Vous êtes sur la page 1sur 10

Continental Medical College

HVAC Load Analysis


for

Prepared By:
Mudassir Mustafa
Haier Pakistan
8th Floor, Mega Tower, Gulberg II,
Lahore, 54000
Monday, November 07, 2016

Chvac - Full Commercial HVAC Loads Calculation Program


York International
Dubai,

Elite Software Development, Inc.


Continental Medical College
Page 2

General Project Data Input


General Project Information
Project file name:

E:\PROJECTS\Design Projects\FROM JAHAZEB\MEDICAL


COLLEGE\ELITE SOFTWARE CALCULATIONS.CHV
Continental Medical College
Lahore
54000
Monday, October 03, 2011
LAHORE, PAKISTAN
Haier Pakistan
Mudassir Mustafa
8th Floor, Mega Tower, Gulberg II,
Lahore, 54000

Project title:
Project address:
Project city, state, ZIP:
Project date:
Weather reference city:
Company name:
Company representative:
Company address:
Company city:
Barometric pressure:
Altitude:
Latitude:
Mean daily temperature range:
Starting & ending time for HVAC load calculations:
Number of unique zones in this project:

29.170
702.0997
32
27
1am - 12am
1

in.Hg.
feet
Degrees
Degrees

Building Default Values


Calculations performed:
Lighting requirements:
Equipment requirements:
People sensible load multiplier:
People latent load multiplier:
Zone sensible safety factor:
Zone latent safety factor:
Zone heating safety factor:
People diversity factor:
Lighting profile number:
Equipment profile number:
People profile number:
Building default ceiling height:
Building default wall height:

Both heating and cooling loads


1.50
1.50
250
200
10
10
10
80
2
3
1
8.50
11.00

Watts per square foot


Watts per square foot
Btuh per person
Btuh per person
%
%
%
%

feet
feet

Internal Operating Load Profiles (C = 100)


1
2
3
4
5
6
7
8
9
10

hr
1
C
C
C
C
C
C
C
C
C
C

hr
2
C
C
C
C
C
C
C
C
C
C

hr
3
C
C
C
C
C
C
C
C
C
C

hr
4
C
C
C
C
C
C
C
C
C
C

hr
5
C
C
C
C
C
C
C
C
C
C

hr
6
C
C
C
C
C
C
C
C
C
C

hr
7
C
C
C
C
C
C
C
C
C
C

E:\ ...\ELITE SOFTWARE CALCULATIONS.CHV

hr
8
C
C
C
C
C
C
C
C
C
C

hr
9
C
C
C
C
C
C
C
C
C
C

hr
10
C
C
C
C
C
C
C
C
C
C

hr
11
C
C
C
C
C
C
C
C
C
C

hr
12
C
C
C
C
C
C
C
C
C
C

hr
13
C
C
C
C
C
C
C
C
C
C

hr
14
C
C
C
C
C
C
C
C
C
C

hr
15
C
C
C
C
C
C
C
C
C
C

hr
16
C
C
C
C
C
C
C
C
C
C

hr
17
C
C
C
C
C
C
C
C
C
C

hr
18
C
C
C
C
C
C
C
C
C
C

hr
19
C
C
C
C
C
C
C
C
C
C

hr
20
C
C
C
C
C
C
C
C
C
C

hr
21
C
C
C
C
C
C
C
C
C
C

hr
22
C
C
C
C
C
C
C
C
C
C

hr
23
C
C
C
C
C
C
C
C
C
C

hr
24
C
C
C
C
C
C
C
C
C
C

Monday, November 07, 2016, 02:34 PM

Chvac - Full Commercial HVAC Loads Calculation Program


York International
Dubai,

Elite Software Development, Inc.


Continental Medical College
Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design
Month

Outdoor
Dry Bulb

Outdoor
Wet Bulb

Indoor
Rel.Hum

Indoor
Dry Bulb

Grains
Diff

In/Outdoor
Correction

August
Winter

112
37

82

50%

75
75

57.64

16

Master Roofs
Roof
ASHRAE
No.
Roof#
1
12
Roof #1 Description: standered 6" slab

Roof
U-Fac
0.460

Dark
Color
No

Wall
U-Fac

Wall
Color

0.350

0.470

Partition
U-Factor

Cool
T-D

Heat
T-D

1
0.460
2
0.370
3
0.470
Partition #3 Description: Partition Slab

10
10
10

10
10
10

Susp.
Ceil
Yes

Master Walls
Wall
No.

