below.
English

19
3P184443-4D

Installation of Indoor / Outdoor Unit

161

Installation of Indoor Unit

EDSG281001

12-2 HOW TO DIAGNOSE FOR MALFUNCTION


If the air conditioner does not operate normally after installing the air conditioner, a malfunction shown in
the table below may happen.
Remote control display

No display

88*
88 flashing

Malfunction
Power supply trouble or Open phase connection
Wrong wiring between indoor and outdoor unit
Indoor PC board faulty
Power supply PCB assy faulty
Wrong remote control connection wiring
Remote control faulty
Fuse faulty
Indoor PC board faulty
Wrong wiring between indoor and outdoor unit
Wrong wiring between indoor and outdoor unit

*After turning on the power, the maximun is 90 seconds, although it will only display 88. This is not a problem, and it will be set for 90 seconds.
Diagnose with the display on the liquid crystal display remote controller.
1. With the wired remote controller. (Note 1)
When the operation stops due to trouble, operation lamp flashes, and
and the malfunction code
are indicated on the liquid crystal display. In such a case, diagnose the fault contents by referring to the
table on the malfunction code list in case of group control, the unit No. is displayed so that the indoor unit
No. with the trouble can be recognized. (Note 2)
2. With the wireless remote controller.
(Refer also to the operation manual attached to the wireless remote controller)
When the operation stops due to trouble. the display on the indoor unit flashes. In such a case, diagnose
the fault contents with the table on the Error code list looking for the error code which can be found by following procedures. (NOTE 2)
(1)Press the INSPECTION /TEST OPERATION button,
is displayed and 0 flashes.
(2)Press the PROGRAMMING TIME button and find the unit No. which stopped due to trouble.
Number of beeps 3 short beeps ............................. Perform all the following operations
1 short beep............................... Perform (3) and (6)
1 long beep ................................ No trouble
(3)Press the OPERATION MODE SELECTOR button and upper figure of the error code flashes.
(4)Continue pressing the PROGRAMMING TIME button unit it makes 2 short beeps and find the upper code.
(5)Press the OPERATION MODE SELECTOR button and lower figure of the error code flashes.
(6)Continue pressing the PROGRAMMING TIME button unit it makes a long beep and find the lower code.
A long beep indicate the error code.
NOTE
1.In case wired remote controller. Press the INSPECTION/TEST OPERATION button on remote controller,

starts flashing and changes the inspection mode.


2.Keep down the ON/OFF button for 5 seconds or longer in the inspection mode and the above trouble
history disappears, after the trouble code goes on and off twice, followed by the code 00(normal).
The display changes from the inspection mode to the normal mode.
Caution:
Check the items in b. Items to be checked at time of delivery on page 4 after a test operation.
12-3 Malfunction code list
For places where the Malfunction code is left blank, the
indication is not displayed. Though the system continues operating, be sure to inspect the system and make repairs as necessary.
Depending on the type of indoor or outdoor unit, the Malfunction code may or may not be displayed.
Code
A0
A1
A3
A6
AF
20

Malfunction/Remarks
Safety device operates
Indoor units PC board faulty
Drain water level abnormal
Indoor fan motor overloaded, overcurrent or locked
Humidifier faulty
English
3P184443-4D

162

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

AH
AJ
C4
C9
CC
CJ
E0
E1
E3
E4
E5
E7
E9
F3
H3
H4
H7
H9
JA
JC
J1
J2
J3
J5
J6
J7
J8
J9
L1
L4
L5
L8
L9
LC

Air cleaner faulty


Only the air cleaner does not function.
Type set improper
Capacity data is wrongly preset. Or there is nothing programmed in the data hold IC.
Sensor for heat exchanger temperature is fault
Sensor for suction air temperature is fault
Humidity sensor abnormal
Sensor for remote controller is fault
The remote controller thermistor does not function, but the system thermo run is
possible.
Action of safety device (outdoor unit)
Outdoor units PC board faulty
High pressure abnormal (outdoor unit)
Low pressure abnormal (outdoor unit)
Compressor motor lock malfunction
Outdoor fan motor lock malfunction
Outdoor fan instantaneous overcurrent malfunction
Electronic expansion valve faulty (outdoor unit)
Discharge pipe temperature abnormal (outdoor unit)
High pressure switch faulty (outdoor unit)
Low pressure switch faulty (outdoor unit)
Outdoor motor position signal malfunction
Outdoor air thermistor faulty (outdoor unit)
Equipment operation in response to errors will vary according to model.
Discharge pipe pressure sensor faulty
Suction pipe pressure sensor faulty
Pressure sensor system error (batch) (outdoor unit)
Power sensor system error (outdoor unit)
Discharge pipe thermistor faulty (outdoor unit)
Equipment operation in response to errors will vary according to model.
Suction pipe thermistor faulty (outdoor unit)
Heat exchanger thermistor faulty (outdoor unit)
Equipment operation in response to errors will vary according to model.
Heat exchanger thermistor faulty (outdoor unit)
Equipment operation in response to errors will vary according to model.
Liquid piping temperature sensor system error (outdoor unit)
Intake temperature sensor error (outdoor unit)
Inverter system error (outdoor unit)
Overheated heat-radiating fin (outdoor unit)
Inverter cooling defect.
Instantaneous overcurrent (outdoor unit)
Possible earth fault or short circuit in the compressor motor.
Electric thermal (outdoor unit)
Possible electrical overload in the compressor or cut line in the compressor motor.
Stall prevention (outdoor unit)
Compressor possibly locked.
Transmission malfunction between the outdoor control units inverters (outdoor unit)

English

21
3P184443-4D

Installation of Indoor / Outdoor Unit

163

Installation of Indoor Unit

P1
P3
P4
PJ
U0
U1
U2
U4
UF
U5
U8
UA
UC
UJ

22

EDSG281001

Open-phase (outdoor unit)


P-board temperature sensor malfunction (outdoor unit)
Heat-radiating fin temperature sensor malfunction (outdoor unit)
Type set improper (outdoor unit)
Capacity data is wrongly preset. Or there is nothing programmed in the data hold IC.
Suction pipe temperature abnormal
Reverse phase
Reverse two phase of the L1,L2and L3 leads.
Power source voltage malfunction (outdoor unit)
Includes the defect in 52C.
Transmission error (indoor unit outdoor unit)
Wrong wiring between indoor and outdoor units or malfunction of the PC board
mounted on the indoor and the outdoor units.
Transmission error (indoor unit remote controller)
Transmission is improper between the indoor unit and the remote controller.
Malfunction in transmission between main and sub remote controls.
(Malfunction in sub remote controller.)
Miss setting for multi system
Setting is wrong for selector switch of multi-system. (see switch SS2 on the main
units PC board)
Central control address overlapping
Peripheral equipment transmission fault

English
3P184443-4D

164

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

2.3

FHQ35BVV1B / FHQ50BVV1B / FHQ60BVV1B / FHQ71BVV1B / FHQ100BVV1B


/ FHQ125BVV1B

2.3.1

Names and Functions of Parts

2
f

e
i
g
h

d
j

b
d
c

e
f

k
a

c
d
e
f
g
h
i
j
k

Indoor unit
Outdoor unit
The external appearance of the outdoor unit varies
depending on its capacity class.
The outdoor unit shown in the figure is for reference to indicate features.
Contact your Daikin Dealer and verify which outdoor unit you have.
Remote controller
Inlet air
Discharged air
Air outlet
Air flow flap (at air outlet)
Refrigerant piping, connection electric wire
Drain pipe
Suction grille
The built-in air filter removes dust and dirt.
Ground wire
Wire to ground from the outdoor unit to prevent electrical shocks.
3PN07753-3E
3PN07753-4E

Installation of Indoor / Outdoor Unit

165

Installation of Indoor Unit

2.3.2

EDSG281001

Installation
FHQ35BVV1B
FHQ50BVV1B
FHQ60BVV1B
FHQ71BVV1B
FHQ100BVV1B
FHQ125BVV1B

SPLIT SYSTEM
Air Conditioner
Installation manual

CONTENTS
1. SAFETY PRECAUTIONS...............................................................................................1
2. BEFORE INSTALLATION ..............................................................................................3
3. SELECTING INSTALLATION SITE................................................................................5
4. PREPARATIONS BEFORE INSTALLATION .................................................................6
5. INDOOR UNIT INSTALLATION .....................................................................................8
6. REFRIGERANT PIPING WORK ....................................................................................9
7. DRAIN PIPING WORK .................................................................................................13
8. WIRING EXAMPLE ......................................................................................................15
9. ELECTRIC WIRING WORK .........................................................................................16
10. FIELD SETTINGS ........................................................................................................19
11. TEST OPERATION ......................................................................................................21

1. SAFETY PRECAUTIONS
Please read these SAFETY PRECAUTIONS carefully before installing air conditioning equipment and be
sure to install it correctly.
After completing installation, conduct a trial operation to check for faults and explain to the customer how to
operate the air conditioner and take care of it with the aid of the operation manual. Ask the customer to store
the installation manual along with the operation manual for future reference.
This air conditioner comes under the term appliances not accesible to the general public.
Meaning of WARNING and CAUTION notices.
WARNING .........Failure to follow these instructions properly may result in personal injury or loss of life.
CAUTION ..........Failure to observe these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances.

WARNING
Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage,
electric shocks or fire.
Install the air conditioner in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shocks or fire.
Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.

English

1
C : 3PN06588-3H

166

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
A foundation of insufficient strength may result in the equipment falling and causing injury.
Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit falling and causing accidents.
Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried
out by qualified personnel according to local laws and regulations and this installation manual.
An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.
Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal
connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or fire.
When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the
wires so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric shocks, fire or overheating terminals.
If refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into contact with fire.
After completing installation, check for refrigerant gas leakage.
Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source
of fire, such as a fan heater, stove or cooker.
Be sure to switch off the unit before touching any electrical parts.
Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead.
Imperfect earthing may result in electric shocks or fire.
A high surge current from lightning or other sources may cause damage to the air conditioner.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks or fire.

CAUTION
While following the instructions in this installation manual, install drain piping to ensure proper drainage and
insulate piping to prevent condensation.
Improper drain piping may result in indoor water leakage and property damage.
Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televisions
or radios to prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 1 meter may not be sufficient to eliminate noise.)
Remote controller (wireless kit) transmitting distance can be shorter than expected in rooms with electronic
fluorescent lamps (inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as possible.
Do not install the air conditioner in the following locations:
1. Where there is a high concentration of mineral oil spray or vapour (e.g. a kitchen).
Plastic parts will deteriorate, parts may fall off and water leakage could result.
2. Where corrosive gas, such as sulphurous acid gas, is produced.
Corroding of copper pipes or soldered parts may result in refrigerant leakage.
3. Near machinery emitting electromagnetic radiation.
Electromagnetic radiation may disturb the operation of the control system and result in a malfunction of
the unit.
4. Where flammable gas may leak, where there is carbon fibre or ignitable dust suspensions in the air, or
where volatile flammables such as paint thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.
The air conditioner is not intended for use in a potentially explosive atmosphere.

English

3PN06588-3H

Installation of Indoor / Outdoor Unit

167

Installation of Indoor Unit

EDSG281001

2. BEFORE INSTALLATION
When moving the unit while removing it from the carton box, be sure to lift it by holding on to the
four lifting lugs without exerting any pressure on other parts, especially swing flap, the refrigerant
piping, drain piping, and other resin parts.
Be sure to check the type of refrigerant to be used before installing the unit. (Using an incorrect refrigerant
will prevent normal operation of the unit.)
The accessories needed for installation must be retained in your custody until the installation work is completed. Do not discard them!
Decide upon a line of transport.
Leave the unit inside its packaging while moving, until reaching the installation site. Where unpacking is
unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid damage or scratches to the unit.
When selecting installation site, refer to the paper pattern.
For the installation of an outdoor unit, refer to the installation manual attached to the outdoor unit.
Do not use the unit in locations with high salt content in the air such as beachfront property, locations where
the voltage fluctuates such as factories, or in automobiles or marine vessels.

2-1 ACCESSORIES
Check the following accessories are included with your unit.
Name

1) Drain hose

2) Clamp

3) Washer for
hanger bracket

4) Clamp

5) Paper pattern
for installation

Quantity

1 pc.

1 pc.

8 pcs.

6 pcs.

1 pc.

Shape

Name Insulation for fitting


Quan1 each.
tity
6) For gas pipe
Shape

Sealing pad
1 each.
(Other)
8) Large
Operation manual
Installation manual

7) For liquid pipe

9) Small

2-2 OPTIONAL ACCESSORIES


The remote controller are required for this indoor unit Table 1 on page 3.
(However, the remote controller is not required for the slave unit of a simultaneous operation system.)
These are two types of remote controllers: wired and wireless. Select a remote controller from
Table 1 on page 3 according to customer request and install in an appropriate place.
Table 1
Remote controller type
Wired type
Wireless type

English

Cooling only type


Heat pump type
BRC1C517, BRC1D527, BRC1D528, BRC1C61
BRC7E66, BRC7EA66
BRC7E63W, BRC7EA63W

3
3PN06588-3H

168

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

NOTE
If you wish to use a remote controller that is not listed in Table 1 on page 3, select a suitable remote controller after consulting catalogs and technical materials.

FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND
CHECK AFTER INSTALLATION IS FINISHED.

a. Items to be checked after completion of work


Items to be checked
Are the indoor and outdoor unit fixed firmly?
Is the gas leak test finished?
Is the unit fully insulated?
Does drainage flow smoothly?
Does the power supply voltage correspond
to that shown on the name plate?
Are wiring and piping correct?
Is the unit safely grounded?
Is wiring size according to specifications?
Is something blocking the air outlet or inlet
of either the indoor or outdoor units?
Are refrigerant piping length and additional
refrigerant charge noted down?

If not properly done, what is likely to occur


The units may drop, vibrate or make noise.
It may result in insufficient cooling.
Condensate water may drip.
Condensate water may drip.
The unit may malfunction or the components burn out.
The unit may malfunction or the components burn out.
Dangerous at electric leakage.
The unit may malfunction or the components burn out.

Check

It may result in insufficient cooling.


The refrigerant charge in the system is not
clear.

b. Items to be checked at time of delivery


Also review the SAFETY PRECAUTIONS
Items to be checked

Check

Did you explain about operations while showing the instruction manual to your customer?
Did you hand the instruction manual over to your customer?
c. Points for explanation about operations
The items with
WARNING and
CAUTION marks in the instruction manual are the items pertaining
to possibillties for bodily injury and material damage in addition to the general usage of the product.
Accordingly, it is necessary that you make a full explanation about the described contents and also ask
your customers to read the instruction manual.

2-3 NOTE TO THE INSTALLER


Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating different
functions, and adjusting the temperature) by having them carry out operations themselves while looking at the
manual.

English
3PN06588-3H

Installation of Indoor / Outdoor Unit

169

Installation of Indoor Unit

EDSG281001

3. SELECTING INSTALLATION SITE

30

30

Air outlet
Required service
space

Air inlet

Obstruction
Floor

300

(1) Select an installation site where the following conditions are fulfilled and that meets your customers approval.
Where optimum air distribution can be ensured.
Where nothing blocks air passage.
Where condensate can be properly drained.
Where the ceiling is strong enough to bear the indoor unit weight.
Where the false ceiling is not noticeably on an incline.
Where there is no risk of flammable gas leakage.
Where sufficient clearance for maintenance and service can be ensured.
NOTE
If there is space left over in the section, opening it up 200 mm will make servicing easier.

2500 or higher
from the floor
For installation
in high places
(Length : mm)

Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the installation manual for the outdoor unit.)
Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the
noise.)
(2) Use suspension bolts for installation. Check whether the ceiling is strong enough to support the
weight of the unit or not. If there is a risk, reinforce the ceiling before installing the unit.
(Installation pitch is marked on the paper pattern for installation. Refer to it to check for points requiring
reinforcing.)
(3) This product may be installed on ceilings up to 3.5 m in height. However, if the ceiling is higher
than 2.7 m, the remote control will have to be set locally. (Refer to 10. FIELD SETTINGS on page
19)

English

5
3PN06588-3H

170

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

4. PREPARATIONS BEFORE INSTALLATION


(1) Relation of holes for indoor unit, suspension bolt position, piping and wiring.

A
B

Left side piping hole

85
160
185

210
680

Front view

False ceiling view

260

160

135

C
D
E

Top side drain


piping hole

Rear side piping hole

Air outlet

Top gas piping hole


Suspension
bolt (4)
Top liquid piping hole
(Length : mm)

Model
Type 35, 45, 50
Type 60, 71
Type 100
Type 125

A
960
1160
1400
1590

B
920
1120
1360
1550

C
390
490
610
705

D
375
475
595
690

E
310
410
530
625

F
400
500
620
715

G
375
475
595
690

(2) Make holes for suspension bolts, refrigerant and drain piping, and wiring.
Refer to the paper pattern for installation.
Select the location for each of holes and open the holes in the ceiling.
(3) Remove the parts from the indoor unit.
(3-1)Detach the suction grille.
Slide the locking knobs (2) on the suction grille inward (direction of arrows) and lift upwards.
(Refer to Fig. 1)
With the suction grille open, remove the suction grille forward, holding on to the rear tabs on the suction
grille. (Refer to Fig. 2)
Fig. 1

(3-2)Remove the dressing boards (left and right).


After removing the securing screws for the
dressing boards (one each), pull them forward
(in the direction of the arrow) and remove
them. (Refer to Fig. 3)
Take out the accessories.

Fig. 2

Fig. 3

Accessories

Dressing board securing


screw (M4)

Dressing board
6

English
3PN06588-3H

Installation of Indoor / Outdoor Unit

171

Installation of Indoor Unit

EDSG281001

(3-3)Remove the hanger brackets.


Loosen the 2 bolts (M8) used to attach the hanger brackets which are on each side (4 places left and
right) to within 10 mm. (Refer to Fig. 4. 5)
After removing the securing screws (M5) for the hanger brackets which are on the rear side, pull the
hanger brackets back (in the direction of the arrow), and remove them. (Refer to Fig. 5)
Fig. 4

Fig. 5

Hanger bracket
fixing screw (M5)

Length of loosening
should be less than
10 mm
10

Indoor unit
Hanger bracket
setting bolt (M8)
Hanger bracket

Hanger bracket

(4) Attach the suspension bolts. (Use suspension bolts which are W3/8 or M8-M10 in size.)
Adjust the distance of the suspension bolts from the ceiling in advance. (Refer to Fig. 6)
NOTE
Use a hole-in anchor for existing ceilings, and a sunken insert, sunken anchor or other field supplied parts
for new ceilings to reinforce the ceiling to bear the weight of the unit. Adjust clearance from the ceiling
before proceeding further.
Fig. 6

Ceiling slab

25-55

Anchor
Suspension bolt
False ceiling

(Length : mm)

All the above parts are field supplied.

English

7
3PN06588-3H

172

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

5. INDOOR UNIT INSTALLATION


It may be easier to attach accessory parts before installing the indoor unit. Therefore, please also
read the instruction manuals which are provided with the accessory parts.
As for the parts to be used for installation work, be sure to use the provided accessories and specified parts
designated by our company.

(1) Secure the hanger brackets to the suspension bolts. (Refer to Fig. 7)
NOTE
To ensure they are safely secured, use the included washers, and secure them with double nuts to make sure.
(2) Lift the indoor units main body, insert the bolts (M8) for the hanger brackets into the attachment
part on the hanger brackets, while sliding the main body from the front. (Refer to Fig. 8)
(3) Fasten the bolts for the hanger brackets (M8) securely in 4 places, left and right. (Refer to Fig. 8)
(4) Replace the screws for the hanger brackets which had been removed (M5) securely in 2 places left
and right. This is necessary to prevent any forward and back slide in the main body of the indoor
unit. (Refer to Fig. 8)
Fig. 7

Fig. 8

Hanger bracket

Nut (Field supplied)


Washer (3) (attached)
Attachment
part
Hanger bracket
setting bolt (M8)

Double nuts (Field supplied)


Hanger bracket

Hanger bracket
fixing screw (M5)

(5) When hanging the indoor unit main body, be sure to use a level or a plastic tube with water in it to
make sure the drain piping is set either level or slightly tilted, in order to ensure proper drainage.
(Refer to Fig. 9)
Fig. 9

A.B
1

B
1

A.When the drain piping is tilted to the right, or to the right and back.
Place it level, or tilt it slightly to the right or the back. (Within 1.)
B.When the drain piping is tilted to the left, or to the left and back.
Place it level, or tilt it slightly to the left or the back. (Within 1.)
CAUTION
Setting the unit at an angle opposite to the drain piping might cause a water leakage.

English
3PN06588-3H

Installation of Indoor / Outdoor Unit

173

Installation of Indoor Unit

EDSG281001

6. REFRIGERANT PIPING WORK


For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.
Execute heat insulation work completely on both sides of the gas piping and the liquid piping.
Otherwise, a water leakage can result sometimes.
(When using a heat pump, the temperature of the gas piping can reach up to approximately 120C, so use
insulation which is sufficiently resistant.)
Also, in cases where the temperature and humidity of the refrigerant piping sections might exceed
30C or RH80 %, reinforce the refrigerant insulation. (20 mm or thicker) Condensation may form on the
surface of the insulating material.
Before refrigerant piping work, check which type of refrigerant is used. Proper operation is not possible if the types of refrigerant are not the same.
CAUTION
Use a pipe cutter and flare suitable for the type of refrigerant.
Apply ester oil or ether oil around the flare section before connecting.
To prevent dust, moisuture or other foreign matter from infiltrating the tube, either pinch the end
or cover it with tape.
Do not allow anything other than the designated refrigerant to get mixed into the refrigerant
circuit, such as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room
thoroughly right away.
The outdoor unit is charged with refrigerant.
Use copper alloy seamless pipes (ISO 1337).
Be sure to use both a spanner and torque wrench together, as
shown in the drawing, when connecting or disconnecting pipes
to/from the unit. (Refer to Fig. 10)
Refer to Table 2 for the dimensions of flare nut spaces.
When connecting the flare nut, coat the flare section (only
inside) with ester oil or ether oil, rotate three or four times first,
then screw in. (Refer to Fig. 11)

Fig. 10

Torque wrench
Piping union
Flare nut
Spanner

NOTE
Use the flare nut included with the unit main body.

Fig. 11

CAUTION
Do not let oil get on the screw holders on the dressing board.
Oil can weaken the screw holders.

Coat the flare section (only inside)


with ester oil or ether oil.

Table 2
Flare dimensions A (mm)
R410A

14.2-17.2 N m

8.7 9.1

6.4(1/4)

Pipe size Tightening torque

Flare
FHQ

45 2

Type of refrigerant
Applicable model

32.7-39.9 N m

12.8 13.2

49.5-60.3 N m

16.2 16.6

15.9(5/8)

61.8-75.4 N m

19.3 19.7

19.1(3/4)

97.2-118.8 N m

R0.4-0.8
A

90 0.5

9.5(3/8)
12.7(1/2)

Refer to Table 2 to determine the proper tightening torque.


CAUTION
Overtightening may damage the flare and cause a refrigerant leakage.

English

9
C : 3PN06588-3H

174

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Not recommendable but in case of emergency


You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may
follow the installation method mentioned below.

After the work is finished, make sure to check that there is no gas leak.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque
suddenly increases. From that position, further tighten the flare nut the angle shown below:
Pipe size
6.4 (1/4)
9.5 (3/8)
12.7 (1/2)
15.9 (5/8)
19.1 (3/4)

Further tightening angle


60 to 90 degrees
60 to 90 degrees
30 to 60 degrees
30 to 60 degrees
20 to 35 degrees

Recommended arm length of tool


Approx. 150mm
Approx. 200mm
Approx. 250mm
Approx. 300mm
Approx. 450mm

CAUTION
CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING
Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filler metal
(BCuP-2: JIS Z 3264/B-Cu93P-710/795: ISO 3677) which does not require flux.
(Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is
used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil.)
Before brazing local refrigerant piping, nitrogen gas shall be blown through the piping to expel air from the
piping.
If you brazing is done without nitrogen gas blowing, a large amount of oxide film develops inside the piping,
and could cause system malfunction.
When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution or
while inserting nitrogen into the refrigerant piping. Once this is done, connect the indoor unit with a flared
or a flanged connection.
Nitrogen should be set to 0.02 MPa with a pressure-reducing valve if brazing while inserting nitrogen into
the piping. (Refer to Fig. 12)

Pressure-reducing valve
Refrigerant piping
Part to be
brazed

Taping
hands valve

Nitrogen

Nitrogen
Fig. 12

10

English
3PN06588-3H

Installation of Indoor / Outdoor Unit

175

Installation of Indoor Unit

EDSG281001

Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas
leakage by thoroughly studying the following figure and using the attached heat insulating materials for fitting (6) and (7). (Fasten both ends with the clamps (4).)
(Refer to Fig. 13)
Wrap the sealing pad (9) only around the insulation for the joints on the gas piping side.
(Refer to Fig. 13)
CAUTION
Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.
Fig. 13

Procedure for thermal insulation of gas-side piping


Insulating material for joints (6)
(accessory)
Piping insulation
Flare nut connection
material
(main unit)
Orient so that the end of
the wrapped insulation
Attach to base
material is facing up

Wind around the


pipe, beginning at
the base.
Small seal material
(9) (accessory)

Main unit
Piping insulation material
(Locally procured)

Clamp (4)
(accessory)

Insulation for gas pipe (6) (attached)


Gas piping
Liquid piping
Insulation for liquid pipe (7) (attached)
Clamp (4) (attached) ( 4)
Attach to the bottom
(For both gas piping and liquid piping)
Procedure for thermal insulation of liquid-side piping
Insulating material for
joints (7)(accessory)
Flare nut connection
Orient so that the end of
the wrapped insulation
material is facing up

Piping insulation material (main unit)


Attach to base
Main unit

Piping insulation material


(Locally procured)

English

Clamp (4) (accessory)

11
3PN06588-3H

176

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

(1) For piping facing back.


Remove the rear penetration lid and set the piping. (Refer to Fig. 14.16)
(2) For piping facing up.
When setting the piping to face up, the L-shaped branch piping kit sold separately is required.
Removing the top penetration lid and use the L-shaped branch piping kit sold separately to set the piping.
(Refer to Fig. 14.15)

(3) For piping facing right.


Cut out a slit hole on the dressing board (right) and set the piping. (Refer to Fig. 16)
Fig. 14

Fig. 15

Top plate

Cut out

Upward-facing
refrigerant piping
L-shaped branch piping
kit (Optional accessories)

Rear
penetration lid
Top penetration lid

Cut out
Fig. 17
Fig. 16

Thermistor lead line

Right-facing
refrigerant
piping

Rear-facing
refrigerant piping

Top penetration
lid clamp section

Swing motor
lead line

Rear right-facing
drain piping
Right-facing drain piping
Dressing board (right)
removable part
If only setting the drain piping to
face right, cut this section only.
When piping is complete, cut the removed penetration lid into the shape of the piping using scissors and attach.
As when before removing the top penetration lid, secure the lead lines for the swing motor and thermistor
by passing them through the clamp section on the top penetration lid. (Refer to Fig. 14.17)
When doing this, block any gaps between the piping penetration lid and the pipes using putty to prevent
dust from entering the indoor unit.

12

English
3PN06588-3H

Installation of Indoor / Outdoor Unit

177

Installation of Indoor Unit

EDSG281001

7. DRAIN PIPING WORK


(1) Carry out the drain piping.
Make sure piping provides proper drainage.
You can select whether to bring the drain piping our from the rear right, right, rear left, or left. For rear rightfacing and right-facing situations, refer to 6. REFRIGERANT PIPING WORK on page 9 for rear left-facing
and left-facing situations. (Refer to Fig. 18)
Fig. 18

Rear side (metal plate)


removable part

Rear left-facing drain piping


Left dressing board removable part

Left-facing drain piping


When setting piping facing left, move the rubber stopper and insulation which are attached to the drain pipe
connection hole on the left side of the indoor unit to the right-side drain pipe connection hole.
When doing this, insert the rubber stopper all the way in to prevent a water leakage.
Make sure the pipe diameter is the same or bigger than the branch piping. (vinyl-chloride piping, nominal
diameter 20 mm, external diameter 26 mm)
Make sure the piping is short, has at least a 1/100 slope, and can prevent air pockets from forming.
(Refer to Fig. 19)
Fig. 19

Wrong

Good

Do not lift

Tilt down

Make sure there


is no slack
Make sure it is
not in the water

CAUTION
Water accumulating in the drain piping can cause the drain to clog.
Be sure to use the included drain hose (1) and clamp (2).
Also, insert the drain hose completely into the drain socket, and securely attach the clamp bracket inside
the gray tape area on the inserted tip of the drain hose. (Refer to Fig. 20)
Screw the screws on the clamp bracket until there is 4 mm left. (Pay attention to the direction of the attachment to prevent the clamp bracket from coming into contact with the suction grille.)
(Refer to Fig. 21)

English

13
3PN06588-3H

178

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Fig. 20

Fig. 22

Clamp (2) (attached)

Drain hose (1) (attached)

Taping area (Gray)

Clamp (2)
(attached)

Wrong

Fig. 21

Sealing pad (8)


(attached)

4
Sealing
pad (8)
(attached) Clamp (2)
(attached)

(Length : mm)

< Facing rear right or right >

< Facing rear left or left >

Insulate the clamp bracket and drain hose from the bottom using the included sealing pad (8).
(Refer to Fig. 21)
Be sure to insulate all drain piping running indoors.
Do not allow any slack to gather in the drain hose inside the indoor unit. (Refer to Fig. 22)
(Slack in the drain hose can cause the suction grille to break.)
(2) Check to make sure the drain flows smoothly after piping is complete.
Slowly pour 600 ml of drain-checking water into the drain pan through the air outlet.

Plastic container
for pouring

Air outlet

100 mm
or more

Make sure not to splash the water.

Set a downward slope of 1/100 or


greater to ensure that air does
not accumulate.

Central drain pipe

Water accumulating in the drain piping can


cause the drain to clog.
CAUTION
Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.

14

English
3PN06588-3H

Installation of Indoor / Outdoor Unit

179

Installation of Indoor Unit

EDSG281001

8. WIRING EXAMPLE
For the wiring of outdoor units, refer to the installation manual attached to the outdoor units.
Confirm the system type.
Pair or Multi system: 1 remote controller controls 1 indoor unit. (standard system) (Refer to Fig. 23)
Group control: 1 remote controller controls up to 16 indoor units. (All indoor units operate according to the
remote controller) (Refer to Fig. 25)
Two remote controllers control: 2 remote controllers control 1 indoor unit. (Refer to Fig. 26)
Fig. 23

Pair or Multi system


Main power supply
Main switch
Fuse
Outdoor unit
1 2 3

1 2 3
P1 P2

Indoor unit
P1 P2

Remote controller
(Optional accessories)

Fig. 25

Fig. 26

Group control

Two remote controllers control

Main power supply

Main power supply

Main power supply

Main switch
Fuse

Main switch
Fuse

Main switch
Fuse

Outdoor unit

Outdoor unit

Outdoor unit

Main power supply


Main switch
Fuse
Outdoor unit
1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3
P1 P2

P1 P2

Indoor unit

P1 P2

Indoor unit
P1 P2

P1 P2

Indoor unit

Remote controller (Optional accessories)

Indoor unit
P1 P 2

Remote
controller 1
(Optional
accessories)

English

P1 P2

Remote
controller 2
(Optional
accessories)

15
C : 3PN06588-3H

180

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

NOTE
1. All transmission wiring except for the remote controller wires is polarized and must match the terminal symbol.
2. In case of group control, perform the remote controller wiring to the master unit when connecting to the
simultaneous operation system. (wiring to the slave unit is unnecessary)
3. For group control remote controller, choose the remote controller that suits the indoor unit which has the
most functions (as attached swing flap)

9. ELECTRIC WIRING WORK

All field supplied parts and materials and electric works must conform to local codes.
Use copper wire only.
For electric wiring work, refer to also 8. WIRING EXAMPLE on page 15 attached to the unit body.
For remote controller wiring details, refer to the installation manual attached to the remote controller.
All wiring must be performed by an authorized electrician.
A circuit breaker capable of shutting down power supply to the entire system must be installed.
Refer to the installation manual attached to the outdoor unit for the size of power supply electric wire connected to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
Be sure to ground the air conditioner.
Do not connect the ground wire to gas pipes, water pipes, lightning rods, or telephone ground wires.
Gas pipes: might cause explosions or fire if gas leaks.
Water pipes: no grounding effect if hard vinyl piping is used.
Telephone ground wires or lightning rods: might cause abnormally high electric potential in the ground
during lighting storms.
Specifications for field wire
Table 3
Wire
Wiring between units
Remote controller cord

H05VV - U4G
(NOTE 1, 3)
Vinyl cord with sheath or cable
(2 wires) (NOTE 2)

Size (mm )

Length

2.5

0.75 - 1.25

Max. 500 m
(NOTE 3)

NOTE
1. Shows only in case of protected pipes. Use H07RN-F in case of no protection. (Sheath thickness: 1mm or more)
2. Use double insulated wire for remote controller (Sheath thickness: 1mm or more) or run wires through a
wall or conduit so that the user cannot come in contact with them.
3. This length shall be the total extended length in the system of the group control.
CAUTION
Even if the top or rear penetration lid is removed, pull the remote controller cord and the wiring between
units inside the unit using conduits for each, so that the wiring does not come into contact with the opening
section of the metal casing.
Pass conduits through the wall and secure along with the refrigerant piping in order to prevent external
pressure being applied to the remote controller cord and wiring between units.
Prevent dust from entering into the unit by filling the gap between the conduits and the penetration lid (top
or rear) with corking or putty.
Arrange the wires and fix a lid firmly so that the lid does not float during wiring work.
Do not clamp remote controller cord together with wiring between units together. Doing so may cause malfunction.
Remote controller cord and wiring between units should be located at least 50 mm from other electric wires.
Not following this guideline may result in malfunction due to electrical noise.

16

English
C : 3PN06588-3H

Installation of Indoor / Outdoor Unit

181

Installation of Indoor Unit

EDSG281001

Connection of wiring between units and for the remote control cord (Refer to Fig. 27)
Wiring between units
Holding the control box lid, loosen the two securing screws, remove the control box lid, match up the phases
on the power source terminal block inside (3P), and make the connections.
After this is done, use the attached clamp (4) to bind wiring between units to the anchor point.
(Refer to Fig. 28)
Remote controller cord: The simultaneous operation multi sub-unit is not required. (Refer to Fig. 27.29)
Connect to the remote control terminal block (2P). (There is no polarity.) After this is done, use the attached
clamp (4) to bind remote controller cord to the anchor point. (Refer to Fig. 28)
Attaching the suction grille and the dressing boards
Once wiring is complete, firmly attach the dressing side board by reversing the steps taken to remove the
suction grille.
Fig. 27

Remote control terminal block (2P)


Power supply terminal block (3P)
Control box
Ground terminal

Fig. 28
Conduits

Rear penetration lid


Seal with caulking
material or putty
Liquid pipe
Gas pipe
Drain hose

Remote controller cord

Control box lid fixation


screw
Clamp (4) (attached)
Fastener

Wiring between
units

Clamp (4)
(attached)
Fastener

English

Wiring between units (If wiring the slave


unit, connect to master unit)
How to connect power supply terminal
block (3P)
Fig. 29

After securing the


clamp material
to the bracket,
cut off any extra
material.
Remote controller cord

P1 P2

Fig. 28

Wiring between units

Remote control
terminal block (2P)
Remote controller cord

17
3PN06588-3H

182

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Observe the notes mentioned below when wiring to the terminals.


Tightening torque for the terminal screws.
Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the
head of the screw might be damaged, and the screw will not be properly tightened.
If the terminal screws are tightened too hard, screws might be damaged.
Refer to the table below for the tightening torque of the terminal screws.
Terminal
Remote controller terminal block (2P)
Power supply terminal block (3P)
Ground terminal

Size
M3.5
M4
M4

Tightening torque
0.79 - 0.97 Nm
1.18 - 1.44 Nm
1.18 - 1.44 Nm

Precautions to be taken for power supply wiring


Use a round crimp-style terminal for connection to the power supply terminal block.
In case it cannot be used due to unavoidable reasons, be sure to observe the following instructions.
(Refer to Fig. 30)
Do not connect wires of different gauge to the same power supply terminal. (Looseness in the connection
may cause overheating.) (Refer to Fig. 31)
When connecting wires of the same gauge, connect them according to. (Refer to Fig. 31)
In wiring, make certain that prescribed wires are used, carry out complete connections, and fix the wires so
that external forces are not applied to the terminals.
Fig. 30

Attach insulation sleeve

Round crimp-style terminal


Electric wire
Fig. 31

Connect wires of the


same gauge to both
side. (GOOD)

Good

18

Do not connect wires


of the same gauge to
one side. (WRONG)

Wrong

Do not connect wires


of different gauges.
(WRONG)

Wrong

English
3PN06588-3H

Installation of Indoor / Outdoor Unit

183

Installation of Indoor Unit

EDSG281001

10. FIELD SETTINGS


(1) Make sure the control box lids are closed on the indoor and outdoor units.
(2) Field settings must be made from the remote controller and in accordance with installation conditions.
Settings can be made by changing the Mode No., FIRST CODE NO. and SECOND CODE NO..
The Field Settings included with the remote control lists the order of the settings and method of operation.

10-1 Setting ceiling height


Select the SECOND CODE NO. that corresponds to the ceiling height Table 4.
(SECOND CODE NO. is factory set to 01 for a ceiling height of less than 2.7m .)
Table 4
Ceiling height (m)
Less than 2.7 m
2.7 to 3.5

Mode No.

FIRST CODE NO.

13 (23)

SECOND CODE NO.


01
02

10-2 Settings for options


For settings for options, see the installation instructions provided with the option.

10-3 Setting air filter sign


Remote controllers are equiped with liquid crystal display air filer signs to display the time to clean air filters.
Change the SECOND CODE NO. according to Table 5 depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to 01 for air filter contamination-light.)
Table 5
Setting
Air filter contaminationlight
Air filter contaminationheavy

English

Spacing time of display air filter


sign (long life type)

Mode No.

FIRST CODE
NO.

10 (20)

Approx. 2500 hrs


Approx. 1250 hrs

SECOND
CODE NO.
01
02

19
C : 3PN06588-3H

184

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

10-4 When implementing group control


When using as a pair unit or as a master unit for simultaneous operation multi, you may simultaneous start/
stop (group) control up to 16 unit with the remote controller.
In this case, all the indoor units in the group will operate in accordance with the group control remote controller.
Select a remote controller which matches as many of the functions (swing flap, etc.) in the group as possible.

Outdoor unit 1
Indoor unit 1

Outdoor unit 2

Indoor unit 2

Outdoor unit 3

Indoor unit 3

Group control remote controller


Wiring Method (See 9. ELECTRIC WIRING WORK on page 16.)
(1) Remove the control box lid.
(2) Cross-wire the remote control terminal block (P1 P2) inside the control box. (There is no polarity.)
(Refer to Fig. 25 on page 15 and Table 3 on page 16)
NOTE
When combining with a simultaneous operation multi-type, be sure only to connect the wiring to the master
unit.

20

English
C : 3PN06588-3H

Installation of Indoor / Outdoor Unit

185

Installation of Indoor Unit

EDSG281001

10-5 Two remote controllers control (Controlling 1 indoor unit by 2 remote controllers)
When using 2 remote controllers, one must be set to MAIN and the other to SUB.
MAIN/SUB CHANGEOVER
(1) Insert a
screwdriver into the recess between the upper and lower part of remote controller and, working from the 2 positions, pry off the upper part. (The remote controller PC board is attached to the upper
part of remote controller.) (Refer to Fig. 32)
(2) Turn the main/sub changeover switch on one of the two remote controller PC boards to S. (Leave the
switch of the other remote controller set to M.) (Refer to Fig. 33)
Fig. 32

Fig. 33

Upper part of
remote controller

(Factory setting)

Insert the screwdriver


here and gently work
off the upper part of
remote controller.

(Only one remote


controller needs
to be changed if
factory settings
have remained
untouched.)

Lower part of
remote controller

S
M

S
M

Remote
controller
PC board

Wiring Method (See 9.ELECTRIC WIRING WORK on page16.)


(3) Remove the control box lid
(4) Add remote controller 2 to the remote control terminal block (P1, P2) in the control box.
(There is no polarity.) (Refer to Fig. 26 on page 15 and Table 3 on page 16)
NOTE
When combining with a simultaneous operation multi-type, be sure only to connect the wiring to the master
unit.

11. TEST OPERATION


(1) Make sure the control box lids are closed on the indoor and outdoor units.
(2) Refer to the section of FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED. on page 4.
After finishing the construction of refrigerant piping, drain piping, and electric wiring, conduct test operation
accordingly to protect the unit.

11-1 TEST OPERATION


1.
2.
3.
4.
5.

Open the gas side stop valve.


Open the liquid side stop valve.
Electrify crank case heater for 6 hours. (Not required in case of a unit exclusively designed for cooling only)
Set to cooling operation with the remote controller and start operation by pushing ON/OFF button (
).
Press INSPECTION/TEST OPERATION button 4 times (
) (2 times for wireless remote controller) and
operate at Test Operation mode for 3 minutes.
6. Push AIR FLOW DIRECTION ADJUST button (
) to make sure the unit is in operation.
7. Press INSPECTION/TEST OPERATION button (
) and operate normally.
8. Confirm function of unit according to the operation manual.
TEST

TEST

English

21
3PN06588-3H

186

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

PRECAUTIONS
1. Refer to 11-2 HOW TO DIAGNOSE FOR MALFUNCTION if the unit does not operate properly.
2. After completing the test run, press the INSPECTION/TEST OPERATION run button once to put the unit
in inspection mode, and make sure the malfunction code is 00. (=normal)
If the code reads anything other than 00, refer to 11-2 HOW TO DIAGNOSE FOR MALFUNCTION.
NOTE
If a malfunction is preventing operation, refer to the malfunction diagnoses below.

11-2 HOW TO DIAGNOSE FOR MALFUNCTION


With the power on, it is possible to monitor the type of malfunction by looking at the malfunction code
displayed in the remote controller.
If nothing is displayed in the remote controller, check the following items before attempting a diagnosis based
on the malfunction code, as they might be a cause.
Disconnected or incorrect wiring (between power supply and the outdoor unit, between the outdoor and
indoor units, and between the indoor unit and the remote controller)
Burnt out indoor or outdoor unit fuse
88 will be displayed for a few seconds on the remote controller immediately after the power is turned on.
This display indicates that the remote controller is being checked to see whether it is ok or not, and does
not indicate a malfunction.
Diagnose with the display on the liquid crystal display remote controller.
1. With the wired remote controller. (NOTE 1)
When the operation stops due to trouble, operation lamp flashed, and
and the malfunction code are
indicated on the liquid crystal display. In such a case, diagnose the fault contents by referning to the table
on the malfunction code list it case of group control, the unit No. is displayed so that the indoor unit No. with
the trouble can be recognized. (NOTE 2)
2. With the wireless remote controller.
(Refer also to the operation manual attached to the wireless remote controller)
When the operation stops due to trouble. the display on the indoor unit flashes. In such a case, diagnose
the fault contents with the table on the malfunction code list looking for the malfunction code which can be
found by following procedures. (NOTE 2)
(1) Press the INSPECTION /TEST OPERATION button,
is displayed and 0 flashes.
(2) Press the PROGRAMMING TIME button and find the unit No. which stopped due to trouble.
Number of beeps3 short beeps .............. Perform all the following operations
1 short beep ................ Perform (3) and (6)
1 long beep ................. No trouble
(3) Press the OPERATION MODE SELECTOR button and upper figure of the malfunction code flashes.
(4) Continue pressing the PROGRAMMING TIME button unit it makes 2 short beeps and find the upper code.
(5) Press the OPERATION MODE SELECTOR button and lower figure of the malfunction code flashes.
(6) Continue pressing the PROGRAMMING TIME button unit it makes a long beep and find the lower code.
A long beep indicate the malfunction code.
NOTE
1. In case wired remote controller. Press the INSPECTION /TEST OPERATION button on remote controller,

starts flashing.
2. Keep down the ON/OFF button for 5 seconds or longer in the inspection mode and the above trouble history disappears, after the trouble code goes on and off twice, followed by the code 00(normal).
The display changes from the inspection mode to the normal mode.

22

English
3PN06588-3H

Installation of Indoor / Outdoor Unit

187

Installation of Indoor Unit

EDSG281001

11-3 Malfunciton code


For places where the malfunction code is left blank, the
indication is not displayed. Though the system
continues operating, be sure to inspect the system and make repairs as necessary.
Depending on the type of indoor or outdoor unit, the malfunction code may or may not be displayed.
Code
A1
A3
A5
A6
AF
AH
AJ
C4
C5
C9
CJ
E0
E1
E3
E4
E5
E6
E7
E8
E9
EA
F3
H3
H4
H6
H7
H8
H9
J3
J5
J6
J8
J9
L4
L5
L8
L9

English

Malfunction/Remarks
Indoor units PC board faulty
Drain water level abnormal
Freeze-up protector or stopped by high pressure control
Indoor fan motor overloaded, overcurrent or locked
Humidifier faulty
Air cleaner faulty
Only the air cleaner does not function.
Type set improper
Capacity data is wrongly proset. Or there is nothing programmed in the data hold IC.
Sensor (R2T) for heat exchanger temperature is fault
Sensor (R3T) for heat exchanger temperature is fault
Sensor for suction air temperature is fault
Sensor for remote controller is fault
The remote controller thermistor does not function, but the system thermo run is possible.
Action of safety device (outdoor unit)
Outdoor units PC board faulty
High pressure abnormal(outdoor unit)
Low pressure abnormal (outdoor unit)
Compressor motor lock malfunction
Compressor motor lock by over current (outdoor)
Outdoor fan motor lock malfunction
Outdoor fan instantneous overcurrent malfunction
Input overcurrent (outdoor unit)
Electronic expansion valve faulty (outdoor unit)
Cooling/heating switch malfunction (outdoor)
Discharge pipe temperature abnormal (outdoor unit)
High pressure switch faulty (outdoor unit)
Low pressure switch faulty (outdoor unit)
Faulty position detection sensor (outdoor unit)
Outdoor motor position signal malfunction
CT abnormality (outdoor unit)
Outdoor air thermistor faulty (outdoor unit)
Discharge pipe thermistor faulty (outdoor unit)
Suction pipe thermistor faulty (outdoor unit)
Heat exchanger thermistor faulty (outdoor unit)
Liquid piping thermistor malfunction (heating) (outdoor)
Gas piping thermistor malfunction (cooling) (outdoor)
Overheated heat-radiating fin (outdoor)
Inverter cooling defect.
Instantaneous overcurrent (outdoor)
Possible earth fault or short circuit in the compressor motor.
Electric thermal (outdoor)
Possible electrical overload in the compressor or cut line in the compressor motor.
Stall prevention (outdoor)
Compressor possibly locked.

23
3PN06588-3H

188

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

LC
P1
P3
P4
PJ
U0
U1
U2

U4
UF

U5
U8

UA
UC

Transmission malfunction between the outdoor control units inverters (outdoor)


Open-phase or main circuit low voltage (outdoor)
PC-board temperature sensor malfunction (outdoor)
Heat-radiating fin temperature sensor malfunction (outdoor)
Type set improper (outdoor unit)
Capacity data is wrongly proset. Or there is nothing programmed in the data hold IC.
Suction pipe temperature abnormal or refrigerant shortage
Reverse phase
Reverse two of the L1,L2and L3 leads.
Power source voltage malfunction
Includes the defect in 52C.
Transmission error (indoor unit outdoor unit)
Incorrect wiring between indoor and outdoor units or malfunction of the PC board
mounted on the indoor and the outdoor units.
If UF is shown, the wiring between the indoor and outdoor units is not properly
wired. Therefore, immediately disconnect the power supply and correct the wiring.
(The compressor and the fan mounted on the outdoor unit may start operation independent of the remote controller operation.)
Transmission error (indoor unit outdoor unit)
Transmission is improper between the indoor unit and the remote controller.
Malfunction in transmission between main and sub remote controls.
(Malfunction in sub remote control.)
Miss setting for multi system
Setting is wrong for selector switch of multi-system. (see switch SS2 on the main
units PC board)
Incorrect combination with indoor unit and outdoor unit
Central control address overlapping

24

English
C : 3PN06588-3H

Installation of Indoor / Outdoor Unit

189

Installation of Indoor Unit

EDSG281001

2.4

FBQ50BV1A / FBQ60BV1A / FBQ71BV1A

2.4.1

Names and Functions of Parts

g
d

c
b

a
b
c
d
e
f
g
h

Indoor unit
Remote controller
Inlet air
Discharge air
Refrigerant piping, connection electric wire
Drain pipe
Inlet grille
Drain pumping out device (built-in)
Drains water removed from the room during cooling.
3P156215-7K

190

Installation of Indoor / Outdoor Unit

EDSG281001

2.4.2

Installation of Indoor Unit

Installation
FBQ50BV1A
FBQ60BV1A
FBQ71BV1A

SPLIT SYSTEM Air Conditioner

Installation manual

2
CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.

SAFETY CONSIDERATIONS .........................................................................................1


BEFORE INSTALLATION ...............................................................................................2
SELECTING INSTALLATION SITE.................................................................................5
PREPARATIONS BEFORE INSTALLATION ..................................................................6
INDOOR UNIT INSTALLATION ......................................................................................6
REFRIGERANT PIPING WORK .....................................................................................7
DRAIN PIPING WORK ..................................................................................................10
INSTALLING THE DUCT ..............................................................................................12
ELECTRIC WIRING WORK ..........................................................................................12
WIRING EXAMPLE .......................................................................................................15
FIELD SETTING............................................................................................................16
TEST OPERATION .......................................................................................................17

1. SAFETY CONSIDERATIONS
Please read these SAFETY CONSIDERATIONS carefully before installing air conditioning equipment and
be sure to install it correctly. After completing the installation, make sure that the unit operates properly during
the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained.
Also, inform customers that they should store this installation manual along with the operation manual for
future reference.
This air conditioner comes under the term appliances not accessible to the general public.
Meaning of warning and caution symbols.
WARNING .........Failure to observe a warning may result in death or serious injury.
CAUTION ..........Failure to observe a caution may result in injury or damage to the equipment.

WARNING
Ask your dealer or qualified personnel to carry out installation work. Do not try to install the air conditioner
yourself.
Improper installation may result in water leakage, electric shocks or fire.
Perform installation work in accordance with this installation manual.
Improper installation may result in water leakage, electric shocks or fire.
Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in water leakage, electric shocks, fire or the unit falling.
Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
A foundation of insufficient strength may result in the equipment falling and causing injuries.
Carry out the specified installation work after considering strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment falling and causing accidents.
Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried
out by qualified personnel according to local laws and regulations and this installation manual.
An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.

1
3P156215-8K

Installation of Indoor / Outdoor Unit

191

Installation of Indoor Unit

EDSG281001

Make sure that all wiring is secured, the specified wires and used, and no external forces act on the terminal
connections or wires.
Improper connections or installation may result in fire.
When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the
wires so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric shocks, fire or the terminals overheating.
If the refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant gas comes into contact with fire.
After completing the installation work, check that the refrigerant gas does not leak.
Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source
of fire, such as a fan heater, stove or cooker.
Before touching electrical parts, turn off the unit.
Be sure to establish an earth.
Do not earth the unit to a utility pipe, arrester, or telephone earth.
Incomplete earth may cause electrical shock, or fire.
A high surge current from lightning or other sources may cause damage to the air conditioner.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks, or fire.
Do not directly touch the refrigerant that leaks from the refrigerant piping connection.
CAUTION
While following the instructions in this installation manual, install drain piping in order to ensure proper
drainage and insulate piping in order to prevent condensate.
Improper drain piping may result in water leakage and property damage.
Install the indoor and outdoor units, power supply wiring and connecting wiring at least 1 m away from televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 m may not be sufficient enough to eliminate the noise.)
Remote controller (wireless kit) transmitting distance can result shorter than expected in rooms with electronic fluorescent lamps (inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as possible.
Do not install the air conditioner in the following locations:
(a)where a mineral oil mist or an oil spray or vapor is produced, for example in a kitchen
Plastic parts may deteriorate and fall off or result in water leakage.
(b)where corrosive gas, such as sulfurous acid gas, is produced
Corroding copper pipes or soldered parts may result in refrigerant leakage.
(c) near machinery emitting electromagnetic waves
Electromagnetic waves may disturb the operation of the control system and result in a malfunction of the
equipment.
(d)where flammable gases may leak, where there are carbon fiber or ignitable dust suspensions in the air,
or where volatile flammables such as thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.

