GYPROCK STRATAWALL

INTER-TENANCY WALL SYSTEMS


INSTALLATION GUIDE

System Features

CONTENTS
Introduction

Fire Barrier is created with one or two layers of GYPROCK


SHAFT LINER PANEL in H-studs and tracks.

Applications

Tested fire, acoustic and structural performance.

System Features

Components

35

Design Considerations

68

Unique folding wall track (patent pending), enables fast


installation of fire barrier with little lifting of Shaft Liner
Panels.
Light weight system installed by a single trade.
Systems available for wet areas.

System Selection

9 13

Installation Details

14 17

Junction Details

18 20

Penetration Details

21 23

Health, Safety & Guarantee

24

Contact Information

24

Services may be included in wall cavities.

FIG 1: STRATAWALL FOLDING TRACK AND H-STUDS

INTRODUCTION
The Gyprock StrataWall Systems are designed to provide
separating walls between units in high rise buildings.

Fold line

Gyprock StrataWall is a range of systems characterised by


a fire barrier between the finishing linings. To accommodate
services, cavities are formed by separate framing on one
or both sides. The finishing linings are fixed to the separate
framing, or directly applied to one side of the fire barrier. The
fire barrier allows the finishing linings to be installed as per
normal decorative linings, and to incorporate services and
penetrations.

Restraint tab
IBS rod

25mm GYPROCK
Shaft Liner Panel
H-Stud

The basis of the fire performance is the fire barrier which


consists of one or two layers of 25mm Gyprock Shaft Liner
Panel between purpose designed H-studs. The H-studs are
installed between a unique folding track (patent pending)
at top and bottom. The folding tracks allow the Shaft Liner
Panels to be installed rapidly and with little lifting.

H-Stud

25mm GYPROCK
Shaft Liner Panel

The basis of the acoustic performance is the insulated single


or double cavity. This provides discontinuous construction
for impact isolation.

Restraint tab

Additional systems are available for:

Fold line

Higher acoustic performance.


Security rating.
Impact damage rating.

APPLICATIONS
CSR Gyprock StrataWall systems are designed as nonloadbearing separating walls for Class 2 & 3 buildings
that have concrete floors. Systems are available with
FRL /60/60 to FRL /120/120 and sound ratings to meet
BCA requirements.

GYPROCK STRATAWALL SYSTEMS

COMPONENTS

Gyprock Soundchek
Features

Linings

Designed to provide enhanced


acoustic resistance in wall and
ceiling systems.

Gyprock Shaft Liner Panel

A machine made sheet


composed of a high density
gypsum core encased in a heavy
duty linerboard.

Features
Machine made sheet composed
of a glass fibre reinforced
gypsum core encased in a heavy
duty liner board.

Long edges are recessed to


assist in producing a smooth,
even and continuous surface
once jointed.

25mm thick with a mass of


approximately 19.8kg/m2

13mm thickness.
Manufactured to the
requirements specified in
AS2588 : 1998 Gypsum
Plasterboard.

Applications
Internal walls where a higher sound rating is required.

Applications
Fire rated separating walls and service shafts.

Gyprock Plasterboard CD Recessed Edge


Features

Gyprock Fyrchek
Features

1.5mm recess on face side


allows formation of shallow
channel for joint reinforcement.

Suitable for wall and ceiling


systems where a fire rating is to
be achieved, or where acoustic
performance is required.

Provides smooth. even and


continuous surface once jointed.

Composed of a specially
processed glass fibre reinforced
gypsum core encased in a heavy
duty pink liner board.

10mm and 13mm thickness.


Manufactured to the
requirements specified in
AS2588 : 1998 Gypsum
Plasterboard.

Long edges are recessed for


flush jointing.

Manufactured with CD
technology.

Applications

Applications

Fire rated walls and ceilings.

Internal walls and ceilings.

High performance acoustic rated walls and ceilings.

Gyprock Aquachek
Features

CeminSeal Wallboard

Specially processed
plasterboard.

Features

Both the core and linerboard


facing are treated in manufacture
to withstand the effects of
moisture and high humidity.

CeminSeal Wallboard Sheet


conforms to the requirements
of AS2908.2 : 1992 Cellulosecement products Part 2: Flat
sheets. Type B, Category 3.

Manufactured to the
requirements specified in
American Society for Testing and
Materials C630.

Features an embedded micro


waterblock technology that
prevents water penetrating into
the sheet, repelling water and
providing a more stable sheet.

For use as a wall and ceiling


lining in wet areas and high
moisture areas in residential and
commercial applications.

Long edges are recessed to


enable seamless jointing.

Recessed edges allow flush


jointing to Recessed Edge
Plasterboard.

Applications
Gyprock Aquachek is a suitable substrate for ceramic tiles.
Usage areas include bathrooms, kitchens, laundries. garages and ceiling
applications such as walkways and verandahs.
The Gyprock Aquachek Wet Area Lining System is suitable for walls in
high, medium and low risk level wet areas as defined in AS3740.

In accordance with the Building


Code of Australia, Part 3.7.1.2,
Cemintel fibre cement sheets
can be used wherever noncombustible material is required
by the code.

Applications
Wet area such as bathrooms, laundries and semi-exposed ceilings and
soffits.
Impact resistant walls.

GYPROCK STRATAWALL SYSTEMS

Fire Barrier

TABLE 1: GYPROCK PRODUCT WEIGHTS


Colour shading behind each product approximates the colour of the
product face liner sheets. For detailed sheet sizes and availability,
contact the CSR Gyprock Sales Centre in your region or refer to
www.gyprock.com.au

Gyprock Shaft Liner Panel


One or two layers in H-studs and tracks.

Fasteners

Thickness
mm

Mass
kg/m2

10
13
10
13

6.5
8.5
6.5
8.5

10

6.5

10
13
10
13
13
10
13
13
13
6.5
13
16
13

7.2
13.0
8.0
10.4
10.3
10.4
9.3
10.5
12.1
4.25
10.5
12.5
10.7

16

13.5

Track fasteners:

PERFORATED SHEET

13

10.0

SHAFT LINER PANEL

25

19.8

Must be steel e.g. power actuated concrete nails, flat or


round head expansion anchors.

