Vous êtes sur la page 1sur 29

Guidance Document

Civil Design and Construction


of 132kV, 66kV and 33kV
Substations

Version:

Date of Issue:

February 2007

Author:

Keith Nutter

Job Title:

Civils Manager

Approver:

Patrick Booth

Job Title:

Asset Manager

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

Revision Log
Version 1
First Issue
Version 0.1

Keith Nutter
Prepared by Keith Nutter

February 2007
Date November 2006

First Draft
Version

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 2 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

CONTENTS
1.

INTRODUCTION .................................................................................................................. 5

2.

SCOPE ................................................................................................................................ 5

3.

CHOICE OF SITE.................................................................................................................. 5

3.1

SIZE AND SHAPE................................................................................................................................................... 5

3.2

GROUND CONDITIONS........................................................................................................................................ 6

3.2.1

Substrata nature and bearing capacity...................................................................................................... 6

3.2.2

Ground water levels............................................................................................................................................ 6

3.2.3

Presence of contaminants ............................................................................................................................... 6

3.2.4

Soil resistivity profile .......................................................................................................................................... 7

3.3

PLANNING CONSENT........................................................................................................................................... 7

3.4

BUILDING REGULATIONS .................................................................................................................................. 7

3.5

SITE SURVEY ........................................................................................................................................................... 8

3.6

FLOOD RISK............................................................................................................................................................. 8

4.

SITE LAYOUT REQUIREMENTS ........................................................................................... 8

4.1

OPERATIONAL COMPOUND.............................................................................................................................. 9

4.1.1

Plant........................................................................................................................................................................... 9

4.1.2

Spacing ................................................................................................................................................................... 10

4.2

BUILDINGS ............................................................................................................................................................ 12

4.2.1

Switchrooms......................................................................................................................................................... 13

4.2.2

Control Room ....................................................................................................................................................... 14

4.2.3

W.C............................................................................................................................................................................ 15

4.2.4

Store......................................................................................................................................................................... 15

4.3

OTHER...................................................................................................................................................................... 15

4.3.1

Access...................................................................................................................................................................... 15

4.3.2

Ancillary Plant...................................................................................................................................................... 16

4.3.3

Services................................................................................................................................................................... 16

5.

DESIGN AND CONSTRUCTION ...........................................................................................16

5.1

GENERAL ................................................................................................................................................................ 16

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 3 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

5.2

STANDARDS .......................................................................................................................................................... 17

5.3

BUILDINGS ............................................................................................................................................................ 17

5.3.1

General.................................................................................................................................................................... 17

5.3.2

Walls......................................................................................................................................................................... 18

5.3.3

Floors ....................................................................................................................................................................... 19

5.3.4

Windows and Ventilation ...............................................................................................................................20

5.3.5

Roofs ........................................................................................................................................................................20

5.4

FENCING ................................................................................................................................................................. 21

5.5

TRANSFORMER FOUNDATIONS AND BUND WALLS ............................................................................ 21

5.6

EARTHWORKS/FOUNDATIONS......................................................................................................................22

5.7

CONCRETE..............................................................................................................................................................22

5.8

FORMWORK AND REINFORCEMENT ..........................................................................................................23

5.9

STEELWORK ..........................................................................................................................................................23

5.10

EQUIPMENT SUPPORT STRUCTURES..........................................................................................................23

5.11

CABLE DUCTS / TRENCHES.............................................................................................................................23

5.12

DRAINAGE..............................................................................................................................................................24

5.13

SITE SURFACING .................................................................................................................................................25

5.14

ROADS AND PATHS............................................................................................................................................26

5.15

NOISE HOUSINGS ...............................................................................................................................................26

5.15.1 Design .....................................................................................................................................................................26


5.15.2 Construction .........................................................................................................................................................27
5.16

SECURITY................................................................................................................................................................28

5.17

FIRE PROTECTION ...............................................................................................................................................28

5.18

DOORS.....................................................................................................................................................................29

5.19

HEATING AND LIGHTING .................................................................................................................................29

6.

APPENDICES

Appendix A: Fire Segregation at Primary and Grid Substations.


Appendix B: Substation Drainage
Appendix C: Transformer Foundations and Bund Walls.
Appendix D: Doors for Primary and Grid Substations
Appendix E: Heating, Lighting and Small Power at Primary and Grid Substations
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 4 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

1.

INTRODUCTION
This document details Central Networks requirements for the design and construction of 132kV,
66kV and 33kV Primary and Grid Substations.
This document must be read in conjunction with the Central Networks Network Design Manual,
Distribution Safety Rules, and other relevant Central Networks Policies and Guidance.

2.

SCOPE
This document applies to the design and construction of all Primary and Grid substations at
132kV, 66kV and 33kV that are to be adopted onto the CN Network. It is to be used by Central
Networks staff, Energy Services staff, and External Services Providers.
For substations that are constructed on behalf of customers, and are not adopted as part of the
CN network, then certain amendments relating to future requirements apply. These are noted
within the body of the document.
This document is also to be used where alterations are required to existing Primary and Grid
substations, although it is accepted that it will not be possible to meet all requirements in some
of these cases, due to existing site constraints.

