ELBA FIRA-03-236 DP / Luminaire Data Sheet


Luminous emittance 1:

Luminaire classification according to CIE: 100


CIE flux code: 68 98 100 100 61

Luminous emittance 1:

Application: General indoor lighting


Description: Steel sheet body, painted with powder
Mirrored Al sheet reflector with a reflection factor > 0.85 in variants:
- double parabolic (DP): main variant for 18W-7 lamellas, 36W16 lamellas
- single parabolic (SP): main variant for 18W-9 lamellas, 36W20 lamellas;
- flat (D): main variant for 18W-7 lamellas
- asymmetric (AS)
On request may be fitted with electronic ballast(dimmable version also) and
emergency lighting kit
Luminaire manufactured and certified according to SR EN 60598-1
230V/50Hz, IP 40

Page 1

Project 3
26.05.2014

Operator
Telephone
Fax
e-Mail

Room 1 / Summary

Height of Room: 2.900 m, Mounting Height: 2.900 m, Light loss factor:


0.80
Surface
Workplane
Floor
Ceiling
Walls (4)

Values in Lux, Scale 1:41

[%]

Eav [lx]

Emin [lx]

Emax [lx]

u0

/
20
80
60

523
383
61
210

412
273
37
76

598
463
77
380

0.788
0.713
0.595
/

Workplane:
Height:
0.750 m
Grid:
16 x 16 Points
Boundary Zone:
0.500 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.416, Ceiling / Working Plane: 0.118.
Luminaire Parts List
No.

Pieces

Designation (Correction Factor)


ELBA FIRA-03-236 DP (Type 1)* (1.000)

*Modified Technical Specifications

(Luminaire) [lm]

(Lamps) [lm]

P [W]

1340

2200

84.0

17600

672.0

Total: 10717

Total:

Specific connected load: 50.47 W/m = 9.66 W/m/100 lx (Ground area: 13.31 m)

Page 2

Project 3
26.05.2014

Operator
Telephone
Fax
e-Mail

Room 1 / Luminaire parts list


8 Pieces

ELBA FIRA-03-236 DP (Type 1)


Article No.:
Luminous flux (Luminaire): 1340 lm
Luminous flux (Lamps): 2200 lm
Luminaire Wattage: 84.0 W
Luminaire classification according to CIE: 100
CIE flux code: 68 98 100 100 61
Fitting: 1 x User defined (Correction Factor
1.000).

Page 3

Project 3
26.05.2014

Operator
Telephone
Fax
e-Mail

Room 1 / Photometric Results


Total Luminous Flux:
Total Load:
Light loss factor:
Boundary Zone:
Surface
Workplane
Floor
Ceiling
Wall 1
Wall 2
Wall 3
Wall 4

10717 lm
672.0 W
0.80
0.500 m

Average illuminances [lx]


direct
indirect
total
422
101
523
276
107
383
0.00
61
61
110
97
207
120
95
215
111
96
207
120

95

215

Reflection factor [%]

Average luminance [cd/m]

/
20
80
60
60
60

/
24
16
39
41
40

60

41

Uniformity on the working plane


u0: 0.788 (1:1)
Emin / Emax: 0.688 (1:1)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.416, Ceiling / Working Plane: 0.118.
Specific connected load: 50.47 W/m = 9.66 W/m/100 lx (Ground area: 13.31 m)

Page 4

Project 3
26.05.2014

Operator
Telephone
Fax
e-Mail

Room 1 / 3D Rendering

Page 5

Project 3
26.05.2014

Operator
Telephone
Fax
e-Mail

Room 1 / Calculation Grid 1 / Isolines (E, Perpendicular)

Values in Lux, Scale 1 : 31


Position of surface in room:
Marked point: (0.000 m, 0.041 m,
0.000 m)

Grid: 4 x 3 Points
Eav [lx]
388

Emin [lx]
340

Emax [lx]
452

u0
0.88

Emin / Emax
0.75

Page 6

Project 3
26.05.2014

Operator
Telephone
Fax
e-Mail

Room 1 / Calculation Grid 1 / Greyscale (E, Perpendicular)

Scale 1 : 31
Position of surface in room:
Marked point: (0.000 m, 0.041 m,
0.000 m)

Grid: 4 x 3 Points
Eav [lx]
388

Emin [lx]
340

Emax [lx]
452

u0
0.88

Emin / Emax
0.75

Page 7

Project 3
26.05.2014

Operator
Telephone
Fax
e-Mail

Room 1 / Calculation Grid 1 / Value Chart (E, Perpendicular)

Values in Lux, Scale 1 : 31


Position of surface in room:
Marked point: (0.000 m, 0.041 m,
0.000 m)

Grid: 4 x 3 Points
Eav [lx]
388

Emin [lx]
340

Emax [lx]
452

u0
0.88

Emin / Emax
0.75

Page 8

Project 3
26.05.2014

Operator
Telephone
Fax
e-Mail

Room 1 / Calculation Grid 1 / Table (E, Perpendicular)

Position of surface in room:


Marked point: (0.000 m, 0.041 m,
0.000 m)

2.549

341

406

406

341

1.530

383

452

452

383

0.510

340

405

405

340

m 0.530 1.590 2.650 3.710


Attention: The coordinates refer to the image above. Values in Lux.
Grid: 4 x 3 Points
Eav [lx]
388

Emin [lx]
340

Emax [lx]
452

u0
0.88

Emin / Emax
0.75

Page 9

Project 3
26.05.2014

Operator
Telephone
Fax
e-Mail

Room 1 / Calculation Grid 1 / Point values (E, perpendicular)

Position of surface in room:


Marked point: (0.000 m, 0.041 m,
0.000 m)

No.
1
2
3
4
5

Position [m]
X
0.530
1.590
2.650
3.710
0.530

Value [lx]

Y
0.551
0.551
0.551
0.551
1.570

Z
0.000
0.000
0.000
0.000
0.000

340
405
405
340
383

Quantity Points: 12
Eav [lx]
388

Emin [lx]
340

Emax [lx]
452

u0
0.88

Emin / Emax
0.75

Page 10

Project 3
26.05.2014

Operator
Telephone
Fax
e-Mail

Room 1 / Calculation Grid 1 / Point values (E, perpendicular)


Position of surface in room:
Marked point: (0.000 m, 0.041 m,
0.000 m)

No.
6
7
8
9
10
11
12

Position [m]
X
1.590
2.650
3.710
0.530
1.590
2.650
3.710

Value [lx]

Y
1.570
1.570
1.570
2.590
2.590
2.590
2.590

Z
0.000
0.000
0.000
0.000
0.000
0.000
0.000

452
452
383
341
406
406
341

Quantity Points: 12
Eav [lx]
388

Emin [lx]
340

Emax [lx]
452

u0
0.88

Emin / Emax
0.75