Cemintel Fibre Cement Product

Thickness
mm

Mass
kg/m2

CeminSeal Wallboard

14.3

Gyprock Lining Products


CD RECESSED EDGE
CD SQUARE EDGE
CD RECESSED EDGE/SQUARE
EDGE
SUPACEIL
SOUNDCHEK
AQUACHEK
IMPACTCHEK
SUPERCHEK
EC08 PARTITION
EC08 FIRE
EC08 IMPACT
FLEXIBLE
FYRCHEK
FYRCHEK

MR

Gyprock Plasterboard Laminating Screw:


40mm x N10. for fixing plasterboard to Shaft Liner
Panels.
Order N

Pack Qty

12215

1000

Drill-point wafer-head screw:


10g x 16mm, for fixing H Stud to tracks.
Order N

Pack Qty

39367

1000

40914

100

Needle-point screw:
6g 18 x 25mm for fixing 13mm plasterboard to
steel studs.
Order N

Pack Qty

10606

1000

Sealants
Gyprock Wet Area Acrylic Sealant:
Order N

Pack Qty

10902

450g tube

Gyprock Fire Mastic:


Order N

Pack Qty

10924

600ml tube

Promat IBS Rod


Used at the top of the fire barrier.
Nom. Size

Order N

Length

22mm

51632

100m

29mm

29243

60m

NOTE: Use 22mm rod for gaps up to 19mm.


Use 29mm rod for gaps up to 26mm.

GYPROCK STRATAWALL SYSTEMS

Steel H-stud

Folding Wall Track

Gyprock StrataWall systems incorporate 25mm or 50mm


H-studs to support the SHAFT LINER PANELS at vertical
joints. They are made from 0.55mm BMT G275 galvanised
steel.

Folding Wall Track is used in the following applications:


To locate and support H-studs and SHAFT LINER
PANELS at the top and the bottom of wall.
Support of SHAFT LINER PANELS at the ends of wall.

Nom. Size

Order N

Length

25mm

39156

3000mm

50mm

74016

3000mm

Nom. Size

Order N

Length

25mm

74014

3000mm

50mm

74015

3000mm

25mm

50mm

34mm

34mm

Restraint tab

Restraint tab

Fold line

Fold line

50

50
Slot for
screw fixing
(where noted)
25

Slot for
screw fixing
(where noted)
50

50

50

Insulation
Insulation Product

Abbreviation used in system tables


11kg/m3

50 GW Partition 11kg

75mm Bradford Glasswool Partition batts, 450 or 600mm 11kg/m3

75 GW Partition 11kg

14kg/m3

50 GW Partition 14kg

75mm Bradford Glasswool Partition batts, 450 or 600mm 14kg/m3

75 GW Partition 14kg

100mm Bradford Glasswool Partition batts, 450 or 600mm 14kg/m3

100 GW Partition 14kg

50mm Bradford Glasswool Partition batts, 450 or 600mm

50mm Bradford Glasswool Partition batts, 450 or 600mm

110mm Bradford Glasswool Partition batts, 600mm

11kg/m3

110 GW Partition 11kg

88mm Bradford SoundScreen R2.5 Wall batts 30kg/m3

88mm RW SoundScreen R2.5

Tontine TSB 2 (50mm) Polyester Insulation

TSB2 Polyester batts

Tontine TSB 3 (65mm) Polyester Insulation

TSB3 Polyester batts

Tontine TSB 5 (85mm) Polyester Insulation

TSB5 Polyester batts

GYPROCK STRATAWALL SYSTEMS

DESIGN
CONSIDERATIONS
Structural Design
Gyprock StrataWall systems are non-loadbearing. The
walls are designed to BCA Specification C1.8 Clause 3.4
Walls Generally, including pressure of 0.25kPa.
Shelf loads and internal wind pressures must be determined
by the project structural engineer and the studs must be
designed to suit. H-studs are not suitable for shelf loading.
Wall tracks are to be fixed to the structure at 600mm maximum
centres. Each fixing is to be designed for a minimum shear
load of 0.75kN and to suit the design pressure.

Fire Resistance
The Gyprock StrataWall systems in this manual have
been tested and assessed by Warrington Fire Research
in accordance with the principles of AS1530.4. They are
suitable for the stated FRL when designed in accordance
with the structural considerations above. Report N21241.

Wallboard & Plasterboard Fixing


Walls may be built to achieve a particular Level of Finish
as defined in AS/NZS2589.1. The Level of Finish specified
can have requirements for frame alignment, jointing,
back-blocking methods and sheet orientation. Cemintel
Wallboard and Gyprock plasterboard may be installed
vertically or horizontally, although for some Levels of Finish,
horizontal sheeting must be used.
In wet areas, Gyprock Aquachek of the same thickness
shall be used in lieu of Gyprock Plasterboard CD. Walls
lined with Gyprock plasterboard or Cemintel Wallboard
may be finished with tiles. For tiles greater than 32kg/m2
or over 6.5mm thickness, specific installation details apply.
Refer to the appropriate installation manual.

Control Joints
Control joints must be installed to allow for structural
movement. Allowance for movement must be made through
the frame, lining and any tiles. Refer to construction details
in this guide.
Control joints must be installed at the following locations:
At all construction joints in the building.
At changes of the structural support system.

Acoustic Performance

At junctions with other building elements.

The acoustic performance of wall systems is expressed


in terms of Rw and Rw+Ctr. They have been assessed by
Norman Disney Young (Report NRP 02267S), and the
ratings refer to expected laboratory performance. Laboratory
testing to AS/NZS1276.1 has been performed by National
Acoustic Laboratories. Reports ATF1910, ATF1912,
ATF-1932.
Some systems rely on cavities that are completely filled with
insulation. Contact CSR Gyprock for performance values
where there is any change to the system specification.
The site performance of the systems may be affected by
sound flanking, the effectiveness of workmanship, and the
inclusion of structural elements and bridging items. The
building designer must pay special attention to airborne and
structural flanking paths to minimise the difference between
laboratory and field performance.

At changes of the lining material.


For walls with plasterboard outer layer at 12m maximum
centres.
For non-tiled internal walls with fibre cement outer layer
at 7.2m maximum centres.
For tiled internal walls with fibre cement outer layer at
4.2m maximum centres.

Fixing & Jointing


Refer to publication GYP544 Gyprock Steel Frame Wall
Systems Installation Guide for details on sheet fixing and
jointing.
Refer to publication GYP546 Gyprock Shaft Systems for
laminated service systems fixing details.