3.

CHOICE OF SITE
This section deals with physical factors of the proposed site that can significantly affect its
viability as a substation location. These factors must be considered before construction
commences, and preferably before the land is purchased.

3.1

SIZE AND SHAPE


The area of land to be purchased must be of a suitable size and shape to accommodate the
present and future needs as set out in the Site Layout Requirements section. Care must be
taken to ensure the plot is suitable in all respects and that both existing and potential future
uses of surrounding land have been considered.
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 5 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

In addition suitable access must be available from the public highway. This may require
construction of a simple junction with an existing road, or may require the construction of a
relatively long access road. In either case the access must be suitable for both day to day use,
and also for delivery of large plant items.
3.2

GROUND CONDITIONS
A Geotechnical Ground Investigation Survey should be carried out to determine the following:-

3.2.1

Substrata nature and bearing capacity


The properties of the existing ground can have a major and costly impact on ground working
and foundations.
Without knowledge of the ground conditions, foundation design and excavation requirements
would have to be based on assumptions. If these assumptions are incorrect, any subsequent
changes required will severely impact on cost and programme.
In some cases where poor ground conditions are encountered, then specialist design and
construction will be required, such as piling and de-watering.

3.2.2

Ground water levels


A high water table might affect foundation design and construction. It may also impact on
ground working methods which again can cause increased costs and programme delays. A
high water table may also impact on cable laying requirements.

3.2.3

Presence of contaminants
Contamination of land can lead to expensive clean up measures or to long term remedial /
monitoring requirements. Contaminants may include:

Asbestos Costly specialist removal.


Heavy metals All excavated material removed from site will be classed as contaminated
waste, the disposal of which carries a premium price.
Oils Can migrate, via ground water, to adjacent properties and lead to the possibility of
future litigation.
Gas either naturally occurring from ground conditions, or from previous uses of the land.
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 6 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

In addition to cost and programme implications, the presence of contaminants may present
potential health risks during both the construction stage and subsequent operation of the site.
It should be noted that if contamination is discovered after the purchase of the land, then
Central Networks will be responsible for clean up costs, unless the original polluter can be
identified.
3.2.4

Soil resistivity profile


This is required to determine if the site is able to support an adequate earthing system.
The resistance of the substation earth will depend on the soil resistivity and the area of the
earth nest. High soil resistivity requires a large site. To determine the earthing requirements
calculations are required in accordance with the Central Networks Earthing Manual.
A Hot site in terms of earthing has safety and operational implications touch, step and
transfer potentials have to be carefully controlled.

3.3

PLANNING CONSENT
If the substation is to be located on an existing operational site, then it is possible that a formal
Planning Consent will not be required. To determine whether a site is exempt, reference should
be made to Schedule 2 (Class G) of The Town & Country Planning (General Permitted
development) Order 1995.
In all other cases Planning Consent will be required. If the site is located in a sensitive area, i.e.
residential, conservation area, national park, etc, it is preferable to obtain an Outline Planning
Consent before fully committing to purchase of the site.

3.4

BUILDING REGULATIONS
Operational Buildings within substations may be exempt from requiring Building Regulation
approval. They are covered by Building Regulations 2000; Regulation 9; Schedule 2; Exempt
Buildings and Work Class II; Buildings not frequented by people.
However there are several other instances, such as connection to existing drainage systems,
which would require a submission under Building Regulations.

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 7 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

It is Central Networks policy that the design and construction of all operational buildings should
comply fully with current Building Regulations, even if approval is not required.
Substations that are designed and build by ESP Contractors and Third Party Developers shall be
subject to full formal Building Regulations Approval, and copies of Consents supplied to Central
Networks to prove compliance with this requirement.
3.5

SITE SURVEY
In order to achieve the most practical and cost effective site layout, a detailed topographic site
survey should be carried out, ideally prior to the purchase of the land.
The site survey information will assist with the design and layout of the site, and will identify
issues with ground levels and suitable access.

3.6

FLOOD RISK
All substations are to be constructed so that the general compound and ground levels are
above the 1 in 1000 year flood level as identified by the Environment Agency. Building floor
levels will be a minimum 0f 150mm above the 1 in 1000 year level. At the planning stage the
access route to the substation should also be considered to ensure access will be available
during flood conditions.

4.

SITE LAYOUT REQUIREMENTS


This section deals with the factors that need to be taken into consideration when designing the
substation layout. The components that make up the layout are generally the Compound (may
be only a transformer compound or may also contain open terminal busbars and equipment),
Building, Access Roads and Fencing. The layout must take into account factors such as
practical use of space available, operational requirements, safety requirements, and inspection
and maintenance requirements.
Before considering possible layouts, the following basic system information is required:

Version: 1

Plant and equipment to be accommodated & maintained type, quantity and


electrical safety clearances.
Date of Issue: February 2007
The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 8 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

Likely need for future expansion.


Cables type, number & site exit/entry locations and directions.

