Vous êtes sur la page 1sur 72

TECHNICAL MANUAL

FAN COIL

FCX

ISO 9001 - Cert. n 0128/4

IFCXTY
0806
6191101_00
Replace : 64560.41_01 / 0308

4
5
6
7
8
10
11
12
16
17
25
27
28
30
32
33
34
35
37
38
53
54
58
74

DECLARATION OF CONFORMITY
Carriage Safety symbol
Important information
Description Versions
Main components Component description
Selection
System configuration
Technical data
Operating limits
Delivery cooling capacity
Heating power input (3R)
Heating power input ( (4R)
Potenza termica resa BV (1R)
Cooling power yield (direct expansion)
Hanging version available static pressure
Battery pressure drop
Fattori di correzione nel funzionamento with glycol water
Sound power and sound pressure
Sound power level delle versioni pensili canalizzate
Accessories
Unit installation Electrical connections
Dimensions
Wiring diagram
Trouble shooting Maintenance

REMARKS
Store the manuals in a dry location to avoid deterioration, as
they must be kept for at least 10 years for any future reference.
All the information in this manual must be carefully read and
understood. Pay particular attention to the operating standards
with DANGER or WARNING signals as failure to
comply with them can cause damage to the machine and/or
persons or objects.
If any malfunctions are not included in this manual, contact
the local After-sales Service immediately.
The apparatus must be installed in such a way that maintenance and/or repair operations are possible.
The apparatus's warranty does not in any case cover costs due

to automatic ladders, scaffolding or other lifting systems necessary for carrying out repairs under guarantee.
Normal wear of components and filter is not covered by the
warranty.
AERMEC S.p.A. declines all responsibility for any damage
whatsoever
caused by improper use of the machine, and a partial
or superficial acquaintance with the information contained in
this manual.
The number of pages in this manual is: 76.

Italiano

INDEX

Sovrapponibilit: controllare sullimballo la posizione della freccia per


conoscere il numero di macchine impilabili.
Stacking: control the packing for the arrow position to know the number of machines that can be stacked.
Empilement: vrifier sur lemballage la position de la flche pour connatre le nombre dappareils pouvant tre empils.
Stapelung: Anhand der Position des Pfeiles an der Verpackung kontrollieren, wieviele Gerte stapelbar sind.
Apilamiento: observe en el embalaje la posicin de la flecha para saber
cuntos equipos pueden apilarse.

English

NON calpestare Do NOT trample


NE PAS marcher sur cet emballage Nicht betreten
NO pisar

NON lasciare gli imballi sciolti durante il trasporto.


Do NOT leave loose packages during transport.
ATTACHER les emballages pendant le transport.
Die Verpackungen nicht ungesichert transportieren.
NO lleve las cajas sueltas durante el transporte.

35Kg

Deutsche

NON trasportare la macchina da soli se il suo peso supera i 35 Kg.


DO NOT handle the machine alone if its weight is over 35 Kg.
NE PAS transporter tout seul lappareil si son poids dpasse 35 Kg.
Das Gert NICHT alleine tragen, wenn sein Gewicht 35 Kg berschreitet.
NO maneje los equipos en solitario si pesan ms de 35 kg.

Franais

NON bagnare Do NOT wet


CRAINT lhumidit Vor Nsse schtzen
NO mojar

Italiano

TRASPORTO CARRIAGE TRANSPORT TRANSPORT TRANSPORTE

Pericolo:
Tensione

Pericolo:
Organi in movimento

Pericolo!!!

Danger:
Power supply

Danger:
Movings parts

Danger!!!

Danger:
Tension

Danger:
Organes en mouvement

Danger!!!

Gefahr !
Spannung

Gefahr !
Rotierende Teile

Gefahr!!!

Peligro:
Tensin

Peligro:
Elementos en movimiento

Peligro!!!

Espaol

SIMBOLI DI SICUREZZA SAFETY SYMBOL SIMBOLES DE SECURITE


SICHERHEITSSYMBOLE SMBOLOS DE SEGURIDAD

English

IMPORTANT MAINTENANCE INFORMATION


WARNING: The fancoil is connected to
the power supply and a water circuit.
Operations performed by persons
without
the required technical skills can lead
to personal injury to the operator or
damage to the unit and surrounding
objects.
DANGER: never switch the appliance on
without having re/mounted the fan coil
casing.
The ultra-violet radiation emitted
from the bulbs inside is dangerous and
can cause conjunctivitis, burns and
dermatitis.
The device has safety micro switches
that prevent functioning if the casing
and filter are missing.
DANGER: do not tamper with the micro
switches as this would make functioning
of the fan coil unsafe..
FUNCTIONING ANOMALIES
In the case of functioning anomalies,
remove the voltage from the unit
and then re-apply it and re-start the
appliance. If the problem persists, call
the area after-sales service immediately.
ONLY POWER THE FAN COIL USING
230 VOLT, SINGLE-PHASE, 50 Hz
The fan coil may undergo permanent
damage if different electric power
supplies are used.
DO NOT PULL THE ELECTRIC CABLE
It is very dangerous to pull, step on,
crush or fix the electric power supply
cable using nails or staples.
The damaged cable can cause short
circuits and injury to persons.
DO NOT INTRODUCE OBJECTS INTO
AIR VENTS
Do not introduce any type of object into
the air outlet slots.

This could cause injury to persons or


damage the fan.
N E V E R U S E T H E FA N C O I L F O R
APPLICATIONS FOR WHICH IT WAS
NOT DESIGNED
Do not use the fancoil in husbandry
applications (e.g. incubation).
AIR THE ROOM
Periodically air the room in which
the fancoil has been installed; this is
particularly important if the room is
occupied by many people, or if gas
appliances or sources of odours are
present.
C O R R E C T LY
ADJUST
THE
TEMPERATURE
Room temperature should be regulated
to ensure maximum comfort to persons
present, particularly in the case of the
elderly, infants and invalids. Prevent
temperature fluctuations between
indoors and outdoors greater than 7 C
during summer.
Note that very low temperatures during
summer will lead to greater electricity
consumption.
ORIENT AIR FLOW CORRECTLY
Air delivered by the fancoil should
not be oriented directly at people;
even if air temperature is greater than
room temperature, it can cause a cold
sensation and consequently discomfort.
DO NOT USE HOT WATER
When cleaning the indoor unit, use rags
or soft sponges soaked in warm water
(no higher than 40C).
Do not use chemical products or solvents to clean any part of the fancoil.
Do not splash water on interior or exterior surfaces of the fancoil; danger of
short circuit.).

PERIODICALLY CLEAN THE FILTER


Frequent cleaning of the filter will ensure
more efficient unit operation.
Check whether the filter requires cleaning; if it is particularly dirty, clean it
more often.
Clean the filter frequently. Use a vacuum
cleaner to remove built up dust.
After cleaning and drying the filter, fit it
on the fancoil by following the removal
procedure in reverse order.
The normal wear of the germicidal lamp
and of the filter are not covered by warranty.
SPECIAL CLEANING
The removable drip tray and fan volute
ensure thorough cleaning of the unit (by
specifically trained personnel), essential for installations in venues subject to
crowding or in those with special hygiene requirements.
IT IS NORMAL
During cooling, water vapour may be
present in the air delivery of the fan coil.
In the heating function it might be
possible to hear a slight hiss around the
fan coil. Sometimes the fan coil might
give off unpleasant smells due to the
accumulation of dirt in the air of the
environment (especially if the room is
not ventilated regularly, clean the filter
more often).
During the operation, there could be
noises and creaks inside the device, due
to the various heat expansions of the
elements (plastic and metallic), but this
does not indicate any malfunctioning
and does not cause damage to the
unit unless the maximum input water
temperature is exceeded.

FCX - - FAN COIL


Congratulations on your purchase of the Aermec FCX fan coil.
Made with materials of superior quality in strict compliance with safety regulations, the "FCX " is easy to use and
will have a long life.
used in summer as an air conditioner if
the heating system has a water chiller..
The removable drip tray and fan
volute ensure thoroug cleaning of the
unit essential for installations in venues
subject to crowding or in those with
special hygiene requirements.
The quietness of the new centrifugal fan
assembly is such that at normal speed of
use you cannot hear when the FCX cuts
in.

The FCX fan coil has been designed to


meet all system requirements thanks to
its extensive range of accessories.
The AERMEC fan coil versions without
control panels can be combined to an
AERDOMUS central control unit.
Full respect for accident prevention
regulations

English

The fan coil units treat room air during


summer and winter seaqsons.
Th e F C X f a n c o i l c o n c e n t ra t e s
high technological and functional
characteristics that make it the ideal
climate control unit for all types of
rooms. The supply of climate controlled
air is immediate and distributed
throughout the room;; FCX generates
heat if included in a heating system with
boiler or heat pump but may also be

VERSION
SIZES AVAILABLE
The FCX fan coil series are avaailable in
with 3 row coil
9 versions for 8 sizes
FCX 17 (*)
FCX 62
FCX 22
FCX 82
FCX 32
FCX 102 (**)
FCX 42
FCX 50

with 4-row coil battery


2 version P and PO for 6 sizes
FCX 24
FCX 34
FCX 44
FCX 54

FCX 64
FCX 84

(*) FCX 17 not available in UE, PE and PO versions .


(**) FCX 102 not available in PO versions .

