VP223R, VP224R
SPECIFICATIONS
MATERIALS
KEY FEATURES
Media Compatibility
It is the responsibility of the installer or product
specifier to verify media compatibility of the
valves construction materials with the supplier
of water treatment/heat transfer solution.
Best Practice Guidelines
It is recommended to fit a strainer upstream
of the valve to increase reliability and to follow
water treatment guidelines as detailed in
VDI 2035.
Recommendations
The pipework system should be flushed prior
to the operation. The inner cartridge should
be removed and the valve capped with the
pre-setting/blind cap prior to flushing.
Valves should be installed in the return pipe
to reduce exposure to media temperature
extremes.
Field Devices
02
DN 50 S
DN 40 S
DN 32 S
DN 25 H
DN 25 S
DN 20 H
DN 20 S
DN 15 H
DN 15 S
DN 15 L
Size
Flow range*
Venturi (Kvm)**
m3/h
GPM (US)
I/s
0.036 - 0.118
0.16 - 0.52
0.010 - 0.033
0.23
0.09 - 0.45
0.40 - 1.98
0.025 - 0.125
0.78
VP223R-15BQH
0.30 - 1.40
1.32 - 6.18
0.083 - 0.390
2.5
VP223R-20BQS
0.32 - 0.88
1.41 - 3.88
0.089 - 0.245
1.9
0.84 - 2.22
3.68 - 9.78
0.232 - 0.617
4.7
0.87 - 2.34
3.80 - 10.30
0.240 - 0.650
5.05
1.75 - 3.33
7.69 - 14.66
0.485 - 0.925
8.25
1.91 - 4.40
8.40 - 19.34
0.530 - 1.220
8.35
VP223R-15BQL
VP223R-15BQS
VP223R-20BQH
VP223R-25BQS
VP223R-25BQH
VP223R-32BQS
DN15
DN20
DN25
DN32
VP224R-40BQS
DN40
3.67 - 7.56
16.17 - 33.29
1.02 - 2.10
17
VP224R-50BQS
DN50
5.18 - 12.60
22.83 - 55.48
1.44 - 3.50
28.5
Actuator
MP200, MP140
AVUE, AVUM,
AVUX
* Adjustable Maximum Flow range for a fully open valve. Flow will control down to close off from chosen actuator.
2014 Schneider Electric. All rights reserved.
** Kvm, Venturi measurement for fine flow adjustment using hand held flow meter devices,
do not size the valve using traditional valve sizing calculations with this figure.
May 2014
Field Devices
03
KEY FEATURES
1 - PICV with Thermal or electro-motoric actuator
(flow limiting balancing valve without)
2 - Flow pre-setting unit adjusted radially
independent of full linear stroke of the valve plug
1
8
2
3
4
5
6
REMOVABLE CARTRIDGE
The flow balancing cartridge can be removed
from the valve body to enable unrestricted system
flushing. The flow presetting tool doubles as a blind
cap to seal the valve housing. A hex key is used to
tighten and remove the cap.
Schneider Electric Telephone Europe: Malm, Sweden +46 40 38 68 50 Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
03-00278-01-en
May 2014
Field Devices
P REGULATOR
04
m3/h
Qsized
kPa
0
30.0
400
m3/h
Within the working pressure range of 30400kPa (PminA to Pmax) a high flow control
accuracy (Qsized) of at least 7% (QA - QB) is
ensured, compared with the flow set point.
QA
Qsized
QB
PminA
30.0
Pmax
400
ACTUATORS
MP140
Thermal On / Off for VP223R
(NC/NO) pressure independent
flow limiting control
AVUE
Proportional Electro-Motoric
for VP224R (DN40/50)