The layout should be prepared using this information, together with the information available
from section 3 above, to give a practical, safe, cost effective solution.
4.1

OPERATIONAL COMPOUND

4.1.1

Plant
At 33kV sites with cable connected transformers there may also be a need for NERs, NER
switches, Fault Thrower cubicles and Ring Main Units.
At 33kV and 66kV sites with open terminal busbars and plant, then the layout may also need to
include for Busbars and supports, Circuit Breakers, Fault Throwers, etc, together with
appropriate ancillary equipment.
At 132kV sites the layout will be dependent on the individual requirements for the substation.
The majority of sites will be open terminal sites with similar plant to the 33/66 open terminal
sites. Some 132kV substations may be constructed as indoor sites utilising GIS switchgear.
Where possible, substations at all voltages shall be designed with sufficient space to
incorporate an additional transformer, and switchgear bay where required, at a later date.
(Two transformer sites shall therefore have space for a third unit). 132kV sites may require
additional measures to incorporate future expansion (e.g. space for four transformers with two
installed initially). These requirements will be specified by Network Strategy at the planning
stage.
33kV sites may be designed with 12/24MVA or 20/40MVA transformers. However the
transformer foundations and bunds shall be designed to accept both 12/24 and 20/40 units.
This will allow subsequent upgrading with minimum additional work.
The above requirements may be relaxed where the substation is for a Customers use only and
will not supply distribution load. In these cases the sites can be designed for the exact
requirements of the Customer.

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 9 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

At 66kV and 132kV sites transformer foundations and bunds shall be designed for the actual
units to be installed, there is no requirement to incorporate any possible upgrading.
4.1.2

Spacing
When designing the compound layout consideration must be given to the following factors:
4.1.2.1 Fire
The clear distance between transformers or between a transformer and any
other oil-containing equipment shall be not less than 12m at 132kV, or 6m at
66kV and 33kV. Where transformers are in noise enclosures this separation may
be reduced but should be not less than 6m at 132kV, or 4m at 66kV and 33kV. If
this separation can not be achieved then the provision of a fire barrier wall will
be required. This structure shall have a minimum fire resistance of 4 hrs at 132kV,
or 2 hrs at 6kV and 33kV.
There shall also be adequate fire separation between the transformers and
control buildings. This shall be not less than 6m.
For full details of fire segregation requirements see Appendix A: Fire Segregation
at Primary and Grid Substations.
4.1.2.2 Touch Potential
In situations where there is more than one earthing system (fence earthed
separated from main earth grid), it is essential that separately earthed plant,
structures, etc are sufficiently spaced so that they cannot be touched
simultaneously. To prevent this, a horizontal separation of 3.0m is preferred, and
a minimum separation of 2.0m must be provided. In certain circumstances
insulated fence panels may be required. Refer to the Earthing Manual for full
details.

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 10 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

4.1.2.3 Access & Maintenance


All plant and equipment shall be provided with sufficient free space to permit
safe operation and maintenance.
Plant over 2.0m high (which will include all transformers) will require full access
by powered mobile access equipment. Depending on compound layout and
transformer orientation, vehicle access routes within the compound may be
required. Spacing of equipment must be such that access for maintenance is
possible with adjacent plant / circuits live. Refer also to the guidance given in
the Power Systems Operation Manual, section 6.2.
Consideration must be given to means of transformer installation and removal
with the other transformer(s) live. The provision of removable compound fence
panels (i.e., with bolt down posts) will usually be necessary
4.1.2.4 Cable Routing
Cables need to be as accessible as possible, in case of future faults, jointing, etc.
Where cable runs beneath structures cannot be avoided they must be ducted.
It is likely that cable/duct excavation and laying will not occur until after the
structures have been completed. The potential risk of undermining and/or
destabilising the structures must be considered when planning cable routes.
If cable trenches are provided, these must be of sufficient strength to bear the
weight of any plant or vehicles that may need to pass over them for the purpose
of equipment installation and/or maintenance.
4.1.2.5 Fence Layout
In addition to the requirements above for positioning the fence with regard to
touch potential, access and maintenance requirements, the security of the site
must be considered when designing the layout. The compound fence must be
inset from the boundary of the site by a minimum distance of 2 metres. This 2
metre gap prevents neighbours from constructing anything which may be used

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 11 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

as a climbing aid and therefore compromise the security of the site. See section
5.15 for further guidance on site security.
All compounds must have at least two points of access / egress. On sites with
small cable connected transformer compounds these can be personnel gates, of
minimum width 1.675 metres (centre to centre of gate posts), with removable
fence posts and fence panels provided to cater for transformer removal and
plant maintenance.
On sites of open terminal design, one access / egress must be a set of double
gates of minimum width 4.57 metres (centre to centre of gate posts) to allow
access for maintenance vehicles.
For full details of fencing requirements see separate policy document:
Specification for Fencing for Grid, Primary and Distribution Substations.
4.2

