Deluge Valve

The sizing of deluge valve depends on the total water flow required for the Spray system.
Valve
a.
b.
c.

Size (mm)
150
100
80

LPM
13500
5000
1150

Whereas for foam system 80mm DV is sufficient.


Inline Inductor maximum working pressure is 12bar, minimum is 6.4bar. Selection of inline inductor size:
Q=Kp
Q= total solution flow rate in LPM
K= Inductor constant
P= Inlet pressure in Kg/sq.cm
To find K factor: (example)
Q= 200Lpm
P= 7 kg/sq.cm
Ie. K = 80.71

Inductor Size
50NB
65NB
80NB

K factor range
28.4 to 85.00
76.0 to 170.0
151.2 to 340.2

100NB
Ie for the above K factor 50NB inductor is sufficient

302.0 to 680.3