Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 1 of 32
Dwg. Ref.:
Record No.:
INDEX
Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Description
MECHANICAL CHECK AND VISUAL INSPECTION
POWER TRANSFORMER DATA
GENERAL CHECKS
TRANSFORMER TURNS RATIO TEST
CAPACITANCE AND TAN DELTA OF WINDING
CAPACITANCE AND TAN DELTA OF BUSHING
MAGNETIZING CURRENT TEST
MAGNETIC BALANCE TEST
VECTOR GROUP TEST
SHORT CIRCUIT TEST (IMPEDANCE MEASUREMENT)
ZERO SEQUENCE IMPEDANCE TEST
WINDING RESISTANCE TEST
INSULATION RESISTANCE TEST OF TRANSFORMER WINDING
AND POLARIZATION INDEX TEST
OIL AND WINDING TEMPRATURE GAUGES CALIBRATION
WINDING TEMPRATURE CALIBRATION BY SECONDARY
CURRENT INJECTION
SUPERVISION EQUIPMENT FUNCTIONAL CHECK
COOLING FANS TESTING
OLTC TEST
OIL BREAKDOWN TEST
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Remarks
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 2 of 32
Item
1
2
3
4
5
6
7
8
9
Dwg. Ref.:
Record No.:
Description
Inspect for physical damage/defects
Check nameplates information as per contract specification
Check quality for paint work, condition of lifting lugs, quality of weld areas
rust spots and wheel stoppers
Check tightness of all bolted connections
Check impact recorder for any abnormal impact during transportation
Check integrity of diagram/airbag in the conservator
Check piping to buchholz relay has proper slope
Check that all grounding are securely connected
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
27
30
Check the oil sampling devices are reachable from ground level
Check oil level in main tank, conservator, tap changer tank and bushing etc
Check all external wiring for correctness and tightness
Bleed trapped air at the bushing turrets and tank top
Check flow of oil in flow meter in correct direction and proper rate
Check that the temperature sensor oil well is two third filled with oil
Check that the Tank Pressure is Positive
Neutral grounding.
1ZTR 130609
SERIAL NUMBER
TEST DATE:
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Checked
Ok
Ok
Ok
Ok
Ok
Ok
Ok
Not all
connected
Ok
Ok
Ok
Ok
Ok
Ok
Ok
Ok
Ok
Will be
done
Ok
Ok
Ok
Ok
Ok
Ok
Ok
Will be
done
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 3 of 32
Dwg. Ref.:
Record No.:
TYPE
TR67-EOA-OH-1
MANUFACTURER / YEAR
ABB / 2014
IEC-60076
STANDARD
53-TMSS-01 Rev.01
POWER (MVA)
50/67
COOLING TYPE
ONAN/ONAF
FREQUENCY(Hz)
60
PHASE
VECTOR GROUP
Dyn1
OLTC ABB
NUMBER OF TAPS
27
NORMAL TAP
VOLTAGE AT NORMAL TAP
(HV/LV)
RATED CURRENT HV
(50/67MVA)
RATED CURRENT LV
(50/67MVA)
PERCENTAGE IMPEDANCE
(%Z) AT TAP (1/11/27)
ZERO SEQUENCE
IMPEDANCE Z0% AT
NORMAL TAP
TEMP. RISE
(WINDING/OIL/MAX
AMBIENT)
11
115/13.8 KV
251/336.4 A
2091.8 / 2803.1 A
22.58 / 21.19 / 20.92 %
22.36 %
50 / 45 / 55 C
TEST DATE:
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 4 of 32
ATTACHED
Equipment :
Dwg. Ref.:
Record No.:
TEST RESULTS
TEST DATE:
30 C
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 5 of 32
Test Mode
SI
No.
Measured
Dwg. Ref.:
Test
Connecti
on
KV
Record No.:
mA
Watt
s
%Pf
Capacita
nce
(pF)
UST
1
MEASURE
RED,GROUND
BLUE
CHL
GST
2
GROUND
RED,BLUE
CHL+CH
HVBLACK
12.52
0.182
7
0.15
3320.7
26.02
0.432
0.17
6903.2
13.5
0.244
4
0.18
3582.4
12.5
0.186
5
0.15
3320.2
43.1
1.3
0.2
11409
30.6
1.138
0.37
8116.9
LV-RED
GST
3
GUARD
RED,BLUE
CH
10
UST
4
MEASURE
RED,GROUND
BLUE
CLH
HV-RED
GST
5
GROUND
RED,BLUE
CLH+CL
LVBLACK
GST
6
GUARD
RED,BLUE
CL
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 6 of 32
Dwg. Ref.:
Record No.:
Equivalent 10 KV
Reading
No.
