Vous êtes sur la page 1sur 41

Technical slides

SIMATIC S7-1200
Basic Controller in the TIA Portal

Intern / © Siemens AG 2014. Alle Rechte vorbehalten. I IA AS S SUP FA


New SIMATIC controller generation
Always the appropriate controller with comprehensive functionalities!

Engineered with TIA Portal


System performance

Advanced Controller
Software Controller
SIMATIC S7-1500 SIMATIC S7-1500

Distributed Controller
SIMATIC ET 200SP CPU

Basic Controller
SIMATIC S7-1200

Application complexity

Intern / © Siemens AG 2014. Alle Rechte vorbehalten.


Seite 2 19.03.2014 TIA Portal V13 - S7-1200 FW V4
Design and handling
S7-1200 CPU features (1/4)

CPU 1211C CPU 1212C CPU 1214C CPU 1215C CPU 1217C
CPU type DC/DC/DC, AC/DC/RLY, DC/DC/RLY DC/DC/DC

Work memory, integrated 50 KB 75 KB 100 KB 125 KB 150 KB

Load memory, integrated 1 MB 4 MB

Retentive memory, integr. 10 KB

Marker(M) 4 KB 8 KB

Integrated Digital I/O 1) 6 inputs / 4 outputs 8 inputs / 6 outputs 14 inputs / 10 outputs

RS485 Differential I/O 4 / 4 (1 MHz)

Integrated Analog I/O 2 inputs 2 inputs / 2 outputs

Process image size 1024 bytes for inputs / 1024 bytes for outputs

Board (SB/CB) Expansion 1 max.

Extension: Signal Module none 2 max. 8 max.

Max. Local I/O – Digital 14 82 284 284

Max. Local I/O – Analog 3 19 67 69


1) See Technical Specifications for the number of inputs or outputs allowed on simultaneously.
Some models are de-rated for 60°C horizontal mounting and 50°C vertical mounting
Intern / © Siemens AG 2014. Alle Rechte vorbehalten.
Seite 3 19.03.2014 TIA Portal V13 - S7-1200 FW V4
Design and handling
S7-1200 CPU features (2/4)

CPU 1211C CPU 1212C CPU 1214C CPU 1215C CPU 1217C
Total Max. 6, configured for the use of integrated or SB inputs

1 MHz none 4
High-speed
100 / 80 kHz 1) 6
counters
30 / 20 kHz 1) - 1 3

200 kHz with SB 1221 DI x 24 VDC 200 kHz or SB 1221 DI 4 x 5 VDC 200 kHz

Total Max. 4, configured for the use of integrated or SB outputs

1 MHz none 4
Pulse
outputs 2) 100 kHz 4 10

20 kHz

Pulse Catch Inputs 6 8 14

1) lower frequency with HSC configuration in 2-phase operation (A/B counter operation)
2) CPU versions with relay outputs require a digital signal board (SB) with use of pulse outputs
Intern / © Siemens AG 2014. Alle Rechte vorbehalten.
Seite 4 19.03.2014 TIA Portal V13 - S7-1200 FW V4
Design and handling
S7-1200 CPU features (3/4)

CPU 1211C CPU 1212C CPU 1214C CPU 1215C CPU 1217C
Execution time
0.08 μs/operation
Binary instruction
Execution time
1.7 μs/operation
Word instruction
Execution time
2.3 μs/operation
Real number instruction

PROFINET Ports 1 2

Type RJ45

Data rate 10/100 MBaud

Additional communication
3 max
modules
Ambient conditions - -20°C to 60 °C horizontal assembly / -20°C to 50°C vertical assembly
Operation (observe derating conditions for individual modules)

Real-time clock buffering 20 days, typ./min. 12 days at 40°C (maintenance-free high-performance capacitor)

Dimensions W x H x D
90 x 100 x 75 110 x 100 x 75 130 x 100 x 75 150 x 100 x 75
(mm)

Intern / © Siemens AG 2014. Alle Rechte vorbehalten.