FCX A - AS - ACB - ACT - APC

ZX

FCX 17 50 U - UE

FCX 62 102 U - UE

FCX P - PPC

- PO - PE

FCX_A: with selector and a 3 speed fan unit, free standing for vertical installation coated
with anti rust polyester, colour RAL 9002. The delivery grill and the skirting for floor standing
installations (accessory ZX) are made of plastic and are colour RAL 7044.
FCX_AS: without control panels and with a 3 speed fan unit, free standing for vertical
installation coated with anti rust polyester, colour RAL 9002. The delivery grill and the skirting
for floor standing installations (accessory ZX) are made of plastic and are colour RAL 7044. An
external control panel is necessary (accessory).
FCX_ACB: with an electronic thermostat and a 3 speed fan unit free standing for vertical
installation coated with anti rust polyester, colour RAL 9002. The delivery grill and the skirting for
floor standing installations (accessory ZX) are made of plastic and are colour RAL 7044.
FCX_ACT: with an electronic multifinction thermostat and a 3 speed fan unit, free standing
for vertical installation coated with anti rust polyester, colour RAL 9002. The delivery grill and
the skirting for floor standing installations (accessory ZX) are made of plastic and are colour RAL
7044.
FCX_APC: with a PLASMACLUSTER ionizing filter, with an electronic multifinction thermostat
and a 3 speed fan unit free standing for vertical installation coated with anti rust polyester, colour
RAL 9002. The delivery grill and the skirting for floor standing installations (accessory ZX) are
made of plastic and are colour RAL 7044..
FCX_U: without control panels and with a 3 speed fan unit, free standing for vertical installation
coated with anti rust polyester, colour RAL 9002. The delivery grill and the skirting for floor
standing installations (accessory ZX) are made of plastic and are colour RAL 7044. An external
control panel is necessary (accessory)..
FCX_UE: with direct expansion coil, without control panels and with a 3 speed fan unit, free
standing for vertical installation coated with anti rust polyester, colour RAL 9002. The delivery grill
and the skirting for floor standing installations (accessory ZX) are made of plastic and are colour
RAL 7044. An external control panel is necessary (accessory).
FCX_P: version in galvanised steel without cabinet, without control panels and with a 3 speed
fan unit, for horizontal and vertical wall installation. An external control panel is necessary
(accessory).
FCX_PE: with direct expansion coil, version in galvanised steel without cabinet, without control
panels and with a 3 speed fan unit, for horizontal and vertical wall installation. An external
control panel is necessary (accessory).
FCX_PPC: with a PLASMACLUSTER ionizing filter, version in galvanised steel without cabinet,
without control panels and with a 3 speed fan unit, for horizontal and vertical wall installation.
An external PXAE control panel is necessary (accessory).
FCX_PO: version in galvanised steel without cabinet, without control panels and with a 7
speed fan unit, for horizontal and vertical wall installation. An external control panel is necessary
(accessory).

COMPONENTI PRINCIPALI
1
2
3
4
5

6 Fan
7 Main Frame
8 Condensate pump
9 Hydraulic connections
10 Head with adjustable fins (RAL7044)

Control panel (accessory)


Thermic exchange coil
Air Filter
Cover cabinet (RAL9002)
Fan motor

1
10

FCX 42 U

English

3
4

5
6
9

DESCRIPTION OF COMPONENTS
CONTROL PANEL
The control panel is located under the
grill positioined at the right of the fan
coil.In A, AS, ACB, ACT, APC and U
(62U, 82U e 102U) versions, the panel
can be protected from tampering by
using a screw to block the cover door.
In the AS and U versions, the controls
panel (accessory) can be installed on the
fan coil or on the wall.
In versions P, PO and PE, the controls
panel (accessory) can be installed only
on the wall.
The AERMEC fan coil versions without
control panels can be combined to a
HSH AERDOMUS central control unit
with or without connection cables.
Before selecting, consult the control
panels features.
FCX A
:
fan coil equipped with control panel for
use and selcting the fan speed.

WITH MANUAL SELECTORS

FCX ACT e APC


WITH ELECTRONIC
THERMOSTAT :

M U LT I F U N C T I O N

fan coils equipped with multifunction


electronic thermostat control panels,
the fan coils FCX ACT and FCX APC
are supplied ready for use with standard
configuration, but the installer can adapt
them the special requirements of the
system with the appropriate accessories
and personalising the functions by acting
on the internal Dip-Switch.
The controls are prompt but if valves are
presence they could delay.

System types
The FCX-ACT fan coils have been
designed for systems with 2 pipes, in the
following versions:
- without valve;
- with water valve (VCF);
- with electrical resistance (RX);
- with electrical resistance (RX) and valve
(VCF);
- with hot water battery (BV) and 2 valves
(VCF).
FCX APC : fancoils with
PLASMACLUSTER designed for 2-pipes
plant, in the following models:
- without valve;
- with water valve (VCF);
Ventilation
Th e t h r e e - s p e e d ve n t i l a t i o n c a n
be controlled either manually or
automatically.
For systems with valve and Water Probe
installation upstream of the valve there
may be a delay (delayed ventilation up
to 240 max) between the valve start-up
and the fan activation (exchanger preheating).
- manually with the selector in V1, V2 e
V3 position (the fan coil is used with on
off cycles on selected speed);
- automatically with the selector
in AUTO position (the fan speed is
controlled by the thermostat according
to the room temperature)
Change over
The thermostat automatically changes
over from Heating/cooling mode.
Change over is based on the water
temperature detected in the system. It is
possible to choose between two change

over modes by changing the settings on


the DIP switch :
- only minimum/maximum temperature
control;
- with minimum/maximum temperature
control and the preheating of the coil
(fan delayed for a maximum of 240).
Only systems with water probes
positioned downstream of the valve
or with a two way valve, change over
occurs on the air side by acting on
the temperature selector; this setting
allows the fan coil to be used in
systems with two way valves but is not
advised because it reduces the use of
the electronic thermostat (the heating/
cooling modes displayed by the led
are altered depending on the selected
temperature and of the air temperature
in the environment.
Water temeperature controls
The
thermostat
enables
ventilatsolamenteon only if the water
temperature is suited to Hetaing or
Cooling mode.
The enabling threshold is 35C or
39C for Heating and 17C or 22C for
Cooling and can be configured by the
Dip-Switch.
The control panels signal the situation
when the water temperature is not
adequate to the function mode set by
means of the alternate flashing of the
pink C led with red or blue depending
on the relative active modes.
If a three way valve is inserted with a
water probe as per standard, it must be
replaced with the SW3 accessory in
which the bulb must be positioined on

FCX ACB
WITH SIMPLIFIED ELECTRONIC THERMOSTAT:

fan coil equipped with control panel


with electronic room thermostat for
controlling switch on and switch off of
the fan.
The control panel controls the function
of the fan coil in order to maintain the
set room temperature. It allows the
electronic adjustment of the temperature,
manual speed change on the fan,manual
function selection in Heating or Cooling
mode (manual change over).
The room probe temperature is located
bext to the AERMEC plate.
It is not possible to couple the thermostat
with a water temperature probe.
If the power supply is cut, the fan coils
restarts resetting the previous modes set

The controls are prompt if the room


temperature allows it. Water temperature
control of the system is not foreseen
Type of system
The fan coil series FCX ACB are designed
for two pipe systems :
- without valve;
- with water valve (VCF);
Ventilation
The 3 speed fan is manually controlles
with a selector positioned in V1, V2 and
V3 (the fan is used with on off cycles on
the speed selected).
Change over
Change over is manual, the user selects
the function mode (Heating or Cooling)
by acting on the selector of the controls
panel.
Valve control
The valve (accessory) opens or closes in
correspondance with the switching on
and switching off of the fan .

and with a door for accessing the control


panel.
Version U, UE : are inserted with
adjustable grills on the top in thermo
plastic material for the diffusion of air
and with a door for accessing the control
panel. With the adjustable grill closed,
intervening on the micro switch stops the
fan, interrupting any heat change with
the room. The cabinet has a front grill in
thermoplastic material for air intake. .

HEAT EXCHANGE COIL

Made from thick galvanised steel The


rear has holes for fitting the appliance
to the wall For wall panels, a panel for
closing the fan group is provided. Each
appliance is supplied with a condensate
drain tray

Coil with copper pipe and finned


in blocked aluminium by means of
mechanical expansion pipes The
collectors are attached with female
connectors and air relief at the top of
the coil.

FILTER SECTION
Easily removable and built with
regenerised materialsand can be cleaned
by washing
Versions P and PO filters with filtration
class G2.

CABINET CASE
Colour RAL9002
Delivery and Intake grill colour
RAL7044
The steel case is treated and coated with
powered polyester to guarantee high rust
resistance and corrosion.
Versions A, AS, ACT, APC, ACB : are
inserted with grills on the top in thermo
plastic material for the diffusion of air

ELECTRO FAN UNIT


It is made up of double inlet centrifugal
fans with blades along its length for
obtaining a high capacity with a low
number of revs. The electric motor
protects from over loads, it is three speed
with condenser always inserted, directly
coupled with the fans and with elastic
supports. The FCX PO versions have 7
speed motors. (3 selections) .

SUPPORT STRUCTURE

CONDENSATE DRAIN
Each appliance is supplied with a
condensate drain tray connected to the
condensate outlet produced from the
unit id cooling mode.

HYDRAULIC CONNECTIONSI
The connections, positioned on the
left side have female attachments. It is
possible to rotate the coil.

PACKING
The units are shipped in cardboard box
standard packing and polystirene shells.

English

the delivery pipe upstream of the valve.


Valve control
The valve can be controlled in two
ways::
- optimised: uses the fan coil capacity
in Heatingto produce heat even with
ventilation off and in Cooling for a
continuous ventilation controlling the
room temperature by means of a valve;
- normal: the valve opens and closes in
correspondance with the switch on and
switch off of the fan coil.
Emergency mode
In case of probe troubleshooting SA, the
thermostat enters in emergency mode,
indicated by a flashing led (D) yellow. In
this condition the thermostat behaves as
follows::
- with selector (A) in OFF position the
water valave is closed and the fan is off.
- with selector (A) in AUTO position,
V1, V2 and V3 the water valve is always
open and the fan performs on off cycles;
in this situation, the power provided by
the terminal is manually controlled by
selcetor (B): turning towards the right
the duration of the On cycle increases;
turningn towards the left it reduces.

English

CRITERIA OF CHOICE
The versions with high cabinet (A, AS,
ACB, ACT and APC) have intake from
below and can be used for vertical wallhung or floor installation using the relevant skirting (accessory ZX). The accessory SE (external air damper) where
requested, also allows, to change the
environment air.
The versions with universal cabinet (U
and UE) have front intake and can be
vertically wall-hung or installed horizontally on the ceiling.
The suspended versions (P, PPC, PO and
PE), without cover cabinets and intake
from below, are suitable for vertical or
horizontal installation.
In the case of ducted installations where
the loss of load of the channel is relevant, the PO version (with multi-speed
enhanced motor) allows to obtain the
static pressure necessary to guarantee a
correct air flow rate.
The PO version is available with coils
with 3 and 4 rows.
The AS, U, UE versions require coupling
with a control panel to be applied inside or outside, consult the features and
the compatibility of the control panels
supplied as accessories.
The P, PE and PO require coupling with
a control panel to be applied outside,
consult the features and the compatibility of the control panels supplied as
accessories.
The PPC version must be coupled to
panel PXA E.
The other versions of fan coil are supplied with incorporated control panel.
Some control panels can control a network of fan coils if they are combined
with the SIT3 and SIT5 interface board
supplied as an accessory.
In the versions without control
panels, the AERMEC fan coils can all
be coupled to the centralised HSH
AERDOMUS control system with wired
or wireless connection.
The main technical data of the FCX are
summarised in the tables.