ASHRAE
Group

1
Wall #1 Description: 9" brick wall
2
Wall #2 Description: 4.5" Wall

Master Partitions
Partition
No.

Master Glass
Glass
No.

Summer
U-Factor

1
1.040
Glass #1 Description: single clear glass

E:\ ...\ELITE SOFTWARE CALCULATIONS.CHV

Winter
U-Factor

Glass
Shd.Coef.

Interior
Shading

Interior
Shd.Coef

1.100

0.950

0.000

Monday, November 07, 2016, 02:34 PM

Chvac - Full Commercial HVAC Loads Calculation Program


York International
Dubai,

Elite Software Development, Inc.


Continental Medical College
Page 4

Zone Input
Zone 1: OT Emergency (586 sq.ft) (Group 0)
Air Handler number:
1
Zone length: (feet)
29.30
Lighting Watts:
500
Number of people in zone:
8
Lighting profile number:
2
Ceiling height (feet):
9.00
Sensible safety factor (%):
10
Sensible heat per person (Btuh):
250
Cooling ventilation method:
AC/Hr
Cooling infiltration method:
AC/Hr
Heating ventilation method:
AC/Hr
Heating infiltration method:
AC/Hr
Winter exhaust air CFM:
317
Minimum supply CFM:
0
Ceil. exposed to plenum (sq.ft):
586
Both heating and cooling loads are calculated for this zone.
Roof

ASHRAE#

U-Factor

Dark

Length

Width

Area

Susp.Ceil

12

0.460

No

29.30

20.00

586.0

Yes

Type

U-Factor

Cool TD

Heat TD

Height

Width

Area

2
2
2
1
1

0.37
0.37
0.37
0.46
0.46

10.000
10.000
10.000
10.000
10.000

10.000
10.000
10.000
10.000
10.000

11.00
11.00
11.00
11.00
11.00

29.30
20.00
19.00
15.00
9.50

322.3
220.0
209.0
165.0
104.5

1
2
3
4
5
Glass
1

1
20.00
6,500
1
3
10
10
250
4.000
0.000
4.000
0.000
317
0
0

Type

1
Part

Zone occurrences:
Zone width (feet):
Equipment Watts:
People profile number:
Equipment profile number:
Heating safety factor (%):
Latent safety factor (%):
Latent heat per person (Btuh):
Cooling ventilation value:
Cooling infiltration value:
Heating ventilation value:
Heating infiltration value:
Summer exhaust air CFM:
Latent Btuh equipment load:
Exposed floor slab perimeter (ft):

Type

S.U-F.

Shd C.

Height

Width

Occur.

Area

Shade

Tilt

Ref

1.040

0.950

4.00

7.25

29.0

90

E:\ ...\ELITE SOFTWARE CALCULATIONS.CHV

Monday, November 07, 2016, 02:34 PM

Chvac - Full Commercial HVAC Loads Calculation Program


York International
Dubai,

Elite Software Development, Inc.


Continental Medical College
Page 5

Building Summary Loads


Building peaks in August at 5pm.

Bldg Load
Descriptions
Roof
Wall
Glass
Floor Slab

Area
Quan

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

1,172
0
29
0

19,451
0
351
0

47.32
0.00
0.85
0.00

0
0
0
0

25,026
0
332
0

25,026
0
332
0

24.95
0.00
0.33
0.00

19,802

48.17

25,358

25,358

25.28

0
0
0
4,303
0
0
0
13,993
0
0
0
0
0
0
2,007
1,003
0
0

0.00
0.00
0.00
10.47
0.00
0.00
0.00
34.04
0.00
0.00
0.00
0.00
0.00
0.00
4.88
2.44
0.00
0.00

0
0
1,760
0
0
0
15,111
0
0
0
0
0
0
0
0
0
0
0

1,877
24,397
1,760
4,303
0
0
14,780
0
0
0
5,898
0
428
0
3,791
854
0
0

1,877
24,397
3,520
4,303
0
0
29,892
0
0
0
5,898
0
428
0
3,791
854
0
0

1.87
24.32
3.51
4.29
0.00
0.00
29.80
0.00
0.00
0.00
5.88
0.00
0.43
0.00
3.78
0.85
0.00
0.00