Seite 5 19.03.2014 TIA Portal V13 - S7-1200 FW V4
Design and handling
S7-1200 CPU features (4/4) Integrated I/O of the CPU and SB I/O options

1211C 1212C 1214C 1215C 1217C


CPU 6 8 14
DI digital input
SB ≤ 4 (optional)
including HSC
high-speed counters
CPU or SB inputs 6

CPU 4 6 10
DQ digital output
SB ≤ 4 (optional)
CPU 2
AI Analog input
SB 1 (optional)
CPU - 2
AQ analog output
SB 1 (optional)
Technological outputs

PWM / PTO pulse output CPU or SB outputs 4

Position-controlled axes
(PROFIdrive, analog)
8

Intern / © Siemens AG 2014. Alle Rechte vorbehalten.


Seite 6 19.03.2014 TIA Portal V13 - S7-1200 FW V4
SIMATIC S7-1200
CPU 12xx – Integrated and external memory

Integrated user memory

The following memory areas are available in the S7-


1200:
§ Load memory (retentive) – For the user program,
data and configuration.
§ Work memory (non retentive) – For some data used
Memory card - 4 / 12 / 24MB … 32GB
and changed by the PLC during execution of the user (SD card – FAT32 file system)
program.
§ Retentive memory – Storage of a imitated data Can be configured or 3 types of operation:
volume when PLC is powered off.
§ Program card – Replaces the internal load memory allowing a
higher capacity (use of data logging, user web pages,…)
§ Transfer card – For the copy of the program in the load
memory without need of a PC.
§ Firmware update card – Update of the S7-1200 PLC firmware
as well as the connected devices

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Design and handling
Set-up and extension options - maximum

CM/CP CPU

1 board

S7-1200:
variable extension and set-up options for differing requirements
© Siemens SA 2013. All Rights Reserved.
Industry Sector
Design and handling
Set-up and extension options - maximum

CM/CP CPU SM

1 board

CPU 1211C
CPU 1212C
CPU 1214C / 1215C / 1217C

S7-1200:
variable extension and set-up options for differing requirements
© Siemens SA 2013. All Rights Reserved.
Industry Sector
Design and handling
Digital signal modules and signal boards

SM 1221 digital input SM 1223 digital input/output SM 1222 digital output


45 mm 1. 8 DI, 24V DC 45 mm 1. DI 8x 24 VDC, DQ8 x RLY 45 mm 1. DQ 8x RLY
2. 16 DI, 24V DC 2. DI 8/DQ 8 24 VDC 2. DQ 8x 24 VDC
3. DQ 16x RLY
SINK/SOURCE
70 mm 1. DI 16x 24 VDC, DQ 16x RLY 70 mm 1. DQ 8x RLY
2. DI 16/DQ 16 24 VDC (changeover contact)

3. DI 8 x120/230 V AC / DQ 8 x relays 2. DO 16x 24 VDC

SB 1221 digital input SB 1223 digital input/output SB 1222 digital output


1. 4DI, 5VDC 200kHz 1. 2DI/2DQ 24VDC 1. 4DQ, 5VDC 200kHz
2. 4DI, 24VDC 200kHz 2. 2DI/2DQ, 5VDC 200kHz 2. 4DQ, 24VDC 200kHz
3. 2DI/2DQ, 24VDC 200kHz

Reading M

Intern / © Siemens AG 2014. Alle Rechte vorbehalten.