10

The sensitive and total cooling capacity at maximum speed depending on


the temperature of the inlet water, its
heat drop and the dry and wet bulb
temperatures of the air respectively for
sensitive capacity and total capacity for
the versions with coils with 3 rows are
stated in the table. The efficiency at average and minimum speed is obtained by
multiplying the table values by the corrective factors indicate. For the versions
with 4 rows, they are obtained by multiplying the table values by the corrective
factors indicated for every speed.
The water side pressure drop for the
coils with 3, 1 and 4 rows is respectively stated in the graphics.
The correction factors in functioning
with glycoled water in cooling mode
and in heating mode are stated in the
graphics per percentages of glycol of
10%, 20% and 35%.
The heating capacity of the coils with 3,
4 and 1 row (accessory BV) depending
on the water flow rate and the temperature difference between inlet water
and inlet air is stated in a graphical
form and is referred at maximum speed.
Performance at average and minimum
speed is obtained by multiplying the
values obtained from the graphics at
maximum speed by the indicated corrective factors.
The sensitive and total cooling capacities of the direct expansion coils (FCX
PE) depending on the evaporation temperature and the dry and wet bulb temperatures of the air entering are stated in
the graphical form respectively for total
and sensitive capacity and are stated at
maximum speed. Performance at average and minimum speed is obtained
by multiplying the values obtained from
the graphics at maximum speed by the
indicated corrective factors.
For the ducted, suspended versions
(P-PE-PO) the performance stated above
must be intended as referring to air flow
rates equal to those of corresponding
models of other versions (A-U) at maximum speed (nominal flow rate).

The head of the suspended versions,


depending on the air flow rate and fan
speed, are stated in table form. The curves are indicated for every speed.
For dimensioning of the ducted, suspended versions, it is recommended to proceed as follows: select the size which,
in nominal flow rate conditions, have
immediate power that is higher than
that requested; trace the curve of the
channel pressure drop on the flow ratestatic pressure diagram relative to the
machine in question, thus identify the
functioning points of the machine at
the different speeds. On the basis of the
flow rate values corresponding to the
above-mentioned points, the corrective
factors are finally obtained that allow to
calculate the power yielded in real air
flow conditions. The above-mentioned
procedure allows, in the case of multispeed versions, to appropriately choose
the speed to be set.
The sound power and sound pressure level of the fan coils at the various
speeds is stated in separate tables for
the versions with 3 rows and versions
with 4 rows. For ducted, suspended versions, the sound power level is expressed depending on the air flow rate and
static pressure and is represented using
graphics.
A wide range of accessories is available for FCX series fan coils, sometimes some of them cannot be used at
the same time. The compatibility of the
accessories with the selected fan coil
must be checked. The manual contains
the description, drawing and compatibility of each accessory.
The information regarding installation
is inserted in the manual supplied with
every fan coil and every accessory. This
manual is limited to general information
in order to perform correct installation.
There are also drawings with dimensions of the fan coils and wiring diagrams with connections to the control
panels.

FCX UNIT LAY-OUT


Reading Key:
Water temperature probe
Solenoid valve (Heating / Cooling)
Solenoid valve (Heating),
Solenoid valve (Cooling)

SA
V3,V2,V1
RX
PC

Ambient temperature probe


Maximum, Average, Minimum Fan Coil speed.
Resistance
Plasmacluster

2-pipe unit with water probe


AIR

SA

AIR

SW

SA

VCF SW

SA

SW

RX

SA

PC

RX

BV

SA

VCF SW

VC/VF

SW

VC

SW

SA

RX

SA

BV

VC

VF SW

SA

VCF

VCF SW

SA

SA

VCF

AIR

AIR

SA

220V

PC

SA

VCF

PC

AIR

AIR

SA

RX

RX

VCF

VCF

AIR

SA

RX

VCF

4-pipe unit without water probe

SW

BV

VCF

220V

PC

AIR

AIR

SA

AIR

AIR

AIR

AIR

VF

SA

220V

PC

4-pipe unit with water probe


AIR

SA

VCF

220V

AIR

SW

SW

SA

SW

AIR

AIR

220V

AIR

SA

SA

AIR

220V

PC

AIR

AIR

AIR

SA

2-pipe unit without water probe

SA

BV

VC

AIR

VF

SA

BV

VC

VF

AIR

SA

BV

11

English

SW
VCF
VC
VF

TECHNICAL DATA
FCX A-AS-ACT-APC-ACB-U-P with 3-row coil
FCX 17

FCX 22

FCX 32

FCX 42

FCX 50

FCX 62

FCX 82 FCX 102

W (max.)
W (med.)
W (min.)

2490
2070
1610

3400
2700
1915

4975
4085
3380

7400
6415
5115

8620
7530
5420

12920
10940
8330

15140
13350
10770

17020
15240
12560

W (E)

1360

2100

3160

4240

4900

6460

7990

9670

W
l/h
kPa

700
214
2,8

950
292
6,3

1300
427
14,2

1650
636
14,1

1950
741
14,2

2200
1110
14,8

2200
1300
19,8

2200
1464
16,6

W (max.) (E)
W (med.)
W (min.)
W (max.) (E)
W (med.)
W (min.)
l/h
kPa (E)

1000
890
720
830
710
540
172
2,6

1500
1330
1055
1240
1055
755
258
5,8

2210
2055
1570
1750
1540
1100
380
16,6

3400
2800
2310
2760
2115
1635
585
14,3

4190
3640
2840
3000
2750
2040
721
19,3

4860
4660
3950
3980
3510
2825
836
11,6

7420
5500
4710
5680
4250
3450
1276
13,5

7620
7140
6270
5980
4984
4263
1311
19,2

m3/h (max.)
m3/h (med.)
m3/h (min.)
n.
dB (A) (max.)
dB (A) (med.)
dB (A) (min.)
dB (A) (max.) (E)
dB (A) (med.) (E)
dB (A) (min.) (E)
l
W (E)
A

200
160
110
1
36,5
29,5
22,5
45
38
31
0,58
35
0,16

290
220
140
1
41,5
34,5
22,5
50
43
31
0,79
25
0,12

450
350
260
2
39,5
32,5
25,5
48
41
34
1,11
44
0,21

600
460
330
2
42,5
35,5
28,5
51
44
37
1,48
57
0,28

720
600
400
2
47,5
42,5
33,5
56
51
42
1,48
67
0,35

920
720
520
3
48,5
42,5
33,5
57
51
42
2,52
82
0,40

1140
930
700
3
53,5
48,5
41,5
62
57
50
2,52
106
0,49

1300
1120
900
3
57,5
52,5
47,5
66
61
56
2,52
131
0,58

735

975

1344

1707

2017

2282

2306

2331

3,2

4,25

5,86

7,45

8,83

9,97

10,06

10,15

1/2
1/2

1/2
1/2

1/2
1/2

3/4
1/2

3/4
1/2

3/4
1/2

3/4
1/2

3/4
1/2

Mod.
Heating
Heating capacity

English

Heating capacity*
(water inlet 50C)
Heating capacity (accessory RX)
Water flow rate
Water pressure drop
Cooling
Total cooling capacity

Sensible cooling capacity


Water flow rate
Water pressure drop

Air flow rate


Fans
 Sound pressure

Sound power
Water contents
Max. motor power
Max. input current
Max. motor power
with electric heater
Input current
with electric heater
Coil connections 3R
Coil connections 1R

Power supply = 230V ~ 50Hz

Performance values refer to the following conditions:


 Sound pressure measured in an 85 m 3 semi-reverberant test
chamber with reverberation time Tr = 0.5s.
Cooling:
- room air temperature 27 C B.S., 19 C B.U.;
maximum speed:
- water inlet temperature 7 C; t water 5 C.
medium and low speed:
- water inlet temperature 7 C;
- water flow rate remains same as at maximum speed.

12

(E) = EUROVENT certified performance

Heating:
room air temperature 20 C B.S.;
maximum speed:
- water inlet temperature 70 C; t water 10 C;
medium and low speed:
- water inlet temperature 70 C;
- water flow rate remains same as at maximum speed.
maximum speed (water inlet 50C):
- water inlet temperature 50 C;
- water flow rate same as in cooling operation.

TECHNICAL DATA

FCX 22

FCX 32

FCX 42

FCX 50

FCX 62

FCX 82

W (max.)
W (med.)
W (min.)

3400
2700
1915

4975
4085
3380

7400
6415
5115

8620
7530
5420

12920
10940
8330

15140
13350
10770

W (E)

2100

3160

4240

4900

6460

7990

W
l/h
kPa

950
292
6,3

1300
427
14,2

1650
636
14,1

1950
741
14,2

2200
1110
14,8

2200
1300
19,8

W (max.) (E)
W (med.)
W (min.)
W (max.) (E)
W (med.)
W (min.)
l/h
kPa (E)

1500
1330
1055
1240
1055
755
258
5,8

2210
2055
1570
1750
1540
1100
380
16,6

3400
2800
2310
2760
2115
1635
585
14,3

4190
3640
2840
3000
2750
2040
721
19,3

4860
4660
3950
3980
3510
2825
836
11,6

7420
5500
4710
5680
4250
3450
1276
13,5

m3/h (max.)
m3/h (med.)
m3/h (min.)
n.
dB (A) (max.)
dB (A) (med.)
dB (A) (min.)
dB (A) (max.) (E)
dB (A) (med.) (E)
dB (A) (min.) (E)
l
W
A

290
220
140
1
41,5
34,5
22,5
50
43
31
0,79
54
0,25

450
350
260
2
39,5
32,5
25,5
48
41
34
1,11
97
0,45

600
460
330
2
42,5
35,5
28,5
51
44
37
1,48
111
0,51

720
600
400
2
47,5
42,5
33,5
56
51
42
1,48
82
0,36

920
720
520
3
48,5
42,5
33,5
57
51
42
2,52
97
0,48

1140
930
700
3
53,5
48,5
41,5
62
57
50
2,52
135
0,62

1004

1397

1761

2032

2297

2335

4,38

6,00

7,68

8,84

10,05

10,19

1/2
1/2

1/2
1/2

3/4
1/2

3/4
1/2

3/4
1/2

3/4
1/2

Mod.
Heating
Heating capacity
Heating capacity*
(water inlet 50C)
Heating capacity (accessory RX)
Water flow rate
Water pressure drop
Cooling
Total cooling capacity

Sensible cooling capacity


Water flow rate
Water pressure drop

Air flow rate


Fans
 Sound pressure

Sound power
Water contents
Max. motor power
Max. input current
Max. motor power
with electric heater
Input current
with electric heater
Coil connections 3R
Coil connections 1R

Power supply = 230V ~ 50Hz

Performance values refer to the following conditions:


 Sound pressure measured in an 85 m3 semi-reverberant test chamber
with reverberation time Tr = 0.5s.
Cooling:
- room air temperature 27 C B.S., 19 C B.U.;
maximum speed:
- water inlet temperature 7 C; t water 5 C.
medium and low speed:
- water inlet temperature 7 C;
- water flow rate remains same as at maximum speed.

