AHU L1
CW AHU
VAV
Number of zones
Floor Area
Location
15
1186.3 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
251.9
176.3
13204
15464
16334
0.700
4.7
212.3
8.61
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1500
34.0 / 28.0
25.7 / 19.6
14.6 / 14.1
13.4
0.100
54
16.0
15 of 15
0.0
C
C
C
C
%
C
OK
K
15464 L/s
15424 L/s
13.04 L/(s-m)
29.63 BHP
22.09 kW
1000 Pa
1658 L/s
1.40 L/(s-m)
L/s/person
4.53 L/s/person
Page 1 of 1
07/27/2015
03:22PM
AHU L1
CW AHU
VAV
Number of zones
Floor Area
Location
15
1186.3 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Maximum
Cooling
Sensible
(kW)
10.4
1.8
2.0
1.6
3.0
22.2
8.0
15.0
8.7
17.4
14.5
19.1
1.9
1.9
10.1
Design
Air
Flow
(L/s)
1234
213
233
192
353
2636
949
1782
1030
2061
1724
2272
226
229
1200
Minimum
Air
Flow
(L/s)
66
22
21
8
10
384
139
49
37
119
261
95
6
21
420
Time
of
Peak
Load
Dec 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1500
Aug 1500
Jul 1600
Nov 1600
Jul 1600
Jul 1600
Oct 1500
Aug 1100
Jul 1500
Jul 1600
Jul 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
45.8
32.5
27.2
25.0
34.8
125.8
64.2
80.5
123.3
187.5
113.0
150.0
20.7
28.0
128.0
Zone
L/(s-m)
26.94
6.56
8.56
7.67
10.15
20.95
14.78
22.14
8.35
10.99
15.26
15.15
10.94
8.19
9.38
Zone Name /
Space Name
Zone 1
L1 Baby activity area
Zone 2
L1 BCS/Fire Control
Zone 3
L1 BSS
Zone 4
L1 Corridor 1
Zone 5
L1 Corridor 2+Uti R2
Zone 6
L1 D.Menunggu (Double V)
Zone 7
L1 Female surau
Zone 8
L1 K.Pertanyaan + Office
Zone 9
L1 Lift lobby 1
Zone 10
L1 Main lobby (double V)
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
10.4
Dec 1600
1234
0.0
45.8
26.94
1.8
Jul 1600
213
0.0
32.5
6.56
2.0
Jul 1600
233
0.0
27.2
8.56
1.6
Jul 1600
192
0.0
25.0
7.67
3.0
Jul 1500
353
0.0
34.8
10.15
22.2
Aug 1500
2636
0.0
125.8
20.95
8.0
Jul 1600
949
0.0
64.2
14.78
15.0
Nov 1600
1782
0.0
80.5
22.14
8.7
Jul 1600
1030
0.0
123.3
8.35
12.2
Jul 1500
1446
0.0
97.0
14.91
Page 1 of 2
Zone Name /
Space Name
L1 Main lobby (single V)
Zone 11
L1 Male surau
Zone 12
L1 Office (Double V)
L1 Office (Single V)
Zone 13
L1 Service lobby
Zone 14
L1 Sleeping R+ Prep Area
Zone 15
L1 Taska open area
07/27/2015
03:22PM
Mult.
1
Cooling
Sensible
(kW)
5.2
Time
of
Load
Jul 1600
Air
Flow
(L/s)
616
Heating
Load
(kW)
0.0
Floor
Area
(m)
90.5
Space
L/(s-m)
6.80
14.5
Oct 1500
1724
0.0
113.0
15.26
1
1
6.7
12.6
Sep 1000
Aug 1500
799
1501
0.0
0.0
27.8
122.2
28.74
12.28
1.9
Jul 1500
226
0.0
20.7
10.94
1.9
Jul 1600
229
0.0
28.0
8.19
10.1
Jul 1600
1200
0.0
128.0
9.38
Page 2 of 2
07/27/2015
03:22PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
66
45.8
0.90
5.0
5.00
1.00
66
66
1.000
22
32.5
0.30
5.0
2.50
1.00
22
22
1.000
21
27.2
0.30
5.0
2.50
1.00
21
21
1.000
25.0
0.30
0.0
0.00
1.00
1.000
10
34.8
0.30
0.0
0.00
1.00
10
10
1.000
384
125.8
0.30
91.0
3.80
1.00
384
384
1.000
139
64.2
0.30
48.0
2.50
1.00
139
139
1.000
49
80.5
0.30
10.0
2.50
1.00
49
49
1.000
37
123.3
0.30
0.0
2.50
1.00
37
37
1.000
1
1
54
65
97.0
90.5
0.30
0.30
10.0
15.0
2.50
2.50
1.00
1.00
54
65
54
65
1.000
1.000
261
113.0
0.30
91.0
2.50
1.00
261
261
1.000
1
1
16
79
27.8
122.2
0.30
0.30
3.0
17.0
2.50
2.50
1.00
1.00
16
79
16
79
1.000
1.000
20.7
0.30
0.0
2.50
1.00
1.000
21
28.0
0.30
5.0
2.50
1.00
21
21
1.000
420
1658
128.0
0.90
61.0
5.00
1.00
420
420
1658
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
176 m
19292
5 m
181
0 m
0
176 m
9247
0 m
0
0 m
0
1156 m
21777
1216 m
27758
0 m
0
13049 W
10439
0W
0
16608 W
15126
366
19413
0
0
5% / 5%
6162
129393
135190
0%
0
70%
0
0%
0
13204 L/s
0
1658 L/s
18963
13204 L/s
22109
0
0%
0
176262
176262
176262
Positive values are clg loads
Negative values are htg loads
07/27/2015
03:22PM
Latent
(W)
19730
0
0
986
20716
20716
54871
75587
75593
75593
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
176 m
5 m
0
0 m
0
176 m
0
0 m
0
0 m
0
1156 m
0
1216 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-5768
0
0
0
0
0
0
0
1658 L/s
0
1658 L/s
-5548
-4652
1658 L/s
-11837
0
0%
0
-23153
-4652
-23153
-4652
-23153
-4652
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L2-1
CW AHU
VAV
Number of zones
Floor Area
Location
11
857.9 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
151.0
91.9
6291
6625
6789
0.609
5.7
176.0
5.16
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1500
34.0 / 28.0
26.9 / 21.0
14.7 / 14.3
13.4
0.100
55
16.0
9 of 11
0.1
C
C
C
C
%
C
OK
K
6625 L/s
6608 L/s
7.72 L/(s-m)
1419 L/s
1.65 L/(s-m)
L/s/person
12.69 BHP
9.46 kW
1000 Pa
4.16 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L2-1
CW AHU
VAV
Number of zones
Floor Area
Location
11
857.9 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Maximum
Cooling
Sensible
(kW)
7.1
5.4
1.2
8.1
4.0
3.6
5.2
3.0
6.7
6.9
6.2
Design
Air
Flow
(L/s)
838
637
146
964
471
425
617
352
794
813
731
Minimum
Air
Flow
(L/s)
206
33
5
311
172
36
35
36
52
285
248
Time
of
Peak
Load
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Aug 1600
Nov 1600
Nov 1600
Jul 1600
Dec 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
128.5
108.8
18.1
125.4
67.0
54.0
50.0
52.0
73.2
115.6
65.3
Zone
L/(s-m)
6.52
5.86
8.08
7.69
7.03
7.88
12.33
6.77
10.85
7.04
11.20
Zone Name /
Space Name
Zone 1
L2 Kaunter Pendaftaran 2
Zone 2
L2 Lift Lobby
Zone 3
L2 Service Lobby
Zone 4
L2 Dewan Menunggu 3
Zone 5
L2 Dewan Menunggu 2
Zone 6
L2 Bilik Temuduga 1&2
Zone 7
L2 Bilik Temuduga 3&4
Zone 8
L2 Bilik Temuduga 5&6
Zone 9
L2 Bilik Temuduga 7,8,9
Zone 10
L2 Dewan Menunggu 1
Zone 11
L2 Dewan Menunggu 7
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
7.1
Jul 1600
838
0.0
128.5
6.52
5.4
Jul 1600
637
0.0
108.8
5.86
1.2
Jul 1600
146
0.0
18.1
8.08
8.1
Jul 1600
964
0.0
125.4
7.69
4.0
Jul 1600
471
0.0
67.0
7.03
3.6
Jul 1600
425
0.0
54.0
7.88
5.2
Aug 1600
617
0.0
50.0
12.33
3.0
Nov 1600
352
0.0
52.0
6.77
6.7
Nov 1600
794
0.0
73.2
10.85
6.9
Jul 1600
813
0.0
115.6
7.04
6.2
Dec 1600
731
0.0
65.3
11.20
Page 1 of 1
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
206
128.5
0.30
67.0
2.50
1.00
206
206
1.000
33
108.8
0.30
0.0
2.50
1.00
33
33
1.000
18.1
0.30
0.0
2.50
1.00
1.000
311
125.4
0.30
72.0
3.80
1.00
311
311
1.000
172
67.0
0.30
40.0
3.80
1.00
172
172
1.000
36
54.0
0.30
8.0
2.50
1.00
36
36
1.000
35
50.0
0.30
8.0
2.50
1.00
35
35
1.000
36
52.0
0.30
8.0
2.50
1.00
36
36
1.000
52
73.2
0.30
12.0
2.50
1.00
52
52
1.000
285
115.6
0.30
66.0
3.80
1.00
285
285
1.000
248
1419
65.3
0.30
60.0
3.80
1.00
248
248
1419
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
74 m
5039
166 m
658
0 m
0
74 m
3494
0 m
0
0 m
0
0 m
0
358 m
6545
0 m
0
9437 W
7549
0W
0
12011 W
10938
341
17360
0
0
5% / 5%
2579
54163
66705
0%
0
70%
0
0%
0
6291 L/s
0
1419 L/s
15710
6291 L/s
9513
0
0%
0
91928
91928
91928
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
12900
0
0
645
13545
13545
45502
59047
59051
59051
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
74 m
166 m
0
0 m
0
74 m
0
0 m
0
0 m
0
0 m
0
358 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2333
0
0
0
0
0
0
0
1419 L/s
0
1419 L/s
-7350
0
1419 L/s
-5881
0
0%
0
-15565
0
-15565
0
-15565
0
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L2-2
CW AHU
VAV
Number of zones
Floor Area
Location
9
900.2 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
195.7
111.9
7329
7461
7662
0.572
4.6
217.4
6.69
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1400
33.7 / 27.9
27.5 / 21.7
14.8 / 14.3
13.4
0.100
55
16.0
6 of 9
0.3
C
C
C
C
%
C
OK
K
7461 L/s
7441 L/s
8.29 L/(s-m)
2066 L/s
2.30 L/(s-m)
L/s/person
14.29 BHP
10.66 kW
1000 Pa
4.26 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L2-2
CW AHU
VAV
Number of zones
Floor Area
Location
9
900.2 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Maximum
Cooling
Sensible
(kW)
12.4
21.3
5.9
2.6
4.6
2.9
4.8
3.9
6.3
Design
Air
Flow
(L/s)
1470
2528
696
313
543
343
565
465
742
Minimum
Air
Flow
(L/s)
293
985
52
36
35
36
209
172
249
Time
of
Peak
Load
Nov 1600
Jul 1600
Nov 1500
Nov 1200
Jul 1500
Jul 1500
Jul 1600
Jul 1600
Dec 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
128.5
344.5
73.3
52.1
50.0
54.0
62.2
66.5
69.1
Zone
L/(s-m)
11.44
7.34
9.49
6.01
10.85
6.34
9.08
6.99
10.73
Zone Name /
Space Name
Zone 1
L2 Kaunter Pendaftaran 1
Zone 2
L2 Dewan Menunggu 6
Zone 3
L2 B.Temuduga 10,11,12
Zone 4
L2 Bilik Temuduga 13&14
Zone 5
L2 Bilik Temuduga 15&16
Zone 6
L2 Bilik Temuduga 17&18
Zone 7
L2 Dewan Menunggu 4
Zone 8
L2 Dewan Menunggu 5
Zone 9
L2 Dewan Menunggu 8
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
12.4
Nov 1600
1470
0.0
128.5
11.44
21.3
Jul 1600
2528
0.0
344.5
7.34
5.9
Nov 1500
696
0.0
73.3
9.49
2.6
Nov 1200
313
0.0
52.1
6.01
4.6
Jul 1500
543
0.0
50.0
10.85
2.9
Jul 1500
343
0.0
54.0
6.34
4.8
Jul 1600
565
0.0
62.2
9.08
3.9
Jul 1600
465
0.0
66.5
6.99
6.3
Dec 1600
742
0.0
69.1
10.73
Page 1 of 1
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
293
128.5
0.30
67.0
3.80
1.00
293
293
1.000
985
344.5
0.30
232.0
3.80
1.00
985
985
1.000
52
73.3
0.30
12.0
2.50
1.00
52
52
1.000
36
52.1
0.30
8.0
2.50
1.00
36
36
1.000
35
50.0
0.30
8.0
2.50
1.00
35
35
1.000
36
54.0
0.30
8.0
2.50
1.00
36
36
1.000
209
62.2
0.30
50.0
3.80
1.00
209
209
1.000
172
66.5
0.30
40.0
3.80
1.00
172
172
1.000
249
2066
69.1
0.30
60.0
3.80
1.00
249
249
2066
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1400
COOLING OA DB / WB 33.7 C / 27.9 C
Sensible
Details
(W)
110 m
6291
250 m
980
0 m
0
110 m
5051
0 m
0
0 m
0
0 m
0
90 m
1590
0 m
0
9902 W
7782
0W
0
12603 W
11399
485
24063
0
0
5% / 5%
2858
60014
79483
0%
0
70%
0
0%
0
7329 L/s
0
2066 L/s
21700
7329 L/s
10677
0
0%
0
111861
111861
111861
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
17968
0
0
898
18867
18867
64954
83821
83835
83835
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
110 m
250 m
0
0 m
0
110 m
0
0 m
0
0 m
0
0 m
0
90 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2455
0
0
0
0
0
0
0
2066 L/s
0
2066 L/s
-11643
0
2066 L/s
-7158
0
0%
0
-21256
0
-21256
0
-21256
0
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L3-1
CW AHU
VAV
Number of zones
Floor Area
Location
12
1139.4 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
162.0
108.3
7794
8165
8199
0.669
7.0
142.2
5.54
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jun 1500
33.4 / 28.0
26.3 / 20.1
14.8 / 14.2
13.5
0.100
53
16.0
9 of 12
0.2
C
C
C
C
%
C
OK
K
8165 L/s
8144 L/s
7.17 L/(s-m)
1249 L/s
1.10 L/(s-m)
L/s/person
15.64 BHP
11.67 kW
1000 Pa
5.55 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L3-1
CW AHU
VAV
Number of zones
Floor Area
Location
12
1139.4 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Maximum
Cooling
Sensible
(kW)
2.2
7.0
7.1
1.9
10.9
12.1
10.5
1.5
6.4
5.4
1.2
2.8
Design
Air
Flow
(L/s)
262
829
845
228
1294
1436
1248
180
762
636
146
333
Minimum
Air
Flow
(L/s)
12
162
24
20
270
389
270
18
25
33
5
20
Time
of
Peak
Load
Jul 1600
Jun 1600
Jun 1600
Jul 1600
Jun 1600
Jun 1600
Jun 1600
Jul 1600
Jun 1500
Jul 1600
Jul 1600
Jul 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
40.5
86.5
81.0
67.4
190.0
143.7
190.0
60.3
84.5
110.0
18.1
67.4
Zone
L/(s-m)
6.48
9.58
10.43
3.38
6.81
10.00
6.57
2.99
9.02
5.78
8.08
4.94
Zone Name /
Space Name
Zone 1
L3 Bilik bakat
Zone 2
L3 Latihan komputer 1
Zone 3
L3 Bilik pemeriksaan (P)
Zone 4
L3 Corridor 1
Zone 5
L3 Dewan peperiksaan 2
Zone 6
L3 Ruang Menunggu
Zone 7
L3 Dewan peperiksaan 1
Zone 8
L3 Corridor 2
Zone 9
L3 Bilik pemeriksaan (L)
Zone 10
L3 Lift Lobby
Zone 11
L3 Service Lobby
Zone 12
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.2
Jul 1600
262
0.0
40.5
6.48
7.0
Jun 1600
829
0.0
86.5
9.58
7.1
Jun 1600
845
0.0
81.0
10.43
1.9
Jul 1600
228
0.0
67.4
3.38
10.9
Jun 1600
1294
0.0
190.0
6.81
12.1
Jun 1600
1436
0.0
143.7
10.00
10.5
Jun 1600
1248
0.0
190.0
6.57
1.5
Jul 1600
180
0.0
60.3
2.99
6.4
Jun 1500
762
0.0
84.5
9.02
5.4
Jul 1600
636
0.0
110.0
5.78
1.2
Jul 1600
146
0.0
18.1
8.08
Page 1 of 2
Zone Name /
Space Name
L3 Corridor 5+Pantry
Mult.