Seite 10 19.03.2014 TIA Portal V13 - S7-1200 FW V4
Design and handling
Analog signal modules and signal boards

SM 1231 analog input SM 1234 analog input/output SM 1232 analog output


45 mm 1. 4 AI 13 bit, ±10V, ±5V, ±2.5V, or 45 mm 1. 4 AI 13 bit, ±10V ±5V or 45 mm 1. 2 AQ, ±10V, 14 bit or
0-20/4-20 mA ±2.5V or 4-20 mA / 2 AQ 14 0 – 20 or 4 - 20 mA, 13 bit
2. 8 AI 13 bit, ±10V, ±5V, ±2.5V, or Bit, ±10V or 4-20 mA
2. 4 AQ, ±10V, 14 bit or
0-20/4-20 mA 0 – 20 or 4 - 20 mA, 13 bit
3. 4 AI 16 bit, ±10V, ±5V, ±2.5V, or
0-20/4-20 mA
4. 4 AI 16 bit TC
5. 8 AI 16 bit TC
6. 4 AI 16 bit RTD
7. 8 AI 16 bit RTD

SB 1231 analog input SB 1232 analog output


1. 1 AI, 12 bit ±10VDC or 0-20 mA 1. 1 AQ, ±10V (12 bit) or
2. 1 AI, 16 bit RTD (Pt) 0 - 20 mA (11 bit)

3. 1 AI, 16 bit TC
(type: J,K; ± 80 mV)

Intern / © Siemens AG 2014. Alle Rechte vorbehalten.


Seite 11 19.03.2014 TIA Portal V13 - S7-1200 FW V4
Design and handling
SIMATIC S7-1200 accessories

Accessory part Details


PM1207 Inputs: 120/230 V AC
Power supply 50/60 Hz, 1.2 A / 0.7 A
Outputs: 24 V DC / 2.5 A
Battery board for real-time clock long-term buffering
(without CR1025 battery)

CSM 1277 4 x RJ45 jacks


Compact Switch Module 10/100 MBit/s

Digital SIM 1274 input simulator

Analog input simulator Potentiometer for direct


entry of analog value

Extension cable for 2-row station configuration, 2 m

Intern / © Siemens AG 2014. Alle Rechte vorbehalten.


Seite 12 19.03.2014 TIA Portal V13 - S7-1200 FW V4
SIMATIC S7-1200
Optimized portfolio

Switch- Power- Communication- Signal- Technology- Signal-


CPUs
module module modules modules modules boards

CPU 1211C-1PN
CSM PM 13x CM / CP 22x I/Q 2xTM 11x SB
CPU 1212C-1PN
CPU 1214C-1PN 1x CB
CPU 1215C-2PN 1x BB
CPU 1217C-2PN SM 1226 F-DO 2x Relay
CPU 1214FC SM 1226F-DO 4 x 24 V DC
Unrestricted / © Siemens AG 2014. All Rights Reserved. CPU 1215FC SM 1226 F-DI 16 x 24 V DC
Page 13 V1.0
Communication

Point-to-Point,
USS, Modbus RTU
GPRS

… to answer each of your network requirements

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Communication
S7-1200 integrated PROFINET (Ethernet) interface

Communication ...
… with the STEP 7 software
o CPU hardware configuration
o Loading a project
o Monitoring/amending runtime tags
o Set runtime I/O statuses
o Diagnostics information
... with HMI panels
o Data from or to the CPU
o System diagnostics
... from CPU to CPU
o Open communication with T-block instructions
o Supported protocols: TCP/IP, ISO on TCP, UDP, S7 Com. (PUT/GET)
... With PROFINET devices
o PROFINET Basis services, I/O controller and shared device / Shared I-
Device

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Communication
S7-1200

Module Communication CM CP CPU SM


CB 1241 RS485 SM 1278
CM 1241 RS232 serial
CM 1241 RS422/485 serial
CM 1243-2 AS-i master
CM 1242-5 PROFIBUS DP slave
CM 1243-5 PROFIBUS DP master USS
MODBUS RTU
Mobile communications
CP 1242-7 GPRS
telecontrol
SINAMICS
Mobile communications
CP 1243-7 LTE V20
telecontrol
VPN/Firewall, Ethernet
CP1243-1 Security
telecontrol
CP1243-1 DNP3 DNP3 telecontrol
CP1243-1 IEC IEC 60870-5-104 telecontrol
RF120C RFID 1 Reader port; RS422