Bushing
Serial No:
MO
DE
H1
1ZSCT250097
24/03
UST
H2
1ZSCT250097
24/02
UST
H3
1ZSCT250097
24/01
UST
Tes
t
KV
P.F
%
Milli
Amps
POWER
WATTS
Meter
Reading
Watt
Reading
0.857
0.0358
0.4
2
227.68
0.857
0.0359
0.4
2
227.63
0.857
0.0316
0.3
7
227.53
10
Instrument
Serial No.
Calibration Date
Calibration Due
DELTA 2000
56810607
6/4/2016
6/4/2017
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Capacita
nce (pF)
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 7 of 32
Dwg. Ref.:
Record No.:
Applying voltage at high voltage side H1,H2,H3= 400 V while low side is open and
measuring high side current.
TAP NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
TEST DATE:
IS
(mA)
IT
(mA)
2.91
3.05
2.60
2.77
2.78
2.85
2.86
2.88
2.96
3.02
3.09
3.17
3.27
3.35
3.47
3.55
3.62
3.70
3.79
3.88
3.95
4.03
4.14
4.26
4.35
4.47
4.57
2.64
2.58
2.35
2.26
2.32
2.40
2.51
2.85
2.66
2.71
2.75
2.82
2.88
2.90
3.14
3.21
3.26
3.30
3.40
3.48
3.57
3.66
3.75
3.78
3.98
4.05
4.16
4.29
4.14
3.88
3.92
4.00
4.08
4.14
4.26
4.35
4.43
4.57
4.67
4.75
4.87
5.07
5.19
5.32
5.43
5.58
5.70
5.81
5.96
6.11
6.25
6.41
6.57
6.73
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 8 of 32
Dwg. Ref.:
Record No.:
CRITERIA: Io<0.5%
Instrument
Serial No.
Calibration Date
Calibration Due
FLUKE 289
56810607
6/4/2016
6/4/2017
CLAMP METER
87945001
6/4/2016
6/4/2017
TEST DATE:
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 9 of 32
Dwg. Ref.:
Record No.:
Tap 1
X3-X0
X2-XO
X1-X0
H1-H3
H2-H3
H1-H2
APPLIED VOLTGAGE
(V)
(V)
(V)
(V)
(V)
(V)
AT TERMINALS
12.6
24.1
12.1
197.1
205.1
392.5
H1-H2
24.3
23.2
1.3
21.8
395.2
375.8
H2-H3
1.1
23.4
24.1
391.4
17.1
379.3
H1-H3
X3-X0
X2-XO
X1-X0
H1-H3
H2-H3
H1-H2
APPLIED VOLTGAGE
(V)
(V)
(V)
(V)
(V)
(V)
AT TERMINALS
12.4
27.2
15.2
219.6
178.3
391.1
H1-H2
27.4
25.9
1.6
23.6
395.5
373.7
H2-H3
1.1
26.1
27.1
389.7
17.2
376.3
H1-H3
Tap 11
Tap 27
X3X0
TEST DATE:
X2XO
X1X0
H1H3
H2H3
APPLIED
VOLTGAGE
Signature: ________________
Name
017
H1H2
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 10 of 32
Dwg. Ref.:
Record No.:
(V)
(V)
(V)
(V)
(V)
(V)
AT TERMINALS
16.9
33.9
17.1
197.
1
196.
9
392.
4
H1-H2
34.2
31.9
2.3
27.8
397.
1
368.
5
H2-H3
1.5
32.4
33.7
390.
1
18.7
373.
2
H1-H3
Instrument
Serial No.
