Académique Documents
Professionnel Documents
Culture Documents
The phase-bushings on a three phase transformer are marked either ABC, UVW or 123
(HV-side capital, LV-side small letters)
Two winding, three phase transformers can be devided into four main categories (Clock
hour number and phase displacement of those most frequently encountered in practice
in brackets)
Group
Group
Group
Group
Vector Groups
Transformer nameplates carry a vector group reference such at Yy0, Yd1, Dyn11 etc. This relatively
simple nomenclature provides important information about the way in which three phase windings are
connected and any phase displacement that occurs.
Winding Connections
HV windings are designated: Y, D or Z (upper case)
LV windings are designated: y, d or z (lower case)
Where:
Y or y indicates a star connection
D or d indicates a delta connection
Z or z indicates a zigzag connection
N or n indicates that the neutral point is brought out
Phase Displacement
The digits ( 0, 1, 11 etc) relate to the phase displacement between the HV and LV windings using a
clock face notation. The phasor representing the HV winding is taken as reference and set at 12
o'clock. It then follows that:
Digit 0 means that the LV phasor is in phase with the HV phasor
Digit 1 that it lags by 30 degrees
Digit 11 that it leads by 30 degrees
etc
All references are taken from phase-to-neutral and assume a counter-clockwise phase rotation. The
neutral point may be real (as in a star connection) or imaginary (as in a delta connection)
When transformers are operated in parallel it is important that any phase shift is the same through
each. Paralleling typically occurs when transformers are located at one site and connected to a
common busbar (banked) or located at different sites with the secondary terminals connected via
distribution or transmission circuits consisting of cables and overhead lines
Basic Theory
An ac voltage applied to a coil will induce a voltage in a second coil where the two are linked by a
magnetic path. The phase relationship of the two voltages depends upon which way round the coils
are connected. The voltages will either be in-phase or displaced by 180 deg as below:
In phase
180deg displacement
Page 3 of 15
When 3 coils are used in a 3 phase transformer winding a number of options exist. The coil voltages
can be in phase or displaced as above with the coils connected in star or delta and, in the case of a
star winding, have the star point (neutral) brought out to an external terminal or not.
Example - Dyn11
We now know that this transformer has a delta connected primary winding (D) a star connected
secondary (y) with the star point brought out (n) and a phase shift of 30 deg leading (11).
Connections and vector diagrams are as follows::
HV
LV
Other Configurations
By connecting the ends of the windings in other ways a wide range of options becomes available as
set out below.
Phase shift (deg)
Connections
Yy0
Dd0
Dz0
30 lag
Yd1
Dy1
Yz1
60 lag
Dd2
Dz2
120 lag
Dd4
Dz4
150 lag
Yd5
Dy5
Yz5
180 lag
Yy6
Dd6
Dz6
150 lead
Yd7
Dy7
Yz7
120 lead
Dd8
Dz8
60 lead
Dd10
Dz10
30 lead
Yd11
Dy11
Yz11
Page 4 of 15
The figure calculated above is a maximum. In practice, the actual fault level will be reduced by the
source impedance, the impedance of cables and overhead lines between the transformer and the
fault, and the fault impedance itself.
As well as fault level considerations, the impedance value also:
determines the volt drop that occurs under load - known as 'regulation'
affects load sharing when two or more transformers operate in parallel
Sequence Impedance (Z1 Z2 Z0)
The calculation above deals with a balanced 3-phase fault. Non-symmetrical faults (phase-earth,
phase-phase etc) lead to more complex calculations requiring the application symmetrical component
theory. This in turn involves the use of positive, negative and zero sequence impedances (Z 1, Z2 and
Z0 respectively).
As with all passive plant, the positive and negative sequence impedances (Z 1 and Z2) of a transformer
are identical.
However, the zero sequence impedance is dependent upon the path available for the flow of zero
sequence current and the balancing ampere turns available within the transformer. Generally, zero
sequence current requires a delta winding, or a star connection with the star point earthed. Any
impedance in the connection between the star point and earth increases the overall zero sequence
impedance. This has the effect of reducing the zero sequence current and is a feature that is
frequently put to practical use in a distribution network to control the magnitude of current that will
flow under earth fault conditions.
