www.tyco-fire.com
Contacts
Features
Technical
Data
Approvals
LPCB Approved
(Refer to Tables A, B, C, and D.)
Working Pressure Range
1,4 to 12,0 bar
Temperature Ratings
Refer to Tables A, B, C, and D.
Pressure Loss
Refer to Graphs A and B.
Construction
The TYCO Series MJC Multiple Jet
Controls are manufactured from cast
iron, leaded gun metal, copper, brass,
nickle silver, and glass (Figures 3, 4, 5,
and 6).
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10
OCTOBER 2014
TFP1346
TFP1346
Page 2 of 10
FROM NORMALLY
WET LINE SUPPLY
TO OPEN
SPRINKLERS
OR NOZZLES
TO OPEN
SPRINKLERS
OR NOZZLES
MJC's
IN PENDENT
POSITION
SUPPLY
PIPING
SUPPLY
PIPING
FRANGIBLE GLASS
BULB AT BOTTOM
MJC
MJC's
OPEN
SPRINKLERS
OR NOZZLES
FROM
NORMALLY
WET LINE
SUPPLY
OPEN
SPRINKLERS
OR NOZZLES
FROM
NORMALLY
WET LINE
SUPPLY
NOTE:
Supply piping and MJC's are to be
located in areas at 4C or greater.
FIGURE 1A
FIGURE 1B
FIGURE 1
TYPICAL PIPING ARRANGEMENT
NORMALLY WET LINE SUPPLY
(Series MJC Multiple Jet Controls in Pendent Position with Heat Sensitive Bulb at Bottom)
FRANGIBLE GLASS
BULB AT TOP
TO OPEN
SPRINKLERS
OR NOZZLES
TO OPEN
SPRINKLERS
OR NOZZLES
MJC's
IN UPRIGHT
POSITION
MJC
FROM NORMALLY
DRY LINE SUPPLY
MJC's
SUPPLY
PIPING
OPEN
SPRINKLERS
OR NOZZLES
FROM
NORMALLY
DRY LINE
SUPPLY
FIGURE 2A
OPEN
SPRINKLERS
OR NOZZLES
FROM
NORMALLY
DRY LINE
SUPPLY
SUPPLY
PIPING
FIGURE 2B
FIGURE 2
TYPICAL PIPING ARRANGEMENT
NORMALLY DRY LINE SUPPLY
(Series MJC Multiple Jet Controls in Upright Position with Heat Sensitive Bulb at Top)
TFP1346
Page 3 of 10
Design
Criteria
Ambient Temperature
For normally wet pipe systems, do not
install Series MJC Multiple Jet Controls
in areas that are subject to freezing.
Water Supply
Water should be free of particles and/
or site debris. Do not use sea or brackish water.
Piping Arrangements
A wet supply line is typically being
supplied from an alarm valve (Figure
1) and the dry supply line is typically
being supplied from either a dry pipe
valve or deluge valve (Figure 2). Waterflow alarms, system pressure gauges,
and flow test capability are therefore
provided by the alarm, dry pipe, or deluge valve.
Sequence of Operation
For a wet pipe system supply, water
is readily available for flow through
the TYCO Series MJC Multiple Jet
Controls; however, water is only allowed past the MJCs when the glass
bulb in the MJCs is actuated by heat
(or the thermoelectric actuator).
For a dry pipe system supply, operation of the glass bulb in the MJCs
when actuated by heat (or the thermoelectric actuator) releases air
pressure to permit operation of a dry
pipe valve, and then upon operation
of the dry pipe valve, water becomes
available to flow through the operated MJCs.
For a deluge system supply and upon
operation of the deluge system in response to a dedicated supplemental detection system, water becomes
available to the MJCs; however, water
is only permitted past the glass bulb
in the MJCs if the glass bulb has been
actuated by heat (or the thermoelectric actuator).
MJC Installation Position
The MJCs is installed in the upright position (heat sensitive bulb at top as illustrated in Figures 3, 4, 5, and 6) when
supplied from a dry pipe or deluge system, or can be installed in the pendent
position for a wet pipe system supply
(heat sensitive bulb at bottom). For example, in a wet pipe system supply, the
MJCs can be installed above a ceiling
where its heat sensitive bulb is exposed
below the ceiling line. In all cases, the
heat sensitive bulb must be in the protected area.