1
07/27/2015
02:46PM
Cooling
Sensible
(kW)
2.8
Time
of
Load
Jul 1600
Air
Flow
(L/s)
333
Heating
Load
(kW)
0.0
Floor
Area
(m)
67.4
Space
L/(s-m)
4.94
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
12
40.5
0.30
0.0
2.50
1.00
12
12
1.000
162
86.5
0.60
22.0
5.00
1.00
162
162
1.000
24
81.0
0.30
0.0
2.50
1.00
24
24
1.000
20
67.4
0.30
0.0
0.00
1.00
20
20
1.000
270
190.0
0.30
56.0
3.80
1.00
270
270
1.000
389
143.7
0.30
91.0
3.80
1.00
389
389
1.000
270
190.0
0.30
56.0
3.80
1.00
270
270
1.000
18
60.3
0.30
0.0
0.00
1.00
18
18
1.000
25
84.5
0.30
0.0
2.50
1.00
25
25
1.000
33
110.0
0.30
0.0
2.50
1.00
33
33
1.000
18.1
0.30
0.0
2.50
1.00
1.000
20
1249
67.4
0.30
0.0
0.00
1.00
20
20
1249
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Jun 1500
COOLING OA DB / WB 33.4 C / 28.0 C
Sensible
Details
(W)
144 m
13930
251 m
1050
0 m
0
144 m
6397
0 m
0
0 m
0
0 m
0
364 m
6286
0 m
0
12533 W
10026
0W
0
15952 W
14528
225
11818
0
0
5% / 5%
3202
67236
83799
0%
0
70%
0
0%
0
7794 L/s
0
1249 L/s
12806
7794 L/s
11718
0
0%
0
108324
108324
108324
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
11257
0
0
563
11819
11819
41890
53709
53710
53710
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
144 m
251 m
0
0 m
0
144 m
0
0 m
0
0 m
0
0 m
0
364 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2423
0
0
0
0
0
0
0
1249 L/s
0
1249 L/s
-6100
-734
1249 L/s
-6677
0
0%
0
-15200
-734
-15200
-734
-15200
-734
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L3-2
CW AHU
VAV
Number of zones
Floor Area
Location
16
1204.8 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
163.1
107.2
7765
8292
8570
0.657
7.4
135.4
5.58
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1400
33.7 / 27.9
26.2 / 20.2
14.7 / 14.2
13.5
0.100
54
16.0
13 of 16
0.2
C
C
C
C
%
C
OK
K
8292 L/s
8271 L/s
6.88 L/(s-m)
1232 L/s
1.02 L/(s-m)
L/s/person
15.89 BHP
11.85 kW
1000 Pa
4.81 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L3-2
CW AHU
VAV
Number of zones
Floor Area
Location
16
1204.8 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Maximum
Cooling
Sensible
(kW)
3.6
3.1
2.0
4.5
1.7
9.4
2.4
1.8
1.6
2.0
10.4
10.8
1.9
6.2
3.4
7.2
Design
Air
Flow
(L/s)
424
368
243
538
197
1119
282
217
195
235
1235
1283
227
739
409
860
Minimum
Air
Flow
(L/s)
32
35
37
38
29
82
50
36
30
34
142
395
23
60
47
162
Time
of
Peak
Load
Jul 1600
Jun 1200
Nov 1600
Sep 1100
Oct 1600
Dec 1500
Jul 1600
Jul 1600
Jan 1600
Dec 1200
Dec 1600
Dec 1600
Jul 1600
Dec 1600
Sep 1600
Nov 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
107.0
49.2
48.8
36.6
46.2
139.0
50.0
52.0
59.1
57.4
131.1
177.0
75.3
49.3
40.0
86.8
Zone
L/(s-m)
3.96
7.49
4.98
14.69
4.27
8.05
5.64
4.17
3.29
4.10
9.42
7.25
3.01
15.00
10.22
9.90
Zone Name /
Space Name
Zone 1
L3 Corridor 3
Zone 2
L3 M52+ruang kerja
Zone 3
L3 M52+bilik PA
Zone 4
L3 M54
Zone 5
L3 M52+bilik fail
Zone 6
L3 Open office
Zone 7
L3 B.perbincangan+stor
Zone 8
L3 Ruang tamu mes.
Zone 9
L3 Kaunter pertanyaan
Zone 10
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
3.6
Jul 1600
424
0.0
107.0
3.96
3.1
Jun 1200
368
0.0
49.2
7.49
2.0
Nov 1600
243
0.0
48.8
4.98
4.5
Sep 1100
538
0.0
36.6
14.69
1.7
Oct 1600
197
0.0
46.2
4.27
9.4
Dec 1500
1119
0.0
139.0
8.05
2.4
Jul 1600
282
0.0
50.0
5.64
1.8
Jul 1600
217
0.0
52.0
4.17
1.6
Jan 1600
195
0.0
59.1
3.29
Page 1 of 2
Zone Name /
Space Name
L3 Bilik fail
Zone 11
L3 Bilik mesyuarat bah.
Zone 12
L3 Bilik latihan ASPA
Zone 13
L3 Corridor 4
Zone 14
L3 Bilik Bengkel
Zone 15
L3 Bilik Kaunseling
Zone 16
L3 Latihan komputer 2
07/27/2015
02:46PM
Mult.
1
Cooling
Sensible
(kW)
2.0
Time
of
Load
Dec 1200
Air
Flow
(L/s)
235
Heating
Load
(kW)
0.0
Floor
Area
(m)
57.4
Space
L/(s-m)
4.10
10.4
Dec 1600
1235
0.0
131.1
9.42
10.8
Dec 1600
1283
0.0
177.0
7.25
1.9
Jul 1600
227
0.0
75.3
3.01
6.2
Dec 1600
739
0.0
49.3
15.00
3.4
Sep 1600
409
0.0
40.0
10.22
7.2
Nov 1600
860
0.0
86.8
9.90
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
32
107.0
0.30
0.0
0.00
1.00
32
32
1.000
35
49.2
0.30
8.0
2.50
1.00
35
35
1.000
37
48.8
0.30
9.0
2.50
1.00
37
37
1.000
38
36.6
0.30
11.0
2.50
1.00
38
38
1.000
29
46.2
0.30
6.0
2.50
1.00
29
29
1.000
82
139.0
0.30
16.0
2.50
1.00
82
82
1.000
50
50.0
0.30
14.0
2.50
1.00
50
50
1.000
36
52.0
0.30
8.0
2.50
1.00
36
36
1.000
30
59.1
0.30
5.0
2.50
1.00
30
30
1.000
34
57.4
0.60
0.0
0.00
1.00
34
34
1.000
142
131.1
0.30
41.0
2.50
1.00
142
142
1.000
395
177.0
0.30
90.0
3.80
1.00
395
395
1.000
23
75.3
0.30
0.0
0.00
1.00
23
23
1.000
60
49.3
0.30
12.0
3.80
1.00
60
60
1.000
47
40.0
0.30
14.0
2.50
1.00
47
47
1.000
162
1232
86.8
0.60
22.0
5.00
1.00
162
162
1232
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1400
COOLING OA DB / WB 33.7 C / 27.9 C
Sensible
Details
(W)
179 m
9373
314 m
1183
0 m
0
179 m
8199
0 m
0
0 m
0
0 m
0
130 m
2355
0 m
0
13253 W
10415
0W
0
16867 W
15256
256
13465
0
0
5% / 5%
3012
63258
81985
0%
0
70%
0
0%
0
7765 L/s
0
1232 L/s
13296
7765 L/s
11922
0
0%
0
107203
107203
107203
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
15386
0
0
769
16155
16155
39767
55922
55934
55934
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
179 m
314 m
0
0 m
0
179 m
0
0 m
0
0 m
0
0 m
0
130 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2840
0
0
0
0
0
0
0
1232 L/s
0
1232 L/s
-5568
-922
1232 L/s
-6739
0
0%
0
-15147
-922
-15147
-922
-15147
-922
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L4-1
CW AHU
VAV
Number of zones
Floor Area
Location
18
1300.6 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
114.0
95.9
7618
7780
7881
0.841
11.4
87.6
3.90
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jul 0800
26.4 / 26.2
25.2 / 18.6
14.8 / 14.2
13.6
0.100
50
16.0
5 of 18
0.9
C
C
C
C
%
C
OK
K
7780 L/s
7760 L/s
5.98 L/(s-m)
14.91 BHP
11.12 kW
1000 Pa
642 L/s
0.49 L/(s-m)
L/s/person
16.06 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L4-1
CW AHU
VAV
Number of zones
Floor Area
Location
18
1300.6 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Zone 18
Maximum
Cooling
Sensible
(kW)
4.9
1.2
2.6
1.6
7.1
1.0
1.4
3.9
11.7
4.1
1.4
1.7
2.1
5.7
3.3
5.4
1.2
6.1
Design
Air
Flow
(L/s)
582
142
304
187
843
113
165
466
1386
491
165
199
244
679
397
643
147
729
Minimum
Air
Flow
(L/s)
64
24
18
37
31
19
18
51
125
53
18
24
21
25
39
33
5
36
Time
of
Peak
Load
Jul 1600
Jul 1600
Jun 1600
Jul 1600
Jun 1600
Jul 1600
Jan 1600
Jun 1600
Jun 1600
Jun 1600
Jan 1600
Jul 1600
Jul 1600
Jul 1100
Jun 1200
Jul 1600
Jul 1600
Sep 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
131.5
39.5
44.5
61.5
68.6
32.2
60.8
85.0
208.2
89.1
61.0
63.3
71.6
48.6
54.7
110.0
18.1
52.4
Zone
L/(s-m)
4.42
3.60
6.83
3.05
12.29
3.51
2.71
5.48
6.66
5.51
2.71
3.14
3.41
13.98
7.25
5.85
8.12
13.92
Zone Name /
Space Name
Zone 1
L4 Open office 2
Zone 2
L4 Bilik utiliti L&P
Zone 3
L4 Bilik penyediaan dok1
Zone 4
L4 Bilik setor 1&2
Zone 5
L4 Ruang kerja unit 1&2
Zone 6
L4 Bilik setor 3
Zone 7
L4 Corridor 1
Zone 8
L4 Bilik fail sulit
Zone 9
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
4.9
Jul 1600
582
0.0
131.5
4.42
1.2
Jul 1600
142
0.0
39.5
3.60
2.6
Jun 1600
304
0.0
44.5
6.83
1.6
Jul 1600
187
0.0
61.5
3.05
7.1
Jun 1600
843
0.0
68.6
12.29
1.0
Jul 1600
113
0.0
32.2
3.51
1.4
Jan 1600
165
0.0
60.8
2.71
3.9
Jun 1600
466
0.0
85.0
5.48
Page 1 of 2
Zone Name /
Space Name
L4 Bilik fail terbuka
Zone 10
L4 Bilik fail tertutup
Zone 11
L4 Corridor 2
Zone 12
L4 Bilik pakej
Zone 13
L4 B.surat tawaran+util
Zone 14
L4 Ruang kerja unit 3&4
Zone 15
L4 M52+Bilik PA
Zone 16
L4 Lift Lobby
Zone 17
L4 Service Lobby
Zone 18
L4 Open office 7
07/27/2015
02:46PM
Mult.
1
Cooling
Sensible
(kW)
11.7
Time
of
Load
Jun 1600
Air
Flow
(L/s)
1386
Heating
Load
(kW)
0.0
Floor
Area
(m)
208.2
Space
L/(s-m)
6.66
4.1
Jun 1600
491
0.0
89.1
5.51
1.4
Jan 1600
165
0.0
61.0
2.71
1.7
Jul 1600
199
0.0
63.3
3.14
2.1
Jul 1600
244
0.0
71.6
3.41
5.7
Jul 1100
679
0.0
48.6
13.98
3.3
Jun 1200
397
0.0
54.7
7.25
5.4
Jul 1600
643
0.0
110.0
5.85
1.2
Jul 1600
147
0.0
18.1
8.12
6.1
Sep 1600
729
0.0
52.4
13.92
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Page 1 of 2
07/27/2015
02:46PM
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
64
131.5
0.30
10.0
2.50
1.00
64
64
1.000
24
39.5
0.60
0.0
0.00
1.00
24
24
1.000
18
44.5
0.30
2.0
2.50
1.00
18
18
1.000
37
61.5
0.60
0.0
0.00
1.00
37
37
1.000
31
68.6
0.30
4.0
2.50
1.00
31
31
1.000
19
32.2
0.60
0.0
0.00
1.00
19
19
1.000
18
60.8
0.30
0.0
0.00
1.00
18
18
1.000
51
85.0
0.60
0.0
0.00
1.00
51
51
1.000
125
208.2
0.60
1.0
0.00
1.00
125
125
1.000
53
89.1
0.60
0.0
0.00
1.00
53
53
1.000
18
61.0
0.30
0.0
0.00
1.00
18
18
1.000
24
63.3
0.30
2.0
2.50
1.00
24
24
1.000
21
71.6
0.30
0.0
2.50
1.00
21
21
1.000
25
48.6
0.30
4.0
2.50
1.00
25
25
1.000
39
54.7
0.30
9.0
2.50
1.00
39
39
1.000
33
110.0
0.30
0.0
2.50
1.00
33
33
1.000
18.1
0.30
0.0
2.50
1.00
1.000
36
642
52.4
0.30
8.0
2.50
1.00
36
36
642
1.000
1.000
Page 2 of 2
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Jul 0800
COOLING OA DB / WB 26.4 C / 26.2 C
Sensible
Details
(W)
173 m
8867
281 m
679
0 m
0
173 m
3390
0 m
0
0 m
0
0 m
0
334 m
3929
0 m
0
14307 W
9701
0W
0
18208 W
15593
40
1717
0
0
5% / 5%
2194
46070
84033
0%
0
70%
0
0%
0
7618 L/s
0
459 L/s
706
7618 L/s
11138
0
0%
0
95878
95878
95878
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
2404
0
0
120
2524
2524
15566
18090
18077
18077
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
173 m
281 m
0
0 m
0
173 m
0
0 m
0
0 m
0
0 m
0
334 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2233
0
0
0
0
0
0
0
642 L/s
0
642 L/s
-2150
-3068
642 L/s
-5716
0
0%
0
-10099
-3068
-10099
-3068
-10099
-3068
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L4-2
CW AHU
VAV
Number of zones
Floor Area
Location
14
1048.5 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
110.1
81.0
6087
6717
6938
0.735
9.5
105.0
3.76
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1500
34.0 / 28.0
25.7 / 19.3
14.7 / 14.1
13.5
0.100
52
16.0
10 of 14
0.3
C
C
C
C
%
C
OK
K
6717 L/s
6700 L/s
6.41 L/(s-m)
645 L/s
0.62 L/(s-m)
L/s/person
12.87 BHP
9.60 kW
1000 Pa
5.33 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L4-2
CW AHU
VAV
Number of zones
Floor Area
Location
14
1048.5 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Maximum
Cooling
Sensible
(kW)
1.7
5.4
1.0
1.7
10.8
1.6
1.7
1.4
6.3
3.3
4.0
9.8
6.2
3.6
Design
Air
Flow
(L/s)
201
638
118
199
1284
193
197
166
749
389
472
1164
740
427
Minimum
Air
Flow
(L/s)
18
42
15
25
214
30
45
32
14
41
41
65
38
25
Time
of
Peak
Load
Jul 1600
Sep 1100
Jul 1600
Dec 1200
Jul 1600
Jan 1600
Jul 1600
Jan 1600
Nov 1600
Nov 1600
Dec 1600
Dec 1600
Dec 1500
Aug 1100
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
60.3
47.0
25.6
33.7
330.4
58.6
34.7
41.0
48.1
67.8
68.8
99.1
67.6
65.8
Zone
L/(s-m)
3.33
13.57
4.61
5.92
3.89
3.30
5.67
4.05
15.58
5.73
6.87
11.74
10.95
6.49
Zone Name /
Space Name
Zone 1
L4 Corridor 3
Zone 2
L4 M54
Zone 3
L4 Bilik utiliti 2
Zone 4
L4 M48
Zone 5
L4 Open office 1
Zone 6
L4 Kaunter pertanyaan
Zone 7
L4 B. perbincangan+util
Zone 8
L4 Bilik temuduga 1&2
Zone 9
L4 Bilik rujukan+mesin
Zone 10
L4 Bilik utiliti R
Zone 11
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.7
Jul 1600
201
0.0
60.3
3.33
5.4
Sep 1100
638
0.0
47.0
13.57
1.0
Jul 1600
118
0.0
25.6
4.61
1.7
Dec 1200
199
0.0
33.7
5.92
10.8
Jul 1600
1284
0.0
330.4
3.89
1.6
Jan 1600
193
0.0
58.6
3.30
1.7
Jul 1600
197
0.0
34.7
5.67
1.4
Jan 1600
166
0.0
41.0
4.05
6.3
Nov 1600
749
0.0
48.1
15.58
3.3
Nov 1600
389
0.0
67.8
5.73
Page 1 of 2
Zone Name /
Space Name
L4 Open office 3
Zone 12
L4 Open office 4
Zone 13
L4 Open office 5
Zone 14
L4 Open office 6
07/27/2015
02:46PM
Mult.
1
Cooling
Sensible
(kW)
4.0
Time
of
Load
Dec 1600
Air
Flow
(L/s)
472
Heating
Load
(kW)
0.0
Floor
Area
(m)
68.8
Space
L/(s-m)
6.87
9.8
Dec 1600
1164
0.0
99.1
11.74
6.2
Dec 1500
740
0.0
67.6
10.95
3.6
Aug 1100
427
0.0
65.8
6.49
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
18
60.3
0.30
0.0
0.00
1.00
18
18
1.000
42
47.0
0.30
11.0
2.50
1.00
42
42
1.000
15
25.6
0.60
0.0
0.00
1.00
15
15
1.000
25
33.7
0.30
6.0
2.50
1.00
25
25
1.000
214
330.4
0.30
46.0
2.50
1.00
214
214
1.000
30
58.6
0.30
5.0
2.50
1.00
30
30
1.000
45
34.7
0.30
14.0
2.50
1.00
45
45
1.000
32
41.0
0.30
8.0
2.50
1.00
32
32
1.000
14
48.1
0.30
0.0
2.50
1.00
14
14
1.000
41
67.8
0.60
0.0
0.00
1.00
41
41
1.000
41
68.8
0.30
8.0
2.50
1.00
41
41
1.000
65
99.1
0.30
14.0
2.50
1.00
65
65
1.000
38
67.6
0.30
7.0
2.50
1.00
38
38
1.000
25
645
65.8
0.30
2.0
2.50
1.00
25
25
645
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
167 m
9379
262 m
1069
0 m
0
167 m
7862
0 m
0
0 m
0
0 m
0
98 m
1769
0 m
0
11534 W
9226
0W
0
14679 W
13369
121
6517
0
0
5% / 5%
2460
51651
64083
0%
0
70%
0
0%
0
6087 L/s
0
645 L/s
7189
6087 L/s
9686
0
0%
0
80959
80959
80959
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
7272
0
0
364
7636
7636
21524
29160
29159
29159
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
167 m
262 m
0
0 m
0
167 m
0
0 m
0
0 m
0
0 m
0
98 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-1934
0
0
0
0
0
0
0
645 L/s
0
645 L/s
-2467
-2325
645 L/s
-5052
0
0%
0
-9453
-2325
-9453
-2325
-9453
-2325
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L5-1
CW AHU
VAV
Number of zones
Floor Area
Location
14
1233.9 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
130.5
99.8
7551
8105
8188
0.764
9.5
105.8
4.46
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jul 1500
34.0 / 28.0
25.7 / 19.1
14.7 / 14.1
13.5
0.100
52
16.0
10 of 14
0.2
C
C
C
C
%
C
OK
K
8105 L/s
8084 L/s
6.57 L/(s-m)
702 L/s
0.57 L/(s-m)
L/s/person
15.53 BHP
11.58 kW
1000 Pa
6.21 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L5-1
CW AHU
VAV
Number of zones
Floor Area
Location
14
1233.9 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Maximum
Cooling
Sensible
(kW)
5.0
2.0
6.8
9.4
6.1
2.0
1.3
2.1
1.7
1.5
5.4
1.2
10.1
14.4
Design
Air
Flow
(L/s)
590
239
810
1115
725
234
152
248
199
184
643
147
1198
1704
Minimum
Air
Flow
(L/s)
56
30
37
197
22
36
26
50
36
24
33
5
69
81
Time
of
Peak
Load
Jul 1600
Jul 1600
Jun 1600
Jan 1600
Jun 1200
Jul 1600
Jan 1600
Jul 1600
Jul 1600
Aug 1500
Jul 1600
Jul 1600
Sep 1600
Jun 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
135.0
65.8
61.5
305.0
56.7
52.1
43.4
50.0
60.5
40.8
110.0
18.1
98.3
136.7
Zone
L/(s-m)
4.37
3.64
13.17
3.66
12.78
4.48
3.50
4.96
3.29
4.50
5.85
8.12
12.19
12.47
Zone Name /
Space Name
Zone 1
L5 Open office 1
Zone 2
L5 B. utiliti L&P+Temu3
Zone 3
L5 Bilik fail
Zone 4
L5 Open office 2
Zone 5
L5 Ruang kerja unit 1&2
Zone 6
L5 Bilik temujanji 1&2
Zone 7
L5 Ruang Menunggu 2
Zone 8
L5 Bilik perbincangan
Zone 9
L5 Bilik fail sulit per.