Page 6 of 15
Differential Protection
Differential protection is a unit scheme that compares the current on the primary side of a transformer
with that on the secondary side. Where a difference exists (other than that due to the voltage ratio) it
is assumed that the transformer has developed a fault and the plant is automatically disconnected by
tripping the relevant circuit breakers. The principle of operation is made possible by virtue of the fact
that large transformers are very efficient and hence under normal operation power-in equals powerout. Differential protection detects faults on all of the plant and equipment within the protected zone,
including inter-turn short circuits.
Principle of Operation
The operating principle employed by transformer differential protection is the Merz-Price circulating
current system as shown below. Under normal conditions I1and I2 are equal and opposite such that
the resultant current through the relay is zero. An internal fault produces an unbalance or 'spill'
current that is detected by the relay, leading to operation.
Design Objectives
An ideal scheme is required to be:
Extremely stable under through fault conditions
Very fast to operate for an internal fault
Design Considerations
A number of factors have to be taken into account in designing a scheme to meet these objectives.
These include:
The matching of CT ratios
Current imbalance produced by tap changing
Dealing with zero sequence currents
Phase shift through the transformer
Magnetising inrush current
Each of these is considered further below.
The Matching of CT Ratios
The CTs used for the Protection Scheme will normally be selected from a range of current
transformers with standard ratios such as 1600/1, 1000/5, 200/1 etc. This could mean that the
currents fed into the relay from the two sides of the power transformer may not balance perfectly. Any
imbalance must be compensated for and methods used include the application of biased relays (see
below) and/or the use of the interposing CTs (see below).
Page 7 of 15
Page 8 of 15
Interposing CTs
The main function of an interposing CT is to balance the currents supplied to the relay where there
would otherwise be an imbalance due to the ratios of the main CTs. Interposing CTs are equipped
with a wide range of taps that can be selected by the user to achieve the balance required.
As the name suggests, an interposing CT is installed between the secondary winding of the main CT
and the relay. They can be used on the primary side or secondary side of the power transformer
being protected, or both. Interposing CTs also provide a convenient method of establishing a delta
connection for the elimination of zero sequence currents where this is necessary.
Modern Relays
It should be noted that some of the newer digital relays eliminate the need for interposing CTs by
enabling essentials such as phase shift, CT ratios and zero sequence current elimination to be
programed directly into the relay
Page 9 of 15
H2
CH4
C2H6
C2H4
C2H2
CO2
CO
Page 10 of 15
Page 11 of 15
Moisture
The life of a transformer is dependent upon three crucial parameters; temperature, oxygen and
moisture. This tutorial deals with moisture. Information about the detrimental effects of oxygen is
given elsewhere.
Most power transformers use paper and oil as the main form of insulation and during manufacture
stringent efforts are made to ensure that both are as dry as possible when new plant leaves the
factory. Once in service the moisture content begins to increase. Excessive moisture can put the life
of a transformer at risk. It is important to understand the source of this moisture, its effect and the
preventive measures that can be taken.
Source of Moisture
Once in service a transformer is subjected to the following sources of moisture:
external - from the atmosphere
internal - from manufacture
internal - from cellulose (paper) ageing
External moisture is repeatedly drawn into a free-breathing transformer as the working temperature
rises and falls with load.
Internal moisture is generated as cellulose insulation ages. The process by which this occurs is
extremely complex but can be summarised as follows. Cellulose consists of long chains of hydrocarbons. When these chains are broken the carbon and hydrogen combine with any oxygen present
to form carbon monoxide, carbon dioxide and water. The gases are dissolved in the oil - see Tutorial
T3 DGA. The water remains largely in the paper where its presence contributes to further ageing as
a vicious cycle is established.
Effect of Moisture
Moisture reduces the dielectric strength of paper and oil which in turn increases the risk of electrical
failure. It also reduces the mechanical strength of the paper.
Since hot oil is able to support more moisture than cold oil, percentage saturation is temperature
dependent. If hot oil is cooled the relative saturation will increase and an emulsion of water and oil
may form. Free water may also be produced which will have a serious effect on dielectric strength
and can lead to the formation of rust where it collects, typically in the bottom of main tanks and
conservators.
