Vous êtes sur la page 1sur 124

XE- M CONTROLLERS USER INTERFACE

The standard user interface configuration of the controller consists of the membrane and the LCD display.
The membrane consists of five command keys (Start, Stop, Load, Unload, and Reset), four navigation
keys (Up, Right, Left and Down), and an Edit mode selection key (Enter). These keys, in conjunction with
the color graphics display and the LED icons, make up the user interface to the compressor.

Figure : X -90M

LED STATUS ICONS


Three LED icons are used to indicate the current status of the control system from a distance and are
located on the upper left side of the user interface.

Icon

Name

Function

OK

Illuminates when no Warnings or Trips are sensed. Can be in a Ready or Not


Ready state.

Alert

Illuminates when an Warning (flashes) or Trip (constant on) is sensed. Can be


in a Ready (Warning) or Not Ready (Trip) state.

Auto

Illuminates when the compressor stops in auto restart.

Table : X -90M LED Status Icons

COMMAND KEYS
These keys command the controller to perform actions as specified in the following table. When any of
these keys are pressed the action below will be initiated and logged in the event log.

Key

Name

Function

---

None

Load

Puts the compressor into the selected mode


of operation. Unit will load if the pressure
conditions are right.

Unload

Puts the compressor into an unloaded state.


Unit will run unloaded.

Reset

Clears Warnings and Trips once the


condition is corrected.

Start

Starts the compressor.

Stop

Stops the compressor. This button should


be pressed instead of the E-Stop for normal
stopping operation.

Enter

Toggles the display between the Navigation


mode and the Edit mode.
e

Table : X -90M Command Keys

The Load and Unload keys are not used on the variable speed compressors.

NAVIGATION KEYS
There are four navigation keys (UP, RIGHT, DOWN and LEFT). While the ENTER key is not considered a
navigation key, it is used in conjunction with the navigation keys to make or confirm a selection.

Figure : X -90Ms Navigation Keys


The navigation keys rollover. Pressing one of the navigation keys will lead the user down a navigation
path. Each time the key is pressed, another step in the path is taken. Once the end of a navigation path is
reached, pressing the key one more time will bring the user back to the beginning of the path. Pressing
the opposite key, will move the user through the navigation path in the opposite direction. Once the
beginning is reached, pressing the opposite key will take the user to the end of the path.

DISPLAY LAYOUT

Figure : X -90Ms Display Layout


Folder Bar:
Title Bar:
Page Content:
Dashboard:

Uses tabs to graphically identify each folder.


Identifies current folder and page (underlined).
Content of the current page.
Displays system status.

FOLDER NAVIGATION & ICONS


To move among the tabbed folders shown on the LCD display, press the RIGHT and LEFT keys. The
navigation rolls over from the last to the first folder and vice-versa.

Folder Name

Icon

Description

Home

System performance and status main information. The first page of this
folder is the default page when the controller first powers up.

Operator Settings

System options and configuration settings.

Events

System events log.

Trip History

Details on the most recent trips.

Graphing

On-board graphing of system data. (Optional for X -145M Only)

Maintenance

Status and notification setup for compressor maintenance items.

General Settings

General settings such as Language, Time, and Units of Measure.

Integral
Sequencing

Inter Module communication status and configuration.

Status

Measurements or status from/of all analog and digital I/O.

Factory Settings

Compressor tuning parameters. Also displays hardware and software


versions.

Table : Folder Bar Icons

PAGE NAVIGATION
Once the desired folder is selected, press the DOWN key to move to the page selection area and then
use the RIGHT and LEFT keys to select the desired page. Use the UP key to get back to the folder tabs.

Icon

Description
Start of the page selection area.
Indicates that there are more pages available by navigating right.
Indicates that there are more pages available by navigating left.
Table : Title Bar Page Icons

ACCESSING PARAMETERS
After the desired page is selected, the pages parameters can be selected by using the DOWN key. The
cursor will move to the next parameter each time the DOWN key is pressed. Use the UP key to go back

to the previous one.


The cursor rolls over, so once the last parameter is selected, pressing the DOWN key will navigate the
cursor to the Folder Bar. If the first parameter is selected, pressing the UP key will move the cursor to the
page selection area.
Once selected, access parameters by pressing the ENTER key. Make changes using the NAVIGATION
keys and then enter the setting by pressing the ENTER key again. After a parameter is accessed,
pressing the ENTER key will enter the current setting into the control program and navigate the cursor
back to the selected parameter on the page.
When the cursor is on a parameter that has an enabled/disabled box, pressing the ENTER key will cause
the setting to toggle.
appears on numeric entry windows (see Figure 5.4 below). Placing the cursor on it and then
This icon
pressing the ENTER key will cancel the entry and any changes that were made.

Figure : Numeric Entry Window

Not all pages have adjustable parameters. Some just have read-only information.

DASHBOARD ICONS
The dashboard is intended to be a quick at-a-glance view of system status. The following table lists
standard dashboard icons and their definition. Note that the color of these icons changes based on the
state set by the application while running.

Name

Icon

Description

Network Control

Network control is enabled.

Service Required

A service reminder is nearing or has expired


(i.e.: an air or oil filter needs to be changed).

Unloaded
or
Loaded

Compressor is in the unloaded state.


Compressor is in the loaded state.
e

Table : X -90Ms Dashboard Icons

Fixed Speed Compressor


HOME FOLDER
PAGE 1 SYSTEM OVERVIEW

This is the factory default display after powering up the system.


Online Pressure Setpoint - indicated in the white box and by the white arrow, which is always left of
center on the gauge. The compressor will load when package discharge pressure falls below this value.
Offline Pressure Setpoint - indicated in the white box and by the white arrow, which is always right of
center on the gauge. The compressor will unload when package discharge pressure rises above this
value.
Package Discharge Pressure - indicated by the large numbers centered below the gauge and by the red
arrow. This is the air pressure that the compressor is supplying to the plant.
Pressure Unit of Measure - indicated below the Package Discharge Pressure. This is selectable from
the GENERAL SETTINGS folder.
Airend Discharge Temperature - indicated by the numbers in the lower left of the display.
Temperature Unit of Measure - indicated to the right of the Airend Discharge Temperature. This is
selectable from the GENERAL SETTINGS folder.
Run Hours - indicate the number of hours the compressor has been running.

The online and offline set points can be selected and modified on this page. All other information
on this page is read only.

PAGE 2 - COUNTERS

Hour Meters - Indicates the hours that: the controller has been powered up, the compressor has been
running, and the compressor has running loaded.
Starts - Indicates the number of times a start is attempted on the compressor.
Date & Time Indicates the current date and time.
SETTINGS folder.

All information on this page is read only.

Adjustable and configurable in the GENERAL

PAGES 3 THRU 4 ANALOG INPUTS

Pressure
Temperature

is indicated by this icon.


is indicated by this icon.

Any sensor that is not installed or is reporting a failure will show an X symbol.

All information on these pages is read only.

The following analog inputs are displayed in this section.

Package Discharge Pressure


Sump Pressure
Airend Discharge Temperature
Injected Coolant Temperature
Aftercooler Discharge Temperature
Separator Pressure Drop
Coolant Filter Pressure Drop
Inlet Vacuum
Aftercooler Discharge Pressure (integrated dryer units only)
Remote Pressure (optional)
Dryer Run Status (Integrated dryer units only)

OPERATOR SETTINGS FOLDER


PAGES 1-2 OPERATOR SETTINGS

The below values are all setpoints


Offline Pressure The compressor will unload when package discharge pressure falls below this value.
Online Pressure The compressor will load when the package discharge pressure rises above this
value
Lead/Lag When this box is checked the compressor is operating as a lead machine. Unchecking the
box causes the machine to run as a lag machine.
Lag Offset If the machine is running as a lag compressor, the lag offset will be subtracted from the
online and offline setpoints.
Mode of Operation Selections are Online/Offline, Modulation/ACS, and Modulation only determines
how the compressor will try to maintain a specific pressure. Modulation will adjust the inlet valve to
maintain a steady pressure.
Condensate Release Time period that determines how long the condensate drain valve will remain
open every cycle.
Condensate Interval Time period that determines how often the condensate drain valve will open.
Stop Delay Time Time period that the machine must run unloaded before the motor is allowed to stop
after a stop command is received.
Starter Time Time period that the compressor needs in order to come up to operating speed after a
start command before being able to produce air.

The parameters on these pages are adjustable any time. The table below shows the range and default
values for the setoints on these screens.

OPERATOR SETTINGS
Offline Pressure
Online Pressure
Lead/Lag
Lag Offset
Mode of Operation*
Condensate Release
Condensate Interval
Stop Delay Time
Star-Delta Time / Start Time

SELECTION

MIN.

MAX.

DEFAULT

STEP

UNIT

----Lead/Lag
--Mode
---------

75
65
--0
--2
90
10
5

Rated+10
Offline-10
--45
--20
270
30
30

Rated+10
Offline-10
Lead
0
On/off line
5
180
10
10

1
1
--1
--1
1
1
1

psi
psi
--psi
--sec
sec
sec
sec

*Please note that Mode of Operation can only be adjusted if the modulation option has been purchased
for the compressor and the Enable Modulation factory setpoint has been turned on.

PAGES 3-5 OPERATOR OPTIONS

The below values are all setpoints


Enable Auto-Restart Enabling this will allow the compressor to stop if it has been running unloaded for
a period of time, and the motor has exceeded its minimum running time.
Auto-Restart Time The time period the compressor must run unloaded before stopping in auto-restart.
Auto-Restart Delay The time period after the package discharge pressure has fallen below the online
setpoint before the compressor can automatically restart
Comm Control Enabling this setpoint allows the compressor to be controlled by a serial or Ethernet
device. This is equivalent to the Sequencer option on older Intellisys controllers.
Enable Remote Start/Stop Enabling this setpoint allows the compressor to be started and stopped
using the switch inputs on the controller.
Enable PORO Enabling this setpoint will allow the compressor to automatically restart after a power
outage has been restored if the compressor was running loaded at the time of the outage.
PORO Time Time after the controller power has been restored and controller has finished booting
before the compressor will perform a PORO start.
Low Ambient Temp Temperature below which the low ambient option will come into effect.
Lead/Lag Cycle Time - Time interval after which the compressor will switch from lead to lag mode or
vice versa.
Scheduled Start Day Day (or days) of the week for which a scheduled start will be performed
Scheduled Start Hour Hour of the day for which a scheduled start will be performed
Scheduled Start Minute Minute of the hour for which a scheduled start will be performed.
Scheduled Stop Day Day (or days) of the week for which a scheduled stop will be performed.

Scheduled Stop Hour Hour of the day for which a scheduled stop will be performed.
Scheduled Stop Minute Minute of the hour for which a scheduled stop will be performed.
Enable High Dust Filter Enabling this when a high dust filter is installed will adjust the change inlet
filter warning and high inlet vacuum trip thresholds to a higher value.
Enable Remote Sensor Enabling this allows the compressor to load and unload based off a sensor
reading installed in a remote location.
Please note that in order to disable Scheduled Start/Stop, the Scheduled Start and Stop days,
hours, and minutes must match exactly.

The parameters immediately below are only adjustable when the compressor is stopped. The table below
shows the range and default values for the setoints on these screens.

OPERATOR OPTIONS

SELECTION

MIN.

MAX.

DEF.

STEP

UNIT

Enable Auto Restart


Auto Restart Time
Auto Restart Delay
Comm Control
Remote Start/Stop
Enable PORO
PORO Time
Low Ambient Temp*
Lead/Lag Cycle Time**
Scheduled Start - Day
Scheduled Start Hour
Scheduled Start Minute
Scheduled Stop - Day
Scheduled Stop Hour
Scheduled Stop Minute
High Dust Filter
Remote Sensor

ON/OFF
----ON/OFF
ON/OFF
ON/OFF
--------------ON/OFF
ON/OFF

--2
0
------10
30
0
Day
0
0
Day
0
0
-----

--60
60
------600
60
750
Day
23
59
Day
23
59
-----

Off
10
0
Off
Off
Off
10
35
0
Sun
0
0
Sun
0
0
Off
Off

--1
1
------1
1
1
1
1
1
1
1
1
-----

--min
sec
------sec
degF
hours
day
Hour
Min
day
Hour
Min
-----

* The low ambient temperature is only adjustable if the low ambient factory set point is on.
** A value of 0 will disable the lead/lag cycle time feature.

Installed
Option
Required
No
No
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No

PAGES 6-7 CALIBRATE SENSORS

Sensor calibration can only take place when the machine is stopped. There should be no pressure on a
sensor when it is calibrated. Calibration only needs to take place after a sensor is replaced, the controller
is replaced, or the operator suspects the sensor reading is in error. Calibrate a sensor by selecting the
checkbox beside the sensor name.
Each of the sensors listed below can be calibrated.

Inlet Vacuum (1AVPT)


Sump Pressure (3APT)
Package Discharge Pressure (4APT)
Coolant Filter Inlet Pressure (5CPT)
Coolant Filter Outlet Pressure (6CPT)
Remote Pressure (10APT) Only on units with the remote sensor option
Interstage Pressure (2APT) Only on 2-stage units
Aftercooler Discharge Pressure (7APT) Only on units with integrated dryer

Please note that if a sensor is currently reading a value that is +/- 10% of its range from zero, the sensor
will not be able to be calibrated and an warning will be logged in the event log. Please make sure the
sensor is being exposed to atmosphere before attempting calibration.

EVENTS FOLDER
PAGES 1 TO A MAX OF 42

The pages in the Events folder document up to the last 250 events that the controller has experienced,
and time stamps each. The events are recorded in sequence, with number one being the newest and
250 being the oldest. When a new event occurs, it becomes number one and all others are shifted up in
number.
The page numbers in the Title Bar are used to scroll through the events, with each page displaying up to
seven. Page one displays events one through six, page two displays seven through twelve, and so on.
The following items will generate an event.

Power On
Power Off
Press the Start Key
Press the Stop Key
Press the Load Key
Press the Unload Key
Starting the compressor remotely
Stopping the compressor remotely
Loading the compressor remotely
Unloading the compressor remotely
Warning
Trip
Start Inhibit

Active Warnings will be highlighted in amber while cleared Warnings will have amber text.
Active Trips will be highlighted in red while cleared Trips will have red text.
Active Start Inhibits will be listed in the Event log, but not highlighted. The display will indicate the
compressor is not ready to start if a start inhibit is active.

Warning Events List


Change Inlet Filter
Will occur if 1AVPT is greater than 0.7 psi vacuum (or 1.3 psi vacuum if the high dust filter option
is enabled) and the unit has been loaded for at least 8 seconds. This condition must exist for 3
seconds before the warning is issued.
Change Coolant Filter
This will occur if the unit has been running loaded for at least 8 seconds, is warmed up, and the
coolant filter pressure drop (5CPT - 6CPT) is greater than 25 psi. This condition must exist for 3
seconds before the warning is issued.
Sensor Failure
This will occur whenever sensors 4ATT, 5DTT, 6DTT, and 7APT are recognized as missing or
broken. The sensor failure message shall follow the following format: SENSOR FAILURE 4ATT.
The 5DTT, 6DTT, and 7APT sensor failures will be shown only when the integrated dryer is
installed (accessed in the factory settings menu). This condition must exist for 3 seconds before
the warning is issued.
Change Separator Element
Will occur if the unit is loaded, the unit is warmed up (the injected coolant temperature is at least
120 degF), the package discharge pressure is at least 90 psi, and the separator pressure drop is
greater than 12 psi. This condition must exist for 3 seconds before the warning is issued.
High Airend Discharge Temperature
Will occur if the unit is running and 2ATT is greater than 221 degF (97% of 228) and the unit is
running. This condition must exist for 3 seconds before the warning is issued.
High Sump Pressure
If the unit is running loaded, has been loaded for at least 8 seconds and the sump pressure is
more than 25 psi above the rated pressure for the compressor. If this warning occurs, the online
and offline pressures will be reduced. For example, a rated pressure of 100 psi would have a
maximum offline pressure of 110 psi. This warning would occur if the sump pressure goes above
125 psi in this example. This condition must exist for 3 seconds before the warning is issued.
Auxiliary 1
This will occur if auxiliary input 1 closes. The contact must be closed for at least 3 seconds
before the warning will occur.
Auxiliary 2
This will occur if auxiliary input 2 closes. The contact must be closed for at least 3 seconds
before the warning will occur.
Service
Service warnings occur when the unit has operated a certain number of hours, based on the total
hours. Service warnings can have multiple levels, depending on the service level selection. A
service level selection of 0 disables service warnings.
Service Level 1
If service level 1 has been selected for the unit, a SERVICE REQUIRED warning will be
issued on hour intervals equal to the service time period set point. This warning can be
reset the same as any other warning.
Service Level 2

If service level 2 has been selected for the unit, the service complete factory set point will
be used to clear a level 2 service warning and reset the service time or date. The service
complete can be reset before a service warning occurs.
The initial SERVICE REQUIRED warning will occur at total hour intervals equal to the
service time period set point. However, 100 hours before this a 100 HOURS TO
SERVICE warning will occur. This warning can be reset the same as any other warning.
One hundred hours later the SERVICE REQUIRED warning will occur. This warning
can be reset the same as any other warning, however this warning will return in 24 hours
if the service complete factory set point has not be set. If the service complete has not
been set, 100 hours later, the ALARM SERVICE REQUIRED warning will be issued.
This warning can only be cleared by the service complete factory set point. Once the
service complete factory set point is set, indicating the service is completed, the time for
the next SERVICE REQUIRED warning will be calculated by adding the service time
period to the total hours value, with the 100 HOURS TO SERVICE warning occurring
100 hours before and the ALARM SERVICE REQUIRED warning occurring 100 hours
after that time.
Communication Failure
This will occur if the unit is the lead compressor in integral sequencing and is unable to
communicate with another unit.
Sensor Failure 10APT Remote Sensor
This will occur if the remote sensor option is on and the remote sensor is recognized as missing
or broken. If this occurs, the unit will automatically start using 4APT for loading and unloading the
compressor. Units equipped with an integrated dryer cannot have a remote pressure sensor.
This condition must exist for 3 seconds before the warning is issued.
High Discharge Pressure
Will occur if the unit is using a remote sensor or is under the control of an external device, such
as an X8I, is loaded, and the discharge pressure (4APT) is greater than the maximum offline
pressure. This condition must exist for 3 seconds before the warning is issued. If this condition
occurs, the compressor will automatically unload. The unit will be available to reload once the
discharge pressure falls to the rated pressure value.
Condensate Drain Error
This will occur if the compressor is running, the package discharge pressure is over 50 psi, and
the condensate drain error contact closes for at least 240 seconds. This warning will be ignored
for 4.5 minutes after starting.
Freeze Warning
This will occur if the evaporator sensor has a value of 687 (about 0.5 C) or below (low temp) while
the dryer is running, on units with the integrated dryer. This is a dryer fault. If this happens, the
compressor will continue to run, but the dryer will stop. The condition must exist for at least 180
seconds before the warning will occur. NOTE: If this warning is reset while the conditions for
running the dryer exist, the dryer can restart. Also the dryer can restart if the evaporator value
rises to 709 (about 5 C). However the warning will still be displayed.
Dryer High Pressure
On units with the integrated dryer, this will occur if the dryer high pressure switch opens while the
dryer is running. This is a dryer fault. If this happens, the compressor will continue to run, but the
dryer will stop. The contact must be open for at least 3 seconds before the warning will occur. If
this warning is reset while the conditions for running the dryer exist, the dryer can restart.
However, this switch is a locking switch. The switch must be reset before the dryer can run.
Resetting the warning on the display does not reset the switch.

Condenser Temperature High


This will occur if the condenser sensor has a value above high temperature threshold while the
dryer is running, on units with the integrated dryer. This is not a dryer fault. If this happens, the
compressor and dryer will continue to run. The condition must exist for at least 180 seconds
before the warning will occur.
Condenser Temperature Low
This will occur if the condenser sensor has a value below the low temperature threshold while the
dryer is running, on units with the integrated dryer. This is not a dryer fault. If this happens, the
compressor and dryer will continue to run. The condition must exist for at least 180 seconds
before the warning will occur.
Change HE Filter
The HE filter is located between the aftercooler discharge and the inlet to the dryer and is only on
units with an integrated dryer. The drop across the HE filter is measured by subtracting the
package discharge pressure from the aftercooler discharge pressure. If the compressor is
running, the measured drop across the HE filter is at or above 10 psi (0.7 bar), the unit is hot
(injected coolant temp above 120 degF), and the package discharge pressure (4APT) is above 90
psi, this warning can occur. The condition must exist for at least 3 seconds before the warning
will occur. This is not a dryer fault. If this happens, the warning will be displayed, but the dryer
will continue to run.

