Electrical devices
Volume 2
Electrical devices
2nd edition
February 2004
Index
Introduction .............................................................................................. 2
1 Standards
1.1 General aspects .............................................................................. 3
1.2 IEC Standards for electrical installation .......................................... 15
2 Protection of feeders
2.1 Introduction ................................................................................... 22
2.2 Installation and dimensioning of cables ......................................... 25
2.2.1 Current carrying capacity and methods of installation .......... 25
Installation not buried in the ground ..................................... 31
Installation in ground ............................................................ 44
2.2.2 Voltage drop ........................................................................ 56
2.2.3 Joule-effect losses ............................................................... 66
2.3 Protection against overload ........................................................... 67
2.4 Protection against short-circuit ...................................................... 70
2.5 Neutral and protective conductors ................................................ 78
2.6 Busbar trunking systems ............................................................... 86
3 Protection of electrical equipment
3.1 Protection and switching of lighting circuits ................................. 101
3.2 Protection and switching of generators ....................................... 110
3.3 Protection and switching of motors ............................................. 115
3.4 Protection and switching of transformers .................................... 131
4 Power factor correction
4.1 General aspects .......................................................................... 146
4.2 Power factor correction method .................................................. 152
4.3 Circuit-breakers for the protection and
swiching of capacitor banks ........................................................ 159
5 Protection of human beings
5.1 General aspects: effects of current on human beings .................. 162
5.2 Distribution systems .................................................................... 165
5.3 Protection against both direct and indirect contact ...................... 168
5.4 TT system ................................................................................... 171
5.5 TN system .................................................................................. 174
5.6 IT system .................................................................................... 177
5.7 Residual current devices ............................................................. 179
5.8 Maximum protected length for the protection of human beings ... 182
Annex A: Calculation tools
A.1 Slide rules ............................................................................. 200
A.2 DOCWin ............................................................................... 205
Annex B: Calculation of load current Ib .............................................. 209
Annex C: Calculation of short-circuit current ................................... 213
Annex D: Calculation of the coefficient k for the cables .................. 227
Annex E: Main physical quantities and
electrotechnical formulas ................................................... 230
Introduction
1 Standards
The scope of this electrical installation handbook is to provide the designer and
user of electrical plants with a quick reference, immediate-use working tool.
This is not intended to be a theoretical document, nor a technical catalogue,
but, in addition to the latter, aims to be of help in the correct definition of
equipment, in numerous practical installation situations.
Juridical Standards
These are all the standards from which derive rules of behavior for the juridical
persons who are under the sovereignty of that State.
The electrical installation handbook is a tool which is suitable for all those who
are interested in electrical plants: useful for installers and maintenance technicians
through brief yet important electrotechnical references, and for sales engineers
through quick reference selection tables.
Validity of the electrical installation handbook
Some tables show approximate values due to the generalization of the selection
process, for example those regarding the constructional characteristics of
electrical machinery. In every case, where possible, correction factors are given
for actual conditions which may differ from the assumed ones. The tables are
always drawn up conservatively, in favour of safety; for more accurate
calculations, the use of DOCWin software is recommended for the dimensioning
of electrical installations.
Application fields
Electrotechnics and
Electronics
International Body
European Body
IEC
CENELEC
Telecommunications
ITU
ETSI
Mechanics, Ergonomics
and Safety
ISO
CEN
This technical collection takes into consideration only the bodies dealing with electrical and electronic
technologies.
1 Standards
1 Standards
The Low Voltage Directive refers to any electrical equipment designed for use
at a rated voltage from 50 to 1000 V for alternating current and from 75 to 1500 V for
direct current.
In particular, it is applicable to any apparatus used for production, conversion,
transmission, distribution and use of electrical power, such as machines,
transformers, devices, measuring instruments, protection devices and wiring
materials.
The following categories are outside the scope of this Directive:
electrical equipment for use in an explosive atmosphere;
electrical equipment for radiology and medical purposes;
electrical parts for goods and passenger lifts;
electrical energy meters;
plugs and socket outlets for domestic use;
electric fence controllers;
radio-electrical interference;
specialized electrical equipment, for use on ships, aircraft or railways, which
complies with the safety provisions drawn up by international bodies in which
the Member States participate.
1 Standards
1 Standards
CE conformity marking
The manufacturer
draw up the technical
documentation
covering the design,
manufacture and
operation of the
product
The manufacturer
guarantees and declares
that his products are in
conformity to the technical
documentation and to the
directive requirements
The international and national marks of conformity are reported in the following
table, for information only:
COUNTRY
Symbol
Mark designation
Applicability/Organization
EUROPE
AUSTRALIA
AS Mark
AUSTRALIA
S.A.A. Mark
Standards Association of
Australia (S.A.A.).
The Electricity Authority of New
South Wales Sydney Australia
AUSTRIA
ASDC008045F0201
Manufacturer
EC declaration of
conformity
It is always advisable to ask ABB SACE as regards the typologies and the
performances of the certified circuit-breakers or to consult the section certificates
in the website http://bol.it.abb.com.
Flow diagram for the conformity assessment procedures established by the Directive
73/23/EEC on electrical equipment designed for use within particular voltage range:
Technical file
RINA
DNV
BV
GL
LRs
ABS
OVE
ABB SACE - Electrical devices
1 Standards
COUNTRY
Symbol
1 Standards
Mark designation
Applicability/Organization
COUNTRY
AUSTRIA
VE Identification
Thread
Cables
BELGIUM
CEBEC Mark
BELGIUM
Mark designation
Applicability/Organization
CROATIA
KONKAR
DENMARK
DEMKO
Approval Mark
CEBEC Mark
FINLAND
Safety Mark
of the Elektriska
Inspektoratet
BELGIUM
Certification of
Conformity
FRANCE
ESC Mark
Household appliances
CANADA
CSA Mark
FRANCE
NF Mark
CHINA
CCEE Mark
FRANCE
NF Identification
Thread
Cables
Czech Republic
EZU Mark
FRANCE
NF Mark
Slovakia
Republic
FRANCE
NF Mark
Household appliances
EVPU Mark
Symbol
1 Standards
COUNTRY
Symbol
1 Standards
Mark designation
Applicability/Organization
COUNTRY
GERMANY
VDE Mark
GERMANY
VDE
Identification Thread
GERMANY
Symbol
Mark designation
Applicability/Organization
ITALY
IMQ Mark
NORWAY
Norwegian Approval
Mark
NETHERLANDS
KEMA-KEUR
KWE
Electrical products
Certification of
Conformity
SISIR
SIQ
AEE
Electrical products.
The mark is under the control of
the Asociacin Electrotcnica
Espaola(Spanish Electrotechnical
Association)
KEUR
HUNGARY
MEEI
B
RUSSIA
Electrical equipment
SLOVENIA
IIRS Mark
Electrical equipment
SPAIN
SIN
PP
R O V ED T
IIRS Mark
IRELAND
OF
CO N F
R M I DA D A
AR
R MA S U N
TY
MAR
FO
NO
MI
C A DE CON
IRELAND
GAPO
STA N D AR
SINGAPORE
E
JIS Mark
JAPAN
POLAND
geprfte
Sicherheit
VDE-GS Mark
for technical
equipment
GERMANY
M
I . I. R . S .
10
11
1 Standards
Mark designation
Applicability/Organization
COUNTRY
SPAIN
AENOR
Asociacin Espaola de
Normalizacin y Certificacin.
(Spanish Standarization and
Certification Association)
SWEDEN
SEMKO
Mark
UNITED
KINGDOM
SWITZERLAND
Safety Mark
UNITED
KINGDOM
SWITZERLAND
Symbol
UNITED
KINGDOM
B R IT I S
AN I
Y
ET
AF
ND
Applicability/Organization
BEAB
Safety Mark
BSI
Safety Mark
BEAB
Kitemark
UNDERWRITERS
LABORATORIES
Mark
DENT LA B
OR
EN
TI
Mark designation
OR
AT
EP
TES
U.S.A.
A N D AR
ST
ROVED
TO
PP
Symbol
COUNTRY
1 Standards
FO
R P U B L IC
L I S T E D
(Product Name)
(Control Number)
U.S.A.
UNDERWRITERS
LABORATORIES
Mark
UNITED
KINGDOM
ASTA Mark
U.S.A.
UL Recognition
UNITED
KINGDOM
BASEC Mark
CEN
CEN Mark
UNITED
KINGDOM
BASEC
Identification Thread
Cables
CENELEC
Mark
Cables
AD
E
M
AR
K
C
ER
TI
FI
C
AT
IO
N
TR
12
SWITZERLAND
13
1 Standards
COUNTRY
Symbol
1 Standards
Mark designation
CENELEC
Harmonization Mark
EC
Ex EUROPEA Mark
CEEel
CEEel Mark
Applicability/Organization
STANDARD
YEAR
TITLE
IEC 60027-1
1992
IEC 60034-1
1999
IEC 60617-DB-12M
2001
IEC 61082-1
1991
IEC 61082-2
1993
IEC 61082-3
1993
IEC 61082-4
1996
IEC 60038
IEC 60664-1
1983
2000
IEC 60909-0
2001
IEC 60865-1
1993
IEC 60781
1989
IEC 60076-1
IEC 60076-2
2000
1993
IEC 60076-3
2000
IEC 60076-5
2000
IEC/TR 60616
1978
IEC 60726
IEC 60445
1982
1999
EC - Declaration of Conformity
The EC Declaration of Conformity is the statement of the manufacturer, who
declares under his own responsibility that all the equipment, procedures or
services refer and comply with specific standards (directives) or other normative
documents.
The EC Declaration of Conformity should contain the following information:
name and address of the manufacturer or by its European representative;
description of the product;
reference to the harmonized standards and directives involved;
any reference to the technical specifications of conformity;
the two last digits of the year of affixing of the CE marking;
identification of the signer.
A copy of the EC Declaration of Conformity shall be kept by the manufacturer
or by his representative together with the technical documentation.
14
15
1 Standards
16
1 Standards
STANDARD
YEAR
TITLE
STANDARD
YEAR
TITLE
IEC 60073
1996
IEC 60947-5-6
1999
IEC 60446
1999
IEC 60947-6-1
1998
Low-voltage switchgear and controlgear Part 5-6: Control circuit devices and
switching elements DC interface for
proximity sensors and switching
amplifiers (NAMUR)
Low-voltage switchgear and controlgear Part 6-1: Multiple function equipment
Automatic transfer switching equipment
IEC 60447
1993
IEC 60947-6-2
1999
IEC 60947-1
2001
IEC 60947-2
2001
IEC 60947-7-1
1999
IEC 60947-3
2001
IEC 60947-7-2
1995
IEC 60439-1
1999
IEC 60439-2
2000
IEC 60439-3
2001
IEC 60439-4
1999
IEC 60439-5
1999
IEC 61095
2000
IEC 60947-4-1
2000
IEC 60947-4-2
2002
IEC 60947-4-3
1999
IEC 60947-5-1
2000
IEC 60947-5-2
1999
IEC 60947-5-3
1999
IEC 60947-5-4
1996
IEC 60947-5-5
1997
Low-voltage switchgear and controlgear Part 6-2: Multiple function equipment Control and protective switching devices
(or equipment) (CPS)
Low-voltage switchgear and controlgear Part 7: Ancillary equipment - Section 1:
Terminal blocks
Low-voltage switchgear and controlgear Part 7: Ancillary equipment - Section 2:
Protective conductor terminal blocks for
copper conductors
Low-voltage switchgear and controlgear
assemblies - Part 1: Type-tested and
partially type-tested assemblies
Low-voltage switchgear and controlgear
assemblies - Part 2: Particular
requirements for busbar trunking systems
(busways)
Low-voltage switchgear and controlgear
assemblies - Part 3: Particular
requirements for low-voltage switchgear
and controlgear assemblies intended to
be installed in places where unskilled
persons have access for their use Distribution boards
Low-voltage switchgear and controlgear
assemblies - Part 4: Particular
requirements for assemblies for
construction sites (ACS)
17
1 Standards
1 Standards
STANDARD
YEAR
TITLE
IEC 60890
1987
IEC 61117
1992
IEC 60092-303
1980
IEC 60092-301
1980
IEC 60092-101
1994
IEC 60092-401
1980
IEC 60092-201
1994
IEC 60092-202
1994
IEC 60092-302
1997
IEC 60092-350
2001
IEC 60092-352
1997
IEC 60364-5-52
2001
IEC 60227
1998
1997
1997
1997
1998
2001
1995
IEC 60228
IEC 60245
1978
1998
1998
1994
18
STANDARD
YEAR
TITLE
1994
1994
1994
1998
IEC 60309-2
1999
IEC 61008-1
1996
IEC 61008-2-1
1990
IEC 61008-2-2
1990
IEC 61009-1
1996
IEC 61009-2-1
1991
IEC 61009-2-2
1991
IEC 60670
1989
IEC 60669-2-1
2000
IEC 60669-2-2
2000
IEC 606692-3
1997
19
1 Standards
1 Standards
STANDARD
YEAR
TITLE
STANDARD
YEAR
TITLE
IEC 60079-10
1995
IEC 61032
1997
IEC 61000-1-1
1992
IEC 60079-14
1996
IEC 61000-1-2
2001
IEC 60079-17
1996
IEC 60269-1
1998
IEC 61000-1-3
2002
IEC 60269-2
1986
IEC 60269-3-1
2000
IEC 60127-1/10
1999
1989
1988
1996
1988
1994
20
IEC 60730-2-7
2001
1990
IEC 60364-1
2001
IEC 60364-4
2001
IEC 60364-5
20012002
IEC 60364-6
2001
IEC 60364-7
19832002
IEC 60529
2001
21
2.1 Introduction
2.1 Introduction
2 Protection of feeders
2 Protection of feeders
The following definitions regarding electrical installations are derived from the
Standard IEC 60050.
Characteristics of installations
Voltages
Nominal voltage (of an installation) Voltage by which an installation or part of
an installation is designated.
Note: the actual voltage may differ from the nominal voltage by a quantity within
permitted tolerances.
Currents
Design current (of a circuit) The current intended to be carried by a circuit in
normal service.
Current-carrying capacity (of a conductor) The maximum current which can
be carried continuously by a conductor under specified conditions without its
steady-state temperature exceeding a specified value.
22
Wiring systems
Wiring system An assembly made up of a cable or cables or busbars and the
parts which secure and, if necessary, enclose the cable(s) or busbars.
Electrical circuits
Electrical circuit (of an installation) An assembly of electrical equipment of
the installation supplied from the same origin and protected against overcurrents
by the same protective device(s).
Distribution circuit (of buildings) A circuit supplying a distribution board.
Final circuit (of building) A circuit connected directly to current using
equipment or to socket-outlets.
Other equipment
Electrical equipment Any item used for such purposes as generation,
conversion, transmission, distribution or utilization of electrical energy, such as
machines, transformers, apparatus, measuring instruments, protective devices,
equipment for wiring systems, appliances.
Current-using equipment Equipment intended to convert electrical energy
into another form of energy, for example light, heat, and motive power
Switchgear and controlgear Equipment provided to be connected to an
electrical circuit for the purpose of carrying out one or more of the following
functions: protection, control, isolation, switching.
Portable equipment Equipment which is moved while in operation or which
can easily be moved from one place to another while connected to the supply.
Overcurrent Any current exceeding the rated value. For conductors, the rated
value is the current-carrying capacity.
23
2.1 Introduction
2 Protection of feeders
2 Protection of feeders
Installation dimensioning
The flow chart below suggests the procedure to follow for the correct
dimensioning of a plant.
Load analysis:
- definition of the power absorbed by the loads and relevant position;
- definition of the position of the power distribution centers (switchboards);
- definition of the paths and calculation of the length of the connection elements;
- definition of the total power absorbed, taking into account the utilization factors
and demand factors.
Dimensioning of conductors:
- evaluation of the current (I b ) in the single connection elements;
- definition of the conductor type (conductors and insulation materials,
configuration,...);
- definition of the cross section and of the current carrying capacity;
- calculation of the voltage drop at the load current under specific reference
conditions (motor starting,).
insulation material (none, PVC, XLPE-EPR): the insulation material affects the
maximum temperature under normal and short-circuit conditions and therefore
the exploitation of the conductor cross section [see Chapter 2.4 Protection
against short-circuit].
the type of conductor (bare conductor, single-core cable without sheath, singlecore cable with sheath, multi-core cable) is selected according to mechanical
resistance, degree of insulation and difficulty of installation (bends, joints along
the route, barriers...) required by the method of installation.
- verification of the protection against overload: the rated current or the set current
of the circuit-breaker shall be higher than the load current, but lower than the
current carrying capacity of the conductor:
Ib In Iz
- verification of the protection against short-circuit: the specific let-through energy
by the circuit breaker under short-circuit conditions shall be lower than the specific
let-through energy which can be withstood by the cable:
I2t k2S2
negative
outcome
24
1SDC010001F0901
Conductors and
cables
Bare conductors
Insulated conductors
Sheathed cables
Multi-core
(including armoured and
mineral insulated)
Single-core
Method of installation
Cable trunking
(including skirting
Cable ladder
trunking, flush floor Cable
Without Clipped
Cable tray
On in- Support
fixings direct Conduit
trunking)
ducting Cable brackets sulators wire
+
+
+
+
+
+
+ Permitted.
Not permitted.
0 Not applicable, or not normally used in practice.
25
2 Protection of feeders
2 Protection of feeders
For industrial installations, multi-core cables are rarely used with cross section
greater than 95 mm2.
To define the current carrying capacity of the conductor and therefore to identify
the correct cross section for the load current, the standardized method of
installation that better suits the actual installation situation must be identified
among those described in the mentioned reference Standard.
From Tables 2 and 3 it is possible to identify the installation identification number,
the method of installation (A1, A2, B1, B2, C, D, E, F, G) and the tables to
define the theoretical current carrying capacity of the conductor and any
correction factors required to allow for particular environmental and installation
situations.
Situations
Building voids
Cable channel
Buried in
Ground
Embedded in
Structure
Surface
Mounted
Overhead
Without
fixings
40, 46,
15, 16
56
72, 73
57, 58
Item n.
Description
Room
A1
Room
A2
Room
A1
Methods of
installation
Method of installation
Cable trunking
(including skirting
Cable ladder
Support
trunking, flush floor Cable
With
Cable tray
On
fixings Conduit
trunking)
ducting Cable brackets insulators wire
30, 31,
0
15, 16
0
32, 33, 34
30, 31, 32,
56
54, 55
0
44
33, 34
0
70, 71
1, 2
59, 60
20, 21
4, 5
10, 11
70, 71
44, 45
36
36
35
6, 7, 8, 9
-
30, 31,
32, 33, 34
30, 31, 32,
33, 34
6
7
TV
TV
ISDN
A1
13
14
B1 (13)
or
B2 (14)
20
21
B1
12
16
B2
B1 (8) or B2 (9)
15
26
B1
8
9
ISDN
or
in
A1
or
in
A1
1SDC010001F0201
Methods of installation
Reference
method of
installation to be
used to
obtain currentcarrying
capacity
27
2 Protection of feeders
Methods of
installation
Item n.
2 Protection of feeders
Reference
method of
installation to be
used to
obtain currentcarrying
capacity
Description
Methods of
installation
Description
Reference
method of
installation to be
used to
obtain currentcarrying
capacity
40
1.5 De V < 20 De
B2
V 20 De
B1
24
1.5 De V < 20 De
B2
V 20 De
B1
44
Item n.
0.3 De
V
De
30
On unperforated tray
0.3 De
V
De
0.3 De
31
On perforated tray
1.5 De V < 5 De
E or F
V
0.3 De
B2
5 De V < 50 De
B1
0.3 De
1.5 De V < 5 D e
V
De
32
46
E or F
B2
5 De V < 50De
B1
0.3 De
34
On ladder
E or F or G
E or F
TV
ISDN
35
36
28
B1
51
B2
52
53
B1 (52)
or
B2 (53)
54
TV
ISDN
E or F
De
1.5 De V < 20 De
B2
V 20 De
B1
29
1SDC010002F0201
33
50
2 Protection of feeders
Methods of
installation
Item n.
2 Protection of feeders
Description
Reference
method of
installation to be
used to
obtain currentcarrying
capacity
where:
I0 is the current carrying capacity of the single conductor at 30 C reference
ambient temperature;
k1 is the correction factor if the ambient temperature is other than 30 C;
k2 is the correction factor for cables installed bunched or in layers or for
cables installed in a layer on several supports.
The cable carrying capacity of a cable that is not buried in the ground is obtained
by using this formula:
I z = I 0 k1k2 = I 0 ktot
55
B1
56
B1
57
58
59
B1
Correction factor k1
The current carrying capacity of the cables that are not buried in the ground
refers to 30 C ambient temperature. If the ambient temperature of the place
of installation is different from this reference temperature, the correction factor
k1 on Table 4 shall be used, according to the insulation material.
B2
70
71
72
73
30
1SDC010003F0201
60
Ambient
temperature (a)
C
10
15
20
25
35
40
45
50
55
60
65
70
75
80
85
90
95
PVC
1.22
1.17
1.12
1.06
0.94
0.87
0.79
0.71
0.61
0.50
(a)
Mineral (a)
PVC covered or
bare and exposed Bare not exposed
to touch 70 C
to touch 105 C
1.26
1.14
1.20
1.11
1.14
1.07
1.07
1.04
0.93
0.96
0.85
0.92
0.87
0.88
0.84
0.67
0.80
0.57
0.75
0.45
0.70
0.65
0.60
0.54
0.47
0.40
0.32
31
2 Protection of feeders
2 Protection of feeders
Correction factor k2
The cable current carrying capacity is influenced by the presence of other cables
installed nearby. The heat dissipation of a single cable is different from that of
the same cable when installed next to the other ones. The factor k2 is tabled
according to the installation of cables laid close together in layers or bunches.
a)
b)
> 2 De2
a)
De2
1SDC010003F0001
De1
c)
b)
bunch: several circuits constituted by cables that are not spaced and are not
installed in a layer; several layers superimposed on a single support (e.g. tray)
are considered to be a bunch.
32
1SDC010002F0001
c)
< 30 cm
33
2 Protection of feeders
2 Protection of feeders
The reduction factor for a group containing different cross sections of insulated
conductors or cables in conduits, cable trunking or cable ducting is:
k2 =
1
n
where:
k2 is the group reduction factor;
n is the number of circuits of the bunch.
The reduction factor obtained by this equation reduces the danger of overloading
of cables with a smaller cross section, but may lead to under utilization of
cables with a larger cross section. Such under utilization can be avoided if large
and small cables are not mixed in the same group.
Perforated
trays
0.98
0.91
0.87
0.96
0.87
0.81
0.95
0.85
0.78
0.96
0.86
0.95
0.84
32
1.00
0.97
0.96
33
0.98
0.93
0.89
0.97
0.90
0.86
1.00
0.98
0.96
0.97
0.93
0.89
0.96
0.92
0.86
1.00
0.91
0.89
1.00
0.90
0.86
31
(note 2)
Ladder
supports,
cleats, etc.
(note 2)
Three cables in
horizontal
formation
Touching
31
225 mm
(note 3)
To be used with
current-carrying
capacities,
reference
Use as a
multiplier to
rating for
20 mm
Perforated
trays
Three cables in
vertical
formation
Touching
34
Three cables in
horizontal
formation
20 mm
Methods A to F
2 D
2D
ee
31
D
Dee
(note 2)
No further
reduction
factor for more
than
nine circuits or
1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72
multicore cables
Number of three-phase
circuits (note 4)
Touching
Vertical
perforated
trays
20 mm
Method C
Spaced
Vertical
perforated
trays
2 D e
31
225 mm
Three cables in
trefoil formation
(note 3)
De
Methods E and F
NOTE 1 These factors are applicable to uniform groups of cables, equally loaded.
NOTE 2 Where horizontal clearances between adjacent cables exceeds twice their overall diameter, no reduction
factor need be applied.
NOTE 3 The same factors are applied to:
groups of two or three single-core cables;
multi-core cables.
NOTE 4 If a system consists of both two- and three-core cables, the total number of cables is taken as the number of
circuits, and the corresponding factor is applied to the tables for two loaded conductors for the two-core
cables, and to the tables for three loaded conductors for the three-core cables.
NOTE 5 If a group consists of n single-core cables it may either be considered as n/2 circuits of two loaded
conductors or n/3 circuits of three loaded conductors.
Ladder
supports,
cleats, etc.
32
1.00
1.00
1.00
33
0.97
0.95
0.93
(note 2)
34
0.96
0.94
0.90
2 D e
De
20 mm
NOTE 1 Factors are given for single layers of cables (or trefoil groups) as shown in the table and do not apply
when cables are installed in more than one layer touching each other. Values for such installations may be
significantly lower and must be determined by an appropriate method.
NOTE 2 Values are given for vertical spacings between trays of 300 mm. For closer spacing the factors should be
reduced.
NOTE 3 Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back and at
least 20 mm between the tray and any wall. For closer spacing the factors should be reduced.
NOTE 4 For circuits having more than one cable in parallel per phase, each three phase set of conductors should
be considered as a circuit for the purpose of this table.
34
35
1SDC010004F0201
Arrangement
Item (cables touching)
1
Bunched in air, on a
surface, embedded or
enclosed
Single layer on wall,
2
floor or unperforated
tray
Single layer fixed
3
directly under a
wooden ceiling
Single layer on a
4
perforated horizontal or
vertical tray
Single layer on ladder
5
support or cleats etc.
Number of
trays
2 Protection of feeders
2 Protection of feeders
To summarize:
Number of cables
Number
of trays
1.00
0.88
0.82
0.79
0.76
0.73
1.00
0.87
0.80
0.77
0.73
0.68
1.00
0.86
0.79
0.76
0.71
0.66
1.00
1.00
0.98
0.95
0.91
1.00
0.99
0.96
0.92
0.87
1.00
0.98
0.95
0.91
0.85
Touching
Perforated
trays
20 mm
31
(note 2)
Spaced
De
20 mm
Touching
225 mm
Vertical
perforated
trays
1.00
0.88
0.82
0.78
0.73
0.72
1.00
0.88
0.81
0.76
0.71
0.70
I'b =
31
Spaced
Ib
I
= b
k1k2 k tot
(note 3)
225 mm
D
Dee
1.00
0.91
0.89
0.88
0.87
1.00
0.91
0.88
0.87
0.85
1.00
0.87
0.82
0.80
0.79
0.78
1.00
0,86
0.80
0.78
0.76
0.73
1.00
0.85
0.79
0.76
0.73
0.70
1.00
1.00
1.00
1.00
1.00
1.00
0.99
0.98
0.97
0.96
1.00
0.98
0.97
0.96
0.93
Touching
20 mm
Ladder
supports,
cleats, etc.
32
33
Spaced
(note 2)
34
DDee
20 mm
NOTE 2 Values are given for vertical spacings between trays of 300 mm and at least 20 mm between trays and wall.
For closer spacing the factors should be reduced.
NOTE 3 Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. For closer
spacing the factors should be reduced.
36
1SDC010005F0201
NOTE 1 Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in
more than one layer touching each other. Values for such installations may be significantly lower and must be
determined by an appropriate method.
37
2 Protection of feeders
2 Protection of feeders
Conductor
Insulation
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
38
Loaded
conductors
A2
A1
Cu
Al
XLPE
EPR
PVC
19
26
35
45
61
81
106
131
158
200
241
278
318
362
424
486
17
23
31
40
54
73
95
117
141
179
216
249
285
324
380
435
Cu
XLPE
EPR
3
14.5 13.5
19.5 18
26
24
34
31
46
42
61
56
80
73
99
89
119 108
151 136
182 164
210 188
240 216
273 245
321 286
367 328
PVC
20
27
35
48
64
84
103
125
158
191
220
253
288
338
387
19
25
32
44
58
76
94
113
142
171
197
226
256
300
344
14.5 14
20 18.5
26
24
36
32
48
43
63
57
77
70
93
84
118 107
142 129
164 149
189 170
215 194
252 227
289 261
XLPE
EPR
PVC
3
Cu
Al
XLPE
EPR
2
B2
B1
13
18.5 16.5 14 13.0
25
22 18.5 17.5 19.5
33
30
25
23
26
42
38
32
29
33
57
51
43
39
45
76
68
57
52
60
99
89
75
68
78
121 109 92
83
96
145 130 110 99 115
183 164 139 125 145
220 197 167 150 175
253 227 192 172 201
290 259 219 196 230
329 295 248 223 262
386 346 291 261 307
442 396 334 298 352
PVC
3
18
24
31
41
55
71
87
104
131
157
180
206
233
273
313
Al
XLPE
EPR
3
14.5 13.5
20 17.5
25
23
33
31
44
41
58
53
71
65
86
78
108 98
130 118
150 135
172 155
195 176
229 207
263 237
23
31
42
54
75
100
133
164
198
253
306
354
20
28
37
48
66
88
117
144
175
222
269
312
Cu
XLPE
EPR
PVC
3
17.5 15.5
24
21
32
28
41
36
57
50
76
68
101 89
125 110
151 134
192 171
232 207
269 239
25
33
43
59
79
105
130
157
200
242
281
22
29
38
52
71
93
116
140
179
217
251
18.5 16.5
25 22.0
32
28
44
39
60
53
79
70
97
86
118 104
150 133
181 161
210 186
2
22
30
40
51
69
91
119
146
175
221
265
305
XLPE
EPR
PVC
3
19.5 16.5
26
23
35
30
44
38
60
52
80
69
105 90
128 111
154 133
194 168
233 201
268 232
Cu
Al
XLPE
EPR
PVC
PVC
15
20
27
34
46
62
80
99
118
149
179
206
23
31
40
54
72
94
115
138
175
210
242
21
28
35
48
64
84
103
124
156
188
216
Al
XLPE
EPR
3
17.5 15.5
24
21
30 27.0
41
36
54
48
71
62
86
77
104 92
131 116
157 139
181 160
PVC
24
33
45
58
80
107
138
171
209
269
328
382
441
506
599
693
22
30
40
52
71
96
119
147
179
229
278
322
371
424
500
576
XLPE/EPR
3
19.5 17.5
27
24
36
32
46
41
63
57
85
76
112 96
138 119
168 144
213 184
258 223
299 259
344 299
392 341
461 403
530 464
PVC
26
35
45
62
84
101
126
154
198
241
280
324
371
439
508
24
32
41
57
76
90
112
136
174
211
245
283
323
382
440
21
28
36
49
66
83
103
125
160
195
226
261
298
352
406
18.5
25
25.0
32
44
59
73
90
110
140
170
197
227
259
305
351
39
1SDC010006F0201
Installation
method
2 Protection of feeders
2 Protection of feeders
or
or
De
De
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
40
Loaded
conductors
Cu
XLPE
EPR PVC
2
26
36
49
63
86
115
149
185
225
289
352
410
473
542
641
741
22
30
40
51
70
94
119
148
180
232
282
328
379
434
514
593
Al
Cu
XLPE
XLPE
EPR PVC EPR PVC
3
28
38
49
67
91
108
135
164
211
257
300
346
397
470
543
23
31
39
54
73
89
111
135
173
210
244
282
322
380
439
23
32
42
54
75
100
127
158
192
246
298
346
399
456
538
621
18.5
2
34
43
60
80
101
126
153
196
238
276
319
364
430
497
Al
Cu
Al
XLPE
XLPE
XLPE
EPR PVC EPR PVC EPR PVC
2
24
32
42
58
77
97
120
146
187
227
263
304
347
409
471
19.5
26
33
46
61
78
96
117
150
183
212
245
280
330
381
Cu
XLPE
EPR PVC
Al
XLPE
EPR PVC
3
Cu
Al
XLPE
EPR
XLPE
EPR
C
PVC
PVC
3H
3V
3H
3V
3H
3V
3H
3V
182
226
275
353
430
500
577
661
781
902
1085
1253
1454
161
201
246
318
389
454
527
605
719
833
1008
1169
1362
146
181
219
281
341
396
456
521
615
709
852
982
1138
130
162
197
254
311
362
419
480
569
659
795
920
1070
138
172
210
271
332
387
448
515
611
708
856
991
1154
122
153
188
244
300
351
408
470
561
652
792
921
1077
112
139
169
217
265
308
356
407
482
557
671
775
900
99
124
152
196
241
282
327
376
447
519
629
730
852
161
200
242
310
377
437
504
575
679
783
940
1083
1254
131
162
196
251
304
352
406
463
546
629
754
868
1005
121
150
184
237
289
337
389
447
530
613
740
856
996
98
122
149
192
235
273
316
363
430
497
600
694
808
13
169
207
268
328
383
444
510
607
703
823
946
1088
110
137
167
216
264
308
356
409
485
561
656
749
855
103
129
159
206
253
296
343
395
471
547
663
770
899
845
105
128
166
203
237
274
315
375
434
526
610
711
141
176
216
279
342
400
464
533
634
736
868
998
1151
114
143
174
225
275
321
372
427
507
587
689
789
905
107
135
165
215
264
308
358
413
492
571
694
806
942
87
109
133
173
212
247
287
330
392
455
552
640
746
1SDC010100F0201
Insulation
Al
XLPE
EPR
PVC
Cu
XLPE
EPR PVC
41
2 Protection of feeders
2 Protection of feeders
E or F
Metallic sheath temperature 105 C
Bare cable not
exposed to touch
PVC covered or
bare exposed to touch
70 C
PVC covered or
bare exposed to touch
PVC covered or
bare exposed to touch
or
Loaded
conductors
or
or
or
or
or
De
De
De
500 V
750 V
Note 1
Note 2
Note 3
Note 4
42
De
S[mm2]
1.5
23
19
21
28
24
27
25
21
23
31
26
29
26
29
2.5
31
26
29
38
33
36
33
28
31
41
35
39
34
39
33.0
33
43
37.0
37
49
40
35
38
51
44
47
44
37
41
54
46
51
45
51
56
64
1.5
25
21
23
31
26
30
26
22
26
33
28
32
28
32
35
40
2.5
34
28
31
42
35
41
36
30
34
45
38
43
37
43
47
54
45
37
41
55
47
53
47
40
45
60
50
56
49
56
61
70
57
48
52
70
59
67
60
51
57
76
64
71
62
71
78
89
10
77
65
70
96
81
91
82
69
77
104
87
96
84
95
105
120
16
102
86
92
127
107
119
109
92
102
137
115
127
110
125
137
157
25
133
112
120
166
140
154
142
120
132
179
150
164
142
162
178
204
35
163
137
147
203
171
187
174
147
161
220
184
200
173
197
216
248
50
202
169
181
251
212
230
215
182
198
272
228
247
213
242
266
304
70
247
207
221
307
260
280
264
223
241
333
279
300
259
294
323
370
95
296
249
264
369
312
334
317
267
289
400
335
359
309
351
385
441
120
340
286
303
424
359
383
364
308
331
460
385
411
353
402
441
505
150
388
327
346
485
410
435
416
352
377
526
441
469
400
454
498
565
185
240
440
514
371
434
392
457
550
643
465
544
492
572
472
552
399
466
426
496
596
697
500
584
530
617
446
497
507
565
557
624
629
704
1SDC010007F0201
Installation
method
For single-core cables the sheaths of the cables of the circuit are connected together at both ends.