2. BEFORE INSTALLATION
Do not exert pressure on the resin parts when opening the unit or when moving it after opening.
Be sure to check the type of refrigerant to be used before installing the unit. (Using an incorrect refrigerant
will prevent normal operation of the unit.)
The accessories needed for installation must be retained in your custody until the installation work is completed. Do not discard them!
Decide upon a line of transport.
Leave the unit inside its packaging while moving, until reaching the installation site. Where unpacking is
unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid damage or scratches to the unit.
For the installation of an outdoor unit, refer to the installation manual attached to the outdoor unit.

2
3P156215-8K

192

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Do not use the unit in locations with high salt content in the air such as beachfront property, locations where
the voltage fluctuates such as factories, or in automobiles or marine vessels.

1. Precautions
Be sure to read this manual before installing the indoor unit.
This unit is suitable for installation in a household, commercial and light industrial environment.
Do not install or operate the unit in rooms mentioned below.
Laden with mineral oil, or filled with oil vapor or spray like in kitchens. (Plastic parts may deteriorate.)
Where corrosive gas like sulfurous gas exists. (Copper tubing and brazed spots may corrode.)
Where volatile flammable gas like thinner or gasoline is used.
Where machines can generate electromagnetic waves. (Control system may malfunction.)
Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates
greatly such as that in factories. Also in vehicles or vessels.
The unit should be installed at least 2.5m from the floor.

2. Accessories
Check if the following accessories are included with your unit.
Name

(1) Metal clamp

(2) Chain

(3) Drain hose

Insulation for
fitting

Sealing pad

Quantity

1 pc.

1 set

1 pc.

1 each

1 each

(4) For gas pipe

(6) Large

(5) For liquid pipe

(7) Middle

Shape
FBQ50BV1A

2 pcs.

FBQ60 71BV1A 3 pcs.

Name

(8) Washer for


hanger
bracket

Quantity

8 pcs.

Clamp
4 pcs.
(9) Large

2 pcs.

(11) Screw for chains

(12) Duct companion flange connection screw

1 set

1 set

(10) Small

Shape
FBQ50BV1A

4 pcs.

FBQ50BV1A

8 pcs.

FBQ60 71BV1A 6 pcs. FBQ60 71BV1A 12 pcs.

Name
Quantity

(13) Small sealing


pad
2 pcs.

(Other)
Operation manual
Installation manual

Shape

3
3P156215-8K

Installation of Indoor / Outdoor Unit

193

Installation of Indoor Unit

EDSG281001

3. Optional accessories
For this indoor unit, the optional remote controller is necessary.
Remote controller
Remote controller

BRC1C61

NOTE
If the customer wishes to use a remote controller that is not listed on the table, select a suitable remote
controller after consulting catalogs and technical materials.
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER
INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
Items to be checked

If not properly done, what is likely to occur

Are the indoor unit and outdoor unit fixed


firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond


to that shown on the name plate?

The unit may malfunction or the components burn out.

Are wiring and piping correct?

The unit may malfunction or the components burn out.

Is the unit safely grounded?

It may result in electric shock.

Is wiring size according to specifications?

The unit may malfunction or the components burn out.

Is something blocking the air outlet or inlet


of either the indoor or outdoor units?

It may result in insufficient cooling.

Are refrigerant piping length and additional


refrigerant charge noted down?

The refrigerant charge in the system is not


clear.

Check

b. Items to be checked at time of delivery


Also review the 1. SAFETY CONSIDERATIONS
Items to be checked

Check

Did you explain about operations while showing the operation manual to your customer?
Did you hand the operation manual over to your customer?
c. Points for explanation about operations
The items with
WARNING and
CAUTION marks in the operation manual are the items pertaining
to possibilities for bodily injury and material damage in addition to the general usage of the product.
Accordingly, it is necessary that you make a full explanation about the described contents and also ask
your customers to read the operation manual.

4. Note to the installer


Be sure to instruct customers how to properly operate the unit (especially cleaning filters <field supplied
parts>, operating different functions, and adjusting the temperature) by having them carry out operations themselves while looking at the manual.

4
3P156215-8K

194

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

3. SELECTING INSTALLATION SITE


Please attach additional thermal insulation material to the unit body when it is believed that the relative humidity in the ceiling exceeds 80%. Use glass wool, polyethylene foam, or similar with a thickness of 10 mm or
more as thermal insulation material. (After attaching additional thermal insulation material, manufactures
label should appear.)

1. Select an installation site where the following conditions are fulfilled and that meets
your customers approval.
In the upper space (including the back of the ceiling) of the indoor unit where there is no possible
dripping of water from the refrigerant pipe, drain pipe, water pipe, etc.
Where optimum air distribution can be ensured.
Where nothing blocks air passage.
Where condensate can be properly drained.
Where the ceiling is strong enough to bear the indoor unit weight.
Where the false ceiling is not noticeably on an incline.
Where sufficient clearance for maintenance and service can be ensured.
Where there is no risk of flammable gas leakage.
Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the
installation manual for the outdoor unit.)
CAUTION
Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 m away from televisions and radios. This is to prevent image interference and noise in those electrical appliances.
(Noise may be generated depending on the conditions under which the electric wave is generated, even if
1 m is kept.)
Drain pipe
Power supply
wiring port

Maintenance
space (*)

300
or more

2500 or more

Liquid pipe
300
or more
Maintenance
space

Gas pipe

Transmission wiring port


Maintenance drain hose

Floor surface

(*) If the ceiling is removable, this maintenance space don't need.

(Length : mm)

2. Use suspension bolts for installation. Check whether the ceiling is strong enough to
support the weight of the unit or not. If there is a risk, reinforce the ceiling before
installing the unit.
(Installation pitch is marked on the paper pattern for installation. Refer to it to check for points requiring
reinforcement.)

5
3P156215-8K

Installation of Indoor / Outdoor Unit

195

Installation of Indoor Unit

EDSG281001

4. PREPARATIONS BEFORE INSTALLATION


1. Relation of ceiling opening to unit and suspension bolt position. (Refer to Fig. 1)

A
B
Suspension bolt pitch

Install the inspection opening on the control


box side where maintenance and inspection
of the control box.
Install the inspection opening also in the
lower part of the unit.
(Length : mm)
Model

FBQ50BV1A

700

Indoor unit

750 400400

FBQ60 71BV1A 1000 1050 600600

145
Pipe

Inspection opening
size C
Control box

630

Suspension
bolt pitch
Suspension bolt (4)
800
Fig. 1

2. The fan speed for this indoor unit is preset to provide standard external static pressure.
If higher or lower external static pressure is required, reset the external static pressure by changing
the initial setting from the remote controller. Refer to the section entitled 11. FIELD SETTING.

3. Install the suspension bolts. (Refer to Fig. 2)


(Use M10 size bolt for the suspension bolt)
Use anchors for existing ceilings, and a sunken insert,
sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit.
NOTE
All the above parts are field supplied.

<Installation example>
Ceiling slab
Anchor
Long nut or
turn-buckle
Suspension bolt

Indoor unit
Fig. 2

5. INDOOR UNIT INSTALLATION


<When installing optional accessories, read also the installation manual for optional accessories.
Depending on the field conditions, it may be easier to install optional accessories before the indoor
unit is installed.>
Be sure to use the furnished accessories or ones that match the specifications when installing.

1. Install the indoor unit temporarily.


Attach the hanger bracket to the suspension bolt. Be sure to
fix it securely by using a nut and washer (8) from the upper
and lower sides of the hanger bracket. (Refer to Fig. 3)

Field supply
(8)Washer for hanger
bracket (attached)

Tighten (double nuts)


Fig. 3
[PRECAUTION]
Since the unit uses a plastic drain pan, prevent welding spatter and other foreign substances from
entering the outlet hole during installation.

6
3P156215-8K

196

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

2. Check the unit is horizontally level. (Refer to Fig. 4)

Level

Fig. 4

Vinyl tube

CAUTION
The indoor unit is equipped with a built-in drain pump and float switch. Verify that it is level by using a level
or a water-filled vinyl tube.
(If the unit is tilted against condensate flow, the float switch may malfunction and cause water to drip.)

3. Tighten the upper nut.


4. Fix the attached chains.
Make sure to install the chains as shown
below.

Bottom plate

(2) Chain (attached)


Bottom frame
Fig. 5

(11) Screw for chains


(attached)

CAUTION
Otherwise, the bottom plate may fall off.

5. Setting up the attached chains.


Fix the chains with the machine screws at the hole position of the bottom plate and the bottom frame.
(2 or 3 positions)

6. REFRIGERANT PIPING WORK


For refrigerant piping of outdoor unit, see the installation manuals attached to the outdoor unit.
Execute heat insulation work completely on both sides of the gas piping and the liquid piping. Otherwise, a
water leakage can result sometimes.
(When using a heat pump, the temperature of the gas piping can reach up to approximately 120C, so use
insulation which is sufficiently resistant.)
Also, in cases where the temperature and humidity of the refrigerant piping sections might exceed 30C or
RH80%, reinforce the refrigerant insulation. (20 mm or thicker) Condensate may form on the surface of the
insulating material.
Be sure to check the type of refrigerant to be used before doing any work. (Using an incorrect refrigerant will
prevent normal operation of the unit.)

7
3P156215-8K

Installation of Indoor / Outdoor Unit

197

Installation of Indoor Unit

EDSG281001

CAUTION
Use a pipe cutter and flare suitable for the type of refrigerant.
Apply ester oil or ether oil around the flare section before connecting.
To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end or cover it
with tape.
Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit, such as
air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.
Be sure to use both a spanner and torque wrench together, as shown
in the drawing, when connecting or disconnecting pipes to/from the
unit. (Refer to Fig. 6)
Refer to Table 1 for the dimensions of flare nut spaces.
When connecting the flare nut, apply ester oil or ether oil to the flare
section (only inside), and spin 3-4 times before screwing in.
(Refer to Fig. 7)

Torque wrench

Spanner
Pipe union
Flare nut

NOTE
Use the flare nut included with the unit main body.

Fig. 6

Coat the flare section (only inside)


with ester oil or ether oil.

Fig. 7

Table 1
Tightening torque

Flare dimensions A (mm)

6.4

14.2 17.2N m

8.7 9.1

12.7

49.5 60.3N m

16.2 16.6

15.9

61.8 75.4N m

19.3 19.7

Flare

R0.4-0.8
A

90 2

45 2

Pipe size

Refer to Table 1 to determine the proper tightening torque.


CAUTION
Over-tightening the flare nut may break it and/or cause the refrigerant to leak.
Not recommendable but in case of emergency
You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may
follow the installation method mentioned below
After the work is finished, make sure to check that there is no gas leak.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque suddenly increases. From that position, further tighten the flare nut the angle shown below:
Pipe size

Further tightening angle

Recommended arm length of tool

6.4 (1/4)

60 to 90 degrees

Approx. 150mm

12.7 (1/2)

30 to 60 degrees

Approx. 250mm

15.9 (5/8)

30 to 60 degrees

Approx. 300mm

8
C : 3P156215-8K

198

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas
leakage by thoroughly studying the following figure and using the attached heat insulating materials for fitting (4) and (5). (Fasten both ends with the clamps (9).) (Refer to Fig. 8)
Wrap the sealing pad (7) only around the insulation for the joints on the gas piping side. (Refer to Fig. 8)

(7) Middle sealing pad (attached)


(Wrap from the bottom up)
(4) Insulation for fitting (attached)
(for gas line)

Gas pipe
Liquid pipe
(5)Insulation for fitting (attached)
(for liquid line)

Attach to the bottom


(For both gas piping
and liquid piping)

(9) Clamp (attached) (4)


Fig. 8

CAUTION
For local insulation, be sure to insulate local piping all the way into the pipe connections inside the machine.
Exposed piping may cause condensation or burns on contact.
CAUTION
CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING
Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filler metal
(BCuP-2: JIS Z 3264/B-Cu93P-710/795: ISO 3677) which does not require flux.
(Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is
used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil.)
Before brazing local refrigerant piping, nitrogen gas shall be blown through the piping to expel air from the
piping.
If you brazing is done without nitrogen gas blowing, a large amount of oxide film develops inside the piping,
and could cause system malfunction.
When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution or
while inserting nitrogen into the refrigerant piping. Once this is done, connect the indoor unit with a flared
or a flanged connection.
2
Nitrogen should be set to 0.02 MPa (0.2 kg/cm ) with a pressure-reducing valve if brazing while inserting
nitrogen into the piping. (Refer to Fig. 9)

Pressure-reducing valve
Refrigerant piping
Part to be
brazed
Nitrogen

Taping
hands valve

Nitrogen

Fig. 9

9
3P156215-8K

Installation of Indoor / Outdoor Unit

199

Installation of Indoor Unit

EDSG281001

7. DRAIN PIPING WORK


1. Rig drain piping (Refer to Fig. 10, Fig. 11)
As for drain work, perform piping in such a manner that water can be drained properly.
As for drain piping, the connection can be made from three different directions.
Employ a pipe with either the same diameter or with the diameter larger (excluding the raising section)
than that of the connecting pipe (PVC pipe, nominal diameter 25 mm, outside diameter 32 mm).
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets
from forming.
If the drain pipe cannot be sufficiently set on a slope, execute the drain raising piping.
To keep the drain pipe from sagging, space hanging wires every 1 to 1.5 m.
Hanger bracket

1~1.5 m

1/100 gradient or more

Fig. 11

Fig. 10
CAUTION
Water pooling in the drainage piping can cause the drain to clog.

Use the attached drain hose (3) and Metal clamp (1).
Insert the drain hose into the drain socket up to the base, and tighten the Metal clamp securely within
the portion of a white tape of the hose-inserted tip. Tighten the Metal clamp until the screw head is less
than 4 mm from the hose.
Wrap the attached sealing pad (6) over the Metal clamp and drain hose to insulate.
Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water
leakage due to dew condensation.
Indoor drain pipe
Drain socket
Metal clamp (1)
(attached)

Metal clamp (1)


(attached)

Large sealing pad (6)


(attached)

Bring the seam


of the sealer to
the top

Drain hose (3)


Tape (White)

4 mm

Fig. 13

Fig. 12

<PRECAUTIONS FOR DRAIN RAISING PIPING>


Install the drain raising pipes at a height of less than 250 mm.
Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit.
Ceiling slab
Less 300 mm

1~1.5 m

Hanging bar

(1) Clamp (Attached with unit)


Adjustable range
(0~250 mm)
Drain raising pipe
(Part to be product in the field)
Drain hose
(3) Drain hose (Attached with unit)
Horizontal or up-grade
The drain hose must be horizontally positioned or have a slight up-grade.

Fig. 14

If the air accumulates inside the hose and the drain pump is at a
standstill, the drain may flow back and generate an abnormal sound.

10
3P156215-8K

200

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

NOTE
To ensure no excessive pressure is applied to the included drain hose (3), do not bend or twist when
installing. (This may cause leakage.)
If converging multiple drain pipes, install according to the procedure shown below.

0~250 mm

Multiple drain piping

Keep the drain pipe short and sloping


downwards at a gradient of at least 1/100
to prevent air pockets from forming.
Water pooling in the drain piping
can cause the drain to clog.
Fig. 15

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.

2. After piping work is finished, check if drainage flows smoothly.


Open the water inlet lid, add approximately 1 L of water gradually and check drainage flow.
(Refer to Fig. 16)

Water inlet

Portable pump
Water inlet lid

Refrigerant pipes
Drain outlet for maintenance
(with rubber plug)
Fig. 16

Bucket

Close
Open

NOTE
Use the drain outlet for maintenance to drain water from the drain pan.
WHEN ELECTRIC WIRING WORK IS FINISHED
Check drainage flow during cool running, explained in the section entitled. 12. TEST OPERATION
WHEN ELECTRIC WIRING WORK IS NOT FINISHED
CAUTION
Electrical wiring work should be done by a certified electrician.
If someone who does not have the proper qualifications performs the work, perform the following after
test run is complete.
Remove the control box lid. Connect the single phase power supply (Single plase 50 Hz 220-240V) to
connections No.1 and No.2 on the terminal block for wiring the units. Do not connect to No.3 of the terminal block for wiring the units. (The drain pump will not operate.) Connect the ground wire firmly.
When carrying out wiring work around the control box, make sure none of the connectors come
undone. Be sure to attach the control box before turning on the power.
After confirming drainage (Fig. 16, Fig. 17), turn off the power and remove the power supply.
Attach the control box lid as before.

Terminal block for wiring

1 2 3
Control box

Fig. 17

Single phase power supply

11
3P156215-8K

Installation of Indoor / Outdoor Unit

201

Installation of Indoor Unit

EDSG281001

8. INSTALLING THE DUCT


Connect the duct supplied in the field.
Air inlet side
Attach the duct and intake-side flange.
Wrap the intake-side flange and duct connection area with aluminum tape or something similar to prevent
air escaping.
CAUTION
Be sure to attach an air filter <field supply> inside the air passage on the intake side. (Use an air filter
whose dust collecting efficiency is at least 50% in a gravimetric technique.)

Flange

Main unit

Flange

Insulation material
(Field supply)

Aluminum tape
(Field supply)
Aluminum tape
(Field supply)
Air inlet side

Air outlet side

Air outlet side


Connect the duct according to the air inside of the outlet-side flange.
Wrap the outlet-side flange and the duct connection area with aluminum tape or something similar to prevent air escaping.
CAUTION
Be sure to insulate the duct to prevent condensation from forming. (Material: glass wool or polyethylene
foam, 25 mm thick)
Use electric insulation between the duct and the wall when using metal ducts to pass metal laths of the net
or fence shape or metal plating into wooden buildings.

9. ELECTRIC WIRING WORK

All field supplied parts and materials and electric works must conform to local codes.
Use copper wire only.
For electric wiring work, see also the wiring diagram attached to the control box lid.
For remote controller wiring details, refer to the installation manual attached to the remote controller.
All wiring must be performed by an authorized electrician.
A circuit breaker capable of shutting down power supply to the entire system must be installed.
Refer to the installation manual attached to the outdoor unit for the size of power supply electric wire connected to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
Be sure to ground the air conditioner
Do not connect the ground wire to gas pipes, plumbing pipes, lightning rods, or telephone ground wires.
Gas pipes: might cause explosions or fire if gas leaks.
Plumbing: no grounding effect if hard vinyl piping is used.
Telephone ground wires or lightning rods: might cause abnormally high electric potential in the ground
during lighting storms.
Install a wiring interrupter or ground-fault circuit interrupter for the power wiring.
Make sure the earth resistance is no greater than 100 .

Specifications for field wire


The remote controller cord should be procured locally. Refer to the Table 2 when preparing one.

12
3P156215-8K

202

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Table 2
2

Wire
Wiring the units

H05VV - U4G (NOTE 1, 2)

Remote controller cord

Shield wire (2 wires) (NOTE 3)

Size (mm )

Length

2.5

0.75 - 1.25 Max. 300 m (NOTE. 4)

2
NOTE
1. Shows only in case of protected pipes. Use H07RN-F in case of no protection.
2. Run transmission wiring between the indoor and outdoor units through a conduit to protect against external forces, and feed the conduit through the wall together with refrigerant piping.
3. Use double insulation wire for remote controller (sheath thickness: 1 mm) or run wires through a wall or
conduit so that the user can not come in contact with them.
4. This length shall be the total extended length in the system of the group control.
PRECAUTION
Connection of wiring units, ground wire and remote controller cord. (Refer to Fig. 18 and 19)
Wiring the units and ground for the wire
Remove the control box lid and pull out the control box. (Refer to Fig. 18)
Next, pull the wires inside through the rubber bush A and connect them to their respective terminals on the
terminal block for wiring the units (4P) inside. Also, connect the ground wire to the ground terminal. In doing
this, pull the wiring through the rubber bush A and fix it in place with the clamp.
Remote controller cord
Connect the cord to the terminal block for remote controller (2P) (no polarity). In doing this, pull the wiring
through the rubber bush B and fix it in place with the clamp.

Rubber bush A
*Wiring the units

Rubber bush B

After wiring, adhere the attached


small sealing pad (13) around the
wires as shown below.
(Be sure to adhere it to avoid
water from outside unit.)

*Do not clamp remote


controller cords together with
wires connecting the units.
Doing so may cause
malfunction.

*Remote controller cord

CAUTION

Note) No gap are allowed.


(Between rubber bush
and sealing material.)

Rubber bush
Wire

Control box
Inside unit
WIRING DIAGRAM

Outside unit
Small sealing pad (13)
(Adhere it around the wire)

Control box lid


Fig. 18

[ How to adhere it ]
Note) In case of two wires or more,
adhere sealing material to
each wire separately.

13
3P156215-8K

Installation of Indoor / Outdoor Unit

203

Installation of Indoor Unit

EDSG281001

Terminal block for


wiring the units

Control box Motor lead wire


Clamp material

Grounding terminal for


the remote controller

Wiring the
units

123

Ground the shield


part of shield wire.
Refer to NOTE of
10. WIRING EXAMPLE
Grounding
terminal
Shield part

C-cup
washer

Ground
wire
(10) Clamp (attached)
Clamp material
Remote
controller
cord

P1 P2

(10) Clamp (attached)


Indoor PC board Terminal block for remote controller
Arrow view A
Fig. 19
Observe the notes mentioned below when wiring to the terminal block for wiring the units.
CAUTION
When clamping wiring, use the included clamping material to prevent outside pressure being exerted on the
wiring connections and clamp firmly. When doing the wiring, make sure the wiring is neat and does not
cause the control box lid to stick up, then close the cover firmly.
When attaching the control box lid, make sure you do not pinch any wires.
After all the wiring connections are done, fill in any gaps in the through holes with putty or insulation (procured locally) to prevent small animals and insects from entering the unit from outside. (If any do get in, they
could cause short circuits in the control box.)
Outside the machine, separate the weak wiring (remote controller cord) and strong wiring (interunit,
ground, and other power wiring) at least 50 mm so that they do not pass through the same place together.
Proximity may cause electrical interference, malfunctions, and breakage.
Do not connect wires of different gauge to the same power supply terminal. (Looseness in the connection
may cause overheating.) (Refer to Fig. 20)
Observe the notes when wiring to the terminal block for wiring the units.
(Use a round crimp-style terminal with insulation sleeve for connection to the terminal block for wiring the
units. In case it cannot be used due to unavoidable reasons, connect wires of the same gauge to the both
side as shown in Fig. 20.)

Round crimp-style
terminal

Attach insulation
sleeve

Connect wires of the


same gauge to both
side. (GOOD)

Do not connect wires


of the same gauge to
one side. (WRONG)

Do not connect
wires of different
gauges. (WRONG)

Electric wire
Fig. 20

Follow the instructions below if the wiring gets very hot due to slack in the power wiring.
In wiring, make certain that prescribed wires are used, carry out complete connections, and fix the wires so
that outside forces are not applied to the terminals.
Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the
head of the screw might be damaged, and the screw will not be properly tightened.
If the terminal screw are tightened too hard, screws might be damaged.
Refer to the table below for the tightening torque of the terminal screws.

14
3P156215-8K

204

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Tightening torque (N m)
Terminal block for remote controller

0.79 to 0.97

Terminal block for wiring the units

1.18 to 1.44

Ground terminal

1.44 to 1.94

2
10. WIRING EXAMPLE
For the wiring of outdoor unit, refer to the installation manuals attached to the outdoor unit.
Confirm the system type.
1 remote controller control: 1 remote controller controls 1 indoor unit (standard system). (Refer to Fig. 21)
Group control: 1 remote controller controls up to 16 indoor units.
(All indoor units operate according to the remote controller.) (Refer to Fig. 22)
2 remote controllers control: 2 remote controllers control 1 indoor unit. (Refer to Fig. 23)

Fig. 21
1 remote controller control
Outdoor unit
1 2 3

Indoor unit
1 2 3
P1 P2

(NOTE. 2)
Remote controller
(Optional accessory)

(NOTE. 2)

P1 P2

Fig. 23

Fig. 22

2 remote controllers control

Group control
Outdoor unit

Outdoor unit

1 2 3

Outdoor unit

1 2 3

Indoor unit

Outdoor unit
1 2 3

1 2 3

Indoor unit

Indoor unit

Indoor unit

1 2 3

1 2 3

1 2 3

1 2 3
P1 P2

P 1 P2

P1 P2

(NOTE. 2)

(NOTE. 2)
(NOTE. 2)

P1 P2

P 1 P2

(NOTE. 2) (NOTE. 2)

Remote controller
(Optional accessory)

(NOTE. 2)

(NOTE. 2)
(NOTE. 2)

(NOTE. 2)
P1 P2

P1 P2

(NOTE. 2)

Remote controllers
(Optional accessories)

NOTE
1. All transmission wiring except for the remote controller wires is polarized and must match the terminal symbol.
2. Connect a shielded portion with the grounding terminal for remote controller inside the control box. (Also,
connect the ground for the remote control to a grounded metal part.)
3. For group control remote controller, choose the remote controller that suits the indoor unit which has the
most functions (as attached swing flap)

15
3P156215-8K

Installation of Indoor / Outdoor Unit

205

Installation of Indoor Unit

EDSG281001

11. FIELD SETTING


<Field setting must be made from the remote controller in accordance with the installation condition.>
Setting can be made by changing the Mode No., FIRST CODE NO. and SECOND CODE NO..
For setting procedures and instructions, refer to the FIELD SETTING in the installation manual of the
remote controller.

1. Setting external static pressure


Change the SECOND CODE No. according to Table 3 depending on the resistance of the connecting duct.
(SECOND CODE NO. is factory set to 01 normal.)
Table 3
External static pressure

Mode No.

FIRST CODE NO.

SECOND CODE NO.

Normal: 49Pa (5 mmH2O)

01

High static pressure:


88 Pa (9 mmH2O)

13 (23)

02

Low static pressure: 20Pa


(2 mmH2O)

03

2. Setting with installing optional accessories


Refer to the installation manual of the optional accessories for the optional accessories installation.

3. Setting air filter sign <Filter : Field supplied parts>


Remote controllers are equipped with liquid crystal display air filer signs to display the time to clean air
filters.
Change the SECOND CODE No. according to Table 4 depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to 01 for filter contamination-light)
Table 4
Setting

Spacing time of display air filter


sign (long life type)

Air filter
contamination-light

Approx. 2500 hrs

Air filter
contamination-heavy

Approx. 1250 hrs

Mode No.

FIRST CODE
NO.

10 (20)

SECOND
CODE NO.
01
02

4. When implementing group control


When using as a pair unit or as a parent unit for simultaneous operation multi, you may simultaneous
start/stop (group) control up to 16 units with the remote controller.
In this case, all the indoor units in the group will operate in accordance with the group control remote
controller.
Select a remote controller which matches as many of the functions (swing flap, etc) in the group as
possible.

Indoor unit 1

Indoor unit 2

Indoor unit 3

Group control remote control

Fig. 24

Wiring Method
(1)Remove the control box lids. (See 9. ELECTRIC WIRING WORK.)
(2)Cross-wire the terminal block for remote controller (P1, P2) inside the control box. (There is no
polarity.) (Refer to Fig. 22 on page 15 and Table 2 on page 13)

5. Control by 2 remote controllers (Controlling 1 indoor unit by 2 remote controllers)


When using 2 remote controllers, one must be set to MAIN and the other to SUB.
16
3P156215-8K

206

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

MAIN/SUB CHANGEOVER
(1)Insert a
screwdriver into the recess between the upper and lower part of remote controller and,
working from the 2 positions, pry off the upper part. (The remote controller PC board is attached to
the upper part of remote controller.) (Refer to Fig. 25)
(2)Turn the MAIN/SUB changeover switch on one of the two remote controller PC board to S.
(Leave the switch of the other remote controller set to M.) (Refer to Fig. 26)

Upper part of remote controller

S
M

(Factory setting)
S
M

Lower part of
remote
controller
Insert the screwdriver here and gently
work off the upper part of remote controller.
Fig. 25

Remote controller
PC board

(Only one remote controller


needs to be changed
if factory settings have
remained untouched.)
Fig. 26

Wiring Method (See 9. ELECTRIC WIRING WORK on page 12)


(3)Remove the control box lids.
(4)Add remote control 2 (slave) to the terminal block for remote controller (P1, P2) in the control
box. (There is no polarity.) (Refer to Fig. 23 on page 15 and Table 2 on page 13)

12. TEST OPERATION


Refer to the section of FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED .
After finishing the construction of refrigerant piping, drain piping, and electric wiring, conduct test operation
accordingly to protect the unit.

1. How to test operation


1.
2.
3.
4.
5.

Open the gas side stop valve.


Open the liquid side stop valve.
Electrify crank case heater for 6 hours (Not required in case of a unit exclusively designed for cooling only).
Set to cooling operation with the remote controller and start operation by pushing ON/OFF button (
).
Press INSPECTION/TEST OPERATION button (
) 4 times (2 times for wireless remote controller)
and operate at Test Operation mode for 3 minutes.
6. Press INSPECTION/TEST OPERATION button (
) and operate normally.
7. Confirm function of unit according to the operation manual.
TEST

TEST

PRECAUTIONS
Refer to the diagnoses below if the unit does not operate properly.
After completing the test run, press the INSPECTION/TEST OPERATION button once to put the
unit in inspection mode, and make sure the Malfunction code is 00 (=normal).
If the code reads anything other than 00, refer to the malfunction diagnoses below.
NOTE
If a malfunction is preventing operation, refer to the malfunction diagnoses below.

2. Cautions for servicing


With the power on. Troubles can be monitored on the remote controller.
If the air conditioner does not operate normally after installing the air conditioner, a malfunction shown
in the table below may happened.

17
3P156215-8K

Installation of Indoor / Outdoor Unit

207

Installation of Indoor Unit

EDSG281001

Remote control display

No display

88*
88 flashing

Malfunction

Power supply trouble or Open phase connection


Wrong wiring between indoor and outdoor unit
Indoor PC board faulty
Wrong remote control connection wiring
Remote control faulty
Fuse faulty
Indoor PC board faulty
Wrong wiring between indoor and outdoor unit
Wrong wiring between indoor and outdoor unit

* After turning on the power, the maximum is 90 seconds, although it will only display 88. This is not
a problem, and it will be set for 90 seconds.
Trouble shooting with the display on the liquid crystal display remote controller.
With the wired remote controller. (NOTE 1)
When the operation stops due to trouble, operation lamp flashed, and
and the Malfunction
code are indicated on the liquid crystal display. In such a case, diagnose the fault contents by refering
to the table on the Malfunction code list it case of group control, the unit No. is displayed so that the
indoor unit no with the trouble can be recognized. (NOTE 2)
NOTE
1. In case wired remote controller. Press the INSPECTION /TEST OPERATION button on remote controller,
starts flashing and changes the inspection mode.
2. Keep pressing the ON/OFF button for 5 seconds or longer in the inspection mode and the above trouble history disappears, after the Malfunction code goes on and off twice, followed by the code
00(normal). The display changes from the inspection mode to the normal mode.
CAUTION
If the interior finish work is not completed yet at the time when the commissioning of the system is
finished, instruct the user not to operate the unit until the interior finish work is completed for protection of the indoor unit. If the unit is operated before the interior finish work is completed, the indoor
unit may be contaminated by substances generated from paint and adhesives used during the interior finish work and cause a splash or a water leak.

3. Malfunction code
For places where the malfunction code is left blank, the
indication is not displayed. Though the
system continues operating, be sure to inspect the system and make repairs as necessary.
Depending on the type of indoor or outdoor unit, the malfunction code may or may not be displayed.
Code

Malfunction/Remarks

A1

Indoor units PC board faulty

A3

Drain water level abnormal

A5

Freeze-up protector or stopped by high pressure control

A6

Indoor fan motor overloaded, overcurrent or locked

AF

Humidifier faulty

AH
AJ

Air cleaner faulty


Only the air cleaner does not function.
Type set improper
Capacity data is wrongly proset. Or there is nothing programmed in the data hold IC.

C4

Sensor (R2T) for heat exchanger temperature is fault

C5

Sensor (R3T) for heat exchanger temperature is fault

C9

Sensor for suction air temperature is fault

18
3P156215-8K

208

Installation of Indoor / Outdoor Unit

EDSG281001

CJ
E0

Installation of Indoor Unit

Sensor for remote controller is fault


The remote controller thermistor does not function, but the system thermo run is possible.
Action of safety device (outdoor unit)

E1

Outdoor units PC board faulty

E3

High pressure abnormal(outdoor unit)

E4

Low pressure abnormal (outdoor unit)

E5

Compressor motor lock malfunction

E6

Compressor motor lock by over current (outdoor)

E7

Outdoor fan motor lock malfunction


Outdoor fan instantneous overcurrent malfunction

E8

Input overcurrent (outdoor unit)

E9

Electronic expansion valve faulty (outdoor unit)

EA

Cooling/heating switch malfunction (outdoor)

F3

Discharge pipe temperature abnormal (outdoor unit)

F6

High pressure control (in cooling)

H3

High pressure switch faulty (outdoor unit)

H4

Low pressure switch faulty (outdoor unit)

H6

Faulty position detection sensor (outdoor unit)

H7

Outdoor motor position signal malfunction

H8

CT abnormality (outdoor unit)

H9

Outdoor air thermistor faulty (outdoor unit)

J3

Discharge pipe thermistor faulty (outdoor unit)

J5

Suction pipe thermistor faulty (outdoor unit)

J6

Heat exchanger thermistor faulty (outdoor unit)

J8

Liquid piping thermistor malfunction (heating) (outdoor)

J9

Gas piping thermistor malfunction (cooling) (outdoor)

L3

Electrical parts heat fault

L4
L5
L8
L9

Overheated heat-radiating fin (outdoor)


Inverter cooling defect.
Instantaneous overcurrent (outdoor)
Possible earth fault or short circuit in the compressor motor.
Electric thermal (outdoor)
Possible electrical overload in the compressor or cut line in the compressor motor.
Stall prevention (outdoor)
Compressor possibly locked.

LC

Transmission malfunction between the outdoor control units inverters (outdoor)

P1

Open-phase or main circuit low voltage (outdoor)

P3

PC-board temperature sensor malfunction (outdoor)

P4

Heat-radiating fin temperature sensor malfunction (outdoor)

PJ
U0
U1

Type set improper (outdoor unit)


Capacity data is wrongly proset. Or there is nothing programmed in the data hold IC.
Suction pipe temperature abnormal or refrigerant shortage
Reverse phase
Reverse two of the L1,L2and L3 leads.

19
3P156215-8K

Installation of Indoor / Outdoor Unit

209

Installation of Indoor Unit

U2

EDSG281001

Power source voltage malfunction


Includes the defect in 52C.
Transmission error (indoor unit outdoor unit)

U4
UF

U5
U8

Incorrect wiring between indoor and outdoor units or malfunction of the PC board
mounted on the indoor and the outdoor units.
If UF is shown, the wiring between the indoor and outdoor units is not properly wired.
Therefore, immediately disconnect the power supply and correct the wiring. (The compressor and the fan mounted on the outdoor unit may start operation independent of
the remote controller operation.)
Transmission error (indoor unit remote controller)
Transmission is improper between the indoor unit and the remote controller.
Malfunction in transmission between main and sub remote controls.
(Malfunction in sub remote control.)
Miss setting for multi system

UA

Setting is wrong for selector switch of multi-system. (see switch SS2 on the main units
PC board)
Incorrect combination with indoor unit and outdoor unit

UC

Central control address overlapping

20
3P156215-8K

210

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

2.5

FBQ71DV1 / FBQ100DV1 / FBQ125DV1 / FBQ140DV1

2.5.1

Names and Functions of Parts

j k l

2
RZR100 125 140
f e

nd

RZR71

b
d

h
e

a
b
c
d
e
f
g
h
i
j
k
l
m
n
p

Indoor unit
Outdoor unit
Remote controller
Depending on the system configuration, the remote
controller is not provided.
Inlet air
Discharge air
Air outlet (Field supply)
Exhaust duct (Field supply)
Refrigerant piping, connection electric wire
Drain pipe
Model name (model name plate)
Air filter (Sold separately)
Suction filter chamber (Sold separately)
Suction duct (Field supply)
Suction grille (Field supply)
Ground wire
The line passes electricity from the inside unit to the
ground to prevent accidental electrical shock.
C : 3PN11586-1

Installation of Indoor / Outdoor Unit

211

Installation of Indoor Unit

2.5.2

EDSG281001

Installation

FBQ71DV1
FBQ100DV1
FBQ125DV1
FBQ140DV1

SPLIT SYSTEM Air Conditioner

Installation manual

CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.

SAFETY PRECAUTIONS................................................................................................1
BEFORE INSTALLATION ...............................................................................................3
SELECTING INSTALLATION SITE.................................................................................6
PREPARATIONS BEFORE INSTALLATION ..................................................................7
INDOOR UNIT INSTALLATION ......................................................................................9
REFRIGERANT PIPING WORK .....................................................................................9
DRAIN PIPING WORK ..................................................................................................12
DUCT WORK ................................................................................................................14
ELECTRIC WIRING WORK ..........................................................................................15
WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER.....................16
FIELD SETTING............................................................................................................20
TEST OPERATION .......................................................................................................23
WIRING DIAGRAM .....................................................................................................27

1. SAFETY PRECAUTIONS
Please read the these " SAFETY CONSIDERATIONS" carefully before installing air conditioning unit and be
sure to install it correctly. After completing the installation, make sure that the unit operates properly during the
start-up operation.
Please instruct the customer on how to operate the unit and keep it maintained.
After completing installation, conduct a trial operation to check for faults and explain to the customer how to
operate the air conditioner and take care of it with the aid of the operation manual. Ask the customer to store
the installation manual along with the operation manual for future reference.
This air conditioner comes under the term appliances not accessible to the general public.
Meaning of WARNING and CAUTION notices.
WARNING .........Failure to follow these instructions properly may result in personal injury or loss of life.
CAUTION ..........Failure to observe these instructions properly may result in property damage or
personal injury, which may be serious depending on the circumstances.
WARNING
Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage,
electric shocks or fire.
Install the air conditioner in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shocks or fire.
Consult your local dealer regarding what to do in case of refrigerant leakage, when the air coditioner is to
be installed in a small room, it is necessary to take proper measures so that the amount of any leaked
refrigerant does not exceed the concentration limit in the event to leakage. Otherwise, this may lead to an
accident due to oxygen depletion.
Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.

3PN11585-1

212

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
A foundation of insufficient strength may result in the equipment falling and causing injury.
Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit falling and causing accidents.
Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried
out by qualified personnel according to local laws and regulations and this installation manual.
An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.
Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal
connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or fire.
When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the
wires so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric shocks, fire or overheating terminals.
If refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into contact with fire.
After completing installation, check for refrigerant gas leakage.
Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source
of fire, such as a fan heater, stove or cooker.
Be sure to switch off the unit before touching any electrical parts.
Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may
result in electric shocks or fire.
A high surge current from lightning or other sources may cause damage to the air conditioner.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks or fire.
Do not directly touch refrigerant that has leaked from refrigerant pipes or other areas, as there is a danger
of frostbite.
After completing installation, check for refrigerant gas leakage. Toxic gas may be produced if the refrigerant
gas leaks into the room and comes into contract with a source of fire, such as a fan heater, stove or cooker.
Do not allow children to climb on the outdoor unit and avoid placing objects on the unit.
Injury may result if the unit becomes loose and falls.

CAUTION
While following the instructions in this installation manual, install drain piping to ensure proper drainage and
insulate piping to prevent condensation.
Improper drain piping may result in indoor water leakage and property damage.
Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televisions
or radios to prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 1 meter may not be sufficient to eliminate noise.)
Remote controller (wireless kit) transmitting distance can be shorter than expected in rooms with electronic
fluorescent lamps (inverter or rapid start types).
Install the receiver as far away from fluorescent lamps as possible.
In a domestic environment this product may cause radio interference in which case the user may be
required to take adequate measures.
Do not install the air conditioner in the following locations:
1. Where there is a high concentration of mineral oil spray or vapour (e.g. a kitchen).
Plastic parts will deteriorate, parts may fall off and water leakage could result.
2. Where corrosive gas, such as sulphurous acid gas, is produced.
Corroding of copper pipes or soldered parts may result in refrigerant leakage.
3. Near machinery emitting electromagnetic radiation.
Electromagnetic radiation may disturb the operation of the control system and result in a malfunction of the unit.
4. Where flammable gas may leak, where there is carbon fibre or ignitable dust suspensions in the air, or
where volatile flammables such as paint thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.
Make sure to provide for adequate measure in order to prevent that the outdoor unit be used as a shelter
by small animals.

3PN11585-1

Installation of Indoor / Outdoor Unit

213

Installation of Indoor Unit

EDSG281001

Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct
the customer to keep the area around the unit clean
Install in a machine room that is free of moisture. The unit is designed for indoor use.
Disposal requirements Dismantling of the unit, treatment of the refrigerant, of the oil and of other parts must
be done in accordance with relevant local and national legislation.

1-2 SPECIAL NOTICE OF PRODUCT


Refrigerant
The refrigerant R410A requires that strict Precautions be observed for keeping the system clean, dry
and tightly sealed
A. Clean and Dry
Strict measure must be taken to keep impurities (including SUNISO oil and other mineral oils as well
as moisture) out of the system
B. Tightly
R410A will contribute only slightly to the greenhouse effect if released into the atmosphere.
Therefore, sealing tightness is particularly important in installation. Carefully read the chapter
REFRIGERANT PIPING and strictly observe the correct procedures.
Since design pressure is 4.0MPa or 40 bar the thickness of pipes must be greater than previously.
Since R410A is a mixed refrigerant, the required additional refrigerant must be changed its liquid state.
(If the system is charged with refrigerant in its gaseous state, due to composition change, the system will
not function normally)
The indoor units are designed for R410A use. See the catalogue for indoor unit models that can be
connected (Normal operation is not possible when connecting units that are originally designed for other
refrigerants)

2. BEFORE INSTALLATION
Hold the hanging brackets in the case of moving the indoor and outdoor units at the time of and
after opening the packages. Do not impose undue force on other parts, such as the refrigerant
piping, drain piping, or flanges, in particular.
Be sure to check the type of R410A refrigerant to be used before installing the unit. (Using an incorrect
refrigerant will prevent normal operation of the unit.)
The accessories needed for installation must be retained in your custody until the installation work is
completed. Do not discard them!
Decide upon a line of transport.
Leave the unit inside its packaging while moving, until reaching the installation site. Where unpacking is
unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid
damage or scratches to the unit.
When moving the unit or affter opening, hold the unit by the hanger brackets ( 4). Do not apply force to the
refrigerant piping, drain piping, flanges or plastic parts.
For the installation of outdoor unit, refer to the installation manual attached to the outdoor unit.
Do not install or operate the unit in rooms mentioned below.
Laden with mineral oil, or filled with oil vapor or spray like in kitchens. (Plastic parts may
deteriorate which could eventually cause the unit to fall out of place, or could lead to leaks.)
Where corrosive gas like sulfurous gas exists. (Copper tubing and brazed spots may corrode
which could eventually lead to refrigerant leaks.)
Where exposed to combustible gases and where volatile flammable gas like thinner or gasoline
is used. (Gas in the vicinity of the unit could ignite.)
Where machines can generate electromagnetic waves. (Control system may malfunction.)
Where the air contains high levels of salt such as that near the ocean and where voltage
fluctuates greatly such as that in factories.
Also in vehicles or vessels.
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment.
If installed as a household appliance it could cause electromagnetic interference.

3PN11585-1

214

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

2-1 PRECAUTIONS
Be sure to read this manual before installing the indoor unit.
Entrust installation to the place of purchase or a qualified serviceman. Improper installation could lead to
leaks and, in worse cases, electric shock of fire.
Use only parts provided with the unit or parts satisfying required specifications. Unspecified parts could
cause the unit to fall out of place, or could lead to leaks and, in worse cases, electric shock or fire.
Be sure to mount an air filter (part to be procured in the field) in the suction air passage in order to prevent
water leaking, etc.

2-2 ACCESSORIES
Check that the following accessories are provided and that each accessory is correct in amount.
Refer to the Fig. 1 of this sheet.
[PRECAUTION]
The accessories are required for the installation of the air conditioner. Be sure to keep them until the
installation work is completed.

(1) - (13)

Operation manual
Installation manual
Fig. 1
Name

Metal clamp (1)

Drain hose (2)

Quantity

1 pc.

1 pc.

Screws for duct


flanges (3)
As described in table
below

M516
Shape

71 type
100 125
140 type

Name

Sealing pad

Clamp (8)

Quantity

9 pcs.

Shape

1 pc.
Large (Dark gray) (6)

18
26

Washer fixing plate


(9)
4 pcs.

Insulation for fitting


1 each

Thin
for liquid pipe (4)
Thick
for gas pipe (5)
Wire sealing material
(10)
2 pcs.

Small (Gray)
2 pcs.
Middle (Dark gray) (7)

3PN11585-1

Installation of Indoor / Outdoor Unit

215

Installation of Indoor Unit

EDSG281001

Name

Washer (11)

Quantity

8 pcs.

Wire fixing bracket


(12)
2 pcs.

Wire fixing screw


(13)
2 pcs.

M48

Shape

(Other)
Operation manual
Installation manual

2-3 OPTIONAL ACCESSORIES


These are two types of remote controllers: wired and wireless. Select a remote controller according to
customer request and install in an appropriate place.
Table 1
Remote controller
Wired type
Wireless type

BRC1C61
BRC4C62

NOTE
If you wish to use a remote controller that is not listed in Table 1, select a suitable remote controller
after consulting catalogs and technical materials.
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER
INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
Items to be checked
Are the indoor and outdoor unit fixed firmly?
Was the installation of the outdoor unit
completed?
Is the gas leak test finished?
Is the unit fully insulated? (Refrigerant
piping, drain piping, and duct)
Dose drainage flow smoothly?
Does the power supply voltage conform to
the indication on the name plate?
Are wiring and piping correct?
Is the air conditioner properly grounded?
Is wiring size according to specifications?
Is something blocking the air outlet or inlet of
either the indoor or outdoor units?
Did you set the external static pressure?
Are refrigerant piping length and additional
refrigerant charge noted down?
Did you check that no wiring connection
screws were loose?

If not properly done, what is likely to occur.


The units may drop, vibrate or make noise.
The unit may malfunction or the components
burn out.
No cooling or heating.

Check

Condensate water may drip.


Condensate water may drip.
The unit may malfunction or the components
burn out.
The unit may malfunction or the components
burn out.
Dangerous in case of current leakage.
The unit may malfunction or the components
burn out.
No cooling or heating.
No cooling or heating.
The refrigerant charge in the system is not
clear.
Electric shock or fire.

Also review the SAFETY PRECAUTIONS.

3PN11585-1

216

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

b. Items to be checked at time of delivery


Items to be checked
Are you sure the control box lid, air filter, air inlet grille, and air outlet grille are mounted?
Did you explain about operations while showing the operation manual to your customer?
Did you deliver the operation manual along with the installation manual to the customer?
Did you explain the customer the handling and cleaning methods of the field supplies
(e.g., the air filter, air inlet grilles, and air outlet grille)?
Did you deliver instruction manual, if any, for the field supplies to the customer?

Check

c. Points for explanation about operations


The items with WARNING and CAUTION marks in the operation manual are the items pertaining to
possibilities for bodily injury and material damage in addition to the general usage of the product.
Accordingly, it is necessary that you make a full explanation about the described contents and also ask
your customers to read the operation manual.

2-4 NOTE TO INSTALLER


Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating
different functions, and adjusting the temperature) by having them carry out operations themselves
while looking at the manual.

3. SELECTING INSTALLATION SITE


Hold the hanging brackets in the case of moving the indoor and outdoor units at the time of and
after opening the packages. Do not impose undue force on other parts, such as the refrigerant
piping, drain piping, or flanges, in particular.
Add heat insulation material to the indoor unit if the temperature above the ceiling is likely to
exceed 30C and a relative humidity of 80%.
Make sure that the insulation material is made of glass wool or polyethylene foam, has a minimum
thickness of 10 mm, and can be accommodated in the opening on the ceiling.
1)Select an installation site where the following conditions are fulfilled and that meets with your customers
approval.
A place where cool (warm) air is delivered to the entire room.
Where nothing blocks the air passage.
Where condensate can be properly drained.
If supporting structural members are not strong enough to take the units weight, the unit could fall out
of place and cause serious injury.
Where the false ceiling is not noticeably on an incline.
Where there is no risk of flammable gas leakage.
Where sufficient clearance for maintenance and service can be ensured. (Refer to Fig. 2-1)
Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the
installation manual of the outdoor unit.)
CAUTION
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from
televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.)
In the case of the installation of a wireless remote controller, the transmission distance of the wireless
remote controller may be shortened if the room has a fluorescent light of electronic lighting type
(i.e., an inverter or rapid-start fluorescent light).
Keep the distance between the receiver and the fluorescent light as far as possible.

3PN11585-1

Installation of Indoor / Outdoor Unit

217

Installation of Indoor Unit

EDSG281001

Min. 450

*H2=Min. 620

(length: mm)

Min. 2500
(If no ceiling board is provided.)

Ceiling

Min. 300 *H1=300

Min. 20

2)Use hanging bolts to install the indoor unit. Check that the place of installation withstands the weight of
the indoor unit. Secure the hanging bolts with proper beams if necessary.

Floor surface

* The H1 dimension indicates the height of the


product.
* Determine the H2 dimension by maintaining
a downward slope of at least 1/100 as
specified in 7. DRAIN PIPING WORK.

Min. 700 (service space)

[Required installation place]


The dimensions indicate the
minimum required space of
installation.
Fig. 2-1

4. PREPARATIONS BEFORE INSTALLATION


1. Check the positional relationship between the ceiling opening hole and the hanging bolt of the unit.
For the maintenance, inspection, and other servicing purposes of the control box and drain pump,
prepare one of the following service spaces.
1)Inspection hatch 1 (450 450) for the control box and a minimum space of 300 mm for the lower part
of the product. (Refer to Fig. 2-2)
2)Inspection hatch 1 (450 450) for the control box and inspection hatch 2 for the lower part of the
product (see axial direction view A-1). (Refer to Fig. 2-3)
3)Inspection hatch 3 for the lower part of the product and the lower part of the control box (see axial
direction view A-2). (Refer to Fig. 2-3)

Control box

700
631
(Hanging bolt pitch)

*H3=Min. 300

Air outlet

Bottom of unit

Air inlet
Fig. 2-2

(Hanging bolt pitch)

Ceiling

Control box

Inspection hatch

Inspection hatch 1
(450450)

Case 1

Hanging bolt ( 4)

3PN11585-1

218

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Case 2, 3

Min. 200

Control box

Control box
B

Inspection hatch

Ceiling

Control box
Min. D=B+300

*H3=Min. 20

Inspection hatch
(Ceiling opening)

Inspection hatch 3
(Same as the indoor
unit size +300 or more)

Inspection hatch 1
(450450)

700

700

Inspection hatch 2
(Same as the indoor
unit size or more)
* Determine the H3 dimension by
maintaining a downward slope
of at least 1/100 as specified in
7. DRAIN PIPING WORK.

Axial direction view A-1

Axial direction view A-2


Fig. 2-3

Model
B
C
D
71 type
1000 1038 1300
100 125 140 type 1400 1438 1700

(length: mm)

2. Mount the canvas ducts to the air outlet and inlet so that the vibration of the air conditioner will not be
transmitted to the duct or ceiling. Apply a sound-absorbing material (insulation material) to the inner wall
of the duct and vibration insulation rubber to the hanging bolts (refer to 8. DUCT WORK).
3.Open installation holes (if the ceiling already exists).
Open the installation holes on the ceiling. Lay the refrigerant piping, drain piping, power line,
transmission wiring, and remote controller wiring for the piping and wiring connection port of the unit.
In the case of the installation of a wireless remote controller, refer to the installation manual provided
with the wireless remote controller.
Refer to 6. REFRIGERANT PIPING WORK, 7. DRAIN PIPING WORK, and 10. WIRING EXAMPLE
AND HOW TO SET THE REMOTE CONTROLLER.
The ceiling framework may need reinforcement in order to keep the ceiling horizontal and prevent the
vibration of the ceiling after the installation holes are opened. For details, consult your construction or
interior contractor.
4. Install the hanging bolts. Make sure that the hanging bolts are M10 in size.
Use hole-in anchors if the hanging bolts
Installation example
already exist; otherwise use embedded
inserts and embedded foundation bolts so that
Ceiling slab
they will withstand the weight of the unit.
Anchor
Adjust the distance to the ceiling surface in
advance.
Long nut or turn-buckle

Hanging bolt
Indoor unit
NOTE

All the above parts are field supplied.