Full pressure independent
flow control
Floating or 0-10V modulating
control
MP200
Proportional Electro-Motoric for VP223R
Full pressure independent flow control
Floating or 0-10V modulating control
Control
MP140NC-24T
24 V AC
MP140NC-230T
230V AC
MP140NO-24T
24V AC
MP140NO-230T
230V AC
MP200-230F
230V AC
Floating
MP200-24F
24V AC
Floating
MP200-24M
24V AC
0-10V*
AVUX5202
24V AC
Floating
AVUM5601
230V AC
Floating
AVUE5354
24V AC
0-10V
Valve Type
Data Sheet
2014 Schneider Electric. All rights reserved.
Part Number
03-00280
DN15-32
03-00279
DN40-50
03-00281
May 2014
Field Devices
05
5
Specification Code
Family
P 2 2 3 R
1 5
End Connection:
R - Rp /Rs internal thread
Valve Type:
P- PIVC
Number of Ways:
2 - 2-Way
Actuator Connection
Linear Valves:
3 - M30 x 1.5 (3.5mm Stroke)
4 - V Groove (Satchwell)
Q 0 . 4 5 E
Material:
B - Bronze body, Brass trim
S D 0 0
Seal:
E - EPDM
Options, Specials
and Revisions:
00 - no specials
Orifice - Examples:
15 - 15 DN
Part Number
Part Number Annex
Main Type
Family
Valve Type
Number of Ways
Plug Type
End Connection
Size, Material
Orifice
Flow
Material
QL - Low Flow
QS - Standard Flow
QH - High Flow
Actuator Connection
Description
VP223R-15BQL
VP223R-15BQS
VP223R-15BQH
VP223R-20BQS
VP223R-20BQH
VP223R-25BQS
VP223R-25BQH
VP223R-32BQS
VP224R-40BQS
VP224R-50BQS
3
3
3
3
3
3
3
3
H2
Size
H1
H2
DN15
95
35
75
44
DN20
120
49
83
55
DN25
127
56
81
71
DN32
154
72
87
82
DN40
190
212
110
DN50
195
212
111
H1
Schneider Electric Telephone Europe: Malm, Sweden +46 40 38 68 50 Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
03-00278-01-en
May 2014
DIMENSIONS (mm)
Field Devices
06
EXPLANATION OF CHARTS
Black Curve
Notch
This curve indicates the flow rate for a given valve setting when using the scale
on the presetting caps (+/- 7% Accuracy).
Scale
Red Curve
This curve represents the Venturi signal for setting the valve using a manometer
(+/- 3% Accuracy).
Precise setting of the valves max flow is easily done with a digital flow meter. Simply
enter the Venturi Kvm into the flow meter and turn the pre-setting tool until the design
flow is displayed on the meter.
For valve setting with a differential pressure manometer, the red curve on the charts
indicates the Venturi signal that will be measured on the valve for any given flow.
NOTE: Before setting the design flow on the VP223R / VP224R valves, the pump must
be set at maximum capacity and all service valves in the system must be in fully open
position. The differential pressure across the valve must at all times not exceed 400 kPa.
The design flow is easily adjusted with the supplied pre-setting tool. The pre-setting tool
is mounted on top of the valve covering the valve stem. The scale on the pre-setting
tool is read against the notch on the brass housing of the valve. Flow charts are based
on water with an Specific Gravity of 1.0.
Valve setting
setting
% Valve
%
kPa
100%
90%
36
32
70%
70%
28
Venturi signal
60%
24
22kPa
50%
20
40%
16
30%
12
20%
10%
0%
0.005
18
0.01
36
0.015
54
0.02
72
0.025
90
0.03
108
80%
0.035 l/h
118 l/h
Flow, Q
Shaded area is where the setting tolerance using a manometer or flow meter is less than the normal 3% accuracy.
Schneider Electric Telephone Europe: Malm, Sweden +46 40 38 68 50 Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
03-00278-01-en
May 2014
Field Devices
07
7
kPa
ValveValve
setting
setting
% %
kPa
100%
36
90%
Venturi signal
80%
32
70%
28
60%
24
50%
20
40%
16
30%
12
20%
10%
0%
0.025
90
0.035
126
0.045
162
0.055
198
0.065
234
0.075
270
0.085
306
0.095
342
0.105
378
0.115
414
0.125 l/s
450 l/h
Flow, Q
kPa
kPa
90%
45
80%
40
Venturi signal
35
70%
60%
30
50%
25
40%
20
30%
15
20%
10
10%
Valve setting
Valve setting
%
%
100%
0%
0.05
0.1
360
0.15
540
0.2
720
0.25
900
0.3
1,080
0.35
1,260
0.4
1,440
l/s
l/h
Flow, Q
Shaded area is where the setting tolerance using a manometer or flow meter is less than the normal 3% accuracy.