For bare cables exposed to touch, values should be multiplied by 0.9.
De is the external diameter of the cable.
For metallic sheath temperature 105 C no correction for grouping need to be applied.
43
2 Protection of feeders
2 Protection of feeders
Correction factor k2
The cable current carrying capacity is influenced by the presence of other cables
installed nearby. The heat dissipation of a single cable is different from that of
the same cable installed next to the other ones.
The correction factor k2 is obtained by the formula:
I z = I 0 k1k 2k 3 = I 0 k tot
k2 = k 2' . k 2''
where:
I0 is the current carrying capacity of the single conductor for installation in the
ground at 20C reference temperature;
k1 is the correction factor if the temperature of the ground is other than 20C;
k2 is the correction factor for adjacent cables;
k3 is the correction factor if the soil thermal resistivity is different from the
reference value, 2.5 Km/W.
Tables 11, 12, and 13 show the factor k2 values for single-core and multi-core
cables that are laid directly in the ground or which are installed in buried ducts,
according to their distance from other cables or the distance between the ducts.
Table 11: Reduction factors for cables laid directly in the ground
Correction factor k1
The current carrying capacity of buried cables refers to a ground temperature
of 20 C. If the ground temperature is different, use the correction factor k1
shown in Table 10 according to the insulation material.
44
Nil (cables
touching)
0.75
0.65
0.60
0.55
0.50
One cable
diameter
0.80
0.70
0.60
0.55
0.55
0.125 m
0.85
0.75
0.70
0.65
0.60
0.25 m
0.90
0.80
0.75
0.70
0.70
0.5 m
0.90
0.85
0.80
0.80
0.80
Multi-core cables
Insulation
PVC
1.10
1.05
0.95
0.89
0.84
0.77
0.71
0.63
0.55
0.45
Single-core cables
NOTE The given values apply to an installation depth of 0.7 m and a soil thermal resistivity of 2.5 Km/W.
45
2 Protection of feeders
2 Protection of feeders
Table 12: Reduction factors for multi-core cables laid in single way
ducts in the ground
Number
of circuits
2
3
4
5
6
0.5 m
0.95
0.90
0.85
0.85
0.80
0.25 m
0.90
0.85
0.80
0.80
0.80
1.0 m
0.95
0.95
0.90
0.90
0.90
k 2'' =
1
n
Multi-core cables
where:
n is the number of circuits in the duct.
Correction factor k3
NOTE The given values apply to an installation depth of 0.7 m and a soil thermal resistivity of 2.5 Km/W.
Soil thermal resistivity influences the heat dissipation of the cable. Soil with low
thermal resistivity facilitates heat dissipation, whereas soil with high thermal
resistivity limits heat dissipation. IEC 60364-5-52 states as reference value for
the soil thermal resistivity 2.5 Km/W.
Table 14: Correction factors for soil thermal resistivities other than
2.5 Km/W
Table 13: Reduction factors for single-core cables laid in single way
ducts in the ground
Number of single-core
circuits of
two or three cables
2
3
4
5
6
1
1.18
1.5
1.1
2
1.05
2.5
1
3
0.96
0.5 m
0.90
0.85
0.80
0.80
0.80
0.25 m
0.90
0.80
0.75
0.70
0.70
1.0 m
0.95
0.90
0.90
0.90
0.90
Single-core cables
NOTE The given values apply to an installation depth of 0.7 m and a soil thermal resistivity of 2.5 Km/W.
46
47
2 Protection of feeders
2 Protection of feeders
To summarize:
START
2. use Table 11, Table 12, Table 13 or the formula for groups of non-similar
cables to determine the correction factor k2 according to the distance
between cables or ducts;
yes
D method?
Ground temperature
<>
20 C?
no
Ib
I
Ib =
= b
k1k2 k 3 k tot
'
yes
k 1 from table 4
k1 = 1
no
k1 = 1
yes
multi-core cable?
k2 = 1
similar
sections?
yes
k 2 from table 7
yes
no
multi-core cable?
single layer?
XLPE
EPR
Insulation
k 2 from table 6
XLPE
EPR
PVC
no
k 2 ' from table 13
1
n
more than one
cable per conduit?
yes
no
Al
no
k 2 '' =
Cu
k 2 from table 5
yes
similar
sections?
no
k 2 '' =
1
n
yes
k 2 ''=1
PVC
k 2 '' from table 6
S[mm ]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
48
Loaded
conductors
26
34
44
56
73
95
121
146
173
213
252
287
324
363
419
474
22
29
37
46
61
79
101
122
144
178
211
240
271
304
351
396
22
29
38
47
63
81
104
125
148
183
216
246
278
312
361
408
18
24
31
39
52
67
86
103
122
151
179
203
230
258
297
336
26
34
42
56
73
93
112
132
163
193
220
249
279
322
364
22
29
36
47
61
78
94
112
138
164
186
210
236
272
308
22
29
36
48
62
80
96
113
140
166
189
213
240
277
313
18.5
24
30
40
52
66
80
94
117
138
157
178
200
230
260
k tot =k 1 *k 2
I' b =I b /k tot
k tot =k 1 *k 2 *k 3
k 2 =k 2 '*k 2 ''
Thermal resistivity
<> 2.5 Km/W?
yes
k 3 from table 14
no
k3 = 1
1SDC010008F0201
1SDC010009F0201
for cables?
yes
no
Conductor
yes
no
I z = I 0 k 1k 2 k 3
Installation
method
k 1 from table 10
no
5. from Table 15, determine the cross section of the cable with I0 Ib, according
to the method of installation, the insulation and conductive material and the
number of live conductors;
yes
S [mm2 ]
I z = I 0 *k tot
END
49
2 Protection of feeders
2 Protection of feeders
1SDC010007F0001
50
Reduction factor
Size selection is
based on phase
current
0 15
15 33
0.86
Current to take in
account for the
cable selection
Ib
Size selection is
based on neutral
current
Current to take in
account for the
cable selection
Ib
Ib
k tot
Ib
k tot . 0.86
I 'b =
I 'b =
33 45
0.86
> 45
IN =
I'b =
IN
0.86
I 'b = I N
Ib
.3 . k
III
k tot
51
2 Protection of feeders
2 Protection of feeders
Procedure:
In Table 3, it is possible to find the reference number of the installation and the
method of installation to be used for the calculations. In this example, the
reference number is 31, which corresponds to method E (multi-core cable on
tray).
Type of installation
insulation material:
PVC
type of cable:
multi-core
installation:
load current:
100 A
k 1 = 0.87
Correction factor for adjacent cables k2
Installation conditions:
ambient temperature:
For the multi-core cables grouped on the perforated tray see Table 5.
As a first step, the number of circuits or multi-core cables present shall be
determined; given that:
40 C
k 2 = 0.54
I 'b =
a
b
52
From Table 8, for a multi-core copper cable with PVC insulation, method of
installation E, with three loaded conductors, a cross section with current carrying
capacity of I0 Ib = 212.85 A, is obtained. A 95 mm2 cross section cable can
carry, under Standard reference conditions, 238 A.
The current carrying capacity, according to the actual conditions of installation,
is Iz = 238 . 0.87. 0.54 = 111.81 A
1SDC010008F0001
Ib
100
=
= 212.85A
k1k2 0.87. 0.54
53
2 Protection of feeders
2 Protection of feeders
Example of dimensioning a cable in a balanced threephase circuit with a significant third-harmonic content
If no harmonics are present, from Table 8, for a multi-core copper cable with
PVC insulation, method of installation E, with three loaded conductors, a cross
section with current carrying capacity of I0 Ib = 115 A, is obtained. A 35 mm2
cross section cable can carry, under Standard reference conditions, 126 A.
The current carrying capacity, according to the actual conditions of installation,
is still 126 A, since the value of factors k1 and k2 is 1.
PVC
type of cable:
multi-core
installation:
load current:
115 A
30 C
Installation conditions:
ambient temperature:
no adjacent circuits.
Ib
115
=
= 133.7 A
k1 . k 2 . 0.86 0.86
From Table 8, a 50 mm2 cable with carrying capacity of 153 A shall be selected.
If the third harmonic content is 40 %, Table 16 shows that the cable shall be
dimensioned according to the current of the neutral conductor and a reduction
factor of 0.86 must be applied.
The current in the neutral conductor is:
Procedure:
Type of installation
On Table 3, it is possible to find the reference number of the installation and the
method of installation to be used for the calculations. In this example, the
reference number is 31, which corresponds to method E (multi-core cable on
tray).
IN =
Ib . .
3 k III = 115. 3 . 0.4 = 138 A
ktot
I 'b =
k1 = 1
From Table 8, a 70 mm2 cable with 196 A current carrying capacity shall be
selected.
If the third harmonic content is 60 %, Table 16 shows that the cable shall be
dimensioned according to the current of the neutral conductor, but a reduction
factor of 1 must be applied.
The current in the neutral conductor is:
k2 = 1
After k1 and k2 have been determined, Ib is calculated by:
I 'b =
138
IN
=
= 160.5 A
0.86 0.86
Ib
= 115 A
k1k 2
IN =
Ib . .
3 kIII = 115. 3 . 0.6 = 207A
ktot
From Table 8, a 95 mm2 cable with current carrying capacity of 238 A must be
selected.
54
55
2 Protection of feeders
2 Protection of feeders
56
= 1 - cos 2 .
Normally, the percentage value in relation to the rated value Ur is calculated by:
u% =
U
100
Ur
(2)
Resistance and reactance values per unit of length are set out on the following
table by cross-sectional area and cable formation, for 50 Hz; in case of 60 Hz,
the reactance value shall be multiplied by 1.2.
57
S
[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
2 Protection of feeders
2 Protection of feeders
The following tables show the Ux [V/(A.km)] values by cross section and
formation of the cable according to the most common cos values.
single-core cable
r[/km]
x[/km]
@ 80 [C]
14.8
0.168
8.91
0.156
5.57
0.143
3.71
0.135
2.24
0.119
1.41
0.112
0.889
0.106
0.641
0.101
0.473
0.101
0.328
0.0965
0.236
0.0975
0.188
0.0939
0.153
0.0928
0.123
0.0908
0.0943
0.0902
0.0761
0.0895
two-core/three-core cable
r[/km]
x[/km]
@ 80 [C]
15.1
0.118
9.08
0.109
5.68
0.101
3.78
0.0955
2.27
0.0861
1.43
0.0817
0.907
0.0813
0.654
0.0783
0.483
0.0779
0.334
0.0751
0.241
0.0762
0.191
0.074
0.157
0.0745
0.125
0.0742
0.0966
0.0752
0.078
0.075
58
single-core cable
r[/km]
x[/km]
@ 80 [C]
24.384
0.168
14.680
0.156
9.177
0.143
6.112
0.135
3.691
0.119
2.323
0.112
1.465
0.106
1.056
0.101
0.779
0.101
0.540
0.0965
0.389
0.0975
0,310
0.0939
0.252
0.0928
0.203
0.0908
0.155
0.0902
0.125
0.0895
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
two-core/three-core cable
r[/km]
x[/km]
@ 80 [C]
24.878
0.118
14.960
0.109
9.358
0.101
6.228
0.0955
3.740
0.0861
2.356
0.0817
1.494
0.0813
1.077
0.0783
0.796
0.0779
0.550
0.0751
0.397
0.0762
0.315
0.074
0.259
0.0745
0.206
0.0742
0.159
0.0752
0.129
0.075
cos = 1
single-core cable
single-phase
three-phase
29.60
25.63
17.82
15.43
11.14
9.65
7.42
6.43
4.48
3.88
2.82
2.44
1.78
1.54
1.28
1.11
0.95
0.82
0.66
0.57
0.47
0.41
0.38
0.33
0.31
0.27
0.25
0.21
0.19
0.16
0.15
0.13
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
cos = 0.9
single-core cable
single-phase
three-phase
26.79
23.20
16.17
14.01
10.15
8.79
6.80
5.89
4.14
3.58
2.64
2.28
1.69
1.47
1.24
1.08
0.94
0.81
0.67
0.58
0.51
0.44
0.42
0.36
0.36
0.31
0.30
0.26
0.25
0.22
0.22
0.19
59
2 Protection of feeders
2 Protection of feeders
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
cos = 0.85
single-core cable
single-phase
three-phase
25.34
21.94
15.31
13.26
9.62
8.33
6.45
5.59
3.93
3.41
2.51
2.18
1.62
1.41
1.20
1.04
0.91
0.79
0.66
0.57
0.50
0.44
0.42
0.36
0.36
0.31
0.30
0.26
0.26
0.22
0.22
0.19
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
60
cos = 0.8
single-core cable
single-phase
three-phase
23.88
20.68
14.44
12.51
9.08
7.87
6.10
5.28
3.73
3.23
2.39
2.07
1.55
1.34
1.15
0.99
0.88
0.76
0.64
0.55
0.49
0.43
0.41
0.36
0.36
0.31
0.31
0.26
0.26
0.22
0.23
0.20
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
cos = 0.75
single-core cable
single-phase
three-phase
22.42
19.42
13.57
11.75
8.54
7.40
5.74
4.97
3.52
3.05
2.26
1.96
1.47
1.28
1.10
0.95
0.84
0.73
0.62
0.54
0.48
0.42
0.41
0.35
0.35
0.31
0.30
0.26
0.26
0.23
0.23
0.20
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
cos = 1
single-core cable
single-phase
three-phase
48.77
42.23
29.36
25.43
18.35
15.89
12.22
10.59
7.38
6.39
4.65
4.02
2.93
2.54
2.11
1.83
1.56
1.35
1.08
0.94
0.78
0.67
0.62
0.54
0.50
0.44
0.41
0.35
0.31
0.27
0.25
0.22
61
2 Protection of feeders
2 Protection of feeders
Table 11: Specific voltage drop at cos = 0.8 for aluminium cables
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
cos = 0.9
single-core cable
single-phase
three-phase
44.04
38.14
26.56
23.00
16.64
14.41
11.12
9.63
6.75
5.84
4.28
3.71
2.73
2.36
1.99
1.72
1.49
1.29
1.06
0.92
0.78
0.68
0.64
0.55
0.53
0.46
0.44
0.38
0.36
0.31
0.30
0.26
Table 10: Specific voltage drop at cos = 0.85 for aluminium cables
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
62
cos = 0.85
single-core cable
single-phase
three-phase
41.63
36.05
25.12
21.75
15.75
13.64
10.53
9.12
6.40
5.54
4.07
3.52
2.60
2.25
1.90
1.65
1.43
1.24
1.02
0.88
0.76
0.66
0.63
0.54
0.53
0.46
0.44
0.38
0.36
0.31
0.31
0.27
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
Table 12: Specific voltage drop at cos = 0.75 for aluminium cables
cos = 0.8
single-core cable
single-phase
three-phase
39.22
33.96
23.67
20.50
14.85
12.86
9.94
8.61
6.05
5.24
3.85
3.34
2.47
2.14
1.81
1.57
1.37
1.18
0.98
0.85
0.74
0.64
0.61
0.53
0.51
0.45
0.43
0.38
0.36
0.31
0.31
0.27
S[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
cos = 0.75
single-core cable
single-phase
three-phase
36.80
31.87
22.23
19.25
13.95
12.08
9.35
8.09
5.69
4.93
3.63
3.15
2.34
2.02
1.72
1.49
1.30
1.13
0.94
0.81
0.71
0.62
0.59
0.51
0.50
0.43
0.42
0.37
0.35
0.31
0.31
0.27
63
2 Protection of feeders
2 Protection of feeders
Example 1
u% =
U .
2.03 .
100 =
100 = 0.51%
400
Ur
Ib =
Example 2
To calculate a voltage drop on a three-phase cable with the following
specifications:
rated voltage: 690 V;
cable length: 50 m;
cable formation: multi-core copper cable, 2x(3x10) mm2;
load current Ib: 50 A;
power factor cos: 0.85.
From Table 5, for a multi-core 10 mm2 cable it is possible to read that Ux
voltage drop corresponds to 3.42 V/(Akm). By multiplying this value by the
length in km and by the current in A, and by dividing it by the number of cables
in parallel, it results:
L
0.05
U = U x . I b . = 3.42. 50 .
= 4.28 V
2
2
64
u% =
U .
28.2 .
100 =
100 = 7.05%
400
Ur
u% =
Pu
35000
=
= 56 A
.
.
3 U r cos
3 . 400. 0.9
U .
4.28 .
100 =
100 = 0.62%
690
Ur
U x max =
u% .U r
2% . 400
=
= 1.02 V/(A . km)
100 . I b . L 100 . 56 . 0.14
65
2 Protection of feeders
2 Protection of feeders
Pj =
3. r . I b2 . L
[W]
1000
Pj =
I b In I z
(1)
I2 1.45 . Iz
(2)
Where:
Ib is the current for which the circuit is dimensioned;
Iz is the continuous current carrying capacity of the cable;
In is the rated current of the protective device; for adjustable protective releases,
the rated current In is the set current;
I2 is the current ensuring effective operation in the conventional time of the
protective device.
2 . r . I b2 . L
[W]
1000
Ib
where:
Ib is the load current [A];
r is the phase resistance per unit of length of the cable at 80 C [/km] (see
Table 1);
L is the cable length [m].
Iz
In
1.45Iz
1SDC010009F0001
I2
66
Cu
14.8
8.91
5.57
3.71
2.24
1.41
0.889
0.641
0.473
0.328
0.236
0.188
0.153
0.123
0.0943
0.0761
AI
24.384
14.680
9.177
6.112
3.691
2.323
1.465
1.056
0.779
0.540
0.389
0.310
0.252
0.203
0.155
0.125
Two-core/three-core cable
Cu
15.1
9.08
5.68
3.78
2.27
1.43
0.907
0.654
0.483
0.334
0.241
0.191
0.157
0.125
0.0966
0.078
AI
24.878
14.960
9.358
6.228
3.740
2.356
1.494
1.077
0.796
0.550
0.397
0.315
0.259
0.206
0.159
0.129
67
2 Protection of feeders
2 Protection of feeders
Example 2
Load specifications
Ib In 0.9 .Iz
In
1SDC010010F0001
Ib
Cable specifications
Iz = 171 A
Protective device specifications
T2N160 PR221DS-LS In160; set current I1 = 0.88 x In = 140.8 A
Ib
0.9 Iz
In
1SDC010011F0001
Example 3
Load specifications
Pr = 100 kW; cos = 0.9; Ur = 400 V ; three-phase load so Ib = 160 A
Cable specifications
Iz = 190 A
Examples
Load specifications
Example 1
Example 4
Load specifications
Pr = 70 kW; Ur = 400 V; cos = 0.9; three-phase load so Ib = 112 A
Cable specifications
Iz = 134 A
Cable specifications
Protective device specifications
Iz = 134 A
68
69
2 Protection of feeders
2 Protection of feeders
Table 2 shows the maximum withstood energy for cables according to the
cross section, the conductor material and the type of insulation, which are
calculated by using the parameters of Table 1.
where
I2t is the specific let-through energy of the protective device which can be
read on the curves supplied by the manufacturer (see Electrical installation
handbook, Vol. 1, Chapter 3.4 Specific let-through energy curves) or from a
direct calculation in the case of devices that are not limiting and delaying;
S is the cable cross section [mm2]; in the case of conductors in parallel it is
the cross section of the single conductor;
k is a factor that depends on the cable insulating and conducting material.
The values of the most common installations are shown in Table 1; for a more
detailed calculation, see Annex D.
1.5
Cu
115
2.9810
-2
8.2710
-2
2.1210
-1
4.7610
-1
Al
76
1.3010
-2
3.6110
-2
9.2410
-2
2.0810
-1
Cu
143
4.6010
-2
1.2810
-1
3.2710
-1
7.3610
-1
Al
94
1.9910
-2
5.5210
-2
1.4110
-1
3.1810
-1
1.2410
-1
3.1810
-1
7.1610
-1
5.4110
-2
1.3810
-1
3.1110
-1
Cable
PVC
EPR/XLPE
Rubber
2.5
Cu
141
4.4710
-2
Al
93
1.9510
-2
50
115
3.3110
10
16
25
35
1.32
3.39
8.27
1.6210
1.48
3.61
7.08
5.23
1.2810
2.26
5.52
5.7810
-1
2.04
8.8410
-1
1.99
8.6510
-1
5.09
1.2410
2.21
5.41
2.5110
1.0810
2.4410
1.0610
PVC
EPR/XLPE
G2
PVC
>300 mm2
EPR
XLPE
Rubber
60 C
Initial temperature C
70
70
90
Final temperature C
160
140
115
Aluminium
tin-soldered joints
in copper conductors
Mineral
PVC
Bare
60
70
105
250
200
160
250
103
143
141
115
135/115 a
76
68
94
93
115
Material of conductor:
Copper
120
1.1910
150
1.9010
185
2.9810
240
4.5310
300
7.6210
1.1910
Al
76
1.4410
2.8310
5.2110
8.3210
1.3010
1.9810
3.3310
5.2010
Cu
143
5.1110
1.0010
1.8510
2.9410
4.6010
7.0010
1.1810
1.8410
Al
94
2.2110
4.3310
7.9710
1.2710
1.9910
3.0210
5.0910
7.9510
9.7410
1.7910
2.8610
4.4710
6.8010
1.1510
1.7910
4.2410
7.8110
1.2510
1.9510
2.9610
4.9810
7.7810
Cu
141
4.9710
Al
93
2.1610
70
6.4810
1SDC010010F0201
95
The formula (1) must be verified along the whole length of the cable. Due to the
shape of the specific let-through energy curve of a circuit breaker, it is generally
sufficient to verify formula (1) only for the maximum and minimum short-circuit
current that may affect the cable. The maximum value is normally the value of
the three-phase short-circuit current at the beginning of the line, while the
minimum value is the value of the phase to neutral short-circuit current (phase
to phase if the neutral conductor is not distributed) or phase to earth at the end
of the cable.
Conductor insulation
PVC
300 mm2
Cu
70
71
1SDC010002F0901
Cable
2 Protection of feeders
2 Protection of feeders
[(KA)2s] 102
10
Ikmin =
Ikmin =
sec
par
L
1.5 . . (1 + m) .
S
(2.1)
(2.2)
where:
10-1
1SDC010011F0001
10-2
10-3
10-1
10
[KA]
120
0.9
150
0.85
180
0.80
240
0.75
300
0.72
number of parallel
conductors
kpar*
2
2
3
2.7
4
3
5
3.2
m is the ratio between the resistances of the neutral conductor and the phase
conductor (if they are made of the same material m is the ratio between the
cross section of the phase conductor and the cross section of the neutral
conductor).
After calculating the minimum short-circuit current, verify that
72
73
2 Protection of feeders
Example
2 Protection of feeders
Table 3: Maximum protected length
Ur = 400 V
Ik = 30 kA
Choice of CB1
CB1
System data:
Rated voltage 400 V
Ik = 30 kA
T1N160 In160
Cable data:
Insulated copper conductor in PVC
Length = 150 m
S = 50 mm2
Iz = 134 A
PVC Cu
L = 150 m
Iz = 134.0 A
L
Protection against short-circuit at the beginning of the conductor
T1N160 In160 (breaking capacity 36 kA@400 V)
I2t (@30 kA) = 7.5 10-1 (kA)2s (for the curves of specific let-through energy, see
Volume 1, Chapter 3.4)
k2S2 = 1152 502 = 3.31.101 (kA)2s
The cable is therefore protected against short-circuit at the beginning of the
conductor.
Protection against short-circuit at end of the conductor
The minimum short-circuit current at end of the conductor (ksec=1 and kpar=1) is:
Ikmin =
The magnetic threshold of the circuit breaker T1N160 In160 is set at 1600 A. If
tolerance is 20%, the circuit breaker shall definitely trip if the values exceed
1920 A; the cable is therefore fully protected against short-circuit.
1SDC010011F0201
section [mm2]
I3[A]
1.5
2.5
20
370
617
30
246
412
40
185
309
50
148
247
60
123
206
70
105
176
80
92
154
90
82
137
100
74
123
120
61
102
140
52
88
150
49
82
160
46
77
180
41
68
200
37
61
220
33
56
250
29
49
280
26
44
300
24
41
320
23
38
350
21
35
380
19
32
400
18
30
420
17
29
450
16
27
480
15
25
500
14
24
520
14
23
550
13
22
580
12
21
600
12
20
620
11
19
650
11
19
680
10
18
700
10
17
750
16
800
15
850
14
900
13
950
13
1000
12
1250
1500
1600
2000
2500
3000
3200
4000
5000
6300
8000
9600
10000
12000
15000
20000
24000
30000
4
658
494
395
329
282
246
219
197
164
141
131
123
109
98
89
79
70
65
61
56
52
49
47
43
41
39
38
35
34
32
31
30
29
28
26
24
23
21
20
19
15
13
12
741
593
494
423
370
329
296
246
211
197
185
164
148
134
118
105
98
92
84
78
74
70
65
61
59
57
53.
51
49
47
45
43
42
39
37
34
32
31
29
23
19
18
14
11
10
705
617
549
494
412
353
329
309
274
247
224
198
176
165
154
141
130
123
118
110
103
99
95
90
85
82
80
76
73
71
66
62
58
55
52
49
40
33
31
25
20
16
15
12
10
16
790
658
564
527
494
439
395
359
316
282
263
247
226
208
198
188
176
165
158
152
144
136
132
127
122
116
113
105
99
93
88
83
79
63
53
49
40
32
26
25
20
16
13
10
25
772
686
617
561
494
441
412
386
353
325
309
294
274
257
247
237
224
213
206
199
190
182
176
165
154
145
137
130
123
99
82
77
62
49
41
39
31
25
20
15
13
12
10
35
786
691
617
576
540
494
455
432
412
384
360
346
332
314
298
288
279
266
254
247
230
216
203
192
182
173
138
115
108
86
69
58
54
43
35
27
22
18
17
14
12
50
772
705
650
617
588
549
514
494
475
449
426
412
398
380
363
353
329
309
290
274
260
247
198
165
154
123
99
82
77
62
49
39
31
26
25
21
16
12
10
70
95
120
150
185
240
300
768
720
691
665
629
596
576
558
532
508
494
461
432
407
384
364
346
277
230
216
173
138
115
108
86
69
55
43
36
35
29
23
17
14
12
809
782
757
722
690
670
626
586
552
521
494
469
375
313
293
235
188
156
147
117
94
74
59
49
47
39
31
23
20
16
847
790
667
627
593
561
533
427
356
333
267
213
178
167
133
107
85
67
56
53
44
36
27
22
20
840
787
741
700
663
630
504
420
394
315
252
210
197
157
126
100
79
66
63
52
42
31
26
25
731
585
487
457
365
292
244
228
183
146
116
91
76
73
61
49
37
30
30
711
593
556
444
356
296
278
222
178
141
111
93
89
74
59
44
37
40
667
533
427
356
333
267
213
169
133
111
107
89
71
53
44
49
75
2 Protection of feeders
2 Protection of feeders
To summarize:
Multiply the length value obtained from the table by the correction factor kv:
On the table, for the cross section and magnetic trip threshold it is possible to
read a maximum protected value L0. This length shall then be multiplied, if
necessary, by the correction factors in order to obtain a value that is compatible
with the installation operating conditions:
Ur [V]
(three-phase value)
230(*)
400
440
500
690
kv
0.58
1
1.1
1.25
1.73
(*)
230 V single-phase is the equivalent of a three-phase 400 V system with distributed
neutral and with the cross section of the phase conductor the same as the cross section
area of the neutral conductor, so that kv is 0.58.
L = L 0 k v kd k r
Example 1
Neutral not distributed
Rated voltage = 400 V
Protective device: T2N160 TMD In100
Magnetic threshold: I3 = 1000 A
Phase cross section = Neutral cross section = 70 mm2
The table shows that at I3 = 1000 A, the 70 mm2 cable is protected up to 346 m.
Example 2
Neutral distributed
Rated voltage = 400 V
Protective device: T3S250 TMD In200
Magnetic threshold: I3 = 2000 A
Phase cross section = 300 mm2
Neutral cross section = 150 mm2
For I3 = 2000 A and S = 300 mm2, a protected length equivalent of L0= 533 m
is obtained.
2 . 1
kd =
3 1+ S
SN
where
S is the phase cross section [mm2];
SN is the neutral cross section [mm2].
In particular:
if S = SN
if S = 2.S N
kd is 0.58;
kd is 0.39.
kd =
76
2 . 1
2 . 1
=
= 0.39
3 1+ S
3 1+ 300
150
SN
77
2 Protection of feeders
2 Protection of feeders
TT or TN systems:
if the cross section of the neutral conductor is the same or larger than the
cross section of the phase conductor, there is neither the need to detect
overcurrents on the neutral conductor nor to use a breaking device (neutral
conductor is not protected or disconnected); this requirement applies only if
there are no harmonics that may, at any instant, cause r.m.s. current values
on the neutral conductor higher than the maximum current detected on the
phase conductors;
if the cross section of the neutral conductor is less than the cross section of
the phase conductor, overcurrents on the neutral conductor must be detected
so as to have the phase conductors, but not necessarily the neutral conductor,
disconnected (neutral conductor protected but not disconnected): in this case
the overcurrents on the neutral conductor do not need to be detected if the
following conditions are simultaneously fulfilled:
1.the neutral conductor is protected against short-circuit by
the protective device of the phase conductors;
2.the maximum current that can flow through the neutral
conductor during normal service is lower than the neutral
current carrying capacity.
In TN-S systems, the neutral need not be disconnected if the supply conditions
are such that the neutral conductor can be considered to be reliable at earth potential.
As already mentioned, in TN-C systems, the neutral conductor is also a
protective conductor and cannot therefore be disconnected. Furthermore, if
the neutral conductor is disconnected, the exposed conductive parts of the
single-phase equipment could take the system rated voltage to earth.
In certain specific cases, the neutral conductor has to be disconnected to
prevent currents circulating between parallel supply sources (see Figures 2 and 3).
Neutral conductor
The neutral conductor is a conductor that is connected to the system neutral
point (which generally but not necessarily coincides with the star centre of the
secondary windings of the transformer or the windings of the generator); it is
able to contribute to the transmission of electric power, thereby making available
a voltage that is different from the phase to phase voltage. In certain cases and
under specific conditions, the functions of neutral conductor and protective
conductor can be combined in a single conductor (PEN).
Protection and disconnection of the neutral conductor
U1 =
P
N
U1
R1
3 . U0 . R 1
R1+ R2
R2
Power supply 1
L1
L2
L3
PEN
PE
L1
L2
L3
Supplier
User
1SDC010012F0201
1SDC010013F0001
If fault conditions arise, a voltage to earth may occur on the neutral conductor.