Trip Events List


Low Sump Pressure
Will occur if the unit is running unloaded or loaded and 3APT is less than 13 psi for 15 seconds.
High Airend Discharge Temperature
This will occur if 2ATT is greater than 228 degF and the unit is running.
Check Motor Rotation
This will occur if 3APT is less than 1 psi on a unit, 3 seconds after starting (6 seconds if the unit is
equipped with a soft starter or airend discharge temperature is less than 50 degF). This condition
can be caused by the motor running in reverse. Once correct motor rotation is established, this
trip will not be checked again unless power is removed from the controller.
Main Motor Overload
This will occur if the motor overload relay contact opens. The contact must be open for at least 3
seconds before the trip will occur.
Fan Motor Overload
Will occur if a fan motor overload relay contact opens. The contact must be open for at least 3
seconds before the trip will occur.
Remote Stop Failure
Will occur if the remote start/stop option is enabled, the remote stop button remains open and
either start button is pressed.
Remote Start Failure
Will occur if the remote start/stop option is enabled, the unit is started by the remote start button,
and the button stays closed for 7 seconds after the unit starts.
Sensor Failure
This will occur when a sensor is recognized as missing or broken. The sensors affected by this
trip are 1AVPT, 3APT, 4APT, 5CPT, 6CPT, 2APT (if 2 stage unit), 2CTT, and 2ATT. The sensor

should be displayed along with the sensor failure message. The sensor failure message shall
follow the following format: SENSOR FAILURE 1AVPT.
Emergency Stop
This will occur when the EMERGENCY STOP button is engaged.
High Sump Pressure
This will occur if the compressor is running loaded for at least 8 seconds, and any one of the 3
following conditions exist. (1) The sump pressure is above the rated pressure by 35 psi. (2) The
separator pressure drop is measured to be more than 25 psi and the package discharge pressure
at least equal to the minimum online set point value. (3) The sump pressure is above 165 psi if
the rated pressure is less than 190 psi or the sump pressure is above 220 if the rated pressure is
190 psi.
High Coolant Filter Pressure Drop
This will occur if the unit has been running loaded for at least 8 seconds, is warmed up, already
has a change coolant filter warning, and the coolant filter pressure drop (5CPT - 6CPT) is greater
than 35 psi.
High Inlet Vacuum
This will occur if the unit is running loaded and the inlet vacuum is greater than 1.8 psi. If the unit
has a high dust filter, the trip threshold for inlet vacuum is 2.4 psi.
Unit Too Cold To Start
This will occur if the unit does not have the low ambient option, the airend discharge temperature
(2ATT) is less than 35 deg F, and the operator attempts to start the compressor. This fault can
only occur once a day. Once this fault occurs, the operator can reset it and start the compressor.
This fault will be logged in the trip history to indicate that the unit is being started in low ambient
conditions.
High Interstage Pressure
This will occur if the unit is running and the interstage pressure (2APT) is greater than 75 psi.
This trip will only occur in 2 stage units.
Invalid Calibration
Will occur if the sensor zero value is +/- 10% of its scale. This will only occur when a sensor is
calibrated.

Start Inhibit List


High Airend Discharge Temperature
This will occur if 2ATT is greater than 95% of 228 degF.
High Sump Pressure
This will occur if the sump pressure (3APT) is 25 psi or higher than the rated pressure of the
compressor.

TRIP HISTORY
PAGES 1 TO A MAX OF 4

The pages in the Trips History folder document up to the last 15 trips that the controller has experienced,
and time stamps each. The trips are recorded in sequence, with number one being the newest and 15
being the oldest. When a new trip occurs, it becomes number one and all others are shifted up in number.
The page numbers in the Title Bar are used to scroll through the events, with each page displaying up to
seven. Page one displays events one through five, page two displays six through ten, and so on.
The following items will generate an entry in the trip history.

Trips

Active Trips will be highlighted in red while cleared Trips will have red text.
The trip history also records compressor data at the time of the trip to assist in diagnostics and
troubleshooting. Navigating to the trip entry and hitting the enter button will bring up the trip history dialog
box.

While the dialog box is active, press the left and right keys in order to scroll through the displayed data.
The name of the trip will always be shown in the title bar of the dialog box. Press enter when finished
viewing the data to return to the trip history screen.

MAINTENANCE FOLDER
PAGE 1 FILTER STATUS

This page displays the status of the filters. The filter status will either be OK or Change depending on
the compressors diagnostic readings. If a filter reaches the change status, a warning will be issued and
the service indicator will light up yellow to notify the user.
The following filters are displayed:

Coolant Filter
Separator Element
Inlet Filter

PAGE 2 MAINTENANCE STATUS

This page displays the time until the unit should be serviced. The service meter will deplete as the hours
count down closer to a service appointment. Once the counter reaches the yellow zone, the service

indicator will light up yellow. Once the counter reaches the red zone the service indicator will light up red
and maintenance must be performed.

PAGE 3 MAINTENANCE CONFIGURATION

This page allows the user to set the service interval and to reset the counter after the service has been
performed. The service interval may be set to any value between 1000 and 8000 hours, but must be set
in accordance with the factory maintenance schedule. After maintenance has been performed, the user
can reset the counter by navigating to the Reset button and pressing the enter key.

GENERAL SETTINGS FOLDER


All parameters in the general settings folder are adjustable.

PAGE 1 LANGUAGE SELECTION

Language is selectable from the following 30 selections:


English (default)
Bulgarian
Chinese, simplified
Croatian
Czech
Danish
Dutch
Estonian

Finish
French
German
Greek
Hungarian
Italian
Indonesian
Korean

Latvian
Lithuanian
Maltese
Norwegian
Polish
Portuguese
Romanian
Russian

Slovak
Slovenian
Spanish
Swedish
Thai
Turkish

The controller will display all screens in the selected language and only one language can be selected at
a time.
Each language appears in its native translation.

PAGE 1 UNITS OF MEASURE SETTINGS

Temperature is selectable between F and C.


2

Pressure is selectable between psi, kpa, bar, kg/cm .


Power is selectable between kW and HP

PAGE 3 HOME PAGE SELECTION

Auto Return to Home enables the controller to return the display back to the selected Home Page if
there is no user activity for the Delay Time shown. This is only enabled when an x appears in the
checkbox.
Delay Time determines how many seconds of inactivity it will take before the controller will return to the
Home Page.
Select Home Folder is used to select the Home Folder.
Select Home Page is used to select the Home Page within the selected Home Folder.

PAGE 4 AND 5 TIME & DATE SETTINGS

All items are adjustable.


Hours allows the current hour to be set. The hours format is fixed on 24-hour.
Minutes allows current minutes to be set.
Seconds allows current seconds to be set.
Year allows current year to be set.
Month allows current month to be set.
Day allows current day to be set.
Date Format is selectable between dd/mm/yyyy (default) and mm/dd/yyyy.
Confirm New Time and Date is used to verify that changes to selections are desired. An x must appear
in the checkbox before any changes will take affect.
The controller will continue to display any changes, even when the selections have not been confirmed
and the user exits the page, then returns. Cycling of the power returns all selections to their current
settings.

The controller does not support Daylight Savings Time.

PAGE 6 BACKLIGHT SETTINGS

Backlight Brightness adjusts the brightness of the display.


Enable Backlight Auto-Off enables the controller to shut-off the backlight if there is no user activity for
the delay time shown.
Backlight Auto-Off Delay Time determines how many seconds of inactivity it will take before the
controller will shut-off the backlight.

The backlight will be switched on whenever any of the controllers keys are pressed.

THE START, STOP, LOAD, UNLOAD, RESET, AND ACKNOWLEDGE KEYS ON THE
CONTROLLER REMAIN FUNCTIONAL WHILE THE BACKLIGHT IS SWITCHED OFF. IT IS
RECOMMENDED TO PRESS THE ENTER KEY OR ONE OF THE NAVIGATION KEYS IN
ORDER TO SWITCH THE BACKLIGHT ON.

PAGE 7 - SERIAL PORT ADDRESS SETTINGS

This page allows the user to set up the network addresses for the RS-485 networks the controller is
capable of communicating with.
MODBUS Address Sets the modbus node ID for the controller to communicate with a Modbus capable
device, this can be any value between 1 and 254.
Airbus Address Sets the airbus address that allows the controller to communicate over Integral
Sequencing or an X-Series system controller network.

PAGES 8 THROUGH 11 COM PORT CONFIGURATION

This will most likely be removed from the software

PAGES 12 AND 13 ETHERNET SETTINGS

IP Address Setting When DHCP is not enabled, this setpoint sets the IP address of the controller.
IP Address Actual This will match the IP address setting when DHCP is not enabled. If DHCP is
enabled this will display the address assigned to the controller by the DHCP server.
Default Gateway Setting Setpoint for the default gateway.
Default Gateway Actual Current reading/setting for the default gateway.
Subnet Mask Setting Setpoint for the subnet mask
Subnet Mask Actual Current reading/setting for the subnet mask
MAC Address This is the unique hardware MAC address for the controller. This can not be changed.
Enable DHCP Allow the controller to automatically receive an IP address from the Local Area Network
(LAN)
Accept After editing the desired setpoint navigate to the accept setting and press enter in order for the
values in the setting variables to be confirmed by the controller.
Cancel Discard any changes made to the Ethernet settings.

INTEGRAL SEQUENCING FOLDER

Integral Sequencing allows the compressor to be networked with up to three other compressors (fixed or
variable speed) to maintain a stable system pressure by loading and unloading compressors as needed.
Integral sequencing requires no additional hardware other than a serial two wire connection daisy chained
between all compressors in the system.
Please note that the compressors address in the integral sequencing system is defined by the airbus
address that is set on the general settings folder. Also note that the pressure signal used to determine
when to load or unload another compressor is based on the pressure reading from the compressor at
address 1 in the system.
Integral Sequencing Enabling Integral Sequencing immediately places the compressor under integral
sequence control. The default is disabled. Please make sure all compressors are set up for integral
sequencing before enabling this function.
Unload Pressure Determines the pressure at which a compressor will be unloaded by the system
Load Pressure Determines the pressure at which a compressor will be loaded by the system.
Start Delay Interval Determines the amount of time between loading compressors. This prevents all
compressors from loading at once.
Damping The pressure control Damping setting which is used to tune how quickly the system
responds to pressure deviations. The default is 10 and should not normally be changed.
Tolerance - The pressure control Tolerance setting, which is used to tell the system how to respond to
changes in pressure above and below the load/unload pressures. The default is 3.0 psi and should not
normally be changed.
Number of Compressors Defines how many compressors are in the system.
Sequence Displays the current load/unload order of the system. Each compressor in the system is
assigned a letter, with A being the compressor to load first and unload last, and D being the
compressor to load last and unload first.
Priority Each compressor can be assigned a priority level. Compressors will only rotate positions with
other compressors of the same priority level.

Rotation Interval Determines the time period between sequence rotations.


Time Left Counts down the time until the sequence rotation will occur.
System Pressure Shows the current pressure reading that the system is using for control. This is
typically compressor 1s package discharge pressure reading.

STATUS FOLDER

All information on these pages is read only.

Some values may only be visible when the factory settings password is entered.

PAGES 1 THRU 3 ANALOG INPUTS

Analog Inputs:
The following analog inputs are displayed in this section.

Package Discharge Pressure


Sump Pressure
Airend Discharge Temperature
Injected Coolant Temperature
Aftercooler Discharge Temperature
Separator Pressure Drop
Coolant Filter Pressure Drop
Inlet Vacuum
Aftercooler Discharge Pressure (integrated dryer units only)
Remote Pressure (optional)
Coolant Filter Inlet Pressure (Password Required)
Coolant Filter Outlet Pressure (Password Required)
Interstage Pressure (2-stage units only) (Password Required)
Evaporator (Password Required)
Condenser (Password Required)

PAGE 4 COMPRESSOR DATA

Compressor Data:

Power On Hours
Running Hours
Loaded Hours
Real Time Clock

PAGES 5 & 6 DIGITAL INPUTS

Digital Inputs:
An x in the checkbox beside a digital input indicates that the input is in its TRUE state. For example,
Starter Feedback is TRUE when its input is in the high state, where as, Emergency Stop is TRUE when
its input is at 0Vdc.

Emergency Stop
Main Motor Overload
Fan Motor Overload
Condensate Drain Error
Remote Stop
Remote Start
Remote Lead/Lag
Remote Load Enable
Remote Load/Unload
Auxiliary Input 1
Auxiliary Input 2
Dryer High Pressure

PAGES 7 & 8 DIGITAL OUTPUTS

Digital Outputs:
An x in the checkbox beside a digital output indicates that it is energized.

Starter Contact 1
Starter Contact 2
Fan Starter Contact
1SV
Modulation Solenoid
Condensate Drain
Dryer Run / Fan Run
PORO Horn
Trip Relay
Warning Relay

PAGE 9 ANALOG OUTPUTS

Analog Outputs:
The value for the analog outputs will be in mA.

VSD Blower Output

FACTORY SETTINGS FOLDER


This folder is for IR factory and service personnel. A password must be entered on page one in order to
adjust values in this folder. This folder is used for setting parameters that are specific to that compressor
and displaying software information for the controller.

PAGE 1 PASSWORD

Password:
Provides access to enter a valid password to gain access to password protected parameters. The
password is entered by scrolling down to the password value and pressing the return key.
Password entered:
This checkbox will indicate a valid password has been entered. If this checkbox is blank, a valid
password has not been entered or it has timed out. This is read only.
Password timeout enable:
Checking this box will enable the password time feature.
Password timeout:
This timeout along with the password timeout enable allows the user to set an adjustable amount of time
to require a valid password to be re-entered. Once this timeout is reached re-entry of a valid password is
required. The timeout counter is reset after any button press.

PAGES 2 & 3 FACTORY SETTINGS

These pages are used for setting parameters that are specific to the compressor. All of the factory
settings that are adjustable are listed below. All settings on these pages are password protected.
Rated Pressure (psi 100, 115, 135, 190)
Enable Two Stage (On/Off)
Starter Type (Star-delta, Remote Starter, Soft Starter)
Service Level (0, 1, or 2)
Service Time Period (1000 8000, in increments of 1000 hours)
Enable Modulation (On/Off)
Enable PAC (On/Off)
Enable Dryer (On/Off)
Constant Run Dryer (On/Off)
Enable VSD Blower (On/Off)
Limit Blower VSD (On/Off)
Enable Low Ambient (On/Off)
Running Hours (adjustable)
Loaded Hours (adjustable)
Power On Hours (Read Only)

PAGES 4 & 5 FACTORY SETTINGS

These pages are used for displaying software information for the controller. All items are read only.

Variable Speed Compressor


HOME FOLDER
PAGE 1 SYSTEM OVERVIEW

This is the factory default display after powering up the system.


Target Pressure Setpoint is indicated in the white box and by the white arrow, which is always centered
on the gauge. This is the pressure that the compressor is trying to maintain.
Automatic Stop Setpoint is indicated in the white box and by the white arrow, which is always right of
center on the gauge. When the compressor reaches this setpoint the compressor will unload and stop.
Package Discharge Pressure is indicated by the large numbers centered below the gauge and by the
red arrow. This is the output pressure of the compressor.
Pressure Unit of Measure is indicated below the Package Discharge Pressure. This is selectable from
the GENERAL SETTINGS folder.
Percent Capacity is indicated on the lower left side of the screen in numeric and bar graph form. This is
how much air the compressor is producing as a percentage of its maximum capacity.
Airend Discharge Temperature is indicated by the numbers in the lower right of the display.
Temperature Unit of Measure is indicated to the right of the Airend Discharge Temperature. This is
selectable from the GENERAL SETTINGS folder.
Run Hours indicate the number of hours the compressor has been running.

The target pressure and automatic stop set points can be selected and modified on this page. All
other information on this page is read only.

PAGE 2 - COUNTERS

Hour Meters Indicate the hours that: the controller has been powered up, and the compressor has been
running.
Starts indicate the number of times a start is attempted on the compressor.
Date & Time is adjustable and configurable in the GENERAL SETTINGS folder.

All information on this page is read only.

PAGES 3 THRU 5 ANALOG INPUTS AND COMPRESSOR INFORMATION

Pressure
Temperature

is indicated by this icon.


is indicated by this icon.

All information on these pages is read only.

The following analog inputs are displayed in this section:

Package Discharge Pressure


Sump Pressure
Airend Discharge Temperature
Injected Coolant Temperature
Aftercooler Discharge Temperature
Separator Pressure Drop
Coolant Filter Pressure Drop
Inlet Vacuum
Remote Pressure (optional)
Aftercooler Discharge Pressure (integrated dryer units only)

Additionally, the following compressor status readings are included in this section:

Motor Speed
Package kW
Average Package kW/hour
Average % Capacity
Average Capacity
Energy Cost
Energy Savings
Lifetime Energy Savings

OPERATOR SETTINGS FOLDER


PAGES 1-2 OPERATOR SETTINGS

Target Pressure The compressor will vary its speed in order to maintain a package discharge pressure
as close to this value as possible.
Automatic Stop Pressure The compressor will stop if the package discharge pressure reaches this
value and the compressor is running at minimum speed.
Immediate Stop Pressure The compressor will stop if the package discharge pressure reaches this
value, regardless of its speed.
Savings Compared The energy savings calculation compares how much energy is saved by this
compressor when compared to a compressor operating in the mode selected here. The options are
Geometry, Online/Offline, or Modulation
Energy Rate - Setpoint to enter the current energy cost for this compressor in local currency. This is
used for energy savings calculations
Reset Averaging This setpoint is selected to reset the energy savings calculation and start anew.

The parameters immediately below are adjustable any time. The table below shows the range and
default values for the setoints on these screens.

OPERATOR SETPOINTS
Target Pressure
Automatic Stop Pressure
Immediate Stop Pressure
% Savings Compared To
Energy Rate
Reset Averaging

Default
100
110
120
Modulation
0.000
--/--/--

MIN.
65
Target+1
Auto
--0.000
-

MAX.
145
Target+10
Auto+10
--9999.999
-

STEP
1
1
1
-----

UNIT
psi
psi
psi
----date

PAGES 3-5 OPERATOR OPTIONS

The options set points are similar to the operator set points except these set points cannot be changed
while the unit is running.
Comm Control Enabling this setpoint allows the compressor to be controlled by a serial or Ethernet
device. This is equivalent to the Sequencer option on older Intellisys controllers.
Enable Remote Start/Stop Enabling this setpoint allows the compressor to be started and stopped
using the switch inputs on the controller.
Enable PORO Enabling this setpoint will allow the compressor to automatically restart after a power
outage has been restored if the compressor was running loaded at the time of the outage.
PORO Time Time after the controller power has been restored and controller has finished booting
before the compressor will perform a PORO start.
Scheduled Start Day Day (or days) of the week for which a scheduled start will be performed
Scheduled Start Hour Hour of the day for which a scheduled start will be performed
Scheduled Start Minute Minute of the hour for which a scheduled start will be performed.
Scheduled Stop Day Day (or days) of the week for which a scheduled stop will be performed.
Scheduled Stop Hour Hour of the day for which a scheduled stop will be performed.
Scheduled Stop Minute Minute of the hour for which a scheduled stop will be performed.
Enable Remote Sensor Enabling this allows the compressor to load and unload based off a sensor
reading installed in a remote location.

Please note that in order to disable Scheduled Start/Stop, the Scheduled Start and Stop days,
hours, and minutes must match exactly.
The parameters immediately below are only adjustable when the compressor is stopped. The table below
shows the range and default values for the setoints on these screens.

OPTION ITEMS

Remote Sensor
Comm Control
Remote Start/Stop
Power Out Restart
Power Out Restart Time
Scheduled Start Day
Scheduled Start
Scheduled Stop Day
Scheduled Stop
Modbus Protocol
Modbus Address

SELECTION

MIN.

MAX.

STEP

UNIT

ON/OFF
ON/OFF
ON/OFF
ON/OFF
----------ON/OFF/ICU
---

--------10
Day
00:00
Day
00:00
--1

--------600
Day
23:59
Day
23:59
--247

--------1
1
1
1
1
--1

--------sec
day
time
day
time
-----

Installed
Option
Required
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No

* The low ambient temperature is only adjustable if the low ambient factory set point is on.
** A value of 0 will disable the lead/lag cycle time feature.

PAGES 6-7 CALIBRATE SENSORS

Sensor calibration can only take place when the machine is stopped. There should be no pressure on a
sensor when it is calibrated. Calibration only needs to take place after a sensor is replaced, the controller
is replaced, or the operator suspects the sensor reading is in error. Calibrate a sensor by selecting the
checkbox beside the sensor name.
Each of the sensors listed below can be calibrated.

Inlet Vacuum (1AVPT)


Sump Pressure (3APT)
Package Discharge Pressure (4APT)
Coolant Filter Inlet Pressure (5CPT)
Coolant Filter Outlet Pressure (6CPT)
Remote Pressure (10APT) Only on units with the remote sensor option
Interstage Pressure (2APT) Only on 2-stage units
Aftercooler Discharge Pressure (7APT) Only on units with integrated dryer

Please note that if a sensor is currently reading a value that is +/- 10% of its range from zero, the sensor
will not be able to be calibrated. Please make sure the sensor is being exposed to atmosphere before
attempting calibration.

EVENTS FOLDER
PAGES 1 TO A MAX OF 42

The pages in the Events folder document up to the last 250 events that the controller has experienced,
and time stamps each. The events are recorded in sequence, with number one being the newest and
250 being the oldest. When a new event occurs, it becomes number one and all others are shifted up in
number.
The page numbers in the Title Bar are used to scroll through the events, with each page displaying up to
seven. Page one displays events one through six, page two displays seven through twelve, and so on.
The following items will generate an event.