3PN11585-1

Installation of Indoor / Outdoor Unit

219

Installation of Indoor Unit

EDSG281001

5. INDOOR UNIT INSTALLATION


It may be easier to install accessories (sold separately) before installing the indoor unit. Refer to the
installation manuals provided to the accessories as well.
Be sure to use the accessories and specified parts for installation work.
1) Temporally install the indoor unit.
Connect the hanging brackets to the hanging bolts. Be sure to use and tighten the nut and washer (11) for
each hanging bracket from both upper and lower sides of the hanging bracket. (Refer to Fig. 3) At that time,
the fall of the washer (11) for the hanging bracket can be prevented if the washing fixing plate (9) is used.

[Fixing hanging brackets]


Part to be procured in the field

[Fixing method of washers]


Nut on the upper side

Washer (11) (accessory)


Insert

Tighten from above and below


(Double nut)
Fig. 3

Washer fixing plate (9)


(accessory)

CAUTION
During the installation work, perform the curing of the air outlet and protect the resin drain pan of
the indoor unit from the intrusion of foreign substances, such as welding spatters.
Otherwise, water leakage may occur as a result of damage, such as hole damage, to the resin drain pan.
2) Make adjustments so that the unit will be in the right position.
3) Check the level of the unit.
4) Remove the washer fixing plates for
the falling prevention of the washers
for the hanging brackets, tighten the
nuts on the upper side, and securely
fix the unit.

Hanging bracket

Bottom of product
Level

Vinyl tube

CAUTION
Use the level and check that the unit is installed horizontally. (4-directions)
In the case of using a vinyl tube in place of the level, put the both edges of the vinyl tube in close contact
with the bottom of the product to make levelness adjustment.
If the unit is installed at a slant with the drain pipe side set high, in particular, the float switch will not operate
normally and water leakage may result.

6. REFRIGERANT PIPING WORK


As for the refrigerant piping of the outdoor unit, refer to the installation manual provided to the
outdoor unit.
Perform heat insulation work on both gas piping and liquid piping, or otherwise water leakage may
result.
Use the insulation material that withstands a temperature of 120C.

3PN11585-1

220

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Reinforce the insulation material for the refrigerant piping if the ambient temperature is high, or
otherwise dew condensation may result on the surface of the insulation material.
Make sure that the refrigerant is R410A before refrigerant piping work. If the refrigerant is different,
the air conditioner will not operate normally.

CAUTION
This product uses new refrigerant (R410A) only. Be sure to keep the items on the right-hand side and
conduct the installation work.
Use a dedicated pipe cutter and flare tool for R410A.
When connecting the flare, apply ether oil or ester oil to the flare.
Be sure to use the flare nut provided with the unit. (Do not use a different flare nut (such as a
type-1 flare nut), or otherwise refrigerant leakage may result.)
Perform the curing of the piping with pinching or taping of the piping in order to prevent the
intrusion of dirt, dust, and moisture into the piping.
CAUTION
Be sure to use the specified type of refrigerant for the refrigeration cycle and do not contaminate
the refrigerant with air.
Ventilate the room in case of refrigerant leakage during installation work.
1) Connect the piping.
The outdoor unit is filled with refrigerant.
When connecting or disconnecting piping to or
from the unit, be sure to use two spanners and
two torque wrenches. (Refer to Fig. 4)
Refer to Table 2 for the processing dimensions of
the flare.
Use the flare nut provided with the unit.

Torque wrench

Spanner
Flare nut
Piping union

Apply ether oil or ester oil to both inner and


outer sides of the flare and screw in the flare
nut three to four turns first by hand at the time of
connecting the flare nut. (Refer to Fig. 5)
Refer to Table 2 for the corresponding tightening
torque.

Fig. 4

Ester oil or ether oil.

Fig. 5

Table 2

6.4

14.2 17.2Nm

8.7 9.1

9.5

32.7 39.9Nm

12.8 13.2

12.7

49.5 60.3Nm

16.2 16.6

15.9

61.8 75.4Nm

19.3 19.7

Flare shape
452

Flare dimensions A (mm)

R0.4-0.8
A

Tightening torque

902

Pipe size (mm)

CAUTION
Do not excessively tighten the flare nut.
Doing so will break the flare nut and refrigerant leakage may result.
Make sure that all parts around the flare are free of oil.
The drain pan and the resin part may be deteriorated if oil is attached.
If no torque wrenches are available, refer to Table 3 as a standard.
When the flare nut is tightened with the spanner, the tightening torque should increase suddenly.
Tighten the flare nut further for the corresponding angle shown in Table 3.

10

3PN11585-1

Installation of Indoor / Outdoor Unit

221

Installation of Indoor Unit

EDSG281001

Table 3
Pipe size (mm)
6.4
9.5
12.7
15.9

Further tightening angle


60 to 90 degrees
60 to 90 degrees
30 to 60 degrees
30 to 60 degrees

Recommended arm length of tool


Approx. 150mm
Approx. 200mm
Approx. 250mm
Approx. 300mm

2) On completion of installation work, check that there is no gas leakage.


3) Refer to the illustration on the right-hand side and be sure to perform heat insulation work on the piping
joints after gas leakage checks. (Refer to Fig. 6)

Heat insulation procedure for liquid piping


Insulation for fitting (4) (accessory)
Flare nut joint

Insulation material for piping


(on unit side)

Make sure that the seam faces upward.

Attached to the surface.

Middle sealing pad (7) (accessory)

Main unit
Clamp (8) (accessory)
Wrap the insulation material around the
portion from the surface of the main unit
to the upper part of the flare nut joint.

Insulation material for piping (field supply)

Liquid pipe

Gas pipe
Fig. 6
Heat insulation procedure for gas piping
Insulation for fitting (5) (accessory)
Insulation material for piping
(on unit side)
Attached to the surface.

Flare nut joint


Make sure that the seam faces upward.
Middle sealing pad (7) (accessory)

Clamp (8) (accessory)

Insulation material for piping (field supply)

Wrap the insulation material around the


portion from the surface of the main unit
to the upper part of the flare nut joint.

Use the insulation for fitting (4) and (5) provided to the liquid piping and gas piping, respectively, and
conduct heat insulation work.
(Tighten both edges of the insulation for fitting (4) and (5) for each joint with the clamp (8).)

11

3PN11585-1

222

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

Make sure that the joint of the insulation for fitting (4) and (5) for the joint on the liquid piping and gas
piping side faces upward.
Wrap the middle sealing material (7) around the insulation for fitting (4) and (5) for the joint (flare nut part).

CAUTION
Be sure to perform the heat insulation of the local piping up to the piping joint.
If the piping is exposed, dew condensation may result. Furthermore, a burn may be caused if a human body
comes in contact with the piping.
Perform nitrogen substituent or apply nitrogen into the refrigerant piping (see NOTE
1) in the case
of refrigerant piping blazing (see NOTE
2). Then perform the flare connection of the indoor unit.
(Refer to Fig. 7)

Refrigerant
piping

Pressurereducing valve
Part to be
brazed

Taping
hands
valve

Nitrogen
Fig. 7

Nitrogen

CAUTION
Do not use any antioxidant at the time of piping blazing.
The piping may be clogged with a residual antioxidant and parts may malfunction.
NOTE
1. At the time of blazing, set the pressure of nitrogen to approximately 0.02 MPa (close to the pressure of
a breeze coming in contact with the cheek) with a decompression valve.
2. Do not use flux at the time of blazing and connecting the refrigerant piping. Use a copper phosphorus
brazing alloy (BCuP-2: JIS Z 3264/BCu 93P-710/795: ISO3677), which does not require flux, for blazing.
(Flux has a bad influence on the refrigerant piping. Chlorine-based flux will cause piping corrosion.
Furthermore, if it contains fluorine, the flux will deteriorate refrigerant oil.)
As for the branching of the refrigerant piping or refrigerant, refer to the installation manual provided with the
outdoor unit.

7. DRAIN PIPING WORK


1) Remove the drain socket cover. (for transportation)
2) Conduct drain piping work.
Check that the piping ensures proper draining.
Make sure that the diameter of the piping excluding the rising
part is the same as or larger than the diameter of the
connecting pipe (vinyl chloride pipe with an outer diameter of
32 mm and a nominal inner diameter of 25 mm).
Make sure that the piping is short enough with a downward
slope of at least 1/100 and that there is no air bank formed.
No drain trap is required.

Refrigerant
piping
Screw (4 portions)
Drain socket
Drain socket cover
(for transportation)

CAUTION
The drain piping will be clogged with water and water leakage may result if the water is accumulated in the
drain piping.

12

3PN11585-1

Installation of Indoor / Outdoor Unit

223

Installation of Indoor Unit

EDSG281001

Conduct drain-up piping work if the gradient is insufficient.


Attach a support bracket at 1 to 1.5 m intervals for the prevention of piping deflection.

Support bracket

1 - 1.5 m

Downward slope of at least 1/100


Be sure to use the drain hose (2) and metal clamp (1).
Insert the drain hose (2) deep into the base of the drain
socket, and securely fasten the metal clamp (1) within the
taped part on the insertion front end of the hose.
Be sure to fasten the screw of the metal clamp (1) until the
Tape
margin of the screw thread decreases to 4 mm or less.

Metal clamp (1)


(accessory)

Drain hose (2)


(accessory)

Min. 100 mm

NOTE
Be sure to follow the instructions as below.
Do not connect the drain piping directly to a sewer that smells of ammonia.
The ammonia in the sewer may reach through the drain piping and corrode the heat exchanger of the
indoor unit.
Do not bend or twist the provided drain hose (2) in order not to impose excessive force on the hose.
(Doing so may result in water leakage.)
Take the procedure shown in the following illustration to perform concentrated drain piping.

Concentrated drain piping


Maintain a downward slope of at least
1/100 so that no air bank will be formed.
The drain piping will be clogged with
water and water leakage may result if the
water is accumulated in the drain piping.

Select the diameter of the concentrated drain piping to suit the capacity of equipment connecting to the
concentrated drain piping (see the equipment design sheet).

Ceiling slab
1 - 1.5 m

Support bracket

Metal clamp (1) (accessory)


Drain hose (2) (accessory)
3) Check the smooth draining of the piping on completion of the installation of the piping.
Provide approximately one liter of water gradually into the drain pan through the water inlet on the
bottom of the drain socket or the outlet.

13

3PN11585-1

224

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

4) Be sure to conduct heat insulation work on the following portions, or otherwise water leakage may
occur as a result of dew condensation.
Drain piping indoors
Water inlet
Drain socket
Drain pan
Refrigerant piping

Air outlet

Water inlet lid


Screw
Drain socket

Plastic water
container

On completion of the drainage check, refer to the following illustration, and use the provided large
sealing pad (6) and heat insulate the metal clamp (1) and drain hose (2).

Make sure that the


seam faces upward.

Large sealing pad (6)


(accessory)
Metal clamp (1)
(accessory)

4 mm max.

8. DUCT WORK
Pay the utmost attention to the following items and conduct the duct work.
Check that the duct will not be in excess of the setting range of external static pressure for the unit.
(Refer to the technical datasheet for the setting range.)
Attach a canvas duct each to the air outlet and air inlet so that the vibration of the equipment will not be
transmitted to the duct or ceiling.
Use a sound-absorbing material (insulation material) for the lining of the duct and apply vibration insulation
rubber to the hanging bolts.
At the time of duct welding, perform the curing of the duct so that the sputter will not come in contact with
the drain pan for the filter.
If the metal duct pass through a metal lath, wire lath, or metal plate of a wooden structure, separate the duct
and wall electrically.
Be sure to heat insulate the duct for the prevention of dew condensation. (Material: Glass wool or styrene
foam; Thickness: 25 mm)
Be sure to attach the field supply air filter to the air inlet of the unit or field supply inlet in the air passage on
the air suction side. (Be sure to select an air filter with a duct collection efficiency of 50 weight percent.)
Explain the operation and washing methods of the locally procured components (i.e., the air filter, air inlet
grille, and air outlet grille) to the customer.
Locate the air outlet grille on the indoor side for the prevention of drafts in a position where indirect contact
with people.

14

3PN11585-1

Installation of Indoor / Outdoor Unit

225

Installation of Indoor Unit

EDSG281001

The air conditioner incorporates a function to adjust the fan to rated speed automatically. (11. FIELD SETTING)
Therefore, do not use booster fans midway in the duct.
Connection method of ducts on air inlet and outlet sides.
Connect the field supply duct in alignment with the inner side of the flange.
Connect the flange and unit with the flange connection screw (3).
Wrap aluminum tape around the flange and duct joint in order to prevent air leakage.

Flange on air inlet side


(provided with the unit)

Flange on air outlet side


(provided with the unit)
Insulation material
(field supply)

Screws for duct


flanges (3)
(accessory)

Air inlet

Insulation material
(field supply)

Unit

Air outlet
Canvas duct
(field supply)

Screws
for duct
flanges (3)
(accessory)

CAUTION
Connect the flange and unit with the flange connection screw (3) regardless of whether the duct is
connected to the air inlet side.

9. ELECTRIC WIRING WORK

All field supplied parts and materials and electric works must conform to local codes.
Use copper wire only.
For electric wiring work, refer to also Wiring diagram attached to the control box lid.
For remote controller wiring details, refer to the installation manual attached to the remote controller.
All wiring must be performed by an authorized electrician.
A circuit breaker capable of shutting down power supply to the entire system must be installed.
Be sure to install an earth leakage breaker.
Install a wiring interrupter or ground-fault circuit interrupter for the power wiring.
Make sure the earth resistance is no greater than 100 .
Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected
to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
Be sure to ground the air conditioner.
Do not connect the ground wire to gas and water pipes, lightning rods, or telephone ground wires.
Gas pipes : might cause explosions or fire if gas leaks.
Water pipes : no grounding effect if hard vinyl piping is used.
Telephone ground wires or lightning rods : might cause abnormally high electric potential in the ground
during lighting storms.
Specifications for field wire
Field fuses

Wiring the units


Power supply wiring
(for Fan)
Remote controller cord
(In case of installing the
control panel separately)

Wire

Size (mm )

Length

H05VV-U4G
( NOTE
1)

2.5

15A

H05VV-U2

2.5

Vinyl cord with sheath or


cable (2 wire)( NOTE
2)

0.75 - 1.25

Max. 500m

NOTE
1. Shows only in case of protected pipes. Use H07RN-F in case of no protection.
2. Insulated thickness : 1mm or more.
15

3PN11585-1

226

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

10. WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER


10-1 CONNECTING WIRING THE UNITS, POWER SUPPLY, GROUND, AND REMOTE
CONTROLLER WIRING

(Remove the control box lid as shown below and connect each wire.)
1) Remove the control box lid.

Screw
(3 portions)

2) Lay the wires in the control box


through the wire inlet on the side of
the control box.

Low-voltage wiring inlet


Remote controller wiring
(Low voltage)

High-voltage wiring inlet


Wiring the units (High voltage)
Power supply wiring (High voltage)
Ground wiring (High voltage)
CAUTION
Do not lay the remote controller wiring along with the wiring the units, power supply wiring or other electric
wiring in the same route. Separate the remote controller wiring at least 50 mm from the wiring the units,
power supply wiring or other electric wiring, or otherwise malfunctions or failures may be caused by
external electric noise that may interfere with the remote controller wiring.
For the installation and wiring of the remote controller, refer to the remote controller installation manual
provided with the remote controller.
For wiring the units, power supply wiring, refer to the wiring diagram as well.
Be sure to connect the remote controller wiring correctly to the right terminal block.

16

3PN11585-1

Installation of Indoor / Outdoor Unit

227

Installation of Indoor Unit

EDSG281001

3) Follow the instructions below, and lay the wires in the control box.

Fix the wires with


clamp (8) to the wire
fixing bracket
provided to the
control box.
Wiring the units
(High voltage)
Power supply wiring
(High voltage)
Ground wiring
(High voltage)

Remote controller
wiring (Low voltage)

Insert the cord


into the wire clips
provided with the
control box.
PROHIBITED
Never connect wiring the units
and the power supply wiring.
P1 P2 F1 F2

Power supply terminals (X1M)

Ground 1 2 3 L N

Power supply
Wiring
the units wiring
Connection method of
power supply terminals

Remote controller
wiring (No polarity)
Twist and fix the upper part so
that the wires will not drop out.
Fix the cord with the
clamp (8) to the wire
fixing bracket provided
to the control box.

Connection method of remote


controller terminals (X2M)
If stranded wires are used,
do not solder the front end
of the wires.

WARNING
Trim and lay the wiring neatly and attach the control box lid securely.
An electric shock or fire may result if the control box lid catches any wiring or the wires push up the lid.
4) Put the control box lid, and wrap the wire sealing
material (Small) (10) around the wires so as to
block the wire through holes.

Wire through holes

CAUTION
After all the wiring connections are done, fill in any gaps in the through holes with putty or insulation
(procured locally) to prevent small animals and insects from entering the unit from outside. (If any do get in,
they could cause short circuits in the control box.)

17

3PN11585-1

228

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

5) Mount the provided wire fixing bracket (12) with


the wire fixing screw (13). Fix each wire with the
provided clamp (8).

Remote controller
wiring
Wiring the units
Power supply wiring
Ground wiring

Fixing use Clamp (8) (accessory)

Wire fixing bracket (12) (accessory)


Wire fixing screw (13) (accessory)
[Precautions for Wiring the Units and power
supply wiring]
Connect round crimp-style terminals provided with
insulation sleeves to the terminal block for power
supply.
Be sure to follow the instructions provided below if
the specified terminals cannot be used.
Otherwise, abnormal heat may be generated as
a result of the loosening of the wires.

Connect the wires


evenly.

Attach insulation sleeve

Round crimp-style terminal

Do not connect a
wire to the single
side only.

Electric wire

Do not connect
wires different
from each other in
diameter.

If stranded wires are used, do not solder the front end of the wires.
Connect proper wires securely and fix the wires so that external force will not be imposed on the terminals.
Use an appropriate screwdriver to tighten the terminal screws. The screw heads may be damaged if the
screwdriver is too small and the terminal screws will not be tightened properly.
Do not tighten the terminal screws excessively, or otherwise the screw heads may be damaged.
Refer to the table below for the required tightening torque values of the terminal screws.
Terminal block for remote controller and transmission wires
Terminal block for power supply, and wiring the units

Tightening torque (Nm)


0.80 - 0.96
1.18 - 1.44

10-2 WIRING EXAMPLE


WARNING
Install an earth leakage breaker.
The installation of an earth leakage breaker is imperative for the prevention of electric shocks and fire
accidents.

18

3PN11585-1

Installation of Indoor / Outdoor Unit

229

Installation of Indoor Unit

EDSG281001

(For the wiring of outdoor units, refer to the installation manual attached to the outdoor unit.)
Confirm the system type.
Pair type: 1 remote controller controls 1 indoor unit. (standard system)
2 remote controllers control: 2 remote controllers control 1 indoor unit.
Group control: 1 remote controller controls up to 16 indoor units. (All indoor units operate according to the
remote controller)

Pair type

2 remote controllers control

Main power supply


Main switch
Fuse

Main switch
Fuse

Main power supply

Outdoor unit

Outdoor unit

1 2 3

1 2 3

Indoor unit
P1
P2

(NOTE

P1
P2

Remote controller

Remote controller
(Optional accessory)
Power supply

1
2
3
L
N

L
N

Power supply

Indoor unit

220-240V
50Hz

2)

P1
P2

P1
P2

P1
P2
1
2
3
L
N

L
N

Remote controller
(Slave)
(Optional accessories)

Indoor unit

220-240V
50Hz

Group control
Main power supply

Main power supply

Main switch
Fuse

Main switch
Fuse

Main switch
Fuse

Outdoor unit

Outdoor unit

Outdoor unit

1 2 3

1 2 3

P1 P2

Power supply
220-240V
L
50Hz N

Main power supply

P1 P2

Remote
controller
(Optional
accessory)

1 2 3

P1 P2

Power supply
1
2
3
L
N

Indoor unit

220-240V
L
50Hz N

P1 P2

Remote
controller
(Optional
accessory)

P1 P2

Power supply
1
2
3
L
N

Indoor unit

220-240V
L
50Hz N

1
2
3
L
N

P1 P2

Remote
controller
(Optional
accessory)

Indoor unit

NOTE
1. All transmission wiring except for the remote controller wires must match the terminal symbol.
2. If the unit is under 2 remote controller control, perform additional wiring of the remote controller to the
remote controller terminal board.
3. If the unit is under group control, detach the remote controller cord connecting the remote controller
terminal board and the remote controller.

19

3PN11585-1

230

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

10-3 CONTROL BY 2 REMOTE CONTROLLERS (Controlling 1 indoor unit by 2 remote


controllers)
Set one of the remote controllers to main and the other to sub in the case of remote control with two remote
controllers.

Switching Main/Sub
1) Insert a
screwdriver into the clearance between the grooves of the lower casing and the upper casing
to remove the upper casing. (2 grooves) (The remote controller PCB is attached to the upper casing.)
2) Set the main/sub switch on one of the remote controller PCBs to sub. (Keep the switch of the other remote
controller PCB set to main.)

Upper part of
remote controller

(Factory setting)

S
M
Remote controller
PC board

Lower part of
remote controller
Insert the screwdriver here and gently work
off the upper part of remote controller.

Only one remote


controller needs to be
changed if factory
settings have
remained untouched.

S
M

11. FIELD SETTING


NOTE
Before 12. TEST OPERATION, be sure to make the following field settings as explained in 11. FIELD
SETTING.
Make sure the control box lids are closed on the indoor and outdoor units.
Field setting must be made from the remote controller in accordance with the installation condition.
Setting can be made by changing the MODE NO., FIRST CODE NO., and SECOND CODE NO..
For setting and operation, refer to the FIELD SETTING in the installation manual of the remote controller.

SECOND
CODE NO.

MODE NO.

FIRST
CODE NO.
SETTING

FIELD SET
MODE

Set the remote controller to the FIELD SET MODE. For details, refer to the HOW TO SET IN THE
FIELD, in the remote controller manual.

20

3PN11585-1

Installation of Indoor / Outdoor Unit

231

Installation of Indoor Unit

EDSG281001

With Wireless Remote Controller Used


Set the wireless remote controller address before using the wireless remote controller.
For the setting method of the address, refer to the operation manual provided with the wireless remote
controller.
NOTE
A MODE NO. is set on a group basis. To make a mode setting on a room unit basis or check the setting
made, however, set the corresponding mode number in the parentheses.
1. Settings for Optional Accessories
In the case of connecting optional accessories, refer to the operation manuals provided with the optional
accessories and make necessary settings.
2. External Static Pressure Settings
Make settings in either method (a) or method (b) as explained below.
(a) Use the airflow auto adjustment function to make settings.
Airflow auto adjustment: The volume of blow-off air is automatically adjusted to the rated quantity.
NOTE
Be sure to check that the external static pressure is within the rated range before making the settings.
If the external static pressure is beyond the rated range, no automatic adjustments will be made and an
airflow rate insufficiency or water leakage may result. (Refer to the relevant technical datasheet for the
rated range of the external static pressure.)
1) Check that power supply wiring and wiring the units to the air conditioner is completed along with
duct installation. If a closing damper is installed in the air-conditioning system, make sure that the
closing damper is opened. Furthermore, check that the air filter as a field supply is attached to the
air passage on the suction side.
2) If there are a number of air outlets and inlets, adjust the throttles so that the airflow rate of each air
outlet and inlet will coincide with the designed airflow rate. At that time, operate the air conditioner
in fan operation mode. To change the airflow rate, press and set the airflow adjustment button of
the remote controller to H, or L.
3) Make settings for airflow automatic adjustment. After setting the air conditioner to fan operation
mode, stop the air conditioner, go to FIELD SET MODE, select MODE NO. 21 (11 in the case
of group settings), set the setting FIRST CODE NO. to 7, and set the setting SECOND CODE
NO. to 03.
Return to normal mode after these settings, and press the ON/OFF OPERATION button. Then the
operation lamp will be lit and the air conditioner will go into fan operation for airflow automatic
adjustment. Do not adjust the throttles of the air outlets or inlets during automatic adjustment of the
air conditioner. After the air conditioner runs approximately one to eight minutes, the air conditioner
will finish airflow adjustment automatically, the operation lamp will be turned OFF, and the air
conditioner will come to a stop.
Table 4
MODE NO.
11 (21)
01
OFF

FIRST CODE NO.


7
SECOND CODE NO.
02
Completion of airflow adjustment

Setting contents
Airflow adjustment
03
Start of airflow adjustment

4) After the air conditioner stops operating, check with MODE NO. 21 on an indoor unit basis that 02
is set for the SECOND CODE NO. in Table 4. If the air conditioner does not stop operating
automatically or the SECOND CODE NO. is not 02, repeat steps from 3). If error is displayed,
check the defective point.

21

3PN11585-1

232

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

CAUTION
If there is any change after airflow adjustment in the ventilation paths (e.g., the duct and air outlet), be sure
to make airflow auto adjustment again.
Consult your Daikin representative if there is any change in the ventilation paths (e.g., the duct and air
outlet) after the test operation is finished or the air conditioner is moved to another place.

(b) Select External Static Pressure with Remote Controller


Check that 01 (OFF) is set for the SECOND CODE NO. in MODE NO. 21 for airflow adjustment on
an indoor unit basis in Table 4. The SECOND CODE NO. is set to 01 (OFF) at factory set. Change
the SECOND CODE NO. as shown in Table 5 according to the external static pressure of the duct to
be connected.
1) The SECOND CODE NO. is set to 01 (an external static pressure of 50 Pa) at factory set.
Table 5
External Static Pressure
50Pa
60Pa
70Pa
80Pa
90Pa
100Pa
110Pa
120Pa
130Pa
140Pa
150Pa
160Pa
180Pa
200Pa

MODE NO.

FIRST CODE NO.

13 (23)

06

SECOND CODE NO.


01
02
03
04
05
06
07
08
09
10
11
12
13
14

CAUTION
Keep in mind that a shortage of airflow quantity or water leakage will result because the air conditioner will
be operated outside the rated range of airflow quantity if the external static pressure is wrongly set.
3. Filter Sign Settings
The remote controller is provided with an LCD that tells the time of air filter cleaning.
If the air conditioner is used in places with excessive dust, change the SECOND CODE NO. as shown
in Table 6. The SECOND CODE NO. is set to 01 (standard) at factory set.
Table 6
Dirt

Time for display

Approximately
2500 hours
Approximately
Excessive dust
1250 hours
No display (*)

MODE NO.

FIRST CODE NO.

Standard

SECOND CODE
NO.
01

10 (20)

0
02
3

* Select No display under conditions in which the cleaning display is not required, such as the time of regular
maintenance.

22

3PN11585-1

Installation of Indoor / Outdoor Unit

233

Installation of Indoor Unit

EDSG281001

12. TEST OPERATION


Refer to the section of FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING
CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED .
After finishing the construction of refrigerant piping, drain piping, and electric wiring, conduct test operation
accordingly to protect the unit.

1. HOW TO TEST OPERATION


1) Open the gas side stop valve.
2) Open the liquid side stop valve.
3) Electrify crank case heater for 6 hours (Not required in case of a unit exclusively designed for cooling
only).
4) Set to cooling operation with control panel and start operation by pushing ON/OFF button (
).
5) Press INSPECTION/TEST OPERATION button (
) 4 times (2 times for wireless remote controller)
and operate at Test Operation mode for 3 minutes.
6) Press INSPECTION/TEST OPERATION button (
) and operate normally.
7) Confirm function of unit according to the operation manual.
TEST

TEST

PRECAUTIONS
Refer to the diagnoses below if the unit does not operate properly.
After completing the test run, press the INSPECTION/TEST OPERATION button once to put the unit in
inspection mode, and make sure the malfunction code is 00 (=normal).
If the code reads anything other than 00, refer to the malfunction diagnoses below.

2. HOW TO DIAGNOSE FOR PROBLEMS


With the power on. Troubles can be monitored on the remote controller.
If the air conditioner does not operate normally after installing the air conditioner.
a malfunction shown in the table below may happened.
Remote controller display

No display

88*
88 flashing

Malfunction
Power supply trouble or Open phase connection
Wrong wiring between indoor and outdoor unit
Indoor PC board faulty
Wrong remote controller conection wiring
Remote controller faulty
Fuse faulty
Indoor PC board faulty
Wrong wiring between indoor and outdoor unit
Wrong wiring between indoor and outdoor unit

*After turning on the power, the maximum is 90 seconds, although it will only display 88. This is not a
problem, and it will be set for 90 seconds.
Trouble shooting with the display on the liquid crystal display remote controller.
1. With the remote controller. ( NOTE
1)
When the operation stops due to trouble, operation lamp flashed, and
and the error code are
indicated on the liquid crystal display . In such a case, diagnose the fault contents by referring to
the table on the Error code list it case of group control, the unit No. is displayed so that the indoor
unit no with the trouble can be recognized.( NOTE
2)
2. With the wireless remote controller.
(Refer also to the operation manual attached to the wireless remote controller)
When the operation stops due to trouble. the display on the indoor unit flashes. In such a case,
diagnose the fault contents with the table on the Error code list looking for the error code which
can be found by following procedures.( NOTE
2)

23

3PN11585-1

234

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

1) Press the INSPECTION /TEST OPERATION button,


is displayed and 0 flashes.
2) Press the PROGRAMMING TIME button and find the unit No. which stopped due to trouble.
Number of beeps
3 short beeps...............Perform all the following operations
1 short beep ................Perform 3) and 6)
1 long beep..................No trouble
3) Press the OPERATION MODE SELECTOR button and upper figure of the error code flashes.
4) Continue pressing the PROGRAMMING TIME button unit it makes 2 short beeps and find the
upper code.
5) Press the OPERATION MODE SELECTOR button and lower figure of the error code flashes.
6) Continue pressing the PROGRAMMING TIME button unit it makes a long beep and find the lower
code.
A long beep indicate the error code.

NOTE
1. Press the INSPECTION /TEST OPERATION button on remote controller,
starts flashing and
changes the inspection mode.
2. Keep down the ON/OFF button for 5 seconds or longer in the inspection mode and the above trouble
history disappears, after the trouble code goes on and off twice, followed by the code 00(normal).
The display changes from the inspection mode to the normal mode.

3. Malfunction code
For places where the error code is left blank, the
indication is not displayed. Though the system
continues operating, be sure to inspect the system and make repairs as necessary.
Depending on the type of indoor or outdoor unit, the malfunction code may or may not be displayed.
Code
A1
A3
A6
A7
A8
AF
AH
AJ
C1
C4
C6
C9
CC
CJ
E0
E1
E3
E4
E5
E7
E9

Malfunction/Remarks
Indoor units PC board faulty
Drain water level abnormal
Indoor fan motor overloaded, overcurrent or locked
Swing flap motor locked
Indoor unit power supply voltage abnormal
Humidifier faulty
Air cleaner faulty
Only the air cleaner does not function.
Type set improper
Capacity data is wrongly preset. Or there is nothing programmed in the data hold IC.
Indoor unit fan driver PCB
Indoor control PCB transmission abnormal
Power source malfunction (indoor unit)
Sensor for heat exchanger lamp is fault
Indoor unit fan driver PCB combination failure, control PCB type-wise setting failure
Sensor for suction air lamp is fault
Temperature sensor system faulty

Sensor for remote controller is fault


The remote controller thermistor does not function, but the system thermo run is possible.
Action of safety device (outdoor unit)
Outdoor units PC board faulty (outdoor unit)
High pressure abnormal (outdoor unit)
Low pressure abnormal (outdoor unit)
Compressor motor lock malfunction (outdoor unit)
Outdoor fan motor lock malfunction
Outdoor fan instantaneous overcurrent malfunction (outdoor unit)
Electronic expansion valve faulty (outdoor unit)

24

3PN11585-1

Installation of Indoor / Outdoor Unit

235

Installation of Indoor Unit

F3
H3
H7
H9
J1
J2
J3
J5
J6

J7
J8
J9
JA
JC
L1
L4
L5
L8
L9
LC
P1
P3
P4
PJ
U0
U1
U2

U4
UF

EDSG281001

Discharge pipe temperature abnormal (outdoor unit)


High pressure switch faulty (outdoor unit)
Outdoor motor position signal malfunction (outdoor unit)
Outdoor air thermistor faulty (outdoor unit)
The air conditioner comes to a stop due to an error depending on the model or operating
conditions.
Pressure sensor system error (batch) (outdoor unit)
Current sensor faulty
Discharge pipe thermistor faulty (outdoor unit)
The air conditioner comes to a stop due to an error depending on the model or operating
conditions.
Suction pipe thermistor faulty (outdoor unit)
Heat exchanger thermistor faulty (outdoor unit)
The air conditioner comes to a stop due to an error depending on the model or operating
conditions.
Heat exchanger thermistor faulty (outdoor unit)
Equipment operation in response to errors will vary according to model.
Liquid piping temperature sensor system error (outdoor unit)
Suction temperature sensor faulty (outdoor unit)
Pressure sensor for discharge pipe faulty (outdoor unit)
Pressure sensor for suction pipe faulty (outdoor unit)
Inverter system error (outdoor unit)
Overheated heat-radiating fin (outdoor unit)
Inverter cooling defect.
Instantaneous overcurrent (outdoor unit)
Possible earth fault or short circuit in the compressor motor.
Electric thermal (outdoor unit)
Possible electrical overload in the compressor or cut line in the compressor motor.
Stall prevention (outdoor unit)
Compressor possibly locked.
Transmission malfunction between the outdoor control units inverters (outdoor unit)
Open-phase (outdoor unit)
PC board temperature sensor malfunction (outdoor unit)
Heat-radiating fin temperature sensor malfunction (outdoor unit)
Type set improper (outdoor unit)
Capacity data is wrongly preset. Or there is nothing programmed in the data hold IC.
Suction pipe temperature abnormal
The quantity of refrigerant may be insufficient.
Reverse phase
Reverse two of the L1,L2 and L3 leads.
Power source voltage malfunction (outdoor unit)
Inverter phase loss or a failure in the main circuit capacitor may be resulting.
Transmission error (indoor unit outdoor unit)
Wrong wiring between indoor and outdoor units or malfunction of the PC board mounted
on the indoor and the outdoor units.
If UF is shown, the wiring between the indoor and outdoor units is not properly wired. Therefore,
immediately disconnect the power supply and correct the wiring. (The compressor and the fan
mounted on the outdoor unit may start operation independent of the remote controller operation.)

25

3PN11585-1

236

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Indoor Unit

U5
U8
UA
UC
UJ

Transmission error (indoor unit remote controller)


Transmission is improper between the indoor unit and the remote controller.
Malfunction in transmission between main and sub remote controllers.
(Malfunction in sub remote controller.)
Miss setting for multi system
Error in multi-system settings for simultaneous ON/OFF operation.

Central control address overlapping


Transmission failure in accessory equipment

CAUTION
If interior finish work is continuing on completion of the test operation of the air conditioner, explain the customer not to operate the air conditioner until the interior finish work is completed for the protection of the
air conditioner.
Otherwise, substances that will be generated from interior finish work materials, such as paint and
adhesive agents, may contaminate the air conditioner.

26

3PN11585-1

Installation of Indoor / Outdoor Unit

237

Installation of Outdoor Unit

EDSG281001

3. Installation of Outdoor Unit


3.1

RKS25AVMG / RKS35AVMG

3.1.1

Installation

3P208365-6C M07B057A

DAIKIN AIR CONDITIONER


Two-dimensional bar code
is a code for manufacturing.

Safety Precautions
Read these Safety Precautions carefully to ensure correct installation.
This manual classifies the precautions into WARNING and CAUTION.
Be sure to follow all the precautions below: they are all important for ensuring safety.
WARNING Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
CAUTION

Failure to follow any of CAUTION may result in grave consequences in some cases.

The following safety symbols are used throughout this manual:


Be sure to observe this instruction.

Be sure to establish an earth connection.

Never attempt.

After completing installation, test the unit to check for installation errors. Give the user adequate instructions
concerning the use and cleaning of the unit according to the Operation Manual.

WARNING
Installation should be left to the dealer or another professional. Improper installation may cause water leakage, electrical shock, or fire.
Install the air conditioner according to the instructions given in this manual. Incomplete installation may cause water leakage, electrical shock, or fire.
Be sure to use the supplied or specified installation parts. Use of other parts may cause the unit to come to lose, water leakage, electrical shock, or fire.
Install the air conditioner on a solid base that can support the weight of the unit. An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring
rules or code of practice. Insufficient capacity or incomplete electrical work may cause electrical shock or fire.
Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
For wiring, use a cable length enough to cover the entire distance with no connection. Do not use an extension cord. Do not
put other loads on the power supply, use a dedicated power circuit.(Failure to do so may cause abnormal heat, electric shock or fire.)
Use the specified types of wires for electrical connections between the indoor and outdoor units.
Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating or fire.

After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the
electrical covers or panels. Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire.
When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the specified
refrigerant (R410A), such as air. (Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)
If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)

After all installation is complete, check to make sure that no refrigerant is leaking out.
(The refrigerant produces a toxic gas if exposed to flames.)

During pump-down, stop the compressor before removing the refrigerant piping. If the compressor is still running and the stop valve is open during
pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.

During installation, attach the refrigerant piping securely before running the compressor.
If the compressor is not attached and the stop valve is open during pump-down, air will be sucked in when the compressor is run, causing
abnormal pressure in the freezer cycle which will lead to breakage and even injury.

Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone earth.
Incomplete earth may cause electrical shock, or fire.

A high surge current from lightning or other sources may cause damage to the air conditioner.

Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shocks, or fire.

CAUTION
Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may catch fire.

Establish drain piping according to the instructions of this manual. Inadequate piping may cause flooding.
Tighten the flare nut according to the specified method such as with a torque wrench.
If the flare nut is tightened too hard, the flare nut may crack after a long time and cause refrigerant leakage.

Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.

3P208365-6C

238

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Accessories
Accessories supplied with the outdoor unit:
(B) Drain plug (Heat pump-Models)
(A) Installation manual

2
1

There is on the bottom packing case.

Precautions for Selecting the Location


1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will
not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a
nuisance to the neighbors of the user.
3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient spaces for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
7) Install units, power cords and inter-unit cables at least 3 meter away from television and radio sets. This is
to prevent interference to images and sounds. (Noises may be heard even if they are more than 3 meter
away depending on radio wave conditions.)
8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the
air conditioner.
9) Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away
from moisture.
NOTE
Cannot be installed hanging from ceiling or stacked.

CAUTION
When operating the air conditioner in a low outdoor ambient
temperature, be sure to follow the instructions described
below.
1) To prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.
2) Never install the outdoor unit at a site where the suction
side may be exposed directly to wind.
3) To prevent exposure to wind, it is recommended to install a
baffle plate on the air discharge side of the outdoor unit.
4) In heavy snowfall areas, select an installation site where the
snow will not affect the unit.

Construct a large canopy.


Construct a pedestal.

Install the unit high enough off


the ground to prevent burying in
snow.

Precautions on Installation

20

Check the strength and level of the installation ground so that the unit will not cause any operating vibration
or noise after installed.
In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare
four sets of M8 or M10 foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their
length are 20mm from the foundation surface.

3P208365-6C

Installation of Indoor / Outdoor Unit

239

Installation of Outdoor Unit

EDSG281001

Outdoor Unit Installation Drawings


Wrap the insulation pipe with
the finishing tape from bottom
to top.
Max. allowable length
Max. allowable height

20m
15m

Additional refrigerant
required for refrigerant
pipe exceeding
10m in length.

20g/m

Gas pipe
Liquid pipe

O.D. 9.5mm
O.D. 6.4mm
* Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
** When connecting the FVXS indoor unit, the shortest piping
length should be no less than around 2.5m.

Stop valve cover


How to remove the stop valve cover.
Remove the screw on the
stop valve cover.
Slide the lid downward
to remove it.

250mm from wa

ll

3
Foo 11
cen t bolt
tres -hole

How to attach the stop valve cover.


Insert the upper part of the
stop valve cover into the
outdoor unit to install.
Tighten the screws.

In sites with poor drainage, use


block bases for outdoor unit.
Adjust foot height until the unit
is leveled. Otherwise, water
leakage or pooling of water may
occur.

574
lt-hole
centre
s)

(Foot b
o

Allow space for piping


and electrical servicing.

105.5

(From
u

nits s

ide)

Where there is a danger of the unit


falling, use foot bolts, or wires.
Unit: mm

Installation Guidelines
Where a wall or other obstacle is in the path of outdoor units intake or exhaust airflow, follow the
installation guidelines below.
For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Wall facing one side
More than 50

Walls facing two sides

Walls facing three sides

More than 100

1200
or less

More than 50
More than 50

Side view

More than 150

More than 150


More
than 100

More than 50
Top view

More than 300


Top view
Unit: mm

3P208365-6C

240

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Outdoor Unit Installation (1)


1.

Installing outdoor unit.


1) When installing the outdoor unit, refer to Precautions for Selecting the Location and the Outdoor
Unit Installation Drawings.
2) If drain work is necessary, follow the procedures below.

2.

Drain work (Heat pump-models).


1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or floor surface, place
additional foot bases of at least 30mm in height under the outdoor units feet.
3) In cold areas, do not use a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating performance.)

3.

Drain-water hole
Bottom frame
Drain plug
Hose (available commercially,
inner dia. 16mm)

Flaring the pipe end.


(Cut exactly at
right angles.)

1) Cut the pipe end with a pipe cutter.


2) Remove burrs with the cut surface
facing downward so that the chips do
not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

Remove burrs

Flaring
Set exactly at the position shown below.
A

Die

Flare tool for R410A

Conventional flare tool

Clutch-type

Clutch-type (Rigid-type) Wing-nut type (Imperial-type)

0-0.5mm

1.0-1.5mm

1.5-2.0mm

Check
Flares inner
surface must
be flaw-free.

The pipe end must


be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.

WARNING
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.

4.

Refrigerant piping.
CAUTION

1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil
for R410A.)
3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully
with the torque wrenches.
[Apply oil]
Do not apply refrigeration
oil to the outer surface.

[Tighten]
Apply refrigeration oil to the

Torque wrench

inner surface of the flare.

Flare nut
Spanner

Piping union

Do not apply refrigeration oil to the flare

Flare nut

nut avoid tightening with over torque.

Flare nut tightening torque


Gas side
Liquid side
3/8 inch
1/4 inch
32.7-39.9N m
14.2-17.2N m
(330-407kgf cm)
(144-175kgf cm)

Valve cap tightening torque


Gas side
Liquid side
3/8 inch
1/4 inch
21.6-27.4N m
21.6-27.4N m
(220-280kgf cm)
(220-280kgf cm)
Service port cap
tightening torque

10.8-14.7N m
(110-150kgf cm)

3P208365-6C

Installation of Indoor / Outdoor Unit

241

Installation of Outdoor Unit

EDSG281001

Outdoor Unit Installation (2)


5.

Purging air and checking gas leakage.


When piping work is completed, it is necessary to purge the air and check for gas leakage.

WARNING
1) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
2) When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
3) R410A, as well as other refrigerants, should always be recovered and never be released directly into the
environment.
4) Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants
may damage the vacuum pump or the unit.
If using additional refrigerant, perform air purging from the refrigerant
pipes and indoor unit using a vacuum pump, then charge additional
refrigerant.
Use a hexagonal wrench (4mm) to operate the stop valve rod.
All refrigerant pipe joints should be tightened with a torque wrench at
the specified tightening torque.

Compound
Pressure
pressure gauge meter
Gauge
manifold

Low-pressure
valve

Highpressure
valve

Valve caps

Liquid
stop
valve

Charging
hoses
Vacuum pump Service port
Gas stop valve

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valves service port.

2) Fully open gauge manifolds low-pressure valve (Lo) and completely close its high-pressure valve (Hi).
(High-pressure valve subsequently requires no operation.)

3) Do vacuum pumping and make sure that the compound pressure gauge reads 0.1MPa ( 76cmHg)*1.

4) Close gauge manifolds low-pressure valve (Lo) and stop vacuum pump.
(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2.

5) Remove covers from liquid stop valve and gas stop valve.

6) Turn the liquid stop valves rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor units flare and outdoor units flare and valve rods.
After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valves service port, then fully open liquid and gas stop valves.
(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

*1. Pipe length vs. vacuum pump run time


Pipe length

Up to 15 metres

More than 15 metres

Run time

Not less than 10 min.

Not less than 15 min.

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe
joint may exists. Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

3P208365-6C

242

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Outdoor Unit Installation (3)


6.

Refilling the refrigerant.

Filling a cylinder with an

Filling other cylinders

Check the type of refrigerant to be used on the machine


attached siphon
Turn the cylinder
Stand the cylinder upright when filling.
nameplate.
upside-down when
There is a siphon pipe inside,
filling.
Precautions when adding R410A
so the cylinder need not be
Fill from the liquid pipe in liquid form.
upside-down to fill with liquid.
It is a mixed refrigerant, so adding it in gas form may cause the
refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like liquid
filling siphon attached displayed on it.)
Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.

7.

Refrigerant piping work.

7-1 Cautions on pipe handling.


1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for bending.
7-2

Wall

Be sure to
place a cap.
Rain

Selection of copper and heat insulation materials.

If no flare cap is
available, cover the
flare mouth with
tape to keep dirt or
water out.

When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/(mh C))
Refrigerant gas pipes surface temperature reaches 110C max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
Gas side

Liquid side

Gas pipe
thermal insulation

Liquid pipe
thermal insulation

O.D. 9.5mm

O.D. 6.4mm

I.D. 12-15mm

I.D. 8-10mm

Minimum bend radius

Inter-unit wiring
Gas pipe

Liquid pipe

Thickness 10mm Min.

30mm or more
Thickness 0.8mm (C1220T-O)

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas pipe
insulation

Liquid pipe
insulation
Finishing tape

Drain hose

Pump Down Operation


In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1)
2)
3)
4)

Remove the valve cap from liquid stop valve and gas stop valve.
Carry out forced cooling operation.
After five to ten minutes, close the liquid stop valve with a hexagonal wrench.
After two to three minutes, close the gas stop valve and stop forced cooling operation.

Liquid stop
valve

Hexagonal
wrench
Close

Gas stop
valve
Valve cap

How to force cooling operation mode

Using the indoor unit operation/stop button


Press the indoor unit operation/stop button for at least five seconds. (Operation will start.)
Forced cooling operation will stop automatically after around 15 minutes.
To force a test run to stop, press the indoor unit operation/stop button.
n Using the main units remote controller
1) Press the operation/stop button. (Operation will start.)
2) Press the temperature
button and the operation select button at the same time.
3) Press the operation select button twice. ( will be displayed and the unit will enter test run mode.)
4) Press the operation select button to return the operation mode to cooling.
Test run mode will stop automatically after around 30 minutes. To force a test run to stop, press the operation/stop button.

CAUTION
1) When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock.
2) After closing the liquid stop valve, close the gas stop valve within three minutes, then stop the forced operation.

3P208365-6C

Installation of Indoor / Outdoor Unit

243

Installation of Outdoor Unit

EDSG281001

Wiring
WARNING
1) Do not use tapped wires, stranded wires, extensioncords, or starburst connections, as they may cause
overheating, electrical shock, or fire.
2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain
pump, etc., from the terminal block.) Doing so may cause electric shock or fire.
3) Be sure to install an earth leakage breaker. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that it must be used an earth leakage breaker capable
handling harmonics in order to prevent malfunctioning of the earth leakage breaker itself.)
4) Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
Do not turn ON the safety breaker until all work is completed.
Firmly fix the wires with
1) Strip the insulation from the wire (20mm).
the terminal screws.
2) Connect the connection wires between the
indoor and outdoor units so that the terminal
numbers match. Tighten the terminal screws
securely. We recommend a flathead
screwdriver be used to tighten the screws.

Outdoor unit
1 23

When wire length exceeds 10m,


use 2.0mm diameter wires.

Indoor
unit

Use 2.0mm diameter wires.

1
2
3

Safety
breaker
Firmly fix the wires with
the terminal screws.

1
1

LN

Earth leakage
circuit breaker

H05VV

Power supply
50Hz 220V-240V
60Hz 220V-230V
Safety breaker
RX(K)S
10A
RYN
15A
RXG

Earth

Power supply
terminal block

Shape wires so
that the service
lid and stop
valve cover fit
securely.

Use the specified wire type and


connect it securely.

Firmly secure wire retainer so


wire terminations will not receive
external stress.

Observe the notes mentioned below when wiring to the power


supply terminal board.
Round crimp-style
Precautions to be taken for power supply wiring.
Use a round crimp-style terminal for connection to the power terminal
supply terminal board. In case it cannot be used due to
unavoidable reasons, be sure to observe the following instruction.

Stranded Wire

CAUTION
When connecting the connection wires to the terminal board using a single core wire, be sure to perform curling.
Problems with the work may cause heat and fires.

Strip wire end


to this point.

Good

Excessive strip length


may cause electrical
shock or leakage.

Wrong

Stripping wire at terminal block

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.

3P208365-6C

244

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Test Run and Final Check


1.

Trial operation and testing.


1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in eitr cooling or heating mode.

For heat pump


In cooling mode, select the lowest programmable temperature; in heating mode, select the highest
programmable temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (26C to 28C in cooling mode,
20C to 24C in heating mode).
3) For protection, the unit disables restart operation for 3 minutes after it is turned off.

For cooling only

Select the lowest programmable temperature.


1) Trial operation in cooling mode may be disabled depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (26C to 28C).
3) For protection, the unit disables restart operation for 3 minutes after it is turned off.

1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and
parts, such as louver movement, are working properly.
The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for
some time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original
operation mode when the circuit breaker is opened again.

2.

Test items.
Test items

Symptom
(diagnostic display on RC)

Indoor and outdoor units are installed properly on


solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating function

Refrigerant gas and liquid pipes and indoor drain


hose extension are thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly earthed.

Electrical leakage

The specified wires are used for interconnecting


wire connections.

Inoperative or burn damage

Indoor or outdoor units air intake or exhaust has


clear path of air.
Stop valves are opened.

Incomplete cooling/heating function

Indoor unit properly receives remote controller


commands.

Inoperative

Check

3P208365-6C

Installation of Indoor / Outdoor Unit

245

Installation of Outdoor Unit

EDSG281001

3.2

RXS50FAVMA / RXS60FVMA / RKS50AVMG / RKS60AVMG

3.2.1

Installation

3P192027-7D M06B260C

DAIKIN AIR CONDITIONER


Two-dimensional bar code
is a code for manufacturing.

Safety Precautions
Read these Safety Precautions carefully to ensure correct installation.
This manual classifies the precautions into WARNING and CAUTION.
Be sure to follow all the precautions below: they are all important for ensuring safety.
WARNING

Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.

CAUTION

Failure to follow any of CAUTION may result in grave consequences in some cases.

The following safety symbols are used throughout this manual:


Be sure to observe this instruction.

Be sure to establish an earth connection.

Never attempt.

After completing installation, test the unit to check for installation errors. Give the user adequate instructions
concerning the use and cleaning of the unit according to the Operation Manual.

WARNING
Installation should be left to the dealer or another professional. Improper installation may cause water leakage, electrical shock, or fire.
Install the air conditioner according to the instructions given in this manual. Incomplete installation may cause water leakage, electrical shock, or fire.
Be sure to use the supplied or specified installation parts. Use of other parts may cause the unit to come to lose, water leakage, electrical shock, or fire.
Install the air conditioner on a solid base that can support the weight of the unit. An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring
rules or code of practice. Insufficient capacity or incomplete electrical work may cause electrical shock or fire.
Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
For wiring, use a cable length enough to cover the entire distance with no connection. Do not use an extension cord.
Do not put other loads on the power supply, use a dedicated power circuit. (Failure to do so may cause abnormal heat, electric shock or fire.)
Use the specified types of wires for electrical connections between the indoor and outdoor units. When installing
wiring for the outdoor unit, after cutting the wires for each connection point, a length of 3mm or longer is required.
Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating or fire.

