Today, most people involved in the HVAC industry around the world are familiar with
Nailor Industries Inc. and our comprehensive line of Air Distribution, Air Control and
Air Terminal Unit products. However, many may not know that the company had
humble beginnings.
The company commenced operations at a small facility in Toronto, Canada
manufacturing a single air control device. Michael T. Nailor (President and CEO)
started with the founding principle that the company would be customer focused and
service orientated, dedicated to fulfilling the need for high quality, competitively
priced products, delivered to our customers on schedule.
Nailor management has maintained strict adherence to the 'Superior Customer
Service' philosophy for more than 30 years and as a result, the company has been
rewarded with a continually increasing demand for our products. An ever
expanding product offering includes air control and fire/smoke dampers, a
complete line of grilles, registers and diffusers as well as fan coil units, fan powered
terminal units, silencers, and electric duct heaters that exceed industry standard
design and performance specifications.
Recently, Nailor International Group has expanded their already outstanding
repertoire of companies with Thermal Corporation manufacturers of custom air
handling equipment, and Manufactured Air Products a complete line of top quality
air distribution and air control products that are available through stocking
wholesalers across North America.
Today, with Group International Headquarters in Houston, Texas, the company has
ten manufacturing plants totaling over 600,000 square feet strategically located in
three countries to service the North American, European, Middle Eastern and Asian
Pacific markets. An international distribution network of representatives in most
major cities work together to not only meet but exceed the expectations of clients,
engineers and customers around the world.
As a private company, employing a staff of dedicated professionals, Nailor
Industries Inc. is prepared to set new benchmarks for service and quality as the
company continues to grow and remain the source for your . . .
Nailor
Industries Inc.
A1
Contents
Page No.
A2
A3
A8
Common Components
A9
Controls
A11
A17
Model 3001
See Page B3
See Page C3
Model 3230
Better than 1 in 12 mixing.
Economical compact design.
Integral mixing attenuator.
See Page C3
A3
Model 35SW
Model 35SEST
A4
Model 37SE
Model 37SWST
A5
Model 35N
Model 37STL
A6
See Page E5
Model 36VRR
Model 36VRS
Model 36VRS
Model 36VRBS
A7
See Page F3
ARI CERTIFICATION
Model 3400
INDEPENDENT LABORATORY
CERTIFICATION
Although ARI Certification, as explained above, provides
some assurance of product performance, the program
only verifies a single "standard rating condition"
(certification rating point) for each terminal size. This is for
valid logistical reasons. However, the correlation of the
ARI rating points with the comprehensive application data
is sometimes difficult to reconcile in some manufacturers
catalogs.
In order to provide assurance and complete credibility to
the engineering community, Nailor has taken the
unprecedented step of conducting 100% of its sound
power level testing at an independent laboratory
Energistics Laboratory. Compare that to the competition!
A8
A Participating
Corporation
in the ARI 880
Certification program.
COMMON COMPONENTS
'Diamond Flow' Sensor
A9
Electric Heaters
All Nailor terminal units supplied with electric heaters will
have heaters manufactured by Nailor Industries. Special
orders are not required for specific kW ratings. All units
have built-in controls for all options required by the
engineer. Controls for the terminal unit will also be in the
heater control box. Units are ETL listed for safety with the
electric heaters as a component of the terminal unit.
A10
CONTROLS
Pneumatic Controls
A comprehensive range of factory supplied, installed and calibrated controls are available for pressure independent control
applications with all terminal types. Pressure dependent controls are also available for certain terminals and applications.
Features:
The controller is factory calibrated to the specified
airflow, and is field adjusted easily. Field adjustment is
needed only when operating conditions change.
Pressure independent.
A11
100
MAX. 1
80
MAX. 2
60
40
MIN. 2
MIN. 1
20
0
8
13
THERMOSTAT OUTPUT, PSI
100
MAX. 1
80
MAX. 2
60
40
MIN. 2
MIN. 1
20
0
8
13
THERMOSTAT OUTPUT, PSI
A12
A13
Model T641A
A14
Controller/Actuator Features
Compact combination design eliminates separate circuit
boards.
Onboard flow-through transducer utilizing twin platinum
resistance temperature detectors.
Direct drive 24 VAC tri-state damper actuator @ 50 in. lb. (5.7 Nm) torque.
Magnetic clutch and gear disengagement button.
Tri-color LED indicates green for opening, red for
closing and white for satisfied damper positions.
Available control options include proportional (0 10
VDC) or two position hot water or electric reheat, dual
minimum, fan induction, dual duct and automation
interface. (Additional relays supplied as necessary).
Heat/cool auto changeover ability with addition of duct
temperature sensor.
A15
A16
A17
A18
B5
B6
3001 Cooling/Heating Only 30RW Cooling w/Hot Water Reheat 30RE Cooling w/Electric Reheat
Dimensional Data
3001 Basic Unit
3001 Integral Sound Attenuator 30RW Hot Water Reheat Only or plus Integral Attenuator
30RE Integral Electric Controls
B7
B8
B9
B12
B13
B14
Performance Data
SINGLE DUCT TERMINAL UNITS
Suggested Specifications
B15
B16
B17
B18
B19
B20
B26
B27
Dimensional Data
3000Q Basic Unit
30RWQ Hot Water Reheat Coil 30REQ Integral Electric Reheat
30RE Integral Sound Attenuator
B28
B29
B30
B31
Performance Data
NC Level Application Guide
Discharge Sound Power Levels Basic Unit
Radiated Sound Power Levels
AHRI Certification and Performance Notes
Suggested Specifications
B2
8-2-12
B32
B33
B34
B35
B36
B39
B40
30HQ Cooling/Heating Only 30RW Cooling w/Hot Water Reheat 30RE Cooling w/Electric Reheat
Dimensional Data
30HQ Basic Unit
30HQW Hot Water Reheat Coils 30HQE Integral Electric Controls
B41
B42
B43
Performance Data
B44
B45
B46
B47
B48
Suggested Specifications
B51
B52
Dimensional Data
B53
B54
B55
Performance Data
30X NC Level Application Guide
30X Discharge Sound Power Levels
30X Radiated Sound Power Levels
30X with Optional Attenuator VAV & Attenuator:
30X with Optional Attenuator VAV & Attenuator:
30X with Optional Attenuator VAV & Attenuator:
30X with Optional Attenuator VAV & Attenuator:
30X with Optional Attenuator VAV & Attenuator:
30X with Optional Attenuator VAV & Attenuator:
AHRI Certification and Performance Notes
Suggested Specifications
Fiberglass
Fiberglass
Fiberglass
Steri-Liner
Steri-Liner
Steri-Liner
B56
B57
B58
NC Level Application Guide
B59
Discharge Sound Power Levels B60
Radiated Sound Power Levels B61
NC Level Application Guide
B62
Discharge Sound Power Levels B63
Radiated Sound Power Levels B64
B65
B66
8-2-12
B3
B67
Dimensional Data
30HQX Basic Unit
B68
B68
B69
Performance Data
30HQX NC Level Application Guide
30HQX Discharge Sound Power Levels
30HQX Radiated Sound Power Levels
AHRI Certification and Performance Notes
Suggested Specifications
B70
B71
B72
B73
B74
GENERAL SECTIONS
Performance Data Explanation
B75
B76
B77
B79
B72
Performance Data
Models: 30RW, 30RWQ and 30HQW Hot Water Coil Mbh Capacities
Models: 30RW, 30RWQ and 30HQW Hot Water Coil Pressure Drop
B83
B90
B4
8-2-12
B92
B
SINGLE DUCT TERMINAL UNITS
3-31-14
B5
SINGLE DUCT
VARIABLE OR CONSTANT
AIR VOLUME
3000 SERIES
Models:
3001
Cooling or Heating
only
30RE
Cooling with
Electric Reheat
Model 3001
The 3000 Series Single Duct Terminal Units form the backbone of Nailors single duct line. Utilizing an inclined opposed
blade damper, the 3000 Series exhibit a more linear flow characteristic than the common butterfly type. Used in constant
volume or VAV applications, the 3000 series provides minimal system pressure drop while offering maximum system
flexibility. 3000 Series units are available with electric and hot water reheat as well as options like removable flow sensors
and access doors. Each unit is available with multiple insulation types, ranging from standard fiberglass to "IAQ" types.
STANDARD FEATURES:
22 ga. (0.86) zinc coated steel
casing, mechanically sealed, low
leakage construction. Leakage is less
than 1% of the terminal rated airflow
at 1" w.g. (249 Pa).
16 ga. (1.63) corrosion-resistant
steel inclined opposed blade damper
with extruded PVC seals (single blade
on size 4, 5 and 6). 45 rotation, CW
to close. Tight close-off. Damper
leakage is less than 2% of nominal
flow at 3" w.g. (746 Pa).
Self-lubricating Celcon bearings.
1/2" (13) dia. plated steel drive
shaft. An indicator mark on the end of
the shaft shows damper position.
Inclined opposed blade valve is
inherently more linear in its flow
characteristics than the standard
butterfly type damper. More accurate
flow control is ensured, which reduces
hysteresis for more stable control of
the temperature in the zone.
Available in 11 unit sizes to handle
from 0 8300 cfm (85 3917 l/s).
Maximum unit height is only 12 1/2"
(318) for sizes 4 through 16. Unit
sizes 4 through 10 feature round
B6
4-19-12
Options:
Steri-Liner.
Fiber-Free Liner.
Solid metal liner.
Removable Flow Sensor.
1" (25) Fiberglass liner.
Bottom access door.
24 VAC Control transformer.
Hanger bracket.
Controls enclosure for field
mounted controls.
Dust tight enclosure seal.
Low temperature construction.
Ultra Low Leakage casing.
Bottom mount controls enclosure.
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
UNIVERSAL PNEUMATIC
CONTROL MOUNTING PANEL AND
PROTECTIVE SHROUD
DAMPER
DRIVESHAFT
AIRFLOW
H
H
6 1/2"
(165)
1/2"
(13)
5 3/4"
(146)
5 1/2"
(140)
14 1/2" (368)
15 1/2" (394)
OPTIONAL
ACCESS DOOR
5 3/4"
(146)
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
CONTROLS ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
A full NEMA 1 controls enclosure is provided for factory mounted controls. Optional for field mounted controls.
DAMPER
DRIVESHAFT
11"
(279)
1/2"
(13)
AIRFLOW
H
6"
(152)
5 1/2"
(140)
14" (356)
15 1/2" (394)
OPTIONAL
ACCESS DOOR
6"
(152)
1/2"
(13)
Analog Electronic and Digital Controls with Bottom Mount Control Enclosure
MULTI-POINT
AVERAGING
FLOW SENSOR
1/2"
(13)
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
5 1/2"
(140)
1/2"
(13)
15 1/2" (394)
OPTIONAL
ACCESS DOOR
AIRFLOW
H
DAMPER
DRIVESHAFT
6"
(152)
CONTROLS ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
11" (279)
14" (356)
6"
(152)
11" (279)
12-16-11
B7
MULTI-POINT
AVERAGING
FLOW SENSOR
AIRFLOW
H
6 1/2"
(165)
1/2"
(13)
5 3/4"
(146)
5 1/2"
(140)
14 1/2" (368)
5 3/4"
(146)
51 1/2" (1308)
OPTIONAL
ACCESS DOOR
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
11"
(279)
1/2"
(13)
B8
CONTROLS ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
11-8-13
6"
(152)
DAMPER
DRIVESHAFT
AIRFLOW
5 1/2"
(140)
14" (356)
51 1/2" (1308)
OPTIONAL ACCESS DOOR
6"
(152)
Pneumatic Controls
MULTI-POINT
AVERAGING
FLOW SENSOR
INLET: ROUND,
UNIVERSAL PNEUMATIC
FLAT OVAL OR CONTROL MOUNTING PANEL AND
PROTECTIVE SHROUD
RECTANGULAR
AIRFLOW
H
6 1/2"
(165)
1/2"
(13)
5 3/4"
(146)
5 1/2"
(140)
14" (356)
15 1/2" (394)
OPTIONAL
ACCESS DOOR
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
CONTROLS ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
11"
(279)
1/2"
(13)
AIRFLOW
5 1/2"
(140)
6"
(152)
14" (356)
15 1/2" (394)
OPTIONAL
ACCESS DOOR
Analog Electronic and Digital Controls with Bottom Mount Controls location
MULTI-POINT INLET: ROUND,
AVERAGING
FLAT OVAL OR
FLOW SENSOR RECTANGULAR
1/2"
W
(13)
5 1/2"
(140)
22 1/2" (572)
AIRFLOW
H
CONTROLS
ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
6"
(152)
11" (279)
DAMPER
DRIVESHAFT
L
OPTIONAL
ACCESS DOOR
14" (356)
W
DIMENSION "L"
1 OR 2 ROW COILS, L = 5" (127)
3 OR 4 ROW COILS, L = 7" 1/2 (191)
4-24-12
B9
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
CONTROLS ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
DAMPER
DRIVESHAFT
11" AIRFLOW
(279)
1/2"
(13)
5 1/2"
(140)
6"
(152)
14" (356)
51 1/2" (1308)
L
OPTIONAL ACCESS DOOR
Analog Electronic and Digital Controls with Bottom Mount Controls Location
SINGLE DUCT TERMINAL UNITS
5 1/2"
(140)
51 1/2" (1308)
CONTROLS
ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
6"
(152)
11" (279)
B10
5-3-11
DAMPER
DRIVESHAFT
DAMPER
DRIVESHAFT
14" (356)
OPTIONAL
ACCESS DOOR
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
CONTROLS ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
1/2"
(13)
6"
(152)
ELECTRIC COIL
CONTROLS
ENCLOSURE
(HINGED ACCESS
DOOR)
PRIMARY
AIR
VALVE
CONTROLS
ENCLOSURE
AIRFLOW
11"
(279)
5 1/2"
(140)
1/2" (13)
11"
(279)
29" (737)
31" (787)
OPTIONAL ACCESS DOOR
6"
(152)
Analog Electronic and Digital Controls with Bottom Mount Control Enclosure
MULTI-POINT
AVERAGING
FLOW SENSOR
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
1/2" (13)
AIRFLOW
DAMPER
DRIVESHAFT
CONTROLS ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
6" (152)
1/2"
(13)
W
(CONTROL ENCLOSURE
& TERMINAL)
PRIMARY
ELECTRIC COIL
AIR VALVE
CONTROLS ENCLOSURE
CONTROLS ENCLOSURE (HINGED ACCESS DOOR)
5 1/2"
(140)
6" (152)
W
29" (737)
31" (787)
(CONTROL ENCLOSURE
& TERMINAL)
Dimensional Data
Unit
Size
Inlet Size
4
5
6
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
7
8
9
12 (305) 12 12 (318)
12 (305) 12 12 (318)
14 (356) 12 12 (318)
10
12
14
14 (356) 12 12 (318)
9 78 (251) Round
1
15
18 (457) 12 2 (318) 12 16 x 9 1316 (329 x 249) Oval
24 (610) 12 12 (318) 16 116 x 9 1316 (408 x 249) Oval
16
28 (711) 12 12 (318)
24 x 16 38 (965) 18 (457)
Coil Connections
1 Row
2 Row
3 Row
3 8 (98) Round
4 78 (124) Round
5 78 (149) Round
2 (13)
2 (13)
1
2 (13)
8 (22)
8 (22)
7
8 (22)
8 (22)
8 (22)
7
8 (22)
8 (22)
8 (22)
7
8 (22)
5 (127)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
7 12 (191)
6 78 (175) Round
7 78 (200) Round
8 78 (225) Round
2 (13)
2 (13)
1
2 (13)
8 (22)
8 (22)
7
8 (22)
8 (22)
8 (22)
7
8 (22)
8 (22)
8 (22)
7
8 (22)
5 (127)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
7 12 (191)
2 (13)
2 (13)
1
2 (13)
8 (22)
8 (22)
7
8 (22)
8 (22)
8 (22)
7
8 (22)
8 (22)
8 (22)
7
8 (22)
5 (127)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
7 12 (191)
8 (22)
8 (22)
7
8 (22)
1 38 (35)
7
8 (22)
1 38 (35)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
8 (22)
8 (22)
5-3-11
B11
Nominal
Door Size
Max. Leakage
8"w.g. (2 kPa) cfm
4 12
8" x 5"
(203 x 127)
0.036 cfm
(1.02 l/min.)
14 24 x 16
12" x 6"
(305 x 152)
0.064 cfm
(1.8 l/min.)
0.5" (124)
4, 5, 6
7, 8
9, 10
12
14
16
24 x 16
1 (0.5)
1 (0.5)
1 (0.5)
2 (1)
2 (1)
2 (1)
3 (1)
1 (0.5)
2 (1)
2 (1)
3 (1)
3 (1)
3 (1)
4 (2)
3 (1)
4 (2)
4 (2)
5 (2)
5 (2)
5 (2)
6 (3)
6" (1049)
Inlet
Size
6 (3)
7 (3)
8 (4)
9 (4)
9 (4)
10 (5)
12 (6)
4, 5, 6
7, 8
9, 10
12
14
16
24 x 16
3 (1)
2 (1)
2 (1)
2 (1)
3 (1)
3 (1)
7 (3)
4 (2)
3 (1)
3 (1)
3 (1)
4 (2)
4 (2)
9 (4)
The ULC option consists of silicone applied to all internal seams during
assembly, resulting in an air tight casing to meet the strictest project
specifications.
NOM.
- 1/8" (3)
2" (51)
4" (102)
SIDE VIEW
B12
11-5-12
END VIEW
Unit Size
4, 5, 6
7, 8
7, 8 (178, 203)
9, 10
9, 10 (229, 254)
12
12 12 (318)
14
12 12 (318)
16
12 12 (318)
24 x 16
N/A
3 (1)
7 (3)
5 (2)
6 (3)
4 (2)
6 (3)
7 (3)
Unit
Size
3 (916) Long
5 (1524) Long
4, 5, 6
7, 8
9, 10
12
36" (914) OR 59" (1499)
W
4" (102)
TYPICAL
SIDE VIEW
END VIEW
14, 16
4" (102)
TYPICAL
Outlet
Size
1, 2, or 3
2, 3, 4 or 5
3, 4 or 5
2, 3 or 4
4 or 5
3, 4 or 5
4 or 5
6 (152)
6, 8 (152, 203)
8 (203)
10 (254)
8 (203)
10 (254)
10 (254)
OPTIONS:
Steri-Liner.
Fiber-Free Liner.
1" (25) Fiberglass Liner.
FEATURES:
22 ga. (0.86) galvanized steel construction, mechanically sealed, low leakage
construction.
Only one outlet size to be specified per M.O.A. No mixing of outlet sizes on the same
unit. Number and size of outlets on M.O.A. not to exceed the limits listed in table,
both maximum quantity of outlets and maximum size of outlet.
All round outlets include manual dampers with hand locking quadrant.
3/4" (19) dual density insulation, exposed edges coated to prevent erosion.
Denotes inlet airflow direction.
For special outlet sizes and arrangements, consult your Nailor representative.
Slip and drive cleat duct connection.
3 (916) Long
5 (1524) Long
AD
FEATURES:
22 ga. (0.86) galvanized steel
construction.
Shipped loose for field
attachment.
Slip and drive connection.
3/4" (14) dual density fiberglass
insulation, exposed edges coated
to prevent erosion as standard.
Unit Size
AD
4, 5, 6
7, 8
9, 10
12
14
16
24 x 16
10" (254)
12" (305)
14" (356)
18" (457)
24" (610)
28" (711)
38" (965)
10" (254)
12 12" (318)
12 12" (318)
12 12" (318)
12 12" (318)
12 12" (318)
18" (457)
12" (305)
12" (305)
12" (305)
12" (305)
12" (305)
12" (305)
12" (305)
W
END VIEW
OPTIONS:
Steri-Liner.
Fiber-Free Liner.
Solid Metal Liner.
1" (25) Fiberglass Liner.
2" (51) Fiberglass Liner.
Perforated Metal Liner.
Steri-Liner with Perforated Liner.
Access Door
Sizes 4 to 12 : 8" x 5" (203 x 127)
Oval; Sizes 14 to 24 x 16: 12" x 16"
(305 x 406) Oval.
Note: Select Insulation to match VAV
terminal.
4-20-12
B13
Unit
Size
Inlet
Type
4
5
Round
6
7
8
Round
9
10
12
14
Flat Oval
16
24 x 16 Rect.
Total
Airflow
Range,
cfm
Airflow at
2000 fpm
Inlet
Velocity
(nom.), cfm
0 225
0 400
0 550
0 800
0 1100
0 1400
0 1840
0 2500
0 3125
0 3725
0 8330
150
250
400
550
700
900
1100
1600
2100
2800
5350
Model 30RE
1.5
225
400
550
800
1100
1400
1840
2500
3125
3725
8330
374
106
189
260
378
519
661
868
1180
1475
1758
3931
Unit
Size
Inlet
Type
4
5
Round
6
7
8
Round
9
10
12
14
Flat Oval
16
24 x 16 Rect.
B14
4-19-12
Total
Airflow
Range,
l/s
Airflow at
10.2 m/s
Inlet
Velocity
(nom.), l/s
0 106
0 189
0 260
0 378
0 519
0 661
0 868
0 1180
0 1475
0 1758
0 3931
71
118
189
260
330
425
519
755
991
1321
2525
10
12
14
16
24
x
16
cfm
225
200
150
100
75
50
350
300
250
200
125
100
500
450
400
300
200
100
650
550
335
225
110
900
800
700
600
400
175
1050
900
675
450
225
1350
1100
825
550
275
2000
1600
1200
800
400
2700
2100
1550
1050
525
3500
2800
2100
1400
700
8000
7000
6000
5350
5000
4000
3000
l/s
106
94
71
47
35
24
165
142
118
94
59
47
236
212
189
142
94
47
307
260
158
106
52
425
378
330
283
189
83
495
425
319
212
106
637
519
389
260
130
944
755
566
378
189
1274
991
731
495
248
1652
1321
991
661
330
3775
3303
2831
2525
2360
1888
1416
RADIATED
0.5"
1.0"
1.5" 2.0" 3.0"
Min. w.g. w.g. w.g.
w.g. w.g.
Ps 125 Pa 249 Pa 375 Pa 500 Pa 750 Pa
20
23
24
28
23
41
40
36
32
31
24
20
20
20
25
20
26
21
30
24
44
41
39
38
37
35
31
20
21
20
23
22
21
21
24
21
29
25
20
30
26
24
33
29
26
21
48
47
45
44
43
39
36
23
21
21
23
21
23
22
21
20
24
24
20
27
24
24
23
20
24
23
23
28
24
21
31
28
24
20
34
31
28
24
36
34
30
26
51
49
47
46
45
43
38
25
24
22
20
25
23
22
20
27
24
25
21
29
28
22
29
28
26
25
21
28
28
25
20
29
25
23
33
30
28
21
37
34
30
28
39
36
34
29
23
54
51
49
48
47
45
40
29
28
22
23
20
30
28
25
22
30
29
29
25
20
34
32
24
33
30
31
31
25
33
32
26
22
32
31
28
22
37
35
31
24
40
37
34
28
43
40
36
31
21
57
55
53
52
50
47
44
Airflow
Performance Notes:
1. NC Levels are calculated based on procedures as outlined on
page B75.
2. Dash (-) in space indicates a NC less than 20.
B15
Inlet Airflow
Size cfm l/s
225 106
200 94
150 71
4
100 47
75 35
50 24
350 165
300 142
250 118
5
200 94
125 59
100 47
500 236
450 212
400 189
6
300 142
200 94
100 47
650 307
550 260
7 335 158
225 106
110 52
900 425
800 378
700 330
8
600 283
400 189
175 83
1050 495
900 425
9 675 319
450 212
225 106
1350 637
1100 519
10 825 389
550 260
275 130
2000 944
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1550 731
1050 495
525 248
3500 1652
2800 1321
16 2100 991
1400 661
700 330
8000 3775
7000 3303
24 6000 2831
x 5350 2525
16 5000 2360
4000 1888
3000 1416
Min. inlet
Ps
"w.g. Pa
0.14 35
0.11 27
0.06 15
0.03 7
0.01 2
0.01 2
0.05 12
0.04 10
0.03 7
0.02 5
0.01 2
0.01 2
0.11 27
0.09 22
0.07 17
0.04 10
0.02 5
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.04 10
0.03 7
0.02 5
0.02 5
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.40 99
0.31 77
0.23 57
0.18 45
0.16 40
0.10 25
0.06 15
Minimum Ps
2 3 4 5 6 7
- 50 53 57 48 43
- 44 47 49 39 35
- 44 47 49 39 35
- - 38 37 27 - - 32 28 20 - - - - - 56 59 53 57 49 47
55 58 54 57 49 47
- 49 49 51 42 40
- 44 44 44 34 32
- - 33 30 - - - 30 25 - 58 54 54 60 48 45
58 54 53 59 48 45
56 51 49 54 44 40
- 45 41 46 35 31
- - 30 32 - - - - - - 60 58 63 59 51 48
58 54 57 53 46 42
53 42 42 38 29 22
- - 31 26 - - - - - - 60 56 60 58 51 44
60 56 60 58 51 44
59 54 57 56 48 40
56 52 52 50 42 32
- 41 41 38 29 - - - - - 59 56 61 59 54 48
56 54 55 54 48 41
- 46 47 45 39 30
- - 34 30 - - - - - - 57 55 60 59 54 51
54 49 53 52 47 43
- 43 46 44 38 33
- - 32 28 - - - - - - 62 59 63 61 56 53
57 51 55 53 48 44
52 45 47 44 38 34
49 38 37 33 28 - - - - - 64 60 66 64 60 54
58 56 58 55 51 44
52 44 48 46 41 33
- 36 36 32 27 - - - - - 64 60 66 64 60 54
60 55 56 58 54 48
54 47 51 49 44 38
- 38 39 35 30 - - 25 23 - 77 73 72 67 66 62
74 70 71 65 64 60
71 69 67 62 61 56
70 66 63 58 57 52
69 65 62 57 56 51
67 60 58 51 50 45
64 58 56 50 48 43
For full performance table notes, see page B19; RED highlighted numbers indicate embedded AHRI certification points.
B16
4-12-12
Minimum Ps
2 3 4 5 6 7
- 41 44 43 31 31
- 40 44 43 31 31
- - 38 35 22 23
- - 29 23 - - - - - - - - - - - 53 54 50 43 - 52 53 49 43 - - 44 44 37 - - 39 39 30 - - - 28 - - - - 25 - - 53 50 50 46 - 53 50 49 46 - 51 47 45 41 - - 41 37 33 - - - 26 - - - - - - - 53 52 58 48 30 30
51 48 52 42 25 24
47 36 37 27 - - - 26 - - - - - - - 54 51 57 48 37 27
54 51 56 48 37 27
53 49 53 46 34 23
51 46 48 40 28 20
- 36 37 28 - - - - - - 56 52 58 50 37 34
53 50 52 45 31 27
- 42 44 36 22 - - 31 21 - - - - - - 55 53 58 50 38 39
52 47 51 43 31 31
- 41 44 35 22 21
- - 30 - - - - - - - 59 56 58 50 42 41
54 48 50 41 34 33
49 42 42 33 24 23
46 35 32 22 - - - - - - 62 58 62 59 49 45
56 54 54 46 40 35
50 42 44 37 30 24
- 34 32 23 - - - - - - 61 59 62 57 52 46
57 54 52 51 46 40
51 46 47 42 36 30
- 37 35 28 22 - - - - - 76 73 69 59 60 57
73 69 68 57 58 55
70 68 64 54 55 51
69 66 62 52 53 48
68 64 59 49 50 46
66 59 55 43 44 40
63 57 53 42 42 38
B17
Inlet Airflow
Size cfm l/s
225 106
200 94
150 71
4
100 47
75 35
50 24
350 165
300 142
250 118
5
200 94
125 59
100 47
500 236
450 212
400 189
6
300 142
200 94
100 47
650 307
550 260
7 335 158
225 106
110 52
900 425
800 378
700 330
8
600 283
400 189
175 83
1050 495
900 425
9 675 319
450 212
225 106
1350 637
1100 519
10 825 389
550 260
275 130
2000 944
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1550 731
1050 495
525 248
3500 1652
2800 1321
16 2100 991
1400 661
700 330
8000 3775
7000 3303
24 6000 2831
x 5350 2525
16 5000 2360
4000 1888
3000 1416
Min. inlet
Inlet Airflow
Ps
Size cfm l/s "w.g. Pa
225 106 0.14 35
200 94 0.11 27
150 71 0.06 15
4
100 47 0.03 7
75 35 0.01 2
50 24 0.01 2
350 165 0.05 12
300 142 0.04 10
250 118 0.03 7
5
200 94 0.02 5
125 59 0.01 2
100 47 0.01 2
500 236 0.11 27
450 212 0.09 22
400 189 0.07 17
6
300 142 0.04 10
200 94 0.02 5
100 47 0.01 2
650 307 0.01 2
550 260 0.01 2
7 335 158 0.01 2
225 106 0.01 2
110 52 0.01 2
900 425 0.04 10
800 378 0.03 7
700 330 0.02 5
8
600 283 0.02 5
400 189 0.01 2
175 83 0.01 2
1050 495 0.01 2
900 425 0.01 2
9 675 319 0.01 2
450 212 0.01 2
225 106 0.01 2
1350 637 0.01 2
1100 519 0.01 2
10 825 389 0.01 2
550 260 0.01 2
275 130 0.01 2
2000 944 0.01 2
1600 755 0.01 2
12 1200 566 0.01 2
800 378 0.01 2
400 189 0.01 2
2700 1274 0.01 2
2100 991 0.01 2
14 1550 731 0.01 2
1050 495 0.01 2
525 248 0.01 2
3500 1652 0.01 2
2800 1321 0.01 2
16 2100 991 0.01 2
1400 661 0.01 2
700 330 0.01 2
8000 3775 0.40 99
7000 3303 0.31 77
24 6000 2831 0.23 57
x 5350 2525 0.18 45
16 5000 2360 0.16 40
4000 1888 0.10 25
3000 1416 0.06 15
Minimum Ps
2 3 4 5 6 7
- 37 33 33 - - 36 33 32 - - 35 29 31 - - - - - - - - - - - - - - - - 48 39 33 32 30 27
47 38 32 32 30 27
- 35 31 25 23 - - - - - - - - - - - - - - - 48 44 38 36 30 28
48 44 37 35 30 28
- 42 33 33 28 26
- 34 27 26 - - - - - - - - - - - 48 45 46 38 31 30
49 43 41 33 27 25
- - 28 33 - - - - - - - - - - - 51 47 40 34 31 29
51 46 40 33 31 28
50 43 37 31 29 25
- 39 33 29 26 - 35 26 - - - - - - - 50 44 44 41 34 32
48 40 39 36 30 29
47 37 31 29 22 - - 24 - - - - - - - 53 42 41 36 30 23
51 37 35 30 25 - 33 29 25 - - - - - - - - - - - 54 50 49 44 37 33
52 45 41 36 30 27
47 39 33 29 24 - - - - - - - - - - 57 54 50 46 42 36
54 48 44 39 35 30
46 40 35 30 28 - 32 24 - - - - - - - 57 57 53 49 43 36
54 51 49 43 37 32
49 44 41 34 28 - 34 31 - - - - - - - 71 67 66 61 58 53
67 64 65 59 57 53
64 60 61 55 53 51
63 57 57 52 52 47
62 56 56 51 51 46
61 52 50 46 43 40
56 48 46 43 39 37
For full performance table notes, see page B19; RED highlighted numbers indicate embedded AHRI certification points.
B18
6-28-13
4
5
6
7
8
9
10
12
14
16
24 x 16
Airflow
Min. Inlet
Ps
cfm l/s
" w.g. Pa
0.24
0.08
0.05
0.08
0.01
0.01
0.01
0.01
0.01
0.05
0.01
69
71
74
78
79
78
77
79
80
82
87
68
72
75
73
73
73
72
74
74
75
81
150
250
400
550
700
900
1100
1600
2100
2800
5350
71
118
189
260
330
425
519
755
991
1321
2525
61
20
12
21
2
2
2
2
2
12
2
Octave Band
4
5
6
62
63
66
68
68
68
68
71
73
72
79
58
61
64
65
65
65
66
70
72
69
76
51
51
53
59
58
59
59
63
65
63
72
48
48
50
55
54
56
56
59
60
59
69
49
55
59
61
61
60
60
61
63
65
72
50
48
52
54
53
54
54
58
61
63
70
47
45
47
49
50
49
50
53
55
57
70
39
35
40
43
40
44
45
49
48
50
65
31
35
36
36
39
39
39
42
44
44
60
30
30
33
33
35
36
36
39
43
39
55
2-12-15
Octave Band
4
5
6
B19
3.
Unit casing shall be 22 ga. (.86) galvanized steel with round,
flat oval or rectangular inlets with 5 12" (140) deep inlet duct collar
for field connection. Outlets shall be rectangular and configured
for slip and drive connections. Casing leakage downstream of the
damper shall not exceed 1% @ 1" w.g. (249 Pa). High side casing
leakage shall not exceed 2% @ 3" w.g. (746 Pa).
4.
Damper assemblies of 16 ga. (1.63) galvanized steel shall
be multiple opposed blade construction arranged to close at 45
degrees from full open to minimize air turbulence and provide near
linear operation. Damper blades shall be fitted with flexible seals
for tight closure and minimized sound generation. Damper blades
shall be screwed through the shaft to insure that no slippage
occurs. Blade shafts shall pivot on corrosion free Celcon bearings.
In the fully closed position, air leakage past the closed damper shall
not exceed 2% of the nominal catalog rating at 3" w.g. (746 Pa) inlet
static pressure as rated by ASHRAE Standard 130.
5.
The terminal units shall be capable of operation as described
herein with a minimum inlet static pressure that shall not exceed
.18" w.g. (45 Pa) @ 2000 fpm (10.2 m/s) inlet velocity. (The
sequence of operations should be described here, if not part of the
temperature controls specifications.) Each unit shall be complete
with factory mounted (pneumatic, electric, analog electronic, or
DDC) controls. Gauge tap ports shall be supplied in the piping
between the flow pick up and the controller.
6.
Each unit shall be constructed with single point electrical or
pneumatic connection. All electrical components shall be ETL or
UL listed or recognized and installed in accordance with the
National Electrical Code. All electrical components shall be
installed in a control box. The entire assembly shall be ETL listed
and so labeled.
7.
Each unit shall be internally lined with 34" (19) dual density
fiberglass insulation. Edges shall be sealed against airflow
erosion. Units shall meet NFPA 90A and UL 181 standards.
8.
All sound data shall be compiled in an independent
laboratory and in accordance with the latest version of AHRI
Standard 880 and ANSI/ASHRAE Standard 130. All units shall be
AHRI certified and bear the AHRI certification label.
OPTIONS
Electric Heat:
Model: 30RE
Staged
(Substitute the following paragraphs:)
1.
Furnish and install Nailor Model 30RE Single Duct
Variable Volume Terminal Units of the sizes and capabilities as
indicated on the drawings. Units shall be pressure independent
with (pneumatic, analog electronic, DDC) controls. Units shall
reset to any flow between minimum and the maximum cataloged
airflow as allowed by the specific controller.
9.
Single
Duct
VAV
Terminal
Unit
Staged
Electric Heating Coils:
a. Electric heating coils shall consist of open coils of high grade
nickel and chromium resistance wire or nichrome elements and
insulated with ceramic insulators in galvanized steel brackets,
supported in heavy gauge galvanized steel frames. Each unit
employing an electric heating coil shall be constructed and
installed in accordance with the requirements of the local
authorities and shall be UL or ETL listed specifically with the
heater as a component of the terminal unit device.
b. Coils shall have the capacities indicated in Contract
Documents. Coils rated up through 16.5 kW shall be single phase,
347 volt, 60 hertz and coils larger than 16.5 kW shall be three
phase, four wire, 208, 480 or 600 volt, 60 hertz. Coils shall be
available in one, two or three stages.
c. Terminal bolts, nuts and washers shall be of corrosion resistant
materials. Coils shall be constructed so the installation may be
accomplished in accordance with the provisions of the National
Electrical Code, for zero clearance. Coils shall be given a 2000
volt dielectric test at the factory.
d. Automatic reset thermal cutouts shall be furnished for primary
protection with manually resettable limit switches in power circuits for
secondary protection. Both devices shall be serviceable through
terminal box without removing heating element from the terminal
device. The air pressure safety cutout pickup probe shall be remotely
mounted near the volume control damper for maximum fidelity.
e. Heating coils shall have a terminal box and cover, with quiet
type built-in magnetic step controlled contactors for each circuit,
branch circuit fusing for each branch circuit on heaters over 48
amps per the NEC and an air flow safety interlock switch for
installation in the heater control enclosure. Provide a 120 or 24
VAC control power transformer with an integral or separately
mounted primary and/or secondary overcurrent protection device
in accordance with NEC requirements.
f. All wiring of built-in devices shall be brought to clearly marked
terminal strips. A complete wiring diagram shall be permanently
attached to the heating coil panel cover.
g. Electric heating coils shall be designed for operation with the
DDC controller and control system.
h. Electric heating coils and the associated control panels shall be
constructed as a component of the entire terminal unit and
mounted in the discharge attenuator downstream of the terminal
unit. The resulting unit, including the heater and the VAV damper,
shall be no longer than 37" (940) in length.
i. The manufacturer shall prove adequate even airflow over the
electric heating coil under the full range of airflow scheduled
(minimum to maximum) to prevent uneven heating of the electric
coils. The terminal device shall be listed in accordance with UL
1995 as a composite assembly consisting of the VAV terminal
device and the electric heating device.
B20
4-25-12
4-25-12
B21
1.
Furnish and install Nailor Model 30RE Single Duct
Variable Volume Terminal Units of the sizes and capabilities as
indicated on the drawings. Units shall be pressure independent with
(pneumatic, analog electronic, DDC) controls. Units shall reset to
any flow between minimum and the maximum cataloged airflow as
allowed by the specific controller.
9. Single Duct VAV Terminal Unit Proportional Electric Heating
Coils:
a. Electric heating coils shall consist of open coils of high grade
nickel and chromium resistance wire or nichrome elements and
insulated with ceramic insulators in galvanized steel brackets,
supported in heavy gauge galvanized steel frames. Each unit
employing an electric heating coil shall be constructed and installed
in accordance with the requirements of the local authorities and shall
be UL or ETL listed specifically with the heater as a component of the
terminal unit device.
B22
4-25-12
Liner:
Steri-Liner
(Substitute the following paragraph:)
7.
Each unit shall be fully lined with non-porous, sealed
liner which complies with NFPA 90A and UL 181. Installation shall
be 1/2" (13) minimum thickness, 4 lb./cu. ft. (64 kg/m3) density
with reinforced aluminum foil-scrim-kraft (FSK) facing. All cut
edges shall be secured with steel angles or end caps to
encapsulate edges and prevent erosion. Insulation shall be Nailor
Steri-Liner or equal.
Fiber-Free Liner
(Substitute the following paragraph:)
7.
Each unit shall be fully lined with a non-porous closed
cell elastomeric foam liner which complies with NFPA 90A, ASTM
E84 and UL 181. Installation shall be 3/8" (10) minimum thickness
and secured to the interior of the terminal with mechanical
fasteners. No fiberglass is permitted. Insulation shall be Nailor
Fiber-Free Liner or equal.
Section 15 - - - General.
2.
3.
4.
5.
6.
7.
1.02 SUMMARY
A. Furnish and install all air terminal units herein specified and
as indicated on the Drawings.
1.03 REFERENCE STANDARDS
1.
2.
3.
4.
1.
Discharge Noise: Maximum permissible sound power levels
in octave bands of discharge sound through discharge ducts from
terminal units operated at an inlet pressure of 1.0" w.g. (249 Pa)
and the maximum amount of air volume shown on the Project
Mechanical Drawings leaving the terminal unit and entering the
reverberant chamber shall be as follows:
NC-35
67
64
67
66
67
67
NC-40
71
69
72
71
72
72
Table 2.
NC-35
64
57
53
50
50
53
NC-40
68
62
58
55
55
58
1.07 WARRANTY
A. Manufacturer shall warrant equipment for one year from start
up or 18 months from shipment.
PART 2 PRODUCTS
2.01 UNAUTHORIZED MATERIALS
A. Materials and products required for the work of this section
shall not contain asbestos, polychlorinated biphenyls (PCB) or
other hazardous materials identified by the Engineer or Owner.
2.02 ACCEPTABLE MANUFACTURERS
A. These Specifications set forth the minimum requirements for
single duct VAV terminal units. If they comply with these
Specifications, single duct VAV terminal units manufactured by
one of the following manufacturers will be acceptable:
1. Nailor Industries.
2.03 SINGLE DUCT AIR VOLUME TERMINAL UNITS
A. Furnish and install single duct VAV terminal units as indicated
on the Drawings. The units shall be designed and built as a single
unit and provided with a primary variable air volume damper that
controls the primary air quantity in response to a temperature
control signal. The damper construction shall be rectangular with
multiple opposed blades designed to operate on a 45 arc. Blades
shall be 16 ga. (1.63) galvanized steel, single thickness
construction with heavy-duty gasket glued to the blades. Units
shall be suitable for pressure independent operation with digital
(DDC) controls. The units shall contain a damper assembly as
described above and [electric or hot water] heating coils where
scheduled and/or indicated on the Drawings. The space limitations
shall be reviewed carefully to ensure all terminal units will fit into
the space provided including National Electric Code clearances
required in front of all panels containing electrical devices. Unit
shall be fully lined with at least 34" (186) thick, dual density
fiberglass insulation that complies with NFPA 90 for fire and
smoke resistivity and UL 181 for erosion.
5-3-11
B23
Octave Band
2
3
4
5
6
7
B24
11-14-11
OPTIONS
Electric Heat:
Model: 30RW
Model: 30RE
11-14-11
B25
e. Heating coils shall have a terminal box and cover, with quiet
type built-in magnetic step controlled contactors for each circuit,
branch circuit fusing for each branch circuit on heaters over 48
amps per the NEC and an air flow safety interlock switch for
installation in the heater control enclosure. Contactors mounted in
terminal units that are located above the ceiling in tenant occupied
spaces shall be mercury step type. Provide a 120 or 24 VAC
control power transformer with an integral or separately mounted
primary and/or secondary overcurrent protection device in
accordance with NEC requirements.
B26
12-21-11
Models:
3001Q
Cooling or Heating
only
Model 3001Q
STANDARD FEATURES:
Designed for noise sensitive
applications such as classrooms,
libraries, studios and performance
halls.
22 ga. (0.86) galvanized steel
casing, mechanically sealed, low
leakage construction.
16 ga. (1.63) corrosion-resistant
steel inclined opposed blade damper
with extruded PVC seals (single blade
on size 4, 5, 6). 45 rotation, CW to
close. Tight close-off. Damper leakage
is less than 2% of the terminal rated
airflow at 3" w.g. (746 Pa).
1/2" (13) dia. plated steel drive
shaft. An indicator mark on the end of
the shaft shows damper position.
Multi-point averaging Diamond
Flow Sensor. Aluminum construction.
Supplied with balancing tees.
Rectangular discharge with slip and
drive cleat duct connection.
Full NEMA 1 type controls
enclosure for factory mounted
controls.
VAV section is lined with 3/4" (19),
dual density insulation, exposed
11-7-11
B27
3000Q Series Quiet terminal units are used in noise sensitive applications such as libraries, studios, performance halls,
classrooms and conference rooms. The integral dissipative silencer minimizes pressure loss, reduces self-generated sound
and maximizes acoustical attenuation, providing an extremely quiet terminal without the addition of downstream acoustic
insulation. Model 3000Q Series are available with electric and hot water reheat as well as options like removable flow
sensors and access doors. Each unit is available with multiple insulation types, ranging from standard fiberglass to "IAQ"
types.
UNIVERSAL PNEUMATIC
CONTROL MOUNTING
PANEL AND
PROTECTIVE SHROUD
RECTANGULAR
DISSIPATIVE SILENCER
DAMPER
DRIVESHAFT
AIRFLOW
H
6 1/2"
(165)
OPTIONAL
(FMI)
5 1/2"
REMOVABLE (140)
FLOW SENSOR
6"
(152)
W
1/2"
(13)
14 1/2" (368)
15 1/2" (394)
36" (914)
6"
(152)
1/2"
(13)
51 1/2" (1308)
OPTIONAL ACCESS DOOR
14" (356)
AIRFLOW
11"
(279)
6"
(152)
W
1/2"
(13)
51 1/2" (1308)
OPTIONAL
ACCESS DOOR
Unit
Size
Inlet Size
4
5
6
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
3 78 (98) Round
4 78 (124) Round
5 78 (149) Round
7
8
9
12 (305) 12 12 (318)
12 (305) 12 12 (318)
14 (356) 12 12 (318)
10
12
14
14 (356) 12 12 (318)
9 78 (251) Round
1
15
18 (457) 12 2 (318) 12 16 x 9 1316 (329 x 249) Oval
24 (610) 12 12 (318) 16 116 x 9 1316 (408 x 249) Oval
11-14-11
36" (914)
15 1/2" (394)
Dimensional Data
B28
DAMPER
DRIVESHAFT
OPTIONAL
5 1/2"
(FMI)
(140)
REMOVABLE
FLOW SENSOR
16
28 (711) 12 12 (318)
24 x 16 38 (965) 18 (457)
RECTANGULAR
DISSIPATIVE SILENCER
6 78 (175) Round
7 78 (200) Round
8 78 (225) Round
6"
(152)
1/2"
(13)
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
CONTROLS ENCLOSURE
FOR FACTORY MOUNTED
CONTROLS
11"
(279)
connection.
Optional low leakage gasketed access door is recommended
for coil access and cleaning.
AHRI Certified.
Coil Performance data on pages B??-??.
RECTANGULAR
DISSIPATIVE SILENCER
14" (356)
AIRFLOW
H
DAMPER
DRIVESHAFT
1/2"
(13)
6"
(152)
OPTIONAL
(FMI)
REMOVABLE
FLOW SENSOR
5 1/2"
(140)
B
6"
(152)
48" (1219)
15 1/2" (394)
63 1/2" (1613)
OPTIONAL
ACCESS DOOR
6"
(152)
RECTANGULAR
DISSIPATIVE SILENCER
29" (737)
PRIMARY
AIR
VALVE
CONTROLS
ENCLOSURE
AIRFLOW
11 3/4"
(298)
1/2"
(13)
CONTROLS ENCLOSURE
FOR FACTORY
MOUNTED
CONTROLS
OPTIONAL
5 1/2"
(FMI)
REMOVABLE (140)
FLOW SENSOR
ELECTRIC COIL
CONTROLS
ENCLOSURE
(HINGED
ACCESS DOOR)
48" (1219)
31" (787)
79" (2007)
6"
(152)
1/2"
(13)
OPTIONAL
ACCESS DOOR
Dimensional Data
Hot Water Coil
Unit
Size
Inlet Size
4
5
6
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
3 78 (98) Round
4 78 (124) Round
5 78 (149) Round
5 (127)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
7 12 (191)
7
8
9
12 (305) 12 12 (318)
12 (305) 12 12 (318)
14 (356) 12 12 (318)
6 78 (175) Round
7 78 (200) Round
8 78 (225) Round
5 (127)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
7 12 (191)
10
12
14
14 (356) 12 12 (318)
9 78 (251) Round
1
15
18 (457) 12 2 (318) 12 16 x 9 1316 (329 x 249) Oval
24 (610) 12 12 (318) 16 116 x 9 1316 (408 x 249) Oval
5 (127)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
7 12 (191)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
16
28 (711) 12 12 (318)
24 x 16 38 (965) 18 (457)
11-7-11
B29
Right or left hand coil connection is determined by looking through the terminal inlet in the direction of airflow.
GROMMET
SUPPORT
BRACKET
HIGH
PRESSURE
LOW PRESSURE
GASKET
SCREW
HEAD
ROUND OR
FLAT OVAL
INLET
FEATURES:
CONNECTIONS
FOR 1/4" (6.35)
O.D. FR TUBING
AIRFLOW
DIRECTION
Rectangular Inlet
3/16" (4.76) DIA. O.D.
SUPPORT
BRACKET
GROMMET
GASKET
FLOW
SCREW INSERT
DIRECTION
TO DUCT
LABEL
AT PERIMETER
HOLES
CONNECTIONS
FOR 1/4" (6.35)
O.D. FR TUBING
HIGH
PRESSURE
LOW PRESSURE
RETANGULAR
INLET
AIRFLOW
DIRECTION
Access Door
Ultra-low leakage, premium quality and performance. Flat oval design.
B30
11-7-11
Nominal
Door Size
Max. Leakage
8"w.g. (2 kPa) cfm
4 10
8" x 5"
(203 x 127)
0.036 cfm
(1.02 l/min.)
14 24 x 16
12" x 6"
(305 x 152)
0.064 cfm
(1.8 l/min.)
Unit
Size
Inlet
Type
4
5
Round
6
7
8
Round
9
10
12
14
Flat Oval
16
24 x 16 Rect.
Total
Airflow
Range,
cfm
Airflow at
2000 fpm
Inlet
Velocity
(nom.), cfm
0 225
0 400
0 550
0 800
0 1100
0 1400
0 1840
0 2500
0 3125
0 3725
0 8330
150
250
400
550
700
900
1100
1600
2100
2800
5350
1.5
225
400
550
800
1100
1400
1840
2500
3125
3725
8330
374
106
189
260
378
519
661
868
1180
1475
1758
3931
Unit
Size
Inlet
Type
4
5
Round
6
7
8
Round
9
10
12
14
Flat Oval
16
24 x 16 Rect.
Total
Airflow
Range,
l/s
Airflow at
10.2 m/s
Inlet
Velocity
(nom.), l/s
0 106
0 189
0 260
0 378
0 519
0 661
0 868
0 1180
0 1475
0 1758
0 3931
71
118
189
260
330
425
519
755
991
1321
2525
3-25-14
B31
Model 3001Q
10
12
14
16
24
x
16
Min. inlet
Ps
Airflow
cfm
200
150
100
75
50
300
250
200
125
100
450
400
300
200
100
650
550
335
225
110
800
700
600
400
175
1050
900
675
450
225
1350
1100
825
550
275
2000
1600
1200
800
400
2700
2100
1550
1050
525
3500
2800
2100
1400
700
8000
7000
6000
5350
5000
4000
3000
l/s
94
71
47
35
24
142
118
94
59
47
212
189
142
94
47
307
260
158
106
52
378
330
283
189
83
495
425
319
212
106
637
519
389
260
130
944
755
566
378
189
1274
991
731
495
248
1652
1321
991
661
330
3775
3303
2831
2525
2360
1888
1416
"w.g.
0.30
0.18
0.08
0.05
0.02
0.16
0.11
0.08
0.03
0.02
0.10
0.09
0.06
0.03
0.01
0.08
0.06
0.03
0.02
0.01
0.10
0.08
0.06
0.03
0.01
0.09
0.07
0.04
0.02
0.01
0.19
0.14
0.08
0.04
0.01
0.22
0.14
0.07
0.03
0.01
0.28
0.18
0.10
0.05
0.01
0.46
0.30
0.17
0.07
0.02
0.43
0.33
0.24
0.18
0.17
0.11
0.06
Pa
75
45
20
12
5
40
27
20
7
5
25
22
15
7
2
20
15
7
5
2
25
20
15
7
2
22
17
10
5
2
47
35
20
10
2
55
35
17
7
2
70
45
25
12
2
114
75
42
17
5
107
82
60
45
42
27
15
Min.
0.5"
w.g.
Ps
(125 Pa)
(250 Pa)
(375 Pa)
(500 Pa)
(750 Pa)
Ps
(125 Pa)
28
23
20
-
20
20
20
22
28
27
24
23
23
20
-
20
24
23
22
23
23
22
20
22
24
22
27
23
28
23
27
24
30
29
32
28
25
23
20
20
22
24
20
23
23
22
20
29
27
20
27
29
28
20
27
27
25
28
24
22
29
27
23
29
25
22
30
27
23
38
35
35
32
29
27
24
20
23
24
22
25
24
23
20
32
29
20
29
30
29
20
30
28
27
20
29
27
24
20
30
29
24
30
28
24
33
29
25
42
40
38
34
32
29
25
20
24
25
23
28
27
23
20
33
30
22
33
33
30
22
33
30
29
23
33
30
27
23
35
32
27
20
34
30
28
22
35
33
28
22
45
43
39
36
35
33
28
20
23
24
28
23
41
40
36
34
31
24
20
20
20
25
20
26
21
30
24
44
41
39
38
37
35
31
2.0"
w.g.
21
20
22
21
21
24
21
29
25
20
30
26
24
33
29
26
21
48
47
45
44
43
39
36
21
21
21
22
21
20
24
24
20
24
24
23
20
24
23
22
28
24
21
31
28
24
20
34
31
28
24
36
34
30
26
51
49
47
46
45
43
38
24
22
20
23
22
20
24
25
21
29
28
22
28
26
25
21
28
28
25
20
29
25
23
33
30
28
21
37
34
30
28
39
36
34
29
23
54
51
49
48
47
45
40
3.0"
w.g.
(750 Pa)
28
22
23
20
28
25
22
29
29
25
20
34
32
24
30
31
31
25
33
32
26
22
32
31
28
22
37
35
31
24
40
37
34
28
43
40
36
31
21
57
55
53
52
50
47
44
Performance Notes:
1. NC Levels are calculated based on procedures as outlined on
page B75.
2. Dash (-) in space indicates a NC less than 20.
B32
1-18-13
Airflow
Minimum Ps
2 3 4 5 6 7
- 44 33 21 26 31
- - 27 14 17 23
- - - - - - - - - - - - - - - - 43 32 24 20 25
- 40 28 18 14 20
- 37 23 - - - - - - - - - - - - - 45 38 37 28 23
- 42 37 34 23 19
- - 31 24 - - - - - - - - - - - 58 49 41 35 32 34
56 46 36 31 27 27
- 37 24 - - - 36 - - - - 37 - - - - 49 40 38 35 31
- 47 37 35 30 27
- 43 34 31 25 22
- - 24 16 - - - - - - 61 47 39 39 37 35
59 44 36 36 32 29
52 38 31 28 20 17
- - - - - - - - - - 66 51 41 44 45 39
60 46 38 41 38 31
- - 34 34 26 20
- - 27 21 - - - - - - 64 53 48 48 51 46
61 49 43 45 44 38
56 44 40 39 34 28
- - 33 28 19 - - - - - 66 56 52 53 53 50
60 50 46 48 46 41
- 41 39 41 35 28
- - 32 29 17 - - - - - 68 57 54 54 56 53
61 50 47 48 49 44
54 42 41 42 39 32
- - 34 30 21 - - - - - 75 65 64 62 63 61
71 59 61 59 58 56
69 59 59 57 56 52
66 55 54 53 51 46
64 54 54 52 50 45
59 49 47 47 42 37
54 43 42 40 34 27
3.0" w.g.(750Pa)Ps
2 3 4 5 6 7
67 58 48 36 35 43
62 53 44 36 35 42
- 44 39 30 34 41
- 40 35 27 30 39
- - 30 18 21 32
70 60 48 37 35 42
68 57 46 34 33 41
66 54 44 33 31 39
60 47 39 33 34 39
58 43 36 29 35 41
73 65 53 44 42 42
72 63 51 42 39 40
69 59 47 37 32 37
64 53 43 33 26 33
62 44 35 31 33 38
77 68 58 43 49 52
75 66 56 41 47 51
68 59 50 36 43 47
63 53 45 33 39 45
- 40 30 22 38 46
79 70 57 45 48 50
77 68 55 43 46 48
75 67 54 40 44 46
68 60 48 35 39 42
- 46 36 25 34 40
79 69 57 47 53 54
77 67 55 45 51 52
74 63 51 41 47 49
69 57 46 37 44 46
59 47 36 30 40 46
79 68 57 50 54 55
77 66 55 47 51 51
74 63 52 44 47 47
69 58 47 39 42 43
60 49 40 32 39 42
81 71 63 58 60 62
78 69 59 54 57 57
74 65 55 49 51 51
69 59 50 45 46 47
60 51 44 40 44 46
80 70 66 64 62 62
77 68 64 62 59 58
75 65 60 58 55 54
70 60 57 53 51 50
59 50 49 48 47 49
81 73 68 64 63 64
79 71 66 61 60 61
75 67 62 57 57 56
70 62 58 53 52 52
60 54 51 48 48 50
89 80 78 74 76 73
87 79 77 74 74 71
84 79 76 71 72 71
81 76 72 69 68 69
79 75 72 68 67 68
77 73 70 67 66 66
74 69 68 65 64 64
For full performance table notes, see page B35; RED highlighted numbers indicate embedded AHRI certification points.
1-18-13
B33
Min. inlet
Ps
"w.g. Pa
0.30 75
0.18 45
0.08 20
0.05 12
0.02 5
0.16 40
0.11 27
0.08 20
0.03 7
0.02 5
0.10 25
0.08 22
0.06 15
0.03 7
0.01 2
0.08 20
0.06 15
0.03 7
0.02 5
0.01 2
0.10 25
0.08 20
0.06 15
0.03 7
0.01 2
0.09 22
0.07 17
0.04 10
0.02 5
0.01 2
0.19 47
0.14 35
0.08 20
0.04 10
0.01 2
0.22 55
0.14 35
0.07 17
0.03 7
0.01 2
0.28 70
0.18 45
0.10 25
0.05 12
0.01 2
0.46 114
0.30 75
0.17 42
0.07 17
0.02 5
0.43 107
0.33 82
0.24 60
0.20 50
0.17 42
0.11 27
0.06 15
Inlet Airflow
Size cfm l/s
200 94
150 71
4 100 47
75 35
50 24
300 142
250 118
5 200 94
125 59
100 47
450 212
400 189
6 300 142
200 94
100 47
650 307
550 260
7 335 158
225 106
110 52
800 378
700 330
8 600 283
400 189
175 83
1050 495
900 425
9 675 319
450 212
225 106
1350 637
1100 519
10 825 389
550 260
275 130
2000 944
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1550 731
1050 495
525 248
3500 1652
2800 1321
16 2100 991
1400 661
700 330
8000 3775
7000 3303
24
6000 2831
x
5350 2525
16
5000 2360
4000 1888
3000 1416
Min. inlet
Ps
"w.g. Pa
0.30 75
0.18 45
0.08 20
0.05 12
0.02 5
0.16 40
0.11 27
0.08 20
0.03 7
0.02 5
0.10 25
0.09 22
0.06 15
0.03 7
0.01 2
0.08 20
0.06 15
0.03 7
0.02 5
0.01 2
0.10 25
0.08 20
0.06 15
0.03 7
0.01 2
0.09 22
0.07 17
0.04 10
0.02 5
0.01 2
0.19 47
0.14 35
0.08 20
0.04 10
0.01 2
0.22 55
0.14 35
0.07 17
0.03 7
0.01 2
0.28 70
0.18 45
0.10 25
0.05 12
0.01 2
0.46 114
0.30 75
0.17 42
0.07 17
0.02 5
0.43 107
0.33 82
0.24 60
0.20 50
0.17 42
0.11 27
0.06 15
MinimumPs
2 3 4 5 6 7
- 36 33 32 - - 35 29 31 - - - - - - - - - - - - - - - - 47 38 32 32 30 27
- 35 31 25 23 - - - - - - - - - - - - - - - 48 44 37 35 30 28
- 42 33 33 28 26
- 34 27 26 - - - - - - - - - - - 48 45 46 38 31 30
49 43 41 33 27 25
- - 28 33 - - - - - - - - - - - 51 46 40 33 31 28
50 43 37 31 29 25
- 39 33 29 26 - 35 26 - - - - - - - 50 44 44 41 34 32
48 40 39 36 30 29
47 37 31 29 22 - - 24 - - - - - - - 53 42 41 36 30 23
51 37 35 30 25 - 33 29 25 - - - - - - - - - - - 54 50 49 44 37 33
52 45 41 36 30 27
47 39 33 29 24 - - - - - - - - - - 57 54 50 46 42 36
54 48 44 39 35 30
46 40 35 30 28 - 32 24 - - - - - - - 57 57 53 49 43 36
54 51 49 43 37 32
49 44 41 34 28 - 34 31 - - - - - - - 71 67 66 61 58 53
67 64 65 59 57 53
64 60 61 55 53 51
63 57 57 52 52 47
62 56 56 51 51 46
61 52 50 46 43 40
56 48 46 43 39 37
For full performance table notes, see page B35; RED highlighted numbers indicate embedded AHRI certification points.
B34
1-18-13
4
5
6
7
8
9
10
12
14
16
24 x 16
Airflow
Min. Inlet
Ps
cfm l/s
" w.g. Pa
0.23
0.08
0.09
0.05
0.09
0.12
0.16
0.20
0.19
0.30
0.01
63
68
70
76
77
77
76
76
75
74
86
56
60
63
65
66
64
62
63
64
64
78
150
250
400
550
700
900
1100
1600
2100
2800
5350
71
118
189
260
330
425
519
755
991
1321
2525
57
21
22
13
22
29
40
50
48
76
2
Octave Band
4
5
6
41
44
46
49
50
51
51
55
59
60
76
27
34
37
37
39
44
46
50
55
54
72
28
31
34
43
43
47
49
55
57
57
73
36
37
39
46
46
48
49
54
55
56
73
49
55
59
61
61
60
60
61
63
65
72
50
48
52
54
53
54
54
58
61
63
70
47
45
47
49
50
49
50
53
55
57
70
39
35
40
43
40
44
45
49
48
50
65
31
35
36
36
39
39
39
42
44
44
60
30
30
33
33
35
36
36
39
43
39
55
2-12-15
Octave Band
4
5
6
B35
3.
Unit casing shall be 22 ga. (.86) galvanized steel with round,
flat oval or rectangular inlets with 5 12" (140) deep inlet duct collar
for field connection. Outlets shall be rectangular and configured
for slip and drive connections. Casing leakage downstream of the
damper shall not exceed 1% @ 1" w.g. (250 Pa). High side casing
leakage shall not exceed 2% @ 3" w.g. (746 Pa).
4.
Damper assemblies of 16 ga. (1.63) galvanized steel shall
be multiple opposed blade construction arranged to close at 45
degrees from full open to minimize air turbulence and provide near
linear operation. Damper blades shall be fitted with flexible seals
for tight closure and minimized sound generation. Damper blades
shall be screwed through the shaft to insure that no slippage
occurs. Blade shafts shall pivot in corrosion free self-lubricating
bronze oilite bearings. In the fully closed position, air leakage past
the closed damper shall not exceed 2% of the nominal catalog
rating at 3" w.g. (746 Pa) inlet static pressure as rated by ASHRAE
Standard 130.
5.
The terminal units shall be capable of operation as described
herein with a minimum inlet static pressure that shall not exceed
0.30" w.g. (75 Pa) @ 2000 fpm (10.2 m/s) inlet velocity. (The
sequence of operations should be described here, if not part of the
temperature controls specifications.) Each unit shall be complete
with factory mounted (pneumatic, electric, analog electronic, or
DDC) controls. Gauge tap ports shall be supplied in the piping
between the flow pick up and the controller.
OPTIONS
Electric Heat:
Model: 30REQ
Staged
(Substitute the following paragraphs:)
1.
Furnish and install Nailor Model 30REQ Single Duct
Variable Volume Quiet Terminal Units of the sizes and
capabilities as indicated on the drawings. Unit shall be pressure
independent with (pneumatic, analog electronic, DDC) controls.
Unit shall reset to any flow between minimum and the maximum
cataloged airflow as allowed by the specific controller.
10. Single Duct VAV Quiet Terminal Unit Staged Electric
Heating Coils:
a. Electric heating coils shall consist of open coils of high grade
nickel and chromium resistance wire or nichrome elements and
insulated with ceramic insulators in galvanized steel brackets,
supported in heavy gauge galvanized steel frames. Each unit
employing an electric heating coil shall be constructed and
installed in accordance with the requirements of the local
authorities and shall be UL or ETL listed specifically with the
heater as a component of the terminal unit device.
b. Coils shall have the capacities indicated in Contract
Documents. Coils rated up through 16.5 kW shall be single
phase, 347 volt, 60 hertz and coils larger than 16.5 kW shall be
three phase, four wire, 208, 480 or 600 volt, 60 hertz. Coils shall be
available in one, two or three stages.
c. Terminal bolts, nuts and washers shall be of corrosion resistant
materials. Coils shall be constructed so the installation may be
accomplished in accordance with the provisions of the National
Electrical Code, for zero clearance. Coils shall be given a 2000
volt dielectric test at the factory.
d. Automatic reset thermal cutouts shall be furnished for primary
protection with manually resettable limit switches in power circuits for
secondary protection. Both devices shall be serviceable through
terminal box without removing heating element from the terminal
device. The air pressure safety cutout pickup probe shall be remotely
mounted near the volume control damper for maximum fidelity.
6.
Each unit shall be constructed with single point electrical
(and pneumatic) connections. All electrical components shall be
ETL or UL listed or recognized and installed in accordance with
the National Electrical Code. All electrical components shall be
installed in a control box. The entire assembly shall be ETL listed
and so labeled.
e. Heating coils shall have a terminal box and cover, with quiet
type built-in magnetic step controlled contactors for each circuit,
branch circuit fusing for each branch circuit on heaters over 48
amps per the NEC and an air flow safety interlock switch for
installation in the heater control enclosure. Provide a 120 or 24
VAC control power transformer with an integral or separately
mounted primary and/or secondary overcurrent protection device
in accordance with NEC requirements.
7.
Each VAV section unit shall be internally lined with 34" (19)
dual density fiberglass insulation. Edges shall be sealed against
airflow erosion. Units shall meet NFPA 90A and UL 181 standards.
8.
All sound data shall be compiled in an independent
laboratory and in accordance with the latest version of AHRI
Standard 880 and ANSI/ASHRAE Standard 130.
9.
Dissipative silencers shall contain a unit casing constructed
of 22 ga. (.86) galvanized steel. Inlet and discharge shall be
rectangular and configured for slip and drive connections. Each
silencer shall be lined with fiberglass insulation, placed inside the
top and bottom sides of the silencer, thereby eliminating the
requirement for field wrapping with thermal insulation. The
silencer baffles shall be filled with fiberglass absorption media and
encapsulated by 22 ga. (.86) perforated coated steel baffles. The
perforated metal baffles shall be rigidly fastened to the casing of
the silencer. Units shall meet NFPA 90A and UL 181 standards.
B36
5-1-11
e. Heating coils shall have a terminal box and cover, with quiet
type built-in magnetic step controlled contactors for each circuit,
branch circuit fusing for each branch circuit on heaters over 45
amps per the NEC and an air flow safety interlock switch for
installation in the heater control enclosure. Provide a 120 or 24
VAC control power transformer with an integral or separately
mounted primary and/or secondary overcurrent protection device
in accordance with NEC requirements.
1.
Furnish and install Nailor Model 30REQ Single Duct
Variable Volume Quiet Terminal Units of the sizes and
capabilities as indicated on the drawings. Unit shall be pressure
independent with (pneumatic, analog electronic, DDC) controls.
Unit shall reset to any flow between minimum and the maximum
cataloged airflow as al
the electric heater shall be ETL listed for zero clearance and so
labeled and shall meet all requirements of the latest National
Electrical Code, (CSA C22.2 No.236). The unit shall have a single
point electrical and/or pneumatic connection (dual point electrical on
600V). Heater casing and panel shall be a minimum of 20 ga. (1.00)
galvanized steel. Each heater shall be complete with automatic
reset high limit thermal cut-outs, control voltage transformer as
required, ground terminal, fan relay for interlocking the heater and
fan and high grade nickel chrome alloy wire.
Element wires shall be supported by ceramic isolators. Each heater
shall be supplied with factory supplied and pre-wired branch circuit
fusing as required by NEC and UL. Circuiting and fusing shall also be
in accordance with the circuiting requirements as shown on the plans.
Additional accessories shall include (control transformer, circuit
fusing, disconnect switch, pneumatic electric switches) for heater
control.
Heater shall be capable of providing proportional control of heater
capacity from an input signal of 420 mA, 210 VDC or 0 10 VDC.
The SCR controller shall provide a 1 24 VDC pulsed output to
SSR(s) [solid state relay(s)] in proportion to zone heating demand.
The SSRs shall switch with zero cross over to reduce system
noise and thermal shock on heater coils.
11-10-11
B37
B38
11-14-11
Model: 30RWQ
(Substitute the following paragraphs:)
Liner:
Steri-Liner
(Substitute the following paragraph:)
3.
Unit casings shall be 20 ga. (1.00) galvanized steel. Unit
shall be fully lined with non-porous, sealed liner which complies
with NFPA 90A and UL 181. Installation shall be 1/2" (13) minimum
thickness, 4 lb./cu. ft. (64 kg/m3) density with reinforced aluminum
foil-scrim-kraft (FSK) facing. All cut edges shall be secured with
steel angles or end caps to encapsulate edges and prevent
erosion. Insulation shall be Nailor Steri-Liner or equal.
Fiber-Free Liner
(Substitute the following paragraph:)
3.
Unit casings shall be 20 ga. (1.00) galvanized steel. Unit
shall be fully lined with a non-porous closed cell elastomeric foam
liner which complies with NFPA 90A, ASTM E84 and UL 181.
Installation shall be 3/8" (10) minimum thickness and secured to
the interior of the terminal with mechanical fasteners. No
fiberglass is permitted. Insulation shall be Nailor Fiber-Free Liner
or equal.
12-21-11
B39
Models:
30HQ Cooling or Heating
only
30HQW Cooling with Hot
Water Reheat
30HQE Cooling with
Electric Reheat
Model 30HQ
Hospital system designs have to contend with the presence of infectious diseases, chemical hazards, biological
contaminants and low sound level requirements. The 30HQ hospital grade terminal unit has been purposely designed to
address these parameters by using innovative options and construction methods, resulting in simplified maintenance and
improved sound performance.
Each unit includes a factory mounted dissipative silencer that maximizes acoustical attenuation, minimizes pressure loss
and reduces self-generated sound. Acoustic insulation in the silencer is wrapped in mylar, which acts to isolate the media
from the airstream. Mylar also works as a vapor barrier preventing mold and bacterial growth in the acoustic media. FSK
(Foil-Scrim-Kraft) faced Steri-Liner is the only liner available on the 30HQ series. This insulation offers a durable, cleanable
surface throughout the VAV section and exposed silencer portions. By fully lining the silencer, there is no need to field apply
external thermal duct wrap. Optional components such as access doors and removable flow sensors enhance the
functionality of the 30HQ Series units to provide optimum performance and flexibility in hospital environments.
STANDARD FEATURES:
Designed for hospital and other
critical environment applications
where IAQ (Indoor Air Quality) is a
concern.
22 ga. (0.86) galvanized steel
casing, mechanically sealed, low
leakage construction.
16 ga. (1.63) corrosion-resistant
steel inclined opposed blade damper
with extruded PVC seals (single blade
on size 4, 5, 6). 45 rotation, CW to
close. Tight close-off. Damper
leakage is less than 2% of the
terminal rated airflow at 3" w.g. (746
Pa)
1/2" (13) dia. plated steel drive
shaft. An indicator mark on the end of
the shaft shows damper position.
Multi-point averaging Diamond
Flow Sensor. Aluminum construction.
Supplied with balancing tees.
Rectangular discharge with slip and
drive cleat duct connection.
Full NEMA 1 type controls
enclosure for factory mounted
controls.
B40
5-1-11
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
UNIVERSAL PNEUMATIC
CONTROL MOUNTING
PANEL AND
PROTECTIVE SHROUD
RECTANGULAR DISSIPATIVE
MYLAR LINED SILENCER
DAMPER
DRIVESHAFT
AIRFLOW
H
6 1/2"
(165)
6"
(152)
W
1/2"
(13)
OPTIONAL
FMI
5 1/2"
REMOVABLE (140)
FLOW SENSOR
14 1/2" (368)
15 1/2" (394)
36" (914)
6"
(152)
W
1/2"
(13)
51 1/2" (1308)
CONTROLS ENCLOSURE
FOR FACTORY MOUNTED
CONTROLS
11"
(279)
RECTANGULAR DISSIPATIVE
MYLAR LINED SILENCER
AIRFLOW
H
DAMPER
DRIVESHAFT
OPTIONAL
5 1/2"
FMI
(140)
REMOVABLE
FLOW SENSOR
6"
(152)
W
1/2"
(13)
14" (356)
36" (914)
15 1/2" (394)
51 1/2" (1308)
6"
(152)
W
1/2"
(13)
OPTIONAL
ACCESS DOOR
Dimensional Data
Unit
Size
Inlet Size
4
5
6
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
3 78 (98) Round
4 78 (124) Round
5 78 (149) Round
7
8
9
12 (305) 12 12 (318)
12 (305) 12 12 (318)
14 (356) 12 12 (318)
10
12
14
14 (356) 12 12 (318)
9 78 (251) Round
1
15
18 (457) 12 2 (318) 12 16 x 9 1316 (329 x 249) Oval
24 (610) 12 12 (318) 16 116 x 9 1316 (408 x 249) Oval
16
28 (711) 12 12 (318)
24 x 16 38 (965) 18 (457)
6 78 (175) Round
7 78 (200) Round
8 78 (225) Round
11-14-11
B41
MULTI-POINT
AVERAGING
FLOW SENSOR
14" (356)
AIRFLOW
11"
(279)
DAMPER
DRIVESHAFT
1/2"
(13)
6"
(152)
5 1/2"
OPTIONAL
(140)
FMI
REMOVABLE
FLOW SENSOR
15 1/2" (394)
48" (1219)
L
63 1/2" (1613)
6"
(152)
OPTIONAL
ACCESS DOOR
CONTROLS ENCLOSURE
FOR FACTORY
MOUNTED
CONTROLS
AIRFLOW
11 3/4"
(298)
1/2"
(13)
6"
(152)
RECTANGULAR DISSIPATIVE
MYLAR LINED SILENCER
29" (737)
PRIMARY
AIR
VALVE
CONTROLS
ENCLOSURE
OPTIONAL
5 1/2"
FMI
REMOVABLE (140)
FLOW SENSOR
ELECTRIC COIL
CONTROLS
ENCLOSURE
(HINGED
ACCESS DOOR)
48" (1219)
31" (787)
79" (2007)
OPTIONAL
ACCESS DOOR
Dimensional Data
W
Inlet Size
4
5
6
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
3 8 (98) Round
4 78 (124) Round
5 78 (149) Round
5 (127)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
7 12 (191)
7
8
9
12 (305) 12 12 (318)
12 (305) 12 12 (318)
14 (356) 12 12 (318)
6 78 (175) Round
7 78 (200) Round
8 78 (225) Round
5 (127)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
7 12 (191)
10
12
14
14 (356) 12 12 (318)
9 78 (251) Round
1
15
18 (457) 12 2 (318) 12 16 x 9 1316 (329 x 249) Oval
24 (610) 12 12 (318) 16 116 x 9 1316 (408 x 249) Oval
5 (127)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
7 12 (191)
5 (127)
5 (127)
7 12 (191)
7 12 (191)
16
28 (711) 12 12 (318)
24 x 16 38 (965) 18 (457)
B42
Unit
Size
11-15-11
6"
(152)
1/2"
(13)
Unit
Size
Inlet
Type
4
5
Round
6
7
8
Round
9
10
12
14
Flat Oval
16
24 x 16 Rect.
Total
Airflow
Range,
cfm
Airflow at
2000 fpm
Inlet
Velocity
(nom.), cfm
0 225
0 400
0 550
0 800
0 1100
0 1400
0 1840
0 2500
0 3125
0 3725
0 8330
150
400
500
800
1100
1285
1655
2450
3125
3725
8330
1.5
225
400
550
800
1100
1400
1840
2500
3125
3725
8330
374
106
189
260
378
519
661
868
1180
1475
1758
3931
Unit
Size
Inlet
Type
4
5
Round
6
7
8
Round
9
10
12
14
Flat Oval
16
24 x 16 Rect.
Total
Airflow
Range,
l/s
Airflow at
10.2 m/s
Inlet
Velocity
(nom.), l/s
0 106
0 189
0 260
0 378
0 519
0 661
0 868
0 1180
0 1475
0 1758
0 3931
71
189
260
378
519
661
868
1180
1475
1758
3831
3-31-14
B43
Model 30HQ
10
12
14
16
24
x
16
Airflow
cfm
200
150
100
75
50
300
250
200
125
100
450
400
300
200
100
650
550
335
225
110
800
700
600
400
175
1050
900
675
450
225
1350
1100
825
550
275
2000
1600
1200
800
400
2700
2100
1550
1050
525
3500
2800
2100
1400
700
8000
7000
6000
5350
5000
4000
3000
Min. inlet
Ps
Min.
0.5"
w.g.
Ps
Ps
(125 Pa)
(250 Pa)
(375 Pa)
(500 Pa)
(750 Pa)
Ps
82
45
20
10
5
32
22
15
7
5
67
55
35
17
5
25
17
7
4
2
17
15
10
5
2
20
15
10
5
2
37
25
15
7
2
47
30
17
7
2
65
37
20
7
2
107
70
40
17
5
99
77
57
45
40
25
15
23
-
21
23
21
30
29
27
27
23
-
20
20
23
25
22
25
20
22
30
28
30
28
24
23
21
20
24
20
23
20
22
23
20
20
22
24
22
30
26
30
24
25
32
29
30
28
26
24
23
22
24
27
25
25
22
22
20
25
24
23
25
23
22
26
23
30
25
30
26
25
35
34
33
30
29
27
26
23
20
27
24
28
29
23
25
27
24
29
28
24
29
27
23
30
28
20
31
27
21
33
30
29
20
38
37
34
32
30
29
27
20
23
24
28
23
41
40
36
34
31
24
20
20
20
25
20
26
21
30
24
44
41
39
38
37
35
31
21
20
22
21
21
24
21
29
25
20
30
26
24
33
29
26
21
48
47
45
44
43
39
36
2.0"
w.g.
3.0"
w.g.
(375 Pa)
(500 Pa)
(750 Pa)
21
21
21
22
21
20
24
24
20
24
24
23
20
24
23
23
28
24
21
31
28
24
20
34
31
28
24
36
34
30
26
51
49
47
46
45
43
38
24
22
20
23
22
20
24
25
21
29
28
22
28
26
25
21
28
28
25
20
29
25
23
33
30
28
21
37
34
30
28
39
36
34
29
23
54
51
49
48
47
45
40
28
22
23
20
28
25
22
29
29
25
20
34
32
24
30
31
31
25
33
32
26
22
32
31
28
22
37
35
31
24
40
37
34
28
43
40
36
31
21
57
55
53
52
50
47
44
Performance Notes:
1. NC Levels are calculated based on procedures as outlined on
page B75.
2. Dash (-) in space indicates a NC less than 20.
B44
1-18-13
Inlet
10
12
14
16
24
x
16
200 94
150 71
100 47
75 35
50 24
300 142
250 118
200 94
125 59
100 47
450 212
400 189
300 142
200 94
100 47
650 307
550 260
335 158
225 106
110 52
800 378
700 330
600 283
400 189
175 83
1050 495
900 425
675 319
450 212
225 106
1350 637
1100 519
825 389
550 260
275 130
2000 944
1600 755
1200 566
800 378
400 189
2700 1274
2100 991
1550 731
1050 495
525 248
3500 1652
2800 1321
2100 991
1400 661
700 330
8000 3775
7000 3303
6000 2831
5350 2525
5000 2360
4000 1888
3000 1416
0.33
0.18
0.08
0.04
0.02
0.13
0.09
0.06
0.03
0.02
0.27
0.22
0.14
0.07
0.02
0.10
0.07
0.03
0.02
0.01
0.07
0.06
0.04
0.02
0.01
0.08
0.06
0.04
0.02
0.01
0.15
0.10
0.06
0.03
0.01
0.19
0.12
0.07
0.03
0.01
0.26
0.15
0.08
0.03
0.01
0.43
0.28
0.16
0.07
0.02
0.40
0.31
0.23
0.18
0.16
0.10
0.06
82
45
20
10
5
32
22
15
7
5
67
55
35
17
5
25
17
7
4
2
17
15
10
5
2
20
15
10
5
2
37
25
15
7
2
47
30
17
7
2
65
37
20
7
2
107
70
40
17
5
99
77
57
45
40
25
15
55
58
56
52
51
53
54
52
49
49
45
50
44
56
42
36
49
57
57
51
57
52
52
71
67
65
64
61
59
56
41
44
54
42
44
44
41
35
53
49
36
51
50
47
36
46
43
35
48
44
39
52
37
33
29
52
51
38
29
51
46
45
27
63
56
56
52
47
48
46
41
37
38
32
44
39
44
33
30
39
36
30
19
52
46
31
31
46
44
38
28
43
37
29
16
48
42
37
25
46
40
34
28
53
48
40
28
50
41
44
30
25
59
56
53
49
45
45
44
29
24
37
28
35
29
24
30
25
38
35
27
32
47
42
26
26
44
40
34
22
40
34
24
30
45
40
34
17
44
39
33
20
25
53
46
39
24
48
44
43
23
23
54
51
49
44
38
39
39
48 24
39 35
27 - - 27 28
42 40
34 32
- - 35 31
30 25
35 31
- - 31 37
24 31
29 22
- - 34 32
30 27
21 18
29 - 35 35
26 25
39 30
- - 47 46
39 37
28 24
- - 48 49
40 36
27 25
28 20
- 54 52
47 44
36 31
27 - 51 52
46 45
45 45
17 - 56 54
51 49
48 45
41 42
34 39
41 38
40 37
53
53
54
53
51
48
58
59
56
52
57
55
52
50
63
60
58
50
59
57
54
61
58
54
52
64
56
50
52
52
65
62
58
53
48
61
62
61
52
54
77
76
74
74
71
68
65
53
50
50
48
46
55
53
48
43
42
53
52
50
44
42
58
55
48
44
41
61
57
55
48
39
60
57
53
49
37
59
57
53
46
40
61
54
48
48
43
59
55
49
44
37
57
55
54
52
38
68
68
66
65
64
62
61
48
48
48
46
40
52
48
44
38
36
48
47
43
36
29
54
49
44
40
35
53
50
48
40
29
53
49
44
37
26
53
49
43
38
30
53
48
40
39
34
57
51
44
39
32
56
53
53
42
34
65
63
63
62
61
59
57
35
32
29
26
28
41
37
32
26
23
42
41
34
26
39
49
39
33
30
22
45
41
40
30
17
46
42
37
28
14
48
44
37
28
18
49
46
37
36
26
57
50
42
35
28
56
53
51
39
30
59
59
58
57
57
55
53
49
44
41
37
40
29
22
42
36
33
40
36
24
38
33
34
28
45
41
34
40
35
32
42
37
45
39
31
24
38
51
44
36
24
38
54
50
37
35
24
59
52
43
35
25
56
54
51
38
27
63
61
60
58
56
54
53
24
21
35
31
31
30
24
37
31
30
36
32
20
34
31
41
37
29
25
21
42
39
40
29
19
44
39
33
30
18
51
42
33
28
20
57
49
36
33
26
59
50
41
34
28
57
53
52
40
31
63
60
59
58
57
55
54
56
55
56
43
53
51
56
64
63
60
56
60
59
57
53
65
62
62
57
63
62
59
53
48
64
61
61
56
46
65
61
58
59
57
69
67
63
59
50
70
66
68
58
48
75
75
77
75
72
70
66
47
53
48
44
38
59
56
53
48
46
57
57
53
48
44
59
57
55
52
46
61
59
57
52
46
63
60
58
54
47
63
60
57
53
45
63
59
54
54
49
63
59
54
50
42
64
61
61
52
44
69
68
70
68
66
65
63
54
49
47
47
44
55
51
47
44
45
52
51
47
41
40
56
53
49
46
39
54
51
50
44
38
56
53
49
46
40
56
52
49
43
37
56
52
45
44
43
60
55
50
45
39
61
57
57
46
41
69
68
67
66
64
63
62
40
36
34
37
35
43
40
36
33
36
44
42
37
31
27
46
43
37
33
26
46
43
42
33
25
47
45
40
33
27
50
45
41
35
27
52
47
40
38
35
57
52
46
42
34
59
54
54
43
36
68
68
64
62
61
59
59
22
50
47
49
55
31
27
47
43
46
49
45
27
45
55
34
27
53
49
45
41
36
32
20
44
46
42
35
26
22
52
46
39
29
35
57
51
41
39
33
60
54
47
41
33
60
56
56
44
37
70
68
65
64
62
61
60
30
29
27
26
27
33
32
28
24
25
37
34
27
23
27
44
40
35
32
29
47
44
41
33
27
49
45
40
36
33
53
47
42
36
31
59
52
43
41
35
61
58
51
44
36
61
56
58
45
40
66
64
63
62
60
58
57
57
54
56
57
60
52
56
67
70
63
58
65
68
59
55
67
68
64
61
51
65
65
64
57
49
66
66
64
59
48
68
67
61
61
51
72
71
66
59
51
73
69
71
61
50
78
76
76
75
71
69
67
59
56
49
40
35
59
59
55
49
46
59
60
56
51
46
62
64
59
55
48
63
62
60
57
49
65
63
62
56
48
64
62
61
56
45
65
64
58
57
46
65
62
58
53
41
67
64
65
55
46
69
70
71
69
67
66
64
54
52
51
47
46
57
53
50
49
48
55
54
48
45
44
59
57
52
49
45
55
54
52
47
43
57
55
52
47
43
58
55
51
47
40
59
57
48
48
42
63
59
54
49
43
63
61
60
51
45
69
69
68
66
65
65
63
42
39
41
39
37
46
44
39
41
45
46
45
39
33
31
49
46
40
36
31
47
45
43
37
31
49
46
42
35
31
50
48
43
37
28
54
52
42
41
36
58
55
50
44
38
61
56
56
46
40
68
68
65
64
62
60
61
25
22
53
56
60
34
29
21
51
25
41
39
29
49
53
34
30
23
52
49
40
36
32
23
49
47
43
37
27
27
53
48
41
33
31
57
55
44
43
39
66
56
50
43
39
62
58
58
46
43
71
69
67
65
63
62
62
35
33
31
30
33
37
35
33
31
34
40
37
32
29
30
47
44
40
37
31
47
45
42
38
32
51
48
46
41
37
55
50
45
42
38
60
57
47
46
41
66
62
54
46
42
66
60
61
47
47
66
64
66
64
62
60
59
58
53
55
59
60
52
45
70
72
64
57
68
69
60
57
68
68
66
62
51
68
72
65
57
54
73
67
65
60
49
69
67
62
61
50
74
71
67
61
49
74
71
72
62
52
81
80
77
76
73
71
69
60
56
48
40
43
63
59
57
49
45
64
62
57
53
47
66
66
61
55
49
64
63
62
59
50
67
66
64
56
48
66
65
64
57
44
66
65
61
58
46
66
64
60
54
41
70
66
67
57
48
73
72
73
71
69
67
65
57
55
52
47
45
58
54
52
50
48
60
56
51
47
47
62
59
56
52
42
57
56
55
50
46
59
58
54
49
44
60
57
53
50
41
60
57
51
50
42
64
60
56
52
44
65
63
63
54
48
72
72
70
69
68
66
65
44
43
44
40
34
47
43
43
47
47
53
47
41
35
37
51
48
42
40
31
48
46
45
39
43
50
47
43
37
33
52
50
44
38
31
55
52
44
44
38
60
56
51
46
41
61
57
57
49
43
71
70
68
67
65
63
64
27
24
26
28
60
36
30
24
27
32
46
39
30
23
58
35
31
24
55
51
39
36
32
24
20
48
44
38
32
30
53
49
42
35
33
58
55
46
46
43
62
56
51
45
42
63
60
55
50
47
74
71
70
68
66
65
64
37
35
35
36
36
40
37
36
37
39
44
39
34
32
32
48
47
43
41
35
48
47
44
40
38
53
50
47
43
41
57
53
47
43
44
62
57
50
47
46
67
61
54
48
47
67
62
58
50
50
70
67
68
67
65
63
62
56
52
43
59
56
54
43
72
70
66
58
70
71
64
59
71
72
68
63
51
71
70
64
57
49
70
69
68
60
51
73
69
65
62
50
76
73
68
61
51
77
74
73
64
57
83
82
78
77
74
72
70
60
56
45
42
43
64
61
58
47
42
65
64
60
54
46
68
69
64
59
51
67
67
65
61
48
70
69
65
58
46
70
68
65
57
44
71
69
63
60
44
70
67
62
56
41
72
71
70
60
49
75
74
74
72
70
68
67
59
57
50
47
43
60
57
55
50
47
61
58
55
51
47
63
64
59
53
50
60
59
58
54
46
63
61
57
53
45
63
59
57
53
43
64
61
56
53
42
67
64
61
55
45
68
66
65
58
51
75
74
73
71
69
67
66
48
49
44
42
34
48
47
38
48
45
52
49
44
42
42
51
51
47
43
36
50
48
47
43
37
53
50
46
42
36
54
51
47
42
34
58
54
47
47
39
64
59
55
51
44
64
60
60
52
47
74
74
71
70
68
66
65
33 40
32 41
33 42
31 41
58 38
37 43
32 41
29 41
37 46
38 46
51 44
40 42
31 38
24 38
29 38
34 50
35 50
29 47
25 46
24 45
40 51
37 49
33 48
28 44
24 44
49 57
45 54
40 51
36 49
33 46
55 59
50 55
45 51
37 48
36 49
60 65
57 61
51 53
50 52
48 54
63 68
58 63
54 57
49 52
46 51
65 70
62 65
61 61
54 56
50 54
76 72
74 70
72 70
70 69
68 67
66 65
65 63
For performance table notes, see page B47; RED highlighted numbers indicate embedded AHRI certification points.
1-18-13
B45
Airflow
10
12
14
16
24
x
16
Min. inlet
Ps
cfm l/s "w.g. Pa
200 94 .33 82
150 71 .18 45
100 47 .08 20
75 35 .04 10
50 24 .02 5
300 142 .13 32
250 118 .09 22
200 94 .06 15
125 59 .03 7
100 47 .02 5
450 212 .27 67
400 189 .22 55
300 142 .14 35
200 94 .07 17
100 47 .02 5
650 307 .10 25
550 260 .07 17
335 158 .03 7
225 106 .02 4
110 52 .01 2
800 378 .07 17
700 330 .06 15
600 283 .04 10
400 189 .02 5
175 83 .01 2
1050 495 .08 20
900 425 .06 15
675 319 .04 10
450 212 .02 5
225 106 .01 2
1350 637 .15 37
1100 519 .10 25
825 389 .06 15
550 260 .03 7
275 130 .01 2
2000 944 .19 47
1600 755 .12 30
1200 566 .07 17
800 378 .03 7
400 189 .01 2
2700 1274 .26 65
2100 991 .15 37
1550 731 .08 20
1050 495 .03 7
525 248 .01 2
3500 1652 .43 107
2800 1321 .28 70
2100 991 .16 40
1400 661 .07 17
700 330 .02 5
8000 3775 .40 99
7000 3303 .31 77
6000 2831 .23 57
5350 2525 .18 45
5000 2360 .16 40
4000 1888 .10 25
3000 1416 .06 15
Airflow
MinimumPs
2 3 4 5 6 7
- 36 33 32 - - 35 29 31 - - - - - - - - - - - - - - - - 47 38 32 32 30 27
- 35 31 25 23 - - - - - - - - - - - - - - - 48 44 37 35 30 28
- 42 33 33 28 26
- 34 27 26 - - - - - - - - - - - 48 45 46 38 31 30
49 43 41 33 27 25
- - 28 33 - - - - - - - - - - - 51 46 40 33 31 28
50 43 37 31 29 25
- 39 33 29 26 - 35 26 - - - - - - - 50 44 44 41 34 32
48 40 39 36 30 29
47 37 31 29 22 - - 24 - - - - - - - 53 42 41 36 30 23
51 37 35 30 25 - 33 29 25 - - - - - - - - - - - 54 50 49 44 37 33
52 45 41 36 30 27
47 39 33 29 24 - - - - - - - - - - 57 54 50 46 42 36
54 48 44 39 35 30
46 40 35 30 28 - 32 24 - - - - - - - 57 57 53 49 43 36
54 51 49 43 37 32
49 44 41 34 28 - 34 31 - - - - - - - 71 67 66 61 58 53
67 64 65 59 57 53
64 60 61 55 53 51
63 58 59 53 52 49
62 56 56 51 51 46
61 52 50 46 43 40
56 48 46 43 39 37
3.0" w.g.(750Pa)Ps
2 3 4 5 6 7
54 55 53 47 37 37
48 48 48 50 40 37
- 42 44 51 43 38
- 36 41 48 44 40
- 32 36 37 35 37
59 55 53 43 43 39
57 53 51 42 41 35
53 48 48 44 41 34
49 42 44 47 46 37
47 41 43 47 46 37
64 58 54 46 42 41
65 58 54 45 42 41
60 55 51 43 39 39
55 49 46 43 37 37
46 40 40 46 44 38
67 63 58 51 44 43
65 61 57 50 42 40
57 53 50 47 39 38
52 48 45 42 35 36
- 38 35 35 32 36
66 58 55 46 47 41
64 59 56 45 44 40
63 59 56 46 43 40
59 54 51 41 40 39
49 42 40 35 37 38
66 62 51 52 46 44
61 61 57 50 44 42
60 57 52 47 41 39
56 52 48 45 39 38
48 42 39 38 35 38
65 61 57 54 48 45
64 61 55 51 45 43
61 57 53 49 43 40
57 52 48 45 39 37
48 43 40 40 36 36
68 66 61 58 51 49
65 64 58 55 48 46
61 61 55 52 45 44
56 55 50 48 42 42
47 44 40 43 40 42
69 69 63 57 53 51
66 66 60 55 50 48
62 63 57 52 47 45
56 58 52 48 43 42
49 49 44 42 40 42
71 71 64 59 53 48
68 69 62 56 50 46
64 65 58 53 47 44
58 61 54 49 44 42
51 53 46 43 41 41
83 80 80 75 69 63
81 78 78 73 68 61
78 76 76 72 66 59
77 75 75 71 65 58
75 73 74 70 63 57
72 70 71 67 60 54
67 66 68 64 56 50
For performance table notes, see page B47; RED highlighted numbers indicate embedded AHRI certification points.