Schneider Electric Telephone Europe: Malm, Sweden +46 40 38 68 50 Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
03-00278-01-en
May 2014
Field Devices
08
8
kPa
Valve
setting
Valve
setting
% %
kPa
100%
25
90%
Venturi signal
20
80%
70%
15
60%
50%
10
40%
30%
20%
10%
0%
0
0.08 0.09 0.1
288 326 360
0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.2 0.21 0.22 0.23 0.24 0.245 l/s
396 432 468 504 540 576 612 648 684 720 756 792 828 864 882 l/h
Flow, Q
Valvesetting
setting
Valve
%%
kPa
kPa
25
90%
Venturi signal
80%
20
70%
60%
15
50%
40%
100%
10
30%
20%
10%
0%
0.2
0.25
0.3
0.35
0.4
0.45
0.5
0.55
0.6
0
0.617 l/s
720
900
1,080
1,260
1,440
1,620
1,800
1,980
2,160
2,221 l/h
Flow, Q
Schneider Electric Telephone Europe: Malm, Sweden +46 40 38 68 50 Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
03-00278-01-en
May 2014
Field Devices
09
9
kPa
Valve setting
Valve
setting
%
%
kPa
100%
25
90%
Venturi signal
80%
20
70%
15
60%
50%
10
40%
30%
20%
10%
0%
0.20
720
0.25
900
0.30
1,080
0.35
1,260
0.40
1,440
0.45
1,620
0.50
1,800
0.55
1,980
0.60
2,160
0
0.65 l/h
2,340 l/h
Flow, Q
100%
20
90%
18
80%
Venturi signal
16
70%
14
60%
12
50%
10
40%
30%
20%
10%
2
0
0%
0.45
1,620
kPa
kPa
Valvesetting
setting
Valve
%%
0.50
1,800
0.55
1,980
0.60
2,160
0.65
2,340
0.70
2,520
0.75
2,700
0.80
2,880
0.85
3,060
0.90
3,240
0.925 I/s
3,330 I/h
Flow, Q
Schneider Electric Telephone Europe: Malm, Sweden +46 40 38 68 50 Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
03-00278-01-en
May 2014
Field Devices
010
10
kPa
kPa
100%
40
90%
35
80%
30
70%
Venturi signal
25
60%
50%
20
40%
15
30%
10
20%
10%
0%
0
0.95 1.00 1.05 1.10 1.15 1.20 1.22 I/s
3,420 3,600 3,780 3,960 4,140 4,320 4,400 I/h
Flow, Q
DN40
Venturi Kvm: 17
kPa
kPa
100%
20
90%
18
80%
16
70%
14
60%
12
50%
10
40%
30%
20%
10%
0%
1
L/sec
I/hour 3600
Venturi signal
1.2
4320
1.4
5040
1.6
5760
Flow Q [l/sec.]
1.8
6480
2
7200
Valve setting
setting
Valve
%
0
l/sec
l/hour
Flow, Q
Schneider Electric Telephone Europe: Malm, Sweden +46 40 38 68 50 Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
03-00278-01-en
May 2014
Field Devices
011
11
Valvesetting
setting
Valve
%%
kPa
kPa
100%
20
90%
18
80%
16
70%
14
60%
12
50%
10
40%
30%
20%
10%
0%
1.4
5040
Venturi signal
1.6
5760
1.8
6480
2
7200
2.2
7920
2.4
8640
2.6
9360
2.8
10080
3
10800
3.2
11520
3.4
12240
0
l/sec
I/hour
Flow, Q
Schneider Electric Telephone Europe: Malm, Sweden +46 40 38 68 50 Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
03-00278-01-en
May 2014
Field Devices
012
12
Schneider Electric Telephone Europe: Malm, Sweden +46 40 38 68 50 Telephone Asia Pacific: Singapore +65 6776 3166 www.schneider-electric.com
03-00278-01-en
May 2014