Substitution
Plasterboard linings and barriers, and fibre cement linings,
must be as specified in the system and be supplied by CSR
Gyprock and Fibre Cement. No statement of performance
will be provided by CSR when other product brands are
used.

GYPROCK STRATAWALL SYSTEMS

TABLE 1: MAXIMUM WALL HEIGHT WITH H-STUDS AT 600mm CENTRES


Wall Type

or

Wind Loading
Pservice
kPa

Maximum Wall Height (m)


25H55 H-studs at 600mm ctrs

50H55 H-studs at 600mm ctrs

0.25

3.0

0.25

3.0

or

TABLE 2: MAXIMUM WALL HEIGHT WITH C-STUDS AT 600mm CENTRES WALL SYSTEM FRL /60/60
Wall Type
FRL/60/60

Wind
Loading
Pservice
kPa

0.25

0.35

0.50

Maximum Wall Height (m) with Rondo C-Studs at 600mm centres


Wall Lining
(both sides)

Stud C64

Stud C76

Stud C92

0.50

0.75

1.15

0.55

0.75

0.55

0.75

13mm GYPROCK
plasterboards

2.72

3.13

3.53

3.20

3.30*

3.30*

3.30*

13mm FYRCHEK

2.72

3.13

3.53

3.20

3.58

3.60*

3.60*

6 or 9mm
Cemintel Wallboard

2.72

3.00*

3.00*

3.00*

3.00*

3.00*

3.00*

13mm GYPROCK
plasterboards

2.34

2.80

3.15

2.76

3.20

3.06

3.30*

13mm FYRCHEK

2.34

2.80

3.15

2.76

3.20

3.06

3.60*

6 or 9mm
Cemintel Wallboard

2.34

2.80

3.00*

2.76

3.00*

3.00*

3.00*

13mm GYPROCK
plasterboards

1.95

2.47

2.80

2.32

2.73

2.56

2.96

13mm FYRCHEK

1.95

2.47

2.80

2.32

2.73

2.56

2.96

6 or 9mm
Cemintel Wallboard

1.95

2.47

2.80

2.32

2.73

2.56

2.96

TABLE 3: MAXIMUM WALL HEIGHT WITH C-STUDS AT 600mm CENTRES WALL SYSTEM FRL /90/90
(FRL /120/120 SYSTEMS MUST USE 13mm FYRCHEK BOTH SIDES AND HEIGHTS MARKED * ARE LIMITED TO 3.20m)
Wall Type
FRL /90/90

Wind
Loading
Pservice
kPa

0.25

0.35

0.50

Maximum Wall Height (m) with Rondo C-Studs at 600mm centres


Wall Lining
(both sides)
13mm GYPROCK
plasterboards
13mm FYRCHEK
6 or 9mm
Cemintel Wallboard
13mm GYPROCK
plasterboards
13mm FYRCHEK
6 or 9mm
Cemintel Wallboard
13mm GYPROCK
plasterboards
13mm FYRCHEK
6 or 9mm
Cemintel Wallboard

Stud C64

Stud C76

Stud C92

0.50

0.75

1.15

0.55

0.75

0.55

0.75

2.72

3.13

3.20*

3.20

3.20*

3.20*

3.20*

2.72

3.13

3.30*

3.20

3.30*

3.30*

3.30*

2.72

3.00*

3.00*

3.00*

3.00*

3.00*

3.00*

2.34

2.80

3.15

2.76

3.20

3.06

3.20*

2.34

2.80

3.15

2.76

3.20

3.06

3.30*

2.34

2.80

3.00*

2.76

3.00*

3.00*

3.00*

2.47

2.80

2.32

2.73

2.56

2.96

2.47

2.80

2.32

2.73

2.56

2.96

2.47

2.80

2.32

2.73

2.56

2.96

NOTES for Tables 1, 2 and 3:


Height marked with * are limited by the 50mm H-stud.
Deflection limit is Span/240 to a maximum of 30mm, in accordance
with BCA Specification C1.8.
Refer to table 5 for nogging requirements.
Tabulated heights do not include axial loads (except self weight) or
shelf loading.

Loadings: Pultimate = 0.375 kPa, Pservice = 0.25 kPa.


Pultimate = 0.525 kPa, Pservice = 0.35 kPa.
Pultimate = 0.750 kPa, Pservice = 0.50 kPa.
Walls are not for external applications.
All loadings in accordance with AS1170:2002.
Walls analysed in accordance with AS4600:1996.

GYPROCK STRATAWALL SYSTEMS

TABLE 4: MAXIMUM PERMITTED WALL HEIGHT/


WIDTH FOR LAMINATED SERVICES SYSTEMS. (LOAD
UDL = 0.35 kPa).
Wall Height (maximum)
System N

2400

3000

3600

7200

CSR967S

1200

1200

1200

NA

CSR968S

1200

1200

1200

1200

CSR967SA

2200

2100

2000

NA

CSR968SA

3100

2700

2600

1200

CSR969SA

4200

3200

3000

NA

Wall Width (maximum)

S = Screw ONLY plasterboard fixing


SA = Screw and Adhesive plasterboard fixing
NA = Not Applicable

TABLE 5: MINIMUM NUMBER OF NOGGINGS


Lining Configuration

Wall Height (m)


Rows of Noggings
0.0 3.0
1
Lined One Side
3.0 6.0
2
NOTE: Noggings in accordance with Table 5, are in addition to head
nogging track required in Rondo stud wall systems, and are to be
equally spread over the wall.

FIG 2: HEAD NOGGING DETAIL FOR RONDO


C-STUD WALLS

100mm
max. to
Head
Nogging
Track

Head nogging
track required by
RONDO in C-stud
walls lined one
side. (In addition to
noggings required
in Table 5).

100mm
max. to
first row of
fasteners

GYPROCK STRATAWALL SYSTEMS

SYSTEM SELECTION
StrataWall Single Cavity
Intertenancy Walls Corridors Wet Area Options Narrow Footprint
SYSTEM SPECIFICATION

ACOUSTIC
OPINION
or
TEST

TYPICAL LAYOUT (CSR 222a shown)

Test
ATF 1912

Lining material as per system table laminated to Shaft


Liner Panel.

Test
ATF 19322

2 x 25mm GYPROCK Shaft Liner Panel in H-studs at


600mm maximum centres.
Minimum 12mm gap.