Zone 10
L5 Bilik mesin
Zone 11
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
5.0
Jul 1600
590
0.0
135.0
4.37
2.0
Jul 1600
239
0.0
65.8
3.64
6.8
Jun 1600
810
0.0
61.5
13.17
9.4
Jan 1600
1115
0.0
305.0
3.66
6.1
Jun 1200
725
0.0
56.7
12.78
2.0
Jul 1600
234
0.0
52.1
4.48
1.3
Jan 1600
152
0.0
43.4
3.50
2.1
Jul 1600
248
0.0
50.0
4.96
1.7
Jul 1600
199
0.0
60.5
3.29
1.5
Aug 1500
184
0.0
40.8
4.50
Page 1 of 2
Zone Name /
Space Name
L5 Lift Lobby
Zone 12
L5 Service Lobby
Zone 13
L5 Open office 5
Zone 14
L5 Open office 6
07/27/2015
02:46PM
Mult.
1
Cooling
Sensible
(kW)
5.4
Time
of
Load
Jul 1600
Air
Flow
(L/s)
643
Heating
Load
(kW)
0.0
Floor
Area
(m)
110.0
Space
L/(s-m)
5.85
1.2
Jul 1600
147
0.0
18.1
8.12
10.1
Sep 1600
1198
0.0
98.3
12.19
14.4
Jun 1600
1704
0.0
136.7
12.47
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
56
135.0
0.30
6.0
2.50
1.00
56
56
1.000
30
65.8
0.30
4.0
2.50
1.00
30
30
1.000
37
61.5
0.60
0.0
0.00
1.00
37
37
1.000
197
305.0
0.30
42.0
2.50
1.00
197
197
1.000
22
56.7
0.30
2.0
2.50
1.00
22
22
1.000
36
52.1
0.30
8.0
2.50
1.00
36
36
1.000
26
43.4
0.30
5.0
2.50
1.00
26
26
1.000
50
50.0
0.30
14.0
2.50
1.00
50
50
1.000
36
60.5
0.60
0.0
0.00
1.00
36
36
1.000
24
40.8
0.60
0.0
0.00
1.00
24
24
1.000
33
110.0
0.30
0.0
2.50
1.00
33
33
1.000
18.1
0.30
0.0
2.50
1.00
1.000
69
98.3
0.30
16.0
2.50
1.00
69
69
1.000
81
702
136.7
0.30
16.0
2.50
1.00
81
81
702
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Jul 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
174 m
15064
268 m
1163
0 m
0
174 m
8230
0 m
0
0 m
0
0 m
0
334 m
6024
0 m
0
13573 W
10858
0W
0
17275 W
15733
113
6086
0
0
5% / 5%
3158
66315
80408
0%
0
70%
0
0%
0
7551 L/s
0
702 L/s
7734
7551 L/s
11657
0
0%
0
99800
99800
99800
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
6791
0
0
340
7131
7131
23619
30750
30746
30746
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
174 m
268 m
0
0 m
0
174 m
0
0 m
0
0 m
0
0 m
0
334 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2197
0
0
0
0
0
0
0
702 L/s
0
702 L/s
-2589
-3086
702 L/s
-5996
0
0%
0
-10783
-3086
-10783
-3086
-10783
-3086
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L5-2
CW AHU
VAV
Number of zones
Floor Area
Location
15
1106.4 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
116.4
85.3
6438
7006
7342
0.733
9.5
105.2
3.98
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1400
33.7 / 27.9
25.7 / 19.4
14.7 / 14.1
13.5
0.100
53
16.0
11 of 15
0.2
C
C
C
C
%
C
OK
K
7006 L/s
6988 L/s
6.33 L/(s-m)
687 L/s
0.62 L/(s-m)
L/s/person
13.42 BHP
10.01 kW
1000 Pa
5.29 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L5-2
CW AHU
VAV
Number of zones
Floor Area
Location
15
1106.4 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Maximum
Cooling
Sensible
(kW)
2.6
3.2
5.5
1.7
3.7
1.7
1.5
1.7
1.0
9.7
6.2
6.6
5.6
5.1
6.1
Design
Air
Flow
(L/s)
308
383
658
206
435
196
182
198
117
1156
738
778
664
602
722
Minimum
Air
Flow
(L/s)
26
34
41
25
69
31
30
31
16
142
114
19
41
41
27
Time
of
Peak
Load
Jul 1600
Jun 1200
Sep 1100
Dec 1200
Jan 1600
Jul 1600
Jul 1600
Jan 1600
Jan 1600
Dec 1600
Jul 1600
Nov 1600
Dec 1600
Dec 1500
Nov 1100
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
88.3
54.4
46.0
34.0
130.0
51.2
50.3
60.3
38.0
130.0
205.0
47.7
61.0
61.0
49.2
Zone
L/(s-m)
3.49
7.05
14.29
6.06
3.35
3.83
3.62
3.28
3.07
8.89
3.60
16.30
10.89
9.87
14.68
Zone Name /
Space Name
Zone 1
L5 Corridor 1
Zone 2
L5 M52+Bilik PA
Zone 3
L5 M54
Zone 4
L5 M48
Zone 5
L5 Open office 3
Zone 6
L5 Bilik utiliti+setor
Zone 7
L5 Bilik rujukan+fail
Zone 8
L5 Ruang Menunggu 1
Zone 9
L5 Bilik pakej
Zone 10
L5 Bilik mesyuarat bah.
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.6
Jul 1600
308
0.0
88.3
3.49
3.2
Jun 1200
383
0.0
54.4
7.05
5.5
Sep 1100
658
0.0
46.0
14.29
1.7
Dec 1200
206
0.0
34.0
6.06
3.7
Jan 1600
435
0.0
130.0
3.35
1.7
Jul 1600
196
0.0
51.2
3.83
1.5
Jul 1600
182
0.0
50.3
3.62
1.7
Jan 1600
198
0.0
60.3
3.28
1.0
Jan 1600
117
0.0
38.0
3.07
9.7
Dec 1600
1156
0.0
130.0
8.89
Page 1 of 2
Zone Name /
Space Name
Zone 11
L5 Open office 4
Zone 12
L5 Ruang kerja unit 3&4
Zone 13
L5 Open office 7
Zone 14
L5 Open office 8
Zone 15
L5 Open office 9
07/27/2015
02:46PM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
6.2
Jul 1600
738
0.0
205.0
3.60
6.6
Nov 1600
778
0.0
47.7
16.30
5.6
Dec 1600
664
0.0
61.0
10.89
5.1
Dec 1500
602
0.0
61.0
9.87
6.1
Nov 1100
722
0.0
49.2
14.68
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
26
88.3
0.30
0.0
0.00
1.00
26
26
1.000
34
54.4
0.30
7.0
2.50
1.00
34
34
1.000
41
46.0
0.30
11.0
2.50
1.00
41
41
1.000
25
34.0
0.30
6.0
2.50
1.00
25
25
1.000
69
130.0
0.30
12.0
2.50
1.00
69
69
1.000
31
51.2
0.60
0.0
0.00
1.00
31
31
1.000
30
50.3
0.60
0.0
0.00
1.00
30
30
1.000
31
60.3
0.30
5.0
2.50
1.00
31
31
1.000
16
38.0
0.30
2.0
2.50
1.00
16
16
1.000
142
130.0
0.30
41.0
2.50
1.00
142
142
1.000
114
205.0
0.30
21.0
2.50
1.00
114
114
1.000
19
47.7
0.30
2.0
2.50
1.00
19
19
1.000
41
61.0
0.30
9.0
2.50
1.00
41
41
1.000
41
61.0
0.30
9.0
2.50
1.00
41
41
1.000
27
687
49.2
0.30
5.0
2.50
1.00
27
27
687
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1400
COOLING OA DB / WB 33.7 C / 27.9 C
Sensible
Details
(W)
178 m
9521
266 m
1011
0 m
0
178 m
8149
0 m
0
0 m
0
0 m
0
92 m
1656
0 m
0
12170 W
9564
0W
0
15490 W
14010
130
6838
0
0
5% / 5%
2537
53286
67746
0%
0
70%
0
0%
0
6438 L/s
0
687 L/s
7441
6438 L/s
10090
0
0%
0
85276
85276
85276
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
7813
0
0
391
8204
8204
22885
31089
31097
31097
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
178 m
266 m
0
0 m
0
178 m
0
0 m
0
0 m
0
0 m
0
92 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2118
0
0
0
0
0
0
0
687 L/s
0
687 L/s
-2572
-2370
687 L/s
-5288
0
0%
0
-9977
-2370
-9977
-2370
-9977
-2370
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L6-1
CW AHU
VAV
Number of zones
Floor Area
Location
16
1041.4 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
125.2
88.8
6557
7027
7085
0.709
8.3
120.2
4.28
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jun 1500
33.4 / 28.0
26.0 / 19.6
14.7 / 14.2
13.5
0.100
52
16.0
11 of 16
0.3
C
C
C
C
%
C
OK
K
7027 L/s
7008 L/s
6.75 L/(s-m)
851 L/s
0.82 L/(s-m)
L/s/person
13.46 BHP
10.04 kW
1000 Pa
7.28 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L6-1
CW AHU
VAV
Number of zones
Floor Area
Location
16
1041.4 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Maximum
Cooling
Sensible
(kW)
2.1
2.3
1.2
2.5
1.5
1.5
1.8
1.9
3.0
4.5
5.4
1.2
4.9
7.6
11.6
6.7
Design
Air
Flow
(L/s)
248
269
147
293
178
183
212
229
354
537
643
147
578
904
1370
791
Minimum
Air
Flow
(L/s)
104
15
25
9
19
20
31
47
41
138
33
5
58
78
169
59
Time
of
Peak
Load
Jan 1600
Jul 1600
Jul 1600
Sep 1600
Jan 1600
Jan 1600
Jul 1600
Jul 1600
Aug 1100
Jan 1600
Jul 1600
Jul 1600
Jun 1600
Jun 1600
Jun 1600
Jun 1500
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
56.1
49.0
42.0
30.3
63.0
65.0
62.6
78.2
67.8
132.2
110.0
18.1
29.2
58.2
121.4
58.3
Zone
L/(s-m)
4.42
5.50
3.51
9.68
2.82
2.82
3.38
2.93
5.22
4.06
5.85
8.12
19.80
15.54
11.29
13.57
Zone Name /
Space Name
Zone 1
L6 Dewan peperiksaan 4
Zone 2
L6 Corridor 1
Zone 3
L6 Bilik setor 2
Zone 4
L6 Bilik percetakan
Zone 5
L6 Corridor 2
Zone 6
L6 Corridor 3
Zone 7
L6 Ruang menunggu 2
Zone 8
L6 Bilik fail terbuka
Zone 9
L6 Bilik utiliti S (P)
Zone 10
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.1
Jan 1600
248
0.0
56.1
4.42
2.3
Jul 1600
269
0.0
49.0
5.50
1.2
Jul 1600
147
0.0
42.0
3.51
2.5
Sep 1600
293
0.0
30.3
9.68
1.5
Jan 1600
178
0.0
63.0
2.82
1.5
Jan 1600
183
0.0
65.0
2.82
1.8
Jul 1600
212
0.0
62.6
3.38
1.9
Jul 1600
229
0.0
78.2
2.93
3.0
Aug 1100
354
0.0
67.8
5.22
Page 1 of 2
Zone Name /
Space Name
L6 Dewan Pep. bertulis 1
Zone 11
L6 Lift Lobby
Zone 12
L6 Service Lobby
Zone 13
L6 Dewan peperiksaan 6
Zone 14
L6 Dewan Pep. bertulis 2
Zone 15
L6 Dewan Pep. bertulis 3
Zone 16
L6 Dewan Pep. bertulis 4
07/27/2015
02:46PM
Mult.
1
Cooling
Sensible
(kW)
4.5
Time
of
Load
Jan 1600
Air
Flow
(L/s)
537
Heating
Load
(kW)
0.0
Floor
Area
(m)
132.2
Space
L/(s-m)
4.06
5.4
Jul 1600
643
0.0
110.0
5.85
1.2
Jul 1600
147
0.0
18.1
8.12
4.9
Jun 1600
578
0.0
29.2
19.80
7.6
Jun 1600
904
0.0
58.2
15.54
11.6
Jun 1600
1370
0.0
121.4
11.29
6.7
Jun 1500
791
0.0
58.3
13.57
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
104
56.1
0.60
14.0
5.00
1.00
104
104
1.000
15
49.0
0.30
0.0
0.00
1.00
15
15
1.000
25
42.0
0.60
0.0
0.00
1.00
25
25
1.000
30.3
0.30
0.0
2.50
1.00
1.000
19
63.0
0.30
1.0
0.00
1.00
19
19
1.000
20
65.0
0.30
1.0
0.00
1.00
20
20
1.000
31
62.6
0.30
5.0
2.50
1.00
31
31
1.000
47
78.2
0.60
0.0
0.00
1.00
47
47
1.000
41
67.8
0.60
0.0
0.00
1.00
41
41
1.000
138
132.2
0.30
26.0
3.80
1.00
138
138
1.000
33
110.0
0.30
0.0
2.50
1.00
33
33
1.000
18.1
0.30
0.0
2.50
1.00
1.000
58
29.2
0.60
8.0
5.00
1.00
58
58
1.000
78
58.2
0.30
16.0
3.80
1.00
78
78
1.000
169
121.4
0.30
35.0
3.80
1.00
169
169
1.000
59
851
58.3
0.30
11.0
3.80
1.00
59
59
851
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Jun 1500
COOLING OA DB / WB 33.4 C / 28.0 C
Sensible
Details
(W)
143 m
13842
252 m
1055
0 m
0
143 m
6371
0 m
0
0 m
0
0 m
0
288 m
4959
0 m
0
11455 W
9164
0W
0
14580 W
13278
117
6302
0
0
5% / 5%
2748
57718
69849
0%
0
70%
0
0%
0
6557 L/s
0
851 L/s
8812
6557 L/s
10106
0
0%
0
88767
88766
88766
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
7032
0
0
352
7383
7383
29005
36388
36387
36387
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
143 m
252 m
0
0 m
0
143 m
0
0 m
0
0 m
0
0 m
0
288 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2208
0
0
0
0
0
0
0
851 L/s
0
851 L/s
-3600
-1685
851 L/s
-5490
0
0%
0
-11299
-1685
-11299
-1685
-11299
-1685
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L6-2
CW AHU
VAV
Number of zones
Floor Area
Location
16
1219.6 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
138.5
98.9
7373
8108
8404
0.714
8.8
113.6
4.74
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1500
34.0 / 28.0
25.8 / 19.5
14.7 / 14.1
13.4
0.100
53
16.0
13 of 16
0.3
C
C
C
C
%
C
OK
K
8108 L/s
8086 L/s
6.65 L/(s-m)
871 L/s
0.71 L/(s-m)
L/s/person
15.53 BHP
11.58 kW
1000 Pa
5.13 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L6-2
CW AHU
VAV
Number of zones
Floor Area
Location
16
1219.6 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Maximum
Cooling
Sensible
(kW)
4.6
3.2
5.1
1.7
4.0
6.1
5.2
1.8
1.7
9.3
2.1
5.9
2.1
7.2
6.0
4.8
Design
Air
Flow
(L/s)
543
380
606
204
469
725
617
214
198
1108
252
702
249
857
709
572
Minimum
Air
Flow
(L/s)
60
34
42
25
63
49
54
22
31
142
52
99
104
18
20
57
Time
of
Peak
Load
Jul 1600
Jun 1200
Sep 1100
Dec 1200
Aug 1600
Nov 1100
Dec 1600
Jul 1600
Jan 1600
Dec 1600
Jul 1600
Jul 1600
Jan 1600
Dec 1600
Oct 1600
Nov 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
133.9
54.4
47.7
34.0
127.8
62.8
81.0
55.3
60.3
132.0
55.2
181.3
56.5
59.1
50.0
28.3
Zone
L/(s-m)
4.06
6.98
12.70
6.00
3.67
11.54
7.61
3.86
3.28
8.39
4.57
3.87
4.41
14.51
14.18
20.20
Zone Name /
Space Name
Zone 1
L6 Open office 1
Zone 2
L6 M48+Bilik PA
Zone 3
L6 M54
Zone 4
L6 M52
Zone 5
L6 Open office 2
Zone 6
L6 N44 (1)
Zone 7
L6 N44 (2)
Zone 8
L6 Bilik menaip soalan
Zone 9
L6 Ruang menunggu 1
Zone 10
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
4.6
Jul 1600
543
0.0
133.9
4.06
3.2
Jun 1200
380
0.0
54.4
6.98
5.1
Sep 1100
606
0.0
47.7
12.70
1.7
Dec 1200
204
0.0
34.0
6.00
4.0
Aug 1600
469
0.0
127.8
3.67
6.1
Nov 1100
725
0.0
62.8
11.54
5.2
Dec 1600
617
0.0
81.0
7.61
1.8
Jul 1600
214
0.0
55.3
3.86
1.7
Jan 1600
198
0.0
60.3
3.28
Page 1 of 2
Zone Name /
Space Name
L6 Bilik mesyuarat bah.
Zone 11
L6 B. perbincangan+fail
Zone 12
L6 Open office 3
Zone 13
L6 Dewan peperiksaan 3
Zone 14
L6 Open office 4
Zone 15
L6 Open office 5+setor
Zone 16
L6 Dewan peperiksaan 5
07/27/2015
02:46PM
Mult.