BUILDINGS
All sites will usually require a building to house switchgear, control equipment, etc. The
building shall be segregated from the main compound area. This can be achieved either by
placing the building outside the compound fence area, or by placing the building within the
security fence area, but providing a segregating fence between the building and the compound
plant. Exact layout will depend on site requirements, including an assessment of security
issues.
Buildings will consist of:
Switchroom(s) for the indoor 11kV or 33kV switchgear
Separate control room for relay panels, batteries, LVAC board etc.
Separate store room for cones, chain, etc.
Separate WC
All rooms must have separate external access; there must be no connecting doors between
rooms.
On smaller sites the above requirements will usually result in a linear building layout with
switchroom, control room and store/WC all in one line. For larger sites, or sites with space
restrictions, other layouts may be preferred.
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 12 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

4.2.1

Switchrooms
At 33/11kV substations switchrooms shall be designed to accept one of three options for the
11kV switchgear. Either 13, 17 or 21 panel switchboards will be provided. No space allowance is
to be made for future additional units, the number of panels to be installed initially must take
into account future requirements where known. Regardless of initial requirements, the building
must be capable of accommodating 2000 amp switchgear.
At 132/11kV, 66/11kV and 132/33kV sites the 11kV and 33kV switchboards are to be designed to
the requirements of the individual site. Again no space should be allowed for future units, but
the number of panels installed initially must take into account known future requirements.
If 33kV and 11kV switchboards are provided at the same site then they must be in separate
rooms.
All switchboards shall be broken up into discrete sub-boards with no more than two
transformer incomers on each. Each sub-board shall be housed in a separate switchroom,
segregated by fire barrier walls with no interconnecting doors.
Where modifications are carried out to existing sites, the above design rule for segregation of
switchboards shall be complied with wherever reasonably practicable. For general guidance:
Where additional switchboards with incomer(s) are added to existing sites already having two
or more incomers in one switchroom, the new switchboards shall be segregated by providing
new switchrooms. The new switchroom(s) shall either be separate from existing switch-houses
or fire barrier walls shall be provided between switchboards. Where existing switchboards are
being replaced within existing switch-houses and more than two incomers are involved, then
where it is reasonably practicable to do so, the new switchboard shall be split and fire barrier
walls provided.
There must be sufficient space around plant and equipment for its safe operation, testing and
maintenance, and to allow for future replacement of an individual panel. To accommodate
these requirements the following minimum clearances must be provided:
Rear
End
Front
Head
Version: 1

1100mm
1100mm
The greater of: Switchgear panel depth +500mm, OR 2000mm
The greater of: IEC test requirements, OR 1000mm
Date of Issue: February 2007
The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 13 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

Entrance and exit doors must be sized and positioned to enable pedestrian access, equipment
access, and statutory fire escape requirements. Exact positioning of doors will be dependant on
individual site layout.
For full details of clearances, escape requirements and fire segregation requirements see
Appendix A: Fire Segregation at Primary and Grid Substations.
4.2.2

Control Room
Control rooms shall be designed to accommodate the following equipment as a minimum:
Transformer relay and AVC panels (including space for future units where appropriate)
Telecontrol panel and outstation
Substation battery
Telecontrol battery
Switchgear local control panel
Feeder and bus section relay panels as required
LVAC board
Intruder alarm panel
Desk and chair
Telephone
Four drawer filing cabinet
Safety notice board
Key cabinet / key safe
Fire point with extinguishers
Equipment shall be positioned so there is adequate clearance for installation, inspection,
maintenance and future replacement. Specific minimum distances are required to the front
and rear of control and relay panels, see Appendix A: Fire Segregation at Primary and Grid
Substations for full details.
The height of the control room will usually be the same as the adjacent switchroom, but as a
minimum there must be 500mm clearance above the relay / control panels.
Suitable provision must be made for personnel and equipment access and exit. Usually one
door will be suitable for all requirements but on some larger sites two doors may be required.

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 14 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

The control room access door must be clearly marked as this will be the normal substation
building entry point providing access to the intruder alarm panel.
4.2.3

W.C.
The WC shall contain:
WC suite
Wash hand basin with cold tap and instantaneous electric hot water heater
Separate bib tap for hose connection
Stop tap for incoming water supply
Warm air hand dryer
Toilet roll holder
Coat hook
Extractor fan with over-run timer connected to lighting circuit

4.2.4

Store
The store room is required for the storage of cones and chain, temporary earths, etc.
On 33kV and 66kV sites a room with a minimum floor area of 3 square metres shall be provided.
On 132kV sites a room with a minimum floor area of 6 square metres shall be provided.

4.3

OTHER

4.3.1

Access
Suitable access must be provided form the public highway to the substation site, and also
within the substation site. All access roads must be suitable for the delivery of large, heavy
plant items. In addition consideration shall be given for the positioning of a crane to offload
plant items, including transformers.
For 33kV and 66kV sites a minimum road width of 4.0 metres must be provided, and for 132kV
sites this should be a minimum of 4.5 metres. These dimensions are for straight sections of
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 15 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

road; bends will require either a greater road width, or provision for overhang of large plant
delivery vehicles. Exact requirements will depend on site layout and access route.
Within the substation site a turning area shall be provided, suitable for a long wheel base panel
van. Where feasible an area for the parking of two cars or vans, which does not block the main
access, should also be provided. This can either be part of the existing road layout or a separate
area of hardstanding.
The design of the junction of the substation access road with the public highway also needs
careful consideration. Designs should take into account sight lines and space required for
turning into / out of the access road.
4.3.2

Ancillary Plant
In addition to the main plant items within the compound there may be a requirement for a
local distribution substation. Where required, allowance shall be made for this within the site
layout, ensuring that access is available for installation of the package switchgear.

