Académique Documents
Professionnel Documents
Culture Documents
19
50
JOURNAL
YE A R S
592009
The following article was published in ASHRAE Journal, July 2009. Copyright 2009 American
Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for
educational purposes only. This article may not be copied and/or distributed electronically or in
paper form without permission of ASHRAE.
This paper examines the evaporation of a refrigerant in various types of heat transfer structures by (a) relating refrigerant evaporation to control with load changes; (b) evaluating the effect of large volume increases
at low temperatures; and (c) reviewing specific examples of compressor damage and the corrections made.
he compressor is a vapor
pump and must have, as a part
of the system, foolproof means
for protection against damage from
hydraulics such as liquid refrigerant or
oil. Positive displacement compressors
for refrigeration service are designed for
pumping a refrigerant vapor at a temperature above 10F above the satura-
CONTROL LIMITATION
Control limitation may be compared to a pan of water on a stove
ASHRAE Journal
July 2009
ASHRAE
19
50
JOURNAL
YE A R S
592009
F I G . 1 Control limitation.
MISUSE
An example of misuse resulting in compressor damage was an installation specified and engineered to chill
brine from 30F to 35F. The gpm was given and the
overall tons of refrigeration were about 150. Investigation
revealed that some of the brine was used in the coils and
jacket of a large reaction tank. No brine was being used
during the reaction time and, as a result, the brine in the
coils and in the jacket reached 90F. After a given length of
time the 90F brine in the coils and jacket was returned to
the chiller. This suddenly applied hot load caused a liquid
refrigerant return to the compressor, resulting in broken
compressor valves.
The mechanism was simply the normal decrease of
vapor volume at the time of reduced load, thus permitting an increase of liquid volume in the chiller. The sudden return of the 90F brine generated an overall volume
July 2009
43
ASHRAE
19
50
JOURNAL
YE A R S
592009
Fig. 4 shows the chiller in a vertical position. The physical dimensions are unchanged, but control of the refrigerant
cannot be obtained by a float level device positioned on
the shell because the area for vapor release has been greatly
reduced from that in the horizontal position. The overall
liquid lift caused by boiling is inversely proportional to
the reduction in area. Thus, control of the pressure head
for refrigerant feed must be accomplished externally of the
shell.
Fig. 5 depicts a commonly used evaporator for all types of
refrigerated storage and freezer service. It is operated as a flooded
unit, very often consisting of a bank of vertically mounted serpentine coils connected in parallel by a bottom feed and top
vapor header. Unlike the horizontal flooded chiller, this unit has
a relatively high vapor releasing velocity. The vapor bubbles cannot rise vertically, but must be caused to flow horizontally. This
gravity flow recirculation system, when properly proportioned,
has excellent performance character. The height of the float above
the coil is calculated from the load, internal pipe area, and the
resulting leaving vapor velocity. When fixed for one set of conditions, it is correctly placed for that set of conditions only. The fan
is representative of the fact that the product being cooled is air.
FIG.4
FIG.5
FIG.6
LOAD LOSSES
An excessive liquid refrigerant return will always occur if
product flow is stopped, in this or any other type of evaporator, without stopping the refrigerant flow, the reason being
that refrigerant feed is at a fixed head established for full
heat load. Stopping the fan (product flow) causes a loss of
load; the evaporator feed, if permitted to continue, will fill
the coil, and on a restart of the fan the excess refrigerant will
be returned to the separator at a rate higher than normal
design. A carryover to the compressor will then occur.
A basic design rule should be that refrigerant flow must
be stopped when product flow is stopped.
Fig. 6 illustrates a dry expansion type chiller and simulates an installation situation which resulted in serious
damage to three compressors during the first month of
operation. After corrections were made, this same installation had no compressor damage of a serious nature in ten
years of operation. The design specification for the system
called for multistage R-22 refrigeration at 80F evaporation to chill a nitrogen vapor from 40F to 60F, and to
be suitable for continuous operation. Investigation following reported compressor failures showed that the product
44
ASHRAE Journal
July 2009
ASHRAE
19
50
JOURNAL
YE A R S
592009
45
www.info.hotims.com/25206-33
ASHRAE
19
50
592009
PARALLEL DRAINAGE
Parallel condenser drainage, not fully understood, has caused
serious problems in numerous installations. These problems stem
All evaporators have the ability to accumulate excess liquid refrigerant at low load conditions and means must be
provided to prevent this kind of accumulation.