B46
1-18-13
4
5
6
7
8
9
10
12
14
16
24 x 16
Airflow
Min. Inlet
Ps
cfm l/s
" w.g. Pa
0.24
0.08
0.06
0.06
0.08
0.07
0.14
0.19
0.19
0.30
0.01
65
67
71
74
77
75
77
76
75
77
87
60
62
67
67
67
65
65
64
68
68
80
150
250
400
550
700
900
1100
1600
2100
2800
5350
71
118
189
260
330
425
519
755
991
1321
2525
60
20
15
16
21
17
34
48
46
75
2
Octave Band
4
5
6
55
53
58
59
58
57
57
58
64
63
77
48
49
51
48
48
48
50
52
57
55
72
29
30
37
36
39
44
49
54
57
58
74
37
38
41
45
47
48
50
55
55
58
75
49
55
59
61
61
60
60
61
63
65
72
50
48
52
54
53
54
54
58
61
63
70
47
45
47
49
50
49
50
53
55
57
70
39
35
40
43
40
44
45
49
48
50
65
31
35
36
36
39
39
39
42
44
44
60
30
30
33
33
35
36
36
39
43
39
55
2-12-15
Octave Band
4
5
6
B47
3.
Unit casing shall be 22 ga. (0.86) galvanized steel with round
or flat oval inlets with 5 12" (140) deep inlet duct collar for field
connection. Outlets shall be rectangular and configured for slip
and drive connections. Casing leakage downstream of the damper
shall not exceed 1% @ 1" w.g. (250 Pa). High side casing leakage
shall not exceed 2% @ 3" w.g. (746 Pa).
4.
Damper assemblies of 16 ga. (1.63) galvanized steel shall
be multiple opposed blade construction arranged to close at 45
degrees from full open to minimize air turbulence and provide near
linear operation. Damper blades shall be fitted with flexible seals
for tight closure and minimized sound generation. Damper blades
shall be screwed through the shaft to insure that no slippage
occurs. Blade shafts shall pivot in corrosion free self-lubricating
bronze oilite bearings. In the fully closed position, air leakage past
the closed damper shall not exceed 2% of the nominal catalog
rating at 3" w.g. (746 Pa) inlet static pressure as rated by ASHRAE
Standard 130.
5.
The terminal units shall be capable of operation as described
herein with a minimum inlet static pressure that shall not exceed
0.28" w.g. (70 Pa) @ 2000 fpm (10.2 m/s) inlet velocity. (The
sequence of operations should be described here, if not part of the
temperature controls specifications.) Each unit shall be complete
with factory mounted (pneumatic, electric, analog electronic, or
DDC) controls. Gauge tap ports shall be supplied in the piping
between the flow pick up and the controller.
OPTIONS
Electric Heat:
Model: 30HQE
Staged
(Substitute the following paragraphs:)
1.
Furnish and install Nailor Model 30HQE Single Duct
Variable Volume Hospital Grade Terminal Units of the sizes
and capabilities as indicated on the drawings. Unit shall be
pressure independent with (pneumatic, analog electronic, DDC)
controls. Unit shall reset to any flow between minimum and the
maximum cataloged airflow as allowed by the specific controller.
10. Single Duct VAV Hospital Grade Terminal Unit Staged
Electric Heating Coils:
a. Electric heating coils shall consist of open coils of high grade
nickel and chromium resistance wire or nichrome elements and
insulated with ceramic insulators in galvanized steel brackets,
supported in heavy gauge galvanized steel frames. Each unit
employing an electric heating coil shall be constructed and
installed in accordance with the requirements of the local
authorities and shall be UL or ETL listed specifically with the
heater as a component of the terminal unit device.
b. Coils shall have the capacities indicated in Contract
Documents. Coils rated up through 16.5 kW shall be single phase,
347 volt, 60 hertz and coils larger than 16.5 kW shall be three
phase, four wire, 208, 480 or 600 volt, 60 hertz. Coil shall be
available in one, two or three stages.
c. Terminal bolts, nuts and washers shall be of corrosion resistant
materials. Coils shall be constructed so the installation may be
accomplished in accordance with the provisions of the National
Electrical Code, for zero clearance. Coils shall be given a 2000
volt dielectric test at the factory.
6.
Each unit shall be constructed with single point electrical
(and pneumatic) connections. All electrical components shall be
ETL or UL listed or recognized and installed in accordance with
the National Electrical Code. All electrical components shall be
installed in a control box. The entire assembly shall be ETL listed
and so labeled.
7.
Each VAV section shall be internally lined with 13/16 (21)
thick, 4 lb. /cu. ft. (64 Kg/m3) density fiberglass insulation with a
reinforced aluminum FSK facing. Units shall meet NFPA 90A and
UL 181 standards.
e. Heating coils shall have a terminal box and cover, with quiet
type built-in magnetic step controlled contactors for each circuit,
branch circuit fusing for each branch circuit on heaters over 48
amps per the NEC and an air flow safety interlock switch for
installation in the heater control enclosure. Provide a 120 or 24
VAC control power transformer with an integral or separately
mounted primary and/or secondary overcurrent protection device
in accordance with NEC requirements.
8.
All sound data shall be compiled in an independent
laboratory and in accordance with the latest version of AHRI
Standard 880 and ANSI/ASHRAE Standard 130. All units shall be
AHRI certified and bear the AHRI certification label.
9.
Dissipative silencer sections shall contain a unit casing
constructed of 22 ga. (.86) galvanized steel. Inlet and discharge
shall be rectangular and configured for slip and drive connections.
Each silencer shall be internally lined with 13/16 (21) thick, 4 lb.
density fiberglass insulation with a reinforced aluminum FSK
facing, placed inside the top and bottom sides of the silencer,
B48
11-15-11
11-14-11
B49
1.
Furnish and install Nailor Model 30HQE Single Duct
Variable Volume Hospital Grade Terminal Units of the sizes
and capabilities as indicated on the drawings. Unit shall be
pressure independent with (pneumatic, analog electronic, DDC)
controls. Unit shall reset to any flow between minimum and the
maximum cataloged airflow as allowed by the specific controller.
B50
11-15-11
30HQW
1.
Furnish and install Nailor Model Series 30HQW Single
Duct Variable Volume Hospital Grade Terminal Units of the
sizes and capabilities as indicated on the drawings. Units shall be
pressure independent with (pneumatic, analog electronic, DDC)
controls. Units shall reset to any flow between minimum and the
maximum cataloged airflow as allowed by the specific controller.
10. Single Duct VAV Hospital Grade Terminal Device Hot
Water Heating Coils
a. Terminal unit hot water heating coils shall be mounted on the
discharge of the unit with slip and drive connections. Provide an
access door or panel on the bottom of the attenuator section of the
terminal unit for servicing and cleaning the unit.
b. Hot water heating coils shall be constructed with copper tubes
and aluminum plate fins. Coils shall have a maximum of 10 fins per
inch. Supply and return connections shall be on the same end of the
coil. Fins shall be bonded to the tubes by means of mechanical
expansion of the tubes. Fins shall be at least .0045" (.11) thick.
c. Coils shall have galvanized steel casings on all sides no lighter
than 22 ga. (1.0).
d. Tubes shall be 12" (13) O.D. and shall be spaced approximately
1 14" (32) apart and shall have a minimum wall thickness of 0.016"
(.41). Hot water shall be equally distributed through all tubes by
the use of orifices or header design. Water velocity in the tubes
shall not exceed five feet per second. The water pressure drop
through the coil shall not exceed 10 feet. Heating coil face
velocities shall not exceed the maximum face velocity indicated in
the schedules on the Contract Documents.
e. Coils shall be tested by air pressure under water. Coils shall be
tested at 350 psig (2,413 kPa) air static pressure.
f. Coil ratings, calculations and selection data shall be in
accordance with the applicable AHRI Standards and shall be
submitted with the Shop Drawings.
11-20-11
B51
B
SINGLE DUCT TERMINAL UNITS
Models:
30X Basic Unit
Model 30X
The 30X Basic Unit has been designed to provide optimum performance in exhaust applications. By including the optional attenuator, this
terminal unit offers quiet operation with minimal system pressure loss.
STANDARD FEATURES:
Venturi valve inlet for reduced pressure drop.
22 ga. (0.86) zinc coated steel casing, mechanically sealed, low
leakage construction.
16 ga. (1.63) corrosion-resistant steel inclined opposed blade
damper with extruded PVC seals. 45 rotation, CW to close. Tight
close-off. Damper leakage is less than 2% of the terminal rated
airflow at 3" w.g. (746 Pa).
1/2" (13) dia. plated steel drive shaft. An indicator mark on the end
of the shaft shows damper position.
Multi-point averaging Diamond Flow Sensor. Aluminum
construction. Supplied with balancing tees.
Rectangular inlet and discharge with slip and drive cleat duct
connection.
Full NEMA 1 type controls enclosure for factory mounted controls.
3/4" (19), fiberglass dual density insulation, exposed edges coated to
prevent air erosion. Meets the requirements of NFPA 90A and UL
181.
Right-hand controls location is standard (shown) when looking in
direction of airflow. Optional left hand controls mounting is
available.
Available in 11 unit sizes to handle from 308575 cfm (144047 l/s).
Controls:
B52
11-28-11
6"
(152)
30" (762)
14" (356)
DAMPER
DRIVESHAFT
11" AIRFLOW
(279)
MULTI-POINT
AVERAGING
FLOW SENSOR
CONTROLS ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
CONTROLS
OPTIONAL 08SCL SERIES
ENCLOSURE
ACCESS DOOR 8" x 8" (4 6),
10" x 10" (7 16), 18" x 10" (24 x 16)
36" (914)
6"
(152)
14" (356)
11" AIRFLOW
(279)
MULTI-POINT
AVERAGING
FLOW SENSOR
30" (762)
CONTROLS ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
OPTIONAL
SOUND ATTENUATOR
DAMPER
DRIVESHAFT
CONTROLS
ENCLOSURE
Dimensional Data
Unit
Size
4
5
6
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
7
8
9
12 (305) 12 12 (318)
12 (305) 12 12 (318)
14 (356) 12 12 (318)
10
12
14
14 (356) 12 12 (318)
18 (457) 12 12 (318)
24 (610) 12 12 (318)
16
28 (711) 12 12 (318)
24 x 16 38 (965) 18 (457)
11-28-11
B53
5/8" (16)
B54
1 1/4"
(32)
6-28-13
Rectangular Inlet
3/16" (5) DIA. O.D.
SUPPORT
BRACKET
GROMMET
GASKET
FLOW
SCREW INSERT
DIRECTION
TO DUCT
LABEL
AT PERIMETER
HOLES
CONNECTIONS
FOR 1/4" (6)
O.D. FR TUBING
HIGH
PRESSURE
RETANGULAR
INLET
AIRFLOW
DIRECTION
LOW PRESSURE
The high end of the tabulated Total Airflow Range on pneumatic and
analog electronic controls represents the Diamond Flow Sensors
differential pressure reading at 1" w.g. (249 Pa). The high end airflow
range for digital controls is represented by the indicated transducer
differential pressure.
AHRI Standard 880 "Performance Rating of Air Terminals" is the
Minimum airflow limits are based upon .02" w.g. (5 Pa) differential
pressure signal from Diamond Flow Sensor on analog/ digital controls
and .03" (7.5) for pneumatic controllers. This is a realistic low limit for
many transducers used in the digital controls industry. Setting airflow
minimums lower, may cause damper hunting and result in a failure to
meet minimum ventilation requirements. Factory settings will
therefore not be made outside these ranges; however, a minimum
setting of zero (shut-off) is an available option on pneumatic units.
Where an auxiliary setting is specified, the value must be greater
than the minimum setting.
4
5
6
7
8
9
10
12
14
16
24 x 16
Inlet
Type
Rect.
Total
Airflow
Range,
cfm
Airflow at
2000 fpm
Inlet
Velocity
(nom.), cfm
0 260
0 425
0 710
0 835
0 1190
0 1480
0 1885
0 2780
0 3085
0 4385
0 8575
150
250
400
550
700
900
1100
1600
2100
2800
5350
Pneumatic 3000
Controller
Min.
.03
35
60
100
120
170
210
265
395
435
620
1215
Max.
1.0
210
345
580
680
970
1210
1540
2270
2520
3580
7000
1.5
260
425
710
835
1190
1480
1885
2780
3085
4385
8575
374
123
201
335
394
562
698
890
1312
1456
2069
4047
4
5
6
7
8
9
10
12
14
16
24 x 16
Inlet
Type
Rect.
Total
Airflow
Range,
l/s
Airflow at
10.2 m/s
Inlet
Velocity
(nom.), l/s
0 123
0 201
0 335
0 394
0 562
0 698
0 890
0 1312
0 1456
0 2069
0 4047
71
118
189
260
330
425
519
755
991
1321
2525
Pneumatic 3000
Controller
Min.
7.5
17
28
47
57
80
99
125
186
205
293
573
Max.
249
99
163
274
321
458
571
727
1071
1189
1689
3303
5-13-14
B55
Unit
Size
10
12
14
16
24
x
16
Airflow
cfm
200
150
100
75
50
30
300
250
200
125
100
45
450
400
300
200
100
65
650
550
335
225
110
800
700
600
400
175
1050
900
675
450
225
1350
1100
825
550
275
2000
1600
1200
800
400
2700
2100
1550
1050
525
3500
2800
2100
1400
700
5350
5000
4000
3200
3000
2000
l/s
94
71
47
35
24
14
142
118
94
59
47
21
212
189
142
94
47
31
307
260
158
106
52
378
330
283
189
83
495
425
319
212
106
637
519
389
260
130
944
755
566
378
189
1274
991
731
495
248
1652
1321
991
661
330
2525
2360
1888
1510
1416
944
Min. Inlet
Ps
"w.g. Ps
0.63 157
0.37 92
0.17 42
0.10 25
0.05 12
0.02 5
0.55 137
0.35 87
0.23 57
0.10 25
0.06 15
0.01 2
0.38 94
0.30 75
0.18 45
0.08 20
0.02 5
0.01 2
0.49 122
0.35 87
0.13 32
0.06 15
0.02 5
0.35 87
0.27 67
0.20 50
0.09 22
0.02 5
0.37 97
0.27 67
0.15 37
0.07 17
0.02 5
0.38 94
0.25 62
0.15 37
0.07 17
0.02 5
0.37 92
0.24 60
0.14 35
0.06 15
0.02 5
0.54 134
0.33 82
0.18 45
0.08 20
0.02 5
0.48 119
0.31 77
0.18 45
0.08 20
0.02 5
0.45 112
0.39 97
0.25 62
0.16 40
0.14 35
0.06 15
Performance Notes:
Min.
Ps
22
20
32
28
22
-
B56
7-31-12
B
SINGLE DUCT TERMINAL UNITS
Min. inlet
Unit Airflow
Ps
Size cfm l/s "w.g. Pa
200 94 0.63 157
150 71 0.37 92
100 47 0.17 42
4
75 35 0.10 25
50 24 0.05 12
30 14 0.02 5
300 142 0.55 137
250 118 0.35 87
200 94 0.23 57
5
125 59 0.10 25
100 47 0.06 15
45 21 0.01 2
450 212 0.38 94
400 189 0.30 75
300 142 0.18 45
6
200 94 0.08 20
100 47 0.02 5
65 31 0.01 2
650 307 0.49 122
550 260 0.35 87
7 335 158 0.13 32
225 106 0.06 15
110 52 0.02 5
800 378 0.35 87
700 330 0.27 67
8 600 283 0.20 50
400 189 0.09 22
175 83 0.02 5
1050 495 0.37 92
900 425 0.27 67
9 675 319 0.15 37
450 212 0.07 17
225 106 0.02 5
1350 637 0.38 94
1100 519 0.25 62
10 825 389 0.15 37
550 260 0.07 17
275 130 0.02 5
2000 944 0.37 92
1600 755 0.24 60
12 1200 566 0.14 35
800 378 0.06 15
400 189 0.02 5
2700 1274 0.54 134
2100 991 0.33 82
14 1550 731 0.18 45
1050 495 0.08 20
525 248 0.02 5
3500 1652 0.48 119
2800 1321 0.31 77
16 2100 991 0.18 45
1400 661 0.08 20
700 330 0.02 5
5350 2525 0.45 112
5000 2360 0.39 97
24
4000 1888 0.25 62
x
3200 1510 0.16 40
16
3000 1416 0.14 35
2000 944 0.06 15
For performance table notes, see page B65; highlighted numbers indicate embedded AHRI certification points.
1-14-15
B57
Unit Airflow
Size cfm l/s
200 94
150 71
100 47
4
75 35
50 24
30 14
300 142
250 118
200 94
5
125 59
100 47
45 21
450 212
400 189
300 142
6
200 94
100 47
65 31
650 307
550 260
7 335 158
225 106
110 52
800 378
700 330
8 600 283
400 189
175 83
1050 495
900 425
9 675 319
450 212
225 106
1350 637
1100 519
10 825 389
550 260
275 130
2000 944
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1550 731
1050 495
525 248
3500 1652
2800 1321
16 2100 991
1400 661
700 330
5350 2525
5000 2360
24
4000 1888
x
3200 1510
16
3000 1416
2000 944
Min. inlet
-Ps
"w.g. Pa
0.63 157
0.37 92
0.17 42
0.10 25
0.05 12
0.02 5
0.55 137
0.35 87
0.23 57
0.10 25
0.06 15
0.01 2
0.38 94
0.30 75
0.18 45
0.08 20
0.02 5
0.01 2
0.49 122
0.35 87
0.13 32
0.06 15
0.02 5
0.35 87
0.27 67
0.20 50
0.09 22
0.02 5
0.37 92
0.27 67
0.15 37
0.07 17
0.02 5
0.38 94
0.25 62
0.15 37
0.07 17
0.02 5
0.37 92
0.24 60
0.14 35
0.06 15
0.02 5
0.54 134
0.33 82
0.18 45
0.08 20
0.02 5
0.48 119
0.31 77
0.18 45
0.08 20
0.02 5
0.45 112
0.39 97
0.25 62
0.16 40
0.14 35
0.06 15
MinimumPs
2 3 4 5 6 7
52 42 33 27 27 21
48 35 27 - - - - - - - - - - - - - - - - - - - - - - 51 42 35 27 25 - 39 31 23 - - - - - - - - - - - - - - - - - - - - - 53 43 35 28 25 51 40 33 24 - - 34 25 - - - - - - - - - - - - - - - - - 56 50 42 33 27 25
53 46 38 28 24 - - - - - - - - - - - - - - - 57 47 41 32 26 20
53 44 38 29 22 50 40 34 26 - 51 38 30 22 - - - - - - 59 50 44 34 30 28
54 46 40 30 25 21
- 40 33 23 - - - - - - - - - - - 56 48 40 34 32 25
52 43 34 28 23 - 39 29 - - - - - - - - - - - - 60 50 44 35 34 29
54 47 42 37 39 33
48 37 31 21 - - - - - - - - - - - 65 57 53 42 35 31
59 50 46 35 29 22
54 42 32 22 - 49 34 21 - - - - - - - 66 55 49 42 35 30
59 49 43 35 29 52 42 34 26 - - - 22 - - - - - - - 74 57 52 48 42 38
73 56 51 47 41 37
66 50 44 40 35 28
60 45 38 34 28 19
58 44 36 32 26 17
51 37 25 - - -
For performance table notes, see page B65; highlighted numbers indicate embedded AHRI certification points.
B58
12-2-11
10
12
14
16
24
x
16
cfm
200
150
100
75
50
30
300
250
200
125
100
45
450
400
300
200
100
65
650
550
335
225
110
800
700
600
400
175
1050
900
675
450
225
1350
1100
825
550
275
2000
1600
1200
800
400
2700
2100
1550
1050
525
3500
2800
2100
1400
700
5350
5000
4000
3200
3000
2000
l/s
94
71
47
35
24
14
142
118
94
59
47
21
212
189
142
94
47
31
307
260
158
106
52
378
330
283
189
83
495
425
319
212
106
637
519
389
260
130
944
755
566
378
189
1274
991
731
495
248
1652
1321
991
661
330
2525
2360
1888
1510
1416
944
Min. Inlet
Ps
Min.
"w.g. Ps Ps
0.63 157 0.37 92
0.17 42
0.10 25
0.05 12
0.02 5
0.55 137 0.35 87
0.23 57
0.10 25
0.06 15
0.01 2
0.38 94
0.30 75
0.18 45
0.08 20
0.02 5
0.01 2
0.50 124 0.35 87
0.13 32
0.06 15
0.02 5
0.35 87
0.27 67
0.20 50
0.09 22
0.02 5
0.39 97
0.29 72
0.16 40
0.07 17
0.02 5
0.44 109 0.29 72
0.16 40
0.07 17
0.02 5
0.43 107 0.27 67
0.16 40
0.07 17
0.02 5
0.57 142 0.33 82
0.18 45
0.09 22
0.02 5
0.48 119 0.31 77
0.18 45
0.08 20
0.02 5
0.47 117 27
0.41 102 25
0.27 67
0.17 42
0.15 37
0.07 17
-
Performance Notes:
12-2-11
B
SINGLE DUCT TERMINAL UNITS
Airflow
B59
Unit Airflow
Size cfm l/s
200 94
150 71
100 47
4
75 35
50 24
30 14
300 142
250 118
200 94
5
125 59
100 47
45 21
450 212
400 189
300 142
6
200 94
100 47
65 31
650 307
550 260
7 335 158
225 106
110 52
800 378
700 330
8 600 283
400 189
175 83
1050 495
900 425
9 675 319
450 212
225 106
1350 637
1100 519
10 825 389
550 260
275 130
2000 944
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1550 731
1050 495
525 248
3500 1652
2800 1321
16 2100 991
1400 661
700 330
5350 2525
5000 2360
24
4000 1888
x
3200 1510
16
3000 1416
2000 944
Min. inlet
Ps
"w.g. Pa
0.63 157
0.37 92
0.17 42
0.10 25
0.05 12
0.02 5
0.55 137
0.35 87
0.23 57
0.10 25
0.06 15
0.01 2
0.38 94
0.30 75
0.18 45
0.08 20
0.02 5
0.01 2
0.50 124
0.35 87
0.13 32
0.06 15
0.02 5
0.35 87
0.27 67
0.20 50
0.09 22
0.02 5
0.39 97
0.29 72
0.16 40
0.07 17
0.02 5
0.44 109
0.29 72
0.16 40
0.07 17
0.02 5
0.43 107
0.27 67
0.16 40
0.07 17
0.02 5
0.57 142
0.33 82
0.18 45
0.09 22
0.02 5
0.48 119
0.31 77
0.18 45
0.08 20
0.02 5
0.47 117
0.41 102
0.27 67
0.17 42
0.15 37
0.07 17
MinimumPs
2 3 4 5 6 7
52 49 45 37 28 23
48 43 40 32 21 - 37 33 22 - - - 27 - - - - - - - - - - - - 49 52 49 41 26 21
- 48 44 36 20 - 43 38 30 - - - 28 - - - - 23 - - - - - - - 53 48 41 34 23 22
51 46 39 31 20 - 39 33 25 - - - - - - - - - - - - - - - - 57 52 46 43 29 31
54 48 42 38 24 25
- 37 30 24 - - - - - - - - - - - 51 49 44 40 27 27
- 46 42 36 25 23
- 43 39 33 21 - 37 32 21 - - - - - - 54 53 50 44 33 33
51 50 46 40 28 26
49 45 40 31 - - - 30 20 - - - - - - 57 51 45 43 34 34
55 46 41 37 28 25
- 39 35 29 - - - 26 - - - - - - - 61 54 48 45 39 37
55 49 43 39 32 27
51 43 37 31 21 48 36 28 20 - - - - - - 65 59 53 48 41 40
59 52 46 40 35 29
54 42 37 30 23 - - 27 - - - - - - - 66 57 52 50 42 41
59 51 46 44 37 32
53 46 40 36 29 21
54 37 30 23 - - - - - - 74 62 56 50 45 41
73 61 55 49 44 40
67 55 49 42 36 31
63 50 43 36 30 23
62 52 45 35 29 25
56 44 27 - - -
B60
12-2-11
MinimumPs
2 3 4 5 6 7
52 42 33 27 27 21
48 35 27 - - - - - - - - - - - - - - - - - - - - - - 51 42 35 27 25 - 39 31 23 - - - - - - - - - - - - - - - - - - - - - 53 43 35 28 25 51 40 33 24 - - 34 25 - - - - - - - - - - - - - - - - - 56 50 42 33 27 25
53 46 38 28 24 - - - - - - - - - - - - - - - 57 47 41 32 26 20
53 44 38 29 22 50 40 34 26 - 51 38 30 22 - - - - - - 59 50 44 34 30 28
54 46 40 30 25 21
- 40 33 23 - - - - - - - - - - - 56 48 40 34 32 25
52 43 34 28 23 - 39 29 - - - - - - - - - - - - 60 50 44 35 34 29
54 47 42 37 39 33
48 37 31 21 - - - - - - - - - - - 65 57 53 42 35 31
59 50 46 35 29 22
54 42 32 22 - 49 34 21 - - - - - - - 66 55 49 42 35 30
59 49 43 35 29 52 42 34 26 - - - 22 - - - - - - - 74 57 52 48 42 38
73 56 51 47 41 37
66 50 44 40 35 28
60 45 38 34 28 19
58 44 36 32 26 17
51 37 25 - - -
B
SINGLE DUCT TERMINAL UNITS
Unit Airflow
Size cfm l/s
200 94
150 71
100 47
4
75 35
50 24
30 14
300 142
250 118
200 94
5
125 59
100 47
45 21
450 212
400 189
300 142
6
200 94
100 47
65 31
650 307
550 260
7 335 158
225 106
110 52
800 378
700 330
8 600 283
400 189
175 83
1050 495
900 425
9 675 319
450 212
225 106
1350 637
1100 519
10 825 389
550 260
275 130
2000 944
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1550 731
1050 495
525 248
3500 1652
2800 1321
16 2100 991
1400 661
700 330
5350 2525
5000 2360
24
4000 1888
x
3200 1510
16
3000 1416
2000 944
B61
Unit
Size
10
12
14
16
24
x
16
Airflow
cfm
200
150
100
75
50
30
300
250
200
125
100
45
450
400
300
200
100
65
650
550
335
225
110
800
700
600
400
175
1050
900
675
450
225
1350
1100
825
550
275
2000
1600
1200
800
400
2700
2100
1550
1050
525
3500
2800
2100
1400
700
5350
5000
4000
3200
3000
2000
l/s
94
71
47
35
24
14
142
118
94
59
47
21
212
189
142
94
47
31
307
260
158
106
52
378
330
283
189
83
495
425
319
212
106
637
519
389
260
130
944
755
566
378
189
1274
991
731
495
248
1652
1321
991
661
330
2525
2360
1888
1510
1416
944
Min. Inlet
Ps
Min.
"w.g. Ps Ps
0.63 157 0.37 92
0.17 42
0.10 25
0.05 12
0.02 5
0.55 137 0.35 87
0.23 57
0.10 25
0.06 15
0.01 2
0.38 94
0.30 75
0.18 45
0.08 20
0.02 5
0.01 2
0.50 124 0.35 87
0.13 32
0.06 15
0.02 5
0.35 87
0.27 67
0.20 50
0.09 22
0.02 5
0.39 97
0.29 70
0.16 40
0.07 17
0.02 5
0.42 104 0.30 75
0.15 37
0.07 17
0.02 5
0.41 102 0.27 67
0.15 37
0.07 17
0.02 5
0.58 144 0.34 85
0.18 45
0.09 22
0.02 5
0.48 119 0.31 77
0.18 45
0.08 20
0.02 5
0.46 114 27
0.40 99 25
0.26 65
0.18 45
0.15 37
0.07 17
-
Performance Notes:
B62
12-2-11
MinimumPs
2 3 4 5 6 7
51 49 45 40 43 41
- 42 39 35 35 33
- 34 32 24 23 - - 25 - - - - - - - - - - - - 50 51 50 44 42 42
48 46 44 38 36 34
- 42 40 34 29 26
- - 29 21 - - - 22 - - - - - - - 51 47 42 38 43 41
- 44 39 35 38 36
- - 34 29 28 25
- - - - - - - - - - - - - - - 57 53 47 47 43 46
54 48 42 42 39 39
48 39 30 28 22 45 36 20 - - 44 36 - - - 52 49 45 43 42 41
48 46 43 40 38 35
48 44 40 36 33 30
- 38 32 24 - - - - - - 55 52 50 47 47 47
52 49 47 43 40 39
47 44 40 35 29 27
- 36 29 21 - - 33 - - - 55 50 46 46 48 45
54 45 42 41 40 35
47 39 35 32 28 23
- - 25 20 - - - - - - 60 54 49 47 49 45
55 48 44 41 42 36
49 42 37 33 30 25
- - 28 22 - - - - - - 65 59 53 50 48 50
58 51 46 42 41 37
- 42 38 33 32 25
- - 27 21 - - - - - - 67 56 53 52 50 51
62 53 50 48 47 42
52 46 41 38 34 28
51 38 31 25 - - - - - - 74 61 56 52 48 45
73 60 55 51 47 44
68 55 49 44 40 35
63 50 43 37 32 27
62 48 41 35 28 22
56 44 27 20 - -
B
SINGLE DUCT TERMINAL UNITS
Unit Airflow
Size cfm l/s
200 94
150 71
100 47
4
75 35
50 24
30 14
300 142
250 118
200 94
5
125 59
100 47
45 21
450 212
400 189
300 142
6
200 94
100 47
65 31
650 307
550 260
7 335 158
225 106
110 52
800 378
700 330
8 600 283
400 189
175 83
1050 495
900 425
9 675 319
450 212
225 106
1350 637
1100 519
10 825 389
550 260
275 130
2000 944
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1550 731
1050 495
525 248
3500 1652
2800 1321
16 2100 991
1400 661
700 330
5350 2525
5000 2360
24
4000 1888
x
3200 1510
16
3000 1416
2000 944
B63
Unit Airflow
Size cfm l/s
200 94
150 71
100 47
4
75 35
50 24
30 14
300 142
250 118
200 94
5
125 59
100 47
45 21
450 212
400 189
300 142
6
200 94
100 47
65 31
650 307
550 260
7 335 158
225 106
110 52
800 378
700 330
8 600 283
400 189
175 83
1050 495
900 425
9 675 319
450 212
225 106
1350 637
1100 519
10 825 389
550 260
275 130
2000 944
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1550 731
1050 495
525 248
3500 1652
2800 1321
16 2100 991
1400 661
700 330
5350 2525
5000 2360
24
4000 1888
x
3200 1510
16
3000 1416
2000 944
Min. inlet
Ps
"w.g. Pa
0.63 157
0.37 92
0.17 42
0.10 25
0.05 12
0.02 2
0.55 137
0.35 87
0.23 57
0.10 25
0.06 15
0.01 2
0.38 94
0.30 75
0.18 45
0.08 20
0.02 5
0.01 2
0.50 124
0.35 87
0.13 32
0.06 15
0.02 5
0.35 87
0.27 67
0.20 50
0.09 22
0.02 5
0.39 97
0.28 70
0.16 40
0.07 17
0.02 5
0.42 104
0.30 75
0.15 37
0.07 17
0.02 5
0.41 102
0.27 67
0.15 37
0.07 17
0.02 5
0.56 144
0.34 85
0.18 45
0.09 22
0.02 5
0.48 119
0.31 77
0.18 45
0.08 20
0.02 5
0.46 114
0.40 99
0.26 65
0.18 45
0.15 37
0.07 17
MinimumPs
2 3 4 5 6 7
52 42 33 27 27 21
48 35 27 - - - - - - - - - - - - - - - - - - - - - - 51 42 35 27 25 - 39 31 23 - - - - - - - - - - - - - - - - - - - - - 53 43 35 28 25 51 40 33 24 - - 34 25 - - - - - - - - - - - - - - - - - 56 50 42 33 27 25
53 46 38 28 24 - - - - - - - - - - - - - - - 57 47 41 32 26 20
53 44 38 29 22 50 40 34 26 - 51 38 30 22 - - - - - - 59 50 44 34 30 28
54 46 40 30 25 21
- 40 33 23 - - - - - - - - - - - 56 48 40 34 32 25
52 43 34 28 23 - 39 29 - - - - - - - - - - - - 60 50 44 35 34 29
54 47 42 37 39 33
48 37 31 21 - - - - - - - - - - - 65 57 53 42 35 31
59 50 46 35 29 22
54 42 32 22 - 49 34 21 - - - - - - - 66 55 49 42 35 30
59 49 43 35 29 52 42 34 26 - - - 22 - - - - - - - 74 57 52 48 42 38
73 56 51 47 41 37
66 50 44 40 35 28
60 45 38 34 28 19
58 44 36 32 26 17
51 37 25 - - -
B64
12-2-11
Min. Inlet
Ps
cfm l/s
" w.g. Pa
0.37
0.35
0.30
0.35
0.27
0.27
0.25
0.24
0.33
0.31
0.45
60
67
71
72
74
74
76
75
80
76
83
57
62
64
62
63
64
65
66
69
67
74
150
250
400
550
700
900
1100
1600
2100
2800
5350
71
118
189
260
330
425
519
755
991
1321
2525
92
87
75
87
67
67
62
60
82
77
112
Octave Band
4
5
6
50
55
56
54
55
57
58
60
61
64
69
50
52
51
54
52
55
54
58
59
60
67
44
47
48
50
51
52
53
56
57
59
66
41
43
45
49
50
49
51
54
54
56
64
54
58
62
64
65
64
66
67
67
68
72
45
49
52
52
53
54
55
57
57
57
64
Octave Band
4
5
6
37
39
41
44
43
48
44
48
48
49
57
2-12-15
31
34
34
40
36
40
37
41
40
41
47
23
27
28
32
32
32
32
40
34
36
44
19
21
22
27
27
36
26
35
29
31
44
4
5
6
7
8
9
10
12
14
16
24 x 16
Airflow
B65
1.
Furnish and install Nailor Model Series 30X Single Duct
Variable Volume Exhaust Terminal Units of the sizes and capabilities
as indicated on the drawings. Units shall be pressure independent with
pneumatic, analog electronic or DDC controls. Units shall reset to any
flow between minimum and the maximum cataloged airflow as allowed
by the specific controller.
2.
The entire exhaust terminal unit shall be designed and built as a
single unit. The units shall be provided with a variable air volume
damper that controls the air quantity in response to a control signal. The
units shall also include all options such as attenuators and access
doors. Exhaust units shall feature a venturi valve inlet with integrated
flow sensor for optimized airflow performance and reduced pressure
drop. The space limitations shall be reviewed carefully to insure that all
units will fit into the space allowed.
3.
Unit casing shall be 22 ga. (.86) galvanized steel with rectangular
inlet and outlet connections, configured for slip and drive connections.
Basic valve assembly shall not exceed 30" (762) in length. Casing
leakage downstream of the damper shall not exceed 1% @ 1" w.g. (250
Pa). High side leakage shall not exceed 2% @ 3" w.g. (746 Pa).
4.
Damper assemblies of 16 ga. (1.6) galvanized steel shall be
multiple opposed blade construction arranged to close at 45 degrees
from full open to minimize air turbulence and provide near linear
operation. Damper blades shall be fitted with flexible seals for tight
closure and minimized sound generation. Damper blades shall be
screwed through the shaft to insure that no slippage occurs. Blade
shafts shall pivot on corrosion free Celcon bearings. In the fully closed
position, air leakage past the closed damper shall not exceed 2% of the
nominal catalog rating at 3" w.g. (746 Pa) inlet static pressure as rated
by ASHRAE Standard 130.
5.
The terminal unit shall be capable of operation as described
herein with a minimum inlet static pressure that shall not exceed 0.37"
w.g. (92 Pa) at 2000 fpm (10.2 m/s) inlet velocity for unit sizes 4 through
16. (The sequence of operations should be described here, if not part
of the temperature controls specifications.) Gauge tap ports shall be
supplied in the piping between the flow pick up and the controller.
6.
Each unit shall be constructed with single point electrical
connections. All electrical components shall be ETL or UL listed or
recognized and installed in accordance with the National Electrical
Code. All electrical components shall be installed in a control box. The
entire assembly shall be ETL listed and so labeled.
7.
Each unit shall be internally lined with " (19) dual density
fiberglass insulation. Edges shall be sealed against airflow erosion.
Units shall meet NFPA 90A and UL 181 standards.
8.
All sound data shall be compiled in an independent laboratory and
in accordance with the latest version of AHRI Standard 880 and
ANSI/ASHRAE Standard 130. All units shall be AHRI certified and bear
the AHRI certification label.
9.
The unit shall be capable of being changed from Right Hand to
Left Hand configuration by flipping the unit over. No controls, field
adjustments, nor field re-assembly shall be required to accomplish this.
The unit shall be listed by UL or ETL under UL 1995 to operate in either
orientation.
B66
12-16-11
OPTIONS
Attenuator:
30HQX
Model 30HQX
The 30HQX Hospital Grade exhaust terminal unit has been purposely designed to provide optimum performance, while
addressing the needs of hospital and other critical environment applications where indoor air quality (IAQ) is a concern. Standard
features, like the access door and removable flow sensor, ensure that maintenance is simplified. The standard fully insulated
dissipative silencer is designed to minimize undue pressure loss while maximizing attenuation, specifically in the 2nd and 3rd
octave bands.
STANDARD FEATURES:
Venturi valve inlet for reduced pressure drop.
22 ga. (0.86) zinc coated steel casing, mechanically sealed,
Model:
Controls:
12-16-11
B67
66" (1676)
36" (914)
1/2"
(13)
6"
(152)
30" (762)
RECTANGULAR DISSIPATIVE
MYLAR LINED SILENCER
14" (356)
DAMPER
DRIVESHAFT
11" AIRFLOW
(279)
MUlTI-POINT
AVERAGING
FLOW SENSOR
FMI REMOVABLE
FLOW SENSOR
Dimensional Data
Unit
Size
4
5
6
7
8
9
10
12
14
16
24 x 16
10 (254)
10 (254)
10 (254)
12 (305)
12 (305)
14 (356)
14 (356)
18 (457)
24 (610)
28 (711)
38 (965)
10 (254)
10 (254)
10 (254)
12 12 (318)
12 12 (318)
12 12 (318)
12 12 (318)
12 12 (318)
12 12 (318)
12 12 (318)
18 (457)
B68
6-28-13
GROMMET
GASKET
FLOW
SCREW INSERT
DIRECTION
TO DUCT
LABEL
AT PERIMETER
HOLES
CONNECTIONS
FOR 1/4" (6)
O.D. FR TUBING
HIGH
PRESSURE
RETANGULAR
INLET
AIRFLOW
DIRECTION
LOW PRESSURE
The high end of the tabulated Total Airflow Range on pneumatic and
analog electronic controls represents the Diamond Flow Sensors
differential pressure reading at 1" w.g. (249 Pa). The high end airflow
range for digital controls is represented by the indicated transducer
differential pressure.
AHRI Standard 880 "Performance Rating of Air Terminals" is the
Model 30HQX
Minimum airflow limits are based upon .02" w.g. (5 Pa) differential
pressure signal from Diamond Flow Sensor on analog/ digital controls
and .03" (7.5) for pneumatic controllers. This is a realistic low limit for
many transducers used in the digital controls industry. Setting airflow
minimums lower, may cause damper hunting and result in a failure to
meet minimum ventilation requirements. Factory settings will
therefore not be made outside these ranges; however, a minimum
setting of zero (shut-off) is an available option on pneumatic units.
Where an auxiliary setting is specified, the value must be greater
than the minimum setting.
4
5
6
7
8
9
10
12
14
16
24 x 16
Inlet
Type
Rect.
Total
Airflow
Range,
cfm
Airflow at
2000 fpm
Inlet
Velocity
(nom.), cfm
0 260
0 425
0 710
0 835
0 1190
0 1480
0 1885
0 2780
0 3085
0 4385
0 8575
150
250
400
550
700
900
1100
1600
2100
2800
5350
Pneumatic 3000
Controller
Min.
.03
35
60
100
120
170
210
265
395
435
620
1215
Max.
1.0
210
345
580
680
970
1210
1540
2270
2520
3580
7000
1.5
260
425
710
835
1190
1480
1885
2780
3085
4385
8575
374
123
201
335
394
562
698
890
1312
1456
2069
4047
4
5
6
7
8
9
10
12
14
16
24 x 16
Inlet
Type
Rect.
Total
Airflow
Range,
l/s
Airflow at
10.2 m/s
Inlet
Velocity
(nom.), l/s
0 123
0 201
0 335
0 394
0 562
0 698
0 890
0 1312
0 1456
0 2069
0 4047
71
118
189
260
330
425
519
755
991
1321
2525
Pneumatic 3000
Controller
Min.
7.5
17
28
47
57
80
99
125
186
205
293
573
Max.
249
99
163
274
321
458
571
727
1071
1189
1689
3303
5-13-14
B69
Inlet
Size
Airflow
Min. Inlet
Ps
Performance Notes:
B70
12-16-11
B
SINGLE DUCT TERMINAL UNITS
Inlet Airflow
Size cfm l/s
200 94
150 71
100 47
4
75 35
50 24
30 14
300 142
250 118
200 94
5
125 59
100 47
45 21
450 212
400 189
300 142
6
200 94
100 47
65 31
650 307
550 260
7 335 158
225 106
110 52
800 378
700 330
8 600 283
400 189
175 83
1050 495
900 425
9 675 319
450 212
225 106
1350 637
1100 519
10 825 389
550 260
275 130
2000 944
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1550 731
1050 495
525 248
3500 1652
2800 1321
16 2100 991
1400 661
700 330
5350 2525
5000 2360
24
4000 1888
x
3200 1510
16
3000 1416
2000 944
For performance table notes, see page B73; highlighted numbers indicate embedded AHRI certification points.
1-14-15
B71
Inlet Airflow
Size cfm l/s
200 94
150 71
100 47
4
75 35
50 24
30 14
300 142
250 118
200 94
5
125 59
100 47
45 21
450 212
400 189
300 142
6
200 94
100 47
65 31
650 307
550 260
7 335 158
225 106
110 52
800 378
700 330
8 600 283
400 189
175 83
1050 495
900 425
9 675 319
450 212
225 106
1350 637
1100 519
10 825 389
550 260
275 130
2000 944
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1550 731
1050 495
525 248
3500 1652
2800 1321
16 2100 991
1400 661
700 330
5350 2525
5000 2360
24
4000 1888
x
3200 1510
16
3000 1416
2000 944
Min. inlet
Ps
"w.g. Pa
0.63 157
0.37 92
0.17 42
0.10 25
0.05 12
0.02 5
0.60 149
0.40 99
0.24 60
0.10 25
0.06 15
0.01 2
0.49 122
0.39 97
0.22 55
0.10 25
0.03 7
0.01 2
0.50 124
0.35 89
0.14 35
0.06 15
0.02 5
0.36 89
0.28 70
0.20 50
0.09 22
0.02 5
0.43 107
0.32 80
0.18 45
0.08 20
0.02 5
0.49 122
0.32 80
0.18 45
0.08 20
0.02 5
0.53 132
0.34 85
0.19 47
0.08 20
0.02 5
0.55 137
0.33 82
0.18 45
0.09 22
0.02 5
0.50 124
0.31 77
0.18 45
0.08 20
0.02 5
0.49 122
0.43 107
0.27 67
0.18 45
0.16 40
0.07 17
Minimum Ps
2 3 4 5 6 7
52 42 33 27 27 21
48 35 27 - - - - - - - - - - - - - - - - - - - - - - 51 42 35 27 25 - 39 31 23 - - - - - - - - - - - - - - - - - - - - - 53 43 35 28 25 51 40 33 24 - - 34 25 - - - - - - - - - - - - - - - - - 56 50 42 33 27 25
53 46 38 28 24 - - - - - - - - - - - - - - - 57 47 41 32 26 20
53 44 38 29 22 50 40 34 26 - 51 38 30 22 - - - - - - 59 50 44 34 30 28
54 46 40 30 25 21
- 40 33 23 - - - - - - - - - - - 56 48 40 34 32 25
52 43 34 28 23 - 39 29 - - - - - - - - - - - - 60 50 44 35 34 29
54 47 42 37 39 33
48 37 31 21 - - - - - - - - - - - 65 57 53 42 35 31
59 50 46 35 29 22
54 42 32 22 - 49 34 21 - - - - - - - 66 55 49 42 35 30
59 49 43 35 29 52 42 34 26 - - - 22 - - - - - - - 74 57 52 48 42 38
73 56 51 47 41 37
66 50 44 40 35 28
60 45 38 34 28 19
58 44 36 32 26 17
51 37 25 - - -
For performance table notes, see page B73; highlighted numbers indicate embedded AHRI certification points.
B72
8-9-12
Model Series 30HQX Hospital Grade Dissipative Silencer AHRI Certification Rating Points
VAV: Steri-Liner Silencer: Mylar, Spacer, Steri-Liner (MSSL) Media
Inlet
Airflow
Size
l/s
71
118
189
7
8
9
10
12
14
16
24 x 16
550
700
900
1100
1600
2100
2800
5350
260
330
425
519
755
991
1321
2525
0.36
0.28
0.32
0.32
0.34
0.33
0.31
0.49
64
65
64
66
67
67
68
72
89
70
80
80
85
82
77
122
68
70
69
71
71
72
74
75
57
58
59
61
61
61
62
69
42
43
44
45
47
48
53
59
37
38
39
42
44
47
51
57
22
30
32
38
41
44
50
56
32
34
35
38
42
43
48
56
52
53
54
55
57
57
57
64
44
43
48
44
48
48
49
57
2-12-15
40
36
40
37
41
40
41
47
32
32
32
32
40
34
36
44
27
27
36
26
35
29
31
44
4
5
6
cfm
150
250
400
B73
1.
Furnish and install Nailor Model 30HQX Single Duct Variable
Volume Exhaust Terminal Units of the sizes and capabilities as
indicated on the drawings. Units shall be pressure independent with
DDC controls. Units shall reset to any flow between minimum and the
maximum cataloged airflow as allowed by the specific controller.
2.
The entire terminal unit shall be designed and built as a single
unit. The units shall be provided with a variable air volume damper that
controls the air quantity in response to a control signal. The units shall
also include dissipative silencers and access doors. Exhaust units shall
feature a venturi valve inlet with integrated flow sensor for optimized
airflow performance and reduced pressure drop. The space limitations
shall be reviewed carefully to insure that all units will fit into the space
allowed.
3.
Unit casing shall be 22 ga. (0.86) galvanized steel with
rectangular inlet and outlet connections, configured for slip and drive
connections. Casing leakage downstream of the damper shall not
exceed 1% @ 1" w.g. (250 Pa). High side leakage shall not exceed 2%
@ 3" w.g. (746 Pa).
4.
Damper assemblies of 16 ga. (1.61) galvanized steel shall be
multiple opposed blade construction arranged to close at 45 degrees
from full open to minimize air turbulence and provide near linear
operation. Damper blades shall be fitted with flexible seals for tight
closure and minimized sound generation. Damper blades shall be
screwed through the shaft to insure that no slippage occurs. Blade
shafts shall pivot on corrosion free Celcon bearings. In the fully closed
position, air leakage past the closed damper shall not exceed 2% of the
nominal catalog rating at 3" w.g. (746 Pa) inlet static pressure as rated
by ASHRAE Standard 130.
5.
The terminal unit shall be capable of operation as described
herein with a minimum inlet static pressure that shall not exceed 0.40"
w.g. (100 Pa) at 2000 fpm (10.2 m/s) inlet velocity for unit sizes 4
through 16. (The sequence of operations should be described here, if
not part of the temperature controls specifications.) Gauge tap ports
shall be supplied in the piping between the flow pick up and the controller.
6.
Each unit shall be constructed with single point electrical
connections. All electrical components shall be ETL or UL listed or
recognized and installed in accordance with the National Electrical
Code. All electrical components shall be installed in a control box. The
entire assembly shall be ETL listed and so labeled.
7.
Each VAV section shall be internally lined with 13/16" (21) thick, 4
lb. density fiberglass insulation with a reinforced aluminum FSK facing.
Units shall meet NFPA 90A and UL 181 standards.
8.
All sound data shall be compiled in an independent laboratory and
in accordance with the latest version of AHRI Standard 880 and
ANSI/ASHRAE Standard 130. All units shall be AHRI certified and bear
the AHRI certification label.
9.
The unit shall be capable of being changed from Right Hand to
Left Hand configuration by flipping the unit over. No controls, field
adjustments, nor field re-assembly shall be required to accomplish this.
The unit shall be listed by UL or ETL under UL 1995 to operate in either
orientation.
B74
5-3-11
Explanation of NC Levels
Tabulated NC levels are based on attenuation values as outlined in
AHRI Standard 885 "Procedure for Estimating Occupied Space
Sound Levels in the Application of Air Terminals and Air Outlets".
AHRI Standard 885, Appendix E provides typical sound attenuation
values for air terminal discharge sound and air terminal radiated
sound.
As stated in AHRI-885, Appendix E, "These values can be used as a
quick method of estimating space sound levels when a detailed
evaluation is not available. The typical attenuation values are
recommended for use by manufacturers to estimate application
sound levels. In product catalogs, the end use environments are not
known and the following factors are provided as typical attenuation
values. Use of these values will allow better comparison between
manufacturers and give the end user a value which will be expected
to be applicable for many types of space."
Please refer to the Performance Data Caveat on page A18 of this
catalog.
Radiated Sound
Environmental Effect
Ceiling/Space Effect
Total Attenuation Deduction
6-11-14
2
16
18
1
18
19
Octave Band
4
5
6
0
20
20
0
26
26
0
31
31
7
0
36
36
Discharge Sound
Small Box
< 300 cfm
Environmental Effect
5 ft. (1.5 m) 1" (25) Duct Lining
Branch Power Division (1 outlet)
5 ft. (1.5 m), 8 in. dia. (203) Flex Duct
End Reflection
Space Effect
Total Attenuation Deduction
Medium Box
300 700 cfm
2
2
0
5
10
5
24
Octave Band
3 4 5 6
1
6
0
10
5
6
28
0
12
0
18
20
7
39
0
29
0
21
0
9
59
0
18
0
12
0
10
40
Octave Band
3 4 5 6
Environmental Effect
5 ft. (1.5 m) 1" (25) Duct Lining
Branch Power Division (2 outlets)
5 ft. (1.5 m), 8 in. dia. (203) Flex Duct
End Reflection
Space Effect
Total Attenuation Deduction
2
2
3
5
10
5
27
1
4
3
10
5
6
29
0
20
3
21
0
9
53
0
14
3
12
0
10
39
Large Box
>700 cfm
Octave Band
3 4 5 6
Environmental Effect
5 ft. (1.5 m) 1" (25) Duct Lining
Branch Power Division (3 outlets)
5 ft. (1.5 m), 8 in. dia. (203) Flex Duct
End Reflection
Space Effect
Total Attenuation Deduction
2
2
5
5
10
5
29
1
3
5
10
5
6
30
0
10
3
18
2
7
40
0
25
0
19
1
8
53
0
9
5
18
2
7
41
0
20
3
19
1
8
51
0
18
5
19
1
8
51
0
17
5
21
0
9
52
B
SINGLE DUCT TERMINAL UNITS
The Nailor Model Series: 3000, 3000Q, 30HQ, 30X and 30HQX
single duct terminal unit performance data is presented in two forms.
The laboratory obtained discharge and radiated sound power levels
in octave bands 2 through 7 (125 through 4000 Hz) center frequency
for each unit size at various flow rates and inlet static pressures is
presented. This data is derived in accordance with ANSI/ASHRAE
Standard 130 and AHRI Standard 880-2011. This data is "raw" with
no attenuation deductions and includes AHRI Certification standard
rating points.
Nailor also provides an "NC Level" table as an application aid in
terminal selection, which include attenuation allowances as
explained below. The suggested attenuation allowances are typical
and are not representative of specific job site conditions. It is
recommended that the sound power level data be used and a
detailed NC calculation be performed using the procedures outlined
in AHRI 885 for accurate space sound levels.
0
12
5
12
0
10
39
B75
B
SINGLE DUCT TERMINAL UNITS
VAV TERMINAL
SILENCER
DD
Fiberglass
1" DD
Fiberglass
SteriLiner
3000
Std.
Opt.
3000Q
Std.
N/A
30HQ
N/A
N/A
Std.
N/A
N/A
30X
Std.
N/A
Opt.
Opt.
Opt.
30HQX
N/A
N/A
Std.
N/A
N/A
N/A
LINERS
FAM
FCL
MSL
(Fiberglass (Fiberglass (Mylar/
Acoustic
Cloth
Spacer
Media)
"Liner")
"Liner")
MSSL
(Mylar/
Spacer/
SteriLiner)
Fiber
Free
Perforated
Metal
Liner
Perforated
Metal +
Steri-Liner
Solid
Metal
Liner
Opt.
Opt.
Opt.
Opt.
Opt.
N/A
N/A
N/A
N/A
Opt.
Opt.
Opt.
Opt.
Opt.
Std.
Opt.
Opt.
N/A
N/A
N/A
N/A
N/A
N/A
Std.
Opt.
Opt.
N/A
N/A
N/A
N/A
Opt.
N/A
N/A
N/A
Std.
SERIES
30X Series
Liner inside optional attenuator will match VAV terminal liner unless
otherwise stated.
Liner inside optional attenuator will match VAV terminal liner unless
otherwise stated.
3000Q Series
30HQX Series
There are two components to the 3000Q Series terminal units, the
VAV terminal and the dissipative silencer. Liner selection
determines the liner type installed into the terminal portion only.
Each dissipative silencer is lined top and bottom with fiberglass as
standard. When the FCL or MSL acoustic media is selected, a foil
faced fiberglass is used. As the entire silencer is internally
insulated, there is no need for field applied duct wrap.
There are three acoustic media options available within the side
pods of the dissipative silencer. From the standard FAM (Fiberglass
Acoustic Media) to IAQ sensitive options, each version provides
superior attenuation characteristics.
30HQ Series
Model 30HQ Hospital Grade terminal units include, as standard,
Steri-Liner in the VAV section. The top and bottom of the dissipative
silencer is lined with Steri-Liner while the side pods include
fiberglass acoustic media encapsulated within a Mylar bag, and
then covered with perforated metal baffles. An acoustical spacer
separates the Mylar from the internal baffles and functions to
attenuate sound levels in the 2nd and 3rd octave bands. Like the
3000Q series, the 30HQ Series does not require field applied
thermal duct wrap.
B76
5-3-11
GRIPNAIL
This liner includes a 50% free area perforated metal sheet that
covers the Steri-Liner insulation. By covering the Steri-Liner, the
perforated metal helps to protect the FSK facing from punctures.
3/4" (19) FIBERGLASS
1" (25) OPTIONAL
CAN/ULC S102-M88
Steri-Liner
13/16" (21) thick, 4 lb./cu. ft. (64 kg/m) density rigid fiberglass with
a fire resistant reinforced aluminum foil-scrim-kraft (FSK) facing.
NOTCH AND
TUCK
FABRICATION
PERFORATED
*
METAL
5-3-11
B77
Nailor offers a solid inner metal liner that completely isolates the
standard fiberglass liner from the airstream. Solid metal liners offer
the ultimate protection against exposure of fiberglass particles to
the airstream, all but eliminating the possibility of punctures that
expose fiberglass. This option is also resistant to moisture. The
encased insulation still provides thermal resistance and radiated
sound attenuation, but acoustic absorption of discharge sound is
eliminated. Solid Metal fabrication is a box within a box and uses
metal end nosing to encapsulate exposed edges of the insulation.
Solid inner liner is 22 ga. (.86) steel.
3/4" (19) dual density fiberglass insulation, 4 lb./ cu. ft. (64 kg/m)
skin.
Meets requirements:
UL 181, 723
ASTM E 84, C 655, C 1071
NFPA 90A & 90B
SOLID
METAL LINER
A Dissipative Silencer is standard on all 3000Q, 30HQ and 30HQX Series terminal units. There are three acoustic media options available
on the 3000Q Series silencers, FAM, FCL and MSL. All 30HQ and 30HQX Hospital Grade units include, as standard, a MSSL acoustic media
option. From the standard fiberglass media to the IAQ sensitive options, each version provides superior attenuation characteristics.
Mylar/Spacer (MSL)
The Standard FAM choice is the simplest of the types offered and
provides the best attenuation of discharge sound. Fiberglass
insulation is packed
between the silencer
casing and the side
pod metal silencer
baffles.
There
is
minimal exposure of
END NOSING
FIBERGLASS
the fiberglass through
MEDIA
PERFORATED
the perforations of the
METAL SIDE POD
metal side baffles.
Meets requirements:
UL 181
FIBERGLASS
NFPA 90A & 90B
ASTM E 84,
C 1071, C 655
FIBERGLASS
MEDIA
MYLAR
FILM
END NOSING
PERFORATED
METAL SIDE POD
ACOUSTICAL
SPACER
FOIL FACED
FIBERGLASS
Mylar/Spacer/Steri-Liner (MSSL)
FIBERGLASS
MEDIA
MYLAR
FILM
END NOSING
PERFORATED
METAL SIDE POD
ACOUSTICAL
SPACER
STERI-LINER
B78
5-3-11
VAV COOLING
DIRECT ACTING THERMOSTAT, NORMALLY OPEN DAMPER
When main control air is off, damper is fully open. Morning warm-up setting
(if required) with warm air from system supplied at full flow rate.
Main control air on controller is activated. Begins modulating cold airflow
on thermostat demand.
Increase in room temperature increases thermostat output pressure (thus
increasing airflow).
Minimum airflow is maintained between 0 and 8 psi thermostat signal.
Further increase in room temperature will increase thermostat signal from 8
to 13 psi which will increase airflow. At 13 psi and above, preset maximum
airflow is maintained.
If main control air fails, damper fails open.
The sequences illustrated feature the Nailor 3000 controller and a constant 5 psi reset span which does not vary with
minimum and maximum settings. For a more detailed explanation of control options and terminology, refer to the
engineering section in the back of this catalog.
MORNING WARM UP
60
40
20
MIN.
8
THERMOSTAT OUTPUT, PSI
TEMPERATURE INCREASE
RESET SPAN 8 13 PSI
15
13
VAV COOLING
REVERSE ACTING THERMOSTAT, NORMALLY OPEN DAMPER
80
MORNING WARM UP
100
60
40
20
MAX.
CLG.
MIN.
0
0
8
THERMOSTAT OUTPUT, PSI
TEMPERATURE DECREASE
RESET SPAN 3 8 PSI
13
15
VAV COOLING
DIRECT ACTING THERMOSTAT, NORMALLY CLOSED DAMPER
100
AIRFLOW, % OF TOTAL CAPACITY
MAX.
CLG.
MAX.
CLG.
80
60
40
MIN.
20
0
0
8
THERMOSTAT OUTPUT, PSI
TEMPERATURE
RESET SPAN 8 13 PSI
13
15
VAV COOLING
REVERSE ACTING THERMOSTAT, NORMALLY CLOSED DAMPER
100
MAX.
CLG.
80
60
40
MIN.
20
0
0
8
THERMOSTAT OUTPUT, PSI
TEMPERATURE
RESET SPAN 3 8 PSI
13
5-5-11
15
B79
When main control air is off, damper is fully open. Morning warm-up setting
available if required.
Main control air on controller is activated. Begins modulating cold airflow
according to thermostat output.
Decrease in room temperature increases thermostat output pressure (thus
decreasing airflow).
Maximum airflow is maintained between 0 and 3 psi thermostat signal.
Further decrease in room temperature will increase thermostat signal from 3
to 8 psi which will decrease airflow to room. At 8 psi and above, minimum
airflow is maintained.
If main control air fails, damper fails open.
80
100
100
MAX.
80
HO
60
W
LO
RF
ATE
TW
40
MIN.
20
0
0
3
8
THERMOSTAT OUTPUT, PSI
TEMPERATURE INCREASE
RESET SPAN 8 13 PSI
13
15
Hot water reheat coils may also be sequenced with 2P3, 3P3 and 4P3.
STEP 2
80
MAX.
60
STEP 1
40
MIN.
20
0
0
8
THERMOSTAT OUTPUT, PSI
TEMPERATURE INCREASE
RESET SPAN 8 13 PSI
13
15
Electric reheat coils may also be sequenced with 2P3, 3P3 and 4P3.
CONSTANT VOLUME
100
AIRFLOW, % OF TOTAL CAPACITY
CONSTANT AIRFLOW
80
60
40
20
0
MAIN CONTROL AIR
100
CONSTANT AIRFLOW
80
60
TER
WA
W
FLO
40
T
HO
20
0
MAIN CONTROL AIR
B80
5-3-11
PROPORTIONAL
BAND
FIXED 2F
(1.1C)
AIRFLOW INCREASE
MAX.
CLG.
MIN. CLG.
+2F
(+1.1C)
SET POINT
Control Sequence 3 EL
Cooling/Heating with Auto Changeover
AIRFLOW INCREASE
PROPORTIONAL
BAND
FIXED 2F
(1.1C)
PROPORTIONAL
BAND
FIXED 2F
(1.1C)
MAX.
CLG.
MAX. HTG.
MIN. CLG.
MIN. HTG.
2F
(1.1C)
HEATING COOLING
SET POINT SET POINT
+2F
(+1.1C)
Control Sequence 4 EL
Cooling with Morning Warm-Up
MAXIMUM FLOW WITH WARM-UP ACTIVATED
AIRFLOW INCREASE
PROPORTIONAL
BAND
FIXED 2F
(1.1C)
MAX.
CLG.
MIN. CLG.
SET POINT
+2F
(+1.1C)
5-3-11
B81
PROPORTIONAL
BAND
FIXED 2F (1.1C)
STAGE
THREE
AIRFLOW INCREASE
DEAD
BAND
PROPORTIONAL
BAND
FIXED 2F (1.1C)
MAX.
CLG.
STAGE
TWO
STAGE
ONE
AUX. MIN.
MIN.
CLG.
HEATING COOLING
SET POINT SET POINT
2F
(1.1C)
+2F
(+1.1C)
Control Sequence 8 EL
Cooling with Proportional Hot Water Reheat and Auxiliary Minimum Flow
AIRFLOW INCREASE
OW
FL
5-3-11
PROPORTIONAL
BAND
FIXED 2F
(1.1C)
MAX.
CLG.
ER
AT
W
B82
AUX. MIN.
DEAD
BAND
PROPORTIONAL
BAND
FIXED 2F
(1.1C)
HO
MIN.
CLG.
2F
(1.1C)
HEATING COOLING
SET POINT SET POINT
+2F
(+1.1C)
2 Row (multi-circuit)
kW MBH
4.4 15
GPM l/s
3 .19
2 .13
1.5 .09
3.8 13
kW MBH
7.3 25
GPM l/s
6.4 22
.19
.13
1.5 .09
.06
5.6 19
3.2 11
0.5 .03
2.6
.06
5.6 16
0.5 .03
4.7 13
2.1
3.8 10
1.5
3
50
24
100
47
150
71
200
94
250
118
300
142
350
165
400
189
450
212
3 Row (multi-circuit)
kW MBH
9.4 32
3
2
.19
.13
1.5 .09
7.6 26
1.2
500 CFM
236 l/s
GPM l/s
8.5 29
2.9
50
24
100
47
150
71
200
94
250
118
300
142
350
165
400
189
450
212
4 Row (multi-circuit)
kW MBH
11.1 38
500 CFM
236 l/s
GPM l/s
.19
.13
10.3 35
9.4 32
1.5 .09
8.5 29
6.7 23
.06
1
7.6 26
5.9 20
.06
6.7 23
5.0 17
0.5 .03
5.9 20
0.5 .03
5.0 17
4.1 14
4.1 14
3.2 11
3.2 11
2.3
1.5
5
50
24
100
47
150
71
200
94
250
118
300
142
350
165
400
189
450
212
500 CFM
236 l/s
2.3
1.5
5
50
24
100
47
150
71
200
94
250
118
300
142
400
189
450
212
500 CFM
236 l/s
NOTES:
1. Capacities are in MBH (kW), thousands of Btu
per hour (kilo Watts).
350
165
Altitude
ft. (m)
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
t F (C) 40 (22)
50 (28)
60 (33)
70 (39)
80 (44)
90 (50)
100 (56) 110 (61) 125 (69) 140 (78) 160 (89) 180 (100)
Factor .320 (.319) .400 (.406) .480 (.478) .560 (.565) .640 (.638) .720 (.725) .800 (.812) .880 (.884) 1.00 (1.00) 1.12 (1.13) 1.28 (1.29) 1.44 (1.45)
11-13-13
B83
0.9
2 Row (multi-circuit)
kW MBH
7.3 25
GPM l/s
6.7 23
6.2 21
5
4
3
.32
.25
.19
.13
1.5 .09
5.6 19
.06
GPM l/s
kW MBH
12.9 44
5
4
.32
.25
.19
.13
12.0 41
11.1 38
10.3 35
1.5 .09
9.4 32
5.0 17
8.5 29
4.4 15
7.6 26
.06
0.5 .03
6.7 23
3.8 13
5.9 20
0.5 .03
3.2 11
5.0 17
2.6
2.1
4.1 14
3.2 11
200
94
300
142
400
189
500
236
600
283
700
330
800
378
900
425
1000 CFM
472 l/s
200
94
3 Row (multi-circuit)
300
142
400
189
500
236
600
283
700
330
800
378
900
425
1000 CFM
472 l/s
4 Row (multi-circuit)
GPM l/s
5 .32
4 .25
kW MBH
16.7 57
15.5 53
.19
13.2 45
.13
12.0 41
1.5 .09
14.4 49
10.8 37
GPM l/s
5 .32
4 .25
kW MBH
19.6 67
18.5 63
.19
14.9 51
.13
13.8 47
1.5 .09
17.3 59
16.1 55
12.6 43
1
9.7 33
.06
11.4 39
.06
10.3 35
8.5 29
9.1 31
7.3 25
0.5 .03
6.2 21
7.9 27
0.5 .03
6.7 23
5.0 17
5.6 19
4.4 15
3.8 13
200
94
300
142
400
189
500
236
600
283
700
330
800
378
900
425
1000 CFM
472 l/s
200
94
300
142
400
189
500
236
600
283
800
378
900
425
1000 CFM
472 l/s
NOTES:
1. Capacities are in MBH (kW), thousands of Btu
per hour (kilo Watts).
700
330
Altitude
ft. (m)
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
t F (C) 40 (22)
50 (28)
60 (33)
70 (39)
80 (44)
90 (50)
100 (56) 110 (61) 125 (69) 140 (78) 160 (89) 180 (100)
Factor .320 (.319) .400 (.406) .480 (.478) .560 (.565) .640 (.638) .720 (.725) .800 (.812) .880 (.884) 1.00 (1.00) 1.12 (1.13) 1.28 (1.29) 1.44 (1.45)
B84
11-13-13
2 Row (multi-circuit)
GPM l/s
7.5 .47
5 .32
8.5 29
.19
.13
kW MBH
17.0 58
GPM l/s
7.5 .47
15.8 54
14.7 50
7.6 26
.32
.19
.13
.09
13.5 46
12.3 42
6.7 23
.09
11.1 38
5.9 20
10.0 34
5.0 17
0.5 .03
8.8 30
7.6 26
4.1 14
6.4 22
3.2 11
4.1 14
8
300
142
400
189
500
236
600
283
700
330
800
378
900
425
300
142
3 Row (multi-circuit)
500
236
600
283
700
330
800
378
900
425
4 Row (multi-circuit)
GPM l/s
7.5 .47
kW MBH
22.3 76
400
189
20.8 71
.32
GPM l/s
7.5 .47
kW MBH
26.4 90
24.9 85
.32
.19
.13
.09
23.4 80
19.3 66
3
17.9 61
.19
22.0 75
20.5 70
16.4 56
.13
19.0 65
14.9 51
17.6 60
13.5 46
16.1 55
14.7 50
12.0 41
1
.09
10.5 36
13.2 45
11.7 40
9.1 31
10.3 35
7.6 26
0.5 .03
8.8 30
6.2 21
7.3 25
4.7 16
5.9 20
300
142
400
189
500
236
600
283
700
330
800
378
900
425
0.5 .03
300
142
400
189
500
236
600
283
700
330
800
378
900
425
NOTES:
1. Capacities are in MBH (kW), thousands of Btu
per hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 125F (69C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
Altitude
ft. (m)
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
t F (C) 40 (22)
50 (28)
60 (33)
70 (39)
80 (44)
90 (50)
100 (56) 110 (61) 125 (69) 140 (78) 160 (89) 180 (100)
Factor .320 (.319) .400 (.406) .480 (.478) .560 (.565) .640 (.638) .720 (.725) .800 (.812) .880 (.884) 1.00 (1.00) 1.12 (1.13) 1.28 (1.29) 1.44 (1.45)
11-13-13
B85
2.3
0.5 .03
5.3 18
2 Row (multi-circuit)
GPM l/s
10 .63
7.5 .47
5 .32
kW MBH
12.9 44
GPM l/s
10 .63
7.5 .47
kW MBH
24.0 82
22.6 77
11.7 40
10.5 36
.19
.13
21.1 72
.32
.19
.13
.09
19.6 67
18.2 62
9.4 32
16.7 57
1
8.2 28
.09
15.2 52
13.8 47
7.0 24
12.3 42
10.8 37
5.9 20
9.4 32
4.7 16
7.9 27
6.4 22
3.5 12
400
189
550
260
700
330
850 1000 1150 1300 1450 1600 1750 1900 2050 2200 CFM
401 472 543 613 684 755 826 897 967 1038 l/s
400
189
3 Row (multi-circuit)
550
260
700
330
850 1000 1150 1300 1450 1600 1750 1900 2050 2200 CFM
401 472 543 613 684 755 826 897 967 1038 l/s
4 Row (multi-circuit)
GPM l/s
10 .63
7.5 .47
kW MBH
32.2 110
30.2 103
28.1 96
.32
.19
26.1 89
GPM l/s
10 .63
7.5 .47
kW MBH
38.1 130
35.2 120
32.2 110
.32
.19
.13
.09
29.3 100
24.0 82
26.4 90
22.0 75
2
19.9 68
.13
23.4 80
20.5 70
17.9 61
17.6 60
15.8 54
14.7 50
13.8 47
.09
11.7 40
11.7 40
9.7 33
8.8 30
5.9 20
7.6 26
400
189
550
260
700
330
850 1000 1150 1300 1450 1600 1750 1900 2050 2200 CFM
401 472 543 613 684 755 826 897 967 1038 l/s
400
189
550
260
700
330
850 1000 1150 1300 1450 1600 1750 1900 2050 2200 CFM
401 472 543 613 684 755 826 897 967 1038 l/s
NOTES:
1. Capacities are in MBH (kW), thousands of Btu
per hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 125F (69C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
Altitude
ft. (m)
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
t F (C) 40 (22)
50 (28)
60 (33)
70 (39)
80 (44)
90 (50)
100 (56) 110 (61) 125 (69) 140 (78) 160 (89) 180 (100)
Factor .320 (.319) .400 (.406) .480 (.478) .560 (.565) .640 (.638) .720 (.725) .800 (.812) .880 (.884) 1.00 (1.00) 1.12 (1.13) 1.28 (1.29) 1.44 (1.45)
B86
11-13-13
2 Row (multi-circuit)
GPM l/s
10 .63
7.5 .47
kW MBH
16.7 57
15.5 53
.32
14.4 49
.19
.13
kW MBH
30.2 103
GPM l/s
10 .63
28.7 98
7.5 .47
27.2 93
.32
.19
.13
.09
25.8 88
24.3 83
13.2 45
22.9 78
21.4 73
12.0 41
19.9 68
10.8 37
18.5 63
1
9.7 33
.09
17.0 58
15.5 53
8.5 29
14.1 48
12.6 43
7.3 25
11.1 38
6.2 21
9.7 33
500
236
700
330
900
425
1100 1300 1500 1700 1900 2100 2300 2500 2700 CFM
519 613 708 802 897 991 1085 1180 1274 l/s
500
236
700
330
3 Row (multi-circuit)
kW MBH
40.1 137
900
425
1100 1300 1500 1700 1900 2100 2300 2500 2700 CFM
519 613 708 802 897 991 1085 1180 1274 l/s
4 Row (multi-circuit)
GPM l/s
10 .63
kW MBH
47.2 161
GPM l/s
10 .63
7.5 .47
44.5 152
7.5 .47
37.8 129
41.9 143
35.5 121
.32
33.1 113
39.3 134
.32
.19
.13
.09
36.6 125
30.8 105
3
28.4 97
.19
34.0 116
31.4 107
26.1 89
28.7 98
23.7 81
.13
26.1 89
21.4 73
23.4 80
19.0 65
20.8 71
16.7 57
18.2 62
1
14.4 49
.09
15.5 53
12.0 41
12.9 44
10.3 35
9.7 33
500
236
700
330
900
425
1100 1300 1500 1700 1900 2100 2300 2500 2700 CFM
519 613 708 802 897 991 1085 1180 1274 l/s
500
236
700
330
900
425
1100 1300 1500 1700 1900 2100 2300 2500 2700 CFM
519 613 708 802 897 991 1085 1180 1274 l/s
NOTES:
1. Capacities are in MBH (kW), thousands of Btu
per hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 125F (69C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
Altitude
ft. (m)
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
t F (C) 40 (22)
50 (28)
60 (33)
70 (39)
80 (44)
90 (50)
100 (56) 110 (61) 125 (69) 140 (78) 160 (89) 180 (100)
Factor .320 (.319) .400 (.406) .480 (.478) .560 (.565) .640 (.638) .720 (.725) .800 (.812) .880 (.884) 1.00 (1.00) 1.12 (1.13) 1.28 (1.29) 1.44 (1.45)
11-13-13
B87
8.2 28
5.0 17
2 Row (multi-circuit)
GPM l/s
10 .63
7.5 .47
kW MBH
19.9 68
18.2 62
.32
kW MBH
36.6 125
GPM l/s
10 .63
34.3 117
7.5 .47
31.9 109
5
.32
.19
.13
.09
29.6 101
16.4 56
3
.19
27.2 93
14.7 50
2
.13
24.9 85
22.6 77
12.9 44
20.2 69
11.1 38
.09
17.9 61
15.5 53
9.4 32
13.2 45
7.6 26
10.8 37
8.5 29
5.9 20
700
330
700
330
950 1200 1450 1700 1950 2200 2450 2700 2950 3200 3450 3700 CFM
448 566 684 802 920 1038 1156 1274 1392 1510 1628 1746 l/s
3 Row (multi-circuit)
950 1200 1450 1700 1950 2200 2450 2700 2950 3200 3450 3700 CFM
448 566 684 802 920 1038 1156 1274 1392 1510 1628 1746 l/s
4 Row (multi-circuit)
kW MBH
48.3 165
GPM l/s
10 .63
45.4 155
7.5 .47
GPM l/s
10 .63
kW MBH
56.5 193
53.6 183
7.5 .47
50.7 173
42.5 145
5
39.6 135
.32
47.8 163
44.8 153
36.6 125
.32
.19
.13
.09
41.9 143
33.7 115
3
30.8 105
.19
39.0 133
36.0 123
33.1 113
27.8 95
2
24.9 85
.13
30.2 103
27.2 93
22.0 75
24.3 83
19.0 65
21.4 73
16.1 55
.09
18.5 63
13.2 45
15.5 53
10.3 35
12.6 43
700
330
950 1200 1450 1700 1950 2200 2450 2700 2950 3200 3450 3700 CFM
448 566 684 802 920 1038 1156 1274 1392 1510 1628 1746 l/s
700
330
950 1200 1450 1700 1950 2200 2450 2700 2950 3200 3450 3700 CFM
448 566 684 802 920 1038 1156 1274 1392 1510 1628 1746 l/s
NOTES:
1. Capacities are in MBH (kW), thousands of Btu
per hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 125F (69C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
Altitude
ft. (m)
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
t F (C) 40 (22)
50 (28)
60 (33)
70 (39)
80 (44)
90 (50)
100 (56) 110 (61) 125 (69) 140 (78) 160 (89) 180 (100)
Factor .320 (.319) .400 (.406) .480 (.478) .560 (.565) .640 (.638) .720 (.725) .800 (.812) .880 (.884) 1.00 (1.00) 1.12 (1.13) 1.28 (1.29) 1.44 (1.45)
B88
11-13-13
kW MBH
39.6 135
10 .63
36.6 125
7.5 .47
33.7 115
5
.32
.19
30.8 105
27.8 95
24.9 85
22.0 75
19.0 65
16.1 55
1
.09
13.2 45
1700
802
2400
1133
3100
1463
3800
1793
4500
2124
5200
2454
5900
2784
6600
3115
7300
3445
8000 CFM
3775 l/s
MBH
240
230
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
1000
472
GPM l/s
15 .95
10 .63
7.5 .47
5
.32
.19
B
1
1700
802
3 Row (multi-circuit)
2400
1133
3100
1463
3800
1793
4500
2124
5200
2454
5900
2784
6600
3115
7300
3445
.09
8000 CFM
3775 l/s
4 Row (multi-circuit)
GPM l/s
15 .95
kW MBH
93.8 320
GPM l/s
15 .95
kW MBH
108.4 370
102.6 350
87.9 300
10 .63
82.0 280
96.7 330
10 .63
90.8 310
76.2 260
7.5 .47
70.3 240
85.0 290
7.5 .47
79.1 270
64.5 220
73.3 250
5
58.6 200
.32
67.4 230
.32
.19
.09
61.5 210
52.7 180
55.7 190
46.9 160
3
41.0 140
.19
49.8 170
44.0 150
35.2 120
38.1 130
29.3 100
32.2 110
23.4 80
26.4 90
1
17.6 60
11.7 40
1000
472
1700
802
2400
1133
3100
1463
3800
1793
4500
2124
5200
2454
5900
2784
6600
3115
7300
3445
.09
8000 CFM
3775 l/s
20.5 70
14.7 50
1000
472
1700
802
2400
1133
3100
1463
3800
1793
4500
2124
5900
2784
6600
3115
7300
3445
8000 CFM
3775 l/s
NOTES:
1. Capacities are in MBH (kW), thousands of Btu
per hour (kilo Watts).
5200
2454
Altitude
ft. (m)
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
t F (C) 40 (22)
50 (28)
60 (33)
70 (39)
80 (44)
90 (50)
100 (56) 110 (61) 125 (69) 140 (78) 160 (89) 180 (100)
Factor .320 (.319) .400 (.406) .480 (.478) .560 (.565) .640 (.638) .720 (.725) .800 (.812) .880 (.884) 1.00 (1.00) 1.12 (1.13) 1.28 (1.29) 1.44 (1.45)
11-13-13
B89
10.3 35
1000
472
kW
113
109
104
99
94
90
85
80
76
71
66
61
57
52
47
42
38
33
28
21
19
17.9 6.0
149 0.60
17.9 6.0
149 0.60
100 0.40
3 ROW
4 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
3 ROW
6.0 2.0
50 0.20
2 ROW
25 0.10
20 0.08
15 0.06
1 ROW
10 0.04
5 0.02
0.6 0.2
2 0.01
0.3 0.1
2
4
6 8 10 GPM
.13
.25 .38 .50.63l/s
WATER FLOW
4 ROW
1 ROW
2 ROW
6.0 2.0
3 ROW
4 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
500 CFM
236 l/s
200
300
94
142
AIRFLOW
2
4
6 8 10 GPM
.13
.25 .38 .50.63l/s
WATER FLOW
17.9 6.0
497 2.0
3 ROW
4 ROW
6.0 2.0
1.2 0.4
249 1.0
199 0.8
149 0.6
99 0.4
4 ROW
3 ROW
50 0.2
2 ROW
1 ROW
25 0.1
20 0.08
15 0.06
10 0.04
0.6 0.2
994 4.0
1 ROW
497 2.0
2 ROW
6.0 2.0
3 ROW
4 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
249 1.0
199 0.8
149 0.6
2
4
6 8 10 GPM
.13
.25 .38 .50 .63 l/s
WATER FLOW
50 0.2
1 ROW
25 0.1
20 0.08
15 0.06
10 0.04
0.6 0.2
0.3 0.1
100
47
200
94
2 0.01
1
.06
2
4
6 8 10 GPM
.13
.25 .38 .50 .63 l/s
WATER FLOW
NOTES:
1. Capacities are in MBH (kW), thousands of Btu
per hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 110F (61C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
B90
8-29-11
3 ROW
2 ROW
5 0.02
2 0.01
0.3 0.1
4 ROW
99 0.4
5 0.02
1
.06
1000CFM
472 l/s
200
400 600
94
189 283
AIRFLOW
11.9 4.0
2 ROW
1.8 0.6
100
47
994 4.0
3.0 1.0
2.4 0.8
1 ROW
10 0.04
2 0.01
1
.06
1 ROW
11.9 4.0
15 0.06
Unit Size 12
Pa in. H2O
2486 10.0
1989 8.0
1492 6.0
17.9 6.0
20 0.08
0.3 0.1
100
47
2 ROW
25 0.10
5 0.02
3 ROW
50 0.20
0.6 0.2
1
.06
100 0.40
11.9 4.0
4 ROW
2 ROW
1 ROW
Pa in. H2O
249 1.00
199 0.80
11.9 4.0
100
47
200
94
3000 CFM
1416 l/s
Pa in. H2O
2486 10.0
1989 8.0
1492 6.0
17.9 6.0
994 4.0
11.9 4.0
497 2.0
2 ROW
6.0 2.0
3 ROW
4 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
249 1.0
199 0.8
149 0.6
4 ROW
3 ROW
99 0.4
50 0.2
2 ROW
25 0.1
20 0.08
15 0.06
10 0.04
1 ROW
0.6 0.2
1 ROW
497 2.0
2 ROW
6.0 2.0
3 ROW
4 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
11.9 4.0
17.9 6.0
994 4.0
1 ROW
Unit Size 16
1 ROW
25 0.1
20 0.08
15 0.06
10 0.04
0.6 0.2
0.3 0.1
100
47
200
94
3000 CFM
1416 l/s
2 0.01
1
.06
2
4
6 8 10 GPM
.13
.25 .38 .50.63l/s
WATER FLOW
100
47
200
94
Unit Size 24 x 16
Water Pressure Drop
kPa ft. H2O
29.8 10.0
23.9 8.0
497 2.0
1 ROW
2 ROW
6.0 2.0
3 ROW
4 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
17.9 6.0
11.9 4.0
249 1.0
199 0.8
149 0.6
4 ROW
99 0.4
3 ROW
50 0.2
2 ROW
25 0.1
20 0.08
15 0.06
1 ROW
10 0.04
0.6 0.2
5 0.02
2 0.01
0.3 0.1
1
.06
2
4 6 8 10
20 GPM
.13
.25 .38 .50.63 1.26 l/s
WATER FLOW
NOTES:
1. Capacities are in MBH (kW), thousands of Btu
per hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 110F (61C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
8-29-11
B91
2
4
6 8 10 GPM
.13
.25 .38 .50.63l/s
WATER FLOW
2 ROW
50 0.2
5 0.02
2 0.01
1
.06
3 ROW
99 0.4
5 0.02
0.3 0.1
4 ROW
249 1.0
199 0.8
149 0.6
Model 30RE
Selection Guidelines:
The table above provides a general guideline as to the
voltages and maximum kilowatts available for each terminal
unit size. Up to three stages of heat are available. A
minimum of 0.5 kW/stage is required.
For optimum diffuser performance and maximum thermal
comfort, ASHRAE recommends that discharge temperatures
do not exceed 15F (8C) above room set point, as
stratification and short circuiting may occur. ASHRAE
Standard 62.1 limits discharge temperatures to 90F (32C)
Unit
Size
Heating Range*
cfm (l/s)
120V
4
5
6
7
8
9
10
12
14
16
24 x 16
3.0
5.0
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
Single Phase
208V 240V 277V
3.0
5.0
7.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
3.0
5.0
7.5
9.5
11.0
11.0
11.0
11.0
11.0
11.0
11.0
3.0
5.0
7.5
9.5
13.0
13.0
13.0
13.0
13.0
13.0
13.0
347V
3.0
5.0
7.5
9.5
13.0
16.0
16.5
16.5
16.5
16.5
16.5
Three Phase
208V 480V 600V
3.0
5.0
7.5
9.5
13.0
16.0
17.0
17.0
17.0
17.0
17.0
3.0
5.0
7.5
9.5
13.0
16.0
21.0
30.0
31.0
31.0
31.0
3.0
5.0
7.5
9.5
13.0
16.0
21.0
30.0
38.5
38.5
38.5
Options:
Mercury contactors.
Toggle type disconnect
switch.
Door interlock disconnect
switch.
Power circuit fusing.
Dust tight construction.
SCR control.
Class 'A' 80/20 wire.
* * Minimum airflow must be the greater of the air volume listed or 70 cfm per kilowatt (33 L/s/kW)
Standard Features:
Primary auto-reset high limit thermal cut-out (one per coil in
control circuit).
Secondary manual reset high limit thermal cut-outs (one per
element).
Positive pressure airflow switch.
Derated high quality nickel-chrome alloy heating elements.
Magnetic or safety contactors and / or PE switches as
required.
B92
5-3-11
ANSI/UL
1996, 4th ed.
CSA C22.2
No. 155-M1986.
C1
Contents
Page No.
Model Series 3200
Product Overview
3210
C4
C5
C6
C7
C8
C9
C10
C11
3230
C12
C13
C14
C15
C16
C17
C18
C19
3240
C22
C23
C24
C25
C26
C27
C28
C29
C2
C3
6-26-13
C32
C33
C35
C36
C37
C39
C
3210
3230
3240
4-21-11
C3
Opposed
blade valve
configuration minimizes
noisy turbulence and
provides smooth,
accurate, near linear
flow control.
Model:
3210
Without Attenuator
Model 3210
Nailor model 3210 is an economical dual duct terminal ideal for non-mixing variable volume applications. Constructed as
two single ducts, the 3210 consists of a dedicated hot and cold deck. The decks work in tandem to regulate the cold and
hot airstreams to provide precise volume and temperature control for the conditioned zone. Each inlet contains a standard
Diamond Flow Sensor for pressure independent operation.
STANDARD 3210 FEATURES:
22 ga. (0.86) zinc coated steel
casing, mechanically sealed, low
leakage construction.
16 ga. (1.63) corrosion-resistant
steel inclined opposed blade dampers
with extruded PVC seals (single blade
on size 4, 5, 6). 45O rotation, CW to
close. Tight close-off. Damper
leakage is less than 2% of the
terminal rated airflow at 3" wg (750
Pa).
1/2" (13) dia. plated steel drive
shaft. An indicator mark on the end of
the shaft shows damper position.
Multi-point averaging Diamond
Flow Sensors in each inlet. Aluminum
construction. Supplied with balancing
tees.
C4
4-21-11
field
15 1/2" (394)
14 1/2" (368)
5 1/2"
(140)
6 1/2"
(165)
Pneumatic
Controls
MULTI-POINT
AVERAGING
FLOW SENSOR
Universal
pneumatic control
mounting panel
features double wall
stand-off
construction for
strength and rigidity.
Controls mounting
screws do not
penetrate casing.
DAMPER
DRIVE
SHAFT
HOT
AIR INLET
ROUND OR
FLAT OVAL
INLET COLLARS
COLD
AIR INLET
5 3/4"
(146)
SLIP AND DRIVE
DAMPER
DRIVE SHAFT CONNECTION
PLAN VIEW
UNIVERSAL PNEUMATIC
CONTROL MOUNTING PANEL
AND PROTECTIVE SHROUD
Analog Electronic
and Digital
Controls
A full NEMA 1
controls enclosure is
provided for factory
mounted controls.
Optional for field
mounted controls.
5 1/2"
(140)
11" (279)
15 1/2" (394)
14" (356)
MULTI-POINT
AVERAGING
FLOW SENSOR
DAMPER
DRIVE
SHAFT
HOT
AIR INLET
ROUND OR
FLAT OVAL
INLET COLLARS
COLD
AIR INLET
6"
(152)
CONTROLS ENCLOSURE
FOR FACTORY MOUNTED
CONTROLS
DAMPER
DRIVE SHAFT
PLAN VIEW
Dimensional Data
Unit Size
4
5
6
7
8
9
10
12
14
16
W
21 (533)
21 (533)
21 (533)
25 (635)
25 (635)
29 (737)
29 (737)
37 (940)
49 (1245)
57 (1448)
H
10 (254)
10 (254)
10 (254)
12 12 (318)
12 12 (318)
12 12 (318)
12 12 (318)
12 12 (318)
12 12 (318)
12 12 (318)
A
11 (279)
11 (279)
11 (279)
13 (330)
13 (330)
15 (381)
15 (381)
19 (483)
25 (635)
29 (737)
Inlet Size
3 7/8 (98) Round
4 7/8 (124) Round
5 7/8 (149) Round
6 7/8 (175) Round
7 7/8 (200) Round
8 7/8 (225) Round
9 7/8 (251) Round
12 1516 x 9 1316 (329 x 249) Oval
16 116 x 9 1316 (408 x 249) Oval
19 316 x 9 1316 (487 x 249) Oval
4-21-11
C5
Model 3210
4
5
6
7
8
9
10
12
14
16
Total
Airflow
Range
cfm
Airflow at
2000 fpm Inlet
Velocity (nom.)
cfm
0 225
0 350
0 500
0 650
0 900
0 1050
0 1350
0 2000
0 2700
0 3500
150
250
400
550
700
900
1100
1600
2100
2800
Pneumatic
3000 Controller
Min.
30
55
80
115
155
200
260
355
440
525
180
325
450
650
900
1050
1350
2000
2550
3040
25
45
65
95
125
165
215
290
360
430
180
325
450
650
900
1050
1350
2000
2550
3040
25
45
65
95
125
165
215
290
360
430
180
325
450
650
900
1050
1350
2000
2550
3040
200
350
500
650
900
1050
1350
2000
2700
3390
225
350
500
650
900
1050
1350
2000
2700
3500
4
5
6
7
8
9
10
12
14
16
C6
4-21-11
Total
Airflow
Range
l/s
Airflow at
10.2 m/s Inlet
Velocity (nom.)
l/s
0 106
0 165
0 236
0 307
0 425
0 495
0 637
0 944
0 1274
0 1652
71
118
189
260
330
425
519
755
991
1321
Pneumatic
3000 Controller
Min.