4.3.3

Services
In addition to requirements for cabling across the site (power and multicore cables), provision
must also be made for other services. A water supply, surface water drainage (including
interceptor), foul water drainage, and telecoms connection will usually be required.

5.

DESIGN AND CONSTRUCTION

5.1

GENERAL
All aspects of the civil works shall be designed to provide a low maintenance durable end
product suitable for the purpose intended. Particular emphasis shall be placed on security of
the site. Design life for structural elements shall be a minimum of 40 years.
In accordance with the requirements of the Construction (Design & Management)
Regulations the design of buildings and structures should be carried out to ensure that
construction, maintenance and demolition may be carried out in a safe manner.
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 16 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

It is also important that any buildings are built to a high standard and that the finished
building shall be designed to be aesthetically acceptable.
The design of the civil works and the specification of civil materials shall take into account
the environmental impact of all elements. Where possible environmentally friendly
materials and methods of construction should be incorporated into the works.
Emphasis is placed upon prevention and limitation of fire damage. Measures are specified
in Appendix A: Fire Segregation at Primary and Grid Substations, and these shall be adopted
as a minimum requirement. This document shall also be used as a guide for clearances
around switchgear and other equipment. Power cables and control cables shall be routed
and/or segregated such that minimal loss of control or supplies occurs in the event of fire or
damage.
With modern SF6 and vacuum switchgear there is no requirement to incorporate any blast
relief measures into the building construction. Where existing oil filled switchgear is used
in a building requiring alteration or extension then consideration shall be given for the need
for blast relief measures.
5.2

STANDARDS
All design and construction including all materials, testing and other procedures shall be
undertaken in accordance with appropriate Electricity Supply Industry Standards and
current British / European Standards.

5.3

BUILDINGS

5.3.1

General
Buildings may be either:

Brick / block construction with a variety of different roof constructions.

Steel portal frame design with profile steel sheet cladding, and brick / block perimeter
walls to a minimum height of 2.0 metres.
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 17 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

Access to plant and apparatus shall be adequate for operational and maintenance purposes
and provision shall be made for escape in the event of fire. The escape route shall be
designed to be clear of any obstructions. Passageways and the minimum spacing between
equipment shall be provided in accordance with Appendix A: Fire Segregation at Primary
and Grid Substations.
Provision shall be made for entry of power, multicore, telephone and pilot cables, water
supply and foul drainage pipes.
Sufficient width and depth shall be available for the cable routes such that de-rating of the
11kV feeder cables is kept to a minimum. There shall be no mutual de-rating of outgoing
feeder, Bus Interconnector or Transformer Incoming 11kV cables.
Ducts from buildings shall normally extend a minimum distance of 500mm from the
external face of the building. If the access road is immediately adjacent to the building,
then the ducts should be continued beneath the access road to facilitate cable installation.
5.3.2

Walls
All brickwork and blockwork shall be of a high standard facing quality with bucket handle
pointed joints, unless a match with existing brickwork pointing is required.
Clay facing bricks 65mm thick shall be used externally and shall be a minimum strength of
50N/mm2 and a maximum water absorption of 7% when tested in accordance with the
appropriate British Standard. All facing bricks used externally shall be FL designation.
Internal walls shall be constructed to give a durable, low maintenance, dust free finish.
Walls shall be painted with smooth masonry paint, magnolia colour. Final coat of paint is to
be applied after installation of electrical equipment.
All proposed bricks and blocks to be used are to be approved by the Companys
representative. Aerated concrete blocks are not acceptable for internal or external walls.
Quoin blocks shall be used at cavity closures in blockwork.
Cavity walls in substation buildings shall achieve a U value as required by the current issue of
the Building Regulations for new buildings other than dwellings.
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 18 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

All brickwork and blockwork shall be laid in mortar of appropriate strength for the location
and exposure of the wall.
Facing brickwork shall be used in the outer leaf below DPC level and shall extend at least 2
courses below finished ground level on all faces of the building. The type and colour of
facing bricks used shall comply with Local Authority requirements. Bricks for use below
ground shall be approved Class B uniform colour engineering bricks
Wall ties shall be stainless steel. Walls of one brick thickness or greater to be cross bonded
or tied together with stainless steel reinforcement or ties.
Where expansion or contraction joints are incorporated they shall be constructed with an
approved joint filler and finished with appropriate coloured sealant. Expansion joints shall
be so positioned as to coincide with Brick/Block modular sizes to avoid unnecessary cutting.
5.3.3

