Académique Documents
Professionnel Documents
Culture Documents
Raychem HVBT
TE Connectivity
Clearance Reduction
The table below indicates the clearance
reductions which are possible using HVBT
tape. These are derived from BIL, AC
withstand, DC withstand and discharge
extinction tests. These clearances should
not be adopted without testing by the
user. Sharp electrodes and unusual
geometries may require wider clearances.
Rated
Voltage
(kV)
PhasePhase
(mm)
Round Busbars
12
17.5
24
36
55
70
95
150
Rectangular Busbars
12
17.5
24
36
65
85
115
200
PhaseGround
(mm)
65
85
125
205
120
160
220
320
75
104
150
285
120
160
220
320
Product Performance
Key Product Specifications
Test Method
Requirement
Dielectric strength
Accelerated aging
Tensile strength
Ultimate elongation
ASTM D2671
Procedure C
No cracking after
4 hrs @ -40C
Volume resistivity
Smoke Index
NES 711
Less than 50
VDE 0370
Note: For further product specification information see Raychem PPS 3010/33. The above
information refers to backing material only.
IEC
Application
Recommended
Product
IEEE
Applications
HVBT Length
Needed/meter
of Busbar
IEC
Round
Busbars
Diameter
Application
Recommended
Product
IEEE
Applications
HVBT Length
Needed/meter
of Busbar
1.0 (25)
HVBT-12-A
HVBT-1-R-01
33 (10.0)
0.5 (12)
HVBT-12-A
HVBT-1-R-01
16.5 (5.0)
2.0 (50)
HVBT-14-A
HVBT-2-R-01
25 (7.6)
1.0 (25)
HVBT-14-A
HVBT-2-R-01
16.5 (5.0)
3.0 (75)
HVBT-14-A
HVBT-2-R-01
38 (11.4)
2.0 (50)
HVBT-14-A
HVBT-2-R-01
33 (10.0)
4.0 (100)
HVBT-14-A
HVBT-2-R-01
52 (15.6)
3.0 (75)
HVBT-14-A
HVBT-2-R-01
55 (16.7)
4.0 (100)
HVBT-16-A
HVBT-4-R-01
33 (10.0)
6.0 (150)
HVBT-14-A
HVBT-2-R-01
82 (25.0)
8.0 (200)
HVBT-16-A
HVBT-4-R-01
52 (15.6)
Ordering
Description
Q a W1 a
min. min.
W1 b
min.
W2 b
min.
UOM: Roll of
length, P
HVBT-12-A
25
0.56
0.86
10 meters
HVBT-1-R-01 (8)
.014
.022
0.034
25 feet
.014
.022
0.034
25 feet
.014
.022
0.034
25 feet
0.38
Ordering
Description
Q a W1 a
min. min.
W1 b
min.
W2 b
min.
UOM: Roll of
length, P
HVBT-12-A
50
0.38
0.56
0.86
10 meters
HVBT-2-R-01 (4)
HVBT-12-A
75
0.38
0.56
0.86
10 meters
HVBT-4-R-01 (2)
HVBT-12-A
100
0.38
0.56
0.86
10 meters
+1 (800) 327-6996
Canada:
+1 (905) 475-6222
Mexico:
Technical Report:
EDR-5466
Qualification
report for HVBT
France:
Netherlands:
China:
energy.te.com
2001, 2009-2012 Tyco Electronics Corporation,
a TE Connectivity Ltd. Company. All Rights Reserved.
1-1773455-0 E356 04/2012
Raychem, TE Connectivity and TE connectivity (logo) are
trademarks. Other logos, product and/or company names
might be trademarks of their respective owners.
While TE has made every reasonable effort to ensure the accuracy of the information in this brochure, TE does not guarantee that it is
error-free, nor does TE make any other representation, warranty or guarantee that the information is accurate, correct, reliable or current. TE
reserves the right to make any adjustments to the information contained herein at any time without notice. TE expressly disclaims all implied
warranties regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or fitness for a
particular purpose. The dimensions in this catalog are for reference purposes only and are subject to change without notice. Specifications
are subject to change without notice. Consult TE for the latest dimensions and design specifications.