41,109

100.00

16,871

83,446

100,317

100.00

Skin Loads
Lighting
Equipment
People
Partition
Cool. Pret.
Heat. Pret.
Cool. Vent.
Heat. Vent.
Cool. Infil.
Heat. Infil.
Draw-Thru Fan
Blow-Thru Fan
Reserve Cap.
Reheat Cap.
Supply Duct
Return Duct
Misc. Supply
Misc. Return

500
6,500
6
992
0
0
352
352
0
0
0
0
0
0
0
0
0
0

Building Totals

Building
Summary

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

Ventilation
Infiltration
Pretreated Air
Zone Loads
Plenum Loads
Fan & Duct Loads

13,993
0
0
17,861
6,245
3,010

34.04
0.00
0.00
43.45
15.19
7.32

15,111
0
0
1,760
0
0

14,780
0
0
46,125
11,997
10,543

29,892
0
0
47,885
11,997
10,543

29.80
0.00
0.00
47.73
11.96
10.51

Building Totals

41,109

100.00

16,871

83,446

100,317

100.00

Check Figures
Total Building Supply Air (based on a 15 TD):
Total Building Vent. Air (9.95% of Supply):

3,535 CFM
352 CFM

Total Conditioned Air Space:


Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:

586
6.0331
70.1
0.0143
70.15

Total Heating Required With Outside Air:


Total Cooling Required With Outside Air:

41,109 Btuh
8.36 Tons

E:\ ...\ELITE SOFTWARE CALCULATIONS.CHV

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft
Btuh/Sq.ft

Monday, November 07, 2016, 02:34 PM

Chvac - Full Commercial HVAC Loads Calculation Program


York International
Dubai,

Elite Software Development, Inc.


Continental Medical College
Page 6

Air Handler #1 - AHU-1 OT - Summary Loads


Zn
No

Description
Zone Peak Time

OT Emergency
9pm August

Plenum
9pm in August
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

586
8
5,274

17,861
953
1.63

46,434
3,536
6.03

2,200
317
317

4AC/Hr
352
352

4AC/Hr
352
352

0
0
0

6,245
0
0

12,294
0
0

0
0
0

None
0
0

None
0
0

586
8
5,274

17,861
953
1.63

58,728
3,536
6.03

2,200
317
317

352
352

352
352

E:\ ...\ELITE SOFTWARE CALCULATIONS.CHV

Monday, November 07, 2016, 02:34 PM

Chvac - Full Commercial HVAC Loads Calculation Program


York International
Dubai,

Elite Software Development, Inc.


Continental Medical College
Page 7

Air Handler #1 - AHU-1 OT - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

AHU-1 OT Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 2.38 HP
70% motor and fan efficiency with 3 in. water across the fan
0.97
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

5pm in August.
Clg: 109 DB, 82 WB, 128.85 grains, Htg: 37 DB
Clg: 70 DB, 55% RH, Htg: 75 DB

Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

17,861
0
13,993
2,007
1,003
6,245

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

41,109 Btuh

Heating Supply Air: 19,868 / (.975 X 1.08 X 20) =


Winter Vent Outside Air (36.9% of supply) =
Zone space sensible gain:
45,697
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
5,898
Supply duct sensible gain:
3,791
Reserve sensible gain:
428
Total sensible gain on supply side of coil:

953 CFM
352 CFM

Btuh
Btuh
Btuh
Btuh
Btuh
55,815 Btuh

Cooling Supply Air: 56,111 / (.975 X 1.1 X 15) =


Summer Vent Outside Air (9.9% of supply) =
Return duct sensible gain:
854
Return plenum sensible gain:
11,997
Outside air sensible gain:
14,780
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
352 CFM

3,535 CFM
352 CFM
Btuh
Btuh
Btuh
Btuh

352 CFM
27,631 Btuh
83,446 Btuh

Zone space latent gain:


1,760 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
15,111 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

16,871 Btuh
100,317 Btuh

Check Figures
Total Air Handler Supply Air (based on a 15 TD):
Total Air Handler Vent. Air (9.95% of Supply):

3,535 CFM
352 CFM

Total Conditioned Air Space:


Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:

586
6.0331
70.1
0.0143
70.15

Total Heating Required With Outside Air:


Total Cooling Required With Outside Air:

41,109 Btuh
8.36 Tons

E:\ ...\ELITE SOFTWARE CALCULATIONS.CHV

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft
Btuh/Sq.ft

Monday, November 07, 2016, 02:34 PM

Chvac - Full Commercial HVAC Loads Calculation Program


York International
Dubai,

Elite Software Development, Inc.