After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels.
Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire. When electrical appliances are connected in Y formation,
if the power supply is damaged in some way, to avoid danger the power supply must be replaced by the maker or by someone with an equivalent certification.

When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the specified
refrigerant (R410A), such as air. (Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)
If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)

After all installation is complete, check to make sure that no refrigerant is leaking out.
(The refrigerant produces a toxic gas if exposed to flames.)

During pump-down, stop the compressor before removing the refrigerant piping. If the compressor is still running and the stop valve is open during
pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.

During installation, attach the refrigerant piping securely before running the compressor. If the compressor is not attached and the stop valve is
open during pump-down, air will be sucked in when the compressor is run, causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.

Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone earth.
Incomplete earth may cause electrical shock, or fire. A high surge current from lightning or other sources may cause damage to the air conditioner.

Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shocks, or fire.

CAUTION
Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may catch fire.

Establish drain piping according to the instructions of this manual. Inadequate piping may cause flooding.
Tighten the flare nut according to the specified method such as with a torque wrench. If the flare nut is tightened too hard, the flare nut may crack after a long time and cause refrigerant leakage.
Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.

3P192027-7D

246

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Accessories
Accessories supplied with the outdoor unit:
(B) Drain plug (Heat pump-Models)
(A) Installation manual

2
1

There is on the bottom packing case.

Precautions for Selecting the Location


1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will
not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a
nuisance to the neighbors of the user.
3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient spaces for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
7) Install units, power cords and inter-unit cables at least 3 meter away from television and radio sets. This is
to prevent interference to images and sounds. (Noises may be heard even if they are more than 3 meter
away depending on radio wave conditions.)
8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the
air conditioner.
9) Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away
from moisture.
NOTE
Cannot be installed hanging from ceiling or stacked.

CAUTION
When operating the air conditioner in a low outdoor ambient
temperature, be sure to follow the instructions described below.
1) To prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.
2) Never install the outdoor unit at a site where the suction side
may be exposed directly to wind.
3) To prevent exposure to wind, it is recommended to install a
baffle plate on the air discharge side of the outdoor unit.
4) In heavy snowfall areas, select an installation site where the
snow will not affect the unit.

Construct a large canopy.


Construct a pedestal.

Install the unit high enough off the


ground to prevent burying in snow.

Precautions on Installation

20

Check the strength and level of the installation ground so that the unit will not cause any operating vibration
or noise after installed.
In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare
four sets of M8 or M10 foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their length are 20mm from the foundation surface.

3P192027-7D

Installation of Indoor / Outdoor Unit

247

Installation of Outdoor Unit

EDSG281001

Outdoor Unit Installation Drawings


Wrap the insulation
pipe with the finishing
tape from bottom to top.
Model

50/60 class

Max. allowable length

30m

Min. allowable length

1.5m

Max. allowable height

20m

Additional refrigerant
required for refrigerant
pipe exceeding 10m
in length.

20g/m

Gas pipe

O.D. 12.7mm

Liquid pipe

O.D. 6.4mm

CAUTION
Set the piping length
from 1.5m to 30m.

Service lid

Stop valve cover

250m

m from

In sites with poor drainage,


use block bases for outdoor
unit.
Adjust foot height until the
unit is leveled. Otherwise,
water leakage or pooling of
water may occur.

0m

-h
olt
tb )
oo tres
F
( en
c

33
580m
m
(Foot
bolt-ho
120mm
le cen
tres)
(From
units
side)

ole

wall

Allow space for piping


and electrical servicing.

Where there is a danger of


the unit falling, use foot bolts,
or wires.

Installation Guidelines
Where a wall or other obstacle is in the path of outdoor units intake or exhaust airflow, follow the
installation guidelines below.
For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Wall facing one side
More than 100

Walls facing two sides


More than 350
More than 350
More
than 100

1200
or less
More than 50

More than 50
Top view

Side view

Walls facing three sides


More than
100
More than 50

More
than 350
Top view

Unit: mm

C : 3P192027-7D

248

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Outdoor Unit Installation (1)


1.

Installing outdoor unit.


1) When installing the outdoor unit, refer to Precautions for Selecting the Location and the Outdoor
Unit Installation Drawings.
2) If drain work is necessary, follow the procedures below.

2.

Drain work.
1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or floor surface, place
additional foot bases of at least 30mm in height under the outdoor units feet.
3) In cold areas, do not use a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating performance.)

3.

Drain-water hole
Bottom frame
Drain plug
Hose (available commercially,
inner dia. 16mm)

Flaring the pipe end.


1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface
facing downward so that the chips do
not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

(Cut exactly at
right angles.)

Remove burrs

Flaring
Set exactly at the position shown below.
A

Die

Flare tool for R410A

Conventional flare tool

Clutch-type

Clutch-type (Rigid-type) Wing-nut type (Imperial-type)

0-0.5mm

1.0-1.5mm

1.5-2.0mm

Check
Flares inner
surface must
be flaw-free.

The pipe end must


be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.

WARNING
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.

4.

Refrigerant piping.
CAUTION

1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil
for R410A.)
3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully
with the torque wrenches.
[Apply oil]

Do not apply refrigeration


oil to the outer surface.

[Tighten]

Apply refrigeration oil to the


inner surface of the flare.

Torque wrench

Flare nut
Spanner

Piping union

Do not apply refrigeration oil to the flare

Flare nut

nut avoid tightening with over torque.

Flare nut tightening torque


Gas side
1/2 inch

Valve cap tightening torque

Liquid side
5/8 inch

49.5-60.3N m 61.8-75.4N m
(505-615kgf cm) (630-770kgf cm)

1/4 inch
14.2-17.2N m
(144-175kgf cm)

Gas side
1/2 inch

Liquid side
5/8 inch

48.1-59.7N m 44.1-53.9N m
(490-610kgf cm) (450-550kgf cm)

Service port cap tightening torque

1/4 inch
21.6-27.4N m
(220-280kgf cm)
10.8-14.7N m
(110-150kgf cm)

3P192027-7D

Installation of Indoor / Outdoor Unit

249

Installation of Outdoor Unit

EDSG281001

Outdoor Unit Installation (2)


5.

Purging air and checking gas leakage.

When piping work is completed, it is necessary to purge the air and check for gas leakage.

WARNING
1)
2)
3)
4)

Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants
may damage the vacuum pump or the unit.

If using additional refrigerant, perform air purging from the refrigerant


pipes and indoor unit using a vacuum pump, then charge additional
refrigerant.
Use a hexagonal wrench (4mm) to operate the stop valve rod.
All refrigerant pipe joints should be tightened with a torque wrench at
the specified tightening torque.

Compound
Pressure meter
pressure gauge
Gauge
manifold
High-pressure
valve Valve caps
Low-pressure
valve
Charging
hoses

Liquid
stop
valve

Gas
stop
Vacuum pump Service port valve

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valves service port.

2) Fully open gauge manifolds low-pressure valve (Lo) and completely close its high-pressure valve (Hi).
(High-pressure valve subsequently requires no operation.)

3) Do vacuum pumping and make sure that the compound pressure gauge reads 0.1MPa ( 76cmHg)*1.

4) Close gauge manifolds low-pressure valve (Lo) and stop vacuum pump.
(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2.

5) Remove valve caps from liquid stop valve and gas stop valve.

6) Turn the liquid stop valves rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor units flare and outdoor units flare and valve rods.
After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valves service port, then fully open liquid and gas stop valves.
(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port cap for the liquid and gas stop valves with a torque wrench at the specified torques.

*1. Pipe length vs. vacuum pump run time


Pipe length

Up to 15 metres

More than 15 metres

Run time

Not less than 10 min.

Not less than 15 min.

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe
joint may exists. Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

3P192027-7D

250

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Outdoor Unit Installation (3)


6.

Refilling the refrigerant.


Check the type of refrigerant to be used on the machine nameplate.
Precautions when adding R410A
Fill from the liquid pipe in liquid form.
It is a mixed refrigerant, so adding it in gas form may cause the
refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not.
(It should have something like liquid filling siphon attached displayed on it.)

Filling a cylinder with an


attached siphon

Filling other cylinders

Stand the cylinder upright


when filling.

Turn the cylinder


upside-down when filling.

There is a siphon pipe


inside, so the cylinder
need not be upsidedown to fill with liquid.

Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.

7.

Refrigerant piping work.


1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for bending.

7-2

Wall

Be sure to
place a cap.

7-1 Cautions on pipe handling.


Rain

Selection of copper and heat insulation materials.

If no flare cap is
available, cover the
flare mouth with
tape to keep dirt or
water out.

When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/mhC)
Refrigerant gas pipes surface temperature reaches 110C max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
Gas side

Gas pipe thermal insulation

Liquid side

50/60 class
O.D. 12.7mm

O.D. 6.4mm

50/60 class
I.D. 14-16mm

I.D. 8-10mm

Gas pipe

Liquid pipe

Thickness 10mm Min.

Minimum bend radius


40mm or more 50mm or more
Thickness
Thickness
1.0mm
0.8mm
(C1220T-O) (C1220T-O)

Inter-unit wiring

Liquid pipe
thermal insulation

30mm or more
Gas pipe
insulation

Thickness 0.8mm
(C1220T-O)

Liquid pipe
insulation
Finishing tape

Drain hose

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Pump Down Operation


In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve caps from liquid stop valve and gas stop valve.
Hexagonal wrench

2) Carry out forced cooling operation.


3) After five to ten minutes, close the liquid stop valve with a
hexagonal wrench.
4) After two to three minutes, close the gas stop valve and
stop forced cooling operation.

Close

Liquid stop valve

Forced cooling operation


1) Press the Forced Operation switch (SW1) to begin forced cooling.
Press the Forced Operation switch (SW1) again to stop forced cooling.

Gas stop valve

Valve cap

Service port

S102

S2

ON

A B CD

LED-A

SW4

Forced
operation
switch
SW1

C : 3P192027-7D

Installation of Indoor / Outdoor Unit

251

Installation of Outdoor Unit

EDSG281001

Wiring
WARNING
1) Do not use tapped wires, stranded wires, extensioncords, or starburst connections, as they may cause
overheating, electrical shock, or fire.
2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain
pump, etc., from the terminal block.) Doing so may cause electric shock or fire.
3) Be sure to install an earth leak detector. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that it must be used an earth leak detector capable handling
harmonics in order to prevent malfunctioning of the earth leak detector itself.)
4) Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
fix the wires with
Do not turn ON the safety breaker until all work is completed. Firmly
the terminal screws.
1) Strip the insulation from the wire (20mm).
When wire length exceeds 10m,
2) Connect the connection wires between
use 2.0mm diameter wires.

the indoor and outdoor units so that the


terminal numbers match. Tighten the
terminal screws securely. We recommend
a flathead screwdriver be used to tighten
the screws.

Indoor
unit

Outdoor unit
1 23

LN

Use 2.0mm diameter wires.

1
2
3

Safety
breaker
20A
Firmly fix the wires with 60245 IEC57
(H05RN)
the terminal screws.

Earth leakage
circuit breaker

Power supply
FVM
50Hz 220V-240V :
F(A)VMA
60Hz 220V-230V
FBVMA
50Hz 220V-240V : FV1A

Earth

Power supply terminal block

Use the specified wire type


and connect it securely.

Firmly secure wire retainer


so wire terminations will not
receive external stress.

Shape wires so that the


service lid and stop
valve cover fit securely.

Observe the notes mentioned below when wiring to the power supply terminal board.
Precautions to be taken for power supply wiring.
Round
Use a round crimp-style terminal for connection to the power
crimp-style
supply terminal board. In case it cannot be used due to
terminal
unavoidable reasons, be sure to observe the following instruction.
Place the round crimp-style terminals on the wires up to the
covered part and secure in place.
Ground terminal installation
Use the following method when installing the round
crimp-style terminal.

Screw

Screw

Round crimpstyle terminal

Flat washer
Round crimpstyle terminal

Flat washer

Good

Electric
Wire

Wrong

CAUTION
When connecting the connection wires to the terminal
board using a single core wire, be sure to perform curling.
Problems with the work may cause heat and fires.

Stripping wire at terminal block

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
3P192027-7D

252

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Test Run and Final Check


1.

Trial operation and testing.


1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.

For Heat pump


In cooling mode, select the lowest programmable temperature; in heating mode, select the highest
programmable temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (26C to 28C in cooling mode,
20C to 24C in heating mode).
3) For protection, the unit disables restart operation for 3 minutes after it is turned off.

For Cooling only

Select the lowest programmable temperature.


1) Trial operation in cooling mode may be disabled depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (26C to 28C).
3) For protection, the unit disables restart operation for 3 minutes after it is turned off.

1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and
parts, are working properly.
The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for
some time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the
original operation mode when the circuit breaker is opened again.

2.

Test Items.
Test Items

Symptom

Indoor and outdoor units are installed properly on


solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating function

Refrigerant gas and liquid pipes and indoor drain


hose extension are thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly earthed.

Electrical leakage

The specified wires are used for inter-unit wiring


connections.

Inoperative or burn damage

Indoor or outdoor units air intake or exhaust has


clear path of air.
Stop valves are opened.

Incomplete cooling/heating function

Indoor unit properly receives remote controller


commands.

Inoperative

Check

3P192027-7D

Installation of Indoor / Outdoor Unit

253

Installation of Outdoor Unit

3.3

RXS71FVMA

3.3.1

Installation

EDSG281001

3P182980-1E M06B009C

DAIKIN AIR CONDITIONER


Two-dimensional bar code
is a code for manufacturing.

Safety Precautions
Read these Safety Precautions carefully to ensure correct installation.
This manual classifies the precautions into WARNING and CAUTION.
Be sure to follow all the precautions below: they are all important for ensuring safety.
WARNING

Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.

CAUTION

Failure to follow any of CAUTION may result in grave consequences in some cases.

The following safety symbols are used throughout this manual:


Be sure to observe this instruction.

Be sure to establish an earth connection.

Never attempt.

After completing installation, test the unit to check for installation errors. Give the user adequate instructions
concerning the use and cleaning of the unit according to the Operation Manual.

WARNING
Installation should be left to the dealer or another professional. Improper installation may cause water leakage, electrical shock, or fire.
Install the air conditioner according to the instructions given in this manual. Incomplete installation may cause water leakage, electrical shock, or fire.
Be sure to use the supplied or specified installation parts. Use of other parts may cause the unit to come to lose, water leakage, electrical shock, or fire.
Install the air conditioner on a solid base that can support the weight of the unit. An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring
rules or code of practice. Insufficient capacity or incomplete electrical work may cause electrical shock or fire.
Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
For wiring, use a cable length enough to cover the entire distance with no connection. Do not use an extension cord.
Do not put other loads on the power supply, use a dedicated power circuit. (Failure to do so may cause abnormal heat, electric shock or fire.)
Use the specified types of wires for electrical connections between the indoor and outdoor units.
Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating or fire.

After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the
electrical covers or panels. Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire.
When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the specified
refrigerant (R410A), such as air. (Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)
If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)

After all installation is complete, check to make sure that no refrigerant is leaking out.
(The refrigerant produces a toxic gas if exposed to flames.)

During pump-down, stop the compressor before removing the refrigerant piping. If the compressor is still running and the stop valve is open during
pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.

During installation, attach the refrigerant piping securely before running the compressor. If the compressor is not attached and the stop valve is
open during pump-down, air will be sucked in when the compressor is run, causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.

Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone earth.
Incomplete earth may cause electrical shock, or fire. A high surge current from lightning or other sources may cause damage to the air conditioner.

Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shocks, or fire.

CAUTION
Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may catch fire.

Establish drain piping according to the instructions of this manual. Inadequate piping may cause flooding.
Note for installing the outdoor unit. (For heat pump model only.) In cold area where the outside air temperature keep below or around freezing-point
for a few days, the outdoor units drain may freeze. If so, it is recommended to install an electric heater in order to protect drain from freezing.

Tighten the flare nut according to the specified method such as with a torque wrench. If the flare nut is tightened too hard, the flare nut may crack after a long time and cause refrigerant leakage.
Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.

3P182980-1E

254

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Accessories
Accessories supplied with the outdoor unit:
(B) Drain socket assy

(HEAT PUMP ONLY)

(A) Installation manual

Precautions for Selecting the Location


1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will
not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a
nuisance to the neighbors of the user.
3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient spaces for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
7) Install units, power cords and inter-unit cables at least 3 meter away from television and radio sets. This is
to prevent interference to images and sounds. (Noises may be heard even if they are more than 3 meter
away depending on radio wave conditions.)
8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the
air conditioner.
9) Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away
from moisture.
NOTE
Cannot be installed hanging from ceiling or stacked.

CAUTION
When operating the air conditioner in a low outdoor ambient
temperature, be sure to follow the instructions described below.
1) To prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.
2) Never install the outdoor unit at a site where the suction side
may be exposed directly to wind.
3) To prevent exposure to wind, it is recommended to install a
baffle plate on the air discharge side of the outdoor unit.
4) In heavy snowfall areas, select an installation site where the
snow will not affect the unit.

Construct a large canopy.


Construct a pedestal.

Install the unit high enough off the


ground to prevent burying in snow.

Precautions on Installation

20

Check the strength and level of the installation ground so that the unit will not cause any operating vibration
or noise after installed.
In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare
four sets of M8 or M10 foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their length are 20mm from the foundation surface.

3P182980-1E

Installation of Indoor / Outdoor Unit

255

Installation of Outdoor Unit

EDSG281001

Outdoor Unit Installation Drawings


Model

71/80/90 class

Max. allowable length

30m

Min. allowable length

1.5m

Max. allowable height

20m

Additional refrigerant
required for refrigerant
pipe exceeding 10m
in length.

20g/m

Gas pipe

O.D. 15.9mm

Liquid pipe

O.D. 6.4mm

Wrap the insulation


pipe with the finishing
tape from bottom to top.

CAUTION

* Be sure to add the proper amount of additional refrigerant.


Failure to do so may result in reduced performance.

Allow 30cm of work


space below the
ceiling surface.

Set the piping length


from 1.5m to 30m.

Allow space for piping


and electrical servicing.
25cm from wa

ll

If there is the danger of the unit falling


or overturning, fix the unit with
foundation bolts, or with wire or other
means.
If the location does not have good
drainage, place the unit on a level
mounting base (or a plastic pedestal).
Install the outdoor unit in a level
position. Failure to do so may result in
water leakage or accumulation.

Right side plate

cm

le

ho
ltbo s)
t
oo re
(F ent
c
35

(Foot
bo

lt-hole

62cm
centre
s

Also insulate the connection on the outdoor unit.


Clamping material

Level mounting base


(available separately)

Insulation tube
Tape

Service lid

Use tape or insulating material on all connections


to prevent air from getting in between the copper
piping and the insulation tube.
Be sure to do this if the outdoor unit is installed
above.

Installation Guidelines
Where a wall or other obstacle is in the path of outdoor units intake or exhaust airflow, follow the
installation guidelines below.
For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.

Wall facing one side


More than 100

Walls facing two sides

Walls facing three sides

More than 350


More than 350

1200
or less

More than 50
More than 50

Side view

More than 100

More
than 100

Top view

More than 50

More than 350


Top view
Unit: mm

3P182980-1E

256

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Outdoor Unit Installation (1)


1.

Installing outdoor unit.


1) When installing the outdoor unit, refer to Precautions for Selecting the Location and the Outdoor
Unit Installation Drawings.
2) If drain work is necessary, follow the procedures below.

2.

Drain work.
Use drain plug for drainage.
If the drain port is covered by a mounting base or floor surface, place additional foot bases of at least
100mm in height under the outdoor units feet.
In cold areas, do not use a drain hose with the outdoor unit. (Otherwise, drain water may freeze,
impairing heating performance.)
1) Insert drain receiver (C) onto drain socket (A) and drain cap (B) beyond
4 projections around drain socket and drain cap.
2) Insert drain socket and drain caps into their matching drain hole ; Drain
socket (A) into drain hole I and drain caps (B) into drain hole II and III.
After insertion, turn them about 40 clockwise.

II

(A) Drain socket


Projections

(B) Drain cap


Projections

(Be sure not to insert them into wrong drain


holes, or there causes water leakage.)

I
III

(View from bottom)


(C) Drain receiver

NOTE
Check that the drain receiver (C) is correctly engaged with the projections of the drain socket (A) and
drain cap (B). Otherwise, water leakage may result.
Projections
(4 points)

Projections
(4 points)

3) Connect vinyl hose on the market (internal diameter of 25mm) to drain socket (A).
(If the hose is too long and hangs down, fix it carefully to prevent the kinks.)
4) Make sure that there is no water leakage from portion I, II, or III.
NOTE
If the drain holes of the outdoor unit are covered with the mounting bracket or the floor, raise the unit to
provide the space of more than 100mm under the leg of the outdoor unit.

3.

Flaring the pipe end.


1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing
downward so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

Flaring
Set exactly at the position shown below.
A

Die

Flare tool for R410A

Conventional flare tool

Clutch-type

Clutch-type (Rigid-type) Wing-nut type (Imperial-type)

0-0.5mm

1.0-1.5mm

1.5-2.0mm

Check
(Cut exactly at
right angles.)

Flares inner
surface must
be flaw-free.
Remove burrs

The pipe end must


be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.

WARNING
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.

3P182980-1E

Installation of Indoor / Outdoor Unit

257

Installation of Outdoor Unit

EDSG281001

Outdoor Unit Installation (2)


4.

Refrigerant piping.
CAUTION

1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.
[Apply oil]
Do not apply refrigeration
oil to the outer surface.

[Tighten]
Apply refrigeration
oil to the inner
surface of the flare.

Torque wrench

Flare nut
Spanner

Do not apply refrigeration oil to the flare


nut avoid tightening with over torque.

5.

Piping
union

Flare nut tightening torque


Gas side
Liquid side
5/8 inch
1/4 inch
61.8-75.4N m
14.2-17.2N m
(630-770kgf cm) (144-175kgf cm)

Valve cap tightening torque


Gas side
Liquid side
5/8 inch
1/4 inch
48.1-59.7N m
21.6-27.4N m
(490-610kgf cm) (220-280kgf cm)

Service port cap tightening torque

10.8-14.7N m (110-150kgf cm)

Flare nut

Purging air and checking gas leakage.


When piping work is completed, it is necessary to purge the air and check for gas leakage.

WARNING
1)
2)
3)
4)

Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
To prevent air pollution, a vacuum pump should be used for air purging wherever possible.
Refrigerant gas leaks during air purging, ventilate the room as soon as possible.
Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may
damage the vacuum pump or the unit.
If using additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a
vacuum pump, then charge additional refrigerant.
Use a hexagonal wrench (4mm) to operate the stop valve rod.
All refrigerant pipe joints should be tightened with a torque wrench at the specified tightening torque.

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valves service port.
2) Fully open gauge manifolds low-pressure valve (Lo) and completely close its high-pressure valve (Hi).
(High-pressure valve subsequently requires no operation.)
3) Do vacuum pumping and make sure that the compound pressure gauge reads 0.1MPa (76cmHg)*1.
4) Close gauge manifolds low-pressure valve (Lo) and stop vacuum pump.
(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2.
5) Remove covers from liquid stop valve and gas stop valve.
6) Turn the liquid stop valves rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor units flare and outdoor units flare and valve rods.
After the check is complete, wipe all soapy water off.
7) Disconnect charging hose from gas stop valves service port, then fully open liquid and gas stop valves.
(Do not attempt to turn valve rod beyond its stop.)
8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

*1. Pipe length vs. vacuum pump run time


Pipe length
Run time

Up to 15 metres
Not less than 10 min.

More than 15 metres


Not less than 15 min.

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe
joint may exists. Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

3P182980-1E

258

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Outdoor Unit Installation (3)


6.

Refilling the refrigerant.


Check the type of refrigerant to be used on the machine nameplate.
Precautions when adding R410A
Fill from the liquid pipe in liquid form.
It is a mixed refrigerant, so adding it in gas form may cause the
refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not.
(It should have something like liquid filling siphon attached displayed on it.)

7.

Filling a cylinder with an


attached siphon

Filling other cylinders

Stand the cylinder upright


when filling.

Turn the cylinder


upside-down when filling.

There is a siphon pipe


inside, so the cylinder
need not be upsidedown to fill with liquid.

Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.

Refrigerant piping work.

Wall

Be sure to
place a cap.

7-1 Cautions on pipe handling.

Rain

If no flare cap is
available, cover the
flare mouth with
tape to keep dirt or
water out.

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for bending.

7-2 Selection of copper and heat insulation materials.


When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/mhC)
Refrigerant gas pipes surface temperature reaches 110C max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
Gas side

Liquid side

Gas pipe thermal insulation

Liquid pipe thermal insulation

O.D. 15.9mm

O.D. 6.4mm

I.D. 16-20mm

I.D. 8-10mm

Minimum bend radius

Inter-unit wiring
Gas pipe

Liquid pipe

Thickness 10mm Min.

50mm or more

30mm or more

Thickness 1.0mm
(C1220T-O)

Thickness 0.8mm
(C1220T-O)

Gas pipe
insulation

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Liquid pipe
insulation
Finishing tape

Drain hose

Pump Down Operation


In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After five to ten minutes, close the liquid stop valve with a
hexagonal wrench.
4) After two to three minutes, close the gas stop valve and stop
forced cooling operation.

Service port

Hexagonal
wrench

Close

Gas stop valve


Liquid stop valve

valve cap
Forced cooling operation
1) Press the Forced Operation switch (SW1) to begin forced cooling. Press the Forced Operation switch (SW1) again
to stop forced cooling.

S102

S2

ON

A B CD

LED-A

SW4

SW1

Forced
operation
switch

3P182980-1E

Installation of Indoor / Outdoor Unit

259

Installation of Outdoor Unit

EDSG281001

Wiring
WARNING
1) Do not use tapped wires, stranded wires, extensioncords, or starburst connections, as they may cause
overheating, electrical shock, or fire.
2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain
pump, etc., from the terminal block.) Doing so may cause electric shock or fire.
3) Be sure to install an earth leak detector. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that it must be used an earth leak detector capable handling
harmonics in order to prevent malfunctioning of the earth leak detector itself.)
4) Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
Do not turn ON the safety breaker until all
work is completed.
1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between
the indoor and outdoor units so that the
terminal numbers match. Tighten the
terminal screws securely. We recommend
a flathead screwdriver be used to tighten
the screws.

Firmly fix the wires with


the terminal screws.
Outdoor unit
1 23

When wire length exceeds 10m,


use 2.0mm diameter wires.

Indoor
unit

LN

Use 2.0mm diameter wires.

1
2
3

Safety
breaker
20A
Firmly fix the wires with
the terminal screws.

Earth leakage
circuit breaker

H05VV

Power supply
50Hz 220-240V
: FVMA
60Hz 220-230V
50Hz 220-240V : FV1A

Earth

Power supply terminal block

Use the specified wire type


and connect it securely.

Firmly secure wire retainer


so wire terminations will not
receive external stress.

Shape wires so that the


service lid and stop
valve cover fit securely.

Observe the notes mentioned below when wiring to the power supply terminal board.
Precautions to be taken for power supply wiring.
Use a round crimp-style terminal for connection to the power supply terminal board.
In case it cannot be used due to unavoidable reasons, be sure to observe the
following instruction.
Place the round crimp-style terminals on the wires up to the covered part and secure in place.
Ground terminal installation
Use the following method when installing
the round crimp-style terminal.

Round crimp-style
terminal

Electric Wire

Screw

Screw

Round crimpstyle terminal

Flat washer
Round crimpstyle terminal

Flat washer

Good

Wrong

CAUTION
When connecting the connection wires to the terminal board using a single
core wire, be sure to perform curling.
Problems with the work may cause heat and fires.

Stripping wire at terminal block

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
3P182980-1E

260

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

Test Run and Final Check


1.

Trial Operation and Testing.


1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in cooling or heating mode.

For Heat pump


In cooling mode, select the lowest programmable temperature; in heating mode, select the highest
programmable temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (26C to 28C in cooling mode, 20C
to 24C in heating mode).
3) For protection, the unit disables restart operation for 3 minutes after it is turned off.

For Cooling only

Select the lowest programmable temperature.


1) Trial operation in cooling mode may be disabled depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (26C to 28C).
3) For protection, the unit disables restart operation for 3 minutes after it is turned off.

1-3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions
and parts, such as louver movement, are working properly.
The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for
some time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the
original operation mode when the circuit breaker is opened again.

2.

Test Items.
Test items

Symptom

Indoor and outdoor units are installed properly on


solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating function

Refrigerant gas and liquid pipes and indoor drain


hose extension are thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly earthed.

Electrical leakage

The specified wires are used for interconnecting


wire connections.

Inoperative or burn damage

Indoor or outdoor units air intake or exhaust has


clear path of air.
Stop valves are opened.

Incomplete cooling/heating function

Indoor unit properly receives remote controller


commands.

Inoperative

Check

3P182980-1E

Installation of Indoor / Outdoor Unit

261

Installation of Outdoor Unit

EDSG281001

3.4

RZR71KUV1 / RZR100KUV1 / RZR125KUV1 / RZR140KUV1


RZR100HUY1 / RZR125HUY1 / RZR140HUY1

3.4.1

Installation

1PN11569A

262

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

1PN11569A

Installation of Indoor / Outdoor Unit

263

Installation of Outdoor Unit

EDSG281001

1PN11569A

264

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

1PN11569A

Installation of Indoor / Outdoor Unit

265

Installation of Outdoor Unit

EDSG281001

1PN11569A

266

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

1PN11569A

Installation of Indoor / Outdoor Unit

267

Installation of Outdoor Unit

EDSG281001

1PN11569A

268

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

1PN11569A

Installation of Indoor / Outdoor Unit

269

Installation of Outdoor Unit

EDSG281001

1PN11571A

270

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

1PN11571A

Installation of Indoor / Outdoor Unit

271

Installation of Outdoor Unit

EDSG281001

1PN11571A

272

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

1PN11571A

Installation of Indoor / Outdoor Unit

273

Installation of Outdoor Unit

EDSG281001

1PN11571A

274

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

1PN11571A

Installation of Indoor / Outdoor Unit

275

Installation of Outdoor Unit

EDSG281001

1PN11571A

276

Installation of Indoor / Outdoor Unit

EDSG281001

Installation of Outdoor Unit

1PN11571A

Installation of Indoor / Outdoor Unit

277

Installation of Outdoor Unit

278

EDSG281001

Installation of Indoor / Outdoor Unit

EDSG281001

Part 3
Detail Information
of Options
3
1. Accessories.........................................................................................281
1.1 Indoor Unit............................................................................................281
1.2 Outdoor Unit .........................................................................................284

2. Remote Controller ...............................................................................285


2.1 BRC1C61 Wired Remote Controller ................................................285
2.2 BRC1D61 Wired Remote Controller with
Weekly Schedule Timer .......................................................................289
2.3 BRC1E61 Navigation Remote Controller (Wired Type)...................297
2.4 Wireless Remote Controller .................................................................336

3. FCQ.....................................................................................................338
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
3.11
3.12
3.13
3.14
3.15
3.16

BYCP125K-W1 Decoration Panel ...................................................338


KDBH55K160F Sealing Member of Air Discharge Outlet................343
KDBP55H160FA Panel Spacer .......................................................347
KDDP55K160(K) Fresh Air Intake Kit (Chamber Type)...................350
KDDP55X160 Fresh Air Intake Kit (Direct Installation Type)...........355
KAFP556H80 / KAFP556H160, KAFP557H80 / KAFP557H160
High Efficiency Filter (Including Chamber) ......................................358
KAFP552H80 / KAFP552H160, KAFP553H80 / KAFP553H160
Replacement High Efficiency Filter..................................................361
KDDFP55H160 High Efficiency Filter Chamber ..............................362
KAFP551K160 Replacement Long-life Filter ...................................365
KAFP55H160 Ultra Long-life Filter Unit (Including Chamber) .........366
KAFP55H160H Replacement Ultra Long-life Filter..........................369
KKSJ55K160 Chamber Connection Kit ...........................................370
KDJP55H80 / KDJP55H160 Branch Duct Chamber........................371
KDTP55K80 / KDTP55K160 Insulation Kit for High Humidity..........374
KRP1H98 Installation Box for Adaptor PCB ....................................376
KRCS01-4B Remote Sensor (for Indoor Temperature)...................381

4. FFQ .....................................................................................................385
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8

BYFQ60B8W1 Decoration Panel.....................................................385


KDBH44BA60 Sealing Member of Air Discharge Outlet..................388
KDBQ44BA60A Panel Spacer.........................................................390
KAFQ441BA60 Replacement Long-life Filter ..................................393
KDDQ44XA60 Fresh Air Intake Kit (Direct Installation Type) ..........394
DTA112BA51 Interface Adaptor for SkyAir Series ..........................396
KRP1BA101 Installation Box for Adaptor PCB ................................398
KRCS01-1B Remote Sensor (for Indoor Temperature)...................403

5. FHQ.....................................................................................................407
5.1 KDU50N60VE / KDU50N125VE Drain-up Kit..................................407

Detail Information of Options

279

EDSG281001

5.2 KAF501DA56 / KAF501DA80 / KAF501DA112 / KAF501DA160


Replacement Long-life Filter............................................................412
5.3 KHFP5MA35 / KHFP5MA63 / KHFP5MA160
L-type Piping Kit (for Upward Direction) ..........................................413
5.4 KRP1CA93 Installation Box for Adaptor PCB..................................414
5.5 KRCS01-1B Remote Sensor (for Indoor Temperature)...................416
5.6 DTA112BA51 Interface Adaptor for SkyAir Series ..........................420
5.7 KJB212AA / KJB311AA Electrical Box with Earth Terminal ............422

6. FBQ.....................................................................................................424
6.1 KTBJ25K56W / KTBJ25K80W (T) (F) / KTBJ25K160W(T) (F)
Service Access Panel ......................................................................424
6.2 KDAJ25K56A / KDAJ25K71A / KDAJ25K140A
Air Discharge Adaptor......................................................................427
6.3 KAF372AA80 / KAF372AA160 / KAF373AA80 / KAF373AA160
High Efficiency Filter ........................................................................429
6.4 KDDF37AA80 / KDDF37AA160 High Efficiency Filter Chamber .....430
6.5 KAF371AA80 / KAF371AA160 Long Life Filter ...............................433
6.6 KAF375AA80 / KAF375AA160 Long Life Filter Chamber Kit ..........434
6.7 KRP4A96 Mounting Plate for Adaptor PCB.....................................437
6.8 KRCS01-4B Remote Sensor (for Indoor Temperature)...................440
6.9 DTA112BA51 Interface Adaptor for SkyAir Series ..........................444

7. Outdoor Unit........................................................................................446
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8

280

KPW937A4 Air Direction Adjustment Grille .....................................446


KPW945A4 Air Direction Adjustment Grille .....................................447
KKP937A4 Drain Plug .....................................................................448
KKP945A4 Drain Plug .....................................................................449
KKPJ5F180 Central Drain Plug .......................................................450
K-KYZP15C Wire Fixture for Preventing Overturning......................451
KPT-60B160 Fixture for Preventing Overturning .............................453
KRP58M51 Demand Adaptor ..........................................................455

Detail Information of Options

EDSG281001

Accessories

1. Accessories
1.1

Indoor Unit

1.1.1

FCQ

Optional
accessories
Name of option

Remark

Decoration panel
Sealing member of air discharge outlet
Panel spacer

Fresh air intake kit

Without T-joint
pipe and fan
Chamber type
With T-joint pipe,
without fan
Direct installation type

Chamber connection kit *2


Insulation kit for high humidity
High-efficiency filter
Replacement high-efficiency
Filter

(Colorimetric method 65%)


(Colorimetric method 90%)
(Colorimetric method 65%)
(Colorimetric method 90%)

High-efficiency filter chamber


Replacement long-life filter
Ultra long-life filter
Replacement ultra long-life filter
Branch duct chamber
Wired type *1
Remote controller
Wireless type
Wired remote controller with weekly schedule timer *1
Navigation remote controller Wired type *1
Central remote controller *3
Unified ON/OFF controller *3
Schedule timer *3
intelligent Touch Controller *3
Adaptor for wiring *4
Group control adaptor *4
Installation box for adaptor PCB
Remote sensor (for indoor temperature)

Kit name
FCQ100 FCQ125 FCQ140
FCQ71KVEA
KVEA
KVEA
KVEA
BYCP125K-W1
KDBH55K160F
KDBP55H160FA
KDDP55K160
KDDP55K160K
KDDP55X160
KKSJ55K160
KDTP55K80
KDTP55K160
KAFP556H80
KAFP556H160
KAFP557H80
KAFP557H160
KAFP552H80
KAFP552H160
KAFP553H80
KAFP553H160
KDDFP55H160
KAFP551K160
KAFP55H160
KAFP55H160H
KDJP55H80
KDJP55H160
BRC1C61
BRC7F632F
BRC1D61
BRC1E61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1C63
KRP4AA53
KRP1H98
KRCS01-4B
C : 3D058465A

Notes:

*1. Wiring for wired remote controller to be procured locally.


*2. Required for installing high-efficiency filter of ultra long-Llife filter.
*3. The indoor unit is equipped standardly with the Interface for SkyAir series and an option is unnecessary.
*4. Installation box for adaptor PCB (KRP1H98) is necessary.

Detail Information of Options

281

Accessories

1.1.2

EDSG281001

FFQ

Optional
accessories

Name of option

Remark

Kit name
FFQ35BV1B FFQ50BV1B
BYFQ60B8W1
BRC1C61
BRC7E531W
BRC1D61
BRC1E61
KRP1BA57
KRP4AA53
KRCS01-1B
KRP1BA101
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
DTA112BA51
KAFQ441BA60
KDDQ44XA60
KDBH44BA60
KDBQ44BA60A

FFQ25BV1B

Decoration panel
Remote controller

Wired type *1
Wireless type

Wired remote controller with weekly schedule timer *1


Navigation remote controller Wired type *1
Adaptor for wiring *2
Group control adaptor *2
Remote sensor (for indoor temperature)
Installation box for adaptor PCB
Central remote controller *3
Unified ON/OFF controller *3
Schedule timer *3
intelligent Touch Controller *3
Interface adaptor for SkyAir series
Replacement long-life filter
Fresh air intake kit
Direct installation type
Sealing member of air discharge outlet
Panel spacer

FFQ60BV1B

C : 3D038936A

Notes:

1.1.3

*1. Wiring for wired remote controller to be procured locally.


*2. Installation box for adaptor PCB (KRP1BA101) is necessary.
*3. This optional accessory requires DTA112BA51.

FHQ

Optional
accessories

Kit name
Name of option
Long-life filter

Remark
Resin net

Drain-up kit

FHQ50
BVV1B

KAF501DA56

KHFP5
MA35

KAF501 KAF501
DA112 DA160

KDU50N125VE

BRC1C61

Wireless type

BRC7EA66

KHFP5MA160

BRC1D61

Wired type *1

BRC1E61

Central remote controller *2

DCS302CA61

Unified ON/OFF controller *2

DCS301BA61

Schedule timer *2

DST301BA61

intelligent Touch Controller *2

DCS601C51

Adaptor for wiring

KRP1BA54
KRP4AA52

Interface adaptor for SkyAir series

DTA112BA51

Installation box for adaptor PCB

282

KAF501DA80

Wired type *1

Group control adaptor *3

Notes:

FHQ71 FHQ100 FHQ125


BVV1B BVV1B BVV1B

KHFP5MA63

Wired remote controller with weekly schedule timer *1


Navigation remote controller

FHQ60
BVV1B

KDU50N60VE

L-type piping kit (for upward direction)


Remote controller

FHQ35
BVV1B

KRP1CA93

Remote sensor (for indoor temperature)

KRCS01-1B

Electrical box with earth terminal (3 blocks)

KJB311AA

Electrical box with earth terminal (2 blocks)

KJB212AA
C : 3D038056A
C : 3D044485B

*1. Wiring for wired remote controller to be procured locally.


*2. This optional accessory requires DTA112BA51.
*3. Installation box for adaptor PCB (KRP1CA93) is necessary.

Detail Information of Options

EDSG281001

1.1.4

Accessories

FBQ-B

Optional
accessories

Name of option

Remark

Service access panel

KTBJ25K56W

Air discharge adaptor


Remote controller

Kit name
FBQ50BV1A
KDAJ25K56A

FBQ60BV1A

KDAJ25K71A

Wired type *1

BRC1C61

Wireless type

BRC4C62

Wired remote controller with weekly schedule timer *1

BRC1D61

Navigation remote controller

BRC1E61

Wired type *1

FBQ71BV1A

KTBJ25K80W

Adaptor for wiring (interlock for fresh air intake fan)

KRP1BA54

Group control adaptor

KRP4AA51

Interface adaptor for SkyAir series

DTA112BA51

Central remote controller *2

DCS302CA61

Unified ON/OFF controller *2

DCS301BA61

Schedule timer *2

DST301BA61

intelligent Touch Controller *2

DCS601C51

C : 4D053094A

Notes:

1.1.5

*1. Wiring for wired remote controller to be procured locally.


*2. This optional accessory requires DTA112BA51.

FBQ-D

Optional
accessories

Name of option

Remark

Kit name
FBQ71DV1

FBQ100DV1 FBQ125DV1 FBQ140DV1

65%

KAF372AA80

KAF372AA160

90%

KAF373AA80

KAF373AA160

Filter chamber

KDDF37AA80

KDDF37AA160

Long life replacement filter

KAF371AA80

KAF371AA160

Long life filter chamber kit

KAF375AA80

KAF375AA160

KTBJ25K80W

KTBJ25K160W

KTBJ25K80F

KTBJ25K160F

High efficiency filter

Service access panel


Air discharge adaptor
Remote controller

KTBJ25K160T

KDAJ25K71A

KDAJ25K140A

Wired type *2

BRC1C61

Wireless type

BRC4C62

Wired remote controller with weekly schedule timer *2


Navigation remote controller

KTBJ25K80T

Wired type *2

Adaptor for wiring

BRC1D61
BRC1E61
*KRP1C64

Wiring adaptor for electrical appendices (2)

*KRP4AA51

Remote sensor (for indoor temperature)

KRCS01-4B

Mounting plate for adaptor PCB **

KRP4A96 *5 *6

Interface adaptor for SkyAir series

DTA112BA51

Central remote controller *3

DCS302CA61

Unified ON/OFF controller *3

DCS301BA61

Schedule timer *3

DST301BA61
3D066072
3D066074

Notes:

*1. If installing a high efficiency filter on the unit, an assembly chamber for either bottom or rear suction is
required.
*2. Wiring for wired remote controller to be procured locally.
*3. This optional accessory requires DTA112BA51.
*4. Mounting plate ** is necessary for each adaptor marked*.
*5. Up to 2 adaptors can be fixed for each mounting plate.
*6. Only one mounting plate can be installed for each indoor unit.

Detail Information of Options

283

Accessories

EDSG281001

1.2

Outdoor Unit

1.2.1

RXS

Optional
accessories

Name of option

Remark

Kit name
RXS50FAVMA

RXS60FVMA

Air direction adjustment grille


One set includes 5
pieces for 5 units

Drain plug

1.2.2

KKP937A4

KKP945A4

RKS

Optional
accessories

Name of option

Remark

Kit name
RKS25AVMG

Air direction adjustment grille

RKS35AVMG

RKS50AVMG

KPW937A4

One set includes 5


pieces for 5 units

Drain plug

1.2.3

RXS71FVMA

KPW945A4

RKS60AVMG

KPW945A4
KKP937A4

RZR

Optional
accessories

Kit name
Name of option

RZR71
KUV1

RZR100 RZR125 RZR140 RZR100 RZR125 RZR140


KUV1
KUV1
KUV1
HUY1
HUY1
HUY1

Central drain plug

KKPJ5F180

Wire fixture for preventing overturning

K-KYZP15C

Fixture for preventing overturning

KPT-60B160

Demand adaptor

KRP58M51
4D046721F

284

Detail Information of Options

EDSG281001

Remote Controller

2. Remote Controller
2.1

BRC1C61 Wired Remote Controller

Names and functions of parts


5 12

3
7

hr

6
8

hr

NOT
AVAILABLE

TEST

L H

14

9
11
10
13
21
20

TEST

16

1
2

19

15

17

ON/OFF BUTTON
Press the button and the system will start.
Press the button again and the system will stop.
OPERATION LAMP (RED)
The lamp lights up during operation.
DISPLAY
(UNDER CENTRALIZED
CONTROL)
When this display shows, the system is UNDER
CENTRALIZED CONTROL.
DISPLAY

(VENTILATION/AIR CLEANING)
This display shows that the total heat exchange
and the air cleaning unit are in operation
(These are optional accessories).

DISPLAY
(OPERATION MODE)
This display shows the current OPERATION
MODE. For cooling only type,
(Auto)
and (Heating) are not installed.

DISPLAY
TEST (INSPECTION/TEST
OPERATION)
When the INSPECTION/TEST OPERATION
BUTTON is pressed, the display shows the
system mode is in.
hr

DISPLAY

(PROGRAMMED TIME)

18

22

12

DISPLAY

(DEFROST)

NON-FUNCTIONING DISPLAY
If that particular function is not available, pressing
the button may display the words NOT
AVAILABLE for a few seconds.
When running multiple units simultaneously the
13 NOT AVAILABLE message will only be appear
if none of the indoor units is equipped with the
function. If even one unit is equipped with the
function, the display will not appear.
14
15

TIMER MODE START/STOP BUTTON


TIMER ON/OFF BUTTON

INSPECTION/TEST OPERATION BUTTON


16 This button is used only by qualified service
persons for maintenance purposes.
PROGRAMMING TIME BUTTON
17 Use this button for programming START and/or
STOP time.
TEMPERATURE SETTING BUTTON
18
Use this button for SETTING TEMPERATURE.
FILTER SIGN RESET BUTTON
19

hr

This display shows the PROGRAMMED TIME


of the system start or stop.

DISPLAY
(SET TEMPERATURE)
This display shows the set temperature.

DISPLAY
(FAN SPEED)
This display shows the set fan speed.

10
11

DISPLAY
DISPLAY

(AIR FLOW FLAP)


(TIME TO CLEAN AIR FILTER)

FAN SPEED CONTROL BUTTON


20 Press this button to select the fan speed,
HIGH or LOW, of your choice.
OPERATION MODE SELECTOR BUTTON
21
Press this button to select OPERATION MODE.
AIR FLOW DIRECTION ADJUST BUTTON
22
NOTE
For the sake of explanation, all indications are shown
on the display in the above figure contrary to actual
running situations.
3PA59583-16Z

Detail Information of Options

285

Remote Controller

EDSG281001

Installation

286

Detail Information of Options

EDSG281001

Remote Controller

Detail Information of Options

287

Remote Controller

Notes:

EDSG281001

1. Setting is carried out in the group mode, however, set the mode number inside the ( ) for individual setting of
the each indoor unit or confirmation after setting.
2. The SECOND CODE number is set to 01 when shipped from the factory.
However for the following cases it is set to 02.
Air flow direction range setting.
3. Do not make any settings not given in the table above.
4. Not displayed if the indoor unit is not equipped with that function.
5. When returning to the normal mode, 88 may be displayed in the LCD in order for the remote controller to
initialize itself.
2P068938

288

Detail Information of Options

EDSG281001

2.2

Remote Controller

BRC1D61 Wired Remote Controller with Weekly Schedule Timer


Adds new, advanced functions to those of the wired remote controller.
Includes ventilation mode and airflow rate switching, the main

functions of HRV series.


24-hour clock function (1-hour backup for power failures).
Programming function for each day of week.
Scheduling possible of start/stop and temperature limit

(5 settings/day).
Programming can be enabled or disabled.
Copy function for programmed schedules.

Features and functions


The BRC1D61 is a state of the art remote controller that offers full control over your installation.
1

BASIC REMOTE CONTROLLER

The basic remote controller functions are:

ON/OFF,

operation mode change-over,

temperature, adjustment,

air volume adjustment

air flow direction adjustment.


2

CLOCK FUNCTION

The clock functions are:

24 hours real time clock,

day of the veek indicator.


3

SCHEDULE TIMER FUNCTION

The schedule timer functions are:

a maximum of 5 actions can be programmed for each day of the week (totalling 35 actions),

schedule timer can be enabled/disabled at any time,

linked to a set temperature or a LIMIT operation or an OFF operation,

"last command" overrules previous command until next scheduled command.


4

LIMIT OPERATION

Limit operation provides thermostat control within the range of the set minimum and maximum temperature.
The minimum temperature setting will trigger heating, the maximum temperature setting will trigger cooling.
5

LEAVE HOME

The leave home function prevents the room temperature from dropping when the occupants are out for a longer
period. If the room temperature drops below 10C, heating is started automatically. As soon as 15C is reached, the
controller returns to its original status.
6

BUTTON PERMISSION LEVEL

Three hierarchical permission levels can be set to limit the user action.
3P107422-3D

Detail Information of Options

289

Remote Controller

EDSG281001

Names and functions

3P107422-3D

290

Detail Information of Options

EDSG281001

Remote Controller

Name and function of switches and icons (refer to figure 1)

3P107422-3D

Detail Information of Options

291

Remote Controller

EDSG281001

3P107422-3D

292

Detail Information of Options

EDSG281001

Remote Controller

Installation

3P107422-4D

Detail Information of Options

293

Remote Controller

EDSG281001

3P107422-4D

294

Detail Information of Options

EDSG281001

Remote Controller

3P107422-4D

Detail Information of Options

295

Remote Controller

EDSG281001

3P107422-4D

296

Detail Information of Options

EDSG281001

Remote Controller

2.3

BRC1E61 Navigation Remote Controller (Wired Type)

2.3.1

Features

3
BRC1E61

Clear Display Equipped with backlight and large sized character display and buttons.
Stylish Basic tone is white and arrow keys are located at the center.
Simple Operation Simple operation used with arrow keys and menu-driven method.
Multilingual Display Available for selection of 10 languages to display arbitrarily
Other Features Wide variety of functions to meet customer needs such as schedule setting
and contact address display.

2.3.2

Dimensions
Unit (mm)

3D064037

Detail Information of Options

297

298

3P243520-1B

Detail Information of Options

Useful Information

Maintenance

Manipulating the Main Menu Screen ..................... 26

Menu Manipulation

Failure to observe these instructions properly may result in property


damage or personal injury, which may be serious depending on the
circumstances.

Failure to follow these instructions properly may result in personal


injury or loss of life.

Absolutely keep wet hands away.

Be sure to ground the unit.

WARNING

5/15/2009 10:20:58 AM

English

Do not clean the product with organic solvents such as paint thinner.
The use of organic solvents may cause crack damage to the product, electric shocks, or
re.

Do not use ammable materials (e.g., hairspray or insecticide) near the


product.

Improper installation may result in electric shocks or re.


Consult your Daikin dealer.

Do not relocate or reinstall the remote controller by yourself.

This may result in electric shocks or re.


Consult your Daikin dealer.

Do not modify or repair the remote controller.

Improper installation may result in electric shocks or re.


Consult your Daikin dealer.

Do not install the remote controller by yourself.

About Remote Controller

Absolutely keep water and moisture


away.

Always follow the instructions given.

Never do.

The following pictograms are used in this manual.

CAUTION

WARNING

The precautions described herein are classified as WARNING and CAUTION.


They both contain important information regarding safety. Be sure to observe all precautions
without fail.

Read the safety precautions attentively for the correct use of the product.

