Académique Documents
Professionnel Documents
Culture Documents
Overcurrent Protection
Miscoordination
Voltage Flicker
Sympathetic Tripping
Overvoltages from Solar PV
DG and Power Quality
Ferroresonance
Wind Generation Interconnection
Large Induction Machines
OY/OD Transformer Issues
Load Forecasting
TRVs on Transmission Substation
CBs
But there are many more
4
Stuff Happens
Source: http://s130.photobucket.com/user/case600lp/media/wrecks/powerlines.jpg.html
2015 Electric Power Research Institute, Inc. All rights reserved.
Source: https://youtu.be/MPfHdzq4cSY
2015 Electric Power Research Institute, Inc. All rights reserved.
Source: https://youtu.be/MPfHdzq4cSY
2015 Electric Power Research Institute, Inc. All rights reserved.
Source: https://youtu.be/MPfHdzq4cSY
10
Source: https://youtu.be/Oc7-trMOVVQ
11
EPRI
EPRI
12
EPRI
R. Dugan
2015 Electric Power Research Institute, Inc. All rights reserved.
13
Critters
14
Birds
Roger Dugan
Roger Dugan
15
Roger Dugan
16
17
18
PQ
19
Phase-to-Phase
Vab
Vbc
0.58
1.00
0.58
0.58
1.00
0.33
0.33
Phase-to-Neutral
Vca
Van
Vbn
Vcn
0.00
1.00
1.00
0.58
0.33
0.88
0.88
0.88
0.88
----
0.88
0.88
0.58
----
Phasor Diagram
----
0.58
1.00
o
150
b
19
20
150
100
50
0
-50
-100
-150
Fe br u ar y 2 0, 1 99 4 at 12 :5 2:52 PQ N od e Lo c al
Fe br u ar y 2 0, 1 99 4 at 12 :5 2:52 PQ N od e Lo c al 32 96
Tr igg er Ph as e A C ur r e nt
R MS Va r ia tion
250
Min 2 .3 0 2
D u r a tio n
200
Av e 1 3 7 .4
0 .6 3 3 Se c
150
Ma x2 2 8 .2
Min 0 .1 6 6
100
R e f C y c le
Av e 7 5 .5 0
50
43760
Ma x1 3 8 .8
0
R
e
f
C
y
c
le
0
0.25 0.5 0.75
1
1.25 1.5 1.75
2
0.5 0.75
1
1.25 1.5 1.75
2
43760
Time (S econds)
Time (S econds)
Amps
% Vol ts
140
120
100
80
60
40
20
0
% Vol ts
32 96
Ph as e A Vo ltag e
R MS Va r ia tion
0.25
Amps
25
50
75
100 125
Time (mS econds)
150
175
200
25
50
75
100 125
Time (mS econds)
150
175
200
BMI/Ele c tr o te k
BMI/Ele c tr o te k
150
100
50
0
-50
-100
-150
20
10
21
21
22
ITI Curve
22
11
Transient Overvoltages
Lightning and Switching Transients
GROUNDED
STRUCTURE
PRIMARY
PHASE
SECONDARY
PHASE
ARRESTER
PRIMARY
GROUND
SECONDARY GROUND
24
12
25
Lightning Research by Phil Barker and Tom Short for National Grid and LILCO
26
13
27
Lightning Research by Phil Barker and Tom Short for National Grid and LILCO
28
14
Lightning Research by Phil Barker and Tom Short for National Grid and LILCO
2015 Electric Power Research Institute, Inc. All rights reserved.
29
Lightning
Lightning transients are caused by the injection of current impulses
into the system
High frequency, high magnitude transients can propagate on the
system and into customer facilities
Time (uSec)
Current
(kA)
30
15
ResistanceGraded
Gap
Structure
SiC
ZnO
ZnO
MOV
SiC
(a)
Gapped
Silicon
Carbide
Gapped MOV
(b)
Gapless
MOV
(c)
Gapped
MOV
31
Shielding
SHIELDING AT
THE SUBSTATION
SHIELDING
SPANS WITH
HIGH EXPOSURE
32
16
Line Arresters
---
---
33
34
17
SERVICE CABLE
VOLTAGE DROP
LIGHTNING
STROKE
DISCHARGED
THROUGH
PRIMARY
ARRESTER
CURRENT SPLITS
BETWEEN UTILITY AND
CUSTOMER
UTILITY GROUND
CUSTOMER
GROUND
The current divides according to the ratio of the utility and customer grounds.