1
Cooling
Sensible
(kW)
9.3
Time
of
Load
Dec 1600
Air
Flow
(L/s)
1108
Heating
Load
(kW)
0.0
Floor
Area
(m)
132.0
Space
L/(s-m)
8.39
2.1
Jul 1600
252
0.0
55.2
4.57
5.9
Jul 1600
702
0.0
181.3
3.87
2.1
Jan 1600
249
0.0
56.5
4.41
7.2
Dec 1600
857
0.0
59.1
14.51
6.0
Oct 1600
709
0.0
50.0
14.18
4.8
Nov 1600
572
0.0
28.3
20.20
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
60
133.9
0.30
8.0
2.50
1.00
60
60
1.000
34
54.4
0.30
7.0
2.50
1.00
34
34
1.000
42
47.7
0.30
11.0
2.50
1.00
42
42
1.000
25
34.0
0.30
6.0
2.50
1.00
25
25
1.000
63
127.8
0.30
10.0
2.50
1.00
63
63
1.000
49
62.8
0.30
12.0
2.50
1.00
49
49
1.000
54
81.0
0.30
12.0
2.50
1.00
54
54
1.000
22
55.3
0.30
2.0
2.50
1.00
22
22
1.000
31
60.3
0.30
5.0
2.50
1.00
31
31
1.000
142
132.0
0.30
41.0
2.50
1.00
142
142
1.000
52
55.2
0.30
14.0
2.50
1.00
52
52
1.000
99
181.3
0.30
18.0
2.50
1.00
99
99
1.000
104
56.5
0.60
14.0
5.00
1.00
104
104
1.000
18
59.1
0.30
0.0
2.50
1.00
18
18
1.000
20
50.0
0.30
2.0
2.50
1.00
20
20
1.000
57
871
28.3
0.60
8.0
5.00
1.00
57
57
871
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
197 m
11364
331 m
1357
0 m
0
197 m
9288
0 m
0
0 m
0
0 m
0
131 m
2410
0 m
0
13416 W
10732
0W
0
17074 W
15550
170
9156
0
0
5% / 5%
2993
62850
77525
0%
0
70%
0
0%
0
7373 L/s
0
871 L/s
9723
7373 L/s
11687
0
0%
0
98936
98936
98936
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
10217
0
0
511
10728
10728
28852
39579
39581
39581
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
197 m
331 m
0
0 m
0
197 m
0
0 m
0
0 m
0
0 m
0
131 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2438
0
0
0
0
0
0
0
871 L/s
0
871 L/s
-3507
-2431
871 L/s
-6208
0
0%
0
-12153
-2431
-12153
-2431
-12153
-2431
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L7-1
CW AHU
VAV
Number of zones
Floor Area
Location
20
1045.5 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
108.1
83.5
6339
6798
6964
0.772
9.7
103.4
3.70
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jul 1600
33.7 / 27.9
25.7 / 19.1
14.7 / 14.1
13.5
0.100
51
16.0
14 of 20
0.2
C
C
C
C
%
C
OK
K
6798 L/s
6780 L/s
6.50 L/(s-m)
608 L/s
0.58 L/(s-m)
L/s/person
13.02 BHP
9.71 kW
1000 Pa
9.66 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L7-1
CW AHU
VAV
Number of zones
Floor Area
Location
20
1045.5 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Zone 18
Zone 19
Zone 20
Maximum
Cooling
Sensible
(kW)
5.0
1.5
4.3
3.0
5.8
3.4
4.2
1.3
1.3
1.3
1.2
1.7
2.8
0.6
0.4
1.6
9.2
5.4
1.2
3.4
Design
Air
Flow
(L/s)
597
184
514
353
686
399
503
153
157
156
143
202
327
74
43
188
1094
643
147
403
Minimum
Air
Flow
(L/s)
24
34
13
19
62
30
20
21
31
31
26
28
64
12
8
21
109
33
5
17
Time
of
Peak
Load
Oct 1600
Jul 1600
Oct 1600
Jul 1600
Aug 1600
Jun 1600
Jun 1600
Jul 1600
Jul 1600
Jan 1600
Jan 1600
Jul 1600
Jan 1600
Jan 1600
Jan 1600
Jan 1600
Jun 1600
Jul 1600
Jul 1600
Jun 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
40.1
56.0
44.4
62.4
102.7
50.7
33.7
36.0
35.6
37.1
37.6
42.3
80.2
22.2
10.9
69.2
99.0
110.0
18.1
57.3
Zone
L/(s-m)
14.89
3.28
11.57
5.65
6.68
7.87
14.91
4.25
4.40
4.19
3.81
4.77
4.08
3.33
3.97
2.71
11.05
5.85
8.12
7.03
Zone Name /
Space Name
Zone 1
L7 Bilik utiliti R
Zone 2
L7 Bilik utiliti S(L/P)
Zone 3
L7 B. utiliti R+line pri
Zone 4
L7 Corridor 1
Zone 5
L7 Bilik file sulit
Zone 6
L7 Bilik setor 1&2
Zone 7
L7 B.simpanan sulit+stor
Zone 8
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
5.0
Oct 1600
597
0.0
40.1
14.89
1.5
Jul 1600
184
0.0
56.0
3.28
4.3
Oct 1600
514
0.0
44.4
11.57
3.0
Jul 1600
353
0.0
62.4
5.65
5.8
Aug 1600
686
0.0
102.7
6.68
3.4
Jun 1600
399
0.0
50.7
7.87
4.2
Jun 1600
503
0.0
33.7
14.91
Page 1 of 2
Zone Name /
Space Name
L7 Bilik multimedia
Zone 9
L7 Bilik scanner OMR
Zone 10
L7 B.pembangunan/penguji
Zone 11
L7 Bilik R&D
Zone 12
L7 Bilik baikpulih komp.
Zone 13
L7 Bilik jurutera/vendor
Zone 14
L7 Staging/operator room
Zone 15
L7 Tape
Zone 16
L7 Corridor 2
Zone 17
L7 Pusat sumber ICT
Zone 18
L7 Lift Lobby
Zone 19
L7 Service Lobby
Zone 20
L7 Corridor 4
07/27/2015
02:46PM
Mult.
1
Cooling
Sensible
(kW)
1.3
Time
of
Load
Jul 1600
Air
Flow
(L/s)
153
Heating
Load
(kW)
0.0
Floor
Area
(m)
36.0
Space
L/(s-m)
4.25
1.3
Jul 1600
157
0.0
35.6
4.40
1.3
Jan 1600
156
0.0
37.1
4.19
1.2
Jan 1600
143
0.0
37.6
3.81
1.7
Jul 1600
202
0.0
42.3
4.77
2.8
Jan 1600
327
0.0
80.2
4.08
0.6
Jan 1600
74
0.0
22.2
3.33
0.4
Jan 1600
43
0.0
10.9
3.97
1.6
Jan 1600
188
0.0
69.2
2.71
9.2
Jun 1600
1094
0.0
99.0
11.05
5.4
Jul 1600
643
0.0
110.0
5.85
1.2
Jul 1600
147
0.0
18.1
8.12
3.4
Jun 1600
403
0.0
57.3
7.03
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Page 1 of 3
07/27/2015
02:46PM
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
24
40.1
0.60
0.0
0.00
1.00
24
24
1.000
34
56.0
0.60
0.0
0.00
1.00
34
34
1.000
13
44.4
0.30
0.0
2.50
1.00
13
13
1.000
19
62.4
0.30
0.0
0.00
1.00
19
19
1.000
62
102.7
0.60
1.0
0.00
1.00
62
62
1.000
30
50.7
0.60
0.0
0.00
1.00
30
30
1.000
20
33.7
0.60
0.0
0.00
1.00
20
20
1.000
21
36.0
0.30
4.0
2.50
1.00
21
21
1.000
31
35.6
0.30
8.0
2.50
1.00
31
31
1.000
31
37.1
0.30
8.0
2.50
1.00
31
31
1.000
26
37.6
0.30
6.0
2.50
1.00
26
26
1.000
28
42.3
0.30
6.0
2.50
1.00
28
28
1.000
64
80.2
0.30
16.0
2.50
1.00
64
64
1.000
12
22.2
0.30
2.0
2.50
1.00
12
12
1.000
10.9
0.30
2.0
2.50
1.00
1.000
21
69.2
0.30
0.0
0.00
1.00
21
21
1.000
109
99.0
0.60
10.0
5.00
1.00
109
109
1.000
33
110.0
0.30
0.0
2.50
1.00
33
33
1.000
18.1
0.30
0.0
2.50
1.00
1.000
17
608
57.3
0.30
0.0
0.00
1.00
17
17
608
1.000
1.000
Page 2 of 3
07/27/2015
02:46PM
Page 3 of 3
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Jul 1600
COOLING OA DB / WB 33.7 C / 27.9 C
Sensible
Details
(W)
149 m
14184
268 m
1250
0 m
0
149 m
6987
0 m
0
0 m
0
0 m
0
329 m
5913
0 m
0
11501 W
9351
0W
0
14637 W
13416
63
3467
0
0
5% / 5%
2728
57297
67179
0%
0
70%
0
0%
0
6339 L/s
0
608 L/s
6540
6339 L/s
9777
0
0%
0
83496
83496
83496
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
3786
0
0
189
3976
3976
20680
24656
24646
24646
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
149 m
268 m
0
0 m
0
149 m
0
0 m
0
0 m
0
0 m
0
329 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-1896
0
0
0
0
0
0
0
608 L/s
0
608 L/s
-2254
-2518
608 L/s
-5055
0
0%
0
-9206
-2518
-9206
-2518
-9206
-2518
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L7-2
CW AHU
VAV
Number of zones
Floor Area
Location
18
1101.7 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
111.5
82.3
6312
6314
6831
0.738
9.9
101.2
3.81
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1200
31.9 / 27.5
25.6 / 19.3
14.8 / 14.2
13.6
0.100
52
16.0
12 of 18
0.5
C
C
C
C
%
C
OK
K
6314 L/s
6298 L/s
5.73 L/(s-m)
655 L/s
0.59 L/(s-m)
L/s/person
12.10 BHP
9.02 kW
1000 Pa
5.50 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L7-2
CW AHU
VAV
Number of zones
Floor Area
Location
18
1101.7 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Zone 18
Maximum
Cooling
Sensible
(kW)
3.0
3.2
2.4
2.9
1.2
6.0
1.7
4.7
0.9
3.3
8.9
1.8
3.1
2.6
1.7
2.1
4.9
3.1
Design
Air
Flow
(L/s)
355
377
290
343
148
716
203
555
109
396
1053
213
367
309
198
253
576
372
Minimum
Air
Flow
(L/s)
12
15
16
32
22
51
25
20
12
70
142
32
31
33
31
52
30
28
Time
of
Peak
Load
Jun 1600
Jun 1500
Jul 1100
Jul 1600
Jul 1600
Aug 1500
Dec 1200
Oct 1100
Jul 1600
Jan 1600
Dec 1600
Jan 1600
Dec 1600
Jul 1600
Jan 1600
Jul 1600
Dec 1500
Nov 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
41.0
34.2
51.7
105.8
37.4
70.0
33.6
50.7
24.0
108.2
132.7
65.8
51.3
77.4
60.3
55.3
58.8
43.5
Zone
L/(s-m)
8.65
11.02
5.61
3.24
3.95
10.23
6.04
10.95
4.55
3.66
7.93
3.23
7.15
3.99
3.28
4.57
9.80
8.54
Zone Name /
Space Name
Zone 1
L7 Corridor 5
Zone 2
L7 B. mesin lipat+line p
Zone 3
L7 B.util R+penyediaan
Zone 4
L7 Corridor 3
Zone 5
L7 Bilik fail tertutup
Zone 6
L7 M54+Bilik PA
Zone 7
L7 M48
Zone 8
L7 Bilik rujukan+util
Zone 9
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
3.0
Jun 1600
355
0.0
41.0
8.65
3.2
Jun 1500
377
0.0
34.2
11.02
2.4
Jul 1100
290
0.0
51.7
5.61
2.9
Jul 1600
343
0.0
105.8
3.24
1.2
Jul 1600
148
0.0
37.4
3.95
6.0
Aug 1500
716
0.0
70.0
10.23
1.7
Dec 1200
203
0.0
33.6
6.04
4.7
Oct 1100
555
0.0
50.7
10.95
Page 1 of 2
Zone Name /
Space Name
L7 Ruang kerja unit 1
Zone 10
L7 Open office 1
Zone 11
L7 Bilik mesyuarat bah.
Zone 12
L7 Open office 2
Zone 13
L7 Bilik mesin
Zone 14
L7 B. temujanji+fail
Zone 15
L7 Ruang menunggu 1
Zone 16
L7 B. perbincangan+util
Zone 17
L7 Open office 3
Zone 18
L7 Open office 4
07/27/2015
02:46PM
Mult.
1
Cooling
Sensible
(kW)
0.9
Time
of
Load
Jul 1600
Air
Flow
(L/s)
109
Heating
Load
(kW)
0.0
Floor
Area
(m)
24.0
Space
L/(s-m)
4.55
3.3
Jan 1600
396
0.0
108.2
3.66
8.9
Dec 1600
1053
0.0
132.7
7.93
1.8
Jan 1600
213
0.0
65.8
3.23
3.1
Dec 1600
367
0.0
51.3
7.15
2.6
Jul 1600
309
0.0
77.4
3.99
1.7
Jan 1600
198
0.0
60.3
3.28
2.1
Jul 1600
253
0.0
55.3
4.57
4.9
Dec 1500
576
0.0
58.8
9.80
3.1
Nov 1600
372
0.0
43.5
8.54
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Page 1 of 2
07/27/2015
02:46PM
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
12
41.0
0.30
0.0
2.50
1.00
12
12
1.000
15
34.2
0.30
2.0
2.50
1.00
15
15
1.000
16
51.7
0.30
0.0
2.50
1.00
16
16
1.000
32
105.8
0.30
0.0
0.00
1.00
32
32
1.000
22
37.4
0.60
0.0
0.00
1.00
22
22
1.000
51
70.0
0.30
12.0
2.50
1.00
51
51
1.000
25
33.6
0.30
6.0
2.50
1.00
25
25
1.000
20
50.7
0.30
2.0
2.50
1.00
20
20
1.000
12
24.0
0.30
2.0
2.50
1.00
12
12
1.000
70
108.2
0.30
15.0
2.50
1.00
70
70
1.000
142
132.7
0.30
41.0
2.50
1.00
142
142
1.000
32
65.8
0.30
5.0
2.50
1.00
32
32
1.000
31
51.3
0.60
0.0
0.00
1.00
31
31
1.000
33
77.4
0.30
4.0
2.50
1.00
33
33
1.000
31
60.3
0.30
5.0
2.50
1.00
31
31
1.000
52
55.3
0.30
14.0
2.50
1.00
52
52
1.000
30
58.8
0.30
5.0
2.50
1.00
30
30
1.000
28
655
43.5
0.30
6.0
2.50
1.00
28
28
655
1.000
1.000
Page 2 of 2
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1200
COOLING OA DB / WB 31.9 C / 27.5 C
Sensible
Details
(W)
161 m
9354
329 m
1070
0 m
0
161 m
6209
0 m
0
0 m
0
0 m
0
93 m
1516
0 m
0
12119 W
9146
0W
0
15424 W
13736
119
5927
0
0
5% / 5%
2348
49304
67719
0%
0
70%
0
0%
0
6312 L/s
0
655 L/s
5533
6312 L/s
9020
0
0%
0
82273
82273
82273
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
7152
0
0
358
7509
7509
21697
29207
29216
29216
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
161 m
329 m
0
0 m
0
161 m
0
0 m
0
0 m
0
0 m
0
93 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-1969
0
0
0
0
0
0
0
655 L/s
0
655 L/s
-2497
-1994
655 L/s
-4807
0
0%
0
-9274
-1994
-9274
-1994
-9274
-1994
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L8-1
CW AHU
VAV
Number of zones
Floor Area
Location
15
1153.9 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
112.9
85.7
6461
6928
7127
0.759
10.2
97.8
3.86
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jul 1500
34.0 / 28.0
25.7 / 19.2
14.7 / 14.1
13.5
0.100
52
16.0
12 of 15
0.3
C
C
C
C
%
C
OK
K
6928 L/s
6910 L/s
6.00 L/(s-m)
659 L/s
0.57 L/(s-m)
L/s/person
13.27 BHP
9.90 kW
1000 Pa
8.44 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L8-1
CW AHU
VAV
Number of zones
Floor Area
Location
15
1153.9 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Maximum
Cooling
Sensible
(kW)
7.0
2.2
4.5
2.4
3.0
1.2
1.7
6.7
1.7
1.2
5.4
1.2
10.5
6.0
5.5
Design
Air
Flow
(L/s)
834
256
529
287
350
137
207
794
199
137
643
147
1241
717
648
Minimum
Air
Flow
(L/s)
68
48
41
80
33
30
35
33
17
30
33
5
133
34
37
Time
of
Peak
Load
Oct 1600
Jan 1600
Jul 1600
Jan 1600
Jul 1600
Jan 1600
Jun 1600
Jun 1600
Jul 1600
Jan 1600
Jul 1600
Jul 1600
Jun 1600
Jul 1600
Dec 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
135.4
66.7
138.3
65.5
109.4
50.5
58.0
54.5
58.0
50.6
110.0
18.1
126.7
55.8
56.4
Zone
L/(s-m)
6.16
3.84
3.83
4.39
3.20
2.71
3.57
14.58
3.43
2.71
5.85
8.12
9.79
12.84
11.49
Zone Name /
Space Name
Zone 1
L8 Open office 4
Zone 2
L8 Bah. pengurusan mak.1
Zone 3
L8 Corridor 1
Zone 4
L8 Bilik latihan/opr 1
Zone 5
L8 Corridor 2
Zone 6
L8 Bilik setor 1
Zone 7
L8 B.Fail sulit+tertutup
Zone 8
L8 Bilik dokumentasi+uti
Zone 9
L8 B. fail terbuka+peny.