Power On
Power Off
Press the Start Key
Press the Stop Key
Press the Load Key
Press the Unload Key
Starting the compressor remotely
Stopping the compressor remotely
Loading the compressor remotely
Unloading the compressor remotely
Warning
Trip
Start Inhibit

Active Warnings will be highlighted in amber while cleared Warnings will have amber text.
Active Trips will be highlighted in red while cleared Trips will have red text.
Active Start Inhibits will be listed in the Event log, but not highlighted. The display will indicate the
compressor is not ready to start if a start inhibit is active.

Warning Events List


Change Inlet Filter
This will occur if the unit has been running for at least 7 seconds, the motor speed is equal to or
greater than the minimum speed, and the inlet vacuum is greater than 0.7 psi.
Change Coolant Filter
This will occur if the unit has been running for at least 7 seconds, the injected coolant
temperature is at least 140 deg F, the motor speed is at least equal to the minimum speed, and
the coolant filter pressure drop (5CPT - 6CPT) is greater than 25 psi.
Sensor Failure (Units without Integrated Dryer)
Will occur whenever a sensor is recognized as missing or broken. The sensors affected by this
warning are 1ATT, 2ATT, 4ATT, and 3CTT. The sensor failure message shall follow the following
format: SENSOR FAILURE 4ATT.
Sensor Failure (Units with Integrated Dryer)
Will occur whenever a sensor is recognized as missing or broken and the unit has an integrated
dryer (3.3.1.6). The sensors affected by this warning are 7APT, 5DTT, and 6DTT. The sensor
failure message shall follow the following format: SENSOR FAILURE 7APT.
Change Separator Element
This will occur if the unit has been running for at least 7 seconds, the injected coolant
temperature is at least 120 degF, the package discharge pressure is at least 65 psi, and the
separator pressure drop is at least 12 psi. If the target pressure is less than 90 psi, the warning
value will increase 1 psi per 5 psi in reduced target pressure. For example, if the target pressure
is between 89 and 85 psi, the warning value will be 13 psi.
High Airend Disch Temp
Will occur if the unit is running and 2ATT is greater than 221 degF (97% of 228) or the unit is in
idle mode (3.3.7.1) and 2ATT is greater than 184 degF. This warning will normally have a 5
second delay, however, if the hot side thermal valve (3.3.1.5) is set to ON, this warning will have
a 90 second delay.
High Discharge Press
Will occur if the unit is under the control of an external device, such as an X-series, and the
discharge pressure is greater than the immediate stop pressure.
Auxiliary Warning 1 (2)
This will occur if the auxiliary warning input closes.
Service
Service warnings could change significantly once the predictive maintenance warnings have been
determined.

Service warnings occur when the unit has operated a certain number of hours, based on the total
hours. Service warnings can have multiple levels, depending on the service level selection.
Selecting service level 0 disables service warnings.
Service Level 1
If service level 1 (3.3.1.9) has been selected for the unit, a SERVICE REQUIRED
warning will be issued the amount of operating hours in the Service Time Period set point
(3.3.1.10). This warning can be reset the same as any other warning.
Service Level 2
If service level 2 has been selected for the unit, the service complete factory set point
(3.3.1.11) will be used to clear a level 2 service warning and reset the service time or
date. The service complete can be reset before a service warning occurs.
The first SERVICE REQUIRED warning will occur at the total hours value of the service
time period set point (3.3.1.10). However, 100 hours before this a 100 HOURS TO
SERVICE warning will occur. This warning can be reset the same as any other warning.
One hundred hours later, at the total hours value of the service time period, the
SERVICE REQUIRED warning will occur. This warning can be reset the same as any
other warning, however this warning will return in 24 hours if the service complete factory
set point has not be set. If the service complete has not been set, 100 hours later (service
time period + 100) the ALARM SERVICE REQUIRED warning will be issued. This
warning can only be cleared by the service complete factory set point. Once the service
complete factory set point is set, indicating the service is completed, the time for the next
SERVICE REQUIRED warning will be calculated by adding the service time period to
the total hours value, with the 100 HOURS TO SERVICE warning occurring 100 hours
before and the ALARM SERVICE REQUIRED warning occurring 100 hours after that
time.
Condensate Drain Error
This will occur if the compressor is running, the package discharge pressure is over 50 psi, and
the condensate drain error contact closes for at least 240 seconds. This warning will be ignored
for 4.5 minutes after starting.
High VSD Ambient Temperature
This warning will occur if the VSD ambient temperature gets within 5% of the shutdown value
(133 degF).
Freeze Warning
This will occur if the evaporator sensor has a value of 687 (about 0.5 C) or below (low temp) while
the dryer is running, on units with the integrated dryer. This is a dryer fault. If this happens, the
compressor will continue to run, but the dryer will stop. The condition must exist for at least 180
seconds before the warning will occur. NOTE: If this warning is reset while the conditions for
running the dryer exist, the dryer can restart. Also the dryer can restart if the evaporator value
rises to 709 (about 5 C). However the warning will still be displayed.
Dryer High Pressure
On units with the integrated dryer, this will occur if the dryer high pressure switch opens while the
dryer is running. This is a dryer fault. If this happens, the compressor will continue to run, but the
dryer will stop. The contact must be open for at least 3 seconds before the warning will occur. If

this warning is reset while the conditions for running the dryer exist, the dryer can restart.
However, this switch is a locking switch. The switch must be reset before the dryer can run.
Resetting the warning on the display does not reset the switch.
Sensor Failure Remote
Will occur whenever the remote sensor is recognized as missing or broken. The sensor failure
message shall follow the following format: SENSOR FAILURE REMOTE. If this warning occurs,
the unit will automatically switch to the package discharge pressure sensor for control.
High Sump Pressure
This will occur if the compressor is running, the package discharge pressure is at least 65 psi,
and the sump pressure is more than 15 psi above the target pressure. The occurrence of this
warning will cause the controller to evaluate the need to lower the maximum speed (see 4.11).
Condenser Temperature High
This will occur if the condenser sensor has a value of 1019 (about 65 C) or above (high temp)
while the dryer is running, on units with the integrated dryer. This is not a dryer fault. If this
happens, the compressor and dryer will continue to run. The condition must exist for at least 180
seconds before the warning will occur.
Condenser Temperature Low
This will occur if the condenser sensor has a value of 887 (about 40 C) or below (low temp) while
the dryer is running, on units with the integrated dryer. This is not a dryer fault. If this happens,
the compressor and dryer will continue to run. The condition must exist for at least 180 seconds
before the warning will occur.
Change HE Filter
The HE filter is located between the aftercooler discharge and the inlet to the dryer and is only on
units with an integrated dryer. The drop across the HE filter is measured by subtracting the
package discharge pressure from the aftercooler discharge pressure. If the compressor is
running at a minimum of 75% capacity, the measured drop across the HE filter is at or above 10
psi (0.7 bar), the unit is hot (injected coolant temp above 120 degF), and the package discharge
pressure (4APT) is above 90 psi, this warning can occur. The condition must exist for at least 3
seconds before the warning will occur. This is not a dryer fault. If this happens, the warning will
be displayed, but the dryer will continue to run.

Trip Events List

High Airend Disch Temp


This will occur if 2ATT is greater than 228 degF during normal operation. This trip will occur at
200 degF if the unit is in idle mode.
Blower Fault
Will occur if the fault contact opens for 3 seconds on the blower VSD.
Remote Stop Failure

Will occur if the REMOTE START/STOP option is enabled, the remote stop button remains open
and either start button is pressed.
Remote Start Failure
Will occur if the unit is started by the remote start button and the button stays closed for 7
seconds after the unit starts.
Sensor Failure
Will occur when a sensor is recognized as missing or broken. The sensors affected by this trip
are 4APT, 3APT, 2APT, 1AVPT, 5CPT, 6CPT, and 2ATT. The sensor should be displayed along
with the sensor failure message. The sensor failure message shall follow the following format:
SENSOR FAILURE 4APT. Sensor 4APT has the following additional logic. A sensor failure
4APT will be issued if the sump pressure is over 100 psi and the package discharge pressure
(4APT) is 50 psi less than the sump pressure.
Emergency Stop
This will occur when the EMERGENCY STOP button is engaged.
VSD Fault
The VSD fault is read from the drive. The controller will read the status menu of the variable
speed drive. If a fault condition is returned in the status information, the controller will issue a
VSD FAULT trip and display the number of the fault condition. VSD faults 39 42 and 44 cant
be cleared by pressing the reset button. All other VSD faults can be cleared by pressing the reset
button. The only way to clear a VSD fault 39 42 or 44 is by cycling the power on the
compressor. Cycling the power causes the VSD to execute a power module test. The power
module test must be passed before the compressor can be restarted after a VSD fault 39 42 or
44. VSD faults 39, 40, and 41 (IGBT failures) have additional logic associated with them. Due to
false trips the logic was modified to allow an automatic restart. If the VSD fault 39, 40, or 41
occurs, the controller will trip and display the fault message. After 2 minutes, the controller will
issue a command to the VSD to run the power module test. While the VSD is running the power
module test, the controller will force itself into a reset. Upon completing the reset, the controller
will monitor the VSD for completion of the power module test. If the power module test is
completed and all conditions have passed, the controller will automatically restart the
compressor. If the power module test is failed, the controller will show the power module test
failure message and the failure code. The controller will not allow more than 5 automatic restarts
of VSD Fault 39 41 within a 24 hour period. The controller will also not allow 2 automatic
restarts of VSD Fault 39 41 within a 10 minute period. If a VSD Fault 39 41 occurs and
violates the time periods, the controller will not issue a power module test and restart. It will
display the fault and not allow a reset from the controller. The operator will have to cycle power.
Another exception on all drives are VSD faults 10, 12 14, and 16. If the compressor trips due to
one of these faults, instead of shutting down on the VSD fault, the controller will reset and then
restart the compressor. If the compressor is equipped with PORO, the controller will execute a
PORO restart. If the unit does not have PORO, the controller will restart the compressor 10
seconds after the controller has reset. A unit will be allowed to do this up to 5 times in a 1 hour
th
period. If the unit exceeds 5 occurrences within a 1 hour period, the 6 occurrence will be treated
like a regular VSD fault.
Low Sump Pressure
Will occur if the compressor is operating and the sump pressure drops below 13 psi for 15
seconds.

Check Motor Rotation


This will occur if the controller reads a negative speed from the VSD when starting.
VSD Communication Failure
This will occur if the controller does not receive a response from the VSD when requesting
information. This trip will take about 8 seconds to occur.
VSD Initialization Fault
Will occur if the controller is unable to establish communications with the VSD after a power up.
Replace Coolant Filter
Will occur if the idle mode is set to on. This trip is used as a reminder to IR service to only use
idle mode if a new coolant filter is installed.
Incorrect VSD Type
Will occur at power up if the VSD type does not match the size of compressor. The controller will
determine this by comparing the compressor type with the drive ID board. See section 3.3.1.3 for
this data.
Control Power Loss
This will occur if the compressor should be running and the AC input voltage, as read from the
VSD, falls below 100 VAC. There is a delay of 2 seconds on this trip in case the power quickly
returns. A phase monitor is something that can cause this trip.
Stop Failure
This will occur if the compressor should be stopped, but the motor speed has not dropped below
the minimum motor speed set point. The controller will wait 4 seconds for the compressor to stop
before issuing this trip.
High Interstage Pressure
This will occur if the compressor is running, it is a 2 stage unit, and the interstage pressure is
above 75 psi.
High Coolant Filter Pressure Drop
This will occur if the unit has been running for at least 7 seconds, the injected coolant
temperature is at least 140 deg F, already has a change coolant filter warning, the motor speed is
at least equal to the minimum speed, and the coolant filter pressure drop (5CPT - 6CPT) is
greater than 35 psi.
High Inlet Vacuum
This will occur if the compressor is running loaded, the motor speed is at least minimum speed,
and the inlet vacuum is greater than 1.8 psi (vacuum).
High Sump Pressure

This will occur if the compressor is running and any one of the 3 following conditions exist. (1)
The sump pressure is above the target pressure by 25 psi. (2) The separator pressure drop is
measured to be more than 25 psi and the package discharge pressure is at least 65 psi. (3) The
sump pressure is above 168 psi.

Start Inhibit List


High Airend Discharge Temperature
This will occur if 2ATT is greater than 95% of 228 degF.
High Sump Pressure
This will occur if the sump pressure (3APT) is 25 psi or higher than the rated pressure of the
compressor.
Waiting for VSD Comms
This will occur if the compressor VSD has not responded to the initial communications from the
controller.

TRIP HISTORY
PAGES 1 TO A MAX OF 4

The pages in the Trips History folder document up to the last 15 trips that the controller has experienced,
and time stamps each. The trips are recorded in sequence, with number one being the newest and 15
being the oldest. When a new trip occurs, it becomes number one and all others are shifted up in number.
The page numbers in the Title Bar are used to scroll through the events, with each page displaying up to
seven. Page one displays events one through five, page two displays six through ten, and so on.
The following items will generate an entry in the trip history.

Trips

Active Trips will be highlighted in red while cleared Trips will have red text.
The trip history also records compressor data at the time of the trip to assist in diagnostics and
troubleshooting. Navigating to the trip entry and hitting the enter button will bring up the trip history dialog
box.

While the dialog box is active, press the left and right keys in order to scroll through the displayed data.
The name of the trip will always be shown in the title bar of the dialog box. Press enter when finished
viewing the data to return to the trip history screen.

MAINTENANCE FOLDER
PAGE 1 FILTER STATUS

This page displays the status of the filters. The filter status will either be OK or Change depending on
the compressors diagnostic readings. If a filter reaches the change status, a warning will be issued and
the service indicator will light up yellow to notify the user.
The following filters are displayed:

Coolant Filter
Separator Element
Inlet Filter

PAGE 2 MAINTENANCE STATUS

This page displays the time until the unit should be serviced. The service meter will deplete as the hours
count down closer to a service appointment. Once the counter reaches the yellow zone, the service

indicator will light up yellow. Once the counter reaches the red zone the service indicator will light up red
and maintenance must be performed.

PAGE 3 MAINTENANCE CONFIGURATION

This page allows the user to set the service interval and to reset the counter after the service has been
performed. The service interval may be set to any value between 1000 and 8000 hours, but must be set
in accordance with the factory maintenance schedule. After maintenance has been performed, the user
can reset the counter by navigating to the Reset button and pressing the enter key.

GENERAL SETTINGS FOLDER


All parameters in the general settings folder are adjustable.

PAGE 1 LANGUAGE SELECTION

Language is selectable from the following 30 selections:


English (default)
Bulgarian
Chinese, simplified
Croatian
Czech
Danish
Dutch
Estonian

Finish
French
German
Greek
Hungarian
Italian
Indonesian
Korean

Latvian
Lithuanian
Maltese
Norwegian
Polish
Portuguese
Romanian
Russian

Slovak
Slovenian
Spanish
Swedish
Thai
Turkish

The controller will display all screens in the selected language and only one language can be selected at
a time.
Each language appears in its native translation.

PAGE 2 UNITS OF MEASURE SETTINGS

Temperature is selectable between F and C.


2

Pressure is selectable between psi, kpa, bar, kg/cm .


Power is selectable between kW and HP

PAGE 3 HOME PAGE SELECTION

Auto Return to Home enables the controller to return the display back to the selected Home Page if
there is no user activity for the Delay Time shown. This is only enabled when an x appears in the
checkbox.
Delay Time determines how many seconds of inactivity it will take before the controller will return to the
Home Page.
Select Home Folder is used to select the Home Folder.
Select Home Page is used to select the Home Page within the selected Home Folder.

PAGE 4 AND 5 TIME & DATE SETTINGS

All items are adjustable.


Hours allows the current hour to be set. The hours format is fixed on 24-hour.
Minutes allows current minutes to be set.
Seconds allows current seconds to be set.
Year allows current year to be set.
Month allows current month to be set.
Day allows current day to be set.
Date Format is selectable between dd/mm/yyyy (default) and mm/dd/yyyy.
Confirm New Time and Date is used to verify that changes to selections are desired. An x must appear
in the checkbox before any changes will take affect.
The controller will continue to display any changes, even when the selections have not been confirmed
and the user exits the page, then returns. Cycling of the power returns all selections to their current
settings.

The controller does not support Daylight Savings Time.

PAGE 6 BACKLIGHT SETTINGS

Backlight Brightness adjusts the brightness of the display.


Enable Backlight Auto-Off enables the controller to shut-off the backlight if there is no user activity for
the delay time shown.
Backlight Auto-Off Delay Time determines how many seconds of inactivity it will take before the
controller will shut-off the backlight.

The backlight will be switched on whenever any of the controllers keys are pressed.

THE START, STOP, LOAD, UNLOAD, RESET, AND ACKNOWLEDGE KEYS ON THE
CONTROLLER REMAIN FUNCTIONAL WHILE THE BACKLIGHT IS SWITCHED OFF. IT IS
RECOMMENDED TO PRESS THE ENTER KEY OR ONE OF THE NAVIGATION KEYS IN
ORDER TO SWITCH THE BACKLIGHT ON.

PAGE 7 - SERIAL PORT ADDRESS SETTINGS

This page allows the user to set up the network addresses for the RS-485 networks the controller is
capable of communicating with.
MODBUS Address Sets the modbus node ID for the controller to communicate with a Modbus capable
device, this can be any value between 1 and 254.
Airbus Address Sets the airbus address that allows the controller to communicate over Integral
Sequencing or an X-Series system controller network.

PAGES 8 AND 9 COM PORT CONFIGURATION

This will most likely be removed from the software

PAGES 10 AND 11 ETHERNET SETTINGS

IP Address Setting When DHCP is not enabled, this setpoint sets the IP address of the controller.
IP Address Actual This will match the IP address setting when DHCP is not enabled. If DHCP is
enabled this will display the address assigned to the controller by the DHCP server.
Default Gateway Setting Setpoint for the default gateway.
Default Gateway Actual Current reading/setting for the default gateway.
Subnet Mask Setting Setpoint for the subnet mask
Subnet Mask Actual Current reading/setting for the subnet mask
MAC Address This is the unique hardware MAC address for the controller. This can not be changed.
Enable DHCP Allow the controller to automatically receive an IP address from the Local Area Network
(LAN)
Accept After editing the desired setpoint navigate to the accept setting and press enter in order for the
values in the setting variables to be confirmed by the controller.
Cancel Discard any changes made to the Ethernet settings.

INTEGRAL SEQUENCING FOLDER

Integral Sequencing allows the compressor to be networked with up to three other compressors (fixed or
variable speed) to maintain a stable system pressure by loading and unloading compressors as needed.
Integral sequencing requires no additional hardware other than a serial two wire connection daisy chained
between all compressors in the system.
Please note that the compressors address in the integral sequencing system is defined by the airbus
address that is set on the general settings folder. Also note that the pressure signal used to determine
when to load or unload another compressor is based on the pressure reading from the compressor at
address 1 in the system.
Integral Sequencing Enabling Integral Sequencing immediately places the compressor under integral
sequence control. The default is disabled. Please make sure all compressors are set up for integral
sequencing before enabling this function.
Unload Pressure Determines the pressure at which a compressor will be unloaded by the system
Load Pressure Determines the pressure at which a compressor will be loaded by the system.
Start Delay Interval Determines the amount of time between loading compressors. This prevents all
compressors from loading at once.
Damping The pressure control Damping setting which is used to tune how quickly the system
responds to pressure deviations. The default is 10 and should not normally be changed.
Tolerance - The pressure control Tolerance setting, which is used to tell the system how to respond to
changes in pressure above and below the load/unload pressures. The default is 3.0 psi and should not
normally be changed.
Number of Compressors Defines how many compressors are in the system.
Sequence Displays the current load/unload order of the system. Each compressor in the system is
assigned a letter, with A being the compressor to load first and unload last, and D being the
compressor to load last and unload first.
Priority Each compressor can be assigned a priority level. Compressors will only rotate positions with
other compressors of the same priority level.

Rotation Interval Determines the time period between sequence rotations.


Time Left Counts down the time until the sequence rotation will occur.
System Pressure Shows the current pressure reading that the system is using for control. This is
typically compressor 1s package discharge pressure reading.

STATUS FOLDER

All information on these pages is read only.

PAGES 1 THRU 2 ANALOG INPUTS

Analog Inputs:
The following analog inputs are displayed in this section.

Package Discharge Pressure


Sump Pressure
Airend Discharge Temperature
Injected Coolant Temperature
Aftercooler Discharge Temperature
Separator Pressure Drop
Coolant Filter Pressure Drop
Inlet Vacuum
Aftercooler Discharge Pressure (integrated dryer units only)
Remote Pressure (optional)
Coolant Filter Inlet Pressure (Password Required)
Coolant Filter Outlet Pressure (Password Required)
Interstage Pressure (2-stage units only) (Password Required)
Evaporator (Password Required)
Condenser (Password Required)

PAGE 4 COMPRESSOR DATA

Compressor Data:

% Energy Savings
% Capacity
Package Power
Power On Hours
Running Hours
Motor Speed
Time
Motor Current
Motor Voltage
AC Input Voltage
DC Bus Voltage
IGBT U Temperature
IGBT V Temperature
IGBT W Temperature
Input Rectifier Temperature
VSD Ambient Temperature
Remote Maximum Speed
Remote Maximum Pressure
Target Pressure

PAGES 7 AND 8 DIGITAL INPUTS

Digital Inputs: (Password Required)

An x in the checkbox beside a digital input indicates that the input is in its TRUE state. For example,
Starter Feedback is TRUE when its input is in the high state, where as, E-Stop is TRUE when its input is
at 0Vdc.