The voltage induced in the service cable may appear at the load causing insulation
failure.
If current can flow in secondary phases, transformer failure may occur.
35
Roger Dugan
36
18
37
PRIMARY
ARRESTER
ARRESTERS ON
TRANSFORMER
SERVICE
ENTRANCE
HEAVY-DUTY
ARRESTERS IN
SERVICE
ENTRANCE
INTERLACED
WINDINGS AID
SURVIVAL
INDIVIDUAL LOADS
3-MODE TVSS
B
W
G
BOND SIGNAL GROUND
TO POWER GROUND
38
19
Well-Protected Transformer
Courtesy of
Cooper Power
Systems
2015 Electric Power Research Institute, Inc. All rights reserved.
39
SURGE
CURRENT
+ L di/dt -
LOAD
SOURCE
Clamping devices
(MOVs, gas tubes, capacitors, etc.)
40
20
41
+
-
+
+
-
+
-
+
-
PRIMARY ARRESTER
ALLOWS
350 - 400 V TO
APPEAR ON
120-V SECONDARY
FOR TOV CASES
21
OPEN-POINT
ARRESTER
PADMOUNT
TRANSFORMER
43
Voltages On Cable
VOLTAGE
40.00 kV/div
OPEN POINT
TIME
0.500 microsec/div
44
22
INCOMING
SURGE
UD CABLE
RISER POLE
ARRESTER
45
23
MONITOR
LOCATION
Phase A Voltage
SWITCHED
CAPACITOR
Phase A Current
Wave Fault
Wave Fault
150
400
300
200
Volts. %
100
Amps
100
0
-100
-200
-300
50
0
-50
-100
-150
-400
0
10
20
30
40
50
60
70
10
Time (ms)
20
30
40
Time, ms
50
60
70
47
Source
Service
Transformer
L1
Feeder
L2
C1
6.0 MVAR
2000
C2
Energy (J)
Substation
VC1
Load
L2
4.5 MVAR
1000
C2
L1
1500
500
VC2
C1
2500
1.2 MVAR
0
100
200
300
400
500
Low Voltage Capacitor Size (kVAR)
3.0 MVAR
2.4 MVAR
1.8 MVAR
600
Arrester Energy
Switching frequency
f1 =
Natural frequency of
customer resonant circuit f2 =
Voltage magnifaction
1
2p L1 C1
1
2p L2C2
f f
1
2
48
24
Switching transient
49
P ha se A
The Result:
Dont do
this !!
V o lt a g e ( V p u )
-1
-2
0
200
400
T im e ( m s )
600
800
50
25
THE GRID
LOAD
GEN
2015 Electric Power Research Institute, Inc. All rights reserved.
52
26
LOAD
GEN
53
Wind Turbines
Wind and PV fastest growing
renewable energy sector
1000 2000 MW installed each year
in U.S.A.
Cost is nearly competitive with fossil
fuel generation
Cornerstone of Green Power
programs
Generators:
Simple induction
Scalar controlled induction
Vector controlled induction
Alternators w/ inverters
Roger Dugan
54
27
Photovoltaics
Favored by many
environmentalists
Fastest growing?
Very costly but number of
applications is rapidly growing
Generates dc
Inverter interface to utility
Utility interactive mode
Sizes:
Residential: 2-6 kW
Commercial: 500 kW 5 MW
55
56
28
57
Sustained Interruptions
Much of presently installed DG was installed as backup
generation.
Recip engine gensets most common in this application
Many DG installations will operate better while paralleled
with the utility
Not all DG can be paralleled without great expense
Some DG not capable of serving load by itself (e.g. PV)
Utilities can use DG to cover contingencies
Can allow for deferral of major construction expenses for
a few years.