Opinion
RP 02267S

Steel studs at 600mm maximum centres.


Cavity insulation as per system table.

Discontinuous
Construction

Lining material as per system table, fixed to studs.

FRL
Report/Opinion

SYSTEM
N

GAP + STUD DEPTH mm

WALL LININGS

76

100

Rw / Rw+Ctr

CAVITY INFILL (Refer to Components)

CSR 222
/120/120
WFRA
21241

SHAFT LINER PANEL SIDE

(a) Nil

52/44

53/45

1 x 13mm GYPROCK
plasterboard CD.

(b) 75 GW Partition 11kg

56/48

(c) 100 GW Partition 14kg

59/51

56/48

153

177
54/46

STUD SIDE
1 x 13mm GYPROCK
plasterboard CD.

CSR 223
/120/120
WFRA
21241

(d) TSB5 Polyester batts


WALL THICKNESS mm

SHAFT LINER PANEL SIDE

(a) Nil

53/45

1 x 13mm GYPROCK
plasterboard CD.

(b) 75 GW Partition 11kg

58/50

(c) 100 GW Partition 14kg

59/51

58/50

153

177

(a) Nil

53/45

53/45

(b) 75 GW Partition 11kg

58/50

STUD SIDE

(c) 100 GW Partition 14kg

58/50

1 x 6mm CeminSeal
Wallboard.

(d) TSB5 Polyester batts

58/50

146

170
55/47

STUD SIDE

(d) TSB5 Polyester batts

1 x 13mm GYPROCK
SOUNDCHEK.

WALL THICKNESS mm

WET AREA SYSTEMS

CSR 225

SHAFT LINER PANEL SIDE


1 x 13mm GYPROCK
plasterboard CD.

/120/90
WFRA
21241

WALL THICKNESS mm

CSR 226
/120/90
WFRA
21241

SHAFT LINER PANEL SIDE

(a) Nil

54/46

1 x 13mm GYPROCK
plasterboard CD.

(b) 75 GW Partition 11kg

59/51

(c) 100 GW Partition 14kg

60/52

59/51

149

173

STUD SIDE
1 x 9mm CeminSeal
Wallboard.

(d) TSB5 Polyester batts

GYPROCK STRATAWALL SYSTEMS

WALL THICKNESS mm

StrataWall Services Cavity


Intertenancy Walls Additional Services Cavity Medium Footprint
SYSTEM SPECIFICATION

TYPICAL LAYOUT (CSR 230 shown)

Lining material as per system table fixed to furring


channels.

ACOUSTIC
OPINION
or
TEST
Opinion
RP 02267S

Cavity insulation as per system table.

Discontinuous
Construction

Furring channel fixed to all H-studs with Rondo Beta Fix


Clips at 600mm max.vertical centres, in 50mm cavity.
2 x 25mm GYPROCK Shaft Liner Panel in H-studs at
600mm maximum centres.
20mm gap.
Steel studs at 600mm maximum centres.
Cavity insulation as per system table.
Lining material as per system table, fixed to studs.

FRL
Report/Opinion

SYSTEM
N

STUD DEPTH mm
WALL LININGS

CSR 230
/120/120
WFRA
21241

CAVITY INFILL (Refer to Components)


STUD CAVITY
FURRING CAVITY

Rw / Rw+Ctr

(a) 75 GW Partition 11kg

50 GW Partition 11kg

60/50

60/50

1 x 13mm GYPROCK
plasterboard CD.

(b) 100 GW Partition 14kg 50 GW Partition 11kg

61/51

61/51

(c) TSB5 Polyester batts

60/50

60/50

211

239

1 x 13mm GYPROCK
plasterboard CD.

CSR 231

WFRA
21241

92

STUD SIDE

FURRING CHANNEL SIDE

/120/120

64

TSB2 Polyester batts

MINIMUM WALL THICKNESS mm

STUD SIDE

(a) 75 GW Partition 11kg

50 GW Partition 11kg

62/53

62/53

1 x 13mm GYPROCK
SOUNDCHEK.

(b) 100 GW Partition 14kg 50 GW Partition 11kg

62/53

62/53

(c) TSB5 Polyester batts

61/52

62/53

211

239

50 GW Partition 11kg

60/50

60/50

(b) 100 GW Partition 14kg 50 GW Partition 11kg

61/51

61/51

(c) TSB5 Tontine Polyester TSB2 Tontine Polyester 60/50

60/50

FURRING CHANNEL SIDE


1 x 13mm GYPROCK
SOUNDCHEK.

TSB2 Polyester batts

MINIMUM WALL THICKNESS mm

WET AREA SYSTEMS


(a) 75 GW Partition 11kg

CSR 235
STUD SIDE

/120/120
WFRA
21241

1 x 13mm GYPROCK
AQUACHEK.
FURRING CHANNEL SIDE
1 x 13mm GYPROCK
AQUACHEK.

MINIMUM WALL THICKNESS mm

GYPROCK STRATAWALL SYSTEMS

10

211

239

StrataWall Double Cavity


Intertenancy Walls Services Both Sides Wet Area Options High Acoustic Performance
SYSTEM SPECIFICATION

ACOUSTIC
OPINION
or
TEST

TYPICAL LAYOUT (CSR 240a shown)

Lining material as per system table fixed to studs Side 1.

Opinion
RP 02267S

Steel studs at 600mm maximum centres.


Cavity insulation as per system table.

Discontinuous
Construction

20mm gap.
2 x 25mm GYPROCK Shaft Liner Panel in H-studs at
600mm maximum centres.
20mm gap.
Cavity insulation as per system table.
Steel studs at 600mm maximum centres
Lining material as per system table fixed to studs Side 2.

FRL
Report/Opinion

SYSTEM
N

CAVITY INFILL (Refer to Components)

CSR 240
/120/120

SIDE 1 AND 2

64

76

Rw / Rw+Ctr

(a) Nil

58/47

58/47

(b) 75 GW Partition 11kg - both sides

62/53

62/53

63/54

62/53

62/53

245

269

(a) Nil

59/48

60/49

SIDE 1 AND 2

(b) 75 GW Partition 11kg - both sides

64/55

65/56

1 x 13mm GYPROCK
SOUNDCHEK.