Since the MJCs utilize a thermal sensing element similar to that used for a
standard response, standard coverage,
frangible glass bulb type sprinkler, the
positioning rules for MJCs are the same
as standard sprinklers. The heat sensitive bulb to ceiling distance and the
area of thermal coverage is based on
standard coverage sprinklers as a function of the protected hazard and ceiling construction provided in the applicable standards recognized by the
Approval agency for standard coverage sprinklers.
Pressure Loss
Graph A provides the pressure loss versus flow for the MJC configured as a
single outlet, and Graph B provides the
pressure loss versus flow for the MJC
configured for double outlets.
Thermoelectric Actuation
When the Thermoelectric Actuation
is applied, the MJCs can be operated
automatically as part of a heat/smoke
detection system or manually. In either case, suitable control equipment
must be selected based on the actuator electrical ratings (Figure 7), the requirements of the customer, and the
codes governing installation of electric
detection systems. The actuator leads
are encased in a flexible conduit (Figure
7) for attachment to an electrical junction box.
When considering the power supply for
operating the Thermoelectric Actuators,
be aware that the Thermoelectric Actuator, after operation, may be an open
circuit, short circuit, or connected to
earth. Therefore, it is essential that the
power supply be suitably protected.
The recommended storage life (at ambient temperature) for the Thermoelectric Actuator according to the supplier
is 10 years (for METRON* Actuators,
refer to DR2005/C1). The working temperature for the Thermoelectric Actuator is -40C to 100C (for up to 20 hours
provided any temperature greater than
70C occurs immediately prior to firing).
Storage temperature is -30C to 70C.
After 10 years, the TYCO Series MJC
Multiple Jet Controls supplier should
be contacted regarding the suitability
of the unit for continued use.
Operation
The DN20 TYCO Series MJC Multiple Jet Controls has an inlet connected to either a single or double outlet
(Figure 3). For the DN25, DN40, and
DN50 MJCs, the central inlet is connected to the double outlets (Figures 4,
5, and 6). Using a cap instead of one of
the two unions on the DN25 and DN40
TFP1346
Page 4 of 10
Components:
- Body
- Inlet *
- Diaphragm
- Plunger
- Bulb
- Gasket
- Compression
Screw
8 - Upper Cone
Assembly
9 - Union
10 - Thrust Plate
11 - Lower Cone
1
2
3
4
5
6
7
12 - O-Ring **
13 - O-Ring
Housing **
14 - Spring Plate **
MJC shown
upright; may be
oriented as
pendent.
11
* Temperature rating
and year of manufacture indicated on
Inlet wrench flat.
5
14
13
10
12
** Single Outlet
only.
4
BULB SEAT
DETAIL
165 mm
109 mm
82,5 mm
82,5 mm
82,5 mm
56 mm
8
WRENCHING
SQUARE 30 mm
ACROSS FLATS
3/4"
BSPT
113 mm
1
3
3/4" BSPT
SINGLE OUTLET
SEE DETAIL
ABOVE
DOUBLE OUTLET
19,0 mm DIA.
ORIFICE
48 mm
FIGURE 3
DN20 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE818 SINGLE OUTLET AND FIGURE FE186 DOUBLE OUTLET
Components:
- Body
- Inlet *
- Diaphragm
- Plunger
- Bulb
- Union
- Lever
- Upper Cone
Assembly
1
2
3
4
5
6
7
8
9 - Compression
Screw
10 - Plunger
Cap
11 - Lower Cone
12 - Lower Tip
13 - Guard
14 - Guard Screw
15 - Warning
Label
16 - Pipe Cap
(Single Outlet
only)
* Temperature rating
and year of manufacture indicated on
Inlet wrench flat.
MJC shown
upright; may be
oriented as
pendent.
196 mm
98 mm
76 mm
98 mm
111 mm
98 mm
1"
BSPT
145 mm
16
WRENCHING
SQUARE 38 mm
ACROSS FLATS
SINGLE OUTLET
10
62 mm
1" BSPT
DOUBLE OUTLET
FIGURE 4
DN25 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE190 SINGLE AND DOUBLE OUTLET
15
13
11
12
14
3
25,4 mm DIA.