Floors
Floors of switch-houses will be of reinforced concrete power float finish and designed to
withstand the weight of switchgear to be installed. The finished floor level will normally be
a minimum of 150mm higher than the substation compound. Solid concrete floors shall
incorporate a damp proof membrane.
Floors shall be sealed against dust prior to installation of plant, and finished with coloured
floor paint. The final coat of paint is to be completed after installation of electrical
equipment.
Unistrut channels are to be set into the switchroom floor to provide fixings for the
switchgear.
Floors of control rooms may be of reinforced concrete, or removable floor panels supported
on pedestals on a concrete sub-floor. Floor panels are to have an antistatic sheet vinyl
finish. A suitable skirting shall be provided around the room perimeter. Concrete floors are
to be finished as stated above.
Where internal cable trenches are provided they shall be fitted with GRP removable covers
(with suitable lifting holes) on galvanised steel bearers or concrete walls. Covers shall have
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 19 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

a non slip solid top surface. Covers shall be designed for easy removal and reinstatement,
and shall be of manageable dimensions and weight. Trench designs shall incorporate
suitable access arrangements including ladders and hand rails where appropriate.
Where water ingress is considered possible, cable trenches within buildings shall be fitted
with drainage gullies connected to the storm drainage system, or with a sump and
automatic pump.
All ducts passing into buildings shall be sealed to prevent ingress of water and vermin.
Minimum depths of external ducts shall generally be 450mm for multicore cables and
750mm for power cables.
There is no requirement to comply with the U value for floor elements, as stated in the
Building Regulations, but floors shall be designed to be as energy efficient as possible
whilst accommodating the various cable entries required.
5.3.4

Windows and Ventilation


Windows are not required for daylight conditions or ventilation in substation and shall not
therefore be provided. Adequate mechanical ventilation shall be provided to the W.C. as
required by Building Regulations.

5.3.5

Roofs
Roofs can be a variety of different constructions including:

Flat and constructed from pre-cast concrete beams overlaid with insulation board and/or
lightweight screed laid to falls and covered with asphalt, or built up felt system.

Flat, with steel supporting structure and metal profile sheeting, finished with insulation and
built up felt system.

Pitched, with concrete or clay tile finish on timber trusses or rafters. Ridge and edge
details shall be of low maintenance proprietary design. Consideration shall be given to
security aspects of pitched roofs, and these shall normally be used where the building is
within the security boundary of the site.
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 20 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

Portal frame construction with steel profile sheet cladding.

System roof made up from proprietary system panels

Single ply membrane systems will not be accepted.


Where fascia and soffit boards are provided, these shall be of low maintenance design (e.g.
uPVC).
The overall construction of the roof shall be such as to provide a minimum thermal insulation U
value as required by the current issue of the Building Regulations for new buildings other than
dwellings. Solar heat gain shall be limited by the use of suitable solar reflective finishes.
Adequate means for the disposal of rainwater from the roof shall be made. Where possible,
connections shall be made to the main surface water drain.
The underside of pre-cast concrete roof units shall have a fair face finish. Units shall be
manufactured with tolerances specified in the appropriate British Standard. Differences in
soffit level of two adjacent units shall not exceed 6mm. No paint finish shall be applied to
the underside of precast units.
Roofs shall be designed for occasional access and maintenance, snow and wind loading in
accordance with the appropriate British Standard.
5.4

FENCING
For full details of the fencing requirements see separate policy document: Specification for
Fencing for Grid, Primary and Distribution Substations.

5.5

TRANSFORMER FOUNDATIONS AND BUND WALLS


For full details of the design and construction of transformer foundations and bund walls
see Appendix C: Transformer Foundations and Bund Walls.

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 21 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

5.6

EARTHWORKS/FOUNDATIONS
Any earthworks shall be carried out in accordance with the Manual of Contract Documents
for Highways Work: Volumes 1 and 2, as published by the Highways Agency. General site fill
material shall be imported graded granular material to the approval of the Companys
representative. All surplus spoil will be removed from site. An assessment of any imported
fill material must be made to ensure it is compatible with the earthing requirements of the
site.
Suitable measures to mitigate unsuitable or contaminated ground conditions shall be
adopted by the contractor. Measures may include removal or in situ treatment of the
ground or containment. All such works shall be conducted in accordance with procedures
approved by the relevant environmental authorities. Foundations and other below ground
constructions shall be designed to resist chemical attack from ground contaminants.
Excavations for foundations shall be taken down to such depths as to provide a solid
foundation suitable for the loading to be applied. Foundations shall be taken down to
sufficient depth to avoid being undermined by cable trench excavations. Foundations shall
be of a type to suit the ground conditions and shall be designed such that long term
differential settlement is kept within acceptable limits for operation of the electrical plant
and apparatus.
The total area of the substation compound must be suitable for access by a mobile elevated
work platform. (MEWP) The existing subgrade must be assessed for MEWP access. A layer
of suitable graded stone (MOT type 1 or 2) will be provided beneath the substation
surfacing. The thickness of the stone layer will be designed to support the MEWP, but must
be a minimum of 100mm. The Contractor will be responsible for any additional subgrade
improvement that is required solely for construction use.