(d) TSB5 Polyester - both sides

63/54

63/54

245

269

(a) Nil

58/47

58/47

(b) 75 GW Partition 11kg - both sides

62/53

63/54

(c) 100 GW Partition 14kg - both sides

63/54

62/53

63/54

245

269

(b) 75 GW Partition 11kg - both sides

62/53

62/53

(c) 100 GW Partition 14kg - both sides

63/54

237

261

1 x 13mm GYPROCK
plasterboard CD.

WFRA
21241

STUD DEPTH mm

WALL LININGS

(c) 100 GW Partition 14kg - both sides


(d) TSB5 Polyester - both sides
MINIMUM WALL THICKNESS mm

CSR 241
/120/120
WFRA
21241

MINIMUM WALL THICKNESS mm


WET AREA SYSTEMS

CSR 243
/120/120

SIDE 1 AND 2
1 x 13mm GYPROCK
AQUACHEK.

WFRA
21241

(d) TSB5 Polyester - both sides


MINIMUM WALL THICKNESS mm

CSR 244
/60/60

SIDE 1 AND 2

SF 45743

1 x 9mm CeminSeal
Wallboard.
MINIMUM WALL THICKNESS mm

GYPROCK STRATAWALL SYSTEMS

11

StrataWall Double Cavity (25mm Fire Barrier)


Intertenancy Walls Low Cost Double Cavity 3.0m Maximum Wall Height
SYSTEM SPECIFICATION

TYPICAL LAYOUT (CSR 100 shown)

ACOUSTIC
OPINION
PKA-052

Lining material as per system table.


Steel studs at 600mm maximum centres.

Discontinuous
Construction

Cavity insulation as per system table.


20-40mm separation between frame and GYPROCK
SHAFT LINER PANEL.
25mm GYPROCK SHAFT LINER PANEL between steel
H-studs at 600mm maximum centres.
20-40mm separation between frame and GYPROCK
SHAFT LINER PANEL.
Cavity insulation as per system table.
Steel studs at 600mm maximum centres.
Lining material as per system table.

FRL
Report/Opinion

SYSTEM
N

STUD DEPTH mm
WALL LININGS

CAVITY INFILL (Both Sides)


(Refer to Components)

64

76

Rw / Rw+Ctr

CSR 100
(a) 75 GW Partition 14kg

60/48

61/49

60/60/60

BOTH SIDES

(b) 110 GW Partition 11kg

62/50

62/50

EWFA 45743

2 x 10mm GYPROCK
Plasterboard CD.

(c) 88 RW Soundscreen R2.5

61/49

62/50

257

289

MINIMUM WALL THICKNESS mm

CSR 101
(a) 75 GW Partition 14kg

62/50

62/51

60/60/60

BOTH SIDES

(b) 110 GW Partition 11kg

63/52

63/52

EWFA 45743

2 x 13mm GYPROCK
Plasterboard CD.

(c) 88 RW Soundscreen R2.5

63/51

63/52

269

301

MINIMUM WALL THICKNESS mm

CSR 102
(a) 75 GW Partition 14kg

60/48

61/49

60/60/60

BOTH SIDES

(b) 110 GW Partition 11kg

62/50

62/50

EWFA 45743

1 x 13mm GYPROCK
SOUNDCHEK.

(c) 88 RW Soundscreen R2.5

61/49

62/50

243

275

MINIMUM WALL THICKNESS mm


WET AREA SYSTEMS

CSR 103
BOTH SIDES

(a) 75 GW Partition 11kg

61/49

61/50

60/60/60

1 x 6mm CeminSeal
Wallboard.

(b) 75 GW Partition 14kg

62/50

62/51

EWFA 45743

1 x 10mm GYPROCK
AQUACHEK.

(c) 88 RW Soundscreen R2.5

63/51

63/52

249

281

MINIMUM WALL THICKNESS mm

GYPROCK STRATAWALL SYSTEMS

12

StrataWall Services Systems


Services Systems
SYSTEM SPECIFICATION

TYPICAL LAYOUT

ACOUSTIC
OPINION
or
TEST
RP 02267S

2 x 25mm GYPROCK SHAFT LINER PANEL between steel


H-studs at 600mm maximum centres.
Lining material as per system table laminated to Shaft Liner Panel.

FRL
Report/Opinion

SYSTEM
N

WALL LININGS
FACE SIDE

/90/30

Rw/Rw + Ctr

CAVITY INFILL
(a) Nil

36/33

CSR 248 1 x 13mm GYPROCK Plasterboard


WFRA 21241

WALL THICKNESS mm

CD.

/120/90
CSR 249
WFRA 21241

(a) Nil

FACE SIDE

64
36/33

1 x 13mm GYPROCK FYRCHEK.

WALL THICKNESS mm

64

Steel Frame Laminated Services Systems


SYSTEM SPECIFICATION

TYPICAL LAYOUT

ACOUSTIC
OPINION
or
TEST
PKA-A025

Perimeter framing 25/50 x 50 x 0.7mm BMT steel angle.


3 x GYPROCK FYRCHEK laminated with screws and/or
adhesive.

FRL
Report/Opinion

/90/90
RIR 21898

/120/120
RIR 21898

SYSTEM
N

CSR
967S

WALL LININGS

3 x 13mm GYPROCK FYRCHEK


plasterboard.

CAVITY INFILL

Rw

(a) Nil

35
WALL THICKNESS mm

CSR
968S

3 x 16mm GYPROCK FYRCHEK


plasterboard.

36

(a) Nil
WALL THICKNESS mm

GYPROCK STRATAWALL SYSTEMS

39

13

48

INSTALLATION DETAILS
FIG 3: STRATAWALL INSTALLATION STEPS 1, 2, 3

FIG 5: STRATAWALL INSTALLATION STEPS 6, 7, 8

1
8

Install
Shaft
Liner
Panels

Install stud
frame or
furring
channel as
per system
specifications

2
8
Install wall
linings as per
system
specifications
to outer sides
of the wall
system

3
1

Install
H-Studs to
restraint
tabs in
head and
foot tracks

7
Install
insulation

Install Folding Track to


floor, soffit, and end wall

FIG 4: STRATAWALL INSTALLATION STEPS 4, 5

FIG 6: LAMINATING DETAIL PLASTERBOARD TO


SHAFT LINER PANEL

Install
IBS Rod

600mm StrataWall Module

30mm
100mm

Fold track

1200mm outer layer


of Plasterboard

Fold track

400mm

400mm

GYPROCK STRATAWALL SYSTEMS

14

30mm

100mm

FIG 7: HEAD & BASE DETAIL SINGLE CAVITY


C-STUDS ONE SIDE

FIG 8: HEAD & BASE DETAIL SERVICES CAVITY


C-STUDS ONE SIDE, FURRING CHANNEL ONE SIDE
Concrete slab

Concrete slab

Flexible
sealant

IBS rod

100mm
max. to
head
nogging
track
required
in Rondo
C-stud
walls

15mm
deflection
gap nom.