5/15/2009 10:20:58
01_EN_3P243520-1B.indd
AM
2

After-sale Service ................................................... 54

Error code Display ................................................. 53

Maintenance of Unit and LCD ................................ 52

Filter Sign Resetting ............................................... 51

Language changeover ........................................... 50

Clock Setting .......................................................... 48

Setting Status List .................................................. 48

Convenient Functions ............................................ 45

Service Contact/Model Information ........................ 44

Timer Settings ........................................................ 34

Ventilation .............................................................. 32

Quick Cooling/Heating On/Off ................................ 31

Airow Direction Setting ......................................... 28

Set temp mode changeover ................................... 27

Main Menu Items ................................................... 24

Ease of Cellular-like Function Settings

Key Lock ............................................................... 23

Eligibility ................................................................. 21

Setting Method of the Cooling/Heating Selection

Ventilation Operation .............................................. 20

Quick Reference of
Main Menu Items

01_EN_3P243520-1B.indd 1

English

(Use of Direct Buttons)

Home Leave ........................................................... 19

Program Dry Operation .......................................... 17

Basic Operation Method

Simple Settings in Direct Buttons for


Basic Operation Items

Names and Functions ............................................... 8

Safety Precautions Items to be Strictly Observed ......... 2

Safety Precautions

2.3.3

Cool/Heat/Auto/Fan Operation .............................. 14

Notices

Contents

Remote Controller
EDSG281001

Operation Manual

Safety precautions

Detail Information of Options

3P243520-1B

299

01_EN_3P243520-1B.indd 3

English

Using the product in such places may cause re or product failures.

5/15/2009 10:20:59 AM

English

The use of any other power supply may cause heat generation, re, or product failures.

Be sure to use a dedicated power supply for the air conditioner.

Do not operate the air conditioner in that case, or otherwise a malfunction, electric
shock, or re may result.

Consult the dealer if the air conditioner submerges owing to a natural


disaster, such as a ood or typhoon.

Failure to install an earth leakage breaker may result in electric shocks or re.

Be sure to install an earth leakage breaker.

When the air conditioner is to be installed in a small room, it is necessary to take proper
measures so that the amount of any leaked refrigerant does not exceed the
concentration limit in the event of a leakage.
Otherwise, this may lead to an accident due to oxygen depletion.

Consult your local dealer regarding what to do in case of refrigerant


leakage.

Continued operation under such circumstances may result in a failure, electric shocks or
re hazards.

When the air conditioner is malfunctioning (giving off a burning odour, etc.)
turn off power to the unit and contact your local dealer.

Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect
earthing may result in electric shocks or re. A high surge current from lightning or other
sources may cause damage to the air conditioner.

Be sure to earth the unit.

Otherwise, re or water leakage may result.


Furthermore, the fan will rotate abruptly if power failure compensation is enabled, which
may result in injury.

Do not start or stop operating the air conditioner with the power supply
breaker turned ON or OFF.

Use of an ordinary conductive wire may cause malfunctions or re.

In the case of using a load breaker provided with a fuse, make sure that
the capacity of the fuse is correct.

If the air conditioner is not operating correctly, i.e. not generating cool or warm air,
refrigerant leakage could be the cause. Consult your dealer for assistance. The
refrigerant within the air conditioner is safe and normally does not leak. However, in the
event of a leakage, contact with a naked burner, heater or cooker may result in generation
of noxious gas. Do not longer use the air conditioner until a qualied service person
conrms that the leakage has been repaired.

Beware of re in case of refrigerant leakage.

WARNING

Safety Precautions

5/15/2009 10:20:58
01_EN_3P243520-1B.indd
AM
4

Do not use the product in places with excessive oily smoke, such as
cooking rooms, or in places with ammable gas, corrosive gas, or metal
dust.

Oil vapor may cause crack damage, electric shocks, or re.

Do not use the product in the atmosphere contaminated with oil vapor,
such as cooking oil or machine oil vapor.

If a defect results from your own workmanship, it may result in water leaks, electric
shock or re.

Contact professional personnel about attachment of accessories and be


sure to use only accessories specied by the manufacturer.

Injury may result due to contact with the air conditioners highspeed fan blades.

Be aware that prolonged, direct exposure to cool or warm air from the air
conditioner, or to air that is too cool or too warm can be harmful to your
physical condition and health.
Do not place objects, including rods, your ngers, etc., in the air inlet or
outlet.

WARNING

Indoor Unit and Outdoor Unit

If water gets into the remote controller there is a risk of electrical leakage and damage to
electronic components.

Do not leave the remote controller wherever there is a risk of wetting.

Doing so may cause electric leakage and result in electric shocks or re.

Do not wash the remote controller.

To avoid electric shocks, do not operate with wet hands.

Touching the interior parts may result in electric shocks or re.


Consult your Daikin dealer or authorized contractor for internal inspections and
adjustments.

Never disassemble the remote controller.

Accidental operation by a child may result in impairment of bodily functions and harm
health.

Do not play with the unit or its remote controller.

CAUTION

Items to be Strictly Observed

EDSG281001
Remote Controller

300

3P243520-1B

Detail Information of Options

01_EN_3P243520-1B.indd 5

English

5/15/2009 10:21:00 AM

English

If proper drainage from the outdoor drain pipe does not occur during air conditioner
operation, there could be a blockage due to dirt and debris build-up in the pipe.
This may result in a water leakage from the indoor unit. Under these circumstances,
stop air conditioner operation and consult your dealer for assistance.

Arrange the drain to ensure complete drainage.

If the units are not mounted securely, the units may fall or topple and injury may result.

Fix the units securely.

Leaves are a hotbed for small animals which can enter the unit. Once in the unit, such
animals can cause malfunctions, smoke or re when making contact with electrical
parts.

Do not place objects in direct proximity of the outdoor unit and do not let
leaves and other debris accumulate around the unit.

The use of an incorrect washing method or incorrect detergent may damage the resin
parts of the indoor unit or cause water leakage.
Moreover, malfunctions, smoke generation, or ignition may result if the electric parts or
motor in the indoor unit is wet with detergent.

Do not wash the interior of the indoor and outdoor units by yourself.
Always consult your Daikin dealer.

Failure to do so may result in an electric shock or injury.

Always stop the operation of the air conditioner and turn OFF the
breaker at the time of cleaning.

Be careful when using the air conditioner with other heating equipment.
Insufcient ventilation may result in oxygen deciency.

Perform ventilation from time to time.

Do not wash the air conditioner with water, as this may result in electric
shocks or re.

The motor in operation is at high temperatures and a burn may result.

Do not touch the motor at the time of lter replacement.

The base may topple down and injury may result.

Do not sit or stand on any unstable base at the time of operating or


maintaining the air conditioner.

CAUTION

Safety Precautions

5/15/2009 10:21:00
01_EN_3P243520-1B.indd
AM
6

In the event of a gas leakage, build-up of gas near the air conditioner may result in re
hazards.

Do not install the air conditioner at any place where there is a danger of
ammable gas leakage.

The containers may explode because the warm air output of the indoor or outdoor unit
will affect them.

Do not put ammable containers, such as spray cans, within 1m from the
blow-off mouth.

Be sure that children, plants or animals are not exposed directly to


airow from the unit, as adverse effects may ensue.

Do not place heaters directly below the unit, as resulting heat can cause
deformation.

Do not place appliances that produce naked ames in places exposed to


the air ow from the unit as this may impair combustion of the burner.

Do not use the air conditioner for cooling precision instruments, food, plants, animals or
works of art as this may adversely affect the performance, quality and/or longevity of the
object concerned.

Do not use the air conditioner for purposes other than those for which it
is intended.

Do not place water containers (ower vases, etc.) on the unit, as this
may result in electric shocks or re.

Under certain conditions, condensation on the main unit or refrigerant pipes, air lter dirt
or drain blockage may cause dripping, resulting in fouling or failure of the object
concerned.

Do not place objects that are susceptible to moisture directly beneath


the indoor or outdoor units.

The guard protects against the units high speed fan, which may cause injury.

Do not remove the outdoor units fan guard.

To avoid injury, do not touch the air inlet or aluminium ns of the unit.

Impaired air ow may result in insufcient performance or trouble.

Do not block air inlets nor outlets.

Falling or tumbling may result in injury.

Do not allow a child to mount on the outdoor unit or avoid placing any
object on it.

If left in a damaged condition, the unit may fall and cause injury.

After prolonged use, check the unit stand and its mounts for damage.

CAUTION

Items to be Strictly Observed

Remote Controller
EDSG281001

Detail Information of Options

3P243520-1B

301

English

Used to highlight the next items on the


right-hand side.
Each screen is scrolled in the right-hand
direction.
Home leave settings are enabled with this
button kept pressed for at least four
seconds. (See page 19.)

6. Right button (Be sure to press


the part with the symbol )

Used to lower the set temperature.


The next items on the lower side will be
highlighted.
(The highlighted items will be scrolled
continuously when the button is kept
pressed.)
Used to change the item selected.

5. Down button (Be sure to press


the part with the symbol )

Used to raise the set temperature.


The next items on the upper side will be
highlighted.
(The highlighted items will be scrolled
continuously when the button is kept
pressed.)
Used to change the item selected.

4. Up button (Be sure to press the


part with the symbol )

Used to indicate the main menu.


(See page 24 for the menu items.)
Used to enter the setting item selected.

3. Menu/Enter button

Press this button to select the fan speed of


your preference. (See page 15.)
* Available fan speed vary with the
connecting model.

2. Fan speed control button

Press this button to select the operation


mode of your preference. (See page 14.)
* Available modes vary with the connecting
model.

1. Operation mode selector button

5/15/2009 10:21:01
01_EN_3P243520-1B.indd
AM
9

English

Do not install the remote controller in places exposed to direct sunlight.


Otherwise, the LCD may become discolored and nothing may be displayed.
Do not pull or twist the remote controller cord.
Otherwise, the remote controller may error.
Do not press the buttons on the remote controller with objects with sharp ends.
Otherwise, the remote controller may receive damage or error.

NOTE

01_EN_3P243520-1B.indd 8

2. Fan speed control


button

10. Cancel button

3. Menu/Enter button

8. On/Off button

9. Operation lamp

4. Up button
5. Down button
6. Right button
7. Left button

11. LCD (with backlight)

1. Operation mode
selector button

Functions other than basic operation items (i.e., On/Off, Operation


mode selector, Fan speed control, and temperature settings) are set
from the menu screen.

Names and Functions

5/15/2009 10:21:01 AM

The backlight will be light for approximately


30 seconds by pressing any operation
button. Operate buttons excluding the On/
Off button while the backlight is lit.
If two remote controllers are used to control
a single indoor unit, the backlight of the
remote controller operated earlier than the
other one will be lit.

11. LCD (with backlight)

Used to return to the previous screen.

10.Cancel button

This lamp lights up during operation.


This lamp blinks if a error occurs.

9. Operation lamp (Green)

Press this button and system will start.


Press this button again and system will
stop.

8. On/Off button

Used to highlight the next items on the


left-hand side.
Each screen is scrolled in the left-hand
direction.
Home leave settings are enabled with this
button kept pressed for at least four
seconds. (See page 19.)

7. Left button (Be sure to press


the part with the symbol )

EDSG281001
Remote Controller

Names and functions

302

<Standard display example>

This function not available

20C

Set temperature

) display

6.Message

4.Set temperature
display
5.Defrost/Hot start

8.(

12.Home Leave
9.( ) display

3P243520-1B

Detail Information of Options

01_EN_3P243520-1B.indd 10

10

(with no airflow direction


settings)

Airflow direction
display

(with no fan speed


control function)

3.Fan speed display

(Displayed only when


the air conditioner is in
operation.)

13.Airflow direction

12:05

Setting

20C
20C

Set temp Room

--:--

Setting

20C

Set temp

<Detailed display example 2>

Return

Heat

Auto

<Detailed display example 1>

Return

Heat

Auto

) display

English

Displayed for a few seconds when an


operation button is pressed if the indoor
unit is not provided with the corresponding
function.
If a number of indoor units are in operation,
the message will appear only if none of the
indoor units is provided with the
corresponding function, i.e., the message
will not appear if at least one of the indoor
units is provided with the corresponding
function.

The following messages are displayed.


This function not available.

6. Message

If Ventilating operation
is displayed:
Displayed when a total heat exchanger
unit, such as the Ventiair, is connected.
For details, refer to the Operation Manual
of the Ventiair.

(See page 16.)

5. Defrost/Hot start

Used to display the temperature set for the


air conditioner.

4. Set temperature display

Used to display the fan speed that is set for


the air conditioner.
The fan speed will not be displayed if the
air conditioner does not have fan speed
control function.

3. Fan speed

Used to display the present automatic


operation mode (Cool or Heat).

2. Automatic operation mode

Used to display the present operation


mode Cool, Heat, Vent, Fan, Dry or Auto
mode.

1. Operation mode

5/15/2009 10:21:01
01_EN_3P243520-1B.indd
AM
11

English

(with no detailed items


selected)

Detailed selection

16. (

(with no clock settings)

Clock display

(with room
temperature settings)

15.Detailed selection

14.Clock (24 hours


real time clock)

The airow direction, clock, and detailed selection items appear


on the detailed display screen in addition to the items appearing
on the standard display.

Detailed display

7.Ventilation

3.Fan speed

2.Automatic
operation mode

Heat

11. Changeover under control


10.Under centralized
control
1.Operation mode
Auto

Standard display

Two types of liquid crystal display (LCD) are available. The standard display is by
default set.
To go to the detailed display, select the detailed display in the main menu. (See page 46.)
The displayed contents of the screen vary with the operation mode of the equipment
interlocked. (The following display will appear when the air conditioner is in automatic
heating operation.)

Liquid Crystal Display

Names and Functions

display (See page 23.)

Displayed if the schedule timer or OFF


reminder timer is enabled.

display (See page 34.)

Displayed when the key lock is set.

11

5/15/2009 10:21:02 AM

Displayed on the remote controller if the


remote controller has no cooling/heating
selection eligibility mode (see page 21).

(VRV only)

11. Changeover under control

Displayed if the system is under the


management of central control equipment
(optional accessories) and the operation of
the system through the remote controller is
prohibited.

10.Under Centralized control

9.

8.

Displayed when a total heat exchanger


unit, such as the Ventiair, is connected.
Ventilation mode icon.

These icons indicate the current ventilation


mode (HRV only) (AUTOMATIC, HEAT
EXCHANGE, BYPASS).

AIR Purifying ICON


This icon indicates that the air cleaning unit
(option) is operational.

7. Ventilation / Purifying

Clean the lter.


Clean the element.
Clean the lter and element.
Displayed when the time to clean the lter
or element has come (see page 51).

Quick Cool/Heat (SkyAir only)


Displayed if the quick cooling/heating
function is turned ON (see page 31).

Error: Press Menu Button.


Warning: Press Menu Button.
Displayed if the error or warning is detected
(see page 53).

Remote Controller
EDSG281001

(See page 19.)

Detail Information of Options

3P243520-1B

303

01_EN_3P243520-1B.indd 12

12

display

Displayed to inform that the clock needs


setting again.
The schedule timer function will not work
unless the clock is set again.

16.

Displayed if the detailed display items are


selected (see page 47).
No detailed items are by default selected.

15.Detailed selection

Displayed if the clock is set (see page 48).


If the clock is not set, -- : -- will be
displayed.

14.Clock (24 hours real time clock)

Displayed when the airow direction and


swing are set (see page 28).
This item is not displayed if the system is
not provided with a function to set airow
directions.

Home Leave is disabled

OFF

13.Airow direction

Home Leave is active

FLASHING

The home leave icon shows the status of


the home leave function.
ON
Home leave is enabled

12.Home leave

Names and Functions

English

5/15/2009 10:21:03
01_EN_3P243520-1B.indd
AM
13

English

5/15/2009 10:21:03 AM

13

EDSG281001
Remote Controller

304

3P243520-1B

Detail Information of Options

01_EN_3P243520-1B.indd 14

Return

Cool

Return

Setting

28C

Set temperature

Operation Method

14

Setting

Setting

Schedule timer
Off reminder timer

Timer setting

Return

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model info

MainMenu

Disable
Disable

2/2

1/2

buttons to select

* Items presently enabled or disabled are


displayed.

screen.
Press Menu/Enter button to display
the timer settings screen.

Timer setting on the main menu

Press

(See page 26.)

Displays the main menu screen.

Explains a button operation


procedure for the remote controller.
Operate the buttons according to
the procedure.
Displays the positions of
buttons to be operated.

English

Low

Return

Cool

Return

Cool

Middle

Setting

28C

Set temperature

Setting

28C

Set temperature

High

5/15/2009 10:21:03
01_EN_3P243520-1B.indd
AM
15

English

Note
Before making a mode change, make sure that Changeover
under control is not displayed on the remote controller.
The cooling or heating mode cannot be selected if the above is
displayed on the remote controller. See page 21 if Changeover
under control display blinks.

* Unavailable operation modes are not displayed.


* Only the Cooling or Fan mode can be selected if the air
conditioner is a cooling-only model.
* The Auto mode can be set in the case of the VRV cooling/
heating simultaneous operation system.
* Changeover under control will appear on each remote controller,
but only the Cooling or Fan mode can be set in the case of the
VRV cooling-only system.

Press Operation Mode Selector button


several times until the desired mode
Cooling, Heating, Fan, or Auto mode is
selected.

For mechanical protection purposes, turn ON the system at least six hours before starting the
operation of the system.
Do not turn OFF the system in season in order to ensure the smooth starting of the system.

Preparation

Describes screens that


will be displayed on the
remote controller in
operation.

Operation screen
display

Operation Method

Remote Controller Functions

Operation button
display

(SkyAir and VRV)

Operation procedure

Cool/Heat/Auto/Fan Operation

Basic Operation Method (Use of Direct Buttons)

15

5/15/2009 10:21:03 AM

* The airow direction of the system cannot be changed unless


the system is provided with a function to allow airow direction
changes.

Make airow direction settings from the main menu


(see page 28).

* Two fan speed adjustment levels Low, High may be available


depending on the type of indoor unit.
* The system may be in automatic fan speed control for
mechanical protection purposes.
* The system may be in automatic fan speed control according to
the room temperature.
The fan may stop operating, which, however, is not a failure.
* The completion of fan speed selection may take time, which,
however, is not a failure.

To make fan speed control, press Fan


speed control button and select the
desired fan speed from Low, Middle or
High.

* No temperature settings are possible while in fan mode.

The set temperature will increase by


1C when button is pressed and
decrease by 1C when button is
pressed.

Press On/Off button.


The Operation lamp (green) will be lit
and the system will start operating.

Remote Controller
EDSG281001

Basic operation method (Use of direct buttons)

Detail Information of Options

Note
Do not turn power OFF soon after the system stops operating.
Be sure to wait for at least ve minutes so that the drain
discharging device will nish discharging the residual drain.
Otherwise, water leakage or failures may result.

* While the system is in heating operation, the


system will be in fan operation for approximately
one minute in order to eliminate the heat in the
indoor unit after the heating operation comes to a
stop.

The system in heating operation generally requires a long time to


attain the set temperature compared with the system in cooling
operation.
It is recommended to start operating the system in advance by utilizing
the timer.

3P243520-1B

305

01_EN_3P243520-1B.indd 16

The heating capability of the system will drop with a decrease in


outdoor temperature.
If that happens, use the system along with another heating appliance.
(In the above case, be sure to ventilate the room as frequently as
possible.)
Do not use the heating appliance in places where the heating
appliance is exposed to the wind from the system.
The system is of hot air circulation type. Therefore, it takes some time
for the room to become warm after the system starts operating.
The indoor fan will automatically go into breezing operation until the
inner temperature of the system rises to a certain level.
If the hot air stays around the ceiling and your feet feel cold, the use of
a circulator is recommended.
For details, consult your Daikin dealer.

English

1
Return

Dry

Setting

28C

Set temperature

Operation Method

5/15/2009 10:21:04 AM

17

* The dry operation may not be available depending on the type of


indoor unit.

Press Operation Mode Selector button


several times until the Dry operation is
selected.

For mechanical protection purposes, turn ON the system at least six hours before starting the
operation of the system.
Do not turn OFF the system in season in order to ensure the smooth starting of the system.
The dry mode may not be selected if the remote controller has no right to select cooling/
heating mode (see page 22 for details).

Preparation

Program Dry Operation

Outdoor
temperature and
heating capability

5/15/2009 10:21:04
01_EN_3P243520-1B.indd
AM
17

English

When the system goes into heating operation, the wind will stop in
order to prevent cold air from blowing out of the system in defrosting
operation.
(Defrost/Hot start) will be displayed on the
(In that case,
remote controller.)

Hot start
(VRV only)

16

The heating capability of the system will drop if the outdoor unit frosts
up. Therefore, the system will go into defrosting operation
automatically.
(Defrost/Hot
The system will stop blowing out hot air, and
start) will be displayed on the remote controller.
The system will return to normal operation with an elapse of
approximately six to eight minutes (but not more than 10 minutes).

Defrosting
operation

Perform the following operation of the system in order to prevent the


degradation of the heating capability or cold winds from blowing out.

Starting operation

Characteristics of Heating Operation

The Operation lamp will be turned OFF


and the system will stop operating when
On/Off button is pressed again.

Basic Operation Method (Use of Direct Buttons)

EDSG281001
Remote Controller

306

3P243520-1B

Detail Information of Options

01_EN_3P243520-1B.indd 18

18

English

1
Return

Cool

Return

Cool

28C

Setting

28C

Set temperature

Setting

Home leave is disabled

To cancel the home leave mode, continue


pressing or button for at least
four seconds. (During backlight lit)

Home leave is active


OFF

Home leave is enabled


FLASHING

ON

The Home Leave icon shows the status


of the home leave function.

Press and hold the or button


for at least four seconds. (During
backlight lit)
The Home Leave icon displays and
function is enabled.

5/15/2009 10:21:05 AM

19

The home leave can not be enabled when a centralized control is connected.

Set temperature

Operation Method

Note
This function will switch on heating if the installation is switched off.

Home Leave is a feature that enables to keep the room temperature above 10C when the
occupants are out.

Home Leave

The microcomputer is in automatic temperature and fan speed control. Therefore, temperature or
fan speed settings cannot be made or changed while the air conditioner is in operation.

Program Dry Operation

The Program dry function of the system repeats the weak cooling
operation of the system intermittently to dehumidify the room without
dropping the room temperature as much as possible for the
prevention of excessive cooling.

Program Dry

Operation Contents

5/15/2009 10:21:05
01_EN_3P243520-1B.indd
AM
19

English

Note
Do not turn power OFF soon after the system stops operating.
Be sure to wait for at least ve minutes so that the drain
discharging device will nish discharging the residual drain.
Otherwise, water leakage or failures may result.

The Operation lamp will be turned OFF


and the system will stop operating when
On/Off button is pressed again.

* The airow direction of the system cannot be changed unless the


system is provided with a function to allow airow direction
changes.

Make airow direction settings from the main menu


(see page 28).

* The microcomputer is in automatic temperature and fan speed


control. Therefore, temperature or fan speed settings cannot be
made or changed while the air conditioner is in operation.

Press On/Off button.


The Operation lamp (green) will be lit
and the system will start operating.

Basic Operation Method (Use of Direct Buttons)

Remote Controller
EDSG281001

Detail Information of Options

3P243520-1B

307

01_EN_3P243520-1B.indd 20

Return

Vent

Setting

20C

Set temperature

Operation Method

20

When Air Conditioner Interlocked with Total Heat Exchanger

The Operation lamp will be turned OFF


and the system will stop operating when
On/Off button is pressed again.

Press On/Off button.


The Operation lamp (green) will be lit
and the system will start operating.

* Ventilation rate: Low or High

English

Return

Cool

Return

Cool

English

Return

Cool

Return

Cool

28C

Setting

28C

Set temperature

Setting

28C

Set temperature

The display

Setting

28C

Set temperature

Setting

Press Operation Mode Selector button


of the remote controller for which the
selection eligibility to be set.
Then the cooling/heating selection
eligibility will be set and the display

(Changeover under control) will


disappear.
The display
(Changeover under
control) will appear on the other remote
controllers.

5/15/2009 10:21:06 AM

21

(Changeover under control) will blink when the power is turned ON for the first time.

Set a cooling/heating selection eligibility as


explained below.

* Vent mode setting changes are possible regardless of the


cooling/heating selection eligibility.
* If a cooling/heating selection eligibility is set in the cooling/
heating selection remote controller ( ), all the remote controllers
will display
(Changeover under control). In this case, no
cooling/heating selection eligibility can be set in the remote
controllers.
Refer to the operation manual provided to the outdoor unit for the
details of the cooling/heating selection remote controller.

Continue pressing Operation Mode


Selector button of the remote controller for
at least four seconds. (During backlight lit)
A remote controller will not display

(Changeover under control) if a


cooling/heating selection eligibility is
granted to the remote controller.
The display
(Changeover under control) on
each remote controller connected to the same
outdoor unit or BS unit will start blinking.

See page 22 for an explanation of the cooling/heating selection eligibility.

Set temperature

Selection Settings

Setting Changes

(VRV only)

Setting Method of the Cooling/Heating Selection Eligibility

5/15/2009 10:21:05
01_EN_3P243520-1B.indd
AM
21

To change the ventilation rate, make necessary


settings from the main menu (see page 32).

* Ventilation mode: Automatic, Heat exchange, and Bypass

To change the ventilation mode setting, make


necessary settings from the main menu (see page 33).

Set the Operation mode selector button


to Ventilation in the case of operating
the total heat exchanger without the
system between seasons.

For mechanical protection purposes, turn ON the system at least six hours before starting the
operation of the system.
Do not turn OFF the system in season in order to ensure the smooth starting of the system.

Preparation

Ventilation Operation

Basic Operation Method (Use of Direct Buttons)

EDSG281001
Remote Controller

308

Return

Cool

Setting

28C

Set temperature

Press the remote controller that has the


cooling/heating selection eligibility (or
the remote controller without the display

(Changeover under control))


several times until the desired mode is
selected. The display will change to
Fan, Dry, Auto, Cool, Heat each
time the button is pressed.
The display Auto will appear for the
heating/cooling simultaneous operation
system only.
At that time, the other remote controllers
with no selection right will follow suit and
change the display automatically.

3P243520-1B

Detail Information of Options

The remote controller with


the selection eligibility

(without
(Changeover under
control) displayed)

01_EN_3P243520-1B.indd 22

22

2.

1.

The remote controller with


the selection eligibility

(without
(Changeover under
control) displayed)

Set to Fan mode.

Set to Cool, Heat,


Dry, Auto mode.

Precautions for Setting Cooling/Heating Selection Eligibility

English

1
Setting

28C

Set temperature

Return

Cool

Setting

28C

Set temperature

Basic screen

Return

Cool

Operation Method

will appear.
All buttons are disabled when the keys
are locked.
To cancel the key lock mode, continue
pressing Menu/Enter button for at least
four seconds. (During backlight lit)

Continue pressing Menu/Enter button for


at least four seconds. (During backlight lit)

Make settings and cancel settings in the basic screen.

23

5/15/2009 10:21:08 AM

Set the cooling/heating/auto/fan selection


eligibility in one of the remote controllers.

Set the cooling/heating/fan selection


eligibility in one of the remote controllers.

Key Lock

A single BS unit is connected to a


number of indoor units.

Indoor unit

BS unit:
The BS unit is used for cooling or
heating mode selection.

(Cooling/Heating simultaneous operation system)

A number of indoor units are


connected to a single outdoor unit.

Indoor unit

(Cooling/Heating selected operation system)

The cooling/heating selection eligibility needs to be set for a single remote controller in the
following case.

5/15/2009 10:21:07
01_EN_3P243520-1B.indd
AM
23

English

The system cannot be set to other


modes except fan mode.

(with

(Changeover under
control) displayed)

Other remote controllers

The system will go into the mode set in


the remote controller. No other modes
are available.
The system, however, can be switched
to fan mode or from Cool to Dry.

(with

(Changeover under
control) displayed)

Other remote controllers

The Cool, Heat, Auto can be set for only the remote controller for which the cooling/heating
selection eligibility is set.
(The display Auto will appear for the heating/cooling simultaneous operation system only.)

Cool/Heat Selection Eligibility

Operation Selection

Basic Operation Method (Use of Direct Buttons)

Remote Controller
EDSG281001

Detail Information of Options

Ventilation mode

Ventilation rate

3P243520-1B

309

01_EN_3P243520-1B.indd 24

24

Service Contact/Model
Information

Off reminder timer

Timer setting Schedule timer

Ventilation
operation
settings for total
heat exchanger

Ventilation

(SkyAir only)

Used to display the service contact and model


information.

Possible to set in 10 minute units from 30 to


180 minutes.

Used to set each operation period of the system.

* Clock settings are necessary.


* The system goes into schedule timer operation in
the previous mode set for the system.

English

Set temp mode changeover


Schedule timer
Off reminder timer
Home leave

If two remote controllers are in control of a single indoor


unit, the following menu items are not set in the sub remote
controller. Set them in the main remote controller.

Menu Items of Sub Remote Controller

Outdoor unit

5/15/2009 10:21:12 AM

25

Two remote
controllers in control

50

48

48

46

45

Reference page

Indoor unit

The displayed language can be selected from


the following language. (English/Deutsch/
Franais/Espaol/Italiano/E/
Nederlands/Portugues/Pycc/rke)

The clock is in 24 hours real time clock.


The accuracy of the clock is within
30 seconds per month.
If there is a power failure for a period not
exceeding 48 hours, the clock will continue
working with the built-in backup power
supply. The clock needs settings again if the
power failure period exceeds 48 hours.

Used to make date and time settings and


corrections.

Used to display a list of current settings for


available items.

Display
Standard or detailed display
Detailed display settings
Selectable from the display room
temperature, outdoor temperature, system, or
without any display items.

Note: Available setting items vary with the model connected.


Only the available setting items appear in the menu.

Language changeover

Clock setting

Setting status list

Standard or detailed
display

Used to set to standard or detailed display


mode.

Display changeover

Description
Used to make LCD contrast adjustment.

Contrast adjustment

Setting and display items

Convenient
functions

5/15/2009 10:21:11
01_EN_3P243520-1B.indd
AM
25

English

44

42

35

33

Used to set Automatic, Heat exchange, and


Bypass.

Operation start time and stop time can be


set according to the day of the week.
Either one of the following operation modes
can be selected.
Operation at set temperature: Normal
operation
Operation within set temperature range
(between max. and min. temperatures):
Limit operation
Up to 5 actions can be set for each day.
Convenient holiday settings and temporary
closure settings are possible.

32

31

Used to set to Low High

Used to set the room to a conformable


temperature quickly (unless the system is
not in program dry or fan operation).
The maximum quick cooling/heating
operation period is 30 minutes.

* This function is not available to all models.

Used to make airow direction settings.


The airow direction blade are automatically
operated up and down (left and right).
The xed airow directions are set to ve
positions.

Quick Cooling/Heating On/Off

27

Select normal set temperature or limit control.

Set temp mode changeover

Airow direction setting


28

Reference page

Description

Setting and display items

The main menu has the following items.

Quick Reference of Main Menu Items

EDSG281001
Remote Controller

Quick reference of main menu items

310

3P243520-1B

Detail Information of Options

Setting

1/2

Main menu screen

Return

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info

MainMenu

To go back to the basic screen from the


main menu screen, press the Cancel
button.

2. Press Menu/Enter button to display the


selected settings screen.

1. Press
buttons to select the desired
item to be set.

Selecting items from the main menu.

Instructions for manipulating the


buttons will appear.

The main menu screen will appear.

English

1
28 C
20 C

min

28 C
20 C

min

28 C
20 C

Set temperature
max

Return
Press the menu button

Fan

Return
Press the menu button

min

Set temperature
max

Basic screen

Fan

1/2

Pressing
buttons switches the
variable set temperature between
max. and min.

27

5/15/2009 10:21:13 AM

Note
The difference between the maximum and minimum
temperatures cannot be set to less than 6C.
(* Maximum temperature Minimum temperature 6C)

To change the set temperature,


buttons.
press
The set temperature is highlighted
and ready to be changed.
The set temperature will increase by
1C when the button is pressed
and decrease by 1C when the
button is pressed.

* To return to the normal set temperature


screen, use Set temp mode changeover in
the Main Menu again.

Press
buttons to select Set
temp mode changeover on the
main menu screen.
Pressing Menu/Enter button takes
you back to the basic screen, and
the set temperature is displayed in
max C min C. (Limit Operation)

(See page 26.)

Display the main menu screen.

The limit operation can not be enabled when a centralized control is connected.

Set temperature
max

Setting

Return
Press the menu button

Fan

Return

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info

MainMenu

Operation Method

5/15/2009 10:21:12
01_EN_3P243520-1B.indd
AM
27

English

While setting items, if a button is not pressed for 5 minutes, the screen will automatically go
back to the basic screen.

01_EN_3P243520-1B.indd 26

26

Setting

28C

Set temperature

Basic screen

Return

Caution

Press Menu/Enter button.

Operation Method

Cool

Limit Operation
Limit operation provides thermostat control within the range of the set minimum and maximum temperature.
The minimum temperature setting will trigger heating. The maximum temperature setting will trigger cooling.

Set temp mode changeover

Display Method for Main Menu

Manipulating the Main Menu Screen

Menu Manipulation

Remote Controller
EDSG281001

Menu manipulation

Detail Information of Options

3P243520-1B

311

Setting

Setting

1/2

Setting

Airow direction
setting (left/right)

Return

Swing

Airflow Direction

Airow direction
setting (up/down)

Return

Swing

Airflow Direction

Return

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info

01_EN_3P243520-1B.indd 28

28

MainMenu

Operation Method

3 4

Up/down direction

0
1
1
2

Left/right direction

0
1
2
3
4

English

0
1
2
3
4

English

3
Setting

Setting

Setting

Setting

Left/right direction

Return

Position 2

Airflow Direction

Up/down direction

Return

Position 2

Airflow Direction

Left/right direction

Return

Swing

Airflow Direction

Up/down direction

Return

Swing

Airflow Direction

5/15/2009 10:21:13
01_EN_3P243520-1B.indd
AM
29

: Position
: Position
: Position
: Position
: Position

Note
Airow direction appears on the screen as below.

The airow direction setting screen will


appear.

(For models with no airow direction


adjustment, Airow Direction will not be
displayed on the main menu screen.)

Press
buttons to select
Airow Direction on the main menu
screen and press the Menu/Enter
button.

(See page 26.)

Display the main menu screen.

Manipulating Airow Direction Setting

Airow Direction Setting

Menu Manipulation

Press
buttons to select the
desired airow direction.
Press Menu/Enter button to return
to the basic screen.

* The illustration is a display when position 2


is selected.

When you select one of positions 0


to 4, the airow direction blades
stay in a xed position.

Selecting Swing will cause the


airow direction blades to swing
back and forth.
For the swing setting only, all
positions will be displayed.

Pressing
buttons changes the
setting to (in order) Swing ,
Position 0 ,
Position 1 ,
Position 2 ,
Position 3 , and
Position 4 .

5/15/2009 10:21:14 AM

29

EDSG281001
Remote Controller

312

(Automatic)

3P243520-1B

Detail Information of Options

(Desired position)

(Desired position)

Heating mode includes automatic operation.

Operation
condition

1/2

28C

Set temperature

Setting

Quick Cool/Heat

Cool

Return

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info

MainMenu

While operating in Cooling, Heating, or


Auto mode, display the main menu
screen (see page 26).
Press
buttons to select
Quick Cool/Heat On/Off on the main
menu screen.
Press Menu/Enter button to return to the
basic screen.
Quick Cooling/Heating will appear on
the basic screen.
Quick Cooling/Heating is now on.

English

2
Return

Cool

Return

1/2

Setting

28C

Set temperature

Setting

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info

MainMenu

Operation Method

While Quick Cooling/Heating is


displayed on the basic screen, display
the main menu screen (see page 26).
Press
buttons to select
Quick Cool/Heat On/Off on the main
menu screen.
Press Menu/Enter button to return to the
basic screen.
Quick Cooling/Heating will no longer
appear on the basic screen.
Quick Cooling/Heating is now off.

Quick Cooling/Heating Off

Operation Method

Quick Cooling/Heating On

Quick Cooling/Heating On/Off

5/15/2009 10:21:15
01_EN_3P243520-1B.indd
AM
31

English

Room temperature is higher than the remote controllers set temperature


(in heating mode).
When defrosting (in heating mode).
(The airow is blowing horizontally so that people in the room are not in
direct line of the cold air.)
Under continuous operation with the airow blowing horizontally.

Under the operation conditions shown below, airow direction is controlled automatically. Actual
operation may thus be different than what is displayed on the remote controller.

01_EN_3P243520-1B.indd 30

30

Airow direction
You can select from one of ve xed
directions. (This has no relation to the
angle of the louvers.)
Indoor unit

Movement of airow direction blades

(Automatic)

Indoor unit

The airow direction blades automatically


swing up and down.

Airow direction swing

There are two types of airow direction setting.

Operational Details and Functions

Menu Manipulation

5/15/2009 10:21:15 AM

31

Remote Controller
EDSG281001

Detail Information of Options

Return

Ventilation rate
Ventilation mode

Ventilation

Return

Setting

Setting

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info

MainMenu

2/2

1/2

Press Menu/Enter button to display the


ventilation settings screen.

(For models with no ventilation function,


Ventilation will not be displayed on the main
menu screen.)

Press
buttons to select Ventilation
on the main menu screen.

(See page 26.)

Display the main menu screen.

3P243520-1B

313

Return

Ventilation rate
Ventilation mode

01_EN_3P243520-1B.indd 32

32

Ventilation

Setting

Operation Method

2/2

Bring up the ventilation settings screen


(see above).
Press
buttons to select
Ventilation rate on the ventilation
settings screen.
Press Menu/Enter button to display the
ventilation rate settings screen.

Changing the ventilation rate

Operation Method

English

Low

Return

Setting

High

Ventilation rate

Ventilation

High

(Pressing Cancel button takes you back to the


previous screen without changing the ventilation
rate.)

Selecting the desired ventilation rate


and pressing Menu/Enter button selects
the setting and takes you back to the
basic screen.

* Only modes that can be set are displayed.

Pressing
buttons changes the
setting to in order Low and High .

English

Return

Setting

Setting

Bypass

Ventilation mode

Ventilation

Return

Ventilation rate
Ventilation mode

Ventilation

Operation Method

2/2

2/2

Heat exchange

Automatic
* Only modes that can be set are displayed.

Bypass

Pressing
buttons changes the
settings in order as shown below.

Press
buttons to select
Ventilation mode on the ventilation
settings screen.
Press Menu/Enter button to display the
ventilation mode settings screen.

(See page 32.)

Display the ventilation settings screen.

Changing ventilation mode

5/15/2009 10:21:16
01_EN_3P243520-1B.indd
AM
33

Display method for ventilation settings screen

Ventilation

Fan speed display goes off and fan speed can no longer be switched.
Cannot be set when in fan and dry modes.
Quick Cooling/Heating mode will run for a maximum of 30 minutes before the unit automatically
returns to normal operation.
Activating mode selector will return the air conditioner to normal operation.
In heating mode, fan speed may increase and the wind temperature may decrease.
Adjust the operation as desired.

outdoor unit and quickly bringing the room to a comfortable temperature.

Quick Cooling/Heating The indoor unit is automatically controlled, increasing the power of the

Quick Cooling/Heating

Menu Manipulation

5/15/2009 10:21:16 AM

33

EDSG281001
Remote Controller

314

Return

Cool

Setting

28C

Set temperature

3P243520-1B

Detail Information of Options

Setting

Return

Cool

Return

Disable
Disable

2/2

1/2

Setting

28C

Set temperature

Setting

Schedule timer
Off reminder timer

Timer setting

Return

01_EN_3P243520-1B.indd 34

34

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model info

MainMenu

Operation Method

English

1
Setting

Yes

No

Setting

Setting

Return

Setting

Enable/Disable setting
Condition setting
Holiday setting

Schedule timer

Return

00:00

Year 2008
Month 01
Day
01
Tuesday

Clock setting

Return

Clock setting is not carried


out. Do you want to set?

Schedule timer

Return

Schedule timer
Off reminder timer

Timer setting

Operation Method

Disable
Disable

2/2

Press
buttons to select the desired
setting items on the schedule timer
settings screen and press Menu/Enter
button.

(See clock settings on page 48.)

Before setting the schedule timer, the


clock must be set.
If the clock has not been set, a screen
like the one on the left will appear.
Press
buttons to select Yes and
press Menu/Enter button.
Set the current year, month, day, and
time.

Press
buttons to select the
Schedule timer on the timer settings
screen.
Press Menu/Enter button to display the
schedule timer settings screen.

(See page 34.)

Bring up the timer settings screen.

5/15/2009 10:21:18 AM

35

The schedule timer can not be enabled when a centralized control is connected.

Setting the schedule timer


Display method for the schedule timer settings
screen

5/15/2009 10:21:17
01_EN_3P243520-1B.indd
AM
35

English

When either schedule timer or off reminder timer is


enabled, appears on the basic screen.

* Currently enabled/disabled is displayed.

Press
buttons to select
Timer setting on the main menu
screen.
Press Menu/Enter button to display the
timer settings screen.

(See page 26.)

Display the main menu screen.

Display method for timer settings screen

Timer Settings

Outside air undergoes Heat exchange and is supplied to inside the room.

Heat exchange mode


Bypass mode

Outside air is supplied to inside the room without undergoing heat exchange.

Using information from the air conditioner (cooling, heating, fan,


and set temperature) and the total heat exchanger unit (indoor and
outdoor temperatures), mode is automatically changed between
Heat exchanger and Bypass.

(Pressing the Cancel button takes you back to the


previous screen without changing the ventilation
mode. )

Automatic mode

Ventilation Mode

Selecting the desired ventilation mode


and pressing Menu/Enter button enters
the settings and takes you back to the
basic screen.

Menu Manipulation

Remote Controller
EDSG281001

Detail Information of Options

3P243520-1B

315

Return

Monday

Operation

Operation

Setting

Time
06:00
:
:
:
:

Setting

Time
06:00
:
:
:
:

Schedule timer

Return

Monday

Setting

Operation

Setting

Time
:
:
:
:
:

Schedule timer

Return

Sunday

Schedule timer

Return

01_EN_3P243520-1B.indd 36

36

Enable/Disable setting
Condition setting
Holiday setting

Schedule timer

Operation Method

2/2

Press
buttons to move the
highlighted item and press
buttons
to input the desired operation start time.
Each press of
buttons moves the
numbers by 1 hour or 1 minute.
Holding down the button causes the
number to change continuously.

The schedule timer can accept a maximum of


5 operations per day.

Press
buttons to select the day to
be set on the condition setting screen.
Input the program for the selected day
next.

Display the schedule timer settings


screen. (See page 35.)
Press
buttons to select
Condition setting on the schedule timer
settings screen.
Press Menu/Enter button to display the
condition setting screen.

Schedule timer
Condition setting

Menu Manipulation

English

Return

Monday

Operation
28C

Operation
28C

Setting

Time
06:00
:
:
:
:

Setting

Time
06:00
:
:
:
:

Schedule timer

Return

Monday

Operation
22C

Setting

Time
06:00
:
:
:
:

Schedule timer

Return

Monday

Operation
22C

Setting

Time
06:00
:
:
:
:

Schedule timer

Return

Monday

Schedule timer

5/15/2009 10:21:19
01_EN_3P243520-1B.indd
AM
37

English

*1

*2

20C-26C

*3

OFF

To change the set temperature, press


the Menu/Enter button so that the set
temperature will be highlighted and
ready to be changed.
Press
buttons to change the set
temperature.
The set temperature will increase by 1C
when the button is pressed and
decrease by 1C when the button is
pressed.
Pressing Menu/Enter button enters the
set temperature change.

To make an operation change at set


temperature, press
buttons to move
the highlighted item and press
buttons to set the operation to 22C .

22C

The display changes in sequence as shown below


when
buttons are pressed.

The following three types of operations are


available.
*1. switch on the installation at a scheduled time,
in combination with a set point (exact
temperature control)
*2. switch on the installation at a scheduled time,
in limit operation
*3. switch off the installation (end of control)
* The status remain unchanged in the case of .

Press
buttons to move the
buttons
highlighted item and press
to select the desired operation.

5/15/2009 10:21:20 AM

37

EDSG281001
Remote Controller

316

3P243520-1B

Detail Information of Options

Return

Monday

Operation
28C
20C 28C

Operation
28C
22C 28C

Setting

Time
06:00
12:30
:
:
:

Setting

Time
06:00
12:30
:
:
:

Schedule timer

Return

Monday

Operation
28C
20C 26C

Setting

Time
06:00
12:30
:
:
:

Schedule timer

Return

Monday

Operation
28C
20C26C

Setting

Time
06:00
12:30
:
:
:

Schedule timer

Return

Monday

Operation
28C
20C26C

Setting

Time
06:00
12:30
:
:
:

Schedule timer

Return

Monday

Schedule timer

01_EN_3P243520-1B.indd 38

38

Pressing Menu/Enter button enters the


set temperature change.

English

English

Operation
28C
22C 28C
OFF

Return

Yes

Setting

No

Is it settled by setting?

Setting

Time
06:00
12:30
15:00
:
:

Schedule timer

Return

Monday

Operation
28C
22C 28C
OFF

Setting

Time
06:00
12:30
15:00
:
:

Schedule timer

Return

Monday

Schedule timer

5/15/2009 10:21:21
01_EN_3P243520-1B.indd
AM
39

Note
The difference between the maximum and minimum
temperatures cannot be set to less than 6C.
(* Maximum temperature Minimum temperature 6C)

Press
buttons to change the set
temperature.
The set temperature will increase by 1C
when the button is pressed and
decrease by 1C when the button is
pressed.

Press
buttons to select the desired
temperature to be changed.

To change the maximum and minimum


temperatures, press the Menu/Enter
button so that the temperatures will be
ready to be changed.

To make limit operation settings, press


buttons to move the highlighted
item and press
buttons to input the
desired set time.
Press
buttons to move the
buttons
highlighted item and press
to set the operation to 20C - 26C .

Menu Manipulation

Press
button to select Yes on the
settings conrmation screen.
Pressing Menu/Enter button enters the
schedule timer settings and takes you
back to the basic screen.

When the entire day settings are


completed, highlight the items other than
the operation and press the Menu/Enter
button.
The settings conrmation screen will
appear.

* To copy the settings for the previous day, select


the operation mode selector button so that the
settings will be copied as they are.
Example: The contents for Monday are copied by
pressing the operation mode selector
button after selecting Tuesday.

To set a different day of the week, press


buttons to highlight the day
presently set.
Press
buttons to change the day
and input the program in the same
manner.

To make operation stop settings, press


buttons to move the highlighted
item and press
buttons to input the
desired operation stop time.
Press
buttons to move the
buttons
highlighted item and press
to turn OFF the operation.

5/15/2009 10:21:22 AM

39

Remote Controller
EDSG281001

Detail Information of Options

3P243520-1B

317

Setting

Setting

Setting

Return

Yes

Setting

No

Is it settled by setting?

Schedule timer

Return

Sun Mon Tue Wed Thu Fri Sat

Holiday setting
Multi selection possible

Schedule timer

Return

Sun Mon Tue Wed Thu Fri Sat

Holiday setting
Multi selection possible

Schedule timer

Return

Enable/Disable setting
Condition setting
Holiday setting

Schedule timer

01_EN_3P243520-1B.indd 40

40

Operation Method

Press
button to select Yes on the
settings conrmation screen.
Pressing Menu/Enter button enters the
holiday settings and takes you back to
the schedule timer settings screen.

To complete the holiday settings, press


Menu/Enter button.
The settings conrmation screen will
appear.

Note: To able the schedule timer for the day


selected as a holiday, the holiday setting
must be released.

Press
buttons to select the desired
day.
Press
buttons to display to
make the holiday settings.
Pressing
buttons switches the
setting between set and release.
Multiple days can be selected as
holidays.

Bring up the schedule timer settings


screen. (See page 35.)
Press
buttons to select
Holiday setting on the schedule timer
settings screen.
Press Menu/Enter button to display the
holiday settings screen.

Operation

Setting

Time
:
:
:
:
:

English

Setting

Setting

Return

Yes

Setting

No

Is it settled by setting?

Schedule timer

Return

Disable

Enable/Disable setting

Schedule timer

Return

Enable/Disable setting
Condition setting
Holiday setting

Schedule timer

Operation Method

Holiday that are set will be displayed on


the condition settings screen.

Press
button to select Yes on the
settings conrmation screen.
Pressing Menu/Enter button enters the
enable/disable settings for the schedule
timer and takes you back to the basic
screen.

Press
buttons to select Enable or
Disable on the enable/disable settings
screen.
Press Menu/Enter button after selecting
the item. Then the settings conrmation
screen will appear.

Bring up the schedule timer settings


screen. (See page 35.)
Press
buttons to select
Enable/Disable setting on the schedule
timer settings screen.
Press Menu/Enter button to display the
enable/disable settings screen.

Enabling or disabling the schedule timer without


changing the set day or time

Return

Sunday
Holiday

Schedule timer

5/15/2009 10:21:22
01_EN_3P243520-1B.indd
AM
41

English

(The schedule timer will be disabled for days that have been set as holiday.)

Holiday setting

Menu Manipulation

5/15/2009 10:21:23 AM

41

EDSG281001
Remote Controller

318

3P243520-1B

Detail Information of Options

Setting

Setting

Setting

Return

Yes

Setting

No

Is it settled by setting?

Off reminder Timer

Return

minutes.

60

Each time after pressing


the operation button,
automatically stops after

Off reminder Timer

Return

Enable/ Disable setting


Condition setting

Off reminder Timer

Return

01_EN_3P243520-1B.indd 42

42

Schedule timer
Off reminder Timer

Timer setting

Operation Method

Disable
Disable

Press
button to select Yes on the
settings conrmation screen.
Pressing Menu/Enter button enters the
off reminder timer settings and takes
you back to the basic screen.

Use
buttons to set the time from
operation start until the unit
automatically stops.
Selections can be made in increments of
10 minutes from 30 to 180 minutes.
Holding down the button causes the
number to change continuously.
Select the desired time and press Menu/
Enter button.
The settings conrmation screen will
appear.

Press
buttons to select
Condition setting on the off reminder
timer settings screen.
Press Menu/Enter button to display the
condition settings screen.

Press
buttons to select the
Off reminder timer on the timer settings
screen.
Press Menu/Enter button to display the
off reminder timer settings screen.

(See page 34.)

Bring up the timer settings screen.

English

1
Setting

Setting

Return

Yes
Setting

No

Is it settled by setting?

Off reminder Timer

Return

Disable

Enable/ Disable setting

Off reminder Timer

Return

Enable/ Disable setting


Condition setting

Off reminder Timer

Operation Method

Press
button to select Yes on the
settings conrmation screen.
Pressing Menu/Enter button enters the
enable/disable settings for the off
reminder timer settings and takes you
back to the basic screen.

Press
buttons to select Enable or
Disable on the enable/disable settings
screen.
Press Menu/Enter button after selecting
the item. Then the settings conrmation
screen will appear.

Bring up the off reminder timer settings


screen. (See page 42.)
Press
buttons to select
Enable/Disable setting on the off
reminder timer settings screen.
Press Menu/Enter button to display the
enable/disable settings screen.

43

5/15/2009 10:21:25 AM

Enabling or disabling the off reminder timer without


changing the set time

5/15/2009 10:21:24
01_EN_3P243520-1B.indd
AM
43

English

Making and checking the off reminder timer settings

Menu Manipulation

Remote Controller
EDSG281001

Detail Information of Options

3P243520-1B

319

Setting

Return

Indoor unit
Outdoor unit

Setting

/000
/000

Contact address
01234567890

Service Contact/Model Info

Return

01_EN_3P243520-1B.indd 44

44

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info

MainMenu

Operation Method

1/2

* The error code record may also appear.


If it is not blinking, the unit is working properly.
The error code record will disappear if you press
On/Off button for more than 4 seconds.

* The model name will not appear if you have had


the circuit board replaced.

(For some models the product code may appear. )

The model information of the indoor and


outdoor units of your product will appear
on the bottom of the screen.

(If you have not yet registered your product, it will


not appear. )

The phone number for the contact


address will appear at the top of the
screen.

Press
buttons to select
Service Contact/Model Info on the
main menu screen and press Menu/
Enter button.

(See page 26.)

Display the main menu screen.

Display method for service contact and model


information

Service Contact/Model Information

Menu Manipulation

English

Setting

Setting

Return

Adjusts contrast

Setting

Light

Dark

Contrast adjustment

Return

Contrast adjustment
Display changeover

Convenient functions

Return

Convenient functions
Setting status list
Clock setting
Language changeover

MainMenu

5/15/2009 10:21:26
01_EN_3P243520-1B.indd
AM
45

English

Operation Method
2/2

On the contrast adjustment settings


screen press
buttons until you reach
the desired contrast.
After setting, press Menu/Enter button
and return to the basic screen.

