Vous êtes sur la page 1sur 3

PMAC720 Multifunction Power Meter

Feature

Suit for LV/ HV voltage system

Compact design with all real-time measurement

Consist of basic unit and optional modules

10 years back-up of integrated energy data

Large LCD, high brightness

High accuracy, V or I is 0.2%, kWh is class 1

CT and PT programmable

Panel size: 96 x 96mm

Password protect

Standard: IEC62053-21/ 23, CE

Basic Function
PMAC720 provides one RS485 communication,
measures and display real-time parameters:

VoltageUa, Ub, Uc, Uab, Ubc, Uca,

CurrentIa, Ib, Ic, In

Active power Pa, Pb, Pc, P

Reactive power Qa, Qb, Qc, Q

Power factorPFa, PFb, PFc, PF

Frequency--F

Active energykWh

Reactive energy kvarh

Optional Function

Up to 31st harmonic analysis

Clock and SOE (event log)

TOU (multi-tariff)

Two RS485 communication port

One 4~20mA analog input

One 4~20mA analog output

Basic unit

Optional module

Optional Module

4 status input (dry contact) + 4 relay output

8 status input (dry contact) + 2 relay output

4 status input (wet contact) + 4 relay output

8 status input (wet contact) + 2 pulse output

2 pulse output + 2 analog output

Status input apply to monitoring various kinds of switch status


Relay output apply to monitoring over limit alarm with setpoint system
Pulse output apply to exporting pulse signal for active/ reactive energy

Technical Specification
Metering

True RMS, 1 sec refresh time

Power supply

85~265VAC, 80~300VDC

Input

Rate current: 5A (optional 1A)


Rate voltage: direct 120 ~277Vph-N, (optional)
PT secondary 57.7V/ 100V
Frequency: 50/ 60Hz

Power loss

2VA

Communication

RS485 serial, support Modbus-RTU


Baud rate: 2400, 4800, 9600, 19200bps
Address: 1~247

Dimension
(L x W x H)

Panel: 96 x 96 x 16 mm
Cut-out: 89.5 x 89.5 x 55 mm (+0.5mm)

IP index

IP54 (front panel) and IP20 (case)

Weight

Approx. 500gr.

Overload

120% of rated, continuously


Instantaneous current: 10 times/ sec
Instantaneous voltage: 2 times/ sec

Status input
(optional)

8 channels,
provides 30VDC power if it is dry contact

Relay output
(optional)

4 channels,
Node capacity: 220VAC/5A, 30VDC/5A

Analog output
(optional)

2 channels,
4~20mA, load resistance: 400

Pulse output
(optional)

2 channels, Pulse width: 20ms


Pulse constant: 1~65535 programmable
1 pulse = (1 pulse constant PT CT) kWh

Power frequency withstand voltage

AC 2KV/minute

Insulation resistance

50M

Impulse withstand voltage

4kV (peak),
1.2/50uS
15

PMAC720 Multifunction Power Meter


Standard (EMC)

Environment

Electrostatic discharge immunity test


RF immunity test
Electrical fast transient/burst immunity test
Surge immunity test (1, 2/50s8/20s)
Conducted emissions
Radiated emissions

Operating temperature: -20~ +60


Storage temperature: -30~ +70
Humidity: 5%~95% non-condensing

IEC 61000-4-2 Edition 2.0 (2008)


IEC 61000-4-3 Edition 3.0 (2007)
IEC 61000-4-4 Edition 2.0 (2004)
IEC 61000-4-5 Edition 2.0 (2005)
EN 61326-1:2006, CISPR 11:2004
EN 61326-1:2006, CISPR 11:2004

Parameter

Accuracy

Resolution

Voltage

0.2%

0.01V

Current

0.2%

0.001A

Power

0.5%

0.1W/ var

Measuring Range
Directly: 300Vph-N, 520Vph-ph
PT primary: 0~599,999V
PT secondary: 57.7Vph-N, 100Vph-ph
CT primary: 0~49,999A
CT secondary: 1 A or 5A
each phase: 0~100 MW/ Mvar
Total: 0~300 MW/ Mvar

Power factor

0.5%

0.001

-1.000~+1.000

Frequency

0.01

0.01Hz

45~ 65 Hz

Active energy

1.0%

0.1kWh

0~ 99,999,999.9 kWh

Reactive energy

2.0%

0.1kvarh

0~ 99,999,999.9 kVarh

Individual harmonic

1.0%

0.001

0~100.0%

Un-balance

1.0%

0.001

0~100.0%

PMAC-

720N

720A

720B

720C

720D

720E

Feature
U-LL, U-LN, 3I, In, 3P, P, 3Q, Q,
F, 3PF, PF, kWh, kvarh,
RS485 communication

4 status input (dry contact) + 4 relay output

8 status input (dry contact) + 2 relay output

4 status input (wet contact) + 4 relay output

8 status input (wet contact) + 2 relay output

2 pulse output + 2 analog output (4~20mA)


H

Up to 31st harmonic analysis

Clock and SOE (event log) function

TOU ( time-of-use)

Two RS485 communication ports

AI

One 4~20mA analog input

AO

One 4~20mA analog output

Apparent power

Demand function

Remark: = standard feature, =optional function = conditional function


1. If select -F, -T should be selected also.
2. Analog port-AI and AO are incompatible feature, can not be selected together
3. For module PMAC720N-, PMAC720E- , the SOE function is invalid.

16

PMAC720 Multifunction Power Meter


Dimension & Installation
unit: mm

Order Information
PMAC720---- ----
N
A
B
C
D
E

Basic Module
Basic Module + 4 Status Inputs (Dry Contact) + 4 Relay Outputs
Basic Module + 8 Status Inputs (Dry Contact) + 2 Relay Outputs
Basic Module + 4 Status Inputs (Wet Contact) + 4 Relay Outputs
Basic Module + 8 Status Inputs (Wet Contact) + 2 Relay Outputs
Basic Module + 2 Pulse Outputs + 2 Analog Outputs (4-20mA)

H
T
F
M

Up to 31st Harmonic Analysis


Clock and SOE (Event Log) Function
TOU (Time- of- Use)
Two RS485 Communication Ports

AI
AO

One 4-20mA Analog Input


One 4-20mA Analog Output

V1
V2
V3
V4
V5
V6
V7

57.7/ 100V (via PT), 5A


57.7/ 100V (via PT), 1A
220/ 380V (direct), 5A
220/ 380V (direct), 1A
120/ 208V (direct), 5A
240/ 415V (direct), 5A
277/ 480V (direct), 5A

Example: Model No. PMAC720-A-H-AO-V1, which indicates the device provides basic function + 4 status input + 4 relay
output + harmonic analysis + one analog output, rated input 57.7/ 100V, 5A