FACTORY TEST PROCEDURE OF


FM-200 EXTINGUISHING PANEL MODEL RP-2002
Visual Inspection
S.No

DESCRIPTION

Check the wiring hookup with the wiring diagram

Insure that no pieces of wire have fallen into the


circuitry

Ensure correct input power connect to F.E.C.P.

Ensure All Input & Output Devices or dummy load


are connected properly in accordance with the
wiring diagram.

OK / Not OK

FUNCTIONAL TEST
S.No

DESCRIPTION

Disconnect AC power and Battery Power of the


F.E..C.P

Connect an EOL (End Of Line) device to serve as a


dummy load.

Reconnect AC & Battery Power.

Simulate a first zone alarm condition by


introducing smoke into 1 detector. This should
cause the first zone alarm condition.
-

The red Fire Alarm Indicator will illuminate


The LCD display will indicate an alarm
condition for Zone 1
The control panel piezo will sound
The alarm relay will Energize
The devices connect to the indicating
circuit (s) programmed to activate on Zone
1 alarm will turn on

OK / Not OK

JOB NO.:
ENERGY HOUSE COMPANY
FIRE & SECURITY DIVISION

EH-227-08-B

PROJECT:
Al MISFALAH
SUBSTATION

P.O. 92102 RIYADH 11653


TEL#01 4780320 FAX#01 4731604

Simulate a second zone alarm condition by


introducing smoke into zone 2 detector. This
should cause the second zone alarm condition.
-

Simulate a Manual Release Activation This should


Cause:-

Sr.
No

The red Fire Alarm Indicator will illuminate


The LCD display will indicate an alarm
condition for Zone 2
The control panel piezo will sound
The devices connect to the indicating
circuit (s) programmed to activate on Zone
2 alarm will turn on
Pre- Discharge delay timer shall start.
Output 1 will perform agent release at the
end of the Pre- Discharge delay timer
Output 2 (Release Stage Notification will
indicate the Release Stage.

The red Fire Alarm Indicator will illuminate


The LCD display will indicate Manual
Release
The control panel piezo will sound
The alarm relays will Energize
Output 1 will perform and agent release
Output 2 (Release Stage Notification) will
indicate the Release Stage.

Simulate an Abort Station Under UL 864 Approved


should cause :The Pre Discharge Timer will count down to 10
second and hold there. If the Abort Switch is
Released, the timer resumes the countdown from
10 second.

COMMENTS IF ANY

INSPECTION CONDUCTED AND WITNESS BY


Signature
Name & Company

Page:
2