5.7

CONCRETE
All structural concrete for work below ground level shall meet the requirements for
sulphates as identified for each particular site. In addition suitable measures must be taken
to avoid the risk of alkali-silica reaction.
The minimum grade of structural concrete shall have a crushing strength of 35 N/mm2 at 28
days.
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 22 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

5.8

FORMWORK AND REINFORCEMENT


All concrete surfaces except top surfaces shall be constructed using suitable formwork of a
quality and strength necessary to obtain true surfaces with a fair face.
Where concrete is exposed at or above ground level, formed surfaces shall have the
following grades of finish:
All exposed items
Type C finish as defined in BS EN 1992
Unseen surfaces
Type A finish as defined in BS EN 1992
Top exposed surfaces shall have a steel trowelled finish, unless stated otherwise.
Bases for steel or aluminium structures, transformers and other kiosks shall be set 75mm
above finished compound level, and their edges finished with chamfers. Edges of bases and
trenches cast flush with the compound level shall be finished with a bull-nosed trowel.
Formwork ties will not be permitted to pass through oil bund walls or exposed structural
concrete.

5.9

STEELWORK
Any structural steelwork incorporated into the works shall receive appropriate surface
preparation and be hot dip galvanised in accordance with BS EN ISO 1461. Likewise all
associated fasteners, packings, etc shall receive the same galvanised treatment.

5.10

EQUIPMENT SUPPORT STRUCTURES


Support structure for plant and equipment including busbars shall be constructed from
galvanised steel or aluminium. Structures shall be designed to accommodate all normal
vertical and horizontal loads plus additional loadings associated with electrical fault
conditions.

5.11

CABLE DUCTS / TRENCHES


All cable ducts and trenches shall be designed to cater for specified future requirements
and shall be of suitable construction to sustain all stated applied loadings.
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 23 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

The preferred option is to direct lay all power and multicore cables with suitable ducts
beneath roads and other inaccessible areas. Ducts for power and multicore cables will
generally be 125mm diameter and coloured black. On larger sites a cable duct and pit
system may be used for multiicore cables. Alternatively an in situ or precast concrete
trough solution is acceptable. Minimum depths of external ducts shall generally be 450mm
for multicore cables and 750mm for power cables.
When laying cable ducts the opportunity should be taken to lay additional spare ducts for
potential future use. This is particularly advantageous beneath access roads or foundations.
Covers of cable trenches/pits shall be so designed to carry the applied loadings and to be
capable of being removed easily without a risk of compound chippings falling into the
trench/trough. Also, when in place, lids shall not present a trip hazard. The preferred
trench cover material is GRP with a solid top surface. In certain circumstances heavy duty
trench covers of concrete construction may be necessary. In these instances any reinforcing
bars must be stainless steel.
Trenches into buildings and compounds shall be designed so they cannot be used to gain
unauthorised access into these areas. This may require the use of lockable covers.
Bases of cable trenches shall be laid to falls and include suitable drainage provision. Where
possible the drainage points shall be connected to the site surface water drainage system.
5.12

DRAINAGE
For drainage requirements on Primary and Grid substation sites see Appendix B: Substation
Drainage
For drainage requirements associated with transformer bund walls see Appendix C:
Transformer Foundations and Bund Walls
Suitable waste pipes and drainage gullies shall be provided to take away the condensate
from dehumidification equipment.
Surface water and foul drainage systems shall comply with the requirements of the
appropriate statutory authorities. Discharge into water courses or into the any existing

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 24 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

drainage systems will not be permitted without written consent of the appropriate
statutory authorities, which shall be obtained prior to commencement of the works.
The design of the drainage systems must take into account the loadings which may be
applied from heavy vehicles such as transformer delivery vehicles, or the use of MEWPs in
compound areas.
5.13

SITE SURFACING
All newly developed or re-developed areas of substation compound shall be stripped of all
topsoil and vegetation.
The finished area of the substation compound shall be resurfaced with a low maintenance
finish suitable for easy access for maintenance of equipment. This layer will also act as an
electrical insulator to minimise touch and step potentials during electrical fault conditions.
This finish will be a 75mm thickness of 20mm single size granite, basalt or carboniferous
limestone chippings laid on geotextile material conforming to clause 609 of the Specification
for Highway Works (SHW), Volume 1 of the Highways Agencys Manual of Contract Documents
for Highway Works. Other similar types of chippings may be suitable subject to approval by the
Company.
The chipping layer must extend a minimum of 1.5 metres outside the line of the compound
fence.
Site surfacing and geotextile material shall not be laid until after installation of all cables
and electrical equipment. It is the Contractors responsibility to protect the formation prior
to laying of the geotextile material and surfacing
Areas outside the compound but within the boundary fence shall generally be finished in
accordance with the compound requirements above. However on some sites there may be
a planning requirement for landscaping which will replace some of the stone chipped areas.
All landscaping shall be designed to avoid future problems with overhead lines, buried
services, etc. and must have minimum maintenance requirements.