Zone 10
L8 Bilik setor 2&3
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
7.0
Oct 1600
834
0.0
135.4
6.16
2.2
Jan 1600
256
0.0
66.7
3.84
4.5
Jul 1600
529
0.0
138.3
3.83
2.4
Jan 1600
287
0.0
65.5
4.39
3.0
Jul 1600
350
0.0
109.4
3.20
1.2
Jan 1600
137
0.0
50.5
2.71
1.7
Jun 1600
207
0.0
58.0
3.57
6.7
Jun 1600
794
0.0
54.5
14.58
1.7
Jul 1600
199
0.0
58.0
3.43
1.2
Jan 1600
137
0.0
50.6
2.71
Page 1 of 2
Zone Name /
Space Name
Zone 11
L8 Lift Lobby
Zone 12
L8 Service Lobby
Zone 13
L8 Bilik latihan/opr1(2)
Zone 14
L8 Bah.pengurusan ma1(2)
Zone 15
L8 Open office 7
07/27/2015
02:46PM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
5.4
Jul 1600
643
0.0
110.0
5.85
1.2
Jul 1600
147
0.0
18.1
8.12
10.5
Jun 1600
1241
0.0
126.7
9.79
6.0
Jul 1600
717
0.0
55.8
12.84
5.5
Dec 1600
648
0.0
56.4
11.49
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
68
135.4
0.30
11.0
2.50
1.00
68
68
1.000
48
66.7
0.30
11.0
2.50
1.00
48
48
1.000
41
138.3
0.30
0.0
0.00
1.00
41
41
1.000
80
65.5
0.30
16.0
3.80
1.00
80
80
1.000
33
109.4
0.30
0.0
0.00
1.00
33
33
1.000
30
50.5
0.60
0.0
0.00
1.00
30
30
1.000
35
58.0
0.60
0.0
0.00
1.00
35
35
1.000
33
54.5
0.60
0.0
0.00
1.00
33
33
1.000
17
58.0
0.30
0.0
2.50
1.00
17
17
1.000
30
50.6
0.60
0.0
0.00
1.00
30
30
1.000
33
110.0
0.30
0.0
2.50
1.00
33
33
1.000
18.1
0.30
0.0
2.50
1.00
1.000
133
126.7
0.30
25.0
3.80
1.00
133
133
1.000
34
55.8
0.30
7.0
2.50
1.00
34
34
1.000
37
659
56.4
0.30
8.0
2.50
1.00
37
37
659
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Jul 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
139 m
11076
305 m
1279
0 m
0
139 m
6568
0 m
0
0 m
0
0 m
0
319 m
5733
0 m
0
12693 W
10154
0W
0
16155 W
14712
78
4201
0
0
5% / 5%
2686
56409
68418
0%
0
70%
0
0%
0
6461 L/s
0
659 L/s
7299
6461 L/s
9964
0
0%
0
85682
85682
85682
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
4688
0
0
234
4922
4922
22286
27208
27205
27205
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
139 m
305 m
0
0 m
0
139 m
0
0 m
0
0 m
0
0 m
0
319 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2002
0
0
0
0
0
0
0
659 L/s
0
659 L/s
-2492
-2424
659 L/s
-5202
0
0%
0
-9695
-2424
-9695
-2424
-9695
-2424
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L8-2
CW AHU
VAV
Number of zones
Floor Area
Location
20
1205.7 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
135.3
94.0
7010
7060
7480
0.695
8.9
112.2
4.62
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jul 1300
33.0 / 27.8
25.9 / 19.8
14.8 / 14.3
13.6
0.100
53
16.0
14 of 20
0.5
C
C
C
C
%
C
OK
K
7060 L/s
7042 L/s
5.86 L/(s-m)
902 L/s
0.75 L/(s-m)
L/s/person
13.53 BHP
10.09 kW
1000 Pa
4.80 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L8-2
CW AHU
VAV
Number of zones
Floor Area
Location
20
1205.7 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Zone 18
Zone 19
Zone 20
Maximum
Cooling
Sensible
(kW)
2.4
3.5
2.2
1.5
1.7
0.7
3.0
8.6
3.1
1.5
2.0
1.9
1.6
0.9
1.6
9.8
5.3
3.8
6.3
1.5
Design
Air
Flow
(L/s)
286
418
256
180
201
83
356
1026
364
184
238
221
194
109
194
1159
633
452
753
173
Minimum
Air
Flow
(L/s)
80
47
47
15
27
11
41
143
37
35
36
45
30
19
34
133
34
33
41
13
Time
of
Peak
Load
Jan 1600
Jul 1600
Jan 1600
Jul 1600
Jan 1600
Jan 1600
Dec 1200
Nov 1600
Nov 1600
Dec 1600
Jul 1600
Jul 1600
Jan 1600
Jan 1600
Jul 1600
Jun 1600
Jul 1200
Oct 1100
Dec 1500
Jul 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
65.1
106.4
66.4
49.6
66.6
28.0
44.4
133.8
40.0
32.2
52.3
34.7
59.0
30.0
57.2
127.3
55.8
50.4
62.5
44.0
Zone
L/(s-m)
4.40
3.93
3.85
3.62
3.02
2.96
8.02
7.67
9.10
5.71
4.55
6.38
3.29
3.63
3.38
9.10
11.35
8.97
12.05
3.93
Zone Name /
Space Name
Zone 1
L8 Bilik latihan/opr 2
Zone 2
L8 Open office 1
Zone 3
L8 Bah. pengurusan mak 2
Zone 4
L8 Open office 2
Zone 5
L8 Open office 3
Zone 6
L8 Bilik PA+util
Zone 7
L8 F54
Zone 8
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.4
Jan 1600
286
0.0
65.1
4.40
3.5
Jul 1600
418
0.0
106.4
3.93
2.2
Jan 1600
256
0.0
66.4
3.85
1.5
Jul 1600
180
0.0
49.6
3.62
1.7
Jan 1600
201
0.0
66.6
3.02
0.7
Jan 1600
83
0.0
28.0
2.96
3.0
Dec 1200
356
0.0
44.4
8.02
Page 1 of 2
Zone Name /
Space Name
L8 Bilik mesyuarat bah.
Zone 9
L8 F48 (1)
Zone 10
L8 F48 (2)
Zone 11
L8 Ruang kerja u 1,2,3,4
Zone 12
L8 Bilik perbincangan
Zone 13
L8 Ruang menunggu
Zone 14
L8 Bilik temujanji
Zone 15
L8 Bilik util R+mesin
Zone 16
L8 Bilik latihan/opr2(2)
Zone 17
L8 Bah.pengurusan ma2(2)
Zone 18
L8 Open office 5
Zone 19
L8 Open office 6
Zone 20
L8 Corridor 3
07/27/2015
02:46PM
Mult.
1
Cooling
Sensible
(kW)
8.6
Time
of
Load
Nov 1600
Air
Flow
(L/s)
1026
Heating
Load
(kW)
0.0
Floor
Area
(m)
133.8
Space
L/(s-m)
7.67
3.1
Nov 1600
364
0.0
40.0
9.10
1.5
Dec 1600
184
0.0
32.2
5.71
2.0
Jul 1600
238
0.0
52.3
4.55
1.9
Jul 1600
221
0.0
34.7
6.38
1.6
Jan 1600
194
0.0
59.0
3.29
0.9
Jan 1600
109
0.0
30.0
3.63
1.6
Jul 1600
194
0.0
57.2
3.38
9.8
Jun 1600
1159
0.0
127.3
9.10
5.3
Jul 1200
633
0.0
55.8
11.35
3.8
Oct 1100
452
0.0
50.4
8.97
6.3
Dec 1500
753
0.0
62.5
12.05
1.5
Jul 1600
173
0.0
44.0
3.93
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Page 1 of 3
07/27/2015
02:46PM
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
80
65.1
0.30
16.0
3.80
1.00
80
80
1.000
47
106.4
0.30
6.0
2.50
1.00
47
47
1.000
47
66.4
0.30
11.0
2.50
1.00
47
47
1.000
15
49.6
0.30
0.0
2.50
1.00
15
15
1.000
27
66.6
0.30
3.0
2.50
1.00
27
27
1.000
11
28.0
0.30
1.0
2.50
1.00
11
11
1.000
41
44.4
0.30
11.0
2.50
1.00
41
41
1.000
143
133.8
0.30
41.0
2.50
1.00
143
143
1.000
37
40.0
0.30
10.0
2.50
1.00
37
37
1.000
35
32.2
0.30
10.0
2.50
1.00
35
35
1.000
36
52.3
0.30
8.0
2.50
1.00
36
36
1.000
45
34.7
0.30
14.0
2.50
1.00
45
45
1.000
30
59.0
0.30
5.0
2.50
1.00
30
30
1.000
19
30.0
0.30
4.0
2.50
1.00
19
19
1.000
34
57.2
0.60
0.0
0.00
1.00
34
34
1.000
133
127.3
0.30
25.0
3.80
1.00
133
133
1.000
34
55.8
0.30
7.0
2.50
1.00
34
34
1.000
33
50.4
0.30
7.0
2.50
1.00
33
33
1.000
41
62.5
0.30
9.0
2.50
1.00
41
41
1.000
13
902
44.0
0.30
0.0
0.00
1.00
13
13
902
1.000
1.000
Page 2 of 3
07/27/2015
02:46PM
Page 3 of 3
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Jul 1300
COOLING OA DB / WB 33.0 C / 27.8 C
Sensible
Details
(W)
148 m
8959
339 m
1216
0 m
0
148 m
6333
0 m
0
0 m
0
0 m
0
151 m
2612
0 m
0
13263 W
10223
0W
0
16880 W
15154
188
9635
0
0
5% / 5%
2707
56839
75078
0%
0
70%
0
0%
0
7010 L/s
0
902 L/s
8815
7010 L/s
10094
0
0%
0
93986
93986
93986
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
11299
0
0
565
11864
11864
29397
41261
41275
41275
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
148 m
339 m
0
0 m
0
148 m
0
0 m
0
0 m
0
0 m
0
151 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2496
0
0
0
0
0
0
0
902 L/s
0
902 L/s
-3659
-1480
902 L/s
-5570
0
0%
0
-11725
-1480
-11725
-1480
-11725
-1480
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L9-1
CW AHU
VAV
Number of zones
Floor Area
Location
15
1237.6 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
107.2
88.6
7124
7380
7538
0.827
11.5
86.6
3.66
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jul 0800
26.4 / 26.2
25.1 / 18.6
14.8 / 14.2
13.6
0.100
50
16.0
6 of 15
0.7
C
C
C
C
%
C
OK
K
7380 L/s
7361 L/s
5.96 L/(s-m)
14.14 BHP
10.54 kW
1000 Pa
622 L/s
0.50 L/(s-m)
L/s/person
12.70 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L9-1
CW AHU
VAV
Number of zones
Floor Area
Location
15
1237.6 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Maximum
Cooling
Sensible
(kW)
5.4
1.2
2.1
6.0
0.8
2.0
2.0
5.4
1.2
7.8
1.6
9.9
6.8
1.7
9.6
Design
Air
Flow
(L/s)
636
141
250
708
97
242
239
643
147
924
189
1176
803
201
1142
Minimum
Air
Flow
(L/s)
60
24
19
156
13
14
20
33
5
41
28
82
31
20
77
Time
of
Peak
Load
Jul 1600
Jul 1600
Jun 1600
Jan 1600
Jan 1600
Jun 1600
Jul 1600
Jul 1600
Jul 1600
Jun 1600
Jan 1600
Aug 1600
Nov 1600
Jul 1600
Jun 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
132.8
39.5
45.0
260.8
33.4
46.5
65.2
110.0
18.1
68.7
59.6
116.0
54.0
59.6
128.4
Zone
L/(s-m)
4.79
3.56
5.55
2.71
2.92
5.21
3.67
5.85
8.12
13.45
3.17
10.14
14.86
3.37
8.89
Zone Name /
Space Name
Zone 1
L9 Open office 1
Zone 2
L9 Bilik utiliti S (L/P)
Zone 3
L9 Bilik dok1+penjilidan
Zone 4
L9 Bilik fail terbuka 1
Zone 5
L9 Bilik fail terbuka 2
Zone 6
L9 Bilik fail sulit+dok2
Zone 7
L9 Corridor 1
Zone 8
L9 Lift Lobby
Zone 9
L9 Service Lobby
Zone 10
L9 Open office 3
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
5.4
Jul 1600
636
0.0
132.8
4.79
1.2
Jul 1600
141
0.0
39.5
3.56
2.1
Jun 1600
250
0.0
45.0
5.55
6.0
Jan 1600
708
0.0
260.8
2.71
0.8
Jan 1600
97
0.0
33.4
2.92
2.0
Jun 1600
242
0.0
46.5
5.21
2.0
Jul 1600
239
0.0
65.2
3.67
5.4
Jul 1600
643
0.0
110.0
5.85
1.2
Jul 1600
147
0.0
18.1
8.12
7.8
Jun 1600
924
0.0
68.7
13.45
Page 1 of 2
Zone Name /
Space Name
Zone 11
L9 Open office 4
Zone 12
L9 Open office 5
Zone 13
L9 Open office 6
Zone 14
L9 Open office 7
Zone 15
L9 Bilik fail terbuka 3
07/27/2015
02:46PM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.6
Jan 1600
189
0.0
59.6
3.17
9.9
Aug 1600
1176
0.0
116.0
10.14
6.8
Nov 1600
803
0.0
54.0
14.86
1.7
Jul 1600
201
0.0
59.6
3.37
9.6
Jun 1600
1142
0.0
128.4
8.89
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
60
132.8
0.30
8.0
2.50
1.00
60
60
1.000
24
39.5
0.60
0.0
0.00
1.00
24
24
1.000
19
45.0
0.30
2.0
2.50
1.00
19
19
1.000
156
260.8
0.60
0.0
0.00
1.00
156
156
1.000
13
33.4
0.30
1.0
2.50
1.00
13
13
1.000
14
46.5
0.30
0.0
2.50
1.00
14
14
1.000
20
65.2
0.30
0.0
0.00
1.00
20
20
1.000
33
110.0
0.30
0.0
2.50
1.00
33
33
1.000
18.1
0.30
0.0
2.50
1.00
1.000
41
68.7
0.30
8.0
2.50
1.00
41
41
1.000
28
59.6
0.30
4.0
2.50
1.00
28
28
1.000
82
116.0
0.30
19.0
2.50
1.00
82
82
1.000
31
54.0
0.30
6.0
2.50
1.00
31
31
1.000
20
59.6
0.30
1.0
2.50
1.00
20
20
1.000
77
622
128.4
0.60
0.0
0.00
1.00
77
77
622
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Jul 0800
COOLING OA DB / WB 26.4 C / 26.2 C
Sensible
Details
(W)
157 m
6298
292 m
702
0 m
0
157 m
3082
0 m
0
0 m
0
0 m
0
353 m
4182
0 m
0
13614 W
9231
0W
0
17326 W
14838
49
2104
0
0
5% / 5%
2022
42459
77254
0%
0
70%
0
0%
0
7124 L/s
0
457 L/s
789
7124 L/s
10580
0
0%
0
88624
88624
88624
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
2945
0
0
147
3092
3092
15459
18551
18548
18548
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
157 m
292 m
0
0 m
0
157 m
0
0 m
0
0 m
0
0 m
0
353 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2099
0
0
0
0
0
0
0
622 L/s
0
622 L/s
-2148
-2867
622 L/s
-5439
0
0%
0
-9686
-2867
-9686
-2867
-9686
-2867
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:46PM
AHU L9-2
CW AHU
VAV
Number of zones
Floor Area
Location
20
1124.4 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
123.4
88.6
6759
6840
7304
0.718
9.1
109.8
4.22
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1200
31.9 / 27.5
25.7 / 19.5
14.8 / 14.2
13.6
0.100
53
16.0
12 of 20
0.3
C
C
C
C
%
C
OK
K
6840 L/s
6822 L/s
6.08 L/(s-m)
757 L/s
0.67 L/(s-m)
L/s/person
13.10 BHP
9.77 kW
1000 Pa
4.79 L/s/person
Page 1 of 1
07/27/2015
02:46PM
AHU L9-2
CW AHU
VAV
Number of zones
Floor Area
Location
20
1124.4 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Zone 18
Zone 19
Zone 20
Maximum
Cooling
Sensible
(kW)
1.1
4.1
3.2
0.6
2.8
9.1
4.5
2.4
1.2
0.7
1.4
1.2
1.6
1.7
1.8
1.3
6.8
9.3
1.0
5.7
Design
Air
Flow
(L/s)
133
483
377
75
331
1084
534
283
136
87
167
140
194
200
216
158
805
1106
118
674
Minimum
Air
Flow
(L/s)
17
65
47
10
40
143
27
25
30
19
21
14
30
44
22
24
38
93
15
34
Time
of
Peak
Load
Jul 1600
Jul 1600
Dec 1600
Jan 1600
Dec 1200
Dec 1600
Dec 1600
Dec 1600
Jan 1600
Jan 1600
Jul 1600
Jul 1600
Jan 1600
Jul 1600
Jul 1600
Jan 1600
Jun 1500
Aug 1500
Jan 1600
Nov 1500
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
22.0
115.6
40.2
25.3
41.7
133.6
40.0
34.0
50.3
32.2
54.2
45.5
59.0
28.8
57.4
48.0
67.0
135.0
41.0
53.6
Zone
L/(s-m)
6.06
4.18
9.37
2.98
7.95
8.11
13.34
8.33
2.71
2.71
3.09
3.08
3.29
6.94
3.77
3.28
12.02
8.19
2.88
12.57
Zone Name /
Space Name
Zone 1
L9 Ruang kerja unit 3&4
Zone 2
L9 Open office 2
Zone 3
L9 Bilik perbincangan 2
Zone 4
L9 Bilik PA+util 3
Zone 5
L9 M54
Zone 6
L9 Bilik mesyuarat bah.
Zone 7
L9 M52
Zone 8
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.1
Jul 1600
133
0.0
22.0
6.06
4.1
Jul 1600
483
0.0
115.6
4.18
3.2
Dec 1600
377
0.0
40.2
9.37
0.6
Jan 1600
75
0.0
25.3
2.98
2.8
Dec 1200
331
0.0
41.7
7.95
9.1
Dec 1600
1084
0.0
133.6
8.11
4.5
Dec 1600
534
0.0
40.0
13.34
Page 1 of 2
Zone Name /
Space Name
L9 M48
Zone 9
L9 Bilik utiliti 1
Zone 10
L9 Bilik setor 1
Zone 11
L9 Ruang kerja unit1+dok
Zone 12
L9 Corridor 2
Zone 13
L9 Ruang menunggu
Zone 14
L9 Bilik perbincangan 1
Zone 15
L9 Ruang kerja unit 2
Zone 16
L9 Open office 8
Zone 17
L9 Open office 9
Zone 18
L9 Open office 10
Zone 19
L9 Open office 11
Zone 20
L9 Open office 12
07/27/2015
02:46PM
Mult.