100mm max. to
first row of lining
fasteners
Folding Wall
Track

Steel studs

Refer to
system table
for wall lining
and insulation

25mm
GYPROCK
SHAFT LINER
PANEL with
steel H-studs at
vertical panel
joints

Gyprock Fire Mastic


to seal all gaps above
folding wall track
where slab is uneven

IBS rod

Gyprock Fire Mastic


to seal all gaps above
folding wall track
where slab is uneven

Flexible
sealant
100mm
max. to
head
nogging
track
required
in Rondo
C-stud
walls

15mm
deflection
gap nom.

100mm
max. to first
row of lining
fasteners

Steel
studs

Screw fix
folding wall
track to all
H-studs
through
slotted holes

Refer to
system table
for wall lining
and
insulation

Rondo Beta
Fix Clip at
600mm max
vertical
centres on
every H-Stud

25mm
GYPROCK
SHAFT
LINER
PANEL with
steel
H-studs at
vertical
panel joints

Furring
channel

25mm
GYPROCK
SHAFT
LINER
PANEL with
steel H-studs
at vertical
panel joints

Steel studs
Refer to
system table
for wall lining
and insulation

25mm
GYPROCK
SHAFT LINER
PANEL with
steel H-studs at
vertical panel
joints

Steel studs

Refer to
system table
for wall lining
and
insulation

Rondo
Beta Fix
Clip
Furring
channel

Laminating
screws
Gyprock Fire
Mastic to seal
all gaps under
steel angle
where slab is
uneven

Folding Wall
Track

Flexible
sealant

Flexible
sealant

Screw fix
folding wall
track to all
H-studs
through
slotted holes

Folding Wall
Track

Flexible
sealant

Flexible
sealant

Concrete slab

Concrete slab

GYPROCK STRATAWALL SYSTEMS

15

Gyprock Fire Mastic


to seal all gaps
under steel angle
where slab is
uneven

FIG 9: HEAD & BASE DETAIL DOUBLE CAVITY


C-STUDS TWO SIDES
Concrete slab

FIG 10: HEAD & BASE DETAIL SINGLE LAYER FIRE


BARRIER C-STUDS TWO SIDES
Concrete slab

Gyprock Fire Mastic to seal all


gaps above folding wall track
where slab is uneven

Flexible
sealant

IBS rod

Gyprock Fire Mastic to seal all


gaps above folding wall track
where slab is uneven

Flexible
sealant

100mm
max. to
head
nogging
track
required
in Rondo
C-stud
walls

10mm
deflection
gap nom.

100mm
max. to
first row
of lining
fasteners

100mm
max. to
head
nogging
track
required
in Rondo
C-stud
walls

15mm
deflection
gap nom.

100mm
max. to
first row
of lining
fasteners

Folding
Wall
Track
Steel
studs

25mm
GYPROCK
SHAFT
LINER
PANEL with
steel
H-studs at
vertical
panel joints

Refer to
system
table for
wall lining
and
insulation

Refer to
system
table for
wall lining
and
insulation

25mm
GYPROCK
SHAFT
LINER
PANEL
with steel
H-studs at
vertical
panel joints

Folding Wall
Track
Steel studs

25mm
GYPROCK
SHAFT
LINER
PANEL with
steel
H-studs at
vertical
panel joints

Refer to
system
table for
wall
lining
and
insulation

25mm
GYPROCK
SHAFT LINER
PANEL with
steel H-studs
at vertical
panel joints

Refer to
system table
for wall lining
and insulation

Folding Wall
Track

Steel
studs
Gyprock
Fire Mastic
to seal all
gaps
under steel
angle
where slab
is uneven

Folding
Wall Track

Flexible
sealant

Flexible
sealant

Gyprock Fire
Mastic to
seal all gaps
under steel
angle where
slab is
uneven

Steel
studs

Flexible
sealant

Flexible
sealant

Concrete slab

Concrete slab

GYPROCK STRATAWALL SYSTEMS

16

TABLE 6: REDUCED FRL FOR HEAD DETAILS


FIG 11 & 12 (I.E. WITHOUT IBS ROD)
System Number
CSR 225
CSR 226
CSR 222
CSR 223
CSR 230
CSR 231
CSR 235

FIG 13: HEAD & BASE DETAIL SERVICES SYSTEM

Head Detail

FRL

FIG 11

/60/60

FIG 11

/90/90

FIG 12

/90/90

FIG 11: ALTERNATIVE HEAD DETAIL SINGLE CAVITY


C-STUDS ONE SIDE (REDUCED FRL)

Flexible
sealant

Concrete
soffit

100mm
max. to
head
nogging
track
required
in Rondo
C-stud
walls

Gyprock Fire Mastic


to seal all gaps above
folding wall track
where slab is uneven

Concrete slab
Gyprock Fire Mastic to
seal all gaps under
folding head track
where slab is uneven
15mm
deflection
gap nom.
Folding wall
track (fold
this side)

IBS
rod

100mm max.
to first row of
laminating
screws

Refer to system
table for wall lining

SHAFT
SIDE

25mm GYPROCK
SHAFT LINER
PANEL with 50mm
H-studs at vertical
panel joints

10mm
deflection
gap nom.