14
26
38
54
73
94
123
168
208
248
85
153
212
307
425
495
637
944
1203
1435
12
21
31
45
59
78
101
137
170
203
85
153
212
307
425
495
637
944
1203
1435
12
21
31
45
59
78
101
137
170
203
85
153
212
307
425
495
637
944
1203
1435
94
165
236
307
425
495
637
944
1274
1600
106
165
236
307
425
495
637
944
1274
1652
10
12
14
16
Min. inlet
Ps
Performance Notes:
1. NC Levels are calculated based on procedures as outlined on
page C32
2. Dash (-) in space indicates a NC less than 20.
4-12-13
C7
Min. inlet
Ps
"w.g. Pa
0.14 35
0.11 27
0.06 15
0.03 7
0.01 2
0.01 2
0.05 12
0.04 10
0.03 7
0.02 5
0.01 2
0.01 2
0.11 27
0.09 22
0.07 17
0.04 10
0.02 5
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.04 10
0.03 7
0.02 5
0.02 5
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
Minimum Ps
2 3 4 5 6 7
- 49 53 57 48 43
- 48 53 57 48 43
- 43 47 49 39 35
- - 38 37 27 - - 32 28 - - - - - - 54 58 53 57 49 47
53 57 54 57 49 47
- 48 49 51 42 40
- 43 44 44 34 32
- - 33 30 - - - 30 25 - 56 53 54 60 48 45
56 53 53 59 48 45
54 50 49 54 44 40
- 44 41 46 35 31
- - 30 32 - - - - - - 58 57 62 59 51 48
56 53 56 53 46 42
51 41 41 38 29 22
- - 30 26 - - - - - - 58 55 59 58 51 44
58 55 59 58 51 44
57 53 56 56 48 40
54 51 51 50 42 32
- 40 40 38 29 - - - - - 57 55 60 59 54 48
54 53 54 54 48 41
- 45 46 45 39 30
- - 33 30 - - - - - - 55 54 59 59 54 51
52 48 52 52 47 43
- 42 45 44 38 33
- - 31 28 - - - - - - 60 58 62 61 56 53
55 50 54 53 48 44
50 44 46 44 38 34
47 37 36 33 28 - - - - - 62 60 66 64 60 54
56 56 58 55 51 44
50 44 48 46 41 33
- 36 36 32 27 - - - - - 62 60 66 64 60 54
58 55 56 58 54 48
52 47 51 49 44 38
- 38 39 35 30 - - 25 23 - -
For full performance table notes, see page C10; RED highlighted numbers indicate embedded AHRI certification points.
C8
4-12-13
For full performance table notes, see page C10; RED highlighted numbers indicate embedded AHRI certification points.
4-12-13
C9
Min. inlet
Inlet Airflow
Ps
Size cfm l/s "w.g. Pa
225 106 0.14 35
200 94 0.11 27
150 71 0.06 15
4
100 47 0.03 7
75 35 0.01 2
50 24 0.01 2
350 165 0.05 12
300 142 0.04 10
250 118 0.03 7
5
200 94 0.02 5
125 59 0.01 2
100 47 0.01 2
500 236 0.11 27
450 212 0.09 22
400 189 0.07 17
6
300 142 0.04 10
200 94 0.02 5
100 47 0.01 2
650 307 0.01 2
550 260 0.01 2
7 335 158 0.01 2
225 106 0.01 2
110 52 0.01 2
900 425 0.04 10
800 378 0.03 7
700 330 0.02 5
8
600 283 0.02 5
400 189 0.01 2
175 83 0.01 2
1050 495 0.01 2
900 425 0.01 2
9 675 319 0.01 2
450 212 0.01 2
225 106 0.01 2
1350 637 0.01 2
1100 519 0.01 2
10 825 389 0.01 2
550 260 0.01 2
275 130 0.01 2
2000 944 0.01 2
1600 755 0.01 2
12 1200 566 0.01 2
800 378 0.01 2
400 189 0.01 2
2700 1274 0.01 2
2100 991 0.01 2
14 1550 731 0.01 2
1050 495 0.01 2
525 248 0.01 2
3500 1652 0.01 2
2800 1321 0.01 2
16 2100 991 0.01 2
1400 661 0.01 2
700 330 0.01 2
4
5
6
7
8
9
10
12
14
16
Airflow
Min. Inlet
Ps
cfm l/s
" w.g. Pa
0.24
0.08
0.05
0.08
0.01
0.01
0.01
0.01
0.01
0.05
69
71
74
78
79
78
77
79
80
82
68
72
75
73
73
73
72
74
74
75
150
250
400
550
700
900
1100
1600
2100
2800
71
118
189
260
330
425
519
755
991
1321
61
20
12
21
2
2
2
2
2
12
Octave Band
4
5
6
62
63
66
68
68
68
68
71
73
72
58
61
64
65
65
65
66
70
72
69
51
51
53
59
58
59
59
63
65
63
48
48
50
55
54
56
56
59
60
59
49
55
59
61
61
60
60
61
63
65
50
48
52
54
53
54
54
58
61
63
C10
2-12-15
Octave Band
4
5
6
47
45
47
49
50
49
50
53
55
57
39
35
40
43
40
44
45
49
48
50
31
35
36
36
39
39
39
42
44
44
30
30
33
33
35
36
36
39
43
39
2 The terminal units shall be provided with two primary variable air
volume dampers that control the air quantity in response to a
(pneumatic, electric, analog electronic, or DDC) thermostat. The
space limitations shall be reviewed carefully to insure that all units
will fit into the space allowed.
3 Unit casing shall be 22 ga. (.86) galvanized steel with round or flat
oval inlets with 5 12" (140 mm) deep inlet duct collar for field
connection. Outlets shall be rectangular and configured for slip and
drive connections. Casing leakage downstream of the damper shall
not exceed 1% at 1" w.g. (250 Pa) of terminal.
4-21-11
C11
7 Each unit shall be internally lined with 34" (19) dual density
fiberglass insulation. Edges shall be sealed against airflow erosion.
Units shall meet NFPA 90A and UL 181 standards.
Model:
3230
With Compact
Mixing Attenuator
Model 3230
When blending of hot and cold air is required, the Model 3230 comes with an integral compact mixing attenuator section which
provides some attenuation of discharge noise and through the use of internal baffles, mixing of the hot and cold airstreams. The
compact design of the 3230 lends itself to applications where there are tight space limitations, while still meeting or exceeding
industry standard sound and mixing requirements. Minimum mixing efficiency is 1 in 12. That means there is less than a 1F
(0.55C) temperature variation at the discharge for each 12F (6.66C) temperature difference between the hot and cold decks.
C12
4-21-11
Options:
24 VAC Control transformer.
Toggle disconnect switch.
Steri-liner.
Fiber-free liner.
Solid metal liner.
1" (25) liner.
Bottom access door (Model 0800M1)
Controls enclosure for field
mounted controls.
Dust tight enclosure seal.
Hanger brackets.
6 1/2"
(165)
Pneumatic
Controls
MULTI-POINT
AVERAGING
FLOW SENSOR
DAMPER
DRIVE
SHAFT
HOT
D
AIR INLET
ROUND
INLET
COLLARS
A
COLD
MIXING
ATTENUATOR
10"
(254)
DW 1/8" (3)
AIR INLET
RECTANGULAR
DISCHARGE
5 3/4"
(146)
UNIVERSAL PNEUMATIC
CONTROL MOUNTING PANEL
AND PROTECTIVE SHROUD
DAMPER
DRIVE SHAFT
OPTIONAL
ACCESS DOOR
18" X 10" (457 X 254)
PLAN VIEW
11" (279)
Analog Electronic
and Digital
Controls
MULTI-POINT
AVERAGING
FLOW SENSOR
HOT
DH
DH(3)
- 1/8"
- 1/8" (3)
W/ TOTAL
DISCHARGE SENSOR
14" (356)
DAMPER
DRIVE
SHAFT
AIR INLET
ROUND OR
FLAT OVAL
NLET COLLARS
A
COLD
MIXING
ATTENUATOR
10"
(254)
DW 1/8" (3)
AIR INLET
RECTANGULAR
DISCHARGE
6"
(152)
CONTROLS ENCLOSURE
FOR FACTORY MOUNTED
CONTROLS
DAMPER
DRIVE SHAFT
DH
DH(3)
- 1/8"
- 1/8" (3)
OPTIONAL
ACCESS DOOR
18" X 10" (457 X 254)
PLAN VIEW
W/ TOTAL
DISCHARGE SENSOR
Dimensional Data
Unit
Size
4
5
6
7
8
9
10
12
14
16
24 (610)
24 (610)
24 (610)
24 (610)
24 (610)
34 (864)
34 (864)
34 (864)
42 (1067)
42 (1067)
10 (254)
10 (254)
10 (254)
12 12 (318)
12 12 (318)
14 (356)
14 (356)
16 (406)
18 (457)
18 (457)
24 (610)
24 (610)
24 (610)
24 (610)
24 (610)
34 (864)
34 (864)
34 (864)
38 (965)
38 (965)
11 (279)
11 (279)
11 (279)
11 (279)
11 (279)
16 18 (410)
16 18 (410)
16 18 (410)
20 18 (511)
20 18 (511)
Inlet Dia.
D
3 78 (98)
4 78 (124)
5 78 (149)
6 78 (175)
7 78 (200)
8 78 (225)
9 78 (251)
11 78 (302)
13 78 (353)
15 78 (403)
Outlet
DW x DH
8 x 8 (203 x 203)
10 x 10 (254 x 254)
14 x 12 (356 x 305)
18 x 14 (457 x 356)
22 x 16 (559 x 406)
24 x 18 (610 x 457)
6-30-14
C13
Universal
pneumatic control
mounting panel
features double
wall stand-off
construction for
strength and rigidity.
Controls mounting
screws do not
penetrate casing.
A full NEMA 1
controls enclosure
is provided for
factory mounted
controls. Optional
for field mounted
controls.
2"
(51)
14 1/2" (368)
4
5
6
7
8
9
10
12
14
16
Total
Airflow
Range
cfm
Airflow at
2000 fpm Inlet
Velocity (nom.)
cfm
0 225
0 350
0 500
0 650
0 900
0 1050
0 1350
0 2050
0 2740
0 3680
150
250
400
550
700
900
1100
1600
2100
2750
Pneumatic
3000 Controller
Min.
30
55
80
115
155
200
260
355
475
640
180
325
450
650
900
1050
1350
2050
2740
3680
25
45
65
95
125
165
215
290
390
520
180
325
450
650
900
1050
1350
2050
2740
3680
25
45
65
95
125
165
215
290
390
520
180
325
450
650
900
1050
1350
2050
2740
3680
200
350
500
650
900
1050
1350
2050
2740
3680
225
350
500
650
900
1050
1350
2050
2740
3680
4
5
6
7
8
9
10
12
14
16
C14
4-21-11
Total
Airflow
Range
l/s
Airflow at
10.2 m/s Inlet
Velocity (nom.)
l/s
0 106
0 165
0 236
0 307
0 425
0 495
0 637
0 967
0 1293
0 1737
71
118
189
260
330
425
519
755
991
1298
Pneumatic
3000 Controller
Min.
14
26
38
54
73
94
123
168
224
302
85
153
212
307
425
495
637
967
1293
1737
12
21
31
45
59
78
101
137
184
245
85
153
212
307
425
495
637
967
1293
1737
12
21
31
45
59
78
101
137
184
245
85
153
212
307
425
495
637
967
1293
1737
94
165
236
307
425
495
637
967
1293
1737
106
165
236
307
425
495
637
967
1293
1737
10
12
14
16
Min. inlet
Ps
Performance Notes:
1. NC Levels are calculated based on procedures as documented on page C32.
2. Dash (-) in space indicates a NC less than 20.
4-21-11
C15
10
12
14
16
200 94
150 71
100 47
75 35
50 24
300 142
250 118
200 94
125 59
75 35
500 236
400 189
300 142
200 94
100 47
650 307
550 260
335 158
225 106
110 52
850 401
700 330
500 236
350 165
200 94
1050 495
900 425
675 319
450 212
225 106
1350 637
1100 519
800 378
500 236
250 118
1950 920
1600 755
1200 566
800 378
400 189
2700 1274
2100 991
1600 755
1050 495
550 260
3425 1616
2750 1298
2050 967
1375 649
700 330
Min. inlet
Ps
"w.g. Pa
0.11 27
0.06 15
0.03 7
0.02 5
0.01 2
0.22 55
0.15 37
0.10 25
0.04 10
0.01 2
0.49 122
0.31 77
0.17 42
0.07 17
0.02 5
0.48 119
0.33 82
0.11 27
0.05 12
0.01 2
0.71 177
0.47 117
0.23 57
0.11 27
0.03 7
0.31 77
0.22 55
0.11 27
0.04 10
0.01 2
0.48 119
0.31 77
0.16 40
0.07 17
0.01 2
0.75 186
0.49 122
0.26 65
0.11 27
0.03 7
0.63 157
0.37 92
0.21 52
0.08 20
0.02 5
1.05 261
0.66 164
0.37 92
0.16 40
0.04 10
2
51
49
48
58
52
50
49
66
60
54
51
62
59
49
68
62
50
49
61
60
50
47
50
70
61
52
48
50
73
68
59
51
76
70
60
50
75
70
61
51
-
Min. Ps
3 4 5 6 7
45 37 30 23 43 34 27 - 34 23 - - - - - - - - - - 54 48 42 33 30
46 39 32 25 44 36 29 - 35 25 - - - - - - 62 55 50 44 40
56 50 44 35 32
48 41 34 27 37 28 - - - - - - 61 52 46 41 37
58 49 43 38 34
45 36 30 25 6
33 - - - 30 - - - 68 58 53 48 45
61 52 46 41 37
49 39 33 29 23
45 36 30 25 6
33 - - - 56 49 41 37 34
55 48 40 36 33
40 32 28 22 33 24 - - 33 - - - 64 57 48 45 43
56 49 41 37 34
45 38 28 22 35 26 - - 33 - - - 71 60 54 50 48
64 55 47 44 42
54 46 38 35 33
43 34 28 25 34 25 - - 68 61 55 52 49
61 54 48 45 42
51 45 39 35 30
40 34 27 - 32 24 - - 71 64 59 56 53
64 58 53 49 46
53 48 44 39 34
43 39 33 28 23
33 24 - - -
For full performance table notes, see page C18; RED highlighted numbers indicate embedded AHRI certification points.
C16
6-21-13
Minimum Ps
2 3 4 5 6 7
- 34 32 26 28 - 32 29 23 57 - - 27 24 23 - - - 20 - - - - - - 47 41 37 32 30 26
- 35 34 28 30 - 33 31 25 - - - 29 26 25 - - - - - 56 49 46 39 36 33
49 43 39 34 32 28
- 37 36 30 32 - - 32 29 29 - - - - - 57 52 42 36 30 54 49 39 33 27 - - 25 - - - - - - - - - - - - 59 56 45 40 37 32
57 52 42 36 30 50 42 33 28 - - - 25 - - - - - - - 55 49 42 39 33 25
54 48 41 38 32 24
45 40 34 31 - - - - - - - - - - - 60 55 48 45 39 33
55 49 42 39 33 25
45 40 34 31 - - - - - - - - - - - 64 60 51 50 46 40
58 53 47 46 41 33
50 45 40 38 31 - 37 32 28 - - - - - - 64 56 48 40 36 33
58 49 42 36 31 28
51 41 35 29 - - - - - - - - - 30 - 67 63 52 47 45 41
62 56 47 43 40 36
55 46 40 35 31 26
- - 30 26 - - - - - - -
For full performance table notes, see page C18; RED highlighted numbers indicate embedded AHRI certification points.
6-26-13
C17
Inlet Airflow
Size cfm l/s
200 94
150 71
4 100 47
75 35
50 24
300 142
250 118
5 200 94
120 59
75 35
500 236
400 189
6 300 142
200 94
100 47
650 307
550 260
7 335 158
225 106
110 52
850 401
700 330
8 500 236
350 165
200 94
1050 495
900 425
9 675 319
450 212
225 94
1350 637
1100 519
10 800 378
500 260
250 118
1950 920
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1600 755
1050 496
550 260
3425 1617
2750 1298
16 2050 968
1375 649
700 330
Airflow
4
5
6
7
8
9
10
12
14
cfm
150
250
400
550
700
900
1100
1600
2100
l/s
71
118
189
260
330
425
519
755
991
16
2750 1321
62
C18
6-20-13
51
46
43
40
Section 15840
The following specification is recommended where an
independent laboratory test and performance verification is
required.:
PART 1 GENERAL
1.01 RELATED DOCUMENTS
A. The requirements of the General Conditions, Supplementary
Conditions and the following specification sections apply to all Work
herein:
1. Section 15 - - - General.
2. Section 15 - - - Scope of Work.
3. Section 15 - - - Design Conditions.
4. Section 15 - - - Electric Motors and Controllers.
5. Section 15 - - - Access Doors and Color Coded.
Identification in General Construction.
6. Section 15 - - - Ductwork and Sheet Metal.
7. Section 15 - - - Testing, Balancing and Adjusting.
1.02 SUMMARY
A. Furnish and install all air terminal units herein specified and as
indicated on the Drawings.
1.03 REFERENCE STANDARDS
A. All air terminal units shall be designed, manufactured and tested
in accordance with the latest applicable industry standards
including the following:
1. ANSI/ASHRAE Standard 130-08.
2. AHRI Standard 880-08.
3. Underwriters Laboratories UL Standard 1995.
4. Underwriters Laboratories UL Standard 1996.
1.04 QUALITY ASSURANCE
A. All equipment and material to be furnished and installed on this
Project shall be UL or ETL listed, in accordance with the
requirements of the Authority having jurisdiction and suitable for its
intended use on this Project. Space limitations shall be reviewed to
ensure that the equipment will fit into the space allowed.
B. All equipment and material to be furnished and installed on this
Project shall be run tested at the factory and results of that testing
shall be tabulated and provided to the engineer when the equipment
ships to the job site. See paragraph 2.03 G for specific
requirements.
1.05 SUBMITTALS
A. The following submittal data shall be furnished according to the
Conditions of the Construction Contract, Division 1 Specifications
and Section 15 - - - General and shall include but not be limited to:
1. Dual Duct Variable Air Volume Terminal Units, complete with
capacity data, test data, construction details, physical dimensions,
electrical characteristics, etc.
1.06 ACOUSTICS
This acoustical specification describes sound power levels as
tested to AHRI 880 and ASHRAE 130.
A. Sound Power Acoustical Performance:
1. Discharge Noise: Maximum permissible sound power levels in
octave bands of discharge sound through discharge ducts from
terminal units operated at an inlet pressure of 1.0" w.g. (250 Pa) and
the maximum amount of air volume shown on the Project
Mechanical Drawings leaving the terminal unit and entering the
reverberant chamber shall be as follows:
Octave Band
2
3
4
5
6
7
NC-35
67
64
67
66
67
67
NC-40
71
69
72
71
72
72
Table 1.
Maximum Discharge
Sound Power Levels
(dB re 10-12 Watts).
4-21-11
C19
Octave Band
2
3
4
5
6
7
Table 2.
NC-35
64
57
53
50
50
53
NC-40
68
62
58
55
55
58
1.07 WARRANTY
A. Manufacturer shall warrant equipment for one year from start up
or 18 months from shipment.
PART 2 - PRODUCTS
2.01 UNAUTHORIZED MATERIALS
A. Materials and products required for the work of this section shall
not contain asbestos, polychlorinated biphenyls (PCB) or other
hazardous materials identified by the Engineer or Owner.
2.02 ACCEPTABLE MANUFACTURERS
A. These Specifications set forth the minimum requirements for dual
duct VAV terminal units. If they comply with these Specifications,
dual duct VAV terminal units manufactured by one of the following
manufacturers will be acceptable:
1. Nailor Industries.
2.03 DUAL DUCT VARIABLE AIR VOLUME TERMINAL UNITS
A. Furnish and install dual duct VAV terminal units as indicated on
the Drawings. The units shall be designed and built as a single unit
and provided with two primary variable air volume dampers that
control the primary cold and warm air quantity in response to a
temperature control signal. The damper construction shall be
rectangular with multiple opposed blades designed to operate on a
90 arc. Blades shall be extruded aluminum, single thickness
construction with heavy-duty gasket for tight shut-off. Units shall be
suitable for pressure independent control with [pneumatic, analog
electronic or electronic DDC] controls. The space limitations shall
be reviewed carefully to ensure all terminal units will fit into the
space provided including National Electric Code clearances
required in front of all panels containing electrical devices. Unit
casings shall be of minimum 20 ga. (1.00) galvanized steel.
Removable access doors rated for high pressure and low leakage
shall be factory installed in the mixing section of the unit and shall
provide access to service all internal components. Unit shall be fully
lined with at least 34" (19) thick, fiberglass board type insulation
completely encapsulated between solid outer and foil inner liners,
which comply with NFPA 90 for fire and smoke resistivity and UL
181 for erosion. Casing leakage shall not exceed 1% of terminal
rated airflow at 6" w.g. (1492) interior casing pressure. All high side
casing joints shall be sealed with approved sealant and high side
casing and damper leakage shall not exceed 1% of terminal rated
airflow at 6" w.g. (1492).
Terminal unit manufacturer shall provide flow curves for the air
sensors at both inlets and/or at the outlet, as required, clearly
labeled and permanently attached on the bottom or side of each
terminal unit.
C20
4-21-11
4-21-11
C21
Opposed
blade valve
configuration minimizes
noisy turbulence and
provides smooth,
accurate, near linear
flow control.
SQUARE
SQUAREROUND
ROUNDNECK
NECK
3200 SERIES
"BLENDMASTER"
1 : 30 MIXING
Lorem
INDUSTRY
LEADING
ipsum
dolor sit
PERFORMANCE
amet, consectetuer
adipiscing elit.
Model:
Sed diam nonummy nibh
3240 With
Highut
Efficiency
euismod
tincidunt
Mixing
Attenuator
laoreet dolore
magna
aliquam erat volutpat. Ut
ner
Steri-Li ce
wisi enim ad minim
an
Perform
Tested
is nostrud exerc
Model
3240 tincidunt ut laoreet dolore magna
Lorem ipsum dolor sit amet, consectetuer adipiscing elit, sed diam nonummy nibh
euismod
aliquam erat volutpat. Ut wisi enim ad minim veniam, quis nostrud exerci tation ullamcorper suscipit lobortis nisl ut aliquip ex ea
commodo
consequat.
The model
3240 "BlendMasterTM" is a dual duct terminal unit offering superior performance for the most demanding
Maintaining
high
rates,tation
humidity
controlsuscipit
and achieving
high
in the pursuit
of
Utapplications.
wisi enim ad minim
veniam,
quisventilation
nostrud exerci
ullamcorper
lobortis nisl
ut comfort
aliquip exlevels
ea commodo
consequat.
improved
indoor
quality
regenerated
interest
in esse
the benefits
a dual duct
design.
Duis
autem vel
eumair
iriure
dolorhave
in hendrerit
in vulputate
velit
molestieofconsequat,
velsystem
illum dolore
euApplications
feugiat nulla include
facilisis at
hospitals,
research laboratories,
schools and
other institutional
facilities
where
both
overhead
heating
and cooling
are
vero
eros et accumsan
et iusto odio dignissim
qui blandit
praesent luptatum
zzril
delenit
augue
duis dolore
te feugait
nulla facilisi.
required and a dual duct design has been deemed the preferred system.
Equipped with specially designed low leakage opposed blade dampers, the "BlendMasterTM" provides accurate airflow
control of the hot and cold decks with tight shut-off. An extended integral mixer attenuator section provides superior
Duis autem
vel eum
iriure dolor
in
qui mixing
blandit praesent
luptatum
zzril operating
Lorem
ipsumofdolor
blending
the sit
hotamet,
and cold airflow during
at reduced
minimum
pressures
compared
to other
hendrerit
in vulputate
velit essemixing
delenitflow
augue
duistemperature
dolore te feugait
consectetuer
adipiscing
elit, thus
sed diam
manufacturers
designs
ensuring uniform
and
equalization
downstream.
Minimum
molestie
dolore
nonummy
nibh
tincidunt ut 1:30; less nulla
efficiency
is euismod
an unprecedented
than facilisi.
1F (0.55C) temperature variation
at theconsequat,
dischargevelforillum
each
30Feu
feugiat
nulla
facilisis
at
vero
eros
et
laoreet
doloretemperature
magna aliquam
erat between theNam
(16.67C)
difference
hot liber
and cold
decks.
tempor cum soluta
accumsan et iusto odio dignissim qui
volutpat. Ut wisi enim ad minim
nobis
eleifend
option
congue
nihil
Dual duct terminals, being inherently suited to high indoor air quality applications, are frequently specified with an 'IAQ'
blandit praesent luptatum zzril delenit
veniam, quis nostrud exerci tation
imperdiet
doming
quod
mazim
insulation option. For this reason, the sound data
presented
for id
this
terminal
unit uses the Steri-Liner option, rather than
augue duis dolore te feugait nulla
ullamcorper suscipit lobortis nisl ut
placerat
facer selection
possim assum.
standard fiberglass insulation, thus permitting a more
accurate
than is possible with other manufacturers equipment.
aliquip ex ea commodo consequat.
3240
FEATURES:
STANDARD
Duis autem vel
eum
iriure dolor in
hendrerit
Integral inmixing
vulputateattenuator
velit esse with
baffles.
1:30 minimum
mixing
molestie consequat,
vel illum dolore
efficiency.
eu feugiat nulla facilisis at vero eros
et iusto
dignissim
et22accumsan
ga. (0.86)
zincodio
coated
steel
qui blandit
praesent luptatum
zzrillow
casing,
mechanically
sealed,
delenit augue
duis dolore te feugait
leakage
construction.
nulla
facilisi.
Lorem
ipsum
dolor
sit
Low leakage opposed
blade
damper
amet,
consectetuer
adipiscing
elit,
design with blade and jamb seals
sed diam
nonummy
(single
blade
on size nibh
4, 5, euismod
6). Damper
tincidunt ut laoreet dolore magna
leakage is less than 1% of nominal
aliquam erat volutpat.
flow at 6" w.g. (1.5 kPa). 90 rotation,
CW
Ut wisi
enim ad minim veniam, quis
to close.
nostrud
tation steel
ullamcorper
1
2" (13)exerci
dia. plated
driveshaft.
suscipit
lobortis
nisl
ut
aliquip
An indicator mark at the
end ex
of ea
the
commodoshows
consequat.
Duis
autem
driveshaft
damper
position.
vel eum iriure dolor in hendrerit in
vulputate
Designed
foresse
pneumatic,
velit
molestie analog
electronic
or illum
digital
pressure
consequat, vel
dolore eu
independent
control.
feugiat nulla facilisis at vero eros et
accumsan et iusto odio dignissim
C22
4-21-11
wisileakage
enim adcasing.
minimLess
veniam,
UtLow
than quis
1% of
nostrud
exerci
tation
rated
airflow
at 6"
w.g.ullamcorper
(1.5 kPa).
suscipit lobortis nisl ut aliquip ex ea
Steri-liner.
commodo consequat. Duis autem vel
eum
Fiber-free
liner. in hendrerit in
iriure dolor
vulputate
Solid metal
velitliner.
esse molestie
vel illum dolore eu feugiat
consequat,
1" (25) liner.
nulla facilisis at vero eros et accumsan
et iusto odio dignissim qui blandit
praesent luptatum zzril delenit augue
duis dolore te feugait nulla facilisi.
Pneumatic Controls
5 1/2"
(140)
6 1/2"
(165)
2"
(51)
14 1/2" (368)
MULTI-POINT
AVERAGING
FLOW SENSOR
HOT
AIR INLET
A
HIGH
PERFORMANCE
MIXING
ATTENUATOR
10"
(254)
COLD
DW 1/8" (3)
DH
DH(3)
- 1/8"
- 1/8" (3)
AIR INLET
5 3/4"
(146)
UNIVERSAL PNEUMATIC
CONTROL MOUNTING PANEL
AND PROTECTIVE SHROUD
DAMPER
DRIVE SHAFT
OPTIONAL
ACCESS DOOR
18" X 10" (457 X 254)
RECTANGULAR
DISCHARGE
W/ TOTAL
DISCHARGE SENSOR
PLAN VIEW
5 1/2"
(140)
11" (279)
2"
(51)
14" (356)
MULTI-POINT
AVERAGING
FLOW SENSOR
H
DAMPER
DRIVE
SHAFT
HOT
D
AIR INLET
A
COLD
HIGH
PERFORMANCE
MIXING
ATTENUATOR
10"
(254)
DW 1/8" (3)
DH
DH(3)
- 1/8"
- 1/8" (3)
AIR INLET
6"
(152)
CONTROLS ENCLOSURE
FOR FACTORY MOUNTED
CONTROLS
DAMPER
DRIVE SHAFT
OPTIONAL
ACCESS DOOR
18" X 10" (457 X 254)
W/ TOTAL
DISCHARGE SENSOR
PLAN VIEW
RECTANGULAR
DISCHARGE
W/ COLD & HOT
DUCT INLET SENSORS
Dimensional Data
Unit
Size
4
5
6
7
8
9
10
12
14
24 (610)
24 (610)
24 (610)
24 (610)
24 (610)
34 (864)
34 (864)
34 (864)
42 (1067)
10 (254)
10 (254)
10 (254)
12 12 (318)
12 12 (318)
14 (356)
14 (356)
16 (406)
18 (457)
47 (1194)
47 (1194)
47 (1194)
47 (1194)
47 (1194)
60 (1524)
60 (1524)
60 (1524)
72 (1829)
11 (279)
11 (279)
11 (279)
11 (279)
11 (279)
16 18 (410)
16 18 (410)
16 18 (410)
20 18 (511)
Inlet Dia.
D
3 78 (98)
4 78 (124)
5 78 (149)
6 78 (175)
7 78 (200)
8 78 (225)
9 78 (251)
11 78 (302)
13 78 (353)
Outlet
DW x DH
8 x 8 (203 x 203)
10 x 10 (254 x 254)
14 x 12 (356 x 305)
18 x 14 (457 x 356)
22 x 16 (559 x 406)
4-21-11
C23
Universal
pneumatic
control
mounting
panel features
double wall
stand-off ROUND
INLET
construction COLLARS
for strength
and rigidity.
Controls
mounting
screws do not
penetrate
casing.
4
5
6
7
8
9
10
12
14
Total
Airflow
Range
cfm
Airflow at
2000 fpm Inlet
Velocity (nom.)
cfm
0 225
0 350
0 500
0 650
0 900
0 1050
0 1350
0 2050
0 2740
150
250
400
550
700
900
1100
1600
2100
Pneumatic
3000 Controller
Min.
30
55
80
115
155
200
260
355
475
180
325
450
650
900
1050
1350
2050
2740
25
45
65
95
125
165
215
290
390
180
325
450
650
900
1050
1350
2050
2740
25
45
65
95
125
165
215
290
390
180
325
450
650
900
1050
1350
2050
2740
200
350
500
650
900
1050
1350
2050
2740
225
350
500
650
900
1050
1350
2050
2740
4
5
6
7
8
9
10
12
14
C24
4-21-11
Total
Airflow
Range
l/s
Airflow at
10.2 m/s Inlet
Velocity (nom.)
l/s
0 106
0 165
0 236
0 307
0 425
0 495
0 637
0 967
0 1293
71
118
189
260
330
425
519
755
991
Pneumatic
3000 Controller
Min.
14
26
38
54
73
94
123
168
224
85
153
212
307
425
495
637
967
1293
12
21
31
45
59
78
101
137
184
85
153
212
307
425
495
637
967
1293
12
21
31
45
59
78
101
137
184
85
153
212
307
425
495
637
967
1293
94
165
236
307
425
495
637
967
1293
106
165
236
307
425
495
637
967
1293
10
12
14
cfm
200
150
100
75
50
300
250
200
125
75
500
400
300
200
100
650
550
335
225
110
850
700
500
350
200
1050
900
675
450
225
1350
1100
800
550
250
1950
1600
1200
800
400
2700
2100
1600
1050
550
Airflow
Performance Notes:
1. NC Levels are calculated based on procedures as documented on page XX.
2. Dash (-) in space indicates a NC less than 20.
4-21-11
C25
Min. inlet
Ps
Min. Ps
"w.g. Pa 2 3 4 5 6
0.08 20 49 38 29 - 0.05 12 47 36 26 - 0.03 7 - 33 - - 0.02 5 - - - - 0.01 2 - - - - 0.15 37 54 45 39 29 22
0.11 27 50 39 31 - 0.07 17 48 37 28 - 0.03 7 - 34 - - 0.01 2 - - - - 0.32 80 60 54 47 37 31
0.22 55 56 47 41 31 24
0.13 32 52 41 33 22 0.06 15 - 36 23 - 0.02 5 - - - - 0.57 142 57 54 49 42 36
0.43 107 54 51 46 39 33
0.18 45 48 39 32 23 0.09 22 - 37 29 - 0.03 7 - 34 26 - 0.72 179 62 59 54 48 42
0.51 127 57 54 49 42 36
0.29 72 52 46 40 32 26
0.15 37 48 39 32 23 0.06 15 - 37 29 - 0.29 72 60 54 50 44 38
0.22 55 59 53 49 43 37
0.13 32 54 44 40 33 30
0.06 15 51 39 34 27 0.02 5 44 36 31 - 0.40 99 66 60 56 50 45
0.28 70 60 54 50 44 38
0.16 40 55 47 43 36 30
0.08 20 52 41 36 29 0.02 5 44 36 31 - 0.74 184 72 71 60 54 51
0.50 124 66 63 54 47 44
0.28 70 58 54 46 39 35
0.13 32 51 45 37 30 27
0.03 7 - - 28 - 0.78 194 75 69 62 55 52
0.45 112 68 61 55 48 44
0.26 65 61 53 47 40 35
0.11 27 50 40 33 26 0.03 7 49 34 26 - -
7
27
30
27
37
30
32
31
24
40
32
24
48
41
31
49
41
31
-
For full performance table notes, see page C28; RED highlighted numbers indicate embedded AHRI certification points.
C26
6-21-13
Min. Ps
2 3 4 5 6
- 33 27 23 - 31 24 20 - - 21 - - - 21 - - - 21 - 48 40 35 30 28
- 34 29 25 20
- 32 26 22 - - 23 - - - 23 20 53 46 41 37 33
50 42 37 32 30
- 36 31 27 22
- - 26 - - - 25 22 54 49 40 37 31
51 46 37 34 28
- 35 26 - - - - - - - - - 57 52 43 39 34
54 49 40 37 31
- 41 33 30 24
- 35 26 - - - - - 54 47 39 32 28
53 46 38 31 27
- 39 31 24 - - - - - - - - 59 54 45 38 34
54 47 39 32 28
- 39 31 24 - - - - - - - - 65 60 48 41 37
59 53 42 35 28
52 45 34 27 - 33 - - - - 26 29 65 60 48 41 37
59 53 42 35 28
52 45 34 27 - 33 - - - - 26 29 -
7
25
31
27
29
26
31
29
27
26
32
27
33
23
33
23
-
200 94
150 71
4 100 47
75 35
50 24
300 142
250 118
5 200 94
125 59
75 35
500 236
400 189
6 300 142
200 94
100 47
650 307
550 260
7 335 158
225 106
110 52
850 401
700 330
8 500 236
350 165
200 94
1050 495
900 425
9 675 319
450 212
225 106
1350 637
1100 519
10 800 378
550 260
250 118
1950 920
1600 755
12 1200 566
800 378
400 189
2700 1274
2100 991
14 1600 755
1050 496
550 260
Min. inlet
Ps
"w.g. Pa
0.08 21
0.05 13
0.03 6
0.02 4
0.01 2
0.15 36
0.11 26
0.07 18
0.03 8
0.01 3
0.32 80
0.22 55
0.13 32
0.06 15
0.02 5
0.50 141
0.43 106
0.18 45
0.09 23
0.03 7
0.72 179
0.51 126
0.29 72
0.15 37
0.06 15
0.29 72
0.22 55
0.13 33
0.06 16
0.02 5
0.40 99
0.28 70
0.16 40
0.08 20
0.02 5
0.74 184
0.50 124
0.28 70
0.13 32
0.03 8
0.78 194
0.45 112
0.26 65
0.11 27
0.03 8
For performance table notes, see page C28; RED highlighted numbers indicate embedded AHRI certification points.
6-26-13
C27
DUAL
DUALDUCT
DUCTTERMINAL
TERMINALUNITS
UNITS
Performance Data AHRI Certification and Performance Notes
Model Series 3240 With Mixing Attenuator BlendMaster AHRI Certification Rating Points
VAV: Steri-Liner
Inlet
Size
4
5
6
7
8
9
10
12
14
Airflow
cfm
150
250
400
550
700
900
1100
1600
2100
l/s
71
118
189
260
330
425
519
755
991
C28
2-11-15
Section 15840
The following specification is recommended where an
independent laboratory test and performance verification is
required.:
PART 1 GENERAL
1.01 RELATED DOCUMENTS
A. The requirements of the General Conditions, Supplementary
Conditions and the following specification sections apply to all Work
herein:
1. Section 15 - - - General.
2. Section 15 - - - Scope of Work.
3. Section 15 - - - Design Conditions.
4. Section 15 - - - Electric Motors and Controllers.
5. Section 15 - - - Access Doors and Color Coded.
Identification in General Construction.
6. Section 15 - - - Ductwork and Sheet Metal.
7. Section 15 - - - Testing, Balancing and Adjusting.
1.02 SUMMARY
A. Furnish and install all air terminal units herein specified and as
indicated on the Drawings.
1.03 REFERENCE STANDARDS
A. All air terminal units shall be designed, manufactured and tested
in accordance with the latest applicable industry standards
including the following:
1. ANSI/ASHRAE Standard 130-08.
2. AHRI Standard 880-08.
3. Underwriters Laboratories UL Standard 1995.
4. Underwriters Laboratories UL Standard 1996.
1.04 QUALITY ASSURANCE
A. All equipment and material to be furnished and installed on this
Project shall be UL or ETL listed, in accordance with the
requirements of the Authority having jurisdiction and suitable for its
intended use on this Project. Space limitations shall be reviewed to
ensure that the equipment will fit into the space allowed.
B. All equipment and material to be furnished and installed on this
Project shall be run tested at the factory and results of that testing
shall be tabulated and provided to the engineer when the equipment
ships to the job site. See paragraph 2.03 G for specific
requirements.
1.05 SUBMITTALS
A. The following submittal data shall be furnished according to the
Conditions of the Construction Contract, Division 1 Specifications
and Section 15 - - - General and shall include but not be limited to:
1. Dual Duct Variable Air Volume Terminal Units, complete with
capacity data, test data, construction details, physical dimensions,
electrical characteristics, etc.
1.06 ACOUSTICS
This acoustical specification describes sound power levels as
tested to AHRI 880 and ASHRAE 130.
A. Sound Power Acoustical Performance:
1. Discharge Noise: Maximum permissible sound power levels in
octave bands of discharge sound through discharge ducts from
terminal units operated at an inlet pressure of 1.0" (250 Pa) w.g. and
the maximum amount of air volume shown on the Project
Mechanical Drawings leaving the terminal unit and entering the
reverberant chamber shall be as follows:
Octave Band
2
3
4
5
6
7
NC-35
67
64
67
66
67
67
NC-40
71
69
72
71
72
72
Table 1.
Maximum Discharge
Sound Power Levels
(dB re 10-12 Watts).
4-21-11
C29
TM
Octave Band
2
3
4
5
6
7
Table 2.
NC-35
64
57
53
50
50
53
NC-40
68
62
58
55
55
58
1.07 WARRANTY
A. Manufacturer shall warrant equipment for one year from start up
or 18 months from shipment.
PART 2 - PRODUCTS
2.01 UNAUTHORIZED MATERIALS
A. Materials and products required for the work of this section shall
not contain asbestos, polychlorinated biphenyls (PCB) or other
hazardous materials identified by the Engineer or Owner.
2.02 ACCEPTABLE MANUFACTURERS
A. These Specifications set forth the minimum requirements for dual
duct VAV terminal units. If they comply with these Specifications,
dual duct VAV terminal units manufactured by one of the following
manufacturers will be acceptable:
1. Nailor Industries.
2.03 DUAL DUCT VARIABLE AIR VOLUME TERMINAL UNITS
A. Furnish and install dual duct VAV terminal units as indicated on
the Drawings. The units shall be designed and built as a single unit
and provided with two primary variable air volume dampers that
control the primary cold and warm air quantity in response to a
temperature control signal. The damper construction shall be
rectangular with multiple opposed blades designed to operate on a
90 arc. Blades shall be extruded aluminum, single thickness
construction with heavy-duty gasket for tight shut-off. Units shall be
suitable for pressure independent control with [pneumatic, analog
electronic or electronic DDC] controls. The space limitations shall
be reviewed carefully to ensure all terminal units will fit into the
space provided including National Electric Code clearances
required in front of all panels containing electrical devices. Unit
casings shall be of minimum 20 ga. (1.00) galvanized steel.
Removable access doors rated for high pressure and low leakage
shall be factory installed in the mixing section of the unit and shall
provide access to service all internal components. Unit shall be fully
lined with at least 34" (19) thick, fiberglass board type insulation
completely encapsulated between solid outer and foil inner liners,
which comply with NFPA 90 for fire and smoke resistivity and UL
181 for erosion. Casing leakage shall not exceed 1% of terminal
rated airflow at 6" w.g. (1492) interior casing pressure. All high side
casing joints shall be sealed with approved sealant and high side
casing and damper leakage shall not exceed 1% of terminal rated
airflow at 6" w.g. (1492).
Terminal unit manufacturer shall provide flow curves for the air
sensors at both inlets and/or at the outlet, as required, clearly
C30
4-21-11
4-21-11
C31
Explanation of NC Levels
Tabulated NC levels are based on attenuation values as outlined
in AHRI Standard 885-2008 "Procedure for Estimating Occupied
Space Sound Levels in the Application of Air Terminals and Air
Outlets". AHRI Standard 885-2008, Appendix E provides typical
sound attenuation values for air terminal discharge sound and air
terminal radiated sound.
As stated in AHRI-885-2008, Appendix E, "These values can be
used as a quick method of estimating space sound levels when
a detailed evaluation is not available. The typical attenuation
values are recommended for use by manufacturers to estimate
application sound levels. In product catalogs, the end use
environments are not known and the following factors are
provided as typical attenuation values. Use of these values will
allow better comparison between manufacturers and give the
end user a value which will be expected to be applicable for
many types of space."
Radiated Sound
Table E1 of Appendix E provides typical radiated sound
attenuation values for three types of ceiling: Type 1 Glass
Fiber; Type 2 Mineral Fiber; Type 3 Solid Gypsum Board.
Since Mineral Fiber tile ceilings are the most common
construction used in commercial buildings, these values have
been used to tabulate Radiated NC levels.
The following table provides the calculation method for the
radiated sound total attenuation values based on AHRI Standard
885-2008.
Environmental Effect
Ceiling/Space Effect
Total Attenuation Deduction
Octave Band
4
5
6
7
2
16
18
1
18
19
0
20
20
0
26
26
0
31
31
0
36
36
Discharge Sound
Table E1 of Appendix E provides typical discharge sound
attenuation values for three sizes of terminal unit.
1. Small box; Less than 300 cfm (142 l/s)
(Discharge Duct 8" x 8" [203 x 203]).
2. Medium box; 300 700 cfm (142 - 330 l/s)
(Discharge Duct 12" x 12" [305 x 305]).
3. Large box; Greater than 700 cfm (330 l/s)
(Discharge Duct 15" x 15" [381 x 381]).
These attenuation values have been used to tabulate Discharge
NC levels applied against the terminal airflow volume and not
terminal unit size.
The following tables provide the calculation method for the
discharge sound total attenuation values based on AHRI
Standard 885-2008.
Small Box
< 300 cfm
Octave Band
3 4 5 6
Environmental Effect
5 ft. (1.5 m) 1" (25) Duct Lining
Branch Power Division (1 outlet)
5 ft. (1.5 m), 8 in. dia. (200) Flex Duct
End Reflection
Space Effect
Total Attenuation Deduction
2
2
0
5
10
5
24
1
6
0
10
5
6
28
0
29
0
21
0
9
59
0
18
0
12
0
10
40
0
12
0
18
2
7
39
0
25
0
19
1
8
53
Medium Box
300 700 cfm
Octave Band
3 4 5 6
Environmental Effect
5 ft. (1.5 m) 1" (25) Duct Lining
Branch Power Division (2 outlets)
5 ft. (1.5 m), 8 in. dia. (200) Flex Duct
End Reflection
Space Effect
Total Attenuation Deduction
2
2
3
5
10
5
27
1
4
3
10
5
6
29
0
20
3
21
0
9
53
0
14
3
12
0
10
39
Large Box
>700 cfm
Octave Band
3 4 5 6
Environmental Effect
5 ft. (1.5 m) 1" (25) Duct Lining
Branch Power Division (3 outlets)
5 ft. (1.5 m), 8 in. dia. (200) Flex Duct
End Reflection
Space Effect
Total Attenuation Deduction
2
2
5
5
10
5
29
1
3
5
10
5
6
30
0
12
5
12
0
10
39
0
10
3
18
2
7
40
0
9
5
18
2
7
41
0
20
3
19
1
8
51
0
18
5
19
1
8
51
0
17
5
21
0
9
52
C32
4-21-11
Steri-Liner
Steri-Liner is an internal insulation designed to reduce the risk of
microbial growth within the terminal. A smooth non-porous facing
provides a vapor barrier to moisture and reduces the risk of
microorganisms becoming trapped. This facing also facilitates
cleaning and prevents insulating material erosion. Damage to the
liner though, will expose fiberglass particles to the airstream.
Acoustic absorption of aluminum foil lined insulation is reduced for
discharge sound levels and essentially unchanged for radiated
sound levels when compared to standard fiberglass insulation.
13/16" (21) thick, 4 lb./cu. ft. (64 kg/m) density rigid fiberglass
with a fire resistant reinforced aluminum foil-scrim-kraft (FSK)
facing.
No exposed edges. Steri-Liner features "notch and tuck"
fabrication and full
seam length steel
Z-strip construction
providing
both
superior
edge
13/16" (21) THICK,
protection and an
FSK LINED
extremely
rigid
INSULATION
NOTCH AND
terminal.
TUCK
FABRICATION
Meets requirements:
UL 181, 723
NFPA 90A & 90B
FULL LENGTH Z - STRIPS
ASTM E 84, C 665,
C 1071
PERFORATED
METAL
4-21-11
C33
Standard Construction
Leakage Information
1.
2.
3.
4.
5.
9 3/4"
(248)
11 3/4"
(298)
17 3/4" (451)
19 3/4" (502)
C34
4-21-11
1 1/8"
(29)
LH
RH
3A/OR OR 3A/OL
LH
RH
3B/OL OR 3C/OR
LH
RH
3B/OR OR 3C/OL
4-21-11
C35
Models: 3210
Applicable Controls:
MAX.
AIRFLOW INCREASE
In the cooling mode, as room temperature approaches set point, cold airflow
modulates from maximum to zero flow. As room temperature drops below set point,
hot airflow modulates from zero to maximum. Heating and cooling maximum flow
rates can be different. A deadband may be utilized.
As this is a non-blending application, a mixer/attenuator section is not required.
MAX.
HTG.
MAX.
CLG.
AIRFLOW INCREASE
In the cooling mode, as room temperature approaches set point, cold air modulates
from maximum to a minimum mix flow rate. As temperature continues to drop, hot
airflow modulates open as cold airflow continues to close, maintaining a minimum
total flow rate. Lower heating airflow rates may require smaller hot deck sizes than
cold deck to optimize control. A mixer/attenuator section is required.
CLG.
MAX.
HTG.
Variable Volume Hot and Cold Airflow with Mixing at Minimum Flow
C36
4-21-11
MAX.
HTG.
CLG.
MAX.
MAX.
HTG.
CLG.
AIRFLOW INCREASE
MAX.
Constant Volume with Hot and Cold Airflow Mixing Minimum Air from Cold
Deck
This sequence is similar to the one above, but the cold deck is calibrated with a
minimum setting (rather than zero), providing a minimum outside air ventilation
capability. The hot deck minimum setting is still zero. The proportions of hot and
cold air are indicated by the broken lines. A mixer/attenuator section is required.
CLG.
AIRFLOW INCREASE
MAX.
HTG.
Constant Volume with Hot and Cold Airflow Mixing Hot and Cold Deck
Minimums are Zero
The most commonly used sequence for high 'IAQ' applications. Cooling and
heating maximum airflow rates are the same. Constant volume airflow delivery is
maintained over the entire cooling and heating range. A mixer/attenuator section
is required.
MAX.
AIRFLOW INCREASE
The hot and cold decks may be set for equal or unequal maximum air volumes. In
the cooling mode, as room temperature approaches set point, cold airflow
modulates from maximum to a minimum mix flow rate. As temperature continues
to drop, hot airflow begins to modulate open as cold airflow continues to close. As
the hot deck continues to open, as it passes the minimum cooling setting, the cold
duct damper is closed. A mixer/attenuator section is required.
MAX. CLG.
60
LD
CO
40
20
13
100
MAX. CLG.
80
60
MAX. HTG.
40
20
13
MAX. HTG.
80
100
HO
The typical control diagrams shown on this page represent the most commonly used dual duct control strategies. The
schematics illustrate operation with a direct acting thermostat. Similar control sequences are available for use with reverse
acting thermostats. Further variations for each sequence include right or left hand cold deck and damper failure state,
normally open or normally closed upon loss of main air. Application specific control strategies are available from your Nailor
representative.
100
MAX. HTG.
80
MAX. CLG.
60
40
MIXING
20
0
13
4-21-11
C37
100
MAX.
HTG.
80
PROPORTIONAL
BAND
FIXED 2F
PROPORTIONAL
BAND
FIXED 2F
MAX.
CLG.
60
40
DEAD BAND
The typical control diagrams shown on this page are based on our standard CSP 5000 Series or CSP 4000 Series
electronic controller/actuator. They feature the adjustment of minimum and maximum flow set points at the room
thermostat, rather than at the box controller. The electronic room thermostat has a dual set point for heating and cooling.
MIN.
HTG.
SETTING
IS O.
20
0
HEATING
SET POINT
MIN.
CLG.
SETTING
IS O.
COOLING
SET POINT
C38
4-21-11
100
MAX.
HTG.
80
PROPORTIONAL
BAND
FIXED 2F
PROPORTIONAL
BAND
FIXED 2F
MAX.
CLG.
60
40
20
0
MIN.
HTG.
SETTING
IS O.
MIN.
CLG.
HEATING
SET POINT
COOLING
SET POINT
100
MAX. HTG.
CONSTANT VOLUME
80
PROPORTIONAL
BAND
FIXED 2F
60
40
20
0
MAX.
CLG.
(select one)
Pneumatic Controls
(Pressure Independent)
6-26-13
C39
D1
Page No.
D4
D5
D9
D10
D12
D14
D15
D16
D20
D21
D24
D25
D26
D28
D29
D30
D34
D35
D36
D37
D38
D40
D41
D42
D52
D48
D49
D52
Performance Data
Models 35SW, 35SWST, 35SW-OAI, 35SWST-OAI, 35SW-CVP Series Flow
D53
Suggested Specifications
Model Series 35S
Model Series 35SST "Stealth"
37S Series Low Profile
Features and Options
Dimensional Data
Performance Data - NC Level Application Guide
- Discharge Sound Power Levels
- Radiated Sound Power Levels
- AHRI Certification and Performance Notes
- ECM Motor Option Fan Curves
37SST "Stealth" Series Quiet Low Profile
Features and Options
Dimensional Data
Performance Data - NC Level Application Guide
- Discharge Sound Power Levels
- Radiated Sound Power Levels
- AHRI Certification and Performance Notes
- PSC Motor Fan Curves
- ECM Motor Option Fan Curves
- Models: 37SW and 37SWST Hot Water Coil
D59
D61
D67
D68
D72
D73
D74
D75
D77
D78
D79
D83
D84
D85
D86
D87
D88
D89
Suggested Specifications
ModelT Series 37S
ModelT Series 35SST "Stealth"
D2
D92
D94
6-25-13
D100
D101
D103
D104
D105
D106
D107
D108
D109
D110
Suggested Specifications
Models Series 35N
D114
D120
D121
D122
D123
D124
D125
D126
D129
Suggested Specifications
Models Series 37N
D133
D135
D136
D137
D136
D139
Options
Optional Liners for 'IAQ' Sensitive Applications
90 FN2 Line Voltage Enclosure Option
6-25-13
D143
D144
D3
.PEFM4FSJFT4#BTJD6OJU
Quiet, Series Flow (Constant Volume)
.PEFM4FSJFT4454UFBMUI5.
Super Quiet, Series Flow (Constant Volume)
$PNNPO'BO5FSNJOBM$PNQPOFOUT
In addition to the 'Diamond Flow' multi-point averaging
sensor and opposed blade damper configuration of the
primary air valve that are described in detail on page A9
in this catalog, all Nailor fan powered terminals
incorporate the following features and benefits.
The Diamond sensor is standard on all Nailor VAV
terminal units that are equipped with pressure
independent controls.
4XJUI$71 $POTUBOU7PMVNF1SFTTVSJ[BUJPO6OJU
%
7-1-11
$PNNPO'BO5FSNJOBM$PNQPOFOUT
4JOHMF4QFFE14$*OEVDUJPO.PUPST
All Nailor fan powered terminal units are currently
equipped with single speed, direct drive, fractional
horsepower, high efficiency, psc motors as standard.
These motors are manufactured to specifications
developed by Nailor specifically for the fan powered
terminal unit market. Some of the more important features
are listed and explained below.
.PEFM4FSJFT4#BTJD6OJU
Low Profile, Series Flow (Constant Volume)
t /P$PSPOB&GGFDU
Motors not only provide power, but act as transformers
and generators. Under certain conditions, this causes
the unused speed taps in multiple speed motors to have
large potential or static charges present. While these
charges are not doing any work, they will create
damage to the windings if their potential voltages are
greater than the winding insulating quality. This is often
the case and lifetimes are shortened. Nailor fan
powered terminal units do not suffer from this malady.
All motors are single speed.
t 8JEF0QFSBUJOH3BOHFT
Nailor motors are designed to operate at rotational
speeds lower than those of our competitors. This
requires special stator wire sizing, special capacitor
sizing and special bearings. These items are covered in
our specifications. This assures you of high end
performance equal to or better than any of our
competitors and low end ranges below any of our
competitors.
Low end performance is often ignored. Many times, this
is because the range is not great enough to allow much
difference, or because the low end performance is
achieved by artificial means such as manual dampers to
lower the airflows. Manual dampers lower airflows, but
they increase rpm. Increased rpm put back all the noise
generation in the fan powered terminal unit as if it were
still operating at full airflow. This is due to the noise
caused by tip speed and vibration within the unit. High
rpm, regardless of airflow, will generate high noise.
Nailor solves this problem through low rpm for low
airflows. Typically, the motors in Nailor fan powered
terminal units can rotate as low as 350 rpm at low end,
shedding as many as 14 to 20 decibels in the second
and third octave bands depending on which unit is being
selected. This means real sound level selections, units
that can produce NC's of 30 and 35 when applied
correctly and wider operating ranges on individual units
for greater flexibility in the zone.
.PEFM4FSJFT4454UFBMUI5.
Super Quiet, Series Flow (Constant Volume)
.PEFM4FSJFT/#BTJD6OJU
Compact Design, Parallel Flow (Variable Volume)
/.PEFM4FSJFT#BTJD6OJU
Low Profile Design, Parallel Flow (Variable Volume)
7-1-11
%
%FTJHO$IBSBDUFSJTUJDTBOE
"QQMJDBUJPO
t 1FSNBOFOUMZ-VCSJDBUFE.PUPST
*OUSPEVDUJPO
-PX/PJTF-FWFMTo")3*$FSUJGJFE
4FSJFT'MPX5FSNJOBMTo $POTUBOU7PMVNF
t 1FSNBOFOU4QMJU$BQBDJUPS%FTJHO
All Nailor fan powered terminal units have PSC motors.
The capacitors are sized to provide ample starting
torque, even when turned down to the low minimums
allowed on Nailor fan powered terminal units.
t )JHI&GGJDJFODZ
'BO4QFFE$POUSPMMFST
%
7-1-11
75
25
MINIMUM
PRIMARY
AIR
DISCHARGE
AIR
OPTIONAL
ELECTRIC HEAT
FAN/MOTOR
'JHVSF1BSBMMFM'BO5FSNJOBM
7-1-11
COOLING
90
80
70
60
50
COLD
HOT
'JHVSF4FSJFT0QFSBUJPO
before it reaches its minimum setting. Overlapping the
fan start point and primary air valve minimizes the
likelihood of air stagnation in the conditioned space and
the noticeable air surge when the fan energizes.
With the fan energized, the delivered air temperature
approaches that of the ceiling plenum. If the zone
temperature continues to drop, the thermostat automatically
energizes optional supplemental electric or hot water heat,
thereby raising discharge air temperature. Increasing the
cooling load reverses the sequence. The parallel terminal
unit is therefore variable volume constant temperature on
the cooling cycle and essentially constant volume variable
temperature on the heating cycle. (See Fig. 4).
MAXIMUM
100
RY
AIR
TOTAL AIR
75
MA
PLENUM AIR
PRI
50
25
MINIMUM
0
INDUCED
PLENUM
AIR
FAN
ONLY
HOT
COLD
ELECTRICAL
CONTROLS
ENCLOSURE
FAN AND
HEAT
AT
PRIMARY
AIR VALVE
100
HE
1BSBMMFM'MPX5FSNJOBMTo 7BSJBCMF7PMVNF
HOT
COLD
100
FAN AND
HEAT
FAN
ONLY
COOLING
90
80
70
60
50
COLD
HOT
'JHVSF1BSBMMFM0QFSBUJPO
%
AT
'JHVSF4FSJFT'BO5FSNJOBM
AIR
50
HE
FAN/MOTOR
OPTIONAL
ELECTRIC HEAT
DISCHARGE
AIR
MAXIMUM
PLENUM AIR
INDUCED
PLENUM
AIR
TOTAL AIR
100
ELECTRICAL
CONTROLS
ENCLOSURE
PR
IMA
RY
PRIMARY
AIR VALVE
%
"QQMJDBUJPO
5ZQJDBM"QQMJDBUJPOPG4FSJFT6OJUT
5ZQJDBM"QQMJDBUJPOPG1BSBMMFM6OJUT
Parallel units may be used in perimeter zones of
buildings where loads vary during occupied hours and
core zones maintain a constant cooling requirement utilizing
single duct shut-off type terminal units. Variable volume
airflow to the zone is acceptable in these applications and
low installation and operating costs are desired.
&OFSHZ$POTVNQUJPOBOE*OTUBMMFE$PTU
Dependent upon location, loading, operating hours and
ventilation requirements, either type of fan terminal may be
more advantageous. For an equivalent zone size, series
terminals may be a little higher in first cost as the fan is
sized for total airflow whereas a parallel terminal fan is
sized for the reduced heating airflow only. When fan size is
the same however, installed cost is approximately equal.
Series terminals however unlike parallel, reduce the
operating pressure requirement at the central AHU and
provide energy savings.
7-1-11
series).
'BO0QFSBUJPO
0QFSBUJOH
4FRVFODF
'BO&OFSHJ[BUJPO
5FSNJOBM'BO
4J[JOH
1SJNBSZ"JS7BMWF
4J[JOHBOE
.JOJNVN1SFTTVSF
GPS$FOUSBM'BO
4J[JOH
"DPVTUJDT
7FOUJMBUJPO3BUFT
7-1-11
4FSJFT'MPX
Fan located in the primary airstream (in
$POGJHVSBUJPO
%
t 6OJRVFGBDUPSZQSFTFUBJSWPMVNFDBQBCJMJUZ
t 1SFTTVSFJOEFQFOEFOUGBOPQFSBUJPO
t -&%GPSWJTVBMJOEJDBUJPOPGBJSWPMVNF
t 'JFMEBEKVTUBCMFGBOBJSWPMVNFDPOUSPMMFS
t 3FNPUFGBOBJSWPMVNFBEKVTUNFOUDBQBCJMJUZGSPN
#"4
t -BSHFSUVSOEPXOSBUJPTNFBONPSFGMFYJCJMJUZGPS
UFOBOUDIBOHFT
'&"563&4"/%#&/&'*54
Soft starts and slewed speed ramps are programmed into the
ECM motor eliminating stress transmitted to the mounting
bracket or hardware. They incorporate ball bearings providing
permanent lubrication unlike sleeve bearings requiring a
minimum rpm operation for oiling. The wider operating range
of the ECM motor allows each model to actually replace two
%
0.50
8)"5*4"/&$..0503
0.40
0.30
0.20
0.10
Size 3 with ECM motor
0.00
150
250
350
450
550
650
750
850
950
1050
cfm
Watts per cfm for 35S 4 & 5
0.60
0.50
Size 5 with PSC motor
0.40
Size 4 with PSC motor
0.30
0.20
0.10
0.00
700
900
1100
1300
1500
1700
1900
cfm
5BCMF 1PXFS DPOTVNQUJPO DPNQBSJTPO PG &$. WFSTVT
14$NPUPST
7-1-11
)08%0:0613&4&5'"/"*3'-08
&/&3(:4"7*/(4
The following graphs show the energy savings of units with
ECM motors compared to units with Nailor engineered PSC
motors Since PSC motors used by Nailor are built
specifically for Nailor fan powered terminal units and are
more efficient than those used by most of our competitors.
7-1-11
Annual Dollars
$200
$150
$100
$50
$0
200
400
600
800
1000
DGN
Annual Dollars
$250
$200
$150
$100
$50
$0
700
PSC Motor
1000
1300
1600
1900
DGN
ECM Motor
5BCMF5ZQJDBMPQFSBUJOHDPTUDPNQBSJTPO
8)"5*45)&1":#"$,1&3*0%0/&$.
.05034
The payback period varies. It depends on which unit you
use, where you set the cfm, how much you run the
equipment and what you are paying for electricity. The
graphs above are calculated assuming 66 hours per week
operations and $ .10 per kWh. If you run the equipment
longer in your building or if you pay more for electricity, the
payback will change proportionally. Considering the pre-set
capability of the motor, there should be an up-front savings
on balancing. That should be rebated to the owner and
should be considered as part of the payback from the motor.
Typically, with the balancing rebate and the operating
expenses as shown above, the payback period should be
anywhere from 6 to 18 months.
%
*NQFSJBM6OJUT $VCJD'FFUQFS.JOVUF
*OMFU
5ZQF
5PUBM
"JSGMPX
3BOHF
DGN
"JSGMPXBU
GQN
*OMFU
7FMPDJUZ
OPN
DGN
4
5
6
7
8
Round
9
10
12
14
16
12
Flat
14
16
Oval
18
14 x 8
14 x 10 Rect.
0 225
0 400
0 550
0 800
0 1100
0 1400
0 1840
0 2500
0 3370
0 4525
0 2500
0 3125
0 3725
0 5265
0 2450
0 2950
150
250
400
550
700
900
1100
1600
2100
2800
1600
2100
2800
2500
1560
1900
*OMFU
4J[F
3BOHFPG.JOJNVNBOE.BYJNVN4FUUJOHT
DGN
1OFVNBUJD
"OBMPH
%JHJUBM
$POUSPMMFS
&MFDUSPOJD$POUSPMT
$POUSPMT
5SBOTEVDFS%JGGFSFOUJBM1SFTTVSF XH
.JO
.BY
.JO
.BY
.JO
.BY
30
180
25
180
25
180
200
55
325
45
325
45
325
360
80
450
65
450
65
450
500
115
650
95
650
95
650
725
155
900
125
900
125
900
1000
200
1150
165
1150
165
1150
1285
260
1500
215
1500
215
1500
1675
350
2050
290
2050
290
2050
2290
475
2750
390
2750
390
2750
3075
640
3700
520
3700
520
3700
4140
355
2050
290
2050
290
2050
2300
440
2550
360
2550
360
2550
2850
525
3040
430
3040
430
3040
3400
750
4300
610
4300
610
4300
4800
350
2000
290
2000
290
2000
2240
420
2400
340
2400
340
2400
2700
225
400
550
800
1100
1400
1840
2500
3370
4525
2500
3125
3725
5265
2450
2950
3BOHFPG.JOJNVNBOE.BYJNVN4FUUJOHT
MT
"OBMPH
%JHJUBM
&MFDUSPOJD$POUSPMT
$POUSPMT
5SBOTEVDFS%JGGFSFOUJBM1SFTTVSF 1B
.JO
.BY
.JO
.BY
12
85
12
85
94
21
153
21
153
170
31
212
31
212
236
45
307
45
307
342
59
425
59
425
472
78
543
78
543
606
101
708
101
708
790
137
967
137
967
1081
184
1298
184
1298
1451
245
1746
245
1746
1954
137
967
137
967
1085
170
1203
170
1203
1345
203
1435
203
1435
1604
288
2029
288
2029
2265
137
944
137
944
1057
160
1133
160
1133
1274
106
189
260
378
579
661
868
1080
1590
2135
1180
1475
1758
2485
1156
1392
.FUSJD6OJUT -JUFSTQFS4FDPOE
*OMFU
4J[F
*OMFU
5ZQF
4
5
6
7
8
Round
9
10
12
14
16
12
Flat
14
16
Oval
18
14 x 8
14 x 10 Rect.
%
5PUBM
"JSGMPX
3BOHF
MT
"JSGMPXBU
NT
*OMFU
7FMPDJUZ
OPN
MT
0 106
0 189
0 260
0 378
0 519
0 661
0 868
0 1180
0 1590
0 2135
0 1180
0 1475
0 1758
0 2485
0 1156
0 1392
71
118
189
260
330
425
519
755
991
1321
755
991
1321
1652
736
897
1OFVNBUJD
$POUSPMMFS
.JO
14
26
38
54
73
94
123
165
224
302
168
208
248
354
165
198
.BY
85
153
212
307
425
543
708
967
1298
1746
967
1203
1435
2029
944
1133
12-13-11
7-1-11
%
.PEFMT
4
/P)FBU
4&
&MFDUSJD)FBU
48
)PU8BUFS)FBU
Model 35SW
The 44FSJFT provides many standard design features and superior sound performance when compared with other basic
model designs. The 4 offers a compact and economical design well suited to the majority of applications.
'&"563&4
Unique 16 ga. (1.6) galvanized
steel
channel
space
frame
construction provides extreme rigidity
and 20 ga. (1.00) casing components.
16 ga. (1.6) galvanized steel
inclined opposed blade primary air
damper. 45O rotation, CW to close.
1/2" (13) dia. plated steel drive shaft.
An indicator mark on the end of the
shaft shows damper-position. Leakage
is less than 2% of nominal flow at 3"
w.g. (750 Pa).
Perforated baffle on primary air
discharge optimizes mixing with
induced air for rapid and effective
temperature equalization. The baffle
also converts low frequency primary
air valve generated sound into more
readily attenuated higher frequencies.
Pressure independent primary
airflow control.
Multi-point averaging flow sensor.
Terminal is field flippable, providing
left or right installation connections.
Refer to IOM for details.
Universal access panels on all four
sides of terminal for ease of
maintenance and service.
Energy efficient PSC fan motor with
thermal overload protection.
Motor blower assembly mounted on
%
0QUJPOT
TM
EPIC /ECM Motor.
Primary air valve enclosure for field
mounted controls.
Induced air filter, 1" (25) thick,
disposable type.
Toggle disconnect switch (except
units with electric heat, when
disconnect is an electric heat option
and includes fan).
Various 'IAQ' linings are available.
Fan airflow or P.E. switch for night
shutdown (pneumatic controls).
Fan airflow switch for night
shutdown (analog electronic controls).
Night setback fan/heat cycle
(pneumatic and analog).
Fan unit fusing.
Hanger brackets.
'Q' option induced air attenuator.
Top entry induced air inlet.
FN2 90 Line Voltage enclosure.
Low temperature construction
(ice storage systems).
7-1-11
t HB
DIBOOFMTQBDFGSBNF
DPOTUSVDUJPO. Provides an extremely rigid
terminal.
t *ODMJOFE0QQPTFE#MBEF
1SJNBSZ"JS%BNQFS minimizes
noisy turbulence and ensures
smooth accurate control.
t h%JBNPOE'MPXh.VMUJQPJOU"WFSBHJOH
4FOTPSprovides accurate primary air
control.
t1FSGPSBUFE%JGGVTJPO#BGGMF
optimizes mixing of primary and
induced airflows and improves
sound performance.
t&OFSHZFGGJDJFOU14$
.PUPST are custom made to
Nailor specifications and
permanently lubricated
ensuring quiet running and
many years of reliable
maintenance free operation.
t HB
3FNPWBCMF
1BOFMT on four sides
provides access from
above, beside or below.
t"WBJMBCMF)PU8BUFS
$PJMT for supplementary
heat are mounted in an
insulated plenum section
for improved energy
savings and heat transfer.
Maintenance access
panels on top and bottom
sides are standard.
t
%VBM
%FOTJUZ*OTVMBUJPO
meets requirements of
NFPA 90A and UL 181.
7-1-11
%
t 4PMJE4UBUF'BO4QFFE
$POUSPMMFS is custom
designed by Nailor for
each fan size and
provides the widest turndown available for
maximum flexibility and
accurate primary/
induced air balancing.
PRIMARY
OPTIONAL
INDUCED AIR
INLET FILTER
IH
AIR
IW
IW + 2" (51)
'Q' OPTION INDUCED
AIR ATTENUATOR
INDUCED
AIR
IH +
2" (51)
MULTI-POINT
FLOW SENSOR
OPTIONAL
FILTER
B
W
2
DIA. =
NOM. 1/8" (3)
OPTIONAL
TOP
INLET
PRIMARY
AIR
FAN
TW
DW
DH
TL
1" (25)
5 3/4"
(146)
DRIVESHAFT
14" (356)
14" (356)
L
OPTIONAL
PRIMARY
AIR VALVE
CONTROLS
ENCLOSURE
PRIMARY
AIR
H
2
11"
(279)
HINGED FAN
CONTROLS
ENCLOSURE
H1" (25) H
6" (152)
%JNFOTJPOBM%BUB
%
*OEVDFE"JS*OMFU
'JMUFS4J[F
6OJU
4J[F
*OMFU
4J[F
4JEF TUE
*8Y*)
5PQ PQU
5-Y58
0VUMFU
%JTDIBSHF
%8Y%)
4JEF*OMFU
TUE
5PQ*OMFU
PQU
4, 6, 8
(102, 152, 203)
18
(457)
14
(356)
36
(914)
3 12
(89)
8 x 10
(203 x 254)
10 x 14
(254 x 356)
7 14 x 10 12
(184 x 267)
10 x 12
(254 x 305)
14 x 16
(356 x 406)
6, 8
(152, 203)
18
(457)
14
(356)
36
(914)
6
(152)
8 x 10
(203 x 254)
10 x 14
(254 x 356)
9 14 x 10 12
(235 x 267)
10 x 12
(254 x 305)
14 x 16
(356 x 406)
6, 8, 10, 12
(152, 203, 254, 305)
18
(457)
18
(457)
36
(914)
3 12
(89)
12 x 14
(305 x 356)
14 x 14
(356 x 356)
9 14 x 10 12
(235 x 267)
14 x 16
(356 x 406)
16 x 16
(406 x 406)
8, 10, 12, 14
(203, 254, 305, 356)
26
(660)
18
(457)
41
(1041)
6
(152)
14 x 14
(356 x 356)
12 x 22
(305 x 559)
12 x 10 12
(305 x 267)
16 x 16
(406 x 406)
16 x 25
(406 x 635)
10, 12, 14
(254, 305, 356)
26
(660)
18
(457)
41
(1041)
5
(127)
14 x 14
(356 x 356)
12 x 22
(305 x 559)
13 14 x 11 12
(337 x 292)
16 x 16
(406 x 406)
16 x 25
(406 x 635)
12, 14, 16
(305, 356, 406)
30
(762)
19
(483)
44
(1118)
6
(152)
16 x 15
(406 x 381)
14 x 26
(356 x 660)
13 14 x 11 12
(337 x 292)
17 x 18
(432 x 457)
18 x 28
(457 x 711)
11-5-12
IW
IH
INDUCED
OPTIONAL
TOP
INLET
TW
(TWO)
W AIR
2
13 1/4"
(337)
FAN
MULTI-POINT
FLOW SENSOR
PRIMARY
PW
DW
W
AIR
PH
FAN
TW
INDUCED
AIR
DH
1" (25)
7 3/4"
(197)
TL
5 3/4"
(146)
14" (356)
14" (356)
OPTIONAL INDUCED
AIR FILTER
OPTIONAL INDUCED
AIR ATTENUATOR
OPTIONAL
PRIMARY
AIR VALVE
CONTROLS
ENCLOSURE
PRIMARY
AIR
H
2
11"
(279)
HINGED FAN
CONTROLS
ENCLOSURE
H1" (25) H
6"
(152)
%JNFOTJPOBM%BUB
6OJU
4J[F
11-5-12
*OMFU
4J[F
18Y1)
*OEVDFE"JS*OMFU
8
14 (356) Rd.
13 7 8 (352)
52
16 (406) Rd.
15 7 8 (403)
(1321)
3
7
20
16
x
13 8 (513 x 352)
18 (457) Oval
18
(457)
41
(1041)
4JEF TUE
*8Y*)
'JMUFS4J[F
0VUMFU
%JTDIBSHF
5PQ PQU
4JEF*OMFU 5PQ*OMFU
5-Y58 %8Y%)
TUE
PQU
12 x 14
(305 x 356)
Qty. of 2
8 1 2 x 20
(216 x 508)
Qty. of 2
14 x 16
16 x 25
(356 x 406) (406 x 635)
(997 x 292)
Qty. of 2
Qty. of 2
39 14 x 11 12
%
6OJU4J[FTo
.PEFM48
Available in one, two or three row. Coil
section installed on unit discharge. Right
hand coil connection looking in direction of
airflow standard (shown). Left hand is
optional
(terminals
are
inverted).
Connections must be selected same hand
as controls enclosure location.
4UBOEBSE'FBUVSFT
H
D
12" (305)
1 13/16"
(46)
FAN
HINGED FAN
CONTROLS
ENCLOSURE
3 9/16"
(90)
COIL CONNECTIONS
6OJU4J[F
12"
(305)
H
D
1 13/16"
(46)
FAN
FAN
HINGED FAN
CONTROLS
ENCLOSURE
3 9/16"
(90)
COIL CONNECTIONS
%
6OJU
4J[F
0VUMFU%VDU4J[F
$Y%
&
1, 2
16 x 12 18 (406 x 308)
21 38 (543)
14 (356)
16 x 14 8 (406 x 378)
21 38 (543)
18 (457)
1 916 (40)
4, 5
24 x 14 78 (610 x 378)
29 38 (746)
18 (457)
1 916 (40)
28 x 17 8 (711 x 435)
33 8 (848)
19 (483)
18 (457)
+
16 (24)
15
16 (24)
15
1 916 (40)
11-5-12
6OJU4J[FTo
N
4UBOEBSE'FBUVSFT
easy
access,
removal
and
replacement of heater element without
disturbing ductwork.
1"
(25)
FAN
F
K
HINGED FOR
ELEMENT REMOVAL
1"
(25)
5 1/2"
(140)
14" (356)
ELECTRIC COIL
AND HINGED FAN
CONTROLS ENCLOSURE
6OJU4J[F
N
M
1"
(25)
FAN
4UBOEBSE4VQQMZ7PMUBHF )[
120, 208, 240 and 277V, single phase.
F
0QUJPOT
Toggle disconnect switch (includes
fan).
57 3/4"
(1467)
FAN
HINGED FOR
ELEMENT REMOVAL
1"
(25)
5 3/4"
(140)
11-5-12
ELECTRIC COIL
AND HINGED FAN
CONTROLS ENCLOSURE
6OJU
4J[F
0VUMFU%VDU4J[F
'Y(
1, 2
10 14 x 10 12 (260 x 267)
15 12 (394)
14 (356)
2 12 (64)
12 12 (318)
10 4 x 10 2 (260 x 267)
15 12 (394)
18 (457)
2 12 (64)
15 14 (387)
13 x 10 12 (330 x 267)
21 (533)
18 (457)
5 (127)
15 14 (387)
14 4 x 11 4 (362 x 298)
22 (559)
18 (457)
4 (102)
15 14 (387)
14 14 x 11 34 (362 x 298)
25 (635)
19 (483)
5 (127)
15 14 (387)
40 4 x 11 4 (1022 x 298)
48 (1219)
18 (457)
4 (102)
15 14 (387)
%
Airflow
Min inlet
Ps
Pa
47
25
7
37
22
15
10
2
7
5
2
2
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
45
35
25
17
12
12
12
12
Fan
Only
24
33
25
24
33
26
26
27
20
25
20
22
20
31
27
22
28
25
22
34
30
26
37
34
29
25
31
28
25
20
36
34
29
20
Discharge attenuation
< 300 cfm
300 700 cfm
> 700 cfm
D20
Octave Band
2 3 4 5 6
24 28 39 53 59
27 29 40 51 53
29 30 41 51 52
7
40
39
39
Min.
Ps
23
30
24
21
30
24
23
27
21
25
22
20
30
26
21
26
25
20
34
29
25
37
32
27
22
29
27
25
20
36
32
27
20
Radiated attenuation
Total dB reduction
Octave Band
2 3 4 5 6 7
18 19 20 26 31 36
7-1-11
6
1
10
10
4
12
12
5
14
14
16
7
18
Fan Only
2
79
76
70
58
57
84
79
77
71
73
66
61
59
64
64
63
70
68
65
65
70
69
66
77
74
70
66
73
72
68
66
79
77
73
66
82
79
76
72
67
73
72
68
66
79
77
73
66
3
76
73
65
53
43
77
71
69
62
71
65
60
56
59
58
55
67
64
61
59
68
66
64
75
72
68
63
70
68
64
61
76
73
69
62
80
76
72
68
64
72
70
66
63
78
75
71
64
4
71
68
62
50
32
70
65
63
57
67
63
60
55
60
59
55
69
65
60
55
66
64
62
72
70
66
61
70
68
64
60
74
71
68
62
77
74
69
68
63
72
70
66
62
76
73
70
64
5
69
67
58
46
68
62
60
54
64
58
53
49
56
55
50
65
61
55
50
64
61
58
72
68
64
58
69
66
62
58
74
70
67
60
77
73
69
65
60
72
69
65
61
77
73
70
63
6
66
63
54
40
66
60
57
50
61
56
51
46
52
51
46
62
58
52
46
60
58
54
68
65
60
54
66
63
59
55
71
67
63
56
74
70
66
61
56
69
66
62
58
74
70
66
59
7
63
60
51
34
64
58
55
47
60
54
48
42
48
46
38
61
56
48
38
57
55
50
67
63
57
51
65
62
58
53
70
67
63
54
73
69
65
60
54
68
65
61
56
73
70
66
57
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure (Ps) shown
Minimum Ps
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps 2.0" wg (500Pa)Ps
2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
78 75 69 67 64 62 78 75 69 67 64 61 78 75 70 68 64 62 80 78 71 69 65 63 79 78 71 69 65 63
71 69 65 62 58 56 70 68 63 61 57 54 72 69 64 61 58 55 72 70 64 61 58 55 72 72 65 61 58 55
68 64 60 56 52 49 70 66 61 58 53 50 70 68 62 58 54 50 72 70 63 58 54 51 73 71 64 59 55 52
58 52 47 44 38 31 58 53 47 43 37 30 65 61 52 46 40 35 67 65 57 50 44 40 66 64 57 50 45 41
56 43 33 - - - 57 46 36 26 - - 58 49 41 30 23 22 57 48 45 33 27 26 54 46 44 35 29 28
81 74 67 65 62 60 81 73 66 64 62 59 81 73 66 64 61 59 81 73 66 64 62 59 81 73 66 64 62 59
77 69 63 60 58 55 76 68 62 59 56 54 77 68 62 60 57 54 77 69 63 60 57 54 77 69 63 60 57 55
75 67 61 58 55 53 73 65 60 57 54 51 75 66 60 57 54 51 74 67 61 57 54 52 75 67 61 58 55 52
69 61 56 52 48 45 69 61 55 51 48 44 69 61 55 51 48 44 70 62 56 52 48 45 70 62 57 53 49 46
73 71 67 64 61 59 73 72 68 64 61 60 71 66 64 61 58 57 75 71 68 64 62 60 75 73 68 65 62 61
66 66 64 58 56 54 69 66 64 59 57 55 68 65 63 59 56 55 69 66 63 59 57 55 70 67 64 59 57 55
61 59 61 53 50 47 63 60 61 54 51 48 65 62 59 54 52 49 66 61 59 55 52 50 67 64 60 55 52 50
59 55 52 48 45 40 61 57 55 50 47 42 62 59 55 50 47 43 63 59 56 50 47 44 63 60 57 51 48 44
65 59 60 55 51 48 66 61 61 56 52 48 67 62 61 56 52 48 69 64 61 56 52 48 69 64 62 58 52 48
64 58 59 54 50 45 65 60 60 55 51 46 66 61 60 55 51 46 67 61 60 55 51 46 67 63 60 55 49 46
63 55 55 50 45 37 64 56 56 50 45 38 65 57 56 50 45 38 65 58 56 49 44 38 65 58 56 49 44 38
69 67 69 64 61 60 73 70 69 64 63 61 74 70 70 66 64 62 75 70 70 67 64 62 76 71 70 67 64 62
67 64 64 60 57 55 69 66 66 62 59 56 71 67 66 63 60 57 72 67 66 63 60 58 72 68 66 63 60 58
65 61 59 55 51 48 67 62 61 57 53 49 68 63 61 57 54 50 68 62 61 57 53 50 69 64 61 57 53 50
64 59 55 50 45 38 65 59 56 51 46 39 66 60 56 50 46 39 66 60 56 50 46 39 67 60 56 50 45 40
71 68 66 64 60 58 71 68 66 64 60 58 72 69 66 64 61 59 74 68 67 64 61 59 74 70 67 64 61 59
69 66 64 61 58 55 70 66 64 62 58 56 71 67 65 62 58 56 72 68 64 62 58 56 73 69 65 62 58 56
66 63 61 58 54 51 67 64 62 59 55 51 69 64 62 59 55 51 70 64 62 58 55 52 71 66 62 59 55 52
75 74 72 71 68 67 77 75 73 72 69 68 78 76 73 72 69 68 78 75 73 72 69 68 79 76 73 72 69 68
73 71 70 67 64 63 75 72 70 68 65 64 75 73 70 68 65 64 76 73 70 68 65 64 76 73 70 68 65 64
69 67 67 62 59 56 71 67 67 63 59 57 71 67 67 62 59 57 72 66 67 62 59 57 73 69 67 62 59 57
65 62 61 58 54 50 67 64 61 58 54 51 68 63 61 58 54 50 69 64 61 57 54 50 69 64 61 58 54 51
73 69 69 67 64 63 75 71 70 68 65 65 76 72 70 68 65 65 77 71 70 68 65 65 77 72 70 68 64 64
70 66 66 64 61 61 73 68 67 64 62 62 74 69 67 65 62 62 74 69 67 64 61 61 75 69 68 65 62 61
66 63 63 60 57 57 69 65 63 61 58 58 70 65 64 61 58 57 71 64 64 61 57 57 72 67 64 61 57 57
64 60 60 57 53 53 66 61 60 58 54 53 68 62 60 57 54 53 69 63 61 57 54 53 70 64 61 57 54 53
79 76 74 73 7 70 79 76 75 73 70 70 80 77 75 73 71 70 80 77 75 73 71 70 81 77 75 73 70 70
75 71 71 69 66 66 77 73 72 70 67 66 78 73 72 70 67 66 78 73 71 69 66 66 78 73 71 69 66 66
70 66 67 62 61 61 73 69 67 65 62 62 74 68 67 65 62 62 74 67 67 65 61 61 74 69 67 65 61 62
65 61 60 58 54 53 66 62 61 58 55 54 67 62 61 58 54 54 69 63 61 58 54 54 70 64 61 58 55 54
80 80 78 78 75 74 82 80 78 78 75 74 82 81 79 78 75 74 83 80 79 78 75 75 84 81 79 79 76 75
76 75 74 72 69 69 78 76 75 73 70 69 79 76 75 73 70 70 80 77 75 74 70 70 80 77 75 74 71 70
73 70 70 68 64 64 75 72 71 68 65 65 76 72 71 69 66 65 76 71 72 69 66 66 77 73 72 69 66 65
69 66 66 63 60 58 71 68 66 64 60 59 72 68 67 64 61 60 73 68 67 64 61 60 73 68 67 64 60 59
65 62 62 59 65 52 67 64 63 60 56 54 68 64 63 60 56 54 69 64 63 60 56 54 70 65 63 60 56 54
73 71 71 70 67 66 75 73 72 71 68 68 76 74 72 71 68 68 77 73 72 71 68 68 77 74 72 71 67 67
70 68 68 67 64 64 73 70 69 67 65 65 74 71 69 68 65 65 74 71 69 67 64 64 75 71 70 68 65 64
66 65 65 63 60 60 69 67 65 64 61 61 70 67 66 64 61 60 70 67 66 64 61 60 72 69 66 64 60 60
64 62 62 60 56 56 66 63 62 61 57 56 68 64 62 60 57 56 68 64 62 60 57 56 70 66 63 60 57 56
79 78 76 76 73 73 79 78 77 76 73 73 80 79 77 76 74 73 80 79 77 76 74 73 81 79 77 76 73 73
75 73 73 72 69 69 77 75 74 73 70 69 78 75 74 73 70 69 78 75 74 73 70 69 78 75 73 72 69 69
70 68 69 65 64 64 73 71 69 68 65 65 74 70 69 68 65 65 74 70 69 68 65 65 74 71 69 68 64 65
65 63 62 61 57 56 66 64 63 61 58 57 67 64 63 61 57 57 67 64 63 61 57 57 70 66 63 61 58 57
For performance table notes, see page D26; 3&% highlighted numbers indicate embedded AHRI certification points.
6-21-13
%
500 236
400 189
300 142
200 94
75 35
400 189
300 142
250 118
200 94
675 319
550 260
450 212
300 142
700 330
600 283
450 212
1200 566
900 425
700 330
450 212
1100 519
1000 472
850 401
1500 708
1300 613
1100 519
850 401
1600 755
1400 661
1200 566
1050 495
1925 908
1700 802
1400 661
1050 495
2300 1085
2000 944
1700 802
1400 661
1100 519
3050 1439
2700 1274
2300 1085
2000 944
3650 1722
3250 1534
2600 1227
2000 944
Min. inlet
Ps
"w.g. Pa
0.15 37
0.20 50
0.09 22
0.04 10
0.01 2
0.03 7
0.02 5
0.01 2
0.01 2
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.18 45
0.14 35
0.10 25
0.07 17
0.05 12
0.05 12
0.05 12
0.05 12
6
1
8
3
10
10
4
12
12
5
14
14
16
7
18
500
400
300
200
75
400
300
250
200
670
550
450
300
700
600
450
1200
900
700
450
1100
1000
850
1500
1300
1100
850
1600
1400
1200
1050
1925
1700
1400
1050
2300
2000
1700
1400
1100
3050
2700
2300
2000
3650
3250
2600
2000
236
189
142
142
35
189
142
118
94
316
260
212
142
330
283
212
566
425
330
212
519
472
401
708
614
519
401
755
661
566
495
908
802
661
496
1086
944
802
661
519
1440
1274
1080
948
1723
1534
1227
944
Min. inlet
Ps
" w.g. Pa
0.57 141
0.20 50
0.09 22
0.04 22
0.01 2
0.03 7
0.02 5
0.01 2
0.01 2
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.18 45
0.14 35
0.10 25
0.07 17
0.05 12
0.05 12
0.05 12
0.05 12
Fan Only
2 3
74 62
70 58
68 54
62 48
57 43
74 63
68 56
67 55
65 52
63 58
61 55
58 51
57 49
62 52
61 51
55 43
68 59
66 55
60 52
54 48
68 60
65 56
64 54
74 65
72 63
68 60
64 55
75 66
73 62
71 60
68 56
76 71
73 67
71 64
68 57
76 71
74 68
72 65
69 62
65 57
78 69
76 65
74 63
71 59
79 74
76 70
74 67
71 60
4
53
50
47
42
36
56
49
48
46
55
52
47
45
52
51
49
57
54
51
48
54
51
50
58
58
54
50
58
55
53
50
61
59
56
50
64
61
59
56
53
61
58
56
53
64
62
59
53
5
49
44
39
34
27
51
43
42
39
49
45
40
37
46
44
40
52
49
44
39
50
49
46
56
53
50
45
53
50
47
44
57
54
50
44
61
58
55
51
47
56
53
50
47
60
57
53
47
6 7
44 41
38 35
33 30
28 33
- 46 43
37 34
36 33
34 30
43 41
39 37
34 31
31 28
43 39
42 37
37 31
51 47
46 42
41 36
35 28
47 43
44 40
41 37
54 51
51 47
47 43
41 36
51 48
47 44
45 41
41 37
56 53
52 50
48 46
41 37
59 56
55 52
52 48
47 43
42 39
54 51
50 47
48 44
44 40
59 56
55 53
51 49
44 40
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure (Ps) shown
Minimum Ps
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps 2.0" wg (500Pa)Ps
2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
74 60 56 51 47 44 * * * * * * 74 62 54 51 53 54 74 63 59 57 57 60 75 64 61 59 58 62
71 58 53 47 42 38 71 58 51 46 46 43 71 58 55 51 53 53 72 61 58 55 56 59 72 62 60 57 58 61
65 52 47 40 34 30 66 53 48 43 46 43 67 55 52 49 52 52 67 58 55 52 56 58 68 59 57 54 57 59
61 47 43 33 27 22 62 49 45 42 45 43 63 52 48 46 51 49 64 55 52 49 54 54 64 55 54 51 55 55
52 39 34 24 - - 53 42 38 35 33 30 55 43 42 39 39 37 55 44 46 43 44 43 55 43 42 42 45 45
72 60 54 48 43 41 72 60 54 49 48 46 72 61 55 51 53 52 73 63 58 53 55 57 73 64 59 55 57 59
69 57 51 45 40 37 68 57 51 46 45 43 69 59 53 48 51 50 70 60 55 50 53 53 70 60 56 52 55 56
66 52 47 40 34 31 66 54 48 43 44 41 67 56 50 46 49 48 67 57 53 49 51 51 67 57 54 51 52 52
64 51 45 38 33 29 64 51 46 41 42 39 65 53 48 44 46 44 64 54 50 47 48 47 65 54 52 48 50 50
64 59 56 50 44 42 66 62 58 54 53 52 69 65 61 57 57 58 70 66 63 59 60 62 71 69 64 61 61 64
61 55 52 45 40 37 63 59 55 51 51 49 66 63 58 55 55 55 67 65 60 57 58 59 68 67 62 59 60 62
59 51 44 39 34 31 61 56 52 49 49 46 63 60 55 52 53 53 64 61 58 55 56 57 65 64 60 57 58 59
57 43 44 35 30 27 56 52 48 45 45 42 59 56 52 49 49 47 60 58 55 53 53 51 61 59 57 56 56 54
63 53 52 46 44 39 65 56 54 52 52 50 66 59 57 55 58 59 68 61 60 58 61 64 69 65 62 60 64 67
61 52 51 45 41 37 63 55 53 50 52 50 65 58 56 54 58 58 66 61 59 57 61 63 67 63 60 59 63 65
57 48 48 40 36 30 59 51 50 48 49 48 60 54 53 51 55 54 63 57 56 56 60 60 63 59 58 58 61 61
67 60 57 52 51 47 69 62 59 56 57 55 71 65 61 58 61 61 72 65 64 61 64 65 68 68 65 63 66 68
64 56 54 48 46 42 66 58 56 53 54 52 68 60 59 56 60 60 70 64 62 60 63 64 68 66 63 61 65 67
58 51 50 43 40 36 61 55 53 50 51 48 64 59 56 54 57 57 65 60 59 57 61 62 66 62 60 59 64 66
55 47 48 39 34 27 56 50 49 46 48 45 58 55 53 51 56 55 59 56 55 54 59 60 62 58 57 59 61 62
68 60 54 50 48 45 70 63 57 54 58 58 72 67 61 57 62 65 73 68 64 60 64 69 74 71 65 61 65 71
66 58 53 49 46 42 69 61 56 53 57 57 70 65 59 55 61 63 72 68 62 58 61 68 73 70 65 61 65 71
64 55 51 46 42 37 66 59 53 51 55 55 68 63 58 55 60 63 70 65 61 57 62 67 70 67 63 59 64 70
71 65 59 55 54 52 73 67 61 57 58 56 75 69 64 60 61 63 76 71 66 62 64 67 76 73 68 64 65 70
69 63 57 53 50 48 70 65 59 55 56 55 72 67 63 58 61 62 73 69 65 61 63 67 74 71 67 63 65 69
66 59 54 49 46 43 68 62 57 53 55 54 70 65 61 57 60 61 71 66 64 60 62 66 72 69 65 61 64 68
62 54 50 44 40 35 64 58 54 50 53 51 66 62 58 54 59 60 68 65 61 57 61 64 68 66 63 59 63 66
73 65 58 52 50 48 74 67 63 56 58 57 74 69 64 59 62 64 75 70 67 63 64 68 76 73 69 65 66 71
70 61 55 48 46 44 72 65 60 54 56 55 73 67 63 58 61 63 73 70 66 61 64 68 74 72 68 64 65 70
68 58 52 46 43 40 67 62 57 52 55 54 70 65 61 58 60 62 71 67 64 60 63 66 72 70 66 62 64 69
65 55 50 43 39 36 66 60 55 50 54 53 67 63 59 56 60 61 70 66 62 58 62 65 71 69 65 61 64 68
75 69 62 58 55 53 76 71 64 59 61 61 77 72 66 61 64 66 77 73 67 63 66 70 78 75 69 65 67 73
72 65 59 53 51 49 74 68 61 56 59 59 75 70 64 59 63 66 75 71 65 61 64 69 76 72 67 63 66 71
69 61 55 49 46 44 71 65 58 54 57 57 72 67 61 57 62 64 73 67 63 59 64 68 73 70 64 61 65 70
63 55 50 43 40 37 66 59 53 50 55 53 68 62 57 54 60 62 69 64 59 56 62 65 69 66 62 59 64 69
77 73 65 62 59 57 77 74 67 63 64 65 79 75 68 64 66 69 79 75 69 65 67 71 80 77 71 67 69 73
74 70 62 58 55 52 75 71 64 60 61 62 76 72 65 62 64 67 77 73 67 64 66 70 77 75 69 65 68 73
70 65 59 54 50 47 72 68 61 57 59 59 73 69 63 59 63 66 74 70 65 62 65 69 75 72 67 63 67 72
67 61 56 50 46 42 69 63 58 54 57 56 70 66 61 57 62 64 71 68 63 60 64 68 72 70 65 61 66 71
63 57 52 46 41 36 65 59 54 51 56 54 67 63 58 55 61 63 69 66 61 58 63 67 69 68 63 59 65 69
76 68 61 55 53 51 77 70 66 59 61 60 77 72 67 62 65 67 81 76 73 69 70 74 82 79 75 71 72 77
73 64 58 51 49 47 75 68 63 57 59 58 76 70 66 61 64 66 76 73 69 64 67 71 77 75 71 67 68 73
71 61 55 49 46 43 70 65 60 55 58 57 73 68 64 61 63 65 74 70 67 63 66 69 75 73 69 65 67 72
68 58 53 46 42 39 69 63 58 53 57 56 70 66 62 59 63 64 73 69 65 61 65 68 74 72 68 64 67 71
78 72 65 61 58 56 79 74 67 62 64 64 80 75 69 64 67 69 80 76 70 66 69 73 81 78 72 68 70 76
75 68 62 56 54 52 77 71 64 59 62 62 78 73 67 62 66 69 78 74 68 64 67 72 79 75 70 66 69 74
72 64 58 52 49 47 74 68 61 57 60 60 75 70 64 60 65 67 76 70 66 62 67 71 76 73 67 64 68 73
66 58 53 46 43 40 69 62 56 53 58 56 71 65 60 57 63 65 72 67 62 59 65 68 72 69 65 62 67 72
For performance table notes, see page D26; RED highlighted numbers indicate embedded AHRI certification points.