1
Cooling
Sensible
(kW)
2.4
Time
of
Load
Dec 1600
Air
Flow
(L/s)
283
Heating
Load
(kW)
0.0
Floor
Area
(m)
34.0
Space
L/(s-m)
8.33
1.2
Jan 1600
136
0.0
50.3
2.71
0.7
Jan 1600
87
0.0
32.2
2.71
1.4
Jul 1600
167
0.0
54.2
3.09
1.2
Jul 1600
140
0.0
45.5
3.08
1.6
Jan 1600
194
0.0
59.0
3.29
1.7
Jul 1600
200
0.0
28.8
6.94
1.8
Jul 1600
216
0.0
57.4
3.77
1.3
Jan 1600
158
0.0
48.0
3.28
6.8
Jun 1500
805
0.0
67.0
12.02
9.3
Aug 1500
1106
0.0
135.0
8.19
1.0
Jan 1600
118
0.0
41.0
2.88
5.7
Nov 1500
674
0.0
53.6
12.57
Page 2 of 2
07/27/2015
02:46PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Page 1 of 3
07/27/2015
02:46PM
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
17
22.0
0.30
4.0
2.50
1.00
17
17
1.000
65
115.6
0.30
12.0
2.50
1.00
65
65
1.000
47
40.2
0.30
14.0
2.50
1.00
47
47
1.000
10
25.3
0.30
1.0
2.50
1.00
10
10
1.000
40
41.7
0.30
11.0
2.50
1.00
40
40
1.000
143
133.6
0.30
41.0
2.50
1.00
143
143
1.000
27
40.0
0.30
6.0
2.50
1.00
27
27
1.000
25
34.0
0.30
6.0
2.50
1.00
25
25
1.000
30
50.3
0.60
0.0
0.00
1.00
30
30
1.000
19
32.2
0.60
0.0
0.00
1.00
19
19
1.000
21
54.2
0.30
2.0
2.50
1.00
21
21
1.000
14
45.5
0.30
0.0
0.00
1.00
14
14
1.000
30
59.0
0.30
5.0
2.50
1.00
30
30
1.000
44
28.8
0.30
14.0
2.50
1.00
44
44
1.000
22
57.4
0.30
2.0
2.50
1.00
22
22
1.000
24
48.0
0.30
4.0
2.50
1.00
24
24
1.000
38
67.0
0.30
7.0
2.50
1.00
38
38
1.000
93
135.0
0.30
21.0
2.50
1.00
93
93
1.000
15
41.0
0.30
1.0
2.50
1.00
15
15
1.000
34
757
53.6
0.30
7.0
2.50
1.00
34
34
757
1.000
1.000
Page 2 of 3
07/27/2015
02:46PM
Page 3 of 3
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1200
COOLING OA DB / WB 31.9 C / 27.5 C
Sensible
Details
(W)
171 m
10169
291 m
962
0 m
0
171 m
6619
0 m
0
0 m
0
0 m
0
102 m
1655
0 m
0
12368 W
9335
0W
0
15742 W
14019
158
7869
0
0
5% / 5%
2531
53157
72384
0%
0
70%
0
0%
0
6759 L/s
0
757 L/s
6414
6759 L/s
9783
0
0%
0
88581
88581
88581
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:46PM
Latent
(W)
9496
0
0
475
9971
9971
24863
34834
34850
34850
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
171 m
291 m
0
0 m
0
171 m
0
0 m
0
0 m
0
0 m
0
102 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2275
0
0
0
0
0
0
0
757 L/s
0
757 L/s
-2890
-1957
757 L/s
-5262
0
0%
0
-10428
-1957
-10428
-1957
-10428
-1957
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:35PM
AHU L10-1
CW AHU
VAV
Number of zones
Floor Area
Location
20
1153.4 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
117.8
89.2
6786
7516
7608
0.757
9.8
102.2
4.03
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jul 1600
33.7 / 27.9
25.6 / 19.1
14.7 / 14.1
13.5
0.100
52
16.0
20 of 20
0.0
C
C
C
C
%
C
OK
K
7516 L/s
7497 L/s
6.52 L/(s-m)
658 L/s
0.57 L/(s-m)
L/s/person
14.40 BHP
10.74 kW
1000 Pa
6.39 L/s/person
Page 1 of 1
07/27/2015
02:35PM
AHU L10-1
CW AHU
VAV
Number of zones
Floor Area
Location
20
1153.4 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Zone 18
Zone 19
Zone 20
Maximum
Cooling
Sensible
(kW)
7.2
1.2
1.4
1.6
1.7
1.4
1.7
2.2
1.3
0.6
1.4
7.0
1.3
1.6
4.5
5.4
1.2
8.4
8.7
4.4
Design
Air
Flow
(L/s)
855
145
165
194
198
162
207
259
153
71
161
826
152
189
537
638
146
999
1027
521
Minimum
Air
Flow
(L/s)
114
25
35
43
30
32
29
24
23
16
24
27
24
30
23
33
5
32
44
43
Time
of
Peak
Load
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jan 1600
Jun 1600
Jan 1600
Jan 1600
Jun 1600
Jun 1600
Jul 1600
Jan 1600
Jul 1100
Jul 1600
Jul 1600
Sep 1600
Jun 1600
Jun 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
197.6
41.8
58.3
27.7
59.0
54.1
70.0
31.0
50.0
26.6
31.4
65.0
31.4
58.6
27.8
110.0
18.1
65.6
70.0
59.4
Zone
L/(s-m)
4.33
3.47
2.84
7.02
3.36
2.99
2.95
8.37
3.07
2.67
5.12
12.71
4.84
3.23
19.33
5.80
8.07
15.23
14.68
8.78
Zone Name /
Space Name
Zone 1
L10 Open office 1
Zone 2
L10 Bilik utiliti S(L/P)
Zone 3
L10 Bilik fail+setor
Zone 4
L10 Bilik perbincangan
Zone 5
L10 Ruang menunggu 2
Zone 6
L10 Bilik fail sulit
Zone 7
L10 Open office 2
Zone 8
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
7.2
Jul 1600
855
0.0
197.6
4.33
1.2
Jul 1600
145
0.0
41.8
3.47
1.4
Jul 1600
165
0.0
58.3
2.84
1.6
Jul 1600
194
0.0
27.7
7.02
1.7
Jul 1600
198
0.0
59.0
3.36
1.4
Jul 1600
162
0.0
54.1
2.99
1.7
Jan 1600
207
0.0
70.0
2.95
Page 1 of 2
Zone Name /
Space Name
L10 M52 (1)
Zone 9
L10 M44
Zone 10
L10 Bilik fail tertutup
Zone 11
L10 M48 (1)
Zone 12
L10 Open office 3+fail
Zone 13
L10 M52 (2)
Zone 14
L10 Open office 4
Zone 15
L10 M48 (2)
Zone 16
L10 Lift Lobby
Zone 17
L10 Service Lobby
Zone 18
L10 Open office 8
Zone 19
L10 Open office 9
Zone 20
L10 Open office 10
07/27/2015
02:35PM
Mult.
1
Cooling
Sensible
(kW)
2.2
Time
of
Load
Jun 1600
Air
Flow
(L/s)
259
Heating
Load
(kW)
0.0
Floor
Area
(m)
31.0
Space
L/(s-m)
8.37
1.3
Jan 1600
153
0.0
50.0
3.07
0.6
Jan 1600
71
0.0
26.6
2.67
1.4
Jun 1600
161
0.0
31.4
5.12
7.0
Jun 1600
826
0.0
65.0
12.71
1.3
Jul 1600
152
0.0
31.4
4.84
1.6
Jan 1600
189
0.0
58.6
3.23
4.5
Jul 1100
537
0.0
27.8
19.33
5.4
Jul 1600
638
0.0
110.0
5.80
1.2
Jul 1600
146
0.0
18.1
8.07
8.4
Sep 1600
999
0.0
65.6
15.23
8.7
Jun 1600
1027
0.0
70.0
14.68
4.4
Jun 1600
521
0.0
59.4
8.78
Page 2 of 2
07/27/2015
02:35PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Page 1 of 3
07/27/2015
02:35PM
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
114
197.6
0.30
22.0
2.50
1.00
114
114
1.000
25
41.8
0.60
0.0
0.00
1.00
25
25
1.000
35
58.3
0.60
0.0
0.00
1.00
35
35
1.000
43
27.7
0.30
14.0
2.50
1.00
43
43
1.000
30
59.0
0.30
5.0
2.50
1.00
30
30
1.000
32
54.1
0.60
0.0
0.00
1.00
32
32
1.000
29
70.0
0.30
3.0
2.50
1.00
29
29
1.000
24
31.0
0.30
6.0
2.50
1.00
24
24
1.000
23
50.0
0.30
3.0
2.50
1.00
23
23
1.000
16
26.6
0.60
0.0
0.00
1.00
16
16
1.000
24
31.4
0.30
6.0
2.50
1.00
24
24
1.000
27
65.0
0.30
3.0
2.50
1.00
27
27
1.000
24
31.4
0.30
6.0
2.50
1.00
24
24
1.000
30
58.6
0.30
5.0
2.50
1.00
30
30
1.000
23
27.8
0.30
6.0
2.50
1.00
23
23
1.000
33
110.0
0.30
0.0
2.50
1.00
33
33
1.000
18.1
0.30
0.0
2.50
1.00
1.000
32
65.6
0.30
5.0
2.50
1.00
32
32
1.000
44
70.0
0.30
9.0
2.50
1.00
44
44
1.000
43
658
59.4
0.30
10.0
2.50
1.00
43
43
658
1.000
1.000
Page 2 of 3
07/27/2015
02:35PM
Page 3 of 3
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
07/27/2015
02:35PM
DESIGN COOLING
COOLING DATA AT Jul 1600
COOLING OA DB / WB 33.7 C / 27.9 C
Sensible
Details
(W)
165 m
15647
259 m
956
0 m
0
165 m
7713
0 m
0
0 m
0
0 m
0
324 m
5784
0 m
0
12687 W
10053
0W
0
16148 W
14651
103
5477
0
0
5% / 5%
3014
63295
71174
0%
0
70%
0
0%
0
6786 L/s
0
658 L/s
7143
6786 L/s
10842
0
0%
0
89160
89160
89160
Positive values are clg loads
Negative values are htg loads
Latent
(W)
6190
0
0
310
6500
6500
22172
28672
28666
28666
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
165 m
259 m
0
0 m
0
165 m
0
0 m
0
0 m
0
0 m
0
324 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2109
0
0
0
0
0
0
0
658 L/s
0
658 L/s
-2379
-2837
658 L/s
-5570
0
0%
0
-10058
-2837
-10058
-2837
-10058
-2837
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:35PM
AHU L10-2
CW AHU
VAV
Number of zones
Floor Area
Location
15
1173.2 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
110.8
81.7
6199
6857
7228
0.738
10.6
94.4
3.79
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1500
34.0 / 28.0
25.6 / 19.3
14.7 / 14.1
13.5
0.100
53
16.0
15 of 15
0.0
C
C
C
C
%
C
OK
K
6857 L/s
6839 L/s
5.84 L/(s-m)
656 L/s
0.56 L/(s-m)
L/s/person
13.14 BHP
9.80 kW
1000 Pa
5.86 L/s/person
Page 1 of 1
07/27/2015
02:35PM
AHU L10-2
CW AHU
VAV
Number of zones
Floor Area
Location
15
1173.2 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Maximum
Cooling
Sensible
(kW)
1.4
4.4
5.5
6.1
3.3
0.8
1.5
1.6
1.3
2.4
9.4
2.7
4.7
6.9
8.9
Design
Air
Flow
(L/s)
169
526
650
725
396
96
177
191
151
282
1114
317
559
824
1052
Minimum
Air
Flow
(L/s)
18
48
42
35
59
16
15
30
33
26
142
26
93
35
41
Time
of
Peak
Load
Jul 1600
Aug 1600
Jul 1100
Oct 1000
Jan 1600
Jul 1600
Jul 1600
Jan 1600
Jul 1600
Dec 1200
Dec 1600
Nov 1600
Jan 1600
Dec 1500
Nov 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
42.0
117.0
91.0
115.0
128.6
26.0
49.2
59.0
54.2
35.0
132.2
35.1
167.4
58.9
62.6
Zone
L/(s-m)
4.02
4.50
7.14
6.31
3.08
3.71
3.59
3.23
2.79
8.04
8.43
9.03
3.34
13.98
16.80
Zone Name /
Space Name
Zone 1
L10 Ruang kerja
Zone 2
L10 Open office 5
Zone 3
L10 Bilik penyediaan dok
Zone 4
L10 Bilik percetakan
Zone 5
L10 Open office 6
Zone 6
L10 B. fail+dokumentasi
Zone 7
L10 Bilik latihan+fail
Zone 8
L10 Ruang menunggu 1
Zone 9
L10 Bilik setor+mesin
Zone 10
L10 M52 (3)
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.4
Jul 1600
169
0.0
42.0
4.02
4.4
Aug 1600
526
0.0
117.0
4.50
5.5
Jul 1100
650
0.0
91.0
7.14
6.1
Oct 1000
725
0.0
115.0
6.31
3.3
Jan 1600
396
0.0
128.6
3.08
0.8
Jul 1600
96
0.0
26.0
3.71
1.5
Jul 1600
177
0.0
49.2
3.59
1.6
Jan 1600
191
0.0
59.0
3.23
1.3
Jul 1600
151
0.0
54.2
2.79
2.4
Dec 1200
282
0.0
35.0
8.04
Page 1 of 2
Zone Name /
Space Name
Zone 11
L10 Bilik mesyuarat bah.
Zone 12
L10 M52 (4)
Zone 13
L10 Open office 7
Zone 14
L10 Open office 11
Zone 15
L10 Open office 12
07/27/2015
02:35PM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
9.4
Dec 1600
1114
0.0
132.2
8.43
2.7
Nov 1600
317
0.0
35.1
9.03
4.7
Jan 1600
559
0.0
167.4
3.34
6.9
Dec 1500
824
0.0
58.9
13.98
8.9
Nov 1600
1052
0.0
62.6
16.80
Page 2 of 2
07/27/2015
02:35PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
18
42.0
0.30
2.0
2.50
1.00
18
18
1.000
48
117.0
0.30
5.0
2.50
1.00
48
48
1.000
42
91.0
0.30
6.0
2.50
1.00
42
42
1.000
35
115.0
0.30
0.0
2.50
1.00
35
35
1.000
59
128.6
0.30
8.0
2.50
1.00
59
59
1.000
16
26.0
0.60
0.0
0.00
1.00
16
16
1.000
15
49.2
0.30
0.0
2.50
1.00
15
15
1.000
30
59.0
0.30
5.0
2.50
1.00
30
30
1.000
33
54.2
0.60
0.0
0.00
1.00
33
33
1.000
26
35.0
0.30
6.0
2.50
1.00
26
26
1.000
142
132.2
0.30
41.0
2.50
1.00
142
142
1.000
26
35.1
0.30
6.0
2.50
1.00
26
26
1.000
93
167.4
0.30
17.0
2.50
1.00
93
93
1.000
35
58.9
0.30
7.0
2.50
1.00
35
35
1.000
41
656
62.6
0.30
9.0
2.50
1.00
41
41
656
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
07/27/2015
02:35PM
DESIGN COOLING
COOLING DATA AT Aug 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
174 m
10300
294 m
1047
0 m
0
174 m
8235
0 m
0
0 m
0
0 m
0
94 m
1714
0 m
0
12905 W
10037
0W
0
16425 W
14796
112
5809
0
0
5% / 5%
2597
54535
64446
0%
0
70%
0
0%
0
6199 L/s
0
656 L/s
7398
6199 L/s
9889
0
0%
0
81734
81734
81734
Positive values are clg loads
Negative values are htg loads
Latent
(W)
6731
0
0
337
7068
7068
21962
29030
29034
29034
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
174 m
294 m
0
0 m
0
174 m
0
0 m
0
0 m
0
0 m
0
94 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2046
0
0
0
0
0
0
0
656 L/s
0
656 L/s
-2430
-2383
656 L/s
-5154
0
0%
0
-9630
-2383
-9630
-2383
-9630
-2383
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:45PM
AHU L11-1
CW AHU
VAV
Number of zones
Floor Area
Location
18
1218.8 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
141.8
104.9
7823
8409
8606
0.739
8.6
116.4
4.85
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jul 1500
34.0 / 28.0
25.8 / 19.4
14.7 / 14.1
13.5
0.100
52
16.0
13 of 18
0.4
C
C
C
C
%
C
OK
K
8409 L/s
8387 L/s
6.90 L/(s-m)
850 L/s
0.70 L/(s-m)
L/s/person
16.11 BHP
12.01 kW
1000 Pa
6.30 L/s/person
Page 1 of 1
07/27/2015
02:45PM
AHU L11-1
CW AHU
VAV
Number of zones
Floor Area
Location
18
1218.8 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Zone 18
Maximum
Cooling
Sensible
(kW)
2.0
3.7
5.0
2.1
8.5
1.0
5.4
1.2
6.4
3.0
2.0
4.1
7.8
7.4
1.6
1.5
6.3
3.2
Design
Air
Flow
(L/s)
240
442
593
249
1009
122
643
147
762
354
241
490
930
879
194
179
752
379
Minimum
Air
Flow
(L/s)
25
36
149
21
230
26
33
5
33
15
14
40
50
36
22
37
39
39
Time
of
Peak
Load
Nov 1600
Jul 1600
Jan 1600
Jul 1600
Jan 1600
Jan 1600
Jul 1600
Jul 1600
Oct 1600
Jul 1600
Jun 1600
Aug 1600
Jun 1600
Jun 1600
Jul 1600
Jan 1600
Jul 1100
Jun 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
34.4
68.4
173.0
68.8
200.0
42.6
110.0
18.1
52.8
51.0
18.6
67.3
66.3
45.1
30.7
40.8
65.4
65.5
Zone
L/(s-m)
6.97
6.46
3.43
3.62
5.04
2.87
5.85
8.12
14.44
6.94
12.98
7.28
14.03
19.49
6.30
4.39
11.50
5.78
Zone Name /
Space Name
Zone 1
L11 M48 (1)
Zone 2
L11 Open office 1
Zone 3
L11 Pusat sumber(1)
Zone 4
L11 Ruang tamu mesyua(3)
Zone 5
L11 B.mesyuarat utama(1)
Zone 6
L11 Bilik setor aset(3)
Zone 7
L11 Lift Lobby
Zone 8
L11 Service Lobby
Zone 9
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.0
Nov 1600
240
0.0
34.4
6.97
3.7
Jul 1600
442
0.0
68.4
6.46
5.0
Jan 1600
593
0.0
173.0
3.43
2.1
Jul 1600
249
0.0
68.8
3.62
8.5
Jan 1600
1009
0.0
200.0
5.04
1.0
Jan 1600
122
0.0
42.6
2.87
5.4
Jul 1600
643
0.0
110.0
5.85
1.2
Jul 1600
147
0.0
18.1
8.12
Page 1 of 2
Zone Name /
Space Name
L11 Open office 3
Zone 10
L11 Corridor 1
Zone 11
L11 Pusat sumber(2)
Zone 12
L11 Pusat sumber(3)
Zone 13
L11 Pusat sumber(4)
Zone 14
L11 B.mesyuarat utama(2)
Zone 15
L11 Ruang tamu mesyua(1)
Zone 16
L11 Ruang tamu mesyua(2)
Zone 17
L11 Bilik setor aset(1)
Zone 18
L11 Bilik setor aset(2)
07/27/2015
02:45PM
Mult.