100mm max. to
first row of lining
fasteners

Steel studs

Refer to
system table
for wall lining
and insulation

Folding Wall
Track

Refer to system
table for wall lining

25mm
GYPROCK
SHAFT LINER
PANEL with
steel H-studs at
vertical panel
joints

25mm GYPROCK
SHAFT LINER
PANEL with 50mm
H-studs at vertical
panel joints

SHAFT
SIDE

Laminating screws
Gyprock Fire Mastic
to seal all gaps
under steel angle
where slab is
uneven
Flexible
sealant

FIG 12: ALTERNATIVE HEAD DETAIL SERVICES


CAVITY C-STUDS ONE SIDE, FURRING CHANNEL
ONE SIDE (REDUCED FRL)

Flexible
sealant
100mm
max. to
head
nogging
track
required
in Rondo
C-stud
walls
Steel
studs
Refer to
system table
for wall lining
and
insulation
25mm
GYPROCK
SHAFT
LINER
PANEL with
steel
H-studs at
vertical
panel joints

Concrete
soffit

Concrete slab

Gyprock Fire Mastic


to seal all gaps above
folding wall track
where slab is uneven
10mm
deflection
gap nom.

100mm
max. to first
row of lining
fasteners
Screw fix
folding wall
track to all
H-studs
through
slotted holes
Rondo Beta
Fix Clip at
600mm max
vertical
centres on
every H-Stud
Furring
channel

GYPROCK STRATAWALL SYSTEMS

17

JUNCTION DETAILS
FIG 14: TYPICAL JUNCTION OF STRATAWALL WITH
MASONRY WALL
UNIT 1

FIG 16: CORNER DETAIL FOR STRATAWALL

UNIT 2

H-Stud
Steel studs
Refer to system
table for wall
lining
and insulation

Steel studs

Refer to system
table for wall lining
and insulation

25mm
GYPROCK
SHAFT LINER
PANEL with
steel H-studs at
vertical panel
joints

Gyprock Fire
Mastic to seal all
gaps under steel
angle where slab
is uneven

Folding wall
track

Flexible
Sealant

Flexible
Sealant

25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints and
folding wall track
top and bottom

Laminating
screws

Tape and
set corner

Folding wall
track

Pan head
screws at
600mm
centres

Masonry Wall

Refer to system
table for wall lining
and insulation

External angle
bead and set

FIG 15: TYPICAL JUNCTION OF STRATAWALL


WITH CORRIDOR WALL.

UNIT 1

FIG 17: CORNER DETAIL FOR STRATAWALL

UNIT 2

H-Stud

Refer to system
table for wall lining
and insulation
Tape and
set corner

25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints

GYPROCK
Plasterboard CD

CSR Gyprock
Fire Mastic

Tape and
set wall
joints

Pan head screws at


600mm centres

External angle
bead and set

GYPROCK FYRCHEK
Plasterboard to suit fire and
sound requirement

Plasterboard
screws at 600mm
centres

CORRIDOR

GYPROCK STRATAWALL SYSTEMS

18

25mm GYPROCK SHAFT LINER


PANEL with steel H-studs at
vertical panel joints and folding
wall track top and bottom

FIG 18: JUNCTION OF STRATAWALL WITH


NON-FIRE RATED WALLS

FIG 19: CONTROL JOINT DETAIL (FRL /120/120)

UNIT 2

UNIT 2

Rondo P35
control joint

25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints

H-Stud

25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints

Backing rod

15mm min.
Rondo P35
control joint
Refer to system
table for wall
lining and
insulation

Gyprock Fire
Mastic as
acoustic
sealant

Tape and
set wall
joints

UNIT 1

UNIT 1

FIG 20: HEAD AND JAMB DETAIL FOR TRAFALGAR E-CORE DOOR INSTALLATION (/120/30 FRL)
25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints
Refer to system
table for
plasterboard wall
lining and insulation
Door Closer

Trafalgar door
frame backfilled
to test details
RIR2124104

SIDE ELEVATION VIEW

38mm (nom)
Trafalgar E
core door with
acoustic
sealing to
manuafcturers
detail
Trafalgar door frame
backfilled to test
details RIR2124104

25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints

38mm (nom)
Trafalgar E
core door with
acoustic
sealing to
manuafcturers
detail

Refer to system table for


plasterboard wall lining
and insulation

Refer to system table for


plasterboard wall lining
and insulation

PLAN VIEW

GYPROCK STRATAWALL SYSTEMS

19

Refer to system
table for wall lining
and insulation

FIG 21: TYPICAL DETAIL AT JUNCTION OF STRATAWALL AND ROOF

Bradford
Rockwool

Gyprock ceiling
to system
specifications

Wall track
fixed to studs
Cornice or tape
and set finish

Bradford insulation to system


specifications

Refer to system
table for wall lining
and insulation

FIG 22: TYPICAL DETAIL FOR BALCONY DIVIDING WALL PLAN VIEW
Exterior cladding
system

Framing designed
for site wind loads
Folding wall track

UNIT 1
BALCONY

UNIT 2
BALCONY

25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints
Exterior cladding
system

H-Stud
Exterior cladding
system

Refer to system
table for wall lining
and insulation

UNIT 1
INTERIOR

GYPROCK STRATAWALL SYSTEMS

UNIT 2
INTERIOR

20

PENETRATION DETAILS
FIG 23: PLUMBING SERVICES IN STUD
WALL ONE SIDE (FRL /120/120)

FIG 25: PLUMBING SERVICES IN FURRING CHANNEL


CAVITY (FRL /60/60)

12mm
plywood
fixed to
H-studs for
tap fixings

Gyprock
Silencer
Taps arranged
vertically,
mixer, shower
rose or GPOs

Flexible
sealant

Refer to
system table
for wall lining
and insulation
Flexible
sealant
25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints

25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints

Refer to
system table
for wall lining
and insulation

Rondo
Beta-Fix
clip and
furring
channel

FIG 24: PLUMBING SERVICES IN


FIRE BARRIER SIDE (FRL AS NOTED)

Taps, mixer,
shower rose or
GPOs

FIG 26: PLUMBING OR ELECTRICAL SERVICES IN


STUD WALL TWO SIDES (FRL /90/90)

Gyprock
Silencer

Taps, mixer,
shower rose or
GPOs

NOTE: 200mm
wide strip of
GYPROCK
FYRCHEK fixed at
200mm centres.
(For FRL -/60/60
1 x 16mm
FYRCHEK).
(For FRL -/120/120
1 x 25mm SHAFT
LINER PANEL)

Refer to
system table
for wall lining
and insulation

Taps, mixer,
shower
rose or
GPOs

Flexible
sealant

25mm
GYPROCK
SHAFT LINER
PANEL with
steel H-studs
at vertical
panel joints

Flexible
sealant

25mm
GYPROCK
SHAFT LINER
PANEL with
steel H-studs at
vertical panel
joints
Refer to
system table
for wall lining
and insulation

GYPROCK STRATAWALL SYSTEMS

21

FIG 27: BATHS BACK-TO-BACK IN STUD WALL ONE


SIDE (FRL /90/90)

FIG 29: PVC PIPE THROUGH STRATAWALL


(FRL /120/30)
NOTE: System acoustic performance may be reduced.