This may be caused by a phase to neutral short-circuit and by the disconnection
of the neutral conductor due to accidental breaking or to tripping of single-pole
devices (fuses or single-pole circuit breakers).
If the neutral conductor only is disconnected in a four-conductor circuit, the
supply voltage to the single-phase loads may be altered so that they are supplied
by a voltage different from the U0 phase to neutral voltage (as shown in Fig. 1).
Therefore, all the necessary measures to prevent this type of fault shall be taken,
e.g. by not protecting the neutral conductor with single-pole devices.
78
79
2 Protection of feeders
2 Protection of feeders
L1
L2
L3
PEN
PE
START
L1
L2
L3
no
Upstream protection
for the neutral?
SN S?
TT/TN System?
no
yes
yes
no
yes
NOTE A three-phase
alternative power supply
with a non-suitable 3-pole
switch, due to
unintentional circular stray
currents generating
electromagnetic fields.
1SDC010014F0001
no
no
yes
yes
no
IT system:
The Standard advises against distributing the neutral conductor in IT systems.
If the neutral conductor is distributed, the overcurrents must be detected on
the neutral conductor of each circuit in order to disconnect all the live conductors
on the corresponding circuit, including the neutral one (neutral conductor
protected and disconnected).
Overcurrents do not need to be detected on the neutral conductor in any of the
following cases:
the neutral conductor is protected against short-circuit by a protective device
fitted upstream;
the circuit is protected by a residual current device with rated residual current
lower than 0.15 times the current carrying capacity of the corresponding neutral
conductor. This device must disconnect all the live conductors, the neutral
conductor included.
For all distribution systems, whenever necessary, connection and disconnection
of the neutral conductor, shall ensure that:
the neutral conductor is not disconnected before the phase conductor;
the neutral conductor is connected at the same moment or before the phase
conductor.
80
It is necessary to:
detect the neutral current
in order to open all the contacts
(phase and neutral).
It is necessary to:
- open all the contacts
(phase and neutral)
It is not necessary to:
-detect the neutral current.
It is necessary to:
-open the phase contacts
It is not necessary to:
-detect the neutral overcurrent;
-open the neutral contact.
It is necessary to:
-detect the neutral current;
-open the phase contacts;
It is not necessary to:
-open the neutral contact.
It is not necessary:
-the presence of a
breaking device
for the neutral.
81
1SDC010013F0201
yes
2 Protection of feeders
2 Protection of feeders
Protective conductor
The neutral conductor, if any, shall have the same cross section as the line
conductor:
in single-phase, two-wire circuits whatever the section;
in polyphase and single-phase three-wire circuits, when the size of the line
conductors is less than or equal to 16 mm2 in copper, or 25 mm 2 in
aluminium.1
The cross section of the neutral conductor can be less than the cross section
of the phase conductor when the cross section of the phase conductor is
greater than 16 mm2 with a copper cable, or 25 mm2 with an aluminium cable,
if both the following conditions are met:
the cross section of the neutral conductor is at least 16 mm2 for copper
conductors and 25 mm2 for aluminium conductors;
there is no high harmonic distortion of the load current. If there is high harmonic
distortion (the harmonic content is greater than 10%), as for example in
equipment with discharge lamps, the cross section of the neutral conductor
cannot be less than the cross section of the phase conductors.
S 16
k1 .
16*
S > 25
S*
2
k1 .
16
k
2
k1 . S
k2 2
Where
1
The cross section of phase conductors shall be dimensioned in compliance with the
instructions of the Chapter 2.2.1 Current carrying capacity and methods of installation
k1 is the value of k for the line conductor, selected from Table 1 Chapter 2.4 according to the materials of
the conductor and insulation;
k2 is the value of k for the protective conductor.
* For a PEN conductor, the reduction of the cross section is permitted only in accordance with the rules for sizing of the neutral conductor.
SPE =
I 2t
k
(1)
where:
SPE is the cross section of the protective conductor [mm2];
I is the r.m.s. current flowing through the protective conductor in the event of
a fault with low impedance [A];
t is the trip time of the protective device [s];
82
83
1SDC010014F0201
for TN-C systems, the Standards specify a minimum cross section of 10 mm2 for copper
and 16 mm2 for aluminium conductors
16 < S 25
2 Protection of feeders
2 Protection of feeders
Further values of k can be taken from the Tables in Annex D, which provides
the formula for accurate calculation of the value of k.
If Table 2 or formula (1) do not provide a standardized cross section, a larger
standardized cross section shall be chosen.
Regardless of whether Table 2 or formula (1) are used, the cross section of the
protective conductor, which is not part of the supply cable, shall be at least:
- 2.5 mm2 Cu/16 mm2 Al, if a mechanical protection is provided;
- 4 mm2 Cu/16 mm2 Al, if no mechanical protection is provided.
Initial
Copper
Aluminium
Final
Steel
Values for k
30
160/140 a
143/133 a
95/88 a
52/49 a
90 C PVC
30
52/49 a
90 C thermosetting
30
250
176
116
64
60 C rubber
30
200
159
105
58
85 C rubber
30
220
168
110
60
Silicon rubber
30
350
201
133
70 C PVC
143/133
143/133
95/88
73
2
The lower value applies to PVC insulated conductors of cross section greater than 300 mm .
b
Temperature limits for various types of insulation are given in IEC 60724.
1SDC010015F0201
Conductor insulation
For current using equipment intended for permanent connection and with a
protective conductor current exceeding 10 mA, reinforced protective conductors
shall be designed as follows:
either the protective conductor shall have a cross-sectional area of at least 10
mm2 Cu or 16 mm2 Al, through its total run;
or a second protective conductor of at least the same cross-sectional area as
required for protection against indirect contact shall be laid up to a point
where the protective conductor has a cross-sectional area not less than 10
mm2 Cu or 16 mm2 Al. This requires that the appliance has a separate terminal
for a second protective conductor.
Material of conductor
Temperature
C b
When overcurrent protective devices are used for protection against electric
shock, the protective conductor shall be incorporated in the same wiring system
as the live conductors or be located in their immediate proximity.
Initial
a
b
Material of conductor
Copper
Final
Aluminium
Steel
Values for k
70 C PVC
70
160/140 a
115/103 a
76/68 a
42/37 a
90 C PVC
90
160/140 a
100/86 a
66/57 a
36/31 a
90 C thermosetting
90
250
143
94
52
60 C rubber
60
200
141
93
51
85 C rubber
85
220
134
89
48
Silicon rubber
180
350
132
87
47
The lower value applies to PVC insulated conductors of cross section greater than 300 mm2.
Temperature limits for various types of insulation are given in IEC 60724.
84
1SDC010015F0201
Temperature
C b
Conductor insulation
85
2 Protection of feeders
2 Protection of feeders
BTS geometry
Type of installation:
- flat;
- edge-on;
- vertical.
Length.
NOTE: BTSs shall be placed at a distance from the walls and the ceilings in such a way as
to enable visual inspection of connections during assembly and to facilitate insertion of the
branch units.
If possible, it is preferable to install the BTS edge-on so as to improve mechanical resistance
and reduce any possible deposit of powder and polluting substances that might affect the
level of internal insulation.
Ib =
Pt . b
.
3 U . cos
r
[A]
(1)
where:
Pt is the sum of the active power of all the installed loads [W];
b is the supply factor, which is:
- 1 if the BTS is supplied from one side only;
- 1/2 if the BTS is supplied from the centre or from both ends
simultaneously;
Ur is the operating voltage [V];
cosm is the average power factor of the loads.
Dimensioning of a BTS
To dimension a BTS, the load current must be determined using the following
data:
Power supply
I b I Z 0 . kt = I Z
where:
IZ0 is the current that the BTS can carry for an indefinite time at the reference
temperature (40 C);
Ib is the load current;
kt is the correction factor for ambient temperature values other than the
reference ambient temperature shown on Table 1.
Table 1: Correction factor kt for ambient temperature other than 40 C
Loads
Number, distribution, power and cos and type of loads supplied by the same
BTS
86
(2)
Ambient
Temperature [C] 15
kt
1.2
20
1.17
25
1.12
30
1.08
35
1.05
40
1
45
0.95
50
0.85
87
2 Protection of feeders
2 Protection of feeders
Type
LB254 25A 4 cond. Cu
HL254 25A 4 cond. Cu
HL2544 25A 4+4 cond. Cu
LB404 40A 4 cond. Cu
HL404 40A 4 cond. Cu
HL4044 40A 4+4 cond. Cu
SL 40A 4 cond. Cu
SL 63A 4 cond. Cu
MS 100A 4 cond. Cu
MS 160A 4 cond. Cu
SB4 160A 4 cond. Cu
SB5 160A 5 cond. Cu
SB6 160A 5 cond. Cu
SB7 160A 4 cond. Cu
MR 250A 4 cond. Cu
MRf 250A 5 cond. Cu
SB4 250A 4 cond. Cu
SB5 250A 5 cond. Cu
SB6 250A 5 cond. Cu
SB7 250A 4 cond. Cu
MR 315A 4 cond. Cu
MRf 315A 5 cond. Cu
SB4 350A 4 cond. Cu
SB5 350A 5 cond. Cu
SB6 350A 5 cond. Cu
SB7 350A 4 cond. Cu
MR 400A 4 cond. Cu
MRf 400A 5 cond. Cu
SB4 500A 4 cond. Cu
SB5 500A 5 cond. Cu
SB6 500A 5 cond. Cu
SB7 500A 4 cond. Cu
MR 630A 4 cond. Cu
MRf 630A 5 cond. Cu
SB4 700A 4 cond. Cu
SB5 700A 5 cond. Cu
Number of
conductors
4
4
4+4
4
4
4+4
4
4
4
4
4
5
5
4
4
5
4
5
5
4
4
5
4
5
5
4
4
5
4
5
5
4
4
5
4
5
IZ0
[A]
25
25
25
40
40
40
40
63
100
160
160
160
160
160
250
250
250
250
250
250
315
315
350
350
350
350
400
400
500
500
500
500
630
630
700
700
rph*
[m/m]
6.964
6.876
6.876
3.556
3.516
3.516
2.173
1.648
0.790
0.574
0.335
0.335
0.335
0.335
0.285
0.285
0.194
0.194
0.194
0.194
0.216
0.216
0.142
0.142
0.142
0.142
0.115
0.115
0.092
0.092
0.092
0.092
0.073
0.073
0.077
0.077
xph
[m/m]
1.144
1.400
1.400
0.792
1.580
1.580
0.290
0.637
0.366
0.247
0.314
0.314
0.314
0.314
0.205
0.205
0.205
0.205
0.205
0.205
0.188
0.188
0.188
0.188
0.188
0.188
0.129
0.129
0.129
0.129
0.129
0.129
0.122
0.122
0.122
0.122
Ur
[V]
400
400
400
400
400
400
400
400
400
400
500
500
500
500
1000
1000
500
500
500
500
1000
1000
500
500
500
500
1000
1000
500
500
500
500
1000
1000
500
500
Size
700
700
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
1000
1200
1250
1250
1500
1600
1600
2000
2000
2400
2500
2500
3000
3000
3200
3200
4000
4000
5000
5000
Type
SB6 700A 5 cond. Cu
SB7 700A 4 cond. Cu
MR 800A 4 cond. Cu
MRf 800A 5 cond. Cu
SC 800A 4 cond. Cu
SB4 800A 4 cond. Cu
SB5 800A 5 cond. Cu
SB6 800A 5 cond. Cu
SB7 800A 4 cond. Cu
MR 1000A 4 cond. Cu
MRf 1000A 5 cond. Cu
SC 1000A 4 cond. Cu
HRC1 1000A 4 cond. Cu
SB4 1000A 4 cond. Cu
SB5 1000A 5 cond. Cu
SB6 1000A 5 cond. Cu
SB7 1000A 4 cond. Cu
SC 1200A 4 cond. Cu
SC 1250A 4 cond. Cu
HRC1 1250A 4 cond. Cu
SC 1500A 4 cond. Cu
SC 1600A 4 cond. Cu
HRC1 1600A 4 cond. Cu
SC 2000A 4 cond. Cu
HRC1 2000A 4 cond. Cu
SC 2400A 4 cond. Cu
SC 2500A 4 cond. Cu
HRC1 2500A 4 cond. Cu
SC 3000A 4 cond. Cu
HRC2 3000A 4 cond. Cu
SC 3200A 4 cond. Cu
HRC2 3200A 4 cond. Cu
SC 4000A 4 cond. Cu
HRC2 4000A 4 cond. Cu
SC 5000A 4 cond. Cu
HRC2 5000A 4 cond. Cu
Number of
conductors
5
4
4
5
4
4
5
5
4
4
5
4
4
4
5
5
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
IZ0
[A]
700
700
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
1000
1200
1250
1250
1500
1600
1600
2000
2000
2400
2500
2500
3000
3000
3200
3200
4000
4000
5000
5000
rph*
[m/m]
0.077
0.077
0.047
0.047
0.038
0.072
0.072
0.072
0.072
0.038
0.038
0.037
0.038
0.068
0.068
0.068
0.068
0.035
0.034
0.035
0.030
0.025
0.034
0.020
0.025
0.019
0.016
0.019
0.014
0.017
0.013
0.015
0.011
0.011
0.008
0.008
xph
[m/m]
0.122
0.122
0.122
0.122
0.027
0.122
0.122
0.122
0.122
0.120
0.120
0.026
0.097
0.120
0.120
0.120
0.120
0.021
0.023
0.076
0.022
0.018
0.074
0.015
0.074
0.012
0.011
0.040
0.011
0.031
0.009
0.031
0.007
0.026
0.005
0.023
Ur
[V]
500
500
1000
1000
1000
500
500
500
500
1000
1000
1000
1000
500
500
500
500
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
88
89
2 Protection of feeders
2 Protection of feeders
Type
Number of
conductors
IZ0
[A]
rph*
[m/m]
xph
[m/m]
Ur
[V]
160
160
160
160
160
160
250
250
250
250
250
250
315
315
315
315
315
315
400
400
400
400
400
400
500
500
500
500
630
630
630
MR 160A 4 cond. Al
MRf 160A 5 cond. Al
SB4 160A 4 cond. Al
SB5 160A 5 cond. Al
SB6 160A 5 cond. Al
SB7 160A 4 cond. Al
MR 250A 4 cond. Al
MRf 250A 5 cond. Al
SB4 250A 4 cond. Al
SB5 250A 5 cond. Al
SB6 250A 5 cond. Al
SB7 250A 4 cond. Al
MR 315A 4 cond. Al
MRf 315A 5 cond. Al
SB4 315A 4 cond. Al
SB5 315A 5 cond. Al
SB6 315A 5 cond. Al
SB7 315A 4 cond. Al
MR 400A 4 cond. Al
MRf 400A 5 cond. Al
SB4 400A 4 cond. Al
SB5 400A 5 cond. Al
SB6 400A 5 cond. Al
SB7 400A 4 cond. Al
SB4 500A 4 cond. Al
SB5 500A 5 cond. Al
SB6 500A 5 cond. Al
SB7 500A 4 cond. Al
MR 630A 4 cond. Al
MRf 630A 5 cond. Al
SC 630A 4 cond. Al
4
5
4
5
5
4
4
5
4
5
5
4
4
5
4
5
5
4
4
5
4
5
5
4
4
5
5
4
4
5
4
160
160
160
160
160
160
250
250
250
250
250
250
315
315
315
315
315
315
400
400
400
400
400
400
500
500
500
500
630
630
630
0.591
0.591
0.431
0.431
0.431
0.431
0.394
0.394
0.226
0.226
0.226
0.226
0.236
0.236
0.181
0.181
0.181
0.181
0.144
0.144
0.125
0.125
0.125
0.125
0.102
0.102
0.102
0.102
0.072
0.072
0.072
0.260
0.260
0.260
0.260
0.260
0.260
0.202
0.202
0.202
0.202
0.202
0.202
0.186
0.186
0.186
0.186
0.186
0.186
0.130
0.130
0.130
0.130
0.130
0.130
0.127
0.127
0.127
0.127
0.097
0.097
0.029
1000
1000
500
500
500
500
1000
1000
500
500
500
500
1000
1000
500
500
500
500
1000
1000
500
500
500
500
500
500
500
500
1000
1000
1000
Size
630
630
630
630
800
800
800
800
800
800
800
1000
1000
1200
1250
1250
1500
1600
1600
2000
2000
2250
2400
2500
2500
3000
3200
3200
4000
4000
4500
Type
SB4 630A 4 cond. Al
SB5 630A 5 cond. Al
SB6 630A 5 cond. Al
SB7 630A 4 cond. Al
MR 800A 4 cond. Al
MRf 800A 5 cond. Al
SC 800A 4 cond. Al
SB4 800A 4 cond. Al
SB5 800A 5 cond. Al
SB6 800A 5 cond. Al
SB7 800A 4 cond. Al
SC 1000A 4 cond. Al
HRC1 1000A 4 cond. Al
SC 1200A 4 cond. Al
SC 1250A 4 cond. Al
HRC1 1250A 4 cond. Al
SC 1500A 4 cond. Al
SC 1600A 4 cond. Al
HRC1 1600A 4 cond. Al
SC 2000A 4 cond. Al
HRC1 2000A 4 cond. Al
HRC2 2250A 4 cond. Al
SC 2400A 4 cond. Al
SC 2500A 4 cond. Al
HRC2 2500A 4 cond. Al
SC 3000A 4 cond. Al
SC 3200A 4 cond. Al
HRC2 3200A 4 cond. Al
SC 4000A 4 cond. Al
HRC2 4000A 4 cond. Al
HRC2 4500A 4 cond. Al
Number of
conductors
4
5
5
4
4
5
4
4
5
5
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
IZ0
[A]
630
630
630
630
800
800
800
800
800
800
800
1000
1000
1200
1250
1250
1500
1600
1600
2000
2000
2250
2400
2500
2500
3000
3200
3200
4000
4000
4500
rph*
[m/m]
0.073
0.073
0.073
0.073
0.062
0.062
0.067
0.071
0.071
0.071
0.071
0.062
0.068
0.054
0.044
0.044
0.041
0.035
0.041
0.029
0.034
0.032
0.028
0.022
0.022
0.020
0.017
0.020
0.014
0.017
0.014
xph
[m/m]
0.097
0.097
0.097
0.097
0.096
0.096
0.027
0.096
0.096
0.096
0.096
0.023
0.087
0.023
0.021
0.066
0.023
0.017
0.066
0.016
0.053
0.049
0.012
0.011
0.034
0.011
0.009
0.034
0.008
0.024
0.024
Ur
[V]
500
500
500
500
1000
1000
1000
500
500
500
500
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
90
91
2 Protection of feeders
2 Protection of feeders
BTS protection
START
I b In I z
Ib
(3)
where:
Ib is the current for which the circuit is designed;
In is the rated current of the protective device; for adjustable protective devices,
the rated current In is the set current;
Iz is the continuous current carrying capacity of the BTS.
Temperature
<> 40 C ?
yes
no
kt from
Table 1
kt=1
The BTS must be protected against thermal overload and electrodynamic effects
due to the short-circuit current.
Protection against thermal overload
The following formula shall be fulfilled:
BTS choice
Voltage drop
OK ?
no
yes
Circuit-breaker
choice
no
yes
I2 t CB < I2 t BTS ?
no
yes
where:
Ikp CB is the peak limited by the circuit-breaker at the maximum short-circuit
current value at the installation point. This can be extrapolated from the
limitation curves shown in Volume 1, Chapter 3.3;
Ikp BTS is the maximum peak current value of the BTS (see Tables 4 and 5).
no
1SDC010017F0201
yes
END
92
93
2 Protection of feeders
2 Protection of feeders
Table 4: Values of the withstood energy and peak current of copper BTS
94
Size
Type
25
25
25
40
40
40
40
63
100
160
160
160
160
160
250
250
250
250
250
250
315
315
350
350
350
350
400
400
500
500
500
500
630
630
700
700
I2tph
[(kA)2s]
0.48
0.64
0.64
0.73
1
1
7.29
7.29
20.25
30.25
100
100
100
100
312.5
312.5
169
169
169
169
312.5
312.5
169
169
169
169
900
900
756.25
756.25
756.25
756.25
1296
1296
756.25
756.25
I2tN
[(kA)2s]
0.48
0.64
0.64
0.73
1
1
7.29
7.29
20.25
30.25
60
100
100
100
187.5
312.5
101.4
169
169
169
187.5
312.5
101.4
169
169
169
540
900
453.75
756.25
756.25
756.25
777.6
1296
453.75
756.25
I2tPE
[(kA)2s]
0.48
0.64
0.64
0.73
1
1
7.29
7.29
20.25
30.25
60
100
100
100
187.5
312.5
101.4
169
169
169
187.5
312.5
101.4
169
169
169
540
900
453.75
756.25
756.25
756.25
777.6
1296
453.75
756.25
Ipeakph
[kA]
10
10
10
10
10
10
10
10
10
10
17
17
17
17
52.5
52.5
26
26
26
26
52.5
52.5
26
26
26
26
63
63
58
58
58
58
75.6
75.6
58
58
IpeakN
[kA]
10
10
10
10
10
10
10
10
10
10
10.2
10.2
10.2
10.2
31.5
31.5
15.6
15.6
15.6
15.6
31.5
31.5
15.6
15.6
15.6
15.6
37.8
37.8
34.8
34.8
34.8
34.8
45.4
45.4
34.8
34.8
Size
Type
700
700
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
1000
1200
1250
1250
1500
1600
1600
2000
2000
2400
2500
2500
3000
3000
3200
3200
4000
4000
5000
5000
I2tph
[(kA)2s]
756.25
756.25
1296
1296
3969
756.25
756.25
756.25
756.25
1296
1296
3969
1600
1024
1024
1024
1024
7744
7744
2500
7744
7744
2500
7744
3600
7744
7744
4900
30976
8100
30976
8100
30976
8100
30976
10000
I2tN
[(kA)2s]
756.25
756.25
777.6
1296
3969
453.75
756.25
756.25
756.25
777.6
1296
3969
1600
614.4
1024
1024
1024
7744
7744
2500
7744
7744
2500
7744
3600
7744
7744
4900
30976
8100
30976
8100
30976
8100
30976
10000
I2tPE
[(kA)2s]
756.25
756.25
777.6
1296
2381.4
453.75
756.25
756.25
756.25
777.6
1296
2381.4
960
614.4
1024
1024
1024
4646.4
4646.4
1500
4646.4
4646.4
1500
4646.4
2160
4646.4
4646.4
2940
18585.6
4860
18585.6
4860
18585.6
4860
18585.6
6000
Ipeakph
[kA]
58
58
75.6
75.6
139
58
58
58
58
75.6
75.6
139
84
60
60
60
60
194
194
105
194
194
105
194
132
194
194
154
387
198
387
198
387
198
387
220
IpeakN
[kA]
34.8
34.8
45.4
45.4
83.4
34.8
34.8
34.8
34.8
45.4
45.4
83.4
50.4
36
36
36
36
116.4
116.4
63
116.4
116.4
63
116.4
79.2
116.4
116.4
92.4
232.2
118.8
232.2
118.8
232.2
118.8
232.2
132
95
2 Protection of feeders
2 Protection of feeders
96
Size
Type
160
160
160
160
160
160
250
250
250
250
250
250
315
315
315
315
315
315
400
400
400
400
400
400
500
500
500
500
630
630
630
MR 160A 4 cond. Al
MRf 160A 5 cond. Al
SB4 160A 4 cond. Al
SB5 160A 5 cond. Al
SB6 160A 5 cond. Al
SB7 160A 4 cond. Al
MR 250A 4 cond. Al
MRf 250A 5 cond. Al
SB4 250A 4 cond. Al
SB5 250A 5 cond. Al
SB6 250A 5 cond. Al
SB7 250A 4 cond. Al
MR 315A 4 cond. Al
MRf 315A 5 cond. Al
SB4 315A 4 cond. Al
SB5 315A 5 cond. Al
SB6 315A 5 cond. Al
SB7 315A 4 cond. Al
MR 400A 4 cond. Al
MRf 400A 5 cond. Al
SB4 400A 4 cond. Al
SB5 400A 5 cond. Al
SB6 400A 5 cond. Al
SB7 400A 4 cond. Al
SB4 500A 4 cond. Al
SB5 500A 5 cond. Al
SB6 500A 5 cond. Al
SB7 500A 4 cond. Al
MR 630A 4 cond. Al
MRf 630A 5 cond. Al
SC 630A 4 cond. Al
I2tph
[(kA)2s]
112.5
112.5
100
100
100
100
312.5
312.5
169
169
169
169
625
625
169
169
169
169
900
900
625
625
625
625
625
625
625
625
1296
1296
1444
I2tN
[(kA)2s]
67.5
112.5
60
100
100
100
187.5
312.5
101.4
169
169
169
375
625
101.4
169
169
169
540
900
375
625
625
625
375
625
625
625
777.6
1296
1444
I2tPE
[(kA)2s]
67.5
112.5
60
100
100
100
187.5
312.5
101.4
169
169
169
375
625
101.4
169
169
169
540
900
375
625
625
625
375
625
625
625
777.6
1296
866.4
Ipeakph
[kA]
30
30
17
17
17
17
52.5
52.5
26
26
26
26
52.5
52.5
26
26
26
26
63
63
52.5
52.5
52.5
52.5
52.5
52.5
52.5
52.5
75.6
75.6
80
IpeakN
[kA]
18
18
10.2
10.2
10.2
10.2
31.5
31.5
15.6
15.6
15.6
15.6
31.5
31.5
15.6
15.6
15.6
15.6
37.8
37.8
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
45.4
45.4
48
Size
Type
630
630
630
630
800
800
800
800
800
800
800
1000
1000
1200
1250
1250
1500
1600
1600
2000
2000
2250
2400
2500
2500
3000
3200
3200
4000
4000
4500
I2tph
[(kA)2s]
1024
1024
1024
1024
1296
1296
1764
1024
1024
1024
1024
6400
1600
6400
6400
2500
6400
6400
2500
6400
3600
4900
25600
25600
8100
25600
25600
8100
25600
8100
10000
I2tN
[(kA)2s]
614.4
1024
1024
1024
777.6
1296
1764
614.4
1024
1024
1024
6400
1600
6400
6400
2500
6400
6400
2500
6400
3600
4900
25600
25600
8100
25600
25600
8100
25600
8100
10000
I2tPE
[(kA)2s]
614.4
1024
1024
1024
777.6
1296
1058.4
614.4
1024
1024
1024
3840
960
3840
3840
1500
3840
3840
1500
3840
2160
2940
15360
15360
4860
15360
15360
4860
15360
4860
6000
Ipeakph
[kA]
67.5
67.5
67.5
67.5
75.6
75.6
88
67.5
67.5
67.5
67.5
176
84
176
176
105
176
176
105
176
132
154
352
352
198
352
352
198
352
198
220
IpeakN
[kA]
40.5
40.5
40.5
40.5
45.4
45.4
52.8
40.5
40.5
40.5
40.5
105.6
50.4
105.6
105.6
63
105.6
105.6
63
105.6
79.2
92.4
211.2
211.2
118.8
211.2
211.2
118.8
211.2
118.8
132
97
2 Protection of feeders
2 Protection of feeders
If the outgoing feeder, which generally consists of cable duct, is not already
protected against short-circuit and overload by the device located upstream of
the cable, the following measures shall be taken:
Type of
supply
From one end only
Arrangement
of loads
Load concentrated at the end
Evenly distributed load
Evenly distributed load
Load concentrated at the ends
Evenly distributed load
Current distribution
factor
1
0.5
0.25
0.25
0.125
u% =
u .
100
Ur
(7)
Voltage drop
Calculation of voltage drop for unevenly distributed loads
If a BTS is particularly long, the value of the voltage drop must be verified.
For three-phase systems with a power factor (cosm) not lower than 0.8, the
voltage drop can be calculated by using the following simplified formula:
a . 3 . Ib . L. ( rt . cos
u=
1000
+ x . sin
If the loads cannot be considered to be evenly distributed, the voltage drop can
be calculated more accurately by using the formulas below.
L3
L2
[V]
L1
(6a)
u=
a . 2 . Ib . L. ( rt . cos m + x . sin
1000
[V]
(6b)
l1
l2
L
where:
a is the current distribution factor, which depends on the circuit supply and
the arrangement of the electric loads along the BTS, as shown in Table 6:
For the distribution of the three-phase loads shown in the figure, the voltage
drop can be calculated by the following formula if the BTS has a constant cross
section (as usual):
98
l3
+ I 3 L3 cos
) + x( I 1L1 sin
+ I 2 L2 sin
+ I 3 L3 sin
)]
99
1SDC010015F0001
2 Protection of feeders
Generally speaking, this formula becomes:
3 rt .
I i . Li . cos mi + x .
1000
I i . Li . sin
Introduction
mi
[V]
(8)
where:
rt is the phase resistance per unit of length of BTS, measured under thermal
steady-state conditions [m/m];
x is the phase reactance per unit of length of BTS [m/m];
cosm is average power factor of the i-th load;
Ii is i-th load current [A];
Li is the distance of the i-th load from the beginning of the BTS [m].
Upon supply of a lighting installation, for a brief period an initial current exceeding
the rated current (corresponding to the power of the lamps) circulates on the
network. This possible peak has a value of approximately 1520 times the
rated current, and is present for a few milliseconds; there may also be an inrush
current with a value of approximately 1.53 times the rated current, lasting up
to some minutes. The correct dimensioning of the switching and protection
devices must take these problems into account.
I [A]
I [A]
Joule-effect losses
Joule-effect losses are due to the electrical resistance of the BTS.
The losses are dissipated in heat and contribute to the heating of the trunking
and of the environment. Calculation of power losses is useful for correctly
dimensioning the air-conditioning system for the building.
Three-phase losses are:
Pj =
Peak
1520 In
3 . rt . I b2 . L
[W] (9a)
1000
Inrush
1.53 In
In
2 . rt . I b2 . L
[W] (9b)
Pj =
1000
where:
Ib is the current used [A];
rt is the phase resistance per unit of length of BTS measured under thermal
steady-state conditions [m/m];
L is the length of BTS [m].
For accurate calculations, losses must be assessed section by section on the
basis of the currents flowing through them; e.g. in the case of distribution of
loads shown in the previous figure:
1 section
2 section
3 section
Total losses in BTS
100
Length
L1
L2-L1
L3-L2
Current
I1+I2+I3
I2+I3
I3
Losses
P1=3rtL1(I1+I2+I3)2
P2=3rt(L2-L1)(I2+I3)2
P3=3rt(L3-L2)(I3)2
Ptot=P1+P2+P3
Time [milliseconds]
3- 5 min.
Time [minutes]
Incandescent lamps
Incandescent lamps are made up of a glass bulb containing a vacuum or inert
gas and a tungsten filament. The current flows through this filament, heating it
until light is emitted.
The electrical behaviour of these lamps involves a high peak current, equal to
approximately 15 times the rated current; after a few milliseconds the current
returns to the rated value. The peak is caused by the lamp filament which,
initially cold, presents a very low electrical resistance. Subsequently, due to the
very fast heating of the element, the resistance value increases considerably,
causing the decrease in the current absorbed.
101
1SDC010003F0901
u =
Halogen lamps
Halogen lamps are a special type of incandescent lamp in which the gas
contained within the bulb prevents the vaporized material of the tungsten filament
from depositing on the surface of the bulb and forces re-deposition on the
filament. This phenomenon slows the deterioration of the filament, improves
the quality of the light emitted and increases the life of the lamp.
The electrical behaviour of these lamps is the same as that of incandescent
lamps.
Fluorescent lamps
Fluorescent lamps are a so-called discharge light source. The light is produced
by a discharge within a transparent enclosure (glass, quartz, etc. depending on
the type of lamp) which contains mercury vapour at low pressure.
Once the discharge has started, the gas within the enclosure emits energy in
the ultraviolet range which strikes the fluorescent material; in turn, this material
transforms the ultraviolet radiation into radiation which has a wavelength within
the visible spectrum. The colour of the light emitted depends upon the fluorescent
material used.
The discharge is created by an appropriate peak in voltage, generated by a
starter. Once the lamp has been switched on, the gas offers an ever lower
resistance, and it is necessary to stabilize the intensity of the current, using a
controller (reactor); this lowers the power factor to approximately 0.40.6;
normally a capacitor is added to increase the power factor to a value of more
than 0.9
There are two types of controllers, magnetic (conventional) and electronic, which
absorb from 10% to 20% of the rated power of the lamp. Electronic controllers
offer specific advantages such as a saving in the energy absorbed, a lower
dissipation of heat, and ensure a stable, flicker-free light. Some types of
fluorescent lamps with electronic reactors do not need a starter.