D24
6-24-13
1
2
3
4
5
6
7
6
8
10
12
14
16
16
Fan CFM
cfm
l/s
400
700
1100
1500
1800
2400
3500
189
330
519
708
849
1133
1652
Fan
Watts
100
190
350
570
600
950
1380
Discharge
4 5 6
76
72
75
81
81
82
82
73
70
74
79
78
80
79
68
65
73
75
73
77
76
67
65
72
74
73
77
76
63
62
68
71
71
74
74
60
60
66
70
70
73
73
70
69
73
76
77
77
79
58
60
64
66
67
72
75
Radiated
4 5 6
50
54
61
59
60
65
67
44
51
57
57
57
62
60
38
44
54
55
54
60
55
Primary
CFM
7
cfm
35
41
50
52
50
57
54
400
700
1100
1500
1800
2400
3500
Min. Inlet
Ps
l/s " w.g. Pa
189
330
519
708
849
1133
1652
0.20
0.05
0.05
0.05
0.05
0.05
0.10
50
12
12
12
12
12
25
Radiated
4
5
72
71
74
81
80
81
83
61
66
69
72
73
76
79
58
61
65
69
66
71
73
56
57
62
62
61
68
62
59
61
64
63
63
73
63
55
58
63
65
62
67
65
2-12-15
D25
Unit Size 1
l/s CFM
425 900
212 450
378 800
189 400
MAXIMUM
330 700
MAXIMUM
165 350
283 600
NO HEAT OR
ELECTRIC HEAT
118 250
1 OR 2 ROW
H. W. COIL
94 200
AIRFLOW
AIRFLOW
142 300
Unit Size 2
NO HEAT OR
ELECTRIC HEAT
1 OR 2 ROW
H. W. COIL
236 500
189 400
71 150
142 300
MINIMUM
47 100
MINIMUM
24
50
94 200
47 100
0.0
0
l/s CFM
613 1300
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
0.0
0
Unit Size 3
MAXIMUM
708 1500
472 1000
NO HEAT OR
ELECTRIC HEAT
1 OR 2 ROW
H. W. COIL
661 1400
ELECTRIC HEAT
613 1300
1 OR 2 ROW
H. W. COIL
425
900
378
800
330
700
472 1000
283
600
425
900
378
800
236
500
330
700
189
400
283
600
236
500
MINIMUM
300
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
AIRFLOW
AIRFLOW
MAXIMUM
755 1600
519 1100
142
Unit Size 4
l/s CFM
849 1800
802 1700
566 1200
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
566 1200
519 1100
MINIMUM
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Electrical Data
Fan Curves shown are applicable to
120, 208, 240 and 277 volt, single
phase PSC motors.
D26
2-27-14
l/s CFM
991 2100
944 2000
l/s CFM
1274 2700
1227 2600
MAXIMUM
MAXIMUM
1180 2500
897 1900
1133 2400
849 1800
1085 2300
802 1700
1038 2200
ELECTRIC HEAT
991 2100
708 1500
1 OR 2 ROW
H. W. COIL
661 1400
613 1300
AIRFLOW
755 1600
AIRFLOW
Unit Size 6
ELECTRIC HEAT OR
1 OR 2 ROW
H. W. COIL
944 2000
897 1900
849 1800
802 1700
566 1200
755 1600
519 1100
708 1500
661 1400
472 1000
613 1300
900
378
800
330
700
566 1200
MINIMUM
MINIMUM
519 1100
425
472 1000
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Unit Size 7
l/s CFM
1888 4000
MAXIMUM
1793 3800
1699 3600
1604 3400
1510 3200
ELECTRIC HEAT
AIRFLOW
1416 3000
1 OR 2 ROW
H. W. COIL
1321 2800
1227 2600
1133 2400
1038 2200
944 2000
849 1800
755 1600
MINIMUM
661 1400
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Electrical Data
Fan Curves shown are applicable to
120, 208, 240 and 277 volt, single
phase PSC motors.
2-27-14
D27
l/s CFM
260
550
236
500
212
450
Unit Size 2
l/s CFM
425 900
MAXIMUM
189
400
165
350
142
300
118
250
94
200
71
150
47
100
378
800
330
700
283
600
236
500
189
400
142
300
94
200
47
100
MAX. COOLING
1 ROW HW COIL
2 ROW HW COIL
AIRFLOW
AIRFLOW
MAXIMUM
3 ROW HW COIL
MINIMUM
24
MINIMUM
50
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
0.1
25
Unit Size 3
l/s CFM
566 1200
0.2
0.3
0.4
50
75
100
DISCHARGE STATIC PRESSURE
Unit Size 4
l/s CFM
755 1600
MAXIMUM
MAXIMUM
519 1100
MAX. COOLING
HW COIL:
1 ROW
2 ROW
3 ROW
661 1400
900
378
800
330
700
283
600
236
500
189
400
142
300
94
200
47
100
566 1200
AIRFLOW
AIRFLOW
472 1000
425
472 1000
378
800
283
600
189
400
94
200
MINIMUM
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
MINIMUM
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Electrical Data
NOTES:
277V
1.5
2.5
3.1
4.4
D28A
2-4-16
l/s CFM
991 2100
Unit Size 6
l/s CFM
1133 2400
MAXIMUM
NO HEAT/
ELECTRIC HEAT
897 1900
MAXIMUM
1038 2200
1 ROW HW COIL
802 1700
2 ROW HW COIL
944 2000
3 ROW HW COIL
849 1800
AIRFLOW
AIRFLOW
708 1500
613 1300
519 1100
755 1600
661 1400
425
900
566 1200
330
700
472 1000
236
500
800
283
600
MINIMUM
142
MINIMUM
300
0.0
0
378
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Unit Size 7
l/s CFM
1888 4000
MAXIMUM
NO HEAT/
ELECTRIC HEAT
1 ROW HW COIL
1652 3500
2 ROW HW COIL
AIRFLOW
1416 3000
3 ROW HW COIL
1180 2500
944 2000
708 1500
472 1000
236
MINIMUM
500
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Electrical Data
EPIC ECM Motor FLA
Unit
Size Motor HP 120V
208V
240V
5
9.6
6.2
5.9
*
6
13.6
7.3
6.9
*
7
17.5
11.1
11.4
*
NOTES:
277V
5.8
6.3
11.4
2-10-16
D28B
.PEFMT
445
/P)FBU
4&45
&MFDUSJD)FBU
4845
)PU8BUFS)FBU
Model 35SEST
The 4454UFBMUI5.4FSJFT has been especially designed for the most demanding applications where premium
quality design and performance characteristics are desired. Utilizing "StealthTM" design technology, this terminal unit
has low sound levels that lead the industry.
Unique 16 ga. (1.6) galvanized
steel
channel
space
frame
construction provides extreme rigidity
and 20 ga. (1.00) casing components.
16 ga. (1.6) galvanized steel
inclined opposed blade primary air
damper. 45O rotation, CW to close.
1/2" (13) dia. plated steel drive shaft.
An indicator mark on the end of the
shaft shows damper position.
Leakage is less than 2% of nominal
flow at 3" w.g. (750 Pa).
"StealthTM" design technology
provides significant reductions in
radiated sound levels.
Perforated baffle on primary air
discharge optimizes mixing with
induced air for rapid and effective
temperature equalization. The baffle
also converts low frequency primary
air valve generated sound into more
readily attenuated higher frequencies.
Pressure independent primary
airflow control.
Multi-point averaging flow sensor.
Terminal may be field installed
either way up, providing the additional
flexibility of right or left field
connections.
Universal access panels on all four
sides of terminal for ease of
maintenance and service.
Energy efficient PSC fan motor with
7-1-11
0QUJPOT
EPICTM /ECM Motor.
Primary air valve enclosure for field
mounted controls.
Induced air filter, 1" (25) thick,
disposable type.
Toggle disconnect switch (except
units with electric heat, when
disconnect is an electric heat option
and includes fan).
Various 'IAQ' linings are available.
Fan airflow or P.E. switch for night
shutdown (pneumatic controls).
Fan airflow switch for night
shutdown (analog electronic controls).
Night setback fan/heat cycle
(pneumatic and analog).
Fan unit fusing.
Hanger brackets.
FN2 90 Line Voltage enclosure.
Low temperature construction
(ice storage systems).
$POUSPMT
Pneumatic and analog electronic
controls. Factory supplied, mounted
and calibrated.
Digital controls. Factory mounting
and wiring of DDC controls supplied
by BMS Controls Contractor.
%
'&"563&4
INDUCED
OPTIONAL
INDUCED
AIR FILTER
AIR
7 1/4"
(184)
MULTI-POINT
FLOW SENSOR
DIA. =
NOM.
1/8" (3)
IW
1" (25)
B
W
2
PRIMARY
FAN
DW
W
AIR
DH
1" (25)
5 3/4"
(146)
14" (356)
DRIVESHAFT
OPTIONAL
PRIMARY
AIR VALVE
CONTROLS
ENCLOSURE
PRIMARY
AIR
14" (356)
L
H
2
11"
(279)
HINGED FAN
CONTROLS
ENCLOSURE
H1" (25) H
6" (152)
%JNFOTJPOBM%BUB
%
6OJU
4J[F
*OMFU
4J[F
*OEVDFE"JS
*OMFU
*8Y*)
0VUMFU
%JTDIBSHF
%8Y%)
'JMUFS
4J[F
4, 6, 8
(102, 152, 203)
18
(457)
14
(356)
36
(914)
3 12
(152)
9 x 14
(229 x 356)
7 14 x 10 12
(184 x 267)
10 x 14
(254 x 356)
6, 8
(152, 203)
18
(457)
14
(356)
36
(914)
3 12
(152)
9 x 14
(229 x 356)
9 14 x 10 12
(253 x 267)
10 x 14
(254 x 356)
6, 8, 10, 12
(152, 203, 254, 305)
18
(457)
18
(457)
36
(914)
3 13
(89)
11 x 18
(279 x 457)
9 14 x 10 12
(253 x 267)
12 x 18
(305 x 457)
8, 10, 12, 14
(203, 254, 305, 356)
26
(660)
18
(457)
41
(1041)
6
(152)
15 34 x 14
(400 x 356)
12 x 10 12
(305 x 267)
16 x 14
(406 x 356)
10, 12, 14
(254, 305, 356)
26
(660)
18
(457)
41
(1041)
5
(127)
14 12 x 18
(368 x 457)
13 14 x 11 12
(337 x 292)
14 x 18
(356 x 457)
12, 14, 16
(305, 356, 406)
30
(762)
19
(483)
44
(1118)
6
(152)
17 12 x 19
(444 x 483)
13 14 x 11 12
(337 x 292)
18 x 19
(457 x 483)
7-1-11
16 1/4" (413)
16" INDUCED
(406)
AIR
IW
32 1/4"
(819)
5"
(127)
42"
(1067)
13 1/4"
(337)
FAN
PRIMARY
DW
84"
(2134)
AIR
MULTI-POINT
FLOW SENSOR
DIA. =
NOMINAL - 1/8" (3)
FAN
DH
1" (25)
DRIVESHAFT
7 3/4"
(197)
5 3/4"
(146)
14" (356)
INDUCED
14" (356)
AIR
OPTIONAL
PRIMARY
AIR VALVE
CONTROLS
ENCLOSURE
PRIMARY
AIR
H
2
11"
(279)
HINGED FAN
CONTROLS
ENCLOSURE
H1" (25) H
OPTIONAL
INDUCED
AIR FILTER
6" (152)
%JNFOTJPOBM%BUB
11-12-12
6OJU
4J[F
*OMFU
4J[F
*OEVDFE"JS
*OMFU
*8Y*)
0VUMFU
%JTDIBSHF
%8Y%)
'JMUFS
4J[F
14, 16
(356, 406)
52
(1321)
18
(457)
41
(1041)
11 14 x 13 14
(286 x 337)
Qty. of 2
39 14 x 11 12
(997 x 292)
14 x 14
(356 x 356)
Qty. of 2
%
6OJU4J[FTo
INDUCED
IW
AIR
12" (305)
4UBOEBSE'FBUVSFT
1 13/16"
(46)
FAN
HINGED FAN
CONTROLS
ENCLOSURE
3 9/16"
(90)
COIL CONNECTIONS
6OJU4J[F
12"
(305)
H
D
1 13/16"
(46)
FAN
HINGED FAN
CONTROLS
ENCLOSURE
3 9/16"
(90)
COIL CONNECTIONS
%
6OJU
4J[F
0VUMFU%VDU4J[F
$Y%
&
1, 2
16 x 12 18 (406 x 308)
21 38 (543)
14 (356)
16 x 14 8 (406 x 378)
21 8 (543)
18 (457)
1 916 (40)
4, 5
24 x 14 8 (610 x 378)
29 8 (746)
18 (457)
1 916 (40)
28 x 17 18 (711 x 435)
33 38 (848)
19 (848)
18 (457)
+
16 (24)
15
16 (24)
15
1 916 (40)
7-1-11
INDUCED
IW
AIR
1"
(25)
FAN
HEATER
HINGED FOR
ELEMENT REMOVAL
1"
(25)
ELECTRIC
COIL AND
HINGED FAN
CONTROLS
ENCLOSURE
5 3/4"
(146)
14" (356)
H
Unit Size 7
H
N
M
1"
(25)
FAN
Options:
Toggle disconnect switch (includes
fan).
F
K
HINGED FOR
ELEMENT REMOVAL
1"
(25)
SCR Control.
5 1/2"
(140)
14" (356)
11-12-12
ELECTRIC COIL
AND HINGED FAN
CONTROLS ENCLOSURE
Unit
Size
1, 2
10 14 x 10 12 (260 x 267)
15 12 (394)
14 (356)
2 12 (64)
12 12 (318)
10 4 x 10 2 (260 x 267)
15 2 (394)
18 (457)
2 2 (64)
15 14 (387)
13 x 10 2 (330 x 267)
21 (533)
18 (457)
5 (127)
15 14 (387)
14 14 x 11 34 (362 x 298)
22 (559)
18 (457)
4 (102)
15 14 (387)
14 4 x 11 4 (362 x 298)
25 (635)
19 (635)
5 (127)
15 14 (387)
40 14 x 11 34 (1022 x 298)
48 (1219)
18 (457)
4 (102)
15 14 (387)
D33
8
3
10
10
4
12
12
5
14
14
16
Airflow
cfm
l/s
250
175
100
400
300
250
200
100
400
300
250
200
670
550
450
300
700
600
450
1200
900
700
450
1100
1000
850
1500
1300
1100
850
1600
1400
1200
1050
1925
1700
1400
1050
2300
2000
1700
1400
1100
3500
3000
2500
2000
1500
118
83
47
189
142
118
94
47
189
142
118
94
316
260
212
142
330
283
212
566
425
330
212
519
472
401
708
614
519
401
755
661
566
495
909
802
661
496
1086
944
802
661
519
1652
1416
1180
944
708
Min inlet
Ps
" w.g. Pa
0.19
0.10
0.03
0.15
0.09
0.06
0.04
0.01
0.03
0.02
0.01
0.01
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.24
0.17
0.12
0.07
0.05
47
25
7
37
22
15
10
2
7
5
2
2
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
60
42
30
17
12
Fan
Only
24
33
25
24
33
26
26
27
20
25
20
22
20
31
27
22
28
25
22
34
30
26
37
34
29
25
39
33
26
20
-
Min.
Ps
23
30
24
21
30
24
23
27
21
25
22
20
30
26
21
26
25
20
34
29
25
37
32
27
22
32
29
23
-
2.0" wg
(500 Pa)
31
25
23
39
34
30
28
20
36
31
29
25
40
36
35
27
35
34
29
39
36
34
30
38
36
34
35
39
36
33
40
39
36
36
40
40
36
34
43
40
37
35
34
49
46
44
41
38
&YQMBOBUJPOPG/$-FWFMT
1. NC levels are calculated from the published raw
data and based on procedures outlined in Appendix
E, AHRI 885-2008.
2. Discharge sound attenuation deductions are based
on environmental effect, duct lining, branch power
division, insulated flex duct, end reflection and space
effect and are as follows:
Discharge attenuation
< 300 cfm
300 700 cfm
> 700 cfm
%
Octave Band
2 3 4 5 6
24 28 39 53 59
27 29 40 51 53
29 30 41 51 52
7
40
39
39
Radiated attenuation
Total dB reduction
Octave Band
2 3 4 5 6 7
18 19 20 26 31 36
7-1-11
1
8
10
10
4
12
12
5
14
14
16
Fan Only
2
78
73
68
62
59
84
79
77
71
73
66
61
59
64
64
63
70
68
65
65
70
69
66
77
74
70
66
73
72
68
66
79
77
73
66
82
79
76
72
67
76
73
68
62
56
3
75
70
64
54
48
77
71
69
62
71
65
60
56
59
58
55
67
64
61
59
68
66
64
75
72
68
63
70
68
64
61
76
73
69
62
80
76
72
68
64
77
72
67
61
56
4
69
66
61
54
41
70
65
63
57
67
63
60
55
60
59
55
69
65
60
55
66
64
62
72
70
66
61
70
68
64
60
74
71
68
62
77
74
69
68
63
76
73
68
63
56
5
67
63
56
46
36
68
62
60
54
64
58
53
49
56
55
50
65
61
55
50
64
61
58
72
68
64
58
69
66
62
58
74
70
67
60
77
73
69
65
60
77
73
67
61
54
6
64
60
52
41
28
66
60
57
50
61
56
51
46
52
51
46
62
58
52
46
60
58
54
68
65
60
54
66
63
59
55
71
67
63
56
74
70
66
61
56
75
70
64
57
50
7
61
57
49
34
20
64
58
55
47
60
54
48
42
48
46
38
61
56
48
38
57
55
50
67
63
57
51
65
62
58
53
70
67
63
54
73
69
65
60
54
75
70
63
56
47
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure (Ps) shown
Minimum Ps
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps 2.0" wg (500Pa)Ps
2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
78 75 68 66 63 60 76 73 67 65 62 59 77 74 67 66 62 59 78 75 68 66 62 60 78 75 68 66 62 60
73 69 65 62 58 56 72 69 64 61 57 55 73 70 65 62 58 55 73 71 65 61 58 55 74 71 66 62 58 55
68 63 59 56 52 49 69 63 59 55 51 48 68 64 60 55 51 48 70 65 60 56 51 48 70 66 61 56 52 49
61 53 51 45 40 33 61 55 52 46 40 34 63 57 54 47 42 36 64 59 55 48 43 38 63 60 57 49 44 39
57 47 39 34 26 19 57 48 42 35 28 20 58 49 44 37 30 24 59 50 48 39 32 27 57 49 46 39 33 29
81 74 67 65 63 60 81 73 66 64 62 59 81 73 66 64 61 59 81 73 66 64 62 59 81 73 66 64 62 59
77 69 63 60 58 55 76 68 62 59 56 54 77 68 62 60 57 54 77 69 63 60 57 54 77 69 63 60 57 55
75 67 61 58 55 53 73 65 60 57 54 51 75 66 60 57 54 51 74 67 61 57 54 52 75 67 61 58 55 52
69 61 56 52 48 45 69 61 55 51 48 44 69 61 55 51 48 44 70 62 56 52 48 45 70 62 57 53 49 46
73 71 67 64 61 59 73 72 68 64 61 60 74 72 67 64 62 60 75 71 68 64 62 60 75 73 68 65 62 61
66 66 64 58 56 54 69 66 64 59 57 55 68 65 63 59 56 55 69 66 63 59 57 55 70 67 64 59 57 55
61 59 61 53 50 47 63 60 61 54 51 48 65 62 59 54 52 49 66 61 59 55 52 50 67 64 60 55 52 50
59 55 52 48 45 40 61 57 55 50 47 42 62 59 55 50 47 43 63 59 56 50 47 44 63 60 57 51 48 44
65 59 60 55 51 48 66 61 61 56 52 48 67 62 61 56 52 48 69 64 61 56 52 48 69 64 62 58 52 48
64 58 59 54 50 45 65 60 60 55 51 46 66 61 60 55 51 46 67 61 60 55 51 46 67 63 60 55 49 46
63 55 55 50 45 37 64 56 56 50 45 38 65 57 56 50 45 38 65 58 56 49 44 38 65 58 56 49 44 38
69 67 69 64 61 60 73 70 69 64 63 61 74 70 70 66 64 62 75 70 70 67 64 62 76 71 70 67 64 62
67 64 64 60 57 55 69 66 66 62 59 56 71 67 66 63 60 57 72 67 66 63 60 58 72 68 66 63 60 58
65 61 59 55 51 48 67 62 61 57 53 49 68 63 61 57 54 50 68 62 61 57 53 50 69 64 61 57 53 50
64 59 55 50 45 38 65 59 56 51 46 39 66 60 56 50 46 39 66 60 56 50 46 39 67 60 56 50 45 40
71 68 66 64 60 58 71 68 66 64 60 58 72 69 66 64 61 59 74 68 67 64 61 59 74 70 67 64 61 59
69 66 64 61 58 55 70 66 64 62 58 56 71 67 65 62 58 56 72 68 64 62 58 56 73 69 65 62 58 56
66 63 61 58 54 51 67 64 62 59 55 51 67 64 62 59 55 51 70 64 62 58 55 52 71 66 62 59 55 52
75 74 72 71 68 67 77 75 73 72 69 68 78 76 73 72 69 68 78 75 73 72 69 68 79 76 73 72 69 68
73 71 70 67 64 63 75 72 70 68 65 64 75 73 70 68 65 64 76 73 70 68 65 64 76 73 70 68 65 64
69 67 67 62 59 56 71 67 67 63 59 57 71 67 67 62 59 57 72 66 67 62 59 57 73 69 67 62 59 57
65 62 61 58 54 50 67 64 61 58 54 51 68 63 61 58 54 50 69 64 61 57 54 50 69 64 61 58 54 51
73 69 69 67 64 63 75 71 70 68 65 65 76 72 70 68 65 65 77 71 70 68 65 65 77 72 70 68 64 64
70 66 66 64 61 61 73 68 67 64 62 62 74 69 67 65 62 62 74 69 67 64 61 61 75 69 68 65 62 61
66 63 63 60 57 57 69 65 63 61 58 58 70 65 64 61 58 57 71 64 64 61 57 57 72 67 64 61 57 57
64 60 60 57 53 53 66 61 60 58 54 53 68 62 60 57 54 53 69 63 61 57 54 53 70 64 61 57 54 53
79 76 74 73 70 70 79 76 75 73 70 70 80 77 75 73 71 70 80 77 75 73 71 70 81 77 75 73 70 70
75 71 71 69 66 66 77 73 72 70 67 66 78 73 72 70 67 66 78 73 71 69 66 66 78 73 71 69 66 66
70 66 67 62 61 61 73 69 67 65 62 62 74 68 67 65 62 62 74 67 67 65 61 61 74 69 67 65 61 62
65 61 60 58 54 53 66 62 61 58 55 54 67 62 61 58 54 54 69 63 61 58 54 54 70 64 61 58 55 54
80 80 78 78 75 74 82 80 78 78 75 74 82 81 79 78 75 74 83 80 79 78 75 75 84 81 79 79 76 75
76 75 74 72 69 69 78 76 75 73 70 69 79 76 75 73 70 70 80 77 75 74 70 70 80 77 75 74 71 70
73 70 70 68 64 64 75 72 71 68 65 65 76 72 71 69 66 65 76 71 72 69 66 66 77 73 72 69 66 65
69 66 66 63 60 58 71 68 66 64 60 59 72 68 67 64 61 60 73 68 67 64 61 60 73 68 67 64 60 59
65 62 62 59 55 52 67 64 63 60 56 54 68 64 63 60 56 54 69 64 63 60 56 54 70 65 63 60 56 54
72 72 74 73 71 69 73 72 74 73 71 71 75 74 74 74 71 72 77 74 75 74 72 72 79 77 76 75 73 73
69 68 69 69 66 66 70 69 70 69 67 66 73 71 71 70 68 68 74 72 72 71 69 69 76 74 72 71 69 70
64 63 64 63 60 59 66 64 65 64 61 60 69 67 66 65 63 62 72 69 67 66 64 64 74 72 68 67 65 66
58 57 58 57 53 51 62 60 60 58 56 53 66 63 61 60 59 58 68 66 63 61 61 61 70 69 64 63 63 63
53 62 53 51 46 43 58 55 54 53 51 47 62 60 57 56 57 54 65 63 60 59 60 58 67 66 62 60 61 60
For performance table notes, see page D38; 3&% highlighted numbers indicate embedded AHRI certification points.
6-21-13
%
500 236
400 189
300 142
200 94
75 35
400 189
300 142
250 118
200 94
675 319
550 260
450 212
300 142
700 330
600 283
450 212
1200 566
900 425
700 330
450 212
1100 519
1000 472
850 401
1500 708
1300 613
1100 519
850 401
1600 755
1400 661
1200 566
1050 495
1925 908
1700 802
1400 661
1050 495
2300 1085
2000 944
1700 802
1400 661
1100 519
3500 1652
3000 1416
2500 1180
2000 944
1500 708
Min. inlet
Ps
"w.g. Pa
0.15 37
0.20 50
0.06 15
0.04 10
0.01 2
0.03 7
0.02 5
0.01 2
0.01 2
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.24 60
0.17 42
0.12 30
0.07 17
0.04 10
6
1
8
3
10
10
4
12
12
5
14
14
16
500 236
400 189
300 142
200 94
75 35
400 189
300 142
250 118
200 94
675 319
550 260
450 212
300 142
700 330
600 283
450 212
1200 566
900 425
700 330
450 212
1100 519
1000 472
850 401
1500 708
1300 614
1100 519
850 401
1600 755
1400 661
1200 566
1050 495
1925 909
1700 802
1400 661
1050 496
2300 1086
2000 944
1700 802
1400 661
1100 519
3500 1652
3000 1416
2500 1180
2000 944
1500 708
Min. inlet
Ps
" w.g. Pa
0.57 141
0.20 50
0.06 15
0.04 10
0.01 2
0.03 7
0.02 5
0.01 2
0.01 2
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.05 12
0.15 37
0.17 42
0.12 30
0.07 17
0.04 10
Fan Only
2 3 4 5 6
73 63 52 43 40
69 58 47 38 34
64 52 43 33 29
53 43 35 22 52 41 34 22 71 62 53 46 41
66 55 48 41 36
64 53 45 37 32
63 50 43 35 30
54 63 53 52 49
56 55 47 39 36
55 51 39 34 32
53 49 38 31 29
55 51 46 38 33
55 50 45 37 33
51 42 42 33 30
60 58 50 44 38
58 55 48 41 35
53 51 45 36 31
50 47 41 32 28
63 56 49 42 36
60 52 46 41 33
59 51 45 39 32
68 67 61 58 51
66 59 52 46 39
63 56 49 42 36
59 52 45 38 32
71 61 52 47 45
68 57 49 45 41
65 55 47 42 39
61 52 45 39 35
71 63 54 50 47
69 62 53 48 46
66 59 50 45 42
61 53 45 39 35
73 65 58 53 48
71 63 56 50 45
69 59 53 47 41
65 55 50 42 37
60 51 46 38 32
76 71 63 56 53
73 67 62 52 47
69 63 57 49 45
65 57 52 44 37
61 53 48 37 32
7
36
30
24
40
34
30
27
44
34
29
25
30
29
24
33
30
27
21
32
30
30
47
36
32
29
40
37
35
32
44
42
39
32
43
40
39
36
28
50
44
41
33
28
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure shown
Minimum Ps
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps 2.0" wg (500Pa)Ps
2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
71 60 54 46 40 36 * * * * * * 70 61 52 45 42 39 71 63 57 50 45 44 71 64 58 51 46 46
67 57 49 41 35 31 67 57 47 41 36 31 67 59 51 44 40 38 68 61 54 47 43 43 68 63 56 49 44 45
62 51 43 35 29 24 62 53 44 37 33 28 64 56 48 42 38 37 65 59 52 45 41 41 65 60 53 46 43 43
59 46 38 29 24 - 59 48 41 34 32 27 60 52 45 38 36 33 60 55 48 41 39 38 60 56 50 42 40 39
50 41 32 22 - - 52 41 34 26 20 - 53 42 36 31 27 24 53 43 37 33 31 30 55 44 39 35 33 33
69 59 51 44 39 38 70 59 51 44 40 38 71 61 53 45 42 40 71 63 54 47 44 43 71 64 56 48 45 45
67 56 48 41 36 34 66 57 48 41 37 35 67 59 50 43 40 38 67 60 52 44 41 40 67 61 53 46 43 43
63 52 44 36 31 29 64 54 46 38 34 31 64 56 47 39 37 35 65 57 49 41 39 37 65 57 51 43 40 39
62 51 44 36 31 28 62 51 44 36 32 29 63 53 45 38 36 33 63 54 47 40 37 35 62 54 48 40 38 37
61 60 50 42 39 37 62 62 51 44 40 39 65 66 54 46 42 42 66 66 57 48 45 46 67 69 57 50 45 47
57 55 45 36 35 33 59 59 48 40 37 35 63 63 51 44 39 38 64 64 53 46 41 42 64 66 55 48 43 46
55 50 37 31 31 29 57 56 44 37 33 31 59 60 48 40 36 37 60 60 51 43 39 41 61 64 54 46 41 43
53 42 37 30 28 24 52 51 41 33 30 29 56 55 46 38 33 32 55 57 48 42 36 36 57 58 50 45 40 38
57 51 45 38 33 28 61 56 47 42 36 35 62 58 51 45 41 42 65 60 53 47 43 46 66 65 57 50 45 48
55 50 44 37 31 27 59 55 46 40 35 35 62 57 49 44 41 41 64 60 52 46 43 45 64 63 55 48 44 47
50 46 40 32 28 22 57 51 44 39 34 34 58 54 46 40 37 36 63 57 50 45 42 42 60 59 52 45 43 44
59 58 50 43 37 33 64 62 52 46 41 37 66 64 55 49 44 43 67 64 57 51 46 47 68 68 59 53 47 50
56 54 47 39 33 30 61 59 50 43 38 35 63 61 52 46 42 42 65 63 55 49 44 46 66 65 57 51 46 49
52 49 43 35 29 25 57 55 46 40 35 33 60 58 50 44 40 40 62 59 52 46 43 44 63 63 55 49 45 47
48 45 40 31 26 19 54 50 43 37 33 31 56 55 46 40 38 37 59 57 49 43 41 42 59 60 51 46 43 45
64 55 47 42 37 34 65 58 51 44 42 41 67 62 54 47 45 48 69 64 58 50 48 52 70 67 59 52 49 55
62 53 47 41 35 33 65 56 50 43 41 40 66 60 53 45 44 46 68 64 55 48 45 51 69 66 59 51 49 55
60 51 45 38 33 30 62 55 47 41 39 39 64 59 52 45 43 46 66 61 54 47 46 50 66 63 57 49 48 54
67 61 53 48 42 40 69 63 56 49 45 43 70 65 58 51 47 47 71 65 61 53 49 51 72 69 63 55 51 54
65 58 51 45 39 37 67 61 53 46 42 40 68 63 57 49 45 46 69 65 59 52 47 50 70 68 61 53 49 53
62 54 47 41 35 32 63 57 51 43 39 37 65 60 54 47 43 44 67 62 58 50 46 49 68 65 59 52 48 52
58 50 44 36 31 28 60 54 48 40 37 35 62 58 52 44 42 43 64 61 54 47 45 47 64 62 57 49 47 50
69 62 52 47 44 41 69 63 57 49 45 42 69 65 57 51 47 46 71 66 61 54 50 51 71 70 63 56 51 54
66 57 49 42 40 37 68 60 54 45 42 39 68 63 56 49 45 45 68 66 59 52 48 50 70 68 63 55 50 53
64 54 46 40 37 34 62 57 51 43 40 38 65 61 54 48 44 44 66 63 57 50 47 49 67 66 60 52 48 51
61 52 43 37 33 30 61 56 49 41 38 37 62 60 52 46 43 43 64 63 56 48 46 48 66 66 58 50 48 50
69 64 56 51 47 45 71 66 58 52 49 47 72 68 59 53 50 50 73 67 61 54 51 53 73 70 62 55 52 55
68 62 53 48 45 42 69 64 55 49 46 44 70 66 57 51 48 48 71 67 59 52 50 52 71 69 61 54 51 54
65 57 49 43 40 37 67 60 52 45 43 41 67 63 54 48 46 46 68 63 56 50 48 50 69 66 59 52 50 53
59 52 43 37 34 31 61 55 47 41 39 37 63 59 50 44 43 44 63 61 53 46 46 48 64 63 55 48 48 51
73 67 60 54 49 46 75 68 62 55 52 50 76 69 64 56 53 53 77 69 65 58 54 55 77 72 66 59 56 57
70 63 57 50 45 41 72 65 59 51 48 46 73 66 60 53 50 50 73 68 62 55 52 53 74 70 64 56 54 56
67 59 53 45 40 36 68 61 56 48 45 43 69 63 58 50 48 48 70 64 60 52 51 52 71 67 62 54 53 55
63 55 49 41 35 32 65 57 52 44 42 40 67 61 55 47 46 47 68 63 57 50 49 51 69 65 59 52 51 53
59 50 45 36 31 27 62 54 48 41 39 37 65 58 52 44 45 45 64 60 54 47 47 49 66 63 57 49 49 51
74 68 62 54 48 46 75 68 62 54 48 47 77 69 63 55 50 50 79 69 65 57 52 53 81 72 67 58 54 56
71 65 58 51 44 42 73 65 59 51 45 43 75 66 61 52 48 47 77 68 63 55 50 52 79 70 65 57 53 54
68 61 56 45 39 37 70 61 56 47 42 40 73 64 59 50 47 47 75 64 61 52 49 50 77 68 63 55 51 53
62 55 50 39 33 30 66 57 53 43 40 37 71 61 56 48 45 45 73 63 59 50 47 49 75 66 62 53 50 52
59 51 46 35 29 25 63 54 50 40 37 34 68 58 54 45 43 43 71 61 57 48 46 47 72 63 60 51 48 50
For performance table notes, see page D38; 3&% highlighted numbers indicate embedded AHRI certification points.
%
6-24-13
1
2
3
4
5
6
7
6
8
10
12
14
16
16
Fan CFM
cfm
l/s
400
700
1100
1500
1800
2400
3500
189
330
519
708
849
1133
1652
Fan
Watts
100
190
350
570
600
990
1380
Discharge
4 5 6
76
70
76
81
81
83
83
73
69
75
79
78
81
81
68
65
73
75
74
78
77
67
64
72
75
75
78
78
63
61
68
72
71
75
75
60
59
66
71
70
74
74
69
63
70
72
74
74
78
58
59
64
64
67
66
72
Radiated
4 5 6
47
52
58
58
59
59
62
38
45
54
55
56
54
57
34
39
49
49
52
49
55
Primary
CFM
7
cfm
30
34
46
44
48
44
51
400
700
1100
1500
1800
2400
3500
Min. Inlet
Ps
l/s " w.g. Pa
160
330
519
708
849
1133
1652
0.20
0.05
0.05
0.05
0.05
0.05
0.10
50
12
12
12
12
12
25
Radiated
4
5
68
69
71
77
78
78
82
61
66
68
70
71
70
75
54
59
60
63
63
66
68
43
48
51
52
54
55
56
43
48
50
51
52
56
54
47
51
55
58
57
59
60
2-12-15
D37
Unit Size 1
l/s CFM
425 900
212 450
Unit Size 2
378 800
MAXIMUM
189 400
330 700
MAXIMUM
165 350
283 600
NO HEAT OR
ELECTRIC HEAT
118 250
1 OR 2 ROW
H. W. COIL
94 200
AIRFLOW
AIRFLOW
142 300
NO HEAT OR
ELECTRIC HEAT
1 OR 2 ROW
H. W. COIL
236 500
189 400
71 150
142 300
MINIMUM
47 100
MINIMUM
24
50
94 200
47 100
0.0
0
l/s CFM
613 1300
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
0.0
0
Unit Size 3
MAXIMUM
708 1500
472 1000
NO HEAT OR
ELECTRIC HEAT
661 1400
ELECTRIC HEAT
1 OR 2 ROW
H. W. COIL
613 1300
1 OR 2 ROW
H. W. COIL
425
900
378
800
330
700
472 1000
283
600
425
900
378
800
236
500
330
700
189
400
283
600
236
500
MINIMUM
300
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
AIRFLOW
AIRFLOW
MAXIMUM
755 1600
519 1100
142
Unit Size 4
l/s CFM
849 1800
802 1700
566 1200
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
566 1200
519 1100
MINIMUM
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Electrical Data
Fan Curves shown are applicable to
120, 208, 240 and 277 volt, single
phase PSC motors.
D38
3-3-14
l/s CFM
991 2100
l/s CFM
1274 2700
MAXIMUM
944 2000
1227 2600
MAXIMUM
1180 2500
897 1900
1133 2400
849 1800
1085 2300
802 1700
1038 2200
ELECTRIC HEAT
755 1600
991 2100
708 1500
944 2000
1 OR 2 ROW
H. W. COIL
661 1400
613 1300
AIRFLOW
AIRFLOW
Unit Size 6
ELECTRIC HEAT OR
1 OR 2 ROW
H. W. COIL
897 1900
849 1800
802 1700
566 1200
755 1600
519 1100
708 1500
661 1400
472 1000
613 1300
900
378
800
330
700
566 1200
MINIMUM
519 1100
MINIMUM
425
472 1000
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Unit Size 7
l/s CFM
1888 4000
MAXIMUM
1793 3800
1699 3600
1604 3400
1510 3200
ELECTRIC HEAT
AIRFLOW
1416 3000
1 OR 2 ROW
H. W. COIL
1321 2800
1227 2600
1133 2400
1038 2200
944 2000
849 1800
755 1600
MINIMUM
661 1400
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Electrical Data
Fan Curves shown are applicable to
120, 208, 240 and 277 volt, single
phase PSC motors.
3-3-14
D39
l/s CFM
260
Unit Size 3
l/s CFM
566 1200
550
MAXIMUM
236
500
212
450
189
400
165
350
142
300
118
250
94
200
71
150
47
100
472 1000
MINIMUM
24
50
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
425
900
378
800
330
700
283
600
236
500
189
400
142
300
94
200
47
100
MINIMUM
0.0
0
Unit Size 5
l/s CFM
991 2100
519 1100
AIRFLOW
AIRFLOW
MAXIMUM
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Unit Size 7
l/s CFM
1888 4000
MAXIMUM
MAXIMUM
NO HEAT OR
ELECTRIC HEAT
897 1900
NO HEAT OR
ELECTRIC HEAT
1652 3500
1 ROW H. W. COIL
1 ROW H. W. COIL
2 ROW H. W. COIL
802 1700
2 ROW H. W. COIL
3 ROW H. W. COIL
1416 3000
3 ROW H. W. COIL
AIRFLOW
AIRFLOW
708 1500
613 1300
519 1100
425
900
330
700
236
500
142
300
1180 2500
944 2000
708 1500
472 1000
MINIMUM
236
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Electrical Data
ECM FLA
Unit Motor
Size H. P. 120/1/60 208/1/60 240/1/60 277/1/60
1
2.4
1.6
1.5
1.5
*
3
4.8
3.3
3.2
3.1
*
5
9.6
6.2
5.9
5.8
*
7
17.5
11.1
11.4
11.4
*
D40
MINIMUM
500
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
NOTES:
The fan curves for the ECM are unlike
those for traditional PSC motors. The
ECM is pressure independent and
constant volume in operation at factory
or field set point within the shaded area.
Airflow does not vary with changing
static pressure conditions. The motor
compensates for any changes in
external static pressure or induced air
conditions such as filter loading.
3-3-14
l/s CFM
260
550
236
500
212
450
Unit Size 2
l/s CFM
425 900
MAXIMUM
189
400
165
350
142
300
118
250
94
200
71
150
47
100
378
800
330
700
283
600
236
500
189
400
142
300
94
200
47
100
MAX. COOLING
1 ROW HW COIL
2 ROW HW COIL
AIRFLOW
AIRFLOW
MAXIMUM
3 ROW HW COIL
MINIMUM
MINIMUM
50
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
0.1
25
Unit Size 3
l/s CFM
566 1200
0.2
0.3
0.4
50
75
100
DISCHARGE STATIC PRESSURE
755 1600
MAXIMUM
519 1100
MAX. COOLING
HW COIL:
1 ROW
2 ROW
3 ROW
661 1400
900
378
800
330
700
283
600
236
500
189
400
142
300
94
200
47
100
566 1200
AIRFLOW
AIRFLOW
472 1000
425
472 1000
378
800
283
600
189
400
94
200
MINIMUM
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
MINIMUM
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Electrical Data
NOTES:
277V
1.5
2.5
3.1
4.4
2-4-16
Unit Size 4
l/s CFM
MAXIMUM
24
D40A
l/s CFM
991 2100
Unit Size 6
l/s CFM
1133 2400
MAXIMUM
NO HEAT/
ELECTRIC HEAT
897 1900
MAXIMUM
1038 2200
1 ROW HW COIL
802 1700
2 ROW HW COIL
944 2000
3 ROW HW COIL
849 1800
AIRFLOW
AIRFLOW
708 1500
613 1300
519 1100
755 1600
661 1400
425
900
566 1200
330
700
472 1000
236
500
378
800
283
600
MINIMUM
142
MINIMUM
300
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Unit Size 7
l/s CFM
1888 4000
MAXIMUM
NO HEAT/
ELECTRIC HEAT
1 ROW HW COIL
1652 3500
2 ROW HW COIL
AIRFLOW
1416 3000
3 ROW HW COIL
1180 2500
944 2000
708 1500
472 1000
236
MINIMUM
500
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Electrical Data
EPIC ECM Motor FLA
Unit
Size Motor HP 120V
208V
240V
5
9.6
6.2
5.9
*
6
13.6
7.3
6.9
*
7
17.5
11.1
11.4
*
NOTES:
277V
5.8
6.3
11.4
D40B
2-10-16
426"3&306/%/&$,
40"*4450"*4&3*&4
426"3&306/%/&$,
t .*/*.6.7&/5*-"5*0/h*"2h
"11-*$"5*0/4
.PEFMT
40"*
4&0"*
480"*
4450"*
4&450"*
/P)FBU
&MFDUSJD)FBU
)PU8BUFS)FBU
/P)FBU4UFBMUI
&MFDUSJD)FBU
4UFBMUI
48450"* )PU8BUFS)FBU
4UFBMUI
Model 35S-OAI
40"*4&3*&4'&"563&4
Engineered integral dual duct inlet
design is compact and not a bolt on
single duct terminal.
Diamond Flow Sensor located in
both primary and outside air inlets.
Universal access panels for ease
maintenance and service.
Energy efficient PSC fan motor with
thermal overload protection.
Available with electric or hot water
supplementary heat.
Dual air value enclosure for factory
10-24-11
0QUJPOT
EPIC/ E CM Motor.
Induced air filter, 1" (25) thick
disposable type.
Various 'IAQ' linings.
'Q' option induced air attenuator.
Top entry induced air inlet.
Low temperature construction.
FN2 90 Line Voltage enclosure.
FN3 Remote Line Voltage Controls
Enclosure.
%
A major concern facing building owners and engineers today is Indoor Air Quality (IAQ). Nailor has developed an 'IAQ' fan
powered terminal unit option that addresses this issue. Nailor's 35S-OAI and 35SST-OAI "StealthTM " fan powered terminal
units with the OAI feature provide a direct connection for outside air to the terminal, in addition to the standard cool air
connection. The OAI feature adds a second pressure independent outside air valve.
New standards practice for HVAC system design, including ANSI/ASHRAE Standard 62.1 2010, dictate a minimum
amount of ventilation within buildings. Ventilation control has traditionally been done at the central air handling unit;
however, this does not always ensure the minimum ventilation to each zone is maintained.
The OAI feature controls outside air to each occupied zone, independently of the primary cooling requirement and
therefore prevents over-ventilation that might otherwise occur when relying on sufficient outside air from the primary air
system. The OAI feature dual duct inlet design allows the fan powered terminal unit to mix the outside air to the zone with
the primary cooling air. The outside air pressure independent air valve provides a constant volume to the zone regardless
of thermal conditions. This fixes the outside air requirement for the zone without putting excessive demands for outside
air on the primary air handler. In turn, the primary air handler does not have to reset outside air rates for all zones in the
building. The first cost of the outside air handler and its associated ductwork can be offset by the savings provided by
running smaller outside air volumes for those zones with lower occupancy rates.
The OAI feature is perfect for schools. The high occupancy in the classrooms is served without creating excessive loads
at the primary air handler serving zones with lower occupancies. Office buildings with conference rooms, kitchen areas
and workrooms with copiers can also benefit. When these areas are occupied and require large percentages of outside
air, the primary air handler does not have to reset the outside air for all the office spaces in the building.
When integrated with a DDC building management system, the amount of outside air can be tracked and logged to ensure
'IAQ' standards for each zone are met and by using occupancy sensors, the outside air volume for individual zones can
be reset.
IH + 2" (51)
12"
(305)
10"
(254)
MULTI-POINT
FLOW
SENSOR
OUTSIDE
AIR INLET
DIA. =
NOM.
1/8" (3)
W2
2
CL
W3
+
11 1/2"
(292)
PH
B
W2 W3
2
W3
CL
CL
PW
FAN
TW
DW
W1
1"
(25)
TL
5 3/4" PRIMARY
(146) AIR INLET
5 3/4"
(146)
15"
(381)
14" (356)
W3 = W1 + W2
DH
A=(
W1 + W2
2
OPTIONAL
90 FN2 HINGED
FAN CONTROLS
ENCLOSURE
6 3/4" (171)
14" (356)
6"
(152)
RIGHT-HAND
PRIMARY AIR
VALVE CONTROL
ENCLOSURE
HINGED FAN
CONTROLS
ENCLOSURE
LEFT-HAND
PRIMARY AIR
VALVE CONTROL
ENCLOSURE
H1" (25) H
OPTIONAL
INDUCED AIR
INLET FILTER
IH
8"
(203)
IW
%JNFOTJPOBM%BUB
*OEVDFE"JS*OMFU
'JMUFS4J[F
0VUMFU
%JTDIBSHF
4JEF TUE
5PQ PQU
4JEF*OMFU 5PQ*OMFU
*8Y*)
5-Y58 %8Y%)
TUE
PQU
6OJU
4J[F
*OMFU
4J[F
0VUTJEF
*OMFU4J[F
6, 8
(152, 203)
4, 5, 6
(102, 127, 152)
18
(457)
14
(356)
51 12
(1308)
6
(152)
8 x 10
(203 x 254)
10 x 14
(254 x 356)
9 14 x 10 12
(253 x 267)
10 x 12
(254 x 305)
14 x 16
(356 x 406)
6, 8, 10
(152, 203, 254)
4, 5, 6
(102, 127, 152)
18
(457)
18
(457)
51 12
(1308)
3 12
(89)
12 x 14
(305 x 356)
14 x 14
(356 x 356)
9 14 x 10 12
(253 x 267)
14 x 16
(356 x 406)
16 x 16
(406 x 406)
8, 10, 12*
(203, 254, 305)
6, 7, 8
(152, 178, 203)
26
(660)
18
(457)
56 12
(1435)
6
(152)
14 x 14
(356 x 356)
12 x 22
(305 x 559)
12 x 10 12
(305 x 267)
16 x 16
(406 x 406)
16 x 25
(406 x 635)
6, 7, 8
(152, 178, 203)
26
(660)
18
(457)
56 12
(1435)
5
(127)
14 x 14
(356 x 356)
12 x 22
(305 x 559)
13 14 x 11 12
(337 x 292)
16 x 16
(406 x 406)
16 x 25
(406 x 635)
30
(762)
19
(483)
59 12
(1511)
6
(152)
16 x 15
(406 x 381)
14 x 26
(356 x 660)
13 14 x 11 12
(337 x 292)
17 x 18
(432 x 457)
18 x 28
(457 x 711)
1SJNBSZ*OMFU%JNFOTJPOT
%
0WBM*OMFU%JNFOTJPOT
4J[F
8PS8
4J[F
4, 5, 6
7, 8
10
12*
14*
10 (254)
12 (305)
14 (356)
18 (457)
24 (610)
12*
14*
18Y1)
12 1316 x 9 1316 (329 x 249)
16 116 x 9 1316 (408 x 249)
11-9-12
IH + 2" (51)
5"
(127)
W2
2
DIA. =
NOM.
1/8"
(3)
W3
+
11 1/2"
(292)
PERFORATED
DIFFUSION
BAFFLE
W3
2
W3
13 1/4"
(337)
FAN
W2
CL
52"
(1321)
CL
DW
W1
CL
PW
OPTIONAL
TOP
TW
INDUCED
AIR
INLET
5 3/4"
PRIMARY
(146)
AIR
INLET
DH
1" (25)
TL
14" (356)
A=(
7 3/4"
(197)
5 3/4"
(146)
15"
(381)
INDUCED
AIR
W3 = W1 + W2
PH
FAN
W1 + W2
2
)
6 3/4"
(171)
14" (356)
OPTIONAL
90 FN2
HINGED FAN
CONTROLS
ENCLOSURE
6"
(152)
LEFT-HAND
PRIMARY AIR
VALVE CONTROL
ENCLOSURE
RIGHT-HAND
PRIMARY AIR
VALVE CONTROL
ENCLOSURE
IH
HINGED FAN
CONTROLS
ENCLOSURE
IH
IW
IW
17" 18"
(432) (457)
%JNFOTJPOBM%BUB
*OEVDFE"JS*OMFU
6OJU
4J[F
1SJNBSZ
*OMFU4J[F
0VUTJEF
*OMFU4J[F
6, 7, 8, 10
(152, 178, 203, 254)
1SJNBSZ*OMFU%JNFOTJPOT
4JEF TUE
*8Y*)
5PQ PQU
5-Y58
14 x 14
(356 x 356)
Qty. of 2
8 12 x 20
(216 x 508)
Qty. of 2
0VUMFU
%JTDIBSHF
%8Y%)
39 14 x 11 12
(997 x 292)
'JMUFS4J[F
4JEF*OMFU
TUE
5PQ*OMFU
PQU
14 x 16
(356 x 406)
Qty. of 2
16 x 25
(406 x 635)
Qty. of 2
0WBM*OMFU%JNFOTJPOT
4J[F
8PS8
4J[F
12*
14*
16*
18 (457)
24 (610)
28 (711)
12*
14*
16*
18Y1)
12 1316 x 9 1316 (329 x 249)
16 116 x 9 1316 (408 x 249)
16 316 x 9 1316 (487 x 249)
11-9-12
%
)PU8BUFS$PJM4FDUJPO
.PEFM480"*
Available in one, two or three row. Coil
section installed on unit discharge. Right
hand coil connection looking in direction of
airflow standard (shown). Left hand is
optional
(terminals
are
inverted).
Connections must be selected same hand
as controls enclosure location.
4UBOEBSE'FBUVSFT
H
D
12" (305)
1 13/16"
(46)
FAN
HINGED FAN
CONTROLS
ENCLOSURE
3 9/16"
(90)
COIL CONNECTIONS
6OJU4J[F
12"
(305)
H
D
1 13/16"
(46)
FAN
FAN
HINGED FAN
CONTROLS
ENCLOSURE
3 9/16"
(90)
COIL CONNECTIONS
%
6OJU
4J[F
0VUMFU%VDU4J[F
$Y%
&
16 x 12 18 (406 x 308)
21 38 (543)
14 (356)
16 x 14 8 (406 x 378)
21 8 (543)
18 (457)
1 916 (40)
4, 5
24 x 14 78 (610 x 378)
29 38 (746)
18 (457)
1 916 (40)
28 x 17 8 (711 x 435)
33 8 (848)
19 (483)
50 x 14 8 (1270 x 378)
55 8 (1407)
18 (457)
+
16 (24)
15
16 (24)
15
1 916 (40)
7-1-11
&MFDUSJD$PJM4FDUJPO
.PEFM4&0"*
4UBOEBSE'FBUVSFT
1"
(25)
FAN
F
K
HINGED FOR
ELEMENT REMOVAL
1"
(25)
5 1/2"
(140)
14" (356)
ELECTRIC COIL
AND HINGED FAN
CONTROLS ENCLOSURE
6OJU4J[F
N
M
1"
(25)
FAN
0QUJPOT
Toggle disconnect switch (includes
fan).
57 3/4"
(1467)
FAN
HINGED FOR
ELEMENT REMOVAL
1"
(25)
5 3/4"
(140)
ELECTRIC COIL
AND HINGED FAN
CONTROLS ENCLOSURE
11-12-12
6OJU
4J[F
0VUMFU%VDU4J[F
'Y(
10 14 x 10 12 (260 x 267)
15 12 (394)
14 (356)
2 12 (64)
12 12 (318)
10 4 x 10 2 (260 x 267)
15 2 (394)
18 (457)
2 2 (64)
15 14 (387)
13 x 10 12 (330 x 267)
21 (533)
18 (457)
5 (127)
15 14 (387)
14 4 x 11 4 (362 x 298)
22 (559)
18 (457)
4 (102)
15 14 (387)
14 14 x 11 34 (362 x 298)
25 (635)
19 (635)
5 (127)
15 14 (387)
40 4 x 11 4 (1022 x 298)
48 (1219)
18 (457)
4 (102)
15 14 (387)
%
MULTI-POINT
FLOW
SENSOR
INDUCED
VENTILATION
AIR
INLET
DIA. =
NOM.
1/8" (3)
W3
+
11 1/2"
(292)
7 1/4"
(184)
W3
W2
2
B
W2
W3
2
W1
1" (25)
PRIMARY
AIR INLET
DW
FAN
CL
CL
PW
IW
1" (25)
CL
PH
OPTIONAL
INDUCED
AIR FILTER
AIR
5 3/4"
(146)
DH
5 3/4"
(146)
14" (356)
RIGHT-HAND
PRIMARY AIR
VALVE CONTROL
ENCLOSURE
HINGED FAN
CONTROLS
ENCLOSURE
H1" (25) H
W3 = W1 + W2
A=(
W1 + W2
2
6"
(152)
%JNFOTJPOBM%BUB
*OEVDFE"JS*OMFU
'JMUFS4J[F
0VUMFU
%JTDIBSHF
4JEF TUE
5PQ PQU
4JEF*OMFU
*8Y*)
5-Y58 %8Y%)
TUE
6OJU
4J[F
*OMFU
4J[F
0VUTJEF
*OMFU4J[F
6, 8
(152, 203)
4, 5, 6
(102, 127, 152)
18
(457)
14
(356)
15 12
(1308)
6
(152)
9 x 14
(229 x 356)
10 x 14
(254 x 356)
9 14 x 10 12
(253 x 267)
10 x 14
(254 x 356)
6, 8, 10
(152, 203, 254)
4, 5, 6
(102, 127, 152)
18
(457)
18
(457)
15 12
(1308)
3 12
(89)
11 x 18
(279 x 457)
14 x 14
(356 x 356)
9 14 x 10 12
(253 x 267)
12 x 18
(305 x 457)
8, 10, 12*
(203, 254, 305)
6, 7, 8
(152, 178, 203)
26
(660)
18
(457)
56 12
(1435)
6
(152)
15 34 x 14
(400 x 356)
12 x 22
(305 x 559)
12 x 10 12
(305 x 267)
16 x 14
(406 x 356)
6, 7, 8
(152, 178, 203)
26
(660)
18
(457)
56 12
(1435)
5
(127)
14 12 x 18
(368 x 457)
12 x 22
(305 x 559)
13 14 x 11 12
(337 x 292)
14 x 18
(356 x 457)
30
(762)
19
(483)
59 12
(1511)
6
(152)
17 12 x 19
(445 x 483)
14 x 26
(356 x 660)
13 14 x 11 12
(337 x 292)
18 x 19
(457 x 483)
1SJNBSZ*OMFU%JNFOTJPOT
0WBM*OMFU%JNFOTJPOT
4J[F
8PS8
4J[F
18Y1)
4, 5, 6
7, 8
10
12*
14*
10 (254)
12 (305)
14 (356)
18 (457)
24 (610)
12
14
%
10-10-12
INDUCED
IW
AIR
12" (305)
1 13/16"
(46)
FAN
HINGED FAN
CONTROLS
ENCLOSURE
3 9/16"
(90)
D
COIL CONNECTIONS
6OJU
4J[F
0VUMFU%VDU4J[F
$Y%
&
16 x 12 18 (406 x 308)
21 38 (543)
14 (356)
16 x 14 8 (406 x 378)
21 8 (543)
18 (457)
1 916 (40)
4, 5
24 x 14 8 (610 x 378)
29 8 (746)
18 (457)
1 916 (40)
28 x 17 18 (711 x 435)
33 38 (848)
19 (483)
16 (24)
15
16 (24)
15
&MFDUSJD$PJM4FDUJPO
.PEFM4&450"*
4UBOEBSE'FBUVSFT
Unique hinged heater design permits easy
access, removal and replacement of heater
element without disturbing ductwork.
Coil installed on unit discharge.
Insulated coil element wrapper.
Automatic reset high limit cut-outs (one per
element).
Single point electrical connection for entire
terminal unit.
Positive pressure airflow switch.
Flanged outlet duct connection.
Terminal unit with coil is ETL Listed as an
assembly.
Controls mounted as standard on RH side as
shown. Terminals ordered with LH controls
(optional) are inverted and discharge duct
hanging elevation will therefore change.
4UBOEBSE4VQQMZ7PMUBHF )[
120, 208, 240 and 277V single phase.
208, 480 (4 wire wye) and 600V three phase.
0QUJPOT
Toggle disconnect switch (includes fan)
Door interlock disconnect switch.
Mercury contactors.
Power circuit fusing.
Class 'A' 80/20 Ni./Ch. wire.
Dust tight construction.
Manual reset secondary thermal cut out.
11-12-12
INDUCED
IW
AIR
1"
(25)
FAN
HEATER
HINGED FOR
ELEMENT REMOVAL
ELECTRIC
COIL AND
HINGED FAN
CONTROLS
ENCLOSURE
K
1"
(25)
5 3/4"
(146)
14" (356)
H
6OJU
4J[F
0VUMFU%VDU4J[F
'Y(
10 14 x 10 12 (260 x 267)
15 12 (394)
14 (356)
2 12 (64)
12 12 (318)
10 14 x 10 12 (260 x 267)
15 12 (394)
18 (457)
2 12 (64)
15 14 (387)
13 x 10 2 (330 x 267)
21 (533)
18 (457)
5 (127)
15 14 (387)
14 14 x 11 34 (362 x 298)
22 (559)
18 (457)
4 (102)
15 14 (387)
14 4 x 11 4 (362 x 298)
25 (635)
19 (635)
5 (127)
15 14 (387)
%
t $3*5*$"-&/7*30/.&/5
"11-*$"5*0/
t &1*$&$. .0503
.PEFMT
4$71
/P)FBU
4&$71 &MFDUSJD)FBU
48$71 )PU8BUFS)FBU
Model 35SW-CVP
Nailor's 35S-CVP Series is perfect for use as a pressurization unit for critical environment applications. Utilizing Nailor's EPICTM
fan technology, the fan and blower operate as a pressure independent constant volume assembly. This means that the airflow
through the unit will not change due to pressure changes in the system as the filter loads or as the pressure in the exhaust or
supply ducts change. The induction port is closed so that the unit operates as a straight through cooling unit. Both electric and
hot water reheat options are available. HEPA filters may be installed either upstream or downstream of the terminal unit
depending on whether the room pressure is negative or positive. The fan and damper are set to maintain pressure in the room
being served. Temperature control is through reheat in the unit. The CVP feature allows designers to take advantage of Nailor's
EPIC TM fan technology and its associated low operating costs for pressurization.
"Smart" Brushless DC motor technology provides continuous monitoring, automatic compensation and precise control and
maintenance of discharge airflow regardless of discharge static pressure variations incurred by a HEPA filter. Available in
three units sizes, suitable for 200 3000 cfm (94 1416 l/s) zone designs with up to a maximum total external discharge
static pressure of 1.0" w.g. (249 Pa).
Ideally, suited to clean room applications such as hospital isolation wards, operating rooms, pharmaceutical and
biotechnology manufacturing and research facilities.
'&"563&4
Unique 16 ga. (1.6) galvanized steel
channel space frame construction
provides extreme rigidity and 20 ga.
(1.00) casing components.
16 ga. (1.6) galvanized steel
inclined opposed blade primary air
damper operating on a 45 arc.
EPICTM/ECM motor fan technology.
Solid metal 'IAQ' inner liner.
Pressure independent primary
airflow control.
Multi-point averaging flow sensor.
Terminal is field flippable, providing
left or right installation connections.
Refer to IOM for details.
Universal access panels on all four
sides of terminal for ease of
maintenance and service.
%
$POUSPMT
Digital controls. Factory mounting
and wiring of DDC controls supplied
by BMS Controls Contractor.
0QUJPOT
Primary air valve enclosure for field
mounted controls.
Toggle disconnect switch (except
units with electric heat, when
disconnect is an electric heat option
and includes fan).
Fan unit fusing.
Hanger brackets.
FN2 90 Line Voltage enclosure.
1FSGPSNBODF%BUB
Refer to 35SST "Stealth" data.
10-24-11
DIA. =
NOM. 1/8" (3)
PRIMARY
FAN
DW
AIR
DH
1" (25)
MULTI-POINT
FLOW
SENSOR 5 3/4"
(146)
14" (356)
MAX.
14" (356)
DRIVESHAFT
6OJU4J[F
W
2
13 1/4"
(337)
FAN
PRIMARY
PW
DW
AIR
PH
MULTI-POINT
FLOW SENSOR
FAN
DH
1" (25)
7 3/4"
(197)
5 3/4"
(146)
14" (356)
14" (356)
L
6OJU4J[FT
4JEF7JFX
OPTIONAL
PRIMARY
AIR VALVE
CONTROLS
ENCLOSURE
PRIMARY
AIR
H
2
HINGED FAN
CONTROLS
ENCLOSURE
11"
(279)
H1" (25) H
6"
(152)
%JNFOTJPOBM%BUB
6OJU
4J[F
*OMFU
4J[F
18Y1)
0VUMFU%JTDIBSHF
%8Y%)
18 (457)
18 (457)
36 (914)
3 12 (89)
9 14 x 10 12 (253 x 267)
26 (660)
18 (457)
41 (1041)
5 (127)
13 14 x 11 12 (337 x 292)
14 (356) rnd.
16 (407) rnd.
* 18 (457) oval
13 78 (352)
15 78 (403)
3
20 16 x 13 78 (513 x 352)
52 (1321)
18 (457)
41 (1041)
5 (127)
39 14 x 11 12 (997 x 292)
%
6OJU4J[FTBOE
.PEFM48$71
Available in one, two or three row. Coil
section installed on unit discharge. Right
hand coil connection looking in direction of
airflow standard (shown). Left hand is
optional
(terminals
are
inverted).
Connections must be selected same hand
as controls enclosure location.
4UBOEBSE'FBUVSFT
H
D
12" (305)
1 13/16"
(46)
FAN
HINGED FAN
CONTROLS
ENCLOSURE
3 9/16"
(90)
COIL CONNECTIONS
6OJU4J[F
12"
(305)
H
D
1 13/16"
(46)
FAN
FAN
HINGED FAN
CONTROLS
ENCLOSURE
3 9/16"
(90)
COIL CONNECTIONS
%
6OJU
4J[F
0VUMFU%VDU4J[F
$Y%
&
16 x 14 78 (406 x 378)
21 38 (543)
18 (457)
1 916 (40)
24 x 14 78 (610 x 378)
29 38 (746)
18 (457)
1 916 (40)
50 x 14 8 (1270 x 378)
55 8 (1407)
18 (457)
1 916 (40)
10-24-11
&MFDUSJD$PJM4FDUJPO
.PEFM4&$71
4UBOEBSE'FBUVSFT
1"
(25)
FAN
F
K
HINGED FOR
ELEMENT REMOVAL
1"
(25)
5 1/2"
(140)
14" (356)
ELECTRIC COIL
AND HINGED FAN
CONTROLS ENCLOSURE
6OJU4J[F
N
G
1"
(25)
FAN
4UBOEBSE4VQQMZ7PMUBHF )[
120, 208, 240 and 277V, single phase.
0QUJPOT
Toggle disconnect switch (includes fan).
57 3/4"
(1467)
FAN
HINGED FOR
ELEMENT REMOVAL
1"
(25)
ELECTRIC COIL
AND HINGED FAN
CONTROLS ENCLOSURE
14" (356)
SCR Control.
6OJU
4J[F
0VUMFU%VDU4J[F
'Y(
10 14 x 10 12 (260 x 267)
15 12 (394)
18 (457)
2 12 (64)
15 14 (387)
14 4 x 11 4 (362 x 298)
22 (559)
18 (457)
4 (102)
15 14 (387)
40 14 x 11 34 (1022 x 298)
48 (1219)
18 (457)
4 (102)
15 14 (387)
%
l/s CFM
519 1100
MAXIMUM
472 1000
Unit Size 5
l/s CFM
826 1750
MAXIMUM
779 1650
731 1550
425
900
378
800
330
700
283
600
236
500
189
400
142
300
94
200
47
100
684 1450
AIRFLOW
MINIMUM
0.0
0
0.2
0.4
0.6
0.8
50
100
150
200
DISCHARGE STATIC PRESSURE
ECM FLA
Unit Motor
Size H. P. 120/1/60 208/1/60 240/1/60 277/1/60
3
4.8
3.3
3.2
3.1
*
5
9.6
6.2
5.9
5.8
*
7
17.5
11.1
11.4
11.4
*
The ECM is a variable horsepower motor.
Refer to Selectworks Schedule.
FLA = Full load amperage
EON motor series
D52
495 1050
448
950
401
850
354
750
307
650
260
550
MINIMUM
0.2
0.4
0.6
0.8
50
100
150
200
DISCHARGE STATIC PRESSURE
Unit Size 7
l/s CFM
1510 3200
Electrical Data
543 1150
0.0
0
NOTES:
The fan curves for the ECM are
unlike those for traditional PSC
motors. The ECM is pressure
independent and constant
volume in operation at factory
or field set point within the
shaded area. Airflow does not
vary with changing static
pressure conditions. The motor
compensates for any changes
in external static pressure or
induced air conditions such as
filter loading.
590 1250
1416 3000
1321 2800
1227 2600
AIRFLOW
637 1350
1133 2400
1038 2200
944 2000
849 1800
755 1600
661 1400
566 1200
0.0
0
0.2
0.4
0.6
0.8
50
100
150
200
DISCHARGE STATIC PRESSURE
3-3-14
3PX NVMUJDJSDVJU
kW MBH
5.6 19
GPM l/s
5.0 17
4.4 15
5
4
3
2
1.5
.32
.25
.19
.13
.09
.06
kW MBH
9.7 33
GPM l/s
10
7.5
5
4
3
8.8 30
7.9 27
2 .13
1.5 .09
7.0 24
3.8 13
6.2 21
0.5 .03
3.2 11
5.3 18
2.6
4.4 15
2.1
1.5
.63
.47
.32
.25
.19
.06
0.5 .03
3
150
71
200
94
250
118
300
142
350
165
400
189
450
212
3PX NVMUJDJSDVJU
kW MBH
11.7 40
10.5 36
9.4 32
500 $'.
236 MT
GPM
10
7.5
5
4
3
l/s
.63
.47
.32
.25
.19
.13
1.5 .09
8.2 28
.06
7.0 24
5.9 20
0.5 .03
4.7 16
3.5 12
2.3
1.2
1.8
0.9
3
50
9
100
47
150
71
200
94
250
118
8BUFS1SFTTVSF%SPQ
300
142
350
165
kPa "w.g.
249 1.00
447 0.80
17.9 6.0
149 0.60
11.9 4.0
2 ROW
6.0 2.0
3 ROW
2.4 0.8
1.8 0.6
1.2 0.4
450
212
500 $'.
236 MT
100 0.40
1 ROW
3.0 1.0
400
189
"JS1SFTTVSF%SPQ
kPa 'w.g.
29.8 10.0
23.9 8.0
"*313&4463&%301
100
47
)&"%-044 8"5&313&4463&%301
50
9
2.6
50 0.20
25 0.10
20 0.08
15 0.06
3 ROW
10 0.04
2 ROW
0.6 0.2
5 0.02
1 ROW
0.3 0.1
50
9
100
47
150
71
200
94
250
118
300
142
350
165
400
189
450
212
500 $'.
236 MT
2 0.01
1
0.6
3
5
7 9 (1.
1.9
3.2 4.4 5.7 MT
8"5&3'-08
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
8-3-11
200
300 400 500 $'.
94
142 189 236 MT
"*3'-08
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
U ' $
Factor
100
47
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
%
0.9
3.5 12
3PX NVMUJDJSDVJU
kW MBH
6.4 22
GPM
7.5
5
4
3
l/s
.47
.32
.25
.19
.13
kW MBH
11.7 40
10.5 36
5.9 20
1.5 .09
9.4 32
5.3 18
1
.06
GPM
15
10
7.5
5
4
3
l/s
.95
.63
.47
.32
.25
.19
.13
1.5 .09
8.2 28
4.7 16
1
7.0 24
.06
4.1 14
0.5 .03
5.9 20
0.5 .03
3.5 12
4.7 16
3.5 12
2.3
200
94
kW MBH
14.9 51
300
142
400
189
500
236
600
283
700 $'.
330 MT
3PX NVMUJDJSDVJU
8
200
94
300
142
400
189
500
236
8BUFS1SFTTVSF%SPQ
GPM
15
10
7.5
5
4
l/s
.95
.63
.47
.32
.25
12.6 43
.19
11.4 39
.13
13.8 47
1.5 .09
10.3 35
9.1 31
.06
7.9 27
6.7 23
600
283
700 $'.
330 MT
"JS1SFTTVSF%SPQ
Pa in. H2O
249 1.00
447 0.80
149 0.60
17.9 6.0
1 ROW
100 0.40
11.9 4.0
2 ROW
6.0 2.0
3 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
"*313&4463&%301
2.3
)&"%-044 8"5&313&4463&%301
2.9 10
50 0.20
3 ROW
25 0.10
20 0.08
15 0.06
2 ROW
10 0.04
1 ROW
0.6 0.2
5 0.02
5.6 19
0.3 0.1
4.4 15
200
94
300
142
400
189
500
236
600
283
700 $'.
330 MT
2 0.01
1
.06
2
3 4
6 8 10 (1.
.13 .19 .25 .38 .50 .63 MT
8"5&3'-08
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
%
200
300
94
142
"*3'-08
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
U ' $
Factor
100
47
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
8-9-11
kW MBH
9.4 32
8.5 29
7.6 26
3PX NVMUJDJSDVJU
GPM
7.5
5
4
3
l/s
.47
.32
.25
.19
.13
kW MBH
17.6 60
GPM
15
10
7.5
l/s
.95
.63
.47
5
4
.32
.25
.19
.13
16.1 55
14.7 50
13.2 45
1.5 .09
11.7 40
6.7 23
1.5 .09
.06
10.3 35
5.9 20
.06
8.8 30
7.3 25
5.0 17
0.5 .03
0.5 .03
5.9 20
4.1 14
4.4 15
2.9 10
700
330
900
425
1100
519
3PX NVMUJDJSDVJU
kW MBH
23.4 80
22.0 75
20.5 70
19.0 65
17.6 60
16.1 55
l/s
.95
.63
.47
5
4
.32
.25
.19
.13
1.5 .09
13.2 45
1
.06
10.3 35
8.8 30
7.3 25
500
236
700
330
900
425
8BUFS1SFTTVSF%SPQ
GPM
15
10
7.5
14.7 50
11.7 40
300
142
1300 $'.
613 MT
kPa 'w.g.
29.8 10.0
23.9 8.0
1 ROW
17.9 6.0
11.9 4.0
3 ROW
1.8 0.6
1.2 0.4
0.6 0.2
"JS1SFTTVSF%SPQ
100 0.40
6.0 2.0
2.4 0.8
1300 $'.
613 MT
149 0.60
2 ROW
3.0 1.0
1100
519
kPa "w.g.
249 1.00
447 0.80
"*313&4463&%301
500
236
)&"%-044 8"5&313&4463&%301
300
142
3 ROW
50 0.20
2 ROW
25 0.10
20 0.08
1 ROW
15 0.06
10 0.04
5 0.02
0.5 .03
5.9 20
0.3 0.1
4.4 15
300
142
500
236
700
330
900
425
1100
519
1300 $'.
613 MT
2 0.01
1
.06
2
3 4
6 8 10 (1.
.13 .19 .25 .38 .50 .63 MT
8"5&3'-08
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
8-3-11
200
94
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
U ' $
Factor
100
47
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
%
3.2 11
3PX NVMUJDJSDVJU
kW MBH
13.8 47
kW MBH
24.0 82
GPM l/s
12.6 43
11.4 39
GPM l/s
7.5 .47
22.6 77
10 .63
7.5 .47
.32
21.1 72
.32
.25
.25
.19
.19
.13
19.6 67
18.2 62
10.3 35
.13
16.7 57
1.5 .09
15.2 52
9.1 31
13.8 47
1
12.3 42
.06
.06
9.4 32
7.9 27
5.6 19
0.5 .03
0.5 .03
6.4 22
5.0 17
4.4 15
600
283
800
378
1000
472
1200
566
1400
661
1600
755
1800 $'.
849 MT
3PX NVMUJDJSDVJU
kW MBH
32.8 112
600
283
800
378
1000
472
1200
566
1400
661
8BUFS1SFTTVSF%SPQ
GPM l/s
15 .95
10 .63
29.9 102
7.5 .47
5
27.0 92
24.0 82
.32
.25
.19
21.1 72
2
.13
18.2 62
1.5 .09
15.2 52
1
12.3 42
.06
1600
755
1800 $'.
849 MT
"JS1SFTTVSF%SPQ
Pa in. H2O
249 1.00
447 0.80
149 0.60
17.9 6.0
)&"%-044 8"5&313&4463&%301
10.8 37
6.7 23
1 ROW
100 0.40
11.9 4.0
2 ROW
6.0 2.0
3 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
"*313&4463&%301
7.9 27
1.5 .09
0.6 0.2
3 ROW
50 0.20
2 ROW
25 0.10
20 0.08
15 0.06
10 0.04
1 ROW
5 0.02
9.4 32
6.4 22
600
283
0.5 .03
800
378
1000
472
1200
566
1400
661
1600
755
1800 $'.
849 MT
0.3 0.1
2 0.01
1
.06
2
3 4
6 8 10 (1.
.13 .19 .25 .38 .50 .63 MT
8"5&3'-08
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
%
200
94
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
U ' $
Factor
100
47
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
8-5-11
3PX NVMUJDJSDVJU
kW MBH
18.2 62
kW MBH
32.2 110
GPM l/s
15 .95
10 .63
7.5 .47
16.4 56
5
4
.32
.25
.19
GPM l/s
15 .95
10 .63
29.3 100
7.5 .47
26.4 90
14.7 50
.32
.25
.19
.13
23.4 80
12.9 44
.13
20.5 70
1.5 .09
11.1 38
17.6 60
1
9.4 32
1.5 .09
.06
14.7 50
7.6 26
11.7 40
.06
8.8 30
1400
661
1600
755
1800
849
2000
944
3PX NVMUJDJSDVJU
kW MBH
41.0 140
2200 $'.
1038 MT
1000
472
1200
566
1400
661
1600
755
1800
849
8BUFS1SFTTVSF%SPQ
GPM l/s
15 .95
10 .63
38.1 130
7.5 .47
35.2 120
kPa "w.g.
249 1.00
447 0.80
17.9 6.0
149 0.60
11.9 4.0
32.2 110
.32
.25
29.3 100
3
.19
26.4 90
23.4 80
.13
20.5 70
1.5 .09
17.6 60
14.7 50
.06
2 ROW
6.0 2.0
3 ROW
2.4 0.8
1.8 0.6
1.2 0.4
0.6 0.2
2200 $'.
1038 MT
100 0.40
1 ROW
3.0 1.0
2000
944
"JS1SFTTVSF%SPQ
kPa 'w.g.
29.8 10.0
23.9 8.0
"*313&4463&%301
1200
566
)&"%-044 8"5&313&4463&%301
1000
472
3 ROW
50 0.20
2 ROW
25 0.10
20 0.08
15 0.06
1 ROW
10 0.04
5 0.02
11.7 40
0.3 0.1
8.8 30
1000
472
1200
566
1400
661
1600
755
1800
849
2000
944
2200 $'.
1038 MT
2 0.01
1
.06
2
3 4
6 8 10 (1.
.13 .19 .25 .38 .50 .63 MT
8"5&3'-08
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
8-5-11
200
94
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
U ' $
Factor
100
47
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
%
5.9 20
3PX NVMUJDJSDVJU
kW MBH
26.4 90
GPM l/s
15 .95
10 .63
GPM l/s
15 .95
42.5 145
10 .63
39.6 135
7.5 .47
7.5 .47
23.4 80
20.5 70
.32
.25
.19
.13
36.6 125
33.7 115
27.8 95
14.7 50
22.0 75
19.0 65
.06
2200
1038
2500
1180
2800
1321
3100
1463
10.3 35
1300
613
3400 $'.
1604 MT
3PX NVMUJDJSDVJU
GPM l/s
15 .95
55.7 190
10 .63
52.8 180
49.8 170
7.5 .47
46.9 160
44.0 150
.32
.25
.19
41.0 140
38.1 130
35.2 120
32.2 110
29.3 100
26.4 90
.13
23.4 80
20.5 70
1.5 .09
.19
.13
1600
755
1900
897
2200
1038
2500
1180
Pa in. H2O
249 1.00
447 0.80
17.9 6.0
149 0.60
2 ROW
6.0 2.0
3 ROW
2.4 0.8
1.8 0.6
1.2 0.4
3100
1463
3400 $'.
1604 MT
100 0.40
1 ROW
3.0 1.0
2800
1321
"JS1SFTTVSF%SPQ
11.9 4.0
.06
8BUFS1SFTTVSF%SPQ
kW MBH
58.6 200
1.5 .09
"*313&4463&%301
1900
897
)&"%-044 8"5&313&4463&%301
8.8 30
1600
755
.25
16.1 55
13.2 45
1300
613
.32
24.9 85
1.5 .09
11.7 40
30.8 105
17.6 60
kW MBH
45.4 155
0.6 0.2
50 0.20
3 ROW
25 0.10
2 ROW
20 0.08
15 0.06
10 0.04
1 ROW
5 0.02
17.6 60
1
14.7 50
11.7 40
1300
613
.06
0.3 0.1
1600
755
1900
897
2200
1038
2500
1180
2800
1321
3100
1463
3400 $'.
1604 MT
2 0.01
1
.06
2
3 4
6 8 10 (1.
.13 .19 .25 .38 .50 .63 MT
8"5&3'-08
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
%
200
94
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
U ' $
Factor
100
47
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
8-5-11
7-1-11
"JSGMPX
6OJU
4J[F
DGN
MT
1
2
3
4
5
6
7
300
450
900
1300
1700
2000
2700
142
212
425
613
802
944
1274
59
60
60
67
70
72
70
53
55
59
63
64
65
66
48
52
56
58
59
62
61
51
53
60
61
63
64
64
50
53
60
62
66
67
66
6OJU
4J[F
DGN
MT
1
2
3
4
5
6
7
300
450
900
1300
1700
2000
2700
142
212
425
613
802
944
1274
56
51
55
63
67
68
65
49
47
54
58
59
61
58
43
40
49
53
54
58
53
37
34
46
51
52
55
50
34
31
42
47
50
52
47
6OJU
4J[F
DGN
MT
1
2
3
4
5
6
7
300
450
900
1300
1700
2000
2700
142
212
425
613
802
944
1274
64
59
64
70
71
74
70
61
58
65
69
71
74
69
59
54
63
68
70
73
68
57
52
60
65
67
70
65
54
49
57
64
66
70
65
%
1.
Furnish and install constant volume series fan powered
terminal units of the sizes and capacities as indicated on the
drawings. Units shall be pressure independent with (pneumatic,
analog electronic, digital electronic) controls. Units shall be
manufactured by /BJMPS*OEVTUSJFT*ODModel 4.
2.
The entire terminal unit shall be designed and built as a single
unit. The units shall be provided with a primary variable air volume
damper that controls the air quantity in response to a (pneumatic,
electronic) thermostat. The space limitations shall be reviewed
carefully to ensure that all units will fit into the space allowed.
3.
Unit casings shall be space frame construction utilizing 16 ga.
(1.61) galvanized steel corner structural members and 20 ga. (1.00)
galvanized steel panels. Unit shall be fully lined with fiberglass
insulation which shall be at least 3/4" (19) thick dual density
insulation complying with NFPA 90 for fire and smoke resistivity and
UL 181 for erosion. Any cut edges of insulation shall be coated with
NFPA 90 approved sealant.
4.
Unit casing shall have four access panels, one on each side of
the unit and one on the bottom and top for easy access to motor and
blower assembly and for maintenance and replacement of parts
without disturbing duct connections. The unit shall be rated to
operate in left hand or right hand mode by turning the unit over.
Access panels shall be attached to casing with (screws, quick acting
latches, hinges). Casing leakage shall not exceed 2% of terminal
rated airflow at 0.5" w.g. (125 Pa) interior casing pressure. All high
side casing joints shall be sealed with approved sealant and high
side casing leakage shall not exceed 2% of terminal rated airflow at
3" w.g. (750 Pa).
5.
Units shall have round inlets for the primary air connections
and shall have a 6" (152) deep inlet duct collar for field connection.
The outlets shall be rectangular and suitable for flanged duct
connections. Casing shall have mounting area for hanging by sheet
metal straps from a concrete slab.
6.
The damper shall be of rectangular, multiple inclined opposed
blade construction and designed to operate on a 45 arc. Blades
shall be minimum 16 ga. (1.61) galvanized steel, single thickness
construction with heavy duty gasket glued to the blades. The blades
shall be screwed through the damper shaft to ensure that no
slippage occurs. Blade shafts shall pivot on corrosion free bearings.
Damper leakage shall not exceed 2% of the terminal rated cfm at 3"
w.g. (750 Pa) inlet static pressure.
7.
Entire terminal unit shall be factory assembled with (pneumatic,
electronic) controls. All components including all controls except the
room thermostat and (pneumatic piping, field wiring) shall be factory
installed and mounted with the unit.
8.
Provide a (pneumatic, analog electronic, digital electronic) flow
control device that will limit the maximum and minimum airflow to that
scheduled on the drawings. Airflow limits shall be factory set.
Thermostat signal shall reset the flow control device to adjust
primary airflow to match load requirements. Control of the terminal
unit shall be pressure independent.
9.
The terminal unit shall be capable of operation as described
herein with inlet static pressure of 0.05" w.g. (12 Pa) at full cooling
with no mixing of induced and primary air. (The sequence of
operation should be described here, if not part of the temperature
controls specifications). Mixing of the primary and secondary
airstreams shall be such that no more than 2.5 F (1.4C) variation
shall exist in the discharge airstream for each 20 F (11.1C) of
difference between the primary and secondary airstreams.
10. Blower casings shall be constructed of heavy gauge coated
steel. Blower wheel shall be forward curved centrifugal type,
0QUJPOT
45&"-5)5.
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQIT
1.
Furnish and install series flow (constant volume) fan powered
terminal units of the sizes and capacities as indicated on the
drawings. Units shall be pressure independent with (pneumatic,
analog electronic, digital electronic) controls. Units shall be
manufactured by /BJMPS*OEVTUSJFT*ODModel 4454UFBMUI5..
4.
Unit maximum radiated sound power levels at 1.0" w.g. (249
Pa) inlet pressure and 0.25" w.g. (63 Pa) discharge static pressure
shall not exceed the values in Tables 4 and 5 at the specified airflow.
No credit or reduction shall in any way be considered for room,
plenum, ceiling and/or similar item effects.
"JSGMPX
6OJU
4J[F
DGN
MT
1
2
3
4
5
6
7
300
450
900
1300
1700
2000
2500
142
212
425
613
802
944
1180
59
60
61
63
66
66
64
50
48
52
57
57
60
59
43
40
46
49
51
53
50
40
36
42
45
48
50
47
38
37
42
46
48
50
47
6OJU
4J[F
DGN
MT
1
2
3
4
5
6
7
300
450
900
1300
1700
2000
2500
142
212
425
613
802
944
1274
55
51
55
59
62
63
63
48
39
48
52
53
56
57
41
34
41
46
48
50
49
36
32
35
39
46
45
45
34
29
30
36
42
40
41
6OJU
4J[F
DGN
MT
1
2
3
4
5
6
7
300
450
900
1300
1700
2000
2500
142
212
425
613
802
944
1274
64
59
64
70
71
74
66
61
58
65
69
71
74
66
59
54
63
68
70
73
65
57
52
60
65
67
70
63
%
54
49
57
64
66
70
62
1.
Furnish and install series flow (constant volume) fan powered
terminal units with integral electric heat of the sizes and capacities as
indicated on the drawings. Units shall be pressure independent with
(pneumatic, analog electronic, digital electronic) controls. Units shall
be manufactured by /BJMPS*OEVTUSJFT*ODModel 4& or 4&45
4UFBMUI5. (select one).
12. An electric heater shall be factory mounted and pre-wired as an
integral package with the fan powered terminal unit. Heaters shall be
sized as shown on the drawings. The entire assembly including the
electric heater shall be ETL listed (cETL in Canada) for zero
clearance and so labeled and shall meet all requirements of the
latest National Electrical Code (Canadian Electrical Code, CSA
Standard C22.1). The unit with the heater mounted shall be listed
and rated to be turned over for either left or right hand configuration.
The unit shall have a single point electrical (and pneumatic)
connection. Heater casing and panel shall be a minimum of 20
gauge galvanized steel. Each heater shall be complete with primary
disc type automatic high limit, contactors as required, ground
terminal, fan relay for interlocking the heater and fan and high grade
nickel chrome alloy resistance wire. Element wires shall be
suspended in insulators designed to expose the entire face area of
the wire thereby eliminating hot spots. Each heater shall be supplied
with factory supplied and pre-wired branch circuit fusing as required
by NEC and UL. Circuiting and fusing shall also be in accordance
with the circuiting requirements as shown on the plans. Additional
accessories shall include (control transformer, circuit fusing,
disconnect switch, electric step controller, pneumatic electric
switches) for staging the heater.
(Additional performance requirements that you might want to include
can be found in the electric heater section). The electric heater shall
be located on the discharge side of the fan so as not to add heat to
the motor and shorten its expected lifetime.
Heater voltage and stages to be as follows:
0 to 5.0 kW ..................................... 277V/1 phase, 1 Step
5.1 kW and up ................................ 480V/3 phase, 1 Step
)PU8BUFS)FBUJOH$PJMT
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQIT
1.
Furnish and install series flow (constant volume) fan powered
terminal units with integral hot water coils of the sizes and capacities
as indicated on the drawings. Units shall be pressure independent
with (pneumatic, analog electronic, digital electronic) controls. Units
shall be manufactured by /BJMPS *OEVTUSJFT *OD Model 48 or
48454UFBMUI5. (select one).
12. A hot water coil shall be factory mounted as an integral
package with the fan powered terminal unit. Hot water coils shall be
sized as shown on the drawings. The entire assembly including the
hot water coil shall be ETL listed (cETL in Canada) for zero clearance
and so labeled and shall meet all requirements of the latest National
Electrical Code. The unit shall have a single point electrical (and
pneumatic) connection. Water coil casing and panels shall be a
minimum of 20 ga. (1.00) galvanized steel. Access panels shall be
supplied on the top and bottom of the unit for easy access to the coil
for inspection and cleaning. All copper, including the headers and
return bends, shall be encased to eliminate heat loss during heating
sequence and heat gain during cooling sequence. Coils shall be 1, 2
or 3 row as required and heating capacities shall be as shown on the
plans. Coils shall have aluminum plate fins spaced 10 per inch and
bonded to 1/2" (13) O.D. copper tubes. Copper connections shall be
sweat. All coils shall be tested at a minimum of 300 psi (2.1 MPa)
under water to produce a guaranteed working pressure of 250 psi
(1.7 MPa). Controls and valves for the hot water coils shall be field
mounted. Heating coils shall be located on the discharge side of the
fan so as not to add heat to the motor and shorten its expected lifetime.
7-1-11
1"35o(&/&3" 3&-"5&%%0$6.&/54
A. The requirements of the General Conditions, Supplementary
Conditions and the following specification sections apply to all Work
herein:
1.
