1.0
INTRODUCTION
Combat hose reels are tested and approved by BS EN671 Part 1 by LPCB
(UK) and most models come with MED
The hose reels equipment and systems are elegantly designed and of rugged
reliability providing optimum performance in fire-fighting.
This manual is applicable to all continuous hose reels system manufactured
and supplied by LINGJACK Engineering Works Pte. Ltd.
2.0
LJS-IOM-105
Page 3 of 12
3.0
4.0
INSTALLATION INSTRUCTION
a) With reference to Code of practice for fire hydrants & hose reel
system in Singapore
The minimum flow rate in a hose reel is at least 0.4 L/s with a jet of at least
10m in length.
For a 4mm and 6mm nozzle, a minimum running pressure of 6 bar and 2 bar
will be required at the entry reel respectively.
Maximum static pressure cannot exceed 8 bar.
LJS-IOM-105
Page 4 of 12
Note: Above flow rate is tested on gunmetal & titanium water way with
COMBAT C18 nozzle. Flow rate are subject to change with different
equipment installed at water inlet i.e. pressure reducing valve. For actual flow
rate, kindly consult LINGJACK engineers for verification.
5.0
6.0
INSTALLATION INSTRUCTION
The recommended anchor bolt to be used
1) Mark hole position on Wall (Has to be levelled)
2) Drill hole into wall (minimum depth 30 to 35mm) and insert wall plug
3) Insert M10 anchor bolt
4) Mount hose reel onto wall. Secure using a washer & nuts
5) Ensure hose reel are levelled (use a level gauge when necessary)
LJS-IOM-105
Page 5 of 12
LJS-IOM-105
Page 6 of 12
LJS-IOM-105
Page 7 of 12
LJS-IOM-105
Page 8 of 12
LJS-IOM-105
Page 9 of 12
LJS-IOM-105
Page 10 of 12
LJS-IOM-105
Page 11 of 12
Clear of obstruction
Easily visible
Operating instruction is legible
Rigidly supported
No corrosion or leakage
If it is not possible to test every hose reel, at least the highest reel on each
rising main should be tested.
Corrective actions must be taken immediately should the inspector found any
deficiency during inspection.
A permanent record of all inspection and maintenance shall be recorded and
kept by the owner/occupant. Records must be readily available when
requested by local authority.
Records should include at least the following information:a) Identification of each rising main
b) Date of inspection
c) Test results
d) Any deficiency or replacement of parts and state if further test
required
e) Date of next inspection