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 25 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

5.14

ROADS AND PATHS


Site roads which may be used for the moving of heavy items of plant should normally be
designed to cater for transformer delivery vehicles. It is essential to ensure that all cable
ducts and other services which are to be laid under substation roads are in position before
construction of the road commences.
Roads shall be designed to suitable horizontal and vertical alignments to meet the
requirements in the Site Layout section above. In particular vertical alignments shall avoid
sharp gradient transitions. Within compounds gradients shall kept to a minimum and will
usually be determined by drainage requirements. Roads shall generally have upstand kerbs
to direct water flows, and to contain any oil spillage within the drainage system
The roads shall preferably be of dense bitumen macadam or hot rolled asphalt construction.
Thickness of base and wearing course materials shall be calculated from design loads but
shall be a minimum of 60mm and 30mm respectively.
For substation buildings suitable concrete access paths shall be provided for access to
normal entry doors and doors designated for delivery of plant. Other doors should have a
simple concrete pad outside the door. All paths and pads shall have a non slip finish and
should direct any rainwater away from the building.

5.15

NOISE HOUSINGS

5.15.1 Design
Noise housings shall be constructed from proprietary sandwich panels consisting of an
inner and outer metal sheet with sound absorbing filler material. The proposed design shall
be approved by the Companys representative prior to fabrication.
The required insertion loss to be provided by each enclosure shall be agreed between the
Company and the manufacturer following the necessary site noise survey.
The enclosures shall be designed and constructed as to allow sufficient room for access for
maintenance on the transformer and its ancillaries. Where power or multicore cable runs
restrict pedestrian routes inside housings, suitable galvanised steel internal walkways and
steps shall be designed and fitted to provide safe access.
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 26 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

The enclosure shall be designed to withstand all superimposed and wind loads, including
maintenance access loading for the roof construction.
Provision shall be made for the collection of rainwater and its disposal into the bunded area.
A suitable foam inlet for fire fighting purposes shall be provided to the housing.
Vermin proof grilles shall be provided to apertures between housing and cooler areas.
The position of enclosure walls shall be determined using the minimum requirements in
Appendix A: Fire Segregation at Primary and Grid Substations, and in Appendix C:
Transformer Foundations and Bund Walls.
Two lockable access doors shall be provided with each enclosure at diametrically opposite
corners. These shall give a clear opening 2000mm high by 750mm wide. Doors shall close on to
resilient seals along all meeting faces.
Concrete or steel steps shall be provided to allow safe access/egress to the housing over the
bund wall. Externally a minimum 900mm square platform shall be provided with steps and
handrails.
5.15.2 Construction
For the protection of transformer paintwork, it is a requirement that enclosure roofs shall be
waterproofed and that all seals around pipe work and turrets are water tight.
Proprietary metal sandwich panel construction housings shall have panels bolted together
using a suitable resilient gasket materials to form a watertight seal.
All components shall be galvanised after fabrication. In some instances a coloured paint finish
may be required on top of the galvanising to meet planning requirements. No site drilling or
welding of the housing components will be permitted.

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 27 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

5.16

SECURITY
All sites shall be risk assessed to determine what security measures are appropriate. The
minimum requirement for all sites is to have an intruder alarm which covers the building and
the compound access gates. The risk assessment will determine what type of boundary fencing
is appropriate, subject to planning agreement, and if further measures such as electric fences to
compounds are required.
Substation buildings shall be located, where possible, so they are either inside or outside a
security palisade fence, depending on security risk assessment.
If due to lack of space a substation building forms part of a security perimeter of a site, then
additional measures should be considered to ensure adequate protection. In particular walls
shall be smooth faced without climbing aids, and rainwater pipes shall be positioned inside
the security perimeter, or protected by anti climb measures to prevent unauthorised access.
Measures must also be taken to prevent theft of earth tape. Any exposed earth tape must be
capped in accordance with the requirements stated in the Earthing Manual.

5.17

FIRE PROTECTION
Sites must be individually fire risk assessed to determine what fire prevention and fire
fighting measures are appropriate.
For relatively simple layout sites with single storey buildings then the following minimum
requirements will usually be adequate:

All buildings shall be fitted with smoke detectors to switchrooms and control rooms.

All buildings shall be fitted with a minimum of one fire fighting point, usually situated
immediately inside the control room door. The fire point will consist of one dry powder
extinguisher and one carbon dioxide extinguisher, together with appropriate labels.

A fire action notice will be provided adjacent to the telephone point.

All fire exit routes and final exit doors will be marked with appropriate standard fire exit
signage.
Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 28 of 29

Guidance Document
Civil Design and Construction of 132kV, 66kV and 33kV Substations

For more complex sites additional fire prevention and fire fighting equipment may be
required, dependant on the fire risk assessment.
For further details see the separate policy document: Fire and Bomb Safety at Operational Sites.
5.18

DOORS
For full details see Appendix D: Doors for Primary and Grid Substations

5.19

HEATING AND LIGHTING


Design and installation of heating and lighting systems, including LV power systems, is detailed
in Appendix E: Heating, Lighting and Small Power at Primary and Grid Substations. This
document also includes information on floodlighting for substations, intruder alarms and other
associated electrical items.

Version: 1

Date of Issue: February 2007


The master version of the this document resides in the E.ON UK Documentum database
CAUTION any other copy may be out of date

Central Networks plc

Page 29 of 29

Vous aimerez peut-être aussi