2.
3.
4.
5.
Section
Section
Section
Section
Section
15
15
15
15
15
46.."3:
A. Furnish and install all air terminal units herein specified and as
indicated on the Drawings.
3&'&3&/$&45"/%"3%4
A. All air terminal units shall be designed, manufactured and tested
in accordance with the latest applicable industry standards
including the following:
1. ANSI/ASHRAE Standard 130-2008.
2. AHRI Standard 880-2011.
3. Underwriters Laboratories UL Standard 1995.
4. Underwriters Laboratories UL Standard 1996.
26"-*5:"4463"/$&
A. All equipment and material to be furnished and installed on this
project shall be UL or ETL listed, in accordance with the
requirements of the Authority having jurisdiction and suitable for its
intended use on this Project. Space limitations shall be reviewed to
ensure that the equipment will fit into the space allowed.
B. All equipment and material to be furnished and installed on this
project shall be run tested at the factory and results of that testing
shall be tabulated and provided to the engineer when the equipment
ships to the job site. See paragraph 2.03 G for specific requirements.
C. All equipment and material to be furnished and installed on this
project shall have been pre-tested in a mock up facility suitable to
the engineer. The test shall be as described in 2.03 D. The test
results shall be supplied with the equipment submittal.
46#.*55"-4
A. The following submittal data shall be furnished according to the
Conditions of the Construction Contract, Division 1 Specifications
and Section 15 - - - General and shall include but not be limited to:
1. Series Fan Powered Variable Air Volume Terminal Units,
complete with capacity data, test data, construction details,
physical dimensions, electrical characteristics, etc.
7-1-11
0DUBWF#BOE
2
3
4
5
6
7
/$
67
64
67
66
67
67
/$
71
69
72
71
72
72
General
Scope of Work
Design Conditions
Electric Motors and Controllers
Access Doors and Color Coded Identification
in General Construction
6. Section 15 - - - Ductwork and Sheet Metal
7. Section 15 - - - Testing, Balancing and Adjusting
"$0645*$4
Section A of this acoustical specification describes sound power
levels as tested to AHRI 880 and ASHRAE 130. These are not the
selection criteria for this specification. The selection criteria will be
in section B where sound pressure readings are taken in an actual
mock up that will exhibit worst case performance for the purpose of
guaranteeing equipment performance when the building is
commissioned and turned over to the occupant. Section A is
important in that it provides a guideline for the minimum
performance that the terminal units will have to meet in order to
anticipate performance that will be acceptable under section B.
A. Sound Power Acoustical Performance:
1. Discharge Noise: Maximum permissible sound power levels
in octave bands of discharge sound through discharge ducts
from terminal units operated at an inlet pressure of XH
1B
and the maximum amount of air volume shown on the
Project Mechanical Drawings leaving the terminal unit and
entering the reverberant chamber shall be as follows:
/$
64
57
53
50
50
53
/$
68
62
58
55
55
58
%
8"33"/5:
A. Manufacturer shall warrant equipment for one year from start up
or 18 months from shipment.
1"35130%6$54
6/"65)03*;&%."5&3*"-4
A. Materials and products required for the work of this section shall
not contain asbestos, polychlorinated biphenyls (PCB) or other
hazardous materials identified by the Engineer or Owner.
"$$&15"#-&."/6'"$563&34
A. These Specifications set forth the minimum requirements for
series fan powered VAV terminal units. If they comply with these
Specifications, series fan powered VAV terminal units manufactured
by one of the following manufacturers will be acceptable:
1. Nailor Industries.
7"3*"#-& 13*."3: "*3 70-6.& 4&3*&4 '"/
108&3&%5&3.*/"-6/*54
A. Furnish and install series fan powered VAV terminal units as
indicated on the Drawings. The units shall be designed and built as
a single unit and provided with a primary variable air volume damper
that controls the primary air quantity in response to a temperature
control signal. The damper construction shall be rectangular with
multiple opposed blades designed to operate on a 45 arc. Blades
shall be 16 ga. (1.61) galvanized steel, single thickness construction
with heavy-duty gasket glued to the blades. Units shall be suitable for
pressure independent control with %JHJUBM<%%$>controls. The units
shall contain a fan and motor assembly and [electric or hot water]
heating coils where scheduled and/or indicated on the Drawings. The
fan shall provide a constant volume of discharge air at all air blending
ratios from minimum to maximum scheduled primary air quantities
and zero to 100% return airflow rates and shall be controlled in
sequence as outlined hereinafter. The space limitations shall be
reviewed carefully to ensure all terminal units will fit into the space
provided including National Electric Code clearances required in
front of all panels containing electrical devices. Units shall be of
space frame construction with 16 ga. (1.61) corner posts for
structural support and attachment points. Removable access doors
or panels of minimum 20 ga. (1.00) galvanized steel on the top,
bottom and both sides of the terminal unit shall provide access to
service the fan, electric motor and all internal components. Panels
shall be attached with [screws or quick connect latches or hinges].
Units shall be fully rated, even with electric or hot water heater coils,
to operate in left hand or right hand mode by turning the unit over.
Unit shall be fully lined with at least 3/4" (19) thick, dual density
fiberglass insulation completely encapsulated between solid outer
and inner solid liners, which comply with NFPA 90 for fire and smoke
resistivity and UL 181 for erosion. Casing leakage shall not exceed
2% of terminal rated airflow at 0.5" w.g. (125). interior casing
pressure. All high side casing joints shall be sealed with approved
sealant and high side casing leakage shall not exceed 2% of terminal
rated airflow at 3" w.g. (750). Provide a filter rack with a 1" (25) thick
throwaway filter to be used during construction. Terminal unit
manufacturer shall provide flow curves for the primary air sensor
clearly labeled and permanently attached on the bottom or side of
each fan terminal.
The unit shall include all equipment and controls as required to
provide a complete and operating system with at least the following
equipment and controls:
%
7-1-11
7-1-11
D63
with the floor and box number that identifies it along with the airflow
(cfm) settings. Every unit shall have a unique number combination
that matches numbers on the contractor's coordination drawings as
to its location and capacity and is coordinated with the DDC controller
and the Division 17 Building Control System submittal drawings.
G. The terminal unit manufacturer will verify the operation of each
fan powered terminal before shipment. Testing shall include at least
the following:
1. Apply electric power to the unit.
2. Start the fan and verify fan rotates properly.
3. The terminal unit manufacturer shall factory or field adjust the
Nailor EPICTM motor and associated controller/inverter to the
discharge airflow (cfm) indicated in the Schedules. (Refer to
paragraph 2.03 A.6.a. hereinbefore.)
4. Energize the electric heat through the electric heating coil relay.
Verify the signal with a volt meter and ammeter to ensure proper
heater operation.
5. De-energize the electric heating coil and verify the signal with a
volt-meter to ensure the heater is de-energized.
6. If DDC controls are mounted, disconnect the primary air damper
actuator from the DDC terminal unit controller. Provide separate
power source to the actuator to verify operation and rotation of
damper. Drive the damper closed and verify by feel or observation
that damper is driven fully closed. Return primary air damper to the
fully open position prior to shipment.
7. Provide a written inspection report for each terminal unit signed
and dated by the factory test technician verifying all terminal unit
wiring and testing has been performed per the manufacturer's testing
and quality assurance requirements.
)FBU0QUJPOT
&MFDUSJD)FBU
*OTFSUUIFGPMMPXJOHQBSBHSBQIT
" 'BO1PXFSFE5FSNJOBM6OJU&MFDUSJD)FBUJOH$PJMT
a. Electric heating coils shall consist of open coils of high
grade nickel and chromium resistance wire or nichrome
elements and insulated with ceramic insulators in galvanized
steel brackets, supported in heavy gauge galvanized steel
frames. Each unit employing an electric heating coil shall be
constructed and installed in accordance with the requirements
of the local authorities and shall be UL or ETL listed
specifically with the heater as a component of the terminal
unit device.
b. Coils shall have the capacities indicated in Contract
Documents. Coils rated up through 5 kW shall be single
phase, 277 volt, 60 hertz and coils larger than 5 kW shall be
three phase, four wire, 480Y/277 volt, 60 hertz. Electric
heating coils up to and including 4 kW shall be single stage.
Electric coils above 4 kW shall be two stage.
c. Terminal bolts, nuts and washers shall be of corrosion
resistant materials. Coils shall be constructed so the
installation may be accomplished in accordance with the
provisions of the National Electrical Code, for zero clearance.
Coils shall be given a 2000 volt dielectric test at the factory.
d. Automatic reset thermal cutouts and an airflow switch shall
be furnished for heater protection. An airflow switch shall
prove fan airflow before the electric heater can be energized.
%
)PU8BUFS)FBU
*OTFSUUIFGPMMPXJOHQBSBHSBQIT
" 'BO1PXFSFE5FSNJOBM6OJU)PU8BUFS)FBUJOH$PJMT
a. Terminal unit hot water heating coils shall be installed
completely within the terminal unit casing and enclosing the
coil headers, return bends, "U" bends and the factory piping
assemblies. Provide an access door or panel on the bottom
of the terminal unit for servicing and cleaning the unit and to
completely expose coil headers and any valves supplied by
the terminal unit manufacturer.
b. The factory hydrostatic or air pressure test of the coil and
entire piping assembly shall be maintained for a minimum of
one minute after which each piping joint connection, etc. shall
be examined to verify there is no evidence of weeping or
leakage. If liquid was used for the pressure testing, it shall be
completely drained and blown out of all coils and the internal
piping system prior to shipment. If air pressure is used, the
entire coil and piping assembly shall be completely
submerged under water. Hot water heating coils shall be
constructed with copper tubes and either aluminum plate fins
or spiral fins. Coils shall have a maximum of 10 fins per inch.
Fin thickness shall be 0.0045". Supply and return connections
shall be on the same hard drawn
7-1-11
7-1-11
14$.PUPS
*OMJFVPG&1*$5.&$.
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQI
"
Fan motor assembly shall be forward curved centrifugal fan with a
direct drive motor. Motors shall be specifically designed for use with
a single phase, (120, 208 or 277) volt 60 Hertz electric input, Motor
shall have built-in overload protection, bearings capable of low rpm
oiling and permanently oiled bearings. Motor shall be direct couple to
the blower. Provide isolation between fan motor assembly and unit
casing in at least 4 locations to eliminate any vibration from the fan
to the terminal unit casing. Provide anti-back rotation system or
provide a motor that is designed to overcome reverse rotation and
not affect life expectancy. An electronic motor speed controller sized
and designed for the specific blower motor combination shall be
provided to allow infinitely fan speed from the minimum voltage stop
to the line voltage signal to the motor. A minimum voltage stop shall
be employed to ensure that the fan cannot run in a stall mode.
%
end of the coil and shall be ASTM B88-72, H23, I-59 Type K
hard drawn seamless copper water pipe. Fins shall be
bonded to the tubes by means of mechanical expansion of the
tubes or by spiral winding under tension.
c. Coils shall have galvanized steel casings on all sides no
lighter than 20 ga. (1.00).
d. Tubes shall be 1/2" (13) O.D., spaced on 1 1/4" (32)
centers and shall have a minimum wall thickness of 0.016"
(.40). Hot water shall be equally distributed through all tubes
by the use of orifices or header design. Water velocity in the
tubes shall not exceed 5 fps (1.5 m/s). The water pressure
drop through the coil shall not exceed 10 feet (30 kPa).
Heating coil face velocities shall not exceed the maximum
face velocity indicated in the schedules on the Contract
Documents.
e. Coils shall have manual air vent connections except on
those return connections where the coil header piping is
designed to be self-venting.
f. Coils and piping assemblies shall be tested at 300 psig
(2,068 kPa) static pressure for a working pressure of 250 psig
(1,724 kPa) or as indicated on the Contract Document.
g. Coil ratings, calculations and selection data shall be in
accordance with the applicable AHRI Standards and shall be
submitted with the Shop Drawings.
h. The complete heating coil piping assembly, including all of
the listed appurtenances, shall be provided and factory
installed by the terminal unit manufacturer. The coil and piping
assembly shall be factory pressure tested.
i. All piping, valves and fittings shall be suitable for the
working pressure shown on the Contract Documents. The
internal piping shall be sized to limit the velocity to no more
than 8 fps (2.4 m/s) at maximum design flow.
.PEFM4VCTUJUVUJPO0QUJPOT
%
7-12-11
.PEFMT
4
/P)FBU
4&
&MFDUSJD)FBU
48
)PU8BUFS)FBU
Model 37SE
The 44FSJFT Low Profile terminals are designed for shallow ceiling plenum applications and therefore limited to 11" (279)
in height. Shallow plenums are common where zoning requirements limit building height. When building height is
constrained, building designers will maximize the number of floors by reducing the distance between floors, requiring low
profile products like the 37S Series.
'&"563&4
7-12-11
$POUSPMT
0QUJPOT
EPIC /ECM Motor.
Primary air valve enclosure for field
mounted controls.
Induced air filter, 1" (25) thick,
disposable type.
Toggle disconnect switch (except
units with electric heat, when
disconnect is an electric heat option
and includes fan).
Various 'IAQ' linings are available.
Fan airflow or P.E. switch for night
shutdown (pneumatic controls).
Fan airflow switch for night
shutdown (analog electronic controls).
Night setback fan/heat cycle
(pneumatic and analog).
Fan unit fusing.
Hanger brackets.
FN2 90 Line Voltage controls
enclosure on model 37S and 37SW
(standard on 37SE).
TM
%
IW
OPTIONAL
INDUCED AIR
INLET FILTER
IH
INDUCED
AIR
MULTI-POINT
FLOW SENSOR
B
W
2
DW
PRIMARY
DIA. =
NOM. 1/8" (3)
FAN
AIR
DH
5 3/4" (146)
DRIVESHAFT
14" (356)
OPTIONAL
PRIMARY AIR
VALVE CONTROLS
ENCLOSURE
PRIMARY
AIR
10" (254)
H
2
HINGED FAN
CONTROLS
ENCLOSURE
11"
(279)
5 1/2"
(140)
%JNFOTJPOBM%BUB
%
6OJU
4J[F
*OMFU
4J[F
*OEVDFE"JS
*OMFU
*8Y*)
0VUMFU
%JTDIBSHF
%8Y%)
'JMUFS
4J[F
4, 5, 6, 8
(102, 127, 152, 203)
19
(483)
36
(914)
4 116
(111)
9
(229)
2 116
(32)
6x8
(152 x 203)
10 14 x 6 78
(260 x 175)
8 x 10
(203 x 254)
2, 3
6, 8, 10
(152, 203, 254)
26 12
(673)
40 14
(1022)
4 38
(111)
7 34
(197)
2 116
(52)
15 34 x 8
(400 x 203)
11 14 x 6 78
(286 x 175)
18 x 10
(457 x 254)
10-10-12
IH
OPTIONAL
INDUCED AIR
INLET FILTER
DH
INDUCED
IW
MULTI-POINT
FLOW
SENSOR
AIR
W
2
FAN
11 1/4"
(286)
PRIMARY
DW
AIR
11 1/4"
(286)
FAN
INDUCED
AIR
5 3/4" (146)
PRIMARY
AIR
DRIVESHAFT
H
2
14" (356)
10" (254)
OPTIONAL
PRIMARY AIR
VALVE CONTROLS
ENCLOSURE
HINGED FAN
CONTROLS
ENCLOSURE
11" (279)
5 1/2"
(140)
%JNFOTJPOBM%BUB
6OJU
4J[F
*OMFU
4J[F
*OEVDFE"JS
*OMFU
*8Y*)
0VUMFU
%JTDIBSHF
%8Y%)
'JMUFS
4J[F
10 (254) Round
14 x 10 (356 x 254) Rect.
44
(1118)
36 12
(927)
9 34
(248)
2 116
(52)
12 x 9
(305 x 229)
Qty. of 2
24 12 x 6 78
(622 x 175)
14 x 10
(356 x 254)
Qty. of 2
10-10-12
%
6OJU4J[FTo
.PEFM48
Available in one, two or three row. Coil
section installed on unit discharge. Right
hand coil connection looking in direction of
airflow standard (shown). Left hand is
optional
(terminals
are
inverted).
Connections must be selected same hand
as controls enclosure location.
11" (279)
D
12" (305)
1 1/8" (29)
1 3/4"
(44)
C
FAN
4UBOEBSE'FBUVSFT
3 5/8"
(92)
COIL
CONNECTION
6OJU4J[F
11"
(279)
D
12"
(305)
1" (25)
1 3/4"
(44)
FAN
C E
FAN
3 5/8"
(92)
J
COIL CONNECTION
%
6OJU
4J[F
0VUMFU%VDU4J[F
$Y%
&
14 58 x 8 34 (371 x 222)
20 (508)
1 (25)
2, 3
24 x 9 (610 x 229)
29 8 (746)
2 78 (73)
41 x 9 (1041 x 229)
46 38 (1178)
2 38 (60)
10-10-12
&MFDUSJD$PJM4FDUJPO
.PEFM4&
11"
(279)
8 1/4"
(210)
4UBOEBSE'FBUVSFT
Controls enclosure incorporates a
hinged access door opening upstream
that helps ensure NEC clearance
requirements and reduces footprint.
1"
(25)
FAN
HEATER
1 1/2"
(38)
HINGED FOR
ELEMENT
REMOVAL
ELECTRIC
COIL AND
HINGED FAN
CONTROLS
ENCLOSURE
6 3/4"
(171)
6OJU4J[F
11"
(279)
4UBOEBSE4VQQMZ7PMUBHF )[
120V, 208, 240 and 277V single
phase.
10"
(254)
FAN
1"
(25)
0QUJPOT
F
37 3/8"
(949)
HEATER
K
FAN
Mercury contactors.
1 1/2"
(38)
HINGED FOR
ELEMENT REMOVAL
ELECTRIC
COIL AND
HINGED FAN
CONTROLS
ENCLOSURE
SCR Control.
6 3/4"
(171)
10-10-12
6OJU
4J[F
0VUMFU%VDU4J[F
'Y(
10 14 x 8 (260 x 203)
35 38 (899)
2, 3
11 4 x 8 (286 x 203)
40 (1016)
3 8 (86)
15 (381)
25 x 8 (635 x 203)
52 38 (1330)
8 12 (216)
15 (381)
2 (12)
15 (381)
%
Unit
Size
Inlet
Size
8
2
10
3
10
10
4
14
x
10
Airflow
cfm
l/s
500
350
250
200
700
600
500
400
800
700
550
350
700
600
500
400
950
800
700
550
350
1100
950
800
1900
1600
1350
1100
800
236
165
118
94
330
283
236
189
378
330
260
165
330
283
236
189
448
378
330
260
165
519
448
378
897
755
637
519
378
Min inlet
Ps
" w.g. Pa
0.05
0.05
0.05
0.05
0.08
0.06
0.05
0.05
0.06
0.05
0.05
0.05
0.08
0.06
0.05
0.05
0.08
0.06
0.05
0.05
0.05
0.12
0.08
0.06
0.28
0.19
0.14
0.09
0.05
12
12
12
12
20
15
12
12
15
12
12
12
20
15
12
12
20
15
12
12
12
30
20
16
70
47
35
22
12
Fan
Only
24
25
28
25
25
31
28
25
20
32
27
23
-
Performance Notes:
1. NC levels are calculated from the
published raw data and based on
procedures outlined in Appendix E,
AHRI 885-2008.
2. Discharge sound attenuation
deductions
are
based
on
environmental effect, duct lining,
branch power division, insulated flex
duct, end reflection and space effect
and are as follows:
Min.
Ps
23
27
23
23
30
27
23
32
28
22
-
Discharge attenuation
< 300 cfm
300 700 cfm
> 700 cfm
Octave Band
3 4 5 6
28 39 53 59
29 40 51 53
30 41 51 52
7
40
39
39
3. Radiated
sound
attenuation
deductions are based on a mineral tile
ceiling and environmental effect and
are as follows:
Radiated attenuation
Total dB reduction
D72
2
24
27
29
Octave Band
2 3 4 5 6 7
18 19 20 26 31 36
7-12-11
8
2
10
8
3
10
4
14
x
10
236
165
118
94
330
283
236
189
378
330
260
165
330
283
236
189
448
378
330
260
165
519
448
378
897
755
637
519
378
Fan Only
2
73
66
61
59
69
65
61
56
73
69
63
54
69
65
61
56
75
73
69
63
54
64
62
59
75
72
68
63
56
3
71
64
58
56
68
64
60
56
73
68
62
54
68
64
60
56
75
73
68
62
54
63
60
58
75
71
67
63
57
4
68
64
58
56
65
62
59
56
69
65
61
54
65
62
59
56
70
69
65
61
54
64
62
60
72
69
66
63
59
5
68
61
54
51
64
60
56
53
68
64
58
51
64
60
56
53
70
68
64
58
51
62
59
57
71
68
64
60
55
6
63
56
48
45
60
56
52
48
64
60
54
46
60
56
52
48
66
64
60
54
46
58
56
53
68
65
61
57
50
7
53
53
42
39
58
53
48
43
62
58
51
40
58
53
48
43
65
62
58
51
40
56
52
48
69
63
59
54
45
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure (Ps) shown
Minimum Ps
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps 2.0" wg (500Pa)Ps
2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
69 66 64 62 56 54 71 67 65 63 58 56 72 68 65 63 58 56 72 68 65 62 57 56 72 68 65 62 57 55
61 57 57 53 47 42 63 58 58 54 47 43 64 60 58 53 48 43 64 61 58 53 48 43 65 62 59 54 48 43
58 54 55 51 44 37 58 55 55 50 44 38 59 56 55 50 43 37 59 55 55 50 44 37 60 57 56 50 44 37
57 54 54 49 42 35 58 54 53 48 41 35 58 55 53 48 41 34 58 55 54 48 41 34 58 55 54 48 41 35
68 67 64 63 59 57 69 68 65 63 60 58 70 68 65 63 60 58 70 68 66 64 60 58 70 67 65 63 59 57
64 64 61 59 55 52 65 64 62 60 56 53 65 64 62 60 56 53 66 65 62 60 55 53 66 64 62 59 55 52
60 60 58 56 51 48 61 60 59 56 52 48 61 60 59 56 52 48 63 61 59 56 51 48 63 61 59 56 51 47
56 56 56 52 47 43 56 56 56 53 48 43 57 57 56 52 48 43 59 58 56 52 47 42 59 57 56 52 47 43
73 72 68 67 63 62 73 72 68 67 64 63 73 72 69 68 64 63 73 70 68 67 64 42 74 73 69 68 64 63
68 67 64 63 59 57 69 68 65 63 60 58 70 68 65 63 60 58 70 68 66 64 60 58 70 67 65 63 59 57
62 62 60 57 53 50 63 62 60 58 54 51 63 62 60 58 54 50 65 63 61 58 53 50 64 62 61 57 53 50
54 54 54 50 45 40 54 54 54 51 46 41 55 55 54 50 46 40 57 56 54 50 45 40 57 56 55 50 46 40
68 67 64 63 59 57 69 68 65 63 60 58 70 68 65 63 60 58 70 68 66 64 60 58 70 67 65 63 59 57
64 64 61 59 55 52 65 64 62 60 56 53 65 64 62 60 56 53 66 65 62 60 55 53 66 64 62 59 55 52
60 60 58 56 51 48 61 60 59 56 52 48 61 60 59 56 52 48 63 61 59 56 51 48 63 61 59 56 51 47
56 56 56 52 47 43 56 56 56 53 48 43 57 57 56 52 48 43 59 58 56 52 47 42 59 57 56 52 47 43
75 75 71 69 66 65 75 75 71 70 67 66 75 75 71 70 67 66 76 75 71 70 67 66 76 76 71 70 67 66
73 72 68 67 63 62 73 72 68 67 64 63 73 72 69 68 64 63 73 70 68 67 64 42 74 73 69 68 64 63
68 67 64 63 59 57 69 68 65 63 60 58 70 68 65 63 60 58 70 68 66 64 60 58 70 67 65 63 59 57
62 62 60 57 53 50 63 62 60 58 54 51 63 62 60 58 54 50 65 63 61 58 53 50 64 62 61 57 53 50
54 54 54 50 45 40 54 54 54 51 46 41 55 55 54 50 46 40 57 56 54 50 45 40 57 56 55 50 46 40
64 63 63 60 56 54 67 65 65 62 58 56 67 66 65 63 59 57 68 64 66 63 60 57 68 67 67 64 60 58
62 59 60 57 53 49 64 62 62 59 55 52 65 63 63 60 56 53 65 62 63 60 56 53 66 64 64 60 57 53
60 55 58 54 50 44 62 59 60 57 52 48 63 60 61 57 53 49 63 60 61 57 53 49 64 61 61 57 53 49
75 75 72 71 68 67 75 75 73 71 69 67 76 77 74 73 70 68 77 77 75 73 71 69 77 77 75 74 72 70
72 72 69 68 65 63 72 73 71 69 66 64 73 73 71 70 67 65 74 74 72 71 69 67 74 73 72 71 69 67
66 66 66 63 60 59 65 66 67 64 62 60 68 69 68 67 64 62 70 69 69 68 65 63 71 70 70 68 66 64
62 61 62 59 56 53 64 65 65 63 60 57 66 66 67 65 62 59 67 66 67 66 63 61 69 68 68 66 64 62
56 57 58 53 49 44 59 59 61 58 54 50 62 62 63 60 57 53 62 62 63 60 57 55 63 63 63 61 58 57
For performance table notes, see page D77; 3&% highlighted numbers indicate embedded AHRI certification points.
6-21-13
%
10
500
350
250
200
700
600
500
400
800
700
550
350
700
600
500
400
950
800
700
550
350
1100
950
800
1900
1600
1350
1100
800
Min. inlet
Ps
"w.g. Pa
0.05 12
0.05 12
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.06 15
0.05 12
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.05 12
0.12 30
0.08 20
0.06 15
0.28 70
0.19 47
0.14 35
0.09 22
0.05 12
8
2
10
3
10
10
14
x
10
500
350
250
200
700
600
500
400
800
700
550
350
700
600
500
400
950
800
700
550
350
1100
950
800
1900
1600
1350
1100
800
236
165
118
94
330
283
236
189
378
330
260
165
330
283
236
189
448
378
330
260
165
519
448
378
897
755
637
519
378
Min. inlet
Ps
" w.g. Pa
0.05 12
0.05 12
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.06 15
0.05 12
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.05 12
0.12 30
0.08 20
0.06 15
0.28 70
0.19 47
0.14 35
0.09 22
0.05 12
Fan Only
2 3
64 55
58 49
57 47
56 46
66 56
63 53
60 51
57 49
65 57
61 54
56 49
51 46
66 56
63 53
60 51
57 49
66 61
65 57
61 54
56 49
51 46
67 62
63 59
58 55
77 71
75 68
72 65
67 61
59 55
4
53
49
48
47
55
53
52
50
58
55
51
48
55
53
52
50
59
58
55
51
48
59
57
54
67
64
62
60
55
5
52
46
44
42
52
50
48
46
56
53
47
43
52
50
48
46
58
56
53
47
43
54
51
48
63
61
58
54
50
6 7
45 37
38 34
35 30
32 25
43 33
40 30
38 28
36 25
48 40
44 36
37 30
33 26
43 33
40 30
38 28
36 25
51 43
48 40
44 36
37 30
33 26
43 34
40 30
37 27
53 45
52 48
49 47
45 43
43 43
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure (Ps) shown
Minimum Ps
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps 2.0" wg (500Pa)Ps
2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
58 50 50 47 38 30 59 52 51 49 44 41 60 55 52 51 50 51 61 57 54 53 53 56 61 58 55 54 55 59
55 46 47 42 34 28 56 47 48 45 43 40 57 51 49 47 48 49 56 52 51 49 51 54 56 53 52 51 53 56
54 45 47 41 33 27 54 46 46 43 41 36 55 47 47 44 46 45 54 46 48 47 49 50 55 49 50 49 51 54
56 46 48 42 33 29 57 47 47 44 40 37 56 48 48 45 46 44 55 48 49 47 48 48 56 47 48 47 49 48
63 56 55 52 43 35 64 58 56 53 47 44 65 60 58 55 51 52 66 62 60 57 54 57 66 65 61 58 56 60
60 53 52 49 39 25 61 55 54 50 45 43 62 58 56 53 50 51 63 60 58 55 52 56 63 63 59 56 55 59
57 50 50 45 36 26 59 53 52 48 44 42 59 56 53 50 49 51 60 59 56 52 51 55 61 61 57 54 54 58
54 47 48 42 33 26 56 50 49 45 42 41 57 54 51 48 48 50 58 57 54 50 49 54 59 58 56 52 54 57
67 60 58 57 48 41 67 60 58 58 50 46 68 62 59 59 53 54 68 64 60 60 56 60 68 65 61 58 58 62
62 55 55 54 44 37 63 58 57 55 48 45 65 59 58 56 53 54 65 60 59 58 55 59 65 63 61 59 57 62
56 49 51 48 37 30 57 52 52 49 44 42 58 55 54 52 51 52 60 59 56 54 54 58 60 59 58 55 56 61
51 46 48 43 33 27 52 48 48 45 43 41 53 52 50 48 50 51 53 53 52 50 53 55 54 54 54 53 55 59
63 56 55 52 43 35 64 58 56 53 47 44 65 60 58 55 51 52 66 62 60 57 54 57 66 65 61 58 56 60
60 53 52 49 39 25 61 55 54 50 45 43 62 58 56 53 50 51 63 60 58 55 52 56 63 63 59 56 55 59
57 50 50 45 36 26 59 53 52 48 44 42 59 56 53 50 49 51 60 59 56 52 51 55 61 61 57 54 54 58
54 47 48 42 33 26 56 50 49 45 42 41 57 54 51 48 48 50 58 57 54 50 49 54 59 58 56 52 54 57
70 64 60 60 52 45 70 64 60 60 53 49 70 65 61 61 55 55 71 66 62 62 57 60 71 67 63 63 58 63
67 60 58 57 48 41 67 60 58 58 50 46 68 62 59 59 53 54 68 64 60 60 56 60 68 65 61 58 58 62
62 55 55 54 44 37 63 58 57 55 48 45 65 59 58 56 53 54 65 60 59 58 55 59 65 63 61 59 57 62
56 49 51 48 37 30 57 52 52 49 44 42 58 55 54 52 51 52 60 59 56 54 54 58 60 59 58 55 56 61
51 46 48 43 33 27 52 48 48 45 43 41 53 52 50 48 50 51 53 53 52 50 53 55 54 54 54 53 55 59
62 58 56 49 39 30 63 61 58 51 44 41 65 63 60 54 48 48 66 64 62 56 51 52 68 68 64 59 53 56
58 56 54 48 37 27 61 59 56 50 42 39 62 62 58 52 46 46 65 64 60 54 50 52 67 67 63 56 53 55
55 54 53 46 35 24 58 58 55 49 41 38 60 60 57 50 45 45 63 64 59 53 50 52 66 67 62 54 52 55
76 70 66 61 52 45 77 71 66 62 53 47 77 71 66 62 54 52 78 72 68 63 56 57 78 73 69 64 58 60
73 67 63 59 49 41 74 68 64 59 50 44 75 70 65 61 53 52 77 71 67 62 55 56 76 72 67 62 57 59
70 63 60 56 45 37 71 65 61 57 48 43 73 67 63 58 51 50 74 68 64 59 54 55 73 68 65 60 56 58
67 60 59 53 41 33 69 63 60 55 46 40 70 65 62 57 51 50 70 64 62 57 53 55 71 66 63 58 55 57
59 55 54 48 39 30 61 57 56 51 45 40 62 59 57 53 49 49 63 61 58 54 51 53 64 61 59 55 55 57
For performance table notes, see page D75; RED highlighted numbers indicate embedded AHRI certification points.
D74
7-1-13
Inlet
Size
Fan CFM
cfm
1
2
3
4
8
450
10
700
10
1100
14 x 10 1800
l/s
212
330
519
849
Fan
Watts
2
140
140
440
690
76
68
79
82
Discharge
4 5 6
72
67
77
79
66
64
71
75
63
61
71
74
60
58
69
72
58
56
66
69
73
67
74
77
61
57
64
71
Radiated
4 5 6
54
54
62
67
48
52
59
63
39
43
51
53
Primary
CFM
7
cfm
32
32
41
45
450
700
1100
1800
212
330
519
849
Min. Inlet
0.05
0.06
0.08
0.28
12
15
20
70
72
68
75
78
63
65
69
72
55
58
67
68
50
57
65
63
42
49
56
56
41
46
49
57
ECM Motor.
D
Ratings are certified in
accordance with AHRI
Standards.
1. Discharge (external) static pressure is 0.25" w.g. (63 Pa)
in all cases, which is the difference (Ps) in static
pressure from terminal discharge to the room.
Discharge Sound Power Levels (SWL) now include duct
end reflection energy as part of the standard rating.
Including the duct end correction provides sound power
levels that would normally be transmitted into an
acoustically, non-reflective duct. The effect of including
the energy correction to the discharge SWL, is higher
sound power levels when compared to previous AHRI
certified data. For more information on duct end reflection
calculations see AHRI 880-2011.
2. Radiated sound power is the breakout noise
transmitted through the unit casing walls.
2-12-15
D75
l/s CFM
Unit Size 3
l/s CFM
519 1100
425 900
MAXIMUM
330 700
425 900
ELECTRIC HEAT OR
1 OR 2 ROW H. W. COIL
ELECTRIC HEAT OR
1 OR 2 ROW H. W. COIL
378 800
AIRFLOW
AIRFLOW
283 600
MAXIMUM
472 1000
378 800
236 500
330 700
189 400
283 600
142 300
236 500
MINIMUM
189 400
94 200
MINIMUM
142 300
47 100
0.0
0
l/s CFM
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Unit Size 4
1038 2200
991 2100
MAXIMUM
Electrical Data
944 2000
897 1900
849 1800
AIRFLOW
802 1700
ELECTRIC HEAT OR
1 ROW H. W. COIL
755 1600
2 ROW H. W. COIL
708 1500
661 1400
613 1300
566 1200
519 1100
472 1000
425
900
378
800
MINIMUM
0.0
0
D76
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
2-11-14
l/s CFM
236 500
212
472 1000
MAXIMUM
450
400
165
350
142
300
118
250
94
900
378
800
330
700
283
600
236
500
189
400
142
300
94
200
47
100
150
47
100
MINIMUM
50
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
MINIMUM
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
NOTES:
The fan curves for the ECM are unlike those for traditional
PSC motors. The ECM is constant volume at factory or
field set point and airflow does not vary with changing static
pressure conditions. The motor compensates for any
changes in external static pressure or induced air conditions
such as filter loading.
Airflow can be set to operate on horizontal performance
line at any point within shaded area using the solid state
volume controller provided.
Fan powered terminal units featuring the optional ECM
have considerably wider turn-down ratios than
conventional PSC motors. Hence, a reduced number of
unit sizes are required in order to provide the same fan
airflow range when compared with terminals equipped with
PSC motors. A reduction in the number of different terminal
sizes required on a typical project simplifies design lay-out
and installation and reduces inventory of field service parts.
Fan curves shown are applicable to 120, 208, 240 and 277
volt, single phase ECMs. ECMs, although DC in
operation, include a built-in inverter.
Electrical Data
Unit Size 4
l/s CFM
944 2000
MAXIMUM
849 1800
755 1600
661 1400
AIRFLOW
566 1200
472 1000
378
800
283
600
189
400
94
200
MINIMUM
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
ECM FLA
Unit Motor
Size H. P. 120/1/60 208/1/60 240/1/60 277/1/60
1
1.7
1.1
1.1
1.1
*
3
4.4
3.1
3.0
3.1
*
4
8.4
5.5
5.4
5.8
*
The ECM is a variable horsepower motor.
Refer to Selectworks Schedule.
FLA = Full load amperage
EON motor series
6-1-16
D77
425
MAXIMUM
200
71
24
AIRFLOW
AIRFLOW
189
Unit Size 3
l/s CFM
519 1100
.PEFMT
445
/P)FBU
4&45
&MFDUSJD)FBU
4845
)PU8BUFS)FBU
Model 37SWST
The 37SST "StealthTM" Series are only 11" (279) high and have been specifically designed for shallow ceiling plenum
applications, which are common where zoning requirements limit building height and the architect wishes to maximize the
number of floors. Utilizing "StealthTM" design technology, this terminal has industry leading low sound levels.
'&"563&4
20 ga. (1.00) galvanized steel
construction.
16 ga. (1.6) galvanized steel
inclined opposed blade primary air
damper. 45O rotation, CW to close.
1/2" (13) dia. plated steel drive shaft.
An indicator mark on the end of the
shaft shows damper-position. Leakage
is less than 2% of nominal flow at 3"
w.g. (750 Pa).
"StealthTM" design technology
provides significant reductions in
radiated sound levels.
Perforated baffle on primary air
discharge optimizes mixing with
induced air for rapid and effective
temperature equalization. The baffle
also converts low frequency primary
air valve generated sound into more
readily attenuated higher frequencies.
Pressure independent primary
airflow control.
Multi-point averaging flow sensor.
Terminal may be field installed
either way up, providing the additional
flexibility of right or left field
connections.
Access panels are full size on top
and bottom of terminal for ease of
maintenance and service.
Energy efficient PSC fan motor with
thermal overload protection.
%
0QUJPOT
TM
$POUSPMT
Pneumatic and analog electronic
controls. Factory supplied, mounted
and calibrated.
Digital controls. Factory mounting
and wiring of DDC controls supplied
by BMS Controls Contractor.
7-12-11
IH
INDUCED
IW
AIRFLOW
N
MULTI-POINT
FLOW SENSOR
OPTIONAL
INDUCED
AIR FILTER
W
2
BASIC UNIT
DIA. =
NOM 1/8" (3)
B
W2
DW
PRIMARY
FAN
AIR
P
DH
5 3/4" (146)
DRIVESHAFT
AIR
10" (254)
OPTIONAL
PRIMARY AIR
VALVE CONTROLS
ENCLOSURE
PRIMARY
H
2
14" (356)
5 1/2"
(140)
HINGED FAN
CONTROLS
ENCLOSURE
11" (279)
%JNFOTJPOBM%BUB
10-10-12
6OJU
4J[F
*OMFU
4J[F
8
4, 5, 6, 8
(102, 127, 152, 203)
19
(483)
28
(711)
36
(914)
2, 3
6, 8, 10
(152, 203, 254)
26 12
(673)
*OEVDFE"JS
0VUMFU
*OMFU
%JTDIBSHF
*8Y*)
%8Y%)
'JMUFS
4J[F
16
(21)
7
(178)
2 116
(52)
9 x 11
(229 x 279)
10 14 x 6 78
(260 x 175)
9 x 11
(229 x 279)
38 12 40 14
4 38
(978) (1022) (111)
6 14
(159)
2 116
(52)
12 x 11
(305 x 279)
11 14 x 6 78
(286 x 175)
12 x 11
(305 x 279)
13
%
IH
INDUCED
19 1/2"
(495)
IW
AIR
L
41 1/2"
(114)
MULTI-POINT
AIRFLOW
SENSOR
W
2
DH
FAN
11 1/4"
(286)
PRIMARY
DW
AIR
83"
(2108)
11 1/4"
(286)
FAN
5 3/4"
(146)
33 1/2"
(851)
14"
(356)
10"
(254)
INDUCED
AIR
11"
(279)
5 1/2"
(140)
OPTIONAL
HINGED FAN
PRIMARY AIR
CONTROLS
VALVE CONTROLS
ENCLOSURE
ENCLOSURE
PRIMARY
H
2
AIR
OPTIONAL
INDUCED
AIR FILTER
11" (279)
%JNFOTJPOBM%BUB
%
6OJU
4J[F
*OMFU
4J[F
*OEVDFE"JS
*OMFU
*8Y*)
0VUMFU
%JTDIBSHF
%8Y%)
'JMUFS
4J[F
10 (254) Round
14 x 10 (356 x 254) Rect.
44
(1118)
36 12
(927)
9 34
(248)
2 116
(52)
12 x 9
(305 x 229)
Qty. of 2
24 12 x 6 78
(622 x 175)
14 x 10
(356 x 254)
Qty. of 2
11-12-12
)PU8BUFS$PJM4FDUJPO
.PEFM4845
11" (279)
IW
12" (305)
1 3/4"
(44)
4UBOEBSE'FBUVSFT
W3
FAN
3 5/8"
(92)
D
D
1 1/8" (29)
COIL
CONNECTION
6OJU4J[F
11" (279)
D
12" (305)
1" (25)
1 3/4"
(44)
FAN
C E
FAN
3 5/8"
(92)
J
COIL CONNECTION
11-12-12
6OJU
4J[F
0VUMFU%VDU4J[F
$Y%
*8
8
&
14 58 x 8 34 (371 x 222)
9 (229)
29 (737)
20 (508)
1 (25)
2, 3
24 x 9 (610 x 229)
12 (305)
41 8 (1051)
29 8 (746)
12 18 (308)
41 x 9 (1041 x 229)
46 8 (1178)
2 38 (60)
%
&MFDUSJD$PJM4FDUJPO
.PEFM4&45
11" (279)
4UBOEBSE'FBUVSFT
Controls enclosure incorporates a
hinged
access
door
opening
downstream that helps ensure NEC
clearance requirements and reduces
footprint.
IW
8 1/4"
(210)
H
1"
(25)
FAN
W3
HEATER
G
HINGED FOR
ELEMENT REMOVAL
HINGED FAN
CONTROLS
ENCLOSURE
6 3/4"
(171 )
6OJU4J[F
4UBOEBSE4VQQMZ7PMUBHF )[
11" (279)
10"
(254)
FAN
0QUJPOT
1"
(25)
HEATER
Mercury contactors.
W3
K
FAN
1 1/2"
(38)
HINGED FAN
CONTROLS
ENCLOSURE
M
HINGED FOR
ELEMENT REMOVAL
SCR Control.
6 3/4"
(171)
%
6OJU
4J[F
0VUMFU%VDU4J[F
'Y(
*8
8
10 14 x 8 (260 x 203)
9 (229)
44 78 (1140)
35 38 (899)
2 (12)
15 (381)
2, 3
11 4 x 8 (286 x 203)
12 (305)
55 8 (1407)
40 (1016)
3 38 (86)
15 (381)
25 x 8 (635 x 203)
60 78 (1546)
52 38 (1330)
8 12 (216)
15 (381)
)
1
10-10-12
8
2
10
8
3
10
14
x
10
Min inlet
Ps
" w.g. Pa
500
350
250
200
700
600
500
400
800
700
550
350
700
600
500
400
950
800
700
550
350
1100
950
800
1900
1600
1350
1100
800
0.05
0.05
0.05
0.05
0.08
0.06
0.05
0.05
0.06
0.05
0.05
0.05
0.08
0.06
0.05
0.05
0.05
0.06
0.05
0.05
0.05
0.12
0.08
0.06
0.05
0.19
0.14
0.09
0.05
236
165
118
94
330
283
236
189
378
330
260
165
330
283
236
189
448
378
330
260
165
519
448
378
897
755
637
519
378
12
12
12
12
20
15
12
12
15
12
12
12
20
15
12
12
12
15
12
12
12
30
20
16
12
47
35
22
12
Fan
Only
Min.
Ps
24
25
28
25
25
31
28
25
20
32
27
23
-
23
27
23
23
30
27
23
32
28
22
-
1FSGPSNBODF/PUFT
1. NC levels are calculated from the
published raw data and based on
procedures outlined in Appendix E,
AHRI 885-2008.
2. Discharge sound attenuation
deductions
are
based
on
environmental effect, duct lining,
branch power division, insulated flex
duct, end reflection and space effect
and are as follows:
20
24
28
24
24
30
28
24
20
35
30
26
23
-
Discharge attenuation
< 300 cfm
300 700 cfm
> 700 cfm
2
24
27
29
20
23
28
25
23
32
28
25
22
35
30
27
25
20
Octave Band
3 4 5 6
28 39 53 59
29 40 51 53
30 41 51 52
25
23
20
30
25
23
20
33
30
25
23
21
42
37
31
25
20
7
40
39
39
3. Radiated
sound
attenuation
deductions are based on a mineral tile
ceiling and environmental effect and
are as follows:
Radiated attenuation
Total dB reduction
7-12-11
20
25
25
24
25
31
25
24
20
35
31
27
25
-
Octave Band
2 3 4 5 6 7
18 19 20 26 31 36
24
20
29
26
24
20
32
29
26
21
42
35
31
25
-
20
25
21
30
25
20
25
21
33
30
25
20
25
22
20
43
37
33
30
20
23
27
25
23
20
31
27
22
27
25
23
20
34
31
27
22
28
25
24
44
39
35
33
23
26
21
28
26
25
24
30
29
24
20
28
26
25
24
33
30
29
24
20
29
28
28
44
40
39
32
25
28
21
32
30
27
25
30
29
25
22
32
30
27
25
34
30
29
25
22
34
31
29
45
41
38
33
25
%
10
Airflow
cfm
l/s
4UFBMUI
7"7'JCFSHMBTT
Unit Inlet Airflow
Size Size cfm l/s
8
2
10
3
10
10
4
14
x
10
500
350
250
200
700
600
500
400
800
700
550
350
700
600
500
400
950
800
700
550
350
1100
950
800
1900
1600
1350
1100
800
236
165
118
94
330
283
236
189
378
330
260
165
330
283
236
189
448
378
330
260
165
519
448
378
897
755
637
519
378
Min. inlet
Ps
"w.g. Pa
0.05 12
0.05 12
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.06 15
0.05 12
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.05 12
0.12 30
0.08 20
0.06 15
0.28 70
0.19 47
0.14 35
0.09 22
0.05 12
Fan Only
2
73
66
61
59
69
65
61
56
73
69
63
54
69
65
61
56
75
73
69
63
54
64
62
59
75
72
68
63
56
3
71
64
58
56
68
64
60
56
73
68
62
54
68
64
60
56
75
73
68
62
54
63
60
58
75
71
67
63
57
4
68
64
58
56
65
62
59
56
69
65
61
54
65
62
59
56
70
69
65
61
54
64
62
60
72
69
66
63
59
5
68
61
54
51
64
60
56
53
68
64
58
51
64
60
56
53
70
68
64
58
51
62
59
57
71
68
64
60
55
6
63
56
48
45
60
56
52
48
64
60
54
46
60
56
52
48
66
64
60
54
46
58
56
53
68
65
61
57
50
7
53
53
42
39
58
53
48
43
62
58
51
40
58
53
48
43
65
62
58
51
40
56
52
48
59
63
59
54
45
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure (Ps) shown
Minimum Ps
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps 2.0" wg (500Pa)Ps
2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
69 66 64 62 56 54 71 67 65 63 58 56 72 68 65 63 58 56 72 68 65 62 57 56 72 68 65 62 57 55
61 57 57 53 47 42 63 58 58 54 47 43 64 60 58 53 48 43 64 61 58 53 48 43 65 62 59 54 48 43
58 54 55 51 44 37 58 55 55 50 44 38 59 56 55 50 43 37 59 55 55 50 44 37 60 57 56 50 44 37
57 54 54 49 42 35 58 54 53 48 41 35 58 55 53 48 41 34 58 55 54 48 41 34 58 55 54 48 41 35
68 67 64 63 59 57 69 68 65 63 60 58 70 68 65 63 60 58 70 68 66 64 60 58 70 67 65 63 59 57
64 64 61 59 55 52 65 64 62 60 56 53 65 64 62 60 56 53 66 65 62 60 55 53 66 64 62 59 55 52
60 60 58 56 51 48 61 60 59 56 52 48 61 60 59 56 52 48 63 61 59 56 51 48 63 61 59 56 51 47
56 56 56 52 47 43 56 56 56 53 48 43 57 57 56 52 48 43 59 58 56 52 47 42 59 57 56 52 47 43
73 72 68 67 63 62 73 72 68 67 64 63 73 72 69 68 64 63 73 70 68 67 64 42 74 73 69 68 64 63
68 67 64 63 59 57 69 68 65 63 60 58 70 68 65 63 60 58 70 68 66 64 60 58 70 67 65 63 59 57
62 62 60 57 53 50 63 62 60 58 54 51 63 62 60 58 54 50 65 63 61 58 53 50 64 62 61 57 53 50
54 54 54 50 45 40 54 54 54 51 46 41 55 55 54 50 46 40 57 56 54 50 45 40 57 56 55 50 46 40
68 67 64 63 59 57 69 68 65 63 60 58 70 68 65 63 60 58 70 68 66 64 60 58 70 67 65 63 59 57
64 64 61 59 55 52 65 64 62 60 56 53 65 64 62 60 56 53 66 65 62 60 55 53 66 64 62 59 55 52
60 60 58 56 51 48 61 60 59 56 52 48 61 60 59 56 52 48 63 61 59 56 51 48 63 61 59 56 51 47
56 56 56 52 47 43 56 56 56 53 48 43 57 57 56 52 48 43 59 58 56 52 47 42 59 57 56 52 47 43
75 75 71 69 66 65 75 75 71 70 67 66 75 75 71 70 67 66 76 75 71 70 67 66 76 76 71 70 67 66
73 72 68 67 63 62 73 72 68 67 64 63 73 72 69 68 64 63 73 70 68 67 64 42 74 73 69 68 64 63
68 67 64 63 59 57 69 68 65 63 60 58 70 68 65 63 60 58 70 68 66 64 60 58 70 67 65 63 59 57
62 62 60 57 53 50 63 62 60 58 54 51 63 62 60 58 54 50 65 63 61 58 53 50 64 62 61 57 53 50
54 54 54 50 45 40 54 54 54 51 46 41 55 55 54 50 46 40 57 56 54 50 45 40 57 56 55 50 46 40
64 63 63 60 56 54 67 65 65 62 58 56 67 66 65 63 59 57 68 64 66 63 60 57 68 67 67 64 60 58
62 59 60 57 53 49 64 62 62 59 55 52 65 63 63 60 56 53 65 62 63 60 56 53 66 64 64 60 57 53
60 55 58 54 50 44 62 59 60 57 52 48 63 60 61 57 53 49 63 60 61 57 53 49 64 61 61 57 53 49
75 75 72 71 68 67 75 75 73 71 69 67 76 77 74 73 70 68 77 77 75 73 71 69 77 77 75 74 72 70
72 72 69 68 65 63 72 73 71 69 66 64 73 73 71 70 67 65 74 74 72 71 69 67 74 73 72 71 69 67
66 66 66 63 60 59 65 66 67 64 62 60 68 69 68 67 64 62 70 69 69 68 65 63 71 70 70 68 66 64
62 61 62 59 56 53 64 65 65 63 60 57 66 66 67 65 62 59 67 66 67 66 63 61 69 68 68 66 64 62
56 57 58 53 49 44 59 59 61 58 54 50 62 62 63 60 57 53 62 62 63 60 57 55 63 63 63 61 58 57
For performance table notes, see page D88; 3&% highlighted numbers indicate embedded AHRI certification points.
%
6-21-13
8
2
10
10
10
14
x
10
236
165
118
94
330
283
236
189
378
330
260
165
330
283
236
189
448
378
330
260
165
519
448
378
897
755
637
519
378
Fan Only
2 3
58 56
52 50
50 47
48 45
59 54
55 51
52 48
48 45
66 59
62 55
56 49
50 44
59 54
55 51
52 48
48 45
68 62
66 59
62 55
56 49
50 44
59 55
56 52
54 50
76 68
72 64
67 59
63 55
56 51
4
49
45
42
41
50
47
44
42
53
51
45
42
50
47
44
42
56
53
51
45
42
49
47
45
59
56
53
50
46
5
44
39
36
34
43
40
38
35
47
44
39
34
43
40
38
35
50
47
44
39
34
43
40
38
53
50
47
43
41
6 7
37 33
32 29
31 30
30 30
36 33
33 30
31 27
29 24
40 34
36 31
31 26
27 23
36 33
33 30
31 27
29 24
44 38
40 34
36 31
31 26
27 23
33 29
31 26
29 23
52 46
47 40
44 36
38 31
37 29
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure (Ps) shown
Minimum Ps
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps 2.0" wg (500Pa)Ps
2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
52 49 45 39 32 29 54 52 47 41 34 31 56 55 48 43 37 36 58 58 49 44 39 41 58 59 50 45 40 42
46 43 40 34 29 23 49 47 41 35 31 29 52 51 43 38 34 34 53 53 45 41 37 38 52 54 46 42 38 40
45 42 40 33 29 24 47 44 40 34 30 27 48 47 41 36 32 32 48 46 43 38 35 36 48 49 44 41 37 38
47 43 41 34 30 26 48 45 40 34 30 27 48 46 40 35 32 32 49 46 42 38 34 35 49 46 42 38 36 37
57 53 50 43 35 32 58 55 50 44 37 34 59 58 52 46 38 37 61 59 53 47 40 41 62 62 54 48 41 44
54 50 47 40 33 29 55 52 48 42 35 32 58 56 49 44 37 36 59 57 51 45 39 40 60 60 52 47 40 43
50 46 44 37 31 27 52 50 45 39 33 31 56 54 47 42 35 36 57 56 49 43 37 39 58 58 51 45 39 42
47 43 41 34 29 24 50 47 42 36 31 29 54 52 45 39 34 35 55 55 47 42 36 38 56 56 49 43 38 42
65 58 53 48 40 35 66 59 53 48 40 36 67 60 54 49 41 39 66 60 55 50 42 42 66 61 56 51 43 46
62 56 53 45 37 32 62 56 52 46 37 33 62 57 53 47 39 38 63 57 55 49 40 42 63 58 55 49 40 42
55 48 46 39 30 27 55 50 46 40 32 30 58 53 48 44 36 36 59 55 50 46 38 41 60 56 52 47 40 44
49 43 42 34 27 25 50 44 42 35 29 28 51 47 44 39 33 34 52 49 46 45 36 39 53 41 48 44 38 42
57 53 50 43 35 32 58 55 50 44 37 34 59 58 52 46 38 37 61 59 53 47 40 41 62 62 54 48 41 44
54 50 47 40 33 29 55 52 48 42 35 32 58 56 49 44 37 36 59 57 51 45 39 40 60 60 52 47 40 43
50 46 44 37 31 27 52 50 45 39 33 31 56 54 47 42 35 36 57 56 49 43 37 39 58 58 51 45 39 42
47 43 41 34 29 24 50 47 42 36 31 29 54 52 45 39 34 35 55 55 47 42 36 38 56 56 49 43 38 42
68 60 56 50 42 37 68 61 57 50 43 38 69 62 58 51 44 41 69 62 58 52 44 43 69 63 59 54 45 46
65 58 53 48 40 35 66 59 53 48 40 36 67 60 54 49 41 39 66 60 55 50 42 42 66 61 56 51 43 46
62 56 53 45 37 32 62 56 52 46 37 33 62 57 53 47 39 38 63 57 55 49 40 42 63 58 55 49 40 42
55 48 46 39 30 27 55 50 46 40 32 30 58 53 48 44 36 36 59 55 50 46 38 41 60 56 52 47 40 44
49 43 42 34 27 25 50 44 42 35 29 28 51 47 44 39 33 34 52 49 46 45 36 39 53 41 48 44 38 42
58 52 48 40 31 27 60 56 49 42 33 30 63 58 51 45 36 34 65 59 53 47 38 38 67 63 55 49 40 41
55 50 45 37 29 25 58 54 47 40 32 29 61 57 49 42 34 33 64 58 52 45 37 37 65 61 53 46 38 40
52 48 43 35 27 22 56 52 46 38 30 28 59 55 48 40 33 32 62 58 50 42 36 36 64 59 52 43 37 39
76 67 58 52 49 44 76 67 59 53 49 44 77 68 60 53 50 45 77 69 60 54 51 47 77 70 61 55 52 50
71 62 54 47 43 37 71 64 56 49 45 39 73 65 57 50 46 42 74 66 58 51 48 45 75 67 59 52 50 48
67 58 51 45 40 33 68 61 53 46 42 35 71 63 55 48 45 40 73 64 56 49 47 45 72 64 57 50 49 48
63 54 48 40 36 29 66 57 50 43 39 32 68 59 52 45 42 39 68 58 53 46 45 44 68 61 54 48 48 48
55 48 44 38 35 27 59 52 46 41 38 31 61 54 48 43 41 38 62 55 49 44 45 43 63 56 52 46 47 47
For performance table notes, see page D86; RED highlighted numbers indicate embedded AHRI certification points.
7-11-11
D85
500
350
250
200
700
600
500
400
800
700
550
350
700
600
500
400
950
800
700
550
350
1100
950
800
1900
1600
1350
1100
800
Min. inlet
Ps
" w.g. Pa
0.05 12
0.05 12
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.06 15
0.05 12
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.08 20
0.06 15
0.05 12
0.05 12
0.05 12
0.12 30
0.08 20
0.06 15
0.28 12
0.19 47
0.14 35
0.09 22
0.05 12
1
2
3
4
Inlet
Size
8
10
10
14 x 10
Fan CFM
cfm
l/s
450
700
1100
1800
212
330
519
849
Fan
Watts
140
140
440
690
78
69
77
82
73
68
76
80
Discharge
4 5 6
67
64
69
76
65
62
69
75
62
59
67
73
Primary
CFM
Min. Inlet
Ps
Radiated
4 5 6
cfm
l/s
" w.g.
Pa
Radiated
4
5
60
56
64
70
72
64
72
76
63
56
62
68
56
51
59
59
38
27
40
46
450
700
1100
1800
212
330
519
849
0.05
0.06
0.05
0.05
12
15
12
12
71
65
73
77
63
61
65
69
54
52
61
60
40
37
46
51
35
33
39
47
50
45
54
53
44
37
47
52
47
48
56
54
ECM Motor.
D86
2-12-15
l/s CFM
Unit Size 3
l/s CFM
519 1100
425 900
MAXIMUM
330 700
425 900
ELECTRIC HEAT OR
1 OR 2 ROW H. W. COIL
ELECTRIC HEAT OR
1 OR 2 ROW H. W. COIL
378 800
AIRFLOW
283 600
AIRFLOW
MAXIMUM
472 1000
378 800
236 500
330 700
189 400
283 600
142 300
236 500
MINIMUM
189 400
94 200
MINIMUM
142 300
47 100
0.0
0
l/s CFM
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Unit Size 4
1038 2200
MAXIMUM
991 2100
Electrical Data
944 2000
897 1900
849 1800
AIRFLOW
802 1700
ELECTRIC HEAT OR
1 ROW H. W. COIL
755 1600
2 ROW H. W. COIL
708 1500
661 1400
613 1300
566 1200
519 1100
472 1000
425
900
378
800
MINIMUM
0.0
0
3-3-14
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
D87
l/s CFM
236 500
450
189
400
165
350
142
300
118
250
94
200
71
150
47
100
472 1000
MAXIMUM
425
900
378
800
330
700
283
600
236
500
189
400
142
300
94
200
47
100
50
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
NOTES:
The fan curves for the ECM are unlike those for traditional
PSC motors. The ECM is constant volume at factory or
field set point and airflow does not vary with changing static
pressure conditions. The motor compensates for any
changes in external static pressure or induced air conditions
such as filter loading.
Airflow can be set to operate on horizontal performance
line at any point within shaded area using the solid state
volume controller provided.
Fan powered terminal units featuring the optional ECM
have considerably wider turn-down ratios than
conventional PSC motors. Hence, a reduced number of
unit sizes are required in order to provide the same fan
airflow range when compared with terminals equipped with
PSC motors. A reduction in the number of different terminal
sizes required on a typical project simplifies design lay-out
and installation and reduces inventory of field service parts.
Fan curves shown are applicable to 120, 208, 240 and 277
volt, single phase ECMs. ECMs, although DC in
operation, include a built-in inverter.
Electrical Data
MINIMUM
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Unit Size 4
l/s CFM
944 2000
MAXIMUM
849 1800
755 1600
661 1400
AIRFLOW
MINIMUM
24
MAXIMUM
AIRFLOW
AIRFLOW
212
Unit Size 3
l/s CFM
519 1100
566 1200
472 1000
378
800
283
600
189
400
94
200
MINIMUM
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
ECM FLA
Unit Motor
Size H. P. 120/1/60 208/1/60 240/1/60 277/1/60
1
1.7
1.1
1.1
1.1
*
3
4.4
3.1
3.0
3.1
*
4
8.4
5.5
5.4
5.8
*
The ECM is a variable horsepower motor.
Refer to Selectworks Schedule.
FLA = Full load amperage
EON motor series
D88
6-1-16
3PX NVMUJDJSDVJU
3 .19
2 .13
1.5 .09
4.1 14
GPM l/s
kW MBH
7.9 27
GPM l/s
kW MBH
4.7 16
7.0 24
.19
.13
1.5 .09
.06
6.2 21
3.5 12
.06
5.3 18
0.5 .03
2.9 10
4.4 15
2.3
0.5 .03
8
3.5 12
0.6
2
50
24
150
71
250
118
350
165
450
212
7.3 25
3
50
24
.19
.13
17.9 6.0
.06
5.6 19
0.5 .03
4.7 16
3.8 13
2.9 10
0.9
6.4 22
1.2
1.5 .09
8.2 28
1.8
150
71
250
118
350
165
8BUFS1SFTTVSF%SPQ
GPM l/s
9.1 31
2.1
550 $'.
236 MT
3PX NVMUJDJSDVJU
kW MBH
10.0 34
2.6
149 0.60
150
71
250
118
350
165
450
212
1 ROW
2 ROW
6.0 2.0
3 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
50 0.20
3 ROW
25 0.10
20 0.08
15 0.06
2 ROW
10 0.04
1 ROW
0.6 0.2
5 0.02
550 $'.
236 MT
2 0.01
1
.06
2
3 4
6 8 10 (1.
.13 .19 .25 .38 .50.63 MT
8"5&3'-08
100
47
200
300 400
94
142 189
"*3'-08
600 '.
283 MT
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
1. Capacities are in MBH (kW), thousands of Btu
per hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 110F (61C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
8-10-11
550 $'.
236 MT
100 0.40
11.9 4.0
0.3 0.1
50
24
450
212
"JS1SFTTVSF%SPQ
Pa in. H2O
249 1.00
447 0.80
"*313&4463&%301
1.2
)&"%-044 8"5&313&4463&%301
U ' $
Factor
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
%
1.8
3PX NVMUJDJSDVJU
kW MBH
8.2 28
GPM l/s
7.6 26
5
4
3
.32
.25
.19
.13
kW MBH
13.8 47
GPM l/s
5 .32
4 .25
12.3 42
7.0 24
1.5 .09
.19
.13
10.8 37
6.4 22
1.5 .09
1
5.9 20
.06
9.4 32
1
5.3 18
4.7 16
0.5 .03
6.4 22
0.5 .03
4.1 14
5.0 17
3.5 12
2.9 10
400
189
500
236
600
283
700
330
800
378
900
425
1000 $'.
472 MT
3PX NVMUJDJSDVJU
kW MBH
17.9 61
300
142
400
189
500
236
600
283
700
330
8BUFS1SFTTVSF%SPQ
GPM l/s
16.4 56
5
4
.32
.25
.19
14.9 51
2
.13
13.5 46
1.5 .09
12.0 41
10.5 36
.06
9.1 31
7.6 26
0.5 .03
6.2 21
17.9 6.0
149 0.60
11.9 4.0
2 ROW
2.4 0.8
1.8 0.6
1.2 0.4
3 ROW
0.6 0.2
300
142
400
189
500
236
600
283
700
330
800
378
900
425
1000 $'.
472 MT
1
.06
50 0.20
3 ROW
25 0.10
2 ROW
20 0.08
15 0.06
10 0.04
1 ROW
5 0.02
2 0.01
2
3 4
6 8 10 (1.
.13 .19 .25 .38 .50 .63 MT
8"5&3'-08
100
47
200
400500
94
189236
"*3'-08
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
1. Capacities are in MBH (kW), thousands of Btu
per hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 110F (61C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
U ' $
Factor
1000 $'.
472 MT
100 0.40
1 ROW
6.0 2.0
3.0 1.0
900
425
"JS1SFTTVSF%SPQ
Pa in. H2O
249 1.00
447 0.80
0.3 0.1
4.7 16
800
378
"*313&4463&%301
300
142
)&"%-044 8"5&313&4463&%301
3.5 12
%
.06
7.9 27
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
8-10-11
3PX NVMUJDJSDVJU
kW MBH
14.9 51
GPM l/s
7.5 .47
5
4
13.5 46
kW MBH
25.5 87
.32
.25
.19
GPM l/s
7.5 .47
24.0 82
.32
22.6 77
.25
.19
.13
21.1 72
12.0 41
10.5 36
.13
19.6 67
1.5 .09
18.2 62
16.7 57
9.1 31
1.5 .09
15.2 52
.06
13.8 47
12.3 42
7.6 26
.06
10.8 37
6.2 21
9.4 32
0.5 .03
7.9 27
6.4 22
1200
566
1400
661
1600
755
1800
849
3PX NVMUJDJSDVJU
kW MBH
35.2 120
600
283
2000 $'.
944 MT
800
378
1000
472
1200
566
8BUFS1SFTTVSF%SPQ
GPM l/s
10 .63
7.5 .47
32.2 110
29.3 100
.32
.25
.19
26.4 90
23.4 80
2
20.5 70
17.6 60
.13
1.5 .09
14.7 50
1
.06
1400
661
1600
755
1800 $'.
849 MT
"JS1SFTTVSF%SPQ
Pa in. H2O
249 1.00
447 0.80
149 0.60
1 ROW
100 0.40
11.9 4.0
2 ROW
6.0 2.0
3 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
"*313&4463&%301
1000
472
)&"%-044 8"5&313&4463&%301
800
378
50 0.20
3 ROW
25 0.10
20 0.08
2 ROW
15 0.06
10 0.04
1 ROW
0.6 0.2
5 0.02
11.7 40
0.3 0.1
8.8 30
800
378
1000
472
1200
566
1400
661
1600
755
1800
849
2000 $'.
944 MT
2 0.01
1
.06
2
3 4
6 8 10 (1.
.13 .19 .25 .38 .50.63 MT
8"5&3'-08
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
8-10-11
200
94
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
U ' $
Factor
100
47
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
%
0.5 .03
4.7 16
1.
Furnish and install constant volume series fan powered
terminal units of the sizes and capacities as indicated on the
drawings. Units shall be pressure independent with (pneumatic,
analog electronic, digital electronic) controls. Units shall be
manufactured by /BJMPS*OEVTUSJFT*ODModel 4.
2.
The entire terminal unit shall be designed and built as a single
unit. The units shall be provided with a primary variable air volume
damper that controls the air quantity in response to a (pneumatic,
electronic) thermostat. The space limitations shall be reviewed
carefully to ensure that all units will fit into the space allowed.
3.
Unit casings shall be space frame construction utilizing 16 ga.
(1.61) galvanized steel corner structural members and 20 ga. (1.00)
galvanized steel panels. Unit shall be fully lined with fiberglass
insulation which shall be at least 3/4" (19) thick dual density
insulation complying with NFPA 90 for fire and smoke resistivity and
UL 181 for erosion. Any cut edges of insulation shall be coated with
NFPA 90 approved sealant.
4.
Unit casing shall have four access panels, one on each side of
the unit and one on the bottom and top for easy access to motor and
blower assembly and for maintenance and replacement of parts
without disturbing duct connections. The unit shall be rated to
operate in left hand or right hand mode by turning the unit over.
Access panels shall be attached to casing with (screws, quick acting
latches, hinges). Casing leakage shall not exceed 2% of terminal
rated airflow at 0.5" w.g. (125 Pa) interior casing pressure. All high
side casing joints shall be sealed with approved sealant and high
side casing leakage shall not exceed 2% of terminal rated airflow at
3" w.g. (750 Pa).
5.
Units shall have round inlets for the primary air connections
and shall have a 6" (152) deep inlet duct collar for field connection.
The outlets shall be rectangular and suitable for flanged duct
connections. Casing shall have mounting area for hanging by sheet
metal straps from a concrete slab.
6.
The damper shall be of rectangular, multiple inclined opposed
blade construction and designed to operate on a 45 arc. Blades
shall be minimum 16 ga. (1.61) galvanized steel, single thickness
construction with heavy duty gasket glued to the blades. The blades
shall be screwed through the damper shaft to ensure that no
slippage occurs. Blade shafts shall pivot on corrosion free bearings.
Damper leakage shall not exceed 2% of the terminal rated cfm at 3"
w.g. (750 Pa) inlet static pressure.
7.
Entire terminal unit shall be factory assembled with (pneumatic,
electronic) controls. All components including all controls except the
room thermostat and (pneumatic piping, field wiring) shall be factory
installed and mounted with the unit.
8.
Provide a (pneumatic, analog electronic, digital electronic) flow
control device that will limit the maximum and minimum airflow to that
scheduled on the drawings. Airflow limits shall be factory set.
Thermostat signal shall reset the flow control device to adjust
primary airflow to match load requirements. Control of the terminal
unit shall be pressure independent.
9.
The terminal unit shall be capable of operation as described
herein with inlet static pressure of 0.05" w.g. (12 Pa) at full cooling
with no mixing of induced and primary air. (The sequence of
operation should be described here, if not part of the temperature
controls specifications). Mixing of the primary and secondary
airstreams shall be such that no more than 2.5 F (1.4C) variation
shall exist in the discharge airstream for each 20 F (11.1C) of
difference between the primary and secondary airstreams.
%
6OJU
4J[F
DGN
MT
1
2
3
4
350
600
800
950
165
283
378
448
51
58
62
62
49
56
59
58
47
53
59
52
48
50
53
46
49
51
54
36
6OJU
4J[F
DGN
MT
1
2
3
4
350
600
800
950
165
283
378
448
49
53
57
59
49
53
58
57
46
50
56
51
38
40
48
40
34
30
40
30
6OJU
4J[F
DGN
MT
1
2
3
4
350
600
800
950
165
283
378
448
54
61
69
61
55
61
68
62
52
60
68
60
48
56
64
56
43
53
63
53
7-20-11
0QUJPOT
45&"-5)5.
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQIT
1.
Furnish and install series flow (constant volume) fan powered
terminal units of the sizes and capacities as indicated on the
drawings. Units shall be pressure independent with (pneumatic,
analog electronic, digital electronic) controls. Units shall be
manufactured by /BJMPS*OEVTUSJFT*ODModel 4454UFBMUI5..
4.
Unit maximum radiated sound power levels at 1.0" w.g. (249
Pa) inlet pressure and 0.25" w.g. (63 Pa) discharge static pressure
shall not exceed the values in Tables 4 and 5 at the specified airflow.
No credit or reduction shall in any way be considered for room,
plenum, ceiling and/or similar item effects.
"JSGMPX
6OJU
4J[F
DGN
MT
1
2
3
4
350
600
800
950
165
283
378
448
51
56
60
57
43
49
54
49
38
44
49
42
34
37
41
34
34
36
39
33
"JSGMPX
6OJU
4J[F
DGN
MT
1
2
3
4
350
600
800
950
165
283
378
448
50
51
59
52
45
47
53
47
39
40
47
40
32
33
40
31
29
30
34
26
6OJU
4J[F
DGN
MT
1
2
3
4
350
600
800
950
165
283
378
448
54
61
69
61
55
61
68
62
52
60
68
60
48
56
64
56
7-20-11
43
53
63
53
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQIT
1.
Furnish and install series flow (constant volume) fan powered
terminal units with integral electric heat of the sizes and capacities as
indicated on the drawings. Units shall be pressure independent with
(pneumatic, analog electronic, digital electronic) controls. Units shall
be manufactured by /BJMPS*OEVTUSJFT*ODModel 4& or 4&45
4UFBMUI5. (select one).
12. An electric heater shall be factory mounted and pre-wired as an
integral package with the fan powered terminal unit. Heaters shall be
sized as shown on the drawings. The entire assembly including the
electric heater shall be ETL listed (cETL in Canada) for zero
clearance and so labeled and shall meet all requirements of the
latest National Electrical Code (Canadian Electrical Code, CSA
Standard C22.1). The unit with the heater mounted shall be listed
and rated to be turned over for either left or right hand configuration.
The unit shall have a single point electrical (and pneumatic)
connection. Heater casing and panel shall be a minimum of 20
gauge galvanized steel. Each heater shall be complete with primary
disc type automatic high limit, contactors as required, ground
terminal, fan relay for interlocking the heater and fan and high grade
nickel chrome alloy resistance wire. Element wires shall be
suspended in insulators designed to expose the entire face area of
the wire thereby eliminating hot spots. Each heater shall be supplied
with factory supplied and pre-wired branch circuit fusing as required
by NEC and UL. Circuiting and fusing shall also be in accordance
with the circuiting requirements as shown on the plans. Additional
accessories shall include (control transformer, circuit fusing,
disconnect switch, electric step controller, pneumatic electric
switches) for staging the heater.
(Additional performance requirements that you might want to include
can be found in the electric heater section). The electric heater shall
be located on the discharge side of the fan so as not to add heat to
the motor and shorten its expected lifetime.
Heater voltage and stages to be as follows:
0 to 5.0 kW ..................................... 277V/1 phase, 1 Step
5.1 kW and up ................................ 480V/3 phase, 1 Step
)PU8BUFS)FBUJOH$PJMT
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQIT
1.
Furnish and install series flow (constant volume) fan powered
terminal units with integral hot water coils of the sizes and capacities
as indicated on the drawings. Units shall be pressure independent
with (pneumatic, analog electronic, digital electronic) controls. Units
shall be manufactured by /BJMPS *OEVTUSJFT *OD Model 48 or
48454UFBMUI5. (select one).
12. A hot water coil shall be factory mounted as an integral
package with the fan powered terminal unit. Hot water coils shall be
sized as shown on the drawings. The entire assembly including the
hot water coil shall be ETL listed (cETL in Canada) for zero clearance
and so labeled and shall meet all requirements of the latest National
Electrical Code. The unit shall have a single point electrical (and
pneumatic) connection. Water coil casing and panels shall be a
minimum of 20 ga. (1.00) galvanized steel. Access panels shall be
supplied on the top and bottom of the unit for easy access to the coil
for inspection and cleaning. All copper, including the headers and
return bends, shall be encased to eliminate heat loss during heating
sequence and heat gain during cooling sequence. Coils shall be 1, 2
or 3 row as required and heating capacities shall be as shown on the
plans. Coils shall have aluminum plate fins spaced 10 per inch and
bonded to 1/2" (13) O.D. copper tubes. Copper connections shall be
sweat. All coils shall be tested at a minimum of 300 psi (2.1 MPa)
under water to produce a guaranteed working pressure of 250 psi
(1.7 MPa). Controls and valves for the hot water coils shall be field
mounted. Heating coils shall be located on the discharge side of the
fan so as not to add heat to the motor and shorten its expected lifetime.
%
&MFDUSJD)FBU
1"35o(&/&3"-
3&-"5&%%0$6.&/54
A. The requirements of the General Conditions, Supplementary
Conditions and the following specification sections apply to all Work
herein:
1.
2.
3.
4.
5.
Section
Section
Section
Section
Section
15
15
15
15
15
General
Scope of Work
Design Conditions
Electric Motors and Controllers
Access Doors and Color Coded Identification
in General Construction
6. Section 15 - - - Ductwork and Sheet Metal
7. Section 15 - - - Testing, Balancing and Adjusting
46.."3:
A. Furnish and install all air terminal units herein specified and as
indicated on the Drawings.
3&'&3&/$&45"/%"3%4
A. All air terminal units shall be designed, manufactured and tested
in accordance with the latest applicable industry standards
including the following:
1. ANSI/ASHRAE Standard 130-2008.
2. AHRI Standard 880-2011.
3. Underwriters Laboratories UL Standard 1995.
4. Underwriters Laboratories UL Standard 1996.
26"-*5:"4463"/$&
A. All equipment and material to be furnished and installed on this
project shall be UL or ETL listed, in accordance with the
requirements of the Authority having jurisdiction and suitable for its
intended use on this Project. Space limitations shall be reviewed to
ensure that the equipment will fit into the space allowed.
B. All equipment and material to be furnished and installed on this
project shall be run tested at the factory and results of that testing
shall be tabulated and provided to the engineer when the equipment
ships to the job site. See paragraph 2.03 G for specific requirements.
C. All equipment and material to be furnished and installed on this
project shall have been pre-tested in a mock up facility suitable to
the engineer. The test shall be as described in 2.03 D. The test
results shall be supplied with the equipment submittal.
46#.*55"-4
A. The following submittal data shall be furnished according to the
Conditions of the Construction Contract, Division 1 Specifications
and Section 15 - - - General and shall include but not be limited to:
1. Series Fan Powered Variable Air Volume Terminal Units,
complete with capacity data, test data, construction details,
physical dimensions, electrical characteristics, etc.
%
"$0645*$4
Section A of this acoustical specification describes sound power
levels as tested to AHRI 880 and ASHRAE 130. These are not the
selection criteria for this specification. The selection criteria will be
in section B where sound pressure readings are taken in an actual
mock up that will exhibit worst case performance for the purpose of
guaranteeing equipment performance when the building is
commissioned and turned over to the occupant. Section A is
important in that it provides a guideline for the minimum
performance that the terminal units will have to meet in order to
anticipate performance that will be acceptable under section B.
A. Sound Power Acoustical Performance:
1. Discharge Noise: Maximum permissible sound power levels
in octave bands of discharge sound through discharge ducts
from terminal units operated at an inlet pressure of XH
1B
and the maximum amount of air volume shown on the
Project Mechanical Drawings leaving the terminal unit and
entering the reverberant chamber shall be as follows:
0DUBWF#BOE
2
3
4
5
6
7
/$
67
64
67
66
67
67
/$
71
69
72
71
72
72
/$
64
57
53
50
50
53
/$
68
62
58
55
55
58
7-20-11
8"33"/5:
A. Manufacturer shall warrant equipment for one year from start up
or 18 months from shipment.
1"35130%6$54
6/"65)03*;&%."5&3*"-4
A. Materials and products required for the work of this section shall
not contain asbestos, polychlorinated biphenyls (PCB) or other
hazardous materials identified by the Engineer or Owner.
"$$&15"#-&."/6'"$563&34
A. These Specifications set forth the minimum requirements for
series fan powered VAV terminal units. If they comply with these
Specifications, series fan powered VAV terminal units manufactured
by one of the following manufacturers will be acceptable:
1. Nailor Industries.
7-20-11
%
%
a. Primary duct.
b. Secondary duct.
c. Single point electrical connection. See Drawings for
control box locations required for each terminal unit.
d. DDC controller control signals and wiring.
e. Room sensor connection.
B. The terminal unit shall be capable of operating throughout the full
cataloged primary airflow range with an inlet static pressure of 0.10"
w.g. (25) or less. All downstream static pressure requirements are to
be supplied by the terminal unit internal fan. See the schedules on
the Contract Documents for static pressure requirements.
C. The control sequence shall be as specified in Division 17 (DDC
by others).
D. Each size of each terminal unit to be used on this Project shall be
completely laboratory tested for air performance and acoustics. The
acceptability of the independent testing laboratory is subject to
review by the Owner, Project Acoustical Consultant and the
Engineer. The terminal unit manufacturer shall submit complete
details, brochures, instrumentation information, etc., for review. The
laboratory shall be capable of properly testing the largest terminal
unit on this Project. See paragraph 1.06 B for acoustic guidelines.
The air volume listed on the Drawings for the terminal units shall be
supplied for the test with the primary cold duct supplying 48F (9C)
air and the plenum bypass air at 80F (27C). At primary air damper
or valve positions as indicated hereinafter and with an inlet static
pressure of 0.20" w.g. (50 Pa), 0.50" w.g. (125 Pa) and 1.0" w.g. (249
Pa) the unit shall be capable of producing a mixed airstream of which
the temperature shall not vary more than 2.5F (1.4C) over the duct
48" (1219) downstream of box for each 30F (17C) temperature
difference between the temperatures of the entering warm and cold
air. The variation of temperature shall be proportionally less at smaller
temperature differences. There shall be at least fifteen temperature
readings made at the discharge outlet duct over the entire discharge
area as described in AHRI 880 with the air entering the unit in each
of the following proportions:
1. 25% cold air and 75% plenum air.
2. 50% cold air and 50% plenum air.
3. 75% cold air and 25% plenum air.
Operation of the flow control device shall be demonstrated to repeat
under all conditions of operation of the primary air damper or valve
and duct pressures as specified hereinbefore. If the VAV fan powered
terminal unit manufacturer has conducted the hereinbefore specified
air performance and air mixing tests and has demonstrated to the
Engineer and Owner compliance with the specified criteria the
previous testing will be accepted and will not need to be repeated.
Test results shall clearly state fan performance at test altitude and at
Project altitude. See Section 15 - - - Design Conditions.
E. After the manufacturer has submitted certified copies of the
laboratory air performance and acoustical performance test results to
the Engineer, the Engineer may witness the laboratory tests to verify
compliance with the Specifications. See Section 15 - - - General for
additional submittal and certification requirements.
F. All fan powered terminal units shall be identified on the bottom of
the unit (minimum 1/2" (13) high letters) and on the shipping carton,
with the floor and box number that identifies it along with the airflow
(cfm) settings. Every unit shall have a unique number combination
that matches numbers on the contractor's coordination drawings as
to its location and capacity and is coordinated with the DDC controller
and the Division 17 Building Control System submittal drawings.
G. The terminal unit manufacturer will verify the operation of each
fan powered terminal before shipment. Testing shall include at least
the following:
7-20-11
)FBU0QUJPOT
&MFDUSJD)FBU
*OTFSUUIFGPMMPXJOHQBSBHSBQIT
" 'BO1PXFSFE5FSNJOBM6OJU&MFDUSJD)FBUJOH$PJMT
a. Electric heating coils shall consist of open coils of high grade
nickel and chromium resistance wire or nichrome elements and
insulated with ceramic insulators in galvanized steel brackets,
supported in heavy gauge galvanized steel frames. Each unit
employing an electric heating coil shall be constructed and
installed in accordance with the requirements of the local
authorities and shall be UL or ETL listed specifically with the
heater as a component of the terminal unit device.
b. Coils shall have the capacities indicated in Contract
Documents. Coils rated up through 5 kW shall be single phase,
277 volt, 60 hertz and coils larger than 5 kW shall be three
phase, four wire, 480Y/277 volt, 60 hertz. Electric heating coils
up to and including 4 kW shall be single stage. Electric coils
above 4 kW shall be two stage.
c. Terminal bolts, nuts and washers shall be of corrosion
resistant materials. Coils shall be constructed so the installation
may be accomplished in accordance with the provisions of the
National Electrical Code, for zero clearance. Coils shall be given
a 2000 volt dielectric test at the factory.
d. Automatic reset thermal cutouts and an airflow switch shall be
furnished for heater protection. An airflow switch shall prove fan
airflow before the electric heater can be energized. Both devices
shall be serviceable through terminal box without removing
heating element from the terminal device. The entire heating
element rack shall be removable through an access panel with
a hinged door without disturbing the duct connection.
7-20-11
)PU8BUFS)FBU
*OTFSUUIFGPMMPXJOHQBSBHSBQIT
" 'BO1PXFSFE5FSNJOBM6OJU)PU8BUFS)FBUJOH$PJMT
a. Terminal unit hot water heating coils shall be installed
completely within the terminal unit casing and enclosing the coil
headers, return bends, "U" bends and the factory piping
assemblies. Provide an access door or panel on the bottom of
the terminal unit for servicing and cleaning the unit and to
completely expose coil headers and any valves supplied by the
terminal unit manufacturer.
b. The factory hydrostatic or air pressure test of the coil and
entire piping assembly shall be maintained for a minimum of one
minute after which each piping joint connection, etc. shall be
examined to verify there is no evidence of weeping or leakage.
If liquid was used for the pressure testing, it shall be completely
drained and blown out of all coils and the internal piping system
prior to shipment. If air pressure is used, the entire coil and
piping assembly shall be completely submerged under water.
Hot water heating coils shall be constructed with copper tubes
and either aluminum plate fins or spiral fins. Coils shall have a
maximum of 10 fins per inch. Fin thickness shall be 0.0045".
Supply and return connections shall be on the same hard drawn
end of the coil and shall be ASTM B88-72, H23, I-59 Type K
hard drawn seamless copper water pipe. Fins shall be bonded
to the tubes by means of mechanical expansion of the tubes or
by spiral winding under tension.
c. Coils shall have galvanized steel casings on all sides no
lighter than 20 ga. (1.00).
%
e. Heating coils shall have a terminal box and cover, with quiet
type built-in mercury step controlled contactors for each circuit,
branch circuit fusing for each branch circuit if heater is in excess
of 48 amps per the NEC and a static pressure or air flow safety
interlock switch for installation in the heater control enclosure.
Contactors mounted in terminal units shall be quiet mercury
step type for terminal units, which are located above the ceiling
in tenant occupied spaces with an acoustical requirement of
NC40 or less. Contactors mounted in fan powered terminal units
located in other areas may be quiet type magnetic or mercury
step contactors. Provide a separate 120 or 24 volt control power
transformer with an integral or separately mounted primary
and/or secondary overcurrent protection device in accordance
with NEC requirements. Provide a door interlocking disconnect
switch for each unit.
f. All wiring of built-in devices shall be brought to clearly marked
terminal strips. A complete wiring diagram shall be permanently
attached to the heating coil panel cover or to the bottom of the
terminal unit.
g. Electric heating coils shall be designed for operation with the
DDC controller and control system as specified in the Division
17 specification.
h. Heating coils and the associated control panels shall be
constructed to mount on the discharge end of the terminal unit.
The heating coil control panel NEC required working clearances
shall be parallel to the terminal unit discharge duct.
i. Shop Drawings shall be submitted for review as specified in
Section 15 - - - General. These Shop Drawings shall indicate
specifically the exact construction, materials, internal wiring,
NEC working clearances, etc., of the terminal units and electric
heating coils to be furnished under these Specifications.
%
.PEFM4VCTUJUVUJPO0QUJPOT
.PEFM 4FSJFT 4 'BO 1PXFSFE 5FSNJOBM
6OJUT
4VCTUJUVUF UIF GPMMPXJOH QBSBHSBQI %FMFUFT 4UFBMUI PQUJPO
BOETPMJENFUBMMJOFS
"
The terminal units shall not exceed the depth indicated on the
drawings. Mounting connections for hanging the unit by sheet metal
straps shall be clearly identified on the housing. All components,
including all controls and allowed. The unit shall be complete and
suitable to accept the following field connections.
14$.PUPS
*OMJFVPG&1*$5.&$.
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQI
"
Fan motor assembly shall be forward curved centrifugal fan with a
direct drive motor. Motors shall be specifically designed for use with
a single phase, (120, 208 or 277) volt 60 Hertz electric input, Motor
shall have built-in overload protection, bearings capable of low rpm
oiling and permanently oiled bearings. Motor shall be direct couple to
the blower. Provide isolation between fan motor assembly and unit
casing in at least 4 locations to eliminate any vibration from the fan
to the terminal unit casing. Provide anti-back rotation system or
provide a motor that is designed to overcome reverse rotation and
not affect life expectancy. An electronic motor speed controller sized
and designed for the specific blower motor combination shall be
provided to allow infinitely fan speed from the minimum voltage stop
to the line voltage signal to the motor. A minimum voltage stop shall
be employed to ensure that the fan cannot run in a stall mode.
7-20-11
7-20-11
%
PARALLEL FLOW
VARIABLE AIR VOLUME
35N SERIES
Models:
35N
No Heat
35NE
Electric Heat
35NW
The 35N Series provides many standard design features and excellent sound performance when compared with other designs.
The 35N offers a compact and economical design that provides excellent performance in the most demanding variable air
volume/intermittent fan applications. The fan is mounted at ninety degrees to the primary airflow to provide optimum mixing.
FEATURES:
20 ga. (1.00) galvanized steel
construction.
Round laminated 2 x 20 ga. (1.00)
butterfly primary air damper with
peripheral gasket. 90 rotation, CW to
close. 1/2" (13) dia. plated steel drive
shaft. An indicator mark on the end of
the shaft shows damper-position.
Damper leakage is less than 2% of
nominal flow at 3" w.g. (750 Pa).
Round minimum 6" (152) deep inlet
collars for field duct connection.
Pressure independent primary
airflow control (also available in
pressure dependent configuration).
Multi-point averaging 'Diamond
Flow ' sensor (pressure independent
control only).
Access panels on underside of
terminal for ease of maintenance and
service.
Energy efficient PSC fan motor with
thermal overload protection.
Motor blower assembly mounted on
special 16 ga. (1.6) angles and
isolated from casing with rubber isolators.
Adjustable solid state fan speed
controller with minimum voltage stop.
Gasketed
backdraft
damper
mounted on fan discharge prevents
primary air from escaping through the
fan section into the ceiling plenum.
D100
Options:
Induced air filter, 1" (25) thick,
disposable type.
Primary air valve enclosure for field
mounted controls.
Toggle disconnect switch units with
electric heat, when disconnect is an
electric heat option and includes fan).
Various 'IAQ' linings are available.
Fan airflow switch for night shutdown.
Night setback fan/heat cycle
(pneumatic and analog).
Fan unit fusing.
Hanger brackets.
'Q' option induced air attenuator.
Controls:
Pneumatic and analog electronic
controls. Factory supplied, mounted
and calibrated.
Digital controls. Factory mounting
and wiring of DDC controls supplied
by BAS Controls Contractor.
7-20-11
H
1 1/2" (38)
IH
IW
1 1/2" (38)
OPTIONAL
INDUCED AIR
ATTENUATOR
INDUCED AIR
INLET
IH
+
2" (51)
OPTIONAL
INDUCED
AIR FILTER
FAN
FAN
ROUND INLET
WITH MULTIPOINT FLOW
SENSOR
AIRFLOW
PRIMARY
AIR
5 3/4"
(146)
CONTROLS
ENCLOSURE
C
L
17" (432)
DW
6" (152).
8" (203) FOR
14" (356) &
16" (406) INLETS
RECTANGLAR
DISCHARGE
FOR FLANGED
DUCT
CONNECTION
CONTROLS
ENCLOSURE
CONTROLS
ENCLOSURE
1" (25)
14" (356)
Right hand unit, top view illustrated. Controls mounted as standard on RH side as shown. Left hand units / terminals
ordered with LH controls (optional), are built as mirror image. Inlet, discharge and control enclosure are opposite of the
drawing.
Dimensional Data
Unit
Size
Inlet
Size
Induced Air
Inlet
IW x IH
Outlet
Discharge
DW x DH
Filter
Size
6, 8, 10, 12
(152, 203, 254, 305)
34 34
(883)
14
(356)
27 916
(700)
1
(25)
24 916 x 10 34
(624 x 273)
16 x 12
(406 x 305)
26 x 13
(660 x 330)
8, 10, 12, 14
(203, 254, 305, 356)
38 14
(972)
18
(457)
28 916
(725)
1 12
(38)
25 916 x 14 34
(649 x 375)
16 x 15
(406 x 381)
27 x 17
(686 x 432)
10, 12, 14
(254, 305, 356)
45 58
(1159)
18
(457)
34 12
(876)
1 12
(38)
31 12 x 14 34
(800 x 375)
24 x 15
(610 x 381)
33 x 17
(838 x 432)
12, 14, 16
(305, 356, 406)
50 34
(1289
20
(508)
36
(914)
1 14
(32)
33 x 16 34
(838 x 426)
28 x 17 12
(711 x 445)
35 x 19
(889 x 483)
7-25-11
Inlet Size
Dim. A
6
8
10
12
14
16
5 (127)
6 (152)
7 (178)
8 (203)
9 (229)
10 (254)
D101
Dia =
Nom. 1/8" (3)
DH
FAN
AIRFLOW
HW
COIL
CONTROLS
ENCLOSURE
7"
(178)
1" (25)
Unit
Size
16 x 12 12 (406 x 318)
34 34 (883)
14 (356)
27 916 (700)
16 x 15 (406 x 381)
38 14 (972)
18 (457)
28 916 (725)
1 12 (38)
24 x 15 (610 x 381)
45 8 (1159)
18 (457)
34 2 (876)
1 12 (38)
28 x 17 12 (737 x 445)
50 34 (1289)
20 (508)
36 (914)
1 14 (32)
E
4 (19)
Model 35NE
Standard Features:
Coil installed on unit discharge.
Insulated coil element wrapper.
Automatic reset high limit cutouts (one per element).
Single
point
electrical
connection for entire terminal
unit (except 600V / 3 p h ., which
comes with 120V/ 1 ph. motor).
