Vous êtes sur la page 1sur 7

TSFP

TECHNICAL SCHEDULE

Section VI E
Page -1/7

BID DOCUMENT FOR


DIESEL POWER GENERATION PLANT
Item
No.

Description

Unit

Preferred
Specification

Bidders
Specifications

SECTION VI-E

TECHNICAL SCHEDULE
The Bidder shall fill all the information required for, without disturbing the sequence and
format. If space is not enough, additional pages can be added giving relevant reference
number
2422.1
,2 & 3

DG Sets
Quantity
625 kVA
1250 kVA
Name of manufacturer
Applicable standards
Type, model
Guaranteed Specific fuel
Consumption Considering all
the auxiliaries are
Engine mounted for site
condition
At 100% of rated Load
At 75% of rated Load
At 50% of rated Load
At 25% of rated Load
Lub. Oil Consumption at 100%
of rated Load
Max. Noise Level
Max. vibrations
Smoke (with nominal flow)
AMF/ Manual mode provided
ACB rating
Short circuit rating and duration
Rated voltage
Make, model
Radiator cooled / Cooling
tower
Remote adjustment of Voltage,
speed
kW vs. speed droop provided,
range
kVAr vs. Voltage droop
provided, range
Voltage adjustment facility from
nominal value

* Bidders to specify

1 set
2 sets
*
As per GTC
*
*

*
*
*
*
*
dBA

90
*
*
AMF
2500
50kA, 3s
400
*
*
*
*
*
*

TSFP

TECHNICAL SCHEDULE

Section VI E
Page -2/7

BID DOCUMENT FOR


DIESEL POWER GENERATION PLANT
Item
No.

2422.4

Description

Suitability of the alternators for


parallel operations
Governor details
Type
Make
Model
3000 A, 400 V, TPN Main
Distribution Board (MDB) LV
Switchgear for Construction
Power
Single front or double front
Type of Enclosure
Total dimensions of switchgear
LxWx H
Total weight of complete
Switchgear (kg.)
Width of each vertical section
with cable alley
Width of cable alley only
Busbar continuous rating under
site conditions
Sheet steel CRCA
Material thickness
Front Door LV Chamber
Front Door CB Chamber
Structural Member
(Vertical / Horizontal
Top Cover
Bottom Sheet
Partition for L.T Chamber
Partition cover Between panels
End Cover
Upper inside cover Between
busbar Chamber and rear
Frame
Rear Cover
Barrier sheet between Busbar
and cable/C.B. Chamber
Shutter
Rear Frame
Short time rating (1s)
Momentary rating (Peak)
One minute power frequency
with stand voltage
a)
Main circuit
b)
Control circuit
c)
Aux. circuits connected

* Bidders to specify

Unit

Preferred
Specification
Required
*
*
*
Common for three
sets
Single front
*
*
*
*

Amps

*
3000
*

mm
mm

2
2.5

mm
mm
mm
mm
mm
mm

2.5
2.5
2.5
2.0
1.6
1.6
*

mm
mm

2.0
2.0

mm
mm
kA

2.0
2.0
50
*

kV

3
*
*

Bidders
Specifications

TSFP

TECHNICAL SCHEDULE

Section VI E
Page -3/7

BID DOCUMENT FOR


DIESEL POWER GENERATION PLANT
Item
No.

Description

Degree of protection provided


by the enclosure
Earth busbar size
Busbars
a) Material of busbars
b) Size of Busbars
c) Continuous current rating
under site conditions
d) Whether busbars have been
insulated
e) Type of insulation
f) Temperature rise over the
reference ambient when
carrying rated current
g) Material of busbar supports
h) Clearances in air in mm
i) Between phases
ii) Between phases and earth
i) Short time rating in kA (1 s)
j) Momentary rating (peak)
Circuit Breakers
Make
Circuit breaker type
Rated voltage
Rated operating duty
Rated Insulation Voltage
Rated impulse voltage
withstand
Rated current
Rated symmetrical Breaking
current at rated voltage
Rated peak making current
Rated short time withstand
rating (1s)
Max. temp. rise of main
contacts when circuit breaker is
carrying rated current
Operating mechanism type
Limits of voltage for satisfactory
operation as % of normal
voltage
a) Operating mechanism
Closing coil
Trip coil
Power required for closing at
a) Nominal voltage
b) 80% of nominal voltage

* Bidders to specify

Unit

Preferred
Specification
*
*

Amps

Copper
*
3000
*

Deg. C

*
45
SMC
*
*
*
50
*

V
V

*
*
400
*
690
*
As per SLD
*

kA

*
50
*
*
*
*
*
*
*
*
*

Bidders
Specifications

TSFP

TECHNICAL SCHEDULE

Section VI E
Page -4/7

BID DOCUMENT FOR


DIESEL POWER GENERATION PLANT
Item
No.