English

FCX PO with 3-row coil

(E) = EUROVENT certified performance

Heating:
room air temperature 20 C B.S.;
maximum speed:
- water inlet temperature 70 C; t water 10 C;
medium and low speed:
- water inlet temperature 70 C;
- water flow rate remains same as at maximum speed.
maximum speed (water inlet 50C):
- water inlet temperature 50 C;
- water flow rate same as in cooling operation.

13

TECHNICAL DATA
FCX P with 4-row coil
FCX 24

FCX 34

FCX 44

FCX 54

FCX 64

FCX 84

W (max.)
W (med.)
W (min.)

3950
3200
2200

5850
4850
3850

8600
6930
5200

10100
8760
6240

14300
11500
8500

17100
14420
11200

W (E)

2320

3550

5250

6100

7810

10400

l/h
kPa

340
4

503
8

740
21

869
22

1230
22

1471
30

W (max.) (E)
W (med.)
W (min.)
W (max.) (E)
W (med.)
W (min.)
l/h
kPa (E)

1730
1500
1150
1380
1140
828
297
3

2800
2450
2050
2130
1789
1441
482
9

4450
3780
2970
3300
2722
2079
765
19,2

4970
4770
3620
3540
3101
2281
855
25,9

6350
5520
4500
5030
4195
3330
1092
13

8600
7600
6270
5780
5016
4013
1479
22

m3/h (max.)
m3/h (med.)
m3/h (min.)
n.
dB (A) (max.)
dB (A) (med.)
dB (A) (min.)
dB (A) (max.) (E)
dB (A) (med.) (E)
dB (A) (min.) (E)
l
W (E)
A

290
220
140
1
42,5
37,5
26,5
51
46
35
1
33
0,25
3/4

450
350
260
2
39,5
32,5
27,5
48
41
36
1,5
44
0,45
3/4

600
460
330
2
46,5
41,5
32,5
55
50
41
1,9
57
0,51
3/4

720
600
400
2
47,5
44,5
35,5
56
53
44
1,9
67
0,36
3/4

920
720
520
3
48,5
42,5
35,5
57
51
44
3,4
91
0,48
3/4

1140
930
700
3
52,5
48,5
42,5
61
57
51
3,4
106
0,62
3/4

Mod.
Heating
Heating capacity

English

Heating capacity*
(water inlet 50C)
Water flow rate
Water pressure drop
Cooling
Total cooling capacity

Sensible cooling capacity


Water flow rate
Water pressure drop

Air flow rate


Fans
 Sound pressure

Sound power
Water contents
Max. motor power
Max. input current
Coil connections 4R

Power supply = 230V ~ 50Hz

Performance values refer to the following conditions:


 Sound pressure measured in an 85 m 3 semi-reverberant test
chamber with reverberation time Tr = 0.5s.
Cooling:
- room air temperature 27 C B.S., 19 C B.U.;
maximum speed:
- water inlet temperature 7 C; t water 5 C.
medium and low speed:
- water inlet temperature 7 C;
- water flow rate remains same as at maximum speed.

14

(E) = EUROVENT certified performance

Heating:
room air temperature 20 C B.S.;
maximum speed:
- water inlet temperature 70 C; t water 10 C;
medium and low speed:
- water inlet temperature 70 C;
- water flow rate remains same as at maximum speed.
maximum speed (water inlet 50C):
- water inlet temperature 50 C;
- water flow rate same as in cooling operation.

TECHNICAL DATA

FCX 24

FCX 34

FCX 44

FCX 54

FCX 64

FCX 84

W (max.)
W (med.)
W (min.)

3950
3200
2200

5850
4850
3850

8600
6930
5200

10100
8760
6240

14300
11500
8500

17100
14420
11200

W (E)

2320

3550

5250

6100

7810

10400

l/h
kPa

340
4

503
8

740
21

869
22

1230
22

1471
30

W (max.) (E)
W (med.)
W (min.)
W (max.) (E)
W (med.)
W (min.)
l/h
kPa (E)

1730
1500
1150
1380
1140
828
297
3

2800
2450
2050
2130
1789
1441
482
9

4450
3780
2970
3300
2722
2079
765
19,2

4970
4770
3620
3540
3101
2281
855
25,9

6350
5520
4500
5030
4195
3330
1092
13

8600
7600
6270
5780
5016
4013
1479
22

m3/h (max.)
m3/h (med.)
m3/h (min.)
n.
dB (A) (max.)
dB (A) (max.)
l
W (E)
A

290
220
140
1
49,5
58
1
54
0,25
3/4

450
350
260
2
44
52,5
1,5
97
0,45
3/4

600
460
330
2
50
58,5
1,9
111
0,51
3/4

720
600
400
2
50,5
59
1,9
82
0,36
3/4

920
720
520
3
53,5
62
3,4
97
0,48
3/4

1140
930
700
3
55,5
64
3,4
135
0,62
3/4

Mod.
Heating
Heating capacity
Heating capacity*
(water inlet 50C)
Water flow rate
Water pressure drop
Cooling
Total cooling capacity

Sensible cooling capacity


Water flow rate
Water pressure drop

Air flow rate


Fans
 Sound pressure
Sound power
Water contents
Max. motor power
Max. input current
Coil connections 4R

Power supply = 230V ~ 50Hz

Performance values refer to the following conditions:


 Sound pressure measured in an 85 m 3 semi-reverberant test
chamber with reverberation time Tr = 0.5s.
Cooling:
- room air temperature 27 C B.S., 19 C B.U.;
maximum speed:
- water inlet temperature 7 C; t water 5 C.
medium and low speed:
- water inlet temperature 7 C;
- water flow rate remains same as at maximum speed.

English

FCX PO with 4-row coil

(E) = EUROVENT certified performance

Heating:
- room air temperature 20 C B.S.;
maximum speed:
- water inlet temperature 70 C; t water 10 C;
medium and low speed:
- water inlet temperature 70 C;
- water flow rate remains same as at maximum speed.
maximum speed (water inlet 50C):
- water inlet temperature 50 C;
- water flow rate same as in cooling operation.

15

OPERATING LIMITS
Maximum water inlet temperature............................ 80 C
Maximum working pressure ....................................... 8 bar
Operating Voltage ..............................230V(10%) ~ 50Hz
Room Temperature ................................................. 045C
Room Humidity................................................. <85% U.R.
Water flow limits (3-row coil ):

English

MOD.
Minimum water flow
Maximum water flow

FCX
[l/h]
[l/h]

17
100
750

22
100
750

32
100
750

42
150
1100

50
150
1100

62
300
2200

82
300
2200

102
300
2200

17
50
400

22
50
400

32
50
400

42
50
400

50
50
400

62
100
900

82
100
900

102
100
900

24
150
1100

34
150
1100

44
150
1100

54
150
1100

64
300
2200

84
300
2200

Water flow limits (1-row coil):


MOD.
Minimum water flow
Maximum water flow

FCX
[l/h]
[l/h]

Water flow limits (4-row coil):


MOD.
Minimum water flow
Maximum water flow

FCX
[l/h]
[l/h]

Minimum average water temperature


To prevent the formation of condensation on the exterior of
the unit while the fan is operating, the average water
temperature should not drop beneath the limits shown in the
table below, determined by the thermo-hydrometric ambient
conditions.
These limits refer to unit operation with fan at minimum speed.

In case condensation is formed on the exterior of the unit


if cold water circulates through the coil while the fan is off
for prolonged periods of time, it is advisable to fit the
additional three-way valve.

Dry bulbe air temperature [C]

MINIMUM AVERAGE WATER TEMPERATURE

Wet bulbe air temperature C

16

15
17
19
21
23

21
3
3
3
6
-

23
3
3
3
5
8

25
3
3
3
4
7

27
3
3
3
3
6

29
3
3
3
3
5

31
3
3
3
3
5

COOLING CAPACITY

FCX 17
Water temp.
Inlet [C]

10

11

12

13

SENSIBLE COOLING CAPACITY [W]


Dry bulbe air temperature [C]

15

17

19

21

23

21

23

25

27

29

31

3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7

884
750
699

777
674
627

671
602

597
551

539
500

481

429

1246
1071
920
852

1109
934
823
768

964
825
736

845
718
660

727
635
593

630
575

572
525

514
473

456

1624
1472
1277
1105
1027
1495
1328
1141
991
927
1362
1171

2012
1866
1710
1525
1328
1882
1734
1572
1364
1191
1750
1595
1403
1209
1075
1615
1452
1252
1061
970
1472
1282
1098
941
878
1309
1118
955
843

1152
982
829
757

986
845
730

856
732
654

2428
2286
2137
1975
1803
2299
2157
2002
1833
1638
2167
2021
1859
1684
1466
2031
1879
1710
1505
1296
1889
1730
1555
1346
1146
1744
1578
1378
1177
1023
1591
1405
1205
1027
918
1432
1227
1045
891
826
1259
1071
904
795

723
652
615
583
548
654
595
562
530
498
589
544
512
480
447
532
493
461
429
395
477
443
411
378
345
425
392
360
326
292
374
342
310
275
238
324
292
258
222
182
273
240
206
167
120

857
768
718
685
652
786
711
666
635
601
727
652
615
580
548
658
595
562
530
497
594
544
512
479
446
536
493
461
429
395
479
443
410
378
344
425
392
360
326
292
374
341
309
275
238

996
907
820
781
747
923
840
768
731
699
858
780
716
683
649
796
717
667
634
600
728
654
614
579
548
662
594
561
530
497
598
543
510
479
446
541
492
461
428
395
483
442
410
377
343

1112
1044
956
877
835
1054
980
895
823
791
995
911

1226
1161
1093
1011
933
1170
1104
1029
945
879
1113
1046
966
879
832
1054
982
899
822
788
995
912
835
771
739
930
851
773
725
694
860
787
716
678
648
798
725
664
630
599
732
664
614
578
547

1337
1276
1211
1145
1068
1282
1220
1155
1086
1001
1226
1163
1096
1018
936
1168
1105
1038
954
878
1110
1046
969
891
827
1053
982
903
828
782
993
918
839
770
737
928
853
778
723
693
858
789
720
678
648

1000
891
837
1212
1036
875
807

1055
900
775
725

920
779
694

788
679
622

679
600

605
547

830
777
744
930
849
769
730
695
859
784
715
682
649
797
722
665
631
600
731
659
614
579
547
665
595
561
528
497
602
542
510
479
446

NB: Values of capacity in bold face refer to nominal value.


Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consider only the values of sensible capacity.
The cooling capacities in the table must be multiplied by the following factors:
MOD.
FCX 17
total capacity
1,00
Maximun speed
sensible capacity
1,00
total capacity
0,89
Medium speed
sensible capacity
0,86
total capacity
0,72
Minimum speed
sensible capacity
0,65

17

English

TOTAL COOLING CAPACITY [W]


Wet bulbe air temperature [C]

COOLING CAPACITY

FCX 22
TOTAL COOLING CAPACITY [W]
Wet bulbe air temperature [C]
Water temp.
Inlet [C]

3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7

English

10

11

12

13

SENSIBLE COOLING CAPACITY [W]


Dry bulbe air temperature [C]

15

17

19

21

23

21

23

25

27

29

31

1238
1110
948
866

1085
963
837
779

948
841
750
707

837
748
683

750
671
616

683
593

1731
1579
1372
1167
1049
1555
1387
1198
1015
946
1372
1207
1033
908
847
1198
1046
901
817

1033
907
783
738

901
796
713

782
716
646

713
637

646

2254
2090
1893
1677
1436
2086
1917
1701
1478
1247
1893
1719

2613
2440
2250
2028
2613
2440
2258
2063
1811
2440
2258
2072
1841
1597
2258
2072
1862
1625
1390
2072
1878
1640
1420
1198
1862
1652
1433
1222
1052
1640
1433
1238
1061
933
1433
1247
1073
918
840
1238
1058
921
806

3163
3003
2826
2631

2994
2826
2640
2436

2817
2640
2445
2232

2631
2449
2245
1997

2440
2250
2019
1762
2449
2241
2037
1780
1542
2250
2032
1795
1555
1329
2037
1801
1564
1350
1143
1795
1561
1350
1155
988

1065
973
864
814
768
980
875
786
742
698
885
783
719
673
627
794
701
649
603
558
714
625
580
534
487
633
554
510
464
415
551
486
441
393
342
467
416
370
322
266
392
346
299
246
181

1253
1162
1048
955
907
1164
1068
955
882
840
1066
977
869
814
766
983
891
786
742
696
890
793
717
673
627
799
711
648
603
558
719
629
579
534
487
638
554
510
464
415
556
485
440
393
342

1434
1350
1236
1124
1033
1352
1252
1143
1038
969
1262
1165
1056
953
905
1164
1073
971
882
839
1079
984
878
813
766
986
897
790
741
696
893
801
717
673
627
804
720
648
603
558
723
638
578
534
487

1590
1512
1430
1322
1207
1511
1432
1334
1229
1119
1432
1350

1743
1669
1594
1511
1407
1667
1591
1514
1422
1314
1589
1513
1432
1326
1223
1508
1430
1340
1235
1129
1429
1350
1250
1147
1047
1347
1260
1159
1062
968
1257
1167
1067
975
904
1162
1075
985
889
836
1078
989
896
812
764

1891
1823
1751
1673
1591
1814
1745
1672
1594
1510
1736
1666
1595
1513
1419
1662
1590
1514
1430
1327
1582
1511
1434
1337
1230
1505
1431
1345
1245
1143
1424
1349
1252
1151
1058
1343
1259
1161
1070
974
1253
1165
1070
983
902

1500
1280
1107
1701
1512
1311
1119
994
1527
1314
1137
966
889
1311
1134
977
858

1137
978
854
767

977
854
753
701

854
762
678

1240
1139
1036
1349
1260
1149
1049
967
1261
1166
1061
966
904
1163
1073
979
884
840
1078
986
888
812
764
988
901
799
741
696
896
809
720
671
627

NB: Values of capacity in bold face refer to nominal value.


Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consider only the values of sensible capacity.
The cooling capacities in the table must be multiplied by the following factors:
MOD.
FCX 22
total capacity
1,00
Maximum speed
sensible capacity
1,00
total capacity
0,89
Medium speed
sensible capacity
0,85
total capacity
0,70
Low speed
sensible capacity
0,61

18

FCX 24
1,15
1,11
1,00
0,92
0,77
0,67

COOLING CAPACITY

FCX 32
TOTAL COOLING CAPACITY [W]
Wet bulbe air temperature [C]

SENSIBLE COOLING CAPACITY [W]


Dry bulbe air temperature [C]

10

11

12

13

t
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7

15

17

19

21

23

21

23

25

27

29

31

1303
1618
1415
1231
1064
1587
1407
1236
1056
960
1363
1205
1069
939
871
1174
1056
942
841

1042
952
843

942
847

839

1866
2281
2026
1793
1556
2241
2013
1780
1552
1332
1989
1758
1552
1341
1152
1723
1523
1337
1161
1012
1475
1320
1152
1009
911
1264
1131
1014
900

1095
1007
909

992
904

891

2512
2921
2728
2502
2246

2693
2491
2219
1964

2456

3148

3419
3228
3010

3189
2984
2759

3138
2947
2733
2456

2895
2693
2448
2170

2649
2413
2158
1881

2386
2113
1864
1623
2320
2078
1832
1618
1398
2035
1793
1583
1390
1209
1739
1534
1352
1198
1042

3968
3770

3924
3732
3528

3681
3489
3272

3438
3228
2997

3182
2959
2693

3112
2914
2680
2378

2851
2636
2355
2078

2579
2316
2030
1789

2267
1995
1754
1534

1134
1351
1231
1088
997
1347
1230
1103
974
906
1219
1095
987
878
817
1084
990
878
785
727
981
881
764
695
635
875
774
663
622
542
769
661
574
512
448
661
546
483
419
347
552
452
391
321
238

1368
1604
1485
1360
1222
1593
1477
1366
1236
1104
1479
1355
1240
1114
997
1349
1233
1114
990
906
1221
1114
1001
881
817
1089
997
891
785
727
983
891
778
695
635
880
783
667
605
542
774
672
574
512
448

1612
1851
1750
1623
1493
1831
1733
1623
1494
1368
1726
1604
1488
1377
1248
1593
1476
1372
1255
1120
1477
1357
1248
1128
1003
1348
1240
1134
1008
906
1224
1109
1010
895
817
1091
1003
902
788
727
987
898
792
695
635

1817
2055
1973
1881
1753
2029
1954
1867
1755
1630
1928
1849

2004
2253
2176
2090
2001
2220
2153
2076
1989
1895
2120
2054
1973
1884
1759
2022
1950
1868
1755
1636
1921
1848
1752
1632
1261
1819
1743
1624
1513
1389
1716
1615
1503
1392
1274
1587
1491
1379
1274
1159
1472
1359
1260
1158
1033

2184
2438
2371
2292
2210
2409
2340
2272
2193
2106
2313
2246
2174
2090
2004
2212
2149
2072
1989
1896
2115
2046
1970
1882
1771
2013
1948
1864
1755
1638
1914
1844
1749
1634
1524
1813
1737
1622
1517
1405
1709
1610
1503
1394
1291

2210
1956
1705
2403
2193
1938
1710
1490
2162
1912
1688
1472
1275
1872
1653
1447
1271
1104
1600
1420
1258
1102
963
1363
1212
1087
971

1172
1063
971

1750
1630
1501
1827
1744
1625
1501
1382
1722
1616
1492
1386
1263
1591
1491
1376
1266
1145
1474
1359
1254
1148
1015
1349
1242
1141
1021
911
1210
1114
1019
911
817

NB: Values of capacity in bold face refer to nominal value.


Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consider only the values of sensible capacity.
The cooling capacities in the table must be multiplied by the following factors:
MOD.
FCX 32
total capacity
1,00
Maximum speed
sensible capacity
1,00
total capacity
0,86
Medium speed
sensible capacity
0,81
total capacity
0,65
Low speed
sensible capacity
0,58

FCX 34
1,17
1,12
1,02
0,94
0,85
0,76

19

English

Water temp.
Inlet [C]

COOLING CAPACITY

FCX 42
TOTAL COOLING CAPACITY [W]
Wet bulbe air temperature [C]
Water temp.
Inlet [C]

3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7

English

10

11

12

13

SENSIBLE COOLING CAPACITY [W]


Dry bulbe air temperature [C]

15

17

19

21

23

21

23

25

27

29

31

2871
2491
2156
1808
1602
2491
2166
1879
1563
1457
2146
1882
1621
1415
1321
1850
1647
1482
1279

1644
1482
1266

1482
1312

1320

3516
3110
2717
2278
3497
3103
2730
2343
1924
3071
2742
2375
2014
1689
2704
2382
2040
1737
1518
2324
2033
1782
1515
1386
1995
1769
1563
1350

1727
1579
1392

1566
1412

1405

4551
4241
3825
3368

4194
3832
3426
2962

3825

5329
5010
4635

4963
4626
4204

4898
4579
4223
3471

4523
4185
3748
3297

4128
3741
3297
2846

3683
3284
2846
2446
3625
3245
2852
2465
2098
3149
2800
2433
2117
1789
2730
2375
2104
1824
1544

6191
5854

6126
5816
5460

5751
5423
5048

5357
5010
4616

4954
4588
4109

4869
4532
4109
3619

4448
4083
3613
3155

4012
3580
3142
2710

3535
3103
2691
2317

2336
2149
1920
1648
1544
2131
1939
1706
1496
1402
1929
1740
1523
1355
1260
1740
1564
1334
1216
1118
1571
1388
1169
1074
976
1398
1203
1027
932
831
1224
1010
885
788
684
1047
841
744
642
529
863
698
600
491
359