Positive pressure airflow switch.
Flanged outlet duct connection.
Terminal unit with coil is ETL
Listed as an assembly.
Controls mounted as standard
on RH side as shown. Terminals
ordered with LH controls
(optional) are built as mirror
image.
Standard Supply Voltage (60 Hz):
120, 208, 240 & 277V single phase.
208, 480 and 600V (4 wire wye) three
phase.
Options:
D102
M
FAN
1"
(25)
G
W
ELECTRIC
COIL
LOW VOLTAGE
ENCLOSURE
HIGH VOLTAGE
ENCLOSURE
11"
(280)
14"
(356)
AIRFLOW
F
1"
(25)
6 5/8"
(168)
Unit
Size
17 x 12 (432 x 305)
17 x 16 (432 x 406)
25 x 16 (635 x 406)
29 x 18 (737 x 457)
7-25-11
8
2
10
12
10
3
12
14
10
12
14
12
14
16
Min. Inlet
Ps
cfm l/s
500 236
400 189
300 142
200 94
100 47
875 413
700 330
525 248
350 165
175 83
1375 649
1100 520
825 389
550 260
275 130
2000 944
1600 755
1200 566
800 378
400 189
875 413
700 330
525 248
350 165
175 83
1375 649
1100 519
825 389
550 260
275 130
2000 944
1600 755
1200 566
800 378
400 189
2625 1239
2100 991
1575 743
1050 496
525 248
1375 649
1100 519
825 389
550 260
275 130
2000 944
1600 755
1200 566
800 378
400 189
2625 1239
2100 991
1575 743
1050 495
525 248
2000 944
1600 755
1200 566
800 378
400 189
2625 1239
2100 991
1575 743
1050 495
525 248
3425 1616
2750 1298
2050 967
1375 649
700 330
"w.g. Ps
0.49 122
0.32 80
0.18 45
0.08 20
0.02 5
0.3 75
0.2 50
0.11 27
0.05 12
0.01 2
0.4 100
0.24 60
0.15 37
0.06 15
0.02 5
0.45 112
0.3 75
0.18 45
0.08 20
0.02 5
0.24 60
0.15 37
0.08 20
0.04 10
0.01 2
0.25 62
0.16 40
0.09 22
0.04 10
0.01 2
0.34 85
0.22 55
0.12 30
0.05 12
0.01 2
0.39 97
0.25 62
0.14 35
0.06 15
0.02 5
0.26 65
0.17 42
0.11 27
0.04 10
0.01 2
0.24 60
0.15 37
0.08 20
0.03 7
0.01 2
0.3 75
0.19 47
0.1 25
0.04 10
0.01 2
0.21 52
0.13 32
0.07 17
0.04 10
0.01 2
0.22 55
0.14 35
0.07 17
0.03 7
0.01 2
0.25 62
0.16 40
0.08 20
0.04 10
0.01 2
Min.
Ps
21
32
27
24
-
Airflow
%
8
2
10
12
10
3
12
14
10
12
14
12
14
16
%
500
400
300
200
100
875
700
525
350
175
1375
1100
825
550
275
2000
1600
1200
800
400
875
700
525
350
175
1375
1100
825
550
275
2000
1600
1200
800
400
2625
2100
1575
1050
525
1375
1100
825
550
275
2000
1600
1200
800
400
2625
2100
1575
1050
525
2000
1600
1200
800
400
2625
2100
1575
1050
525
3425
2750
2050
1375
700
236
189
142
94
47
413
330
248
165
83
649
519
389
260
130
944
755
566
378
189
413
330
248
165
83
649
519
389
260
130
944
755
566
378
189
1239
991
743
495
248
649
519
389
260
130
944
755
566
378
189
1239
991
743
495
248
944
755
566
378
189
1239
991
743
495
248
1616
1298
967
649
330
Min. inlet
Ps
" w.g. Pa
0.49 122
0.32 80
0.18 45
0.08 20
0.02 5
0.30 75
0.20 50
0.11 27
0.05 12
0.01 2
0.40 99
0.24 60
0.15 37
0.06 15
0.02 5
0.45 112
0.30 75
0.18 45
0.08 20
0.02 5
0.24 60
0.15 37
0.08 20
0.04 10
0.01 2
0.25 62
0.16 40
0.09 22
0.04 10
0.01 2
0.34 85
0.22 55
0.12 30
0.05 12
0.01 2
0.39 97
0.25 62
0.14 35
0.06 15
0.02 5
0.26 65
0.17 42
0.11 27
0.04 10
0.01 2
0.24 60
0.15 37
0.08 20
0.03 7
0.01 2
0.30 75
0.19 47
0.10 25
0.04 10
0.01 2
0.21 52
0.13 32
0.07 17
0.04 10
0.01 2
0.22 55
0.14 35
0.07 17
0.03 7
0.01 2
0.25 62
0.16 40
0.08 20
0.04 10
0.01 2
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure shown
Minimum Ps
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps 2.0" wg (500Pa)Ps
2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
59 57 52 47 44 46 59 58 53 48 45 47 73 66 60 54 50 53 77 71 64 57 53 57 79 75 67 58 55 60
54 52 46 42 38 38 62 57 51 46 43 43 71 64 58 51 49 51 76 71 63 55 53 56 77 73 66 57 54 58
52 46 40 36 32 30 62 56 49 44 41 41 70 63 57 49 48 49 72 68 61 53 51 54 74 72 64 56 54 58
50 38 31 27 - - 57 52 44 39 37 36 65 60 54 47 46 46 66 64 59 51 50 52 64 66 61 55 52 56
- - - - - - 55 52 45 40 38 36 55 54 52 46 44 44 54 54 55 50 46 47 54 57 58 53 49 51
56 54 50 48 45 45 62 60 54 52 49 49 71 67 61 57 53 55 77 71 65 59 56 60 79 76 69 57 57 61
55 51 45 44 40 38 65 60 53 50 48 48 70 66 59 54 52 54 74 72 65 56 56 59 75 73 67 56 57 60
- 44 38 38 32 29 61 57 49 46 45 43 67 64 57 50 51 52 71 69 64 54 55 57 71 72 66 54 56 58
- 38 31 29 20 - 58 54 47 44 43 41 62 62 55 48 50 50 64 65 60 52 54 55 64 67 64 54 54 55
- - - - - - 55 52 46 43 42 39 55 59 54 47 48 47 56 57 60 50 53 51 58 59 64 60 59 64
60 58 55 50 50 49 62 61 57 51 51 51 69 67 64 55 55 57 75 73 69 59 58 62 76 76 71 59 58 63
56 52 50 45 44 41 61 59 56 49 49 48 68 66 62 53 54 55 72 71 67 57 57 61 73 73 67 57 58 62
51 46 43 39 36 32 60 57 53 46 47 45 65 64 59 50 52 53 68 68 65 54 56 42 68 71 68 54 56 59
- 38 34 29 23 - 56 53 48 43 43 40 60 62 57 48 51 51 63 63 62 52 54 57 62 64 64 53 53 56
- - - - - - 51 51 47 42 42 38 53 56 55 46 47 47 55 58 61 50 51 52 55 60 63 62 61 65
62 59 55 52 50 51 62 59 55 52 50 51 68 67 63 57 56 58 74 73 67 59 59 62 76 76 71 60 60 64
57 54 49 46 44 43 61 59 55 50 50 49 69 67 62 54 55 57 72 72 66 58 58 61 73 74 69 58 58 63
51 45 42 38 35 30 61 57 53 47 46 46 67 66 60 52 54 55 68 69 64 55 57 60 69 71 67 56 56 59
50 39 34 31 26 - 57 53 49 44 45 42 61 61 56 49 51 51 63 66 62 53 55 57 66 66 64 54 53 55
49 35 29 23 - - 52 50 46 42 42 38 54 57 56 48 48 48 56 59 59 51 51 51 57 60 62 59 58 63
59 55 50 48 46 46 64 59 53 52 49 50 72 68 61 57 55 57 76 72 64 59 57 61 75 74 66 59 58 62
55 50 44 44 41 39 67 58 52 51 49 49 70 66 58 54 53 55 73 71 62 56 56 59 75 72 65 56 57 61
- 41 36 35 31 27 62 57 49 46 46 45 66 64 56 50 52 53 68 67 60 53 54 57 68 70 63 54 56 58
- - 28 25 - - 57 52 44 42 43 41 62 61 53 47 50 51 64 65 58 51 53 56 64 64 61 53 52 53
- - - - - - 52 48 44 40 41 38 54 54 52 46 47 47 55 56 56 49 50 51 55 57 59 59 59 63
58 55 53 48 47 46 62 61 58 51 51 50 68 67 61 54 55 56 71 71 65 57 58 61 72 75 68 57 59 62
54 50 48 42 41 38 61 58 54 48 49 47 67 67 59 52 54 55 69 70 63 55 57 59 71 72 67 55 57 60
50 43 40 34 31 24 60 55 50 44 46 44 64 63 56 49 52 52 67 68 61 53 55 57 67 71 65 54 56 58
- 36 31 26 - - 55 51 45 41 43 40 62 62 55 48 51 52 62 66 60 51 54 55 63 66 63 53 54 55
- - - - - - 52 50 45 40 41 39 54 55 53 46 49 48 55 56 56 50 51 51 57 60 58 60 61 66
62 59 58 51 50 50 64 62 59 52 52 53 70 69 64 55 57 59 73 72 67 58 59 63 75 76 70 59 60 65
57 53 52 45 44 41 62 60 56 49 51 50 68 66 61 53 56 57 71 72 65 56 59 62 72 74 69 57 59 64
50 46 43 37 34 28 59 56 52 45 48 46 66 65 59 51 55 56 67 69 63 54 58 60 68 70 66 54 57 61
- 36 31 24 - - 56 51 47 42 44 41 60 61 57 49 54 55 61 63 59 51 56 58 63 63 61 53 55 57
- 35 29 20 - - 49 49 46 41 45 42 52 55 53 47 50 51 56 58 57 50 54 56 54 58 57 62 62 66
66 64 60 55 52 50 67 64 61 55 54 53 72 69 64 58 58 60 74 73 66 60 60 63 75 76 70 59 61 65
62 59 54 49 47 43 64 61 56 51 52 50 69 67 61 55 57 58 70 71 64 57 59 62 73 73 68 57 60 63
55 52 45 40 36 30 60 56 51 47 49 46 66 64 58 52 55 56 68 68 62 55 58 60 69 70 65 56 58 61
48 41 34 29 22 - 56 52 47 44 47 44 60 60 56 49 53 54 62 64 60 52 56 58 64 65 63 54 56 59
- - 24 - - - 49 49 45 42 44 42 54 57 53 48 51 52 55 59 57 51 53 56 58 62 61 59 60 64
59 55 55 50 49 49 65 61 59 52 52 53 71 69 64 56 56 59 73 72 66 57 58 61 72 75 70 57 59 63
53 49 48 43 41 39 62 58 55 48 49 49 69 66 61 52 54 56 71 70 65 56 57 61 72 72 68 56 58 62
50 43 42 36 34 29 61 56 52 45 47 46 66 64 58 50 53 54 67 68 62 53 56 59 69 70 66 54 57 61
- 37 32 27 - - 58 53 48 43 45 43 63 62 57 49 52 53 63 65 61 51 54 57 66 68 65 53 54 57
- - - - - - 51 49 46 40 41 40 53 54 53 45 48 48 55 58 57 50 52 54 56 60 60 61 61 66
59 56 55 49 49 48 63 61 58 52 53 53 70 69 65 56 58 60 71 73 67 59 60 63 72 75 70 59 61 65
55 51 49 44 43 40 62 59 56 50 51 50 68 68 62 54 56 58 70 72 66 57 59 63 71 72 68 58 60 54
49 44 41 37 34 29 59 56 52 47 49 46 65 66 61 52 55 57 66 69 64 55 57 60 68 71 68 56 58 62
- 36 32 28 - - 55 53 49 44 46 44 61 63 59 50 53 54 62 65 63 53 56 59 64 66 64 55 56 59
- - 29 22 - - 51 52 48 43 41 43 55 57 55 48 51 51 57 59 59 52 54 56 57 61 61 61 61 65
63 59 56 51 49 50 65 61 58 53 52 52 71 67 62 56 56 59 71 71 66 58 59 63 73 73 69 59 59 63
58 52 50 45 43 41 63 58 55 49 50 51 68 65 58 54 55 57 69 68 64 57 58 62 71 69 66 58 58 62
51 45 42 37 34 30 58 52 49 45 46 44 64 61 58 51 53 55 65 64 62 55 56 59 68 66 64 56 56 60
- 36 31 27 20 - 53 51 48 43 45 44 60 57 55 49 51 53 61 60 58 52 54 57 63 62 61 53 54 58
- - 23 - - - 48 46 44 40 41 40 53 55 53 48 50 52 55 56 56 51 52 56 56 58 58 60 61 64
62 56 54 49 49 47 64 61 59 52 53 52 69 67 62 55 56 57 71 71 66 58 59 61 72 73 69 58 60 63
56 50 49 43 43 39 62 59 56 49 51 50 66 65 60 53 55 56 69 70 65 56 59 61 70 70 67 56 58 61
49 44 41 36 34 30 60 55 51 46 48 45 63 63 58 51 54 55 65 66 62 54 57 59 66 65 64 55 57 60
- 35 31 28 22 - 55 51 48 44 45 42 57 58 56 49 52 44 60 60 59 52 55 57 62 62 62 54 55 58
- 33 28 23 - - 48 47 46 41 43 40 51 52 53 47 49 19 54 56 57 51 53 54 55 57 59 60 60 64
64 57 55 50 49 48 66 60 57 53 52 52 69 67 62 56 56 58 70 70 65 58 58 61 73 72 67 59 59 62
59 51 49 44 43 39 63 56 53 48 49 48 66 64 60 54 55 56 68 67 63 56 58 60 69 68 65 57 58 61
52 44 41 36 33 29 58 53 49 45 47 44 62 60 56 51 53 53 63 63 60 54 56 58 66 64 62 56 56 59
- 35 29 25 - - 53 50 46 43 44 41 55 55 53 48 51 51 59 57 57 52 54 56 61 60 59 55 54 57
- - - - - - 47 44 44 40 40 38 51 50 50 47 48 49 54 54 54 52 52 54 55 56 57 64 63 67
72 67 63 60 57 55 73 67 64 60 58 57 73 69 65 61 60 60 75 71 67 62 62 64 76 74 70 61 62 65
67 61 57 53 51 47 67 62 58 54 54 52 70 65 61 57 58 58 72 70 65 60 60 63 72 70 67 59 60 64
60 54 48 44 42 37 62 58 54 50 50 48 65 62 58 53 56 56 66 65 62 57 59 61 69 66 64 58 59 62
52 42 36 33 30 27 54 49 46 44 46 41 60 57 55 51 54 54 61 61 59 55 57 59 63 63 62 57 57 62
- - 27 23 - - 50 48 46 44 45 42 52 53 52 49 52 52 56 57 57 54 55 58 56 59 59 57 57 62
For performance table notes, see page D110; 3&% highlighted numbers indicate embedded AHRI certification points. 6-24-13
8
2
10
12
3
12
14
10
12
14
12
14
16
cfm l/s
500 236
400 189
300 142
200 94
100 47
875 413
700 330
525 248
350 165
175 83
1375 649
1100 520
825 389
550 260
275 130
2000 944
1600 755
1200 566
800 378
400 189
875 - 413
700 330
525 248
350 165
175 83
1375 649
1100 519
825 389
550 260
275 130
2000 944
1600 755
1200 566
800 378
400 189
2625 1239
2100 991
1575 743
1050 496
525 248
1375 649
1100 519
825 389
550 260
275 130
2000 944
1600 755
1200 566
800 378
400 189
2625 1239
2100 991
1575 743
1050 495
525 248
2000 944
1600 755
1200 566
800 378
400 189
2625 1239
2100 991
1575 743
1050 495
525 248
3425 1616
2750 1298
2050 967
1375 649
700 330
Min. Inlet
Ps
"w.g. Ps
0.49 122
0.32 80
0.18 45
0.08 20
0.02 5
0.3 75
0.2 50
0.11 27
0.05 12
0.01 2
0.4 100
0.24 60
0.15 37
0.06 15
0.02 5
0.45 112
0.3 75
0.18 45
0.08 20
0.02 5
0.24 60
0.15 37
0.08 20
0.04 10
0.01 2
0.25 62
0.16 40
0.09 22
0.04 10
0.01 2
0.34 85
0.22 55
0.12 30
0.05 12
0.01 2
0.39 97
0.25 62
0.14 35
0.06 15
0.02 5
0.26 65
0.17 42
0.11 27
0.04 10
0.01 2
0.24 60
0.15 37
0.08 20
0.03 7
0.01 2
0.3 75
0.19 47
0.1 25
0.04 10
0.01 2
0.21 52
0.13 32
0.07 17
0.04 10
0.01 2
0.22 55
0.14 35
0.07 17
0.03 7
0.01 2
0.25 62
0.16 40
0.08 20
0.04 10
0.01 2
2
54
48
44
50
49
56
51
46
62
59
52
44
42
49
48
55
49
45
53
48
42
55
51
46
49
45
45
53
48
44
55
54
45
54
50
49
44
54
51
45
62
56
51
44
45
Mininum Ps
3 4 5 6
49 44 39 36
41 37 33 30
35 31 28 23
- - - - - - 46 41 36 32
43 37 32 29
36 31 27 35 28 24 - - - 51 47 39 37
46 42 34 32
39 34 28 26
34 26 - - - - 59 57 49 42
55 52 43 35
48 45 35 27
38 33 22 34 26 - 49 46 42 40
43 41 37 34
35 32 27 34 23 - - - - 47 44 38 35
48 48 42 41
37 34 29 25
34 25 - - - - 49 45 40 38
44 41 35 32
37 33 27 21
- 23 - - - - 51 48 42 38
46 43 36 32
40 35 28 22
- 22 - - - - 43 42 39 38
40 39 36 34
36 33 30 26
33 28 21 - - - 49 46 40 37
43 40 34 31
37 33 28 22
- 27 - - 21 - 49 46 40 38
51 50 45 43
39 33 27 23
38 24 - - - - 47 44 39 38
42 39 34 32
38 34 29 26
36 29 - - 28 - 49 48 43 40
44 43 36 32
39 35 28 25
33 29 24 - 29 - 53 49 44 41
49 45 38 34
41 37 30 26
35 29 - 34 28 - -
7
33
26
29
24
36
30
21
38
30
38
31
31
38
34
27
34
27
34
29
34
27
36
41
34
28
39
30
38
31
-
Primary Air Only Sound Power Octave Bands @ Inlet pressure shown
0.5" w.g. (125 Pa) Ps 1.0" w.g. (250 Pa) Ps 1.5" w.g. (375 Pa) Ps
2 3 4 5 6 7
2 3 4 5 6 7
2 3 4 5 6 7
60 52 49 39 37 35 66 58 53 43 40 39 69 62 57 45 42 42
58 49 45 36 34 31 64 55 51 39 38 36 68 60 55 43 41 40
55 45 41 32 30 26 61 52 49 36 35 33 64 58 54 41 39 38
52 44 40 30 30 25 57 50 47 34 34 31 56 53 52 38 37 35
46 39 36 38 26 - 47 45 46 33 32 29 46 47 50 37 35 33
55 50 45 40 35 32 65 57 52 42 39 38 67 61 56 45 43 42
54 49 43 36 33 29 62 57 51 39 38 36 65 61 57 42 41 41
53 48 41 33 32 29 58 54 49 36 37 35 61 58 55 39 39 39
51 45 39 30 30 26 53 51 46 33 35 33 55 55 52 37 38 37
45 41 36 28 27 22 46 50 48 33 33 31 45 49 52 36 36 33
57 53 50 41 39 38 64 58 54 43 42 43 67 63 58 46 44 47
54 50 46 36 35 33 61 56 52 40 40 40 64 62 56 43 43 45
53 47 43 33 33 32 59 55 51 37 38 39 59 59 55 41 41 44
51 45 39 30 31 29 53 53 49 35 37 37 54 53 52 39 40 42
45 42 38 28 29 25 47 48 46 34 35 35 47 49 50 37 38 39
62 59 57 49 42 38 68 63 60 49 43 408 69 64 60 49 45 44
60 57 54 43 36 31 64 58 53 43 41 38 65 61 56 46 44 43
55 49 44 34 32 26 59 54 50 40 39 35 60 58 54 43 43 42
50 44 38 32 32 26 52 49 46 36 38 35 54 50 48 38 40 41
41 37 34 28 30 21 46 44 44 34 37 34 47 46 47 37 39 41
55 51 47 43 40 38 63 60 55 47 45 45 65 62 57 48 46 47
53 49 46 41 38 36 62 58 52 45 43 42 65 62 57 48 46 47
50 46 41 35 33 30 56 53 48 39 39 38 57 56 52 42 41 42
47 42 36 31 29 27 52 50 45 37 36 36 52 53 49 40 39 40
45 40 36 29 28 25 46 46 45 35 33 33 46 47 46 36 36 36
55 50 48 41 38 36 64 57 53 44 42 42 66 61 56 47 44 45
55 49 46 39 36 34 61 56 51 42 40 40 64 61 55 45 43 45
53 48 42 35 34 31 58 54 49 39 39 38 60 59 54 42 42 43
49 44 36 31 31 29 54 53 47 37 37 37 56 56 52 41 41 42
45 41 37 29 30 28 46 44 42 34 35 34 46 46 45 37 38 38
54 53 49 43 40 38 60 58 54 45 44 44 64 62 57 48 48 48
51 49 44 38 36 32 59 56 51 43 44 42 62 62 56 47 47 48
52 48 43 37 37 33 56 56 49 41 42 41 58 59 54 44 45 45
48 44 37 33 33 28 51 50 47 38 40 38 53 53 50 41 43 43
43 40 35 30 31 27 45 45 43 36 38 37 47 47 46 40 41 42
55 52 49 44 39 36 63 59 55 46 44 44 64 62 57 48 47 48
54 50 46 38 37 33 60 58 52 43 43 43 62 61 56 46 46 47
52 46 42 35 35 31 56 53 48 40 41 40 60 58 54 44 45 46
49 43 39 33 34 30 52 51 47 39 40 40 55 54 52 43 44 45
- 40 38 32 34 34 47 46 44 37 39 40 50 50 49 41 43 44
55 52 48 42 41 40 62 57 51 44 43 43 65 62 55 46 45 48
59 54 50 43 39 37 60 57 50 42 42 42 61 61 54 44 44 47
51 47 39 33 33 31 52 50 44 36 37 37 58 57 51 41 42 44
54 52 48 43 45 43 59 61 57 49 52 53 56 56 50 40 41 43
- 40 35 28 29 28 - 43 42 33 35 35 - 44 45 37 38 39
56 53 49 43 40 38 61 59 54 46 44 44 63 62 57 48 46 47
52 48 44 37 36 33 60 58 51 43 43 42 62 62 56 46 46 47
53 48 43 36 35 32 57 55 48 40 41 39 58 58 53 43 44 44
48 44 37 32 32 28 53 54 49 39 40 39 55 53 50 41 42 42
44 42 35 30 31 28 52 47 43 35 37 35 51 48 47 39 40 39
57 52 48 42 39 38 62 58 52 45 44 44 63 61 55 47 46 47
55 49 45 38 37 35 59 56 50 42 41 41 61 58 53 45 45 46
52 47 41 34 35 33 56 53 48 40 41 42 58 55 51 43 43 45
49 44 38 32 33 31 51 48 44 37 39 39 54 52 48 41 43 44
- 40 34 29 31 29 47 46 42 36 38 39 48 48 45 39 41 43
58 51 46 41 40 37 62 59 51 44 44 43 64 62 55 47 46 46
56 49 43 37 37 34 62 58 51 43 43 41 62 60 53 44 45 45
57 50 46 38 34 31 57 53 46 39 41 39 59 55 50 42 43 43
49 44 36 32 33 30 53 48 44 37 39 38 55 49 47 40 42 41
44 39 34 29 30 28 48 43 41 35 36 35 49 45 44 38 40 39
56 51 48 43 41 39 61 58 53 46 45 46 62 60 55 48 47 48
54 48 44 39 37 35 60 56 52 44 43 44 61 58 54 46 46 48
52 46 41 35 35 34 55 52 46 39 41 41 56 54 49 42 44 46
48 42 37 32 33 31 52 48 45 39 41 42 54 49 47 41 43 45
44 38 36 31 33 32 45 42 40 35 37 38 49 45 44 39 41 42
63 54 50 45 42 39 66 59 54 48 47 46 66 61 56 49 49 49
60 52 47 41 40 36 62 55 50 43 44 43 63 59 54 47 47 48
55 47 42 36 37 33 58 53 49 41 43 42 60 55 52 44 46 46
56 50 48 41 37 32 53 49 46 39 42 41 56 51 48 42 44 45
47 39 35 31 33 29 48 44 41 37 40 40 50 48 45 41 43 46
%
10
Airflow
1850
1600
1400
ALL
1200
1000
800
873
755
661
566
472
378
0.25
0.25
0.25
0.25
0.25
0.25
62
62
62
62
62
62
42
40
38
35
32
29
2100
1900
ALL 1700
1500
1200
991
897
802
708
566
0.25
0.25
0.25
0.25
0.25
62
62
62
62
62
28
25
24
-
42
40
38
37
35
1FSGPSNBODF%BUBt4PVOE1PXFS-FWFMT
.PEFM4FSJFT/t1BSBMMFM'MPXt'BO0OMZt)FBUJOH$ZDMF
7"7'JCFSHMBTT
Discharge
Unit Inlet Airflow Discharge
Ps
Size Size cfm
l/s "w.g. Pa Sound Power Octave Bands
2 3 4 5 6 7
750 354 0.25 62 67 61 61 57 54 53
600 283 0.25 62 65 58 58 58 53 48
2 ALL 500 236 0.25 62 61 49 52 46 43 40
400 189 0.25 62 59 46 48 42 38 33
300 142 0.25 62 54 41 41 35 31 26
1000 472 0.25 62 68 63 63 60 55 53
850 401 0.25 62 66 60 61 57 53 50
3 ALL
700 330 0.25 62 61 55 56 51 46 42
550 260 0.25 62 60 53 54 49 44 39
1850 873 0.25 62 68 65 65 65 62 62
1600 755 0.25 62 66 63 63 63 60 59
1400 661 0.25 62 64 60 61 60 56 55
5 ALL
1200 566 0.25 62 61 58 58 56 53 51
1000 472 0.25 62 58 53 54 52 48 45
800 378 0.25 62 58 53 54 52 48 45
2100 991 0.25 62 71 70 68 68 64 64
1900 897 0.25 62 69 68 66 66 62 61
6 ALL 1700 802 0.25 62 67 67 65 64 60 60
1500 708 0.25 62 64 63 62 61 57 55
1200 566 0.25 62 62 59 60 57 54 51
Radiated
Sound Power Octave Bands
2 3 4 5 6 7
73 67 65 61 56 56
69 63 61 57 51 50
66 61 58 54 47 45
63 58 55 49 42 39
61 54 52 46 38 35
65 62 62 60 57 54
64 61 61 58 54 52
61 58 58 54 50 46
58 55 55 50 45 40
74 68 66 63 60 59
72 66 65 60 57 56
70 64 63 58 54 53
67 61 60 56 51 49
64 57 57 52 47 44
61 55 54 48 43 39
73 67 66 64 62 60
72 66 65 63 60 59
70 64 63 61 58 57
67 62 62 58 55 53
66 58 60 56 52 49
For performance table notes, see page D110; 3&% highlighted numbers indicate embedded AHRI certification points.
%
6-24-13
cfm
l/s
" w.g.
Pa
700
1100
1600
2100
330
519
755
991
0.20
0.16
0.15
0.14
50
40
37
35
74
69
70
68
Primary
Airflow
Unit Inlet
Size Size
2
3
5
6
8
10
12
14
Min. Inlet
Ps
72
70
72
67
65
63
66
63
56
55
57
56
56
57
59
58
59
59
63
60
65
64
62
61
61
61
62
58
57
55
56
54
42
45
46
46
41
43
46
46
41
45
47
48
Fan Airflow
cfm
l/s
600
1000
1850
2100
283
472
873
991
Fan
Watts
254
385
995
814
Discharge
4 5 6
65
68
68
71
58
63
65
70
58
63
65
68
58
60
65
68
53
55
62
64
48
53
62
64
69
65
74
73
63
62
68
67
Radiated
4 5 6
61
62
66
66
57
60
63
64
51
57
60
62
50
54
59
60
PSC Motor.
D
Ratings are certified in
accordance with AHRI
Standards.
12-30-14
D107
l/s CFM
425 900
6OJU4J[F
l/s CFM
661 1400
614 1300
378 800
MAXIMUM
MAXIMUM
330 700
519 1100
472 1000
283 600
"*3'-08
"*3'-08
2 ROW H. W. COIL
236 500
189 400
142 300
330 700
MINIMUM
189 400
MINIMUM
142 300
94 200
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.0
0.5 w.g.
125
Pa
6OJU4J[F
l/s CFM
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.5 w.g.
125
Pa
6OJU4J[F
l/s CFM
991 2100
1133 2400
MAXIMUM
944 2000
1086 2300
NO HEAT,
OR 1 ROW
H.W. COIL
897 1900
850 1800
1038 2200
2 ROW
H. W. COIL
802 1700
MAXIMUM
991 2100
944 2000
755 1600
NO HEAT,
OR 1 & 2 ROW
H.W. COIL
ELECTRIC HEAT
897 1900
ELECTRIC HEAT
708 1500
850 1800
661 1400
"*3'-08
"*3'-08
378 800
236 500
47 100
2 ROW H. W. COIL
425 900
283 600
94 200
NO HEAT,
ELECTRIC HEAT OR
1 ROW H.W. COIL
566 1200
NO HEAT,
ELECTRIC HEAT OR
1 ROW H.W. COIL
614 1300
566 1200
519 1100
802 1700
755 1600
708 1500
472 1000
661 1400
425 900
614 1300
378 800
566 1200
330 700
MINIMUM
519 1100
MINIMUM
283 600
472 1000
236 500
425 900
189 400
378 800
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.5 w.g.
125
Pa
&MFDUSJDBM%BUB
6OJU .PUPS
14$.0503'-"
4J[F )1
2
1/10
2.8
1.4
1.2
3
1/4
4.7
2.0
1.7
5
1/2
9.9
4.1
3.5
6
3/4
8.4
3.8
3.7
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.5 w.g.
125
Pa
%
8-1-11
$'.
550
236
500
212
450
189
400
165
350
142
300
118
250
94
200
71
150
47
100
6OJU4J[F
6OJU4J[F
MT$'.
519 1100
MAXIMUM
472 1000
"*3'-08
"*3'-08
MAXIMUM
MINIMUM
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
800
330
700
283
600
236
500
189
400
142
300
94
200
47
100
0.5 XH
125
1B
0.0
0
6OJU4J[F
MT$'.
378
MINIMUM
50
0.0
0
900
802 1700
MAXIMUM
944 2000
MAXIMUM
755 1600
0.5 XH
125
1B
6OJU4J[F
MT$'.
1038 2200
849 1800
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
24
425
708 1500
849 1800
661 1400
755 1600
566 1200
"*3'-08
"*3'-08
614 1300
519 1100
472 1000
425
900
378
800
330
700
283
600
236
500
189
400
378
800
283
600
189
400
MINIMUM
MINIMUM
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
&MFDUSJDBM%BUB
6OJU .PUPS
&$.'-"
4J[F )1
2
1/3
3.9
2.2
1.8
3
1/3
6.9
3.9
3.5
5
3/4
11.9
6.8
6.1
6
3/4
13.7
7.9
6.7
The ECM is a variable horsepower motor.
Refer to Selectworks Schedule.
FLA = Full load amperage
8-1-11
566 1200
472 1000
0.0
0
661 1400
0.5 XH
125
1B
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.5 XH
125
1B
/05&4
The fan curves for the ECM are unlike
those for traditional PSC motors. The ECM
is pressure independent and constant
volume in operation at factory or field set
point within the shaded area. Airflow does
not vary with changing static pressure
conditions. The motor compensates for any
changes in external static pressure or
induced air conditions such as filter loading.
%
kW MBH
6.4 22
GPM l/s
4
3
.25
.19
.13
3PX NVMUJDJSDVJU
kW MBH
11.7 40
GPM l/s
10.5 36
5.9 20
1.5 .09
5.3 18
1
.06
9.4 32
10
7.5
5
4
3
.63
.47
.32
.25
.19
.13
1.5 .09
8.2 28
4.7 16
1
7.0 24
.06
4.1 14
0.5 .03
5.9 20
3.5 12
0.5 .03
4.7 16
2.9 10
3.5 12
kW MBH
14.9 51
300
142
400
189
500
236
600
283
3PX NVMUJDJSDVJU
700 $'.
330 MT
2.3
8
200
94
300
142
400
189
500
236
600
283
8BUFS1SFTTVSF%SPQ
GPM l/s
15 .95
10 .63
.47
7.5
5 .32
.25
4
.19
13.8 47
12.6 43
11.4 39
.13
2
10.3 35
9.1 31
1.5
.09
.06
7.9 27
6.7 23
700 $'.
330 MT
"JS1SFTTVSF%SPQ
Pa in. H2O
249 1.00
199 0.80
149 0.60
1 ROW
12.0 4.0
100 0.40
2 ROW
6.0 2.0
3 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
"*313&4463&%301
8
200
94
)&"%-044 8"5&313&4463&%301
2.3
50 0.20
3 ROW
25 0.10
2 ROW
20 0.08
15 0.06
1 ROW
10 0.04
0.6 0.2
5 0.02
5.6 19
0.3 0.1
4.4 15
200
94
300
142
400
189
500
236
600
283
700 $'.
330 MT
2 0.01
1
.06
2
.13
3
.19
6
8 10 (1.
.38 .50 .63 MT
8"5&3'-08
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
%
200 300
94
189
"*3'-08
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
U ' $
Factor
100
47
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
8-3-11
3PX NVMUJDJSDVJU
kW MBH
9.4 32
GPM l/s
8.5 29
.25
.19
.13
kW MBH
17.6 60
GPM l/s
7.5 .47
16.1 55
14.7 50
7.6 26
5
4
.32
.25
.19
.13
13.2 45
1.5 .09
11.7 40
6.7 23
1.5 .09
.06
10.3 35
5.9 20
.06
8.8 30
7.3 25
5.0 17
0.5 .03
0.5 .03
5.9 20
4.1 14
4.4 15
2.9 10
700
330
900
425
1100
519
3PX NVMUJDJSDVJU
kW MBH
23.4 80
300
142
1300 $'.
613 MT
500
236
700
330
900
425
8BUFS1SFTTVSF%SPQ
GPM l/s
10 .63
7.5 .47
22.0 75
20.5 70
19.0 65
17.6 60
16.1 55
5
4
.32
.25
.19
.13
14.7 50
1.5 .09
13.2 45
11.7 40
.06
10.3 35
8.8 30
7.3 25
17.9 6.0
1100
519
1300 $'.
613 MT
"JS1SFTTVSF%SPQ
Pa in. H2O
249 1.00
447 0.80
149 0.60
100 0.40
11.9 4.0
2 ROW
6.0 2.0
3 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
"*313&4463&%301
500
236
)&"%-044 8"5&313&4463&%301
300
142
0.6 0.2
3 ROW
50 0.20
2 ROW
25 0.10
20 0.08
15 0.06
1 ROW
10 0.04
5 0.02
0.5 .03
5.9 20
0.3 0.1
4.4 15
300
142
500
236
700
330
900
425
1300 $'.
613 MT
1100
519
2 0.01
1
.06
2
3 4
6 8 10 (1.
.13 .19 .25 .38 .50 .63 MT
8"5&3'-08
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
8-3-11
200
94
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
U ' $
Factor
100
47
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
%
3.2 11
3PX NVMUJDJSDVJU
kW MBH
13.8 47
GPM l/s
12.6 43
kW MBH
24.0 82
10 .63
7.5 .47
22.6 77
7.5 .47
5
4
21.1 72
.32
19.6 67
.25
18.2 62
.19
.13
.32
.25
11.4 39
.19
10.3 35
.13
16.7 57
1.5 .09
15.2 52
9.1 31
GPM l/s
13.8 47
7.9 27
10.8 37
6.7 23
.06
7.9 27
0.5 .03
0.5 .03
6.4 22
5.0 17
600
283
800
378
1000
472
1200
566
1400
661
1600
755
3PX NVMUJDJSDVJU
kW MBH
32.8 112
600
283
1800 $'.
849 MT
800
378
1000
472
1200
566
1400
661
8BUFS1SFTTVSF%SPQ
GPM l/s
10 .63
29.9 102
7.5 .47
17.9 6.0
27.0 92
.32
.25
.19
.13
24.0 82
21.1 72
18.2 62
1.5 .09
15.2 52
1
12.3 42
.06
1600
755
1800 $'.
849 MT
"JS1SFTTVSF%SPQ
Pa in. H2O
249 1.00
447 0.80
1 ROW
149 0.60
100 0.40
11.9 4.0
2 ROW
6.0 2.0
3 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
"*313&4463&%301
1.5
9.4 32
5.6 19
.06
)&"%-044 8"5&313&4463&%301
1.5 .09
12.3 42
3 ROW
50 0.20
2 ROW
25 0.10
20 0.08
15 0.06
10 0.04
1 ROW
0.6 0.2
5 0.02
9.4 32
0.5 .03
6.4 22
600
283
800
378
1000
472
1200
566
1400
661
1600
755
1800 $'.
849 MT
0.3 0.1
2 0.01
1
.06
2
3 4
6 8 10 (1.
.13 .19 .25 .38 .50.63 MT
8"5&3'-08
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
%
200
94
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
U ' $
Factor
100
47
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
8-3-11
3PX NVMUJDJSDVJU
kW MBH
18.2 62
GPM l/s
kW MBH
32.2 110
GPM l/s
10 .63
5
4
.32
.19
10 .63
29.3 100
7.5 .47
16.4 56
7.5 .47
.25
26.4 90
14.7 50
23.4 80
12.9 44
.13
.32
.25
.19
.13
20.5 70
1.5 .09
11.1 38
17.6 60
9.4 32
1.5 .09
.06
14.7 50
7.6 26
1600
3391
1800
3841
2000
4238
3PX NVMUJDJSDVJU
kW MBH
41.0 140
8.8 30
1000
2119
2200 $'.
4662 MT
1200
2543
1400
2967
1600
3391
1800
3841
8BUFS1SFTTVSF%SPQ
GPM l/s
10 .63
38.1 130
7.5 .47
25.2 120
1 ROW
.32
.25
.19
32.2 110
29.3 100
26.4 90
23.4 80
.13
20.5 70
1.5 .09
17.6 60
14.7 50
.06
2200 $'.
4662 MT
"JS1SFTTVSF%SPQ
149 0.60
100 0.40
11.9 4.0
2000
4238
Pa in. H2O
249 1.00
447 0.80
2 ROW
6.0 2.0
3 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
"*313&4463&%301
1400
2967
)&"%-044 8"5&313&4463&%301
1200
2543
.06
0.6 0.2
3 ROW
50 0.20
2 ROW
25 0.10
20 0.08
15 0.06
1 ROW
10 0.04
5 0.02
11.7 40
8.8 30
1000
2119
0.3 0.1
1200
2543
1400
2967
1600
3391
1800
3841
2000
4238
2200 $'.
4662 MT
2 0.01
1
.06
2
3 4
6 8 10 (1.
.13 .19 .25 .38 .50 .63 MT
8"5&3'-08
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
8-3-11
200
94
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
U ' $
Factor
100
47
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
%
5.9 20
1000
2119
11.7 40
1.
Furnish and install variable volume parallel fan powered
terminal units of the sizes and capacities as indicated on the
drawings. Units shall be pressure independent with (pneumatic,
analog electronic, digital) controls. Units shall be manufactured by
/BJMPS*OEVTUSJFT*ODModel /.
2.
The entire terminal unit shall be designed and built as a
single unit. The units shall be provided with a primary variable air
volume damper that controls the air quantity in response to a
(thermostat or digital controller/zone sensor). The units shall also
include a fan that sequences on and off in response to the (thermostat
or digital controller/zone sensor). The space limitations shall be
reviewed carefully to ensure that all units will fit into the space allowed.
3.
Unit casings shall be 20 ga. (1.00) galvanized steel. Unit
shall be fully lined with fiberglass insulation which shall be at least
3/4" (19) thick dual density insulation complying with NFPA 90 for fire
and smoke resistivity and UL 181 for erosion. Any cut edges of
insulation shall be coated with NFPA 90 approved sealant.
4.
The terminal casing shall have full size bottom access
panels for easy access to motor and blower assembly and for
maintenance and replacement of parts without disturbing duct
connections. Access panels shall be attached to casing with (screws,
1/4 turn fasteners).
5.
Units shall have round inlets for the primary air
connections and shall have a minimum 6" (152) deep inlet duct collar
for field connection. Models with no heat or electric heat shall have
rectangular outlets suitable for flanged duct connections. Models
with hot water coils shall have a discharge opening with slip and
drive connection. Casing shall have mounting area for hanging by
sheet metal straps from a concrete slab.
6.
The damper shall be round and of laminated 2 x 20 ga.
(1.00) galvanized steel construction with a peripheral gasket and a
solid steel 1/2" (13) diameter shaft, pivoted in self-lubricating bronze
oilite bearings. Damper leakage shall not exceed 2% of the terminal
rated airflow at 3" w.g. (750 Pa) inlet static pressure.
7.
Entire terminal unit shall be factory assembled with
(pneumatic, analog electronic, digital) controls. All components
including all controls except the room (thermostat or zone sensor)
and (pneumatic piping, field wiring) shall be factory installed and
mounted with the unit.
8.
Provide a (pneumatic, analog electronic, digital) flow
control device that will limit the maximum and minimum airflow to that
scheduled on the drawings. Control of the terminal unit shall be
pressure independent.
9.
(The sequence of operation should be described here, if
not part of the temperature controls specifications).
10.
Blower casings shall be constructed of heavy gauge
coated steel. Blower wheel shall be forward curved centrifugal type,
dynamically balanced and driven by direct drive, single speed split
capacitor motors. Motors shall be suitable for 120 or 208 or 240 or
277 volt single phase power. Motors shall have built-in overload
protection, bearings capable of low rpm oiling, permanently oiled
bearings and a built-in, anti-backward rotation device. Fan assembly
shall be mounted so as to isolate the casing from the motor and
blower vibration at no less than four points. Isolation shall be
supplied at the motor and at the blower mounting points. A gasketed
backdraft damper shall be included on the fan discharge to preclude
primary air leakage back into the plenum space.
11.
A solid state SCR fan speed controller sized and designed
for the specific blower motor combination shall be provided to allow
infinitely adjustable fan speed from the minimum voltage stop to the
line voltage signal to the motor. A minimum voltage stop shall be
employed to ensure that fan cannot run in stall mode.
12.
Units shall incorporate a single point electrical (and
pneumatic) connection for the entire unit. All electrical components
shall be ETL listed or recognized and installed in accordance with the
National Electrical Code. All electrical components shall be mounted
in a control box. The entire assembly shall be ETL listed and labeled
to meet UL 1995 and CSA C22.2 No. 236.
13.
All sound data shall be compiled in an independent
laboratory and in accordance with the latest version of AHRI 880. All
units shall be AHRI certified and bear the AHRI certification label.
14.
Unit maximum radiated and discharge sound power levels
with fan only and 0.25" w.g. (63 Pa) discharge static pressure shall
not exceed the values in Tables 1 and 2 at the specified airflow. No
credit or reduction shall in any way be considered for room, plenum,
ceiling, downstream duct, elbows and/or similar item effects.
DGN
MT
2
3
5
6
400
700
1000
1500
189
330
472
708
5BCMF
"JSGMPX
DGN
MT
2
3
5
6
400
700
1000
1500
189
330
472
708
5BCMF
49
58
57
62
49
58
57
62
42
54
52
38
34
50
47
55
30
46
44
53
6OJU
4J[F
44
53
52
62
47
56
54
62
42
51
52
61
38
46
48
57
33
42
45
55
15.
Unit maximum radiated and discharge sound power levels
with 100% primary air and fan off at 1.0" w.g. (249 Pa) inlet pressure
and 0.25" w.g. (63 Pa) discharge static pressure shall not exceed the
values in Table 3 and 4 at the specified airflow. No credit or reduction
shall in any way be considered for room, plenum, ceiling,
downstream duct, elbows and/or similar item effects.
6OJU
*OMFU
4J[F
2
3
5
6
MT
08 700
10 1100
12 1600
14 2100
330
519
755
991
5BCMF
6OJU
*OMFU
4J[F
2
3
5
6
"JSGMPX
DGN
57
56
58
56
51
51
51
52
39
42
43
44
38
40
43
43
36
40
42
44
MT
08 700
10 1100
12 1600
14 2100
330
519
755
991
5BCMF
%
"JSGMPX
6OJU
4J[F
64
65
67
63
58
59
62
60
54
52
54
54
52
54
56
55
54
55
58
58
8-1-11
-JOFS0QUJPOT
0QUJPOT
&MFDUSJD)FBU
4UFSJ-JOFS
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQIT
Unit shall be fully lined with non-porous, sealed liner which complies
with NFPA 90A and UL 181. Installation shall be 13/16" (21) minimum
thickness, 4 lb. 1 cu. ft. (64 kg/m3) density with reinforced aluminum
foil-scrim-kraft (FSK) facing. All cut edges shall be secured with steel
angles or end caps to encapsulate edges and prevent erosion.
Insulation shall be Nailor Steri-Liner or equal.
'JCFS'SFF-JOFS
Unit shall be fully lined with a non-porous closed cell elastomeric
foam liner which complies with NFPA 90A, ASTM E84 and UL 181.
Installation shall be 3/4" (19) minimum thickness and secured to the
interior of the terminal with mechanical fasteners. No fiberglass is
permitted. Insulation shall be Nailor Fiber-Free Liner or equal.
1.
Furnish and install variable volume parallel fan powered
terminal units with integral electric heat of the sizes and capacities as
indicated on the drawings. Units shall be pressure independent with
(pneumatic, analog electronic, digital) controls. Units shall be
manufactured by /BJMPS*OEVTUSJFT*ODModel /&.
2.
An electric heater shall be factory mounted and pre-wired as
an integral package with the fan powered terminal unit. Heaters shall
be sized as shown on the drawings. The entire assembly including the
electric heater shall be ETL listed for zero clearance and so labeled
and shall meet all requirements of the latest National Electrical Code,
CSA C22.2 No.236). The unit shall have a single point electrical (and
pneumatic) connection. Heater casing and panel shall be a minimum
of 20 ga. (1.00) galvanized steel. Each heater shall be complete with
automatic reset high limit thermal cut-outs, control voltage transformer
as required, ground terminal, fan relay for interlocking the heater and
fan and high grade nickel chrome alloy resistance wire.
Element wires shall be suspended in insulators designed to expose the
entire face area of the wire thereby eliminating hot spots. Each heater
shall be supplied with factory supplied and pre-wired branch circuit
fusing as required by NEC and UL. Circuiting and fusing shall also be in
accordance with the circuiting requirements as shown on the plans.
Additional accessories shall include (control transformer, circuit
fusing, disconnect switch, SCR controller, pneumatic electric
switches) for staging the heater. (Additional performance
requirements that you might want to include can be found in the
electric heater section). The electric heater shall be located on the
discharge side of the fan so as not to add heat to the motor and
shorten its expected lifetime.
Coils rated up through 5 kW shall be single phase, 277 volt, 60 Hz
and coils larger than 5 kW shall be three phase, four wire wye, 480
volt, 60 Hz. Electric heating coils up to and including 4 kW shall be
single stage. Electric coils above 4 kW shall be two stage.
)PU8BUFS)FBUJOH$PJMT
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQIT
1.
Furnish and install Variable Volume Parallel Fan Powered
Terminal Units with integral hot water coils of the sizes and capacities
as indicated on the drawings. Units shall be pressure independent
with (pneumatic, analog electronic, digital) controls. Units shall be
manufactured by /BJMPS*OEVTUSJFT*ODModel /8.
2.
A hot water coil shall be factory mounted as an integral
package with the fan powered terminal unit. Hot water coils shall be
sized as shown on the drawings. The entire assembly including the
hot water coil shall be ETL listed for zero clearance and so labeled
and shall meet all requirements of the latest National Electrical Code
(CSA C22.2 No.236). The unit shall have a single point electrical
(and pneumatic) connection. Access panels on the bottom of the unit
shall permit easy access to the coil for inspection and cleaning. Coils
shall be 1, 2 or 3 row as required and heating capacities shall be as
shown on the plans. Coils shall have aluminum plate fins spaced 10
per inch and bonded to 1/2" (13) O.D. copper tubes. Copper
connections shall be sweat. All coils shall be tested at a minimum of
300 psi (2.1 MPa) under water to produce a guaranteed working
pressure of 250 psi (1.7 MPa). Controls and valves for the hot water
coils shall be field mounted. Heating coils shall be located on the
discharge side of the fan so as not to add heat to the motor and
shorten its expected lifetime.
8-1-11
%
1"3"--&-'-08
7"3*"#-&"*370-6.&
/4&3*&4
t-08130'*-&
.PEFMT
/
/P)FBU
/&
&MFDUSJD)FBU
/8
)PU8BUFS)FBU
The /-PX1SPGJMF4FSJFT provides many standard design features and excellent sound performance when compared with
other parallel designs. The / offers a compact and economical design that provides excellent performance in the most
demanding variable air volume/intermittent fan applications. The fan is mounted at ninety degrees to the primary airflow to
provide optimum mixing.
Model 37NW
'&"563&4
Only 11" (279) to 12 1/2" (318) high
20 ga. (1.00) galvanized steel
construction.
2 x 20 ga. (1.00) round or
rectangular primary air damper with a
polyurethane peripheral gasket. 90
rotation, CW to close. 1/2" (13) dia.
plated steel drive shaft. An indicator
mark on the end of the shaft shows
damper-position. Damper leakage is
less than 2% of nominal flow at 3" w.g.
(750 Pa).
Round or rectangular 6" (152) deep
inlet collars for field duct connection.
Multi-point averaging 'Diamond
Flow ' sensor (pressure independent
control only).
Access panels on underside of
terminal for ease of maintenance and
service.
Energy efficient PSC fan motor with
thermal overload protection.
Solid state fan speed controller with
minimum voltage stop.
Motor blower assembly mounted on
special 16 ga. (1.6) angles and
isolated from casing with rubber isolators.
Gasketed
backdraft
damper
mounted on fan discharge prevents
primary air from escaping through the
fan section into the ceiling plenum.
%
0QUJPOT
ECM motor option. EPIC fan
volume controller.
Induced air filter, 1" (25) thick,
disposable type.
Primary air valve enclosure for field
mounted controls.
Toggle disconnect switch. Units with
electric heat also offer door
Interlocking type.
Various 'IAQ' linings are available.
Fan airflow switch for night shutdown.
Night setback fan/heat cycle
(pneumatic and analog).
Fan unit fusing.
Hanger brackets.
Induced air attenuator.
$POUSPMT
Pneumatic and analog electronic
controls. Factory supplied, mounted
and calibrated.
Digital controls. Factory mounting
and wiring of DDC controls. Controls
supplied by BAS controls contractor.
10-31-11
IH
OPTIONAL
INDUCED AIR
INLET FILTER
INDUCED
IW
FAN
AIR
DH
W
PRIMARY
DIA. =
NOM. -1/8" (3)
CL
AIR
A
MULTI-POINT
FLOW SENSOR
BACKDRAFT
DAMPER
BUTTERFLY
DAMPER
DAMPER
DRIVESHAFT
6"
(152)
5 1/2" (140)
B
10" (254)
14" (356)
PRIMARY
CONTROLS
ENCLOSURE
FAN
CONTROLS
ENCLOSURE
H
PRIMARY
AIR
%JNFOTJPOBM%BUB
6OJU
4J[F
*OMFU
4J[F
*OEVDFE
"JS*OMFU
*8Y*)
0VUMFU
%JTDIBSHF
%8Y%)
'JMUFS
0QUJPOBM
4J[F
12 x 10
(305 x 254)
10 x 8
(254 x 203)
1 12
(38)
1 12
(38)
14 x 11
(356 x 279)
8 8 (206)
16 x 10
(406 x 254)
16 x 8
(406 x 203)
1 12
(38)
1 12
(38)
18 x 11
(457 x 279)
13
(330)
19 x 10
(483 x 254)
19 x 11
(483 x 279)
1
(25)
22 x 11
(559 x 279)
"
32
(813)
36
(914)
11
(279)
7 78 (200)
36
(914)
11
(279)
12 (305)
14 x 8 (356 x 203)
38
(965)
14 x 8 (356 x 203)
14 x 10 (356 x 254)
43
(1092)
36
(914)
12 12
(318)
6 (152), 8 (203)
10 (254)
8 (203), 10 (254)
6 2 (165)
1
(19)
0QUJPOTBOE"DDFTTPSJFT
2PQUJPOo*OEVDFE"JS"UUFOVBUPS
22 ga. (0.86) galvanized steel construction.
Shipped loose for field attachment.
8JUIPVU)8$PJM
OPTIONAL
INDUCED
AIR INLET
FILTER
AL
Flanged connection.
1/2" (13) thick dual density fiberglass liner.
Meets requirements of NFPA 90A & UL 181.
8JUI)8$PJM
AC
6OJU
4J[F
INDUCED
AIR
IW + 2" (51)
OPTIONAL INDUCED
AIR INLET FILTER
S
10-28-11
*8
"-
"$
11 12 13 11 36 36
(279) (305) (330) (279) (914) (914)
11 16 17 11 36 36
(279) (406) (432) (279) (914) (914)
12 12 19 22 11 36 36
(318) (483) (559) (279) (914) (914)
CL
1" (25)
FLANGE
%
DW
OPTIONAL
INDUCED AIR
INLET FILTER
G
D
COIL
CONNECTION
.PEFM/8
Available in one or two row. Coil section
mounted on induced air inlet.
4UBOEBSE'FBUVSFT
FAN
AIR
DH
W
DIA. =
NOM.
-1/8" (3)
PRIMARY
AIR
$PJM)BOE$POOFDUJPOT
INDUCED
WATER
COIL
MULTI-POINT
FLOW SENSOR
5 1/2" (140)
H
CL
BACKDRAFT
DAMPER
BUTTERFLY
DAMPER
DW
DAMPER
DRIVESHAFT
6"
(152)
PRIMARY
CONTROLS
ENCLOSURE
10" (254)
14" (356)
FAN
CONTROLS
ENCLOSURE
6OJU4J[F
$Y%
&
'
%8Y%)
2
3
4
32 (813)
38 (965)
43 (1092)
36 (914)
36 (914)
36 (914)
11 (279)
11 (279)
12 12 (318)
1 2 (38)
1 12 (38)
1 (25)
12 x 10 (305 x 254)
16 x 10 (406 x 254)
21 x 10 (533 x 254)
13 (330)
17 (432)
22 (559)
5 (127)
5 (127)
5 (127)
11 (279)
11 (279)
11 (279)
10 x 8 (254 x 203)
16 x 8 (406 x 203)
19 x 11 (483 x 279)
&MFDUSJD$PJM4FDUJPO
3/4"
(19)
.PEFM/&
IH
4UBOEBSE'FBUVSFT
Unique hinged heater design permits
easy
access,
removal
and
replacement of heater element
without disturbing ductwork.
Coil installed on unit discharge.
Insulated coil element wrapper.
Automatic reset high limit cut-outs
(one per element).
Single point electrical connection
(except 600V).
Positive pressure airflow switch.
Flanged outlet duct connection.
Terminal unit with coil is ETL Listed as
an assembly.
Controls mounted as standard on RH
side as shown. Terminals ordered with
LH controls (optional) are built as
mirror image.
4UBOEBSE4VQQMZ7PMUBHF )[
120, 208, 240 and 277V single phase.
208, 480 (4 wire wye) and 600V (Dual
point connection) three phase.
%
OPTIONAL
INDUCED AIR
INLET FILTER
INDUCED
IW
FAN
AIR
12"
(305)
W
PRIMARY
DIA. =
NOM.
-1/8" (3)
A
MULTIPOINT
FLOW
SENSOR
BUTTERFLY
DAMPER
6"
(152)
DAMPER
DRIVESHAFT
HEATER
EW
K
FAN / HEATER
CONTROLS ENCLOSURE
BACKDRAFT
DAMPER
CL
AIR
EH
34 5/8" (879)
0QUJPOT
Toggle disconnect switch (includes
fan).
Door interlock disconnect switch.
Power circuit fusing.
6OJU4J[F
*8Y*)
&8Y&)
2
3
4
32 (813)
38 (965)
43 (1092)
36 (914)
36 (914)
36 (914)
11 (279)
11 (279)
12 12 (318)
12 x 10 (305 x 254)
16 x 10 (406 x 254)
19 x 10 (483 x 254)
18 12 (470)
24 12 (622)
27 (686)
19 (483)
19 (483)
22 (559)
112 (38)
112 (38)
3
4 (19)
10 12 x 9 (267 x 229)
16 12 x 9 (419 x 229)
19 x 10 12 (483 x 267)
10-31-11
21
20
-
26
25
23
-
30
29
25
21
-
25
23
21
-
31
31
28
23
-
35
34
30
24
-
36
35
31
26
-
800
700
600
400
175
378
330
283
189
83
0.11
0.08
0.06
0.03
0.01
27
20
15
7
2
20
-
25
24
21
-
28
26
24
-
29
29
26
21
-
38
36
34
26
-
40
38
35
26
21
39
39
35
26
23
10
1400
1100
825
550
275
661
519
389
260
130
0.27
0.16
0.09
0.04
0.01
67
40
22
10
2
20
-
26
24
-
30
28
24
-
33
29
26
20
-
28
-
29
28
24
21
-
36
34
33
28
20
41
39
35
29
24
43
40
36
31
25
800
700
600
400
175
378
330
283
189
83
0.14
0.10
0.07
0.03
0.01
35
25
17
7
2
21
20
-
25
25
23
-
28
28
25
-
28
24
21
-
34
31
29
21
-
36
34
31
23
21
38
35
33
25
24
10
1400
1100
825
550
275
661
519
389
260
130
0.30
0.17
0.09
0.04
0.01
75
42
22
10
2
21
-
29
24
20
-
33
30
25
-
35
33
28
20
-
28
20
-
33
29
25
20
-
38
34
30
25
-
41
38
34
28
22
44
40
35
29
24
14
x
8
2100
1600
1200
800
400
991
755
566
378
189
0.30
0.17
0.10
0.04
0.01
75
42
24
10
2
20
-
29
25
20
-
34
29
24
-
38
30
25
21
-
26
21
-
33
30
28
-
38
36
33
26
20
43
40
35
29
26
45
41
38
28
29
14
x
8
2100
1600
1200
800
400
991
755
566
378
189
0.08
0.04
0.02
0.01
0.01
20
11
5
2
2
23
-
28
24
-
33
29
25
-
35
31
26
21
-
24
-
34
30
24
-
38
35
30
25
-
41
40
34
26
26
44
43
35
30
29
14
x
10
2700
1950
1550
1050
525
1274
920
731
495
248
0.10
0.05
0.03
0.01
0.01
25
12
7
2
2
24
-
30
25
21
-
35
30
28
23
-
37
33
30
25
-
26
-
34
30
26
21
-
40
36
34
29
-
45
43
39
34
24
49
45
41
36
26
1FSGPSNBODF/PUFT
1. NC levels are calculated from the
published raw data and based on
procedures outlined in Appendix E, AHRI
885-2008.
2. Discharge
sound
attenuation
deductions are based on environmental
effect, duct lining, branch power division,
insulated flex duct, end reflection and
space effect and are as follows:
Octave Band
2 3 4 5 6 7
24 28 39 53 59 40
27 29 40 51 53 39
29 30 41 51 52 39
Discharge attenuation
10-17-11
Radiated attenuation
Total dB reduction
Octave Band
2 3 4 5 6 7
18 19 20 26 31 36
%
10
10
14
x
8
14
x
8
4
14
x
10
450
400
300
200
100
800
700
600
400
175
1400
1100
825
550
275
800
700
600
400
175
1400
1100
825
550
275
2100
1600
1200
800
400
2100
1600
1200
800
400
2700
1950
1550
1050
525
212
189
142
94
47
378
330
283
189
83
661
519
389
260
130
378
330
283
189
83
661
519
389
260
130
991
755
566
378
189
991
755
566
378
189
1274
920
731
495
248
Min. inlet
Ps
" w.g. Pa
0.19 47
0.16 40
0.10 25
0.05 12
0.01 2
0.10 25
0.08 20
0.06 15
0.03 7
0.01 2
0.26 65
0.16 40
0.09 22
0.04 10
0.01 2
0.14 35
0.10 25
0.07 17
0.03 7
0.01 2
0.30 75
0.17 42
0.09 22
0.04 10
0.01 2
0.30 75
0.17 42
0.09 22
0.04 10
0.01 2
0.08 20
0.04 10
0.02 5
0.01 2
0.00 0
0.10 25
0.05 12
0.03 7
0.01 2
0.01 2
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure shown
Minimum Ps
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps 2.0" wg (500Pa)Ps
2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
60 55 51 44 34 32 64 60 57 49 37 36 70 67 62 55 41 40 75 71 66 58 44 44 76 74 68 58 45 46
63 53 49 41 31 29 64 59 56 47 35 33 70 66 61 53 39 38 74 70 65 56 42 42 75 73 67 57 44 45
56 47 43 35 26 21 62 57 53 44 31 29 68 63 58 49 36 36 71 68 62 52 40 41 71 70 65 54 42 44
- 40 35 25 15 - 59 53 49 40 26 25 63 60 55 45 33 35 64 64 59 48 38 41 65 66 62 50 40 44
- - 24 - - - - 50 45 37 24 24 55 56 51 40 31 35 56 59 57 45 36 39 58 60 59 48 39 412
58 53 47 41 33 28 67 62 55 51 40 35 71 67 60 55 43 39 73 71 65 58 45 42 75 73 67 60 47 44
56 50 44 38 30 24 64 60 53 49 38 32 70 65 59 53 41 36 72 69 62 56 43 40 73 71 65 58 45 42
- 47 41 35 27 21 62 58 51 47 35 29 68 64 57 51 38 34 70 67 61 54 41 39 71 69 63 56 43 42
- 42 37 30 25 - 59 55 48 43 30 24 63 59 54 47 34 33 64 62 57 50 36 39 64 62 58 52 37 40
- - 26 18 - - - 47 43 35 28 23 55 52 50 41 25 34 55 54 56 48 31 30 55 55 59 52 34 33
69 63 56 51 48 44 71 67 60 53 49 44 75 72 65 57 52 47 77 75 69 60 54 49 79 77 71 62 55 50
63 58 51 46 42 36 69 64 57 50 45 39 73 69 62 54 48 42 75 72 66 57 50 45 76 74 69 60 52 47
- 52 46 41 35 27 65 61 53 46 40 33 70 66 59 51 44 37 72 70 64 55 48 43 74 72 66 57 49 44
- 46 40 34 27 19 62 57 49 42 34 27 65 62 56 47 40 36 67 65 59 50 42 37 69 66 60 52 43 39
- 40 35 29 24 18 58 51 45 37 29 27 59 55 50 40 31 27 61 57 53 44 34 31 62 59 55 47 37 34
63 56 49 43 37 31 70 63 55 50 40 35 73 67 60 54 43 39 76 70 64 57 46 42 77 72 65 59 47 44
61 53 46 40 33 27 68 60 53 48 38 32 72 65 59 52 41 37 74 68 62 55 44 40 75 70 64 57 46 43
57 49 43 38 30 23 65 58 52 47 36 30 70 64 58 51 40 37 72 66 61 54 42 39 74 69 63 56 44 41
- 42 37 32 27 17 60 53 48 45 32 25 65 58 54 47 35 35 66 61 57 51 38 36 68 63 59 53 40 37
- - - 23 - - - 47 43 34 - - 55 53 53 43 28 25 57 55 57 48 33 31 56 55 59 52 36 35
71 64 58 52 46 41 74 67 61 54 48 42 78 72 66 59 51 46 82 76 70 62 54 48 83 78 73 65 55 50
65 57 52 46 40 34 71 64 58 51 44 38 75 69 63 55 47 41 79 73 68 60 51 46 81 75 70 63 53 48
58 52 47 41 35 28 68 60 55 48 40 33 73 66 60 53 44 38 76 70 65 57 47 44 77 71 66 59 49 45
- 45 40 35 29 - 63 56 51 45 36 28 69 62 56 49 40 37 70 64 59 51 42 39 71 65 60 52 43 41
- - 32 30 26 - 56 49 46 38 34 25 60 53 50 41 32 36 62 56 54 45 36 33 64 58 56 48 38 36
68 63 58 53 47 44 71 66 61 55 48 46 76 73 66 59 52 50 80 77 70 62 55 54 84 81 74 67 61 60
62 56 51 47 41 35 69 63 58 51 44 41 75 70 63 56 48 48 78 73 66 59 51 51 79 74 68 61 53 53
55 50 46 41 35 29 67 60 55 49 40 39 71 65 60 53 45 45 73 69 63 56 49 48 74 70 65 57 50 50
- 43 40 35 28 - 60 55 51 45 36 35 64 60 55 49 41 39 67 64 59 51 44 44 68 66 62 54 45 47
- - 35 32 30 - - 49 45 39 32 26 57 59 53 44 36 36 58 63 60 49 41 41 58 62 62 51 44 44
69 60 56 52 44 43 76 67 63 56 49 48 79 71 67 60 52 52 83 75 71 63 55 55 84 76 72 64 57 57
61 53 49 44 36 33 71 63 59 52 44 43 75 68 64 56 49 49 79 72 67 59 52 53 80 74 70 61 55 55
- 46 42 37 29 23 67 59 55 48 40 39 71 64 61 53 46 47 75 68 65 56 50 52 76 70 67 58 51 53
- 40 36 30 25 - 61 54 51 44 36 37 66 60 57 49 43 43 68 64 61 52 46 47 68 66 63 54 47 49
- - 33 28 24 - 59 50 47 40 33 34 57 59 55 44 38 39 59 63 62 49 42 43 59 63 65 52 45 46
69 62 57 53 46 43 75 68 64 57 51 50 80 73 69 61 55 54 83 76 72 64 59 58 85 79 74 66 61 60
61 53 49 43 36 32 71 64 60 52 46 44 76 69 65 57 52 50 80 73 69 61 56 54 81 75 70 63 58 56
56 47 43 38 30 23 69 61 58 50 43 41 74 66 62 55 49 47 78 70 66 59 54 52 79 73 69 61 56 55
- 41 36 30 25 - 65 57 53 46 39 37 70 63 59 52 47 44 73 67 64 55 50 51 75 69 65 57 50 52
- - 32 29 25 - 58 50 46 40 33 28 61 56 52 44 39 37 63 60 56 48 43 42 64 62 60 51 45 46
For performance table notes, see page D125; 3&% highlighted numbers indicate embedded AHRI certification points.
%
6-24-13
450 212
400 189
300 142
200 94
100 47
800
700
600
400
175
378
330
283
189
83
0.11
0.08
0.06
0.03
0.01
27
20
15
7
2
36
36
36
34
25
27
26
25
23
-
65
65
63
59
49
54
52
50
47
43
46
45
43
40
38
42
40
38
36
32
39
38
38
37
32
32
30
29
27
22
72
71
69
63
52
59
59
55
51
45
51
50
48
44
42
44
43
40
37
33
41
40
38
37
31
35
32
31
28
22
74
72
70
63
53
63
62
59
53
47
55
54
52
48
47
45
44
42
39
37
41
40
39
37
33
35
34
33
31
25
73
73
70
63
54
65
63
61
55
47
57
56
53
50
49
47
45
44
41
40
42
41
40
37
33
37
35
34
32
27
10
1400
1100
825
550
275
661
519
389
260
130
0.27
0.16
0.09
0.04
0.01
67 64 54 47 43 45
40 57 49 43 41 42
22 50 44 38 38 41
10 - 42 38 38 39
- 41 35 37 37
2
38
35
32
31
25
65
64
61
59
54
55
54
52
50
46
48
46
44
42
39
43
41
40
39
38
44
42
41
40
38
37
34
32
31
27
71
69
68
64
58
61
59
57
53
49
53
50
49
45
42
45
43
41
39
38
44
42
40
38
37
37
35
33
31
28
75
73
70
65
61
65
64
60
56
52
57
55
52
48
45
47
45
42
40
39
44
42
39
38
37
39
37
35
32
30
76
74
71
67
62
68
66
62
58
54
59
57
54
51
46
48
46
44
42
40
44
42
39
39
38
40
38
36
34
33
800
700
600
400
175
378
330
283
189
83
0.14
0.10
0.07
0.03
0.01
35 57 48 43 37 31
25 52 46 42 36 29
17 - 44 41 34 28
- 41 41 34 27
7
- 41 42 37 30
2
26
22
20
18
19
64
61
59
53
-
53
51
49
46
44
46
45
43
41
41
41
38
37
34
33
34
31
30
28
28
29
26
24
21
19
69
67
65
59
-
57
55
54
50
46
50
48
47
44
44
43
41
39
36
33
37
35
33
30
27
33
31
30
27
22
71
69
67
60
-
60
59
57
52
47
53
52
50
47
47
44
43
41
38
37
39
37
36
32
30
36
35
33
31
27
72
70
68
62
-
63
61
59
53
47
55
54
52
49
50
46
45
43
41
41
41
39
38
34
32
38
37
36
32
30
10
1400
1100
825
550
275
661
519
389
260
130
0.30
0.17
0.09
0.04
0.01
75 64 54 49 43 40
42 58 48 46 40 34
22 - 45 44 38 28
10 - 43 43 36 25
- 42 42 36 26
2
35
27
18
-
68
65
62
58
52
58
55
53
50
46
51
49
48
45
43
44
43
41
38
35
41
36
33
30
28
37
32
26
21
19
72
69
66
62
54
63
61
58
54
48
56
54
51
47
45
47
46
43
39
37
42
39
36
32
28
39
35
31
29
22
75
72
69
64
57
68
65
62
57
51
60
58
54
50
48
50
48
45
41
40
44
41
37
34
31
42
39
36
33
26
77
74
70
65
58
69
67
63
58
53
62
60
56
51
50
52
50
46
42
42
46
42
39
35
34
44
40
38
35
30
14
x
8
2100
1600
1200
800
400
991
755
566
378
189
0.30
0.17
0.10
0.04
0.01
75 63 54 51 46 40
42 56 50 47 41 34
25 52 46 44 37 28
10 - 43 43 34 25
- 39 42 35 27
2
36
28
17
-
68
66
64
57
-
58
55
51
47
45
53
49
45
42
41
48
44
40
37
35
43
39
37
35
33
39
36
36
35
35
72
71
68
63
56
63
60
56
53
52
56
52
49
46
46
51
47
44
41
39
47
44
42
41
40
45
42
41
41
40
76
74
70
65
57
68
63
60
57
56
59
55
52
49
52
53
49
46
44
43
49
47
46
45
44
48
46
45
45
44
78
75
72
66
56
69
65
62
59
55
60
57
55
53
54
55
51
48
46
46
51
49
48
47
46
50
49
48
47
47
14
x
8
2100
1600
1200
800
400
991
755
566
378
189
0.08
0.04
0.02
0.01
0.01
20 61 53 50 45 40
10 56 45 44 38 32
5 50 41 38 32 27
- - 34 27 24
2
- - 34 27 21
2
35
26
17
-
69
66
61
56
49
59
54
50
46
41
54
49
46
42
38
49
44
41
37
32
44
40
36
32
28
40
36
32
27
22
72
70
66
62
53
62
59
56
52
49
57
53
50
46
44
51
48
45
40
36
47
44
42
37
32
44
41
40
34
30
75
74
69
63
55
65
62
59
56
54
59
56
53
50
52
53
50
47
44
42
49
47
45
41
37
47
46
47
39
36
77
76
70
64
54
67
64
62
58
53
61
58
56
52
54
55
52
49
46
45
52
49
47
43
40
50
49
50
42
39
14
x
10
2700
1950
1550
1050
525
1274
920
731
495
248
0.10
0.05
0.03
0.01
0.01
25 62 55 52 47 44
12 54 48 45 39 35
7 52 44 41 35 31
- 43 37 32 28
2
- 40 36 30 25
2
36
26
23
18
-
69
66
63
59
52
61
56
53
49
45
56
51
49
45
40
50
45
44
41
37
47
41
40
38
35
42
37
35
35
32
74
71
69
65
57
65
60
58
54
49
60
54
52
49
44
54
48
47
44
41
51
45
45
43
40
48
41
42
44
39
78
76
73
69
59
68
64
62
59
53
62
57
56
53
50
56
51
50
47
45
53
48
48
45
44
50
46
47
47
43
81
78
75
71
60
71
67
65
62
55
64
60
59
56
52
58
53
53
50
47
55
50
51
48
46
55
48
51
49
46
56
56
52
50
-
46
44
41
39
-
39
38
36
35
33
37
36
34
33
30
Min. Inlet
Ps
Minimum Ps
"w.g. Pa 2 3 4 5 6
0.19 47 55 48 40 36 32
0.16 40 52 45 38 35 31
0.10 25 - - 36 34 32
0.05 12 - - 33 31 29
- - 29 26 0.02 5
1FSGPSNBODF/PUFT
1. Sound levels are primary air only with
fan turned off cooling cycle.
2. Radiated sound power is the
breakout sound transmitted through the
unit casing walls and the induced air
inlet.
3. Sound power levels are in decibels,
dB re 10 -12 watts.
10-20-11
%
ALL
850
700
550
350
401
330
260
165
0.25
0.25
0.25
0.25
62
62
62
62
20
-
38
35
32
28
ALL
1350
1100
825
450
637
519
389
212
0.25
0.25
0.25
0.25
62
62
62
62
28
21
-
45
41
36
31
1FSGPSNBODF/PUFT
Octave Band
2 3 4 5 6 7
24 28 39 53 59 40
27 29 40 51 53 39
29 30 41 51 52 39
Discharge attenuation
%
Radiated attenuation
Total dB reduction
Octave Band
2 3 4 5 6 7
18 19 20 26 31 36
7-12-11
330
260
189
118
0.25
0.25
0.25
0.25
62
62
62
62
2
68
65
61
-
Radiated
3
64
60
57
53
4
60
56
54
49
5
55
51
47
41
6
46
41
37
30
7
48
43
38
26
2
67
65
63
59
3
60
58
57
54
4
59
56
56
52
5
54
50
48
43
6
49
46
44
38
7
42
38
36
29
ALL
700
550
400
250
ALL
850
700
550
350
401
330
260
165
0.25
0.25
0.25
0.25
62
62
62
62
74
71
70
66
65
61
56
52
63
60
56
51
58
54
50
44
52
47
42
36
55
50
45
35
72
68
67
62
65
60
57
53
63
60
57
53
59
55
51
46
51
47
43
38
43
38
33
26
ALL
1350
1100
825
450
637
519
389
212
0.25
0.25
0.25
0.25
62
62
62
62
79
75
70
63
71
66
60
52
70
67
62
53
68
62
56
46
62
56
49
38
63
57
50
36
77
73
69
64
72
67
61
55
69
66
61
56
66
62
56
49
59
54
47
40
51
46
39
30
%
Inlet
Size
l/s
" w.g.
Pa
519
755
920
0.16
0.17
0.05
40
42
12
75 72 66 57 50 45 73 64 55 45 42 37 550
78 73 66 59 51 51 74 63 55 49 47 46 700
80 73 69 61 56 54 76 64 57 51 48 46 1100
Primary
Airflow
cfm
2
10
1100
3 14 x 8 1600
4 14 x 10 1950
Min. Inlet
Ps
Fan Airflow
cfm
l/s
260
330
519
Fan
Watts
2
Discharge
4 5 6
Radiated
4 5 6
275 65 60 56 51 41 43 65 58 56 50 46 38
355 71 61 60 54 47 50 68 60 60 55 47 38
570 75 66 67 62 56 57 73 67 66 62 54 46
PSC Motor.
2-12-15
D123
378 800
MAXIMUM
MAXIMUM
425 900
330 700
NO HEAT OR
ELECTRIC HEAT
283 600
2 ROW H. W. COIL
189 400
NO HEAT OR
ELECTRIC HEAT
1 ROW H. W. COIL
330 700
"*3'-08
236 500
"*3'-08
378 800
1 ROW H. W. COIL
2 ROW H. W. COIL
283 600
236 500
142 300
189 400
94 200
MINIMUM
142 300
47 100
MINIMUM
94 200
0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.5 w.g.
125
Pa
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.0
0.5 w.g.
125
Pa
6OJU4J[F
l/s CFM
755 1600
708 1500
661 1400
MAXIMUM
"*3'-08
614 1300
566 1200
NO HEAT OR
ELECTRIC HEAT
519 1100
1 ROW H. W. COIL
472 1000
425 900
2 ROW H. W. COIL
378 800
330 700
283 600
&MFDUSJDBM%BUB
6OJU .PUPS
14$.0503'-"
4J[F )1
2
1/6
4.6
1.8
1.8
1.3
3
1/4
5.4
2.2
2.2
1.7
4
1/2
7.5
3.5
3.5
2.6
FLA = Full load amperage
236 500
189 400
MINIMUM
142 300
94 200
0.0
0
10-18-11
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.5 w.g.
125
Pa
%
307
650
283
6OJU4J[F
/P$PJM
3PX)8$PJM
MT$'.
330 700
MAXIMUM
307
650
600
283
600
260
550
260
550
236
500
236
500
212
450
212
450
189
400
189
400
165
350
165
350
142
300
142
300
118
250
118
250
94
200
94
200
71
150
71
150
47
100
"*3'-08
"*3'-08
MT$'.
330 700
MAXIMUM
MINIMUM
47
MINIMUM
100
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.5 XH
125
1B
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.5 XH
125
1B
/05&4
The fan curves for the ECM are unlike those for
traditional PSC motors. The ECM is pressure
independent and constant volume in operation
at factory or field set point within the shaded
area. Airflow does not vary with changing static
pressure conditions. The motor compensates for
any changes in external static pressure or
induced air conditions such as filter loading.
Airflow can be set to operate on horizontal
performance line at any point within shaded
area using the solid state volume controller
provided.
Fan curves shown are applicable to 120/240,
208 and 277 volt, single phase ECMs. ECMs,
although DC in operation, include a built-in
inverter.
&MFDUSJDBM%BUB
6OJU .PUPS
&$.'-"
4J[F )1
2
2.7
1.9
1.8
1.6
*
The ECM is a variable horsepower motor.
Refer to Selectworks Schedule.
FLA = Full load amperage
%
10-18-11
6OJU4J[F
/P$PJM
MT$'.
472 1000
3PX)8$PJM
MT$'.
472 1000
MAXIMUM
900
425
900
378
800
378
800
330
700
330
700
283
600
283
600
236
500
236
500
189
400
189
400
142
300
142
300
MINIMUM
MINIMUM
200
94
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
94
"*3'-08
"*3'-08
MAXIMUM
425
200
0.5 XH
125
1B
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.5 XH
125
1B
6OJU4J[F
3PX)8$PJM
MT$'.
472 1000
425
/05&4
The fan curves for the ECM are unlike those for
traditional PSC motors. The ECM is pressure
independent and constant volume in operation
at factory or field set point within the shaded
area. Airflow does not vary with changing static
pressure conditions. The motor compensates for
any changes in external static pressure or
induced air conditions such as filter loading.
Airflow can be set to operate on horizontal
performance line at any point within shaded
area using the solid state volume controller
provided.
900
"*3'-08
MAXIMUM
378
800
330
700
283
600
236
500
189
400
142
300
94
200
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
&MFDUSJDBM%BUB
0.5 XH
125
1B
6OJU .PUPS
&$.'-"
4J[F )1
3
4.8
3.3
3.1
2.7
*
The ECM is a variable horsepower motor.
Refer to Selectworks Schedule.
FLA = Full load amperage
10-20-11
%
6OJU4J[F
/P$PJM
MT$'.
590 1250
3PX)8$PJM
MT$'.
590 1250
543 1150
496 1050
496 1050
448
950
448
950
401
850
401
850
354
750
354
750
307
650
307
650
260
550
260
550
212
450
212
450
165
350
165
350
"*3'-08
"*3'-08
MAXIMUM
543 1150
MAXIMUM
MINIMUM
MINIMUM
118
250
118
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
250
0.5 XH
125
1B
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.5 XH
125
1B
6OJU4J[F
3PX)8$PJM
MT$'.
590 1250
/05&4
The fan curves for the ECM are unlike those for
traditional PSC motors. The ECM is pressure
independent and constant volume in operation
at factory or field set point within the shaded
area. Airflow does not vary with changing static
pressure conditions. The motor compensates for
any changes in external static pressure or
induced air conditions such as filter loading.
Airflow can be set to operate on horizontal
performance line at any point within shaded
area using the solid state volume controller
provided.
543 1150
496 1050
"*3'-08
MAXIMUM
448
950
401
850
354
750
307
650
260
550
212
450
165
350
&MFDUSJDBM%BUB
MINIMUM
118
250
0.0
0
0.1
0.2
0.3
0.4
25
50
75
100
%*4$)"3(&45"5*$13&4463&
0.5 XH
125
1B
6OJU .PUPS
&$.'-"
4J[F )1
4
5.7
3.9
3.7
3.2
*
The ECM is a variable horsepower motor.
Refer to Selectworks Schedule.
FLA = Full load amperage
%
10-20-11
kW MBH
5.3 18
GPM l/s
5
4
3
4.7 16
3PX NVMUJDJSDVJU
kW MBH
8.8 30
.32
.25
.19
2 .13
1.5 .09
7.3 25
l/s
.32
.25
.19
.13
1.5 .09
4.1 14
1
GPM
5
4
3
.06
1
5.9 20
3.5 12
.06
0.5 .03
2.9 10
2.3
4.4 15
0.5 .03
8
2.9 10
6
1.2
4
100
47
1.5
200
94
300
142
400
189
500
236
600
283
700
330
$'.
MT
5
100
47
200
94
300
142
400
189
500
236
8BUFS1SFTTVSF%SPQ
17.9 6.0
149 0.60
)&"%-044 8"5&313&4463&%301
Pa in. H2O
249 1.00
447 0.80
$'.
MT
100 0.40
2 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
"*313&4463&%301
1 ROW
6.0 2.0
50 0.20
2 ROW
25 0.10
20 0.08
15 0.06
1 ROW
10 0.04
0.6 0.2
5 0.02
0.3 0.1
2 0.01
0.5
.03
1
2
3 4 5 (1.
.06
.13 .19 .25 .32 MT
8"5&3'-08
100
47
750 $'.
354 MT
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
1. Capacities are in MBH (kW)*.
*Thousands of Btu per hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 110F (61C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
10-20-11
700
330
"JS1SFTTVSF%SPQ
11.9 4.0
U ' $
Factor
600
283
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
%
1.8
kW MBH
7.0 24
GPM l/s
6.2 21
10
7.5
5
3
.63
.47
.32
.19
.13
3PX NVMUJDJSDVJU
kW MBH
13.2 45
GPM l/s
10 .63
7.5 .47
11.7 40
10.3 35
5.3 18
1
.06
.32
.19
.13
.06
8.8 30
4.4 15
7.3 25
0.5 .03
3.5 12
5.9 20
9
1.8
4.4 15
2.9 10
200
94
300
142
400
189
500
236
600
283
700
330
800
378
900
425
1000 $'.
472 MT
200
94
300
142
400
189
500
236
600
283
700
330
8BUFS1SFTTVSF%SPQ
Pa in. H2O
249 1.00
199 0.80
18.0 6.0
149 0.60
12.0 4.0
2 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
"*313&4463&%301
1 ROW
6.0 2.0
1000 $'.
472 MT
50 0.20
2 ROW
25 0.10
20 0.08
15 0.06
1 ROW
10 0.04
0.6 0.2
5 0.02
2 0.01
0.5
.03
1
.06
2
3
.13 .19
5 7.5 (1.
.32 .47 MT
8"5&3'-08
200
94
400
600
189
283
"*3'-08
700 $'.
330 MT
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
1. Capacities are in MBH (kW)*.
*Thousands of Btu per hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 110F (61C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
%
900
425
100 0.40
0.3 0.1
U ' $
Factor
800
378
"JS1SFTTVSF%SPQ
0.5 .03
2.6
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
10-20-11
kW MBH
10.3 35
GPM l/s
10 .63
7.5 .47
5 .32
8.8 30
.19
.13
3PX NVMUJDJSDVJU
kW MBH
17.6 60
GPM l/s
10 .63
7.5 .47
.19
.13
.06
.06
8.8 30
0.5 .03
4.4 15
0.5 .03
5.9 20
700
330
900
425
1100
519
2.9 10
300
142
1500 $'.
708 MT
1300
613
500
236
700
330
900
425
1100
519
1500 $'.
708 MT
"JS1SFTTVSF%SPQ
Pa in. H2O
249 1.00
447 0.80
17.9 6.0
149 0.60
)&"%-044 8"5&313&4463&%301
1300
613
100 0.40
11.9 4.0
"*313&4463&%301
1 ROW
6.0 2.0
2 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
50 0.20
2 ROW
25 0.10
20 0.08
15 0.06
1 ROW
10 0.04
0.6 0.2
5 0.02
0.3 0.1
2 0.01
0.5
.03
1
2
3
.06
.13 .19
8"5&3'-08
5 (1.
.32 MT
300
142
600
900
283
425
"*3'-08
1200 $'.
566 MT
"MUJUVEF$PSSFDUJPO'BDUPST
/05&4
1. Capacities are in MBH (kW)*.
*Thousands of Btu per hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 110F (61C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
$PSSFDUJPOGBDUPSTBUPUIFSFOUFSJOHDPOEJUJPOT
.455 (.459)
.545 (.541)
"MUJUVEF
GU N
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
.636 (.639) .727 (.721) .818 (.820) .909 (.918) 1.00 (1.00) 1.09 (1.10) 1.18 (1.18) 1.27 (1.28) 1.36 (1.36)
%
500
236
8BUFS1SFTTVSF%SPQ
10-20-11
11.7 40
5.9 20
U ' $
Factor
.32
14.7 50
7.3 25
2.9 10
300
142
'BO1PXFSFE5FSNJOBMTo
/-PX1SPGJMF4FSJFT
Furnish and install /BJMPS .PEFM 4FSJFT / -PX 1SPGJMF
7BSJBCMF7PMVNF1BSBMMFM'BO1PXFSFE5FSNJOBM6OJUT of the sizes
and capacities as indicated on the drawings. Units shall be pressure
independent with (pneumatic, analog electronic, digital) controls.
The entire terminal unit shall be designed and built as a
single unit. The units shall be provided with a primary variable air
volume damper that controls the air quantity in response to a
(thermostat or digital controller/zone sensor). The units shall also
include a fan that sequences on and off in response to the (thermostat
or digital controller/zone sensor). The space limitations shall be
reviewed carefully to ensure that all units will fit into the space allowed.
Unit casings shall be 20 ga. (1.00) galvanized steel. Unit
shall be fully lined with fiberglass insulation which shall be 1/2"
(13) thick dual density insulation complying with NFPA 90 for fire and
smoke resistivity and UL 181 for erosion. Any cut edges of insulation
shall be coated with NFPA 90 approved sealant.
The terminal casing shall have full size bottom access
panels for easy access to motor and blower assembly and for
maintenance and replacement of parts without disturbing duct
connections. Access panels shall be attached to casing with (screws,
1/4 turn fasteners).
Units shall have round or rectangular inlets for the primary
air connections and shall have a minimum 6" (152) deep inlet duct
collar for field connection. Models with no heat or electric heat shall
have rectangular outlets suitable for flanged duct connections.
Models with hot water coils shall have an induction inlet designed to
accept flanged hot water coils. Duct connection to hot water coil shall
be flanged ducts. Casing shall have mounting area for hanging by
sheet metal straps from a concrete slab.
The damper shall be round or rectangular and constructed
of laminated 20 ga. (1.00) galvanized steel with a peripheral gasket
and a solid steel 1/2" (13) diameter shaft, pivoted in self-lubricating
bronze oilite bearings. Damper leakage shall not exceed 2% of the
terminal rated airflow at 3" w.g. (746 Pa) inlet static pressure.
Entire terminal unit shall be factory assembled with
(pneumatic, analog electronic) controls. All components including all
controls except the room (thermostat or zone sensor) and
(pneumatic piping, field wiring) shall be factory installed and
mounted with the unit. Digital controls shall be supplied by BAS
controls contractor. Digital controls are optionally factory mounted
and wired.
Provide a (pneumatic, analog electronic, digital) flow
control device that will limit the maximum and minimum airflow to that
scheduled on the drawings. Control of the terminal unit shall be
pressure independent.
(The sequence of operation should be described here, if
not part of the temperature controls specifications).
Blower casings shall be constructed of heavy gauge
coated steel. Blower wheel shall be forward curved centrifugal type,
dynamically balanced and driven by direct drive, single speed split
capacitor motor(s). Motor(s) shall be suitable for 120 or 208 or 240
or 277 volt single phase power. Motors shall have built-in overload
protection, bearings capable of low speed oiling, permanently oiled
bearings and be of an anti-backward rotation design. Fan assembly
shall be mounted so as to isolate the casing from the motor and
blower vibration at no less than four points. Isolation shall be
supplied at the motor and at the blower mounting points. A gasketed
backdraft damper shall be included on the fan discharge to reduce
primary air leakage back into the plenum space.
%
A solid state SCR fan speed controller sized and designed
for the specific blower motor combination shall be provided to allow
infinitely adjustable fan speed from the minimum voltage stop to the
line voltage signal to the motor. A minimum voltage stop shall be
employed to ensure that fan cannot run in stall mode.
Units shall incorporate a single point electrical and/or
pneumatic connection for the entire unit. All electrical components
shall be ETL listed or recognized and installed in accordance with the
National Electrical Code. All electrical components shall be mounted
in a control box. The entire assembly shall be ETL listed and labeled
to meet UL 1995 and CSA C22.2 No. 236.
All sound data shall be compiled in an independent
laboratory and in accordance with the latest version of AHRI 880. All
units shall be AHRI certified and bear the AHRI certification label.
Unit maximum radiated and discharge sound power levels
with fan only and 0.25" w.g. (63 Pa) discharge static pressure shall
not exceed the values in Tables 1 and 2 at the specified airflow. No
credit or reduction shall in any way be considered for room, plenum,
ceiling, downstream duct, elbows and/or similar item effects.
"JSGMPX
6OJU
4J[F
DGN
MT
2
3
4
550
700
825
260
330
389
5BCMF
58
60
61
56
60
61
50
55
56
46
47
47
38
38
39
6OJU
4J[F
DGN
MT
2
3
4
550
700
825
260
330
389
5BCMF
65
68
69
57
65
65
56
58
58
55
59
61
50
54
56
41
47
49
43
50
50
Unit maximum radiated and discharge sound power levels
with 100% primary air and fan off at 1.0" w.g. (249 Pa) inlet pressure
and 0.25" w.g. (63 Pa) discharge static pressure shall not exceed the
values in Table 3 and 4 at the specified airflow. No credit or reduction
shall in any way be considered for room, plenum, ceiling,
downstream duct, elbows and/or similar item effects.
6OJU
*OMFU
4J[F
"JSGMPX
DGN
MT
2 08
700
3 10
1100
4 14 x 08 1600
330
519
755
5BCMF
6OJU
*OMFU
4J[F
71
69
70
59
61
59
50
54
53
43
46
48
40
39
44
32
35
41
MT
2 08
700
3 10
1100
4 14 x 08 1600
330
519
755
5BCMF
61
66
66
57
62
64
53
55
56
41
47
49
36
41
49
10-28-11
015*0/4
&MFDUSJD)FBU
.PEFM/&
4UBHFE
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQIT
1SPQPSUJPOBM)FBU 4$3
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQIT
Furnish and install /BJMPS.PEFM4FSJFT/&-PX1SPGJMF
7BSJBCMF 7PMVNF 1BSBMMFM 'BO 1PXFSFE 5FSNJOBM 6OJUT with
integral electric heat of the sizes and capacities as indicated on the
drawings. Units shall be pressure independent with (pneumatic,
analog electronic, digital) controls.