Bring up the convenient functions


settings screen.
Press
buttons to select
Contrast adjustment on the convenient
functions settings screen.
Press Menu/Enter button to display the
contrast adjustment settings screen.

Press
buttons to select
Convenient functions on the main
menu screen.
Press Menu/Enter button to display the
convenient functions settings screen.

(See page 26.)

Display the main menu screen.

Contrast Adjustment

Convenient Functions

5/15/2009 10:21:26 AM

45

EDSG281001
Remote Controller

320

3P243520-1B

Detail Information of Options

Setting

Setting

Return

Display

Setting

Standard

Display changeover

Return

Display
Desired disp select

Display changeover

Return

Contrast adjustment
Display changeover

01_EN_3P243520-1B.indd 46

46

Convenient functions

Operation Method

Standard
None

* Refer to Setting the detailed display selection


to change detailed display selection.
(See page 47.)

Press
buttons to select Standard
or Details on the display settings
screen.
Then, press Menu/Enter button to
conrm settings and return to the basic
screen.

Press
buttons to select Display on
the convenient functions settings
screen.
Press Menu/Enter button to display the
display settings screen.

Bring up the convenient functions


settings screen. (See page 45.)
Press
buttons to select
Display chageover on the convenient
functions settings screen.
Press Menu/Enter button to display the
display selection settings screen.

Display chageover
Display selection

Menu Manipulation

English

Setting

Return

Setting

None

Desired disp select

Display changeover

Return

Display
Desired disp select

Display changeover

5/15/2009 10:21:27
01_EN_3P243520-1B.indd
AM
47

English

Operation Method

Standard
None

buttons displays the following.

After setting, press Menu/Enter button


to conrm settings and return to the
basic screen.

5/15/2009 10:21:28 AM

47

Outdoor temperature
.......... An estimate of the temperature near
the outdoor unit.
The temperature that is detected may
be affected by factors such as the
location of the unit (if it is in direct
sunlight, for e.g.) and unit operation
during defrosting.

Room temperature
.......... An estimate of the temperature near
the remote controller.
The temperature that is detected may
be affected by the location of the unit.

Be sure to read the following notes regarding display


of room temperature and outdoor temperature.

* Some models may not display these items even if they are selected.

Room temperature

* Outdoor temperature

* System

None

Pressing

Bring up the display selection settings


screen. (See page 46.)
Press
buttons to select
Desired disp select on the convenient
functions settings screen.
Press Menu/Enter button to display the
detailed display selection screen.

Setting the detailed display selection

Remote Controller
EDSG281001

Detail Information of Options

Return

Setting

1/2

Swing
Low
Auto
Disable
Disable
Standard

Airflow Direction
Ventilation rate
Ventilation mode
Schedule timer
Off reminder Timer
Display changeover

Setting

Setting status list

Return

Convenient functions
Setting status list
Clock setting
Language changeover

2/2

3P243520-1B

321

Return

Setting

Convenient functions
Setting status list
Clock setting
Language changeover

01_EN_3P243520-1B.indd 48

48

MainMenu

Operation Method

2/2

Off reminder timer


Quick Cool/Heat
Display changeover
Desired disp select

* Display items may differ depending on the model.


Only the items that can be set are displayed.

Airow direction
Ventilation rate
Ventilation mode
Schedule timer

Display items

A list showing the current setting status


will appear.
Press
buttons to go to the next item.
Pressing Cancel button takes you back
to the main menu screen.

Press
buttons to select
Setting status list on the main menu
screen and press Menu/Enter button.

(See page 26.)

Display the main menu screen.

Display the main menu screen. (See page 26.)


Press
buttons to select
Clock setting on the main menu
screen.
Press Menu/Enter button to display the
clock settings screen.

Setting the clock

Clock Setting

MainMenu

Operation Method

Manipulating the setting status list

Setting Status List

Menu Manipulation

English

Return

12:21

Year 2008
Month 10
Day
07
Tuesday

Clock setting

Return

12:00

Year 2008
Month 10
Day
07
Tuesday

Clock setting

Return

00:00

Year 2008
Month 10
Day
07
Tuesday

Clock setting

Return

00:00

Year 2008
Month 10
Day
01
Tuesday

Clock setting

Return

00:00

Year 2008
Month 01
Day
01
Tuesday

Clock setting

5/15/2009 10:21:28
01_EN_3P243520-1B.indd
AM
49

English

Setting

Setting

Setting

Setting

Setting

The date can be set between


January 1, 2008 and December 31, 2099.

Note:

Select Minute with


buttons.
buttons.
Input the minute with
Holding down the button causes the
number to change continuously.
Press Menu/Enter button.
The settings conrmation screen will
appear.

Select Hour with


buttons.
Input the hour with
buttons.
Holding down the button causes the
number to change continuously.

Select Day with


buttons.
buttons.
Input the day with
Holding down the button causes the
number to change continuously.
Days of the week change automatically.

Select Month with


buttons.
Input the month with
buttons.
Holding down the button causes the
number to change continuously.

Select Year with


buttons.
Input the year with
buttons.
Holding down the button causes the
number to change continuously.

5/15/2009 10:21:29 AM

49

EDSG281001
Remote Controller

322

Return

Yes

Setting

No

* When setting schedule timer, the display return to


the settings screens.

Press
button to select Yes on the
settings conrmation screen.
Press Menu/Enter button to set the clock
and return to the basic screen.

3P243520-1B

Detail Information of Options

Setting

Return

Setting

English

Selectable languages

Language changeover

Return

Convinient functions
Setting status list
Clock setting
Language changeover

MainMenu

01_EN_3P243520-1B.indd 50

50

Operation Method

2/2

Press
buttons to select Language
on the language changeover screen.
English/Deutsch/Franais/Espaol/
Italiano/E/Nederlands/
Portugues/Pycc/rke
Pressing Menu/Enter button to conrm
settings and return to the basic screen.

Press
buttons to select
Language changeover on the main
menu screen and press the Menu/Enter
button.

(See page 26.)

Display the main menu screen.

Selectable languages

Language changeover

Is it settled by setting?

Clock setting

Menu Manipulation

English

Return

Cool

Return

1/2

Clean the filter

28C

Set temperature

Setting

Filter Sign Reset


Set temp mode changeover
Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting

MainMenu

28C

Set temperature

Clean the filter

Cool

5/15/2009 10:21:30
01_EN_3P243520-1B.indd
AM
51

English

Operation Method

The display shown in 1 will disappear


from the basic screen when the lter
sign is reset.

Press
buttons to select
Filter Sign Reset on the main menu
screen and press Menu/Enter button.

Reset the lter sign when the lter or


element is washed, cleaned, or replaced.
Press Menu/Enter button.
The main menu screen will appear.

Wash, clean, or replace the lter or


element.
For details, refer to the operation
manual of the indoor unit.

5/15/2009 10:21:31 AM

51

When the time to clean the lter or element has


come, one of the following messages will appear on
the bottom of the basic screen.
Clean the lter
Clean the lter and element
Clean the element

Filter Sign Resetting

Maintenance

Remote Controller
EDSG281001

Maintenance

Detail Information of Options

Be sure to stop the operation of


the air conditioner and turn off
the power supply breaker at the
time of maintenance.
Failure to do so may result in
electric shocks or injury.

3P243520-1B

323

01_EN_3P243520-1B.indd 52

52

Do not use ammable materials (e.g., hairspray or insecticide) near the air
conditioner.
Do not clean the product with organic solvents such as benzine or paint
thinner.
The use of organic solvents may cause crack damage to the product, electric shocks,
or re.

Warning

Note
Do not use any paint thinner, organic solvent, or strong acid.

English

1
28C

Set temperature

Return

Indoor unit
Outdoor unit

Contact address
012345678900

Error code:A1

Setting

/000
/000

Error : Press Menu Button

Cool

Operation Method

The error code blinks and the contact


address and model name will appear.
Notify your Daikin dealer of the Error
code and Model name.

Press Menu/Enter button.

* The operation indicator will not blink.

Warning: Press Menu Button.

* The operation indicator will blink.

Error: Press Menu Button.

If an error occurs, either one of the following


items will blink in the basic screen.

53

5/15/2009 10:21:32 AM

Operation
lamp

Continued operation under such circumstances may result in failure, electric shocks, or re.
Contact your Daikin dealer.

When the air conditioner is malfunctioning (e.g., giving off a burning odor),
stop the air conditioner and turn off power.

Warning

Contact your Daikin dealer in the following cases

Error code Display

Useful Information

5/15/2009 10:21:32
01_EN_3P243520-1B.indd
AM
53

English

Wipe the LCD and other surface part of the remote controller with a dry cloth when they become
dirty.
If the dirt on the surface cannot be removed, soak the cloth in neutral detergent diluted with
water, squeeze the cloth tightly, and clean the surface. Wipe the surface with a dry cloth then.

Maintenance of Unit and LCD

Do not wash the remote


controller.
Doing so may cause electric
leakage and result in electric shocks
or re.

Caution

Maintenance

EDSG281001
Remote Controller

Useful information

324
Improper installation may result in
electric shocks or re.
Consult your Daikin dealer.

Do not relocate or reinstall the


remote controller by yourself.

3P243520-1B

Detail Information of Options

01_EN_3P243520-1B.indd 54

54

Contact your Daikin dealer.

Inquiry about After-sale Service

Consult your Daikin dealer.


Fair-paying services may be possible at the request of the customer.
(The warranty period is one year counting from the date of installation.)

Repairs after Warranty Period

5/15/2009 10:21:33 AM

English

The relocation of the remote controller requires special technology. Consult your Daikin dealer.
Actual expenses required for the relocation of the remote controller will be charged.

Relocation

Model name
Date of installation
Failure conditions: As precise as possible.
Your address, name, and telephone number

Advise the repairer of the following items

Do not disassemble, modify, or


repair the unit.
Doing so may result in electric
shocks or re.
Consult your Daikin dealer.

Warning

After-sale Service

Useful Information

Remote Controller
EDSG281001

Detail Information of Options

3P243521-1

01_EN_3P243521-1.indd 1

English

Failure to follow these instructions properly may result in personal


injury or loss of life.
Failure to observe these instructions properly may result in property
damage or personal injury, which may be serious depending on the
circumstances.

2/3/2009 1:19:14 PM

English

Ask your dealer or qualied personnel to carry out installation work.


Do not attempt to install the remote controller yourself. Improper installation may result in water
leakage, electric shocks or re.
Consult your local dealer regarding relocation and reinstallation of the remote controller.
Improper installation work may result in leakage, electric shocks or re hazards.
Install the remote controller in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shocks or re.
Be sure to use only the specied accessories and parts for installation work.
Failure to use the specied parts may result in the unit falling, water leaakage, electric shocks or re.
Install the remote controller on a foundation strong enough to withstand the weight of the remote
controller.
A foundation of insufcient strength may result in the remote controller falling and causing injury.
Electrical work must be performed in accordance with relevant local and national regulations and
with instructions in this installation manual.
Be sure to use a dedicated power supply circuit only. Insufciency of power circuit capacity and
improper workmanship may result in electric shocks or re.
Always perform installation work with the power supply shut-off.
Touch with energized electric parts causes an electric shock.
Do not disassembly, reconstruct or repair.
Electric shock and/or re are caused.
Make sure that all wiring is secured, the specied wires are used, and that there is no strain on the
terminal connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or re.
The choice of materials and installations must comply with the applicable national and international
standards.

WARNING

After completing installation, conduct a trial operation to check for faults and explain to the customer
how to operate the air conditioner and take care of it with the aid of the operation manual. Ask the
customer to store the installation manual along with the operation manual for future reference.

CAUTION

WARNING

2/3/2009 1:19:14
01_EN_3P243521-1.indd
PM
2

12. Language changeover .................... 22

11. Clock Setting ................................... 22

10. Conrmation of registered


details ............................................... 21

9. Registration method of the


service contract .............................. 20

8. Checking procedure of
error record ..................................... 19

7. Test operation method


(in the case of SkyAir) .................... 16

6. Field setting method ....................... 13

5. Power-on .......................................... 12

4. Functions and menu items


of remote controller buttons .......... 10

3. Remote controller installation


procedure .......................................... 4

2. Accessories ....................................... 4

The precautions described herein are classied as WARNING and CAUTION. They both contain
important information regarding safety. Be sure to observe all precautions without fail.

Please read these Safety Precautions carefully before installing air conditioning
equipment and be sure to install it correctly.

Also see installation manual attached to the indoor unit.

1. Safety Precautions

2.3.4

1. Safety Precautions ............................ 2

Contents

EDSG281001
Remote Controller

Installation Manual

Safety precautions

325

326

3P243521-1

Detail Information of Options

01_EN_3P243521-1.indd 3

English

(M416)

(2 pcs.)

(3.516)

(2 pcs.)

Operation
manual

(1 pc.)

Clamp

(1 pc.)

(1 pc.)

Installation
manual

Safety Precautions when determining the location.

(1 pc.)

Wiring retainer

Through
hole
F8-10

48.5

If the hole size is too large or the location is not


proper, the hole may come out from the controller.

CAUTION

Set the center of the wall hole


to the center of the wiring thro
ugh hole on the controller
lower case when making the
hole.

Take care that dust or moisture does


not touch the PC-board of removed
upper case.

Remote controller PC-board is


installed on the upper case. Take care
not to damage the PC-board with the
screwdriver.

Insert and twist the screwdriver


lightly for removal.

Screwdriver

2/3/2009 1:19:15 PM

English

Lower case

Upper case

Insert a screwdriver in the recess of lower case to remove the upper case (2 points).

3-3 Remove upper case.

Lower case
Through hole

F8-10

External view of the remote controller

3-2 Make a wiring through hole on the wall if the wires are taken
out from the back side.

Make sure to follow 1.

3-1 Determine where to install the remote controller.

3. Remote controller installation


procedure

Small screw

Wood screw

The following accessories are included.

2/3/2009 1:19:14
01_EN_3P243521-1.indd
PM
4

To avoid leakage and electric shock due to entry of water or insects, ll the wiring through hole with
putty.
To avoid electric shocks, do not operate with wet hands.
Do not wash the remote controller with water, as this may result in electric shocks or re.
Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from
televisions or radios to prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 1 meter may not be sufcient to eliminate
noise.)
Do not install the air conditioner in the following locations:
1. Where there is a high concentration of mineral oil spray or vapour (e.g. a kitchen).
Plastic parts will deteriorate, parts may fall off and water leakage could result.
2. Where corrosive gas, such as sulphurous acid gas, is produced.
Corroding of copper pipes or soldered parts may result in refrigerant leakage.
3. Near machinery emitting electromagnetic radiation.
Electromagnetic radiation may disturb the operation of the control system and result in a
malfunction of the unit.
4. Where ammable gas may leak, where there is carbon bre or ignitable dust suspensions in the
air, or where volatile ammables such as paint thinner or gasoline are handled.
Operating the unit in such conditions may result in re.
5. High temperature area or directly amed point.
Heating and/or ring may be caused.
6. Moist area, or place where may be exposed to water.
If water enters inside of the remote controller, electric shock may be caused and inner electronics
may fail.
When remote controller thermo function is used, select the installation location considering the
followings.
A place where average temperature in the room can be detected.
A place where is not exposed to direct sunlight.
A place where is far apart from heat source.
A place where is not affected by outside air due to door opening/closing or the like.

2. Accessories

40

CAUTION

Remote Controller
EDSG281001

Accessories

Remote controller installation procedure

Detail Information of Options


3-4-4 Upper center outlet

Cut off thin area (hatched area) with nippers


or the like, and then remove burr with a le or
the like.

3-4-3 Upper outlet

Cut off thin area (hatched area) with nippers


or the like, and then remove burr with a le or
the like.

CAUTION

3P243521-1

01_EN_3P243521-1.indd 5

English

Sheathed vinyl cord or cable (2 wire) (NOTE)


0.75-1.25mm

Clamp

Clamp

Secure the wiring at


the wiring fixing point
by using attached
clamping material.

Lower case

Cross-section

Indoor unit
P1 P2

<Wiring fixing guideline>

PC-board

Ground the shielded


part on the indoor
unit side. (NOTE.1)

1) Shield wire (2 wire) can be used for remote controller wiring, but it must
conrm to EMC (Electromagnetic Compatibility) (Australian regulation)

NOTE

Wiring fixing
point

Upper case

3-5-1 Back outlet

2/3/2009 1:19:17 PM

English

Connect the terminals (P/P1, N/P2) of the remote controller upper case with the terminals (P1, P2)
of the indoor unit. (P1 and P2 have no polarities.)

Sheath stripping length:


Ca. 150mm for upper outlet
Ca. 200mm for upper center outlet

Cutting guideline
of the wiring

Peel the shield and sheath

Ca. 10mm
For easy wiring, it is better to
keep ca. 10mm difference
between the length of two wires.

Sheath part in the remote controller case should be stripped.

2/3/2009 1:19:16
01_EN_3P243521-1.indd
PM
6

Shield wire (2 wire) can be used for remote controller wiring, but it must conrm to EMC
(Electromagnetic Compatibility) (Australian regulation)

NOTE

Wiring Type
Wiring Size

Wiring Specications

1. Switch box and transmission wiring are not attached.


2. Do not directly touch the remote controller PC-board.

Cut off thin area (hatched area) with nippers


or the like, and then remove burr with a le or
the like.

Cut off resin area (hatched area).

3-5 Conduct wiring.

3-4-2 Left outlet

3-4-1 Back outlet

3-4 Determine the direction of controller wiring outlet (back


outlet, left outlet, upper center outlet, upper outlet).

EDSG281001
Remote Controller

327

328

PC-board

3P243521-1

Detail Information of Options

01_EN_3P243521-1.indd 7

English

Upper case

PC-board

Wiring retainer

Ground the shielded


part on the indoor
unit side. (NOTE.1)
Indoor unit
P1P2

Lower case

Lower case

Lower case

Install attached
wiring retainer to
prevent wiring pinch
according to left
figure.

Upper case

Indoor unit
P1P2

Ground the
shielded part on
Indoor unit
the indoor unit
P1P2
side. (NOTE.1)

Cross-section

Wiring

Wiring retainer

PC-board

3-5-4 Upper center outlet

Upper case

Wiring retainer

3-5-3 Upper outlet

Upper case

Ground the shielded


part on the indoor
unit side. (NOTE.1)

Switch box
(field supply)
(Use optional accessory
KJB211A)

Small screws (M416)

Secure by using attached small screws (2 pcs.).

(Installation pitch)

46

English

2/3/2009 1:19:18 PM

Switch box for two units


(with no cover)

3-6-2 In the case of installation on the switch box

Wood screws
(F3.516)

Secure by using attached wood screws (2 pcs.).

3-6-1 In the case of installation on the wall

In the case of wiring center upward drawing or rearward drawing, see wiring procedure rst as
wiring with the case is needed before xing.

3-6 Fixing procedure of lower case.

2/3/2009 1:19:17
01_EN_3P243521-1.indd
PM
8

CAUTION
Perform wiring apart from a power line not to receive electrical noise (external noise)
during the wiring.
Seal wiring draw-in port securely with putty (eld supply) to prevent entry of insects or
the like.

84

3-5-2 Left outlet

Remote Controller
EDSG281001

Detail Information of Options


84

28
(Installation pitch)

3P243521-1

01_EN_3P243521-1.indd 9

English

10

Depending on connected model

Set temp mode changeover


Airow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info
Convenient functions
Setting status list
Clock setting
Language changeover

Main menu

(3) Menu/Enter button


Used to indicate the main menu.
(For details of main menu, see the
operation manual.)
Used to enter the setting item selected.

(2) Fan speed control button


Used to change the fan control.

(1) Operation mode selector button


Used to change the mode.

4-1 Functions and menu items

2/3/2009 1:19:19 PM

English

(6) Right button


Used to highlight the next items on the
right-hand side.
Display contents are changed to next
screen per page.

(5) Down button


Used to lower the set temperature.
The next items on the lower side will be
highlighted.
(The highlighted items will be scrolled
continuously when the button is kept
pressed.)
Used to change the item selected.

(4) Up button
Used to raise the set temperature.
The next items on the upper side will be
highlighted.
(The highlighted items will be scrolled
continuously when the button is kept
pressed.)
Used to change the item selected.

(2) Fan speed control button

(10) Cancel button

(3) Menu/Enter button

(8) On/Off button

(9) Operation lamp

(4) Up button
(5) Down button
(6) Right button
(7) Left button

(11) LCD (with backlight)

(1) Operation mode selector button

4. Functions and menu items of remote


controller buttons

2/3/2009 1:19:19
01_EN_3P243521-1.indd
PM
10

Align the upper case with tabs of the lower case (6 points), inset and install the upper case.
Install the wiring with care to prevent the pinch.
Peel off a protective seal which is attached on the upper case.

3-7 Install the upper case as original condition.

Select at place for installation face as possible.


And, do not tighten the installation screws too much not to deform the lower case.

CAUTION

Small screws (M416)

Switch box
(field supply)
(Use optional accessory
KJB111A)

Switch box for one unit


(with no cover)

EDSG281001
Remote Controller

Functions and menu items of remote controller buttons

329

330
Depending on connected model

3P243521-1

Detail Information of Options

01_EN_3P243521-1.indd 11

Return

Setting

Test operation ON/OFF


Register Service Contract
Field setting list
Group No. setting
Indoor unit Airnet No. set
Outdoor unit Airnet No. set

Field setting

1/2

<Field setting menu screen>

In the highlighted display (selected items)


setting screen, button operation
descriptions are displayed.

Highlighted display (selected items)

4-2 Displays for button operation descriptions

English

Field setting menu


Test operation ON/OFF
Register Service Contract
Field setting list
Group No. setting
Indoor unit Airnet No. set
Outdoor unit Airnet No. set
Error record
Indoor status display
Outdoor status display
Fan forced operation ON
Main/Sub changeover
Filter element sign OFF

11

12

5-2

5-1

28C

Set temperature

Return
Press the menu button

Fan

<Basic screen>

Main remote contrl

Connection under check


Please wait for a moment

Error code:U5

Main remote contrl

Connection under check


Please wait for a moment

Off reminder Timer

NOTE
When selecting a different language, refer to 12. Language

5-2

5-1

28C

Set temperature

(See page 22.)

2/3/2009 1:19:20 PM

English

Return
Press the menu button

Fan

<Basic screen>

Sub remote contrl

Connection under check


Please wait for a moment

Press and hold 4 seconds


or longer the Operation
mode selector button of sub
remote controller side.

Main remote contrl

Connection under check


Please wait for a moment

Error code:U5

Main remote contrl

Connection under check


Please wait for a moment

Off reminder Timer

<Sub remote controller>

changeover.

<Main remote controller>

If sub remote controller is not set at power-on in the case


of one indoor unit controlled by two remote controllers,
Error code: U5 is displayed in the connection checking
screen.
Select the sub remote controller by pressing the
Operation mode selector button of either one of the
remote controllers for 4 seconds or longer.
If the basic screen is not displayed more than 2 minutes
after sub remote controller display, shut off the power
supply and check the wiring.

CAUTION

5-2 Basic screen is displayed.

Be sure to set sub remote


controller during above display.
Press and hold 4 seconds or
longer the Operation mode
selector button of the remote
controller to be set.
When the display is changed from
main remote controller to sub
remote controller, the setting is
completed.

When 1 indoor unit is


controlled by 2 remote
controllers:

During above display, backlight


does not light by button operation.

power-on.
Connection under check
Please wait for a moment

5-1 Followings are displayed after

Check for completion of indoor/outdoor units wiring.


Check for closing of EL. COMPO. BOX cover of indoor and outdoor units before power-on.

5. Power-on

2/3/2009 1:19:20
01_EN_3P243521-1.indd
PM
12

Operate the button during backlight lit.


However, On/Off may be operated concurrently with backlight lit.
When 1 indoor unit is controlled by 2 remote controllers, a remote controller backlight
which is operated rst light.
To operate Up/Down/Left/Right button, always press of the button.

CAUTION

(11) LCD (with backlight)


The backlight will be light for
approximately 30 seconds by pressing
any operation button.

(10) Cancel button


Used to return to the previous screen.
Press and hold this button for 4 seconds
or longer to display eld setting menu.

(9) Operation lamp


Green lamp lights up during operation. The
lamp will blink if an malfunction occurs.

(8) On/Off button


Press once to operate, and press once
again to stop.

(7) Left button


Used to highlight the next items on the
left-hand side.
Display contents are changed to
previous screen per page.

Remote Controller
EDSG281001

Power-on

3P243521-1

01_EN_3P243521-1.indd 13

English

In the case of group total


setting, all of SECOND CODE
NO. which may be set are
displayed as . is
changed to SECOND CODE
NO. to be set. And, SECOND
CODE NO. - means no
function.

the FIRST CODE NO. to be


changed, and select desired
SECOND CODE NO. by using
(Up/Down) button. Multiple
identical mode number settings
are available.

6-5 Highlight SECOND CODE NO. of

In the case of individual setting


per indoor unit, current settings
are displayed. And, SECOND
CODE NO. - means no
function.

unit during group control (When


Mode No. such as 20 , 21 ,
22 , 23 , 25 are selected),
highlight the unit No. and select
Indoor unit No. to be set by
(Up/Down) button.
using
(In the case of group total setting,
this operation is not needed.)

6-4 In the case of setting per indoor

desired Mode No. by using


(Up/Down) button.

6-3 Highlight the mode, and select

eld setting menu, and press


Menu/Enter button.
Field setting list screen is
displayed.

6-2 Select Field setting list in the

4 seconds or longer.
Field setting menu is displayed.

6-1 Press and hold Cancel button for

6-3
6-4
6-5

Press and hold Cancel


button for 4 seconds or
longer during backlight lit.

Return

Unit No
0
001
4
8
Setting

Mode
20
100
200
5
6
9
a

Setting

1/2

Setting

Mode
10
1

5
6
9
a
3

7
b

11 (21)

10 (20)

Mode
No.
Note) 1

14

6-6
6-7
Yes

No
Setting

Setting conrmation

Press Menu/Enter button.

Return

Is it settled by setting?

Field setting list

<Setting conrmation screen>

Pair

Setting number of connected Sky Air


simultaneous operation system
indoor units (setting for simultaneous operations system)

Display

Spacing time of display time to


clean air lter count (setting for
when the lter sign is not to be
displayed)
0

Use

Thermostat sensor in remote


controller

Long-life
lter

Approx.
200 hrs.

Approx.
2.500 hrs.

Twin

Do not
display

Not use

Ultra-long
life lter

Approx.
100 hrs.

Approx.
1.250 hrs.

Approx.
5.000 hrs.

02

Double twin

Triple

2/3/2009 1:19:21 PM

English

04

03

SECOND CODE NO. Note) 2

Approx.
10.000 hrs.

Standard
lter

Long life
lter

Ultra
long life
lter

01

Long-life lter type (setting of lter


sign indication time).
(Change setting when ultra-long
lter is installed)

Filter Contamination Heavy/Light


(Setting for spacing time
of display time to clean
air lter)
(Setting for when lter
contamination is heavy,
and spacing time of
display time to clean air
lter is to be halved)

Description of setting

FIRST
CODE
NO.

When an optional accessory is installed on the indoor unit, settings of the indoor unit may be
changed. See the manual of the optional accessory.
For eld setting details of the outdoor unit, see installation manual attached to the outdoor unit.

CAUTION

Connection under check


Please wait for a moment is
displayed for initialization. After
the initialization, the basic screen
returns.

6-10 Backlight goes out, and

pleted, press Cancel button


twice.

6-9 After all setting changes are com-

6-8 In the case of multiple setting


changes, repeat 6-3 to 6-7.

Enter button. Setting details are


determined and eld setting list
screen returns.

6-7 Select Yes and press Menu/

2/3/2009 1:19:21
01_EN_3P243521-1.indd
PM
14

13

FIRST CODE (SW) NO.

SECOND CODE NO.

Return

Unit No
0
001
4
8

Field setting list

Press Menu/Enter button.

300
7
b

6-3
6-5

In the case of group total


setting

<Field setting screen>

Press Menu/Enter button.

Return

Test operation ON/OFF


Register Service Contract
Field setting list
Group No. setting
Indoor unit Airnet No. set
Outdoor unit Airnet No. set

Field setting

In the case of individual


setting per indoor unit

6-2

Field setting list

28C

Set temperature

Return
Press the menu button

Fan

<Field setting menu screen>

6-1

<Basic screen>

conrmation screen is displayed.

6-6 Press Menu/Enter button. Setting

Light

Detail Information of Options


Heavy

6. Field setting method

EDSG281001
Remote Controller

Field setting method

331

332

4-way ow

Equipped

Thermostat differential changeover


(setting for when using remote
sensor).

High air outlet velocity (for high


ceiling applications).

Selection of airow direction (setting


for when a blocking pad kit has
been installed).

Selection of airow function (setting


for when using a decoration panel
for outlet).

Airow direction range setting.

Setting the external static pressure


(setting according to the connected
duct resistance) (for FHYK, follow
the high ceiling setting)

3
Permitted

Level 3

Use

Not equipped

High static
pressure
(High ceiling)

Normal

Not equipped

3-way ow

> 2.7 3.0m

0.5C

ON/OFF
operation

02

Low static
pressure

Lower

2-way ow

> 3.0 3.5m

03

SECOND CODE NO. Note) 2

Not permitted

Level 2

Permission level setting

Home leave function

Not use

Thermostat sensor in remote


controller (for limit operation and
Home leave function only)

Equipped

Drain pump operation with


humidifying.

(Normal)

Normal

Upper

2.7m

1C

Forced OFF

ON/OFF input from outside (setting


for when forced ON/OFF is to be
operated from outside).

01

Description of setting

FIRST
CODE
NO.

04

3P243521-1

Detail Information of Options

01_EN_3P243521-1.indd 15

English

16

eld setting menu, and press Menu/


Enter button. Basic screen returns and
Test operation is displayed.

7-5 Select Test operation ON/OFF in the

4 seconds or longer. Field setting


menu is displayed.

7-4 Press and hold Cancel button for

using the remote controller.

7-3 Set the operation mode to cooling by

and gas are opened.


<Make sure that outer panel and
piping cover is closed before
operation (danger of electric
shock). >
After air purge by vacuum pump,
refrigerant pressure may not rise
even though the stop valve is
opened. The reason is that refrigerant system of the outdoor unit is
blocked by electrical expansion valve
or the like. Operation is no problem.

7-2 Conrm that stop valves of both liquid

more than 6 hours before operation


start with front panel closed to protect
compressor.

7-1 Make sure to turn on the power supply

Return

Cool

Setting

28C

Set temperature

<Basic screen>

7-5

Return

Setting

Test operation ON/OFF


Register Service Contract
Field setting list
Group No. setting
Indoor unit Airnet No. set
Outdoor unit Airnet No. set

Field setting

1/2

<Field setting menu screen>

7-3
7-4

2/3/2009 1:19:22 PM

English

Press Menu/Enter button.

Press and hold Cancel


button for 4 seconds or
longer during backlight lit.

The backlight will be light for approximately


30 seconds by pressing any operation button.
Operate the buttons during the backlight lit.
However, On/Off can be operated concurrently with the backlight lit.

Notes for backlight

Check that wiring work of the indoor unit and the outdoor unit is completed.
Check that EL. COMPO. BOX cover of the indoor unit and the outdoor unit is closed.
After refrigerant piping, drain piping and electric wiring are completed, clean inside of the indoor unit
and decorative panel.
Perform the test operation according to following procedure.

Also see installation manuals attached to the indoor unit and the outdoor
unit.

In the case of VRV, see the manual attached to the outdoor unit.

7. Test operation method (in the case of


SkyAir)

2/3/2009 1:19:22
01_EN_3P243521-1.indd
PM
16

15

Notes) 1. Though setting is performed totally in the group, set Mode No. in the parenthesis when
individual setting per indoor unit or checking after the setting should be performed.
2. SECOND CODE NO. at factory shipment is set to 01. However for the following cases it is
set to 02.
Airow direction range setting (except round ow cassette)
Thermostat sensor in remote controller (SkyAir only)
Thermostat sensor in remote controller for limit operation and Home leave function only
Home leave function
3. Any function which the indoor unit does not have is not displayed.

1e

1c

15 (25)

13 (23)

12 (22)

Mode
No.
Note) 1

Remote Controller
EDSG281001

Test operation method (in the case of SkyAir)

Detail Information of Options

3P243521-1

01_EN_3P243521-1.indd 17

English

(If the operation is performed, the


indoor unit may be contaminated with
the materials which arise from paints or
adhesives during the interior work, and
water splash or water leak may occur.)

If interior work is not completed after the


test operation nish, explain to the
customer that operation should not be
performed until the interior work completion to protect the indoor unit.

installed, shut off the power supply


after the test operation nishes.

7-13 When the decorative panel is not

operation manual.

7-12 Check the functions according to the

eld setting menu, and press Menu/


Enter button. Basic screen returns and
normal operation is conducted.

7-11 Select Test operation ON/OFF in the

4 seconds or longer in the basic


screen.
Field setting menu is displayed.

7-10 Press and hold Cancel button for

is conrmed, press Menu/Enter button.


Basic screen returns.

7-9 After the operation of airow direction

direction setting function, select


Airow Direction in the main menu
and check that airow direction is
actuated according to the setting.
For operation of airow direction
setting, see the operation manual.

7-8 In the case of a model having airow

screen. Main menu is displayed.

7-7 Press Menu/Enter button in the basic

7-6 in reverse order, test


operation can start as well.

tioned procedures 7-5 and

10 seconds. The test operation starts.


Check operation condition for
3 minutes.
Note) In the case of above-men-

7-6 Press On/Off button within about

7-11

7-10

7-9

7-8

7-6
7-7

Setting

Setting

<Basic screen>

Return

1/2

28C

Test operation ON/OFF


Register Service Contract
Field setting list
Group No. setting
Indoor unit Airnet No. set
Outdoor unit Airnet No. set

Field setting

Setting

1/2

Set temperature

Test Operation

Cool

Return

Swing

Airflow Direction

Return

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info

MainMenu

<Main menu screen>

28C

Set temperature

Test Operation

Cool

18

Checking
procedure of error record.

conrmed, refer to 8.

When the remote controller displays


any item in following table, inspect the
details in the table.
If a error occurs, code is displayed in
the LCD like right gure.
Conduct the failure analysis referring to
Error code list in the installation
manual of the indoor unit.
And when the unit No. which detected
the error during group control is

Failure diagnosis method

conduct the failure diagnosis referring


to <Error code list> in the installation
manual of the indoor unit.
After the failure diagnosis nishes,
press and hold On/Off button for
4 seconds or longer in the Service
Contact/Model Info screen to erase
the error code record.

7-17 If the error code record is displayed,

screen is displayed. Check that error


code record is not displayed in the
screen.
Screen which does not display the
error code record means normal
status.

7-16 Service Contact/Model Information

the main menu, and press Menu/Enter


button.

7-15 Select Service Contact/Model Info in

screen. Main menu screen is displayed.

7-14 Press Menu/Enter button in the basic

2/3/2009 1:19:22
01_EN_3P243521-1.indd
PM
18

17

Press Menu/Enter button.

Press and hold Cancel


button for 4 seconds or
longer during backlight lit.

Press Menu/Enter button.

Change the airow


direction by using
(Up/Down)button.

Press Menu/Enter button.

Press Menu/Enter button.

Press On/Off button


(within 10 seconds).

CAUTION

7-16
7-17

7-15

7-14

Setting

28C

Set temperature

1/2

28C

Set temperature

Setting

/000
/000

Setting

Test Operat. CODE : U5

Cool

Return

Indoor unit
Outdoor unit

Contact address
012345678900

Error code:U5

Return

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info

MainMenu

<Main menu screen>

Return

Cool

<Basic screen>

2/3/2009 1:19:23 PM

English

Press and hold On/Off


button for 4 seconds or
longer during backlight lit.

Press Menu/Enter button.

Press Menu/Enter button.

If operation is not available due to any malfunction, refer to following Failure diagnosis method .
After the test operation nishes, check that error code record is not displayed in the Service
Contact/Model Information screen of the main menu according to the following procedure.

EDSG281001
Remote Controller

333

334

Indoor PC-board assembly failure


Wrong wiring (between indoor and outdoor units)

Description
Power outage, power voltage error or open-phase
Wrong wiring (between indoor and outdoor units)
Indoor PC-board assembly failure
Remote controller wiring disconnection
Remote controller failure
Fuse blow (outdoor unit)

3P243521-1

Detail Information of Options

01_EN_3P243521-1.indd 19

English

display screen 3 times.


The basic screen returns.

8-5 Press Cancel button in the error record

latest are displayed in order.

8-4 In the error record, 10 items from the

error record menu, and press Menu/


Enter button.
Error codes and unit No. can be
conrmed in the error record display
screen.

8-3 Select Remote controller record in the

menu, and press Menu/Enter button.


The error record menu screen is
displayed.

8-2 Select Error record in the eld setting

4 seconds or longer in the basic


screen. Field setting menu is displayed.

8-1 Press and hold Cancel button for

<Basic screen>

Setting

Setting

Error

Return

Unit
01
02
03
04
Setting

Date
/ /
/ /
/ /
/ /

Remote controller record

Return

Remote controller record


Indoor unit record

Error record

Return

1/3

2/2

2/2

Time
:
:
:
:

Error record
Indoor status display
Outdoor status display
Fan forced operation ON
Main/Sub changeover
Filter element sign
OFF

Field setting

Unit No.
Latest record

8-4
8-5

8-3

8-2

<Field setting menu screen>

8-1

20

The basic screen returns.

9-7 Press Cancel button once.

button.
Setting details are determined and eld
setting menu screen returns.

9-6 Select Yes and press Menu/Enter

Setting conrmation screen is


displayed.

9-5 Press Menu/Enter button.

Numeric varies by using


(Up/
Down) button. Enter from the left end,
and blank digit should be left as - .

9-4 Enter the telephone number.

and press Menu/Enter button.

9-3 Select Register Service Contract ,

the eld setting menu, and press


Menu/Enter button. Register service
contract menu screen is displayed.

9-2 Select Register Service Contract in

4 seconds or longer in the basic


screen.
Field setting menu is displayed.

9-1 Press and hold Cancel button for

Registration of the service contract.


<Basic screen>

Setting

Setting

Setting

Return

Setting

01234567890

Register Service Contract

Register Service Contract

Return

Register Service Contract

Register Service Contract

Return

None
Register Service Contract

Register Service Contract

Return

Test operation ON/OFF


Register Service Contract
Field setting list
Group No. setting
Indoor unit Airnet No. set
Outdoor unit Airnet No. set

Field setting

1/2

1/2

1/2

Return

Yes

Setting

No

Is it settled by setting?

Register Service Contract

<Field setting menu screen>

9-6

<Setting conrmation screen>

9-5

9-4

9-3

9-2

<Field setting menu screen>

9-1

2/3/2009 1:19:25 PM

English

Press Menu/Enter button.

Press Menu/Enter button.

Press Menu/Enter button.

Press Menu/Enter button.

9. Registration method of the service


contract

2/3/2009 1:19:24
01_EN_3P243521-1.indd
PM
20

19

Press Menu/Enter button.

Press Menu/Enter button.

8. Checking procedure of error record

Though
Connection under check
Please wait for a moment is displayed for 90 seconds at maximum after power-on, this does not mean a
failure. (Determine after 90 seconds.)

Display of
Connection under check
Please wait for a moment is turned on.

No display

Remote controller display

Remote Controller
EDSG281001

Checking procedure of error record

Registration method of the service contract

Detail Information of Options

3P243521-1

01_EN_3P243521-1.indd 21

English

The basic screen returns.

10-2 Press Cancel button twice.

10-1

Setting

28C

Set temperature

Setting

Return

Indoor unit
Outdoor unit

Contact address
012345678900

Setting

/000
/000

Service Contact/Model info

Return

Set temp mode changeover


Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info

MainMenu
1/2

<Main menu screen>

Return

Cool

21

11-4

11-2
11-3

11-1

22

(Up/Down) buttons to select


Language on the language changeover screen.
English/Deutsch/ Franais/Espaol/
Italiano/E/Nederlands/
Portugues/Pycc/rke
Pressing Menu/Enter button.
Setting details are conrmed and basic
screen returns.

12-2 Press

screen.
Main menu is displayed.
Select Language changeover in the
main menu, press Menu/Enter button.

12-1 Press Menu/Enter button in the basic

12-2

12-1

Setting

Setting

Setting

No

<Basic screen>

Return

Yes

Is it settled by setting?

Clock setting

Return

00:00

Year 2008
Month 01
Day
01
Tuesday

Clock setting

Return

Convenient functions
Setting status list
Clock setting
Language changeover

MainMenu

Setting

Return

Setting

English

Selectable languages

Language changeover

Return

Convinient functions
Setting status list
Clock setting
Language changeover

MainMenu

2/2

<Main menu screen>

<Basic screen>

2/2

<Main menu screen>

<Basic screen>

12. Language changeover

If duration of power outage exceeds


48 hours, reset is needed.

button.
Setting details are conrmed and basic
screen returns.

11-4 Select Yes and press Menu/Enter

Setting conrmation screen is displayed.

11-3 Press Menu/Enter button.

by using
(Left/Right) button and
(Up/Down) button in
set by using
the clock setting screen. During the
button is pressed and held, numeric
changes continuously.
Day of the week is set automatically.

11-2 Select year, month, day and time

2/3/2009 1:19:25
01_EN_3P243521-1.indd
PM
22

Registered details
are displayed.

Press Menu/Enter button.

Press Menu/Enter button.

screen.
Main menu is displayed.
Select Clock setting in the main
menu, press Menu/Enter button.

11-1 Press Menu/Enter button in the basic

<Basic screen>

10-1 Press Menu/Enter button in the basic

screen.
Main menu is displayed.
Select Service Contact/Model Info in
the main menu, and press Menu/Enter
button.

11. Clock Setting

10. Conrmation of registered details

2/3/2009 1:19:26 PM

English

Press Menu/Enter button.

Press Menu/Enter button.

Press Menu/Enter button.

Press Menu/Enter button.

EDSG281001
Remote Controller

Confirmation of registered details

Clock setting

Language changeover

335

Remote Controller

2.4

EDSG281001

Wireless Remote Controller


Model series

Name of option
Remote controller

Wireless type

FCQ

FFQ

FHQ

FBQ

BRC7F632F

BRC7E531W

BRC7EA66

BRC4C62

Figure 1

1-1
1

ON OFF

8
3

DOWN

1-2

10

ON OFF

UP

TEMP
H

FAN

L TIME

11

C
UP

hr.

DOWN

FAN

hr.

13

RESERVE CANCEL

hr.
5

TIMER

12

MODE

15

hr.
TEST
7

SWING

14
16

TEST
TEST

17

3P107422-11J

Figure 2 (explanation of receiver)


FCQ

FFQ

22

23
21

20

22

23
19
18

18

19
20

21

3P107422-1S

3P107422-11J

FHQ

FBQ (separate type)


18
20

22 23

22

19
21

23

19

21 20

18

3P107422-8S

336

3P107422-21S

Detail Information of Options

EDSG281001

Remote Controller

Names and functions of the operating section (fig. 1, 2)

DISPLAY
SION)

(SIGNAL TRANSMIS-

This lights up when a signal is being transmitted.


DISPLAY

(OPERATION MODE)

DISPLAY

(SET TEMPERATURE)

This display shows the set temperature.


hr.
DISPLAY hr.

(PROGRAMMED
TIME)
4
This display shows PROGRAMMED TIME
of the system start or stop.

5 DISPLAY
6

DISPLAY

(AIR FLOW FLAP)

OPERATION MODE SELECTOR BUTTON


15 Press this button to select OPERATION
MODE.
FILTER SIGN RESET BUTTON

2 This display shows the current OPERATION MODE. For cooling only type,

(Auto) and
(Heating) are not
installed.
3

14 AIR FLOW DIRECTION ADJUST BUTTON

(FAN SPEED)

The display shows the set fan speed.

16 Refer to the section of MAINTENANCE in


the operation manual attached to the
indoor unit.
INSPECTION/TEST OPERATION BUTTON
17 This button is used only by qualified service persons for maintenance purposes.
EMERGENCY OPERATION SWITCH
18 This switch is readily used if the remote
controller does not work.
RECEIVER
19 This receives the signals from the remote
controller.

OPERATING INDICATOR LAMP (Red)


20 This lamp stays lit while the air
conditioner runs. It flashes when the unit is
in trouble.
21

TEST
DISPLAY
(INSPECTION/ TEST OPERATION)
7 When the INSPECTION/TEST OPERATION BUTTON is pressed, the display
shows the system mode is in.
ON/OFF BUTTON
8 Press the button and the system will start.
Press the button again and the system will
stop.
FAN SPEED CONTROL BUTTON
9 Press this button to select the fan speed,
HIGH or LOW, of your choice.

TEMPERATURE SETTING BUTTON


10 Use this button for SETTING TEMPERATURE (Operates with the front cover of the
remote controller closed.)

PROGRAMMING TIMER BUTTON


Use this button for programming START
11 and/or STOP time. (Operates with the
front cover of the remote controller
opened.)
12 TIMER MODE START/STOP BUTTON
13 TIMER RESERVE/CANCEL BUTTON

22

TIMER INDICATOR LAMP (Green)


This lamp stays lit while the timer is set.
AIR FILTER CLEANING TIME
INDICATOR LAMP (Red)
Lights up when it is time to clean the air filter.
DEFROST LAMP (Orange)

23 Lights up when the defrosting operation


has started. (For cooling only type this
lamp does not turn on.)

NOTES
For the sake of explanation, all indications are
shown on the display in Figure 1 contrary to
actual running situations.
Fig. 1-2 shows the remote controller with the
front cover opened.
If the air filter cleaning time indicator lamp
lights up, clean the air filter as explained in the
operation manual provided with the indoor
unit.
After cleaning and reinstalling the air filter,
press the filter sign reset button on the remote
controller. The air filter cleaning time indicator lamp on the receiver will go out.
The Defrost Lamp will flash when the power is
turned on. This is not a malfunction.
C : 3P107422-11J

Detail Information of Options

337

FCQ

EDSG281001

3. FCQ
3.1

BYCP125K-W1 Decoration Panel

1. BEFORE INSTALLATION
1. PRECAUTIONS
Refer also to the installation manual attached to the indoor unit.

2. ACCESSORIES
Installation manual.

3. NOTE TO INSTALLER
Be sure to instruct the customer how to properly operate the system showing him/her the attached
operation manual.

2. PREPARATION OF DECORATION PANEL


For this unit, you are able to select air flow directions. To discharge air in 2 or 3 directions, it is necessary
to purchase optional blocking pad kit.
HANDLING OF DECORATION PANELS
Never place the panel facing down nor lean it against a wall nor leave it on a projecting object.
Never touch or put pressure on the swing flap.
(The swing flap may malfunction)
(1) Remove the suction grille from the decoration panel.
1 Press the lever on the suction grille and lift the lever side. (Refer to Fig. 1)
2 Detach the suction grille from the decoration panel by lifting the grille up approximately 45 degrees.
(Refer to Fig. 2)
3 Remove the transporting cardboard (in 4 locations) from the main unit. (Refer to Fig. 3)
4 Remove the transporting tape (in 4 locations) on the back of the suction grille. (Refer to Fig. 4)

Corner section
decoration cover
Suction grille

Decoration
panel
Lever

45

Swing flaps
Fig. 1

Fig. 2

1
3PA64319-13Q

338

Detail Information of Options

EDSG281001

FCQ

(2) Remove the corner section decoration cover.


Lift the four corner decoration covers in the direction of the arrow and remove. (Refer to Fig. 5)

Cardboard
Tape

Corner section
decoration cover

Suction grille

Rear side of the suction grille


Fig. 3

Fig. 5

Fig. 4

3. INSTALLATION OF THE DECORATION PANEL TO THE INDOOR UNIT BODY


Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.
(1) Match the PIPING SIDE and DRAIN SIDE displays on the decoration panel with the position of the piping section and drain section on the indoor unit.
(2) Install the decoration panel
1 Temporarily install the decoration panel to the indoor unit by hanging the temporary latch of the decoration panel to the hook of the indoor unit body. (2 locations)
2 Hook the four mounting brackets on the corner sections of the decoration panels onto the hooks around
the main indoor unit body.
(Make sure at this time that the swing motor lead wire does not get caught between the decoration panel
and the main unit.)
3 Screw all 4 hexagon head screws located right beneath the latches in approximately 5 mm. (Panel will rise)
4 Adjust the decoration panel by turning it to the arrowed direction in Fig. 6 so that the ceiling opening is
completely covered.

Drain
section

Mounting bracket
Piping section

Hook

Hook

(4 locations)

Temporary latch (2 locations)


PIPING SIDE marking
DRAIN SIDE marking
3 5

4
Fig. 6

2
3PA64319-13Q

Detail Information of Options

339

FCQ

EDSG281001

5 Tighten the screws until the thickness of the sealing material between the decoration panel and the
indoor unit body reduces to 5-8 mm.

Sealing material

Indoor unit

5 - 8mm
Ceiling
material

Swing flaps
Decoration panel

[ PRECAUTIONS ]
Inproper screwing of the screws may cause the
troubles shown in Fig. 7 Screw properly.

Air leak
Air leak from ceiling
Contamination

Dew formation, dew dripping


Fig. 7

If gap is still left between the ceiling and the decoration panel after screwing the screws, readjust the indoor
unit body height. (Refer to Fig. 8)

Adjustment of the indoor unit body


height from the holes in the corner
of the decoration panel is possible
if the indoor unit is kept leveled and
the drain piping, etc. is unaffected.
No gap is allowed
Fig. 8
(3) Wiring of the decoration panel (Refer to Fig. 9)
6 Remove the electric components box lid.
7 Connect the connectors for swing flap motor lead wire installed on the decoration panel.
8 Replace the electric components box lid reversing the procedure to remove it.
Make sure that the swing flap motor lead wire is not caught between the electric components box and its lid,
and between the indoor unit body and the decoration panel.

3
3PA64319-13Q

340

Detail Information of Options

EDSG281001

FCQ

7 Swing flap motor lead wire


Decoration panel side

Connector
Connect securely

Indoor unit side

Hooks

Swing flap motor lead wire


<Wiring Diagram>
(The orientation of the indoor unit is changed
for purposes of description.)

Screw
(2 locations)

6 8 Electric
components box lid

Loosen the two screws, slide the cover


in the direction of the arrows,
and disengage from the hooks.

Fig. 9

4. INSTALLATION OF SUCTION GRILLE AND SERVICE COVER


(1) Install the suction grille
Install by reversing the procedure shown in PREPARATION OF DECORATION PANEL.
It is possible to install the suction grille in 4 directions by turning the suction grille.
Change the direction when adjusting the direction of the suction grille of multiple units or in meeting
customers demands.
Install the suction grill.
1 Tilt the suction grill at a
45 angle and fix 3 hooks
to the decoration panel.

Decoration
panel body

Hook up the strings of the suction grill to the fixtures of the


body corners (2 places) as shown below.
NOTE:
String
When mounting the
suction grill, strings may
be caught in the grill.
Be sure that
strings do not
Suction grill
hang out of the
suction grill edges.
String

Slowly push the suction


grill up and lastly, ensure
the grill is fastened to the
decoration panel body,
keeping pressing 2 knobs.

It should not
hang outside.

Fixture
String

Fixture
String
When installing the grill,
change the direction of
the strings.

Suction grill
Suction grill

NOTE :
Be careful not to get swing flap motor lead wire get caught when installing the suction grille.
C : 3PA64319-13Q

Detail Information of Options

341

FCQ

EDSG281001

(2) Install the corner section decoration cover.


1 Attach the string of the corner section decoration cover to the pin of the decoration panel. (Refer to Fig. 10)
2 Install the corner section decoration cover over the decoration panel. (Refer to Fig. 11)

Hole
Hole
Attach by inserting the
five tabs on the corner
section decoration cover
Tab
into the holes on the
Tab decoration panel.