Calibration Date
Calibration Due
FLUKE 289
56810607
6/4/2016
6/4/2017
CLAMP METER
87945001
6/4/2016
6/4/2017
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 11 of 32
Vector
Group
Dyn1
Dwg. Ref.:
CONNECTION
CONNECT TERMINAL
H1 TO X1
APPLY SOURCE VOLTS
TO H1,H2 and H3
Record No.:
VOLTAGE
RELATIONS
Checked
H3-X2=H3-X3
OK
H3-X2<H1-H3
OK
H2-X2<H2-X3
OK
H2-X2<H1-H3
OK
345
H1H3
395
H2X3
403
H3-X3
345
H2X2
348
H1H2
395
H2-H3
395
Test connections:
30 Degrees according To
Dyn1
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 12 of 32
Dwg. Ref.:
Record No.:
TAP
POSITI
ON
Rated
voltag
e (V)
Rated
curre
nt (A)
Measured short
circuit current in
primary (A)
Applied voltage(V)
R-Y
Y-B
B-R
Mea
n
Mea
n
Calcul
ated
%
Impe
dance
Fact.
Result
%Z
12937
5
223
400
399
401
400
2.
9
2.9
23.77
23.2 +/10%
11
11500
0
251
400
399
401
400
3.
8
3.9
21.83
21 +/- 7.5%
27
92000
313.8
400
399
401
400
6.
2
6.
3
6.4
6.3
21.66
21.4 +/10%
100
Criteria: +/-10 %
Instrument
Serial No.
Calibration Date
Calibration Due
TEST DATE:
FLUKE 289
96820054
2/8/2016
2/8/2017
CLAMP METER
W0153033
17/8/2016
17/8/2017
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 13 of 32
Dwg. Ref.:
Record No.:
Applied
current(A)
6.3
20.0
11
Z0%
FACTORY
Z0%
% ERROR
24.4
22.49
8%
Instrument
Serial No.
Calibration Date
Calibration Due
TEST DATE:
FLUKE 289
56810607
6/4/2016
6/4/2017
CLAMP METER
87945001
6/4/2016
6/4/2017
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 14 of 32
Dwg. Ref.:
Record No.:
CAL
at
H2-H3
Meas.
75 C
FACT:
at 75
C
905.2
CAL.
at
H1-H3
75 C
FACT:
at 75
C
Meas.
CAL.
at 75
C
FACT:
at 75 C
1.066
910.5
1.062
902.5
1.055
895.5
1.055
899.7
1.052
891.5
1.042
884.4
1.041
890.1
1.041
881.3
1.038
874.4
1.028
877.8
1.027
870.1
1.018
862.5
1.016
868.1
1.015
860.2
1.006
852.4
1.004
857.3
1.002
849.3
0.993
841.4
0.992
848.1
0.995
839.4
0.981
831.3
0.980
836.9
0.979
828.2
0.969
820.9
0.967
825.1
0.968
818.1
0.957
10
810.3
0.955
815.7
0.954
807.9
0.945
11
800.1
0.942
805.2
0.942
797.3
0.932
12
790.2
0.930
795.3
0.931
787.4
0.921
TEST DATE:
Meas.
TESTING ENGINEER
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 15 of 32
Dwg. Ref.:
Record No.:
13
780.2
0.919
785.2
0.918
777.3
0.910
14
769.4
0.907
775.3
0.907
767.4
0.898
15
780.1
0.919
786.2
0.919
778.4
0.910
16
792.4
0.934
797.2
0.933
789.2
0.923
17
802.2
0.945
808.1
0.945
800.2
0.935
18
812.5
0.958
818.1
0.957
810.4
0.947
19
823.9
0.970
829.1
0.972
821.2
0.961
20
833.1
0.982
839.1
0.982
831.8
0.972
21
844.0
0.995
850.1
0.994
841.9
0.985
22
854.4
1.0072
860.2
1.0062
852.4
0.997
23
864.4
1.0193
870.2
1.019
862.3
1.008
24
874.2
1.0312
880.3
1.030
872.2
1.025
25
885.2
1.0428
890.2
1.041
882.5
1.037
26
895.6
1.0554
900.3
1.053
892.4
1.044
27
905.4
1.0672
910.3
1.065
903.2
1.056
LV Winding
TAP
TEST DATE:
Measured
X2-X3
Measur
Measur
Signature: ________________
Name
017
Measured :
X3-X1
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Measured:
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 16 of 32
Dwg. Ref.:
: at
ed
11
75C
Record No.:
at
ed
75 C
ed
at 75 C
14.1
17.03
15.06
17.75
16.01
18.77
(235 + 75)
Res @ 75 C. = Meas. Res @ Amb. Temp. X -----------------------------------------------(235 + Avg Oil Temp.)