An electric heater shall be factory mounted and pre-wired as
an integral package with the fan powered terminal unit. Heaters shall
be sized as shown on the drawings. The entire assembly including the
electric heater shall be ETL listed for zero clearance and so labeled
and shall meet all requirements of the latest National Electrical Code,
(CSA C22.2 No.236). The unit shall have a single point electrical
and/or pneumatic connection (dual point electrical on 600V). Heater
casing and panel shall be a minimum of 20 ga. (1.00) galvanized steel.
Each heater shall be complete with automatic reset high limit thermal
cut-outs, control voltage transformer as required, ground terminal,
fan relay for interlocking the heater and fan and high grade nickel
chrome alloy wire.
Element wires shall be supported by ceramic isolators. Each heater shall
be supplied with factory supplied and pre-wired branch circuit fusing as
required by NEC and UL. Circuiting and fusing shall also be in
accordance with the circuiting requirements as shown on the plans.
Additional accessories shall include (control transformer, circuit
fusing, disconnect switch, pneumatic electric switches) for heater
control.
Heater shall be capable of providing proportional control of heater
capacity from an input signal of 4 20 mA, 2 10 VDC or 0 10 VDC.
10-28-11
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQIT
Furnish and install /BJMPS.PEFM4FSJFT/&-PX1SPGJMF
7BSJBCMF 7PMVNF 1BSBMMFM 'BO 1PXFSFE 5FSNJOBM 6OJUT with
integral electric heat of the sizes and capacities as indicated on the
drawings. Units shall be pressure independent with (pneumatic,
analog electronic, digital) controls.
An electric heater shall be factory mounted and pre-wired as
an integral package with the fan powered terminal unit. Heaters shall
be sized as shown on the drawings. The entire assembly including the
electric heater shall be ETL listed for zero clearance and so labeled
and shall meet all requirements of the latest National Electrical Code,
(CSA C22.2 No.236). The unit shall have a single point electrical
and/or pneumatic connection (dual point electrical on 600V). Heater
casing and panel shall be a minimum of 20 ga. (1.00) galvanized steel.
Each heater shall be complete with automatic reset high limit thermal
cut-outs, control voltage transformer as required, ground terminal, fan
relay for interlocking the heater and fan and high grade nickel chrome
alloy wire.
Element wires shall be supported by ceramic isolators. Each heater shall
be supplied with factory supplied and pre-wired branch circuit fusing as
required by NEC and UL. Circuiting and fusing shall also be in
accordance with the circuiting requirements as shown on the plans.
Additional accessories shall include (control transformer, circuit
fusing, disconnect switch, pneumatic electric switches) for heater
control.
The SCR controller shall contain a discharge temperature sensor
capable of limiting leaving air temperature to a user defined setpoint.
The SCR controller shall pulse the coil to maintain zone demand
while providing the set maximum discharge air temperature. Upon
measuring a discharge air temperature above the user defined
setpoint, the controller shall reduce heater capacity to maintain
maximum allowable discharge air temperature. The discharge air
temperature setpoint shall be adjustable from 80 100F (27 149C)
by use of a controller mounted potentiometer.
)PU8BUFS)FBUJOH$PJMT
.PEFM/8
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQIT
Furnish and install /BJMPS .PEFM 4FSJFT /8 -PX
1SPGJMF 7BSJBCMF 7PMVNF 1BSBMMFM 'BO 1PXFSFE 5FSNJOBM 6OJUT
with integral hot water coils of the sizes and capacities as indicated
on the drawings. Units shall be pressure independent with
(pneumatic, analog electronic, digital) controls.
A hot water coil shall be factory mounted as an integral
package with the fan powered terminal unit. Hot water coils shall be
sized as shown on the drawings. The entire assembly including the
hot water coil shall be ETL listed, labeled and shall meet all
requirements of the latest National Electrical Code (CSA C22.2
No.236). The unit shall have a single point electrical and/or
pneumatic connection. Access panels on the bottom of the unit shall
permit easy access to the coil for inspection and cleaning. Coils shall
be 1 or 2 row as required and heating capacities shall be as shown
on the plans. Coils shall have aluminum plate fins spaced 10 per inch
and bonded to 1/2" (13) O.D. copper tubes. Copper connections
%
Furnish and install /BJMPS.PEFM4FSJFT/&-PX1SPGJMF
7BSJBCMF 7PMVNF 1BSBMMFM 'BO 1PXFSFE 5FSNJOBM 6OJUT with
integral electric heat of the sizes and capacities as indicated on the
drawings. Units shall be pressure independent with (pneumatic,
analog electronic, digital) controls.
An electric heater shall be factory mounted and pre-wired as
an integral package with the fan powered terminal unit. Heaters shall
be sized as shown on the drawings. The entire assembly including the
electric heater shall be ETL listed for zero clearance and so labeled
and shall meet all requirements of the latest National Electrical Code,
(CSA C22.2 No.236). The unit shall have a single point electrical
and/or pneumatic connection (dual point electrical on 600V). Heater
casing and panel shall be a minimum of 20 ga. (1.00) galvanized steel.
Each heater shall be complete with automatic reset high limit thermal
cut-outs, control voltage transformer as required, ground terminal, fan
relay for interlocking the heater and fan and high grade nickel chrome
alloy wire.
Element wires shall be supported by ceramic isolators. Each heater shall
be supplied with factory supplied and pre-wired branch circuit fusing as
required by NEC and UL. Circuiting and fusing shall also be in
accordance with the circuiting requirements as shown on the plans.
Additional accessories shall include (control transformer, circuit
fusing, disconnect switch, pneumatic electric switches) for staging
the heater.
shall be sweat. All coils shall be tested at a minimum of 350 psi (2.4
MPa) under water to produce a guaranteed working pressure of 300
psi (2.1 MPa). Controls and valves for the hot water coils shall be
field mounted. Heating coils shall be located on the induction side of
the fan.
-JOFS
4UFSJ-JOFS
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQI
Unit casings shall be 20 ga. (1.00) galvanized steel. Unit
shall be fully lined with non-porous, sealed liner which complies with
NFPA 90A and UL 181. Installation shall be 1/2" (13) minimum
thickness, 4 lb./cu. ft. (64 kg/m3) density with reinforced aluminum
foil-scrim-kraft (FSK) facing. All cut edges shall be secured with steel
angles or end caps to encapsulate edges and prevent erosion.
Insulation shall be Nailor Steri-Liner or equal.
'JCFS'SFF-JOFS
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQI
Unit casings shall be 20 ga. (1.00) galvanized steel. Unit
shall be fully lined with a non-porous closed cell elastomeric foam
liner which complies with NFPA 90A, ASTM E84 and UL 181.
Installation shall be 3/8" (10) minimum thickness and secured to the
interior of the terminal with mechanical fasteners. No fiberglass is
permitted. Insulation shall be Nailor Fiber-Free Liner or equal.
.PUPS
&$.
4VCTUJUVUFUIFGPMMPXJOHQBSBHSBQI
Blower casings shall be constructed of heavy gauge
coated steel. Blower wheel shall be forward curved centrifugal type,
dynamically balanced and driven by Electronically Commutated
Motor(s). Motor(s) shall be suitable for 120 or 208 or 240 or 277 volt
single phase power. Fan airflow volume shall be factory set. Fan
assembly shall be mounted so as to isolate the casing from the motor
and blower vibration at no less than four points. Isolation shall be
supplied at the motor and at the blower mounting points. A gasketed
backdraft damper shall be included on the fan discharge to reduce
primary air leakage back into the plenum space.
%
11-1-11
&YQMBOBUJPOPG/$-FWFMT
3BEJBUFE4PVOE
Table E1 of Appendix E provides typical radiated sound
attenuation values for three types of ceiling: Type 1 Glass
Fiber; Type 2 Mineral Fiber; Type 3 Solid Gypsum Board.
Since Mineral Fiber tile ceilings are the most common
construction used in commercial buildings, these values have
been used to tabulate Radiated NC levels.
The following table provides the calculation method for the
radiated sound total attenuation values based on AHRI Standard
885-2008.
Environmental Effect
Ceiling/Space Effect
5PUBM"UUFOVBUJPO%FEVDUJPO
9-30-11
0DUBWF#BOE
2
16
1
18
0
20
0
26
0
31
0
36
%JTDIBSHF4PVOE
Table E1 of Appendix E provides typical discharge sound
attenuation values for three sizes of terminal unit.
1. Small box; Less than 300 cfm (142 l/s)
[Discharge Duct 8" x 8" (203 x 203)].
2. Medium box; 300 700 cfm (142 - 330 l/s)
[Discharge Duct 12" x 12" (305 x 305)].
3. Large box; Greater than 700 cfm (330 l/s)
[Discharge Duct 15" x 15" (381 x 381)].
These attenuation values have been used to tabulate Discharge
NC levels applied against the terminal airflow volume and not
terminal unit size.
The following tables provide the calculation method for the
discharge sound total attenuation values based on AHRI
Standard 885-2008.
4NBMM#PY
DGN
0DUBWF#BOE
Environmental Effect
5 ft. (1.5 m) 1" (25) Duct Lining
Branch Power Division (1 outlet)
5 ft. (1.5 m), 8 in. dia. (203) Flex Duct
End Reflection
Space Effect
5PUBM"UUFOVBUJPO%FEVDUJPO
2
2
0
5
10
5
1
6
0
10
5
6
0
29
0
21
0
9
0
18
0
12
0
10
0
12
0
19
20
7
0
25
0
19
1
8
.FEJVN#PY
oDGN
0DUBWF#BOE
Environmental Effect
5 ft. (1.5 m) 1" (25) Duct Lining
Branch Power Division (2 outlets)
5 ft. (1.5 m), 8 in. dia. (203) Flex Duct
End Reflection
Space Effect
5PUBM"UUFOVBUJPO%FEVDUJPO
2
2
3
5
10
5
1
4
3
10
5
6
0
20
3
21
0
9
0
14
3
12
0
10
-BSHF#PY
DGN
0DUBWF#BOE
Environmental Effect
5 ft. (1.5 m) 1" (25) Duct Lining
Branch Power Division (3 outlets)
5 ft. (1.5 m), 8 in. dia. (203) Flex Duct
End Reflection
Space Effect
5PUBM"UUFOVBUJPO%FEVDUJPO
2
2
5
5
10
5
1
3
5
10
5
6
0
12
5
12
0
10
0
10
3
19
2
7
0
9
5
19
2
7
0
20
3
19
1
8
0
18
5
19
1
8
0
17
5
21
0
9
%
4UBOEBSE'FBUVSFT
0QUJPOT
4$3$POUSPM0QUJPO
The SCR (Silicon Controlled Rectifier) option provides
infinite solid state heater control using a proportional
signal (0 10 Vdc or 4 20 mA). This option may be
specified compatible with pneumatic, analog electronic or
digital (DDC) controls.
Time proportional control of the electric heater provides
superior comfort and energy savings. The SCR controller
modulates the heater to supply the exact amount of heat
based upon the zone requirement. Rooms set points are
maintained more accurately, undershoot and overshoot
as associated with staged heat are eliminated, reducing
operation costs.
SCR controllers provide silent operation, as mechanical
staged contactors are eliminated. Zero cross switching of
the thyristor prevents electrical noise.
%
.PEFM
35SE
35SEST
37SE
37SEST
35NE
6OJU
4J[F
2
3
4
5
6
7
1
2
3
4
2
3
5
6
.BYJNVN,JMPXBUUT
7PMU
QIBTF
7PMU
QIBTF
7PMU
QIBTF
7PMU
QIBTF
7.0
8.0
8.0
8.0
8.0
8.0
7.0
10.0
10.0
10.0
7.0
8.0
8.0
8.0
7.0
11.5
11.5
11.5
11.5
11.5
7.0
11.5
11.5
11.5
7.0
11.5
11.5
11.5
7.0
11.5
14.5
14.5
14.5
14.5
7.0
11.5
13.5
14.5
7.0
11.5
14.5
14.5
7.0
11.5
16.0
20.5
30.0
30.0
7.0
11.5
13.5
27.0
7.0
11.5
23.0
27.0
3FDPNNFOEFE4FMFDUJPO
The table above is a quick reference guide, to illustrate the
relationship between electrical power supply, heater capacity
in kilowatts and terminal unit size that are available.
Pneumatic and digital control terminals are available
with up to 3 stages of heat. Analog electronic control
terminals are available with 1 or 2 stages of heat only. A
minimum of 0.5 kW per stage is required.
Voltage and kilowatt ratings are sized so as not to
exceed 48 amps, in order to avoid the NEC code
requirement for circuit fusing.
A minimum airflow of 70 cfm (33 l/s) per kW is required
for any given terminal in order to avoid possible nuisance
tripping of the thermal cutouts.
Discharge air temperature should
not exceed 120F (49C).
)FBUFS4FMFDUJPO$IBSU
Assuming 70F inlet air temperature at heater.
170
140
130
120
110F
45
105F
40
100F
35
110
100
90
.#)
115F
50
160
150
&MFDUSJD)FBUFS4FMFDUJPO
kW x 3160
80
70
95F
30
25
90F
20
85F
60
50
15
80F
40
30
20
10
5
10
0
0
0
500
1000
1500
2000
2500
3000
3500
4000
"*3'-08 $'.
%
L8
%JTDIBSHF"JS5FNQFSBUVSF
1OFVNBUJD
1SFTTVSF%FQFOEFOUpneumatic air terminal actuators are
controlled directly by branch line pressure signals from the
room thermostat. They do not compensate for static
pressure changes immediately upstream of the terminal.
Consequently, the thermostat is a damper blade positioner
rather than a flow regulator.
"OBMPH&MFDUSPOJD
The analog electronic controls provide pressure
independent control. The components are matched and
calibrated and provide regulated airflow in response to
the electronic room thermostat, which is furnished as a
part of the control package. Minimum and maximum
airflow settings are adjusted at the thermostat, using a
digital voltmeter. It is not necessary to adjust flow setting
at the terminal in the ceiling space.
The new range of Nailor analog electronic controls utilize
the 'Diamond Flow' multi-point averaging sensor as
standard for accurate flow measurement.
The electronic thermostat has a fixed 2F proportional
band regardless of minimum or maximum velocity set
points and provides a linear reset function. Thermostat
has a built-in thermometer and set point indicator. The
electronic controller/actuator features an on-board flow
transducer.
Electric actuators are not spring return devices (there is
no normally open or normally closed action). If there is a
loss of power to the terminal, the damper will remain in
the position it was in at the time of power failure. All
electric components use low voltage (24 volt) controls. A
step down transformer is provided as standard.
%JSFDU%JHJUBM$POUSPMT
%
/BJMPS*OEVTUSJFT'BO1PXFSFE5FSNJOBMTare generic
in nature and compatible with all DDC controls currently
available.
/BJMPS can supply and mount its own 'Diamond Flow'
multi-point averaging flow sensor.
$FOUSBM4ZTUFN0Ot0DDVQJFE$ZDMF
0DDVQJFE$ZDMF
AI R
IM
AR
Y
PR
CFM INCREASE
HEATING COIL
TEMPERATURE
SETPOINT
MINIMUM
+ 2F
(+1.1C)
D
AIR
COLD
HOT
$FOUSBM4ZTUFN0GGt6OPDDVQJFE$ZDMF
/JHIU4FU#BDL PQU
CFM INCREASE
RECIRCULATED AIR
HEATING COIL
TEMPERATURE
SETPOINT
NO
PRIMARY AIR
1OFVNBUJD4FRVFODF 1SFTTVSF*OEFQFOEFOU
5IFSNPTUBU
"DUJPO
D.A.
R.A.
D.A.
R.A.
%BNQFS
'BJM
1PTJUJPO
NO
NO
NC
NC
&MFDUSJDPS
)PU8BUFS
)FBU0QUJPO
Yes
Yes
Yes
Yes
$PEF
1P3
2P3
3P3
4P3
%
COOLING
TE
LA
CU
CIR
1OFVNBUJD0QUJPOT
MAXIMUM
MIXING
RE
TOTAL AIR
$PEF
4FRVFODF/PUFT
.PSOJOH8BSN6Q
A duct stat is mounted in the terminal inlet. Upon sensing a
central system supply air temperature above 77F (25C),
the primary air damper drives to a full open position.
Optional terminal supplementary heat is locked out. Upon
sensing cool air, the terminal reverts to daytime operation.
"VYJMJBSZPS0OPGG)PU8BUFS)FBU
Control relay provides a 24 VAC output signal for
operation of valve (10 VA maximum by others).
1SPQPSUJPOBM)PU8BUFS)FBU
Thermostat heating output provides an 0 10 Vdc
reverse acting control signal to proportional valve (by
others). Closed at 0 Vdc and fully open at 10 Vdc (10 mA
maximum).
/JHIU$ZDMF
An airflow switch de-energizes fan upon loss of primary
(central system) air. Upon a call for heat, the thermostat
will override the airflow switch and cycle the unit fan
followed by any supplementary heat intermittently to
maintain day set point temperature.
"VUP/JHIU4IVUEPXO
An airflow switch de-energizes fan upon loss of primary
%
A1
A2
A3
A4
A5
A6
A7
A8
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B23
B24
B25
B26
B13
B17
B18
B15
B16
B22
1SFTTVSF%FQFOEFOU
1OFVNBUJD
0DDVQJFE$ZDMF
1. Upon start-up of the central system, cold air is
delivered to the space through the primary air section at
the flow rate dictated by the thermostat. The reset
controller compensates for any variation in inlet static
pressure. The fan remains off. A backdraft damper at the
fan outlet prevents cold air from flowing back through the
fan into the ceiling space.
IR
SETPOINT
$FOUSBM4ZTUFN0Ot1SFTTVSF*OEFQFOEFOU
0DDVQJFE$ZDMF
PR
COOLING
IM
RECIRCULATED AIR
CFM INCREASE
AR
YA
IR
MAXIMUM
HEATING COIL
TEMPERATURE
RY
A
1OFVNBUJDBOE"OBMPH&MFDUSPOJD
RECIRCULATED AIR
IMA
1SFTTVSF*OEFQFOEFOU
$FOUSBM4ZTUFN0Ot1SFTTVSF%FQFOEFOU
0DDVQJFE$ZDMF
PR
CFM INCREASE
SETPOINT
HEATING COIL
TEMPERATURE
+ 2 F
(+ 1.1C)
MINIMUM
$FOUSBM4ZTUFN0GGt1SFTTVSF
%FQFOEFOU*OEFQFOEFOUo6OPDDVQJFE$ZDMF
RECIRCULATED AIR
1. Night Setback
The space temperature may be reset to a lower setting
through a change in main air pressure. The fan and optional
heat will be energized through the P.E. switch furnished
with the unit while the central system remains off.
2. A normally open damper configuration may be utilized
for a central morning warm-up sequence by removing
main air to the terminal.
CFM INCREASE
1OFVNBUJD0QUJPOT
HEATING COIL
TEMPERATURE
SETPOINT
NO
PRIMARY AIR
%
1OFVNBUJD$POUSPM$PNCJOBUJPOT
4VHHFTUFE3BOHF4FUUJOHT
1SFTTVSF
1SFTTVSF
5IFSNPTUBU 5FSNJOBM
%FQFOEFOU *OEFQFOEFOU
"DUJPO
%BNQFS
1SJNBSZ"JS
$PPMJOH3BOHF
.BYo.JO
D.A.
R.A.
D.A.
R.A.
D.A.
R.A.
N.C.
N.O.
N.O.
N.O.
N.C.
N.C.
15
5
13
3
13
3
10 psi
10 psi
8 psi
8 psi
8 psi
8 psi
'BO1&
4XJUDI
0GG0O /PSNBM
4FUUJOH 1PTJUJPO
12 10/N.C.
9 11/N.O.
10 8/N.C.
6 8/N.O.
10 8/N.C.
6 8/N.O.
&MFDUSJD)FBUJOH$PJM
1&0GGo0O
TU
OE
SE
4UBHF 4UBHF 4UBHF
10
11
8
8
8
8
$PEF
8
9-7
8-6
13 12 - 14 13 - 15
5
7-4
6-3
11 9 - 12 10 - 13
5
7-4
6-3
11 9 - 12 10 - 13
D1
D2
1P3
2P3
3P3
4P3
/PUFT
** A normally closed (N.C.) P.E. switch fails on. A normally open (N.O.) P.E. switch fails off.
Hot water coil valves (by others) should be selected to modulate through the desired heating range in sequence with the cooling range.
"OBMPH&MFDUSPOJD4FRVFODFT
%FTDSJQUJPO
$PEF
4FRVFODF/PUFT
.PSOJOH8BSN6Q
A duct stat is mounted in the terminal inlet. Upon sensing a central
system supply air temperature above 77F (25C), the primary air
damper drives to a full open position. Fan and optional supplementary
heat are locked out. Upon sensing cool air, the terminal reverts to
daytime operation.
A1
A2
A3
A4
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B23
B24
B25
B26
B13
B17
B18
B15
B16
B22
"VUP$IBOHFPWFS
Upon a call for heat, the thermostat will cycle the unit-fan followed by any
supplementary heat intermittently to maintain day set point temperature.
"VUP/JHIU4FUCBDL
0QUJPOBM4USBUFHJFT
/JHIU$ZDMF
%
'JCFS'SFF-JOFS
Nailors Fiber-Free liner is 3/4" (19) thick, closed cell elastomeric foam which totally
eliminates fiberglass. The liner has excellent thermal insulating characteristics. The foam
does not absorb water, reducing the likelihood of mold or bacterial growth.
The Fiber-Free liner surface is smooth, so that dirt and debris wont accumulate, durable,
erosion resistant and washable.
Complies with the following standards and tests:
NFPA 90A Supplementary materials for air distribution systems.
ASTM E84 and UL 181 (25/50) Smoke and Flame spread.
ASTM C1071, G21, G22. No bacterial or fungal growth.
Acoustical attenuation of radiated sound is reduced compared with standard dual density
fiberglass insulation.
Fiber-Free liner.
4UFSJ-JOFS
13/16" (21) THICK
FSK LINED
INSULATION
STEEL
END
CAPS
INSULATED
CORNER
POSTS
FULL LENGTH
STEEL INSERTS
4PMJE.FUBM-JOFS
Nailor also offers a solid inner metal liner that completely isolates the standard insulation from the airstream within the terminal
mixing chamber. Solid metal liners offer the ultimate protection against exposure of fiberglass particles to the airstream, all but
eliminating the possibility of punctures exposing fiberglass. This option is also resistant to moisture. Fully performance tested for
our clients, the "Stealth" series terminals with solid metal liner feature the tuned induction attenuation design described above
for Steri-Liner and maintain catalogued radiated sound level ratings. No other terminal manufacturer can make that claim.
1FSGPSBUFE.FUBM-JOFS
Provides additional security and retains standard dual density fiberglass insulation or optional Steri-Liner insulation reducing
possibility of long term erosion or breakdown.
%
)FMQFOTVSF/&$DMFBSBODFSFRVJSFNFOUT
3FEVDFTGPPUQSJOU
D
chance of clear areas already. This again serves to keep the
equipment narrow to fit in the tightest of locations within the
ceiling cavity.
-PX5FNQFSBUVSF$POTUSVDUJPO
Nailor offers series flow (constant volume) fan powered terminal
units with low temperature construction for applications involving
low temperature/cold air distribution systems. The fan powered
terminal unit is ideal for use with low temperature primary air 40
48F (4 9C) supplied to the terminal from chilled water/ice
storage systems. These low temperature system designs are
feasible where off-peak utility rates encourage their use. For
instance, ice can be made at night using cheaper power and then
used during occupied hours to produce cold air.
The terminal is designed to both handle the low temperature
primary air without condensation and effectively mix the cold
supply air with warm induced plenum air, resulting in a uniform
discharge temperature. It is common practice to set the fan
airflow higher than the maximum primary airflow setting in order
to temper the air when used with conventional diffusers in order
to optimize performance and eliminate any risk of dumping.
$POTUSVDUJPO'FBUVSFT
Thermally isolated inlet collar eliminates the risk of
condensation forming on the terminal casing inlet.
Integral perforated mixing baffle on the damper discharge
improves mixing efficiency, reduces stratification and improves
discharge temperature equalization in the discharge duct.
Steri-Liner insulation construction provides a foil vapor/thermal
%
WARM
UNIFORM
PLENUM AIR DISCHARGE
AIR
TEMPERATURE
HIGH
EFFICIENCY
MIXING
CHAMBER
THERMALLY
ISOLATED
INLET COLLAR
COLD
PRIMARY AIR
STERI-LINER
LOW TEMPERATURE
INSULATION
PERFORATED
MIXING
BAFFLE
Models:
33SZ
No Heat
33SZE
Electric Heat
33SZW
Model 33SZ
FEATURES:
Standard height and low-profile
designs available.
Sensible cooling coil on the induced
air inlet handles zone sensible load.
Opposite side to controls location. Coil
is constructed of aluminum ripple fins
(10 FPI) and 1/2" (13) copper tubes.
Hand of coil is determined looking in
direction of airflow.
16 ga. (1.6) galvanized steel channel
frame with 20 ga. (1.0) casing
components. Sizes 40 and 50 only.
20 ga. (1.0) galvanized steel casing
construction. Size 30.
16 ga. (1.6) galvanized steel inclined
opposed blade damper. 45 rotation.
CW to close. Sizes 30, 40 and 50.
Galvanized steel drip pan integral to
sensible coil.
Discharge opening designed for
flanged duct connection.
Controls mounted as standard on RH
side as shown. Terminals ordered with
LH controls (optional) are inverted and
discharge duct hanging elevation will
therefore change.
Single point electrical connection.
Access panels top and bottom.
5-9-16
Electrical:
Left Hand Controls enclosure
Toggle disconnect switch.
FN2 90 line voltage enclosure.
FN3 Remote line voltage enclosure.
Motor fusing.
Others:
Hanger brackets.
1/4-turn fasteners (access panel).
The 33SZ Series Fan Powered Chilled Water Terminal Units (FPCWTU) enhance Nailors already efficient and flexible Series
Fan Terminal Unit product line. A series fan powered terminal unit, the 33SZ incorporates a cooling induction coil to use in
conjunction with a DOAS (dedicated outdoor air system). Useful in a variety of commercial and educational applications, like
classrooms, office space, laboratories and auditoriums, the 33SZ provides a flexible, industry familiar unit that excels at zone
sensible cooling while the dedicated outdoor air inlet delivers ASHRAE 62.1 ventilation requirements.
OPTIONS:
CW Coil:
2-Row, 4-Row and 6-Row
Right or Left Hand coil connections.
Condensate Sensor.
Liner:
Fiber-free liner.
Perforated metal liner.
Solid metal liner.
Steri-liner.
Steri-liner w/perforated liner.
Filter:
1" (25) Throwaway.
2" (51) Pleated MERV 8.
2" (51) Pleated MERV 13.
Ducted Return Filter Rack.
D13
1"
(15)
1/2"
(13)
IH
IW
OPTIONAL FILTER
INTEGRAL
DRIP PAN
RH COIL
CONNECTIONS
2"
(51)
DH
W
DIA. =
NOM. 1/8" (3)
FAN
PRIMARY/
DEDICATED
OUTDOOR
AIR
DW
A
MULTI-POINT
FLOW
SENSOR
DRIVESHAFT
5 3/4"
(146)
14" (356)
16" (406)
L
PRIMARY/
DEDICATED
OUTDOOR
AIR
PRIMARY
CONTROLS
ENCLOSURE
FAN
CONTROLS
ENCLOSURE
2
6"
(152)
Dimensional Data
Unit
Size
30
D14
Inlet
Size
Cooling
Coil
IW x IH
Outlet
Discharge
DW x DH
2 Row: 5 18 (130)
4, 5, 6, 8
26 12 11 40 14
8
2
36 X 8 34
12 38 X 6 78
(102, 127,
7 516 (186)
(673) (279) (1022) (203) (51) (914 X 222) 4 Row:
(314 X 175)
152, 203)
6 Row: 9 12 (241)
CW Coil O.D.
Sweat Connections
Filter
Size
38 X 10
(965 X 254)
Unit
Size
No. of Row
2, 4, & 6
30
7/8" (22)
5-9-16
1 1/2"
(38)
IW
OPTIONAL FILTER
IH
RH COIL
CONNECTIONS
INTEGRAL
DRIP PAN
SENSIBLE COOLING COIL
B
W
2
DIA. =
NOM.
- 1/8"
(3)
PRIMARY/
FAN
DEDICATED
OUTDOOR
AIR
DW
DRIVESHAFT
DH
1" (25)
MULTI-POINT
FLOW SENSOR
5 3/4"
(146)
14" (356)
14" (356)
PRIMARY
AIR VALVE
CONTROLS
ENCLOSURE
PRIMARY/
DEDICATED
OUTDOOR H
2
AIR
11" (279)
18" (457)
HINGED LINE
VOLTAGE
FAN
CONTROLS
ENCLOSURE
H1" (25)
6"
(152)
Dimensional Data
Unit
Size
40
50
5-9-16
Inlet
Size
Cooling
Coil
IW x IH
Outlet
Discharge
DW x DH
4, 5, 6, 8, 10
18 18
36 3 12
31 X 15
9 18 X 10 14
(102, 127, 152,
(457) (457) (914) (89) (787 X 381) 2 Row: 5 18 (130) (232 X 260)
203, 254)
4 Row: 7 516 (186)
5, 6, 8, 10, 12
26 18
41
5
36 x 15
6 Row: 9 12 (241) 13 18 X 11 14
(127, 152, 203,
(660) (457) (1041) (127) (914 X 381)
(232 X 286)
254, 305)
Filter
Size
33 X 16
(838 X 406)
CW Coil O.D.
Sweat Connections
Unit
Size
No. of Row
2, 4, & 6
40
50
7/8" (22)
38 X 16
(965 X 406)
D15
Model 33SZW
Available in one or two row. Coil section
installed on unit discharge. Right hand coil
connection looking in direction of airflow
standard (shown). Left hand is optional.
INTEGRAL
DRIP PAN
1"
(25)
Standard Features:
Coil section installed on unit discharge.
1/2" (13) copper tubes.
Aluminum ripple fins @10 FPI.
DEDICATED
OUTDOOR A
AIR
DRIVESHAFT
FAN CONTROLS
ENCLOSURE
PRIMARY
CONTROLS
ENCLOSURE
HOT WATER
COIL
FAN
PRIMARY/
14" (356)
RH COIL
CONNECTIONS
16" (406)
L
12" (305)
D
H
Coil Rows:
1-Row
2-Row
INTEGRAL
DRIP PAN
1" (25)
W
2
PRIMARY/
HOT WATER
COIL
FAN
DEDICATED
OUTDOOR
AIR
DRIVESHAFT
5 3/4"
(146)
14" (356)
14" (356)
1"
(25)
RH COIL
CONNECTIONS
1"
(25)
12" (305)
D
18" (457)
Dimensional Data
D16
Unit
Size
30
26 12 (673)
11 (279)
40 14 (1022)
1 (25)
24 X 8 34 (610 X 222)
40
18 (457)
36 (914)
16 X 15 (406 X 381)
50
26 (660)
41 (1041)
24 X 15 (610 X 381)
5-9-16
Standard Features:
SENSIBLE COOLING COIL
1"
(25)
M
G
W
PRIMARY/
DEDICATED
OUTDOOR A
AIR
FAN
ELECTRIC
HEATER
FAN CONTROLS
ENCLOSURE
5 3/4" (146)
Single
point
electrical
connection for entire terminal
unit.
DRIVESHAFT
PRIMARY
CONTROLS
ENCLOSURE
14" (356)
1"
1 7/8" (25)
(48)
16" (406)
L
Supply
Voltage
INTEGRAL
DRIP PAN
1"
(25)
G
M
W
2
PRIMARY/
FAN
DEDICATED
OUTDOOR
AIR
ELECTRIC
HEATER
DRIVESHAFT
1" (25)
5 3/4"
(146)
14" (356)
14" (356)
L
15 1/4" (387)
18" (457)
Dimensional Data
Options:
SCR control.
SCR control with discharge
temperature control.
Toggle
disconnect
(includes fan).
Door
interlock
switch.
switch
Unit
Size
30
13 38 x 8 (340 x 203)
40
18 (457)
36 (914)
15 12 (394)
2 12 (64)
10 14 x 10 12 (260 x 267)
50
26 (660)
41 (1041)
22 (559)
4 (102)
14 14 x 11 34 (362 x 298)
disconnect
Quiet contactors.
Main line fusing.
Dust tight construction.
Manual
Reset
thermal cut out.
Positive
switch..
5-9-16
secondary
Pressure
airflow
D17
5 1/2"
(140)
FILTER
RACK
W
DOOR FLAP
OPENING ON
SIDE AND BOTTOM
LATCH
AIRFLOW
MOUNTING
FLANGE
D18
H
1"
(25)
MOUNTING
FLANGE
DESCRIPTION:
The DRFR Ducted Return Filter Rack is an optional
accessory for the Fan Powered Chilled Water
Terminal Model Series 33SZ.
The accessory is required for ducted inlet
applications where a filter is also required and ease
of accessibility is required.
The Ducted Filter Connection features a filter rack,
which accommodates a 1" (25) standard or 2" (51)
optional filter.
Factory mounted on the induced air inlet of the draw
through water coil section.
A piano-hinged door flap with latch on the side and
bottom of the unit accessory allows for easy removal
and replacement of the filter.
The accessory is provided with a nominally sized
duct connection collar.
Dimensional Data
Unit
Size
Inlet Size
WxH
Filter Size
WxH
30
36 x 8 34 (914 x 222)
38 X 10 (965 X 254)
40
31 x 15 (787 x 381)
33 X 16 (838 X 406)
50
36 x 15 (914 x 381)
38 X 16 (965 X 406)
12-1-14
Unit Size 30
l/s CFM
755 1600
Unit Size 40
MAXIMUM
MAXIMUM
590 1250
661 1400
2 ROW CW
4 ROW CW
6 ROW CW
2 ROW CW
495 1050
4 ROW CW
566 1200
401 850
6 ROW CW
AIRFLOW
AIRFLOW
307 650
472 1000
378 800
212 450
283 600
118 250
189 400
MINIMUM
24
MINIMUM
50
94 200
0.1
25
l/s CFM
1062 2250
0.2
0.3
0.4
0.5
0.6
50
75
100
125
150
DISCHARGE STATIC PRESSURE
0.1
25
0.2
0.3
0.4
0.5
0.6
50
75
100
125
150
DISCHARGE STATIC PRESSURE
Unit Size 50
MAXIMUM
944 2000
2 ROW CW
4 ROW CW
6 ROW CW
826 1750
AIRFLOW
708 1500
Electrical Data
590 1250
472 1000
354
750
236
500
MINIMUM
118
250
0.1
25
0.2
0.3
0.4
0.5
0.6
50
75
100
125
150
DISCHARGE STATIC PRESSURE
NOTES:
The fan curves for the ECM are unlike those for traditional PSC
motors. The ECM is pressure independent and constant
volume in operation at factory or field set point within the
shaded area. When the setpoint is on, or below, the respective
maximum curve, airflow does not vary with changing static
pressure conditions. The motor compensates for any changes in
external static pressure or induced air conditions such as filter
loading.
2-5-16
D19
30
D
FAN POWERED TERMINAL UNITS
6
40
8
10
50
10
12
Primary
Airflow
cfm l/s
225 106
150
71
150
71
90
42
90
42
550 260
400 189
400 189
235 111
190
90
1100 519
700 330
415 196
250 118
190
90
225 106
150
71
150
71
90
42
90
42
550 260
400 189
400 189
235 111
145
68
1100 519
700 330
415 196
290 137
175
83
1400 661
660 311
445 210
335 158
260 123
225 106
150
71
150
71
90
42
90
42
550 260
400 189
400 189
235 111
235 111
1100 519
700 330
700 330
415 196
250 118
1840 868
1100 519
660 311
410 193
375 177
2000 944
1600 755
900 425
445 210
395 186
Fan
Min. inlet
Airflow
Ps
cfm l/s "w.g. Pa
1250 590 0.42 104
1000 472 0.15 37
800 378 0.20 50
500 236 0.06 15
250 118 0.10 25
1250 590 0.12 30
1000 472 0.06 15
800 378 0.10 25
500 236 0.03 6
250 118 0.03 7
1250 590 0.09 22
1000 472 0.01 2
800 378 0.01 2
500 236 0.01 2
250 118 0.01 2
1500 708 0.56 139
1200 566 0.21 52
900 425 0.26 65
600 283 0.08 20
300 142 0.10 25
1500 708 0.31 77
1200 566 0.07 17
900 425 0.09 22
600 283 0.03 7
300 142 0.02 5
1500 708 0.09 22
1200 566 0.02 5
900 425 0.01 2
600 283 0.01 2
300 142 0.01 2
1500 708 0.02 5
1200 566 0.01 2
900 425 0.01 2
600 283 0.01 2
300 142 0.01 2
2000 944 0.51 127
1600 755 0.18 45
1200 566 0.24 60
800 378 0.08 20
500 236 0.10 25
2000 944 0.12 30
1600 755 0.04 10
1200 566 0.09 22
800 378 0.02 5
500 236 0.04 10
2000 944 0.12 30
1600 755 0.02 5
1200 566 0.06 15
800 378 0.01 2
500 236 0.01 2
2000 944 0.25 62
1600 755 0.08 20
1200 566 0.01 2
800 378 0.01 2
500 236 0.01 2
2000 944 0.09 22
1600 755 0.06 15
1200 566 0.01 2
800 378 0.01 2
500 236 0.01 2
Fan
Only
44
38
33
44
38
34
44
38
33
37
33
25
37
33
25
37
33
33
37
36
25
25
38
33
25
38
33
25
38
33
33
38
33
25
37
33
25
-
Min.
Ps
44
38
33
44
38
30
44
38
30
38
33
25
20
35
31
24
37
34
30
37
36
25
38
33
24
38
33
25
21
36
31
29
37
31
23
36
30
23
-
RADIATED
0.5" w.g. 1.0" w.g.
(125 Pa) (250 Pa)
48
48
44
44
40
40
30
30
26
28
46
46
43
43
38
38
32
35
28
29
49
49
43
43
39
39
31
32
28
29
45
*
44
44
38
38
35
36
32
32
44
44
40
40
36
37
31
32
28
28
45
45
40
41
37
37
31
33
28
29
44
45
40
40
36
37
31
32
26
29
46
*
40
40
33
34
28
28
23
24
46
46
40
40
34
36
29
30
24
28
46
46
40
41
35
37
29
32
24
28
46
48
40
41
34
35
29
30
24
26
46
49
41
44
33
35
29
30
24
28
1.5" w.g.
(375 Pa)
49
44
40
31
28
46
41
39
38
31
49
44
39
33
30
45
44
38
36
33
45
41
38
33
29
46
41
38
34
29
46
41
37
33
30
48
40
36
29
26
48
41
37
32
30
48
41
39
34
30
49
41
37
32
30
50
45
36
32
31
D20
5-6-16
30
40
8
10
50
10
12
225
150
150
90
90
550
400
400
235
190
1100
700
415
250
190
225
150
150
90
90
550
400
400
235
145
1100
700
415
250
175
1400
660
445
335
260
225
150
150
90
90
550
400
400
235
235
1100
700
700
415
250
1840
1100
660
410
375
2000
1600
900
445
395
106
71
71
42
42
260
189
189
111
90
519
330
196
118
90
106
71
71
42
42
260
189
189
111
68
519
330
196
118
83
661
311
210
158
123
106
71
71
42
42
260
189
189
111
111
519
330
330
196
118
868
519
311
193
177
944
755
425
210
186
Fan
Airflow
cfm l/s
1250
1000
800
500
250
1250
1000
800
500
250
1250
1000
800
500
250
1500
1200
900
600
300
1500
1200
900
600
300
1250
1200
900
500
300
1500
1200
900
600
300
2000
1600
1200
800
500
2000
1600
1200
800
500
2000
1600
1200
800
500
2000
1600
1200
800
500
2000
1600
1200
800
500
590
472
378
236
118
590
472
378
236
118
590
472
378
236
118
708
566
425
283
142
708
566
425
283
142
590
566
425
236
142
708
566
425
283
142
944
755
566
378
236
944
755
566
378
236
944
755
566
378
236
944
755
566
378
236
944
755
566
378
236
Min. inlet
Ps
"w.g. Pa 2
0.42 104 83
0.15 37 80
0.20 50 77
0.06 15 65
0.10 25 57
0.12 30 83
0.06 15 79
0.10 25 77
0.03 6 65
0.03 7 57
0.09 22 83
0.01 2 79
0.01 2 77
0.01 2 66
0.01 2 58
0.56 139 82
0.21 52 78
0.26 65 73
0.08 20 66
0.10 25 61
0.31 77 82
0.07 17 78
0.09 22 73
0.03 7 66
0.02 5 61
0.09 22 83
0.02 5 78
0.01 2 77
0.01 2 66
0.01 2 63
0.02 5 82
0.01 2 81
0.01 2 73
0.01 2 71
0.01 2 66
0.51 127 80
0.18 45 76
0.24 60 72
0.08 20 67
0.10 25 62
0.12 30 80
0.04 10 76
0.09 22 72
0.02 5 67
0.04 10 60
0.12 30 80
0.02 5 77
0.06 15 77
0.01 2 66
0.01 2 62
0.25 62 80
0.08 20 77
0.01 2 72
0.01 2 66
0.01 2 62
0.09 22 80
0.06 15 77
0.01 2 72
0.01 2 65
0.01 2 61
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure (Ps) shown
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps
Minimum Ps
Fan Only
3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
83 76 74 73 70 83 83 76 74 73 70 83 83 76 74 73 70 83 83 76 74 72 70 82 83 76 74 72 70
78 71 69 67 64 80 78 71 69 67 64 80 78 71 69 67 64 80 78 71 69 67 64 80 78 71 69 67 64
73 67 65 62 59 76 73 66 65 62 59 76 73 66 65 62 59 76 73 66 65 62 59 76 73 66 65 62 59
62 59 55 52 47 64 61 58 54 51 46 65 61 58 54 51 46 65 61 58 54 51 46 65 62 59 55 51 46
52 52 47 42 33 58 52 52 46 41 32 58 52 52 46 41 32 58 53 52 46 41 32 58 53 53 47 41 32
83 76 74 73 70 83 83 76 74 73 70 83 83 76 74 73 70 83 83 76 74 72 70 83 82 75 73 72 70
78 71 69 67 64 79 78 71 69 67 64 79 77 70 69 66 64 79 77 70 68 66 64 78 77 70 68 66 64
74 67 65 62 59 75 71 66 64 61 58 75 71 66 64 61 58 75 71 66 64 61 58 75 72 66 64 61 58
62 59 55 52 47 64 60 58 54 51 46 65 61 58 55 51 46 66 62 59 55 51 46 67 62 59 55 51 46
52 52 47 42 33 58 51 52 46 41 32 59 53 53 47 42 33 61 56 54 48 43 34 62 58 54 48 44 35
83 76 74 73 70 83 83 76 74 73 70 83 82 76 74 72 70 83 82 75 73 72 70 83 81 75 73 72 70
78 70 69 67 64 79 78 70 69 67 64 79 77 70 69 66 64 79 76 70 68 66 63 78 76 69 68 65 63
73 67 65 62 59 75 71 66 64 61 58 75 71 66 64 61 58 75 71 66 64 61 58 75 71 66 64 61 58
61 59 55 52 47 65 60 58 54 50 45 66 61 58 54 51 46 66 61 59 55 51 46 67 62 59 55 51 46
52 52 47 42 33 57 51 51 46 40 31 58 53 52 47 41 32 59 54 53 47 42 33 60 56 54 48 43 35
77 76 75 72 70 81 78 77 76 73 71 * * * * * * 81 78 77 76 73 71 82 78 77 76 73 71
73 72 71 67 65 78 73 72 71 68 65 78 73 73 71 68 66 78 74 73 71 68 66 78 74 73 71 68 66
67 68 64 60 58 73 67 67 64 61 58 73 67 67 64 61 58 73 67 68 65 61 59 74 68 68 65 61 59
60 61 57 52 47 67 60 61 57 52 47 67 60 61 57 53 47 67 60 61 57 53 47 67 60 61 57 53 48
54 55 49 44 35 62 55 56 51 45 36 63 57 56 51 46 37 63 56 56 51 46 37 63 56 56 51 45 37
77 76 75 72 70 80 75 74 74 70 69 80 76 75 74 71 69 81 77 75 75 71 69 81 77 75 75 71 70
73 72 71 67 65 77 72 72 69 66 64 77 72 72 69 66 64 78 72 72 70 66 65 78 73 72 70 67 65
67 68 64 60 58 72 66 67 63 60 58 73 68 68 64 60 59 74 68 68 64 61 59 75 69 68 64 61 59
60 61 57 52 47 65 59 60 56 52 47 67 61 61 56 52 48 67 61 60 56 52 48 68 61 60 56 52 48
54 55 49 44 35 61 53 54 48 43 33 61 54 54 48 43 34 61 54 54 48 43 34 61 55 54 48 43 34
83 76 74 73 70 83 83 76 74 73 70 83 82 76 74 72 70 83 82 75 73 72 70 83 81 75 73 72 70
73 73 71 68 65 80 74 73 71 68 65 80 75 73 71 68 66 81 76 74 72 69 66 82 77 74 72 69 67
73 67 65 62 59 75 71 66 64 61 58 74 68 68 65 61 59 74 69 67 64 61 58 75 71 66 64 61 58
61 59 55 52 47 65 60 58 54 50 45 66 61 58 54 51 46 66 61 59 55 51 46 67 62 59 55 51 46
55 56 51 46 38 62 55 55 51 46 38 63 56 56 51 46 39 64 57 56 52 47 39 64 57 57 52 47 40
77 76 76 72 70 81 77 76 75 72 70 82 77 76 76 72 70 82 77 76 76 72 70 82 78 77 75 72 70
76 74 73 69 68 81 76 74 73 69 68 81 76 75 73 70 68 81 76 75 73 70 68 82 76 74 72 70 68
67 67 64 61 59 73 67 68 64 61 60 73 67 68 64 61 60 73 68 68 64 61 60 74 68 68 64 61 60
64 63 59 55 51 65 60 61 57 53 48 69 64 64 60 56 52 71 65 64 61 57 53 72 66 65 61 57 53
59 59 55 50 42 65 59 59 54 49 41 66 60 59 55 50 42 67 61 59 55 50 43 67 62 60 55 51 44
78 75 75 72 71 81 78 75 75 72 71 * * * * * * 81 78 75 75 72 71 81 79 75 75 72 72
73 71 69 66 65 77 73 71 69 66 65 77 73 71 69 66 65 77 73 71 69 66 65 78 74 71 69 66 66
67 64 62 58 56 72 66 63 61 58 56 72 66 63 61 58 56 72 67 63 61 58 56 73 67 63 62 58 56
61 58 55 50 44 67 61 58 55 50 44 68 61 58 55 50 44 68 62 59 55 50 44 68 62 59 55 50 45
56 52 48 42 36 62 56 52 48 42 35 62 56 52 48 42 36 62 56 52 48 42 36 62 56 53 48 42 36
78 75 75 72 71 81 78 74 74 71 71 81 78 74 75 72 71 81 78 75 75 72 72 82 79 75 75 72 72
73 71 69 66 65 77 73 70 68 66 65 77 74 70 68 66 65 78 74 70 68 66 66 78 74 71 69 66 66
67 64 62 59 56 72 67 63 62 58 56 72 67 64 62 58 57 73 68 64 62 59 57 74 68 64 62 59 57
62 59 56 52 47 69 64 60 57 52 47 70 65 61 58 53 48 71 66 62 59 54 49 72 67 63 59 56 50
55 53 48 42 36 59 54 51 47 41 35 60 55 52 47 42 36 61 56 52 47 42 36 62 58 52 47 43 37
78 75 76 72 71 79 76 74 74 71 70 80 77 74 74 71 71 81 78 75 74 71 71 81 78 75 75 72 72
73 71 69 66 65 76 72 70 67 65 64 76 73 70 68 65 65 77 73 70 68 65 65 78 74 70 68 66 65
73 67 65 62 59 74 70 65 63 60 58 74 71 65 64 60 58 75 71 66 64 61 58 75 72 66 64 61 58
61 59 55 52 47 65 60 58 54 50 45 66 61 58 54 51 46 66 61 59 55 51 46 67 62 59 55 51 46
57 54 50 45 40 61 57 53 49 44 39 62 57 53 49 45 39 63 58 54 49 45 40 64 59 54 49 46 40
78 75 75 72 72 80 77 74 73 71 71 81 77 74 73 71 71 82 78 75 74 72 72 84 79 75 74 72 72
73 71 69 66 66 76 72 69 67 65 65 77 73 69 67 65 65 77 73 70 68 66 65 78 74 70 68 66 65
67 63 61 58 56 71 65 62 60 57 54 72 66 62 60 57 54 73 67 63 61 58 55 74 68 63 61 58 55
61 58 55 50 43 65 59 56 53 48 41 66 61 57 54 49 42 66 62 57 54 49 43 67 63 58 55 50 44
56 52 48 42 36 60 55 52 47 41 35 61 56 52 47 42 36 63 58 52 47 43 37 64 59 52 47 44 38
77 75 75 72 71 79 76 74 73 71 71 80 77 74 74 71 71 82 79 75 74 72 72 84 80 75 75 72 72
73 71 69 66 65 75 71 69 67 65 64 77 73 70 68 66 65 80 76 72 70 67 67 83 78 73 71 68 68
67 64 61 58 56 70 65 62 60 57 54 72 66 63 61 58 55 73 68 64 62 59 57 75 69 65 63 60 58
60 58 55 50 44 64 60 57 54 49 42 66 61 58 55 50 44 67 62 58 55 50 44 67 62 58 55 50 44
55 52 47 41 36 60 55 51 46 41 34 61 56 51 46 42 35 62 56 51 47 42 35 63 57 51 47 43 36
D
FAN POWERED TERMINAL UNITS
Primary
Airflow
cfm l/s
5-6-16
D21
30
D
FAN POWERED TERMINAL UNITS
6
40
8
10
50
10
12
Primary
Airflow
cfm l/s
225
150
150
90
90
550
400
400
235
190
1100
700
415
250
190
225
150
150
90
90
550
400
400
235
145
1100
700
415
290
175
1400
660
445
335
260
225
150
150
90
90
550
400
400
235
235
1100
700
700
415
250
1840
1100
660
410
375
2000
1600
900
445
395
106
71
71
42
42
260
189
189
111
90
519
330
196
118
90
106
71
71
42
42
260
189
189
111
68
519
330
196
137
83
661
311
210
158
123
106
71
71
42
42
260
189
189
111
111
519
330
330
196
118
868
519
311
193
177
944
755
425
210
186
Fan
Airflow
cfm l/s
1250
1000
800
500
250
1250
1000
800
500
250
1250
1000
800
500
250
1500
1200
900
600
300
1500
1200
900
600
300
1500
1200
900
600
300
1500
1200
900
600
300
2000
1600
1200
800
500
2000
1600
1200
800
500
2000
1600
1200
800
500
2000
1600
1200
800
500
2000
1600
1200
800
500
590
472
378
236
118
590
472
378
236
118
590
472
378
236
118
708
566
425
283
142
708
566
425
283
142
708
566
425
283
142
708
566
425
283
142
944
755
566
378
236
944
755
566
378
236
944
755
566
378
236
944
755
566
378
236
944
755
566
378
236
Min. inlet
Ps
"w.g. Pa 2
0.42 104 79
0.15 37 76
0.20 50 73
0.06 15 64
0.10 25 56
0.12 30 79
0.06 15 76
0.10 25 73
0.03 6 64
0.03 7 56
0.09 22 82
0.01 2 78
0.01 2 75
0.01 2 64
0.01 2 55
0.56 139 73
0.21 52 69
0.26 65 64
0.08 20 59
0.10 25 55
0.31 77 73
0.07 17 69
0.09 22 64
0.03 7 59
0.02 5 55
0.09 22 71
0.02 5 69
0.01 2 65
0.01 2 56
0.01 2 53
0.02 5 71
0.01 2 68
0.01 2 63
0.01 2 55
0.01 2 55
0.51 127 77
0.18 45 72
0.24 60 68
0.08 20 64
0.10 25 60
0.12 30 77
0.04 10 72
0.09 22 67
0.02 5 62
0.04 10 59
0.12 30 77
0.02 5 73
0.06 15 73
0.01 2 63
0.01 2 59
0.25 62 77
0.08 20 72
0.01 2 67
0.01 2 63
0.01 2 60
0.09 22 76
0.06 15 72
0.01 2 67
0.01 2 62
0.01 2 59
Fan and 100% Primary Air Sound Power Octave Bands @ Inlet pressure (Ps) shown
Fan Only
Minimum Ps
0.5" wg (125Pa)Ps 1.0" wg (249Pa)Ps 1.5" wg (375Pa)Ps
3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7
73 69 68 61 52 80 74 69 68 61 52 80 74 69 68 61 52 80 74 69 68 61 54 81 75 70 68 62 56
69 65 64 56 47 76 69 65 65 57 47 77 69 65 65 57 47 77 69 65 65 57 48 77 70 66 65 57 49
65 62 61 52 42 74 65 62 60 51 42 74 65 62 61 52 43 74 65 62 61 52 45 74 66 63 61 53 47
56 55 52 41 29 65 55 55 51 40 28 64 56 55 51 41 32 64 56 55 52 42 36 64 56 56 52 43 40
53 52 46 35 21 54 52 52 46 35 24 55 53 52 46 37 29 55 53 53 47 39 35 56 54 53 48 41 41
73 69 68 61 52 79 73 69 68 61 52 79 73 69 68 61 54 79 73 69 68 61 57 79 74 70 68 62 59
69 65 64 56 47 76 69 65 64 56 47 76 69 65 64 57 48 76 69 65 64 57 50 75 69 65 64 57 52
65 62 61 52 42 71 63 61 60 51 41 72 64 62 60 52 45 72 66 63 61 54 50 73 67 64 62 55 56
56 55 52 41 29 63 55 55 51 40 28 65 59 57 54 45 38 68 63 60 57 49 47 71 67 62 60 54 57
53 52 46 35 21 56 52 52 46 34 20 58 54 53 48 39 29 60 56 54 50 44 38 62 57 56 52 49 48
74 69 68 62 52 81 74 69 68 61 53 81 74 69 68 61 55 81 74 70 68 62 57 81 75 70 68 62 60
69 65 64 57 47 76 68 65 63 55 46 76 69 65 64 56 49 76 69 65 64 57 52 77 70 66 64 57 55
65 62 60 51 42 73 64 61 60 50 41 73 65 62 60 52 45 73 66 63 61 53 50 73 67 63 61 54 54
56 55 51 40 29 63 55 55 51 40 28 63 57 56 52 43 35 64 59 57 53 47 42 65 60 58 54 50 49
52 52 46 35 22 55 52 51 45 34 21 57 54 53 47 39 30 59 55 54 49 44 38 61 57 55 51 48 47
71 68 68 68 64 72 71 68 68 69 64 * * * * * * 73 71 69 68 69 65 74 72 69 69 70 65
67 66 64 64 60 72 69 67 66 66 61 73 70 68 67 66 62 72 70 68 67 67 62 72 70 68 67 67 63
62 61 59 57 53 67 65 63 61 59 55 68 65 63 61 60 55 68 65 63 62 60 56 68 65 63 62 60 56
58 58 54 51 45 62 61 60 56 54 48 62 62 60 57 54 49 62 62 61 57 55 50 63 62 61 58 56 51
55 54 47 43 34 59 58 56 50 47 38 59 59 57 51 48 41 60 59 57 53 50 43 60 59 58 54 51 46
71 68 68 68 64 71 70 68 67 66 63 72 71 68 67 67 63 73 71 68 67 67 64 74 72 69 68 68 66
67 66 64 64 60 68 66 65 63 62 59 69 67 65 63 63 59 70 68 65 64 63 61 72 69 66 64 64 63
62 61 59 57 53 63 61 61 58 56 52 64 62 61 59 57 54 67 64 62 60 59 57 69 65 63 61 61 60
58 58 54 51 45 55 56 56 51 48 42 59 57 56 53 51 47 61 58 57 54 54 50 63 59 58 55 57 54
55 54 47 43 34 56 53 52 45 41 31 57 54 53 47 46 41 58 55 53 49 48 44 59 55 54 51 51 47
69 67 67 67 63 73 71 69 68 67 63 73 71 69 68 67 64 73 72 69 68 68 65 74 72 70 68 68 67
66 65 63 62 58 68 65 65 63 62 58 68 66 65 63 63 59 70 68 66 64 64 61 72 69 66 65 64 63
63 62 59 57 53 64 63 62 59 57 53 66 63 62 59 58 54 68 64 62 60 59 57 69 65 63 61 61 59
56 55 51 48 42 55 55 55 51 48 41 60 57 56 52 51 47 64 59 58 54 55 53 68 62 59 56 59 58
52 52 44 41 29 53 52 52 44 40 29 56 53 53 47 46 40 56 54 54 49 49 45 56 55 54 51 53 49
69 67 67 67 63 73 70 68 67 67 63 74 71 68 67 67 64 75 72 69 68 68 65 76 72 70 68 68 67
66 65 63 62 58 67 65 64 63 62 58 67 66 65 63 62 58 69 67 65 63 63 60 70 68 66 64 64 62
62 61 58 56 52 61 61 60 58 56 51 63 62 61 58 57 53 65 63 62 59 59 56 66 64 62 60 60 58
56 56 51 48 42 54 56 55 51 48 41 58 57 56 52 51 46 60 58 57 53 54 50 62 60 58 55 57 55
53 52 45 41 31 55 53 52 45 41 31 57 53 52 47 47 42 58 55 54 50 51 47 59 56 55 52 55 51
74 68 66 66 64 77 74 68 66 66 64 * * * * * * 78 74 69 67 66 64 78 75 69 67 66 65
68 64 61 60 57 72 68 64 61 60 57 72 69 64 61 60 58 73 69 64 61 60 58 73 69 65 62 61 59
62 58 54 52 49 68 62 58 54 52 48 68 62 58 54 53 49 69 63 59 55 54 51 69 63 61 56 55 53
55 52 47 43 36 63 54 52 47 43 35 63 54 53 48 44 38 63 55 53 49 46 41 64 55 54 50 48 44
51 48 42 37 27 59 51 48 42 37 28 59 51 49 43 39 32 59 52 50 45 43 38 60 52 52 47 46 44
74 68 66 66 64 77 74 68 66 66 64 77 74 69 67 66 64 77 74 69 67 66 65 77 75 70 67 67 66
68 63 61 60 58 72 68 63 61 60 58 73 69 64 61 61 59 73 69 64 62 61 60 73 70 65 62 62 62
62 57 54 52 48 68 62 59 54 52 49 68 63 59 56 54 52 69 64 61 57 57 56 70 65 62 58 59 60
54 52 47 43 36 62 54 52 47 43 36 63 56 54 49 47 42 64 57 55 51 51 48 66 59 57 53 55 55
51 47 42 36 27 59 51 48 42 37 28 60 53 50 45 43 37 62 55 53 48 49 46 63 58 55 51 55 55
74 69 67 66 64 77 74 69 67 66 64 78 74 69 67 66 65 78 74 70 67 67 66 79 75 70 68 67 67
68 64 61 60 58 73 68 64 61 60 58 74 69 64 62 61 59 74 70 65 62 62 61 75 70 66 63 62 62
68 64 61 60 58 73 68 64 61 60 58 74 69 65 62 61 59 74 70 65 62 62 61 75 70 66 63 62 62
54 52 47 43 36 61 54 52 47 43 35 64 57 54 50 48 43 66 60 57 52 52 50 69 63 59 55 57 57
51 48 42 37 28 58 51 47 41 36 27 60 53 50 44 42 35 61 55 53 47 48 44 63 58 55 51 53 52
74 69 66 66 64 77 74 69 66 66 64 78 74 70 67 66 65 79 75 71 68 67 66 80 76 73 70 68 68
69 64 61 60 58 72 69 64 61 60 58 73 69 65 62 61 59 74 70 65 62 62 61 75 70 66 63 63 63
61 58 54 52 49 67 61 57 53 51 47 68 63 59 55 54 51 70 64 60 56 56 56 71 66 62 58 59 60
54 52 47 43 35 63 53 52 46 42 34 64 56 54 49 48 42 65 58 55 51 52 49 66 60 57 53 57 56
51 48 42 36 27 59 50 47 41 36 26 61 53 50 45 43 37 62 55 52 49 50 46 64 58 55 52 56 55
74 68 67 66 64 76 73 68 66 65 64 77 74 70 67 66 65 79 76 71 68 67 66 80 77 73 69 68 67
69 64 61 60 57 72 69 64 61 60 57 74 70 66 63 61 59 75 72 67 64 63 62 77 73 69 66 64 64
62 58 54 52 48 66 61 57 53 51 47 68 63 59 56 54 52 69 64 61 58 57 55 70 66 63 60 60 59
55 52 47 43 35 60 54 52 46 42 34 62 56 54 49 46 40 63 57 55 53 51 46 65 59 57 57 56 53
51 47 42 36 26 58 51 47 41 36 25 60 53 50 46 42 34 62 55 53 52 49 43 64 57 56 57 56 52
D22
5-6-16
Octave Band
2 3 4 5 6
24 28 39 53 59
27 29 40 51 53
29 30 41 51 52
7
40
39
39
Octave Band
2 3 4 5 6 7
18 19 20 26 31 36
5-6-16
D23
10 .63
2.9 10
6
4
.38
.25
2.6
.19
2.3
.13
2.1
4 Row (multi-circuit)
kW MBH
5.0 17
GPM l/s
GPM l/s
4.7 16
8
6
.50
.38
4.1 14
.25
.19
.13
.06
3.5 12
2.9 10
1.5
1.2
2.3
0.5 .03
0.9
0.6
0.3
1
100
47
300
142
500
236
700
330
900
425
1100
519
GPM l/s
10 .63
8 .50
5.3 18
5 .32
4 .25
4.7 16
3 .19
4.1 14
2 .13
3.5 12
2.9 10
2.3
1.8
1.2
.6
1.2
0.6
2
250
118
0.5 .03
400
189
550
260
700
330
850
401
6 Row (multi-circuit)
kW MBH
5.9 20
1.8
1300 CFM
613 l/s
1 .06
1000
472
1150
543
1300 CFM
613 l/s
Pa in. H2O
249 1.00
447 0.80
17.9 6.0
149 0.60
.06
100 0.40
11.9 4.0
2 ROW
1.8
6.0 2.0
4 ROW
6 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
50 0.20
6 ROW
4 ROW
25 0.10
20 0.08
15 0.06
2 ROW
10 0.04
0.6 0.2
5 0.02
.5 .03
0.3 0.1
250
118
400
189
550
260
700
330
850
401
1000
472
1150
543
1300 CFM
613 l/s
2 0.01
1
.06
2
3 4 5 6 8 10 GPM
.13 .19 .25 .32.38 .50 .63l/s
WATER FLOW
250
118
500
236
AIRFLOW
NOTES:
1. Capacities are in MBH (kW), thousands of
Btu per hour (kilo Watts).
2. MBH (kW) values are based on:
57F (32C) Entering Water Temperature
(EWT).
kW
WTD (F) = 2.04 x MBH , WTD (C) = .224 x
GPM
l/s
5. Connections: 2, 4 & 6 Row: 7/8" (22) O.D.
male solder.
D24
0
0.075
1000
1000
0.072
0.960
2000
0.070
0.930
3000
0.067
0.900
4000
0.065
0.860
5000
0.063
0.830
6000
0.060
0.800
7000
0.058
0.700
8-21-15
2 Row (multi-circuit)
kW MBH
9.4 32
GPM l/s
kW MBH
17.6 60
5 .32
GPM l/s
9 .57
7 .44
3 .19
5 .32
4 .25
2 .13
14.6 50
3 .19
7.6 26
2 .13
1 .06
11.7 40
5.9 20
1 .06
8.8 30
.5 .03
4.1 14
.5 .03
5.9 20
2.3
2.9 10
8
250
118
400
189
550
260
700
330
850
401
1000
472
1300 CFM
613 l/s
1150
543
250
118
400
189
550
260
700
330
850
401
17.9 6.0
149 0.60
Pa in. H2O
249 1.00
447 0.80
100 0.40
1 ROW
2 ROW
6.0 2.0
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
50 0.20
2 ROW
1 ROW
25 0.10
20 0.08
15 0.06
10 0.04
0.6 0.2
5 0.02
0.3 0.1
2 0.01
1
.06
2
3 4
6 8 10 GPM
.13 .19 .25 .38 .50 .63 l/s
WATER FLOW
250
118
500
236
AIRFLOW
NOTES:
1. Capacities are in MBH (kW), thousands of Btu per
hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 120F (67C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
8-21-15
1300 CFM
613 l/s
1150
543
11.9 4.0
t F (C)
Factor
1000
472
50 (28)
.417 (.418)
60 (33)
.500 (.493)
70 (39)
.583 (.582)
Altitude
ft. (m)
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
80 (44)
90 (50)
100 (56)
110 (61)
120 (67)
130 (72)
140 (78)
150 (83)
.667 (.657) .750 (.746) .833 (.836) .917 (.910) 1.00 (1.00) 1.08 (1.08) 1.17 (1.16) 1.25 (1.24)
D25
4 Row (multi-circuit)
kW MBH
6.2 21
GPM l/s
GPM l/s
10 .63
8 .50
3.5 12
.32
.25
.19
5.6 19
.38
5.0 17
.25
.19
.13
.06
4.4 15
2.9 10
2
.13
3.8 13
2.3
8
3.2 11
1
1.8
D
FAN POWERED TERMINAL UNITS
1.2
.06
2.6
2.1
1.5
0.5 .03
0.5 .03
0.9
450
212
600
283
750
354
900
425
1050
495
1200
566
1350
637
GPM l/s
.5
.38
6.2 21
5.3 18
4.4 15
.25
.19
.13
3.5 12
2.6
1.8
300
142
450
212
600
283
750
354
900
425
1050
495
6 Row (multi-circuit)
kW MBH
7 24
1500 CFM
708 l/s
.06
1200
566
1350
637
1500 CFM
708 l/s
Pa in. H2O
249 1.00
447 0.80
17.9 6.0
149 0.60
100 0.40
11.9 4.0
2 ROW
300
142
0.6
6.0 2.0
6 ROW
4 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
50 0.20
6 ROW
4 ROW
25 0.10
20 0.08
15 0.06
2 ROW
10 0.04
0.6 0.2
5 0.02
.5 .03
0.3 0.1
.9
300
142
450
212
600
283
750
354
900
425
1050
495
1200
566
1350
637
1500 CFM
708 l/s
2 0.01
1
.06
2
3 4 5 6 8 10 GPM
.13 .19 .25 .32.38 .50 .63l/s
WATER FLOW
300
142
600
283
AIRFLOW
NOTES:
1. Capacities are in MBH (kW), thousands of
Btu per hour (kilo Watts).
2. MBH (kW) values are based on:
57F (32C) Entering Water Temperature
(EWT).
kW
WTD (F) = 2.04 x MBH , WTD (C) = .224 x
GPM
l/s
5. Connections: 2, 4 & 6 Row: 7/8" (22) O.D.
male solder.
D26
0
0.075
1000
1000
0.072
0.960
2000
0.070
0.930
3000
0.067
0.900
4000
0.065
0.860
5000
0.063
0.830
6000
0.060
0.800
7000
0.058
0.700
8-21-15
2 Row (multi-circuit)
kW MBH
10.3 35
GPM l/s
4 .25
3 .19
kW MBH
20.5 70
.13
GPM l/s
17.6 60
8.8 30
14.6 50
1
7.3 25
8
6
.5
.38
.25
.19
.13
.06
.06
11.7 40
5.9 20
0.5 .03
8.8 30
D
.5 .03
4.4 15
5.9 20
2.9 10
2.9 10
300
142
450
212
600
283
750
354
900
425
1050
495
1200
566
1350
637
1500 CFM
708 l/s
300
142
450
212
600
283
750
354
900
425
1350
637
1500 CFM
708 l/s
149 0.60
1 ROW
100 0.40
11.9 4.0
2 ROW
6.0 2.0
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
0.6 0.2
50 0.20
2 ROW
1 ROW
25 0.10
20 0.08
15 0.06
10 0.04
5 0.02
0.3 0.1
2 0.01
1
.06
2
3 4
6 8 10 GPM
.13 .19 .25 .38 .50 .63 l/s
WATER FLOW
300
142
600
283
AIRFLOW
NOTES:
1. Capacities are in MBH (kW), thousands of Btu per
hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 120F (67C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
8-21-15
1200
566
Pa in. H2O
249 1.00
447 0.80
17.9 6.0
t F (C)
Factor
1050
495
50 (28)
.417 (.418)
60 (33)
.500 (.493)
70 (39)
.583 (.582)
Altitude
ft. (m)
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
80 (44)
90 (50)
100 (56)
110 (61)
120 (67)
130 (72)
140 (78)
150 (83)
.667 (.657) .750 (.746) .833 (.836) .917 (.910) 1.00 (1.00) 1.08 (1.08) 1.17 (1.16) 1.25 (1.24)
D27
4 Row (multi-circuit)
kW MBH
7.9 27
GPM l/s
GPM l/s
.32
.57
.25
.44
.32
.19
.13
.06
4.1 14
6.7 23
.19
.13
3.5 12
5.6 19
2.9 10
4.4 15
2.3
.06
3.2 11
1.2
0.6
2.1
0.9
0.5 .03
0.5 .03
500
236
700
330
900
425
1100
519
1300
613
1500
708
1700
808
1900
897
500
236
2100 CFM
991 l/s
700
330
900
425
1100
519
.50
.38
17.9 6.0
.25
.19
GPM l/s
7.9 27
5.6 19
.13
4.4 15
3.2 11
0.9
.06
0.5 .03
500
236
700
330
900
425
1100
519
1300
613
1500
708
1700
808
1900
897
2100 CFM
991 l/s
1700
808
1900
897
2100 CFM
991 l/s
2 ROW
6.7 23
1500
708
100 0.40
11.9 4.0
2.1
1300
613
6 Row (multi-circuit)
kW MBH
9.1 31
1.8
6.0 2.0
6 ROW
4 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
50 0.20
6 ROW
4 ROW
2 ROW
25 0.10
20 0.08
15 0.06
10 0.04
0.6 0.2
5 0.02
0.3 0.1
2 0.01
1
.06
2
3 4 5 6 8 10 GPM
.13 .19 .25 .32.38 .50 .63l/s
WATER FLOW
500
236
1000
472
AIRFLOW
NOTES:
1. Capacities are in MBH (kW), thousands of
Btu per hour (kilo Watts).
2. MBH (kW) values are based on:
57F (32C) Entering Water Temperature
(EWT).
kW
WTD (F) = 2.04 x MBH , WTD (C) = .224 x
GPM
l/s
5. Connections: 2, 4 & 6 Row: 7/8" (22) O.D.
male solder.
D28
0
0.075
1000
1000
0.072
0.960
2000
0.070
0.930
3000
0.067
0.900
4000
0.065
0.860
5000
0.063
0.830
6000
0.060
0.800
7000
0.058
0.700
8-21-15
2 Row (multi-circuit)
kW MBH
15.8 54
GPM l/s
kW MBH
27.2 93
10 .63
8 .50
6 .38
13.8 47
11.7 40
.25
.19
.13
GPM l/s
7
6
5
.44
.38
.32
.25
.19
.13
.06
22.9 78
18.5 63
9.7 33
.06
14.1 48
7.6 26
0.5 .03
9.7 33
5.6 19
3.5 12
0.5 .03
5.3 18
500
236
700
330
900
425
1100
519
1300
613
1500
708
1700
808
1900
897
2100 CFM
991 l/s
500
236
700
330
900
425
1100
519
1300
613
17.9 6.0
149 0.60
1900
897
2100 CFM
991 l/s
100 0.40
2 ROW
6.0 2.0
1 ROW
3.0 1.0
2.4 0.8
1.8 0.6
1.2 0.4
0.6 0.2
Pa in. H2O
249 1.00
447 0.80
50 0.20
2 ROW
1 ROW
25 0.10
20 0.08
15 0.06
10 0.04
5 0.02
0.3 0.1
2 0.01
1
.06
2
3 4
6 8 10 GPM
.13 .19 .25 .38 .50 .63 l/s
WATER FLOW
500
236
1000
472
AIRFLOW
NOTES:
1. Capacities are in MBH (kW), thousands of Btu per
hour (kilo Watts).
2. MBH (kW) values are based on a t (temperature
difference) of 120F (67C) between entering air
and entering water. For other t's; multiply the
MBH (kW) values by the factors below.
8-21-15
1700
808
11.9 4.0
t F (C)
Factor
1500
708
50 (28)
.417 (.418)
60 (33)
.500 (.493)
70 (39)
.583 (.582)
Altitude
ft. (m)
0 (0)
2000 (610)
3000 (914)
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
80 (44)
90 (50)
100 (56)
110 (61)
120 (67)
130 (72)
140 (78)
150 (83)
.667 (.657) .750 (.746) .833 (.836) .917 (.910) 1.00 (1.00) 1.08 (1.08) 1.17 (1.16) 1.25 (1.24)
D29
E1
RETROFIT TERMINALS
Contents
Page No.
Product Overview
E3
Appplications
E4
E5
E6
E7
E2
E10
E11
Model 36VRR
See page E5
Model 36VRR
Model 36VRS
Model 36VRS
Model 36VR
E3
36V
RS
COLD
DUCT
M
HOT
MAIN AIR
DIRECT
ACTING
THERMOSTAT
DUCT
100%
AIRFLOW
Hot and cold air from the central station is distributed through
the existing supply ducts and terminals. The Series 36VR
Retrofit Terminals will convert the constant volume system to
variable air volume pressure independant operation.
Remove the mechanical constant volume regulator from
the existing terminal, while a Model 36VRS is installed in
the discharge box or duct. A direct acting thermostat
controls both the 36VRS unit and the modulating tandem
damper in the existing box. On a rise in room temperature,
the 36VRS reduces the hot airflow. At the minimum setting,
the damper in the existing terminal begins to modulate,
and mixing occurs. A further temperature rise increases
the cold airflow to the maximum.
The fan capacity may be reduced down since the total air
volume is reduced.
REMOVE
EXISTING
CONTROLLER
VAV
HEATING
CFM
VAV
COOLING
CFM
MIXING
0%
0
18
13
OIL
TC
HEA
RE
RS
36V
DUCT
RS
36V
AIRFLOW
100%
VAV
COOLING
CFM
REHEAT
COIL
0%
0
13
Multizone System
OLD
RC
TO
HO
E1
ZON
RR
36V
DUCT
T
HO
E2
ZON
OR
RR
MAX.
VAV COOLING CFM
WITH DA THERMOSTAT
OR
VAV HEATING CFM
WITH RA THERMOSTAT
MIN.
0%
0
E4
COL
36V
100%
AIRFLOW
13
DAMPER
ACTUATOR
RESET
CONTROLLER
LOW
AIRF
MULTI-POINT
AVERAGING
FLOW SENSOR
MULTI-POINT
FLOW SENSOR
/8" (3
TEE
GAUGES
DAMPER BLADE
L
AIRFLOW
D
CCW
TO OPEN
5"
(127)
DAMPER
DRIVESHAFT
4 1/4"
(108)
5 3/4"
(146)
Dimensional Data:
Unit Size
4
5
6
7
8
9
10
12
14
16
L
22
22
18
18
18
20
20
20
22
22
Unit Size
4
5
6
7
8
9
10
12
14
16
L
559
559
457
457
457
508
508
508
559
559
E5
FEATURES:
Casing 22 ga. (0.86), corrosion-resistant steel with
stiffening beads. Size 14 and 16 are 20 ga. (0.91).
Blade: Two layers of 22 ga. (0.86), corrosion-resistant
steel laminated together (equivalent to 16 guage) with a
cross-linked polyurethane peripheral gasket for tight
shut-off, 90 rotation, CCW to open. Damper leakage is
less than 2% of nominal CFM @ 6" w.g. as tested in
accordance with ANSI/ASHRAE Standard 130.
Bearing: Self-lubricating oilite bronze.
Drive Shaft/Axles: 1/2" (13) diameter plated steel,
double-bolted to blades. Indicator mark on the end of the
shaft to show damper position.
Full electrical controls enclosure for factory mounted
DDC and analog electronic controls.
Multi-point averaging 'Diamond Flow' sensor: Aluminium.
D1
Model 36VRR
AHRI Standard 880 "Performance Rating of Air Terminals" is the
method of test for the certification program. The standard rating
condition" (certification rating point) airflow volumes for each
terminal unit size are tabulated below. These air volumes
equate to an approximate inlet velocity of 2000 fpm (10.2 m/s).
When digital or other controls are mounted by Nailor, but
supplied by others, these values are guidelines only, based
upon experience with the majority of controls currently
available. Controls supplied by others for factory mounting are
configured and calibrated in the field. Airflow settings on
pneumatic and analog controls supplied by Nailor are factory
preset when provided.
4
5
6
7
8
9
10
12
14
16
Total
Airflow
Range
cfm
Airflow at
2000 fpm Inlet
Velocity (nom.)
cfm
0 225
0 350
0 450
0 650
0 900
0 1150
0 1500
0 2100
0 3200
0 4000
150
250
400
550
700
900
1100
1600
2100
2800
Pneumatic
3000 Controller
Min.
30
55
80
115
155
200
260
355
475
640
180
325
450
650
900
1150
1500
2050
2750
3680
25
45
65
95
125
165
215
290
390
520
180
325
450
650
900
1150
1500
2050
2750
3680
25
45
65
95
125
165
215
290
390
520
180
325
450
650
900
1150
1500
2050
2750
3680
200
350
450
650
900
1150
1500
2100
3065
4000
225
350
450
650
900
1150
1500
2100
3200
4000
4
5
6
7
8
9
10
12
14
16
E6
2-2-11
Total
Airflow
Range
l/s
Airflow at
10.2 m/s Inlet
Velocity (nom.)
l/s
0 106
0 165
0 212
0 307
0 425
0 543
0 708
0 991
0 1510
0 1888
71
118
189
260
330
425
519
755
991
1321
Pneumatic
3000 Controller
Min.
14
26
38
54
73
94
123
168
224
302
85
153
212
307
425
543
708
967
1298
1737
12
21
31
45
59
78
101
137
184
245
85
153
212
307
425
543
708
967
1298
1737
12
21
31
45
59
78
101
137
184
245
85
153
212
307
425
543
708
967
1298
1737
94
165
212
307
425
543
708
991
1446
1888
106
165
212
307
425
543
708
991
1510
1888
10
12
14
16
cfm
225
200
150
100
350
300
200
100
450
400
300
200
650
550
450
350
800
700
600
400
1050
850
650
450
1350
1150
950
750
2100
1700
1300
900
3200
2700
2200
1700
4000
3500
3000
2000
Pa
62
50
25
12
80
57
27
7
55
45
25
10
52
35
25
15
42
32
25
10
42
27
17
7
40
30
22
12
47
30
17
7
62
47
30
15
52
37
27
10
0.5"
w.g.
3.0"
w.g.
125 Pa
250 Pa
375 Pa
750 Pa
125 Pa
250 Pa
375 Pa
750 Pa
21
28
27
23
25
24
22
-
20
20
22
20
26
23
21
25
22
32
30
27
21
29
26
23
23
20
25
22
20
25
24
20
25
22
20
26
23
26
25
25
29
26
24
21
34
32
30
27
35
31
30
28
25
24
29
26
21
26
24
30
27
22
26
25
23
30
26
25
21
31
27
26
25
34
31
27
25
38
36
32
27
39
36
34
31
20
21
24
23
30
26
21
31
26
23
-
21
26
21
24
22
26
22
26
24
25
21
27
24
20
33
28
22
35
31
26
21
36
33
30
-
24
26
23
27
24
28
24
26
24
21
29
25
31
27
23
36
31
25
37
33
29
23
39
35
32
28
30
22
33
30
20
32
30
28
33
27
25
33
27
26
35
32
26
21
36
33
30
25
39
35
30
21
42
37
34
27
45
40
37
27
Performance Notes:
1. NC levels are calculated from the
published raw data and based on
procedures outlined in Appendix E,
ARI 885-98.
2. Discharge sound attenuation
deductions
are
based
on
environmental effect, duct lining,
branch power division, insulated flex
duct, end reflection and space effect
and are as follows:
Discharge attenuation
< 300 cfm
300 700 cfm
> 700 cfm
2
24
27
29
Octave Band
3 4 5 6
28 39 53 58
29 40 51 53
30 41 51 52
Airflow
Min. inlet
Ps
7
40
39
39
Octave Band
2 3 4 5 6 7
18 19 20 26 31 36
E7
10
12
14
16
Airflow
cfm
225
200
150
100
350
300
200
100
450
400
300
200
650
550
450
350
800
700
600
400
1050
850
650
450
1350
1150
950
750
2100
1700
1300
900
3200
2700
2200
1700
4000
3500
3000
2000
l/s
106
94
71
47
165
142
94
47
212
189
142
94
307
260
212
165
378
330
283
189
496
401
307
212
637
543
448
354
991
802
614
425
1510
1274
1038
802
1888
1652
1416
944
Min. inlet
Ps
"w.g. Pa
0.25 62
0.20 50
0.10 25
0.05 12
0.32 80
0.23 57
0.11 27
0.03 7
0.22 55
0.18 45
0.10 25
0.04 10
0.21 52
0.14 35
0.10 25
0.06 15
0.17 42
0.13 32
0.10 25
0.04 10
0.17 42
0.11 27
0.07 17
0.03 7
0.16 40
0.12 30
0.09 22
0.05 12
0.19 47
0.12 30
0.07 17
0.03 7
0.25 62
0.19 47
0.12 30
0.06 15
0.21 52
0.15 37
0.11 27
0.04 10
Performance Notes:
1. Discharge sound power is the
noise emitted from the unit discharge
into the downstream duct.
2. Sound power levels are in
decibels, dB re 10-12 watts.
3. All sound data listed by octave
bands is raw data without any
corrections for room absorption or
duct attenuation.
E8
10
12
14
16
cfm l/s
225 106
200 94
150 71
100 47
350 165
300 142
200 94
100 47
450 212
400 189
300 142
200 94
650 307
550 260
450 212
350 165
800 378
700 330
600 283
400 189
1050 496
850 401
650 307
450 212
1350 637
1150 543
950 448
750 354
2100 991
1700 802
1300 614
900 425
3200 1510
2700 1274
2200 1038
1700 802
4000 1888
3500 1652
3000 1416
2000 944
Min. inlet
Ps
"w.g. Pa
0.25 62
0.20 50
0.10 25
0.05 12
0.32 80
0.23 57
0.11 27
0.03 7
0.22 55
0.18 45
0.10 25
0.04 10
0.21 52
0.14 35
0.10 25
0.06 15
0.17 42
0.13 32
0.10 25
0.40 10
0.17 42
0.11 27
0.07 17
0.03 7
0.16 40
0.12 30
0.09 22
0.05 12
0.19 47
0.12 30
0.07 17
0.03 7
0.25 62
0.19 47
0.12 30
0.06 15
0.21 52
0.15 37
0.11 27
0.04 10
Airflow
Performance Notes:
1. Radiated sound power is the
breakout noise transmitted through
the unit casing walls.
2. Sound power levels are in
decibels, dB re 10-12 watts.
3. All sound data listed by octave
bands is raw data without any
corrections for room absorption or
duct attenuation.
E9
SLIDE-IN RETROFIT
TERMINAL UNIT
MODEL 36VRS
05)
SQUARE OR RECTANGULAR
VARIABLE AIR VOLUME
CONVERSION
12" (3
DUCT OPENING
BY OTHERS
H
W
IRFLO
OVERLAP FLANGE
(TOP & BOTTOM)
CCW
TO
OPEN
MOUNTING
PLATE
DRIVE SHAFT
A
A slide-in type Retrofit Air Terminal Unit
FULL ELECTRICAL
for square or rectangular ductwork.
CONTROLS
W
ENCLOSURE
Converts constant volume systems to
FOR FACTORY MOUNTED
)
variable air volume. Available in 15
(408 DDC AND ELECTRONIC CONTROLS
MULTI-POINT
16"
14" x 10" (356 x 254)
AVERAGING
FULL
individual valve sizes up to 15,000 cfm.
FLOW SENSOR GASKET
Nominal valve size is the same as
smallest available duct size in table.
Each unit (valve) size is available to suit various duct sizes as shown in the table. Top, bottom and/or side blank-off plates are
used to bring valve up to the required nominal ductwork dimension. Airflow ranges are based on valve size and acoustical
considerations for duct velocity. Model 36VRS units are available to suit duct sizes within the tabulated range in 1" (25)
increments.
Simple, low cost installation into existing ductwork. The installer cuts a rectangular hole in the side of the duct, cuts away the
insulation (where present), slides the unit into the duct and screws the mounting plate to the side of the duct.
when controls are factory mounted.
FEATURES:
Bearings: Celcon.
Dimensional Data:
Unit
(valve)
Size
7
8
9
10
11
11A
12
13
14
15
15A
16
17
18
19
E10
Options:
7
8
9
10
11
11A
12
13
14
15
15A
16
17
18
19
Nom.
Valve
Size
5x5
6x6
8x6
10 x 8
14 x 8
18 x 6
12 x 10
18 x 10
18 x 12
20 x 14
30 x 12
22 x 16
24 x 18
30 x 20
40 x 20
Unit
Size
E11
Duct
WxH
5x5
5x5
8x8
12 x 8
6x6
6x6
10 x 8
14 x 10
8x6
9
8x6
12 x 8
16 x 10
10 x 8
10 10 x 8
14 x 10
18 x 12
14 x 8
11 14 x 8
18 x 10
24 x 14
18 x 6
11A 18 x 6
22 x 8
26 x 10
12 x 10
12 12 x 10 18 x 12
24 x 14
18 x 10
13 18 x 10 24 x 12
30 x 14
E12
11/18/10
Airflow
cfm
70
140
200
70
140
200
70
140
200
110
200
300
110
200
300
110
200
300
140
270
400
140
270
400
140
270
400
240
480
700
240
480
700
240
480
700
320
650
1000
320
650
1000
320
650
1000
310
650
1000
310
650
1000
310
650
1000
350
725
1100
350
725
1100
350
725
1100
500
1200
1900
500
1200
1900
500
1200
1900
l/s
33
66
94
33
66
94
33
66
94
52
94
142
52
94
142
52
94
142
66
127
189
66
127
189
66
127
189
113
227
330
113
227
330
113
227
330
151
307
472
151
307
472
151
307
472
146
307
472
146
307
472
146
307
472
165
342
519
165
342
519
165
342
519
236
566
897
236
566
897
236
566
897
Duct
WxH
18 x 12
14 18 x 12 24 x 14
28 x 16
20 x 14
15 20 x 14 26 x 16
30 x 18
30 x 12
36 x 16
22 x 16
16 22 x 16 28 x 18
36 x 20
24 x 18
17 24 x 18 30 x 24
36 x 26
30 x 20
18 30 x 20 38 x 24
46 x 26
40 x 20
19 40 x 20 46 x 24
52 x 26
l/s
307
720
1133
307
720
1133
307
720
1133
401
1097
1793
401
1097
1793
401
1097
1793
481
1510
2548
481
1510
2548
481
1510
2548
472
1510
2548
472
1510
2548
472
1510
2548
590
1888
3162
590
1888
3162
590
1888
3162
826
2773
4719
826
2773
4719
826
2773
4719
1085
4082
7079
1085
4082
7079
1085
4082
7079
15A 30 x 12 34 x 14
Airflow
cfm
650
1525
2400
650
1525
2400
650
1525
2400
850
2325
3800
850
2325
3800
850
2325
3800
1020
3200
5400
1020
3200
5400
1020
3200
5400
1000
3200
5400
1000
3200
5400
1000
3200
5400
1250
4000
6700
1250
4000
6700
1250
4000
6700
1750
5875
10000
1750
5875
10000
1750
5875
10000
2300
8650
15000
2300
8650
15000
2300
8650
15000
11/17/10
E13
E14
F1
Contents
Page No.
Introduction and Features
3400
34RW
34RE
Basic Unit
With Hot Water Reheat
With Electric Reheat
F3
F3
F3
Dimensional Data
3400
34RW
34RE
Accessories
Basic Unit
Integral Sound Attenuator
With Hot Water Coil
Integral Sound Attenuator with Hot Water Coil
Integral Electric Coil
AT Discharge Attenuator
FF Round Discharge Collar
MOA Multi-Outlet Attenuator
F5
F6
F6
F6
F6
F7
F7
F7
Performance Data
NC Level Application Guide
Sound Power Levels
F2
F8
F9
F10
F13
F18
Balancing Procedure
F19
Suggested Specifications
F20
"DUMP BOX"
UNIQUE "FLOW DIVERTER"
VALVE
Models:
3400
Cooling
Cooling with
Electric Reheat
Model 3400
The 3400 Series Bypass Terminal Unit is a single duct pressure dependent air terminal unit, designed for use with
popular constant volume low and medium pressure packaged air handling systems or roof top air conditioning units at
low prime cost. Units may be used with cooling and heating/cooling systems. Temperature control is achieved by
supplying only enough conditioned air to the space to satisfy room thermostat demand. Excess air is diverted (bypassed)
directly to the return air ceiling plenum for free or ducted return. Airflow to each occupied zone will vary on thermostat
demand, from full flow to shut-off or to a mechanically set minimum air volume.
A bypass box, commonly referred to also as a "dump box" handles a constant supply of primary air through its inlet and
uses a diverting damper to bypass part of the supply air into the plenum return. The damper is directly controlled by the
room thermostat in the occupied space to provide the volume of air required to meet the thermal demand. The pressure
requirement through the supply air path to the conditioned space is set with an inlet balancing damper. A second manual
balancing damper in the bypass is field adjusted to match the resistance in the discharge duct in order to maintain
minimum airflow to the space, maintain supply air from the primary system at a constant volume and ensure smooth
modulation of the supply airflow volume.
Bypass terminals can be added to a single-zone constant volume system to provide zoning without the energy penalty of
a conventional reheat system, providing low first cost with minimum fan controls. Although variable volume to the space
in operation, total airflow of the fan remains constant, so the fan power and associated energy cost are not reduced. This
method is therefore energy inefficient as compared to a VAV fan system. Its most frequent application is on small systems.
FEATURES:
Easily adjustable
balancing dampers.
bypass
Options:
Hot water and electric reheat coil
sections.
Multi-outlet plenum.
Round/Oval discharge collar.
Controls:
Pressure dependent pneumatic or
analog electronic control. Factory
A Participating
Corporation
in the ARI 880
Certification program.
F3
BYPASS PORT
WITH BALANCING
DAMPER
CONTROLS
ENCLOSURE
INLET
COLLAR
WITH
BALANCING
DAMPER
UNIQUE FLOW
DIVERTER VALVE
DISCHARGE WITH
SLIP AND DRIVE CONNECTION
Electronic Modulating
Controls
Nailor offers a series of state of the art
analog electronic control packages
which provide true modulating control
and superior performance over
conventional electric controls. These
older packages essentially provide
on/off control of the bypass terminal.
Commonly, the damper is driven to the
full supply or full bypass position before
a change in space temperature is
sensed by the room thermostat. Low
speed actuators are often used to slow
the damper response, but result in
sluggish control and large swings in occupied space temperature which waste energy and provide poor comfort.
Nailor's electronic packages feature advanced microcomputer electronics and proportional plus integral (P + I) control
algorithms to provide precise temperature control. The thermostat provides a true multi-position modulating output to a
conventional 24 VAC tri-state floating actuator. The thermostat output cycles the actuator with shorter or longer "on times"
proportional to the temperature offset, preventing temperature overshoot. The thermostat also tracks how long the room
temperature has varied from set point and adjusts the output accordingly. This eliminates wasted energy caused by
typical on/off cycling with conventional SPDT thermostats, resulting in significant energy savings and superior comfort.
Control deadband accuracy is +/- 0.4F (+/- 0.2C) around set point. When a reheat stage is required, the electronic
thermostat provides a time proportioning on/off output signal based on a 15 minute duty cycle that proportionately
modulates the reheat coil, adjusting the amount of "on time" in accordance with room temperature offset. This feature
provides performance similar to an SCR controller, but at a fraction of the cost.