DELAYS
Product freezers designed for a 30F freezing level
are often brought down to temperature prior to product
entrance. Very often a product arrival estimated for 7:00
a.m. may extend to 8:00 a.m. Meanwhile, under many
present-day control arrangements, the freezer will remain
on line and continue to lower in temperature. There is very
little heat load, the liquid content of the coils becomes excessive, and immediately when the warm product load arrives
there is a serious liquid refrigerant return to the compressor.
A proper control would have stopped refrigerant flow the
instant 30F was obtained, and a two degree differential
thermostat would renew refrigerant flow at 28F.
48
ASHRAE Journal
JOURNAL
YE A R S
from the fact that no two condensers will have the exact same
leaving condensate temperature. There will be a migration problem
unless proper structure is used, which will permit migration without
drainage flow interruption. The horizontal drain line (Fig. 11) shown
enlarged from condenser 2 has become filled because of the necessary head required to cause horizontal flow. Assuming that the
outlet temperature of condenser 2 is lower than that of condenser
1, there will be migration flow from 1 to 2 and the pipe line being
filled with liquid acts as a dam against migration flow from condenser 1 to condenser 2. Condenser 2 will thus stop draining and
becomes bottleda term generally applied to that situation.
A plate type of freezer may, by virtue of the operational
program, cause serious compressor damage. An excess liquid
refrigerant return in the operational program occurs when
the freezing day is discontinued, the freezer is left filled with
product, and refrigeration is continued during the night
without any limitation of the amount of liquid refrigerant
being accumulated and stored. When this freezer is opened
and warm product added, the excess liquid thrown out may
well exceed the capabilities of the separator and thereby pass
directly to the compressor. A corrective measure is to limit
the liquid supply during the night so that the evaporator
area will not be filled with liquid at the time of starting the
next freezing day.
COMPRESSOR DAMAGE
Fig. 8 illustrates the low temperature section of a pump
recirculation system. The pumping tank, at evaporator presa s h r a e. o rg
July 2009
ASHRAE
19
50
592009
IDEAL
Fig. 12 represents the ideal parallel condenser-to-receiver
drainage. Horizontal drain piping is avoided and the pitch to
be used is such that liquid drainage will occur without filling
the drain line more than 1/2 of the cross-section. Thus, natural
migration can occur from any area of the condenser-receiver
system into either of the condensers. In this structure of Fig. 12
independent liquid drains are provided into the receiver.
Additional condensers are often added to an existing installation, which has one receiver. The existing inlet connection should
be used to avoid recertification of this pressure vessel. Fig. 13 shows
how to use this receiver inlet with multiple condensers. The size
of the existing receiver inlet may be marginal for the total drainsure, is the separator for the mixture of vapor and unevaporated
liquid returning from the evaporator. It is the collector of liquid
returned during defrost. It is the flash area for reduction of liquid temperature from condensing or any pre-cooler temperature to the evaporator temperature. It must have no less than
three controls. The top control senses the highest permissible
liquid refrigerant level and must sound an alarm of sufficient
intensity to attract responsible personnel for the adjustments
necessary to avoid compressor damage if the level builds higher.
The vapors from the evaporators contain unevaporated liquid
and this unevaporated liquid must be separated from the vapor
in the area above the top control. The volume of this area must
be suitable for the maximum vapor flow of the system.
The next lower control must maintain the normal necessary liquid level for operation. Here the important consideration is that the volume between the normal operating level
July 2009
JOURNAL
YE A R S
49
ASHRAE
19
50
592009
SURFACE REDUCTION
In any system where a trap is used in the drain line between
the condenser and the receiver, the noncondensibles remain in the
condenser, thus reducing effective condensing surface. Also, the
limited internal volume of the condenser causes a much faster rise
in operating condensing pressure than in the open drain system.
The bottom control is for pump protection. It is used
to stop the pump in the event of a low liquid level before
it has lost its prime. On a restart, after the level rises, the
pump will deliver liquid without cavitation.
Compressor damage was caused in this type of system
from an improperly controlled defrost program. A very large
freezer with a more than usual surface was capable of maintaining temperatures at 30F from Monday to Saturday
50
ASHRAE Journal
JOURNAL
YE A R S
July 2009
ASHRAE
19
50
JOURNAL
YE A R S
592009
SUMMARY
Positive action for full compressor
protection begins by designing into the
system correctly sized evaporators, conwww.info.hotims.com/25206-9
July 2009
ASHRAE Journal
51