25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints

Refer to
system table
for wall lining
and insulation

25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints

Refer to
system table
for wall lining
and insulation

Additional
layer of
GYPROCK
AQUACHEK

3-4mm
Promaseal
sealant
FCW
Promaseal
wall collar

Additional
layer of
GYPROCK
AQUACHEK

100mm
max. PVC
pipe

Bath

Refer to system
table for wall lining
and insulation

Bath

Ceiling

FIG 28: INSTALLATION OF LORIENT LVH-O FIRE


DAMPER (FRL /120/)
NOTE: System acoustic performance may be reduced.
Refer to
system table
for wall lining
and insulation

Spigot to terminate with break


away joint as detailed in AS1882.2
Backing rod
where required

FIG 30: COPPER OR STEEL PIPE THROUGH


STRATAWALL (FRL REFER TO BCA SPEC C3.15)
NOTE: System acoustic performance may be reduced.
25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints
Backing rod

Acoustic
sealant

Gyprock Fire Mastic

25mm GYPROCK
SHAFT LINER
Lorient LVH-O type
PANEL with steel
damper supplied in
H-studs at vertical
Two 35 x 35mm
spigot available from
panel joints
Rondo angles
100mm to 450mm 6 to 12mm perimeter gaps
mechanically fixed to diameter, weight
sealed with Gyprock Fire
studs with N6 Type 5.95kg max.
Mastic, or 12 to 20mm
S drill point screws
perimeter gaps filled with
backing rod and Gyprock
Fire Mastic min. 20mm deep

152mm
max.

Copper or
steel pipe

30mm min
Refer to system
table for wall lining
and insulation

Steel H-studs at
600mm centres

Ceiling

GYPROCK STRATAWALL SYSTEMS

22

FIG 31: GPO/SWITCH INSTALLATION IN FURRING


CHANNEL SIDE WITH PENETRATION THROUGH FIRE
WALL (FRL /120/90)

Furring
channel

Refer to system
table for wall
lining and
insulation

Refer to
system
table for
wall lining
and
insulation

Steel studs
Gyprock Fire
Mastic to seal
penetration
min. 25mm
depth

Standard
GPO or
switch

25mm
GYPROCK
SHAFT LINER
PANEL with
steel H-studs
at vertical
panel joints

Rondo Beta
Fix Clip at
600mm max
vertical
centres on
every H-Stud

FIG 32: CABLE PENETRATION THROUGH FIRE


BARRIER (FRL /120/30)

FIG 33: GPO/SWITCH INSTALLATION IN


STUD WALL (FRL /120/90)
25mm
GYPROCK
SHAFT LINER
PANEL with
steel H-studs
at vertical
panel joints

NOTE: Offset
penetration
minimum of
600mm on
opposite sides
of the wall

Acoustic
rated GPO
or switch

Refer to
system table
for wall lining
and insulation

FIG 34: GPO/SWITCH AND PENETRATION


IN FIRE BARRIER (FRL /120/90)
25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints

25mm GYPROCK
SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints

Gyprock Fire
Mastic to seal
penetration
min. 25mm
depth

Cable, up to
3 x twin flex
NOTE: Offset
penetration
minimum of
600mm on
opposite sides
of the wall

38mm
max.

Standard
GPO or
switch

Gyprock Fire Mastic


30mm min. depth in
Shaft Liner Panel

Refer to system
table for wall lining
and insulation

Refer to system
table for wall lining
and insulation

FIG 35: GPO/SWITCH INSTALLATION IN GYPROCK SILENCER


(FRL /120/90)
H-Stud

Refer to system
table for wall lining
and insulation

SHAFT LINER
PANEL with steel
H-studs at vertical
panel joints

Optional hole
for cable
25mm max.

Standard
GPO or
switch

Gyprock
Silencer

Optional hole
for cable
25mm max.

NOTE: Gyprock Silencer may be vertical


and accommodate multiple services

GYPROCK STRATAWALL SYSTEMS

23

Health & Safety

Contact Details

Information on any known health risks of our products and


how to handle them safely is on their package and/or the
documentation accompanying them.

CSR Gyprock Web Site

Additional information is listed in the Material Safety


Data sheet. To obtain a copy, telephone 1800 807 668.

www.gyprock.com.au
CSR Gyprock Sales Support

Telephone: 13 17 44
Facsimile: 1800 646 364
CSR designLINK Technical Support Service

Warranty
Gyprock products are manufactured for life, with all CSR
products designed to achieve optimal performance when
part of a CSR integrated system.
Gyprock

continues to lead the market with premium


quality products which are the preferred choice of plastering
professionals.
Gyprock

plasterboard products are manufactured to


the Australian Standard AS2588 providing confidence in
quality of product and support. For details on our product
warranty, please log onto www.gyprock.com.au, or contact
us on 1300 306 556.

Telephone: 1800 621 117


Facsimile: 1800 069 904
Email: designlink@csr.com.au
New South Wales and ACT

376 Victoria Street,


Wetherill Park NSW 2164
Queensland

768 Boundary Road,


Coopers Plains QLD 4108
Victoria

277 Whitehall Street,


Yarraville VIC 3013
South Australia

ACTU
UF

FO

D
RE

MAN

Lot 100 Sharp Court,


Mawson Lakes SA 5095

R LIFE

Western Australia

21 Sheffield Road,
Welshpool WA 6106
Tasmania

PO Box 61,
Glenorchy TAS 7010
Northern Territory

Cnr Stuart Hwy & Angliss St,


Berrimah NT 0828

GYP949 February 2012


CSR Gyprock, CSR Building Products A.B.N. 55 008 631 356.
The following are trade marks of CSR Limited and are under license. CSR, Gyprock,
Soundchek, Aquachek, Fyrchek, CeminSeal, Bradford, designLINK.
GYP949.BMS9851.0212

Vous aimerez peut-être aussi