Reliance could lead to worse reliability depending on
load growth
58
29
Voltage Regulation
May seem that DG could help regulate voltage
Requires very careful engineering
59
Utility
No Help Here
DG May Help
Adjacent
Customer
DG Facility
60
30
Operating Conflicts
Several Things that Could Go Wrong with DG
LV Network Systems
THESE DEVICES
MUST OPERATE
FAULT
SUBSTATION
PRIMARY FEEDERS
TRANSMISSION
SYSTEM
FEEDER BREAKER
OR RECLOSER
LOW-VOLTAGE NETWORK
NETWORK
PROTECTOR
62
31
Reclosing
Reclosing is a very common
practice in North America and
generally improves the
Reliability
Reclose
Interval
Reclosing on DG is often
harmful to the DG
Damage to generator or prime
mover
63
Reduction of Reach
NORMAL ZONE OF
PROTECTION
REDUCED ZONE
OF PROTECTION
UTILITY BREAKER
FAULT
REDUCED SOURCE
CURRENT
CONTRIBUTION
GENERATOR
INFEED
64
32
Sympathetic Tripping
In-feed from the DG causes
unnecessary tripping of feeder
breaker
More of a problem on ground
faults
In the example at left, only
Breaker A should operate. Infeed may cause B to trip also.
A
12.47 kV
Fault
Fixes:
B
2 MW DG
65
Fault
500 kW
DG
66
33
VOLTAGE PROFILE
BEFORE FAULT
VOLTAGE PROFILE
AFTER RECLOSE
67
Net Power
DG
Regulator Switches
Direction to Try to
Control This Way
68
34
DC
AC SWITCH
FILTER
VOLTAGE
SWITCHING
CONTROL
CURRENT
69
277/480V
Xd"=14%
8.8% Third
Harmonic
Usual problem:
Someone wants to operate
existing backup DG in parallel
with the grid
3 x 8.8% = 26%
Third Harmonic
70
35
CABLE CAPACITANCE
Voltage, pu
3
2
1
0
-1
-2
-3
0.000
0.050
0.100
0.150
0.200
Time, sec
71
UT ILIT Y
INTERRUPT ING
DEVICE OPEN
UNGROUNDED
T RANSFORMER
CONNECT ION
72
36
(MULTI-GROUNDED NEUTRAL)
FAULT
MAIN FAULT
CONTRIBUTION
FROM EPS
CONTRIBUTION
FROM DR
TRANSFORMER
73
74
37
(Movie
Demo)
75
Regulator Operations
76
38
77
39
79
Fundamentals of Harmonics
Fundamental power system frequency = f1
Harmonic frequency = n f1 n is integer
Harmonic distortion: typically caused by nonlinear devices
I(t)
Nonlinear Resistor
V(t)
V
I
79
80
Linear loads
Linear loads: those drawing currents in
linear proportion to the applied voltage.
For a resistive load, the impedance is
constant over time as the voltage and
current waveforms are not only
sinusoidal but they are also perfectly in
phase.
For an inductor load, the current lags the
voltage waveform by 90. It is linearly
proportional to the applied voltage.
80
40
81
Non-linear loads
Nonlinear loads: those drawing currents
in nonlinear proportion to the applied
voltage
Current waveshapes are not sinusoidal,
i.e. contain fundamental + harmonic
frequencies
Current waveshapes are periodic, thus
they can be decomposed into a
weighted sum of sinusoids whose
frequencies is an integer multiple of
fundamental frequency of the periodic
waveform to be decomposed
81
82
60 Hz
(h = 1)
i(t) = i(t + T)
+
+
180 Hz
(h = 3)
300 Hz
(h = 5)
+
420 Hz
(h = 7)
+
+
+
540 Hz
(h = 9)
660 Hz
(h = 11)
780 Hz
(h = 13)
1 T
i (t )dt
T 0
2 T
an = i (t ) cos n1tdt
T 0
2 T
bn = i (t ) sin n1tdt
T 0
a0 =
82
41
83
Source: www.schneider-electric.us
84
transistor
inverter
I(t)