Compact fluorescent lamps are made up of a folded tube and a plastic base
which contains, in some cases, a conventional or electronic controller.
The value of the inrush current depends upon the presence of a power factor
correction capacitor:
- non PFC lamps have inrush currents equal to approximately twice the rated
current and a turn-on time of about ten seconds;
- in PFC lamps, the presence of the capacitor allows the reduction of the turnon time to a few seconds, but requires a high peak current, determined by
the charge of the capacitor, which can reach 20 times the rated current.
If the lamp is fitted with an electronic controller, the initial transient current may
lead to peak currents equal to, at maximum, 10 times the rated current.
102
Lamp type
Incandescent lamps
Halogen lamps
Fluorescent
lamp
High intensity
discharge lamps
Non PFC
PFC
Non PFC
PFC
Peak current
15In
15In
20In
20In
Inrush current
2In
2In
2In
Turn-on time
10 s
16 s
28 min
28 min
103
For the selection of a protection device the following verifications shall be carried
out:
- the trip characteristic curve shall be above the turning-on characteristic curve
of the lighting device to avoid unwanted trips; an approximate example is
shown in Figure1;
[t]
Contactor Icw
With reference to the above verification criteria, the following tables show the
maximum number of lamps per phase which can be controlled by the
combination of ABB circuit-breakers and contactors for some types of lamps,
according to their power and absorbed current Ib(*) , for three phase installations
with a rated voltage of 400 V and a maximum short-circuit current of 15 kA.
Turning-on characteristics
[A]
( )
1SDC010004F0901
- coordination shall exist with the contactor under short-circuit conditions (lighting
installations are not generally characterized by overloads).
Circuit-breaker characteristics
Ik= 15 kA
Incandescent/halogen lamps
104
Circuit-breaker type
S270 D20
S270 D32
S270 D50
T2N160 In63
T2N160 In63
T2N160 In100
T2N160 In100
T2N160 In100
T2N160 In160
Setting PR221 DS
----
----
----
----
----
L= 0.68- A S= 8- B
L= 0.92- A S= 10- B
L= 0.68- A S= 8- B
L= 0.76- A S= 8- B
L= 1- A S= 10- B
L= 0.68- A S= 7- B
Contactor type
A26
A26
A26
A26
A30
A40
A50
A63
A75
A95
A110
60
0.27
57
65
70
103
142
155
220
246
272
355
390
100
0.45
34
38
42
62
85
93
132
147
163
210
240
200
0.91
17
19
20
30
42
46
65
73
80
105
120
300
1.37
11
12
13
20
28
30
43
48
53
70
80
500
2.28
12
16
18
26
29
32
42
48
1000
4.55
13
14
16
21
24
1SDC010032F0201
105
Ik= 15 kA
Fluorescent lamps non PFC
S270 D16
S270 D32
S270 D40
S270 D50
T2N160 In100
T2N160 In100
T2N160 In100
T2N160 In160
L= 0.68- A S= 10- B
L= 0.76- A S= 10- B
L= 0.96- A- S= 10- B
S= 0.68- A S= 10- B
A50
A63
A75
A95
A110
S270 D63
Setting PR221 DS
Contactor type
A26
A26
A26
A30
A26
A40
N lamps per phase
20
0.38
40
44
50
73
100
110
157
173
192
250
278
40
0.45
33
37
42
62
84
93
133
145
162
210
234
65
0.7
21
24
27
40
54
60
85
94
104
135
150
80
0.8
18
21
23
35
47
52
75
82
91
118
132
100
1.15
13
14
16
24
33
36
52
57
63
82
92
110
1.2
12
14
15
23
31
35
50
55
60
79
88
Ur= 400 V
1SDC010033F0201
Circuit-breaker type
Ik= 15 kA
Fluorescent lamps PFC
Circuit-breaker type
S270 D25
S270 D40
S270 D63
T2N160 In63
T2N160 In63
T2N160 In100
T2N160 In100
T2N160 In100
Setting PR221 DS
---
---
---
---
---
L= 0.68- A S= 8- B
L= 1- A S= 10- B
L= 0.68- A S= 10- B
L= 0.76- A S= 10- B
L= 0.96- A S= 10- B
A26
A26
A26
A26
A30
A40
A50
A63
A75
A95
Contactor type
106
Capacitor [F]
20
0.18
83
94
105
155
215
233
335
360
400
530
40
0.26
58
65
75
107
150
160
230
255
280
365
65
0.42
35
40
45
66
92
100
142
158
173
225
80
0.52
28
32
36
53
74
80
115
126
140
180
100
0.65
16
23
26
29
43
59
64
92
101
112
145
110
0.7
18
21
24
27
40
55
59
85
94
104
135
107
Ik= 15 kA
Fluorescent lamps non PFC
Circuit-breaker type
S270 D16
S270 D2
S270 D20
S270 D32
S270 D40
S270 D40
S270 D63
S270 D50
Setting PR221 DS
Contactor type
A26
A26
A26
T2N160 In100
T2N160 In160
L= 1- B S= 8- B
L= 0.8- B S= 6.5- B
A50
A63
A75
A95
A110
17
23
26
29
38
41
10
14
16
17
23
25
10
12
15
17
11
12
T2N160 In160
T2N160 In160
A26
A30
150
1.8
11
15
250
400
4.4
600
6.2
1000
10.3
Ur= 400 V
T2N160 In100
L= 0.8- B S= 6.5- B
A40
N lamps per phase
Ik= 15 kA
Fluorescent lamps PFC
Circuit-breaker type
S270 D16
S270 D32
S270 D40
S270 D40
T2N160 In100
T2N160 In100
T2N160 In100
Setting PR221 DS
---
---
---
---
---
---
L= 0.8- B S= 6.5- B
L= 0.88- B S= 6.5- B
L= 1- B S= 6.5- B
A26
A26
A26
A26
A30
A40
A50
A63
A75
A95
A110
Capacitor [F]
150
20
13
14
15
23
28
30
50
58
63
81
88
250
1.5
36
10
15
18
20
33
38
42
54
59
400
2.5
48
11
12
20
23
25
32
36
600
3.3
65
15
17
19
24
27
1000
6.2
100
10
13
14
1SDC010034F0201
Contactor type
Rated Power [W]
Example:
Switching and protection of a lighting system, supplied by a three phase network
at 400 V 15 kA, made up of 55 incandescent lamps, of 200 W each, per phase.
In Table 1, on the row corresponding to 200 W, select the cell showing the
number of controllable lamps immediately above the number of lamps per phase
present in the installation. In the specific case, corresponding to the cell for 65
lamps per phase the following equipment are suggested:
- ABB Tmax T2N160 In63 circuit-breaker with PR221/DS type electronic release,
with protection L set at 0.92, curve A and protection S set at 10, curve B;
- A50 contactor.
108
109
Ikg =
X 'd' %
where
Irg is the rated current of the generator:
Irg =
Unlike the public supply network, which has a constant contribution, in case of
a short-circuit, the current supplied by the generator is a function of the
parameters of the machine itself, and decreases with time; it is possible to
identify the following successive phases:
1. a subtransient phase: with a brief duration (1050 ms), characterized
by the subtransient reactance Xd (520% of the rated impedance value),
and by the subtransient time constant Td (530 ms);
2. a transitory phase: may last up to some seconds (0.52.5 s), and is
characterized by the transitory reactance Xd (1540% of the rated
impedance value), and by the transitory time constant Td (0.032.5 s);
3. a synchronous phase: may persist until the tripping of external protection,
and is characterized by the synchronous reactance Xd (80300% of
the rated impedance value).
t [s]
Irg . 100
Srg
3 . Ur
The circuit-breaker for the protection of the generator shall be selected according
to the following criteria:
the set current higher than the rated current of the generator: I1 Irg;
breaking capacity Icu or Ics higher than the maximum value of short-circuit
current at the installation point:
- in the case of a single generator: Icu(Ics) Ikg;
- in the case of n identical generators in parallel: Icu(Ics) Ikg(n-1);
- in the case of operation in parallel with the network: Icu(Ics) IkNet,
as the short-circuit contribution from the network is normally
greater than the contribution from the generator;
for circuit-breakers with thermomagnetic releases: low magnetic trip threshold:
I3 =2.5/3In;
for circuit-breakers with electronic releases:
- trip threshold of the delayed short-circuit protection function (S), set
between 1.5 and 4 times the rated current of the generator, in such
a way as to intercept the decrement curve of the generator:
I2 = (1.54)Irg; if the function S is not present, function I can be set
at the indicated values I3 = (1.54)Irg;
- trip threshold of the instantaneous short-circuit protection function
(I3) set at a value greater than the rated short-circuit current of the
generator, so as to achieve discrimination with the devices installed
downstream, and to allow fast tripping in the event of a short-circuit
upstream of the device (working in parallel with other generators or
with the network):
101
Synchronous
phase
1
Transient
phase
10-1
I 3 I kg
Subtransient
phase
10-3
110
1SDC010018F0201
10-2
10
102
x Irg
111
The following tables give ABB SACE suggestions for the protection and switching
of generators; the tables refer to 400 V (Table 1), 440 V (Table 2), 500 V (Table 3)
and 690 V (Table 4).
Srg [kVA]
MCB
4
6
7
9
11
14
17
19
21
22
28
31
35
38
42
44
48
55
69
80
87
100
111
138
159
173
180
190
208
218
242
277
308
311
346
381
415
436
484
554
692
727
865
1107
1730
2180
2214
2250
2500
2800
3150
3500
S20L/S260 B6
S20L/S260 B10
S20L/S260 B13
S20L/S260 B16
MCCB
ACB
T2 160 In=10
T2 160 In=25
S20L/S260 B25
S20L/S260 B32
S20L/S260 B50
T2 160 In=63
S20L/S260 B63
S280 B80
T2 160 In=100
S280 B100
T2 160 In=160
T2 160
T4 250
T3 250
T4 250
T4 320
T5 400
T5 630
S6 800
S6 800
S7 1250
E1/E2 1250
S7 1250
S7 1600
S8 3200
E2/E3 1600
E2/E3 2000
E3 3200
E3 3200/E4 4000
E4 4000
E6 5000/6300
Table 2
Table 3
440 V
Srg [kVA]
MCB
4
6
7
9
11
14
17
19
21
22
28
31
35
38
42
44
48
55
69
80
87
100
111
138
159
173
180
190
208
218
242
277
308
311
346
381
415
436
484
554
692
727
865
1107
1730
2180
2214
2250
2500
2800
3150
3500
S20L/S260 B6
S20L/S260 B8
S20L/S260 B10
S20L/S260 B13
S20L/S260 B16
S20L/S260 B20
S20L/S260 B25
MCCB
ACB
Srg [kVA]
T2 160 In=10
T2 160 In=25
S20L/S260 B32
S20L/S260 B40
S20L/S260 B50
T2 160 In=63
S20L/S260 B63
S280 B80
S280 B100
T2 160 In=100
T2 160 In=160
T2 160 In=160
T4 250
T3 250
T4 250
T4 320
T5 400
T5 630
S6 800
S6 800
S7 1000
S7 1000
S7 1250
S7 1600
E1/E2 1250
E2/E3 1600
E3 2500
S8 3200
E3 3200
E4 3600
E4 4000
E6 5000/6300
4
6
7
9
11
14
17
19
21
22
28
31
35
38
42
44
48
55
69
80
87
100
111
138
159
173
180
190
208
218
242
277
308
311
346
381
415
436
484
554
692
727
865
1107
1730
2180
2214
2250
2500
2800
3150
3500
500 V
MCB
MCCB
T2 160 In=25
T2 160 In=63
T2 160 In=100
T2 160 In=160
T3 250
T4 250
T4 250
T4 320
T5 400
T5 630
S6 800
E1/E2 1250
S7 1250
S7 1600
S8 2500
E2/E3 1600
E3 2500
S8 3200
E3 3200
E4 4000
E6 5000/6300
690 V
MCB
ACB
T2 160 In=10
S6 800
S7 1000
Table 4
4
6
7
9
11
14
17
19
21
22
28
31
35
38
42
44
48
55
69
80
87
100
111
138
159
173
180
190
208
218
242
277
308
311
346
381
415
436
484
554
692
727
865
1107
1730
2180
2214
2250
2500
2800
3150
3500
MCCB
ACB
T2 160 In=10
T2 160 In=25
T2 160 In=63
T2 160 In=100
T2 160 In=160
T3 250
T4 250
T4 320
T5 400
T5 630
T5 630
S6 800
S6 800
S7 1000
S7 1600
S8 2500
E1 800
E1/E2 1250
E2/E3 1600
1SDC010017F0001
400 V
1SDC010016F0001
Table 1
E2 2000
E3 2500
E3 2500
S8 3200
E3 3200
Note: It is always advisable to check that the settings of the releases are correct with respect to the
effective decrement curve of the current of the generator to be protected.
112
113
Example:
Protection of a generator with Srg = 100 kVA, in a system with a rated voltage
of 440 V.
The generator parameters are:
Ur = 440 V
Srg = 100 kVA
f = 50 Hz
Irg = 131.2 A
Xd = 6.5 % (subtransient reactance)
Xd = 17.6 % (transient reactance)
Xd = 230 % (synchronous reactance)
Td = 5.5 ms (subtransient time constant)
Td = 39.3 ms (transient time constant)
From table 2, an ABB SACE T2N160 circuit-breaker is selected, with In = 160
A, with electronic release PR221-LS. For correct protection of the generator,
the following settings are selected:
function L: 0.84 A, corresponding to 134.4 A, value greater than Irg
function I: 1.5
Electromechanical starter
The starter is designed to:
- start motors;
- ensure continuous functioning of motors;
- disconnect motors from the supply line;
- guarantee protection of motors against working overloads.
The starter is typically made up of a switching device (contactor) and an overload
protection device (thermal release).
The two devices must be coordinated with equipment capable of providing
protection against short-circuit (typically a circuit-breaker with magnetic release
only), which is not necessarily part of the starter.
The characteristics of the starter must comply with the international Standard
IEC 60947-4-1, which defines the above as follows:
Contactor: a mechanical switching device having only one position of rest,
operated otherwise than by hand, capable of making, carrying and breaking
currents under normal circuit conditions including operating overload conditions.
Thermal release: thermal overload relay or release which operates in the case
of overload and also in case of loss of phase.
Time-Current Curves
10 4 s
10 3 s
T2 160
The main types of motor which can be operated and which determine the
characteristics of the starter are defined by the following utilization categories:
10 s
10 1 s
Current type
AC-2
1SDC010019F0201
10-1s
10-2s
10-1kA
114
1kA
Utilization categories
101kA
Alternating Current ac
AC-3
AC-4
Typical applications
Slip-ring motors: starting,
switching off
Squirrel-cage motors: starting,
switching off during running(1)
Squirrel-cage motors: starting,
plugging, inching
(1)
AC-3 categories may be used for occasionally inching or plugging for limited time periods
such as machine set-up; during such limited time periods the number of such operations
should not exceed five per minutes or more than ten in a 10 minutes period.
115
The choice of the starting method and also, if necessary, of the type of motor to
be used depends on the typical resistant torque of the load and on the shortcircuit power of the motor supplying network.
With alternating current, the most commonly used motor types are as follows:
- asynchronous three-phase squirrel-cage motors (AC-3): the most widespread
type due to the fact that they are of simple construction, economical and
sturdy; they develop high torque with short acceleration times, but require
elevated starting currents;
- slip-ring motors (AC-2): characterized by less demanding starting conditions,
and have quite a high starting torque, even with a supply network of low
power.
Star-Delta starter
The most common reduced voltage starter is the Star-Delta starter (Y-), in
which:
- on starting, the stator windings are star-connected, thus achieving the
reduction of peak inrush current;
- once the normal speed of the motor is nearly reached, the switchover to delta
is carried out.
After the switchover, the current and the torque follow the progress of the curves
associated with normal service connections (delta).
Starting methods
As can be easily checked, starting the motor with star-connection gives a voltage
reduction of 3, and the current absorbed from the line is reduced by 1/3
compared with that absorbed with delta-connection.
The start-up torque, proportional to the square of the voltage, is reduced by 3
times, compared with the torque that the same motor would supply when delta-connected.
This method is generally applied to motors with power from 15 to 355 kW, but
intended to start with a low initial resistant torque.
MCCB
KL
K
KY
1SDC010019F0001
TOR
MCCB
Motor
KL
Starting sequence
1SDC010018F0001
TOR
Motor
116
By pressing the start button, contactors KL and KY are closed. The timer starts
to measure the start time with the motor connected in star. Once the set time
has elapsed, the first contact of the timer opens the KY contactor and the
second contact, delayed by approximately 50 ms, closes the K contactor.
With this new configuration, contactors KL and K closed, the motor becomes
delta-connected.
117
The thermal release TOR, inserted in the delta circuit, can detect any 3rd harmonic
currents, which may occur due to saturation of the magnetic pack and by
adding to the fundamental current, overload the motor without involving the line.
Therefore, the motor starts at a reduced voltage, and when it has reached
approximately 80% of its normal speed, contactor K1 is opened and main
contactor K3 is closed. Subsequently, contactor K2 is opened, excluding the
autotransformer so as to supply the full network voltage.
With reference to the connection diagram, the equipment used for a Star/Delta
starter must be able to carry the following currents:
Ir
3
Ir
3
KY star contactor
Ir
3
MCCB
K1
K2
K2
K1
K3
Motor
118
1SDC010021F0001
TOR
1SDC010020F0001
Inductance
TOR
Motor
In compliance with the above mentioned Standard, starters can also be classified
according to tripping time (trip classes), and according to the type of coordination
achieved with the short-circuit protection device (Type 1 and Type 2).
119
Trip classes
The trip classes differentiate between the thermal releases according to their
trip curve.
The trip classes are defined in the following table 2:
MCCB
Contactor
where Tp is the cold trip time of the thermal release at 7.2 times the set current
value (for example: a release in class 10 at 7.2 times the set current value must
not trip within 4 s, but must trip within 10 s).
It is normal procedure to associate class 10 with a normal start-up type, and
class 30 with a heavy duty start-up type.
Coordination type
Type 1
It is acceptable that in the case of short-circuit the contactor and the thermal
release may be damaged. The starter may still not be able to function and must
be inspected; if necessary, the contactor and/or the thermal release must be
replaced, and the breaker release reset.
Type 2
In the case of short-circuit, the thermal release must not be damaged, while
the welding of the contactor contacts is allowed, as they can easily be separated
(with a screwdriver, for example), without any significant deformation.
In order to clearly determine a coordination type, and therefore the equipment
necessary to achieve it, the following must be known:
power of the motor in kW and type;
rated system voltage;
rated motor current;
short-circuit current at installation point;
starting type: DOL or Y/ - normal or heavy duty Type 1 or Type 2.
The requested devices shall be coordinated with each other in accordance
with the prescriptions of the Standard.
For the most common voltages and short-circuit values (400 V - 440 V - 500 V
- 690 V 35 kA - 50 kA) and for the most frequently used starting types, such as
direct starting and Star/Delta starting, for asynchronous squirrel-cage motor
(AC-3), ABB supplies solutions with:
magnetic circuit-breaker - contactor - thermal release;
thermomagnetic circuit-breaker - contactor;
thermomagnetic circuit-breaker with PR212 MP electronic release contactor.
120
Current
setting
Pe
Ir
Type
I3
Type
Type
[A]
min.
max.
[kW]
[A]
[A]
[A]
0.37
1.1
T2S160 MF 1.6
21
A9
TA25DU1.4
1.4
0.55
1.5
T2S160 MF 1.6
21
A9
TA25DU1.8
1.3
1.8
0.75
1.9
T2S160 MF 2
26
A9
TA25DU2.4
1.7
2.4
1.1
2.8
T2S160 MF 3.2
42
A9
TA25DU4
2.8
1.5
3.5
T2S160 MF 4
52
A16
TA25DU5
3.5
2.2
T2S160 MF 5
65
A26
TA25DU6.5
4.5
6.5
6.6
T2S160 MF 8.5
110
A26
TA25DU8.5
8.5
8.6
T2S160 MF 11
145
A30
TA25DU11
7.5
11
5.5
11.5
T2S160 MF 12.5
163
A30
TA25DU14
10
14
7.5
15.2
T2S160 MA 20
210
A30
TA25DU19
13
19
11
22
T2S160 MA 32
288
A30
TA42DU25
18
25
15
28.5
T2S160 MA 52
392
A50
TA75DU42
29
42
18.5
36
T2S160 MA 52
469
A50
TA75DU52
36
52
22
42
T2S160 MA 52
547
A50
TA75DU52
36
52
80
30
56
T2S160 MA 80
840
A63
TA75DU80
60
37
68
T2S160 MA 80
960
A75
TA75DU80
60
80
45
83
T2S160 MA 100
1200
A95
TA110DU110
80
110
55
98
T3S250 MA 160
1440
A110
TA110DU110
80
110
75
135
T3S250 MA 200
1800
A145
TA200DU175
130
175
90
158
T3S250 MA 200
2400
A185
TA200DU200
150
200
110
193
2720
A210
E320DU320
100
320
320
132
232
3200
A260
E320DU320
100
160
282
4000
A300
E320DU320
100
320
200
349
5040
AF400
E500DU500
150
500
250
430
6300
AF460
E500DU500
150
500
290
520
8000
AF580
E800DU800
250
800
315
545
9600
AF580
E800DU800
250
800
355
610
9600
AF750
E800DU800
250
800
121
1SDC010022F0201
Trip Class
10A
10
20
30
Motor
Pe
MCCB
Ir
Type
Contactor
Setting of
the
magnetic
release
Type
MOTOR
Type**
Setting
No. of
range
turns of
the CT
primary min. max.
coil
[A]
[A]
MCCB
Contactor
I3
LINE
DELTA
STAR
[A]
Type
Type
Type
A50
A50
A26
TA75DU25
18-25
Pe [kW]
Ir [A]
18.5
36
T2S160 MA52
469
Type
Type
[A]
[kW]
[A]
22
42
T2S160 MA52
547
A50
A50
A26
TA75DU32
22-32
0.37
1.1
T2S160 MF 1.6
21
A9
TA25DU1.4*
1.4
30
56
T2S160 MA80
720
A63
A63
A30
TA75DU42
29-42
0.55
1.5
T2S160 MF 1.6
21
A9
TA25DU1.8*
1.3
1.8
37
68
T2S160 MA80
840
A75
A75
A30
TA75DU52
36-52
0.75
1.9
T2S160 MF 2
26
A9
TA25DU2.4*
1.7
2.4
45
83
T2S160 MA100
1050
A75
A75
A30
TA75DU63
45 - 63
1.1
2.8
T2S160 MF 3.2
42
A9
TA25DU4*
2.8
1.5
3.5
T2S160 MF 4
52
A16
TA25DU5*
3.5
2.2
T2S160 MF 5
65
A26
TA25DU6.5*
4.5
6.5
6.6
T2S160 MF 8.5
110
A26
TA25DU8.5*
8.5
90
158
T3S250 MA200
2000
A110
A110
A95
TA110DU110
80 - 110
8.6
T2S160 MF 11
145
A30
TA25DU11*
7.5
11
110
193
T3S250 MA200
2400
A145
A145
A95
TA200DU135
100 - 135
5.5
11.5
T2S160 MF 12.5
163
A30
TA450SU60
10
15
132
232
2880
A145
A145
A110
E200DU200
60 - 200
7.5
15.2
T2S160 MA 20
210
A30
TA450SU60
13
20
160
282
3600
A185
A185
A145
E200DU200
60 - 200
11
22
T2S160 MA 32
288
A30
TA450SU60
20
30
40
200
349
4410
A210
A210
A185
E320DU320
100 - 320
250
430
5670
A260
A260
A210
E320DU320
100 - 320
15
28.5
T2S160 MA 52
392
A50
TA450SU80
23
18.5
36
T2S160 MA 52
469
A50
TA450SU80
23
40
22
42
T2S160 MA 52
547
A50
TA450SU60
40
60
30
56
T2S160 MA 80
840
A63
TA450SU80
55
80
37
68
T2S160 MA 80
960
A95
TA450SU80
55
80
45
83
T2S160 MA 100
1200
A110
TA450SU105
70
105
55
98
T3S250 MA 160
1440
A145
TA450SU140
95
140
75
135
T3S250 MA 200
1800
A185
TA450SU185
130
185
90
158
T3S250 MA 200
2400
A210
TA450SU185
130
185
110
193
2720
A260
E320DU320
100
320
132
232
3200
A300
E320DU320
100
320
160
282
4000
AF400
E500DU500
150
500
200
349
5040
AF460
E500DU500
150
500
250
430
6300
AF580
E500DU500***
150
500
290
520
8000
AF750
E800DU800
250
800
315
545
9600
AF750
E800DU800
250
800
355
610
9600
AF750
E800DU800
250
800
55
98
T2S160 MA100
1200
A75
A75
A40
TA75DU63
45 - 63
75
135
T3S250 MA160
1700
A95
A95
A75
TA110DU90
66 - 90
1SDC010020F0201
[A]
122
123
1SDC010023F0201
Motor
MCCB
Contactor
Motor
Pe
Ir
[kW]
[A]
0.37
Type
I3
Type
Type
[A]
T2H160 MF 1
13
A9
TA25DU1.4
Pe
Ir
[kW]
[A]
0.37
1.4
0.55
1.4
min.
max.
[A]
[A]
Contactor
Setting of
the
magnetic
release
Type
[A]
T2H160 MF 1
13
A9
TA25DU1.4*
1.4
T2H160 MF 1.6
21
A9
TA25DU1.8*
1.3
1.8
0.55
1.4
T2H160 MF 1.6
21
A9
TA25DU1.8
1.3
1.8
0.75
1.7
T2H160 MF 2
26
A9
TA25DU2.4*
1.7
2.4
0.75
1.7
T2H160 MF 2
26
A9
TA25DU2.4
1.7
2.4
1.1
2.2
T2H160 MF 2.5
33
A9
TA25DU3.1*
2.2
3.1
2.2
T2H160 MF 2.5
33
A9
TA25DU3.1
2.2
3.1
1.5
T2H160 MF 3.2
42
A16
TA25DU4
2.8
2.2
4.4
2.2
4.4
T2H160 MF 5
65
A26
TA25DU5
3.5
5.7
T2H160 MF 6.5
84
A26
TA25DU6.5
4.5
6.5
7.8
T2H160 MF 8.5
110
A30
TA25DU11
7.5
11
5.5
10.5
T2H160 MF 11
145
A30
TA25DU14
10
14
11
19
T2H160 MA 32
240
A30
TA450SU80
18
27
7.5
13.5
T2H160 MA 20
180
A30
TA25DU19
13
19
15
26
T2H160 MA 32
336
A50
TA450SU60
20
30
11
19
T2H160 MA 32
240
A30
TA42DU25
18
25
18.5
32
T2H160 MA 52
469
A50
TA450SU80
28
40
15
26
T2H160 MA 32
336
A50
TA75DU32
22
32
22
38
T2H160 MA 52
547
A50
TA450SU80
28
40
18.5
32
T2H160 MA 52
469
A50
TA75DU42
29
42
30
52
T2H160 MA 80
720
A63
TA450SU60
40
60
22
38
T2H160 MA 52
547
A50
TA75DU52
36
52
37
63
T2H160 MA 80
840
A95
TA450SU80
55
80
30
52
T2H160 MA 80
720
A63
TA75DU63
45
63
45
75
T2H160 MA 100
1050
A110
TA450SU105
70
105
37
63
T2H160 MA 80
840
A75
TA75DU80
60
80
55
90
1200
A145
E200DU200
60
200
45
75
T2H160 MA 100
1050
A95
TA110DU90
65
90
55
90
1200
A110
TA110DU110
80
110
75
120
1750
A145
E200DU200
60
200
90
147
2000
A185
E200DU200
60
200
110
177
2500
A210
E320DU320
100
320
132
212
3200
A260
E320DU320
100
320
160
260
3600
A300
E320DU320
100
320
200
320
4410
AF 400
E500DU500
150
500
250
410
5355
AF 460
E500DU500
150
500
290
448
7560
AF 580
E500DU500*
150
500
315
500
8000
AF 580
E800DU800
250
800
355
549
9600
AF 580
E800DU800
250
800
1SDC010024F0201
1.1
1.5
124
MCCB
Type
Current
setting
T2H160 MF 3.2
42
A16
TA25DU4*
2.8
T2H160 MF 5
65
A26
TA25DU5*
3.5
5.7
T2H160 MF 6.5
84
A26
TA25DU6.5*
4.5
6.5
7.8
T2H160 MF 8.5
110
A30
TA25DU11*
7.5
11
5.5
10.5
T2H160 MF 11
145
A30
TA25DU14*
10
14
7.5
13.5
T2H160 MA 20
180
A30
TA450SU60
10
15
75
120
1750
A185
E200DU200
60
200
90
147
2000
A210
E320DU320
100
320
110
177
2500
A260
E320DU320
100
320
132
212
3200
A300
E320DU320
100
320
160
260
3600
AF400
E500DU500
150
500
200
320
4410
AF460
E500DU500
150
500
250
410
5355
AF580
E500DU500***
150
500
290
448
7560
AF750
E500DU500***
150
500
315
500
8000
AF 750
E800DU800
250
800
355
549
9600
AF 750
E800DU800
250
800
125
1SDC010021F0201
MOTOR
Pe [kW]
MCCB
Ir [A]
Type
Contactor
I3
LINE
DELTA
STAR
[A]
Type
Type
Type
Type
MCCB
Motor
Contactor
Type
Type
Type
[A]
18.5
32
T2H160 MA52
392
A 50
A 50
A 16
TA75DU25
18-25
22
38
T2H160 MA52
469
A 50
A 50
A 26
TA75DU25
18-25
Pe
[kW]
Ir
[A]
I3
[A]
min.
[A]
max.