CM CANopen CANopen 3rd party: HMS © Siemens SA 2013. All Rights Reserved.
Industry Sector
Communication
Serial communication S7-1200

S7-1200 CPU communication via


RS232 and RS485 connections
o ASCII protocol (character-based serial communication)
uses STEP 7 PtP instructions
o USS Drive protocol is programmed with STEP 7 USS
library instructions
o MODBUS protocol is programmed with STEP 7
MODBUS library instructions (Master or Slave)

The CM1241 RS232 and RS485/422 modules are used


for the PtP communication RS232
RS485/422
The CB1241 RS485 Signal board
is another option

© Siemens SA 2013. All Rights Reserved.


Industry Sector
MODBUS communication

MODBUS RTU protocol


o Use of a CM or CB 1241 module for serial communication
o MODBUS instructions of the communication module for simplified MODBUS RTU operation.
o MB_COMM_LOAD for basic initialization of the master and slave operation
o MB_MASTER and MB_SLAVE for controlling the report and connection allocations
o Modbus addressing supports a maximum of 247 slaves (slave numbers 1 to 247).
o Maximum of 32 devices per segment in the Modbus network depending on the loading and drive functions
of the RS485 interface
o Repeater required if using more than 32 devices to extend to the next segment

MODBUS TCP protocol


o Open User Communication MODBUS TCP instructions use
the PROFINET port integrated in the CPU

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Communication
IO-Link support

IO link master specification V1.1


o S7-1200 CPU up to 8 IO-Link master modules -
centralized
o Data rate COM1 (4.8 kbaud), COM2 (38.4 kbaud),
COM3 (230.4 kbaud)
o Standard IO Mode (SIO Mode)
o up to 4 IO-Link devices (3 wire)
or 4 standard actuators
o Diagnostics configurable for each port
o I&M identification
o IO-Link parameter allocation with S7-PCT
(Port Configuration Tool) V3.2

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Communication
AS-i

Master AS-Interface
The AS-i module offers the following features:
• Supports AS-i Spec. 3.0
• Up to 62 AS-i slaves, respectively 992 I/Os per
master can be red and written
• Transmission of binary and analog values
• Easy parameter of motor starters M200D without extra
function blocs
• Optional data decoupling module for 24VDC AS-i network

© Siemens SA 2013. All Rights Reserved.


Industry Sector
PROFIBUS communication
DP master CM 1243-5 and DP slave CM 1242-5

Communication for S7-1200 CPUs according to PROFIBUS standard IEC61158/61784


PROFIBUS DP-Master CM 1243-5
o Connection for up to 16 DP slaves
o PG/OP communication:
up to 4 connection for HMI and 1 connection for PG
o S7 communication:
4 S7 connections to other S7 stations with PUT/GET

PROFIBUS DP-Slave CM 1242-5


o as an intelligent DP slave for communication for the S7-1200
with any other DP master

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Communication
Remote access

Telecontrol Communication

Coupled to the GPRS communication processor, the


S7-1200 PLC can carry out simple telecontrol tasks for
the visualisation and control of remote stations, using
the “General Packet Radio Service” (GPRS).

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Communication
Remote access

Telecontrol Communication

Using the GPRS CP 1242-7 communication


processor, the S7-1200 can reach:

§ The central control station


§ Other remote stations
§ Mobiles devices (SMS)
§ Programming console (Teleservice)
§ Other devices using the open user communication based
on UDP

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Overview of CP 1243-7 product features

CP1243-7 (6GK7243-7KX30-0XE0 – EU version


6GK7243-7SX30-0XE0 – US version)
o 1 connection to LTE (4G) mobile network
(different versions for EU and North America)
o Single-width S7-1200 enclosure (30 x 110 x 75)
o Temperature range in operation from -20ºC to +70ºC
o Standard rail mounting
o Diagnostic LEDs (overall status and detail)
o Integrated security functions (VPN and Firewall)
o Access to the CPU Webserver

