COMMENTS ON 11KV VCB HTMCC PANEL

1.

Incoming & Outgoing panels shall be two (2) separate panels. GA to be revised accordingly.

2.

The panel shall be suitable for Internal arc capability of 40kA/1sec. (AFLR)

3.

Internal arc classification to be mentioned. (LSC 2B)

4.

The size of busbar to be mentioned in SLD.

5.

Ambient design ambient temperature shall be considered as 500C.

6.

Ammeter range & Voltmeter range to be mentioned in SLD & BOM.

7.

R, Y & B phase healthy Indication lamp to be reflected in SLD.

8.

The HT sleeve shall be suitable for operation at 12kV.

9.

All indication lamps shall have cluster LEDs with LVOG protection.

10. PT Core shall have maximum burden of 50VA for each core.
11. MFM shall be considered instead of TVM. The MFM shall have dual RS-485 port on
Modbus port. BOM to be revised accordingly. The MFM shall be fed from external DC
source.
12. The Master trip relay shall be High burden only. Same to be confirmed.
13. 5/15A, 5pin socket to be considered. BOM to be revised accordingly.
14. PT selector switch, AC Source selector switch & DC source selector switch to be provided.
BOM to be revised accordingly.
15. Space heater shall be provided for each compartment separately. The space heater shall be
provided with digital ammeter & ON/FF switch.
16. Detailed GTP of Panel, LA & Breaker to be submitted.
17. In data sheet two different rating of surge arrestor has been proposed. Same to be corrected.
The rating of arrestor shall be considered as per BOM.
18. Logic diagram for breaking closing & tripping shall be revised as per attached sheet. Wring
diagram to be revised accordingly.
19. Explosion vent shall be provided for each chamber. Also, furnish the Isometric view of gas
duct arrangement for safe release of hot gas above man height level.
Page 1 of 3

20. Details of breaker front facia to be furnished.


21. Overall weight of panel to be mentioned.
22. For DC fail, Bell to be provided & for AC fail, buzzer to be considered. Hooter shall be
provided for Annunciation only.
23. TTB to be deleted.
24. The wire size for PT, Control & AC circuit shall be 2.5sq.mm, Cu. The voltage grade of
wires shall be considered as 1100V.
25. The ferruling designation shall be furnished in tabular format for each circuit.
26. Interlocking type ferruling shall be considered for numbering of wire.
27. TB arrangement details to be furnished. Minimum 20% spare TBs for power & Control each
shall be provided separately.
28. SEF relay shall be placed in 11kV CICO panel.
29. AC Source -1 & AC Source - 2 fail Indication lamp in DC circuit to be provided.
30. DC Source -1 & AC Source - 2 fail Indication lamp in AC circuit to be provided.
31. The details of Annunciation shall be considered as follows:
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
l)

Window 1: O/C Optd.


Window 2: E/F Optd.
Window 3: TCS Unhealthy.
Window 4: Bus PT supply fail.
Window 5: 27 Optd.
Window 6: 59 Optd.
Window 7: 86 Optd.
Window 8: 81U + 81O Optd.
Window 9: Spare
Window 10: Spare
Window 11: Spare
Window 12: Spare

32. The details of Relay Input to be considered as follows:


a)
b)
c)
d)
e)
f)
g)
h)

Breaker ON
Breaker OFF
TNC Switch Close.
86 operated.
Local Mode ON
Remote Mode ON
Spring charge
Earthing truck in Service

i)
j)
k)
l)

Earthing truck in Test


Breaker in Test
Breaker in Service
20% DIs Spare.

33. The details of Relay O/P to be considered as follows:


a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
l)
m)
n)

Close Permissive
Remote Close
Remote Trip.
50 Optd.
50N Optd.
51 Optd.
51N Optd.
81U Optd
81O Optd
67 + 67N Optd.
27 Optd.
59 Optd.
TCS Unhealthy.
20% Spare DO.

34. List of goose messages to be considered as follows:


a) Upstream Breaker in Service.
b) Upstream Breaker Close
c) Upstream 86 not Operated.
In case above information are not available in upstream relay, same shall be hardwired in
proposed relay model.
35. Quantity along with GA, BOM & Schematic diagram of earthing truck to be mentioned.
36. Open delta shall be provided for Line PT.
37. The protection relay model no. to be revised as per the above mentioned points
No. 30 & 31).
38. Type test report to be submitted for both panel & breaker.

(SL.