Criteria: +/- 3%
Instrument
S.N
Make
Calibration Date
Calibration Due
CPC100
S.N:KF-134R
OMICRON
26/10/2016
26/10/2017
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 17 of 32
Dwg. Ref.:
Record No.:
Winding Insulation Resistance Test & Polarizing Index Tested with: 5000 VDC
Insulation resistance between
1 Min
( G )
10 Mins
( G )
Polarizing
index
HV (LV+ ground)
LV (HV + ground)
HV-LV
16.9
5.15
28.85
23.9
10.3
45
1.36
2
1.56
Criteria: Polarization Index (I.R at 10 min / I.R at 1 Min) Value > 1.3
Instrument
Make
Serial number
Calibration Date
Calibration Due
MIT520
MEGGER
10003740909091956
17/8/2016
17/8/2017
AKM
Serial
1121882-1
WTI (HV)
TEST DATE:
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 18 of 32
Dwg. Ref.:
Type
AKM
Serial
1121884-15
WTI (LV)
Type
AKM
Serial
REFERENCE
TEMP ( C)
40
60
80
100
120
Record No.:
1121884-10
OTI ( C)
HV WTI ( C)
LV WTI ( C)
40
40
40
60
60
60
80
100
120
80
100
120
80
100
120
TEST DATE:
DEVIC
E
FUNCTION
SETTING
OPERATI
ON
F909
Fan Start
80 C
OK
Signature: ________________
Name
017
REMARKS
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 19 of 32
Dwg. Ref.:
Record No.:
Alarm
115 C
OK
Tripping
130 C
OK
FUNCTION
SETTING
OPERATION
80 C
OK
Alarm
115 C
OK
Tripping
130
C
OK
Fan Start
F910
REMARKS
FUNCTION
F908
TEST DATE:
SETTING
Alarm
95
Trip
105
C
C
REMARKS
OK
OK
Signature: ________________
Name
017
OPERATION
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 20 of 32
Criteria
Dwg. Ref.:
Record No.:
Instrument
Serial number
Calibration Date
Calibration Due
TEMP. CALIBRATOR
GAUGE
861A1784
17/8/2016
17/8/2017
CLASS: 3Fs10
TIME (MIN.)
0
5
10
15
TEST DATE:
TEMP. READING ( C)
36
46
51
53
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 21 of 32
Dwg. Ref.:
Record No.:
20
25
30
35
40
45
55
56
56
56
56
56
36
38
36
56
18
CLASS: 3Fs10
TIME (MIN.)
0
5
10
15
20
25
TEST DATE:
TEMP. READING ( C)
36
41
44
48
48
50
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 22 of 32
Dwg. Ref.:
Record No.:
30
35
40
45
TEST DATE:
50
50
50
50
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 23 of 32
Dwg. Ref.:
Record No.:
TEST DATE:
50
13
Signature: ________________
Name
017
38
39
36
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 24 of 32
Dwg. Ref.:
Record No.:
ZIEHL-ABEGG
TEST DATE:
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 25 of 32
Dwg. Ref.:
Record No.:
Current ( A )
Fa
n
No
.
Drawing
Ref.
Starting
Direction of
Rotation
M101
14.
7
14.
2
14.
5
4.8
4.5
4.8
5.66
TO RADIATOR
M102
17.
5
16.
3
15.
3
4.6
4.7
4.9
3.1
TO RADIATOR
M103
20.
4
15.
9
15.
2
4.8
4.6
4.9
4.29
TO RADIATOR
M104
15.
5
14.
6
20.
5
4.9
5.0
4.9
4.09
TO RADIATOR
M105
15.
0
14.
4
19.
1
4.7
4.9
5.0
6.72
TO RADIATOR
M106
20.
3
14.
2
19.
6
4.7
4.9
5.0
3.76
TO RADIAROR
M107
13.
6
14.
7
12.
5
5.4
4.9
4.9
4.58
TO RADIATOR
M108
16.
8
14.
9
17.