Options:
Thermostat Scale Plate F or C.
24 VAC Control transformer.
Toggle disconnect switch.
F4
BYPASS BALANCING
DAMPER
W 1" (25)
9 1/4" (235)
4" (102)
ROUND OR
FLAT OVAL
INLET
INLET BALANCING
DAMPER
DAMPER
DRIVESHAFT
AIRFLOW
H
1/2"
(13)
5 1/2"
(140)
5"
(127)"
15 1/2" (394)
10" (254)
4" (102)
ROUND OR
FLAT OVAL
INLET
BYPASS
BALANCING
DAMPER
9 1/4" (235)
CONTROLS
ENCLOSURE
FOR FACTORY
MOUNTED
CONTROLS
INLET BALANCING
DAMPER
AIRFLOW
DAMPER
DRIVESHAFT
14 " (356)
1/2"
(13)
5 3/4"
(146)
5 1/2"
(140)
15 1/2" (394)
SLIP AND DRIVE CONNECTION
Dimensional Data
Imperial Units (inches)
Unit
Size
6
8
10
12
14
16
cfm
Range
0 400
0 700
0 1100
0 1600
0 2100
0 2800
10
12
14
18
24
28
12 1/2
12 1/2
12 1/2
12 1/2
12 1/2
12 1/2
Inlet
Size
5 7/8 Round
7 7/8 Round
9 7/8 Round
12 15/16 x 9 13/16 Oval
16 1/16 x 9 13/16 Oval
19 3/16 x 9 13/16 Oval
l/s
Range
0 189
0 330
0 519
0 755
0 991
0 1322
254
305
356
457
610
711
318
318
318
318
318
318
Inlet
Size
149 Round
200 Round
251 Round
329 x 249 Oval
408 x 249 Oval
487 x 249 Oval
F5
5 1/2"
(140)
51 1/2" (1308)
5 1/2"
(140)
15 1/2" (394)
OPTIONAL
ACCESS DOOR
5 1/2"
(140)
51 1/2" (1308)
L
OPTIONAL ACCESS DOOR
5 1/2"
(140)
63 1/2" (1613)
ELECTRIC COIL
CONTROLS
ENCLOSURE
(HINGED
ACCESS DOOR)
15" (381) MAX.
5 3/4"
(146)
Dimensional Data
Metric Units (mm)
F6
W
10
12
14
18
24
28
H
12 12
12 12
12 12
12 12
12 12
12 12
L (1 & 2 row) L (3
5
5
5
5
5
5
& 4 row)
7 12
7 12
7 12
7 12
7 12
7 12
Unit Size
6
8
10
12
14
16
W
254
305
356
457
610
711
H
318
318
318
318
318
318
L (1 & 2 row) L (3
127
127
127
127
127
127
& 4 row)
191
191
191
191
191
191
H
NOM.
- 1/8" (3)
H
36" (914) STANDARD
SIDE VIEW
END VIEW
W
4" (102) 2" (51)
SIDE VIEW
END VIEW
SIDE VIEW
10 (254)
4" (102)
END VIEW TYPICAL
Only one outlet size to be specified per M.O.A. No mixing of outlet sizes on the
same unit. Number and size of outlets on M.O.A. not to exceed the limits listed in
table, both maximum quantity of outlets and maximum size of outlet.
All round outlets c/w manual dampers with hand locking quadrant.
3/4" (19) dual density insulation.
Denotes inlet airflow direction.
For special outlet sizes and arrangements, consult your Nailor representative.
12 (305)
5 @ 8" (203)
5 @ 10" (254)
14, 16
(356, 406)
5 @ 10" (254)
4" (102)
TYPICAL
3 @ 6" (152)
5 @ 8" (203)
5 @ 6" (152)
3 @ 10" (254)
5 @ 8" (203)
Dimensional Data
Imperial Units
Unit
Size
6
8
10
12
14
16
W H
10
12
14
18
24
28
12 12
12 12
12 12
12 12
12 12
12 12
Metric Units
FF Outlet
Size
FF Outlet
Size
6
8
10
12
14
16
254
305
356
457
610
711
318
318
318
318
318
318
152
203
254
305
356
406
F7
10
12
14
16
Airflow
cfm l/s
400 189
300 142
200 94
100 47
700 330
500 236
350 165
200 94
1100 519
800 378
500 236
250 118
1600 755
1200 566
800 378
400 189
2100 991
1600 755
1050 495
550 260
2750 1298
2050 967
1375 649
700 330
Min.
Discharge
Ps
"w.g. Pa
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.05 12
0.03 7
0.01 2
0.01 2
0.06 15
0.03 7
0.01 2
0.01 2
Min.
Bypass
Ps
"w.g. Pa
0.14 35
0.08 20
0.04 10
0.01 2
0.21 52
0.11 27
0.05 12
0.02 5
0.43 107
0.23 57
0.09 22
0.02 5
0.50 124
0.28 70
0.13 32
0.03 7
0.50 124
0.29 72
0.12 30
0.03 7
0.50 124
0.28 70
0.13 32
0.03 7
NC Levels
Radiated
Discharge
Bypass
Bypass
Closed
Open
25
30
20
20
37
25
20
40
33
22
31
43
24
35
23
21
34
47
24
37
27
-
Performance Notes:
F8
Discharge attenuation
Octave Band
2 3 4 5 6 7
24 28 39 53 58 40
27 29 40 51 53 39
29 30 41 51 52 39
Octave Band
3 4 5 6 7
18 19 20 26 31 36
10
12
16
cfm l/s
400 189
300 142
200 94
100 47
700 330
500 236
350 165
200 94
1100 519
800 378
500 236
250 118
1600 755
1200 566
800 378
400 189
2100 991
1600 755
1050 495
550 260
2750 1298
2050 967
1375 649
700 330
Min.
Discharge
Ps
"w.g. Pa
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.01 2
0.05 12
0.03 7
0.01 2
0.01 2
0.06 15
0.03 7
0.01 2
0.01 2
Min.
Bypass
Ps
"w.g. Pa
0.14 35
0.08 20
0.04 10
0.01 2
0.21 52
0.11 27
0.05 12
0.02 5
0.43 107
0.23 57
0.09 22
0.02 5
0.50 124
0.28 70
0.13 32
0.03 7
0.50 124
0.29 72
0.12 30
0.03 7
0.50 124
0.28 70
0.13 32
0.03 7
Discharge
2
45
43
52
45
50
47
44
40
49
44
40
60
54
47
66
58
50
47
3
44
38
31
51
43
34
50
47
40
30
47
40
31
57
49
37
31
64
56
45
31
4
41
34
24
47
38
28
46
36
34
45
38
25
26
54
44
31
61
51
39
-
5
33
25
39
29
43
30
28
43
36
48
39
24
56
46
33
-
6
29
36
24
37
28
44
36
45
34
52
42
27
-
Bypass Open
3 4 5 6
55 52 52 51
48 45 47 37
38 34 32 34 29 - 59 55 53 48
50 46 43 3
40 37 32 25
30 - - 64 62 60 56
55 52 50 46
45 43 41 34
28 - - 69 66 63 60
60 58 56 52
49 49 46 39
40 41 35 28
69 67 65 61
62 60 57 53
50 50 45 40
37 36 29 73 71 69 65
65 63 61 56
53 53 50 44
35 33 25 -
7
37
26
41
28
52
41
56
46
31
57
48
31
61
50
34
-
14
Airflow
Airflow
cfm l/s
400 189
700 330
1100 519
1600 755
2100 991
2750 1298
Min. Inlet
Ps
"w.g. Pa
0.01
2
0.01
2
0.01
2
0.01
2
0.05 12
0.06 15
2
45
52
50
49
60
66
Performance Notes:
1. Discharge sound power is the
noise emitted from the unit
discharge into the downstream duct.
2. Radiated sound power is the
breakout noise transmitted through
the unit casing walls.
3. Sound power levels are in
decibels, dB re 10-12 watts.
7
20
20
23
29
41
37
A Participating
Corporation
in the ARI 880
Certification program.
F9
Control Sequence P1
Cooling (with Optional Reheat) Reverse Acting/Normally
Open
EH
EA
T
100
AI
80
RF
NA
LR
LO
W
60
OP
TI
O
% FLOW
When main control air is off, damper is fully open and the bypass is
closed.
When main control air is on, cooling airflow modulates according to
thermostat output.
On a rise in room temperature, the thermostat line pressure to the
actuator decreases. The actuator moves the damper to the open
position, increasing the cooling airflow to the room, closing the bypass
air at the same time.
If the room thermostat is satisfied before the damper is fully open, the
damper remains in a modulated position until further demand.
On a fall in room temperature, the thermostat line pressure increases,
moving the actuator to close the damper and decreases the cooling
airflow to the room. At the same time, supply air is diverted through the
bypass port into the plenum.
A mechanical minimum stop requires field setting.
An optional hot water coil valve or electric heater may be sequenced
for reheat applications (8 13 psi). Hot water valve is supplied by
others. P.E. switch is included in electric heater.
40
MECH.
MIN. STOP
20
10
13
15
40
AI
RF
W
LO
AT
F10
MECH
MIN. STOP
HE
60
RE
AL
80
ON
If the room thermostat is satisfied before the damper is fully open, the
damper remains in a modulated position until further demand.
TI
OP
100
20
10
13
15
DAMPER
OPEN
100
LING
60
COO
AIRFLOW INCREASE
% OPEN
80
Central system supplies cool air. On a rise in room temperature above set
point, the bypass damper will slowly modulate open, increasing the flow of air
to the room, closing the bypass at the same time. On a fall in room temperature
below set point, the bypass damper will modulate closed, reducing the flow of
cool air into the room and opening the bypass at the same time. A mechanical
air volume minimum stop is provided (field set).
40
20
0
DAMPER
CLOSED
(MIN.)
SET
POINT
Model 3400
Control Sequence E3
Automatic Heating/Cooling Changeover
This arrangement is for systems supplying cool air in summer and hot air in
winter. A duct temperature sensor senses inlet temperature and automatically
reverses control action when supply air is above 78F (26C). A mechanical air
volume minimum stop is provided (field set).
DIAL
SET POINT
HEATING CENTERED IN COOLING
SET
DEAD BAND
SET
POINT
2F (1.1C)
POINT
DAMPER
OPEN
100
20
LING
DAMPER
CLOSED
(MIN.)
SET
POINT
Model 3400
100
ON
DAMPER
OPEN
40
LING
60
COO
AIRFLOW INCREASE
% OPEN
80
EAT
REH
Central system supplies cool air. On a rise in room temperature above set
point, the bypass damper will slowly modulate open, increasing the flow of air
to the room, closing the bypass at the same time. On a fall in room temperature
below set point, the bypass damper will modulate closed, reducing the flow of
cool air into the room and opening the bypass at the same time.
If room temperature continues to fall, the thermostat will energize the control
relay/valve of the perimeter heating or hot water valve for reheat. A mechanical
air volume minimum stop is provided (field set).
COO
AIRFLOW INCREASE
% OPEN
40
60
Heating Mode:
Supply air system in heating mode (above 78F (26C)). On a rise in room
temperature above set point, the bypass damper will modulate closed,
reducing the flow of warm air into the room to maintain set point and opening
the bypass. On a fall in room temperature below set point, the bypass damper
will modulate open, increasing the flow of warm air into the room to maintain
the set point and closing the bypass at the same time.
Control Sequence E4
Cooling with Auxiliary Heat (Perimeter Heating or Hot Water Reheat)
DAMPER
OPEN
80
ING
HEAT
Cooling Mode:
Supply air system in cooling mode (below 75F (24C)). On a rise in room
temperature above set point, the bypass damper will modulate open,
increasing the flow of cool air to the room, closing the bypass at the same time.
On a fall in room temperature below set point, the bypass damper will modulate
closed, reducing the flow of cool air into the room and opening the bypass at
the same time.
20
0
DAMPER
CLOSED
(MIN.)
OFF
SET
POINT
F11
DAMPER
OPEN
60
LING
80
40
COO
EAT
REH
Central system supplies cool air. On a rise in room temperature above set point,
the bypass damper will slowly modulate open, increasing the flow of air to the
room, closing the bypass at the same time. On a fall in room temperature below
set point, the bypass damper will modulate closed, reducing the flow of cool air
into the room and opening the bypass at the same time.
If room temperature continues to fall, the thermostat will energize the control
relay of the electric reheat coil.
Note: When an electric duct reheat coil is used, the adjustable mechanical end
stop on the actuator must be field set to ensure sufficient airflow over the
heating coil [70 cfm (33 l/s) per kW minimum].
100
AIRFLOW INCREASE
% OPEN
Control Sequence E4
Cooling with One Stage Electric Heat
20
DAMPER
CLOSED
(MIN.)
OFF
SET
POINT
Model 34RE
Control Sequence E5
ON
40
20
0
LING
DAMPER
OPEN
COO
60
ING
HEAT
AT
EHE
ER R
WAT
HOT
AIRFLOW INCREASE
% OPEN
80
R
AT O
Cooling Mode:
Supply air system in cooling mode (below 75F (24C)). On a rise in room
temperature above set point, the bypass damper will modulate open, increasing
the flow of cool air to the room, closing the bypass at the same time. On a fall in
room temperature below set point, the bypass damper will modulate closed,
reducing the flow of cool air into the room and opening the bypass at the same
time. If room temperature continues to fall, the thermostat will energize the
control relay/valve of the perimeter heating or hot water reheat valve for reheat.
100
DIAL
SET POINT
HEATING CENTERED IN COOLING
SET
SET
DEAD BAND
POINT
POINT
2F (1.1C)
DAMPER
OPEN
E
ER H
IMET
PER
DAMPER
CLOSED
(MIN.)
OFF
SET
POINT
Heating Mode:
Supply air system in heating mode (above 78F (26C)). On a rise in room temperature above set point, the bypass
damper will modulate closed, reducing the flow of warm air into the room to maintain set point and opening the bypass.
On a fall in room temperature below set point, the bypass damper will modulate open, increasing the flow of warm air
into the room to maintain the set point and closing the bypass at the same time. If room temperature continues to fall,
the thermostat will energize control relay/valve of the perimeter heating or the hot water valve for supplementary heat.
Control Sequence E5
Automatic Heating/Cooling Changeover with One Stage Electric Heat
This arrangement is for systems supplying cool air in summer and hot air in
winter. A duct temperature sensor senses inlet temperature and automatically
reverses control action when supply air is above 78F (26C).
100
ON
DIAL
SET POINT
HEATING CENTERED IN COOLING
SET
SET
DEAD BAND
POINT
POINT
2F (1.1C)
DAMPER
OPEN
DAMPER
OPEN
DAMPER
CLOSED
(MIN.)
20
0
COO
ING
HEAT
40
EAT
REH
60
LING
80
Cooling Mode:
Supply air system in cooling mode (below 75F (24C)). On a rise in room
temperature above set point, the bypass damper will modulate open, increasing
the flow of cool air to the room, closing the bypass at the same time. On a fall
in room temperature below set point, the bypass damper will modulate closed,
reducing the flow of cool air into the room and opening the bypass at the same
time. If room temperature continues to fall, the electric heat is energized.
AIRFLOW INCREASE
% OPEN
OFF
SET
POINT
F12
Unit Size 6
2 Row (multi-circuit)
17
28
15
3 GPM
3 GPM
2 GPM
1.5 GPM
25
1 GPM
22
2 GPM
1.5 GPM
13
1 GPM
19
0.5 GPM
MBH
MBH
11
16
0.5 GPM
9
13
7
10
5
3
50
7
4
100
150
200
250
300
350
400
450
500
50
100
150
200
CFM
250
300
350
400
450
500
Unit Size 8
1 Row (single circuit)
2 Row (multi-circuit)
25
44
5 GPM
4 GPM
3 GPM
23
41
2 GPM
21
15
1.5 GPM
32
MBH
MBH
2 GPM
35
1 GPM
17
3 GPM
38
1.5 GPM
19
5 GPM
4 GPM
29
1 GPM
26
0.5 GPM
23
13
20
11
17
9
7
200
0.5 GPM
14
11
300
400
500
600
700
800
900
200
1000
300
400
500
Notes:
600
700
800
900
1000
CFM
CFM
40
50
60
70
80
90
100
110
125
140
160
180
FACTOR
0.32
0.40
0.48
0.56
0.64
0.72
0.80
0.88
1.00
1.12
1.28
1.44
Altitude
(ft.)
Sensible Heat
Factor
0
2000
3000
4000
5000
6000
7000
1.00
0.94
0.90
0.87
0.84
0.81
0.78
F13
CFM
Unit Size 10
2 Row (multi-circuit)
32
7.5 GPM
5 GPM
29
3 GPM
58
7.5 GPM
54
5 GPM
50
3 GPM
2 GPM
26
46
2 GPM
42
23
MBH
MBH
1 GPM
20
17
0.5 GPM
34
1 GPM
30
26
14
38
22
11
8
300
0.5 GPM
18
14
400
500
600
700
800
900
300
400
500
600
700
800
900
CFM
CFM
Unit Size 12
1 Row (single circuit)
2 Row (multi-circuit)
10 GPM
7.5 GPM
5 GPM
44
82
10 GPM
7.5 GPM
77
40
36
3 GPM
72
2 GPM
67
5 GPM
3 GPM
62
32
28
MBH
MBH
57
1 GPM
2 GPM
52
47
24
42
1 GPM
37
20
32
16
27
12
400 550 700 850 1000 1150 1300 1450 1600 1750 1900 2050 2200
22
400 550 700 850 1000 1150 1300 1450 1600 1750 1900 2050 2200
CFM
CFM
Notes:
1. Capacities are in Mbh (thousands of Btu
per hour).
F14
6t F
40
50
60
70
80
90
100
110
125
140
160
180
FACTOR
0.32
0.40
0.48
0.56
0.64
0.72
0.80
0.88
1.00
1.12
1.28
1.44
Altitude
(ft.)
Sensible Heat
Factor
0
2000
3000
4000
5000
6000
7000
1.00
0.94
0.90
0.87
0.84
0.81
0.78
Unit Size 14
2 Row (multi-circuit)
57
10 GPM
7.5 GPM
53
103
5 GPM
49
93
5 GPM
88
3 GPM
83
45
2 GPM
3 GPM
78
41
73
MBH
MBH
10 GPM
7.5 GPM
98
37
1 GPM
33
68
2 GPM
63
58
53
29
48
25
1 GPM
43
38
21
33
17
500
700
900
28
500
700
900 1100 1300 1500 1700 1900 2100 2300 2500 2700
CFM
Unit Size 16
1 Row (single circuit)
2 Row (multi-circuit)
68
10 GPM
7.5 GPM
62
5 GPM
125
10 GPM
117
7.5 GPM
109
5 GPM
56
101
3 GPM
93
50
MBH
MBH
3 GPM
85
2 GPM
44
77
2 GPM
69
38
61
1 GPM
32
53
1 GPM
45
26
37
20
700 950 1200 1450 1700 1950 2200 2450 2700 2950 3200 3450 3700
29
700 950 1200 1450 1700 1950 2200 2450 2700 2950 3200 3450 3700
CFM
CFM
Notes:
1. Capacities are in Mbh (thousands of Btu
per hour).
40
50
60
70
80
90
100
110
125
140
160
180
FACTOR
0.32
0.40
0.48
0.56
0.64
0.72
0.80
0.88
1.00
1.12
1.28
1.44
Altitude
(ft.)
Sensible Heat
Factor
0
2000
3000
4000
5000
6000
7000
1.00
0.94
0.90
0.87
0.84
0.81
0.78
F15
CFM
8.0
0.80
6.0
0.60
4.0
1 ROW
2 ROW
2.0
1.0
0.8
0.6
0.4
2 ROW
0.08
0.06
0.04
1 ROW
0.2
0.02
0.01
0.1
1
100
8 10
8.0
0.80
6.0
0.60
4.0
1 ROW
2 ROW
2.0
1.0
0.8
0.6
0.4
200
300
500
0.6
0.4
4.0
2.0
1.0
0.8
0.6
0.4
2 ROW
0.2
0.1
0.08
0.04
0.1
0.02
0.01
1
1 ROW
0.06
0.2
8 10
100
F16
200
2000
6.0
6.0
1 ROW
4.0
2 ROW
2.0
1.0
0.8
0.6
0.4
0.1
AIRFLOW, CFM
kW = Mbh x 0.293
2.0
1.0
0.8
0.6
0.4
2 ROW
0.2
0.1
0.08
1 ROW
0.06
0.02
0.01
5. Heat (kilowatts):
4.0
0.04
0.2
400
8.0
200
AIRFLOW, CFM
10.0
8.0
100
1.0
0.8
1 ROW
0.04
2 ROW
8 10
10.0
6.0
1 ROW
0.06
Unit Size 12
6.0
2.0
0.08
10.0
8.0
4.0
2 ROW
0.20
0.10
0.02
0.01
Unit Size 10
Water Pressure Drop
0.40
0.2
AIRFLOW, CFM
10.0
8.0
0.1
0.40
0.20
0.10
1.00
10.0
Unit Size 8
8 10
100
200
AIRFLOW, CFM
6.0
1 ROW
4.0
2.0
2 ROW
1.0
0.8
0.6
0.4
4.0
2.0
1.0
0.8
0.6
0.4
0.2
0.1
0.08
2 ROW
0.06
1 ROW
0.04
0.2
0.02
1
8 10
0.01
100
8.0
6.0
6.0
1 ROW
4.0
2.0
2 ROW
1.0
0.8
0.6
0.4
0.2
AIRFLOW, CFM
2.0
1.0
0.8
0.6
0.4
2 ROW
0.2
0.1
0.08
1 ROW
0.06
0.04
0.02
0.01
0.1
200 400 600
4.0
8 10
100
200
AIRFLOW, CFM
5. Heat (kilowatts):
F17
0.1
6.0
8.0
10.0
8.0
10.0
Unit Size 16
Standard Features:
Selection:
The adjacent table provides a general guideline as to the
voltages and kilowatt range available for each terminal
unit size.
Maximum kilowatt loading is 1 kW per 70 cfm (33 l/s) at
heating condition.
Options:
kW
Range
120/1
0.5 5.7
208/1
0.5 9.9
240/1
0.5 11.5
277/1
0.5 13.0
480/1
0.5 18.0
208/3
0.5 17.3
240/3
0.5 20.0
480/3
0.5 20.8
600/3
0.5 26.0
F18
INLET
BALANCING
DAMPER
SUPPLY
FLOW
DIVERTER
VALVE
DISCHARGE
AIRFLOW
AIRFLOW
HI.(Ps)
DAMPER ACTUATOR
FIELD ADJUST FOR MINIMUM
AIR VOLUME IF REQUIRED
MAGNEHELIC
GAUGE
Electric Actuators
KMC MEP-5071 (standard). Position damper to the full
open position. Depress the gear disengagement button
and position the drive collar so the indicator mark is at the
"90" mark. Tighten setscrews on shaft. Loosen lower
travel stop one-half turn and slide to desired position.
Tighten stop screw.
Honeywell ML6161B-2024 (optional). Use clutch to
position damper in fully open position. Insert setscrew
with lock nut (supplied) in the threaded hole in top left
corner of actuator, turning CW until fully inserted. With
setscrew fully inserted, minimum position is 30, fully out
0. Use conversion of approx. 1.7 angular degrees per
turn of the setscrew. Back screw out of housing and stop
slightly short of the calculated position. This allows the
setscrew to be set accurately while taking airflow
measurements. (Important: Do not back-drive actuator
with setscrew, damage may result.) Rotate actuators to
minimum position using the manual declutch. Accurately
set minimum flow by backing-off setscrew as required
using airflow measurement. Using locknut, secure
against actuator housing to lock setscrew in place.
F19
Construction
Unit casing shall be constructed of 22 gauge zinc coated
steel, acoustically and thermally lined with 3/4" (19) dual
density insulation which meets the requirements of
Standard NFPA 90A and UL 181. Units shall incorporate
a heavy duty steel cylindrical "flow diverter" valve. Single
blade pivoting dampers are not acceptable.
Pneumatic Controls
The control sequence shall be Direct acting (normally
closed damper) or Reverse acting (normally open
damper). All pneumatic actuators shall be furnished and
factory installed by Nailor.
F20
G1
ENGINEERING GUIDE
Contents
Page No.
System Selection
G3
G5
G9
Types of Controls
G11
ENGINEERING GUIDE
Controls Terminology
G12
G14
G17
Introduction Fan Shift in Series Fan Powered Terminal Units Mechanical Trimming
Electronic Fan Speed Control Nameplate Ratings Caution on Meters
G19
G21
G22
G23
G26
G2
G34
G35
G36
Pressure Measurement
G37
G38
Index
G39
ENGINEERING GUIDE
System Selection
Designers have various systems to choose from when
designing a building. Choosing which one to use is not
always easy. The owners' needs must be met for
installation, application and cost of operation. The
designer must consider performance, capacity, reliability
and spatial requirements and restrictions. The following
guidelines describe different types of equipment and their
general uses, restrictions and limitations.
Building Use
The designer must consider the intended building use as
he begins to consider the type of equipment he will use.
Office buildings with daily operational schedules
frequently use fan powered terminal units. Usually fan
powered terminals with auxiliary heaters (supplementary
heat) would be used in the perimeter zones. These
terminal units allow the greatest flexibility for individual
zones while also allowing the central system to be turned
off during unoccupied periods. During the unoccupied
periods, the fan powered terminal units maintain the
minimum or set back temperature levels without the help
of the central air conditioning equipment.
In large buildings, the central air handlers deliver large
quantities of air to many zones with different needs. This
is a perfect application for fan powered terminal units.
Interior zones may not require heat at all; therefore they
can be served either by single duct units or fan powered
units with no supplemental heat. Unless the building is
located in a tropical climate, the perimeter zones will
require some type of heat, either electric or hot water.
These are usually included with the terminal units, but
sometimes baseboard heat is used. Buildings where the
owner desires low operating costs usually employ series
type fan powered terminal units, and the static pressure
in the ducts is lowered to 0.5" w.g. (125 Pa) or less at the
highest points. Interior zones in these buildings would
require fan powered terminal units. Buildings with parallel
type fan powered terminal units usually employ single
duct units in the interior zones.
In shopping malls and other low rise buildings where each
tenant area is small and in very small buildings, it is
common to use small package air conditioners. If terminal
units are employed on these systems, usually bypass units
are selected. A variation of this system uses single duct
units with a main bypass damper in the supply duct. The
bypass damper is regulated by the static pressure in the
supply duct. A nearly constant pressure can be maintained
allowing the package units to operate at constant volume
and the individual zones to be pressure dependent VAV.
Acoustical Constraints
Broadcast studios, theaters, and libraries require very
low noise levels. Equipment selection and location is
important here. If fan powered terminal units are to be
used, careful examination of the equipment sound
performance is imperative. RFI and EMI should also be
considered when designing television studios.
Contamination Considerations
Hospitals, clean rooms and laboratories pose special
problems. Operating rooms, bone marrow transplant,
AIDS patient areas and clean rooms require positive
pressurized environments. In addition to the pressure
requirements, reheat coils and exposed fiberglass are
usually avoided to eliminate the possibility of microbial
growth in hospitals. Hospital rooms and clean rooms
frequently also require constant and high ventilation rates
which tend to favor dual duct terminal units. Patient
housing for highly contagious diseases, such as
tuberculosis, require negative pressure within the rooms
to avoid allowing the germs to escape. Laboratories
handling hazardous materials also require negative
pressure areas. Single duct and dual duct constant
volume terminal units have been usually selected for this
type of building. New pressure independent ECM motor
technology has lead to the development of fan powered
pressurization units also for these applications.
ENGINEERING GUIDE
Building Size
Environmental Factors
Cost Factors
Costs must be considered before the final system
selection is made. Installation, operation and
maintenance all contribute to total cost. Sometimes one of
these costs is more important than others. For example,
if the owner/builder sells the building before construction
begins, then his main concern will be construction costs,
and operating costs will be unimportant. If the tenants pay
their own utilities, operating costs are not a concern to the
developer/builder. Electric heaters usually have a lower
installed cost than hot water coils, but they may have a
higher operating cost. Local rates will have to be
researched to arrive at the correct decision before making
the final selection.
G3
ENGINEERING GUIDE
System Selection (cont).
The following table presents a summary of the different types of terminal units currently available and their suitability
for particular commercial building applications.
Facility Type
Hotels, Multi-Residential
Shopping Centers
Libraries
Public Use
Theaters
Broadcast Studios
Laboratory Space
Operating Areas
Patient Areas
Exterior Zone
Interior Zone
Exterior Zone
Interior Zone
ENGINEERING GUIDE
Single Duct
VAV Without Reheat
VAV With Reheat
Dual Duct
VAV No Mixing
VAV With Mixing
Constant Volume
Fan Powered
Parallel With Heat
Series Without Heat
Series With Heat
Low Temperature
Bypass
Terminal Type
Other Facilities
Small
Building
Noise Sensitive
Applications #
Large
Building
Hospitals,
Clean Rooms &
Laboratories*
Table 1.
=
=
=
* =
# =
G4
Office Space,
Educational &
Institutional Buildings
ENGINEERING GUIDE
Types of Terminal Units
All of the terminal units described below share several common components; corrosion resistant zinc coated steel
casing, sound absorbing internal insulation with coated edges and an erosion resistant facing and a throttling damper
to control conditioned air. Associated controls may be pneumatic, analog electronic or digital.
Single Duct
Description
Basic unit consists of a damper, actuator, flow sensor and selected controls. Accessory
discharge attenuators and multiple outlet attenuators are also frequently used.
Operation
SUPPLY
The terminal resets the volume (variable air volume) of conditioned air delivery to
the space in response to the room thermostat. The terminal can handle hot or cold
air. Occasionally, the terminal is used to control both hot and cold air, where a dual
function thermostat and inlet temperature sensing with change-over controls are
utilized.
Common Applications
Interior zones of a building which have a permanent cooling load and therefore no
heating requirement.
TO
OUTLETS
ENGINEERING GUIDE
Operation
SUPPLY
The terminal resets the volume of conditioned cold air delivery to the space in response to
the room thermostat. Upon a call for heat in the space the heating coil is energized and
reheats the conditioned air. Electric coils are activated in stages upon thermostat demand
and water coils are modulated using a proportional or two position on/off hot water valve.
Common Applications
1. Exterior zones (adjacent to outside walls or the upper floor in the case of multistory buildings) where convective and radiated heat losses create an intermittent
need for moderate heating as the terminal usually reheats at the minimum setting.
An auxiliary higher minimum setting is available as an option with additional
controls.
2. Interior zones where ventilation requirements preclude full shut-off of the
terminal or minimum airflow requires some added heat.
TO
OUTLETS
HOT
TO
OUTLETS
COLD
TO
OUTLETS
Operation
The terminal unit resets the volume flow of either hot or cold air (without mixing) to
the space in response to the room thermostat. Air is supplied from a dual duct
central air handling unit. There is no provision for mixing and therefore hot and cold
air should not be supplied simultaneously as stratification in the discharge duct will
occur, causing uneven temperature discharge from outlets.
Common Applications
Exterior zones in buildings (such as hospitals) where overhead heating and cooling
is desired but use of auxiliary hot water coils is not feasible and zero to low
minimum flow is acceptable during changeover.
G5
ENGINEERING GUIDE
Dual Duct (Mixing)
Description
Basic unit incorporates separate cold and hot air inlets and volume control assemblies
consisting of a damper, actuator, flow sensor and selected controls, and a common
mixing / attenuator section which minimizes stratification of the discharge airstream.
HOT
TO
Operation
The terminal unit resets the volume flow of the hot and cold air supply ducts in response
to the room thermostat. Airflow delivery to the space may be variable volume (with a
minimum flow established through a mixing of the two airstreams) or constant volume.
OUTLETS
COLD
MIXING
ATTENUATOR
Common Applications
Interior and exterior zones in buildings (such as hospitals) where overhead heating and
cooling is desired but use of an auxiliary heat coil is not feasible.
INDUCED
AIR
Basic unit consists of a primary air damper, actuator, flow sensor, blower / motor (with
flow adjustment), and selected controls. Accessory heating coils either hot water or
electric are also generally required.
TO
Operation
ENGINEERING GUIDE
The primary air damper throttles conditioned cold air in response to the room thermostat and
delivers this air stream to the mixing chamber upstream of the blower/motor located in series
with the primary airflow. The blower/motor then delivers a constant volume of air to the
space. Upon demand for maximum cooling, the airflow is derived entirely from the
conditioned air supply. As the cooling demand diminishes, the primary damper reduces the
conditioned air supply and the blower/motor compensates for this reduction by inducing
make-up quantities of plenum air from the ceiling plenum thereby reclaiming otherwise
wasted heat and mixing it with the conditioned air to maintain a constant volume variable
temperature delivery of air to the space. Upon further reductions in space temperature, the
supplemental heating coil is energized. The result is a constant volume of air diffusion to the
space while the central system encounters a variable volume distribution system.
FAN
PRIMARY
INLET
OUTLETS
Common Applications
1. Exterior zones where heating and cooling loads may vary considerably and occupancy
variances allow the central system to be shut-down or set-back during unoccupied hours.
2. Situations where central system economy is desired as central fans can be reduced
in size because they only need to provide sufficient static to deliver air to the terminal.
3. Where occupant comfort is very important since the constant volume air variable
temperature delivery produces optimal air distribution and optimum ventilation.
Description
A terminal similar to above, but incorporating special design and construction
features that provide unusually quiet operation.
Operation
As described on page above.
Common Applications
As described above, but premium performance and high quality construction are
ideally suited to high profile design projects and applications requiring minimum
noise. Especially suitable for larger zones than standard series flow fan powered
terminal units, as reduced radiated sound levels can lower first cost.
G6
FAN
PRIMARY
INLET
OUTLET
ENGINEERING GUIDE
Low Profile Fan Powered Series Flow (Constant Volume)
INDUCED
AIR
Description
Similar in construction to the standard series flow terminal described earlier, but
only 11" (279) in height for all sizes, to minimize the depth of ceiling space required.
Unlike standard fan powered terminals, the fan / motor assembly is installed flat on
its side as shown in the diagram. Sound power levels are somewhat higher than
standard units. A "Stealth" model is also available from Nailor.
FAN
OUTLET
PRIMARY
INLET
Operation
As described on page G6.
Common Applications
As described on page G6. Where zoning requirements limit building height and the
architect wishes to maximize the number of floors, these units will fit in a shallow ceiling
plenum as small as 12" (305) deep.
Operation
Common Applications
General building applications described on page G6 where maintenance and
assurance of high Indoor Air Quality (IAQ) standards are a prime concern e.g.
schools.
INDUCED
AIR
G
FAN
OUTLET
PRIMARY
INLET
ENGINEERING GUIDE
As described on page G6. The second air inlet, which is usually smaller than the
primary air inlet, provides a constant volume of outside air to the zone, ensuring the
minimum ventilation air requirements are met.
OUTSIDE
AIR INLET
THERMALLY
ISOLATED
INLET COLLAR
INDUCED
AIR
Operation
Same as Fan Powered Series (Constant Volume) description above.
The maximum cold air volume is established lower than the fan delivery volume in
order to maintain the minimal mixing required to raise and temper the unit discharge
air temperature to a level acceptable for introduction to the occupied space, usually
55F (13C), with standard air outlets and to maintain ceiling coanda effect.
Common Applications
This unit is used with chilled water/ice storage systems that are designed to provide
low temperature [40 48F (4 9C)] central system air distribution to the zone
terminals.
FAN
OUTLET
PRIMARY
INLET
STERI-LINER
INSULATION
This low profile terminal is designed to fit between the pedestal support grid of
raised, or access floor system HVAC designs, without any modifications to the floor.
Available in two unit sizes, only 8" (203) or 11" (279) deep and 20" (508) wide.
FAN
PRIMARY
INLET
OUTLET
G7
ENGINEERING GUIDE
Fan Powered Parallel Flow (Variable Volume)
INDUCED AIR
Description
Basic unit consists of a primary air damper, actuator, flow sensor, blower/motor
assembly (with flow adjustment) and selected controls. An accessory heating coil,
either hot water or electric, is usually required to satisfy space load conditions.
FAN
Operation
The primary air damper throttles the conditioned cold airflow in response to the
room thermostat. As the room temperature decreases, the primary damper throttles
toward its minimum flow setting and the unit blower, situated in parallel outside the
primary airstream, is energized to provide warm ceiling plenum air to the space. A
further drop in space temperature energizes the supplementary heating coil. The
resultant control provides variable volume air diffusion to the space as well as a
variable air volume distribution system to the central equipment.
Common Applications
PRIMARY
AIR
OUTLET
ENGINEERING GUIDE
Bypass Terminals
Description
INLET BALANCING
DAMPER
Operation
AIRFLOW
The terminal delivers conditioned air to the space during periods of maximum
cooling requirements (as determined and signalled by the room thermostat). As
cooling demands diminish, the unit damper is modulated to bypass increasing
amounts of conditioned air to the ceiling plenum. The result is a variable volume air
supply to the space while a relatively constant volume of air is maintained across
the central system air handling unit.
Common Applications
Bypass terminals are used primarily with packaged roof-top air conditioning
equipment with a direct expansion coil where zoning is desired, but relatively
constant airflows across the system components (i.e. coils, fans) are required. This
allows the coil to operate at 100% airflow at all times in order to avoid freeze-up.
The system offers an economical VAV supply design with low first cost. It does not
provide the energy saving advantages of variable fan volume, but avoids the
expense of a more sophisticated system.
G8
BYPASS BALANCING
DAMPER
Basic unit consists of a diverter type damper, actuator, bypass port and selected
pressure dependent controls. A balancing damper is required ahead of the inlet.
Accessory reheat coils are a common requirement.
TO
OUTLETS
DAMPER
DRIVESHAFT
ENGINEERING GUIDE
Introduction to VAV Terminal
Controls
SUPPLY
AIR
CONTROLS
ENCLOSURE
DIFFUSER
OCCUPIED SPACE
ROOM
THERMOSTAT
ENGINEERING GUIDE
Pressure Dependent
6.00
1b
4.00
2b
2.00
DAMPER
SETTING
#1
1.00
0.80
0.60
3b
0.40
DAMPER
SETTING
#2
0.20
0.10
0.08
0.06
4b
DAMPER
SETTING
#3
1a
0.04
DAMPER
FULL
OPEN
2a
0.02
3a
0.01
100
4a
200
300
400
1000
AIRFLOW (CFM)
G9
ENGINEERING GUIDE
the full open position, line 4a 4b. Pressure dependent
terminals are therefore more prone to constant hunting
when static pressures fluctuate at the terminal inlet, as
the thermostat is responding to variations in flow that it
didnt call for. Control accuracy is therefore poorer, when
compared to a pressure independent terminal.
The pressure dependent terminal is for applications
where neither pressure independence nor airflow limit
regulation is required at the terminal. An example is a
constant volume central air supply where the
downstream static pressure is held constant by other
controls. Another example utilizes a constant volume
central fan and zone bypass dampers that respond to
static pressure variations and short circuit excess air
directly back to the air handler.
SUPPLY
AIR
TO OUTLETS
DAMPER
ACTUATOR
THERMOSTAT
Pressure Independent
6.00
1b
3b
2b
4.00
MINIMUM
AIRFLOW
SETTING
2.00
ENGINEERING GUIDE
VARIABLE
AIRFLOW
SETTING
MAXIMUM
AIRFLOW
SETTING
1.00
0.80
0.60
0.40
0.20
3a
0.10
0.08
0.06
PE
AM
D
EN
2a
IDE
0.04
OP
W
s,
UM
1a
0.02
M
INI
0.01
100
200
300
400
1000
AIRFLOW (CFM)
SUPPLY
AIR
DAMPER
TO OUTLETS
FLOW
SENSOR
ACTUATOR
CONTROLLER
THERMOSTAT
G10
ENGINEERING GUIDE
Types of Controls
The various VAV controls available may include some or all of the following common components:
c) Flow Controller
This device is 'the brain' and receives the signals from the Flow Sensor and the Room Thermostat or Temperature Sensor and
processes the data to regulate the damper actuator.
d) Damper Actuator
This device receives the commands from the controller and opens or closes the damper to change or maintain the required airflow setting.
ROOM
THERMOSTAT
LINE
The room thermostat receives main air at full pressure directly from the air supply. In
response to room temperature changes, the air pressure is modulated to the controller,
which regulates the damper actuator and provides proportional control. A rise in
temperature drives the actuator open in the cooling mode and a fall in temperature
reverses the actuator in the heating mode.
The sensor and controller compensate for changes in duct pressure, so that operation is
pressure independent.
The controller allows the thermostat to modulate the airflow as the room temperature
dictates from a preset minimum to a preset maximum.
TRANSFORMER
ELECTRIC
DAMPER
ACTUATOR
ROOM
THERMOSTAT
PNEUMATIC
CONTROLLER
PNEUMATIC
DAMPER
ACTUATOR
T
M
DAMPER
TERMINAL
MAIN AIR
TERMINAL
DAMPER
ROOM
THERMOSTAT
ELECTRONIC
CONTROLLER
WITH ELECTRIC
DAMPER
ACTUATOR
T
TRANSFORMER
LINE
ROOM
THERMOSTAT
TERMINAL
DAMPER
DIGITAL CONTROLLER
WITH VELOCITY TRANSDUCER
LINE
ELECTRIC
DAMPER
ACTUATOR
TRANSFORMER
G11
ENGINEERING GUIDE
Traditional:
The room thermostat has single-pole-double-throw (SPDT) contacts. A rise in
temperature drives a slow cycling damper actuator open in the cooling mode and a fall
in temperature reverses the actuator in the heating mode.Thermostat response time to
room temperature change is typically less than the actuator response time. Control is
sluggish and large temperature swings may result.
State of the Art: Micro-processor based P + I thermostat provides superior control.
DAMPER
TERMINAL
ENGINEERING GUIDE
Types of Controls (continued)
Digital Control Overview
A direct digital controller uses a digital computer to implement control algorithms on one or multiple control loops. Interface hardware
allows the digital computer to process signals from various input devices. The control software calculates the required state of the
output devices, such as valve and damper actuators and fan starters. The output devices are then positioned to the calculated state
via interface hardware.
The basic principles of temperature control for heating, ventilation and air conditioning systems are well established. These control
strategies have been implemented using pneumatic, electric, and analog electronic control devices. In this computer age, the microprocessor technology is now available in applications specifically designed for HVAC control. Micro-processor based controllers bring
cost effective, state of the art computing power to the control of VAV terminal units, air handling units, packaged heating and cooling
units, and entire building HVAC systems.
Micro-processor based controllers use direct digital control to replace conventional pneumatic or analog electronic controls. A direct
digital controller takes input signals from sensors to generate numbers, processes this information digitally as directed by the
programmed sequence of operation, and generates control action through binary on/off outputs or analog output voltages.
100 %
THERMOSTAT OUTPUT SIGNAL
DIRECT
ACTING
THERMOSTAT
REVERSE
ACTING
THERMOSTAT
DAMPER
ACTUATOR
DAMPER
ACTUATOR
G12
100 %
100 %
MAX. SETTING
DIRECT
ACTING
THERMOSTAT
MAX. SETTING
AIRFLOW
AIRFLOW
ENGINEERING GUIDE
100 %
THERMOSTAT OUTPUT SIGNAL
Controls Terminology
MIN. SETTING
0
REVERSE
ACTING
THERMOSTAT
MIN. SETTING
0
ENGINEERING GUIDE
100 %
100 %
DA THERMOSTAT
DA CONTROLLER
(COLD AIR)
OR
RA THERMOSTAT
DA CONTROLLER
(HOT AIR)
MAX. SETTING
MAX. SETTING
AIRFLOW
AIRFLOW
MIN. SETTING
0
MIN. SETTING
0
ROOM TEMPERATURE INCREASE
DA THERMOSTAT
RA CONTROLLER
(HOT AIR)
OR
RA THERMOSTAT
RA CONTROLLER
(COLD AIR)
PROPORTIONAL BAND
RESET SPAN
OF CONTROLLER
(THROTTLING RANGE) MAXIMUM CFM
100 %
MAX. GPM
HOT WATER
VALVE
MODULATION
MINIMUM
CFM
STOP
POINT
RESET
START
POINT
0%
3
13
15
THERMOSTAT, PSI
Figure 24.
14
13
Thermostat Sensitivity
TEMPERATURE
SET POINT
CFM
ENGINEERING GUIDE
12
11
10
9
8
7
6
5
4
3
CALIBRATION
POINT
ADJUSTABLE
PROPORTIONAL
BAND
SET POINT
2
1
0
69
70
71
72
73
74
ROOM TEMPERATURE , F
Figure 25.
G13
ENGINEERING GUIDE
Features of Series and Parallel Flow Fan Powered Terminal Units
General
Fan powered variable air volume terminal units are the most economical, and consequently the most popular, way to
heat and cool many types of buildings today. Typically used for exterior zones, they have advantages for interior zones
as well.
Applications
Series
Parallel
Configuration
ENGINEERING GUIDE
Series
Parallel
The fan and VAV damper are aligned so that all the
conditioned air that enters the mixing section as well as
all the induced air that enters the mixing section must go
through the fan to exit the unit and enter the occupied
space. The mixing section is between the VAV damper
and the fan. See figure 26 below.
The fan and VAV damper are aligned so that all the
induced air enters the fan, but the conditioned air
bypasses the fan and mixes with the induced plenum air
on the discharge side of the fan. See figure 27 below.
RECIRCULATED
PLENUM AIR
RECIRCULATED
PLENUM AIR
FAN
FAN
PRIMARY
AIR
DISCHARGE
AIR
DISCHARGE
AIR
HEATER
PRIMARY
AIR
HEATER
Fan Design
Series
Parallel
G14
ENGINEERING GUIDE
VAV Cooling and Inlet Static Pressure Requirements
Series
Parallel
All the savings of VAV operation at the air handler and at the
chiller are retained by using the series unit. Additional savings
compared to single or dual duct VAV are realized due to the low
inlet static pressure requirement of the Nailor 35S. Since the air
handler is only required to push the conditioned air through the
ducts to the unit and across the VAV damper into the mixing
section, the pressure at the air handler can be greatly reduced.
Nailor 35S units require only 0.05" w.g. (12 Pa) static pressure at
the inlet to operate properly. This is much less than the
competition. Using the 35S allows the duct designer to reduce the
minimum static pressure in the upstream ductwork to (typically)
0.1 to 0.2" w.g. (25 50 Pa) or whatever is required to allow 0.05"
w.g. (12 Pa) at the terminal while allowing a further reduction in
horsepower and static pressure requirement from the air handler.
All the savings of VAV operation at the air handler and at the
chiller are incorporated in the parallel unit. Like the single or
dual duct VAV, the air handler must push the conditioned air
through the ducts to the unit, across the VAV damper, into
the mixing section, through the discharge duct from the unit
and across the diffuser(s) into the room. Compared to other
manufacturers, Nailor 35N units require very low static
pressure at the inlet to operate properly. This means that the
duct system should be designed for minimum static
pressure, typically 0.5 to 1.25" w.g. (125 310 Pa). Then the
air handler should be adjusted as low as possible to keep
the minimum requirement at the farthest VAV terminal unit.
Control Sequence
Parallel
During full cooling, the controls open the VAV damper to its
maximum set point while the fan does not run. Constant
volume, constant temperature air is then discharged into the
downstream ducts and into the conditioned space.
As cooling demand decreases, the VAV damper modulates
to lower setpoints. The unit delivers variable volume,
constant temperature air to the zone.
Upon a further decrease in zone temperature, the controls
will automatically energize the fan. Fan air and primary air
are blended in the mixing chamber on the discharge side of
the fan. The increased plenum air causes the discharge
temperature to rise to nearly meet the plenum temperature
as the zone temperature continues to fall. This takes
advantage of the recaptured heat from lights, people and
machinery. Blended, variable volume, variable temperature
air is delivered to the zone.
At this same point, the VAV damper will reach its minimum
set point. At some preset zone temperature, supplemental
heat (optional equipment), either electric or hot water coils
will be energized. The discharge temperature will increase
as heat is applied but volume will be constant beyond this
point.
As the temperature increases in the zone, the sequence will
reverse.
Fan Interlocks
Series
Parallel
G15
ENGINEERING GUIDE
Series
ENGINEERING GUIDE
Acoustics
ENGINEERING GUIDE
Series
Parallel
Energy Consumption
Fan powered VAV terminal units were originally designed and introduced to our industry for their ability to save energy.
That is what makes them so necessary and popular. They take advantage of typical VAV savings at the air handler and
the chiller during the cooling periods, but the real savings kick in when heating is required. Fan powered terminals
induce warm plenum air from the ceiling and blend it with the primary air at minimum ventilation requirements during
the heating sequence. This recaptures all the heat created in the zone and plenum by lights, occupants, solar loading,
and machinery or equipment such as computers, coffee machines, copiers, etc. Then the unit returns this heat as free
heating rather than wasting it back at the air handler. If additional heating is required, then supplemental heat is added
to the sequence, but the unit still saves energy by warming blended air at 75F (24C) rather than reheating primary
cooled air at 55F (13C), saving the cost of 20F (11C) at the heating airflow. Costs of operating the units pale in
comparison to the savings over other systems.
Series
Parallel
G16
ENGINEERING GUIDE
Fan Selection
Many times specifications call for fan selections to be
made using medium speed on the blower motor. This can
cause some concern with Nailor fan powered terminal
units because we use only single speed motors, and
consequently there is no medium speed for selecting the
equipment sizes. There is a solution.
Examine a Nailor fan curve like the one shown below
(figure 28). Then examine the comparative fan curve (also
illustrated) for a competitors unit using a 3 speed motor.
HIGH
HIGH
MEDIUM
MINIMUM
AIRFLOW
AIRFLOW
LOW
NAILOR
OTHERS
Introduction
When designing air systems and using fan powered VAV
terminal units, it is as important to match the fan air to the
space requirements as it is to match the primary air. This
is even more true on series units than on parallel units.
To facilitate this process, Nailor Industries designed their
units to work over a wide range of adjustability. Some
competitive products are not as friendly to adjust. The
two commonly used methods are electronic fan speed
control and mechanical trimming.
G17
ENGINEERING GUIDE
ENGINEERING GUIDE
SP
WG
1.0
TORQUE (OZ. IN.)
60
120
180
0.8
240
OPERATING
POINT
0.6
1200 RPM
0.4
1100 RPM
5
0.2
SYSTEM
10
TORQUE (OZ. FT.)
800 RPM
0
0
200
400
600
800
AIRFLOW, CFM
1000 RPM
15
20
1000
900 RPM
1200
PHASE CUT
SIGNAL TO MOTOR
Caution on Meters
Many digital multi-meters are not designed for true RMS
readings. Using these meters when measuring amps or
voltage on the motor in the fan powered terminal unit can
result in erroneous readings. To measure the correct
current and voltage, a true RMS DMM designed for this
type of sine wave is required. These meters can be
relatively expensive.
900
CFM
800
AIRFLOW, CFM
ENGINEERING GUIDE
Nameplate Ratings
700
600
RPM
500
400
WATTS
300
G18
200
100
0
140
160
180
200
220
RMS TO MOTOR
240
260
280
ENGINEERING GUIDE
Sizing Fan Powered Terminals
The selection of fan powered terminal units involves four
elements. How these elements are selected and their
interactive effect determine the final overall performance
of the units.
Q = 1.085 x cfm x t
t = Supply air temperature (SAT) Room
design temperature.
The supply air temperature (SAT) to the space equals the
leaving air temperature (LAT) for the terminal unit.
Once the terminal LAT is determined, the heating
requirements for the coil can be calculated. The leaving air
temperature for the coil varies based on the type of model.
It is generally a good idea to maintain air temperatures of
85 95F (29 35C) for air entering a room. This is LAT
off the heating coil. Air this temperature can be effectively
used to warm the room as it is not so buoyant that it
cannot be driven to the floor, and it is warm enough to not
produce chills from drafts.
Once both coil EAT (entering air temperature) and LAT
are calculated, the heat transfer (Q) for the coil must be
calculated, using the heat transfer equation. For electric
heat, the capacity must be converted from Btu/h to kWh
for selection. The required kW and number of steps
desired should be checked with availability from the
charts in the Performance Data section of the catalog.
For hot water coils, reference the capacity charts in the
Performance Data to select the appropriate coil.
RECIRCULATED
PLENUM AIR
FAN
HEATER
PRIMARY AIR
PRIMARY
AIR
VALVE
INTERNAL
Ps
DOWNSTREAM
DUCTWORK AND
DIFFUSERS
G19
ENGINEERING GUIDE
ENGINEERING GUIDE
In figures 32, 33 and 34, heating coils are located on the
unit discharge so LAT for the coil equals the LAT for the
terminal unit. Heating coil EAT equals the temperature of
blended primary air and plenum air.
RECIRCULATED
PLENUM AIR
FAN
HEATER
PRIMARY AIR
QT
PRIMARY
AIR
VALVE
INTERNAL
Ps
Where:
DOWNSTREAM
DUCTWORK AND
DIFFUSERS
FAN
PRIMARY AIR
PRIMARY
AIR
VALVE
ENGINEERING GUIDE
INTERNAL
Ps
(TO BE OVERCOME BY CENTRAL SYSTEM)
HEATER
DOWNSTREAM
DUCTWORK AND
DIFFUSERS
EXTERNAL Ps
OF FAN TERMINAL
4. Acoustics
Resulting sound levels are due to air valve generated
noise and fan generated noise. The maximum noise
generated by a given air valve size is determined by the
difference between design inlet static pressure (the
valves most pressurized condition) and external static
pressure at design cooling airflow. This represents the
most extreme operating condition.
To determine fan noise levels, fan airflow (adjusted within
its range by the speed controller) and external static
pressure conditions are required.
The acoustical performance data is presented in two
formats for the parallel and series type as their sequence
of operation differs. With a parallel unit, air valve and fan
operation are evaluated separately as their operations
are not simultaneous under most conditions. With a
series unit, air valve and fan are evaluated together for
cooling, as they operate simultaneously and fan only for
heating, in the occupied mode (in the unoccupied mode,
a night setback fan cycling option is available).
G20
ENGINEERING GUIDE
Example: Parallel Terminal with Hot
Water Heat
Select a Model 35NW for a maximum/minimum primary
airflow at 1000/250 cfm with 1" w.g. inlet static pressure.
The heating airflow required is 600 cfm. Downstream
resistance at 1000 cfm is 0.4" w.g.. Zone design heat loss
is 20,000 Btu, design room temperature 72F, plenum air
temperature 75F, primary air temperature 55F.
RECIRCULATED
PLENUM AIR
FAN
Fan Selection:
Fan heating airflow = Heating airflow (600 cfm) primary
airflow (250 cfm) = 350 cfm.
The downstream static pressure the fan must overcome
is the fan airflow plus primary airflow (600 cfm) and since
this is less than maximum design airflow (1000 cfm); fan
downstream S.P. = (600/1000)2 x 0.4 = 0.144" w.g..
From the fan curves a size 2 unit will handle 350 cfm at
0.144" S.P. with correct setting of the speed controller and
allows for the selection of a one or two row hot water coil.
DISCHARGE
AIR
PRIMARY
AIR
Disch.
63
64
61
53
54
55
Rad.
61
56
52
40
40
40
Disch.
54
44
47
42
38
33
Rad.
50
49
49
42
34
30
G21
ENGINEERING GUIDE
ENGINEERING GUIDE
Example: Series Terminal with
Electric Heat
Select a Model 35SE to supply a constant 1500 cfm with
0.5" w.g. inlet static pressure. Minimum primary airflow is
375 cfm and downstream resistance due to ductwork and
diffusers is 0.4" w.g.. Zone design heat loss is 45,000
Btu, design room temperature 72F, plenum air
temperature is 75F, primary air temperature 55F.
Air Valve Section: Choose a size 12 inlet with a
minimum wide open pressure drop of 0.05" w.g.. The
damper will throttle to maintain desired airflow.
Fan Selection:
ENGINEERING GUIDE
FAN
PRIMARY
AIR
TEMPERATURE
= 55F
COIL LAT
(SAT)
= 100F
HEATER
COIL EAT = 70F
Octave Band
Discharge
69
69
69
68
65
65
SAT = 100F
Radiated
74
67
63
56
58
57
G22
ENGINEERING GUIDE
Terminal Installation and Application Precautions
Avoiding Common Errors and Problems
Sizing Terminals
MAXIMUM
FLOW
TOO
LOW
G
MAXIMUM
FLOW
IDEAL
COIL
During the design phase try and ensure terminals are located
for ease of installation, optimum performance and
maintenance accessibility. Figure 39 shows all of the worst
conditions: a convoluted inlet, controls and heating coil
connections are restricted as the terminal is against a wall and
the outlet restricted condition reduces performance.
TERMINAL
UNIT
TERMINAL
UNIT
INLET TAPPED
DIRECTLY OFF
MAIN DUCT
SHORT RADIUS
ELBOW AT INLET
TERMINAL
UNIT
TERMINAL
UNIT
SUPPLY DUCT
SMALLER THAN INLET
CONVOLUTED FLEXIBLE
DUCT
G23
ENGINEERING GUIDE
ENGINEERING GUIDE
Sometimes it is not possible due to space restrictions to
provide an ideal inlet condition. In this case field
adjustment of the airflow settings on the velocity
controller may be required to compensate. The use of
flow straightening devices (equalizing grids) are
recommended after short radius elbows that are
immediately ahead of the terminal and where terminals
are unavoidably tapped directly off the main duct.
ENGINEERING GUIDE
TERMINAL
UNIT
DIFFUSER
DIFFUSER
DIFFUSER
90F
TOO HOT
(INTERIOR
ZONE)
T 72F
TOO COLD
(EXTERIOR
ZONE)
TEE AT
DISCHARGE
TERMINAL
UNIT
TERMINAL
UNIT
EXCESSIVELY LONG
FLEX DUCT
CONVOLUTED
FLEX DUCT
277 VAC
24 VAC
FUSE BLOCK
277 VAC
CONTROL
TRANSFORMER
24 VAC
G24
ENGINEERING GUIDE
Power Source Compatibility
Terminals with an electrical power supply such as fan
powered terminals and single duct terminals with electric
heat should be checked for compatibility with source.
Voltage, phase and frequency must match. Where motor
voltage differs, the single phase voltage requirement
must be tappable from a three phase (4 wire wye) power
source.
L1
L1
L2
L2
L3
L3
3 PHASE
4 WIRE WYE
3 PHASE
3 WIRE
NEUTRAL
COMPRESSION STRAP ON
FLEXDUCT TO ENSURE
AIRTIGHT JOINT.
OPTIONAL
HOT WATER COIL
BASIC
AIR
TERMINAL
PROTECTIVE
5/16" OR 3/8" (8 OR 10) DIAMETER HANGER RODS
METAL
SECURED TO BUILDING STRUCTURE.
SHROUD
DAMPER
SHAFT
OPTIONAL
SOUND
ATTENUATOR
SLIP& DRIVE
CONNECTIONS
DUCT
TERMINAL INLET
COIL
AND DISCHARGE CONNECTION
BRANCH
TAKE-OFF
TERMINAL
UNIT
DIFFUSER
NECK
G25
ENGINEERING GUIDE
Estimating Sound Levels
Room Type
1. Noise Criteria - NC
NC level or Noise Criteria is a widely accepted and popular
way for many engineers to estimate and predict room noise
levels. NC levels are also used as a rating scale for
equipment that is expected to operate within certain levels.
Sound Power levels for VAV terminal units are expressed
over six octave bands: 2, 3, 4, 5, 6 and 7. Each octave band
is defined by the center frequency within that particular band.
Frequency is measured in Hz. Each of these respective
frequencies and octave bands are shown in Table 1.
Octave Band
3
250
ENGINEERING GUIDE
80
70
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-25
NC-20
NC-15
10
63
125
250
500
1000
2000
4000
8000
G26
RC (N) or
NC Levela,b
25 35
25
25
35
35
35
35
45
45
25 35
25 35
25 (max)
30 40
30 45
25
30
25
30
35
40
35
40
25 (max)
25 (max)
35 (max)
45 55
40 50
35 45
25 35
25 35
40 (max)
35 (max)
35 (max)
30 40
25 35
30 40
40 50
45 55
ENGINEERING GUIDE
The ARI 885 Standard forms the basis for the sound
estimation guidelines and examples presented on the
following pages. For a more detailed analysis, refer to
ARI Standard 885-98, the 1997 ASHRAE Fundamentals
Handbook, chapter 7 and the 1999 ASHRAE HVAC
Applications Handbook, chapter 46.
Octave Band
dB Reduction
3. Sound Paths
In order to estimate the sound power level in the occupied
space, one must first identify the sound source and then
determine by which paths the sound enters the occupied space.
The example in Figure 2 illustrates a fan powered terminal as
the sound source and identifies all the sound paths. These are:
1. Upstream Duct Breakout Radiated
This is the sound generated by the terminal unit which
is transmitted through the upstream ductwork.
G
3A.
DUCT
BREAKOUT
2. RADIATED
UNIT INLET
& CASING
RADIATED
1.
UPSTREAM
DUCT
BREAKOUT
RADIATED
3B.
DUCT
BREAKOUT
RADIATED
4.
OUTLET
DISCHARGE
5.
OUTLET
GENERATED
3C.
DUCT
BREAKOUT
RADIATED
4. Radiated Sound
Fig. 3 illustrates the sound path for casing and inlet
radiated sound. The attenuation factors that apply to this
sound path are Ceiling/Space Effect and Environmental
Adjustment Factor (which was presented earlier).
G27
ENGINEERING GUIDE
ENGINEERING GUIDE
Ceiling / Space Effect
ENGINEERING GUIDE
16
18
20
26
31 36
18
27
21
27
25
29
29 35
29 30
5. Discharge Sound
Figure 4 illustrates the sound path for outlet discharge sound.
The attenuation factors which apply to this sound path are:
Environmental Adjustment Factor
Lined Duct Insertion Loss
Elbow and Tee Loss
Branch Power Division
Lined Flexible Duct Insertion Loss
End Reflecton Factor
Space Effect
Octave Band
2
0.4
0.4
0.3
0.3
0.3
0.3
0.2
0.3
0.3
0.3
0.2
0.3
0.3
0.3
0.3
0.2
0.3
0.4
0.4
0.3
0.3
0.4
3
1.0
0.8
0.8
0.7
0.6
0.6
0.4
0.8
0.7
0.7
0.5
0.6
0.6
0.8
0.6
0.5
0.6
0.9
0.8
0.7
0.6
0.8
4
2.1
1.9
1.8
1.7
1.6
1.7
1.3
1.8
1.7
1.7
1.4
1.7
1.6
1.8
1.6
1.4
1.6
2.0
1.9
1.7
1.6
1.9
5
4.4
4.0
3.9
3.7
3.3
3.5
2.7
3.7
3.6
3.5
3.0
3.5
3.3
3.8
3.3
2.9
3.3
4.2
4.1
3.6
3.3
4.0
6
4.7
4.1
3.7
3.5
2.9
3.0
2.0
3.7
3.3
3.3
2.4
3.2
2.9
3.7
2.9
2.4
2.9
4.4
4.2
3.3
2.9
4.1
7
3.1
2.8
2.6
2.5
2.2
2.3
1.7
2.6
2.4
2.4
1.9
2.3
2.2
2.6
2.2
1.9
2.2
2.9
2.8
2.4
2.2
2.8
G28
ENGINEERING GUIDE
Elbow and Rectangular Tee Loss
Lined and unlined rectangular elbows provide attenuation
as per Tables 6a & 6b. Tee fittings can be considered as
if they are two elbows side by side, where mean duct
width for estimation purposes from Tables 6a & 6b is
taken as being 1/2 of the actual duct width. See Figure 5.
% of Total Flow
60
50
40
30
20
15
10
dB Attenuation
10
13
Octave Band
3 4 5 6
0 1 5 8
5 5 8 4
5 8 4 3
8 4 3 3
0 1 6 11
6 6 11 10
6 11 10 10
11 10 10 10
7
4
3
3
3
10
10
10
10
2
0
1
4
4
0
1
4
4
Octave
3 4
0 1
4 6
6 6
6 6
0 1
4 7
7 7
7 7
Band
5 6
4 6
4 4
4 4
4 4
4 7
7 7
7 7
7 7
7
4
4
4
4
7
7
7
7
Duct Dia.
Duct Length
inches (mm)
ft. (m)
3 (3.0)
4 (100)
5 (1.5)
10 (3.0)
3 (0.9)
5 (125)
5 (1.5)
10 (3.0)
3 (0.9)
6 (150)
5 (1.5)
10 (3.0)
3 (0.9)
7 (175)
5 (1.5)
10 (3.0)
3 (0.9)
8 (200)
5 (1.5)
10 (0.9)
3 (0.9)
10 (250)
5 (1.5)
10 (3.0)
3 (0.9)
12 (300)
5 (1.5)
10 (3.0)
3 (0.9)
14 (350)
5 (1.5)
10 (3.0)
3 (0.9)
16 (400)
5 (1.5)
10 (3.0)
2
5
7
10
5
6
10
5
6
10
5
6
10
4
6
10
4
5
9
3
4
8
2
3
6
1
2
4
Octave
3 4
4 12
5 16
9 27
5 13
7 17
12 28
6 13
9 18
15 28
7 14
10 18
16 29
7 14
10 18
18 29
7 14
11 18
19 28
6 12
9 16
17 26
4 10
7 14
13 23
0
8
2 11
7 19
Band
5
6
20 23
24 27
33 38
19 21
23 25
33 37
17 19
22 24
33 35
16 17
21 22
33 34
15 16
20 21
32 32
12 13
18 18
31 29
10 11
16 15
29 26
9
9
14 13
26 23
8
8
12 11
24 20
7
15
18
24
13
16
23
11
15
22
10
13
21
8
12
20
6
9
18
4
7
15
4
6
12
4
5
8
G29
ENGINEERING GUIDE
Duct Width
Inches
mm
5-10 100-125
11-20 260-700
Unlined Duct
21-40 710-1000
41-80 1010-2000
5-10 100-125
11-20 260-700
Lined Duct
21-40 710-1000
41-80 1010-2000
ENGINEERING GUIDE
End Reflection Factor
When plane wave sound passes from a small space such
as a duct into a large space the size of a room, a certain
amount of sound is reflected back into the duct,
significantly reducing low frequency sound. See Table 9.
The values of Table 9 apply to straight runs of duct
entering a room, therefore caution should be exercised
when a condition differs drastically from the test
conditions used to derive the table.
Room
Volume
3
2000 ft.
(56 m3)
2500 ft.
(69 m3)
Duct Dia.
inches (mm)
6 (152)
8 (203)
10 (254)
12 (305)
16 (406)
2
12
9
8
6
5
3
6
5
3
3
2
Octave Band
4
5
3
1
2
0
1
0
1
0
0
0
6
0
0
0
0
0
7
0
0
0
0
0
3000 ft.
(83 m3)
5000 ft.
(140 m3)
Distance
from Source
5 ft. (1.5 m)
10 ft. (3.0 m)
15 ft. (4.6 m)
5 ft. (1.5 m)
10 ft. (3.0 m)
15 ft. (4.6 m)
5 ft. (1.5 m)
10 ft. (3.0 m)
15 ft. (4.6 m)
5 ft. (1.5 m)
10 ft. (3.0 m)
15 ft. (4.6 m)
Octave Band
2 3 4 5
6 7
5
6
7 7 8 9
8
9 10 11 11 12
10 10 11 12 13 14
5
6
7 8 9 10
8
9 10 11 12 13
10 11 12 13 14 14
6
7
7 8 9 10
9 10 10 11 12 13
10 11 12 13 14 15
7
8
9 9 10 11
10 11 12 12 13 14
12 12 13 14 15 16
ENGINEERING GUIDE
Space Effect
G30
ENGINEERING GUIDE
NC
15
20
25
30
35
40
45
50
2
36
40
44
48
52
56
60
64
3
29
33
37
41
45
50
54
58
Octave
4
22
26
31
35
40
45
49
54
Band
5
17
22
27
31
36
41
46
51
6
14
19
24
29
34
39
44
49
7
12
17
22
28
33
38
43
48
10
20
dB addition
10
13
2
1.5
42
43
1
0.5
0
0 2 4 6 8 10
DIFFERENCE BETWEEN TWO LEVELS
TO BE ADDED, dB
Ceiling
Height
200 ft 2 (18.6m2)
300 ft 2 (27.8 m2)
8 ft. (2.4 m)
Octave Band
3 4 5 6
10
10
10
10 11
10 11 12
9 ft. (2.7 m)
G31
ENGINEERING GUIDE
No. of Outlets
ENGINEERING GUIDE
Example 1:
Determining Sound Pressure Levels at
Receiver Location from Radiated and
Discharge Paths.
A size 4 12 Model 35SST 'STEALTH' fan powered
terminal unit is selected to deliver 1100 cfm at 0.5" w.g.
inlet static pressure, with 0.25" w.g. downstream
resistance. The unit serves four rooms, each with its own
supply outlet with the distribution ductwork as illustrated in
Figure 7. The terminal unit is located in the ceiling plenum
above a mineral fiber tile ceiling in one of the rooms.
The results are tabulated in Table 14 below radiated sound
being applicable only for the room above which the terminal
is located and discharge sound applicable to each room.
ENGINEERING GUIDE
5 ft. (1.5 m)
LINED DUCT
15" x 15"
(381 x 381)
35SST 'STEALTH'.
SIZE 4. 12" (305) INLET.
1100 CFM @
1/2" (13) WG Ps.
(Page D31)
(Table 3)
(Table 5)
(Table 6a)
(Table 7)
(Table 8)
(Table 7)
(Table 9)
(Table 10)
63
2
16
45
57
1
18
38
Octave Band
4
5
51
0
20
31
43
0
26
17
39
0
31
8
37
0
36
1
64
2
2
0
3
0
6
3
9
5
34
64
1
4
0
3
0
10
3
5
6
32
66
0
9
1
3
0
18
3
2
7
23
63
0
18
5
3
0
20
3
0
8
6
59
0
17
8
3
0
21
3
0
9
57
0
12
4
3
0
12
3
0
10
13
(NC = 26)
(NC = 19)
Table 14: Resultant Radiated and Discharge Sound Pressure Levels due to terminal unit for Example 1.
Note: * = Less than zero dB.
G32
ENGINEERING GUIDE
Example 2:
Determining Sound Pressure Level at
Receiver Location from Air Outlet Sound
Path.
Let us assume the same terminal selection and operating
conditions as in the previous Example 1, but instead of
supplying four rooms, the terminal is now supplying two
larger rooms, each supplied by two diffusers. (Figure 8).
The diffusers selected are Nailor Model RNS, 24" x 24"
(610 x 610) ceiling module, 8" (203) dia. neck, each
handling 275 cfm (1100 4). From page D82 in 2005 Air
Distribution Catalog; NC = 20.
Octave Band
22
+10
35 32 27
0
0
0
-9 -9 -10
+3 +3 +3
29 26 20
Example 3:
Determining Total Overall Sound Pressure
Level at Receiver Location.
Using the same terminal selection, operating conditions,
room layout and diffuser selection as in Example 2
above, the contributions of the critical sound paths must
be combined to obtain the total Lp at the receiver
location. The discharge and radiated sound paths are
modeled in a similar fashion to Example 1, but with
adjustments for room size and number of outlets.
2
5 ft. (1.5 m)
UNLINED DUCT
35SST 'STEALTH'.
SIZE 4. 12" (305) INLET.
1100 CFM @
1/2" (13) W.G. Ps.
Octave Band
5 ft. (1.5 m)
LINED DUCT
15" x 15" (381 x 381)
ENGINEERING GUIDE
Disch.
Outlet
Octave Band
2 = 45 + 35 + = 45
3 = 38 + 33 + = 39
4 = 31 + 24 + 29 = 34
5 = 17 + 8 + 26 = 27
6 = 8 + 0 + 20 = 20
7 = 1 + 15 + = 15
Plot sound pressure levels on NC curve chart. (Figure 1).
Result: Overall Room NC Level = 29.
G33
ENGINEERING GUIDE
Acoustic Design and Installation
Considerations
To help ensure an acceptable NC Level in the occupied
space, engineers can minimize the sound contribution of
air terminals by taking into account several design
considerations and by using the following guidelines for
good design practice.
1. Design systems to operate at low (minimum) supply
static pressure at the primary air inlet. This will reduce the
generated sound level, provide more energy efficient
operation and allow the central fan to be downsized.
Excessive static pressure generates noise.
ENGINEERING GUIDE
> 2D
1.
MINIMIZE
INLET
STATIC
2.
STRAIGHT
METAL INLET
DUCT
TERMINAL
UNIT
3.
CAREFUL
TERMINAL
SELECTION
8. MAXIMUM VELOCITY
1000 fpm (5 m/s)
4 & 5.
OPTIMAL
INSTALLED
LOCATION
6.
RETURN AIR
GRILLE LOCATION
7.
LINED
DISCHARGE
DUCTWORK
10.
CEILING
TYPE
9.
INSULATED
FLEX DUCT
AND SMALLER
DIFFUSER
SELECTION
SUPPLY AIR
DIFFUSER
Figure 9: Guidelines for VAV and Fan Powered Terminal Unit Installation for Optimal Acoustic Performance.
G34
ENGINEERING GUIDE
Useful Formulas and Definitions
Power DC Circuits
Airflow
Q
Q
V
A
=
=
=
=
VxA
Airflow Rate, cfm (l/s)
Velocity, fpm (m/s)
Area, ft2 (m2)
hp
= E x I x Eff.
746
= ExI
Eff.
= 746 x bhp
W
Pressure
Imperial Units
Metric Units
2
VP =
V (fpm)
VP (Pa) =
V (m/s)
(" w.g.)
4005
1.3
VP = Velocity Pressure
TP
TP
SP
= SP + VP
= Total Pressure, " w.g. (Pa)
= Static Pressure, " w.g. (Pa)
PF
Eff.
= 746 x hp
E x I x PF
kW
= E x I x PF x Eff.
1000
Heat Transfer
Water Coils
Imperial Units
Metric Units
o
o
t( F)= 927 x Mbh
t ( C) = 829 x kW
cfm
l/s
t
= Air Temperature Rise
Mbh = 1000's of Btu's/hr.
o
o
t( F)= 2.04 x Mbh
t ( C) = 0.244 x kW
GPM
l/s
t
= Water Temperature Drop
GPM = Water Flow, gallons per minute
l/s = Liters per second
o
kW
= cfm x t
3160
t
kW
hp
= E x I x PF x Eff.
746
kVA = I x E
1000
=
746 x hp
1.732 x E x PF x Eff.
Eff.
kW
= E x I x PF x 1.732
1000
hp
= E x I x 1.732 x PF x Eff.
746
Electric Coils
t( F)= kW x 3160
cfm
746 x hp
E x Eff. x PF
ENGINEERING GUIDE
Imperial Units
Metric Units
o
o
H
= 1.085 x cfm x t ( F) H= 1.23 x l/s x t ( C)
H
= Heat Transfer, Btu's/hr. H = Heat Transfer, watts
Btu = British Thermal Unit
t
= Temp. Differential
W
ExI
W
E x I x 1.732
746 x hp
E x I x PF x 1.732
kVA = 1.732 x I x E
1000
PF
W
E
I
hp
Eff.
=
=
=
=
=
=
Power Factor
Watts
Volts
Amperes
Horsepower
Efficiency
G35
ENGINEERING GUIDE
Imperial / Metric Guide Conversion Factors
Quantity
Imperial Unit
square foot
square inch
Density
pounds per cubic foot
British thermal unit (BTU)
kilowatt
hour
Energy
watts per second
horsepower hour
ounce force
Force
pound force
kilogram force
BTU
per hour
Heat
BTU per pound
inch
foot
Length
foot
yard
Mass
ounce (avoirdupois)
(weight)
pound (avoirdupois)
horsepower
horsepower (boiler)
Power
foot pound - force per minute
ton of refrigeration
inch of water column
foot of water column
Pressure
inch of mercury column
ounces per square inch
pounds per square inch
Temperature Fahrenheit
ounce - force inch
Torque
pound - force inch
pound - force foot
feet per second
Velocity
feet per minute
miles per hour
cubic foot
cubic inch
Volume
cubic
yard
(capacity)
gallon (U.S.)
gallon (imperial)
cubic feet per minute (cfm)
cubic feet per minute (cfm)
Volume
cubic feet per hour (cfh)
(flow)
gallons per minute (U.S.)
gallons per minute (imperial)
Area
ENGINEERING GUIDE
G36
Metric Unit
square meter
square millimeter
kilograms per cubic meter
joule
megajoule
joule
megajoule
newton
newton
newton
watt
joules per kilogram
millimeter
millimeter
meter
meter
gram
kilogram
kilowatt
kilowatt
watt
kilowatt
kilopascal
kilopascal
kilopascal
kilopascal
kilopascal
Celsius
millinewton-meter
newton-meter
newton-meter
meters per second
meters per second
meters per second
liter
cubic centimeter
cubic meter
liter
liter
liters per second
cubic meters per second
milliliters per second
liters per second
liters per second
(m2)
(mm2)
(kg/M3)
(J)
(MJ)
(J)
(MJ)
(N)
(N)
(N)
(W)
(J/kg)
(mm)
(mm)
(m)
(m)
(g)
(kg)
(kW)
(kW)
(W)
(kW)
(kPa)
(kPa)
(kPa)
(kPa)
(kPa)
(C)
(mN.m)
(N.m)
(N.m)
(m/s)
(m/s)
(m/s)
(l)
2
(cm )
3
(m )
(l)
(l)
(l/s)
3
(m /s)
(ml/s)
(l/s)
(l/s)
From Imperial
To Metric
Multiply By:
0.0929
645.16
16.018
1055.056
3.6
1.0
2.6845
.278
4.4482
9.8067
.2931
2326.0
25.4
304.8
.3048
.9144
28.350
.4536
.7457
9.8095
.0226
3.517
.2486
2.9837
3.3741
.4309
6.8948
5/9(F-32)
7.0616
.1130
1.3558
.3048
.00508
.44704
28.3168
16.3871
.7646
3.785
4.546
.4719
.0004719
7.8658
.06309
0.7577
From Metric
To Imperial
Multiply By:
10.764
.00155
.0624
.000948
.2778
1.0
.3725
3.597
.2248
.102
3.412
.00043
.0394
.00328
3.2808
1.0936
.0353
2.2046
1.341
.1019
44.254
.2843
4.0219
.3352
.2964
2.3206
.145
(9/5C)+32
.1416
8.8495
.7376
3.2808
196.85
2.2369
.03531
.06102
1.308
.2642
.2120
2.119
2119.0
.127133
15.850
13.198
ENGINEERING GUIDE
Pressure Measurement
Concepts of Pressure. Pressure is force per unit area. This may also be defined as energy per unit volume of fluid. There
are three categories of pressure Total Pressure, Static Pressure and Velocity Pressure. They are all associated with air
handling. Unit of pressure is expressed in inches of water, designated in. w.g.
Static Pressure is the normal force per unit area at a small hole in the wall of a duct or other boundaries. It is a function of air
density and degree of compression. It may be thought of as the pressure in a tire or in a balloon which extends in all directions.
Velocity Pressure is the force per unit area capable of causing an equivalent velocity in moving air. Velocity pressure is
a function of air density and velocity. At standard air density, the relationship between velocity pressure and velocity is
expressed in the following formula:
Pv =
( )
V
2 or V = 4005
Pv
4005
Where:
PS
A
PS
PV = P - PS
T
SECTION A-A
PS
STATIC PRESSURE
TOTAL PRESSURE
G37
ENGINEERING GUIDE
Total Pressure, as its name implies, is the sum of static pressure and velocity pressure.
The Pitot Static Tube is an instrument used to measure pressure and velocities as illustrated below. It is constructed of
two tubes. The inner, or impact tube, senses the total pressure as the impact opening faces upstream. The outer tube
senses only the static pressure, which communicates with the airstream through small holes in its wall.
The U-Tube Manometer connects both parts of the Pitot Static Tube. The manometer functions as a subtracting device
to give a reading of velocity pressure.
ENGINEERING GUIDE
CONVERSION CHART for converting VELOCITY PRESSURE
in inches of water to VELOCITY in feet per minute
Note: This chart is based upon standard air conditions of 70 Fahrenheit and 29.92 inches of mercury (barometric
pressure), and assumes that the airflow is essentially non-compressible (under 10 inches of water pressure); as
reflected by the following formula.
ENGINEERING GUIDE
VP
.001
.002
.003
.004
.005
.006
.007
.008
.009
.010
.011
.012
.013
.014
.015
.016
.017
.018
.019
.020
.021
.022
.023
.024
.025
.026
.027
.028
.029
.030
.031
.032
.033
.034
.035
.036
.037
.038
.039
.040
.041
.042
.043
.044
.045
.046
.047
.048
.049
.050
.051
.052
.053
.054
.055
.056
.057
.058
.059
.060
.061
G38
V
127
179
219
253
283
310
335
358
380
400
420
439
457
474
491
507
522
537
552
566
580
594
607
620
633
645
658
670
682
694
705
716
727
738
749
759
770
780
791
801
811
821
831
840
849
859
868
877
887
896
904
913
922
931
939
948
956
964
973
981
989
VP
.062
.063
.064
.065
.066
.067
.068
.069
.070
.071
.072
.073
.074
.075
.076
.077
.078
.079
.080
.081
.082
.083
.084
.085
.086
.087
.088
.089
.090
.091
.092
.093
.094
.095
.096
.097
.098
.099
.100
.101
.102
.103
.104
.105
.106
.107
.108
.109
.110
.111
.112
.113
.114
.115
.116
.117
.118
.119
.120
.121
.122
V
996
1004
1012
1020
1029
1037
1045
1052
1060
1067
1075
1082
1089
1097
1104
1111
1119
1125
1133
1140
1147
1154
1161
1167
1175
1181
1188
1193
1201
1208
1215
1222
1228
1234
1241
1247
1254
1260
1266
1273
1279
1285
1292
1298
1304
1310
1316
1322
1328
1334
1340
1346
1352
1358
1364
1370
1376
1382
1387
1393
1399
VP
.123
.124
.125
.126
.127
.128
.129
.130
.131
.132
.133
.134
.135
.136
.137
.138
.139
.140
.141
.142
.143
.144
.145
.146
.147
.148
.149
.150
.151
.152
.153
.154
.155
.156
.157
.158
.159
.160
.161
.162
.163
.164
.165
.166
.167
.168
.169
.170
.171
.172
.173
.174
.175
.176
.177
.178
.179
.180
.181
.182
.183
V
1404
1410
1416
1422
1427
1433
1439
1444
1449
1455
1461
1466
1471
1477
1482
1488
1493
1498
1504
1509
1515
1520
1525
1530
1536
1541
1546
1551
1556
1561
1567
1572
1577
1582
1587
1592
1597
1602
1607
1612
1617
1622
1627
1632
1637
1642
1646
1651
1656
1661
1666
1670
1675
1680
1685
1690
1695
1699
1704
1709
1713
VP
.184
.185
.186
.187
.188
.189
.190
.191
.192
.193
.194
.195
.196
.197
.198
.199
.200
.201
.202
.203
.204
.205
.206
.207
.208
.209
.210
.211
.212
.213
.214
.215
.216
.217
.218
.219
.220
.221
.222
.223
.224
.225
.226
.227
.228
.229
.230
.231
.232
.233
.234
.235
.236
.237
.238
.239
.240
.241
.242
.243
.244
V
1718
1723
1727
1732
1737
1741
1746
1750
1755
1759
1764
1768
1773
1777
1782
1787
1791
1795
1800
1804
1809
1813
1818
1822
1827
1831
1835
1839
1844
1848
1853
1857
1862
1866
1870
1875
1879
1883
1887
1892
1896
1900
1905
1909
1913
1917
1921
1925
1929
1933
1937
1941
1945
1950
1954
1958
1962
1966
1970
1974
1978
VP
.245
.246
.247
.248
.249
.250
.251
.252
.253
.254
.255
.256
.257
.258
.259
.260
.261
.262
.263
.264
.265
.266
.267
.268
.269
.270
.271
.272
.273
.274
.275
.276
.277
.278
.279
.280
.281
.282
.283
.284
.285
.286
.287
.288
.289
.290
.291
.292
.293
.294
.295
.296
.297
.298
.299
.300
.301
.302
.303
.304
.305
V
1982
1987
1991
1995
1999
2003
2007
2011
2015
2019
2023
2027
2031
2035
2039
2042
2046
2050
2054
2058
2062
2066
2070
2074
2078
2081
2085
2089
2093
2097
2101
2105
2119
2113
2116
2119
2123
2127
2131
2135
2139
2143
2147
2151
2154
2157
2161
2164
2168
2171
2175
2179
2182
2186
2189
2193
2197
2200
2204
2208
2212
V
2215
2219
2223
2226
2230
2233
2236
2239
2242
2245
2248
2251
2254
2257
2260
2264
2268
2272
2276
2280
2284
2289
2293
2297
2301
2304
2308
2311
2315
2318
2322
2325
2329
2332
2335
2338
2342
2345
2349
2352
2356
2360
2363
2366
2369
2372
2376
2379
2383
2386
2389
2393
2396
2400
2403
2406
2410
2413
2416
2420
2423
VP
.367
.368
.369
.370
.371
.372
.373
.374
.375
.376
.377
.378
.379
.380
.381
.382
.383
.384
.385
.386
.387
.388
.389
.390
.40
.41
.42
.43
.44
.45
.46
.47
.48
.49
.50
.51
.52
.53
.54
.55
.56
.57
.58
.59
.60
.61
.62
.63
.64
.65
.66
.67
.68
.69
.70
.71
.72
.73
.74
.75
.76
V
2426
2429
2433
2436
2439
2443
2445
2449
2453
2456
2459
2462
2466
2469
2472
2475
2479
2481
2485
2488
2491
2495
2499
2501
2533
2563
2595
2626
2656
2687
2716
2746
2775
2804
2832
2860
2888
2916
2943
2970
2997
3024
3050
3076
3102
3127
3153
3179
3204
3229
3254
3279
3303
3327
3351
3375
3398
3422
3445
3468
3491
VP
.77
.78
.79
.80
.81
.82
.83
.84
.85
.86
.87
.88
.89
.90
.91
.92
.93
.94
.95
.96
.97
.98
.99
1.00
1.01
1.02
1.03
1.04
1.05
1.06
1.07
1.08
1.09
1.10
1.11
1.12
1.13
1.14
1.15
1.16
1.17
1.18
1.19
1.20
1.21
1.22
1.23
1.24
1.25
1.26
1.27
1.28
1.29
1.30
1.31
1.32
1.33
1.34
1.35
1.36
1.37
V
3514
3537
3560
3582
3604
3625
3657
3669
3690
3709
3729
3758
3779
3800
3821
3842
3863
3884
3904
3924
3945
3965
3985
4005
4025
4045
4064
4084
4103
4123
4142
4162
4181
4200
4219
4238
4257
4276
4295
4314
4332
4350
4368
4386
4405
4423
4442
4460
4478
4495
4513
4531
4549
4566
4583
4601
4619
4636
4653
4671
4688
VP
1.38
1.39
1.40
1.41
1.42
1.43
1.44
1.45
1.46
1.47
1.48
1.49
1.50
1.51
1.52
1.53
1.54
1.55
1.56
1.57
1.58
1.59
1.60
1.61
1.62
1.63
1.64
1.65
1.66
1.67
1.68
1.69
1.70
1.71
1.72
1.73
1.74
1.75
1.76
1.77
1.78
1.79
1.80
1.81
1.82
1.83
1.84
1.85
1.86
1.87
1.88
1.89
1.90
1.91
1.92
1.93
1.94
1.95
1.96
1.97
1.98
V
4705
4722
4739
4756
4773
4790
4806
4823
4840
4856
4873
4889
4905
4921
4938
4954
4970
4986
5002
5018
5034
5050
5066
5082
5098
5114
5129
5144
5160
5175
5191
5206
5222
5237
5253
5268
5283
5298
5313
5328
5343
5359
5374
5388
5403
5418
5433
5447
5462
5477
5491
5506
5521
5535
5550
5564
5579
5593
5608
5623
5637
VP
1.99
2.00
2.01
2.02
2.03
2.04
2.05
2.06
2.07
2.08
2.09
2.10
2.11
2.12
2.13
2.14
2.15
2.16
2.17
2.18
2.19
2.20
2.21
2.22
2.23
2.24
2.25
2.26
2.27
2.28
2.29
2.30
2.31
2.32
2.33
2.34
2.35
2.36
2.37
2.38
2.39
2.40
2.41
2.42
2.43
2.44
2.45
2.46
2.47
2.48
2.49
2.50
2.51
2.52
2.53
2.54
2.55
2.56
2.57
2.58
2.59
V
5651
5664
5678
5692
5706
5720
5734
5748
5762
5776
5790
5804
5817
5831
5845
5859
5872
5886
5899
5913
5927
5940
5954
5967
5981
5994
6008
6021
6034
6047
6060
6074
6087
6100
6113
6126
6139
6152
6165
6179
6191
6204
6217
6230
6243
6256
6269
6281
6294
6307
6319
6332
6345
6358
6370
6383
6395
6408
6420
6433
6445
VP
2.60
2.61
2.62
2.63
2.64
2.65
2.66
2.67
2.68
2.69
2.70
2.71
2.72
2.73
2.74
2.75
2.76
2.77
2.78
2.79
2.80
2.81
2.82
2.83
2.84
2.85
2.86
2.87
2.88
2.89
2.90
2.91
2.92
2.93
2.94
2.95
2.96
2.97
2.98
2.99
3.00
3.01
3.02
3.03
3.04
3.05
3.06
3.07
3.08
3.09
3.10
3.11
3.12
3.13
3.14
3.15
3.16
3.17
3.18
3.19
3.20
V
6458
6470
6482
6495
6507
6519
6532
6544
6556
6569
6581
6593
6605
6617
6629
6641
6654
6666
6678
6690
6702
6714
6725
6737
6749
6761
6773
6785
6797
6809
6820
6832
6844
6855
6867
6879
6890
6902
6913
6925
6937
6948
6960
6971
6983
6994
7006
7017
7028
7040
7051
7063
7074
7085
7097
7108
7119
7131
7142
7153
7164
ENGINEERING GUIDE
INDEX BY NAILOR MODEL NUMBER
MODEL
DESCRIPTION
PAGE NO.
3001
30RE
30RW
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B6
3210
3230
3240
3400
34RE
35N
35NE
35NW
35S
35SE
35SW
35SST
35SEST
"Stealth TM " Fan Powered, Series Flow with electric heat . . . . . . . . . . . . . . . . . . . . . . . .D29
35SWST
"Stealth TM " Fan Powered, Series Flow with hot water heat . . . . . . . . . . . . . . . . . . . . . .D29
35S-OAI
35SE-OAI
Outside Air Inlet Fan Powered, Series Flow with electric heat . . . . . . . . . . . . . . . . . . . .D41
35SW-OAI
Outside Air Inlet Fan Powered, Series Flow with hot water heat . . . . . . . . . . . . . . . . . .D41
ENGINEERING GUIDE
34RW
35SST-OAI "Stealth TM " Outside Air Inlet Fan Powered, Series Flow, no heat . . . . . . . . . . . . . . . . . .D41
35SEST-OAI "Stealth TM " Outside Air Inlet Fan Powered, Series Flow with electric heat . . . . . . . . . . .D41
35SWST-OAI "Stealth TM " Outside Air Inlet Fan Powered, Series Flow with hot water heat . . . . . . . . .D41
35S-CVP
35SE-CVP
35SW-CVP Pressurization Fan Powered, Series Flow with hot water heat . . . . . . . . . . . . . . . . . . .D48
36VRR
Round Retrofit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E5
36VRS
36VR
37S
37SE
Low Profile Fan Powered, Series Flow with electric heat . . . . . . . . . . . . . . . . . . . . . . . .D67
37SW
Low Profile Fan Powered, Series Flow with hot water heat . . . . . . . . . . . . . . . . . . . . . .D67
37SST
"Stealth TM " Low Profile Fan Powered, Series Flow, no heat . . . . . . . . . . . . . . . . . . . . .D78
37SEST
"Stealth TM " Low Profile Fan Powered, Series Flow with electric heat . . . . . . . . . . . . . .D78
37SWST
"Stealth TM " Low Profile Fan Powered, Series Flow with hot water heat . . . . . . . . . . . . .D78
G39