1
Cooling
Sensible
(kW)
6.4
Time
of
Load
Oct 1600
Air
Flow
(L/s)
762
Heating
Load
(kW)
0.0
Floor
Area
(m)
52.8
Space
L/(s-m)
14.44
3.0
Jul 1600
354
0.0
51.0
6.94
2.0
Jun 1600
241
0.0
18.6
12.98
4.1
Aug 1600
490
0.0
67.3
7.28
7.8
Jun 1600
930
0.0
66.3
14.03
7.4
Jun 1600
879
0.0
45.1
19.49
1.6
Jul 1600
194
0.0
30.7
6.30
1.5
Jan 1600
179
0.0
40.8
4.39
6.3
Jul 1100
752
0.0
65.4
11.50
3.2
Jun 1600
379
0.0
65.5
5.78
Page 2 of 2
07/27/2015
02:45PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Page 1 of 2
07/27/2015
02:45PM
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
25
34.4
0.30
6.0
2.50
1.00
25
25
1.000
36
68.4
0.30
6.0
2.50
1.00
36
36
1.000
149
173.0
0.60
18.0
2.50
1.00
149
149
1.000
21
68.8
0.30
0.0
2.50
1.00
21
21
1.000
230
200.0
0.30
68.0
2.50
1.00
230
230
1.000
26
42.6
0.60
1.0
0.00
1.00
26
26
1.000
33
110.0
0.30
0.0
2.50
1.00
33
33
1.000
18.1
0.30
0.0
2.50
1.00
1.000
33
52.8
0.30
7.0
2.50
1.00
33
33
1.000
15
51.0
0.30
0.0
2.50
1.00
15
15
1.000
14
18.6
0.60
1.0
2.50
1.00
14
14
1.000
40
67.3
0.60
0.0
2.50
1.00
40
40
1.000
50
66.3
0.60
4.0
2.50
1.00
50
50
1.000
36
45.1
0.30
9.0
2.50
1.00
36
36
1.000
22
30.7
0.30
5.0
2.50
1.00
22
22
1.000
37
40.8
0.30
10.0
2.50
1.00
37
37
1.000
39
65.4
0.60
0.0
0.00
1.00
39
39
1.000
39
850
65.5
0.60
0.0
0.00
1.00
39
39
850
1.000
1.000
Page 2 of 2
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Jul 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
175 m
15112
268 m
1167
0 m
0
175 m
8259
0 m
0
0 m
0
0 m
0
419 m
7551
0 m
0
13407 W
10725
0W
0
17063 W
15540
135
7271
0
0
5% / 5%
3281
68906
83396
0%
0
70%
0
0%
0
7823 L/s
0
850 L/s
9363
7823 L/s
12097
0
0%
0
104857
104857
104857
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:45PM
Latent
(W)
8114
0
0
406
8519
8519
28473
36992
36988
36988
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
175 m
268 m
0
0 m
0
175 m
0
0 m
0
0 m
0
0 m
0
419 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2238
0
0
0
0
0
0
0
850 L/s
0
850 L/s
-3564
-2745
850 L/s
-6378
0
0%
0
-12179
-2745
-12179
-2745
-12179
-2745
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:45PM
AHU L11-2
CW AHU
VAV
Number of zones
Floor Area
Location
17
1106.2 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
116.2
85.2
6409
6955
7355
0.733
9.5
105.1
3.97
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1500
34.0 / 28.0
25.7 / 19.4
14.7 / 14.1
13.5
0.100
53
16.0
13 of 17
0.3
C
C
C
C
%
C
OK
K
6955 L/s
6937 L/s
6.29 L/(s-m)
684 L/s
0.62 L/(s-m)
L/s/person
13.32 BHP
9.94 kW
1000 Pa
5.22 L/s/person
Page 1 of 1
07/27/2015
02:45PM
AHU L11-2
CW AHU
VAV
Number of zones
Floor Area
Location
17
1106.2 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Maximum
Cooling
Sensible
(kW)
3.3
2.2
4.5
1.3
2.8
1.1
1.7
0.8
1.6
2.2
4.1
10.3
7.4
4.8
6.5
4.6
2.7
Design
Air
Flow
(L/s)
396
262
539
152
337
127
197
93
195
263
481
1226
879
569
772
551
317
Minimum
Air
Flow
(L/s)
35
24
38
23
27
18
32
12
30
56
14
205
35
37
34
38
26
Time
of
Peak
Load
Jun 1200
Jul 1600
Aug 1100
Jul 1600
Dec 1200
Jul 1600
Jul 1600
Jul 1600
Jan 1600
Jul 1600
Nov 1100
Jul 1600
Nov 1600
Dec 1600
Dec 1600
Dec 1600
Aug 1100
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
59.3
64.0
34.3
41.9
41.0
29.4
52.8
22.4
59.1
54.2
21.7
334.0
66.0
57.2
47.3
60.0
61.6
Zone
L/(s-m)
6.68
4.09
15.73
3.62
8.22
4.33
3.73
4.15
3.29
4.86
22.19
3.67
13.31
9.95
16.31
9.18
5.15
Zone Name /
Space Name
Zone 1
L11 Bilik HRMIS
Zone 2
L11 Ruang kerja unit 1&2
Zone 3
L11 M52
Zone 4
L11 Pembantu khas
Zone 5
L11 M48 (2)
Zone 6
L11 Bilik utiliti 1&2
Zone 7
L11 Bilik fail kewangan
Zone 8
L11 Ruang kerja unit 3
Zone 9
L11 Kaunter Pertanyaan
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
3.3
Jun 1200
396
0.0
59.3
6.68
2.2
Jul 1600
262
0.0
64.0
4.09
4.5
Aug 1100
539
0.0
34.3
15.73
1.3
Jul 1600
152
0.0
41.9
3.62
2.8
Dec 1200
337
0.0
41.0
8.22
1.1
Jul 1600
127
0.0
29.4
4.33
1.7
Jul 1600
197
0.0
52.8
3.73
0.8
Jul 1600
93
0.0
22.4
4.15
1.6
Jan 1600
195
0.0
59.1
3.29
Page 1 of 2
Zone Name /
Space Name
Zone 10
L11 B.perbincangan+dok.
Zone 11
L11 S44
Zone 12
L11 Open office 2
Zone 13
L11 Open office 4
Zone 14
L11 Open office 5
Zone 15
L11 Open office 6
Zone 16
L11 Open office 7
Zone 17
L11 Open office 8
07/27/2015
02:45PM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.2
Jul 1600
263
0.0
54.2
4.86
4.1
Nov 1100
481
0.0
21.7
22.19
10.3
Jul 1600
1226
0.0
334.0
3.67
7.4
Nov 1600
879
0.0
66.0
13.31
4.8
Dec 1600
569
0.0
57.2
9.95
6.5
Dec 1600
772
0.0
47.3
16.31
4.6
Dec 1600
551
0.0
60.0
9.18
2.7
Aug 1100
317
0.0
61.6
5.15
Page 2 of 2
07/27/2015
02:45PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Page 1 of 2
07/27/2015
02:45PM
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
35
59.3
0.30
7.0
2.50
1.00
35
35
1.000
24
64.0
0.30
2.0
2.50
1.00
24
24
1.000
38
34.3
0.30
11.0
2.50
1.00
38
38
1.000
23
41.9
0.30
4.0
2.50
1.00
23
23
1.000
27
41.0
0.30
6.0
2.50
1.00
27
27
1.000
18
29.4
0.60
0.0
0.00
1.00
18
18
1.000
32
52.8
0.60
0.0
0.00
1.00
32
32
1.000
12
22.4
0.30
2.0
2.50
1.00
12
12
1.000
30
59.1
0.30
5.0
2.50
1.00
30
30
1.000
56
54.2
0.30
16.0
2.50
1.00
56
56
1.000
14
21.7
0.30
3.0
2.50
1.00
14
14
1.000
205
334.0
0.30
42.0
2.50
1.00
205
205
1.000
35
66.0
0.30
6.0
2.50
1.00
35
35
1.000
37
57.2
0.30
8.0
2.50
1.00
37
37
1.000
34
47.3
0.30
8.0
2.50
1.00
34
34
1.000
38
60.0
0.30
8.0
2.50
1.00
38
38
1.000
26
684
61.6
0.30
3.0
2.50
1.00
26
26
684
1.000
1.000
Page 2 of 2
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
173 m
9937
267 m
1099
0 m
0
173 m
8179
0 m
0
0 m
0
0 m
0
107 m
1958
0 m
0
12168 W
9734
0W
0
15487 W
14104
131
7056
0
0
5% / 5%
2603
54669
67562
0%
0
70%
0
0%
0
6409 L/s
0
684 L/s
7613
6409 L/s
10014
0
0%
0
85189
85189
85189
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:45PM
Latent
(W)
7873
0
0
394
8267
8267
22764
31030
31031
31031
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
173 m
267 m
0
0 m
0
173 m
0
0 m
0
0 m
0
0 m
0
107 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2090
0
0
0
0
0
0
0
684 L/s
0
684 L/s
-2577
-2346
684 L/s
-5251
0
0%
0
-9918
-2346
-9918
-2346
-9918
-2346
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:45PM
AHU L12-1
CW AHU
VAV
Number of zones
Floor Area
Location
23
1184.6 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
146.7
105.4
7863
8383
8514
0.718
8.1
123.9
5.02
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jul 1500
34.0 / 28.0
25.9 / 19.5
14.7 / 14.2
13.5
0.100
53
16.0
17 of 23
0.4
C
C
C
C
%
C
OK
K
8383 L/s
8361 L/s
7.08 L/(s-m)
878 L/s
0.74 L/(s-m)
L/s/person
16.06 BHP
11.98 kW
1000 Pa
4.46 L/s/person
Page 1 of 1
07/27/2015
02:45PM
AHU L12-1
CW AHU
VAV
Number of zones
Floor Area
Location
23
1184.6 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Zone 18
Zone 19
Zone 20
Zone 21
Zone 22
Zone 23
Maximum
Cooling
Sensible
(kW)
2.4
2.8
6.2
3.6
2.8
1.8
1.9
3.1
1.7
6.5
3.1
1.7
2.8
6.4
2.0
1.7
2.1
2.5
1.7
3.0
5.6
5.4
1.2
Design
Air
Flow
(L/s)
283
329
737
427
336
211
221
373
197
771
365
196
328
754
242
200
244
293
196
356
663
643
147
Minimum
Air
Flow
(L/s)
32
42
43
28
42
41
28
41
43
44
42
42
41
43
43
30
46
41
42
42
44
33
5
Time
of
Peak
Load
Aug 1600
Nov 1600
Sep 1600
Jul 1600
Jun 1600
Jul 1600
Sep 1600
Jan 1600
Jan 1600
Jun 1600
Jun 1600
Jul 1600
Jun 1600
Jun 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1500
Jul 1600
Jun 1200
Jun 1500
Jul 1600
Jul 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
53.1
40.8
43.0
92.8
41.0
35.6
47.1
137.6
42.3
46.0
38.5
40.0
38.0
43.0
43.0
58.4
53.8
38.0
40.0
39.3
45.2
110.0
18.1
Zone
L/(s-m)
5.32
8.06
17.13
4.60
8.20
5.92
4.70
2.71
4.66
16.77
9.47
4.91
8.63
17.54
5.63
3.43
4.53
7.72
4.91
9.06
14.68
5.85
8.12
Zone Name /
Space Name
Zone 1
L12 Bilik setor 2a
Zone 2
L12 Jusa C (1)
Zone 3
L12 Jusa C (2)
Zone 4
L12 Corridor 1
Zone 5
L12 Jusa C (3)
Zone 6
L12 Jusa C (4)
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.4
Aug 1600
283
0.0
53.1
5.32
2.8
Nov 1600
329
0.0
40.8
8.06
6.2
Sep 1600
737
0.0
43.0
17.13
3.6
Jul 1600
427
0.0
92.8
4.60
2.8
Jun 1600
336
0.0
41.0
8.20
1.8
Jul 1600
211
0.0
35.6
5.92
Page 1 of 2
Zone Name /
Space Name
Zone 7
L12 Bilik setor 2b
Zone 8
L12 Corridor 2
Zone 9
L12 Jusa C (5)
Zone 10
L12 Jusa C (6)
Zone 11
L12 Jusa C (7)
Zone 12
L12 Jusa C (8)
Zone 13
L12 Jusa C (9)
Zone 14
L12 Jusa C (10)
Zone 15
L12 Jusa C (11)
Zone 16
L12 Kaunter pertanyaan 1
Zone 17
L12 B.perbincangan2+fail
Zone 18
L12 Jusa C (12)
Zone 19
L12 Jusa C (13)
Zone 20
L12 Jusa C (14)
Zone 21
L12 Jusa C (15)
Zone 22
L12 Lift Lobby
Zone 23
L12 Service Lobby
07/27/2015
02:45PM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.9
Sep 1600
221
0.0
47.1
4.70
3.1
Jan 1600
373
0.0
137.6
2.71
1.7
Jan 1600
197
0.0
42.3
4.66
6.5
Jun 1600
771
0.0
46.0
16.77
3.1
Jun 1600
365
0.0
38.5
9.47
1.7
Jul 1600
196
0.0
40.0
4.91
2.8
Jun 1600
328
0.0
38.0
8.63
6.4
Jun 1600
754
0.0
43.0
17.54
2.0
Jul 1600
242
0.0
43.0
5.63
1.7
Jul 1600
200
0.0
58.4
3.43
2.1
Jul 1600
244
0.0
53.8
4.53
2.5
Jul 1500
293
0.0
38.0
7.72
1.7
Jul 1600
196
0.0
40.0
4.91
3.0
Jun 1200
356
0.0
39.3
9.06
5.6
Jun 1500
663
0.0
45.2
14.68
5.4
Jul 1600
643
0.0
110.0
5.85
1.2
Jul 1600
147
0.0
18.1
8.12
Page 2 of 2
07/27/2015
02:45PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Page 1 of 3
07/27/2015
02:45PM
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
32
53.1
0.60
0.0
0.00
1.00
32
32
1.000
42
40.8
0.30
12.0
2.50
1.00
42
42
1.000
43
43.0
0.30
12.0
2.50
1.00
43
43
1.000
28
92.8
0.30
0.0
0.00
1.00
28
28
1.000
42
41.0
0.30
12.0
2.50
1.00
42
42
1.000
41
35.6
0.30
12.0
2.50
1.00
41
41
1.000
28
47.1
0.60
0.0
0.00
1.00
28
28
1.000
41
137.6
0.30
0.0
0.00
1.00
41
41
1.000
43
42.3
0.30
12.0
2.50
1.00
43
43
1.000
44
46.0
0.30
12.0
2.50
1.00
44
44
1.000
42
38.5
0.30
12.0
2.50
1.00
42
42
1.000
42
40.0
0.30
12.0
2.50
1.00
42
42
1.000
41
38.0
0.30
12.0
2.50
1.00
41
41
1.000
43
43.0
0.30
12.0
2.50
1.00
43
43
1.000
43
43.0
0.30
12.0
2.50
1.00
43
43
1.000
30
58.4
0.30
5.0
2.50
1.00
30
30
1.000
46
53.8
0.30
12.0
2.50
1.00
46
46
1.000
41
38.0
0.30
12.0
2.50
1.00
41
41
1.000
42
40.0
0.30
12.0
2.50
1.00
42
42
1.000
42
39.3
0.30
12.0
2.50
1.00
42
42
1.000
Page 2 of 3
07/27/2015
02:45PM
44
45.2
0.30
12.0
2.50
1.00
44
44
1.000
33
110.0
0.30
0.0
2.50
1.00
33
33
1.000
5
878
18.1
0.30
0.0
2.50
1.00
5
878
1.000
1.000
Page 3 of 3
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Jul 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
164 m
14094
289 m
1251
0 m
0
164 m
7758
0 m
0
0 m
0
0 m
0
344 m
6145
0 m
0
13031 W
10424
0W
0
16584 W
15104
197
10611
0
0
5% / 5%
3269
68656
83684
0%
0
70%
0
0%
0
7863 L/s
0
878 L/s
9683
7863 L/s
12051
0
0%
0
105418
105418
105418
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:45PM
Latent
(W)
11840
0
0
592
12432
12432
28898
41329
41329
41329
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
164 m
289 m
0
0 m
0
164 m
0
0 m
0
0 m
0
0 m
0
344 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2521
0
0
0
0
0
0
0
878 L/s
0
878 L/s
-3469
-2611
878 L/s
-6393
0
0%
0
-12383
-2611
-12383
-2611
-12383
-2611
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/27/2015
02:45PM
AHU L12-2
CW AHU
VAV
Number of zones
Floor Area
Location
24
1125.3 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
138.2
94.4
6931
7423
7709
0.683
8.1
122.8
4.73
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1400
33.7 / 27.9
26.0 / 19.9
14.7 / 14.2
13.5
0.100
54
16.0
14 of 24
0.5
C
C
C
C
%
C
OK
K
7423 L/s
7404 L/s
6.60 L/(s-m)
922 L/s
0.82 L/(s-m)
L/s/person
14.22 BHP
10.61 kW
1000 Pa
4.17 L/s/person
Page 1 of 1
07/27/2015
02:45PM
AHU L12-2
CW AHU
VAV
Number of zones
Floor Area
Location
24
1125.3 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Zone 18
Zone 19
Zone 20
Zone 21
Zone 22
Zone 23
Zone 24
Maximum
Cooling
Sensible
(kW)
1.5
1.9
1.6
2.5
5.3
1.9
2.5
0.9
1.5
1.7
2.3
1.6
5.3
3.2
1.6
2.4
6.2
3.8
2.7
1.6
1.6
1.7
3.1
6.4
Design
Air
Flow
(L/s)
178
224
187
301
633
226
295
108
176
201
278
193
632
374
196
287
741
447
321
196
189
196
370
760
Minimum
Air
Flow
(L/s)
41
41
25
42
43
20
42
15
23
41
46
30
44
42
42
41
43
49
41
42
42
42
42
44
Time
of
Peak
Load
Jan 1600
Jul 1600
Aug 1500
Jul 1500
Aug 1100
Jul 1600
Dec 1200
Jul 1600
Aug 1100
Jul 1600
Jul 1600
Jan 1600
Nov 1100
Dec 1600
Aug 1600
Dec 1200
Dec 1600
Jan 1600
Nov 1600
Aug 1600
Jan 1600
Jul 1600
Dec 1600
Nov 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
35.3
36.0
42.0
40.8
43.0
65.1
40.8
25.4
37.8
35.3
53.8
58.6
45.3
39.2
40.0
38.0
43.0
164.6
38.0
40.0
39.2
39.6
38.5
46.0
Zone
L/(s-m)
5.04
6.23
4.45
7.37
14.73
3.47
7.22
4.26
4.65
5.69
5.17
3.30
13.95
9.55
4.89
7.56
17.24
2.71
8.46
4.89
4.81
4.95
9.62
16.52
Zone Name /
Space Name
Zone 1
L12 Jusa C (16)
Zone 2
L12 Jusa C (17)
Zone 3
L12 Bilik setor 3
Zone 4
L12 Jusa C (18)
Zone 5
L12 Jusa C (19)
Zone 6
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.5
Jan 1600
178
0.0
35.3
5.04
1.9
Jul 1600
224
0.0
36.0
6.23
1.6
Aug 1500
187
0.0
42.0
4.45
2.5
Jul 1500
301
0.0
40.8
7.37
5.3
Aug 1100
633
0.0
43.0
14.73
Page 1 of 2
Zone Name /
Space Name
L12 Corridor 3
Zone 7
L12 Jusa C (20)
Zone 8
L12 Bilik utiliti 1
Zone 9
L12 Bilik setor 1
Zone 10
L12 Jusa C (21)
Zone 11
L12 B.perbincangan1+fail
Zone 12
L12 Kaunter pertanyaan 2
Zone 13
L12 Jusa C (22)
Zone 14
L12 Jusa C (23)
Zone 15
L12 Jusa C (24)
Zone 16
L12 Jusa C (25)
Zone 17
L12 Jusa C (26)
Zone 18
L12 Corridor 4
Zone 19
L12 Jusa C (27)
Zone 20
L12 Jusa C (28)
Zone 21
L12 Jusa C (29)
Zone 22
L12 Jusa C (30)
Zone 23
L12 Jusa C (31)
Zone 24
L12 Jusa C (32)
07/27/2015
02:45PM
Mult.