Emergency Stop
Blower Fault
Condensate Drain Error
Remote Stop
Remote Start
Auxiliary Input 1
Auxiliary Input 2
Dryer High Pressure

PAGES 9 AND 10 DIGITAL OUTPUTS

Digital Outputs (Password Required):


An x in the checkbox beside a digital output indicates that it is energized.

Isolation Contact
K1 Contact
PDM Fan Contact
1SV
Condensate Drain
Dryer Running
PORO Horn
Trip Relay
Warning Relay

PAGE 11 ANALOG OUTPUTS

Analog Outputs:
The value for the analog outputs will be in mA.

VSD Blower Output

FACTORY SETTINGS FOLDER


This folder is for IR factory and service personnel. A password must be entered on page one in order to
adjust values in this folder. This folder is used for setting parameters that are specific to that compressor
and displaying software information for the controller.

PAGE 1 PASSWORD

Password:
Provides access to enter a valid password to gain access to password protected parameters. The
password is entered by scrolling down to the password value and pressing the return key.
Password entered:
This checkbox will indicate a valid password has been entered. If this checkbox is blank, a valid
password has not been entered or it has timed out. This is read only.
Password timeout enable:
Checking this box will enable the password time feature.
Password timeout:
This timeout along with the password timeout enable allows the user to set an adjustable amount of time
to require a valid password to be re-entered. Once this timeout is reached re-entry of a valid password is
required. The timeout counter is reset after any button press.

PAGES 2 & 3 FACTORY SETTINGS

These pages are used for setting parameters that are specific to the compressor. All of the factory
settings that are adjustable are listed below. All settings on these pages are password protected.
Compressor Type - The type of compressor will be selected here. The choices are listed below.
Single Stage
37 kW/50 HP 1-S (46, 47) (38, 39)
45 kW/60 HP 1-S (47) (39)
55 kW/75 HP 1-S (48, 49) (40, 41)
75kW/100HP 1-S (49) (41)
90 kW 1-S (50, 51) (42, 43)
125 HP 1-S (50, 51) (42, 43)
110 kW 1-S (51) (43)
150 HP 1-S (51) (43)
132 kW 1-S (52, 53) (44, 45)
200 HP 1-S (53) (45)
160kW 1-S (53) (45)
Enable Two Stage (On/Off)
Enable Water Cooled (On/Off)
Hot Side Thermal Valve (On/Off)
Enable PAC (On/Off)
Enable Dryer (On/Off)
Constant Running Dryer (On/Off)
Running Hours (adjustable)
Power On Hours

2-Stage
90 kW 2-S (50, 51) (42, 43)
125 HP 2-S (50, 51) (42, 43)
110 kW 2-S (51) (43)
150 HP 2-S (51) (43)
132 kW 2-S (52, 53) (44, 45)
200 HP 2-S (53) (45)
160 kW 2-S (53) (45)

PAGES 4 & 5 FACTORY SETTINGS

These pages are used for displaying software information for the controller. All items are read only.

PAGES 6 THROUGH 10 MAXIMUM VALUES

The maximum values pages are used to record the highest value the controller has seen since the last
time the maximum values have been reset. Each maximum value entry displays the highest value
recorded as well as the time and date stamp of when these maximum values have occurred.
The final maximum value page has a reset setting at the bottom of the page, highlighting this button and
hitting enter will cause the controller to clear all history of maximum values and begin recording them
again. The password must be entered in order to use this reset functionality.

PAGES 11 AND 12 VSD DIAGNOSTICS

The VSD Diagnostics screens are used to troubleshoot any drive problems. These screens must only be
used by authorized service technicians. The password must be entered in order to activate these
diagnostic tests.

PAGES 13 THROUGH 16 VSD SERVICE MENUS

The VSD service menus contain parameters used to set up the compressor for optimal operation. These
screens must only be used by authorized service technicians. The password must be entered in order to
modify these parameters.

MODBUS CONNECTION AND CONTROL


Connection to the Modbus Network
The Xe-90M and Xe-145M controllers are designed to interface to any Modbus master capable device using Belden
9841 or equivalent RS-485 cable. In order to connect to the network, the cable must be connected to port COM2 on
the controller as shown in the diagrams below:
Xe-90M / Xe-145M
Phoenix 2Pin Connector

L2
2
1

L1

P9 COM2
L2
L1
RS- 485 NETWORK
RS-485 data communications and other low voltage signals can be subject to electrical interference. This
potential can result in intermittent malfunction or anomaly that is difficult to diagnose. To avoid this possibility always
use earth shielded cables, securely bonded to a known good earth at one end. In addition, give careful consideration
to cable routing during installation.
1) Never route an RS-485 data communications or low voltage signal cable alongside a high voltage 3-phase power
supply cable. If it is necessary to cross the path of a power supply cable(s), always cross at a right angle.
2) If it is necessary to follow the route of power supply cables for a short distance (for example: from a compressor
unit to a wall along a suspended cable tray) attach the RS-485 or signal cable on the outside of an earthed cable tray
such that the cable tray forms an earthed electrical interference shield.
3) Where possible, never route an RS-485 or signal cable near to equipment or devices that may be a source of
electrical interference (for example: 3-phase power supply transformer, high voltage switchgear unit, frequency
inverter drive module, radio communications antenna).

MODBUS ADDRESS SELECTION


Each compressor connected to the MODBUS network will have a unique assigned address, starting at compressor 1
increasing sequentially to the number of compressors connected to the MODBUS network.
The Modbus address for each compressor is set on the General Settings Tab, Page 7. The controllers default
Modbus Address setting is 1

MODBUS MASTER SETTINGS


In order to communicate properly with the Xe-M controller, the Modbus master must be set to communicate with the
following configuration:
Baud Rate 9600
Data Bits 8
Stop Bits 1
Parity None
The following polling parameters are recommended for optimal system operation:
Polling Rate: Not less than 500 ms
Timeout: 500 ms
Retries: 2

XE- 90M AND XE- 145M MODBUS TABLES


R55 R160 Fixed Speed Modbus Table

Register
(40XXX)
001
003
004
005
006
007
008
010
011
012
013
014
015
016
064
065
098
099
100
101
102
103
104
112
113
114
115
116
117
118
119
120
121
122
123
124
125

Variable
Status/Control
Discharge Pressure
Sump Pressure
Inlet Vacuum
Injected Coolant Temperature
Airend Discharge Temperature
Aftercooler Discharge Temperature
Separator Pressure Drop
Coolant Filter In Pressure
Coolant Filter Out Pressure
Coolant Filter Pressure Drop
Interstage Pressure
Remote Pressure
Aftercooler Discharge Pressure
Running Hours (hours)
Loaded Hours (hours)
Rated Pressure
2-Stage
Starter Type
Modulation Enabled
Service Level
Service Time Period
Dryer Installed
Offline Pressure
Online Pressure
Mode of Operation
Starter Time (seconds)
Auto Start/Stop (AS/S) Time (seconds)
Auto Start/Stop (AS/S) On/Off
Communication Control On/Off
Remote Start/Stop Enable
Unused
Power Out Restart Option (PORO) Enable
PORO Time (seconds)
Auto Start/Stop Delay Time (seconds)
Low Ambient Temperature
Unloaded Stop Time

Read/
Write
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

Range

R
R
R/W
R/W
R/W
R/W
R/W
R
R
R

1000 - 8000

R
R/W
R/W
R/W
R/W

Notes
See FIGURE 1

2-Stage Units Only

1-3
0-2

75 - (rated+10)
65-(offline-10)
02
5 30
120 3600

0 = 1 Stage
See FIGURE 2
0=Disabled
0=Level 0, 1=Level 1,
2=Level 2
Increments of 1000
0=Off
rated = rated pressure
offline = offline pressure
See FIGURE 2

0=Off
0=Off
0=Off
0=Off
10 - 120
0 - 60
30 - 60
10 - 60

Degree F

Register
(40XXX)
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
255
256

Variable
Low Ambient Option On/Off
High Dust Filter
Lead/Lag
Lag Offset
Variable Frequency Drive
Lead/Lag Cycle Length (Hours)
Scheduled Start (Day)
Scheduled Start (Hour)
Scheduled Start (Minute)
Scheduled Stop (Day)
Scheduled Stop (Hour)
Scheduled Stop (Minute)
Condensate Release Time
Condensate Interval Time
Remote Sensor
Warning Code
Trip Code

Read/
Write
R
R
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R

Range

0 - 45
0 750
0-9
0 23
0 59
0-9
0 23
0 59
2 - 20
90 - 270

Notes
0=Off
0=Off
0=Lag
psi
0=Off
See FIGURE 2

See FIGURE 2

0=Off
See FIGURE 4
See FIGURE 4

Bit 0: Host/Local (R/W)


Bit 6: Alarm (R)
0 = Local
0 = No Alarms
1 = Host
1 = Alarms
Bit 1: Run/Stop (R/W)
Bit 7: Warning (R)
0 = Stop
0 = No Warnings
1 = Run
1 = Warnings
Bit 2: Load/Unload (R/W)
Bit 8: On/Off Line Mode (R)
0 = Unload
0 = Not in On/Off Line Mode
1 = Load
1 = On/Off Line Mode
Bit 3: Modulating (R)
Bit 9: Mod/ACS or Mod Only (R)
0 = Not Modulating
0 = Not in Mod/ASC Mode
1 = Modulating
1 = Mod/ASC Mode
Bit 4: Unused
Bits 10-12: Unused
Bit 5: Stopped in Auto Restart (R)
Bits 13-15: Unit Type (R)
0 = Not Stopped in Auto Restart
001 = SSR controller
1 = Stopped in Auto Restart
FIGURE 1 XE-90M AND XE-145M FIXED SPEED CONTROLLER REGISTER 01-STATUS/CONTROL

Register 100: Starter Type


1 = Star-Delta
2 = Remote Starter
3 = Soft Starter
Registers 132, 135: Day
0 = Sunday
1 = Monday
2 = Tuesday
3 = Wednesday

Register 114: Mode of Operation


0 = On/Off Line
1 = MOD/ACS
2 = Modulation Only

4 = Thursday
5 = Friday
6 = Saturday

7 = Daily
8 = Weekdays
9 = Weekends

FIGURE 2 XE-90M AND XE-145M FIXED SPEED CONTROLLER REGISTER CODES

Code
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
22
25
26
28
29
30
31
32
33
34
35
36
38
39
40
41
42
43
48
49
50
51
52
53
54
55
200

Description
Sensor Failure 1AVPT
Sensor Failure 3APT
Sensor Failure 4APT
Sensor Failure 5CPT
Sensor Failure 6CPT
Sensor Failure 10APT (Remote)
Sensor Failure 2APT
Sensor Failure 7APT
Sensor Failure 2CTT
Sensor Failure 2ATT
Sensor Failure 4ATT
Sensor Failure T4 (Spare)
Sensor Failure 5DTT
Sensor Failure 6DTT
Sensor Failure T7 (Spare)
Sensor Failure T8 (Spare)
High Inlet Vacuum
Motor Overload (Main)
Fan Motor Overload
Check Motor Rotation
Remote Stop Failure
Remote Start Failure
Low Sump Pressure
High Air Pressure
High Coolant Filter Pressure Drop
High A/E Discharge Temperature
Emergency Stop
Change Inlet Filter
Change Separator Element
Change Coolant Filter
Sensor Error (Calibration)
100 Hours To Service
Service Required
Alarm Service Required
Auxiliary 2
Auxiliary 1
Condensate Drain Error
Unit Too Cold To Start
High Sump Pressure
High Interstage Pressure
Dryer High Pressure
Dryer Freeze Warning
Condenser Low (Dryer)
Condenser High (Dryer)
Change HE Filter (Dryer)
Check SD Card

FIGURE 4 XE-90M AND XE-145M FIXED SPEED CONTROLLER TRIP & WARNING CODES

R55 R160 VariableSpeed Modbus Table

Register
(40XXX)
001
003
004
005
006
007
008
009
010
011
012
013
014
015
016
017
018
019
020
021
022
025
026
027
028
029
030
031
032
033
064
098
099
100
101
102
103
104
112
113
114

Variable
Status/Control
Package Discharge Pressure
Sump Pressure
Inlet Vacuum
Interstage Pressure
Coolant Filter In Pressure
Coolant Filter Out Pressure
Remote Pressure
Aftercooler Discharge Pressure
Injected Coolant Temperature
Airend Temperature
Aftercooler Discharge Temperature
Inlet Temperature
Cooler Out Temperature
Evaporator
Condenser
Spare Temperature
Separator Pressure Drop
Percent Capacity
Percent Energy Savings
Coolant Filter Pressure Drop
Motor Speed
Motor Current
Input Voltage
DC Bus Voltage
Remote Pressure
Motor Voltage
Package kW
kW Hours
mW Hours
Total Hours (hours)
Compressor Type
Service Level
Service Time Period
Water Cooled
Hot Side Thermal Valve
Dryer Installed
2-Stage Enabled
Target Pressure
Auto Stop Pressure
Immediate Stop Pressure

Read/
Write
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W

Range

Notes
See FIGURE 1

Only in 2-stage units.

VAC

0 999

0-2
1000 - 8000

65 - 145
(T+1)-(T+10)
ASP(ASP+10)

Add to (mW hours * 1000)

See FIGURE 2
0=Level 0, 1=Level 1,
2=Level 2
Increments of 1000
0=Off
0=Off
0 = no dryer
0 = 1 stage
T = target pressure
ASP = auto stop pressure

Register
(40XXX)
117
118
119
120
121
122
123
124
127
128
129
130
131
132
251
255
256

Variable
Compare Savings To
Condensate Release Time
Condensate Interval Time
Remote Sensor Enable
Communication Control On/Off
Remote Start/Stop On/Off
Power Out Restart Option (PORO)On/Off
PORO Time (seconds)
Scheduled Start - Day
Scheduled Stop - Day
Scheduled Start (Hour)
Scheduled Start (Minute)
Scheduled Stop (Hour)
Scheduled Stop (Minute)
VSD Software Version Number
Warning Code
Trip Code

Read/
Write
R/W
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R

Range

Notes

0-2
2 - 20
90 - 270

0=Geo, 1=Mod, 2=On/Off

0=Off
0=Off
0=Off
0=Off
10 - 600
0-9
0-9
0 23
0 59
0 23
0 59

See FIGURE 2
See FIGURE 2

Divide by 10
See FIGURE 4
See FIGURE 4

Bit 0: Host/Local (R/W)


0 = Local
1 = Host
Bit 1: Run/Stop (R/W)
0 = Stop
1 = Run
Bit 2: Load/Unload (R/W)
0 = No Loaded Operation
1 = Loaded Operatoin
Bit 3: Operating at Minimum Speed (R)
0 = Operating above Minimum Speed
1 = Operating at Minimum Speed
Bit 4: Operating at Maximum Speed (R)
0 = Operating below Maximum Speed
1 = Operating at Maximum Speed
Bit 5: Stopped in Auto Restart (R)
0 = Not Stopped in Auto Restart
1 = Stopped in Auto Restart

Bit 6: Alarm (R)


0 = No Alarms
1 = Alarms
Bit 7: Warning (R)
0 = No Warnings
1 = Warnings
Bits 8 - 9: Normal/Unload Operate (R)
00 = Unloaded Operation
11 = Normal Operation
Bits 10 11: Unused
Bit 12: Nirvana Compressor (R)
0 = Not Nirvana
1 = Nirvana

Bits 13-15: Unit Type (R)


001 = SSR controller

FIGURE 1 XE-90M AND XE-145M VARIABLE SPEED CONTROLLER REGISTER 01-STATUS/CONTROL

Register 98: Compressor Type


37 = 37kW/50HP
45 = 45kW/60HP
55 = 55kW/75HP
75 = 75kW/100HP
90 = 90kW
93 = 125HP
110 = 110kW
112 = 150HP
132 = 132kW
149 = 200HP
160 = 160Kw
Register 127 & 128: Day
0 = Sunday
1 = Monday
2 = Tuesday
3 = Wednesday

4 = Thursday
5 = Friday
6 = Saturday

7 = Daily
8 = Weekdays
9 = Weekends

FIGURE 2 XE-90M AND XE-145M VARIABLE SPEED CONTROLLER REGISTER CODES

Code
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
44
45
46
47
48
49
51
52
53
54
55
200

Description
Sensor Failure 4APT
Sensor Failure 3APT
Sensor Failure 1AVPT
Sensor Failure 5CPT
Sensor Failure 6CPT
(Spare)
Sensor Failure 2APT (2-stage units)
Sensor Failure 7APT (Dryer)
Sensor Failure 2CTT
Sensor Failure 2ATT
Sensor Failure 4ATT
Sensor Failure 1ATT
Sensor Failure 3CTT
Sensor Failure 5DTT
Sensor Failure 6DTT
Sensor Failure T8 (Spare)
Sensor Failure Remote (Optional)
High VSD Temperature
Blower Fault
VSD Communication Failure
Check Motor Rotation
Stop Failure
Check Incoming Power
Remote Stop Failure
Remote Start Failure
Incorrect VSD Type
Replace Coolant Filter (Idle Mode)
High Air Pressure
Low Sump Air Pressure
High A/E Discharge Temperature
Emergency Stop
Change Inlet Filter
Change Separator Element
Change Coolant Filter
Invalid Calibration
Check Set Points
100 Hours To Service
Service Required
Alarm Service Required
Auxiliary 2
Auxiliary 1
Condensate Drain Error
High Interstage Pressure
High Coolant Filter Pressure Drop
High Inlet Vacuum
High Sump Pressure
Power Module Timeout
Dryer High Pressure
Freeze Warning
Condenser Low
Condenser High
Change HE Filter
Check SD Card
9

100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
133
134
135
136
137
138
139
140
141
142
143
144

VSD Fault 0
VSD Fault 1
VSD Fault 2
VSD Fault 3
VSD Fault 4
VSD Fault 5
VSD Fault 6
VSD Fault 7
VSD Fault 8
VSD Fault 9
VSD Fault 10
VSD Fault 11
VSD Fault 12
VSD Fault 13
VSD Fault 14
VSD Fault 15
VSD Fault 16
VSD Fault 17
VSD Fault 18
VSD Fault 19
VSD Fault 20
VSD Fault 21
VSD Fault 22
VSD Fault 23
VSD Fault 24
VSD Fault 25
VSD Fault 26
VSD Fault 27
VSD Fault 28
VSD Fault 29
VSD Fault 30
VSD Fault 31
VSD Fault 33
VSD Fault 34
VSD Fault 35
VSD Fault 36
VSD Fault 37
VSD Fault 38
VSD Fault 39
VSD Fault 40
VSD Fault 41
VSD Fault 42
VSD Fault 43
VSD Fault 44

FIGURE 4 XE-90M AND XE-145M VARIABLE SPEED CONTROLLER ALARM & WARNING CODES

10

WEB ACCESS
Ingersoll Rand Xe-90M/Xe-145M web pages are a visualization application which offers a window using a web browser on your
PC. The web pages allows the user to monitor air system at a glance or take a more detailed look into system operation,
equipment status and setup through an intuitive web-page based user interface. To access this application running on the
controller, simply connect via a Web Browser from any PC using an Ethernet connection. The PC can be local stand alone or part
of a LAN.

The system administrator can assign a user one of three levels of access (view only, user, and administrator) which will
determine which functions will be available to that user. For example, only users with administrator access will be able to make
new accounts and to view or modify the configuration overview parameters. See section Account Management.
The Xe-90M/Xe-145M functions as a web server for the compressor. The web server offers the following through the interface:

Display of current operating state of the compressor


Compressor Information model number, serial number, rated capacity and other details
Start, Stop, Reset Alarm, Load and Unload buttons
Adjust operating parameters
Display of analog signals
Display of hour meters
Display of Event log
Graphing (Xe-145M Only)
Display of maintenance timers
Edit and display of maintenance log
Notification of alarm/trip events via email

COMMISSIONING PROCEDURES
There are certain parameters that must be configured in order for the controller to properly communicate to the LAN and to the
network. Outlined below is a list of steps that must be completed before the visualization software can be fully utilized. Please
be sure that you have ADMIN rights before attempting to configure the controller.
If you will only be connecting to the controller to a single PC, go to step 1. If you will be using a static IP or DHCP assigned IP
address on your companys LAN please go to step 2.
1) Connect the controller to a PC Follow the procedure outlined in section CONNECTING TO A PC. Please go to step 3.
2) Configure the controller Ethernet settings Obtain a static IP address from your IT department or have an assigned domain
name for DHCP access. Follow the procedures in ETHERNET CONFIGURATION.
3) Login to the web pages Follow the procedure in section LOGIN PROCESS.
4) Configure compressor information Follow the procedures in section COMPRESSOR INFORMATION. Make sure you have
the compressor nameplate data available.
5) Set up user accounts Follow the procedures in section ACCOUNT MANAGEMENT.

CONNECTING TO A PC
In order to configure your computer to communicate point-to-point with the Xe-90M or Xe-145M controller, you must first set
the IP address range of your computer to the default IP address range of the controller. To do this, please follow the instructions
listed below to configure the computer IP address. These settings are accessible using Windows XP by selecting:
Using Classic View:
Select Start
Select Settings
Select Network Connections
Using XP Start View:
Select Start
Select Control Panel
Select Network Connections
Please note that the controller ships with a default IP address of 192.168.2.220
1) Select Local Area Connection from the list.