Communication processor to connect SIMATIC S7-1200 via LTE (4G) mobile


network to control point system with TeleControl Server Basic

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Overview of CP 1243-1 product features

CP1243-1 (6GK7243-1BX30-0XE0)
o Single-width S7-1200 enclosure (30 x 110 x 75)
o Temperature range in operation: -20°C to +70°C
o Standard rail mounting
o Diagnostic LEDs (overall status and detail)
o Power supply using backplane bus
o 1 x Ethernet Port RJ45 (10/100 Mbit/s) for connecting
a modem/router such as SCALANCE M
o Integrated security functions (VPN and Firewall)
o Operation with TeleControl Server Basic from version V3

Communication processor to connect SIMATIC S7-1200 to control point


system with TeleControl Server Basic via various remote networks using
external modem/router such as SCALANCE M

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Overview of CP 1243-1 DNP3 product features

CP1243-1 DNP3 (6GK7243-1JX30-0XE0)


o Single-width S7-1200 enclosure (30 x 110 x 75)
o Temperature range in operation -20°C to +70°C
o Standard rail mounting
o Diagnostic LEDs (overall status and detail)
o Power supply using backplane bus
o 1 x Ethernet Port RJ45 (10/100 Mbit/s)
o DNP3 protocol supported

Communication processor to connect SIMATIC S7-1200 to control point


system via DNP3 protocol

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Overview of CP 1243-1 IEC product features

CP1243-1 IEC (6GK7243-1PX30-0XE0)


o Single-width S7-1200 enclosure (30 x 110 x 75)
o Temperature range in operation -20°C to +70°C
o Standard rail mounting
o Diagnostic LEDs (overall status and detail)
o Power supply using backplane bus
o 1 x Ethernet Port RJ45 (10/100 Mbit/s)
o IEC 60870-5-104 standard supported

Communication processor to connect SIMATIC S7-1200 to control point


system via IEC 60870-5-104 protocol

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Communication
SIMATIC RF120C – Fast communication module

q Integration in TIA Portal (from V12 SP1)


§ Full integration into the device configuration for the TIA Portal
§ Simple function blocks for fast programming
q One reader per RF120C
§ So that the data is available to the application immediately
§ Up to three RF120C can be operated in parallel to the left of the CPU
q Reader cable
§ Submin-D connector on RF120C;
§ Ready-made cables are available
q Firmware update via SIMATIC Manager
§ Rapid bug fixes via ONLINE
update (up to the reader)
• Order number: 6GT2002-0LA00
S7-1200 and RF120C: cost-effective and powerful identification solution

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Communication
SIMATIC RF120C – Fast communication module for S7-1200

RF120C
Interface to the
Internal S7 bus
application
Connection technology S7-1200 setup technology; screw terminals for 24 V supply

Interface to the reader RS422 incl. 24 Volt; up to 115.2 KBaud

Connection technology Submin-D connector

RFID system RF200, RF300, RF600, MOBY D/U, MV400

Instructions: Read, Write, Read_EPC-Mem, Write_EPC-Mem,


FB, driver
Set_Ant_RF300, Set_Ant_RF600, Reset_Reader; based on FB101

Number of readers 1 per RF120C; 3 per S7-1200

Degree of protection IP 20

Dimensions (W x H x D) 30 x 100 x 75
© Siemens SA 2013. All Rights Reserved.
Industry Sector
Communication
Controller Area Network CANopen 021620-B

SIMATIC S7-1200C CANopen master/slave


o A CANopen connection to a S7-1200 system
enables integration between devices and the S7-1200 system
o Up to 3 CANopen modules per S7-1200 CPU
o Connection type to the CAN: 9-pin DSUB (male)
o Up to 16 CANopen nodes per module
o 256 bytes each for inputs and outputs with the CANopen module
o Can be integrated in the hardware catalog of the TIA Portal configuration suite
o Ready-made function blocks for simple PLC programming
available in the TIA Portal
o à To the suppliers Web page

Easy integration in CANopen applications

© Siemens SA 2013. All Rights Reserved.