ORIFICE
TFP1346
Page 5 of 10
Components:
- Body
- Inlet *
- Diaphragm
- Plunger
- Bulb
- Union
- Lever
- Upper Cone
Assembly
1
2
3
4
5
6
7
8
9 - Compression
Screw
10 - Plunger
Cap
11 - Lower Cone
12 - Lower Tip
13 - Guard
14 - Guard Screw
15 - Warning
Label
16 - Pipe Cap
(Single Outlet
only)
* Temperature rating
and year of manufacture indicated on
Inlet wrench flat.
MJC shown
upright; may be
oriented as
pendent.
101 mm
230 mm
115 mm
90 mm
115 mm
115 mm
11
4
14
12
1-1/2"
BSPT
SINGLE OUTLET
15
13
160 mm
72 mm
1"
BSPT
16
WRENCHING
SQUARE 51,5 mm
ACROSS FLATS
10
38,1 mm DIA.
ORIFICE
DOUBLE OUTLET
FIGURE 5
DN40 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE181 SINGLE AND DOUBLE OUTLET
Components:
- Body
- Inlet
- Diaphragm
- Plunger
- Bulb
- Compression
Screw
7 - Lever
1
2
3
4
5
6
8 - Top Plate *
9 - Top Plate
Screw
10 - Union Half
11 - Union Nut
12 - Union Joint
Ring
13 - Stop Screw
225 mm
112,5 mm
112,5 mm
135 mm
136 mm
112,5 mm
84 mm
6
21
12
11
13
52 mm
20
18
14
5
1-1/2"
BSPT
16
182 mm
4
19
17
15
64 mm
SINGLE OUTLET
WRENCHING
HEX 76,2 mm
ACROSS FLATS
10
DOUBLE OUTLET
FIGURE 6
DN50 SERIES MJC MULTIPLE JET CONTROLS
FIGURE FE192 SINGLE AND DOUBLE OUTLET
1
2
3
50,0 mm DIA.
ORIFICE
22
2" BSPT
TFP1346
Page 6 of 10
1,00
0,80
0,60
0,50
0,40
OUTLET
0,06
0,05
)
(K=
640
)
(K=
280
INLET
DN
50
)
DN
25
0,08
(K=
250
0,10
DN
40
(K=
80)
0,20
DN
20
0,30
0,04
OPERATED
SINGLE OUTLET
MJC
0,03
0,02
0,01
10
20
30 40
60
100
200
400
600
1000
GRAPH A
NOMINAL PRESSURE LOSS VERSUS FLOW
SINGLE OUTLET
1,00
0,80
0,60
0,50
0,40
OUTLET
OUTLET
20)
50
(K
=9
50)
=5
40
(K
INLET
DN
0,06
0,05
DN
0,08
DN
20
0,10
25
(K
(K=
=3
125
)
70)
0,20
DN
0,30
0,04
OPERATED
DOUBLE OUTLET
MJC
0,03
0,02
0,01
10
20
30 40
60
100
200
400
600
1000
GRAPH B
NOMINAL PRESSURE LOSS VERSUS FLOW
DOUBLE OUTLET
TFP1346
Page 7 of 10
Installation
The TYCO Series MJC Multiple Jet
Controls must be installed per the system designers specifications, which
have been based on the information
provided in the Design Criteria section.
Exercise care to avoid damage to the
MJCs before, during, and after installation. Replace MJCs damaged by dropping, striking, wrench twist/slippage,
or the like. Also, replace any MJCs that
have a cracked bulb or that has lost liquid from its bulb. The DN25, DN40, and
DN50 MJCs are provided with a Notification Tag (Figure 8).
Do not install a TYCO Series MJC Multiple Jet Control if the bulb is cracked
or there is a loss of liquid from the bulb.
With the MJC held so that the bulb is
horizontal, a small air bubble should be
present. The diameter of the air bubble
is approximately 4,5 mm to 6,4 mm for
the 68C to 141C temperature ratings.
The MJCs utilize a frangible glass bulb
heat sensitive element. Handle with
care. The DN25, DN40, and DN50
MJCs are provided with a guard. Removal of the guard voids the manufacturers warranty.