2) Right click on the Local Area Connection and select Properties.

3) Scroll down the connection list to find the Internet Protocol (TCP/IP). Selecty the Internet Protocol (TCP/IP) and click on
Properties.

4) Click on the Alternative Configuration tab.

5) Clcik on User Configured Button

6) Enter IP address for the computer (192.168.2.221), Enter the Subnet mask for the computer (255.255.255.0) and leave all
other field boxes blank.

7) Click on OK button when it is complete.

8) Connect an Ethernet cable to your computer and to the controller. Within a minute, the computer will make a connection to
the controller. Once connected, you will be able to log into and configure the controller.

ETHERNET WIRES
Wiring the network is accomplished by connecting the user computer to the controller using Category 5 (or better) cables. The
connection point on the user computer is a RJ-45 port located on the Network Interface card.

The Ethernet cables are terminated with CAT 5 RJ-45 (RJ means "Registered Jack") modular plugs. RJ-45 plugs are
similar to those seen on the end of a telephone cable except they have eight versus four or six contacts on the end of
the plug and they are about twice as big..

ETHERNET CONFIGURATION
The Ethernet configuration allows the user to select how the controller will be connected to the LAN.

The controller ships with a default IP address of 192.168.2.220. If Enable DHCP option is true in the General Settings
[screen# 8] of the controller, then it will obtain an IP address via DHCP. Refer R55 - 160 kW Instruction manual for more
information.

Once the user changes the DHCP Enable option to true, the Assigned IP address (e.g. 10.40.193.73) will appear below this
selection in few seconds. The users connected with the local area network can use this new assigned IP to login to the web
pages. Please note that depending on the LAN architecture, not all users will be able to view the web pages from their PC.
Caution! Changing the Ethernet configuration of the controller may cause the web pages to become unresponsive and require IT
or other support to return the web pages to an operational condition. Be certain all Ethernet settings are correct before saving
changes.

LOGIN PROCESS
The server is accessed either by host name or by IP. Accessing by name requires that a router be in the network. During the
installation and commissioning process a network address was assigned to the CONTROLLER by your IT department.
This address may be a static IP (e.g. http://192.168.2.220, recommended) or a DHCP assigned domain name address (e.g.
http://fenixsim.com). A domain name address is a web page address chosen by the user to represent the controller. The
domain name must be approved by your IT department but can generally be any text label you wish. You must have this address
before you can log in to the web pages. See section Ethernet Configuration.
Please note that Web Pages requires Internet Explorer 8 (or newer) or Mozilla Firefox 5 (or newer). Certain functions may not
behave correctly when using older browser software.
To log in to the web pages you must first type the address into your browser and then press the enter button. For example, with
a DHCP enabled controller you might type this:

While with a static IP address you might type this:

If the controller is configured correctly you will then see the web pages in your browser. This may take a few seconds depending
on your network connection speed.

The login screen requires the user to enter their username, password and select the language for the web pages. This login
screen will authenticate the user against the type of account. After log in the user can view/modify the data as per the available
access to the user account.

Enter the username & password for log into system and access the web pages.
Type in your user name (case sensitive)
Type in your password (case sensitive)
If the user name or password are incorrect the login page will show a message Unknown combination of username and
password.
Click on the dropdown control and select the Language from language dropdown control. The full list of languages for the
Fenix controller is supported by the web interface. The user may select one language from this list. This selection will be the
language for the web interface after the login is successful.
Select your language from the dropdown list

Click on Login button to continue. Upon successfully logging in you will see the system HOME screen as shown below.

Note: Only 5 users can concurrently login to the controller at a time. If another user attempts to login, an error message will be
displayed. "The limit on the number of concurrent users has been reached. Please wait for a user to logoff before trying again."
Please see below section for default account information, and section ACCOUNT MANAGEMENT for more detailed information
about the account management process.

DEFAULT ACCOUNTS
The web page software comes with default administator account. The system administrator can assign users one of three levels
of access (view only, user and administrator) which will determine which functions will be available. For example, only users
with administrator access will be able to create a new user account and view or modify the configuration overview parameters.
It is highly advised that the administrator change these accounts as soon as feasible to prevent unauthorized access to the
Visualization software. The three level of access rights are as follows:
1)

VIEW

The user is able to view information on all the screens. The user is unable to change any set points or
access to the configuration overview screens.

2)

USER

The user has all rights available to the VIEW access level as well as being able to change setpoints on the
HOME screen and working duration of the maintanance counter. The user is able to manually start, stop,
load and unload the compressors, as well as reset the alarm.

3)

ADMIN

The user has all rights of the VIEW and USER access levels as well as full access to the configuration
overview screens and the account management utility.

Please note that there can be as many as five (5) maximum users logged into the system at one time, and only one administrator
logged in at one time. Only a user with ADMIN rights will be able to modify these default accounts.
The default account is:
Login
Password

:
:

admin
pwadmin

Rights

ADMIN

NAVIGATION
Each of the main segments is represented by a tab on the top of web pages. Clicking on the tab will bring you to the screen for
that particular segment.
TAB NAVIGATION

The components of the tab navigation are as follows:


Home

Clicking this tab will bring the user to the HOME page.
See section HOME PAGE

Event Log

Clicking this tab will bring the user to the EVENT LOG.
See section EVENT LOG UTILITY

Performance
Log (Xe-145
Only)

Clicking this tab will bring the user to the PERFORMANCE LOG.
See section PERFORMANCE LOG UTILITY

Graphing (Xe145 Only)

Clicking this tab will bring the user to the GRAPHING page.
See section GRAPHING UTILITY

Maintenance

Clicking this tab will bring the user to the MAINTENANCE page.
See section MAINTENANCE UTILITY

Inspection Log
(Xe-145 Only)

Clicking this tab will bring the user to the INSPECTION LOG.
See section INSPECTION LOG UTILITY

Compressor
Information

Clicking this tab will bring the user to the COMPRESSOR INFORMATION page.
See section COMPRESSOR INFORMATION

Account

Clicking this tab will bring the user to the ACCOUNT page.
See section ACCOUNT MANAGEMENT

COMMAND BUTTONS
All pages show five command buttons (Start, Stop, Reset Alarm, Load and Unload), five dash board icons and current status of
the compressor.
Note: If the current user's account type does not have the necessary access rights to control the compressor via the web
interface, remote control from the web interface will be disabled at the controller.
Command Keys on the web pages command the compressor to perform actions as specified in the following table.
Key

Name

Function

Start

Start the Compressor

Stop

Stops the compressor. This button should be pressed instead of the E-Stop
for normal stopping operation.

Reset Alarm

Clears Warnings and Trips once the condition is corrected.

Load

Loads the compressor

Unload

Unloads the compressor

Note: Remote starting and stopping can be accomplished through the Ethernet Port. Panel power must be on, all utilities must be
running and permissive functions satisfied in order for the start-up from the web page.
DASHBOARD ICONS
Dashboard Icons are intended to be a quick at-a-glance view of system status. These icons are always visible regardless of the
folder/page selected.
The following table lists standard dashboard icons and their definition. Note that the color of these icons changes based on the
state set by the application while running.
Icons

Name

Descriptions

Alert

Illuminates when a Warning (flashes) or Trip (constant on) is sensed.

Remote Control

Remote control is enabled.

Service
Required

A Service reminder is nearing or has expired (i.e. an air or oil filter needs to
be changed)

Unloaded

Compressor is in the unloaded state

Loaded

Compressor is in the loaded state

Compressor Name, User Name, Print Button and Log Out button are always visible on the right side top of the page, regardless
of the tab selected.

Compressor
Name

The user can set the Compressor Name from the


Compressor Information tab. The user can use this host name
as a browser address for the web pages. A Compressor Name
is a domain address to log in the CONTROLLER web pages.

Logged in
User

Currently logged in user is shown on the right side top in each


web page.

Print Button

Click on Print button, to print the content on existing web


page.

Log Out
Button

Click on Logout button to terminate the current session.


Clicking this button will log out the current user and return to
the web page login screen.

10

11

HOME PAGE
The HOME tab shows information about the compressor operating parameters, total power consumption, running hours,
loaded hours, number of starts, etc.

Click on the pressure set point value in the white box, to change the Pressure Set Point value. Enter the new pressure set point
value and click on Confirm button. Pressure Set Point is only editable parameter for the Admin and User type accounts.
The user with View type account cant change these system parameters.

12

13

EVENT LOG UTILITY


The EVENT LOG tab shows the event log from the controller. This tab contains the event log details for the system events,
warnings and trips that have occurred and provides first-out indication. It also provides controls for filtering the list of events as
shown. Any time an event occurs, the system will send the display to the first event log page.
Each event is added into EVENT LOG with a date (mm/dd), time (hh:mm:ss) and the event value. This is the value that
triggered the event. The event labeled as 1 is the newest event.

Click on the dropdown control and select the number of events per page. If the events per page are 20, then previous events will
be available in the next page. Click on the Next button will display the previous twenty events.
The Event Type dropdown allows the user to filter the list of events by event type. The user can select the type of event from
the list by clicking the dropdown control. The events recorded and placed into one of three categories: Warnings,
Trips/Shutdowns, and System Events. EVENT LOG page highlights all the trips in red text, warnings in yellow text and system
events in the blue text.

14

The History dropdown allows the user to select the option to see the event log history for a selected time period. Click on the
dropdown command and select option Last 7 Days to see the event log of last 7 days.

The EVENT LOG will record the last 500 events. Once this 500 event limit has been reached the oldest events will be cleared and
the newest events will appear at the top of the event log.

15

MAINTENANCE UTILITY
MAINTENANCE tab contains the service schedule hours same as shown on the MAINTENANCE folder of controller.

This tab provides a service scheduler so that periodic maintenance reminders may be scheduled for consumable parts.
The user can change the working hours of maintenance counter after maintenance. Double click on values in the white box to
reset the timer and slide bar.

16

Click on the service scheduled hours in the white box, to change the maintenance counter. Enter the new value of working
duration and click on Confirm button.
Maintenance counter for the consumable parts is only editable for the Admin and User type accounts. The user with View
type account cant change these system parameters.
After changing the working hours of maintenance counter, click on the Reset Button of the selected variable to reset the slide
bar position.
The user can also change the contact address & contact number to call for parts or service. This is the number of the local
Ingersoll-Rand representative. Click on Confirm button to save the changes.
Note: Admin and User type accounts can only have an access to change the working duration of the maintenance counter
and Contact details. The View type account cant have an access to change these parameters.

17

COMPRESSOR INFORMATION
The COMPRESSOR INFORMATION tab contains the compressor name, compressor model number, compressor serial number,
rated capacity, rated pressure, rated voltage, running current, starting current, power requirement, motor service factor,
measuring units and Email (SMTP) settings.
COMPRESSOR IDENTIFICATION
The Host Name is shown as a Compressor Name on the right side top of each web page. The user can use this domain name
as a web page browser address to access the web pages. To change the existing host name, enter the new hostname in the
white box and click on Submit button.

Once the user will submit the new host name, the compressor name will be changed automatically on the next login.
Enter the Serial Number and Model Number as per the compressor nameplate, and click on Submit button to save these
compressor details.

18

EMAIL (SMTP) SETTINGS


If email notifications are to be used, the SMTP server settings must be obtained from IT and entered in this location. Enter the
SMTP Server & SMTP Account and then click on Submit button to save the SMTP settings.

Note: User account with access level Admin can only have an access to change the parameters in Compressor Identification
and Email (SMTP) Settings blocks. User account with access level User and VIEW cannot have an access to change these
parameters.

19

COMPRESSOR DETAILS
Enter the rated capacity, rated pressure, rated voltage, running current, starting current, nominal power in kW and main motor
service factor as per the data available in the compressor datasheet.
Click on the Submit button to save the compressor details.

UNIT TYPE
Click on the dropdown control and select the measurement unit type for the compressor parameters. Default unit type is
English.
Note: User account with access level Admin and User can only have an access to change these compressor parameters. User
account with access level VIEW can only monitor the data and the user can not have an access to change these parameters.

20

ACCOUNT MANAGEMENT
The administrator can create any number of users desired and assign each user one of three levels of access, as well as assigning
email notifications to various events that may occur.

ADD ACCOUNT
The ACCOUNT tab shows the list of accounts that currently exist which are listed by user name and access rights. Clicking on
an account will highlight that account in blue color. Click on ADD button to add an account with a specified access level for the
web page application. Enter the ADMIN password to proceed.

21

To generate a new user account; enter the unique username, password and select the user access rights. Click on Add Account
button will add the new user account into the list of user accounts. Only a user with ADMIN rights will be able to make a new
account or remove the existing accounts.
Select the user account from the list and click on X button to delete the selected user account.

22

MODIFY THE ACCESS LEVEL


User account with access level ADMIN can also change the access level of existing user accounts. To change the access level or
password of an existing user account, select the user account from the list and click the Change PW/AL button.

Click on the dropdown control and choose the new access level for selected user account. Again, click on Change PW/AL
button to save the changes in access level or password for selected user account.
Set the email address settings for the user by clicking on the Add button in the email list. Then type in the email address and
check the boxes for the type of alerts the user should receive. When finished, press the Submit button.

23

Note: User account with access level Admin can only have an access to make a new account or modify the access level of these
accounts. User account with access level User and VIEW cant have an access to make a new account or modify the user
accounts.
.

24

18,579

825,579

REVISIONS
ZONE

L3
FU7, 8, 9

100

X1:120V

X3:0V

L2

5L1

L3

5L3

H6:0V

122

X6:230V
300VA

125 C
118

50VA

119

L1 L2 L3
PE
PX6

3L1 3L2 3L3

PX1

FU1, 2, 3
4L1 4L2 4L3

L1 L2 L3

FD

01
02
55

N/O

1
2

283

283

284

284

206 BLU

206

207 BLU

207

294 WHI

294

295 BLK

295

AO1

K1A-2

AI1+
AI1AI2

285
P3-5

0V
+24V
DI1
DI2

P3-6

EN

P4-9

0V

P4-10

BLU

BRO

DRYER
RUN
CONTACT
(NOTE 3)

GND
121
120

101

101
127

A2

KM4 A1

112
113

1SV
(NOTE 3)
A2 K3 A1

312

116

PORO

150

K2

K1B A1

150

K3-1

12

A2

117

TX2

B
1L1 1L2 1L3

PX4

KM1

1A

200

201

2
3
6
7

1
2
3
4
5
6
7

Gnd

DI4

Gnd

DI5

Gnd

10

DI6

11

Gnd

12

DI7

13

Gnd

14

DI8

15

Gnd

16

TX4

Gnd

18

6
7

TX5

DI10

19

TX7

TX6

Gnd

V+

TX8

10

GND

Gnd
Sig1
V+
Gnd
Sig2

1
2

+
-

V+
Gnd
Sig3

PSU

V+
Gnd

ST

Sig4
V+
Gnd
Sig5
V+
Gnd
Sig5

BLK

RED
SL

BLK

RED

V+
Gnd
Sig6
V+
Gnd

YEL
BLK
RED
GRE
BRO
BLU
VIO

Sig6

309
MOTOR
RUNNING
CONTACT

U V W

Sig1

306
307
308
313
314
315

CTO

U V W

CWO
K1B-2

1
2
3
4
5
6

N/O

Gnd

Sig2

N/C

Gnd

N/O

Sig3

Gnd

N/C

Sig4

310

Gnd
Sig5
Gnd

MM

FM

17

P2

3L1 3L2 3L3

I> I> I>

104

DI3

DI9

COM3
P9

AIR COOLED

MCB5

TX3

GND

PX3

U W V

1
2
3
4
5
6
7
K1A-1
277
276
8
279
ES-3
9
278
280
10
KM1-1
ES-4
296
1
297
2

Gnd

P8

DR

U V W

FM

311

K1A A1

TX1

RC4

PE

FMP

1
2

11

A2

111

P7

60

COM

SDR

27

150

110

KM1 A1

P10

18

A2

121

GND

PX2

12

GR

1L1 1L2 1L3

KM1

PE

CDV3
KL1
1.3 1.2 1.1

Sig6

WATER COOLED

FD 55

294

BLK

295

WHI
ZNR
CAP

BLK

10

AO1

Sig7

AO+

Gnd

COM

P4

FD 60

WHI

Gnd

Sig8
Gnd

20

206

DESCRIPTION

A
B

79093
79367

79565

ORIGINAL RELEASE
COMMON WARNING OUTPUT 313 WAS 309.
COMMON WARNING OUTPUT 314 WAS 310.
COMMON WARNING OUTPUT 315 WAS 311.
DRYER POWER SUPP FEED FU7,8,9 WAS MCB6.
DRYER POWER SUPP FEED FU7,8,9 WAS MCB6.
CORRECTED SYMBOL FOR FU7,8,9
CHANGED SERIAL LINK PIN NUMBERS ON
CONTROLLER PLUG P9
REMOVED TERMINAL 303
REMOVED TERMINAL 303
CHANGED CONTROL WIRING FOR KM6,
JUMPERED DRYER TERMINALS 12 AND 15
REMOVED RC2, RC3
REMOVED RC3
MOVED RC1 FROM KM1 TO 4SV
CHANGED CDV TO CDV-1, ADDED CDV2 AND CDV3
ADDED TERMINALS 102 AND 150
ADDED TERMINALS 116 AND 117
BLK 7 WAS BLK 5.
RED 8 WAS RED 6.
REMOVED RATINGS FOR FU7, 8 & 9
REMOVED RATINGS FOR MCB1
REMOVED RATIINGS FOR 1T1

207

1D,5
1C,5
1D,5
1D,5
1D,5

AIR
COOLED

FD 02

208
209

ES-2

210

79759

DATE

DRAWN

APP'D

J. HUNT
2010SEP20
B.WARREN
2011JAN07 OWANESIAN B.WARREN

2011JAN31 C. LEAMON B.WARREN

2011MAY19 OWANESIAN B.WARREN


C. LEAMON

RST

213
214

AW1

215
216

AW2

217
218
219

CDE

220

13

221

14

MULTIPLE CDE ALARM


CONTACTS SHOULD BE
WIRED IN PARALLEL

DHP
(NOTE 3)

RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
257
22
258
23
259
24

274
275

3,C5

212

260
261
262
263
264
265
266
267
268
269
270
271

1,B5
1,B5
1,D8

RSP

211

236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253

1
2
3
4
5
6
7
8
11
12
13
14
15
16
17
18

2,B5
2,C5
3,B4

WATER
COOLED

FD 01

KL2

EB

120

DVF

1A

X5:0V

1L1 1L2 1L3

BLK
BRN

150

DI2

FMP

206
207

2.2 2.3

X4:200V

MCB4

CDV2
KL1
1.3 1.2 1.1

124
BLU

X7:0V

102

P1

FM
FD
MM
DR
DVF
1SV
4SV
CDV
RFI
CAB
BP
DOOR
PSU
T1
OV
SGNeV
EMC

LR

123

KM4

2A

T1
PE

150

4SV
MCB2

CDV1
KL1
1.3 1.2 1.1

115V

P5

L1

MCB1

RC1

103

P6

L3

H1:480V
H2:460V
H3:415V
H4:400V
H5:380V

K1B-1

102

24V

EMC

K2-1

128

150

151

151

L1

CONTROLLER

ES-1

101

PS1

105

6A

500VA

RFI

P3

L2

MCB3

BLU

DRYER
POWER
6L2
SUPPLY
(NOTE
3)
6L3
6L1

BRO

L1

GRE

ECN

1,B5
1,B5
1,B5
1,D8
3,D7
1,D8
1,B5

CONNECT CUSTOMER POWER TO LINE REACTOR TERMINALS


L1 L2 L3

REV

C
1AVPT

P
3APT
P
4APT
P
5CPT
P
6CPT
P
10APT

RED
7APT
BLK
WHI

EB

WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK

EB

WHI
BLK

EB
EB
EB
EB
EB

(NOTE 3)

2CTT

2ATT

4ATT

3CTT

(NOTE 4)

5DTT

(NOTE 3)

6DTT

(NOTE 3)

1ATT

23603574 REV D
SHEET 1 OF 3
A

402,81

WARNING: THE EXPORT OR REEXPORT OF THIS DRAWING OR A PRODUCT PRODUCED


BY THIS DRAWING IS SUBJECT TO U.S. EXPORT ADMINISTRATION REGULATIONS
AND OTHER APPLICABLE GOVERNMENT RESTRICTIONS OR REGULATIONS.