1
Cooling
Sensible
(kW)
1.9
Time
of
Load
Jul 1600
Air
Flow
(L/s)
226
Heating
Load
(kW)
0.0
Floor
Area
(m)
65.1
Space
L/(s-m)
3.47
2.5
Dec 1200
295
0.0
40.8
7.22
0.9
Jul 1600
108
0.0
25.4
4.26
1.5
Aug 1100
176
0.0
37.8
4.65
1.7
Jul 1600
201
0.0
35.3
5.69
2.3
Jul 1600
278
0.0
53.8
5.17
1.6
Jan 1600
193
0.0
58.6
3.30
5.3
Nov 1100
632
0.0
45.3
13.95
3.2
Dec 1600
374
0.0
39.2
9.55
1.6
Aug 1600
196
0.0
40.0
4.89
2.4
Dec 1200
287
0.0
38.0
7.56
6.2
Dec 1600
741
0.0
43.0
17.24
3.8
Jan 1600
447
0.0
164.6
2.71
2.7
Nov 1600
321
0.0
38.0
8.46
1.6
Aug 1600
196
0.0
40.0
4.89
1.6
Jan 1600
189
0.0
39.2
4.81
1.7
Jul 1600
196
0.0
39.6
4.95
3.1
Dec 1600
370
0.0
38.5
9.62
6.4
Nov 1600
760
0.0
46.0
16.52
Page 2 of 2
07/27/2015
02:45PM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Page 1 of 3
07/27/2015
02:45PM
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
41
35.3
0.30
12.0
2.50
1.00
41
41
1.000
41
36.0
0.30
12.0
2.50
1.00
41
41
1.000
25
42.0
0.60
0.0
0.00
1.00
25
25
1.000
42
40.8
0.30
12.0
2.50
1.00
42
42
1.000
43
43.0
0.30
12.0
2.50
1.00
43
43
1.000
20
65.1
0.30
0.0
0.00
1.00
20
20
1.000
42
40.8
0.30
12.0
2.50
1.00
42
42
1.000
15
25.4
0.60
0.0
0.00
1.00
15
15
1.000
23
37.8
0.60
0.0
0.00
1.00
23
23
1.000
41
35.3
0.30
12.0
2.50
1.00
41
41
1.000
46
53.8
0.30
12.0
2.50
1.00
46
46
1.000
30
58.6
0.30
5.0
2.50
1.00
30
30
1.000
44
45.3
0.30
12.0
2.50
1.00
44
44
1.000
42
39.2
0.30
12.0
2.50
1.00
42
42
1.000
42
40.0
0.30
12.0
2.50
1.00
42
42
1.000
41
38.0
0.30
12.0
2.50
1.00
41
41
1.000
43
43.0
0.30
12.0
2.50
1.00
43
43
1.000
49
164.6
0.30
0.0
0.00
1.00
49
49
1.000
41
38.0
0.30
12.0
2.50
1.00
41
41
1.000
42
40.0
0.30
12.0
2.50
1.00
42
42
1.000
Page 2 of 3
07/27/2015
02:45PM
42
39.2
0.30
12.0
2.50
1.00
42
42
1.000
42
39.6
0.30
12.0
2.50
1.00
42
42
1.000
42
38.5
0.30
12.0
2.50
1.00
42
42
1.000
44
922
46.0
0.30
12.0
2.50
1.00
44
44
922
1.000
1.000
Page 3 of 3
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1400
COOLING OA DB / WB 33.7 C / 27.9 C
Sensible
Details
(W)
164 m
8969
289 m
1110
0 m
0
164 m
7518
0 m
0
0 m
0
0 m
0
94 m
1680
0 m
0
12378 W
9728
0W
0
15754 W
14249
221
11624
0
0
5% / 5%
2744
57622
73862
0%
0
70%
0
0%
0
6931 L/s
0
922 L/s
9853
6931 L/s
10675
0
0%
0
94391
94391
94391
Positive values are clg loads
Negative values are htg loads
07/27/2015
02:45PM
Latent
(W)
13282
0
0
664
13946
13946
29873
43819
43827
43827
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
164 m
289 m
0
0 m
0
164 m
0
0 m
0
0 m
0
0 m
0
94 m
0
0 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-2470
0
0
0
0
0
0
0
922 L/s
0
922 L/s
-3819
-1680
922 L/s
-5826
0
0%
0
-12114
-1680
-12114
-1680
-12114
-1680
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/28/2015
09:18AM
AHU L13-1
CW AHU
VAV
Number of zones
Floor Area
Location
13
1166.3 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
181.9
127.6
9415
10849
10943
0.702
6.4
155.9
6.22
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Jul 1500
34.0 / 28.0
25.9 / 19.6
14.6 / 14.1
13.4
0.100
53
16.0
13 of 13
0.0
C
C
C
C
%
C
OK
K
10849 L/s
10821 L/s
9.30 L/(s-m)
20.78 BHP
15.50 kW
1000 Pa
1198 L/s
1.03 L/(s-m)
L/s/person
5.16 L/s/person
Page 1 of 1
07/28/2015
09:18AM
AHU L13-1
CW AHU
VAV
Number of zones
Floor Area
Location
13
1166.3 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Maximum
Cooling
Sensible
(kW)
5.0
4.5
5.0
4.9
2.9
2.9
1.2
16.1
19.4
3.2
20.0
5.4
1.7
Design
Air
Flow
(L/s)
597
531
591
587
338
349
140
1905
2302
384
2376
643
198
Minimum
Air
Flow
(L/s)
47
20
40
41
36
20
13
264
157
30
492
33
5
Time
of
Peak
Load
Oct 1600
Jul 1600
Aug 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Aug 1600
Jun 1600
Jul 1600
Jul 1600
Jul 1600
Aug 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
58.2
66.2
32.0
68.1
60.4
58.8
25.1
203.5
190.2
67.1
208.6
110.0
18.1
Zone
L/(s-m)
10.26
8.02
18.47
8.62
5.60
5.94
5.59
9.36
12.10
5.72
11.39
5.85
10.96
Zone Name /
Space Name
Zone 1
L13 Jusa B
Zone 2
L13 Corridor 1
Zone 3
L13 Bilik mesyuarat 1
Zone 4
L13 B. setor+fail sulit
Zone 5
L13 B.fail terbuka+tutup
Zone 6
L13 Kaunter pertanyaan 1
Zone 7
L13 AV Room
Zone 8
L13 B. mesyuarat s/jaya
Zone 9
L13 Bilik rehat s/jaya
Zone 10
L13 Ruang menunggu
Zone 11
L13 Bilik jamuan s/jaya
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
5.0
Oct 1600
597
0.0
58.2
10.26
4.5
Jul 1600
531
0.0
66.2
8.02
5.0
Aug 1600
591
0.0
32.0
18.47
4.9
Jul 1600
587
0.0
68.1
8.62
2.9
Jul 1600
338
0.0
60.4
5.60
2.9
Jul 1600
349
0.0
58.8
5.94
1.2
Jul 1600
140
0.0
25.1
5.59
16.1
Aug 1600
1905
0.0
203.5
9.36
19.4
Jun 1600
2302
0.0
190.2
12.10
3.2
Jul 1600
384
0.0
67.1
5.72
20.0
Jul 1600
2376
0.0
208.6
11.39
Page 1 of 2
Zone Name /
Space Name
Zone 12
L13 Lift Lobby
Zone 13
L13 Service Lobby
07/28/2015
09:18AM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
5.4
Jul 1600
643
0.0
110.0
5.85
1.7
Aug 1600
198
0.0
18.1
10.96
Page 2 of 2
07/28/2015
09:18AM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
47
58.2
0.30
12.0
2.50
1.00
47
47
1.000
20
66.2
0.30
0.0
0.00
1.00
20
20
1.000
40
32.0
0.30
12.0
2.50
1.00
40
40
1.000
41
68.1
0.60
0.0
0.00
1.00
41
41
1.000
36
60.4
0.60
0.0
0.00
1.00
36
36
1.000
20
58.8
0.30
1.0
2.50
1.00
20
20
1.000
13
25.1
0.30
2.0
2.50
1.00
13
13
1.000
264
203.5
0.30
81.0
2.50
1.00
264
264
1.000
157
190.2
0.30
40.0
2.50
1.00
157
157
1.000
30
67.1
0.30
4.0
2.50
1.00
30
30
1.000
492
208.6
0.90
80.0
3.80
1.00
492
492
1.000
33
110.0
0.30
0.0
2.50
1.00
33
33
1.000
5
1198
18.1
0.30
0.0
2.50
1.00
5
1198
1.000
1.000
Page 1 of 1
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Jul 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
153 m
12932
288 m
1252
18 m
396
153 m
7206
0 m
0
0 m
0
0 m
0
355 m
6419
1038 m
19556
12829 W
10263
0W
0
16328 W
14871
232
12496
0
0
5% / 5%
4269
89658
97713
0%
0
70%
924
0%
0
9415 L/s
0
1198 L/s
13409
9415 L/s
15554
0
0%
0
127600
127600
127600
Positive values are clg loads
Negative values are htg loads
07/28/2015
09:18AM
Latent
(W)
13943
0
0
697
14640
14640
39635
54275
54281
54281
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
153 m
288 m
0
18 m
0
153 m
0
0 m
0
0 m
0
0 m
0
355 m
0
1038 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-4130
0
0
0
0
0
0
0
1198 L/s
0
1198 L/s
-4041
-3117
1198 L/s
-8343
0
0%
0
-16514
-3117
-16514
-3117
-16514
-3117
Positive values are htg loads
Negative values are clg loads
Page 1 of 1
07/28/2015
09:18AM
AHU L13-2
CW AHU
VAV
Number of zones
Floor Area
Location
20
1119.0 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
145.8
108.2
8279
9484
9881
0.743
7.7
130.3
4.98
kW
kW
L/s
L/s
L/s
L/s
Load occurs at
OA DB / WB
Entering DB / WB
Leaving DB / WB
Coil ADP
Bypass Factor
Resulting RH
Design supply temp.
Zone T-stat Check
Max zone temperature deviation
Aug 1500
34.0 / 28.0
25.5 / 19.2
14.6 / 14.1
13.4
0.100
53
16.0
20 of 20
0.0
C
C
C
C
%
C
OK
K
9484 L/s
9459 L/s
8.48 L/(s-m)
806 L/s
0.72 L/(s-m)
L/s/person
18.17 BHP
13.55 kW
1000 Pa
4.79 L/s/person
Page 1 of 1
07/28/2015
09:18AM
AHU L13-2
CW AHU
VAV
Number of zones
Floor Area
Location
20
1119.0 m
Kuala Lumpur, Malaysia
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
Zone 17
Zone 18
Zone 19
Zone 20
Maximum
Cooling
Sensible
(kW)
2.5
2.1
6.0
3.5
5.6
2.9
4.3
2.3
2.4
6.0
2.8
6.3
1.9
7.7
7.8
2.5
4.3
4.4
2.9
5.1
Design
Air
Flow
(L/s)
294
250
711
409
668
343
506
274
288
709
329
751
225
910
920
302
510
525
347
611
Minimum
Air
Flow
(L/s)
44
21
48
41
48
34
23
36
36
65
49
44
30
67
56
34
41
23
25
42
Time
of
Peak
Load
Jul 1600
Aug 1600
Jul 1200
Jul 1600
Nov 1200
Aug 1600
Aug 1500
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Dec 1500
Jul 1600
Oct 1500
Nov 1600
Aug 1600
Dec 1600
Oct 1600
Aug 1600
Jul 1600
Maximum
Heating
Load
(kW)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Zone
Floor
Area
(m)
49.0
36.1
59.0
68.1
59.1
47.0
60.9
36.8
36.8
106.8
46.1
46.3
33.7
99.6
86.1
47.0
35.3
25.0
33.3
107.0
Zone
L/(s-m)
5.99
6.93
12.05
6.01
11.30
7.29
8.31
7.44
7.84
6.63
7.13
16.21
6.68
9.14
10.68
6.42
14.46
21.01
10.43
5.71
Zone Name /
Space Name
Zone 1
L13 B. persediaan jamuan
Zone 2
L13 Bilik PA 1
Zone 3
L13 Jusa C (1)
Zone 4
L13 Bilik fail
Zone 5
L13 Jusa C (2)
Zone 6
L13 Bilik PA 2
Zone 7
L13 Open office 1
Zone 8
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.5
Jul 1600
294
0.0
49.0
5.99
2.1
Aug 1600
250
0.0
36.1
6.93
6.0
Jul 1200
711
0.0
59.0
12.05
3.5
Jul 1600
409
0.0
68.1
6.01
5.6
Nov 1200
668
0.0
59.1
11.30
2.9
Aug 1600
343
0.0
47.0
7.29
4.3
Aug 1500
506
0.0
60.9
8.31
Page 1 of 2
Zone Name /
Space Name
L13 Bilik mesyuarat 2
Zone 9
L13 Bilik mesyuarat 3
Zone 10
L13 Galeri setiausaha
Zone 11
L13 Bilik perbincangan
Zone 12
L13 B. mesyuarat 4+fail
Zone 13
L13 Bilik PA 3
Zone 14
L13 Turus III
Zone 15
L13 Jusa A
Zone 16
L13 Bilik PA 4
Zone 17
L13 Bilik mesyuarat 5
Zone 18
L13 L48
Zone 19
L13 Bilik PA 5+fail
Zone 20
L13 Open office 2
07/28/2015
09:18AM
Mult.
1
Cooling
Sensible
(kW)
2.3
Time
of
Load
Jul 1600
Air
Flow
(L/s)
274
Heating
Load
(kW)
0.0
Floor
Area
(m)
36.8
Space
L/(s-m)
7.44
2.4
Jul 1600
288
0.0
36.8
7.84
6.0
Jul 1600
709
0.0
106.8
6.63
2.8
Jul 1600
329
0.0
46.1
7.13
6.3
Dec 1500
751
0.0
46.3
16.21
1.9
Jul 1600
225
0.0
33.7
6.68
7.7
Oct 1500
910
0.0
99.6
9.14
7.8
Nov 1600
920
0.0
86.1
10.68
2.5
Aug 1600
302
0.0
47.0
6.42
4.3
Dec 1600
510
0.0
35.3
14.46
4.4
Oct 1600
525
0.0
25.0
21.01
2.9
Aug 1600
347
0.0
33.3
10.43
5.1
Jul 1600
611
0.0
107.0
5.71
Page 2 of 2
07/28/2015
09:18AM
1. Summary
Ventilation Sizing Method
Design Condition
Occupant Diversity
Uncorrected Ventilation Airflow Rate
System Ventilation Efficiency
Design Ventilation Airflow Rate
Page 1 of 3
07/28/2015
09:18AM
Minimum
Supply Air
Mult.
(L/s)
Floor
Area
(m)
Required
Outdoor Air
(L/(s-m))
Time
Averaged
Occupancy
Required
Air
Outdoor Air Distribution
(L/s/person) Effectiveness
Required
Outdoor Air
(L/s)
Uncorrected
Outdoor Air
(L/s)
Space
Ventilation
Efficiency
44
49.0
0.90
0.0
3.80
1.00
44
44
1.000
21
36.1
0.30
4.0
2.50
1.00
21
21
1.000
48
59.0
0.30
12.0
2.50
1.00
48
48
1.000
41
68.1
0.60
0.0
0.00
1.00
41
41
1.000
48
59.1
0.30
12.0
2.50
1.00
48
48
1.000
34
47.0
0.30
8.0
2.50
1.00
34
34
1.000
23
60.9
0.30
2.0
2.50
1.00
23
23
1.000
36
36.8
0.30
10.0
2.50
1.00
36
36
1.000
36
36.8
0.30
10.0
2.50
1.00
36
36
1.000
65
106.8
0.30
13.0
2.50
1.00
65
65
1.000
49
46.1
0.30
14.0
2.50
1.00
49
49
1.000
44
46.3
0.30
12.0
2.50
1.00
44
44
1.000
30
33.7
0.30
8.0
2.50
1.00
30
30
1.000
67
99.6
0.30
15.0
2.50
1.00
67
67
1.000
56
86.1
0.30
12.0
2.50
1.00
56
56
1.000
34
47.0
0.30
8.0
2.50
1.00
34
34
1.000
41
35.3
0.30
12.0
2.50
1.00
41
41
1.000
23
25.0
0.30
6.0
2.50
1.00
23
23
1.000
25
33.3
0.30
6.0
2.50
1.00
25
25
1.000
42
806
107.0
0.30
4.0
2.50
1.00
42
42
806
1.000
1.000
Page 2 of 3
07/28/2015
09:18AM
Page 3 of 3
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
>> Total Conditioning
Key:
DESIGN COOLING
COOLING DATA AT Aug 1500
COOLING OA DB / WB 34.0 C / 28.0 C
Sensible
Details
(W)
155 m
9117
330 m
1367
0 m
0
155 m
7333
0 m
0
0 m
0
0 m
0
176 m
3234
1119 m
21078
12309 W
9847
0W
0
15666 W
14268
168
9049
0
0
5% / 5%
3765
79057
85493
0%
0
70%
0
0%
0
8279 L/s
0
806 L/s
9140
8279 L/s
13611
0
0%
0
108243
108243
108243
Positive values are clg loads
Negative values are htg loads
07/28/2015
09:18AM
Latent
(W)
10097
0
0
505
10602
10602
26914
37516
37519
37519
DESIGN HEATING
HEATING DATA AT DES HTG
HEATING OA DB / WB 21.7 C / 15.2 C
Sensible
Latent
Details
(W)
(W)
155 m
330 m
0
0 m
0
155 m
0
0 m
0
0 m
0
0 m
0
176 m
0
1119 m
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0%
0
0
0
0
-3201
0
0
0
0
0
0
0
806 L/s
0
806 L/s
-2295
-3664
806 L/s
-6997
0
0%
0
-12493
-3664
-12493
-3664
-12493
-3664
Positive values are htg loads
Negative values are clg loads
Page 1 of 1