Continental Medical College
Page 8

Zone Detailed Loads (At Zone Peak Times)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Htg.
Htg.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Mult.
Loss
Zone 1-OT Emergency peaks (sensible) in August at 9pm, Air Handler 1 (AHU-1 OT), Group 0, 29.3 x
20.0, Construction Type: 20 (Light)
Plenum
Roof-1-12-Susp.C-L
Partition-1-2
Partition-2-2
Partition-3-2
Partition-4-1
Partition-5-1
Gls-P-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=2
Equipment-Prof=3
People-Prof=1

586
586
293.3
220
209
165
104.5
29.0
29.0
500
6,500
8.0

0.50

1.000
0.950
1.000
1.000
1.000

s:10,
w:10
38.2
10/10
10/10
10/10
10/10
10/10
28
0

0.310

1,817

3.100

1,817

0.460
0.370
0.370
0.370
0.460
0.460
1.040
0.000

10,297
1,085
814
773
759
481
302
0
1,706
22,179
2,000

17.388
3.700
3.700
3.700
4.600
4.600
11.000

10,189
1,085
814
773
759
481
319

0
2,000

42,213
+10%
--------46,434

2,000
+10%
--------2,200

Sub-total
Safety factors:
Total w/ safety factors:

16,237
+10%
--------17,861

Plenum 1- peaks in August at 9pm., Construction Type: 20 (Light)


Pl.Credit Cool.
Pl.Credit Heat.
Roof-1-12-Susp.C-L

586
586
586

Sub-total
Safety factors:
Total w/ safety factors:

E:\ ...\ELITE SOFTWARE CALCULATIONS.CHV

0.50

-10
-10
48.2

0.310
0.310
0.460

-1,817
-3.100
12.788

12,993
11,176
+10%
--------12,294

0
+10%
--------0

-1,817
7,494
5,677
+10%
--------6,245

Monday, November 07, 2016, 02:34 PM

Chvac - Full Commercial HVAC Loads Calculation Program


York International
Dubai,

Elite Software Development, Inc.


Continental Medical College
Page 9

Air System #1 (AHU-1 OT) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grains

Sensible

Temp

CFM

5,898
0
3,791
45,994
428

55.000
1.556
0.000
1.000
12.132
0.113

372
0
239
2,898
27

56,111
854
11,997
0
14,780
0

69.800
0.250
3.514
0.000
3.524
0.000

3,535

83,742

77.088

3,535

60.390

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 352 CFM
Blow-Thru Fan
Entering Coil Condition

1,760

0.751

1,760

61.141

15,111

6.490

16,871

67.630

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 29.921)


PR x
1.10 x CFM x (DB entering - DB leaving)
PR x
0.68 x CFM x (Grains entering - Grains leaving)
PR x
4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
0.975
0.975

x
x

1.10
0.68

x
x

3,535
3,535

x(
x(

77.088
67.630

55.000
60.390

)=
)=

SUM
=
GTH
=
0.975
Total System Load

4.50

3,535

x(

29.085

22.566

)=
=

83,742
16,970
---------100,712
101,106
100,317

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

101,106 / (
41,109 / (
41,109 /

6.50
6.50
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

31.1 GPM
12.6 GPM
42.4 lb./hr

Entering Heating Coil Conditions


77.09
63.42
47.55
29.08 Btu/lbm

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

500
500

Dry bulb temperature:

56.70

Leaving Heating Coil Conditions


55.00
53.59
91.58
22.57 Btu/lbm

E:\ ...\ELITE SOFTWARE CALCULATIONS.CHV

Dry bulb temperature:

95.00

Monday, November 07, 2016, 02:34 PM

Chvac - Full Commercial HVAC Loads Calculation Program


York International
Dubai,

Elite Software Development, Inc.


Continental Medical College
Page 10

Air System #1 (AHU-1 OT) Psychrometric Chart


ZC
LC
SD
DTF
RE
SM
PRE

Zone Condition
Leaving Coil Condition
Supply Duct Temperature Rise
Draw Through Fan Sensible Gain
Reserve or Reheat Sensible Gain
Supply Side Miscellaneous Sensible Gain
Pretreated Air Condition

E:\ ...\ELITE SOFTWARE CALCULATIONS.CHV

OC
EC
RD
BTF
PL
RM
HRV

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain
Heat Recovery Ventilator Condition

Monday, November 07, 2016, 02:34 PM