NOTES:

PROPRIETARY NOTICE

1. DECAL MUST CONFORM TO THE LATEST REVISION OF IR SPECIFICATION 92-8.95.

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET


INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND IS
GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY RECEPTION
AND RETENTION OF THE DRAWING ACCEPTS THE DRAWING IN CONFIDENCE
UNLESS OTHERWISE SPECIFIED:
AND AGREES THAT, EXCEPT AS AUTHORIZED IN WRITING BY
- REMOVE ALL BURRS AND SHARP CORNERS
INGERSOLL-RAND CO. IT WILL (1) NOT USE THE DRAWING OR ANY COPY
- WELD SYMBOLS TO BE IN ACCORDANCE
THEREOF OR THE CONFIDENTIAL OR TRADE SECRET INFORMATION
WITH ANSI/AWS A2.4
THEREIN; (2) NOT COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS
EITHER THE DRAWING OR THE CONFIDENTIAL OR TRADE SECRET
COPYRIGHT @ 2011
INFORMATION THEREIN; AND (4) UPON COMPLETION OF THE NEED TO
RETAIN THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
Ingersoll Rand
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.
ALL RIGHTS RESERVED

Ingersoll-Rand Industrial Technologies


18,18

615,81

825,81

THIRD ANGLE PROJECTION


DRAWN

J. HUNT
CHECKED

B.WARREN
APPROVED

B.WARREN

DATE

2010SEP20
DATE

2010SEP20
DATE

2010SEP20

TITLE

SCHEMATIC, ELECTRICAL WIRING


(VSD)
SIZE

A1

SCALE:

ESTIMATED WEIGHT

(KG UNLESS OTHERWISE SPECIFIED)

0.0
1.00 UNIT:

DWG NO.

23603574

R55-75

402,18

8
29-Jun-2011 11:25:20 (model D.1/D.3)

DO NOT SCALE DRAWING


DRAWING CONFORMS TO
ASME Y14.5M - 1994
CAD GENERATED DRAWING,
NO MANUAL REVISIONS ALLOWED

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

REV

SHEET

1 OF 3

18,579
18,579

826,579

LEGEND

LABEL

DESCRIPTION

OV
1ATT
1AVPT
1M1
1M2
1P1
1P2
1Qx
1SV
1T1
2ATT
2CTT
3APT
3CTT
4APT
4ATT
4SV
5CPT
5DTT
6CPT
6DTT
7APT
10APT
AW1
AW2
BP
CAB
CAP
CDE1
CDE2
CDE3
CDV1
CDV2
CDV3
CTO
CWO
DHP
DR
DVF
EB
EMC
ES
EXC
FD
FM
FMP
FUGND
HTRK1
K2
K3
LR
KM1
KM4
KM5
KM6
MCBx
MM
PE
PORO
PS1
PSU
PTC
R1
RCx
RFI
RSP
RST
SL
ST
T1
TH
ZNR

ZERO VOLTAGE
PACKAGE INLET TEMPERATURE
INLET VACUUM PRESSURE
DRYER COMPRESSOR MOTOR
DRYER FAN MOTOR
DRYER SAFTEY PRESSURE SWITCH
DRYER FAN PRESSURE SWITCH
DRYER CIRCUIT BREAKERS
INLET/BLOWDOWN VALVE
DRYER CONTROL POWER TRANSFORMER
AIREND DISCHARGE TEMPERATURE
INJECTED COOLENT TEMPERATURE
WET SUMP PRESSURE
COOLANT COOLER OUT TEMP.
PACKAGE DISCHARGE PRESSURE
PACKAGE DISCHARGE TEMPERATURE
WATER SHUT OFF VALVE (W/C ONLY)
COOLANT FILTER IN PRESSURE
DRYER DEWPOINT
COOLANT FILTER OUT PRESSURE
REFRIGERANT TEMPERATURE
PACKAGE A/C PRESSURE
REMOTE PRESSURE
AUXILIARY WARNING 1
AUXILIARY WARNING 2
BACKPANEL
CABINET
CAPACITOR
CONDENSATE DRAIN ERROR (M/S)
CONDENSATE DRAIN ERROR (DRYER FILTER)
CONDENSATE DRAIN ERROR (DRYER DRAIN)
CONDENSATE NO LOSS DRAIN VALVE (M/S)
CONDENSATE NO LOSS DRAIN VALVE (DRYER FILTER)
CONDENSATE NO LOSS DRAIN VALVE (DRYER DRAIN)
COMMON TRIP OUTPUT
COMMON WARNING OUTPUT
DRYER HIGH PRESSURE SWITCH
DRIVE, MAIN MOTOR
DRIVE VENTILATION FAN
EARTHING BAR
EMC FILTER BOARD
EMERGENCY STOP BUTTON
EXTERNAL COMMUNICATIONS
DRIVE, BLOWER MOTOR
FAN MOTOR
FAN MOTOR PROTECTOR
FUSES
GROUND
PANEL SPACE HEATER
RUN RELAY
DRIVE FAULT RELAY
BLOWER DRIVE CONTROL RELAY
LINE REACTOR
BLOWER MOTOR CONTACTOR
DRIVE FAN MOTOR CONTACTOR
DRYER COMPRESSOR MOTOR CONTACTOR
DRYER FAN MOTOR CONTACTOR
CIRCUIT BREAKERS
MAIN MOTOR
PROTECTED EARTH
POWER OUTAGE RESTART OPTION
LINE FILTER TERMINAL STRIP
POWER SUPPPLY UNIT
MOTOR WINDING THERMISTOR
DRYER PRESSURE SWITCH RELAY
ARC SUPPRESSOR
RADIO FREQUENCY INTERFACE
REMOTE STOP
REMOTE START
SERIAL LINK
SERVICE TOOL CONNECTOR
CONTROL POWER TRANSFORMER
THERMOSTAT
ZENER DIODE

WIRE NUMBER DESIGNATION LEGEND


NUMBERS
FUNCTION
WIRE COLOR
1 - 99

POWER

BLACK

100 - 199

AC CONTROL

RED

100 - 199

GROUNDED AC

WHITE OR LIGHT BLUE

200 - 299

DC CONTROL

BLUE

300 - 399

AUXILIARY

ORANGE

GND

GROUND

GREEN / YELLOW

WIRE COLOR LEGEND


LABEL DESCRIPTION
BLK

BLACK

BLU

BLUE

BRO

BROWN

GRE

GREEN

PIN

PINK

RED

RED

VIO

VIOLET

WHI

WHITE

YEL

YELLOW

TH
(29 C)
T1

100

300

MCB9

302

303

KM4-2

304
151

301

3A

HTR1

HTR2

110/120V
50/60Hz
305

305

NOTES:
1. FACTORY SUPPLIED AS SHOWN BY CONNECTION TO OUTPUT
OF CONTROL TRANSFORMER T1. WIRE TO TERMINAL
NUMBERS 100 & 151.
2. ALTERNATIVELY THE SUPPLY MAY BE TAKEN FROM AN
INDEPENDENT SOURCE; IN THAT CASE, FACTORY SUPPLIED
CONNECTION MUST BE DISCONNECTED.
3. ENSURE PARALLEL CONNECTION OF HEATERS.

TH
(29 C)
300

MCB9

302

KM4-2

303

T
304

301

3A

HTR1

HTR2

220/230V
50/60Hz
305

305

NOTES:
1. APPROVED FUSED DISCONNECT OR CIRCUIT BREAKER PER LOCAL ELECTRICAL
CODES MUST BE PROVIDED BY THE CUSTOMER.

NOTES:
1. CONNECTIONS FOR USE ON 200/230V
SYSTEMS. THE SUPPLY IS INDEPENDENT
OF THE MAIN COMPRESSOR. THE CUSTOMER
MUST PROVIDE AN ISOLATOR / DISCONNECT
SWITCH ADJACENT TO THE MACHINE FOR
THIS SUPPLY. IN THAT CASE, FACTORY SUPPLIED
CONNECTION MUST BE DISCONNECTED.
2. ENSURE SERIES CONNECTION OF HEATERS.

2. SENSOR 3CTT IS NOT INSTALLED, IF THE COMPRESSOR IS WATER COOLED


WITH HOT SIDE THERMAL CONTROL VALVE
3. ONLY USED ON UNITS WITH INTEGRATED DRYERS.
4.

INDICATES OPTIONAL COMPONENTS.

5.

INDICATES OPTIONAL FIELD WIRED COMPONENTS.

23603574 REV D
SHEET 2 OF 3

636,54

825,54

PROPRIETARY NOTICE
THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET
INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND
IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY
RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE
DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS
AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)
NOT USE THE DRAWING OR ANY COPY THEREOF OR THE
CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT
COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE
DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION
THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN
THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

SCHEMATIC, ELECTRICAL WIRING


(VSD)
SIZE

A1

SCALE:

DWG NO.

23603574

SHEET

1.00

636,18

18,18
18,18

8
29-Jun-2011 11:25:20 (model D.1/D.3)

TITLE

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

REV

2 OF 3

18,579
18,579

826,579

6L1

TO FU7, 8, 9

6L2
6L3
PE

1Q2

1Q1

F1

I> I> I>

F1

I> I> I>


1T1
100VA

KM5

0V 12V24V

KM6

KM5

1/24

2/24

U2 V2 W2

L2R

U1 V1 W1

L1R

F2

A2

A2

KM5

A2

KM6
A1

A1

15

A1

R1

1M1

1M2

1/24

X1

X1

X1

X1

X1

X1

X1

X1

X1

18

X1

16

12

12
X1

X1

X1

X2

X2

PE

11

12

13

14

15

16

17

18

19

20

21

22

M
3~

U V W PE

8 9

U V W PE

X1

5 6 7 PE-10

11

X1

2 3 4 PE-1

X1

X1

X2

X1

X1

X1

1/24

21

13

R1

R1

12

22

14

12

22

14

24

1P2

1P1

M
3~

23603574 REV D
SHEET 3 OF 3

636,54

825,54

PROPRIETARY NOTICE
THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET
INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND
IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY
RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE
DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS
AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)
NOT USE THE DRAWING OR ANY COPY THEREOF OR THE
CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT
COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE
DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION
THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN
THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

SCHEMATIC, ELECTRICAL WIRING


(VSD)
SIZE

A1

SCALE:

DWG NO.

23603574

SHEET

1.00

636,18

18,18
18,18

8
29-Jun-2011 11:25:20 (model D.1/D.3)

TITLE

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

REV

3 OF 3

18,579

825,579

REVISIONS
ZONE

REV

A
B

1C,5
1D,6
1D,5
1D,4
1D,3

ALTERNATE

L1

T1

MCB1
EB

L3

3L3

L1

3L1

MCB2

6A

KM1-2

103

150

A2

KM4
A2

6L1 6L2 6L3

DRYER
POWER
SUPPLY
(NOTE 3)

A2

FMP

A2

150
I> I> I>

NOTE 8
11

DRYER
RUN
CONTACT
(NOTE 3)

U V W

U2
V2
W2

U1 V1 W1 (12 LEAD
U5 V5 W5 LOW V)

W2 U2 V2 (12 LEAD
W6 U6 V6 LOW V)

(12 LEAD
U1 V1 W1 HIGH V OR
6 LEAD)

W6 U6 V6

FM

(12 LEAD
HIGH V)

12

311

105

Gnd
DI9
Gnd

DI11

KM1-1

118

5SV

150

9SV

K3-1

110

KM3-1

119 KM3-2
120 KM2-1

111
112
113

115

312

DI12

TX1

Gnd

114

10SV

Gnd

DI13

KM4 A1

150

A2

K3

1A

TX2

TX3

TX4

Gnd
DI14
Gnd
DI15
Gnd
DI16

TX5

TX6

Gnd
V+
Gnd

(NOTE 3)

Sig1
V+

(NOTE 3)

Gnd
Sig2

116
A1

PORO

150

FU1, 2, 3

117

L1 L2 L3

WHT

PE

WHT

18
27
FD

BLK

01
02

BLK
U1 V1 W1

55

283

216
216 BLU

217 BLU
294 WHI

217

Gnd
Sig4
V+
Gnd
Sig5
V+
Gnd
Sig6
V+
Sig7

285

Sig1

P3-13

Gnd

P3-14

295 BLK

WHI

294

BLK

295

WHI
ZNR
CAP

303
MOTOR
RUNNING
CONTACT

DETAIL B
NOTE 8

CT RATIO
200:5

GND

304

CTO
KM1-4
CWO

BLK
305
306
307
308
309
310

10

AO1

AO+

Sig2
Gnd
Sig3
Gnd

COM

1
2
3
4
5
6

N/O

Gnd
Gnd

C
N/C

Sig4
Sig5

N/O

Sig6

P2

FM

10

284

U W V

NOTE 7

TX8

Gnd

U V W

DETAIL A

K3-1

PE

MM

V+

P4

60

Sig3

P8

FR1
(60Hz
I> I> I> ONLY)

201

Gnd

TX7

PSU

GND

12

200

P7

WHT

V+

P10

104

4L1 4L2 4L3

DI10
Gnd

2L1 2L2 2L3

U5
V5
W5
(12 LEAD, HIGH V ONLY)

MOTOR SIZE
55-75kW(ALL)

KM3 A1

11SV

KM4

BLK

DI8

W2 U2 V2 (6 LEAD)

MM

CT1, CT2, CT3

DI7
Gnd

1SV

MCB5

KM2

A1

RC3

2L1 2L2 2L3

FR1
(50Hz
ONLY)

Gnd

P1

KM1 A1
RC2

KM3

Gnd

105

FR1 A1
RC1

A2

KM1

DI5

115V

CDV3
KL1
1.3 1.2 1.1

(60Hz ONLY)

KM2

Gnd

105

CDV2
KL1
1.3 1.2 1.1

150

L1 L2 L3

CONTROLLER

DI6

150

X3:0V

NOTE 9

FU7,8,9

K2-1

CDV1
KL1
1.3 1.2 1.1

L3
L2
L1

L1 L2 L3

105

RC4

105
N/O
102
C
N/C

K2

102

4SV

L3
L2
L1

TRM

101

ES-1

101

Gnd

Sig8

N/C

Gnd

208
209

(NOTE 6)

213 214
215
FR1
PTC1 PTC2 PTC3
212
95

216
217

15 218
16 219
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235

13
P

14

274
17
275
18

DHP
(NOTE 3)

MULTIPLE CDE ALARM


CONTACTS SHOULD
BE WIRED IN PARALLEL

CDE

1,C8
2
3,C5

DATE

DRAWN

79093 ORIGINAL RELEASE


2010SEP27
J. HUNT B.WARREN
79565 MOVED RC1 AND RC2, ADDED RC3
2011MAR10 C. LEAMON B. WARREN
ADDED RC4
CHANGED CDV TO CDV1, ADDED CDV2 AND CDV3
ADDED TERMINAL NUMBERS TO FR1
CHANGED NOTE TO SAY "PARALLEL" INSTEAD
OF "SERIES"
CHANGED MCB6 TO FU7,8,9 AND CHANGED SYMBOL
UPDATED CT RATIO TABLE
MOVED 3ATS AND ADDED K4 AND RC5
ADDED KM1-5 AND K4-1 CONTACTS
CHANGED "MCB6" TO "FU7,8,9"
CHANGE WIRING FOR TERMINAL 15 TO JUMP TO
TERMINAL 12
ADDED INLET VALVE HEATER (IVH)
2011JUN10 OWANESIAN B.WARREN
79852 "TO FU7,8,9" WAS "TO MCB6".
CONT WAS SGN
REMOVED RATING FOR MCB1 AND ADDED ALT.
ADDED CONNECTION DIAGRAM FOR 12 LEAD MOTOR
REMOVED RATING FOR FU7,8,9
ADDED CONT AND TRM TO LEGEND
NOTE 8 37-75KW WAS 55-57KW
575V WIRING DETAIL 37-75KW WAS 55-75KW
REMOVED RATING FOR 1T1

RST
RLL
RLE
RLU
AW1

AW2
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI

1AVPT

P
3APT
P
4APT
P
5CPT
P
6CPT
P
10APT

RED
7APT
BLK
WHI

EB

WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK

EB

WHI
BLK

EB
EB
EB
EB
EB

402,81

WARNING: THE EXPORT OR REEXPORT OF THIS DRAWING OR A PRODUCT PRODUCED


BY THIS DRAWING IS SUBJECT TO U.S. EXPORT ADMINISTRATION REGULATIONS
AND OTHER APPLICABLE GOVERNMENT RESTRICTIONS OR REGULATIONS.

NOTES:
1. DECAL MUST CONFORM TO THE LATEST REVISION OF IR SPECIFICATION 92-8.95.

PROPRIETARY NOTICE

(NOTE 3)
P

2CTT

2ATT

4ATT

3CTT

(NOTE 2)

5DTT

(NOTE 3)

6DTT

(NOTE 3)

1ATT

(NOTE 2)

DO NOT SCALE DRAWING


DRAWING CONFORMS TO
ASME Y14.5M - 1994
CAD GENERATED DRAWING,
NO MANUAL REVISIONS ALLOWED

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET


INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND IS
GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY RECEPTION
AND RETENTION OF THE DRAWING ACCEPTS THE DRAWING IN CONFIDENCE
UNLESS OTHERWISE SPECIFIED:
AND AGREES THAT, EXCEPT AS AUTHORIZED IN WRITING BY
- REMOVE ALL BURRS AND SHARP CORNERS
INGERSOLL-RAND CO. IT WILL (1) NOT USE THE DRAWING OR ANY COPY
- WELD SYMBOLS TO BE IN ACCORDANCE
THEREOF OR THE CONFIDENTIAL OR TRADE SECRET INFORMATION
WITH ANSI/AWS A2.4
THEREIN; (2) NOT COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS
EITHER THE DRAWING OR THE CONFIDENTIAL OR TRADE SECRET
COPYRIGHT @ 2011
INFORMATION THEREIN; AND (4) UPON COMPLETION OF THE NEED TO
RETAIN THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
Ingersoll Rand
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.
ALL RIGHTS RESERVED

Ingersoll-Rand Industrial Technologies


18,18

615,81

825,81

THIRD ANGLE PROJECTION


DRAWN

J. HUNT
CHECKED

B.WARREN
APPROVED

B. WARREN

DATE

2010SEP27
DATE

2010SEP27
DATE

2010SEP27

TITLE

SCHEMATIC, ELECTRICAL WIRING


(FS-SD)
SIZE

A1

SCALE:

ESTIMATED WEIGHT

(KG UNLESS OTHERWISE SPECIFIED)

0.0
1.00 UNIT:

DWG NO.

23603582

R55-75

402,18

APP'D

23603582 REV C
SHEET 1 OF 3

29-Jun-2011 12:46:57 (model C.2/C.3)

FD 01
FD 02
ALTERNATE
SEE DETAIL B

DESCRIPTION

RSP

236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253

260
261
262
263
264
265
266
267
268
269
270
271

216
217

FMP

257
22
258
23
259
24
1
2
3
4
5
6
7
8
11
12
13
14

2B,3
3,C7
1,D8

96

KL2

0.5A

L3
L2
L1

X1:115V

H1:575V
H2:460V
H3:415V
H4:380V
H5:230V
H6:220V
H7:0V

3L1

100

MCB3

7
8
9
10
11
12
13
14

2.2 2.3

FM
MM
OV
T1
CONT
1SV
4SV
5SV
9SV
CDV
CAB
BP
DOOR
PSU

3L3

DI4

P5

L3

(NOTE 6)

P3

FU10,11

P6

PE

24V

L1 L2 L3

1C,8
1A,8
2B,4
2C,5
3C,7
3B,4

ES-2

ECN

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

REV

SHEET

1 OF 3

18,579
18,579

826,579

575V WIRING

WIRE NUMBER DESIGNATION LEGEND


NUMBERS
FUNCTION
WIRE COLOR
1 - 99

POWER

BLACK

100 - 199

AC CONTROL

RED

100 - 199

GROUNDED AC

WHITE

200 - 299

DC CONTROL

BLUE

300 - 399

AUXILIARY

ORANGE

400-499

AC POWER

RED

GND

GROUND

GREEN / YELLOW

FOR 37-75KW: LOW AMBIENT OPTION,


5L3
5L2
5L1

L3
L2
L1

H3

AT1

X3

H2

X2

H1

X1

FU4, 5, 6
KM4

DETAIL C

2L1 2L2 2L3

NOTE 9

1L1

WIRE COLOR LEGEND


LABEL DESCRIPTION
BLACK

BLU

BLUE

BRO

BROWN

GRE

GREEN

PIN

PINK

RED

RED

VIO

VIOLET

WHI

WHITE

YEL

YELLOW

402

DETAIL D

K4-1

30A

406
HEATER
CIRCUIT,
CUSTOMER
SUPPLIED
120/1/60
OR
240/1/50

NOTE 10

3ATS
(4 C / 40 F)