3
4.7
4.8
4.8
4.64
TO RADIAROR
M109
14.
1
15.
5
15.
4
4.7
4.8
4.8
3.89
TO RADIATOR
17. 12.
10
FROM M110
30/10/2016 TO 2 /10/2016
7
17.
7
4.6
4.7
4.9
3.77
TO RADIATOR
TEST DATE:
TESTING ENGINEER
11
M111
Signature: ________________
Name
017
IR with
1000V
@60
seconds
(GOhm)
Running
M112
:12
ISLAM EL
KADY
16.
2
12.
7
15.
2
CSD- Engineer
4.5
4.8
4.8
3.21
TO RADIATOR
Signature: ________________
4.7 5.0
4.9 AL TAMIM
6.06
Name
: AYIDH
TO RADIATOR
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 26 of 32
Dwg. Ref.:
Record No.:
WIRE CHECK: OK
NA
3.
OK
OK
Signature: ________________
Name
017
CHECKED
OK
2.
4.
TEST DATE:
Functions
Main power supply 3ph AC 380/220V,60hz
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 27 of 32
Dwg. Ref.:
Record No.:
5.
OK
6.
OK
7.
Thermostat
OK
8.
OK
9.
OK
OK
OK
OK
80 C
80 C
OK
OK
Auto
OK
Manual
Local
Remote
On
Off
Group
OK
OK
OK
OK
OK
OK
TEST DATE:
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 28 of 32
Dwg. Ref.:
Record No.:
1
2
3
4
5
6
7
8
9
10
11
12
Explanation of event
MCB of tap changer motor
AC socket & MCB
Heater & thermostat
Lighting & door switch
Mechanical operation check
Mechanical upper limit lock
Mechanical lower limit lock
Electrical operation
Upper
Electrical limit lock
Lower
Counter operation check
Local operation check
Stop and rotation pointer
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
14
16
17
18
19
20
21
22
23
IR
0.5
0.4
IS
0.5
0.4
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Signature: ________________
Name
017
CHECKED
13
15
TEST DATE:
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
IT
0.5
0.4
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 29 of 32
24
25
remote
OLTC local
OLTC remote
26
Tap position
27
Dwg. Ref.:
Record No.:
Lower
OK
OK
OK
OK
OK
OK
Raise
Lower
Terminal at
Marshalling Kiosk
Equipment
TEST DATE:
Signature: ________________
Name
017
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
Normal
NO
Alarm/trip
NC
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 30 of 32
Dwg. Ref.:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
18
19
TEST DATE:
X3: (1-28)
X4: (2-22)
X3: (2-29)
X4:(3-23)
X4:(3-24)
X4: (5- 25)
X4:(6-26)
X3: (4-31)
X3: (8-35)
X3: (11-38)
X3: (16-43)
X3: (18-45)
X4: (7-27)
X3: (13-40)
Signature: ________________
: ISLAM EL KADY
X3: (14-41)
X4: (9-29)
X3: (15-42)
CSD- Engineer
Name
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Signature: ________________
NG ID # OSA-
OK
X4: (8-28)
Name
017
X4: (1-21)
17
Record No.:
: AYIDH AL TAMIM
OK
OK
OK
OK
OK
OK
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 31 of 32
Dwg. Ref.:
20
21
22
Record No.:
X3: (20-47)
X3: (22-49)
X4: (14-15)
OK
OK
OK
OK
OK
OK
SAMPLE NO.
SAMPLE
POSITION
TEST NO.
SAMPLE 1
TEST 1
TEST DATE:
AVERAGE(KV)
Signature: ________________
Name
017
BREAKDOWN
VOLATGE(KV)
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM
RESULT(KV)
Date :
Customer:
SEC-EOA
Contractors name:
AL OSAIS CONTRACTING CO
Page 32 of 32
SAMPLE 2
BOTTOM OF MAIN
TANK
SAMPLE 3
OLTC TANK
SAMPLE 4
MAIN TANK
CONSERVATOR
SAMPL 5
TEST DATE:
OLTC
CONSERVATOR
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
TEST
Dwg. Ref.:
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
Signature: ________________
Name
017
Record No.:
: ISLAM EL KADY
CSD- Engineer
Signature: ________________
NG ID # OSA-
Name
: AYIDH AL TAMIM