we eee “9 TEST REPORT FOR VACCUM CIRCUIT BREAKER
VOL T= CH sectne: verurecrresisr
JOB REFNO: VEPLITR) J
EXCELLENCE IN ENGINEERING PRODUCTS & SERVICES DATE: 18/12/14 Page No “|
CLIENT : M/s. RKM POWER GEN. PVT LTD. |
PROJECT :4X360 MW THERMAL POWER PLANT SheetNo 1 of S$
1. Date of testing 19/12/2014
2. Equipment Details
Make ABB
Type vaccum
Rated Volts 1aKV
Rated Current 12508
Making Capacity 410 KA
Breaking Capacity: 44KA RMS.
Operating Duty 3seEC
Sl.No. ‘4VYNo10112000774
Mfg Year 2012
3. Location & Feeder Name = BCN 2B1,2B2 20 KW CHP B
4. Insulation Resistance Test : (UsingSKV& 500V Megger)
Make :KYORISTU Range :SKV ‘SI. No.W0259362 Calib due Date :02-08-2014
— Ref Rph Yph_ | Bph |
| Pots to Eaith (CB Closed) >1T >iTa stra)
I | Bebe Pa ower poeopen >To | tT >1Ta |
[Pole to pole(closed) [ita sata Ta
5.. Contact Resistance Test : (Values in Micro Ohms) (Using Equipments Details)
Make: SCOPE Range :CRM 200B S|. No: 2306.024-141 Calib due Date :05.12.2014
[ph Ye 1 B ph
23.3 po 24.8 uO 24.6u2
I
[ Test Performed by ___| Witnessed by | Witnessed by |
Name :V.JSAHAHUL Name -—=«:DEBASNAN SWAIN Name
HAMEED MURR nonsT tg
Designation: SPT&CENGINEER Designation Designation
Signature &
Date
Signature & Signature &
Date lo Date
2r\a-TEST REPORT FOR VACCUM CIRCUIT BREAKER
\ /Ol T= —~-4 DOC. NO. : VEPLIT&CFICB/003/
JOB REFNO: VEPLITR) /
EXCELLENCE IN ENGINEERING PRODUCTS & sEAVICES DATE: 18/12/14 | Page No
CLIENT : M/s. RKM POWER GEN. PVT LTD.
| PROJECT :4X360 MW THERMAL POWER PLANT | Sheet No 2 of 3
7. Pick up Voltage of Operating Coil : (Using Equipments Details)
Make :FLUKE Range: 178 SI, No.93270239, Calib due Date :26-03-2014
Closing Coil 116.4VDC
Tripping Coil-t 119.3 VDC
Tripping Coll-2 I
8. Breaker Operating Time at Rated Pressure and Rated Coil Voltage Test : (Using Equipments Details)
Make: scope Range :RYB 1. No.2100.02X188 Calib due Date :15/12/2015
— —Yph |B ph
“cising t 57 mses | 87 mses
“Tripping 2Bmsec 28 msec —
(Close ~ Open 35msec | 36 msec.
| ~Yph
| Closing [ 57 msec
Tripping ~ 26 msec |
‘Close = Open ‘36 msec 36 msec }
1 Rph | _Yph _Bph |
“87 msec 57 mséc ST msec |
26 msec 25msec | 26 msec |
39 msec 38msec | 39msec
Test Performed by Witnessed by
Name : Vid SAHAHUL/ :DEBASNAN SWAIN Name
HAMEED
Designation : ou NSN
are Lane
Date 5 a
ayes
Designation |on po TEST REPORT FOR VACCUM CIRCUIT BREAKER |
VOL =H] bocnno. verurecereoios |
a = — JOBREFNO: VEPLTR) / 1
EXCELLENCE IN ENG! PRODUCTS & SERVICES DATE: 18/12/14 Page No
CLIENT : M/s. RKM POWER GEN. PVT LTD
PROJECT :4X360 MW THERMAL POWER PLANT SheetNo 3 of 3 |
09. Operational checks
[a Manual OK]
Close _ 0k
‘Open. Ok
b. Electrical Ok
Close | Ok
Open Ok
tection Tripping Ok
‘Anti Pumping Function Ok
40. Functional Checks:
Emergency Trip - ok
| ON-OFF Indication ok
Spring charge Limit Switch ok
CB Aux. contacts ok
‘Auto Trip Indication ‘ok
Trip circuit heaithy ok
“Interchangeabilty of CB ok
‘Auxillary switch operation ok
Operation Counter ok
Heater / Heater Switch / Thermostat ok
Illumination lamp ok
Relay U/P and O/P have checked Ok
Inter lock between Incomer and Tie checked Ok
‘According to scheme Indication checked ok
44. Remarks : Test will found satisfactory
Name: V.J SAHAHUL Name :DEBASNAN SWAIN Name
“Test Performed by Witnessed by | Witnessed by |
~ Signature &
Designation I
Date