[A]
52
T2H160 MA80
720
A 63
A 63
A 26
TA75DU42
29-42
63
T2H160 MA80
840
A 75
A 75
A 30
TA75DU42
29-42
0.37
0.88
T2L160 MF 1
13
A9
TA25DU1.0
0.63
45
75
T2H160 MA80
960
A 75
A 75
A30
TA75DU52
36-52
0.55
1.2
T2L160 MF 1.6
21
A9
TA25DU1.4
1.4
0.75
1.5
T2L160 MF 1.6
21
A9
TA25DU1.8
1.3
1.8
1.1
2.2
T2L160 MF 2.5
33
A9
TA25DU3.1
2.2
3.1
1.5
2.8
T2L160 MF 3.2
42
A16
TA25DU4
2.8
2.2
T2L160 MF 4
52
A26
TA25DU5
3.5
5.2
T2L160 MF 6.5
84
A26
TA25DU6.5
4.5
6.5
55
90
T2H160 MA100
1150
A 75
A 75
A40
TA75DU63
45 - 63
75
120
1625
A95
A95
A75
TA80DU80
60-80
90
147
1875
A95
A95
A75
TA110DU110
80-110
110
177
2250
A145
A145
A95
E200DU200
60-200
132
212
2720
A145
A145
A110
E200DU200
60-200
160
260
3200
A185
A185
A145
E200DU200
60-200
200
320
4095
A210
A210
A185
E320DU320
100-320
250
410
5040
A260
A260
A210
E320DU320
100-320
1SDC010025F0201
30
37
6.9
T2L160 MF 8.5
110
A30
TA25DU8.5
8.5
5.5
9.1
T2L160 MF 11
145
A30
TA25DU11
7.5
11
7.5
12.2
T2L160 MF 12.5
163
A30
TA25DU14
10
14
11
17.5
T2L160 MA 20
240
A30
TA25DU19
13
19
15
23
T2L160 MA 32
336
A50
TA75DU25
18
25
18.5
29
T2L160 MA 52
392
A50
TA75DU32
22
32
22
34
T2L160 MA 52
469
A50
TA75DU42
29
42
30
45
T2L160 MA 52
624
A63
TA75DU52
36
52
37
56
T2L160 MA 80
840
A75
TA75DU63
45
63
45
67
T2L160 MA 80
960
A95
TA80DU80
60
80
55
82
T2L160 MA 100
1200
A110
TA110DU90
65
90
75
110
1440
A145
E200DU200
60
200
90
132
1875
A145
E200DU200
60
200
110
158
2250
A185
E200DU200
60
200
132
192
2720
A210
E320DU320
100
320
160
230
3600
A260
E320DU320
100
320
200
279
4000
A300
E320DU320
100
320
250
335
4725
AF 400
E 500DU500
150
500
290
394
5040
AF 460
E 500DU500
150
500
315
440
7560
AF 580
E 500DU500*
150
500
355
483
7560
AF 580
E 800DU800
250
800
126
127
1SDC010026F0201
MCCB
Type
Pe
Ir
Contactor
Setting of
the
magnetic
release
Type
[A]
MOTOR
MCCB
Type**
[kW]
[A]
0.37
0.88
T2L160 MF 1
13
A9
TA25DU1.0*
0.63
0.55
1.2
T2L160 MF 1.6
21
A9
TA25DU1.4*
1.4
0.75
1.5
T2L160 MF 1.6
21
A9
TA25DU1.8*
1.3
1.8
1.1
2.2
T2L160 MF 2.5
33
A9
TA25DU3.1*
2.2
3.1
1.5
2.8
T2L160 MF 3.2
42
A16
TA25DU4*
2.8
2.2
T2L160 MF 4
52
A26
TA25DU5*
3.5
5.2
T2L160 MF 6.5
84
A26
TA25DU6.5*
4.5
6.5
6.9
T2L160 MF 8.5
110
A30
TA25DU8.5*
8.5
7.5
11
5.5
9.1
T2L160 MF 11
145
A30
TA25DU11*
7.5
12.2
T2L160 MF 12.5
163
A30
TA450SU60
10
15
11
17.5
T2L160 MA 20
240
A30
TA450SU60
13
20
15
23
T2L160 MA 32
336
A50
TA450SU60
20
30
18.5
29
T2L160 MA 52
392
A50
TA450SU80
27.5
40
22
34
T2L160 MA 52
469
A50
TA450SU80
27.5
40
30
45
T2L160 MA 52
624
A63
TA450SU60
40
60
37
56
T2L160 MA 80
840
A75
TA450SU60
40
60
45
67
T2L160 MA 80
960
A95
TA450SU80
55
80
55
82
T2L160 MA 100
1200
A145
TA450SU105
70
105
75
110
1440
A145
E200DU200
60
200
90
132
1875
A185
E200DU200
60
200
110
158
2123
A210
E320DU320
100
320
132
192
2720
A260
E320DU320
100
320
160
230
3200
A300
E320DU320
100
320
200
279
3600
AF400
E500DU500
150
500
250
335
4725
AF460
E500DU500
150
500
290
394
5040
AF580
E500DU500***
150
500
315
440
7560
AF750
E500DU500***
150
500
355
483
7560
AF750
E500DU500
150
500
Pe [kW]
22
30
37
45
55
75
90
110
132
160
200
250
290
Ir [A]
Contactor
I3
LINE
DELTA
STAR
Type
[A]
Type
Type
Type
T2L160 MA52
430
A 50
A 50
A 16
45
T2L160 MA52
547
A 63
A 63
56
T2L160 MA80
720
A 75
A 75
67
T2L160 MA80
840
A 75
34
Type
[A]
TA75DU25
18-25
A 26
TA75DU32
22-32
A 30
TA75DU42
29-42
A 75
A30
TA75DU52
36 - 52
82
T2L160 MA100
1050
A 75
A 75
A30
TA75DU52
36 - 52
110
1375
A95
A95
A50
TA80DU80
60-80
132
1750
A95
A95
A75
TA110DU90
65-90
158
2000
A110
A110
A95
TA110DU110
80-110
192
2560
A145
A145
A95
E200DU200
60-200
230
2880
A145
A145
A110
E200DU200
60-200
279
3400
A210
A210
A145
E320DU320
100-320
335
4410
A210
A210
A185
E320DU320
100-320
394
5040
A260
A260
A210
E320DU320
100-320
1SDC010021F0201
Motor
128
129
1SDC010027F0201
General aspects
Transformers are used to achieve a change in the supply voltage, for both
medium and low voltage supplies.
The choice of the protection devices must take into account transient insertion
phenomena, during which the current may reach values higher than the rated
full load current; the phenomenon decays in a few seconds.
The curve which represents these transient phenomena in the time-current
diagram, termed inrush current I0, depends on the size of the transformer
and can be evaluated with the following formula (the short-circuit power of the
network is assumed to be equal to infinity)
I0 =
K I r1 e ( t / )
2
where:
K ratio between the maximum peak inrush current value ( I0 ) and the rated
current of the transformer (I1r): (K= I0 / I1r);
time constant of the inrush current;
I1r rated current of the primary;
t time.
The table below shows the indicative values for t and K parameters referred to
rated power Sr for oil transformers.
Sr [kVA]
K = Io/I1r
[s]
50
15
0.10
100
14
0.15
160
12
0.20
250
12
0.22
400
12
0.25
630
11
0.30
1000
10
0.35
1600
9
0.40
2000
8
0.45
Further to the above consideration, the follwing diagram shows the inrush
current curve for a 20/0.4kV of 400kVA transformer. This transformer has an
inrush current during the very first moments equal to about 8 times the rated
current; this transient phenomenon stops after a few tenths of a second.
[s]
10-2
10-3
1SDC010022F0001
10-1
10-2
10-1
1
[kA]
130
131
The transformer protection devices must also guarantee that the transformer
cannot operate above the point of maximum thermal overload under shortcircuit conditions; this point is defined on the time-current diagram by the value
of short-circuit current which can pass through the transformer and by a time
equal to 2 s, as stated by Standard IEC 60076-5. The short-circuit current (Ik)
flowing for a fault with low impedance at the LV terminals of the transformer is
calculated by using the following formula:
In summary: for the correct protection of the transformer and to avoid unwanted
trips, the trip curve of the protection device must be above the inrush current
curve and below the overload point.
The diagram below shows a possible position of the time-current curve of an
upstream protection device of a 690/400 V, 250 kVA transformer with uk% = 4 %.
Ik =
Ur
[A]
3 ( ZNet + Zt )
10 4 s
(1)
where:
Ur is the rated voltage of the transformer [V];
ZNet is the short-circuit impedance of the network [];
Zt is the short-circuit impedance of the transformer; from the rated power of
the transformer (Sr [VA]) and the percentage short-circuit voltage (uk%) it is
equal to:
Zt =
uk % U r2
[]
100 Sr
10 3 s
T4N250 PR221 In=250 A
2
10 s
10 1 s
(2)
250 kVA Trafo
1s
100 Sr
1SDC010024F0001
10-1s
Ur
Ik =
=
3 ( Zt )
(3)
10-2s
The diagram below shows the inrush current curve for a 20/0.4 kV of 400 kVA
transformer (uk% = 4 %) and the point referred to the thermal ability to withstand
the short-circuit current (Ik; 2 sec.).
10-1 kA
1kA
10kA
1s
1SDC010023F0001
10-1s
10-2s
1kA
132
10kA
133
The full voltage three-phase short-circuit current (Ik), at the LV terminals of the
transformer, can be expressed as (assuming that the short-circuit power of the
network is infinite):
Ik =
100 I r
[A]
uk %
(5)
where:
uk% is the short-circuit voltage of the transformer, in %.
Ik1
Ik3
Ik2 + Ik3
134
Ik2
B
Ik = Ik1 + Ik2 + Ik3
135
1SDC010025F0001
If the short-circuit power of the upstream network is not infinite and cable or
busbar connections are present, it is possible to obtain a more precise value
for Ik by using formula (1), where ZNet is the sum of the impedance of the
network and of the impedance of the connection.
uk
Trafo Ir
[kVA]
%
1 x 63
4
2 x 63
1 x 100
4
2 x 100
1 x 125
4
2 x 125
1 x 160
4
2 x 160
1 x 200
4
2 x 200
1 x 250
4
2 x 250
1 x 315
4
2 x 315
1 x 400
4
2 x 400
1 x 500
4
2 x 500
1 x 630
4
2 x 630
3 x 630
1 x 800
5
2 x 800
3 x 800
1 x 1000
2 x 1000 5
3 x 1000
1 x 1250
2 x 1250 5
3 x 1250
[A]
158
158
251
251
314
314
402
402
502
502
628
628
791
791
1004
1004
1255
1255
1581
1581
1581
2008
2008
2008
2510
2510
2510
3138
3138
3138
136
Trafo
Feeder Ik
[kA]
3.9
3.9
6.3
6.2
7.8
7.8
10.0
9.9
12.5
12.4
15.6
15.4
19.6
19.4
24.8
24.5
30.9
30.4
38.7
37.9
74.4
39.3
38.5
75.5
48.9
47.7
93.0
60.7
58.8
114.1
ABB SACE
Circuit-breaker
T1B160
T1B160
T4N320
T4N320
T5N400
T5N400
T5N630
T5N630
T5N630
T5N630
T5N630
T5N630
S6N800
S6N800
S7S1250/E1B1250
S7S1250/E1B1250
S7S1600/E2B1600
S7S1600/E2B1600
S7S1600/E2B1600
S7S1600/E2B1600
S7S1600/E3S1600
E3N2500
E3N2500
E3H2500
E3N3200
E3N3200
E3H3200
E3N3200
E3N3200
S8V3200/E6V3200
Release
Busbar Ik
size
setting
In=160
1
In=160
1
In=320
0.9
In=320
0.9
In=400
0.9
In=400
0.9
In=630
0.7
In=630
0.7
In=630
0.9
In=630
0.9
In=630
1
In=630
1
In=800
1
In=800
1
In=1250
0.9
In=1250
0.9
In=1600
0.9
In=1600
0.9
In=1600
1
In=1600
1
In=1600
1
In=2500
0.9
In=2500
0.9
In=2500
0.9
In=3200
0.8
In=3200
0.8
In=3200
0.8
In=3200
1
In=3200
1
In=3200
1
[kA]
3.9
7.9
6.3
12.5
7.8
15.6
10.0
19.9
12.5
24.8
15.6
30.9
19.6
38.7
24.8
48.9
30.9
60.7
38.7
75.9
111.6
39.3
77.0
113.2
48.9
95.3
139.5
60.7
117.7
171.2
250 A
400 A
630 A
800 A
1250 A
1600 A
2000 A
2500 A
3200 A
4000 A
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3S250
T3N250
T3S250
T4L250
T3N250
T3S250
T4L250
T3N250
T4H250
T4L250
T3S250
T4L250
T4L250
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5S400
T5L400
T5N400
T5S400
T5L400
T5N400
T5H400
T5L400
T5N400
T5L400
T5L400
T5N630
T5N630
T5N630
T5N630
T5N630
T5N630
T5N630
T5N630
T5N630
T5N630
T5S630
T5L630
T5N630
T5S630
T5L630
T5N630
T5H630
T5L630
T5N630
T5L630
T5L630
S6N800
S6N800
S6N800
S6N800
S6N800
S6N800
S6N800
S6S800
S6L800
S6N800
S6S800
S6L800
S6N800
S6H800
S6L800
S6N800
S6L800
S6L800
S7S1250
S7S1250/E1N1250 S7S1600/E2N1600
S7S1250/E2N1250
S7S1250/E1N1250
S7S1250/E2L1250
S7L1250/E2L1250
S7S1250/E1B1250
S7S1250/E2L1250
S7L1250/E2L1250
S7S1250/E1N1250
S7H1250/E2L1250
S7L1250
S7S1250/E2N1250
S7L1250/E2L1250
S7L1250
S7S1600/E2N1600 E2N2000
S7S1600/E2L1600
S7L1600/E2L1600
S7S1600/E2B1600
S7S1600/E2L1600
S7L1600/E2L1600
S7S1600/E2N1600
S7H1600/E2L1600
S7L1600
S7S1600/E2N1600
S7L1600/E2L1600
S7L1600
E3H2000 E3H2500
E3L2000 E3L2500 E6V3200
E3H2000
E3L2000
E2N2000
E3H2000
E6V3200
E2N2000
E3L2000
E3H2500 E3H3200
E3L2500 E6V3200 E6V4000
E3H2500 E3H3200 E4H4000
E6V3200 E6V3200 E6V4000
E3N2500
E3L2500 E6V3200 E6V4000
1SDC010035F0201
Transformer
Sr
137
uk
Trafo I r
Busbar Ib
[kVA]
1 x 63
2 x 63
1 x 100
2 x 100
1 x 125
2 x 125
1 x 160
2 x 160
1 x 200
2 x 200
1 x 250
2 x 250
1 x 315
2 x 315
1 x 400
2 x 400
1 x 500
2 x 500
1 x 630
2 x 630
3 x 630
1 x 800
2 x 800
3 x 800
1 x 1000
2 x 1000
3 x 1000
1 x 1250
2 x 1250
3 x 1250
1 x 1600
2 x 1600
3 x 1600
1 x 2000
2 x 2000
3 x 2000
1 x 2500
1 x 3125
[A]
91
91
144
144
180
180
231
231
289
289
361
361
455
455
577
577
722
722
909
909
909
1155
1155
1155
1443
1443
1443
1804
1804
1804
2309
2309
2309
2887
2887
2887
3608
4510
[A]
91
182
144
288
180
360
231
462
289
578
361
722
455
910
577
1154
722
1444
909
1818
2727
1155
2310
3465
1443
2886
4329
1804
3608
5412
2309
4618
6927
2887
5774
8661
3608
4510
138
4
4
4
4
4
4
4
4
4
4
6.25
6.25
6.25
6.25
Trafo
Feeder Ik
[kA]
2.2
2.2
3.6
3.6
4.5
4.4
5.7
5.7
7.2
7.1
8.9
8.8
11.2
11.1
14.2
14
17.7
17.5
22.3
21.8
42.8
22.6
22.1
43.4
28.1
27.4
53.5
34.9
33.8
65.6
35.7
34.6
67
44.3
42.6
81.9
54.8
67.7
ABB SACE
Circuit-breaker
T1B/T2N160
T1B/T2N160
T1B/T2N160
T1B/T2N160
T3N250
T3N250
T3N250
T3N250
T4N320
T4N320
T5N400
T5N400
T5N630
T5N630
T5N630/S6N800
T5N630/S6N800
S6N800/S7S1250
S6N800/S7S1250
S7S1250/E1B1250
S7S1250/E1B1250
S7S1250/E1N1250
S7S1250/E1B1250
S7S1250/E1B1250
S7S1250/E1N1250
S7S1600/E2B1600
S7S1600/E2B1600
S7H1600/E2N1600
E2B2000
E2B2000
E3S2000
E3N2500
E3N2500
E3S2000
E3N3200
E3N3200
E3H3200
E4S4000
E6H5000
Release
size
In=100
In=100
In=160
In=160
In=250
In=250
In=250
In=250
In=320
In=320
In=400
In=400
In=630
In=630
In=630/800
In=630/800
In=800/1000
In=800/1000
In=1000
In=1000
In=1000
In=1250
In=1250
In=1250
In=1600
In=1600
In=1600
In=2000
In=2000
In=2000
In=2500
In=2500
In=2500
In=3200
In=3200
In=3200
In=4000
In=5000
setting
0.96
0.96
0.92
0.92
0.95/0.8
0.95/0.8
0.95/0.95
0.95/0.95
0.95
0.95
0.95
0.95
0.8
0.8
0.95/0.8
0.95/0.8
0.95/0.8
0.95/0.8
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
1
1
Busbar Ik
[kA]
2.2
4.4
3.6
7.2
4.5
8.8
5.7
11.4
7.2
14.2
8.9
17.6
11.2
22.2
14.2
28
17.7
35.9
22.3
43.6
64.2
22.6
44.3
65
28.1
54.8
80.2
34.9
67.7
98.4
35.7
69.2
100.6
44.3
85.1
122.8
54.8
67.7
32 A 63 A 125 A 160 A
S250/S260
S250/S260 T1B160
S250/S260 T1B160
S250/S260 T1B160
S250/S260
T1B160
S250/S260
T1B160
S250/S260
T1B160
T1B160
S250/S260
T1B160
T1B160
T1B160
S250/S260
T1C160
T1B160
T1C160
T1B160
T1N160
T1C160
T1N160
T1C160
T2S160
T2H160
T1C160
T2S160
T2H160
T1N160
T2H160
T2L160
T1N160
T2H160
T4L250
T2N160
T2H160
T4L250
T2S160
T4L250
T4L250
T2H160
T2H160
250 A
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3S250
T4H250
T3N250
T3S250
T4H250
T3N250
T4H250
T4L250
T3N250
T4H250
T4L250
T3N250
T4H250
T4L250
T3S250
T4L250
T4V250
T4H250
T4H250
400 A
630 A
800 A
1250 A
1600 A
2000 A
2500 A
3200 A
4000 A
E2N2000
E3N2500
E2N2000
E3H2000
E3H2500
E3H3200
E3S2000
E3H2000
E3S2500
E3H2500
E3S3200
E3H3200
E4H4000
E3S2000
E3L2000
E2N2000
E3H2000
E3L2000
E2N2000
E3S2000
E3S2500
E3L2500
E3S3200
E6V3200
E4S4000
E6V4000
E3H2500
E3L2500
E3N2500
E3S2500
E3H3200
E6V3200
E3N3200
E3S3200
E4H4000
E6V4000
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5S400
T5H400
T5N400
T5S400
T5H400
T5N400
T5H400
T5L400
T5N400
T5H400
T5L400
T5N400
T5H400
T5L400
T5S400
T5L400
T5V400
T5H400
T5H400
T5N630
T5N630
T5N630
T5N630
T5N630
T5S630
T5H630
T5N630
T5S630
T5H630
T5N630
T5H400
T5L630
T5N630
T5H630
T5L630
T5N630
T5H630
T5L630
T5S630
T5L630
T5V630
T5H630
T5H630
S6N800
S6N800/E1B800
S6S800/E1N800
S7S1250/E1N1250
S6L800/E2N1250 S7L1250/E2N1250
S6N800/E1B800
S6S800/E1N800
S7S1250/E1N1250
S6L800/E2N1250 S7L1250/E2N1250
S6N800/E1B800
S7S1250/E1B1250
S6H800/E2N1250 S7H1250/E2N1250
S6L800/E3H1250 S7L1250/E3H1250
S6N800/E1B800
S7S1250/E1B1250
S6L800/E3H1250 S7L1250/E3S1250
S6L800/E3H1250 S7L1250/E3H1250
S6N800/E1B800
S7S1250/E1B1250
S6L800/E3S1250 S7L1250/E3S1250
S8V2000/E2L1250
S6S800/E1N800
S7S1250/E1N1250
S6L800/E3H1250 S7L1250/E3H1250
E2L1250
S6H800/E2N1250 S7H1250/E2N1250
S6L800/E3S1250 S7L1250/E3S1250
S7L1600/E2N1600
S7S1600/E2N1600
S7L1600/E2N1600
S7H1600/E2N1600
S7L1600/E3H1600
S7S1600/E2B1600
S7L1600/E3S1600
S7L1600/E3H1600
S7S1600/E2B1600
S7L1600/E3S1600
S8V2000/E2L1600
S7S1600/E2N1600
S7L1600/E3H1600
E2L1600
S7H1600/E2N1600
S7L1600/E3S1600
E4S4000
1SDC010036F0201
Transformer
Sr
139
uk
Trafo I r
Busbar Ib
[kVA]
1 x 63
2 x 63
1 x 100
2 x 100
1 x 125
2 x 125
1 x 160
2 x 160
1 x 200
2 x 200
1 x 250
2 x 250
1 x 315
2 x 315
1 x 400
2 x 400
1 x 500
2 x 500
1 x 630
2 x 630
3 x 630
1 x 800
2 x 800
3 x 800
1 x 1000
2 x 1000
3 x 1000
1 x 1250
2 x 1250
3 x 1250
1 x 1600
2 x 1600
3 x 1600
1 x 2000
2 x 2000
3 x 2000
1 x 2500
1 x 3125
[A]
83
83
131
131
164
164
210
210
262
262
328
328
413
413
525
525
656
656
827
827
827
1050
1050
1050
1312
1312
1312
1640
1640
1640
2099
2099
2099
2624
2624
2624
3280
4100
[A]
83
165
131
262
164
328
210
420
262
525
328
656
413
827
525
1050
656
1312
827
1653
2480
1050
2099
3149
1312
2624
3936
1640
3280
4921
2099
4199
6298
2624
5249
7873
3280
4100
140
4
4
4
4
4
4
4
4
4
4
6.25
6.25
6.25
6.25
Trafo
Feeder Ik
[kA]
2.1
2.1
3.3
3.3
4.1
4.1
5.2
5.2
6.5
6.5
8.1
8.1
10.2
10.1
12.9
12.8
16.1
15.9
20.2
19.8
38.9
20.6
20.1
39.5
25.6
24.9
48.6
31.7
30.8
59.6
32.5
31.4
60.9
40.3
38.7
74.4
49.8
61.5
ABB SACE
Circuit-breaker
T1B/T2N160
T1B/T2N160
T1B/T2N160
T1B/T2N160
T3N/T4N250
T3N/T4N250
T3N/T4N250
T3N/T4N250
T5N400
T5N400
T5N400
T5N400
T5N630
T5N630
T5N630
T5N630
S6N800
S6N800
S7S1250/E1B1250
S7S1250/E1B1250
S7S1250/E1B1250
S7S1250/E1B1250
S7S1250/E1B1250
S7S1250/E1B1250
S7S1600/E2B1600
S7S1600/E2B1600
S7H1600/E2N1600
E2B2000
E2B2000
E2N2000
E2N2500
E2N2500
E2N2500
E3N3200
E3N3200
E3S3200
E4S4000
E6H5000
Release
size
In=100
In=100
In=160
In=160
In=250
In=250
In=250
In=250
In=320
In=320
In=400
In=400
In=630
In=630
In=630
In=630
In=800
In=800
In=1000
In=1000
In=1000
In=1250
In=1250
In=1250
In=1600
In=1600
In=1600
In=2000
In=2000
In=2000
In=2500
In=2500
In=2500
In=3200
In=3200
In=3200
In=4000
In=5000
setting
0.9/0.88
0.9/0.88
0.85/0.88
0.85/0.88
0.9/0.7
0.9/0.7
0.9
0.9
0.9
0.9
0.9
0.9
0.7
0.7
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
Busbar Ik
[kA]
2.1
4.1
3.3
6.5
4.1
8.1
5.2
10.4
6.5
12.9
8.1
16.1
10.2
20.2
12.9
25.6
16.1
31.7
20.2
39.7
58.3
20.6
40.3
59.2
25.6
49.8
72.9
31.7
61.5
89.5
32.5
62.9
91.4
40.3
77.4
111.7
49.8
61.5
32 A 63 A 125 A 160 A
S250/S260
S250/S260 T1B160
S250/S260
T1B160
S250/S260 T1B160
T1B160
S250/S260
T1B160
T1C160
T1B160
T1C160
T1B160
T1N160
T1C160
T1N160
T1C160
T2N160
T1N160
T2S160
T1N160
T2S160
T2L160
T1N160
T2S160
T2L160
T2N160
T2H160
T2L160
T2S160
T2L160
T4L250
T2S160
T2L160
T4L250
T2S160
S4L160
T4V250
T2H160
T2L160
250 A
400 A
630 A
800 A
1250 A
1600 A
2000 A
S7L1600/E2N1600
E2N2000
S7H1600/E2B1600
S7L1600/E2N1600
E2N2000
S7H1600/E2N1600
S7L1600/E3S1600
E2N2000
E3S2000
S7L1600/E2N1600
S8V2000/E2L1600
S7S1600/E2B1600
S7L1600/E2N1600
S8V2000/E2L1600
S7H1600/E2B1600
S7L1600/E3H1600
E2N2000
E3H2000
E2N2000
E3H2000
E2B2000
E3H2000
E6V3200
E2N2000
E2N2000
2500 A
3200 A
4000 A
E3N2500
E3N3200
E4S4000
E3S2500
E3S3200
E3N2500
E3H2500
E3H3200
E4H4000
E3N2500
E3H2500
E3N3200
E3H3200
E4H4000
E3H2500
E3H3200
E3N2500
E3N2500
E3N3200
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3N250
T3S250
T3N250
T3S250
T3N250
T3S250
T4H250
T3N250
T4H250
T4H250
T3S250
T4H250
T4L250
T3S250
T4H250
T4L250
T3S250
T4H250
T4L250
T4H250
T4L250
T4V250
T4H250
T4H250
T5N400
T5N400
T5N400
T5N400
T5N400
T5N400
T5S400
T5N400
T5S400
T5H400
T5N400
T5H400
T5H400
T5N400
T5H400
T5L400
T5S400
T5H400
T5L400
T5S400
T5H400
T5L400
T5H400
T5L400
T5V400
T5H400
T5H400
T5N630
T5N630
T5S630
T5N630
T5S630
T5H630
T5N630
T5H630
T5H630
T5N630
T5H630
T5L630
T5S630
T5H630
T5L630
T5S630
T5H630
T5L630
T5H630
T5L630
T5V630
T5H630
T5H630
S6S800
S6S800/E1B800
S7S1250/E1B1250
S6L800/E2N1250
S7L1250/E2N1250
S6N800/E1B800
S6S800/E1B800
S7H1250/E1B1250
S6L800/E2N1250
S7L1250/E2N1250
S6N800/E1B800
S6L800/E2N1250
S7H1250/E1N1250
S6L800/E3S1250
S7L1250/E3S1250
S6S800/E1B800
S7S1250/E1B1250
S6L800/E2N1250
S7L1250/E2N1250
S8V2000/E2L1250
S6S800/E1B800
S7S1250/E1B1250
S6L800/E2N1250
S7L1250/E2N1250
S8V2000/E2L1250
S6S800/E1B800
S7H1250/E1N1250
S6L800/E3H1250
S7L1250/E3H1250
S6L800/E2N1250
S6L800/E2N1250
S7H1250/E1N1250
S7L1250/E2N1250
S7H1600/E2N1600
S7L1600/E2N1600
E4H4000
E6V4000
1SDC010037F0201
Transformer
Sr
141
uk
Trafo I r
Busbar Ib
[kVA]
1 x 63
2 x 63
1 x 100
2 x 100
1 x 125
2 x 125
1 x 160
2 x 160
1 x 200
2 x 200
1 x 250
2 x 250
1 x 315
2 x 315
1 x 400
2 x 400
1 x 500
2 x 500
1 x 630
2 x 630
3 x 630
1 x 800
2 x 800
3 x 800
1 x 1000
2 x 1000
3 x 1000
1 x 1250
2 x 1250
3 x 1250
1 x 1600
2 x 1600
3 x 1600
1 x 2000
2 x 2000
3 x 2000
1 x 2500
1 x 3125
[A]
53
53
84
84
105
105
134
134
167
167
209
209
264
264
335
335
418
418
527
527
527
669
669
669
837
837
837
1046
1046
1046
1339
1339
1339
1673
1673
1673
2092
2615
[A]
53
105
84
167
105
209
134
268
167
335
209
418
264
527
335
669
418
837
527
1054
1581
669
1339
2008
837
1673
2510
1046
2092
3138
1339
2678
4016
1673
3347
5020
2092
2615
142
4
4
4
4
4
4
4
4
4
4
6.25
6.25
6.25
6.25
Trafo
Feeder Ik
[kA]
1.3
1.3
2.1
2.1
2.6
2.6
3.3
3.3
4.2
4.1
5.2
5.1
6.5
6.5
8.3
8.2
10.3
10.1
12.9
12.6
24.8
13.1
12.8
25.2
16.3
15.9
31.0
20.2
19.6
38.0
20.7
20.1
38.9
25.7
24.7
47.5
31.8
39.2
ABB SACE
Circuit-breaker
T1B/T2N160
T1B/T2N160
T1B/T2N160
T1B/T2N160
T1B/T2N160
T1B/T2N160
T1C/T2N160
T1C/T2N160
T3N250/T4N250
T3N250/T4N250
T3S250/T4N250
T3S250/T4N250
T4N320
T4N320
T5N400
T5N400
T5N630
T5N630
T5N630
T5N630
T5S630
S6N800
S6N800
S6L800
S7S1250/E1B1250
S7S1250/E1B1250
S7L1250/E1B1250
S7H1250/E1B1250
S7S1250/E1B1250
E2B1250
E2B1600
E2B1600
E2B1600
E2B2000
E2B2000
E2B2000
E3N2500
E3N3200
size
In=63
In=63
In=100
In=100
In=160
In=160
In=160
In=160
In=250
In=250
In=250
In=250
In=320
In=320
In=400
In=400
In=630
In=630
In=630
In=630
In=630
In=800
In=800
In=800
In=1000
In=1000
In=1000
In=1250
In=1250
In=1600
In=1600
In=1600
In=1600
In=2000
In=2000
In=2000
In=2500
In=3200
Busbar Ik
setting
0.9/0.88
0.9/0.88
0.9/0.92
0.9/0.92
0.9/0.72
0.9/0.72
0.9/0.88
0.9/0.88
0.9/0.8
0.9/0.8
0.9
0.9
0.9
0.9
0.9
0.9
0.7
0.7
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.7
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
[kA]
1.3
2.6
2.1
4.2
2.6
5.2
3.3
6.6
4.2
8.3
5.2
10.3
6.5
12.9
8.3
16.3
10.3
20.2
12.9
25.3
37.2
13.1
25.7
37.7
16.3
31.8
46.5
20.2
39.2
57.1
20.7
40.1
58.3
25.7
49.3
71.2
31.8
39.2
32 A
63 A 125 A 160 A
T1B160
T1B160
T1B160
T1N160
T1B160
T1N160
T1C160
T2S160
T1N160
T2L160
T1N160
T4N250
T2S160
T4N250
T2L160
T4N250
T4N250
T4S250
T4N250
T4H250
T4H250
T4N250
T4H250
T4H250
T4N250
T4H250
T4L250
T4S250
T4H250
T4L250
T4S250
T4L250
T4L250
T4H250
T4L250
T4V250
T4H250
T4H250
250 A
400 A
630 A
800 A
1250 A
1600 A
2000 A
2500 A
3200 A
4000 A
T4N250
T4N250
T4N250
T4N250
T4N250
T4N250
T4S250
T4N250
T4H250
T4H250
T4N250
T4H250
T4H250
T4N250
T4H250
T4L250
T4S250
T4H250
T4L250
T4S250
T4L250
T4L250
T4H250
T4L250
T4V250
T4H250
T4H250
T5N400
T5N400
T5S400
T5N400
T5H400
T5H400
T5N400
T5H400
T5H400
T5N400
T5H400
T5L400
T5S400
T5H400
T5L400
T5S400
T5L400
T5L400
T5H400
T5L400
T5V400
T5H400
T5H400
T5S630
T5H630
T5H630
T5H630
T5H630
T5N630
T5H630
T5L630
T5S630
T5H630
T5L630
T5S630
T5L630
T5L630
T5H630
T5L630
T5V630
T5H630
T5H630
E2B1600
S6L800
E2B1600
S7L1250/E1B800 S7L1250/E1B1250
S8V2000/E2N1250
S8V2000/E2N1600
S6S800/E1B800
S8H2000/E2B1250
S8H2000/E2B1600
E3N2500
S6S800/E1B800
S8V2000/E2B1250
S8V2000/E2B1600
E3N2500
S6L800/E1B800 S7L1250/E1B1250
S8V2000/E2N1250
S8V2000/E2N1600
E2L1250
E2L1600
S7L1250/E1B800 S7L1250/E1B1250 S7L1600/E2B1600
S8H2000/E2B1250
S8H2000/E2B1600
E2N2000
E2B2000
E3N3200
E2N2000 E3N2500
E3S2000 E3S2500 E3S3200 E4S4000
E2B2000
1SDC010037F0201
Transformer
Sr
143
NOTE
The tables refer to the previously specified conditions; the information for the
selection of circuit-breakers is supplied only with regard to the current in use
and the prospective short-circuit current. For a correct selection, other factors
such as selectivity, back-up protection, the decision to use limiting circuitbreakers etc. must also be considered. Therefore, it is essential that the design
engineers carry out precise checks.
It must also be noted that the short-circuit currents given are determined using
the hypothesis of 750 MVA power upstream of the transformers, disregarding
the impedances of the busbars or the connections to the circuit-breakers.
Example:
Supposing the need to size breakers A1/A2/A3, on the LV side of the three
transformers of 630 kVA 20/0.4 kV with uk% equal to 4% and outgoing feeder
circuit-breakers B1/B2/B3 of 63-400-800 A:
A2
B1
63 A
144
B2
400 A
A3
B3
800 A
1SDC010026F0001
A1
Busbar Ik (64.2 kA) is the short-circuit current due to the contribution of all
three transformers;
corresponding to 63 A, read circuit-breaker B1 Tmax T2H160;
corresponding to 400 A, read circuit-breaker B2 Tmax T5H400;
corresponding to 800 A, read circuit-breaker B3 Isomax S6L800 or E2N1250.
The choice made does not take into account discrimination/back-up
requirements. Refer to the relevant chapters for selections appropriate to the
various cases.
145
IR
I
S
IQ
Power factor (cos) is defined as the ratio between the active component IR
and the total value of the current l; is the phase shifting between the voltage
U and the current l.