2730
2550
2332
2113
1850
2542
2349
2143
1908
1685
2336
2160
1944
1679
1544
2136
1948
1751
1507
1402
1934
1753
1557
1355
1260
1746
1581
1368
1214
1118
1577
1405
1179
1074
976
1407
1226
1027
932
831
1233
1037
885
788
684

3088
2942
2752
2530
2298
2918
2755
2554
2337
2094
2730
2553
2343
2138
1878
2539
2357
2160
1940
1695
2334
2166
1962
1733
1540
2135
1961
1772
1534
1402
1938
1767
1584
1361
1260
1753
1598
1402
1213
1118
1584
1422
1206
1072
976

3401
3279
3134
2955
2737
3240
3112
2962
2754
2528
3076
2941

3715
3602
3468
3320
3155
3552
3437
3303
3150
2951
3393
3275
3133
2960
2754
3228
3108
2958
2761
2559
3064
2936
2758
2565
2362
2899
2750
2560
2380
2169
2732
2547
2373
2186
1966
2529
2356
2177
1999
1768
2329
2172
2003
1808
1564

3907
3791
3653
3507

3749
3628
3489
3339
3702
3592
3465
3322
3163
3540
3429
3298
3151
2975
3379
3267
3131
2964
2760
3215
3100
2956
2762
2573
3052
2929
2757
2570
2373
2883
2741
2561
2385
2189
2717
2545
2374
2195
2004

3400
2987
2556
3761
3381
3013
2601
2195
3342
2987
2588
2233
1859
2936
2581
2246
1924
1615
2517
2195
1927
1647
1450
2149
1901
1669
1466

1850
1669
1502

2760
2558
2338
2909
2754
2561
2353
2140
2739
2554
2369
2172
1932
2536
2357
2169
1977
1718
2333
2168
1990
1770
1547
2136
1984
1794
1574
1402
1945
1780
1604
1382
1260

NB: Values of capacity in bold face refer to nominal value.


Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consider only the values of sensible capacity.
The cooling capacities in the table must be multiplied by the following factors:
MOD.
FCX 42
total capacity
1,00
Maximum speed
sensible capacity
1,00
total capacity
0,82
Medium speed
sensible capacity
0,77
total capacity
0,68
Low speed
sensible capacity
0,59

20

FCX 44
1,31
1,20
1,11
0,99
0,87
0,75

COOLING CAPACITY

FCX 50
Water temp.
Inlet [C]

10

11

12

13

t
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
6
4
5
6
7

SENSIBLE COOLING CAPACITY [W]


Dry bulbe air temperature [C]

15

17

19

21

23

21

23

25

27

29

31

3542
3227
2912
2588
2246
3170
2885
2605
2307
1983
2833
2579
2329
2062
1721
2535
2325
2075
1817

2299
2097
1861

2075
1874

1852

4260
3892
3516
3130

3848
3498
3139
2789
3778
3454
3130
2806
2474
3376
3078
2789
2496
2189
3008
2745
2491
2229
1940
2675
2456
2237
1992

2412
2224
2010

2193
2001

1970

5468
5083
4663
4234

5031
4628
4225
3813

4575

6406
6011
5565

5960
5539
5083

5486
5039
4593

5390
4996
4558
4137

4908
4505
4094
3700

4435
4032
3665
3279

3962
3603
3253
2912
3831
3507
3192
2885
2579
3398
3113
2833
2561
2299

7451
7043

6979
6546

6495
6037

6406
5986
5503

5909
5468
4987

5398
4926
4479

5267
4847
4418
3997

4733
4339
3927
3551

4243
3848
3489
3139

2624
2461
2284
2064
1755
2448
2290
2096
1848
1537
2278
2105
1892
1618
1355
2090
1900
1675
1367

1884
1690
1448
1147

1678
1476
1210

1469
1255
951

1258
1025

1045
765

2952
2810
2643
2467
2251
2788
2642
2470
2290
2053
2623
2472
2301
2104
1827
2448
2298
2119
1892
1581
2282
2122
1917
1666
1367
2093
1917
1702
1428

1892
1706
1481
1174
v
1687
1493
1251

1481
1275
992

3296
3145
2999
2831
2646
3113
2980
2829
2656
2471
2941
2809
2657
2483
2292
2786
2642
2483
2308
2102
2612
2478
2318
2127
1884
2449
2308
2138
1929
1650
2288
2134
1941
1706
1400
2102
1929
1727
1476

1896
1718
1509
1222

3632
3500
3343
3185
3015
3458
3326
3168
3013
2841
3280
3139

3836
3704
3545
3369
3791
3663
3523
3356
3194
3619
3486
3343
3182
3020
3443
3307
3165
3006
2854
3262
3129
2994
2845
2683
3079
2967
2828
2675
2515
2916
2803
2662
2513
2342
2762
2641
2500
2344
2170
2612
2480
2343
2175
1972

4164
4039
3896
3740

3989
3861
3720
3556

3819
3690
3541
3370
3772
3647
3516
3357
3195
3598
3468
3329
3172
3024
3421
3291
3141
3005
2853
3240
3111
2979
2836
2693
3061
2955
2823
2679
2527
2897
2797
2660
2516
2365

4190
3796
3402

4129
3791
3393
3034
4024
3700
3358
3017
2693
3603
3279
2982
2684
2386
3192
2920
2653
2395
2123
2833
2605
2377
2150

2531
2351
2150

3000
2838
2670
3096
2975
2829
2666
2496
2931
2808
2659
2502
2320
2775
2644
2492
2331
2137
2606
2478
2332
2154
1932
2448
2316
2157
1957
1706
2288
2146
1957
1739
1457

NB: Values of capacity in bold face refer to nominal value.


Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consider only the values of sensible capacity.
The cooling capacities in the table must be multiplied by the following factors:
MOD.
FCX 50
total capacity
1,00
Maximum speed
sensible capacity
1,00
total capacity
0,87
Medium speed
sensible capacity
0,92
total capacity
0,68
Low speed
sensible capacity
0,68

FCX54
1,26
1,18
1,14
1,03
0,86
0,76

21

English

TOTAL COOLING CAPACITY [W]


Wet bulbe air temperature [C]

COOLING CAPACITY

FCX 62
TOTAL COOLING CAPACITY [W]
Wet bulbe air temperature [C]
Water temp.
Inlet [C]

3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7

English

10

11

12

13

SENSIBLE COOLING CAPACITY [W]


Dry bulbe air temperature [C]

15

17

19

21

23

21

23

25

27

29

31

4190
3725
3185
2739
2586
3734
3302
2804
2501
2358
3316
2924
2478
2287

2943
2618
2394
2073

2655
2339
2004

2394
2050

2125

5511
5018
4460
3818
3241
5009
4506
3967
3325
2953
4498
4023
3501
2907
2693
4004
3567
3083
2618
2460
3544
3149
2720
2390

3135
2800
2418
2176

2800
2520
2125

2539
2246

2278

6974
6500
5949
5335
4609
6460
5967
5409
4776
4050
5930
5418

8084
7583
7015
6365

7556
7041
6446
5762

7015
6474
5847
5149
6946
6446
5874
5251
4553
6392
5855
5279
4665
3976
5800
5260
4702
4107
3437
5204
4693
4153
3595
2981
4618
4135
3651
3139
2683
4064
3632
3204
2748
2451

9315
8801
8205

9248
8774
8233
7624

8706
8205
7651
6988

8151
7637
7028
6338

7569
7028
6392
5688

6974
6392
5744
5056
6866
6352
5744
5111
4441
6257
5698
5111
4506
3864
5614
5064
4506
3939
3344

3490
3214
2836
2611
2460
3253
2970
2558
2387
2236
3017
2704
2314
2163
2012
2757
2411
2089
1938
1783
2480
2099
1865
1714
1558
2202
1797
1641
1485
1327
1914
1598
1417
1258
1091
1612
1344
1190
1027
845
1283
1116
959
813
575

3981
3725
3424
3030
2867
3735
3482
3171
2818
2975
3499
3240
2909
2606
2460
3262
3001
2616
2387
2236
3031
2742
2323
2163
2012
2777
2455
2089
1938
1783
2498
2158
1865
1714
1558
2221
1836
1641
1485
1327
1938
1566
1415
1258
1091

4464
4222
3955
3637
3249
4210
3982
3710
3372
3053
3977
3738
3463
3102
2869
3728
3499
3216
2836
2671
3502
3266
2967
2906
2455
3269
3029
2694
2382
2231
3043
2777
2382
2158
2007
2786
2494
2094
1936
1783
2513
2202
1860
1711
1558

4949
4720
4465
4184
3848
4701
4468
4219
3934
3581
4456
4227

5415
5208
4977
4717
4419
5175
4964
4727
4465
4167
4934
4721
4471
4213
3913
4691
4471
4233
2967
3648
4448
4226
3982
3717
3382
4198
3980
3742
3472
3107
3957
3746
3514
3229
2880
3727
3520
3281
2972
2674
3504
3293
3044
2681
2455

5861
5681
5465
5231
4963
5620
5441
5224
4986
4714
5388
5200
4977
4733
4453
5155
4960
4731
4482
4203
4915
4714
4474
4227
3955
4675
4462
3982
3982
3697
4433
4208
3986
3746
3447
4182
3978
3753
3504
3188
3944
3744
3522
3268
2921

4860
4237
3492
5391
4869
4330
3725
3111
4833
4349
3827
3251
2813
4302
3836
3363
2822
2567
3790
3380
2962
2515
2348
3334
2990
2627
2278

2957
2683
2344

3980
3685
3304
4205
3985
3729
3431
3066
3965
3742
3489
3170
2867
3735
3508
3252
2897
2973
3506
3278
3005
2626
2455
3273
3049
2753
2382
2231
3050
2806
2451
2158
2007

NB: Values of capacity in bold face refer to nominal value.


Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consider only the values of sensible capacity.
The cooling capacities in the table must be multiplied by the following factors:
MOD.
FCX 62
total capacity
1,00
Maximum speed
sensible capacity
1,00
total capacity
0,96
Medium speed
sensible capacity
0,83
total capacity
0,81
Low speed
sensible capacity
0,67

22

FCX 64
1,31
1,19
1,14
0,99
0,93
0,79

COOLING CAPACITY

FCX 82
Water temp.
Inlet [C]

10

11

12

13

t
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7

SENSIBLE COOLING CAPACITY [W]


Dry bulbe air temperature [C]

15

17

19

21

23

21

23

25

27

29

31

5591
4979
4320
3553
3291
4979
4427
3815
3217
3008
4427
3930
3392
2927
2725
3949
3526
3210
2645

3566
3156
2585

3210
2773

2847

7373
6701
5975
5167
4225
6688
6014
5315
4549
3782
6002
5369
4710
3984
3432
5342
4763
4159
3473
3143
4724
4219
3687
3096
2861
4192
3762
3291
2780

3755
3392
2894

3405
3015

3049

8676
7952
7131
6243

7965
7212
6405
5517
7925
7218

10810
10144
9381
8503

10106
9401
8597
7696

9361
8638
7803
6902

8611
7830
6997
6136

7803
7024
6230
5382
7723
6997
6270
5503
4697
6916
6230
5530
4831
4077
6136
5503
4871
4239
3539
5402
4831
4293
3728
3156

0
12453
11749
10985

11729
10985
10164

10966
10203
9342

10887
10183
9381
8477

10106
9361
8503
7589

9283
8503
7642
6754

8450
7628
6808
5948

7562
6781
6002
5194
7440
6727
5988
5275
4535

4995
4612
4127
3569
3346
4656
4262
3710
3248
3032
4318
3890
3256
2934
2718
3950
3480
2852
2621
2405
3555
3054
2532
2308
2083
3151
2599
2219
1995
1770
2741
2136
1905
1679
1442
2323
1811
1589
1358
1103
1868
1495
1270
1025
732

5671
5326
4927
4400
3939
5338
4990
4576
3978
3658
4996
4652
4211
3591
3346
4670
4310
3815
3248
3032
4340
3942
3375
2934
2718
3971
3539
2905
2621
2405
3576
3114
2532
2308
2088
3181
2681
2219
1995
1770
2774
2196
1905
1679
1444

6366
6023
5664
5232
4689
6008
5672
5313
4879
4291
5669
5337
4972
4504
3953
5337
5009
4624
4115
3651
5002
4671
4275
3674
3346
4678
4340
3898
3271
3032
4355
3986
3472
2934
2718
3994
3584
3017
2621
2405
3599
3166
2554
2308
2088

7036
6722
6367
5983
5556
6699
6373
6019
5643
5193
6354
6011

7680
7409
7082
6715
6331
7344
7073
6732
6357
5969
7018
6723
6381
6015
5619
6679
6364
6022
5668
5263
6329
6008
5688
5320
4898
5978
5686
5357
4984
4538
5647
5357
5026
4650
4132
5326
5026
4704
4297
3718
4995
4713
4372
3915
3346

8303
8055
7760
7440
7069
7987
7735
7428
7085
6718
7657
7401
7084
6742
6367
7324
7056
6740
6380
6006
6978
6711
6375
6032
5660
6644
6356
6034
5694
5315
6300
6000
5694
5351
4968
5953
5671
5369
5026
4617
5622
5348
5038
4691
4254

7420
5705
4817
7185
6486
5773
5033
4172
6432
5786
5113
4414
3648
5719
5113
4508
3875
3284
5046
4522
3984
3405
2995
4448
4003
3553
2988

3957
3600
3176

5680
5290
4818
5999
5681
5337
4938
4427
5654
5347
4996
4588
4008
5336
5017
4668
4219
3666
4997
4692
4329
3808
3346
4679
4370
3971
3346
3032
4365
4024
3547
2949
2718

NB: Values of capacity in bold face refer to nominal value.


Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consider only the values of sensible capacity.
The cooling capacities in the table must be multiplied by the following factors:
MOD.
FCX 82
total capacity
1,00
Maximum speed
sensible capacity
1,00
total capacity
0,80
Medium speed
sensible capacity
0,85
total capacity
0,68
Low speed
sensible capacity
0,69

FCX 84
1,24
1,06
1,10
1,00
0,91
0,80

23

English

TOTAL COOLING CAPACITY [W]


Wet bulbe air temperature [C]

COOLING CAPACITY

FCX 102
TOTAL COOLING CAPACITY [W]
Wet bulbe air temperature [C]
Water temp.
Inlet [C]

3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7
3
4
5
6
7

English

10

11

12

13

SENSIBLE COOLING CAPACITY [W]


Dry bulbe air temperature [C]

15

17

19

21

23

21

23

25

27

29

31

6495
5846
5153
4403
3609
5802
5196
4576
3869
3263
5153
4612
4057
3379
2953
4569
4122
3609
2903

4114
3703
3162

3710
3278

3299

7808
7043
6221
5326

7029
6293
5514
4648
6956
6278
5586
4865
4028
6206
5571
4937
4273
3508
5485
4937
4381
3783
3119
4850
4388
3912
3306

4331
3956
3480

3927
3537

3523

10067
9291
8428
7519

9249
8457
7591
6697

8413

11788
10970
10025

10928
10067
9120

10046
9149
8226

9962
9120
8255
7360

9063
8226
7389
6524

8139
7360
6552
5730

7274
6524
5773
5023
7101
6423
5745
5081
4388
6264
5644
5052
4475
3862

13656
12816

12795
11914

12711
11893
10970

11809
10928
9962

10865
9941
9005

9878
8976
8053

9753
8890
8024
7129

8760
7937
7101
6264

7822
7029
6249
5485

5223
4880
4441
3828
3308
4881
4521
4063
3330
2985
4537
4151
3608
2912
2670
4158
3726
3139
2582
2348
3748
3293
2626
2264
2033
3330
2846
2176
1945
1706
2905
2370
1857
1621
1379
2472
1820
1536
1298
1037
2025
1447
1213
962
662

5958
5605
5230
4778
4140
5588
5248
4866
4399
3696
5227
4900
4503
3978
3315
4886
4554
4124
3491
2985
4551
4195
3696
2978
2670
4180
3770
3242
2582
2352
3770
3345
2751
2264
2033
3352
2905
2209
1945
1709
2934
2436
1857
1621
1381

6664
6333
5974
5582
5122
6294
5963
5607
5208
4725
5932
5610
5249
4847
4315
5581
5261
4898
4481
3843
5223
4921
4554
4084
3374
4888
4575
4183
3623
2993
4559
4224
3770
3125
2670
4195
3806
3315
2612
2355
3784
3381
2846
2264
2033

7366
7080
6715
6348
5940
7003
6693
6352
5971
5562
6630
6329

7784
7473
7105
6716

7426
7094
6717
6347
7337
7056
6715
6357
5969
6968
6687
6339
5991
5618
6598
6295
5988
5631
5247
6231
5951
5628
5278
4896
5878
5609
5288
4943
4525
5559
5270
4947
4595
4134
5203
4936
4623
4229
3667

8471
8200
7863
7501

8107
7835
7489
7120

7754
7460
7117
6734
7659
7390
7087
6727
6373
7297
7027
6707
6362
5996
6935
6652
6334
5999
5638
6563
6278
5976
5646
5293
6189
5930
5632
5302
4937
5845
5595
5295
4968
4589

7620
6798
5918

7562
6812
6033
5196
7447
6754
6033
5312
4547
6639
5990
5341
4677
3956
5860
5283
4713
4129
3451
5153
4677
4194
3667

4569
4186
3761

5980
5608
5195
6264
5964
5623
5255
4820
5913
5614
5273
4901
4432
5574
5265
4927
4548
4015
5217
4928
4594
4171
3506
4889
4598
4239
3733
3029
4571
4253
3828
3257
2670

NB: Values of capacity in bold face refer to nominal value.


Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consider only the values of sensible capacity.
The cooling capacities in the table must be multiplied by the following factors:
MOD.
FCX 102
total capacity
1,00
Maximum speed
sensible capacity
1,00
total capacity
0,94
Medium speed
sensible capacity
0,90
total capacity
0,82
Low speed
sensible capacity
0,77

24

HEATING POWER YIELD 3-ROW COIL

FCX 17

FCX 22
50

40

30

500
400
300
200
100

1,5

2,5

3,5

30

40

2,5

400
300
200

1,5

20

4,5

5,5

t C (temperature entering water - temperature entering air)

60

1050

70

600

Water flow rate [l/h]

Water flow rate [l/h]

50

40

30

500
400
300
200

50

40

30

70

60

900
750
600
450
300
150

1,5 2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5

20

10 11

Heating capacity [kW]

Heating capacity [kW]

FCX 50

FCX 62

t C (temperature entering water - temperature entering air)

1050

20

50

40

30

60

t C (temperature entering water - temperature entering air)

2100

70

900
750
600
450
300

20

1900
Water flow rate [l/h)

Water flow rate [l/h]

FCX 42

t C (temperature entering water - temperature entering air)

150

3,5

Heating capacity [kW]

FCX 32

100

70

60

500

Heating capacity [kW]

700

50

600

100
0,5

20

700

70

60

Water flow rate [l/h]

Water flow rate [l/h]

20

t C (temperature entering water - temperature entering air)

30

40

50

60

70

1700
1500
1300
1100
900
700

9 10 11 12 13

Heating capacity [kW]

500

12

16

20

Heating capacity [kW]

25

English

t C (temperature entering water - temperature entering air)

600

HEATING POWER YIELD 3-ROW COIL

FCX 82

FCX 102

t C (temperature entering water - temperature entering air)

English

20

30

40

50

60

2200

70

2000

1800

Water flow rate (l/h]

Water flow rate (l/h)

2100

t C (temperature entering water - temperature entering air)

1500
1200
900
600

1800
1600
1400
1200
1000
800

300
4

10 12 14 16 18 20

600

22

Heating capacity [kW]

11 13 15 17 19 21 23 25
Heating capacity [kW]

HEATING CAPACITY CORRECTION FACTORS


The heating capacities are at maximum speed. For the other speeds, the values must be multiplied by the following factors:

MOD.
Medium speed
Low speed

26

FCX17

FCX 22

FCX 32

FCX 42

FCX 50

FCX 62

0,83
0,65

0,79
0,56

0,82
0,68

0,87
0,69

0,87
0,63

0,85
0,64

FCX 82 FCX102
0,88
0,71

0,90
0,74

HEATING POWER YIELD 4-ROW COIL

FCX 24

FCX 34

20

50

40

30

700

70

60

600

Water flow rate [l/h]

Water flow rate [l/h]

700

t C (temperature entering water - temperature entering air)

