True double-conversion online UPS

Wide input voltage range (110-300 VAC)


Input power factor correction 0.99
Output Power Factor 0.8
50Hz/60Hz frequency converter mode
Programmable power management outlets
Emergency power off function (EPO)
ECO mode operation for energy saving (ECO)
SNMP+USB+RS-232 multiple communications
Smart battery charger design for optimized battery performance
Selectable output voltage via LCD panel

Online UPS

RCT-6000GT
/ RCT-10000GT

RCT-2000GTS
/ RCT-3000GTS

RCT-1000GTS

MODEL

RCT-1000GTS

RCT-2000GTS

PHASE
CAPACITY
INPUT

Voltage
Range

RCT-3000GTS

RCT-6000GT

RCT-10000GT

Single phase with ground


1000 VA/800 W

2000 VA/1600 W

3000 VA/2400 W

6000 VA/4800 W

10000 VA /8000 W

Low Line Transfer

160 VAC 5% or 80 VAC 5% @ 100% load


110 VAC 5% or 50 VAC 5% @ 50% load

176 VAC 3% @ 100% load


110 VAC 3% @ 50% load

Low Line Comeback

175 VAC 5% or 85 VAC 5% @ 100% load

186 VAC 3% @ 100% load


120 VAC 3% @ 50% load

High Line Transfer

300 VAC 5 % or 150 VAC 5 %

High Line Comeback

290 VAC 5 % or 145 VAC 5 %

290 VAC 3%

40 Hz ~ 70 Hz
0.99 @ Nominal Voltage (Full load)

46 ~ 54 Hz or 56 ~ 64 Hz
0.99 @ 100% load

208/220/230/240 VAC or 110/115/120/127 VAC

208/220/230/240 VAC

Frequency Range
Power Factor
OUTPUT
Output Voltage
AC Voltage Regulation (Batt. Mode)

3%

1%

47~53 Hz or 57~63 Hz

46 ~ 54 Hz or 56 ~ 64 Hz

50 Hz 0.25 Hz or 60Hz 0.3 Hz


3:1

50 Hz 0.1 Hz or 60 Hz 0.1 Hz
3:1

Frequency Range (Synchronized Range)


Frequency Range (Batt. Mode)
Current Crest Ratio

3 % THD
(Linear Load)
6 % THD
(Non-linear Load)

Harmonic Distortion

AC Mode to Batt. Mode


Inverter to Bypass
Waveform (Batt. Mode)
EFFICIENCY
AC Mode
Battery Mode

4 % THD (Linear Load)


7 % THD (Non-linear Load)

4 ms (Typical)

Zero
Pure Sinewave

85%

88%

89%
88%

83%
12 V / 7 Ah
3

Typical Recharge Time

12 V / 7 Ah
6

12 V / 9 Ah
6

4 hours recover to 90% capacity

Charging Current (max.)


Charging Voltage

3 % THD (Linear Load)


6 % THD (Non-linear Load)

Zero

Transfer
Time

BATTERY
Battery Type
Numbers

300 VAC 3%

1.0 A
41.0 VDC 1%

82.1 VDC 1%

12 V / 7 Ah
12 V / 9 Ah
20
20
7 hours recover to 90%
9 hours recover to 90%
capacity
capacity
1.0 A
273.0 VDC 1%

INDICATORS
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

LCD Display
ALARM
Battery Mode

Sounding every 4 seconds

Low Battery

Sounding every second

Overload

Sounding twice every second

Fault

Continuously sounding

PHYSICAL
Dimension,DxWxH(mm)
Net Weight (kgs)

397 x 145 x 220


13

421 x 190 x 318


26

592 x 250 x 576


28

81

83

ENVIRONMENT

Humidity

20-90 % RH @ 0- 40C (non-condensing)

Noise Level

Less than 45dB@ 1 Meter

MANAGEMENT
Smart RS-232
USB

Less than 55dB @ 1 Meter

Less than 58dB @ 1 Meter

Supports Windows 2000/2003/XP/Vista/2008,Windows 7, Linux, Unix, and MAC

Optional SNMP

Power management from SNMP manager and web browser

*Derate to 60% of capacity in Frequency converter mode and to 80% when the output voltage
is adjusted to 208VAC.

Battery Pack (Optional built-in charger)


Capacity (VA)

6K/10K

Battery Type

12 V 7 Ah 12 V 9 Ah 12 V 7 Ah 12 V 9 Ah 12 V 7 Ah 12 V 9 Ah

Battery Number

20 pcs

Dimension
(DxWxH) mm

592 X 250 X 576

Net Weight (kgs)

64

20 pcs

72

40 pcs

40 pcs

592 X 250 X 576


109

125

60 pcs

60 pcs

830 X 250 X 576


166

190
* 6K/10K Battery Pack
(capable for 20 pcs or 40 pcs
or 60 pcs batteries inside)

LCD Display Panel:


Input & Battery Voltage Info

Backup Time Info

Fault Info Mute Operation

Output & Battery Voltage Info

Load Info

Battery Info

Mode Operation Info

Software

ViewPower - UPS Management Software


* Allows control and monitoring of multiple UPSs via LAN and INTERNET
* User-friendly power analysis graphs
* Real-time dynamic graphs of UPS data
* Safely OS shutdown and protection from data loss during power failure
* Warning notifications via audible alarm, broadcast, mobile messenger, and e-mail
* Scheduled UPS on/off, battery test, programmable outlet control, and audible alarm control
* Password security protection and remote access management
* Supports multiple OS and local languages

Accessory(Optional)
Remote Control & Monitoring Agent
SNMP Card (Integrated with ViewPower Pro software)

* Allows control and monitoring of multiple UPSs through RJ-45 network connection
* Real-time dynamic graphs of UPS data (voltage, frequency, load level, battery level)
* Warning notifications via audible alarm, broadcast, mobile messenger, e-mail and
SNMP traps
* Historic data log stored in centralized PC database
* Simple firmware upgrade with one click
* Password security protection and remote access management
Supports optional environmental monitoring detector for temperature, humidity
and smoke
* 2-year product warranty