It results:
cos
IR P
(1)
=
S
I
The reactive demand factor (tan) is the relationship between the reactive power
and the active power:
tan =
146
Q
(2)
P
cos
power factor
0.10.15
0.70.85
0.15
tan
reactive demand factor
9.96.6
1.00.62
6.6
0.350.6
0.70.8
0.40.6
0.750.9
2.71.3
1.00.75
2.31.3
0.90.5
0.9
0.40.6
0.5
0.650.75
0.60.95
0.40.75
0.950.97
1
0.5
2.31.3
1.7
1.20.9
1.30.3
2.30.9
0.330.25
0
The power factor correction is the action increasing the power factor in a specific
section of the installation by locally supplying the necessary reactive power, so
as to reduce the current value to the equivalent of the power required, and
therefore the total power absorbed from the upstream side. Thus, both the line
as well as the supply generator can be sized for a lower apparent power value
required by the load.
In detail, as shown by Figure 1 and Figure 2, increasing the power factor of the
load:
- decreases the relative voltage drop urp per unit of active power transmitted;
- increases the transmittable active power and decreases the losses, the other
dimensioning parameters remaining equal.
147
1
0.50
1SDC010039F0201
Qc = Q2 - Q1 = P ( tan
where:
P
Q1,1
Q2,2
Qc
- tan 2 ) (3)
0.6
0.7
0.8
0.9
P Q2
S2
100
S2
Q1
Qc
S1
0.80
0.90
1.00
P Q1 S1
Motor
1SDC010041F0201
Qc
10
1
0.70
148
Q2
P
1SDC010040F0201
149
Example
Q
K c = c = tan
P
- tan
Supposing the need to change from 0.8 to 0.93 the power factor of a threephase installation (Ur= 400 V) which absorbs an average power of 300 kW.
From Table 2, at the intersection of the column corresponding to the final power
factor (0.93), and the row corresponding to the starting power factor (0.8), the
value of Kc (0.355) can be read. The reactive power Qc which must be generated
locally shall be:
(4)
for different values of the power factor before and after the correction.
Table 2: Factor Kc
Kc
cos1
0.60
0.61
0.62
0.63
0.64
0.65
0.66
0.67
0.68
0.69
0.70
0.71
0.72
0.73
0.74
0.75
0.76
0.77
0.78
0.79
0.80
0.81
0.82
0.83
0.84
0.85
0.86
0.87
0.88
0.89
0.90
150
0.80
0.583
0.549
0.515
0.483
0.451
0.419
0.388
0.358
0.328
0.299
0.270
0.242
0.214
0.186
0.159
0.132
0.105
0.079
0.052
0.026
0.85
0.714
0.679
0.646
0.613
0.581
0.549
0.519
0.488
0.459
0.429
0.400
0.372
0.344
0.316
0.289
0.262
0.235
0.209
0.183
0.156
0.130
0.104
0.078
0.052
0.026
0.90
0.849
0.815
0.781
0.748
0.716
0.685
0.654
0.624
0.594
0.565
0.536
0.508
0.480
0.452
0.425
0.398
0.371
0.344
0.318
0.292
0.266
0.240
0.214
0.188
0.162
0.135
0.109
0.082
0.055
0.028
0.91
0.878
0.843
0.810
0.777
0.745
0.714
0.683
0.652
0.623
0.593
0.565
0.536
0.508
0.481
0.453
0.426
0.400
0.373
0.347
0.320
0.294
0.268
0.242
0.216
0.190
0.164
0.138
0.111
0.084
0.057
0.029
0.92
0.907
0.873
0.839
0.807
0.775
0.743
0.712
0.682
0.652
0.623
0.594
0.566
0.538
0.510
0.483
0.456
0.429
0.403
0.376
0.350
0.324
0.298
0.272
0.246
0.220
0.194
0.167
0.141
0.114
0.086
0.058
0.93
0.938
0.904
0.870
0.837
0.805
0.774
0.743
0.713
0.683
0.654
0.625
0.597
0.569
0.541
0.514
0.487
0.460
0.433
0.407
0.381
0.355
0.329
0.303
0.277
0.251
0.225
0.198
0.172
0.145
0.117
0.089
cos2
0.94 0.95
0.970 1.005
0.936 0.970
0.903 0.937
0.870 0.904
0.838 0.872
0.806 0.840
0.775 0.810
0.745 0.779
0.715 0.750
0.686 0.720
0.657 0.692
0.629 0.663
0.601 0.635
0.573 0.608
0.546 0.580
0.519 0.553
0.492 0.526
0.466 0.500
0.439 0.474
0.413 0.447
0.387 0.421
0.361 0.395
0.335 0.369
0.309 0.343
0.283 0.317
0.257 0.291
0.230 0.265
0.204 0.238
0.177 0.211
0.149 0.184
0.121 0.156
0.96
1.042
1.007
0.974
0.941
0.909
0.877
0.847
0.816
0.787
0.757
0.729
0.700
0.672
0.645
0.617
0.590
0.563
0.537
0.511
0.484
0.458
0.432
0.406
0.380
0.354
0.328
0.302
0.275
0.248
0.221
0.193
0.97
1.083
1.048
1.015
0.982
0.950
0.919
0.888
0.857
0.828
0.798
0.770
0.741
0.713
0.686
0.658
0.631
0.605
0.578
0.552
0.525
0.499
0.473
0.447
0.421
0.395
0.369
0.343
0.316
0.289
0.262
0.234
0.98
1.130
1.096
1.062
1.030
0.998
0.966
0.935
0.905
0.875
0.846
0.817
0.789
0.761
0.733
0.706
0.679
0.652
0.626
0.599
0.573
0.547
0.521
0.495
0.469
0.443
0.417
0.390
0.364
0.337
0.309
0.281
0.99
1.191
1.157
1.123
1.090
1.058
1.027
0.996
0.966
0.936
0.907
0.878
0.849
0.821
0.794
0.766
0.739
0.713
0.686
0.660
0.634
0.608
0.581
0.556
0.530
0.503
0.477
0.451
0.424
0.397
0.370
0.342
1
1.333
1.299
1.265
1.233
1.201
1.169
1.138
1.108
1.078
1.049
1.020
0.992
0.964
0.936
0.909
0.882
0.855
0.829
0.802
0.776
0.750
0.724
0.698
0.672
0.646
0.620
0.593
0.567
0.540
0.512
0.484
151
From this data it is possible to find the size characteristics of the capacitors by
using the following formulae (5):
Starter
Starter
Qc
2
2 fr U r
Irc = 2 f r C U r
I l = I rc
Line current
C=
Qc
2
2 f r U r
Irc = 2 f r C U r / 3
I l = Irc
Three-phase
delta-connection
C=
Starter
Qc
2
2 f r U r 3
I rc = 2 f r C U r
I l = Irc 3
With three-phase systems, for the same reactive power, the star-connection
requires a capacity 3 times larger and subjects the capacitors to a voltage and
a current times less than the analogous delta-connection.
Capacitors are generally supplied with connected discharge resistance,
calculated so as to reduce the residual voltage at the terminals to 75 V in 3
minutes, as stated in the reference Standard.
Diagram 2
Diagram 1
1SDC010028F0001
C=
Three-phase
star-connection
1SDC010005F0901
Single-phase
connection
Diagram 3
In the case of direct connection (diagrams 1 and 2) there is a risk that after
disconnection of the supply, the motor will continue to rotate (residual kinetic
energy) and self-excite with the reactive energy supplied by the capacitor bank,
acting as an asynchronous generator. In this case, the voltage is maintained on
the load side of the switching and control device, with the risk of dangerous
overvoltages of up to twice the rated voltage value.
However, in the case of diagram 3, to avoid the risk detailed above, the normal
procedure is to connect the PFC bank to the motor only when it is running, and
to disconnect it before the disconnection of the motor supply.
As a general rule, for a motor with power Pr, it is advisable to use a PFC with
reactive power Qc below 90% of the reactive power absorbed by the no-load
motor Q0, at rated voltage Ur, to avoid a leading power factor.
Considering that under no-load conditions, the current absorbed I0 [A] is solely
reactive, if the voltage is expressed in volts, it results:
Qc = 0.9 Q0 = 0.9
3 U r I 0
[kvar] (6)
1000
153
Table 3 shows the values of reactive power for power factor correction of some
ABB motors, according to the power and the number of poles.
Table 3: Reactive power for power factor motor correction
Pr
[kW]
154
Qc
[kvar]
Before PFC
cosr
Ir [A]
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
315
400V / 50 Hz / 2 poles
2.5
0.89
2.5
0.88
5
0.9
5
0.91
5
0.89
10
0.88
10
0.89
12.5
0.88
15
0.89
15
0.88
15
0.9
20
0.86
30
0.88
30
0.89
30
0.9
40
0.92
50
0.92
/ 3000 r/min
13.9
20
26.5
32
38.5
53
64
79
95
131
152
194
228
269
334
410
510
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
315
400V / 50 Hz / 4 poles
2.5
0.86
5
0.81
5
0.84
7.5
0.84
10
0.83
15
0.83
15
0.84
20
0.83
20
0.86
20
0.86
20
0.87
30
0.87
40
0.87
40
0.86
50
0.86
50
0.87
60
0.87
/ 1500 r/min
14.2
21.5
28.5
35
41
56
68
83
98
135
158
192
232
282
351
430
545
After PFC
cos2
I2 [A]
0.98
0.95
0.98
0.98
0.96
0.97
0.97
0.96
0.97
0.94
0.95
0.92
0.95
0.95
0.95
0.96
0.96
0.96
0.96
0.95
0.96
0.97
0.98
0.97
0.97
0.97
0.95
0.94
0.96
0.96
0.94
0.94
0.94
0.93
12.7
18.6
24.2
29.7
35.8
47.9
58.8
72.2
87.3
122.2
143.9
181.0
210.9
252.2
317.5
391.0
486.3
12.7
18.2
25.3
30.5
35.1
47.5
59.1
71.1
86.9
122.8
145.9
174.8
209.6
257.4
320.2
399.4
507.9
Pr
[kW]
Qc
[kvar]
Before PFC
cosr
Ir [A]
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
315
5
5
7.5
7.5
10
10
12.5
15
20
25
30
35
45
50
60
70
75
0.98
0.93
0.94
0.94
0.96
0.94
0.94
0.95
0.96
0.93
0.95
0.94
0.95
0.95
0.95
0.94
0.92
12.4
19.3
25.7
30.9
36.5
49.4
60.8
72.6
88.7
123.9
144.2
178.8
210.8
249.6
318.0
404.2
514.4
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
5
7.5
7.5
7.5
10
12.5
15
20
20
30
30
35
50
400V / 50 Hz / 8 poles
0.7
0.76
0.82
0.79
0.77
0.79
0.78
0.78
0.81
0.82
0.82
0.83
0.8
0.91
0.97
0.97
0.93
0.92
0.93
0.92
0.93
0.93
0.95
0.93
0.94
0.93
13.9
18.4
24.5
31.5
37.5
50.0
62.8
75.4
90.2
120.6
146.6
178.8
214.6
/ 750 r/min
18.1
23.5
29
37
45
59
74
90
104
140
167
202
250
After PFC
cos2
I2 [A]
155
Example
Table 4 shows the reactive power of the capacitor bank Qc [kvar] to be connected
on the secondary side of an ABB transformer, according to the different minimum
estimated load levels.
i %
u %
i %
2
2
2
2 u %
Qc = 0 Sr Pfe + K L k Sr Pcu 0 Sr + K L k Sr [kvar] (7)
100
100
100
100
where KL is the load factor, defined as the relationship between the minimum
reference load and the rated power of the transformer.
Pfe
[kW]
Qc [kvar]
Pcu
[kW]
Sr
[kVA]
uk%
[%]
io%
[%]
50
100
160
200
250
315
400
500
630
800
1000
1250
1600
2000
2500
3150
4000
4
4
4
4
4
4
4
4
4
6
6
6
6
6
6
7
7
2.9
2.5
2.3
2.2
2.1
2
1.9
1.9
1.8
1.7
1.6
1.6
1.5
1.2
1.1
1.1
1.4
1.5
2.7
4
4.8
5.8
7
8.5
11
13
16
20
24
30
31
37
48
73
1.8
3.3
5
6.1
7.4
9.1
11
14
17
25
31
38
47
53
64
89
125
2.3
4.3
6.8
8.3
10
13
16
20
25
40
49
61
77
90
111
157
212
2.9
5.7
9.2
11
14
18
22
28
35
60
74
93
118
142
175
252
333
100
160
200
250
315
400
500
630
800
1000
1250
1600
2000
2500
3150
6
6
6
6
6
6
6
6
6
6
6
6
6
6
8
3.7
5.5
6.6
8.1
9.9
12
14
17
20
25
29
38
45
54
81
5.5
8.4
10
13
16
19
23
29
35
43
52
67
82
101
159
8
12
15
19
24
29
36
45
56
69
85
109
134
166
269
load factor KL
0.25
0.5
0.75
Example
Supposing the need for PFC of a 630 kVA oil-distribution transformer which
supplies a load which is less than 60% of its rated power.
From the data on the transformer nameplate:
i0% = 1.8%
uk% = 4%
Pcu = 8.9 kW
Pfe = 1.2 kW
The PFC power of the capacitor bank connected to the transformer is:
i % 2 2 u %
4%
1.8% 2
2
Qc = 0 Sr Pfe + K L k Sr Pcu =
630 1.2 + 0.62 630 8.92 =19.8 kvar
100
100
100
100
while, when using the simplified formula, the result is:
Example
i %
1.8%
4%
2 u %
630 + 0.62
630 = 20.4 kvar
Qc = 0 Sr + K L k Sr =
100
100
100
100
156
For a 630 kVA oil-distribution transformer with a load factor of 0.5, the necessary
PFC power is 17 kvar.
157
PFC in groups
Centralized PFC normally uses automatic units with capacitor banks divided
into several steps, directly installed in the main distribution switchboards; the
use of a permanently connected capacitor bank is only possible if the absorption
of reactive energy is fairly regular throughout the day.
The main disadvantage of centralized PFC is that the distribution lines of the
installation, downstream of the PFC device, must be dimensioned taking into
account the full reactive power required by the loads.
1SDC010029F0001
This consists of local power factor correction of groups of loads with similar
functioning characteristics by installing a dedicated capacitor bank.
This method achieves a compromise between the economical solution and the
correct operation of the installation, since only the line downstream of the
installation point of the capacitor bank is not correctly exploited.
Centralized PFC
C
LV
Feeders
The daily load profile is of fundamental importance for the choice of the most
suitable type of power factor correction.
In installations, in which not all loads function simultaneously and/or in which
some loads are connected for only a few hours a day, the solution of using
single PFC becomes unsuitable as many of the capacitors installed could stay
idle for long periods.
In the case of installations with many loads occasionally functioning, thus having
a high installed power and a quite low average power absorption by the loads
which function simultaneously, the use of a single PFC system at the installation
origin ensures a remarkable decrease in the total power of the capacitors to be
installed.
158
1SDC010030F0001
Qc
1.5 I rc (8)
3 U r
Therefore:
- the rated current of the circuit-breaker shall be greater than 1.5Irc;
- the overload protection setting shall be equal to 1.5Irc.
The connection of a capacitor bank, similar to a closing operation under shortcircuit conditions, associated with transient currents with high frequency (115
kHz), of short duration (13 ms), with high peak (25200 Irc).
Therefore:
- the circuit-breaker shall have an adequate making capacity;
- the setting of the instantaneous short-circuit protection must not cause
unwanted trips.
159
InCB
Irc
[A]
1250
1250
1600
2000
1250
1600
2000
2500
3200
3200
3200
[A]
834
834
1067
1334
834
1067
1334
1667
2134
2134
2134
QC [kvar]
400 V
578
578
739
924
578
739
924
1155
1478
1478
1478
440 V
636
636
813
1017
636
813
1017
1270
1626
1626
1626
500 V
722
722
924
1155
722
924
1155
1444
1848
1848
1848
690 V
997
997
1275
1594
997
1275
1594
1992
2550
2550
2550
Nmech
fmech
25000
25000
25000
25000
20000
20000
20000
20000
20000
15000
12000
[op/h]
60
60
60
60
60
60
60
60
60
60
60
Nel
fel
10000
15000
12000
10000
12000
10000
9000
8000
6000
7000
5000
[op/h]
30
30
30
30
20
20
20
20
20
10
10
fmech
CB Type
[A]
[A]
400 V 440 V 500 V 690 V
T1 B-C-N 160
160
107
74
81
92
127 25000
T2 N-S-H-L 160*
160
107
74
81
92
127 25000
T3 N-S 250*
250
167
115
127
144
199 25000
T4 N-S-H-L-V 250
250
167
115
127
144
199 20000
T4 N-S-H-L-V 320
320
213
147
162
184
254 20000
T5 N-S-H-L-V 400
400
267
185
203
231
319 20000
T5 N-S-H-L-V 630
630
420
291
320
364
502 20000
* for plug-in version reduce the maximum power of the capacitor bank by 10%
InCB
Irc
QC [kvar]
[op/h]
240
240
240
240
240
120
120
Nel
fel
8000
8000
8000
8000
6000
7000
5000
[op/h]
120
120
120
120
120
60
60
160
InCB
Irc
800
1250
1600
2000
2500
3200
533
833
1067
1333
1667
2133
QC [kvar]
369
577
739
924
1155
1478
406
635
813
1016
1270
1626
462
722
924
1155
1443
1847
637
996
1275
1593
1992
2550
Nmech
fmech
Nel
fel
20000
10000
10000
10000
10000
10000
120
120
120
120
120
120
5000
7000
5000
3000
2500
1500
60
20
20
20
20
10
161
AC-4.1
AC-4.2
AC-4.3
1.000
500
AC-1
AC-2
AC-3
AC-4
200
100
50
20
10
0,1
Zone
designation
AC-1
AC-2
The Standard IEC 60479-1 Effects of current on human being and livestock
is a guide about the effects of current passing through the human body to
be used for the definition of electrical safety requirements. This Standard shows,
on a time-current diagram, four zones to which the physiological effects of
alternating current (15 100 Hz) passing through the human body have been
related.
c2 c3
2.000
- breathing arrest: if the current flows through the muscles controlling the
lungs, the involuntary contraction of these muscles alters the normal respiratory
process and the subject may die due to suffocation or suffer the consequences
of traumas caused by asphyxia;
- burns: they are due to the heating deriving, by Joule effect, from the current
passing through the human body.
c1
5.000
1SDC010042F0201
ms 10.000
Danger to persons due to contact with live parts is caused by the flow of the
current through the human body. The effects are:
AC-3
0,2
Zone
limits
Up to 0.5 mA
line a
0.5 mA
up to
line b*
Line b
up to
curve c1
AC-4
Above
curve c1
AC-4.1
AC-4.2
AC-4.3
c1 - c2
c2 - c3
Beyond
curve c3
0,5
10 20
50 100 200
Body current IB
Physiological effects
Usually no reaction.
Usually no harmful physiological effects.
* For durations of current-flow below 10 ms, the limit for the body current for line b
remains constant at a value of 200 mA.
162
163
The Standard IEC 60479-1 has adopted precautionary values for the impedance
reported in the figure so as to get the time-voltage safety curve (Figure 2) related
to the total touch voltage UT (i.e. the voltage which, due to an insulation failure,
is present between a conductive part and a point of the ground sufficiently far,
with zero potential).
This represents the maximum no-load touch voltage value; thus, the most
unfavorable condition is taken into consideration for safetys sake.
The first letter represents the relationship of the power system to earth:
- T: direct connection of one point to earth, in alternating current systems,
generally the neutral point;
- I: all live parts isolated from earth, or one point, in alternating current systems,
generally the neutral point, connected to earth through an impedance.
2
t [s] 10
The second letter represents the relationship of the exposed conductive parts
of the installation to earth:
- T: direct electrical connection of the exposed conductive parts to earth;
- N: direct electrical connection of the exposed conductive parts to the earthed
point of the power system.
10
1SDC010031F0001
10
10
10
PE
10
UT [V]
TN System
From this safety curve it results that for all voltage values below 50 V, the tolerance
time is indefinite; at 50 V the tolerance time is 5 s. The curve shown in the figure
refers to an ordinary location; in particular locations, the touch resistance of the
human body towards earth changes and consequently the tolerable voltage
values for an indefinite time shall be lower than 25 V.
Therefore, if the protection against indirect contact is obtained through the
disconnection of the circuit, it is necessary to ensure that such breaking is
carried out in compliance with the safety curve for any distribution system.
164
L1
L2
L3
PEN
(TN-C)
(TN-S)
N
PE
1SDC010033F0001
10-2
1SDC010032F0001
L1
L2
L3
N
-1
165
IT System
In TN systems, the fault current flows towards the power supply neutral point
through a solid metallic connection, practically without involving the earth
electrode (Figure 2).
Figure 2: Earth fault in TN systems
PE
1SDC010034F0001
L1
L2
L3
Ik
L1
L2
L3
PEN
Ik
(TN-C)
PE N
(TN-S)
1SDC010036F0001
In TT systems, the neutral conductor and the exposed conductive parts are
connected to earth electrodes electrically independent; the fault current flows
towards the power supply neutral point through earth (Fig. 1):
Figure 1: Earth fault in TT systems
Ik
L1
L2
L3
N
RA
Ik
1SDC010035F0001
RB
IT systems have no live parts directly connected to earth, but they can be
earthed through a sufficiently high impedance. Exposed conductive parts shall
be earthed individually, in groups or collectively to an independent earthing
electrode.
The earth fault current flows towards the power supply neutral point through
the earthing electrode and the line conductor capacitance (Figure 3).
Ik
These distribution systems are used for particular plants, where the continuity
of supply is a fundamental requirement, where the absence of the supply can
cause hazards to people or considerable economical losses, or where a low
value of a first earth fault is required. In these cases, an insulation monitoring
device shall be provided for optical or acoustic signalling of possible earth
faults, or failure of the supplied equipment.
167
168
169
FELV circuits are used when for functional reasons the requirements for SELV
or PELV circuits cannot be fulfilled; they require compliance with the following rules:
a) protection against direct contact shall be provided by either:
- barriers or enclosures with degree of protection in accordance with what
stated above (measures of protection against direct contact);
- insulation corresponding to the minimum test voltage specified for the
primary circuit. If this test is not passed, the insulation of accessible nonconductive parts of the equipment shall be reinforced during erection so
that it can withstand a test voltage of 1500 V ac r.m.s. for 1 min.;
b) protection against indirect contact shall be provided by:
- connection of the exposed conductive parts of the equipment of the FELV
circuit to the protective conductor of the primary circuit, provided that the
latter is subject to one of the measures of protection against direct contact;
- connection of a live conductor of the FELV circuit to the protective
conductor of the primary circuit provided that an automatic disconnection
of the supply is applied as measure of protection;
c) plugs of FELV systems shall not be able to enter socket-outlets of other
voltage systems, and plugs of other voltage systems shall not be able to
enter socket-outlets of FELV systems.
Figure 1 shows the main features of SELV, PELV and FELV systems.
5.4 TT System
An earth fault in a TT system involves the circuit represented in Figure 1:
RB
1SDC010035F0001
L1
L2
L3
N
RA
Ik
The fault current involves the secondary winding of the transformer, the phase
conductor, the fault resistance, the protective conductor and the earth electrode
resistance (plant earthing system (RA) and earthing system which the neutral is
connected to (RB)).
According to IEC 60364-4 requirements, the protective devices must be coordinated with the earthing system in order to rapidly disconnect the supply, if
the touch voltage reaches harmful values for the human body.
Assuming 50 V (25 V for particular locations) as limit voltage value, the condition
to be fulfilled in order to limit the touch voltage on the exposed conductive
parts under this limit value is:
no safety source,
connection to earth
is admissible
L1
L2
L3
N
PE
PE
safety isolating
transformer
or equivalent
source,
no earthing
PE
SELV
PELV
Rt
FELV
PELV circuit
E
PE
FELV circuit
1SDC010043F0201
Class II
equipment
50
Ia
or
Rt
50
I n
where:
Rt is the total resistance, equal to the sum of the earth electrode (RA)
and the protective conductor for the exposed conductive parts [];
Ia is the current causing the automatic operation within 5 s of the
overcurrent protective device, read from the tripping curve of the
device [A];
In is the rated residual operating current, within one second, of the
circuit-breaker [A].
170
171
5.4 TT System
5.4 TT System
From the above, it is clear that Rt value is considerably different when using
automatic circuit-breakers instead of residual current devices.
In fact, with the former, it is necessary to obtain very low earth resistance values
(usually less than 1 ) since the 5 s tripping current is generally high, whereas,
with the latter, it is possible to realize earthing systems with resistance value of
thousands of ohms, which are easier to be carried out.
Table 1 reports the maximum earth resistance values which can be obtained
using residual current devices, with reference to an ordinary location (50 V):
104 s
103 s
102 s
Example:
Assuming to provide protection by using an automatic circuit-breaker Tmax
T1B160 In125, the trip current value in less than 5 s, read from the tripping
characteristic curve, is about 750 A, when starting from cold conditions (the
worst case for thermomagnetic releases).
5s
1s
10-1 s
1SDC010038F0001
In
[A]
0.01
0.03
0.1
0.3
0.5
3
10
30
10-2 s
750 A
0.1kA
1kA
10kA
So:
Rt
50
= 0.06
750
Rt
50
= 1666.6
0.03
172
173
5.5 TN System
5.5 TN System
An earth fault in a TN system involves the circuit represented in Figure 1:
The use of residual current devices improves the conditions for protection in
particular when the fault impedance doesnt have a low value, thus limiting the
short-circuit current; this current can persist for quite long time causing
overheating of the conductors and fire risks.
Ik
Ik
PE N
Finally, it is important to highlight the fact that the residual current devices cannot
be used in TN-C system, since the neutral and protective functions are provided
by a unique conductor: this configuration prevents the residual current device
from working.
(TN-S)
The fault loop does not affect the earthing system and is basically formed by
the connection in series of the phase conductor and of the protective conductor.
To provide a protection with automatic disconnection of the circuit, according
to IEC 60364-4 prescriptions, the following condition shall be fulfilled:
Z s . I a U0
Example:
In the plant represented in Figure 2, the earth fault current is:
IkLG = 3 kA
The rated voltage to earth is 230 V, therefore, according to Table 1, it shall be
verified that:
I a ( 0.4s)
U0
= I kLG = 3 kA
Zs
Figure 2
where:
Zs is the impedance of the fault loop comprising the source, the live
conductor up to the point of the fault and the protective conductor
between the point of the fault and the source [];
U0 is the nominal ac r.m.s. voltage to earth [V];
Ia is the current causing the automatic operation of the disconnecting
protective device within the time stated in Table 1, as a function of
the rated voltage U0 or, for distribution circuits, a conventional
disconnecting time not exceeding 5 s is permitted [A]; if the protection
is provided by means of a residual current device, Ia is the rated
residual operating current In.
-QF1
T1B 160 In125
-WC1
3x(1x50)+1x(1x25)+1G25
PVC Cu
dV = 0.38%
Iz = 134.0 A
L = 20 m
-B1
IkLG = 3.0 kA
174
-U1
Ur = 400 V
LLLN / TN-S
L
ABB SACE - Electrical devices
1SDC010039F0001
(TN-C)
1SDC010036F0001
L1
L2
L3
PEN
Sr = 70.00 kVA
cos = 0.90
175
5.5 TN System
From the tripping curve (Figure 3), it is clear that the circuit-breaker trips in 0.4 s
for a current value lower than 950 A. As a consequence, the protection against
indirect contact is provided by the same circuit-breaker which protects the
cable against short-circuit and overload, without the necessity of using an
additional residual current device.
5.6 IT System
As represented in Figure 1, the earth fault current in an IT system flows through
the line conductor capacitance to the power supply neutral point. For this reason,
the first earth fault is characterized by such an extremely low current value to
prevent the overcurrent protections from disconnecting; the deriving touch
voltage is very low.
104 s
103 s
Ik
3x(1x50)+1x(1x25)+1G25
C3 C2 C1
1SDC010037F0001
102 s
T1B160
In125
101 s
Ik
Rt . I d U L
1SDC010040F0001
0.4s
10-1 s
950 A
0.1kA
176
1kA
10kA
where:
Rt is the resistance of the earth electrode for exposed conductive parts [];
Id is the fault current, of the first fault of negligible impedance between
a phase conductor and an exposed conductive part [A];
UL is 50 V for ordinary locations (25 V for particular locations).
If this condition is fulfilled, after the first fault, the touch voltage value on the
exposed conductive parts is lower than 50 V, tolerable by the human body for
an indefinite time, as shown in the safety curve (see Chapter 5.1 General
aspects: effects of current on human beings).
In IT system installations, an insulation monitoring device shall be provided to
177
5.6 IT System
The operating principle of the residual current release is basically the detection
of an earth fault current, by means of a toroid transformer which embraces all
the live conductors, included the neutral if distributed.
Figure 1: Operating principle of the residual current device
U
Zs . r
2 Ia
U
Z 's . 0
2 Ia
where
U0 is the rated voltage between phase and neutral [V];
Ur is the rated voltage between phases [V];
Zs is the impedance of the fault loop comprising the phase conductor and the
protective conductor of the circuit [];
Zs is the impedance of the fault loop comprising the neutral conductor and
the protective conductor of the circuit [];
Ia is the operating current of the protection device in the disconnecting time
specified in Table 1, or within 5 s for distribution circuits.
R
1SDC010041F0001
In absence of an earth fault, the vectorial sum of the currents I is equal to zero;
in case of an earth fault if the I value exceeds the rated residual operating
current In, the circuit at the secondary side of the toroid sends a command
signal to a dedicated opening coil causing the tripping of the circuit-breaker.
A first classification of RCDs can be made according to the type of the fault
current they can detect:
- AC type: the tripping is ensured for residual sinusoidal alternating currents,
whether suddenly applied or slowly rising;
- A type: tripping is ensured for residual sinusoidal alternating currents and
residual pulsating direct currents, whether suddenly applied or slowly rising;
- B type: tripping is ensured for residual direct currents, for residual sinusoidal
alternating currents and residual pulsating direct currents, whether suddenly
applied or slowly rising.
Another classification referred to the operating time delay is:
- undelayed type;
- time delayed S-type.
178
179
I 1 A
t1s
I 0.3 A
t 0.5 s
I 0.03 A
t inst.
180
I 0.3 A
t 0.5 s
I 0.3 A
t 0.5 s
181
k2 = 4
TN system
The formula for the evaluation of the minimum short circuit current is:
I k min =
0.8 U 0 S
k1 k2
1.5 1.2 (1 + m) L
and consequently:
L=
0.8 U 0 S
k1 k2
1.5 1.2 (1 + m) I k min
Dy
L1
L2
L3
N
PE
PE
PE
S n
- m=
is the ratio between the total phase conductor cross section
SPE
Ik
N L3 L2 L1
REN
SN n
is the ratio between the total neutral conductor cross section
SPE
182
n1
n
1SDC010043F0001
120
0.90
150
0.85
185
0.80
240
0.75
300
0.72
IT system
The formulas below are valid when a second fault turns the IT system into a TN
system.
It is necessary to separately examine installations with neutral not distributed
and neutral distributed.
ABB SACE - Electrical devices
183
Dy
L1
I k min
L2
0.8 U r S
=
k1 k2
2 1.5 1.2 (1 + m) L
L3
N
PE
and consequently:
L=
0.8 U r S
k1 k 2
2 1.5 1.2 (1 + m) I k min
Dy
PE
PE
Z
Ik
L3 L2 L1
Ik
N L3 L2 L1
L2
1SDC010045F0001
L1
PE
L3
PE
REN
PE
Z
Ik
L3 L2 L1
1SDC010044F0001
Ik
PE
L3 L2 L1
PE
REN
The tables showing the maximum protected length (MPL) have been defined
considering the following conditions:
- one cable per phase;
- rated voltage equal to 400 V (three-phase system);
- copper cables;
- neutral not distributed, for IT system only;
- protective conductor cross section according to Table 1:
Neutral distributed
Case A: three-phase circuits in IT system with neutral distributed
The formula is:
I k min =
0.8 U 0 S
k1 k2
2 1.5 1.2 (1 + m) L
and consequently:
L=
0.8 U 0 S
k1 k2
2 1.5 1.2 (1 + m) I k min
Note: phase and protective conductors having the same isolation and conductive materials
I k min =
0.8 U 0 SN
k1 k 2
2 1.5 1.2 (1 + m1) L
and consequently:
L=
184
0.8 U 0 SN
k1 k 2
2 1.5 1.2 (1 + m1) I k min
ABB SACE - Electrical devices
For conditions different from the reference ones, the following correction factors
shall be applied.