Industry Sector
Communication
Remote access

Teleservice communication
TIA Portal V11 or higher

TS Adapter IE Basic with a selection of TS modules


for various communication technologies
Analog, ISDN, GSM

§ TS modules:
Modem, ISDN, GSM, RS232

HMI
§ No need of PG/PC on site Analog, ISDN, GSM

§ No need for a specialized staff to go on site for technical TS Adapter IE Basic


intervention
§ Complete range of TeleService functionalities,
local bus extension to the maintenance PC.

© Siemens SA 2013. All Rights Reserved.


Industry Sector
SIWAREX WP231 – basic applications

S7-1200 CPU types supported: Applications:


o S7-1212 à up to two SIWAREX modules o Filling level measurement in silos / bunkers
o S7-1214 or higher o Platform scales
à up to eight SIWAREX modules o Power measurements
o Full parameter access using ready-made o Typical industries: Food & luxury food industry,
function block from the CPU chemical, cement, stone and earth industries
à Complete commissioning
and calibration via CPU/HMI

Connection options:
o Up to eight analog 350 Ohm weighing cells connected in parallel
per SIWAREX (1mV/V, 2mV/V, 3mV/V or 4mV/V)
o 1 SIWAREX = 1 scale
o 4 digital inputs / 4 digital outputs
o 1 analog output
o Ethernet (Modbus TCP & SIWATOOL)
o RS485 (Modbus RTU)

© Siemens SA 2013. All Rights Reserved.


Industry Sector
SIWAREX WP241 – belt weighing applications

S7-1200 CPU types supported: Applications:


o S7-1212 à up to two SIWAREX modules o Conveyor belt scales (cement, gravel and grit plants,
o S7-1214 or higher mines, opencast and deep mining)
à up to eight SIWAREX modules o Dosing belt scales (food and luxury food industry,
o Full parameter access using ready-made chemical and steel industries)
function block from the CPU
à Complete commissioning
and calibration via CPU/HMI

Connection options:
o Up to eight analog 350 Ohm weighing cells connected in parallel
per SIWAREX (1mV/V, 2mV/V, 3mV/V or 4mV/V)
o 1 SIWAREX = 1 scale
o 3 digital inputs / 4 digital outputs
o 1 speed sensor input o Ethernet
o 1 analog output (Modbus TCP & SIWATOOL)
o RS485 (Modbus RTU)

© Siemens SA 2013. All Rights Reserved.


Industry Sector
SIMATIC Integrated Technology
S7-1200 / S7-1500 – integrated compact controllers

PID Compact PID 3-Step Technical features


o Continuous PID controller for o PID controller for integrating actuators o Closed-loop control structures: PI, PID
proportional-acting actuators (e.g. valves) with digital signals for o Inversion of control direction, anti-windup
o Analog or pulse-width modulated (PWM) opening and closing and weighting of P and D portion
output o Output for analog and binary valve o Actual value scaling, alarms for actual and
control target values
o Position feedback/ o Manipulated variable limitation
stop signal o Parameter setting for conduct in the event of
o Integrated motor regulating time fault
measurement o Two-stage optimization procedure with
optimization in the operating point

© Siemens SA 2013. All Rights Reserved.


Industry Sector
SIMATIC Integrated Technology
S7-1200 / S7-1500 – integrated compact controllers

Integrated PID controllers


o For versatile control tasks
o Continuous controllers and step controllers
o Automatic determination of the controller parameters
o Manageable configuration screens
o Commissioning screens with integrated trace
o Available in S7-1200 and S7-1500 (integrated in FW)

Cost savings through integrated PID controllers with premium auto-tuning

© Siemens SA 2013. All Rights Reserved.


