Académique Documents
Professionnel Documents
Culture Documents
The test is divided into two fire scenarios, fire from outside of the duct and fire
from inside of the duct. One duct is needed for each scenario and both scenarios have to be tested in horizontal and vertical direction. A total of four ducts
are therefore necessary for a full test.
A full test covers one type of duct shape (circular or rectangular) and one type
of supporting construction (rigid or flexible). As an example, a full test could
cover circular ducts penetrating a rigid wall/floor.
Each duct are tested with a part of the duct inside the furnace (exposed
surface) and a part outside the furnace (unex-posed surface) as shown in the
photo. The standard heating curve described in EN 1363-1 is used for both
scenarios.
Performance criteria
The ducts are monitored throughout the test for performance against three
criteria: Integrity (E), Insulation (I) and Smoke leakage (S).
The integrity is the ability of the duct system to prevent the passage of flames
and hot gases through the system and to prevent the occurrence of flames on
the unexposed side. The duct can no longer satisfy the integrity criteria if:
sustained flaming on the unexposed side occurs
it fails the cotton pad test or the gap gauge test
the leakage exceeds 15 m3/h per m2 exposed duct surface. This criterion
applies only to duct A.
The duct does no longer satisfy the Insulation criteria if the temperature rise
on the unexposed side exceeds 180 oC on any of the thermocouples or 140
oC in average. (The average temperature criterion only applies for some of the
thermocouples.)
The smoke leakage criterion is equal to the third integrity criterion with a limit
of 10 m3/h per m2 exposed duct surface.
Testing at DBI
The capacity of the combi furnace at DBI makes it possible to test both fire
from inside and fire from outside simultaneously.
It is possible to mount the vertical ducts in a frame away from the furnace,
while at the same time, the horizontal ducts are built in into the combi furnace.
Further information
For further information regarding
testing fire dampers according to
this method, please contact
Anders Drustrup
Phone: +45 36 34 90 38
E-mail: adr@dbi-net.dk
This testing facility makes it possible to mount the vertical and the horizontal
duct at the same time if the sponsor wishes.
The flexible system of double mounting increases the efficiency and reduces
the time for preparation and testing.
At DBI the time needed to make a complete horizontal and a vertical test is 1
weeks.
The dimension of the ducts needed for the test is listed in the table below.
Classification
The three performance criteria are used for classifying the duct system according to prEN 13051-3 (The prEN 13051-3 is not yet finished, but is expected to
be published in 2005).
Ducts tested with the prescribed dimensions cover ducts with rectangular
dimensions up to 1000 mm x 1000 mm and circular ducts with a diameter up to
1000 mm.
Test specimens
C ross-section
C ircular
Rectangular
Scenario
Diameter
Fire outside duct (A) 800 10 mm
Fire inside duct (B)
630 10 mm
Scenario
Width
Fire outside duct (A) 1000 10 mm
Fire inside duct (B)
1000 10 mm
Height
500 10 mm
25010 mm
05/08