Furthermore, when wet paper gets very hot, for example during a period of sustained over-loading,
the possibility of bubble formation arises. When this occurs moisture in the paper is boiled off as
water vapour introducing a risk of partial discharge and electrical breakdown.
Page 12 of 15
Moisture Dynamics
Moisture in a transformer is very dynamic, moving with temperature between the paper and the oil.
By far the greatest quantity is contained in the paper which acts like a sponge. The ratio of water in
paper to oil is about 1000:1 (reducing to 500:1 if the oil is old). As the temperature rises moisture
moves relatively rapidly from the paper to the oil. As the temperature falls the moisture moves back
into the paper, but more slowly.
After a period of prolonged steady temperature, the water in the paper and oil reaches equilibrium. At
that point by measuring the moisture content of the oil it is possible to estimate the quantity of water
in the paper from standard look-up tables. In a large transformer we are talking about tonnes of
paper, thousands of litres of oil and hundreds of litres of water.
Asset Management
Dealing with the problem of moisture in a transformer is a very important part of effective asset
management. For example:
Always record the temperature when an oil sample is taken for moisture analysis.
Never change oil because it is wet. The new oil will very quickly degrade to the same condition as
the old as moisture leaves the paper to re-establish a condition of equilibrium.
Consider:
(a) Careful oil sampling and testing
(b) The use of on-line moisture sensors
(c) Silica gel breather design, application and maintenance
(d) On-line conditioning and monitoring systems
(e) Devices that continuously remove moisture from the air-space in the conservator
(f) Continuous on-line moisture removal systems connected into the oil system
(g) Specialist field drying services using heat and vacuum.
Page 13 of 15
Buchholz Relays
A Buchholz relay is a gas and oil operated device installed in the pipework between the top of the
transformer main tank and the conservator. A second relay is sometimes used for the tapchanger
selector chamber. The function of the relay is to detect an abnormal condition within the tank and
send an alarm or trip signal. Under normal conditions the relay is completely full of oil. Operation
occurs when floats are displaced by an accumulation of gas, or a flap is moved by a surge of oil.
Almost all large oil-filled transformers are equipped with a Buchholz relay, first developed by Max
Buchholz in 1921.
General Arrangement
Front View
B - Upper Float
C - Lower Float
D - Oil Surge Detector
Conditions Detected
A Buchholz relay will detect:
Gas produced within the transformer
An oil surge from the tank to the conservator
A complete loss of oil from the conservator (very low oil level)
Fault conditions within a transformer produce gases such as carbon monoxide, hydrogen and a range
of hydrocarbons (Tutorial T3). A small fault produces a small volume of gas that is deliberately
trapped in the gas collection chamber (A) built into the relay. Typically, as the oil is displaced a float
(B) falls and a switch operates - normally to send an alarm. A large fault produces a large volume of
gas which drives a surge of oil towards the conservator. This surge moves a flap (D) in the relay to
operate a switch and send a trip signal. A severe reduction in the oil level will also result in a float
falling. Where two floats are available these are normally arranged in two stages, alarm (B) followed
by trip (C).
Page 14 of 15
Gas sampling - a graduated sight glass provides an indication of the volume of gas that has
accumulated, typically 100-400cm3. After an alarm or trip signal has been received this must be
collected and analysed before the transformer is returned to service. Gas collection can be done at
the relay, or at ground level if suitable arrangements exist. Clearly the latter is a safer and more
convenient option.
Functional Tests - a test petcock enables dry air to be admitted into the relay to check correct
operation. A trickle of air is equivalent to a gradual accumulation of gas. A blast simulates an oil
surge. These tests are sometimes referred to as 'blowing the Buchholz'. On completion it is
important that the relay is bled to remove the air that has been introduced.
Draining - a valve in the bottom of the relay enables an oil sample to be taken or the relay to be
drained. As with gas sampling, this facility can be brought down to ground level for enhanced
operator safety and convenience.
Accessories
A range of accessories and services are available to assist with the safe and correct operation of
Buchholz relays including:
Ground level oil and gas sampling kits
Gas sampling devices - automatic
Gas sampling devices - manual
On-site gas testers - simple air/fault gas analysis
On-site gas testers - complex fault gas composition
Relay test kits
Recalibration
Page 15 of 15