Rated Speed
Ih
Amperes
Rated Speed
42% Speed
3
11
13
Harmonic Number, h
Harmonic Number, h
2015 Electric Power Research Institute, Inc. All rights reserved.
84
11
42 13
85
Harmonic
Magnitude
(% Fund)
Parameter
Value
208
5.93
50
2.13
Rated PF
1.0
1.52
0.83
11
0.45
13
1.07
15
0.37
17
0.40
19
0.57
Courtesy of A. Maitra,DC Fast Chargers for PEVs Real and Simulated Results
EPRI PQ and Smart Distribution Conference and Exhibition
San Antonio, Texas, June 5, 2012
85
86
Harmonic
Magnitude
(% Fund)
240
8.92
3.3
0.39
1.0
0.26
0.45
11
0.51
13
0.45
15
0.51
17
0.51
19
0.45
Parameter
Value
Courtesy of A. Maitra,DC Fast Chargers for PEVs Real and Simulated Results
EPRI PQ and Smart Distribution Conference and Exhibition
San Antonio, Texas, June 5, 2012
86
43
87
V1 = I1Z s sin( 1t 1 )
voltage drops
perfect
{V
voltage waveshape
Utility
n
n =3, 5, 7 ,...
Customer
Bus
i(t ) = I1 sin( 1t )
n
n =3, 5, 7 ,...
sin (n1t )
87
88
Utility:
Limit the level of harmonic voltage distortions.
Voltage distortions utility can control the impedance
Recall:
For the same amount of harmonic current injections
Strong system (low impedance system) voltage distortions will be low
Weak system (high impedance system) v. distortions will be high.
88
44
89
90
Resonant frequency
|Z|
200
75
MVA3sc =
= 1500 MVA
0.05
hp =
150
Xc
=
Xs
MVA3sc
rated
Qcap
100
50
1500
hp =
=5
60
200
400
600
800
1000 1200
frequency
1400
1600
1800
2000
90
45
kV
100
75
50
25
0
-25
-50
-75
-100
-125
kA
4.0
3.0
2.0
1.0
0.0
-1.0
-2.0
-3.0
-4.0
0.080
Es
Icap
0.100
0.120
0.140
0.160
0.180
0.200
0.220
...
...
...
Most of the Problems with Harmonics are due to Resonance with Capacitors
91
92
30%
50%
40
=10%
30
No Capacitor
20
10
0
1
13
17
21
Harmonic Number h
92
46
93
Series Resonance
Distribution
Substation Bus
High
Voltage
Distortion
High
Harmonic
Currents
Customer
Pow er Factor
Correction
93
94
parallel
: hr =
resonance
X source
Design away
from this!!
XC
X T X source
XT
XC
Ih
Harmonic Number h
Tuned Frequency
series resonance: hs =
XC
XT
94
47
95
2ND ORDER
HIGH-PASS
3RD ORDER
HIGH-PASS
95
96
96
48
97
97
98
98
49
99
99
CORE
FRINGING FLUX
INTERSECTS CONDUCTOR
ON WIDE EDGE
EDDY CURRENT
PATHS
100
50
TANK
101
And In Conclusion
51
103
104
52
Substation
EV/PHEV
Demand Response
High Penetration PV
Energy Storage
Distributed Controls
2015 Electric Power Research Institute, Inc. All rights reserved.
105
Challenge
Distributed Control Systems
106
53
Challenge
Power Electronics Everywhere
VHV_dc
van
iin
Sa1
Sb1
Sa2
Sb2
Sc1
Transformer +
Rectifier + DC filter
Ldc
C1
Lf
+
vin
+
vab
vab
Sc2
DC/AC Inverter
+ AC filter
Lac
Cdc
Cac
+ iac1
vac1
Cdc
Cac
vac2
+ iac2
n
b
Sa3
Sb3
Sa4
Sb4
C2
Sc3
Sc4
Ldc
iac
+
vac
Lac
107
Challenge
Distributed Voltage and Reactive Power Control
From Varentec
10 - 100kVAr
108
54
109
55