185
Correction factors
Correction factor for cable in parallel per phase: the value of the maximum
protected length read in Table 2 (TN system) or Table 3 (IT system) shall be
multiplied by the following factor:
n
kp
2
2
3
2.7
4
3
5
3.2
6
3.3
7
3.4
8
3.5
Correction factor for three-phase voltage different from 400 V: the value
of the maximum protected length read in Table 2 (TN system) or Table 3 (IT
system) shall be multiplied by the following factor:
voltage [V]
kV
230
0.58
400
1
440
1.1
500
1.25
Correction factor for aluminium cables: the value of the maximum protected
length read in Table 2 (TN system) or Table 3 (IT system) shall be multiplied by
the following factor:
0.64
SPE/S
S
16 mm2
25 mm2
35 mm2
>35 mm2
0.5
0.55
0.6
0.66
0.67
0.85
1.06
1.00
0.71
0.91
1.13
1.06
0.75
0.96
1.20
1.13
0.80
1.02
1.27
1.2
0.75
kPE
0.86
1.10
1.37
1.29
0.87
1.25
1.5
0.93
1.19
1.48
1.39
1.00
1.28
1.59
1.5
1.11
1.42
1.77
1.67
1.20
1.54
1.91
1.8
1.33
1.71
2.13
2.00
186
CURVE
In
I3
S
1.5
2.5
4
6
10
16
25
SPE
1.5
2.5
4
6
10
16
16
Z
10
30
Z
13
39
Z
16
48
Z
20
60
Z
25
75
Z
32
96
Z
40
120
Z
50
150
Z
63
189
173
288
461
692
1153
1845
2250
133
221
354
532
886
1419
1730
108
180
288
432
721
1153
1406
86
144
231
346
577
923
1125
69
115
185
277
461
738
900
54
90
144
216
360
577
703
43
72
115
173
288
461
563
58
92
138
231
369
450
45
72
108
180
288
352
690
1.73
kAl
TN system MPL
by MCB
B
6
30
SPE
1.5
2.5
4
6
10
16
16
16
B
8
40
B
10
50
B
13
65
B
16
80
B
20
100
B
25
125
B
32
160
B
40
200
B
50
250
B
63
315
65
108
173
259
432
692
844
52
86
138
208
346
554
675
42
69
111
166
277
443
540
32
54
86
130
216
346
422
26
43
69
104
173
277
338
35
55
83
138
221
270
27
44
66
110
176
214
B
80
400
B
100
500
35
52
86
138
169
190
28
42
69
111
135
152
SPE
1.5
2.5
4
6
10
16
16
16
C
3
30
C
4
40
C
6
60
C
8
80
C
C
C
C
C
C
C
C
C
C
C
C
10
13 16
20
25 32
40 50
63
80 100 125
100 130 160 200 250 320 400 500 630 800 1000 1250
173
288
461
692
1153
1845
2250
130
216
346
519
865
1384
1688
86
144
231
346
577
923
1125
65
108
173
259
432
692
844
52
86
138
208
346
554
675
40
67
106
160
266
426
519
32
54
86
130
216
346
422
26
21 16
13
43
35 27
22 17
14
69
55 43
35 28
22
104 83 65
52 42
33
173 138 108 86 69
55
277 221 173 138 111 88
338 270 211 169 135 107
17
26
43
69
84
95
14
21
35
55
68
76
11
17
28
44
54
61
187
K
2
28
K
3
42
K K K K K K K K K K K K K K K K K K K K
4 4.2 5.8 6
8 10 11 13 15 16 20 25 26 32 37 40 41 45 50 63
56 59 81 84 112 140 154 182 210 224 280 350 364 448 518 560 574 630 700 882
185
308
492
738
1231
1969
2401
123
205
328
492
820
1313
1601
92 88
154 146
246 234
369 350
615 584
984 934
1201 1140
64
106
170
255
425
681
830
62
103
164
246
410
656
800
46
77
123
185
308
492
600
37
62
98
148
246
394
480
34
56
89
134
224
358
437
28
47
76
114
189
303
369
25
41
66
98
164
263
320
23
38
62
92
154
246
300
18
31
49
74
123
197
240
15
25
39
59
98
158
192
14
24
38
57
95
151
185
12
19
31
46
77
123
150
10
17
27
40
67
106
130
9
15
25
37
62
98
120
15
24
36
60
96
117
14
22
33
55
88
107
20
30
49
79
96
16
23
39
63
76
S
1.5
2.5
4
6
10
16
25
35
50
70
95
In
I3
SPE
1.5
2.5
4
6
10
16
16
16
25
35
50
188
D
2
40
D
3
60
D
4
80
D
6
120
D
D
8
10
160 200
D
13
260
D
16
320
D
D
D
D
D
D
D
D
20 25
32
40
50 63
80 100
400 500 640 800 1000 1260 1600 2000
130
216
346
519
865
1384
1688
86
144
231
346
577
923
1125
65
108
173
259
432
692
844
43
72
115
173
288
461
563
32
54
86
130
216
346
422
20
33
53
80
133
213
260
16
27
43
65
108
173
211
13 10
8
22 17
14
35 28
22
52 42
32
86 69
54
138 111 86
169 135 105
26
43
69
104
173
277
338
T1
63
10 In
T1
80
10 In
T1
100
10 In
T1
125
10 In
T1
160
10 In
6
10
15
23
38
62
75
84
128
179
252
12
18
31
49
60
67
102
142
200
10
14
24
38
47
53
80
112
157
8
12
19
31
38
42
64
90
126
6
9
15
25
30
34
51
72
101
7
12
19
23
26
40
56
79
T1
50
500 A
6
11
17
26
43
69
84
9
14
21
35
55
68
7
11
16
27
44
54
9
13
22
35
42
47
7
10
17
28
34
38
S
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
T2
T2
In
1.6
2
I3
10 In 10 In
SPE
1.5 246 197
2.5 410 328
4
655 524
6
983 786
10 1638 1311
16 2621 2097
16
16
25
35
50
70
95
95
T2 T2 T2 T2 T2
T2 T2 T2
T2
T2 T2 T2 T2
T2
2.5 3.2
4
5 6.3
8
10 12.5 1650 63 80 100 125 160
10 In 10 In 10 In 10 In 10 In 10 In 10 In 10 In 500 A 10 In 10 In 10 In 10 In 10 In
157
262
419
629
1048
1677
123
205
328
491
819
1311
1598
98
164
262
393
655
1048
1279
79
131
210
315
524
839
1023
1151
62
104
166
250
416
666
812
914
49
82
131
197
328
524
639
720
1092
39
66
105
157
262
419
511
576
874
31
52
84
126
210
335
409
460
699
979
8
13
21
31
52
84
102
115
175
245
343
417
518
526
17
25
42
67
81
91
139
194
273
331
411
418
13
20
33
52
64
72
109
153
215
261
324
329
10
16
26
42
51
58
87
122
172
209
259
263
8
13
21
34
41
46
70
98
137
167
207
211
10
16
26
32
36
55
76
107
130
162
165
189
TN system MPL
by MCCB
In
I3
SPE
4
6
10
16
16
16
25
35
50
70
95
95
120
S
4
6
10
16
25
35
50
70
95
120
150
185
240
T3
63
10 In
T3
80
10 In
T3
100
10 In
T3
125
10 In
17
25
42
67
81
91
139
194
273
331
411
418
499
13
20
33
52
64
72
109
153
215
261
324
329
393
10
16
26
42
51
58
87
122
172
209
259
263
315
8
13
21
34
41
46
70
98
137
167
207
211
252
T3
160
10 In
10
16
26
32
36
55
76
107
130
162
165
197
T3
200
10 In
8
13
21
26
29
44
61
86
104
130
132
157
S
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
10
17
20
23
35
49
69
83
104
105
126
S
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
190
In
I3
SPE
1.5
2.5
4
6
10
16
16
16
25
35
50
70
95
95
120
150
T4
T4
20
32
320 A 10 In
14
23
36
54
90
144
176
198
300
420
590
717
891
905
1081
1297
14
23
36
54
90
144
176
198
300
420
590
717
891
905
1081
1297
T4
T4
50
80
10 In 5...10 In
9
14
23
35
58
92
113
127
192
269
378
459
570
579
692
830
115
189
2914
4322
7236
11558
14170
15879
240120
336168
472236
574287
713356
724362
865432
1038519
T3
250
10 In
In
I3
SPE
1,5
2,5
4
6
10
16
16
16
25
35
50
70
95
95
120
150
T5
320
5...10 In
T5
400
5...10 In
T5
500
5...10 In
T5
630
5...10 In
31
52
74
115
189
2914
3518
4020
6030
8442
11859
14372
17889
18190
216108
259130
21
42
63
94
147
2312
2814
3216
4824
6734
9447
11557
14371
14572
17386
208104
21
31
52
73
126
189
2311
2513
3819
5427
7638
9246
11457
11658
13869
16683
11
21
42
53
95
157
189
2010
3115
4321
6030
7336
9145
9246
11055
13266
T4
100
5...10 In
T4
125
5...10 In
T4
160
5...10 In
T4
200
5...10 In
T4
T4
250
320
5...10 In 5...10 In
94
147
2312
3517
5829
9246
11356
12763
19296
269135
378189
459229
570285
579290
692346
830415
73
126
189
2814
4623
7437
9045
10151
15477
215108
302151
367184
456228
463232
554277
664332
53
95
147
2211
3618
5829
7035
7940
12060
16884
236118
287143
356178
362181
432216
519259
42
74
126
179
2914
4623
5628
6332
9648
13567
18994
229115
285143
290145
346173
415208
32
31
63
52
95
74
147
115
2312
189
3718
2914
4523
3518
5125
4020
7738
6030
10854
8442
15176 11859
18492 14372
228114 17889
232116 18190
277138 216108
332166 259130
S
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
In
I3
SPE
1.5
2.5
4
6
10
16
16
16
25
35
50
70
95
95
T2
10
5.5 In
T2
25
5.5 In
T2
63
5.5 In
T2
100
5.5 In
T2
160
5.5 In
79
131
210
315
524
839
1023
1151
1747
2446
3434
4172
5183
5265
31
52
84
126
210
335
409
460
699
979
1374
1669
2073
2106
12
21
33
50
83
133
162
183
277
388
545
662
823
836
21
31
52
84
102
115
175
245
343
417
518
526
20
33
52
64
72
109
153
215
261
324
329
Note: if the setting of function I is different from the reference value (5.5), the value of the
MPL shall be multiplied by the ratio between the reference value and the set value.
191
S
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
In
I3
SPE
1,5
2,5
4
6
10
16
16
16
25
35
50
70
95
95
120
150
T4
160
6.5 In
29
48
77
94
106
161
226
317
385
478
486
581
697
T4
250
6.5 In
18
30
48
59
66
101
141
198
241
299
304
363
435
T4
320
6.5 In
19
31
38
43
65
90
127
154
191
194
232
279
T5
320
6.5 In
24
30
33
50
71
99
120
150
152
181
218
T5
400
6.5 In
24
30
33
50
71
99
120
150
152
181
218
T5
630
6.5 In
19
24
27
40
56
79
96
120
121
145
174
15
17
26
36
50
61
76
77
92
111
Note: if the setting of function I is different from the reference value (6.5), the value of the
MPL shall be multiplied by the ratio between the reference value and the set value.
In
I3
SPE
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
2.5
4
6
10
16
16
16
25
35
50
70
95
95
120
150
S6
800
6 In
S7
1000
6 In
S7
1250
6 In
S7
1600
6 In
S8
1600
6 In
S8
2000
6 In
S8
2500
6 In
S8
3200
6 In
CURVE
In
I3
S
1.5
2.5
4
6
10
16
25
SPE
1.5
2.5
4
6
10
16
16
Z
10
30
Z
13
39
Z
16
48
Z
20
60
Z
25
75
Z
32
96
Z
40
120
Z
50
150
Z
63
189
150
250
400
599
999
1598
1949
150
250
400
599
999
1598
1949
115
192
307
461
768
1229
1499
94
156
250
375
624
999
1218
75
125
200
300
499
799
974
60
100
160
240
400
639
780
47
78
125
187
312
499
609
37
62
100
150
250
400
487
50
80
120
200
320
390
40
63
95
159
254
309
SPE
1.5
2.5
4
6
10
16
16
16
B
6
30
B
8
40
B
10
50
B
13
65
B
16
80
B
20
100
B
25
125
B
32
160
B
40
200
B
50
250
B
63
315
150
250
400
599
999
1598
1949
112
187
300
449
749
1199
1462
90
150
240
360
599
959
1169
69
115
184
277
461
738
899
56
94
150
225
375
599
731
45
75
120
180
300
479
585
36
60
96
144
240
384
468
28
47
75
112
187
300
365
22
37
60
90
150
240
292
30
48
72
120
192
234
24
38
57
95
152
186
B
80
400
B
100
500
30
45
75
120
146
165
24
36
60
96
117
132
20
28
39
48
59
60
72
86
22
31
38
48
48
58
69
18
25
31
38
39
46
55
14
20
24
30
30
36
43
14
20
24
30
30
36
43
16
19
24
24
29
35
13
15
19
19
23
28
10
12
15
15
18
22
CURVE
C
C
In
3
4
I3
30
40
S
SPE
1.5 1.5 150 112
2.5 2.5 250 187
4
4
400 300
6
6
599 449
10
10 999 749
16
16 1598 1199
25
16 1949 1462
35
16
C
6
60
C
8
80
C
10
100
C
13
130
C
16
160
C
20
200
C
25
250
C
32
320
C
40
400
C
50
500
C
63
630
75
125
200
300
499
799
974
56
94
150
225
375
599
731
45
75
120
180
300
479
585
35
58
92
138
230
369
450
28
47
75
112
187
300
365
22
37
60
90
150
240
292
18
30
48
72
120
192
234
14
23
37
56
94
150
183
11
19
30
45
75
120
146
15
24
36
60
96
117
12
19
29
48
76
93
C
C
C
80 100 125
800 1000 1250
15
22
37
60
73
82
12
18
30
48
58
66
10
14
24
38
47
53
Note: if the setting of function S or I is different from the reference value (6), the MPL value
shall be multiplied by the ratio between the reference value and the set value. Besides,
using function S the MPL shall be multiplied by 1.1.
192
193
K
2
28
K
3
42
161 107 80
268 178 134
428 285 214
642 428 321
1070 713 535
1712 1141 856
2088 1392 1044
76
127
204
306
510
815
994
55
92
148
221
369
590
720
K K K K K K K K K K K K K K K K K
6
8 10 11 13 15 16 20 25 26 32 37 40 41 45 50 63
84 112 140 154 182 210 224 280 350 364 448 518 560 574 630 700 882
54
89
143
214
357
571
696
40
67
107
161
268
428
522
32
54
86
128
214
342
418
29
49
78
117
195
311
380
25
41
66
99
165
263
321
21
36
57
86
143
228
278
20
33
54
80
134
214
261
16
27
43
64
107
171
209
13
21
34
51
86
137
167
12
21
33
49
82
132
161
10
17
27
40
67
107
130
9
14
23
35
58
93
113
8
13
21
32
54
86
104
13
21
31
52
84
102
12
19
29
48
76
93
17
26
43
68
84
14
20
34
54
66
S
1.5
2.5
4
6
10
16
25
35
50
70
95
194
T1
50
500 A
T1
63
10 In
T1
80
10 In
T1
100
10 In
T1
125
10 In
T1
160
10 In
5
8
13
20
33
53
65
73
111
155
218
11
16
26
42
52
58
88
123
173
8
12
21
33
41
46
69
97
136
7
10
17
27
32
37
55
78
109
5
8
13
21
26
29
44
62
87
6
10
17
20
23
35
49
68
D
4
80
D
6
120
D
8
160
D
10
200
D
13
260
D
16
320
D
20
400
D
25
500
D
32
640
D
D
D
D
D
40
50
63
80 100
800 1000 1260 1600 2000
56
94
150
225
375
599
731
37
62
100
150
250
400
487
28
47
75
112
187
300
365
22
37
60
90
150
240
292
17
29
46
69
115
184
225
14
23
37
56
94
150
183
11
19
30
45
75
120
146
9
15
24
36
60
96
117
7
12
19
28
47
75
91
6
9
15
22
37
60
73
7
12
18
30
48
58
6
10
14
24
38
46
7
11
19
30
37
41
6
9
15
24
29
33
S
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
In
I3
SPE
1.5
2.5
4
6
10
16
16
16
25
35
50
70
95
95
T2
T2
1.6
2
10 In 10 In
213
355
567
851
1419
2270
T2
T2
2.5 3.2
10 In 10 In
170 136
284 227
454 363
681 545
1135 908
1816 1453
T2 T2 T2 T2
T2 T2
T2 T2 T2
4
5 6.3
8
10 12.5 1650 63 80
10 In 10 In 10 In 10 In 10 In 10 In 500 A 10 In 10 In
106
85
177 142
284 227
426 340
709 567
1135 908
1384 1107
68
113
182
272
454
726
886
997
54
90
144
216
360
576
703
791
43
71
113
170
284
454
554
623
946
34
57
91
136
227
363
443
498
757
27
45
73
109
182
291
354
399
605
847
7
11
18
27
45
73
89
100
151
212
297
361
449
456
14
22
36
58
70
79
120
168
236
287
356
362
11
17
28
45
55
62
95
132
186
226
281
285
T2 T2 T2
100 125 160
10 In 10 In 10 In
9
14
23
36
44
50
76
106
149
181
224
228
7
11
9
18 14
29 23
35 28
40 31
61 47
85 66
119 93
145 113
180 140
182 142
195
T3
80
10 In
T3
100
10 In
T3
125
10 In
14
22
36
58
70
79
120
168
236
287
356
362
432
11
17
28
45
55
62
95
132
186
226
281
285
340
9
14
23
36
44
50
76
106
149
181
224
228
272
7
11
18
29
35
40
61
85
119
145
180
182
218
SPE
4
6
10
16
16
16
25
35
50
70
95
95
120
T3
160
10 In
9
14
23
28
31
47
66
93
113
140
142
170
T3
200
10 In
7
11
18
22
25
38
53
74
90
112
114
136
S
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
9
15
18
20
30
42
59
72
90
91
109
S
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
196
In
I3
SPE
1.5
2.5
4
6
10
16
16
16
25
35
50
70
95
95
120
150
T4
T4
T4
20
32
50
320 A 10 In 10 In
12
20
31
47
78
125
152
171
260
364
511
621
772
784
936
1124
12
20
31
47
78
125
152
171
260
364
511
621
772
784
936
1124
7
12
20
30
50
80
97
110
166
233
327
397
494
502
599
719
T3
250
10 In
In
I3
SPE
1.5
2.5
4
6
10
16
16
16
25
35
50
70
95
95
120
150
T5
320
5...10 In
T5
400
5...10 In
T5
500
5...10 In
T5
630
5...10 In
21
42
63
95
168
2512
3015
3417
5226
7336
10251
12462
15477
15778
18794
225112
21
32
52
74
126
2010
2412
2714
4221
5829
8241
9950
12362
12563
15075
18090
11
21
42
63
105
168
1910
2211
3317
4723
6533
7940
9949
10050
12060
14472
11
21
32
52
84
136
158
179
2613
3718
5226
6332
7839
8040
9548
11457
T4
80
5...10 In
T4
100
5...10 In
T4
125
5...10 In
T4
160
5...10 In
T4
200
5...10 In
T4
250
5...10 In
T4
320
5...10 In
95
168
2512
3719
6231
10050
12261
13769
208104
291146
409204
497248
617309
627313
749375
899449
74
126
2010
3015
5025
8040
9749
11055
16683
233117
327164
397199
494247
502251
599300
719360
63
105
168
2412
4020
6432
7839
8844
13367
18693
262131
318159
395198
401201
479240
575288
52
84
126
199
3116
5025
6130
6934
10452
14673
204102
248124
309154
313157
375187
449225
42
63
105
157
2512
4020
4924
5527
8342
11758
16482
19999
247123
251125
300150
360180
31
52
84
126
2010
3216
3919
4422
6733
9347
13165
15979
19899
201100
240120
288144
21
42
63
95
168
2512
3015
3417
5226
7336
10251
12462
15477
15778
18794
225112
S
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
In
I3
SPE
1.5
2.5
4
6
10
16
16
16
25
35
50
70
95
95
T2
10
5.5 In
T2
25
5.5 In
T2
63
5.5 In
T2
100
5.5 In
T2
160
5.5 In
68
113
182
272
454
726
886
997
1513
2119
2974
3613
4489
4559
27
45
73
109
182
291
354
399
605
847
1190
1445
1796
1824
11
18
29
43
72
115
141
158
240
336
472
573
713
724
18
27
45
73
89
100
151
212
297
361
449
456
17
28
45
55
62
95
132
186
226
281
285
Note: if the setting of function I is different from the reference value (5.5), the MPL value
shall be multiplied by the ratio between the reference value and the set value.
197
S
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
In
I3
SPE
1.5
2.5
4
6
10
16
16
16
25
35
50
70
95
95
120
150
25
42
67
82
92
140
196
275
333
414
421
503
603
T4
160
6.5 In
16
26
42
51
58
87
122
172
208
259
263
314
377
T4
250
6.5 In
17
27
33
37
56
78
110
133
166
168
201
241
T4
320
6.5 In
21
26
29
44
61
86
104
129
132
157
189
IT system MPL
by MCCB
T5
320
6.5 In
21
26
29
44
61
86
104
129
132
157
189
T5
400
6.5 In
17
20
23
35
49
69
83
104
105
126
151
T5
630
6.5 In
13
15
22
31
44
53
66
67
80
96
Note: if the setting of function I is different from the reference value (6.5), the value of the
MPL shall be multiplied by the ratio between the reference value and the set value.
198
S
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
In
I3
SPE
2.5
4
6
10
16
16
16
25
35
50
70
95
95
120
150
S6
800
6 In
S7
1000
6 In
S7
1250
6 In
S7
1600
6 In
S8
1600
6 In
S8
2000
6 In
S8
2500
6 In
S8
3200
6 In
17
24
34
41
51
52
62
75
19
27
33
41
42
50
60
16
22
26
33
33
40
48
12
17
21
26
26
31
37
12
17
21
26
26
31
37
14
17
21
21
25
30
11
13
16
17
20
24
9
10
13
13
16
19
Note: if the setting of function S or I is different from the reference value (6), the MPL value
shall be multiplied by the ratio between the reference value and the set value. Besides,
using function S, the MPL shall be multiplied by 1.1.
199
These slide rules represent a valid instrument for a quick and approximate
dimensioning of electrical plants.
All the given information is connected to some general reference conditions;
the calculation methods and the data reported are gathered from the IEC
Standards in force and from plant engineering practice. The instruction manual
enclosed with the slide rules offers different examples and tables showing the
correction coefficients necessary to extend the general reference conditions to
those actually required.
Side
Calculation of the short-circuit current for three-phase fault on the load side of
a cable line with known cross section and length.
In addition, a diagram for the calculation of the short-circuit current on the load
side of elements with known impedance.
1SDC008059F0001
These two-sided slide rules are available in four different colors, easily identified
by subject:
- yellow slide rule: cable sizing;
- orange slide rule: cable verification and protection;
- green slide rule: protection coordination;
- blue slide rule: motor and transformer protection.
Side
Definition of the current carrying capacity, impedance and voltage drop of cables.
200
201
Side
Verification of cable protection against indirect contact and short-circuit with
ABB SACE MCCBs (moulded-case circuit-breakers).
Side
Selection of the circuit-breakers when back-up protection is provided.
Side
Definition of the limit selectivity current for the combination of two circuit-breakers
in series.
202
1SDC008061F0001
1SDC008060F0001
Side
Verification of cable protection against indirect contact and short-circuit with
ABB MCBs (modular circuit-breakers).
203
A.2 DOCWin
A.2 DOCWin
DOCWin is a software for the dimensioning of electrical networks, with low or
medium voltage supply.
Networks can be completely calculated through simple operations starting from
the definition of the single-line diagram and thanks to the drawing functions
provided by an integrated CAD software.
Side
Selection and coordination of the protection devices for the motor starter, DOL
start-up (type 2 coordination in compliance with the Standard IEC 60947-4-1).
Side
Sizing of a transformer feeder.
In addition, a diagram for the calculation of the short-circuit current on the load
side of transformers with known rated power.
Supplies
There are no pre-defined limits: the software manages MV and LV power
supplies and generators, MV/LV and LV/LV transformers, with two or three
windings, with or without voltage regulator, according to the requirements.
1SDC008062F0001
Network calculation
204
Load Flow calculation using the Newton-Raphson method. The software can
manage networks with multiple slacks and unbalances due to single- or twophase loads. Magnitude and phase shift of the node voltage and of the branch
current are completely defined for each point of the network, for both MV as
well as LV.
Calculation of the active and reactive power required by each single power
source.
ABB SACE - Electrical devices
205
A.2 DOCWIN
A.2 DOCWin
206
207
A.2 DOCWIN
Generic loads
The formula for the calculation of the load current of a generic load is:
Ib =
P
k U r cos
where:
P is the active power [W];
k is a coefficient which has the value:
- 1 for single-phase systems or for direct current systems;
for three-phase systems;
Ur is the rated voltage [V] (for three-phase systems it is the line voltage, for
single-phase systems it is the phase voltage);
cos is the power factor.
Table 1 allows the load current to be determined for some power values
according to the rated voltage. The table has been calculated considering cos
to be equal to 0.9; for different power factors, the value from Table 1 must be
multiplied by the coefficient given in Table 2 corresponding to the actual value
of the power factor (cosact).
Table 1: Load current for three-phase systems with cos = 0.9
Printouts
Single-line diagram, curves and reports of the single components of the
network can be printed by any printer supported by the hardware
configuration.
All information can be exported in the most common formats of data exchange.
All print modes can be customized.
208
P [kW]
0.03
0.04
0.06
0.1
0.2
0.5
1
2
5
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
200
230
400
415
0.08
0.11
0.17
0.28
0.56
1.39
2.79
5.58
13.95
27.89
55.78
83.67
111.57
139.46
167.35
195.24
223.13
251.02
278.91
306.80
334.70
362.59
390.48
418.37
557.83
0.05
0.06
0.10
0.16
0.32
0.80
1.60
3.21
8.02
16.04
32.08
48.11
64.15
80.19
96.23
112.26
128.30
144.34
160.38
176.41
192.45
208.49
224.53
240.56
320.75
0.05
0.06
0.09
0.15
0.31
0.77
1.55
3.09
7.73
15.46
30.92
46.37
61.83
77.29
92.75
108.20
123.66
139.12
154.58
170.04
185.49
200.95
216.41
231.87
309.16
Ur [V]
440
Ib [A]
0.04
0.06
0.09
0.15
0.29
0.73
1.46
2.92
7.29
14.58
29.16
43.74
58.32
72.90
87.48
102.06
116.64
131.22
145.80
160.38
174.95
189.53
204.11
218.69
291.59
500
600
690
0.04
0.05
0.08
0.13
0.26
0.64
1.28
2.57
6.42
12.83
25.66
38.49
51.32
64.15
76.98
89.81
102.64
115.47
128.30
141.13
153.96
166.79
179.62
192.45
256.60
0.03
0.04
0.06
0.11
0.21
0.53
1.07
2.14
5.35
10.69
21.38
32.08
42.77
53.46
64.15
74.84
85.53
96.23
106.92
117.61
128.30
138.99
149.68
160.38
213.83
0.03
0.04
0.06
0.09
0.19
0.46
0.93
1.86
4.65
9.30
18.59
27.89
37.19
46.49
55.78
65.08
74.38
83.67
92.97
102.27
111.57
120.86
130.16
139.46
185.94
209
697.28
836.74
976.20
1115.65
1255.11
1394.57
1534.02
1673.48
1812.94
1952.39
2091.85
2231.31
2370.76
2510.22
2649.68
2789.13
400
400.94
481.13
561.31
641.50
721.69
801.88
882.06
962.25
1042.44
1122.63
1202.81
1283.00
1363.19
1443.38
1523.56
1603.75
415
386.45
463.74
541.02
618.31
695.60
772.89
850.18
927.47
1004.76
1082.05
1159.34
1236.63
1313.92
1391.21
1468.49
1545.78
Ur [V]
440
Ib[A]
364.49
437.39
510.28
583.18
656.08
728.98
801.88
874.77
947.67
1020.57
1093.47
1166.36
1239.26
1312.16
1385.06
1457.96
500
600
690
1
0.9
0.95
0.947
0.9
1
320.75
384.90
449.05
513.20
577.35
641.50
705.65
769.80
833.95
898.10
962.25
1026.40
1090.55
1154.70
1218.85
1283.00
267.29
320.75
374.21
427.67
481.13
534.58
588.04
641.50
694.96
748.42
801.88
855.33
908.79
962.25
1015.71
1069.17
232.43
278.91
325.40
371.88
418.37
464.86
511.34
557.83
604.31
650.80
697.28
743.77
790.25
836.74
883.23
929.71
0.85
1.059
0.8
1.125
kcos =
0.75
1.2
30
40
50
60
70
80
90
100
110
120
130
140
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
0.7
1.286
0.9
cos act
P [kW]
0.03
0.04
0.06
0.1
0.2
0.5
1
2
5
10
20
210
400
0.13
0.17
0.26
0.43
0.87
2.17
4.35
8.70
21.74
43.48
86.96
0.08
0.10
0.15
0.25
0.50
1.25
2.50
5.00
12.50
25.00
50.00
130.43
173.91
217.39
260.87
304.35
347.83
391.30
434.78
478.26
521.74
565.22
608.70
652.17
869.57
1086.96
1304.35
1521.74
1739.13
1956.52
2173.91
2391.30
2608.70
2826.09
3043.48
3260.87
3478.26
3695.65
3913.04
4130.43
4347.83
75.00
100.00
125.00
150.00
175.00
200.00
225.00
250.00
275.00
300.00
325.00
350.00
375.00
500.00
625.00
750.00
875.00
1000.00
1125.00
1250.00
1375.00
1500.00
1625.00
1750.00
1875.00
2000.00
2125.00
2250.00
2375.00
2500.00
Ur [V]
415
440
Ib [A]
0.07
0.07
0.10
0.09
0.14
0.14
0.24
0.23
0.48
0.45
1.20
1.14
2.41
2.27
4.82
4.55
12.05
11.36
24.10
22.73
48.19
45.45
Ur [V]
415
440
Ib [A]
72.29
96.39
120.48
144.58
168.67
192.77
216.87
240.96
265.06
289.16
313.25
337.35
361.45
481.93
602.41
722.89
843.37
963.86
1084.34
1204.82
1325.30
1445.78
1566.27
1686.75
1807.23
1927.71
2048.19
2168.67
2289.16
2409.64
68.18
90.91
113.64
136.36
159.09
181.82
204.55
227.27
250.00
272.73
295.45
318.18
340.91
454.55
568.18
681.82
795.45
909.09
1022.73
1136.36
1250.00
1363.64
1477.27
1590.91
1704.55
1818.18
1931.82
2045.45
2159.09
2272.73
500
600
690
60.00
80.00
100.00
120.00
140.00
160.00
180.00
200.00
220.00
240.00
260.00
280.00
300.00
400.00
500.00
600.00
700.00
800.00
900.00
1000.00
1100.00
1200.00
1300.00
1400.00
1500.00
1600.00
1700.00
1800.00
1900.00
2000.00
50.00
66.67
83.33
100.00
116.67
133.33
150.00
166.67
183.33
200.00
216.67
233.33
250.00
333.33
416.67
500.00
583.33
666.67
750.00
833.33
916.67
1000.00
1083.33
1166.67
1250.00
1333.33
1416.67
1500.00
1583.33
1666.67
43.48
57.97
72.46
86.96
101.45
115.94
130.43
144.93
159.42
173.91
188.41
202.90
217.39
289.86
362.32
434.78
507.25
579.71
652.17
724.64
797.10
869.57
942.03
1014.49
1086.96
1159.42
1231.88
1304.35
1376.81
1449.28
Table 4: Correction factors for load current with cos other than 1
Table 3 allows the load current to be determined for some power values
according to the rated voltage. The table has been calculated considering cos
to be equal to 1; for different power factors, the value from Table 3 must be
multiplied by the coefficient given in Table 4 corresponding to the actual value
of the power factor (cosact).
230
400
P [kW]
Table 2: Correction factors for load current with cos other than 0.9
cosact
kcos*
230
500
600
690
0.06
0.08
0.12
0.20
0.40
1.00
2.00
4.00
10.00
20.00
40.00
0.05
0.07
0.10
0.17
0.33
0.83
1.67
3.33
8.33
16.67
33.33
0.04
0.06
0.09
0.14
0.29
0.72
1.45
2.90
7.25
14.49
28.99
cosact
kcos*
*
1
1
0.95
1.053
0.9
1.111
0.85
1.176
Lighting circuits
kcos =
0.8
1.25
0.75
1.333
0.7
1.429
1
cos act
The current absorbed by the lighting system may be deduced from the lighting
equipment catalogue, or approximately calculated using the following formula:
Ib=
PL nL kBkN
U rL cos
where:
PL is the power of the lamp [W];
nL is the number of lamps per phase;
kB is a coefficient which has the value:
- 1 for lamps which do not need any auxiliary starter;
- 1.25 for lamps which need auxiliary starters;
kN is a coefficient which has the value:
- 1 for star-connected lamps;
for delta-connected lamps;
UrL is the rated voltage of the lamps;
cos is the power factor of the lamps which has the value:
- 0.4 for lamps without compensation;
- 0.9 for lamps with compensation.