KM1-3

LOW AMBIENT
OPTION

KM1-5

TH
(29 C / 85 F)
405

403

403

404

403

403

A1

BLK

1L2/N

MCB4

SSH

SSH

DMH

K4

DESCRIPTION
ZERO VOLTAGE
PACKAGE INLET TEMPERATURE
INLET VACUUM PRESSURE
DRYER COMPRESSOR MOTOR
DRYER FAN MOTOR
DRYER SAFETY PRESSURE SWITCH
DRYER SAFETY FAN PRESSURE SWITCH
DRYER CIRCUIT BREAKERS
LOAD VALVE
1SV HEAT TRACE
DRYER CONTROL POWER TRANSFORMER
AIREND DISCHARGE TEMPERATURE
INJECTED COOLENT TEMPERATURE
WET SUMP PRESSURE
AMBIENT TEMP THERMOSTAT
COOLANT COOLER OUT TEMP.
PACKAGE DISCHARGE PRESSURE
PACKAGE DISCHARGE TEMPERATURE
WATER SHUT OFF VALVE (W/C ONLY)
COOLANT FILTER IN PRESSURE
DRYER DEWPOINT
MODULATION VALVE
COOLANT FILTER OUT PRESSURE
REFRIGERANT TEMPERATURE
PACKAGE A/C PRESSURE
MOISTURE SEPARATOR DRAIN VALVE
REMOTE PRESSURE
DRYER FILTER DRAIN VALVE
DRYER DRAIN VALVE
AUTO TRANSFORMER
AUXILIARY WARNING 1
AUXILIARY WARNING 2
BASE LEVEL HEATER
BACKPANEL
CABINET
CAPACITOR
CONDENSATE DRAIN ERROR (M/S)
CONDENSATE DRAIN ERROR (DRYER FILTER)
CONDENSATE DRAIN ERROR (DRYER DRAIN)
CONDENSATE NO LOSS DRAIN VALVE (M/S)
CONDENSATE NO LOSS DRAIN VALVE (DRYER FILTER)
CONDENSATE NO LOSS DRAIN VALVE (DRYER DRAIN)
COMMON TRIP OUTPUT
COMMON WARNING OUTPUT
Xe CONTROLLER
CURRENT TRANSFORMER
DRYER HIGH PRESSURE SWITCH
DRIVE MOTOR HEATER
EARTHING BAR
EMERGENCY STOP BUTTON
FAN DRIVE
FAN MOTOR
FAN MOTOR HEATER
FAN MOTOR PROTECTOR
MAIN MOTOR OVERLOAD
FUSES
PHASE MONITOR RELAY
BLOWER DRIVE CONTROL RELAY
MAIN CONTACTOR
DELTA CONTACTOR
START CONTACTOR
FAN MOTOR CONTACTOR
DRYER COMPRESSOR CONTACTOR
DRYER FAN MOTOR CONTACTOR
CIRCUIT BREAKERS
MAIN MOTOR
MOISTURE SEPARATOR HEAT TRACE
OIL SUMP HEATER
PROTECTED EARTH
POWER OUTAGE RESTART OPTION
POWER SUPPPLY UNIT
MOTOR WINDING THERMISTOR
DRYER PRESSURE SWITCH RELAY
ARC SUPPRESSOR
REMOTE LOAD ENABLE
REMOTE LEAD LAG
REMOTE LOAD/UNLOAD
REMOTE STOP
REMOTE START
SOLID STATE RELAYS
STARTER SPACE HEATER
CONTROL POWER TRANSFORMER
THERMOSTAT
POWER TERMINAL
ZENER DIODE
INLET VALVE HEATER

FMH

1SVT

MSHT

OSH

OSH

OSH

BLH

IVH

A2

LABEL
OV
1ATT
1AVPT
1M1
1M2
1P1
1P2
1Qx
1SV
1SVT
1T1
2ATT
2CTT
3APT
3ATS
3CTT
4APT
4ATT
4SV
5CPT
5DTT
5SV
6CPT
6DTT
7APT
9SV
10APT
10SV
11SV
AT1
AW1
AW2
BLH
BP
CAB
CAP
CDE1
CDE2
CDE3
CDV1
CDV2
CDV3
CTO
CWO
CONT
CTx
DHP
DMH
EB
ES
FD
FM
FMH
FMP
FR1
FUK2
K3
KM1
KM2
KM3
KM4
KM5
KM6
MCB
MM
MSHT
OSH
PE
PORO
PSU
PTCx
R1
RCx
RLE
RLL
RLU
RSP
RST
SS
SSH
T1
TH
TRM
ZNR
IVH

LEGEND

RC5

410

410

410

410

NOTES:
1. APPROVED FUSED DISCONNECT OR CIRCUIT BREAKER PER LOCAL ELECTRICAL CODES
MUST BE PROVIDED BY THE CUSTOMER.

2. SENSORS 1ATT AND 3CTT ARE ONLY USED WHEN THE SMART THERMAL VALVE IS INSTALLED.
3. ONLY USED ON UNITS WITH INTEGRATED DRYERS.
4.

INDICATES OPTIONAL COMPONENTS.

INDICATES OPTIONAL FIELD WIRED COMPONENTS.

6. REMOVE JUMPER(S) WHEN CORRESPONDING OPTION HAS BEEN PURCHASED.


7. 60Hz WYE-DELTA STARTER UNITS REQUIRE CURRENT TRANSFORMERS (CT) TO BE USED
WITH MAIN MOTOR OVERLOAD. SEE DETAIL A.
8. A VARIABLE SPEED DRIVE IS REQUIRED FOR 37-75kW UNITS WITH LOW AMBIENT OPTION.
SEE DETAIL B.
9. A THREE PHASE TRANSFORMER IS REQUIRED FOR 575V 60 Hz UNITS WITH A VARIABLE SPEED
DRIVE CONTROLLING THE BLOWER MOTOR. SEE DETAIL C.
10. THREMOSTAT AND TEMPERATURE SWITCH CONTACTS ARE NORMALLY CLOSED AND WILL OPEN
WHEN THE TEMPERATURE MEETS OR EXCEEDS THE INDICATED SET POINT. SEE DETAIL D.

23603582 REV C
SHEET 2 OF 3

636,54

825,54

PROPRIETARY NOTICE
THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET
INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND
IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY
RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE
DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS
AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)
NOT USE THE DRAWING OR ANY COPY THEREOF OR THE
CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT
COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE
DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION
THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN
THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

SCHEMATIC, ELECTRICAL WIRING


(FS-SD)
SIZE

A1

SCALE:

DWG NO.

23603582

SHEET

1.00

636,18

18,18
18,18

8
29-Jun-2011 12:46:57 (model C.2/C.3)

TITLE

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

REV

2 OF 3

18,579
18,579

826,579

6L1

TO FU7,8,9

6L2
6L3
PE

1Q2

1Q1

F1

F1

C
I> I> I>

I> I> I>


1T1
100VA

KM5

0V 12V24V

KM6

KM5

1/24

2/24

U2 V2 W2

L2R

U1 V1 W1

L1R

F2

A2

A2

KM5

A2

KM6

R1

A1

A1

15

A1

24

22

1M2

X1

X1

X1

X1

X1

22

1/24

X1

13

14

15

16

17

18

19

20

21

22

X1

18

X1

16

1/24

X1

12

X1

13

12

11

X1

X1

X1

X1

X2

X2

PE

U V W PE

8 9

11

14

21

1/24

1M1

X1

5 6 7 PE-10

U V W PE

M
3~

X1

X1

X2

X1

X1

X1

2 3 4 PE-1

12

R1

R1

14

1P2

1P1

M
3~

23603582 REV C
SHEET 3 OF 3

636,54

825,54

PROPRIETARY NOTICE
THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET
INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND
IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY
RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE
DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS
AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)
NOT USE THE DRAWING OR ANY COPY THEREOF OR THE
CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT
COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE
DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION
THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN
THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

SCHEMATIC, ELECTRICAL WIRING


(FS-SD)
SIZE

A1

SCALE:

DWG NO.

23603582

SHEET

1.00

636,18

18,18
18,18

8
29-Jun-2011 12:46:57 (model C.2/C.3)

TITLE

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

REV

3 OF 3

18,579

825,579

REVISIONS
ZONE

REV

C5
D6
D5
D3

L3
L1

3L1

MCB1
EB

L3

3L3

L1

3L1

T1
X1:115V

H1:575V
H2:460V
H3:415V
H4:380V
H5:230V
H6:220V
H7:0V

100

MCB3

101

101

6A

KM1-2

103

102

RC4

CDV1
KL1
1.3 1.2 1.1

4SV

150

RC1

NOTE 9
A2

KM4
A2

K2

A1

A2

KM1 A1

A2

KM4 A1

150

U1

(12 LEAD U1 V1 W1
LOW V) U5 V5 W5

TRM

(12 LEAD
HIGH V OR U1 V1 W1
6 LEAD)

DI9
Gnd

119

A1
150
A2
121
IN1
K1-1
IN2
118
97
119
98
120
13
113
14

I> I> I>

11

DRYER RUN
CONTACT
(NOTE 3)

FM

12

W2 U2 V2 (12 LEAD
W6 U6 V6 LOW V)

111
112
113
14

U1

120

13

114
115

9SV

1A

KM4

K3

TX2

TX3

Gnd
Gnd
DI15

TX4

Gnd
DI16

6
7

Gnd

TX5

V+
TX6

Gnd

Gnd
Sig2

116

A1

117

V+

TX7

TX8

10

GND

Gnd
Sig3
V+

2L1 2L2 2L3

FU1, 2, 3

MM
4L1 4L2 4L3

L1 L2 L3
PE

104
GND

18
FD

01
02

1 2 3 4 5 6 7 8

55

V+
Gnd
Sig6
V+
Sig7

285
216 BLU

216

217 BLU

217

294 WHI

Sig1

P3-13

Gnd

P3-14

295 BLK

WHI

294

BLK

295

WHI
ZNR
CAP

303
MOTOR
RUNNING
CONTACT
304

CTO
KM1-4
CWO

BLK
305
306
307
308
309
310

10

AO1

AO+

COM

Sig2
Gnd
Sig3
Gnd

1
2
3
4
5
6

N/O

Gnd
Gnd

C
N/C

Sig4
Sig5

N/O

Sig6

P2

DETAIL B
NOTE 8

DETAIL A

Gnd

U W V

FM

Sig5

284

U V W

SMC-3 DIP SWITCHES

K3-1

PE

P4

60

201

P8

27

Sig4
Gnd

PSU
283

12

200

Gnd
V+

P7

U5
V5
W5
(12 LEAD, HIGH V ONLY)

DI14

V+

U1

9 10 11 12 13 14 15 16

Sig1

PORO

150

DI13

(NOTE 3)

11SV
A2

DI12

(NOTE 3)

10SV

MCB5

TX1

Gnd

311

312

97

5SV

150
K3-1

Gnd

U1
98

1SV

150

U V W

W2 U2 V2 (6 LEAD)

110

NOTE 8

102

(12 LEAD
HIGH V)

DI11

KM1-1

118

DI10
Gnd

P10

U2
V2
W2

T6 T4 T5
12 8 10

W6 U6 V6

Gnd

P5

3
5

T1 T2 T3
2 4 6

DI8

102

102

RC3

DRYER
POWER
SUPPLY
(NOTE 3)

DI7

P1

FMP

KM1

K1

A1

RC2

2L1 2L2 2L3

Gnd

Gnd

Sig8

N/C

Gnd

ES-2

7
8
(NOTE 6)
9
213 214
215
10
K2-1
PTC1 PTC2 PTC3
212
11
96
95
12
216
216
13
FMP
FD 01
217
217
14
FD 02
13
15 218
DHP
ALTERNATE
P
(NOTE
3)
SEE
DETAIL B
14
16 219
220
MULTIPLE CDE ALARM
17
CDE CONTACTS SHOULD BE
221
18
WIRED IN PARALLEL
222
19
RSP
223
20
224
21
RST
225
22
226
23
227
RLL
24
228
25
RLE
229
26
230
27
231
RLU
28
232
29
AW1
233
30
234
31
AW2
235
32
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI

236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253

257
22
258
23
259
24
1
2
3
4
5
6
7
8
11
12
13
14

260
261
262
263
264
265
266
267
268
269
270
271

274
17
275
18

2-B3
3,D7
1,D8

1,C8
1,B8
2
3,C5

DATE

DRAWN

79093 ORIGINAL RELEASE


2010SEP27
J. HUNT B.WARREN
79565 MOVED RC3
2011MAR11 C. LEAMON B.WARREN
ADDED RC4
CHANGED CDV TO CDV1, ADDED CDV2 AND CDV3
CHANGED NOTE TO SAY "PARALLEL" INSTEAD
OF "SERIES"
CHANGED MCB6 TO FU7,8,9 AND CHANGED SYMBOL
MOVED 3ATS AND ADDED K4 AND RC5
ADDED KM1-5 AND K4-1 CONTACTS
CHANGE WIRING FOR TERMINAL 15 TO JUMP TO
TERMINAL 12
ADDED INLET VALVE HEATER (IVH)
2011JUN10 OWANESIAN B.WARREN
79852 "TO FU7,8,9" WAS "TO MCB6".
CONT WAS SGN
C. LEAMON
REMOVED RATING FOR MCB1 AND ADDED ALT.
ADDED CONNECTION DIAGRAM FOR 12 LEAD MOTOR
REMOVED RATING FOR FU7,8,9
ADDED CONT AND TRM TO LEGEND
NOTE 8 37-75KW WAS 55-57KW
575V WIRING DETAIL 37-75KW WAS 55-75KW
REMOVED RATING FOR 1T1

EB

WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK

EB

WHI
BLK

EB
EB
EB
EB
EB

P
3APT
P
4APT
P
5CPT
P
6CPT
P
10APT

(NOTE 3)
P

2CTT

2ATT

4ATT

3CTT

(NOTE 2)

5DTT

(NOTE 3)

6DTT

(NOTE 3)

1ATT

(NOTE 2)

23603590 REV C
SHEET 1 OF 3

402,81

WARNING: THE EXPORT OR REEXPORT OF THIS DRAWING OR A PRODUCT PRODUCED


BY THIS DRAWING IS SUBJECT TO U.S. EXPORT ADMINISTRATION REGULATIONS
AND OTHER APPLICABLE GOVERNMENT RESTRICTIONS OR REGULATIONS.

NOTES:
1. DECAL MUST CONFORM TO THE LATEST REVISION OF IR SPECIFICATION 92-8.95.

PROPRIETARY NOTICE

DO NOT SCALE DRAWING


DRAWING CONFORMS TO
ASME Y14.5M - 1994
CAD GENERATED DRAWING,
NO MANUAL REVISIONS ALLOWED

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET


INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND IS
GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY RECEPTION
AND RETENTION OF THE DRAWING ACCEPTS THE DRAWING IN CONFIDENCE
UNLESS OTHERWISE SPECIFIED:
AND AGREES THAT, EXCEPT AS AUTHORIZED IN WRITING BY
- REMOVE ALL BURRS AND SHARP CORNERS
INGERSOLL-RAND CO. IT WILL (1) NOT USE THE DRAWING OR ANY COPY
- WELD SYMBOLS TO BE IN ACCORDANCE
THEREOF OR THE CONFIDENTIAL OR TRADE SECRET INFORMATION
WITH ANSI/AWS A2.4
THEREIN; (2) NOT COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS
EITHER THE DRAWING OR THE CONFIDENTIAL OR TRADE SECRET
COPYRIGHT @ 2011
INFORMATION THEREIN; AND (4) UPON COMPLETION OF THE NEED TO
RETAIN THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
Ingersoll Rand
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.
ALL RIGHTS RESERVED

Ingersoll-Rand Industrial Technologies


18,18

615,81

825,81

THIRD ANGLE PROJECTION


DRAWN

J. HUNT
CHECKED

B.WARREN
APPROVED

B. WARREN

DATE

2010SEP27
DATE

2010SEP27
DATE

2010SEP27

TITLE

SCHEMATIC, ELECTRICAL WIRING


(FS-SS)
SIZE

A1

SCALE:

ESTIMATED WEIGHT

(KG UNLESS OTHERWISE SPECIFIED)

0.0
1.00 UNIT:

DWG NO.

23603590

R55-75

402,18

APP'D

1AVPT

RED
7APT
BLK
WHI

NOTE 7

29-Jun-2011 12:44:15 (model C.1/C.4)

C8
2-C4
2-C5
3-C4

DESCRIPTION

KL2

L3
L2
L1

6L1 6L2 6L3

Gnd

Gnd

U1

L1 L2 L3

115V

CDV3
KL1
1.3 1.2 1.1

L3
L2
L1

FU7,8,9

DI5

102

CDV2
KL1
1.3 1.2 1.1

150

Gnd

DI6

150

X3:0V

DI4

CONTROLLER

208
209

2.2 2.3

FM
MM
OV
T1
CONT
1SV
4SV
5SV
9SV
CDV
CAB
BP
DOOR
PSU

3L3

ES-1

P3

FU10,11

24V

PE

ALTERNATE

P6

L1 L2 L3

A
B

ECN

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

REV

SHEET

1 OF 3

18,579
18,579

826,579

1 - 99

POWER

BLACK

100 - 199

AC CONTROL

RED

100 - 199

GROUNDED AC

WHITE

200 - 299

DC CONTROL

BLUE

300 - 399

AUXILIARY

ORANGE

400-499

AC POWER

RED

GND

GROUND

GREEN / YELLOW

575V WIRING

FOR 37-75KW: LOW AMBIENT OPTION,


5L3
5L2
5L1

L3
L2
L1

H3

AT1

X3

H2

X2

H1

X1

FU4, 5, 6
KM4

DETAIL C

2L1 2L2 2L3

NOTE 9

WIRE COLOR LEGEND


LABEL DESCRIPTION
BLACK

BLU

BLUE

BRO

BROWN

GRE

GREEN

PIN

PINK

RED

RED

VIO

VIOLET

WHI

WHITE

YEL

YELLOW

1L2/N

402

DETAIL D

K4-1
406

30A

HEATER
CIRCUIT,
CUSTOMER
SUPPLIED
120/1/60
OR
240/1/50

KM1-3

LOW AMBIENT
OPTION

KM1-5

TH
(29 C / 85 F)
405

NOTE 10

3ATS
(4 C / 40 F)

403

403

404

403

403

SSH

SSH

DMH

K4

A1

BLK

1L1

MCB4

FMH

1SVT

MSHT

OSH

OSH

OSH

BLH

IVH

A2

WIRE NUMBER DESIGNATION LEGEND


NUMBERS
FUNCTION
WIRE COLOR

DESCRIPTION
ZERO VOLTAGE
PACKAGE INLET TEMPERATURE
INLET VACUUM PRESSURE
DRYER COMPRESSOR MOTOR
DRYER FAN MOTOR
DRYER SAFETY PRESSURE SWITCH
DRYER FAN PRESSURE SWITCH
DRYER CIRCUIT BREAKERS
LOAD VALVE
1SV HEAT TRACE
DRYER CONTROL POWER TRANSFORMER
AIREND DISCHARGE TEMPERATURE
INJECTED COOLENT TEMPERATURE
WET SUMP PRESSURE
AMBIENT TEMP THERMOSTAT
COOLANT COOLER OUT TEMP.
PACKAGE DISCHARGE PRESSURE
PACKAGE DISCHARGE TEMPERATURE
WATER SHUT OFF VALVE (W/C ONLY)
COOLANT FILTER IN PRESSURE
DRYER DEWPOINT
MODULATION VALVE
COOLANT FILTER OUT PRESSURE
REFRIGERANT TEMPERATURE
PACKAGE A/C PRESSURE
MOISTURE SEPARATOR DRAIN VALVE
REMOTE PRESSURE
DRYER FILTER DRAIN VALVE
DRYER DRAIN VALVE
AUTO TRANSFORMER
AUXILIARY WARNING 1
AUXILIARY WARNING 2
BASE LEVEL HEATER
BACKPANEL
CABINET
CAPACITOR
CONDENSATE DRAIN ERROR (M/S)
CONDENSATE DRAIN ERROR (DRYER FILTER)
CONDENSATE DRAIN ERROR (DRYER DRAIN)
CONDENSATE NO LOSS DRAIN VALVE (M/S)
CONDENSATE NO LOSS DRAIN VALVE (DRYER FILTER)
CONDENSATE NO LOSS DRAIN VALVE (DRYER DRAIN)
Xe CONTROLLER
COMMON TRIP OUTPUT
COMMON WARNING OUTPUT
CURRENT TRANSFORMER
DRYER HIGH PRESSURE SWITCH
DRIVE MOTOR HEATER
EARTHING BAR
EMERGENCY STOP BUTTON
FAN DRIVE
FAN MOTOR
FAN MOTOR HEATER
FAN MOTOR PROTECTOR
FUSES
START CONTROL RELAY
STARTER FAULT RELAY
DRYER / BLOWER DRIVE RELAY
ISOLATION CONTACTOR
FAN MOTOR CONTACTOR
DRYER COMPRESSOR CONTACTOR
DRYER FAN MOTOR CONTACTOR
CIRCUIT BREAKERS
MAIN MOTOR
MOISTURE SEPARATOR HEAT TRACE
OIL SUMP HEATER
PROTECTED EARTH
POWER OUTAGE RESTART OPTION
POWER SUPPPLY UNIT
MOTOR WINDING THERMISTOR
DRYER PRESSURE SWITCH RELAY
ARC SUPPRESSOR
REMOTE LOAD ENABLE
REMOTE LEAD LAG
REMOTE LOAD/UNLOAD
REMOTE STOP
REMOTE START
STARTER SPACE HEATER
CONTROL POWER TRANSFORMER
THERMOSTAT
POWER TERMINAL
ZENER DIODE
INLET VALVE HEATER

RC5

LABEL
OV
1ATT
1AVPT
1M1
1M2
1P1
1P2
1Qx
1SV
1SVT
1T1
2ATT
2CTT
3APT
3ATS
3CTT
4APT
4ATT
4SV
5CPT
5DTT
5SV
6CPT
6DTT
7APT
9SV
10APT
10SV
11SV
AT1
AW1
AW2
BLH
BP
CAB
CAP
CDE1
CDE2
CDE3
CDV1
CDV2
CDV3
CONT
CTO
CWO
CTx
DHP
DMH
EB
ES
FD
FM
FMH
FMP
FUK1
K2
K3
KM1
KM4
KM5
KM6
MCB
MM
MSHT
OSH
PE
PORO
PSU
PTCx
R1
RCx
RLE
RLL
RLU
RSP
RST
SSH
T1
TH
TRM
ZNR
IHV

LEGEND

410

410

410

410

NOTES:
1. APPROVED FUSED DISCONNECT OR CIRCUIT BREAKER PER LOCAL ELECTRICAL CODES
MUST BE PROVIDED BY THE CUSTOMER.