Industry Sector
SIMATIC Integrated Technology
S7-1200 / S7-1500 – integrated compact controllers

PID Temp – Temperature controller for actively heating and cooling a process
o Two controller parameter sets for heating and cooling – alternatively: cooling factor
o Analog or pulse-width modulated control signals for heating and cooling
o Integrated two-stage self-optimization – specifically for temperature processes
o Heating and cooling optimization available separately (multi-zone applications)
o Deadband and control zone can be set
o Cascade control with anti-windup

© Siemens SA 2013. All Rights Reserved.


Industry Sector
SIMATIC Integrated Technology - PID Control
S7-1200 / S7-1500 – integrated compact controllers

Memory requirements for the instance DB CPU processing time (typical)


Load memory approx. 12000 bytes
CPU 121xC (FW>=4.1) 300 µs
PID Compact Work memory 788 bytes

Residual work memory 44 bytes CPU 1511/16/18 (FW>=1.7) 85/50/4 μs

Load memory approx. 15000 bytes


CPU 121xC (FW>=4.1) 410 µs
PID 3-Step Work memory 1040 bytes

Residual work memory 60 bytes CPU 1511/16/18 (FW>=1.7) 120/65/5 μs

Load memory approx. 17000 bytes


CPU 121xC (FW>=4.1) 580 μs
PID Temp Work memory 1280 bytes

Residual work memory 100 bytes CPU 1511/16/18 (FW>=1.7 130/75/6 μs

© Siemens SA 2013. All Rights Reserved.


Industry Sector
SIMATIC S7-1200
Technology integrated

Control functionality
o Flexible drive connection via PROFINET, PROFIBUS or analog
interfaces
o CPU 1217C with 1.5 V differential outputs for speed and position
control up to 1 MHz
o Easy programming of the motion processes with PLCopen Motion
Control blocks
o Uniform configuration for controller/HMI/drives
o Convenient diagnostics and commissioning tools (control panel, trace)
o Easy troubleshooting using automated alarm messages to the
engineering system
o Wizard for motion control technology with PTO/PWM

Easy scalability through integration of the same Motion Control functions


in all controllers
© Siemens SA 2013. All Rights Reserved.
Industry Sector
SIMATIC S7-1200
Technology integrated - Possible drive versions

Controlled operation via Pulse-Train Interface (PTO) Step-motor drive


o Simple onboard interface without position feedback or servo drive Drive

o Number of drives dependent on the 1200 version Power

o For step-motor drives or servo drives with pulse interface PLC


PTO signal

Position-controlled operation Motor


Enable
o Can be used on all 1200 versions
Ready
o HSC possible as encoder connection
o Up to 8 drives
o Absolute value encoders supported
(no overflows permitted) Servo inverter Drive

Power
PROFIdrive drives
PLC
PTO signal
o For all Sinamics PROFINET/PROFIBUS drives
o Servo or frequency inverter Enable
Encoder Motor

Analog drives Ready


o Plenty of analog Siemens and third-party drives available
Data exchange Encoder data

© Siemens SA 2013. All Rights Reserved.


Industry Sector
SIMATIC S7-1200
Technology integrated - Counting and measuring with high-speed counters
(HSC)

1214C 1217C
Max. number of HSCs
6 6
permitted
1 MHz max. single-phase 0 4

1 MHz max. A/B counter 0 2

100 kHz max. single-phase 6 6 ...


80 kHz max. A/B counter 3 3 Incremental encoder
30 kHz max. single-phase 4 4

20 kHz max. A/B counter 2 2


The two-phase or A/B rotary encoder is the incremental encoder most often used as a
result of its improved accuracy.
© Siemens SA 2013. All Rights Reserved.
Industry Sector
Thank you for your attention!

Michel Avondet
Technical Account Manager for CERN

+41 585 58 47 12
+41 79 247 20 46
michel.avondet@siemens.com

© Siemens SA 2013 All Rights Reserved.

Vous aimerez peut-être aussi