Description

Power required at tripping at


a) Normal voltage
b) 50% of nominal voltage
Spring charging motor details
Rating
Rated voltage
Spring charging time
No. of opening the c. b is
capable of performing without
inspection, replacement of
contacts or better parts at 100%
rated breaking current
Total opening time
Overload release
a) Setting
b) Characteristics enclosed
Short circuit release
Time delay and settings
Under voltage release setting
Earth fault release setting
Anti-pumping provided
Type test certificates enclosed
Current Transformers
a)Type
b) Mounting
c) CT Ratio
d) Burden
e) Class
Selector Switch
a) Type
b) No. of positions
c) Contact rating
Starters
a)Starter Type
b) Class of duty
Moulded Case Circuit Breaker
(MCCB)
a) Type of MCCB
b) No. of Poles Required
c) Short circuit withstand capacity

* Bidders to specify

Unit

Preferred
Specification
*
*
*
*
*
230
*
*

*
*
*
*
*
*
*
*
*
*

VA

Air Core Epoxy Cast


Resin CTs
On the Bus Links
As specified in SLD
20 (Minimum)
As specified in
individual SLD
Rotary Type
As per requirement
4 Amp. 400 Volt A.C.
1 Amp. 110 Volt D.C.
Direct On Line
AC - 3
Current Limiting Type
3 Pole with Neutral
Link
Same As that of
busbar rating of
respective panel

Bidders
Specifications

TSFP

TECHNICAL SCHEDULE

Section VI E
Page -5/7

BID DOCUMENT FOR


DIESEL POWER GENERATION PLANT
Item
No.

Description

Unit

Fuses(Control)
a) Type
b) Voltage
c) Rating
Contactor
a) Type
b) Rated voltage of main
contacts
c) Rated duty
d) No. of auxiliary contacts
required
Control Wiring
a)Size
b) Type
c)Insulation
d)Voltage grade
e)Colour Code
Control Terminal Blocks
a)Type
b)Voltage grade
c)Current rating
d) Minimum Size Required.
e) Spare terminals
Ground Bus
a) Material
b)Size
Push Button
a) Type

HRC
400/230 Volt A.C.
As per individual
requirement
Volts

b) Dial Size (Min)


c) Accuracy Class
Relays

* Bidders to specify

Air Break Contactor


400
AC 3
4 NO + 4 NC

sq mm

2.5
*
*
*
*
*
*
*
*
10% spare terminals
Aluminium
50 x 10 mm
Flush Mounted &
Shrouded
4A, 400 V and 1 A,
110 V DC
2 NO + 2 NC
Mushroom Type
*

b) Rating
c) No. of contacts required
d) Emergency Push Button
e) Colour
Indicating Lamps
a) Type
b) Colour
c) Min. Lumen Output
Indicating Meters
a) Type

Preferred
Specification

Lux

LED Type
As required
300
Digital / Analogue
Moving Coil Type
144 sq. mm
Class 1.0 or Better

Bidders
Specifications

TSFP

TECHNICAL SCHEDULE

Section VI E
Page -6/7

BID DOCUMENT FOR


DIESEL POWER GENERATION PLANT
Item
No.

Description

Unit

a) Solid state or Electromagnetic


or Microprocessor based
b) Type of Relay
i) Over current
ii) Short Circuit
iii) Under Voltage
c) CT Ratio
2422.5 110 V Battery Charger
Quantity
Type- Float and Boost
DC system Voltage
Float charging current
Rated output
Rated overload capacity and
duration
Boost charging current
Max. time for boost charging
Regulation of AVR
Ripple content at rated
continuous load
110 V, 200 Ah Battery
Capacity at 27 0C at 10 hr rate
a) Initial
b) rated
c) End of life
Rated capacity at Ambient
temp.
Type of positive plates
No. of plates / cell
No. of cells required to give
rated DC voltage
No. of spare cells
Capacity at high discharge
rates
a) 15 Minutes
b) 30 Minutes
c) 45 Minutes
d) 1 hr 10 hr
Max. momentary current
(1 Minute)
Expected life of battery
Float charging voltage
Float charging current
Trickle charging voltage
Trickle charging current

* Bidders to specify

Preferred
Specification
As specified in SLD

*
*
*
As per SLD

V DC
A
kW
A

03 (One for each


set)
*
110
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*

Bidders
Specifications

TSFP

TECHNICAL SCHEDULE

Section VI E
Page -7/7

BID DOCUMENT FOR


DIESEL POWER GENERATION PLANT
Item
No.

2422.6

Description

Boost charging voltage


Boost charging current
Whether positive plates of
individual cells are
interchangeable
Whether negative plates of
individual cells are
interchangeable
L V Cables
Name of the manufacturer
Voltage grade
Earthed / Unearthed
Conductor
a) Stranded / Solid
b) Material
c) Conductor shielding
Insulation
General XLPE/ PVC
Individual core shielding
Inner sheath
a) Extruded PVC
b) Wrapped PVC
c) Any other
Armouring
a) Galvanised Wire / Strip
b) Aluminium
c) Any other
Conductor temp. for
continuous rating
Conductor temp. for 1 Sec
short circuit current ratings
Emergency overload
temperature
Screening material, wherever
applicable
a) Conductor screening
b) Insulating (Overall)
screening
Min. bending radius

* Bidders to specify

Unit

Preferred
Specification
*
*
*
*

Deg. C

*
1.1
*
*
*
*
*
*
XLPE
*
*
*
*
*
*
*
*
*
90

Deg. C

Deg C

kV

*
*
*
mm

Bidders
Specifications