ABB SACE - Electrical devices
211
Motors
Table 5 gives the approximate values of the load current for some three-phase
squirrel-cage motors, 1500 rpm at 50 Hz, according to the rated voltage.
Note: these values are given for information only, and may vary according to the motor manifacturer
and depending on the number of poles
212
PS = hp
1/12
1/8
1/6
1/4
1/3
1/2
3/4
1
1.5
2
3
3.4
4
5
5.5
6.8
7.5
8.8
10
11
12.5
15
17
20
25
27
30
34
40
50
54
60
70
75
80
100
110
125
136
150
175
180
190
200
220
245
250
270
300
340
350
400
430
480
545
610
645
680
760
810
910
240 V
[A]
0.35
0.50
0.68
1
1.38
1.93
2.3
3.1
4.1
5.6
7.9
8.9
10.6
13
14
17.2
18.9
21.8
24.8
26.4
29.3
35.3
40.2
48.2
58.7
63.4
68
77.2
92.7
114
123
136
154
166
178
226
241
268
297
327
384
393
416
432
471
530
541
589
647
736
756
868
927
1010
1130
1270
1340
1420
1580
380-400 V
[A]
0.22
0.33
0.42
0.64
0.88
1.22
1.5
2
2.6
3.5
5
5.7
6.6
8.2
8.5
10.5
11.5
13.8
15.5
16.7
18.3
22
25
30
37
40
44
50
60
72
79
85
97
105
112
140
147
170
188
205
242
245
260
273
295
333
340
370
408
460
475
546
580
636
710
800
850
890
1000
1080
1200
415 V
[A]
0.20
0.30
0.40
0.60
0.85
1.15
1.40
2
2.5
3.5
5
5.5
6.5
7.5
8.4
10
11
12.5
14
15.4
17
21
23
28
35
37
40
47
55
66
72
80
90
96
105
135
138
165
182
200
230
242
250
260
280
320
325
340
385
425
450
500
535
580
650
740
780
830
920
990
1100
440 V
[A]
0.19
0.28
0.37
0.55
0.76
1.06
1.25
1.67
2.26
3.03
4.31
4.9
5.8
7.1
7.6
9.4
10.3
12
13.5
14.4
15.8
19.3
21.9
26.3
32
34.6
37.1
42.1
50.1
61.9
67
73.9
83.8
90.3
96.9
123
131
146
162
178
209
214
227
236
256
289
295
321
353
401
412
473
505
549
611
688
730
770
860
920
1030
500 V
[A]
0.16
0.24
0.33
0.46
0.59
0.85
1.20
1.48
2.1
2.6
3.8
4.3
5.1
6.2
6.5
8.1
8.9
10.4
11.9
12.7
13.9
16.7
19
22.5
28.5
30.6
33
38
44
54
60
64.5
73.7
79
85.3
106
112
128
143
156
184
186
200
207
220
254
259
278
310
353
363
416
445
483
538
608
645
680
760
810
910
600 V
[A]
0.12
0.21
0.27
0.40
0.56
0.77
1.02
1.22
1.66
2.22
3.16
3.59
4.25
5.2
5.6
6.9
7.5
8.7
9.9
10.6
11.6
14.1
16.1
19.3
23.5
25.4
27.2
30.9
37.1
45.4
49.1
54.2
61.4
66.2
71.1
90.3
96.3
107
119
131
153
157
167
173
188
212
217
235
260
295
302
348
370
405
450
508
540
565
630
680
760
660-690 V
[A]
0.7
0.9
1.1
1.5
2
2.9
3.3
3.5
4.4
4.9
6
6.7
8.1
9
9.7
10.6
13
15
17.5
21
23
25
28
33
42
44
49
56
60
66
82
86
98
107
118
135
140
145
152
170
190
200
215
235
268
280
320
337
366
410
460
485
510
570
610
680
Three-phase fault
ZL
IkLLL
ZL
IkLLL
ZC = R C2 + X C2
ZL
IkLLL
ZN
Two-phase fault
ZL
ZL
ZL
IkLL
IkLL =
3
Ur
=
IkLLL = 0.87 IkLLL
2Z L
2
ZN
213
ZL
Ur
3( ZL + ZN )
ZL
IkLN =
Ur
Ur
=
= 0.5 IkLLL
3( ZL + ZN )
3(2ZL )
ZL
IkLN =
ZN
IkLN
If Z N 0
Ur
Ur
=
= 0.33IkLLL
3( ZL + ZN )
3(3Z L )
limit condition:
IkLN =
Ur
Ur
=
= I kLLL
3( ZL + ZN )
3( ZL )
Phase to PE fault
IkLPE =
ZL
Ur
3( ZL + ZPE )
ZL
IkLPE =
Ur
Ur
=
= 0.5I kLLL
3( ZL + ZPE )
3(2ZL )
ZL
IkLPE =
ZPE IkLPE
If Z PE 0
Ur
Ur
=
= 0.33I kLLL
3(ZL + ZPE )
3(3ZL )
limit condition:
IkLPE =
Ur
Ur
=
= IkLLL
3( ZL + ZPE )
3 (ZL)
Note
IkLLL
214
Three-phase
short-circuit
Two-phase
short-circuit
IkLLL
IkLL
IkLL
IkLLL=1.16IkLL
IkLN
IkLL=0.87IkLLL
Ik =
Phase to neutral
short-circuit
IkLN
ILN=0.5IkLLL (ZL = ZN)
ILN=0.33IkLLL (ZL = 0,5ZN)
ILN=IkLLL (ZN 0)
IkLN=0.58IkLL (ZL = ZN)
IkLN=0.38IkLL (ZL = 0,5ZN)
IkLN=1.16IkLL (ZN 0)
Phase to PE short-circuit
(TN system)
IkLPE
ILPE=0.5I kLLL (ZL = ZPE)
ILPE=0.33IkLLL (ZL = 0.5ZPE)
ILPE=IkLLL (ZPE 0)
IkLPE=0.58IkLL (ZL = ZPE)
IkLPE=0.38IkLL (ZL = 0.5ZPE)
IkLPE=1.16IkLL (ZPE 0)
Two-phase short-circuit
Ik =
Sk
3 Ur
Sk
2 Ur
where:
Sk is the short-circuit apparent power seen at the point of the fault;
Ur is the rated voltage.
To determine the short-circuit apparent power Sk, all the elements of the network
shall be taken into account, which may be:
elements which contribute to the short-circuit current:
network, generators, motors;
elements which limit the value of the short-circuit current:
conductors and transformers.
The procedure for the calculation of the short-circuit current involves the following
steps:
1. calculation of the short-circuit power for the different elements of the
installation;
2. calculation of the short-circuit power at the fault point;
3. calculation of the short-circuit current.
Calculation of the short-circuit power for the different elements of
the installation
The short-circuit apparent power Sk shall be determined for all the
components which are part of the installation:
Network
An electrical network is considered to include everything upstream of the point
of energy supply.
215
Skmot = 3 U r I k
Transformers
The short-circuit power of a transformer (Sktrafo) can be calculated by using the
following formula:
Generator
Sktrafo =
S kgen =
S r 100
X * d%
The following table gives the approximate values of the short-circuit power of
transformers:
where X*d% is the percentage value of the subtransient reactance (Xd) or of the
transient reactance (Xd) or of the synchronous reactance (Xd), according to the
instant in which the value of the short-circuit power is to be evaluated.
In general, the reactances are expressed in percentages of the rated impedance
of the generator (Zd) given by:
Zd =
Ur
Sr
Sr [kVA]
50
uk%
4
Sktrafo [MVA] 1.3
63
4
1.6
125 160 200 250 320 400 500 630 800 1000 1250 1600 2000 2500 3200 4000
4
4
4
4
4
4
4
4
5
5
5
6
6
6
6
6
3.1
4
5
6.3
8
10 12.5 15.8 16 20
25 26.7 33.3
where Ur and Sr are the rated voltage and power of the generator.
Typical values can be:
- Xd from 10 % to 20 %;
- Xd from 15 % to 40 %;
- Xd from 80 % to 300 %.
Normally, the worst case is considered, that being the subtransient reactance.
The following table gives the approximate values of the short-circuit power of
generators (Xd = 12.5 %):
Cables
A good approximation of the short-circuit power of cables is:
2
S kcable =
216
50
0.4
63
0.5
125 160 200 250 320 400 500 630 800 1000 1250 1600 2000 2500 3200 4000
1.0 1.3 1.6 2.0 2.6 3.2 4.0 5.0 6.4 8.0 10.0 12.8 16.0 20.0 25.6 32.0
Ur
Zc
ZC =
Sr [kVA]
Skgen [MVA]
100
Sr
uk %
RC + X C
The following table gives the approximate values of the short-circuit power of
cables, at 50 and 60 Hz, according to the supply voltage (cable length = 10 m):
217
230 [V]
S [mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
0.44
0.73
1.16
1.75
2.9
4.6
7.2
10.0
13.4
19.1
25.5
31.2
36.2
42.5
49.1
54.2
690 [V]
230 [V]
3.94
6.55
10.47
15.74
26.2
41.5
65.2
90.0
120.8
171.5
229.7
280.4
326.0
382.3
441.5
488.0
0.44
0.73
1.16
1.75
2.9
4.6
7.2
10.0
13.3
18.8
24.8
29.9
34.3
39.5
44.5
48.3
690 [V]
3.94
6.55
10.47
15.73
26.2
41.5
65.0
89.6
119.8
168.8
223.1
269.4
308.8
355.6
400.7
434.7
CB1
With n cables in parallel, it is necessary to multiply the value given in the table
by n. If the length of the cable (Lact) is other than 10 m, it is necessary to
multiply the value given in the table by the following coefficient:
CB2
1SDC010050F0001
CB3
Fault
10
L act
CB1
CB2
1SDC010051F0001
Sk =
Fault
CB3
1
S
i
the short-circuit power of elements in parallel is equal to the sum of the single
short-circuit powers (as for the series of impedances).
Once the short-circuit power equivalent at the fault point has been determined,
the short-circuit current can be calculated by using the following formula:
Sk = S i
The elements of the circuit are considered to be in series or parallel, seeing the
circuit from the fault point.
In the case of different branches in parallel, the distribution of the current between
the different branches shall be calculated once the short-circuit current at the
fault point has been calculated. This must be done to ensure the correct choice
of protection devices installed in the branches.
218
Three-phase short-circuit
Two-phase short-circuit
Ik =
Ik =
Sk
3 Ur
Sk
2 Ur
219
Examples:
The following examples demonstrate the calculation of the short-circuit current
in some different types of installation.
Example 1
Transformer:
140
SkUP = 1000 MVA
SkUP
SkUP =
120
Motor:
110
SkEL
Generic load:
100
Sr = 1600 kVA
uk% = 6%
U1r / U2r =20000/400
CB1
B
Pr = 220 kW
Ikmot/Ir = 6.6
cosr = 0.9
= 0.917
IrL= 1443.4 A
cosr= 0.9
CB2
CB3
90
Ik
80
70
Network:
Transformer:
S ktrafo =
Motor:
S rmot =
60
SkUP = 50 MVA
50
40
SkUP = 40 MVA
30
SkUP = 20 MVA
20
10
SkUP = 10 MVA
0
0
220
10
20
30
40
50
60
70
80
90
1SDC010052F0001
SkUP = 30 MVA
100
S r = 26.7 MVA
uk %
Pr
= 267 kVA
cos r
Skmot = 6.6.Srmot = 1.76 MVA for the first 5-6 periods (at 50 Hz about 100 ms)
Calculation of the short-circuit current for the selection of circuit-breakers
Selection of CB1
For circuit-breaker CB1, the worst condition arises when the fault occurs right
downstream of the circuit-breaker itself. In the case of a fault right upstream,
the circuit-breaker would be involved only by the fault current flowing from the
motor, which is remarkably smaller than the network contribution.
221
1SDC010053F0001
Ik [kA]
150
130
The circuit, seen from the fault point, is represented by the series of the network
with the transformer. According to the previous rules, the short-circuit power is
determined by using the following formula:
Selection of CB2
For circuit-breaker CB2, the worst condition arises when the fault occurs right
downstream of the circuit-breaker itself. The circuit, seen from the fault point, is
represented by the series of the network with the transformer. The short-circuit
current is the same used for CB1.
S kCB1 =
S knet S ktrafo
= 25.35 MVA
S knet + S ktrafo
S kCB1
= 36.6 kA
3 Ur
The rated current of the motor is equal to 385 A; the circuit-breaker to select is
a Tmax T5H 400.
IkCB1 =
S kCB1
= 36.6 kA
3 Ur
The transformer LV side rated current is equal to 2309 A; therefore the circuitbreaker to select is an Emax E3N 2500.
Using the chart shown in Figure 1, it is possible to find IkCB1 from the curve with
SkUP = Sknet = 500 MVA corresponding to SkEL = Sktrafo = 26.7 MVA:
IkCB1 =
Ik [kA]
150
140
Selection of CB3
For CB3 too, the worst condition arises when the fault occurs right downstream
of the circuit-breaker itself.
The circuit, seen from the fault point, is represented by two branches in parallel:
the motor and the series of the network and transformer. According to the
previous rules, the short-circuit power is determined by using the following
formula:
Motor // (Network + Transformer)
130
S kCB3 = S kmot +
1
S knet
120
110
IkCB3 =
100
= 27.11 MVA
1
S ktrafo
S kCB3
= 39.13 kA
3 Ur
The rated current of the load L is equal to 1443 A; the circuit-breaker to select
is a SACE Isomax S7S 1600, or an Emax E2N1600.
90
80
70
Example 2
60
The circuit shown in the diagram is constituted by the supply, two transformers
in parallel and three loads.
50
40
1SDC010054F0001
30
20
10
0
0
10
20
30
40
50
60
70
80
90
100
SkEL [MVA]
CB2
CB1
B
CB3
CB4
CB5
222
Trafo 2
Trafo 1
L2
L3
223
1SDC010055F0001
Ik = 36.5 kA
Transformers 1 and 2
S ktrafo =
Sr
. 100 = 26.7 MVA
uk %
S kbusbar =
I kbusbar =
I kCB1(2) =
S kbusbar
3 Ur
= 69.56 kA
I kbusbar
= 34.78 kA
2
224
The table below allows the determination, in a conservative way, of the threephase short-circuit current at a point in a 400 V network downstream of a
single pole copper cable at a temperature of 20 C. Known values:
- the three-phase short-circuit current upstream of the cable;
- the length and cross section of the cable.
Network
Cable
section
[mm2]
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
2x120
2x150
2x185
3x120
3x150
3x185
Length
[m]
0.8
1
1.2
1.4
1.6
1.8
2
2.4
2.8
3.2
3.6
4.2
4.8
Ik upstream
[kA]
100
96
90
86
80
77
70
68
60
58
50
49
40
39
35
34
30
30
25
25
20
20
15
15
12
12
10
10
8.0
8.0
6.0
6.0
3.0
3.0
1.1
1.5
2
2.4
2.8
3.2
3.7
4
4.8
5.6
6.4
7.2
8.4
10
92
83
75
66
57
48
39
34
29
24
20
15
12
10
7.9
5.9
3.0
0.9
1.2
1.7
2.3
3
3.6
4.2
4.8
5.5
6
7.2
8.4
10
11
13
14
89
81
73
65
56
47
38
34
29
24
20
15
12
10
7.9
5.9
3.0
1.2
1.6
2.3
3.1
4
4.8
5.6
6.4
7.3
8
10
11
13
14
17
19
85
78
71
63
55
46
38
33
29
24
19
15
12
10
7.9
5.9
3.0
0.9
1.4
2
2.8
3.8
5
6
7
8
9.1
10
12
14
16
18
21
24
82
76
69
62
54
45
37
33
28
24
19
15
12
10
7.8
5.9
3.0
1.1
1.7
2.4
3.4
4.6
6
7.2
8.4
10
11
12
14
17
19
22
25
29
0.9
1.5
2.3
3.2
4.5
6.2
8
10
11
13
15
16
19
23
26
29
34
38
78
72
66
60
53
44
37
32
28
24
19
14
12
10
7.8
5.8
3.0
71
67
62
56
50
43
35
32
28
23
19
14
12
10
7.7
5.8
2.9
1.2
1.9
2.9
4
5.7
7.7
10
12
14
16
18
20
24
28
32
36
42
48
65
61
57
53
47
41
34
31
27
23
18
14
11
9.5
7.7
5.8
2.9
0.8
1.4
2.2
3.5
4.8
6.8
9.2
12
14
17
19
22
24
29
34
38
43
51
58
60
57
53
49
45
39
33
30
26
22
18
14
11
9.4
7.6
5.7
2.9
1.1
1.9
3
4.6
6.4
9
12
16
19
23
26
29
32
38
45
51
58
68
77
50
48
46
43
40
35
31
28
25
21
18
14
11
9.2
7.5
5.6
2.9
0.9
1.4
2.3
3.7
5.8
8
11
15
20
24
28
32
37
40
48
56
64
72
84
96
43
42
40
38
36
32
28
26
23
21
17
13
11
9.0
7.4
5.5
2.9
1.2
1.9
2.8
4.7
7.5
12
16
23
31
40
48
56
64
73
80
96
113
128
144
169
192
0.9
1.5
2.3
3.5
5.8
9.3
14
20
28
38
50
60
70
80
91
100
120
141
160
180
211
240
1.1
1.8
2.8
4.2
7
11
17
24
34
46
60
72
84
96
110
120
144
169
192
216
253
288
1.4
2.3
3.7
5.6
9.4
15
23
32
45
62
80
96
113
128
146
160
192
225
256
288
338
384
1.8
2.9
4.7
7
12
19
29
40
57
77
100
120
141
160
183
200
240
281
320
360
422
480
2.5
4.1
6.6
10
16
26
41
56
79
108
140
168
197
224
256
280
336
394
448
505
3.5
5.9
9.4
14
23
37
58
80
113
154
200
240
281
320
366
400
481
563
5.3
8.8
14
21
35
56
87
121
170
231
300
360
422
480
549
7
12
19
28
47
75
116
161
226
308
400
481
9.4
16
25
38
63
100
155
216
303
413
14
24
38
56
94
150
233
324
455
Ik downstream
[kA]
36 31 27 24
35 31 27 24
34 30 27 24
33 29 26 23
31 28 25 23
29 26 23 21
26 24 22 20
24 22 20 19
22 20 19 18
19 18 17 16
16 15 15 14
13 12 12 12
11 10 10 10
8.8 8.5 8.3 8.1
7.2 7.1 6.9 6.8
5.4 5.3 5.2 5.1
2.8 2.8 2.8 2.7
20
20
20
19
19
18
17
16
16
14
13
11
9.3
7.7
6.5
4.9
2.7
17
17
17
16
16
15
15
14
14
13
12
10
8.8
7.3
6.2
4.8
2.6
13
13
13
13
12
12
12
11
11
11
10
8.7
7.8
6.5
5.7
4.4
2.5
11
11
10
10
10
10
10
10
9.3
9.0
8.4
7.6
7.0
5.9
5.2
4.1
2.4
7.8
7.8
7.7
7.6
7.5
7.3
7.1
7.1
7.0
6.8
6.5
6.1
5.7
5.0
4.5
3.6
2.2
5.6
5.6
5.5
5.5
5.4
5.3
5.2
5.1
5.0
5.0
4.8
4.6
4.4
3.9
3.7
3.1
2.0
3.7
3.7
3.7
3.7
3.7
3.6
3.6
3.5
3.5
3.4
3.3
3.2
3.1
2.9
2.8
2.4
1.7
2.7
2.7
2.7
2.7
2.7
2.6
2.6
2.6
2.6
2.6
2.5
2.5
2.4
2.3
2.2
2.0
1.4
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.9
1.9
1.8
1.7
1.6
1.2
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.2
1.2
1.1
0.9
1.2
1.8
2.9
4.7
7.2
10
14
19
25
30
35
40
46
50
60
70
80
90
105
120
0.9
1.4
2.1
3.5
5.6
8.7
12
17
23
30
36
42
48
55
60
72
84
96
108
127
144
1
1.6
2.5
4.1
6.5
10
14
20
27
35
42
49
56
64
70
84
98
112
126
148
168
225
Note:
In the case of the Ik upstream and the length of the cable not being included
in the table, it is necessary to consider:
the value right above Ik upstream;
the value right below for the cable length.
These approximations allow calculations which favour safety.
In the case of cables in parallel not present in the table, the length must be
divided by the number of cables in parallel.
(1)
where:
S is the cross section [mm2];
I is the value (r.m.s) of prospective fault current for a fault of negligible
impedance, which can flow through the protective device [A];
t is the operating time of the protective device for automatic disconnection [s];
k can be evaluated using the tables 27 or calculated according to the formula (2):
Example
Data
Rated voltage =
Cable section =
Conductor =
Length =
I t
2
S=
400 V
120 mm2
copper
29 m
k=
Qc (B+20)
20
ln 1+
f - i
B+i
(2)
where:
Qc is the volumetric heat capacity of conductor material [J/Cmm3] at 20 C;
B is the reciprocal of temperature coefficient of resistivity at 0 C for the
conductor [C];
20 is the electrical resistivity of conductor material at 20 C [mm];
i initial temperature of conductor [C];
f final temperature of conductor [C].
32 kA
400 V
Ik upstream = 32 kA
Cu/PVC
L = 29 m
QF B
Ik downstream = ?
QF C
1SDC010056F0001
120 mm2
B
[C]
Qc
[J/Cmm 3]
20
[mm]
Copper
Aluminium
Lead
Steel
234.5
228
230
202
3.4510-3
2.510-3
1.4510-3
3.810-3
17.24110-6
28.26410-6
21410-6
13810-6
Qc (B+20)
20
226
148
41
78
Procedure
In the row corresponding to the cable cross section 120 mm2, it is possible to
find the column for a length equal to 29 m or right below (in this case 24). In the
column of upstream short-circuit current it is possible to identify the row with a
value of 32 kA or right above (in this case 35). From the intersection of this last
row with the previously identified column, the value of the downstream shortcircuit current can be read as being equal to 26 kA.
226
227
Conductor insulation
Initial temperature C
Final temperature C
Material of conductor:
copper
aluminium
tin-soldered joints
in copper conductors
a
Temperature C b
PVC
300 mm2
70
160
PVC
300 mm2
70
140
EPR
XLPE
90
250
Rubber
60 C
60
200
PVC
70
160
Bare
105
250
115
76
103
68
143
94
141
93
115
-
135/115 a
-
115
Mineral
Conductor insulation
70 C PVC
90 C PVC
90 C thermosetting
60 C rubber
85 C rubber
Silicone rubber
Initial
70
90
90
60
85
180
a
Copper
Conductor insulation
70 C PVC
90 C PVC
90 C thermosetting
60 C rubber
85 C rubber
Silicone rubber
Initial
30
30
30
30
30
30
a
Final
160/140
160/140
250
200
220
350
a
a
143/133 a
143/133 a
176
159
166
201
Aluminium
Value for k
95/88 a
95/88 a
116
105
110
133
Cable covering
PVC
Polyethylene
CSP
Initial
30
30
30
a
228
Final
200
150
220
159
138
166
Steel
42/37 a
36/31 a
52
51
48
47
Material of conductor
Copper
52/49 a
52/49 a
64
58
60
73
Conductor insulation
70 C PVC
90 C PVC
90 C thermosetting
60 C rubber
85 C rubber
Mineral PVC covered a
Mineral bare sheath
Initial
60
80
80
55
75
70
105
a
Final
200
200
200
200
220
200
250
141
128
128
144
140
135
135
Aluminium
Lead
Value for k
93
85
85
95
93
-
Steel
26
23
23
26
26
-
51
46
46
52
51
-
This value shall also be used for bare conductors exposed to touch or in contact with
combustible material.
Material of conductor
Aluminium
Value for k
105
91
110
115/103 a
100/86 a
143
141
134
132
Temperature C
Aluminium
Value for k
76/68 a
66/57 a
94
93
89
87
The lower value applies to PVC insulated conductors of cross section greater than
300 mm2 .
Temperature limits for various types of insulation are given in IEC 60724.
Steel
The lower value applies to PVC insulated conductors of cross section greater than
300 mm2 .
Temperature limits for various types of insulation are given in IEC 60724.
Temperature C a
Final
160/140 a
160/140 a
250
200
220
350
Material of conductor
Material of conductor
Copper
Material of conductor
Steel
58
50
60
Temperature limits for various types of insulation are given in IEC 60724.
Copper
Conductor insulation
Visible and in restricted area
Normal conditions
Fire risk
Aluminium
Steel
Maximum
Maximum
Maximum
Initial
temperature
temperature
temperature
temperature
k value
C
k value
C
k value
C
C
228
500
125
300
82
500
30
159
200
105
200
58
200
30
138
150
91
150
50
150
30
229
Symbol
m
kg
s
A
K
mol
cd
Quantity
Symbol Name
Length, area, volume
Unit name
metre
kilogram
Second
ampere
kelvin
mole
candela
Prefix
yotta
zetta
exa
peta
tera
giga
mega
kilo
etto
deca
Symbol
Y
Z
E
P
T
G
M
k
h
da
Decimal power
10-1
10-2
10-3
10-6
10-9
10-12
10-15
10-18
10-21
10-24
Prefix
deci
centi
milli
mikro
nano
pico
femto
atto
zepto
yocto
Symbol
d
c
m
n
p
f
a
z
y
SI unit
Symbol
Name
Other units
Symbol
Name
Conversion
in
ft
fathom
mile
sm
yd
a
ha
l
UK pt
UK gal
US gal
inch
foot
fathom
mile
sea mile
yard
are
hectare
litre
pint
gallon
gallon
1 in = 25.4 mm
i ft = 30.48 cm
1 fathom = 6 ft = 1.8288 m
1 mile = 1609.344 m
1 sm = 1852 m
1 yd = 91.44 cm
1 a = 102 m2
1 ha = 104 m2
1 l = 1 dm3 = 10-3 m3
1 UK pt = 0.5683 dm3
1 UK gal = 4.5461 dm3
1 US gal = 3.7855 dm3
degrees
1=
lb
pound
1 lb = 0.45359 kg
length
metre
area
m2
square metre
volume
m3
cubic metre
, ,
plane angle
rad
radian
Mass
m
solid angle
sr
steradian
mass, weight
density
kg
kg/m3
specific volume
m3/kg
moment of inertia
kgm2
kilogram
kilogram
cubic metre
for kilogram
kilogram for
square metre
duration
frequency
angular
frequency
s
Hz
second
Hertz
1 Hz = 1/s
1/s
reciprocal second
= 2pf
speed
m/s
Angles
Time
t
f
mile/h
knot
g
acceleration
m/s2
newton
kilometre
per hour
mile per hour
kn
pressure/stress
bar
bar
Hp
horsepower
C
F
Celsius
Fahrenheit
Pa
pascal
W
energy, work
P
power
Temperature and heat
J
W
joule
watt
kelvin
J
J/K
joule
joule per kelvin
cd
cd/m2
lm
lux
candela
candela per square metre
lumen
temperature
Q
quantity of heat
S
entropy
Photometric quantities
I
luminous intensity
L
luminance
luminous flux
E
illuminance
230
1 N = 1 kgm/s2
1 kgf = 9.80665 N
1 Pa = 1 N/m2
1 bar = 105 Pa
1 J = 1 Ws = 1 Nm
1 Hp = 745.7 W
kgf
p
.
rad
180
1 lm = 1 cdsr
1 lux = 1 lm/m2
231
Quantity
Symbol
I
V
R
G
Name
current
voltage
resistance
conductance
SI unit
Symbol Name
A
ampere
V
volt
ohm
S
siemens
reactance
ohm
susceptance
siemens
Z
Y
P
impedance
admittance
active power
S
W
reactive power
var
apparent power
VA
ohm
siemens
watt
reactive volt
ampere
volt ampere
electric charge
coulomb
E
C
H
electric field
V/m
strength
electric capacitance F
magnetic field
A/m
farad
ampere per metre
magnetic induction T
tesla
inductance
henry
Other units
Symbol
Conversion
Name
Ah
ampere/hour
1 C = 1 As
1 Ah = 3600 As
gauss
1 T = 1 Vs/m2
1 G = 10-4 T
1 H = 1 s
Aluminium
Brass, CuZn 40
Constantan
Copper
Gold
Iron wire
Lead
Magnesium
Manganin
Mercury
Ni Cr 8020
Nickeline
Silver
Zinc
232
conductivity
resistivity 20
[mm2 /m]
0.0287
0.067
0.50
0.0175
0.023
0.1 to 0,15
0.208
0.043
0.43
0.941
1
0.43
0.016
0.06
20=1/
20
[m/mm2]
34.84
15
2
57.14
43.5
10 to 6.7
4.81
23.26
2.33
1.06
1
2.33
62.5
16.7
temperature
coefficient 20
[K-1]
3.810-3
210-3
-310-4
3.9510-3
3.810-3
4.510-3
3.910-3
4.110-3
410-6
9.210-4
2.510-4
2.310-4
3.810-3
4.210-3
R=
S
1
conductance of a conductor at temperature G= R =
= 20 [1 + 20 ( 20)]
capacitive reactance
XC= -1 = C
inductive reactance
XL= L = 2 f L
impedance
Z = R + jX
module impedance
Z = R2 + X2
phase impedance
= arctan R
X
conductance
G= 1
R
capacitive susceptance
BC= -1 = C = 2 f C
XC
inductive susceptance
1
BL= -1 = 1 =
2 f L
L
XL
admittance
Y = G jB
module admittance
Y = G2 + B2
phase admittance
= arctan B
G
1
2 f C
+
Z
jXL
R
-jXC
+
Y
jBC
G
-jBL
233
Indipendences in series
Transformers
Z = Z1 + Z 2 + Z 3 +
Z1
Admittances in series
1
Y=
1
1
1
+
+
+
Y1 Y2 Y3
Z2
Y1
Z3
Y2
Y3
Indipendences in parallel
Z=
1
Z1
1
1
1
+
+
+
Z1 Z2 Z3
Z2
Two-winding transformer
rated current
Ir =
short-circuit power
Sk =
short-circuit current
Ik =
longitudinal impedance
ZT =
longitudinal resistance
RT =
longitudinal reactance
XT =
Z3
Sr
3 Ur
Sr
uk%
Sk
3 Ur
uk%
100
pk %
100
100
=
Ir
100
uk%
Sr
u%
U2r
= k
100
3 I2r
Sr
U2r
Sr
p%
= k
100
3 I2r
Sr
ZT2 RT2
Admittances in parallel
Y = Y1 + Y 2 + Y 3 +
Y1
Y2
Y3
Three-winding transformer
1
Z1
Z3
3
Z1
Z12 =
Z12
Z13
Z3
Z2
Z13 =
Z13 = Z3 + Z1 +
234
Z23 =
Z23 = Z2 + Z3 +
u12
100
u13
100
Ur2
Z1 =
Sr12
Ur2
Z2 =
Sr13
1
2
1
2
2
Z23
Z12 = Z1 + Z2 +
Z2
Z1 Z 2
Z3
Z2 Z 3
Z1
Z3 Z 1
Z2
Z1 =
Z2 =
Z3 =
Z12 Z13
u23
100
Ur2
Sr23
Z3 =
1
2
235
voltage drop
percentage
voltage drop
single-phase
three-phase
continuous
U = 2 I (r cos x sin)
U = 3 I (r cos x sin)
U = 2 I r
u =
U
Ur
100
active power
P = U I cos
reactive power
Q = U I sin
apparent power
power factor
power loss
S=UI= P +Q
cos =
P
S
P = 2 r I2
u =
U
Ur
100
u =
Q = 3 U I sin
2
S= 3UI= P +Q
cos =
P
S
P = 3 r I2
Ur
100
P= UI
P = 3 U I cos
P = 2 r I2
Caption
20 resistivity at 20 C
total length of conductor
S
cross section of conductor
20 temperature coefficient of conductor at 20 C
temperature of conductor
resistivity against the conductor temperature
angular frequency
f
frequency
r
resistance of conductor per length unit
x
reactance of conductor per length unit
uk% short-circuit percentage voltage of the transformer
Sr rated apparent power of the transformer
Ur rated voltage of the transformer
pk% percentage impedance losses of the transformer under short-circuit
conditions
236
2 edition
Electrical devices
1SDC010001D0202
Printed in Italy
02/04
1SDC010001D0202
L.V. Breakers
Via Baioni, 35
24123 Bergamo - Italy
Tel.: +39 035.395.111 - Telefax: +39 035.395.306-433
http://www.abb.com
ABB SACE
Electrical devices