Hole
Tab
Fig. 10

Fig. 11

4
C : 3PA64319-13Q

342

Detail Information of Options

EDSG281001

3.2

FCQ

KDBH55K160F Sealing Member of Air Discharge Outlet

KDBH55K160 / KDBH55K160F

Dimensions

Unit:mm

Sealing materials for long air outlets (Polyethylene foam t10): 2 pieces

Sealing materials for horizontal blades (Polyethylene foam t10): 8 pieces

Slit

Sealing materials for air outlets at the corner (Polyethylene foam t10): 1 piece for each

Tape for sealing materials


for long air outlets (Non-woven fabric t0.6): 2

Tape for sealing materials


for air outlets at the corner (Non-woven fabric t0.6): 3

Tape for sealing materials


for air outlets at the corner (Non-woven fabric t0.6): 1

Slit

Side insulation plate (NB foam t10) : 2

Antisweat material (Flocking tape): See right

Applicable part number

Q'ty and colour


4, grey
4 for each, Dark grey or black

Antisweat material (Flocking tape): See right

Applicable part number

Q'ty and colour


4, grey
4 for each, Dark grey or black

J : D3K05112

Detail Information of Options

343

FCQ

EDSG281001

Installation
Precautions
Use this manual with the installation manuals attached to the indoor unit's main body and decoration panel.
When other separately-sold products are mounted, the 3-way blow and 2-way blow may not be selected.
For details, refer to the Engineering Data or catalog.

Parts content
Name

Check the following parts.


Corner air outlet Corner air outlet Corner air outlet Corner air outlet Corner air outlet
sealing material A sealing material B1 sealing material B2 sealing material C sealing material D

Longitudinal air outlet sealing material

Number of pieces

Shape/Symbol

Absorbent (Inside 1)

B2

B1

Longitudinal air outlet


Corner air outlet
Corner air outlet
tape for fixing the sealing material tape for fixing the sealing material tape for fixing the sealing material
2

Absorbent (Inside 2)

Absorbent (Outside)

Absorbent (Bridge centre)

Absorbent (Bridge outside)

10 Use only classes 28 to 56

11 Use only classes 63 to 160

12 Use only classes 28 to 56

Name
Number of pieces

13

The sticking procedure for absorbent


differs with classes 28 to 56 and with
classes 63 to 160.
(Refer to 2 Sticking of absorbent to air outlet.)

15 Use only classes 28 to 56

14

Shape/Symbol
24mm328mm

24mm410mm

Name

Side insulator plate

Number of pieces

24mm290mm

8mm505mm

47mm47mm

Horizontal
blade sealant

Horizontal blade absorbent


With 4-blade
KDBH55K160F

16

With 8-blade (2 colours)


KDBH55K160

With 4-blade
KDBH55K160F
18

17

Shape/Symbol

KDBH55K160, two colours are available,


( With
gray and black, matching the blade colours. )

100mm1480mm

With 8-blade (2 colours)


KDBH55K160

8 pieces
19

15mm200mm

KDBH55K160, two colours are available,


( With
gray and black, matching the blade colours. )

10mm95mm

Blow Direction Selection and Sealing Material Mounting


(1) Blow direction selection
Depending on the installation location, select a blow direction from the table below. For the setting position number, refer to
For the selection of installation location, refer to the installation manual attached to the indoor unit's main body.

Field Setting .

Precautions Blow direction patterns other than those shown in the figure below cannot be selected. (Condensation may occur.)
3

Air outlet 3

Air outlet A

Air outlet C

Pipe side Drain side

4-way

Air outlet B1, B2


Air outlet 2

4-way

3-way

Drain side
1

3-way

Air outlet 1

Air outlet 4
2

Air outlet D

2-way

Pipe side
1

2-way
3

(2) Matching with the corner air outlets A to D that are to be blocked, stick the sealing material to the tape for fixing the sealing material.
(Stick the sealing material so that the sealing material comes to the positions shown in the schematic diagram.)
Sealing material 3

Sealing material 4

(3) Stick the sealing material that was prepared in


(2) to the air outlet of indoor unit main body.

Sealing material 2
B1

Release paper

A
(12

B2

(12

2
(12

Procedure 1
Remove the
release paper.
)

(12

Air outlet B1

the indoor unit's main


( When
)
body belongs to classes 28 to 56

Tape for fixing the sealing material 8

Air outlet B2

the indoor unit's main body


( When
)
belongs to classes 63 to 160

Sealing material 5

(12

Air outlet A

Stick the sealing material to the


tape for fixing the sealing material.

Procedure 2

Sealing material 6

Air outlet

(12)

With air outlets B to D , using the same procedure,


stick the sealing material to the tape for fixing the sealing material as shown in the figure.

Precautions

Tape for fixing the sealing material 8

Tape for fixing the sealing material 8

)
(12

(12

(12

Tape for fixing the sealing material 8

Air outlet C

Tape for fixing the sealing material 9

Indoor unit main body

Air outlet D

The sealing material has a directional property. Be sure to stick the sealing material to the tape for fixing the sealing material so that the printed number of outlet to be blocked becomes visible.
When blocking both the air outlet 1 and air outlet D , start the sticking of sealing material with the air outlet D .

(4) Matching the longitudinal air outlet numbered 1 to 4 that are to be blocked, prepare the sealing material and tape for fixing the sealing material.
Cut both the sealing material and tape for fixing the sealing material along the perforation (dotted line).
Stick the sealing material to the tape for fixing the sealing material.
(Stick so that the sealing material comes to the centre of tape for fixing the sealing material.)
Example) When blocking air outlet 2 or 3

(5) Stick the sealing material that was prepared in


(4) to the air outlet of indoor unit main body.

Indoor unit main body

Sealing material 1

Procedure 2

Procedure 1
Cut off

Remove the
release paper.

Release paper

Procedure 3

Tape for fixing the sealing material 7

<Sealing material treatment> Stick the sealing material so that it comes


to the centre of tape for fixing the sealing material.

Air outlet 1

<Mounting to air outlet>

When blocking the air outlet 1 , the sealing material preparation is not necessary.

Precautions

The sealing material has a directional property. Be sure to stick the sealing material to
the tape for fixing the sealing material so that the printed number of outlet to be blocked becomes visible.

J : 1P177350A

344

Detail Information of Options

EDSG281001

FCQ

Sticking of Absorbent to Air Outlet

Stick the absorbent indicated in the table below to the air outlet that was not blocked in

according to the procedure shown in the figure below.

If the sticking of absorbent is omitted, condensation may occur.


To positions where the absorbent is already stuck,
the sticking of absorbent is not necessary.

Precautions

Classes 63 to 160

Classes 28 to 56
Air outlet 1
Air outlet 2

Absorbent 10

13

14

Air outlet 3

Absorbent 10

13

14

Air outlet 4

Absorbent 12

15

Total 3 pieces
15

Absorbent 11

Total 4 pieces

13

14

Total 3 pieces

Total 2 pieces

Classes 28 to 56
e

ing

10

fe
re

nc

13

re

Air outlet 3
St

ing

en

Stic
kin

g re

ce

ren

refe

10

St

ick

ing

re

fer

ce

10 13 Sticking reference
(Upper surface)

re

fer

14

king
Stic

en

ick

ick
St

13

ce

13 Sticking reference
(Upper surface)

fere

10

nce

10
14

14

10

13

Sticking reference
(Upper surface)

ce
en e)
c
fer
re ren
ing efe
ick tre r
t
S
en
4
C
1
(

13
ce

14

king
Stic

n
fere

15

14

re

15

St
(C ickin
en g
tre refe
re re
fer nc
en e
ce
)

View

Air outlet 2

15

k
Stic

re
ing

fere

S
(C tick
en ing
tre re
re fer
fe en
re ce
nc
e)

View

nce
12 Sticking reference
(Upper surface)

15

12
fere

nce

(5)

g re

(5)

12

kin
Stic

Cross section -

15

Air outlet 1

15

15 Sticking reference

Air outlet 4

Sticking not necessary

Cross section -

Classes 63 to 160
13

king
Stic

refe

renc

11

g
ckin
Sti

ick

ing

re

fer

en
c

Air outlet 3

14

St

11 13 Sticking reference
(Upper surface)

ce
ren
refe

11
14

Air outlet 2
Sticking not necessary

13
14

St
(C ickin
en g
tre refe
re re
fer nc
en e
ce
)

View

Air outlet 1

Air outlet 4
Sticking not necessary

continuted on back side

Sticking not necessary

J : 1P177350A

Detail Information of Options

345

FCQ

EDSG281001

Sticking of Insulator to Indoor Unit Main Body


For safety, be sure to shut off power supply before starting the insulator sticking operation, decoration panel mounting operation, and connecting of connectors for swinging.
Precautions

If the sticking of insulator is omitted, condensation may occur.

16 Sticking reference

Stick the side insulator plate 16 according to the figure below.

Side insulator plate 16

16 Sticking reference

16 Sticking reference

Side insulator plate 16

For a wiring takeoff point with two sections, make a slit on


the side insulator plate 16 as shown in the figure below,
then route the wiring.

Side insulator plate 16

Side insulator plate 16


Side insulator plate 16

Side insulator plate 16

Wiring

Wiring

Slit

Slit

Side insulator plate 16

Superimpose the surplus section.

Wiring takeoff point

Sticking of Absorbent to Panel Horizontal Blade


Perform the operation on soft cloth to prevent damage to the panel.
Perform sticking for the horizontal blades of all air outlets.
Do not apply force to the horizontal blade. (Application of force may lead to horizontal blade
swing failure.)

Stick the horizontal blade sealing pad 19 to the backside of the blade. (For both left and right)

According to the figure below, stick the horizontal blade absorbent 17 and 18 as well as the horizontal blade
sealing pad 19 .
(With KDBH55K160, stick the horizontal blade absorbent with matching blade colour.)

Precautions When the sticking of absorbent and sealant is omitted, condensation may occur.
1 Stick the horizontal blade absorbent 17 in line with the blade shape to the front face of the horizontal blade.
Horizontal blade

Horizontal blade absorbent 17

Horizontal blade sealing pad 19

19 Sticking reference

A
A

19 Sticking reference

Using the base of the rib as a reference, stick without leaving any gap.
Rib
Horizontal blade
Horizontal blade
Front face

Stick the horizontal blade absorbent 18 in between the horizontal blade sealing pad 19 .

Horizontal blade absorbent 18

Backside
18 Sticking reference

A-A cross section


Horizontal blade absorbent 17

Horizontal blade sealing pad 19

17 Sticking reference

18 Sticking reference

B-B cross section

Horizontal blade absorbent 18

Field Setting
Depending on the installation status of the indoor unit's main body, the field setting needs to be performed by remote control operation.
Perform the setting by switching among the following three items: "Mode number", "Setting switch number", and "Setting position number".
The setting procedure and operation method are described in "How to perform field setting" attached to the remote control.
(1) Setting by number of air outlets used
While referring to "How to perform field setting" attached to the remote control, perform the setting according to the table
in the right.
Also, when the corner air outlet is blocked with 4-way blow, set the wind direction slightly downward.
(Note) When the installation height becomes higher than the standard, the setting by ceiling height in (2) becomes
necessary.

[Setting content] (Setting by number of air outlets used)

(2) Setting by ceiling height


For the ceiling height, refer to the guidelines of ceiling height and number of air outlets used, then perform the setting for
each air outlet used according to the table below.

[Setting content] (Setting for when corner air outlet is blocked with 4-way blow)

(Guidelines of ceiling height and number of air outlets used)

Ceiling height

3-way blow
2-way blow

Standard

Types 28 to 90

Types 112 to 160

All-around blow 4-way blow 3-way blow 2-way blow

All-around blow 4-way blow 3-way blow 2-way blow

13 (23)

02
03

Setting position number


4

02
03

[Setting content] (Setting by ceiling height)


Mode number

2.7m or less 3.1m or less 3.0m or less 3.5m or less

3.2m or less 3.4m or less 3.6m or less 4.2m or less

Standard

High ceiling 1 3.0m or less 3.4m or less 3.3m or less 3.8m or less

3.6m or less 3.9m or less 4.0m or less 4.2m or less

High ceiling 1

High ceiling 2 3.5m or less 4.0m or less 3.5m or less

4.2m or less 4.5m or less 4.2m or less

High ceiling 2

Standard

13 (23)

(Wind direction) Mode number


Slightly downward

Number of air outlets used


Indoor unit

(Number of air outlets used) Mode number Setting switch number Setting position number

Setting position number


01

13 (23)

02
03

Values for ceiling height are provided as reference.

J : 1P191031A

346

Detail Information of Options

EDSG281001

3.3

FCQ

KDBP55H160FA Panel Spacer

KDBP55H160FA

Model
Item

KDBP55H160FA

Exterior

Fresh White

Material

Outside frame: Resin


Insulation: Polyethylene foam
Fixture : 4 pieces
Screws : 1 set

Accessories

Sealing material : 1 set


Installation manual.

Mass (Weight)

Using the panel spacer in areas of the ceiling


with limited space makes it possible to install
the air conditioner.
Hides the gap between the decoration panel
and the ceiling.

kg

1.2

Caution
When the panel spacer is installed, it is not possible to have 2-way air outlet.
Refer to the installation manual for both indoor unit and the panel spacer for
its installation.

Dimensions

Unit:mm

4-5 Hole
J : D3K04626

Detail Information of Options

347

FCQ

EDSG281001

Installation

C : 1P136564E

348

Detail Information of Options

EDSG281001

FCQ

1P136564E

Detail Information of Options

349

FCQ

3.4

EDSG281001

KDDP55K160(K) Fresh Air Intake Kit (Chamber Type)

KDDP55K160 (without T-shape, without Fan)

Model

KDDP55K160

Item
Fresh air intake method

Fresh air intake by air conditioning fan


150

Diameter of connection duct


Mass (Weight)

kg

4.5

Dimensions

Unit:mm
Number
Inspection hole o 450 or more
(See note 2)

Name

Indoor unit main body

Decoration panel

Suction chamber

Connecting port chamber (right)

Connecting port chamber (left)

Description

Accessories
Screws (M512) : 4 pieces
Sealing materials for air outlets at the corner
Tape for fixing sealing materials for air outlets at the corner
Installation manual
Inspection hole o 450 or more
(See note 2)

How to establish an inspection hole

(Note 7)

Note)
1. Maximum length of the duct is 4 meters.
2. When installing this kit, an inspection hole is required
(in order to maintain this kit). Establish an inspection holes on either side.
3. This kit is field assembly.
4. Install the hanging fixing for the T joint. Otherwise the load from T-shape pipe
assembly, etc., could create a gap between the indoor unit and suction chamber.
5. When mounting the duct fan, be sure to use the wiring modification adaptor to
interlock with the indoor unit fan.
6. With the intake wind volume, 10% or less of the "H" wind volume of the indoor unit
is recommended.
7. This graph shows values from the inlet of the T joint through that of the
indoor unit when KDDP55K160K (with a T joint) is connected.

Static pressure in the chamber

Resistance in the passage inside the chamber

(Ceiling opening dimension)

Airflow rate

BYCP125K-W1

Indoor unit
Classes 28 to 90
Classes 112 to 160

Mountable Indoor unit models


SkyAir

FCQ(N)71K / 100K / 125K / 140KVEA


F C Q 7 1 K / 1 0 0 K / 1 2 5 K / 1 4 0 K V LT

JC : D3K05058

350

Detail Information of Options

EDSG281001

FCQ

KDDP55K160K (with T-shape, without Fan)

Model

KDDP55K160K

Item
Fresh air intake method

Fresh air intake by air conditioning fan


150

Diameter of connection duct


Mass (Weight)

kg

6.5

Dimensions

Unit:mm
Number
Inspection hole o 450 or more
(See note 2)
Flexible duct
(Accessory)

Name

Indoor unit main body

Decoration panel

Suction chamber

Connecting port chamber (right)

Connecting port chamber (left)

Description

Accessories
Screws (M512) : 4 pieces
Sealing materials for air outlets at the corner
Tape for fixing sealing materials for air outlets at the corner
Installation manual
Inspection hole o 450 or more
(See note 2)

How to establish an inspection hole

T joint
(Accessory)

Suction duct
(Accessory)

Resistance in the passage inside the chamber

(Note 7)

Hanging fitting (Field supplied)


(See note 4)

Note)
1. Maximum length of the duct is 4 meters.
2. When installing this kit, an inspection hole is required
(in order to maintain this kit). Establish an inspection
holes on either side.
3. This kit is field assembly.
4. Install the hanging fixing for the T joint. Otherwise the load
from T-shape pipe assembly, etc., could create a gap between
the indoor unit and suction chamber.
5. When mounting the duct fan, be sure to use the wiring modification
adaptor to interlock with the indoor unit fan.
6. With the intake wind volume, 10% or less of the "H" wind volume
of the indoor unit is recommended.
7. This graph shows values from the inlet of the T joint through that of the
indoor unit when KDDP55K160K (with a T joint) is connected.

Static pressure in the chamber

Plate band (Accessory)

(Ceiling opening dimension)

Airflow rate

BYCP125K-W1

Indoor unit
Classes 28 to 90
Classes 112 to 160

Mountable Indoor unit models


SkyAir

FCQ(N)71K / 100K / 125K / 140KVEA


F C Q 7 1 K / 1 0 0 K / 1 2 5 K / 1 4 0 K V LT

JC : D3K05059

Detail Information of Options

351

FCQ

EDSG281001

Installation
Caution

After thoroughly reading these "Safety precautions", properly perform the installation.

For the installation parts, accessory parts and specified components must always be used.
If the specified components are not used, the kit may fall or an air leak may occur.
After the completion of installation, perform a test run to check that no abnormality is present.

Combination table
Model name

Installable indoor unit / Panel model name


SkyAir

FCQ(N)71K/100K/125K/140KVEA
FCQ71K/100K/125K/140KVLT

Panel

BYCP125K-W1

KDDP55K160 (K)

Parts content Check the following parts. (Shaded part


Name

Suction chamber

Connecting chamber (left)

Recommendations
This product can be mounted to a ceiling mounted cassette-type air conditioner
<Round flow>.
According to the table to the left, check the model name of the indoor unit, then mount the kit.
At the time of mounting, also refer to the installation manual for the indoor unit and to the
one for the decoration panel.
When mounting the duct fan, be sure to use the wiring modification adaptor [KRP1C63] to
interlock with the indoor unit fan.
For the intake wind volume, 10% or less of the indoor unit wind volume of "H" is
recommended.
When the intake wind volume becomes excessive, operation noise may become louder or
the intake temperature detection of the indoor unit may be affected.
Be sure to mount the supplied sensor assembly.
<For the duct used for field connection, those in the table below are recommended.>

Part number

Flexible duct
(Nominal diameter 150)

K-FDS151D (1m)
K-FDS152D (2m)
K-FDS153D (3m)
K-FDS154D (4m)

is included in a different package.)

Connecting chamber (right)

Corner air outlet


sealing material

Shape

Corner air outlet tape for


fixing the sealing material

Name

Part name

Mounting screw 7 Sensor assembly

Clamp

10

Mounting screw
(for sensor)

T joint

11

14

Partition plate

Shape

Number KDDP55K160
of pieces KDDP55K160K

Flexible duct

12

Sealing pad

13

1
1
Installation manual

Number KDDP55K160
of pieces KDDP55K160K

1
1

2
2

1
1

1
1

2
2

M5 12
4
4

2
2

1
1

1
1

(this document)
1
1

Selection of Installation Location and Establishment of Inspection Opening


(1) Refer to the figure below to select the installation location.

(2) Establish an inspection opening.

Inspection opening ( 450 or more)


(Refer to *2.)

Duct (arrangement at site)

*1

Inspection opening
opening
455mm (ceiling
dimension)

Indoor unit main body

(mm)

Indoor unit
classes 28 to 90

306

classes 112 to 160

348

*1. Install the suspension bracket for


the T joint section.
Because of the load from T joint,
etc., a gap may be created in
between the indoor unit and
suction chamber.

*2. Establish an inspection opening ( 450 or more).


Establish an inspection opening to either side.

Inspection opening ( 450 or more)

725

(Refer to *2.)

BYCP125K-W1

Mounting of Sensor Assemblies and Suction Chamber


* When the indoor unit main body is already installed, perform the following operations, complying with precautions below.
Shut off power supply before performing operation.
Remove the decoration panel from the indoor unit main body.
(For details, refer to the installation manual attached to the decoration panel.)

<Mounting of sensor assembly>

<Mounting of suction chamber>

(1) According to the installation manual attached to the indoor unit main
body, remove the cover of the control box.
(2) Using the supplied screws, tighten the sensor assembly together with
the bell mouth to the indoor unit main body.
(Mount without pinching the float switch lead wire.)
(3) Remove the connector (X16A) of the existing sensor from the PC
board of the indoor unit main body.
(4) Connect the lead wire of the mounted sensor assembly to the
connector (X16A) on the PC board of the indoor unit main body as
shown in the figure below.
(5) As shown in the figure below, fix the lead wire using the supplied
clamp.
(6) After all the wiring is completed, fit the control box cover according to
the installation manual attached to the main body.
(7) Making sure that the control box cover is covered with the partition
plate 14 , tighten these together using the screws on the cover. (Hook
the partition plate tab onto the cover.)
Sensor assembly 7

Bell mouth

Fixing screw 9
(2) Using the supplied
screws, tighten the
sensor assembly
together with the bell
mouth.
(5) Tighten with the
existing wiring.

* Figure shows an example where the indoor unit main body is newly
installed.
(1) Stick the corner air outlet tape for fixing the sealing material 5 to
the corner air outlet sealing material 4 , then stick it to the air outlet
Figure 2
of the indoor unit main body. (2 positions) Figure 1
(2) Mount the suction chamber 1 to the indoor unit main body using
the hook (4 positions). Figure 3 to Figure 5
For the fixing method of the hook, refer to Figure 4 , then mount at
4 positions.
* Mount so that the contours of the indoor unit main body and suction
chamber match. Figure 4
Figure 6

)
(12

(5) Tighten with the float switch


lead wire of the indoor unit
main body.

To Figure 4

Sensor assembly 7

Remove the
release paper.
(12

Indoor unit
main body

Procedure 2

Figure 2 For 2 positions

Sensor assembly

Refrigerant piping

|PS<

Air outlet

(3) Disconnect the connector of


the existing sensor.

Hook
(4 positions)

Tape for fixing the sealing material 5

Stick the sealing material to the tape for


fixing the sealing material. (2 pieces)

X16A
WHITE

Procedure 1

Clamp 8

* The figure
shows SkyAir

Control box cover


(1) Remove the control box
cover. (Screws at 2 positions)

Figure 3

Release paper Suction chamber 1


A

(4) Connect the connector of the


mounted sensor assembly.

Partition plate 14
(7) Using screws, tighten the
partition plate together with
the control box cover so that
the box cover is covered
with the partition plate.

Corner air outlet sealing material 4

Figure 1

Float
switch
lead wire

Indoor unit main body

Control box cover


Suspension bracket
(4 positions)

Bell mouth

JC : 3K017588D

352

Detail Information of Options

EDSG281001

FCQ

Figure 4 Mounting status

Figure 5 Status after mounting


Hook

Suction chamber 1

Figure 6 Drawing of mounting at completion

Hook

Hook

Suction chamber 1
Indoor unit main body
Suspension bracket

Match the contour

Fixing method of hook


Indoor unit main body

Suspension bracket

Suspension bracket

Installation of Indoor Unit Main Body and Suction Chamber


Install the indoor unit main body and suction chamber.
At the time of installation, perform the engineering work according to the installation
manual attached to the indoor unit main body. (For the installation height, refer to the figure
to the right.)
When mounting the suction chamber to the existing indoor unit main body, change the
installation height of the indoor unit main body to height in the figure to the right.

(mm)

Suspension bracket

BYCP125K-W1

Indoor unit
main body

185

Mounting of Connecting Chamber and Connection of Flexible Duct


Suction chamber

Ceiling surface

Mount the connecting chamber. (1 piece each for left and right, a total of 2 pieces) Figure 7
(1) Press the square hole area of the connecting chamber 2 ( 3 ) into the hook
section (tab) of the suction chamber 1 . (2 positions)
(2) Using the supplied screws 6 , fix the connecting chamber. (2 positions)
Connecting chamber left (right) 2 ( 3 )

Square hole
(Procedure 1)
Press the square hole area of the
connecting chamber 2 ( 3 ) into the
hook section of suction chamber 1 .
(2 positions each)

Screw 6
Outside air inlet

<How to Tight Sealing Pad>


(1)
7

(2)

(3)

(4)

Flexible duct
Split pin

Suction chamber 1

wrong

correct

(Procedure 2)
Using the supplied screws 6 , fix the
connecting chamber. (2 positions each)

Figure 7 Mounting of connecting chamber

(This figure shows the connecting chamber (left)

.)

(1) Wrap the sealing pad


to the position to be
tightened.

(2) Insert the tip of the


band through the
gap of the split pin,
then lightly tighten
by hand.

Precautions
Drawing of mounting
at completion

(3) Using a standard


tool (driver, pliers,
etc.), turn the split
pin to the direction
shown in the figure
to tighten the band.

(4) This completes


the mounting.

Because the split pin has a structure to prevent counter rotation, be careful with the
turning direction. (When a counter rotation is forced, the ratchet will be damaged, and
the tightening force will be weakened.)

In case of KDDP55K160K
(3) Connect the connecting chamber and T joint. Figure 8
Flexible duct 11
Connecting chamber (right) 3
T joint 10
Duct (field supplied)

Hanging band for duct


(field supplied)

(150)

(4) Mount the supplied installation pattern paper to the indoor unit by using screws to
cure the indoor unit.
(Refer to the installation manual of the indoor unit main body.)
(Refer to the figure below.)
Installation pattern paper
(Mounting of installation
(Supplied with the indoor unit
pattern paper)
main body)
Screw
(Supplied with the indoor unit
main body)

Sealing pad 12
Connecting chamber (left) 2
Insert the flexible duct
until the base of the
connecting chamber.

Figure 8

Duct Connection

To prevent applying weight to the


connecting chamber, hang the T
joint using the hanging band for
the duct.

Complete all the refrigerant and drain piping works for the indoor unit main body.

<<Duct: Nominal diameter 150>>

(1) Connect the duct to the duct connection area.


(2) Wrap the connection area with vinyl tape, etc., (arrangement at site) to prevent an air leak.
Precautions

a) Extreme bending

b) Multiple bending

c) Reduction of connecting duct diameter

For the duct, be sure to apply the insulation treatment to prevent condensation.
Do not perform duct manipulations described in the figure to the right.
Beware that, in accordance with the local law, there may be cases where the use of a nonflammable duct is
compulsory.
When a duct goes through fire protection areas including a fire proof structure, beware that, in accordance with the local law, it may be required to establish a damper or to build a
structure that is not detrimental to fire protection.
When penetrating a wooden construction wall with a metal duct, apply electrical insulation to the duct and wall.
Mount the outside duct so that it has a downslope toward the outside, and prevent rainwater from leaking in with a hood, etc. (Gradient of 1/100 to 1/50)
To prevent the intrusion of small animals, such as birds, and bugs, be sure to attach a netting to sections open to outside air.
To protect the heat exchanger of the indoor unit, be sure to attach an air filter to sections open to outside air.

Mounting of Decoration Panel


After temporarily hooking the decoration panel, pass the swing motor lead wire, which is coming out from the decoration panel, through the wiring hole of the suction chamber.
However, when used in combination with the air purifier unit or streamer deodorization unit, perform wiring without routing through the wiring hole.
Mount the decoration panel according to the installation manual attached to the decoration panel.
Suction chamber 1
Wiring hole
Swing motor lead wire: Route from the panel side to the
suction chamber 1 .
(After temporarily hooking the decoration panel, pass
through the wiring hole.)

With an air purifier unit or


streamer deodorization unit

With wireless unit


For details on connection method, refer to the installation manual
attached to the wireless remote control kit (sold separately).

Decoration panel

JC : 3K017588D

Detail Information of Options

353

FCQ

EDSG281001

KDDP55K160 (without T joint, without fan)

KDDP55K160K (with T joint, without fan)

354

Detail Information of Options

EDSG281001

3.5

FCQ

KDDP55X160 Fresh Air Intake Kit (Direct Installation Type)

KDDP55X160

Model

KDDP55X160

Item
Material

Hot-dip zinc-coated carbon steel sheet


100

Diameter of connection duct

Insulation material retainer plate : 1


Insulation material : 1 set

Accessories

Mounting screws : 4
Installation manual.

Dimensions

Unit:mm

98

12

67

137

124

4 5 Hole (cyclotomic)
J : D3K04240A

Detail Information of Options

355

FCQ

EDSG281001

Installation
Precautions

This kit can be mounted to a ceiling mounted cassette-type air conditioner.


When using this kit, a duct (nominal diameter: 100) is required separately.

Beware that, in accordance with the local law, there may be cases where the use of a nonflammable duct is compulsory.
When a duct goes through fire protection areas including a fire proof structure, beware that, in accordance with the local law,
it may be required to establish a damper or to build a structure that is not detrimental to fire protection.
When penetrating a wooden construction wall with a metal duct, apply electrical insulation to the duct and wall.
Mount the outside duct so that it has a downslope toward the outside, and prevent rainwater from leaking in.
(Gradient of 1/100 to 1/50)
To prevent the intrusion of small animals, such as birds, and bugs, be sure to attach a netting to sections open to
outside air.

Parts content Check the following parts.


Name
1 Duct flange 2 Mounting screws 3 Duct flange insulator
Number of pieces
1
4
1

4 Main body opening insulator 5 Sealing pad retainer 6 Installation manual


1
1
1

Shape
M412

Tools needed for mounting

Phillips-type screwdriver, nippers, and cutter, etc.

Mounting of Duct Flange


1) Cut off the side plate of the indoor unit main body along the dowel hole without damaging
the internal insulator. Figure 1
Piping position
Drain pipe position

Internal insulator

Side plate

Cut off using


nippers, etc.
Slit

Side plate

Figure 1

2) Stick the main body's opening insulator 4 to the opening. Figure 2

Figure 2

Main body opening insulator 4

JC : 2P137676B

356

Detail Information of Options

EDSG281001

FCQ

3) After mounting the duct flange 1 to the opening using the mounting screws 2 (M412, 4 pieces),
stick the duct flange insulator 3 . Figure 3

Duct flange 1

Mounting screws 2
(M412, 4 pieces)

Figure 3

Duct flange insulator 3

4) Before mounting the decoration panel, remove the insulator, and stick the sealing pad retainer 5 to
the indoor unit drain pan. Figure 4

Figure 4

Sealing pad retainer 5


Be careful not to
block the air outlet.

Insulator

Duct Connection

Duct: Nominal diameter 100

1) Connect the duct to the outside of the duct flange. Figure 5


2) After the connection, wrap the connection area with tape (field supplied) to prevent an air leak.
Duct flange 1

Wrap with tape to prevent an air leak.

Figure 5
Indoor unit main body
Tape

Precautions
Perform insulation for all ducts.
Do not perform duct manipulations
shown to the right.

100 duct (field supplied)

a) Extreme bending

b) Multiple bending

c) Reduction of connecting
duct diameter

J : 2P137676B

Detail Information of Options

357

FCQ

3.6

EDSG281001

KAFP556H80 / KAFP556H160, KAFP557H80 / KAFP557H160


High Efficiency Filter (Including Chamber)

KAFP556H80 / KAFP556H160
KAFP557H80 / KAFP557H160

Dimensions

Unit:mm
50 (dimensions when mounted)

842

842

J : D3K04253

Caution
Field setting by remote controller is necessary
when the high efficiency filter is installed.

Model
Item

KAFP556H80

KAFP557H80

Initial
pressure loss

Pa

34 or less

Final pressure
loss

Pa

98 or less

Air flow rate

65 (colorimetric method)

90 (colorimetric method)

m3/min

19

35

19

35

l/sec

317

583

317

583

Life

2,500
(dust concentration 0.15 mg/m3)

Filter element

1,800
(dust concentration 0.15 mg/m3)

Non-woven fabric of synthetic fiber

Number of sheets
included

Installation manual.

Accessories
Mass (Weight)

KAFP557H160

Galvanized sheet iron.


Foam polystyrene.

Material

Average
efficiency

Sealing material : 2
kg

Replacement filter
(optional
accessories)

358

KAFP556H160

3.6

4.2

3.6

4.2

KAFP552H80

KAFP552H160

KAFP553H80

KAFP553H160

Detail Information of Options

EDSG281001

FCQ

Installation
Caution

After thoroughly reading these "Safety precautions", properly perform the installation.

For the installation parts, accessory parts and specified components must always
be used.
If the specified components are not used, the kit may fall or an air leak may occur.
After the completion of installation, perform a test run to check that no abnormality
is present.

Recommendations
This product can be mounted to a ceiling mounted cassette-type air conditioner
<round flow >.
According to the table below, check the model name of the indoor unit main body,
then mount the product.
At the time of mounting, also refer to the installation manual of the indoor unit and to
the installation manual of the decoration panel.

Parts content Check the following parts.


Combination table
Name

High efficiency filter unit

Sealing pad Installation manual

Model name

Installable indoor unit model name / Panel model name

KAFP556H80
KAFP557H80

Shape

FCQ71KVLT

KAFP556H160
KAFP557H160
Number of pieces

FCQ(N)71KVEA

SkyAir

FCQ(N)100K / 125K / 140KVEA

SkyAir

FCQ100K / 125K / 140KVLT

1 (This document)
Panel

BYCP125K-W1

Mounting of High Efficiency Filter Unit


Figure 1

* When the indoor unit main body is already installed, perform the following operations, complying with
precautions below.
Shut off power supply before performing the operation.
Remove the decoration panel from the indoor unit's main body.
(For details, refer to the installation manual attached to the decoration panel.)

High efficiency filter


Filter clasp

* When the indoor unit main body is newly installed

Rotate the filter clasp by 90


to remove the filter
(4 positions)

(1) Remove the high efficiency filter from the chamber. Figure 1
(2) Mount the high efficiency filter unit to the indoor unit main body using the hooks
(4 positions). Figure 2 to Figure 4
For the fixing method of the hooks, refer to the figure to the right. Mount at 4 positions.
* Mount so that the contours of the indoor unit main body and chamber match.

Hook

Figure 3

Figure 5

Suspension bracket

Figure 2

Fixing method of hooks


High efficiency filter
unit

Figure 3

Mounting status

Figure 4 Status after mounting

High efficiency filter unit


Hook
Indoor unit main body

Hook

(4 positions)

Match the contour.


Control box cover
Indoor unit main body
Suspension bracket
Suspension bracket
(4 positions)
Refrigerant piping

Figure 5 Drawing of mounting at


completion
High efficiency filter unit

Indoor unit main body

JC : 3K015220F

Detail Information of Options

359

FCQ

EDSG281001

Installation of Indoor Unit Main Body and High Efficiency Filter Unit
Install the indoor unit main body and high efficiency filter unit.
At the time of installation, perform engineering work according to the installation manual attached
to the air conditioner's main body. (For the installation height, refer to the figure to the right.)

Suspension bracket

When mounting the high efficiency filter unit to the existing indoor unit main body, change the
installation height of the indoor unit main body to height in the figure to the right.

Indoor unit
main body
(Installation height
guideline)

Mount the supplied installation pattern paper to the indoor unit using screws to
cure the indoor unit.
(Refer to the installation manual for the indoor unit main body.)
(Refer to the figure below.)

High efficiency filter unit

Ceiling surface

(mm)

Installation pattern paper


(Supplied with indoor unit main body)

185

BYCP125K-W1

M412 Screws
(Supplied with indoor unit main body)

[Mounting of installation pattern paper]


Complete all the refrigerant and drain piping work for the indoor unit main body.

Mounting of Decoration Panel and Mounting of High Efficiency Filter


After temporarily hooking the decoration panel, pass the swing motor lead wire, which is coming out from the decoration panel, through the wire through hole of
the high efficiency filter unit.
Mount the decoration panel according to the installation manual attached to the decoration panel.

Sealing pad (supplied): For preventing air bypass


(Stick to 2 positions in the same manner.)

Figure 6

High efficiency
filter chamber
Wire through hole

Swing motor lead wire:


Route from the panel side to
the high efficiency filter chamber.

Decoration panel

(After temporarily hooking


the decoration panel,
pass through the wire through hole.)

High efficiency
filter unit

Decoration panel

Mounting of high efficiency filter


After the completion of wiring and sticking of sealing pad (2 positions), mount the high efficiency
filter. Figure 6 Figure 7

Rotate the filter clasp by 90 to


fix the filter.
(4 positions)

Filter clasp

With wireless unit

Figure 7

High efficiency filter

Route the connector of the receiver lead wire through the wire through hole, then connect the connector on the indoor PC board ass'y.
For details on the connection method, refer to the installation manual attached to the wireless remote control kit (sold separately).

Preparation of Indoor Unit


With the mounting of a high efficiency filter unit, setting the indoor unit main
body is required.
Using the field setting mode on the remote control, switch to the setting
position number as shown in the table to the right.
For the field setting mode, refer to "How to perform field setting" attached to
the remote control.

Mode number

Setting switch number Setting position number

Remarks

02

80 only

02

Both 80 and 160

13 or 23

JC : 3K015220F

360

Detail Information of Options

EDSG281001

3.7

FCQ

KAFP552H80 / KAFP552H160, KAFP553H80 / KAFP553H160


Replacement High Efficiency Filter

KAFP552H80 / KAFP552H160
KAFP553H80 / KAFP553H160

Dimensions

Unit:mm
Model
KAFP552H80 KAFP553H80
KAFP552H160 KAFP553H160

A
25
45

560

560

3
0

10

540 -2

10

D3K04256A

Caution
Cannot be water-washed for reuse.
The filter chamber (KDDFP55H160) is required
when the high efficiency filter will be installed.

Model
Item

KAFP552H80

KAFP553H80

Initial
pressure loss

Pa

34 or less

Final pressure
loss

Pa

98 or less

Average
efficiency
Air flow rate

65 (colorimetric method)

90 (colorimetric method)

19

35

19

35

l/sec

317

583

317

583

2,500 (dust concentration 0.15 mg/m3) 1,800 (dust concentration 0.15 mg/m3)

Filter element

Non-woven fabric of synthetic fiber

Number of sheets
included
Mass (Weight)

KAFP553H160

m3/min

Life

Detail Information of Options

KAFP552H160

kg

0.6

1.2

0.6

1.2

361

FCQ

3.8

EDSG281001

KDDFP55H160 High Efficiency Filter Chamber

KDDFP55H160

Dimensions

Unit:mm
50 (dimensions when attached)

842

842

J : D3K04252

Model
Item
65% (colorimetric method)
High efficiency
Inserted filter
90% (colorimetric method)
filter
Ultra long-life filter

KAFP553H160

KAFP55H160H

Installation manual
Sealing pad : 2

Accessories

362

KAFP552H80 KAFP552H160
KAFP553H80

Galvanized sheet iron.


Foam polystyrene.

Material

Mass (Weight)

KDDFP55H160

kg

8.0

Detail Information of Options

EDSG281001

FCQ

Installation
Caution

Recommendations

After thoroughly reading these "Safety Precautions", properly perform the installation.

This product can be mounted to ceiling mounted cassette-type air conditioner


<round flow>.
According to the table below, check the model name of the indoor unit main body, then
mount the product.
At the time of mounting, also refer to the installation manual for the indoor unit and to
the one for the decoration panel.

For the installation parts, accessory parts and specified components must
always be used.
If the specified components are not used, the kit may fall or an air leak may occur.
After the completion of installation, perform a test run to check that no
abnormality is present.
Recommendations (When using ultra-long life filter)

Combination table

The ultra-long life filter can be reused after cleaning.


After engineering work is completed, provide instructions to the customer about
the filter cleaning interval and how to remove the filter.

Model name High efficiency filter Ultra-long life filter Installable indoor unit model name / Panel model name
KAFP552H80
Or
KAFP553H80

Parts content Check the following parts.


Name

Filter chamber

Sealing pad Installation manual

KDDFP KAFP552H160
55H160
Or
KAFP553H160

FCQ(N)100K / 125K / 140KVEA

SkyAir

Panel

FCQ71KVLT

KAFP55H160H

Shape

Number of pieces

FCQ(N)71KVEA

SkyAir

FCQ100K / 125K / 140KVLT

BYCP125K-W1

1 (This document)

Mounting of Filter Chamber


* When the indoor unit main body is already installed, perform the following operations, complying with
precautions below.
Shut off power supply before performing the operation.
Remove the decoration panel from the indoor unit main body.
(For details, refer to the installation manual attached to the decoration panel.)
* When the indoor unit main body is newly installed

Hook

(1) Mount the filter chamber to the indoor unit main body using the hooks (4 positions).
Suspension bracket

Figure 1 to Figure 3
For the fixing method of the hooks, refer to the figure to the right. Mount at 4 positions.

Fixing method of hooks

* Mount so that the contours of the indoor unit main body and chamber are match. Figure 2

Figure 1

Figure 4

Figure 3 Status after mounting

Figure 2 Mounting status


Filter chamber

Filter chamber
Hook

Indoor unit main body

Hook
(4 positions)
Match the contour
Indoor unit main body
Suspension bracket

Lead wire

Suspension bracket
(4 positions)
Refrigerant piping

Figure 4

Drawing of mounting at
completion
Filter chamber

Indoor unit main body

JC : 3K015219F

Detail Information of Options

363

FCQ

EDSG281001

Installation of Indoor Unit Main Body and Filter Chamber


Install the indoor unit main body and filter chamber.
At the time of installation, perform engineering work according to the installation manual
attached to the air conditioner's main body. (For the installation height, refer to the figure to
the right.)
Suspension bracket

When mounting the filter chamber to the existing indoor unit main body, change the
installation height of the indoor unit main body to height
in the figure to the right.
Indoor unit
main body

Mount the supplied installation pattern paper to the indoor unit using screws
to cure the indoor unit.
(Refer to the installation manual of the indoor unit main body.)
(Refer to the figure below.)

Installation pattern paper


(Supplied with indoor unit main body)

(Installation height
guideline)

Filter chamber

Ceiling surface

(mm)

185

BYCP125K-W1
M4 12 screws
(Supplied with indoor unit main body)

[Mounting of installation pattern paper]

Complete all the refrigerant and drain piping work for the indoor unit main body.

Mounting of Decoration Panel and Mounting of Filter Chamber


After temporarily hooking the decoration panel, pass the swing motor lead wire, which is coming out from the decoration panel, through the wire through hole of the filter chamber.
Mount the decoration panel according to the installation manual attached to the decoration panel.
Sealing pad (supplied): For preventing air bypass
(Stick to 2 positions in the same manner.)

Figure 5

Filter chamber
Wire through hole
Decoration panel
Swing motor lead wire:
Route from the panel side to the
filter chamber.
(After temporarily hooking the
decoration panel, pass through
the wire through hole.)

Filter chamber

Rotate the filter clasp by 90


to fix the filter.
(2 positions)

Decoration panel
Filter clasp

Mounting of filter
After the completion of wiring and sticking of sealing pad (2 positions), mount the filter.
Figure 5 Figure 6

Before mounting each filter to the chamber,


cut off at the perforation (2 positions).
Filters

With wireless unit

Figure 6

Route the connector of the receiver lead wire through the wire through hole, then connect the connector on the indoor PC board assembly.
For details on the connection method, refer to the installation manual attached to the wireless remote control kit (sold separately).

Preparation of Indoor Unit


Filter name
Mode number Setting switch number
Depending on the types of mounting filters, setting the
High
indoor unit main body is may be required.
80 only
0
performance
13 or 23
Using the field setting mode on the remote control, switch
Both 80 and 160
1
to the setting position number shown in the table to the right. filter
For the field setting mode, refer to "How to perform field
setting" attached to the remote control.
0
10 or 20
Ultra-long life filter
1

Setting position number Filter sign display interval time


02
02
Where there is minimal fouling
01 Approximately every 10,000 hours
(Example: Office, etc.)
Where there is considerable fouling
02 Approximately every 5,000 hours
(Example: Pachinko parlor, etc.)
02

Initial setting for ultra-long life filter

JC : 3K015219F

364

Detail Information of Options

EDSG281001

3.9

FCQ

KAFP551K160 Replacement Long-life Filter

KAFP551K160

Model

KAFP551K160

Item
Initial pressure loss

Pa

Final pressure loss

Pa

49 or less

Average efficiency

60 (gravity method)

Air flow rate

4.9 or less

m3/min

18

l/sec

300

5,000 (dust concentration 0.15 mg/m3)

Life
Filter element

Mould-proof and antibacterial resin net

Number of sheets included

Mass (Weight)

kg

0.2

Caution
Can be water-washed. Can be reused.
Dimensions

Unit:mm
535.5

2310

492.5

3.5

552.5

>PS<

6 3.5
Square hole (both sides)

J : D3K05114

Detail Information of Options

365

FCQ

EDSG281001

3.10 KAFP55H160 Ultra Long-life Filter Unit (Including Chamber)


KAFP55H160

Dimensions

Unit:mm
50 (dimensions when attached)
842

842

12

J : D3K04254

Caution
In order to mount a ultra long life filter unit,
setting of the main unit of indoor unit should
be made.
Individual filter (KAFP55H160H) is available
as an optional accessory.

Model
Item

Filter cleaning period

Locations with much


dust

Approximately every
5,000 hours

Locations with little dust Approximately every


(e.g. offices)
10,000 hours

Initial pressure loss

Pa

8 or less

Final pressure loss

Pa

49 or less

50 (gravity method)

m3/min

29.5

Average efficiency

Life

l/sec

492

5,000 (dust concentration 0.3 mg/m3)

Filter element

Polypropylene honeycomb (with mould-proof)

Number of sheets included

1
Installation manual.
Sealing pad : 2

Accessories
Mass (Weight)

366

Galvanized steel iron.


Foam polystyrene.

Material

Air flow rate

Mounting locations

KAFP55H160

kg

4.7

Detail Information of Options

EDSG281001

FCQ

Installation
Caution

After thoroughly reading these "Safety precautions", properly perform the installation.

For the installation parts, accessory parts and specified components must
always be used.
If the specified components are not used, the kit may fall or an air leak may occur.
After the completion of installation, perform a test run to check that no
abnormality is present.

Recommendations
This product can be mounted to a ceiling mounted cassette-type air conditioner
<Round flow>.
According to the table below, check the model name of the indoor unit main body, then
mount the product.
At the time of mounting, also refer to the installation manual for the indoor unit and to
the one for the decoration panel.

Recommendations
The ultra-long life filter can be reused after cleaning.
After the engineering works are completed, provide instructions to the customer
about the filter cleaning interval and how to remove the filter.

Combination table
Installable indoor unit model name / Panel model name

Model name

Parts content Check the following parts.


Ultra-long life filter unit

Name

Sealing pad Installation manual

KAFP55H160

FCQ(N)71K/100K/125K/140KVEA
FCQ71K/100K/125K/140KVLT

SkyAir

Shape
Panel

Number of pieces

BYCP125K-W1

1 (This document)

Mounting of Ultra-Long Life Filter Unit


Figure 1

* When the indoor unit main body is already installed, perform the following operations, complying with
precautions below.
Shut off power supply before performing the operation.
Remove the decoration panel from the indoor unit main body.
(For details, refer to the installation manual attached to the decoration panel.)
* When the indoor unit main body is newly installed

Ultra-long life filter


Filter clasp
Rotate the filter clasp by
90 to remove the filter
(4 positions)

(1) Remove the ultra-long life filter from the chamber. Figure 1
(2) Mount the ultra-long life filter unit to the indoor unit main body using the hooks (4 positions).
Figure 2 to Figure 4
For the fixing method of the hooks, refer to the figure to the right. Mount at 4 positions.

Hook

* Mount so that the contours of the indoor unit main body and chamber match. Figure 3

Figure 5

Suspension bracket

Figure 2

Fixing method of hooks

Figure 3 Mounting status

Ultra-long life filter unit

Figure 4 Status after mounting


Ultra-long life filter unit

Indoor unit main body

Hook
(4 positions)

Hook

Match the contour.


Control box cover
Indoor unit main body
Suspension bracket
Suspension bracket
(4 positions)
Refrigerant piping

Figure 5 : Drawing of mounting at completion


Ultra-long life filter unit

Indoor unit main body

JC : 3K015221E

Detail Information of Options

367

FCQ

EDSG281001

Installation of Indoor Unit Main Body and Ultra-Long Life Filter Unit
Install the indoor unit main body and ultra-long life filter unit.
At the time of installation, perform engineering work according to the installation manual
attached to the air conditioner's main body. (For the installation height, refer to the figure to
the right.)

Suspension bracket

Indoor unit
main body

When mounting the ultra-long life filter unit to the existing indoor unit main body, change the
installation height of the indoor unit main body to height in the figure to the right.

(Installation height
guideline)

Mount the supplied installation pattern paper to the indoor unit by using screws
to cure the indoor unit.
(Refer to the installation manual of the indoor unit main body.)
(Refer to the figure below.)

Ultra-long life filter unit

Ceiling surface
(mm)

Installation pattern paper


(Supplied with indoor unit main body)

BYCP125K-W1

185

M4 12 Screw
(Supplied with indoor unit main body)

[Mounting of installation pattern paper]


Complete all the refrigerant and drain piping work for the indoor unit main body.

Mounting of Decoration Panel and Mounting of Ultra-Long Life Filter


After temporarily hooking the decoration panel, pass the swing motor lead wire, which is coming out from the decoration panel, through the wire through hole of the ultra-long
life filter unit.
Mount the decoration panel according to the installation manual attached to the decoration panel.

Sealing pad (supplied): For preventing air bypass


Figure 6 (Stick to 2 positions in the same manner.)
Ultra-long life filter chamber
Wire through hole

Swing motor lead wire:


Route from the panel side to the
ultra-long life filter chamber.

Decoration panel

(After temporarily hooking the


decoration panel, pass through
the wire through hole.)

Ultra-long life filter unit

Decoration panel

Rotate the filter clasp by 90


to fix the filter.
(4 positions)

Mounting of ultra-long life filter


After the completion of wiring and sticking of sealing pad (2 positions), mount the
ultra-long life filter. Figure 6 Figure 7

Filter clasp

Ultra-long life filter

Figure 7

With wireless unit


Route the connector of the receiver lead wire through the wire through hole, then connect the connector on the indoor printed circuit board assembly.
For details on the connection method, refer to the installation manual attached to the wireless remote control kit (sold separately).

Preparation of Indoor Unit


With the mounting of a ultra-long life filter unit, setting the indoor unit main
body is required.
Using the field setting mode on the remote control, switch to the setting
position number shown in the table to the right.
For the field setting mode, refer to "How to perform field setting" attached
to the remote control.

Mode number Setting switch number Setting position Number Filter sign display interval time
Where there is minimal fouling
01 Approximately every 10,000 hours
(Example: Office, etc.)
10 or 20

Where there is considerable fouling


(Example: Pachinko parlor, etc.)
02

02 Approximately every 5,000 hours


Initial setting for ultra-long life filter

JC : 3K015221E

368

Detail Information of Options

EDSG281001

FCQ

3.11 KAFP55H160H Replacement Ultra Long-life Filter


Dimensions

Unit:mm

10

536-20

10

KAFP55H160H

10
536 -20

12

10

12
60

12

12.5
J : D3K04257

Caution
Can be water-washed. Can be reused.
The filter chamber (KDDFP55H160) is
required when the ultra long life filter will be
installed.

Model
Item
Initial pressure loss

Pa

8 or less

Final pressure loss

Pa

49 or less

50 (gravity method)

m3/min

29.5

Average efficiency
Air flow rate
Life

l/sec

492

5,000 (dust concentration 0.3 mg/m3)

Filter element

Mould-proof resin net

Number of sheets included


Mass (Weight)

Detail Information of Options

KAFP55H160H

1
kg

3.4

369

FCQ

EDSG281001

3.12 KKSJ55K160 Chamber Connection Kit


KKSJ55K160

Dimensions

Unit:mm

Vinyl tube

J : D3K2186

Installation

, F H (Y) C ~ K V E
FHC~NUV1, FHC~NUV2S, ~KV2S

C : 3P089651D

370

Detail Information of Options

EDSG281001

FCQ

3.13 KDJP55H80 / KDJP55H160 Branch Duct Chamber


KDJP55H80 / KDJP55H160

Model

KDJP55H80

Item

KDJP55H160

Hot-dip zinc-coated carbon steel sheet


(with insulation)

Material

Mounting screws : 10
Blocking pad : 2
Tape for fixing the blocking pad : 2

Accessories

Opening sealing material : 1 set


Insulation material : 1 set
Installation manual.