Care and
Maintenance
Limited
Warranty
Ordering
Procedure
Multiple Jet Control
Specify: (specify size and temperature
rating) TYCO MJC Series Multiple Jet
Control, Figure (specify) Multiple Jet
Control (with electrical actuator, if applicable), P/N (specify from Tables A,
B, C, or D).
TFP1346
Page 8 of 10
ELECTRICAL CHARACTERISTICS
Nominal Energy . . . . . . . . . . . . . . . . . . 6 millijoules
Resitance Range . . . . . . . . . . . . . . . . . 0.9 - 1.6
Maximum No Fire Current
30 sec. Pulse . . . . . . . . . . . . . . . . . . . 0.15 A
0.05 sec. Pulse . . . . . . . . . . . . . . . . . 0.3 A
Minimum Single Firing Current
D.C. . . . . . . . . . . . . . . . . . . . . . . . . . . 0.6 A
10 ms. Pulse . . . . . . . . . . . . . . . . . . . 0.9 A
Recommended Single Firing Current . . 1.0 A
Recommended Series Firing Current . . 3.0 A
Maximum Monitoring Current . . . . . . . . 0.01 A
GUARD BROKEN
AWAY TO SHOW
DETAIL
BULB
FLEX
CONDUIT
ACTUATOR
ADAPTER
TOP PLATE
ACTUATOR
SUPPORT
FLEX
CONDUIT
ADAPTER
CONDUIT
CONNECTOR
ACTUATOR
LEADS
ACTUATOR
LEADS
GUARD BROKEN
AWAY TO SHOW
DETAIL
BULB
ACTUATOR
TOP PLATE
ACTUATOR
SUPPORT
FIGURE 7
OPTIONAL THERMO-ELECTRIC ACTUATOR FOR
DN25, DN40, AND DN50 SERIES MJC MULTIPLE JET CONTROLS
GUARD
NO ADHESIVE
THIS PORTION
OF LABEL
OUTLET
(WATER FLOW
THROUGH MJC IN
EITHER DIRECTION)
BULB
LEVER
DIAPHRAGM
NON-OPERATED
MJC
GUARD
WARNING
SIDE
BULB
WARNING
SIDE
PLUNGER
OUTLET
(WATER FLOW
FROM MJC)
OUTLET
(WATER FLOW
THROUGH MJC IN
EITHER DIRECTION)
INLET
(PRESSURE
FROM SUPPLY,
NO WATER FLOW)
PLUNGER
OUTLET
(WATER FLOW
FROM MJC)
FIGURE 8
NOTIFICATION TAG FOR
DN25, DN40, AND DN50 SERIES
MJC MULTIPLE JET CONTROLS
DIAPHRAGM
OPERATED
MJC
INLET
(WATER FLOW
FROM SUPPLY)
FIGURE 9
MJC MULTIPLE JET CONTROLS
OPERATION
TFP1346
Page 9 of 10
DN
20
20
FIGURE
NUMBER
and
STYLE
APPROVALS
FIGURE FE818
SINGLE OUTLET
TEMPERATURE
RATING
MAXIMUM
TEMPERATURE
WHERE MJC IS
LOCATED
BULB
LIQUID
COLOR
PART
NUMBER
57C
27C
Orange
MJCSO0027A
68C
38C
Red
MJCSO0027B
79C
49C
Yellow
MJCSO0027D
93C
63C
Green
MJCSO0027E
141C
111C
Blue
MJCSO0027G
57C
27C
Orange
MJCDO0027A
68C
38C
Red
MJCDO0027B
79C
49C
Yellow
MJCDO0027D
93C
63C
Green
MJCDO0027E
141C
111C
Blue
MJCDO0027G
FIGURE FE186
DOUBLE OUTLET
Notes:
1. Approved by the Loss Prevention Certification Board (LPCB Refer to No. 007f/01).
2. Approved by the Loss Prevention Certification Board (LPCB Refer to No. 007f/02).
TABLE A
LABORATORY LISTINGS AND APPROVALS
FOR DN20 SERIES MJC MULTIPLE JET CONTROLS
DN
25
25
FIGURE
NUMBER
and
STYLE
FIGURE FE190
DOUBLE OUTLET
WITH GUARD
FIGURE FE2656
DOUBLE OUTLET
WITH GUARD
AND ELECTRICAL
ACTUATOR**
APPROVALS
TEMPERATURE
RATING
MAXIMUM
TEMPERATURE
WHERE MJC IS
LOCATED
BULB
LIQUID
COLOR
PART
NUMBER
DOUBLE
OUTLET
PART
NUMBER
SINGLE
OUTLET
N/A
57C
27C
Orange
MJCDO0034A
MJCSO0034A
68C
38C
Red
MJCDO0034B
MJCSO0034B
79C
49C
Yellow
MJCDO0034D
MJCSO0034D
93C
63C
Green
MJCDO0034E
MJCSO0034E
141C
111C
Blue
MJCDO0034G
MJCSO0034G
57C
27C
Orange
25013
*- - -
68C
38C
Red
25015
*- - -
79C
49C
Yellow
25017
*- - -
93C
63C
Green
25019
*- - -
N/A
N/A
Notes:
1. Approved by the Loss Prevention Certification Board (LPCB Refer to No. 007f/03).
N/A: Not Approved
* Not Available
** On request, avaiable with Walkbery flex cable.
TABLE B
LABORATORY APPROVALS AND PART NUMBERS
FOR DN25 SERIES MJC MULTIPLE JET CONTROLS
TFP1346
Page 10 of 10
DN
40
40
FIGURE
NUMBER
and
STYLE
FIGURE FE181
DOUBLE OUTLET
WITH GUARD
FIGURE FE2378
DOUBLE OUTLET
WITH GUARD
AND ELECTRICAL
ACTUATOR**
APPROVALS
TEMPERATURE
RATING
MAXIMUM
TEMPERATURE
WHERE MJC IS
LOCATED
BULB
LIQUID
COLOR
PART
NUMBER
DOUBLE
OUTLET
PART
NUMBER
SINGLE
OUTLET
N/A
57C
27C
Orange
MJCDO0048A
MJCSO0048A
68C
38C
Red
MJCDO0048B
MJCSO0048B
79C
49C
Yellow
MJCDO0048D
MJCSO0048D
N/A
93C
63C
Green
MJCDO0048E
MJCSO0048E
141C
111C
Blue
MJCDO0048G
MJCSO0048G
57C
27C
Orange
25025
*- - -
68C
38C
Red
25027
*- - -
79C
49C
Yellow
25029
*- - -
93C
63C
Green
25031
*- - -
N/A
Notes:
1. Approved by the Loss Prevention Certification Board (LPCB Refer to No. 007f/03).
N/A: Not Approved
* Not Available
** On request, avaiable with Walkbery flex cable.
TABLE C
LABORATORY APPROVALS AND PART NUMBERS
FOR DN40 SERIES MJC MULTIPLE JET CONTROLS
DN
50
50
FIGURE
NUMBER
and
STYLE
FIGURE FE192
DOUBLE OUTLET
WITH GUARD
FIGURE FE2073
DOUBLE OUTLET
WITH GUARD
AND ELECTRICAL
ACTUATOR**
APPROVALS
TEMPERATURE
RATING
MAXIMUM
TEMPERATURE
WHERE MJC IS
LOCATED
BULB
LIQUID
COLOR
PART
NUMBER
DOUBLE
OUTLET
PART
NUMBER
SINGLE
OUTLET
N/A
57C
27C
Orange
MJCDO0060A
MJCSO0060A
68C
38C
Red
MJCDO0060B
MJCSO0060B
79C
49C
Yellow
MJCDO0060D
MJCSO0060D
93C
63C
Green
MJCDO0060E
MJCSO0060E
141C
111C
Blue
MJCDO0060G
MJCSO0060G
57C
27C
Orange
25037
*- - -
68C
38C
Red
25039
*- - -
79C
49C
Yellow
25041
*- - -
93C
63C
Green
25043
*- - -
N/A
N/A
Notes:
1. Approved by the Loss Prevention Certification Board (LPCB Refer to No. 007f/03).
N/A: Not Approved
* Not Available
** On request, avaiable with Walkbery flex cable.
TABLE D
LABORATORY APPROVALS AND PART NUMBERS
FOR DN50 SERIES MJC MULTIPLE JET CONTROLS