2. SENSORS 1ATT AND 3CTT ARE ONLY USED WHEN THE SMART THERMAL VALVE IS INSTALLED.
3. ONLY USED ON UNITS WITH INTEGRATED DRYERS.
4.

INDICATES OPTIONAL COMPONENTS.

INDICATES OPTIONAL FIELD WIRED COMPONENTS.

6. REMOVE JUMPER(S) WHEN CORRESPONDING OPTION HAS BEEN PURCHASED.


7. 60Hz WYE-DELTA STARTER UNITS REQUIRE CURRENT TRANSFORMERS (CT) TO BE USED
WITH MAIN MOTOR OVERLOAD. SEE DETAIL A.
8. A VARIABLE SPEED DRIVE IS REQUIRED FOR 37-75kW UNITS WITH LOW AMBIENT OPTION.
SEE DETAIL B.
9. A THREE PHASE TRANSFORMER IS REQUIRED FOR 575V 60 Hz UNITS WITH A VARIABLE SPEED
DRIVE CONTROLLING THE BLOWER MOTOR. SEE DETAIL C.
10. THREMOSTAT AND TEMPERATURE SWITCH CONTACTS ARE NORMALLY CLOSED AND WILL OPEN
WHEN THE TEMPERATURE MEETS OR EXCEEDS THE INDICATED SET POINT. SEE DETAIL D.

23603590 REV C
SHEET 2 OF 3

636,54

825,54

PROPRIETARY NOTICE
THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET
INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND
IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY
RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE
DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS
AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)
NOT USE THE DRAWING OR ANY COPY THEREOF OR THE
CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT
COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE
DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION
THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN
THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

SCHEMATIC, ELECTRICAL WIRING


(FS-SS)
SIZE

A1

SCALE:

DWG NO.

23603590

SHEET

1.00

636,18

18,18
18,18

8
29-Jun-2011 12:44:15 (model C.1/C.4)

TITLE

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

REV

2 OF 3

18,579
18,579

826,579

6L1

TO FU7,8,9

6L2
6L3
PE

1Q2

1Q1

F1

I> I> I>

F1

I> I> I>


1T1
100VA

KM5

0V 12V24V

KM6

KM5

1/24

U2 V2 W2

2/24

U1 V1 W1

L2R

L1R

F2

A2

A2

KM5

A2

KM6

R1

A1

A1

15

A1

24

22

1M1

1M2

X1

X1

X1

X1

X1

22

1/24

X1

14

15

16

17

18

19

20

21

22

X1

18

X1

16

1/24

13

12

X1

X1

13

12

11

X1

PE

X1

X2

X1

X1

X2

X1

U V W PE

8 9

11

14

21

1/24

U V W PE

M
3~

X1

X1

X1

X1

X1

X2

5 6 7 PE-10

12

R1

R1

2 3 4 PE-1

14

1P2

1P1

M
3~

23603590 REV C
SHEET 3 OF 3
A

636,54

825,54

PROPRIETARY NOTICE
THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET
INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND
IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY
RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE
DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS
AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)
NOT USE THE DRAWING OR ANY COPY THEREOF OR THE
CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT
COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE
DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION
THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN
THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

SCHEMATIC, ELECTRICAL WIRING


(FS-SS)
SIZE

A1

SCALE:

DWG NO.

23603590

SHEET

1.00

636,18

18,18
18,18

8
29-Jun-2011 12:44:15 (model C.1/C.4)

TITLE

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

REV

3 OF 3

18,579

825,579

REVISIONS
ZONE

2L1

X1:120V

6A

500VA

FU4,5,6

X3:0V

X3

X2

L3

7L1

MCB1
5L1

7L3
LR

PE

RC1

X6:230V

MCB2
KM4
124
123
122
2A

300VA
X7:0V

125

T1

7L1 7L2 7L3

X4:200V

118

50VA

119

1L1 1L2 1L3

PX1

PX6

PE

COM
N/O

1
2
1
2

FU7,8,9

GND

N
GR

309
MOTOR
RUNNING
CONTACT

121

DRYER
POWER
6L2
SUPPLY
6L3 (NOTE 3)

11

DRYER RUN
CONTACT
(NOTE 3)
101

K2

K1B-2

150

310

121
120
101
127

CDV-2
KL1
1.3 1.2 1.1

KM1 A1

A2

K1A A1

A2

K1B A1

A2

KM4 A1

K3-1

(NOTE 3)

150

111

112

1SV

K3

A2

150

110

TX1

TX2

TX3

113

150

311

312

12

A2

116

A1

PORO

117

TX4

TX5

TX6

TX7

TX8

10

GND

+24V
DI1
DI2

4L1 4L2 4L3

L1 L2 L3

PX4

BLK

BLK
RED

PE
SL

12
18

YEL
BLK
RED
GRE
BRO
BLU
VIO

27
FD

01
02
60
55

Gnd

10

DI6

11

Gnd

12

DI7

13

Gnd

14

DI8

15

Gnd

16

DI9

17

Gnd

18

DI10

19

Gnd

20

V+

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

Sig4
V+
Sig5

I> I> I>

V+
Gnd
Sig5

GND
283

283

284

284

U V W

K1A-2

BLK
SL

FM

RED

5
6

V+
Gnd
Sig6
V+
Gnd

285
206 BLU

206

207 BLU

207

294 WHI

WATER COOLED

Sig6

P3-5

Sig1

P3-6

295 BLK

WHI

294

BLK

295

WHI
ZNR
CAP

BLK

10

AO1

AO+

COM

Gnd
Sig2
Gnd
Sig3
Gnd
Sig4

U W V
CTO
AIR
COOLED

CWO

306
307
308
313
314
315

1
2
3
4
5
6

N/O

Gnd
Sig5

Gnd

N/C

Sig6

N/O

P2

FM

DI5

Gnd

U V W

MM

Gnd

PE

U V W

Gnd

V+

3L1 3L2 3L3

FMP

Sig3

P4

1
2
3
4
5
6
7

RED

ST
FU1, 2,
3

DI4

Gnd

KM1

3L1 3L2 3L3

V+

COM3
P9

2
3
6
7

+
-

PSU

7L1 7L2 7L3

KM1

GND

PX3

DR

7L1 7L2 7L3

201

P8

SDR

0V

Gnd

Sig2

P7

EN

1A

200

Gnd

P5

PX2

0V

104

DI3

V+

P10

AI2

MCB5

Sig1

P6

AI1-

24V

AI1+

1
2
3
4
5
6
7
K1A-1
277
276
8
279
ES-3
9
278
280
10
KM1-1
ES-4
296
1
297
2

Gnd

Gnd

RC4

AO1

Gnd

Sig7

N/C

Gnd
Sig8
Gnd

1
2
3
4
5
6
7
8
11
12
13
14
15
16
17
18

206
207

210
212
214

2011MAR22 B. WARREN

AW1

215
216

AW2

217

CDE

220

13

221

14

MULTIPLE CDE
ALARM CONTACTS
SHOULD BE WIRED
IN PARALLEL

DHP
(NOTE 3)

236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253

RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI
RED
BLK
WHI

257
258
259

RED
7APT
BLK
WHI

274
275

C. LEAMON

APP'D

RST

213

260
261
262
263
264
265
266
267
268
269
270
271

ORIGINAL RELEASE

DRAWN

RSP

211

219

79565

DATE

ES-2

209

218

DESCRIPTION

AIR
COOLED

FD 02

208

ECN

WATER
COOLED

FD 01

KL2

7L3
L1 L2 L3

120

102

CDV-3
KL1
1.3 1.2 1.1

6L1

7L2
EB

MCB4

DVF

BLK
BRN

1A

X5:0V

7L1

150

BLU

H6:0V

3A

150

DI2

FMP

206
207

2.2 2.3

K1B-1 103

CDV-1
KL1
1.3 1.2 1.1

115V

P1

FM
FD
MM
DR
DVF
1SV
4SV
CDV
RFI
CAB
BP
DOOR
PSU
T1
OV
SGNeV
EMC

5L3

4SV

H1:480V
H2:460V
H3:415V
H4:400V
H5:380V

102

150

151

151

H3

L2

K2-1

128

AT1
X1

EMC

H2

H1

L1

ES-1

101

PS1

105

CONTROLLER

P3

L1

100

MCB3

BLU

2L2

RFI

BRO

L2

BLU

2L3

BRO

L3

GRE

L1 L2 L3

REV

EB

WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK
WHI
BLK

EB

WHI
BLK

EB
EB
EB
EB
EB

1AVPT

P
3APT
P
4APT
P
5CPT
P
6CPT
P
10APT
P

(NOTE 3)
P

2CTT

2ATT

4ATT

3CTT

(NOTE 2)

5DTT

(NOTE 3)

6DTT

(NOTE 3)

1ATT

23843899 REV A
SHEET 1 OF 3

402,81

WARNING: THE EXPORT OR REEXPORT OF THIS DRAWING OR A PRODUCT PRODUCED


BY THIS DRAWING IS SUBJECT TO U.S. EXPORT ADMINISTRATION REGULATIONS
AND OTHER APPLICABLE GOVERNMENT RESTRICTIONS OR REGULATIONS.

NOTES:

PROPRIETARY NOTICE

1. DECAL MUST CONFORM TO THE LATEST REVISION OF IR SPECIFICATION 92-8.95.

THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET


INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND IS
GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY RECEPTION
AND RETENTION OF THE DRAWING ACCEPTS THE DRAWING IN CONFIDENCE
UNLESS OTHERWISE SPECIFIED:
AND AGREES THAT, EXCEPT AS AUTHORIZED IN WRITING BY
- REMOVE ALL BURRS AND SHARP CORNERS
INGERSOLL-RAND CO. IT WILL (1) NOT USE THE DRAWING OR ANY COPY
- WELD SYMBOLS TO BE IN ACCORDANCE
THEREOF OR THE CONFIDENTIAL OR TRADE SECRET INFORMATION
WITH ANSI/AWS A2.4
THEREIN; (2) NOT COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS
EITHER THE DRAWING OR THE CONFIDENTIAL OR TRADE SECRET
COPYRIGHT @ 2011
INFORMATION THEREIN; AND (4) UPON COMPLETION OF THE NEED TO
RETAIN THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
Ingersoll Rand
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.
ALL RIGHTS RESERVED

Ingersoll-Rand Industrial Technologies


18,18

DO NOT SCALE DRAWING


DRAWING CONFORMS TO
ASME Y14.5M - 1994
CAD GENERATED DRAWING,
NO MANUAL REVISIONS ALLOWED

615,81

THIRD ANGLE PROJECTION


DRAWN

C. LEAMON
CHECKED

B. WARREN
APPROVED

B. WARREN

DATE

2011MAR22
DATE

TITLE

2011MAR22
DATE

2011MAR22
SIZE

NOMENCLATURE

A1

SCALE:

SCHEMATIC, ELECTRICAL
WIRING 575V (VSD)
ESTIMATED WEIGHT

(KG UNLESS OTHERWISE SPECIFIED)

0.0 kilogram
1.00 UNIT:

DWG NO.

23843899

SHEET

SCHEMATIC, ELECTRICAL WIRING 575V (VSD)

REV

1 OF 3

402,18

For Internal Use:23843899|ASSEM|A.2|Jason Hunt|24-Mar-11 12:13:31 PM|In Work

8
01-Apr-2011 11:55:14 (model A.2/A.4)

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

825,81

18,579
18,579

826,579

LEGEND

LABEL

DESCRIPTION

OV
1ATT
1AVPT
1M1
1M2
1P1
1P2
1Qx
1SV
1T1
2ATT
2CTT
3APT
3CTT
4APT
4ATT
4SV
5CPT
5DTT
6CPT
6DTT
7APT
10APT
AT1
AW1
AW2
BP
CAB
CAP
CDE1
CDE2
CDE3
CDV1
CDV2
CDV3
CTO
CWO
DHP
DR
DVF
EB
EMC
ES
EXC
FD
FM
FMP
FUGND
HTRK1
K2
K3
LR
KM1
KM4
KM5
KM6
MCBx
MM
PE
PORO
PS1
PSU
PTC
R1
RCx
RFI
RSP
RST
SL
ST
T1
TH
ZNR

ZERO VOLTAGE
PACKAGE INLET TEMPERATURE
INLET VACUUM PRESSURE
DRYER COMPRESSOR MOTOR
DRYER FAN MOTOR
DRYER SAFTEY PRESSURE SWITCH
DRYER FAN PRESSURE SWITCH
DRYER CIRCUIT BREAKERS
INLET/BLOWDOWN VALVE
DRYER CONTROL POWER TRANSFORMER
AIREND DISCHARGE TEMPERATURE
INJECTED COOLENT TEMPERATURE
WET SUMP PRESSURE
COOLANT COOLER OUT TEMP.
PACKAGE DISCHARGE PRESSURE
PACKAGE DISCHARGE TEMPERATURE
WATER SHUT OFF VALVE (W/C ONLY)
COOLANT FILTER IN PRESSURE
DRYER DEWPOINT
COOLANT FILTER OUT PRESSURE
REFRIGERANT TEMPERATURE
PACKAGE A/C PRESSURE
REMOTE PRESSURE
AUTO TRANSFORMER
AUXILIARY WARNING 1
AUXILIARY WARNING 2
BACKPANEL
CABINET
CAPACITOR
CONDENSATE DRAIN ERROR (M/S)
CONDENSATE DRAIN ERROR (DRYER FILTER)
CONDENSATE DRAIN ERROR (DRYER DRAIN)
CONDENSATE NO LOSS DRAIN VALVE (M/S)
CONDENSATE NO LOSS DRAIN VALVE (DRYER FILTER)
CONDENSATE NO LOSS DRAIN VALVE (DRYER DRAIN)
COMMON TRIP OUTPUT
COMMON WARNING OUTPUT
DRYER HIGH PRESSURE SWITCH
DRIVE, MAIN MOTOR
DRIVE VENTILATION FAN
EARTHING BAR
EMC FILTER BOARD
EMERGENCY STOP BUTTON
EXTERNAL COMMUNICATIONS
DRIVE, BLOWER MOTOR
FAN MOTOR
FAN MOTOR PROTECTOR
FUSES
GROUND
PANEL SPACE HEATER
RUN RELAY
DRIVE FAULT RELAY
BLOWER DRIVE CONTROL RELAY
LINE REACTOR
BLOWER MOTOR CONTACTOR
DRIVE FAN MOTOR CONTACTOR
DRYER COMPRESSOR MOTOR CONTACTOR
DRYER FAN MOTOR CONTACTOR
CIRCUIT BREAKERS
MAIN MOTOR
PROTECTED EARTH
POWER OUTAGE RESTART OPTION
LINE FILTER TERMINAL STRIP
POWER SUPPPLY UNIT
MOTOR WINDING THERMISTOR
DRYER PRESSURE SWITCH RELAY
ARC SUPPRESSOR
RADIO FREQUENCY INTERFACE
REMOTE STOP
REMOTE START
SERIAL LINK
SERVICE TOOL CONNECTOR
CONTROL POWER TRANSFORMER
THERMOSTAT
ZENER DIODE

WIRE NUMBER DESIGNATION LEGEND


NUMBERS
FUNCTION
WIRE COLOR
1 - 99

POWER

BLACK

100 - 199

AC CONTROL

RED

100 - 199

GROUNDED AC

WHITE OR LIGHT BLUE

200 - 299

DC CONTROL

BLUE

300 - 399

AUXILIARY

ORANGE

GND

GROUND

GREEN / YELLOW

WIRE COLOR LEGEND


LABEL DESCRIPTION
BLK

BLACK

BLU

BLUE

BRO

BROWN

GRE

GREEN

PIN

PINK

RED

RED

VIO

VIOLET

WHI

WHITE

YEL

YELLOW

TH
(29C)
T1

100

300

MCB9

302

303

KM4-2

304
151

301

3A

HTR1

HTR2

110/120V
50/60Hz
305

305

NOTES:
1. FACTORY SUPPLIED AS SHOWN BY CONNECTION TO OUTPUT
OF CONTROL TRANSFORMER T1. WIRE TO TERMINAL
NUMBERS 100 & 151.
2. ALTERNATIVELY THE SUPPLY MAY BE TAKEN FROM AN
INDEPENDENT SOURCE; IN THAT CASE, FACTORY SUPPLIED
CONNECTION MUST BE DISCONNECTED.
3. ENSURE PARALLEL CONNECTION OF HEATERS.

TH
(29C)
300

MCB9

302

KM4-2

303

T
304

301

3A

HTR1

HTR2

220/230V
50/60Hz
305

305

NOTES:
1. APPROVED FUSED DISCONNECT OR CIRCUIT BREAKER PER LOCAL ELECTRICAL
CODES MUST BE PROVIDED BY THE CUSTOMER.

NOTES:
1. CONNECTIONS FOR USE ON 200/230V
SYSTEMS. THE SUPPLY IS INDEPENDENT
OF THE MAIN COMPRESSOR. THE CUSTOMER
MUST PROVIDE AN ISOLATOR / DISCONNECT
SWITCH ADJACENT TO THE MACHINE FOR
THIS SUPPLY. IN THAT CASE, FACTORY SUPPLIED
CONNECTION MUST BE DISCONNECTED.
2. ENSURE SERIES CONNECTION OF HEATERS.

2. SENSOR 3CTT IS NOT INSTALLED, IF THE COMPRESSOR IS WATER COOLED


WITH HOT SIDE THERMAL CONTROL VALVE
3. ONLY USED ON UNITS WITH INTEGRATED DRYERS.
4.

INDICATES OPTIONAL COMPONENTS.

5.

INDICATES OPTIONAL FIELD WIRED COMPONENTS.

23843899 REV A
SHEET 2 OF 3

636,54

825,54

PROPRIETARY NOTICE
THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET
INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND
IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY
RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE
DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS
AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)
NOT USE THE DRAWING OR ANY COPY THEREOF OR THE
CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT
COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE
DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION
THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN
THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

SCHEMATIC, ELECTRICAL
WIRING 575V (VSD)
SIZE

A1

SCALE:

DWG NO.

23843899

SHEET

1.00

636,18

18,18
18,18

8
01-Apr-2011 11:55:14 (model A.2/A.4)

TITLE

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

SCHEMATIC, ELECTRICAL WIRING 575V (VSD)

REV

2 OF 3

18,579
18,579

826,579

6L1

TO FU7, 8, 9

6L2
6L3
PE

1Q2

1Q1

F1

I> I> I>

I> I> I>

F1

AC

1T1 460V
100VA

KM5

0V 12V24V

KM6

KM5

1/24

2/24

U2 V2 W2

L2R

U1 V1 W1

L1R

F2

A2

A2

KM5

A2

KM6
A1

A1

15

A1

R1

1M1

1M2

1/24

X1

X1

X1

X1

X1

X1

X1

X1

X1

18

X1

16

12

12
X1

X1

X1

X2

X2

PE

11

12

13

14

15

16

17

18

19

20

21

22

M
3~

U V W PE

8 9

U V W PE

X1

5 6 7 PE-10

11

X1

2 3 4 PE-1

X1

X1

X2

X1

X1

X1

1/24

21

13

R1

R1

12

22

14

12

22

14

24

1P2

1P1

M
3~

23843899 REV A
SHEET 3 OF 3

636,54

825,54

PROPRIETARY NOTICE
THIS DRAWING CONTAINS CONFIDENTIAL AND TRADE SECRET
INFORMATION, IS THE PROPERTY OF INGERSOLL-RAND CO., AND
IS GIVEN TO THE RECEIVER IN CONFIDENCE. THE RECEIVER BY
RECEPTION AND RETENTION OF THE DRAWING ACCEPTS THE
DRAWING IN CONFIDENCE AND AGREES THAT, EXCEPT AS
AUTHORIZE D IN WRITING BY INGERSOLL-RAND CO. IT WILL (1)
NOT USE THE DRAWING OR ANY COPY THEREOF OR THE
CONFIDENTIAL OR TRADE SECRET INFORMATION THEREIN; (2) NOT
COPY THE DRAWING; (3) NOT DISCLOSE TO OTHERS EITHER THE
DRAWING OR THE CONFIDENTIAL OR TRADESECRET INFORMATION
THEREIN; AND (4) UPON COMPLETION OF THE NEED TO RETAIN
THE DRAWING, OR UPON DEMAND, RETURN THE DRAWING, ALL
COPIES THEREOF, AND ALL MATERIAL COPIED THEREFROM.

SCHEMATIC, ELECTRICAL
WIRING 575V (VSD)
SIZE

A1

SCALE:

DWG NO.

23843899

SHEET

1.00

636,18

18,18
18,18

8
01-Apr-2011 11:55:14 (model A.2/A.4)

TITLE

5
4
UNLESS OTHERWISE SPECIFIED PRINTED DOCUMENT IS UNCONTROLLED

SCHEMATIC, ELECTRICAL WIRING 575V (VSD)

REV

3 OF 3

Vous aimerez peut-être aussi