Caution
1. When mounting, refer to the installation manuals for the indoor unit and the
decoration panel.
Dimensions

Unit:mm
KDJP55H160

208

11

206
198

6-6 10
oblong holes
4-6 holes

J : D3K04231

Detail Information of Options

232
177
106

179
167

77

156
148
15

6-6 10
oblong holes
4-6 holes

256
382
366
200

232
176

190

121
109

382
366
200

240

KDJP55H80

J : D3K04232

371

FCQ

EDSG281001

Installation
Combination table

Precautions
This product can be mounted to a ceiling mounted cassette-type air conditioner <round flow>.
According to the table to the right, check the model name of the indoor unit, then mount the product.
At the time of mounting, also refer to the installation manual for the indoor unit main body and to the
one for the decoration panel.
For the duct (field supplied) to be connected, those specified in the table to the right are recommended.

Parts content
Name

Model name

Installable indoor unit model name

KDJP55H80

SkyAir

KDJP55H160

SkyAir

FCQ(N)71KVEA
FCQ71KVLT

Check the following parts.


Branch duct chamber

Mounting screw Installation manual Sealing material Tape for fixing the sealing material

Shape/
Number

FCQ(N)100K / 125K / 140KVEA


FCQ100K / 125K / 140KVLT

M416
Number
80
of pieces 160

Name

10

Main body insulator


1

Main body opening sealant


3

5A

Recommended duct

5B

Branch duct chamber

Shape/
Number
(Large)

(Small)
Number
80
of pieces 160

Preparation Before Installation

2
1

Connecting duct kit name

KDJP55H80

K-FDK151B (1 m) or K-FDK152B (2 m) (Flexible duct: Nominal diameter of 150)

KDJP55H160

K-FDK201B (1 m) or K-FDK202B (2 m) (Flexible duct: Nominal diameter of 200)

With this branch duct, an independent 4-way and simultaneous 2-branch drawing are also possible.

With this branch duct chamber, the blow directions shown in the
figure to the right can be selected.
Select the blow direction that is most appropriate for the room
shape and installation position. (Blow directions other than those
in the figure to the right cannot be selected.)
From the external static pressure/air volume characteristics (refer
to the technical guide), select the duct length and air outlet.

Closed

Precautions

Branch

Be sure to securely block the air outlet of the indoor unit main
body to which the branch duct chamber is mounted. If the
blocking is incomplete, water spraying or condensation may
occur. Do not block the corner sections.
Mounting of Sealing Material to Indoor Unit .)
(Refer to
When mounting the branch duct chamber, be sure to perform field
setting of the indoor unit main body.
Field Setting .)
(Refer to

1-way branching, main body 3-direction blow


Drain side

Branch
Closed

Closed

Branch

Closed

Piping side

Branch

1-way branching, main body 2-direction blow


Closed

Closed

Closed

2-way branching, main body 2-direction blow

Branching to
either side

Closed

Branching to
either side

Another branch duct chamber set is necessary.


Closed

Closed

Closed

Closed

Branch

Branch

Mounting of Branch Duct Chamber


Face 3

When an installation is performed after mounting the branch duct chamber to the indoor unit main body
(at new installation), do not apply force to the branch duct chamber. (Deformation may occur.)

Face 2

Face 4

(1) Select the position where the branch duct chamber is mounted.
(2) Mount the branch duct chamber to the indoor unit according to the following procedure. ( Figure 2 is an
example of the face 1 side.)
1) Along the slit, cut the side plate of the indoor unit to which the branch duct chamber is mounted. Then,
cut the internal insulator along the groove.
(Use nippers, etc., to cut the slit section, and cutter, etc., to cut the groove section.) Figure 2

Face 3

Face 2

Figure 1

Face 1

Internal insulator

For the port opening operation, do not use a tool that produces chips, such as a saw. The drain system may become clogged, and a water
leak may occur.

Side plate

2) Use the sealant for sticking so that the gaps between the side plate and internal insulator are filled around the full circumference. Figure 3
First, stick the main body's opening sealant 4 to left and right of the opening, and the main body's opening sealant 5A ( 5B ) to the upper and lower sides of Face 4
the opening.
Figure 2
At this time, fold the main body opening sealant towards the inside so that the gap between the side plate and internal insulator is no longer visible.

Main body opening sealant


5A ( 5B )
(Top plate side)

Main body opening sealant 4

Stick without leaving


any gap against the main
body's opening sealant
5A ( 5B ).

Main body opening sealant 4

Stick without leaving


any gap against the main
body's opening sealant
5A ( 5B ).

Main body opening sealant 5A

Face 1

Side plate slit (Internal insulator groove)

Figure 3

Indoor unit main body

Internal
insulator

Side plate

Opening

Main body opening sealant 5A ( 5B )


Internal
insulator

Sectional View

Stick so that the gap between


the side plate and internal
insulator are filled around the
full circumference.

JC : 1P137894D

372

Detail Information of Options

EDSG281001

FCQ

3) Mount the branch duct chamber. Figure 4

Mount so that the flat face becomes


the top plate side of the indoor unit.

Indoor unit

Branch duct chamber


Mounting screw, 10 pieces
(M416)

Figure 4
(3) Stick the main body insulator to the indoor unit. (The figure is an example of the face 1 side) Figure 5

Main body insulator 1


Stick with the end folded.

Stick with the left sides of


the main body insulators
1 , 2 , and 3 aligned.

Main body insulator 2


Stick with the end folded.
Create a slit to the wiring hole using a cutter, etc..
Main body insulator 3

Duct Connection

Stick with the end folded.

Be sure to stick the main body insulator from the top of the branch duct
chamber flange (sheet metal section). Otherwise, condensation may occur.

Main body insulator 3

Figure 5

KDJP55H80 ... Nominal diameter of 150

<<Duct: KDJP55H160 ... Nominal diameter of 200>>


Tape

1) Connect the duct to the outside of the branch duct chamber. Figure 6
After the connection, wrap the connection area with tape (field supplied)
to prevent an air leak.

Indoor unit
main body

Apply insulation for all the ducts.


2) Do not perform duct manipulation described below.

a) Extreme bending

Wrap with tape to prevent


an air leak.

Branch duct chamber

b) Multiple bending

c) Reduction of connecting
duct diameter

Duct of 150 or 200


(field supplied)
Figure 6

1. Beware that, in accordance with the local law, there may be cases where the use of a nonflammable duct is compulsory.
2. When a duct goes through fire protection areas, including a fire proof structure, beware that, in accordance with the local law, it may
be required to establish a damper or to build a structure that is not detrimental to fire protection.
3. When penetrating a wooden construction wall with a metal duct, apply electrical insulation to the duct and wall.

Mounting of Sealing Material to Indoor Unit


For the block position, refer to

<<With the sealing material supplied in this kit, blocking of two openings can be performed.>>

Preparation Before Installation , then determine the position. Always block the branch duct mounting surface.

Closed

Air outlet 2

Air outlet 3

Closed

Closed
3-way blow

Closed
1

Drain side
Air outlet 3

Air outlet 1

Closed
2-way blow

Closed

Closed

Closed
Piping side

(1) Matching the longitudinal air outlets numbered from 1 to 4 to be blocked, prepare the sealing material and tape for fixing the sealing material.
Cut both the sealing material and tape for fixing the sealing material along the perforation (dotted line).
Stick the sealing material to the tape for fixing the sealing material.
(Stick so that the sealing material is at the centre of the tape for fixing the sealing material.)
Example) When blocking air outlet 2 or 3

<Sealing material preparation>


Procedure 2
Remove the
release paper.

Release paper

Indoor unit main body

Sealing material

Procedure 1
Cut off.
Precautions

Procedure 3

Tape for fixing the sealing material

Stick the sealing material so that


it is at the centre of the tape for
fixing the sealing material.

When blocking the air outlet 1 , sealing material preparation is not necessary.

Mounting of Decoration Panel

(2) Stick the sealing material that was prepared in (1) to


the air outlet of the indoor unit main body.

The sealing material has a directional


property. Be sure to stick the sealing
material to the tape for fixing the sealing
material so that the printed number of the
outlet to be blocked becomes visible.

Air outlet 1

<Mounting to air outlet>

For safety, be sure to shut off power supply before starting the decoration
panel mounting operation and connecting the connectors for swinging.

Refer to the installation manual attached to the decoration panel.


After mounting the decoration panel, check that no gap is present between the decoration panel and the unit's main body.

Field Setting
When mounting the branch duct chamber, setting the indoor unit main body is required.
After all the engineering work is completed, perform setting together with field setting of
the indoor unit.
Using the field setting mode on the remote control, switch to the setting position number
shown in the table to the right. For the field setting mode, refer to "How to perform field
setting" attached to the remote control.

Branch blow pattern


1-way branching,
3-direction blow

Mode number

1-way branching and 2-way blow


or
2-way branching and 2-way blow

13 or 23

Setting switch number Setting position number


02
1
03

JC : 1P137894D

Detail Information of Options

373

FCQ

EDSG281001

3.14 KDTP55K80 / KDTP55K160 Insulation Kit for High Humidity


KDTP55K80

Dimensions

Unit:mm
Model
AA
KDTP55K80 245
KDTP55K160 287

Top panel insulation (1) (t10) 1


862

AB
157
186

Side panel insulation (1) (t10) 1


7781

AA

144

slit

Top panel insulation (2) (t10) 1


862

slit

AB

AA

574

Side panel insulation (2) (t10) 1


7651

perforation

Side panel insulation (3) (t10) 1


7691
slit
AA

144

Top panel insulation (3) (t10) 1


862

slit
Insulation for decoration panel (t5) 4
900

AA

7721

34

2-hole

Side panel insulation (4) (t10) 1

J : D3K05113

Model
Item
Material
Applicable ambient temperature
Accessories

374

KDTP55K80

KDTP55K160

Polyethylene foam
(with adhesive on the reverse side)
40CDB, RH85%
Insulation for hanger bracket : 4
Installation manual.

Detail Information of Options

EDSG281001

FCQ

Installation
Precautions
This kit can be mounted to an ceiling mounted cassette-type air conditioner <round flow>.
According to the chart below, check the model name of indoor unit, then mount the kit.
This kit cannot be used for the mounting of humidifier and branch duct.

Combination table
Installable indoor unit model name

Model name

KDTP55K80

SkyAir

FCQ(N)71KVEA
FCQ71KVLT

KDTP55K160

SkyAir

FCQ(N)100K/125K/140KVEA
FCQ100K/125K/140KVLT

Parts content

778mm

765mm

3 Side insulator plate (3)

769mm

80 A=245mm
160 A=287mm

Shape

2 Side insulator plate (2)

80 A=245mm
160 A=287mm
Slit

Name

772mm

5 Top insulator plate (1)

80 A=245mm
160 A=287mm

Slit

Number of pieces

4 Side insulator plate (4)

80 A=245mm
160 A=287mm

1 Side insulator plate (1)

Name

6 Top insulator plate (2)

7 Top insulator plate (3)

8 suspension bracket insulator

9 Panel insulator

1
Others

Shape
This manual
Number of pieces

Sticking Procedure

Perform the work on soft cloth to prevent damage to the indoor unit and panel.

<Procedure>
(1) According to the sticking procedure for the side insulator plate, stick the side insulator plates (1 to 4) in sequential
order without leaving any gap in between. (Figure 1)
(When mounting the fresh air intake kit (KDDP55X160), cut off the side insulator plate (2) with a knife along the
perforation. The cut-off insulator is no longer needed.)
(2) Stick the top insulator plates (1 to 3) without leaving any gap in between. Also, stick the top insulator plates without
leaving any gap against the side insulator plates all the way around. (Figure 2)
(3) Hang the product.
(4) Stick the suspension bracket insulator to the suspension bracket together with the washer and bolt. (Figure 3)
(5) Lastly, stick the panel insulator to the backside of the panel. (Figure 4)
3 Side insulator plate (3)

2 Side insulator plate (2)

Slit

6 Top insulator plate (2)

5 Top insulator plate (1)

Top insulator plate (3)

* Fresh air intake kit


When mounting (KDDP55X160), cut off
the insulator along the perforation.
Slit

(Figure 2)
Perforation
Suspension bracket
(4 points)

8
4 Side insulator plate (4)
2

Slit
Sticking reference for
side insulator plate (2)

Suspension bracket insulator

1 Side insulator plate (1)

Sticking reference for


side insulator plate (3)

Suspension bracket
(4 points)

(Figure 3)
9 Panel insulator

At the suspension bracket section,


the slit must be passed through.

At the suspension bracket section,


the slit must be passed through.

1
3
Sticking reference for
side insulator plate (4)

* After hanging the product, stick the


suspension bracket insulator.

Match these corners


before sticking.

Sticking reference for


side insulator plate (1)
4

Sticking procedure for side insulator plate


(Figure 1)

Panel insulator

(Figure 4)

JC : 3P179341C

Detail Information of Options

375

FCQ

EDSG281001

3.15 KRP1H98 Installation Box for Adaptor PCB


Model
Item
Material
Adaptor for wiring

Accessories

KRP1H98
Hot-dip zinc-coated carbon steel sheet
KRP1C63
KRP4AA53
Clamp : 2
Code sticker : 6
Screws for adaptor box cover : 1
Installation manual.
Wire clamp material : 8
Mounting screws : 3
Earth wire (length 1060m) : 1

Dimensions

Unit:mm

Adaptor box

Adaptor box cover

hole

hole

hole

Fixture

hole
hole

hole
hole
hole

J : D3K04202

376

Detail Information of Options

EDSG281001

FCQ

Installation

2P196605A

Detail Information of Options

377

FCQ

EDSG281001

2P196605A

378

Detail Information of Options

EDSG281001

FCQ

2P196606A

Detail Information of Options

379

FCQ

EDSG281001

2P196606A

380

Detail Information of Options

EDSG281001

FCQ

3.16 KRCS01-4B Remote Sensor (for Indoor Temperature)


Model
Item
Length of branch wiring

Appearance

12
ABS resin

Mass (Weight)

kg

0.3

Dimensions

mm

W50 H60 D15

Component parts

Detail Information of Options

KRCS01-4B

Light ivory (with the Daikin logo)

Box material

Recommended for ceiling suspension and


ceiling-embedded types which often result in a
difference between set temperature and actual
temperature.
The sensor for detecting the temperature can
be placed away from the indoor air conditioner.
(Branch wiring is included in the kit.)

KRCS01-1B

Remote sensor.
Extension cord (12m).
Screws: 2
Clamps: 2
Installation manual.

Caution
Select a location for the sensor where it can detect the average temperature.
Avoid the following locations.
1. Locations in direct sunlight.
2. Locations where the outlet air from the air conditioner is directed.
3. Locations close to other heat sources.
4. Locations near doors which might be affected by air coming in.

381

FCQ

EDSG281001

Installation

3K019189B

382

Detail Information of Options

EDSG281001

FCQ

3K019189B

Detail Information of Options

383

FCQ

EDSG281001

3K019189B

384

Detail Information of Options

EDSG281001

FFQ

4. FFQ
4.1

BYFQ60B8W1 Decoration Panel

Installation

4PW42160-1

Detail Information of Options

385

FFQ

386

EDSG281001

Detail Information of Options

EDSG281001

FFQ

Detail Information of Options

387

FFQ

4.2

EDSG281001

KDBH44BA60 Sealing Member of Air Discharge Outlet

Installation

1P109292B

388

Detail Information of Options

EDSG281001

FFQ

1P109292B

Detail Information of Options

389

FFQ

4.3

EDSG281001

KDBQ44BA60A Panel Spacer


Model
Item
Applicable decoration panel

KDBQ44BA60A
BYFQ60B8W1

Exterior

White

Material

Outside frame: Resin


Insulation: Foam polyethylene
Panel spacer. Insulation. Sealant.
Mounting screws. Installation manual.

Component Parts
Mass (Weight)

kg

1.5

Using the panel spacer in areas of the ceiling with


limited space makes it possible to install the air
conditioner.
Hides the gap between the decoration panel and
the ceiling.

Dimensions

Installation
700
654

Unit:mm

654
700

43

Ceiling surface
Panel spacer

4-5 Hole

FFQ + KDBQ44B60A

Unit:mm

3D041038

390

Detail Information of Options

EDSG281001

FFQ

Installation

C : 1P107764C

Detail Information of Options

391

FFQ

EDSG281001

1P107764C

392

Detail Information of Options

EDSG281001

4.4

FFQ

KAFQ441BA60 Replacement Long-life Filter

2P100214B

Detail Information of Options

393

FFQ

4.5

EDSG281001

KDDQ44XA60 Fresh Air Intake Kit (Direct Installation Type)

Installation

2P108307A

394

Detail Information of Options

EDSG281001

FFQ

2P108307A

Detail Information of Options

395

FFQ

4.6

EDSG281001

DTA112BA51 Interface Adaptor for SkyAir Series

Installation

1P107904C

396

Detail Information of Options

EDSG281001

FFQ

1P107904C

Detail Information of Options

397

FFQ

4.7

EDSG281001

KRP1BA101 Installation Box for Adaptor PCB

KRP1BA101

Model

KRP1BA101

Item
Material

Hot-dip zinc-coated carbon steel sheet


KRP1BA57
KRP4AA53

Adaptor for wiring

Clamp material : 3
Mounting screws : 5
Code sticker : 3
Installation manual.

Accessories

Dimensions

Unit:mm

Adaptor box

Adaptor box cover

hole

hole

Insulation

hole
hole

hole

J : D3K05389

398

Detail Information of Options

EDSG281001

FFQ

Installation

1P107687C

Detail Information of Options

399

FFQ

EDSG281001

1P107687C

400

Detail Information of Options

EDSG281001

FFQ

1P133507

Detail Information of Options

401

FFQ

EDSG281001

1P133507

402

Detail Information of Options

EDSG281001

4.8

FFQ

KRCS01-1B Remote Sensor (for Indoor Temperature)


Model
Item
Length of branch wiring

Appearance

12
ABS resin

Mass (Weight)

kg

0.3

Dimensions

mm

W50 H60 D15

Component parts

Detail Information of Options

KRCS01-4B

Light ivory (with the Daikin logo)

Box material

Recommended for ceiling suspension and


ceiling-embedded types which often result in a
difference between set temperature and actual
temperature.
The sensor for detecting the temperature can
be placed away from the indoor air conditioner.
(Branch wiring is included in the kit.)

KRCS01-1B

Remote sensor.
Extension cord (12m).
Screws: 2
Clamps: 2
Installation manual.

Caution
Select a location for the sensor where it can detect the average temperature.
Avoid the following locations.
1. Locations in direct sunlight.
2. Locations where the outlet air from the air conditioner is directed.
3. Locations close to other heat sources.
4. Locations near doors which might be affected by air coming in.

403

FFQ

EDSG281001

Installation

3K019189B

404

Detail Information of Options

EDSG281001

FFQ

3K019189B

Detail Information of Options

405

FFQ

EDSG281001

3K019189B

406

Detail Information of Options

EDSG281001

FHQ

5. FHQ
5.1

KDU50N60VE / KDU50N125VE Drain-up Kit

KDU50N60VE
KDU50N125VE

Model
Item
Drain-up lift

mm

KDU50N125VE
600

VP20 (Ex. dia. 26, Int. dia. 20)

Drain Con. diameter

Single phase 220-240V/220V 50/60Hz


(from Indoor Unit PCB)

Power supply

Pump

KDU50N60VE

Power consumption

13.5/12 (50/60Hz)

Dimensions

Unit:mm

34

167

Drain outlet
(VP20)

149

140

Drain pump
transmission
wiring

Float switch
Drain pump

115

Float switch transmission wiring

173
227
J : D3K03613A

Detail Information of Options

407

FHQ

EDSG281001

Installation

SkyAir

FHQ355060BVVIB

SkyAir

FHQ71100125BVVIB

C : 3K012642A

408

Detail Information of Options

EDSG281001

Preparations before hanging the indoor unit


The drain up kit is installed after the air conditioner main unit is hung. Preparations are required before hanging the air conditioner.

At least 60 mm
(Installation service space)

Mounting space
Select the place for the indoor unit to be installed in consideration of the installation service space.
Note, however, that there must be at least 60 mm of service space to the right of the indoor unit main unit.
See the installation manual attached to the indoor unit for the service space for the indoor unit. Figure 2

Figure 2

(1) Select the position of the pipe outtake, the drain pipe outtake, and the wiring outtake,
and make holes in those positions.
The locations are displayed on the installation pattern paper attached to the indoor unit,
so use the paper pattern. Figure 3
(2) Perform the refrigerant and drain piping work following the installation manual attached
to the indoor unit.
Field drain piping should be as short as possible and with a downward slope (1/25 1/100)
to prevent air pockets. Figure 4
Be sure to insulate all drainpipes which run above the ceiling.
Be sure to fix the field drain pipe to the support brackets in the ceiling. Figure 4
(3) Connect the attached piping 6 and the field refrigerant piping.
For the attached pipes 6 , select the liquid and gas pipes which match the pipe diameters
of the corresponding indoor unit.
When connecting the flare nuts, refer to the installation manual attached to the indoor unit.
(4) Wrap the insulation pipe cover attached to the indoor unit and fasten with the clamp material 5 .
(For both gas and liquid pipes.) Figure 5
(5) Be sure to use adhesive when connecting the attached drain hose 2 and the field drain piping
in the ceiling. Figure 4
(6) Insulate the drain hose using the attached insulation pipe cover(large) 7 . Figure 6

A (Dimension of the main unit)


B (Hanging pitch)
C

210
260

(Hanging pitch)

680 (Dimension of the main unit)

185

85

D
160

FHQ

(Seen from above)

Eyebolt
(4)

Outlet

Model (FHQ~)
3550 type
6071 type
100 type
125 type

Position for connecting


upward drain hose
Position for connecting
upward gas pipe
Position for connecting
upward liquid pipe

A
960
1160

B
920
1120

C
390
490

D
375
475

E
310
410

1400
1590

1360
1550

610
800

595
785

530
720

Figure 3
Ceiling slab
Field refrigerant piping

Support bracket

(Field supplied)

Anti-condensation tubing

7
5

Fasten with adhesive


Local pipes

Top side

Drain hose

Top side
Install the pipe
to the support
bracket, then fix it.

(70)

VP20

Figure 4

Attached piping

(Select the liquid and gas pipes


which match the pipe diameters
of the corresponding indoor unit.)

Figure 5

(For use outside the unit)

Clamp material

VP20

Wrap with vinyl tape to prevent


air from entering through split.

Insulation pipe cover


(Large)
Hose band instead of
clamp material (20)

1~1.5m

Insulating material

Figure 6

Installation Outline
Remove the lid from the top of the indoor unit, and hang the indoor unit main unit before installing the drain up kit in the following manner. Figure 7
1. Complete the electrical wiring following the installation manual attached to the indoor unit.
(Use the wiring through-hole in the top side of the indoor unit to pull the wiring into the indoor unit main unit.)
2. Connect the refrigerant piping to the indoor unit.
(1) Connect the liquid and gas piping to the indoor unit main unit. Figure 8
(2) Wrap the piping connections with the attached insulation pipe cover (medium and small) 7 and fasten either end with the attached clamp material 5 .
Next, put the attached insulating material 8-1 . Wrap gas-side piping with the insulating material attached the indoor unit on top of the insulation pipe cover
wrapped on the piping connections. (For the KDU50M60VE, there are two types of Insulation pipe covers (medium) for the gas pipe connection. Select the one appropriate for the piping size.)
Also, pass the lead wires of swing moter and thermistor through the clamp section of the top lid and fix it so they are as they were before removing the topside through lid.
In order to prevent dust from entering the indoor unit, block any crevices between the lid and the pipes with putty.
Top
plate

Liquid-side attached piping

Clamp material

Clamp part on the top lid

Insulation pipe cover

Liquid-side: small
Gas-side: medium

(1)

(2) For 9.5 : ID 32L100

8-1

Insulating material attached


with the indoor unit main unit

Gas-side attached piping

Only for gas-side


(One piece, 100230, thickness 5mm)

Figure 7

Thermistor lead wires

Cut to fit
the piping

For 12.7 : ID 35L100

Top lid

Swing motor lead wires

Insulating material

one piece, 150200, thickness 5mm


( Gas-side:
Liquid-side: one piece, 30200, thickness 5mm )

Figure 9

Figure 8

3. Mount the drain up kit to the indoor unit.


(1) Remove the screws from the top of the indoor unit, and insert the attached screws 4 temporarily. Next, temporarily put the screwed clamps on either end of the drain up kit,
and tighten the screws. Figure 10
Take out the lead wires of drain pump and the float switch from the back of the drain up kit.
Wire the local wiring as shown in Figure 11 .
From the rear side of the
drain up kit to the control box
Remote control cord
Replace with the
attached screw 4

Temporary
fixing

Screw
(M4 12)

Float switch lead wires (black)


Drain pump lead wires (yellow)

Swing motor lead wires


Thermistor lead wires

Pass under the


installation stay and
to the control box

Field wiring

Temporary
fixing

Approx. 5mm

Top plate

Drain up kit
installation stay

Screw

Float switch lead wires (black)


Drain pump lead wires (yellow)

A
View from direction of arrow A

Screw

Figure 10

Pass over
the installation Local wiring
stay and to the
Remote control cord
control box

Wiring outline

Figure 11

C : 3K012642A

Detail Information of Options

409

FHQ

EDSG281001

(2) Insert the hose band 3 into the external drain hose, firmly insert the drain hose all the way into the drain socket in the drain up kit, and wrap it firmly with the hose band 3
within the area designated by the black tape on the hose end. Figure 12
(3) Put the attached insulating material 8-3 to the external drain hose connector, as shown in Figure 13 .
(4) Connect the indoor unit drain socket and the drain up kit drain socket with the attached drain hose 2 inserting it all the way in, and wrap it firmly with the hose band 3 within
the area designated by the black tape on the hose end. Make sure the hose band connector comes to the top, as in Figure 15 . Figure 14
(5) Insulate the drain hose 2 fixed by the procedure (4) using the attached insulating material 8-2 . Wrap the entire surface over the hose band on the drain hose. Figure 16

8-3
3

Insulating material
Indoor unit main unit
drain socket

Hose band

3
Insert firmly
all the way in.

Connector

Drain up kit
drain socket
Hose band

Tape section (black)

Tape section (black)

Tape section (black)

8-2

Figure 12
Fix making sure that there are no
split between the rising face of the
drain up kit and the insulation.
External drain hose

8-3

Insulating
material

Insert firmly
all the way in.

Drain hose

8-3

Drain hose

Figure 15

External drain hose

Cross section

Figure 14

Insulating
material

Attach facing the


external drain hose
from the drain up kit wall.

Hose band

Hose band

8-2

Wrap the insulating material

Insulating material

Drain hose

Figure 16

Top view

Figure 13

Electrical wiring
Wire the float switch lead wires (black), coming out of the drain up kit, and the drain pump lead wires (yellow) in the manner described below.
(Removing the control box makes wiring work easier.) When doing wiring work, be sure to shut off the power. Figure 17
Refer also to the Electric Wiring Diagram Plate when performing wiring work. (It can be found on the control box lid.)
(1) Remove the control box from the indoor unit.
(2) Connect the drain pump lead wires (yellow) to X25A (the white connector) on the indoor unit PC board assembly.
(3) The connector on the PC board assembly to which the float switch lead wires (black) must be connected differs depending on the indoor unit series (Sky Air or VRV Air Conditioner).
Sky Air : Remove the short circuit connector connected to X15A (a green connector), and connect the float switch lead wires.
VRV Air Conditioner : Remove the short circuit connector connected to X8A (a green connector), and connect the float switch lead wires.
(4) After all the wires are connected, arrange them, pass the float switch lead wire (black) through the clamping material, and secure it together with the drain
pump lead wire (yellow) from above the wiring inside the indoor unit using the included clamping material 5 .
(5) Store and secure any extra lead wire with the included clamping material 5 , so that the lid is not pushed up.
Attach the control box securely.
Float switch lead wires (black)
Remove the
short circuit
connector.

Pass through
the clamp material

Drain pump lead


wires (yellow)

Drain pump lead wires

5 Clamp material

Float switch
laed wires

Sky Air : X15A


VRV Air Conditioner : X8A

X15A (green) or X25A


X8A (green)
(white)

X25A
Pass through the clamp material
Control box

Fixing screws
for the control box lid (2)
Control box lid

Float switch lead wires

Electric wiring
diagram plate

Field wiring
(wiring between units)
Remote control cord

Clamp material

Internal wiring in the


indoor unit

Bind and fix the lead wires from the drain up kit over
the internal wiring in the indoor unit using the attached
clamp material 5 .

Figure 17

Installing the decorative panels and suction grill


Refer to the installation manual for the indoor unit and mount the decorative panels and suction grill firmly following the procedure in the opposite way of removing.

3K012643

410

Detail Information of Options

EDSG281001

FHQ

Test Run Procedure


In order to determine the condition of the drainage, slowly pour approximately 1500 ml of water into the unit from the air outlet. Follow the procedure below to check the drainage. Figure 18
The test run procedure differs depending on the indoor unit series (Sky Air or VRV Air Conditioner), so follow the appropriate procedure below.
Sky Air

VRV Air Conditioner

If the wiring work is complete


Check the drainage while operating in cooling mode.
If the wiring work is not complete
Remove the control box lid, connect a single-phase power supply (50/60Hz 220-240V)
to No. 1 and No. 2 (in the power supply terminal block), and then for safetys sake, close the lid
before turning the power on. Figure 19
Only the drain pump will run automatically for 10 minutes, so during this time make sure water is
draining out.
Once the drain check is complete, remove the power wires and replace the control box lid as it was.

If the wiring work is complete


Check the drainage while operating in cooling mode.
If the wiring work is not complete
Remove the control box lid and connect the remote control and the singie-phase
power source (50/60Hz 220-240V/220V) to the remote control terminal block (P1, P2)
and the power supply terminal block (L, N).
Next, switch the unit to test run mode from the remote control, press the mode
switch button to select fan, and then press the start/stop button to start the indoor
fan and the drain pump. Check the drainage.
Take precaution, because the fan will operate as well.

Do not connect anything to No. 3 in the power supply terminal block (the drain pump will not operate.)
Do not touch the electrical part, emergency switch. The drain check described above can be
performed without moving the emergency switch.

Plastic container
for pouring

Air outlet

Figure 19
Make sure not to splash the water.

Figure 18
Power supply
terminal block
Single phase
power supply

3K012643

Detail Information of Options

411

FHQ

5.2

EDSG281001

KAF501DA56 / KAF501DA80 / KAF501DA112 / KAF501DA160


Replacement Long-life Filter

KAF501DA56 / KAFJ501D56

Dimensions

Unit:mm
A

254.5
260

Model

530

KAF501DA112
KAFJ501D112

430

KAF501DA160
KAFJ501D160

493

11.5

Model
Item

KAF501DA56
KAFJ501D56

D3K3074A

KAF501DA80
KAFJ501D80

KAF501DA112 KAF501DA160
KAFJ501D112 KAFJ501D160

Initial pressure
loss

Pa

10 or less

Final pressure
loss

Pa

59 or less

Average
efficiency

45 (gravity method)

Air flow rate


Life

m3/min

13

I/sec

217

24

32

283

400

533

Mildew-proof resin net

Number of sheets
included
Mass (Weight)

17

2,500 (dust concentration 0.15 mg/m3)

Filter element

412

430

KAF501DA80
KAFJ501D80

20

Caution
Can be water-washed. Can be reused.

KAF501DA56
KAFJ501D56

kg

0.3

0.4

0.5

0.6

Detail Information of Options

EDSG281001

5.3

FHQ

KHFP5MA35 / KHFP5MA63 / KHFP5MA160


L-type Piping Kit (for Upward Direction)

KHFP5MA35

Dimensions

Unit:mm

KHFP5MA35

Piping for Liquid Side


R410A

6.4

Piping for Gas side


R410A

When you install the refrigerant piping in the


ceiling, the piping is required to be bent L-type
in the unit as shown on the right. This L-type
piping kit is developed to facilitate such
installation.

9.5

KHFP5MA63

Piping for Liquid Side


R410A

6.4

Installation
Piping for Gas side

L-type piping kit

R410A

12.7

KHFP5MA160

Piping for liquid side

Piping for gas side

J : D3K03612B

Model
Item
Accessories

Detail Information of Options

KHFP5MA35

KHFP5MA63

KHFP5MA160

Installation for fitting : 1 set


Clamp material : 4 pieces

413

FHQ

5.4

EDSG281001

KRP1CA93 Installation Box for Adaptor PCB


Model
Item
Installation

Interior of unit

Material
Dimensions

Component parts

KRP1CA93

Hot-dip zinc-coated carbon steel sheet


Width

mm

109

Length

mm

124

Depth

mm

38
Installation box. Box cover. Clamp. Screws.
Installation Manual.

Installation

3K09595B

414

Detail Information of Options

EDSG281001

FHQ

3K09595B

Detail Information of Options

415

FHQ

5.5

EDSG281001

KRCS01-1B Remote Sensor (for Indoor Temperature)


Model
Item
Length of branch wiring

Appearance

12
ABS resin

Mass (Weight)

kg

0.3

Dimensions

mm

W50 H60 D15

Component parts

416

KRCS01-4B

Light ivory (with the Daikin logo)

Box material

Recommended for ceiling suspension and


ceiling-embedded types which often result in a
difference between set temperature and actual
temperature.
The sensor for detecting the temperature can
be placed away from the indoor air conditioner.
(Branch wiring is included in the kit.)

KRCS01-1B

Remote sensor.
Extension cord (12m).
Screws: 2
Clamps: 2
Installation manual.

Caution
Select a location for the sensor where it can detect the average temperature.
Avoid the following locations.
1. Locations in direct sunlight.
2. Locations where the outlet air from the air conditioner is directed.
3. Locations close to other heat sources.
4. Locations near doors which might be affected by air coming in.

Detail Information of Options

EDSG281001

FHQ

Installation

3K019189B

Detail Information of Options

417

FHQ

EDSG281001

3K019189B

418

Detail Information of Options

EDSG281001

FHQ

3K019189B

Detail Information of Options

419

FHQ

5.6

EDSG281001

DTA112BA51 Interface Adaptor for SkyAir Series

Installation

1P107904C

420

Detail Information of Options

EDSG281001

FHQ

1P107904C

Detail Information of Options

421

FHQ

5.7

EDSG281001

KJB212AA / KJB311AA Electrical Box with Earth Terminal

Installation

3PA34878C

422

Detail Information of Options

EDSG281001

FHQ

3PA34878C

Detail Information of Options

423

FBQ

EDSG281001

6. FBQ
6.1

KTBJ25K56W / KTBJ25K80W (T) (F) / KTBJ25K160W(T) (F)


Service Access Panel

KTBJ25K80W
Model
Item
Colour

KTBJ25K36W(T)(F)

KTBJ25K80W(T)(F)

KTBJ25K160W(T)(F)

W : White, T : Brown, F : Fresh white

Accessories
Mass (Weight)

KTBJ25K56W(T)(F)

Installation manual.
kg

6.0

6.5

9.0

10.7

Caution
Ceiling joist and ceiling joist support required. (Locally procured.)

Dimensions

Unit:mm

Filter chamber for


rear side air inlet
(optionl accessories)
Air
conditioner

Rear side
of the unit

Ceiling

Model

Colour
White
Brown
Fresh white
White
Brown
Fresh white
White
Brown
Fresh white
White
Brown
Fresh white

JC : D3K1126A

The inspection hatch can be made to look nice with the service access panel.
Thin 10 mm design for the exposed part.

424

Detail Information of Options

EDSG281001

FBQ

Installation

3P225173A

Detail Information of Options

425

FBQ

EDSG281001

3P225173A

426

Detail Information of Options

EDSG281001

6.2

FBQ

KDAJ25K56A / KDAJ25K71A / KDAJ25K140A Air Discharge Adaptor

KDAJ25K56A

Model
Item
Duct connection
diameter

KDAJ25K36A

KDAJ25K56A

2001 port

Material

KDAJ25K71A

2002 port

KDAJ25K140A
2004 port

Hot-dip zinc coated steel sheets. EPS. Insulation.

Accessories
Mass (Weight)

Screws. Installation manual.


kg

1.0

Dimensions

1.5

2.5

3.5

Unit:mm

KDAJ25K36A

KDAJ25K56A
375

200

150
245

332
300

A arrow view

D3K06518

D3K06136

KDAJ25K71A

KDAJ25K140A

D3K06137

D3K06138A

Installation
Suction duct (Field supply)

To air discharge unit

To air discharge unit

Flexible duct with insulation


(Field supply)

Suction grille (Field supply)


Inlet air

Air discharge adaptor

Detail Information of Options

427

FBQ

EDSG281001

Installation

3P012475C

428

Detail Information of Options

EDSG281001

6.3

FBQ

KAF372AA80 / KAF372AA160 / KAF373AA80 / KAF373AA160


High Efficiency Filter
Model
Item
Initial pressure
loss

Pa

Final pressure
loss

Pa

Average
efficiency
(colourimetric
method)

Air flow rate /


1 sheet

m3/min

Life *1

KAF372 KAF373 KAF372 KAF373 KAF372 KAF373 KAF372 KAF373


AA36
AA36
AA56
AA56
AA80
AA80
AA160 AA160
15 or
less

21 or
less

Caution
Cannot be water-washed for reuse.
The filter chamber (for high efficiency filter)
(KDDF37AA36 / KDDF37AA56 / KDDF37AA80
/ KDDF37AA160) is required when the high
efficiency filter will be installed.

54 or
less

35 or
less

54 or
less

38 or
less

56 or
less

65

90

65

90

2,500

1,800

2,500

1,800

98 or less

65

90

65

90

2,500

1,800

2,500

1,800

9.8

Filter element
Number of sheets
included

35 or
less

Non-woven fabric of synthetic fiber


1

Note:
*1. Dust concentration 0.15 mg/m3

Dimensions

Hook and loose


fastener
(black)

Unit:mm

AA

Hook and
loose fastener
(white)

AA
550
355

Applied models
KAF372AA36
KAF373AA36
KAF372AA56, 80, 160
KAF373AA56, 80, 160

Note:
KAF372AA36, KAF373AA36:
Without hook and loose fastener.

Filter connecting figure


Filter element Filter frame
J : D3K06645
J : D3K07003

Detail Information of Options

429

FBQ

6.4

EDSG281001

KDDF37AA80 / KDDF37AA160 High Efficiency Filter Chamber


Model
KDDF37AA36

KDDF37AA56

KDDF37AA80

KDDF37AA160

65% (colourimetric method)

KAF372AA36

KAF372AA56

KAF372AA80

KAF372AA160

90% (colourimetric method)

KAF373AA36

KAF373AA56

KAF373AA80

KAF373AA160

KAF371AA56

KAF371AA80

KAF371AA160

Item
Inserted
filter

High
efficiency
filter

Long life filter

KAF371AA36

Accessories

Mounting screws. Installation manual.

Mass (Weight)

kg

4.5

Dimensions

Unit:mm

oblong hole

Indoor unit side

Service space
(Service cover side)

High efficiency filter

Long life filter

Service cover

burring

Connection duct side


Model

Connection duct
opening

JC : D3K06642C

430

Detail Information of Options

EDSG281001

FBQ

Installation

C : 3K021007

Detail Information of Options

431

FBQ

EDSG281001

3K021007

432

Detail Information of Options

EDSG281001

6.5

FBQ

KAF371AA80 / KAF371AA160 Long Life Filter


Dimensions

Unit:mm
AA

AA
548
353

Applied models
KAF371AA36
KAF371AA56, 80, 160

J : D3K06644
J : D3K07004

Caution
Can be water-washed. Can be reused.
The filter chamber (KDDF37AA36 /
KDDF37AA56 / KDDF37AA80 / KDDF37AA160)
is required when the long life filter will be
installed.

Model
Item

KAF371AA36

KAF371AA56

3 or less

Initial pressure loss

Pa

Final pressure loss

Pa

49 or less

Average efficiency

50 (gravity method)

8 or less

9.8
2,500 (dust concentration 0.15 mg/m3)

Filter element

Mildew-proof resin net (Polypropylene)

Filter frame
Number of sheets included

KAF371AA160

7 or less

Air flow rate / 1 sheet m3/min


Life

Detail Information of Options

KAF371AA80

Polystyrene
1

433

FBQ

6.6

EDSG281001

KAF375AA80 / KAF375AA160 Long Life Filter Chamber Kit


Model
KAF375AA36

Item
Long life filter *1

KAF371AA36

Accessories

Mounting screws. Installation manual.

Mass (Weight)

kg

KAF375AA56

KAF375AA80

KAF375AA160

KAF371AA56

KAF371AA80

KAF371AA160

Protection net. Mounting screws. Installation manual.

4.5

5.5

7.5

Note: *1. The long life filter is packed inside the chamber.

Dimensions
KAF375AA36

Unit:mm

oblong hole

Indoor unit side

Service space
(Service cover side)
Service space
Long life filter

Air inlet side


Service cover

duct connection of the long


( The
life filter chamber is not possible. )

J: D3K07519A

KAF375AA56 / KAF375AA80 / KAF375AA160

oblong hole

Indoor unit side

Service space
(Service cover side)

Long life filter

Service cover

Air inlet side


duct connection of the long
( The
life filter chamber is not possible. )

Model

J: D3K06729A

434

Detail Information of Options

EDSG281001

FBQ

Installation

C : 3K021008

Detail Information of Options

435

FBQ

EDSG281001

3K021008

436

Detail Information of Options

EDSG281001

6.7

FBQ

KRP4A96 Mounting Plate for Adaptor PCB

Dimension

Unit:mm

Model
Item

Main unit mounting


claw (2 places)

Material
Accessories

Hole

KRP4A96
Steel sheet (t=0.8 coating)
Mounting screws (M48) : 2.
Sealing material : 2.
Clamp : 8. Installation manual.

Hole

Main unit mounting hole


hole

Adaptor mounting hole


hole
Clamp material mounting hole (10 places)

J : D3K06565A

Detail Information of Options

437

FBQ

EDSG281001

Installation

2P226887

438

Detail Information of Options

EDSG281001

FBQ

2P226887

Detail Information of Options

439

FBQ

6.8

EDSG281001

KRCS01-4B Remote Sensor (for Indoor Temperature)


Model
Item
Length of branch wiring

Appearance

12
ABS resin

Mass (Weight)

kg

0.3

Dimensions

mm

W50 H60 D15

Component parts

440

KRCS01-4B

Light ivory (with the Daikin logo)

Box material

Recommended for ceiling suspension and


ceiling-embedded types which often result in a
difference between set temperature and actual
temperature.
The sensor for detecting the temperature can
be placed away from the indoor air conditioner.
(Branch wiring is included in the kit.)

KRCS01-1B

Remote sensor.
Extension cord (12m).
Screws: 2
Clamps: 2
Installation manual.

Caution
Select a location for the sensor where it can detect the average temperature.
Avoid the following locations.
1. Locations in direct sunlight.
2. Locations where the outlet air from the air conditioner is directed.
3. Locations close to other heat sources.
4. Locations near doors which might be affected by air coming in.

Detail Information of Options

EDSG281001

FBQ

Installation

3K019189B

Detail Information of Options

441

FBQ

EDSG281001

3K019189B

442

Detail Information of Options

EDSG281001

FBQ

3K019189B

Detail Information of Options

443

FBQ

6.9

EDSG281001

DTA112BA51 Interface Adaptor for SkyAir Series

Installation

1P107904C

444

Detail Information of Options

EDSG281001

FBQ

1P107904C

Detail Information of Options

445

Outdoor Unit

EDSG281001

7. Outdoor Unit
7.1

KPW937A4 Air Direction Adjustment Grille

KPW937A4

Dimensions

Unit:mm

Item

Model

KPW937A4

Material

Resin

Air direction
80

UpperLowerLeftRight

Colour

Ivory white

Accessories

Screws.
Installation manual.

434 (Bolt Pitch)


490

Mass (Weight) kg

1.1

434 (Bolt Pitch)


490

Installation

Louver
KPW937A4 KPW937AA4

Installation manual

Please be sure to read before installation and follow


the instruction carefully when performing installation work.

Before Installation
Checking the parts

Check the following parts


Name

Louver

Installation manual

Shape

With 4 screws
Quantity

1piece

1piece

Installation Procedure
Selection of Installation Location
Use when installing in a location that meets the following conditions.
When installing near the border to a neighbor's house
If exhaust blows directly on passers-by because outdoor unit is installed facing a road.
Changing the fan direction of the outdoor unit to prevent it blowing directly on shrubbery, etc.

Installation of Louver
Installation is possible in the four directions:
upward, downward, rightward, and leftward.
The installation screws are attached to the louver.
First temporarily attach the louver with 4 screws,
then check that the angle is correct, and finally Prepared hole
pitch 435 mm
tighten the screws fully.
Fan partition

Prepared hole
pitch 435 mm
Fan partition
Part A
(see figure below)

CAUTION

1. Install so that a short circuit is prevented.


2. For the use in snowy regions, avoid installation
with the air outlet facing upward. Install so that
the air outlet faces leftward, rightward, or downward.
The prepared hole is in between the grating of the grill.
Snow accumulates in the air outlet of the outdoor
Part A (prepared hole) cross section (the shape of
unit, causing malfunction of the main body of the
either a or b)
outdoor unit.
a) Grill grating
b) Grill grating
3. Be advised that if the fan direction is up,
dead leaves and other foreign matter
Prepared hole
Prepared hole
easily accumulates in the exhaust vent.
4P104499A

446

Detail Information of Options

EDSG281001

7.2

Outdoor Unit

KPW945A4 Air Direction Adjustment Grille

KPW945A4

Dimensions

Unit:mm

Item

Model

KPW945A4

Material

549
452
(Bolt Pitch)

Resin

Air direction

109

UpperLower

Colour

Ivory white
Screws.
Installation manual.

Accessories
484.5
(Bolt Pitch)
552

Mass (Weight) kg

1.5

3
Installation

Air direction louver

Installation manual

Please be sure to read before installation and follow


the instruction carefully when performing installation work.

KPW945A4 KPW945AA4
Before installation
Check the following parts

Name

Louver

Truss tapping screw

Installation manual

1piece

M4x4screws(max.7.5kW class)
M5x4screws(8.0/9.0kW class)

1piece

Shape

Quantity

Installation Procedure
Selection of Installation Location
Use when installing in a location that meets the following conditions.
When installing near the border to a neighbor's house
If exhaust blows directly on passers-by because outdoor unit is installed facing a road.
If exhaust blows directly on vegetation

Space Needed for Installation


A minimum of 100 is needed
between the back of the outdoor
unit and any obstructions
(walls, etc.)

100
han
re t
mo

Installation of Louvers
Caution
Attach the louvers overlapping the standard grill.
Installing the louvers without the grill would allow hands to enter the fan area,
which is dangerous, so be sure to install the standard grill.
When pointing up

When pointing down

1Remove the 4 attachment screws from


the standard grill.

1Remove the 4 attachment screws from


the standard grill.

2Install the louver pointed up.

2Install the louver pointed down.

Overlap the standard grill and


screw both in together.
The attachment screws
are in the louvers.

3Installation complete

Overlap the standard grill and


screw both in together.
The attachment screws
are in the louvers.

3Installation complete

3P089958-2C

Detail Information of Options

447

Outdoor Unit

7.3

EDSG281001

KKP937A4 Drain Plug

KKP937A4

Dimensions

Unit:mm

Component parts
Drain Plug (5pcs.)
Connectable Drain Hose: 16(I.D.)

16.5

36

448

Detail Information of Options

EDSG281001

KKP945A4 Drain Plug


Dimensions

Unit:mm

12

Receiver

14
43

2 44 3

43

Socket (1pc.)
Cap (2pcs.)
Receiver (3pcs.)

12

Cap
14

Socket

Component parts

Connectable Drain Hose: 25(I.D.)

9.5

KKP945A4

3.5

7.4

Outdoor Unit

Installation

3P089958-1B

Detail Information of Options

449

Outdoor Unit

7.5

EDSG281001

KKPJ5F180 Central Drain Plug

KKPJ5F180

Dimensions

Unit:mm
Drain socket

Drain cap

Drain receiver

J : D3K1342A

Model
Item
Connecting drain hose

KKPJ5F180
25 (inside diameter)

Installation

3P066795B

450

Detail Information of Options

EDSG281001

7.6

Outdoor Unit

K-KYZP15C Wire Fixture for Preventing Overturning

K-KYZP15C
Item

Model

Accessories
Mass (Weight) kg

K-KYZP15C
Adjustor pin: 1 piece
Bolt, nut, plain washer: 1 set
Installation manual.
1.0

3
Dimensions

Unit:mm
Wire rope
(SUS2.020m)

nd
Arou
170

30

15

24

Attachment Plate (1)

32

718
Oblong hole 5

Attachment Plate (2)

35
24

32

12 Hole

10

64
29

2-7 Hole

30

12 14 15

65

Gripple

5
J : D3K2523

C : 3K07319A

Detail Information of Options

451

Outdoor Unit

EDSG281001

Installation

C : 3K07319A

452

Detail Information of Options

EDSG281001

7.7

Outdoor Unit

KPT-60B160 Fixture for Preventing Overturning

KPT-60B160

Model
Item
Material

KPT-60B160
Steel plate (t 3.2)

Colour

Ivory white
Screw : 4
Installation manual.

Accessories

Allows the outdoor unit to be secured to the foundation.


Prevents tipping of the outdoor unit due to strong gusts.
Useful for locations where anti-tipping wires (Locally procured) cannot be
installed.

Dimensions

Oblong hole

Unit:mm

Oblong hole

Oblong hole

Oblong hole

J : D3K2759A

Detail Information of Options

453

Outdoor Unit

EDSG281001

Installation

(1) Check that this kit contains the following parts.

Metal fixture 

Metal fixture 

Metal fixture 

Metal fixture 

Screws (4 pieces)

(2) Installation Procedure


1. Install the metal fixtures  ~  to the base legs as shown
below.

2. Remove the screw from the casing and fix the metal fixture to
the casing.

Note:
When you install the metal fixtures ,  and , fix the metal
fixture through the casing by the screws M513 attached.
When you install the metal fixture , fix the metal fixture through
the casing by the screw M513 attached. However, remove the
screw on the casing, if the screw of the casing will contact with
metal fixture.
3. Fix the metal fixtures firmly by the anchor bolts. (The anchor
bolts, nuts and washers should be M12 type sold on the
market.)

J : 3K07893

454

Detail Information of Options

EDSG281001

7.8

Outdoor Unit

KRP58M51 Demand Adaptor

KRP58M51

Installation

C : 3P134153B

Detail Information of Options

455

Outdoor Unit

EDSG281001

RZR71KUV1

C : 3P201377A

456

Detail Information of Options

EDSG281001

Outdoor Unit

C : 3P134153B

Detail Information of Options

457

Outdoor Unit

EDSG281001

RZR100KUV1 / RZR125KUV1 / RZR140KUV1

C : 3P201377A

458

Detail Information of Options

Warning

Daikin Industries, Ltd.s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a
particular country. Prior to purchase, please therefore confirm with your local authorised importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for
use, in the region where the product will be used. This statement does not purport to exclude, restrict
or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
Organization:
DAIKIN INDUSTRIES, LTD.
AIR CONDITIONING MANUFACTURING DIVISION

JMI-0107

Scope of Registration:
THE DESIGN/DEVELOPMENT AND MANUFACTURE OF
COMMERCIAL AIR CONDITIONING, HEATING, COOLING,
REFRIGERATING EQUIPMENT, COMMERCIAL HEATING
EQUIPMENT, RESIDENTIAL AIR CONDITIONING
EQUIPMENT, HEAT RECLAIM VENTILATION, AIR
CLEANING EQUIPMENT, MARINE TYPE CONTAINER
REFRIGERATION UNITS, COMPRESSORS AND VALVES.

Organization:
DAIKIN INDUSTRIES
(THAILAND) LTD.

JQA-1452

Scope of Registration:
THE DESIGN/DEVELOPMENT
AND MANUFACTURE OF AIR
CONDITIONERS AND THE
COMPONENTS INCLUDING
COMPRESSORS USED FOR THEM

All of the Daikin Groups business


facilities and subsidiaries in Japan
are certified under the ISO 14001
international standard for
environment management.

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global_ac/
c All rights reserved

Specifications, designs and other content appearing in this brochure are current as of February 2010 but subject to change without notice.

EDSG281001
Printed in Japan 02/10/001 FS.K

Vous aimerez peut-être aussi