500
400
300
200
100

400
300
200
0

FCX 54
t C (temperature entering water - temperature entering air)

t C (temperature entering water - temperature entering air)

1050

1000

20

50

40

30

70

60

Water flow rate [l/h]

Water flow rate [l/h]

Heating capacity [kW]

FCX 44

800
600
400

950

20

30

50

40

60

70

12

14

850
750
650
550
450
350
250

200
0

10

12

150

14

FCX 64

10

16

FCX 84

t C (temperature entering water - temperature entering air)


2100
1900

Heating capacity [kW]

Heating capacity [kW]

20

40

30

50

60

t C (temperature entering water - temperature entering air)


2100

70

Water flow rate [l/h]

Water flow rate [l/h]

70

60

500

Heating capacity [kW]

1700
1500
1300
1100
900
700
500
300

50

40

30

600

100

20

20

50

40

30

60

70

1900
1700
1500
1300
1100
900
700
500

10

15

20

25

300

10

15

20

25

30

Heating capacity [kW]

Heating capacity [kW]

HEATING CAPACITY CORRECTION FACTORS


The heating capacities are at maximum speed. For the other speeds, the values must be multiplied by the following factors:

MOD.
Medium speed
Low speed

FCX 24

FCX 34

FCX 44

FCX 54

FCX 64

FCX 84

0,81
0,56

0,83
0,66

0,81
0,60

0,87
0,62

0,80
0,59

0,84
0,65

27

English

t C (temperature entering water - temperature entering air)

1-ROW COIL HEATING CAPACITY (ACCESSORY BV)

FCX 17 (BV 117)


t C (temperature entering water - temperature entering air)

t C (temperature entering water - temperature entering air)

400

400

70

300
250
200
150
100
50

30

20

350
Water flow rate [l/h]

Water flow rate [l/h]

60

50

40

30

20

350

English

FCX 22 (BV122)

300
250
200
150
100

1,2 1,4 1,6 1,8

2,2

0,5

FCX 42 (BV142)
t C (temperature entering water - temperature entering air)

t C (temperature entering water - temperature entering air)

20

30

40

50

60

400

70
Water flow rate [l/h]

350

3,5

2,5

Heating capacity [kW]

FCX 32 (BV132)
400

1,5

Heating capacity [kW]

Water flow rate [l/h]

70

50
0,4 0,6 0,8

300
250
200
150

30

20

350

40

60

50

70

300
250
200
150
100

100

50

50
0,5 1

1,5 2

2,5

3 3,5

4,5 5

0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6


Heating capacity [kW]

Heating capacity [kW]

FCX 50 (BV142)

FCX 62 (BV162)

t C (temperature entering water - temperature entering air)

t C (temperature entering water - temperature entering air)

400

900
800
700

20

350

30

40

60

50

70
Water flow rate [l/h]

Water flow rate [l/h]

60

50

40

300
250
200
150

300
200

50

100

28

1,5

2,5

3,5

4,5

Heating capacity [kW]

5,5

6,5

60

50

70

600
500
400

100
0,5

40

30

20

Heating capacity [kW]

10

1-ROW COIL HEATING CAPACITY (ACCESSORY BV)

FCX 82 (BV162)

FCX 102 (BV162)


60

50

40

30

20

900
800

70

600
500
400
300
200
100

50

40

30

60

70

10 11

700
600
500
400
300
200
100

10 11

20

Heating capacity [kW]

Heating capacity [kW]

HEATING CAPACITY CORRECTION FACTORS


The heating capacities are at maximum speed. For the other speeds, the values must be multiplied by the following factors:

MOD.
Medium speed
Low speed

FCX17

FCX 22

FCX 32

FCX 42

FCX 50

FCX 62

0,89
0,73

0,85
0,64

0,86
0,72

0,88
0,68

0,89
0,74

0,86
0,71

FCX 82 FCX102
0,9
0,76

0,91
0,81

The 3- row coil heating capacity in the fancoil quipped with BV coil accessory ( 3R + 1R lay-out) are detected by the charts /
graphs relating to the 3-row standard coil by applying the here below coefficients.
Total cooling capacity
Sensible cooling capacity
Heating

= 0,99
= 0,98
= 0,99

29

English

900
800
700

t C (temperature entering water - temperature entering air)

Water flow rate [l/h]

Water flow rate [l/h]

t C (temperature entering water - temperature entering air)

DIRECT EXPANSION COIL COOLING CAPACITY


Evaporation temperature:

A = 2,5 C

B = 5 C

C = 7,5 C

D = 10 C

A
B
C
D

2,7

Cooling capacity [kW]

2,2
1,7
1,2
0,7

15

17

19

21

23

1,7

1,5

B
C
D

1,3
1,1
0,9
0,7
21

wet bulb temperature intake air [C]

23

25

27

29

31

wet bulb temperature intake air [C]

A
B
C
D

5
4
3
2
1
15

17

19

21

23

Sensible cooling capacity [kW]

FCX 32
2,5

A
B
C

1,5
1
21

wet bulb temperature intake air [C]

23

25

27

29

31

dry bulb temperature intake air [C]

A
B
C
D

6
5
4
3
2
1
15

17

19

21

23

Sensible cooling capacity [kW]

FCX 42
3,5

A
B
C
D

3
2,5
2
1,5

wet bulb temperature intake air [C]

21

23

25

27

29

31

dry bulb temperature intake air [C]

FCX 50
9

A
B
C
D

7
5
3
1
15

17

19

21

23

wet bulb temperature intake air [C]

30

Sensible cooling capacity [kW]

English

3,2

Sensible cooling capacity [kW]

FCX 22

A
B
C
D

2,5
2
1,5
1
21

23

25

27

29

dry bulb temperature intake air [C]

31

DIRECT EXPANSION COIL COOLING CAPACITY


Evaporation temperature:

A = 2,5 C

B = 5 C

C = 7,5 C

D = 10 C

FCX 62
10
8
6
4
2
15

17

19

21

23

A
B
C
D

5
4
3

English

A
B
C
D

Sensible cooling capacity [kW]

Cooling capacity [kW]

12

2
21

wet bulb temperature intake air [C]

23

25

27

29

31

wet bulb temperature intake air [C]

FCX 82

11
9
7
5
3

15

17

19

21

Sensible cooling capacity [kW]

A
B
C
D

13

23

A
B
C

6
5

4
3
21

wet bulb temperature intake air [C]

23

25

27

29

31

dry bulb temperature intake air [C]

FCX 102
15
12
9
6
3
15

17

19

21

23

A
B
C

Sensible cooling capacity [kW]

A
B
C
D

5
4
3
21

wet bulb temperature intake air [C]

23

25

27

29

31

dry bulb temperature intake air [C]

COOLING CAPACITY CORRECTION FACTORS


The cooling capacity are referred to the maximum speed. For the other speeds, the values must be multiplied by the following factors:

MOD.
Medium speed
Low speed

FCX17
total capacity
sensible capacity
total capacity
sensible capacity

FCX 22

FCX 32
0,84
0,83
0,61
0,58

FCX 42
0,86
0,85
0,7
0,68

FCX 50

0,85
0,84
0,67
0,65

0,9
0,88
0,71
0,68

FCX 62
0,85
0,82
0,67
0,64

FCX 82 FCX102
0,89
0,88
0,74
0,7

0,92
0,91
0,8
0,77

Note: Sensible power values are higher than the total power and they show the cooling is carried out without dehumidification. Only the sensible power values must be kept into consideration.

31

HANGING VERSION AVAILABLE STATIC PRESSURE


IPO series fancoils have been designed to adjust available static pressure provided by the fan to pressure drop in the ducting
system by selecting the appropriate operating speed.
Tables give the available static pressure of machines fitted with
multiple-speed extra-strength motors, according to air flow and

fan speed (L1...L7).


The diagrams also illustrate the available static pressure curves
of models with standard motors (P-PE) operating at maximum
and medium speed.

L1: max. speed PO version


L7: min. speed PO version

max. speed P version


average speed P version

60

Av.Stat.pressure [Pa]

Av.Stat.pressure [Pa]

FCX 32 - 34
L1

45

L2
L3

30

L4

L5
L6

15
L7

140 155 170 185 200 215 230 245 260 275 290

60

L1
L2

45

L3
L4

30
15

L5

L6
L7

0
260 275 290 305 320 335 350 365 380 395 410 425 440 455

Air flow rate [m3/h]

Air flow rate [m3/h]

FCX 42 - 44

FCX 50 - 54
L3
L4

45
L5

30
L6

15
0

Av.Stat.pressure [Pa]

60

60

L1

L2

L7

330 355 380 405 430 455 480 505 530 555 580 605
Air flow rate [m3/h]

FCX 62 - 64
Av.Stat.pressure [Pa]

80
L3

60

L1

L5

40

L2

L4
L6

20

L7

520 560 600 640 680 720 760 800 840 880 920

Air flow rate [m3/h]

FCX 102 (only P)


60
40
20
0
900 940 980 1020 1060 1100 1140 1180 1220 1260 1300

Air flow rate [m3/h]

32

L1

50
L2

40
30

L3

L4

20

L5

10

L6

0
400 430 460 490 520 550 580 610 640 670 700 730
Air flow rate [m3/h]

FCX 82 - 84
Av.Stat.pressure [Pa]

Av.Stat.pressure [Pa]

75

Av.Stat.pressure [Pa]

English

FCX 22 - 24

60
40

L5

L3

L2

L6

20
0

L1

L4

L7

700 740 780 820 860 900 940 980 1020 1060 1100 1140
Air flow rate [m3/h]

3-ROW COIL PRESSURE DROP


FCX 62

50

FCX 32

40

FCX 22
FCX 17

FCX 102

FCX 42
FCX 50
FCX 82

30
20
10
0

200

400

800 1000 1200 1400 1600 1800 2000 2200

600

Water flow rate [l/h]

The pressure drops in the charts above refer to an average water temperature of 10 C. The following table shows the corrections
to apply to the pressure drops with a variation in average water temperature.
Average water temperature
Correction factor

5
1,03

10
1

15
0,96

20
0,91

50
0,78

60
0,75

70
0,72

4-ROW COIL PRESSURE DROP

Coil pressure drop (kPa]

50

FCX 64

40

FCX 44
FCX 54

FCX 34

30

FCX 84

FCX 24

20
10
0

200

400

800 1000 1200 1400 1600 1800 2000 2200

600

Water flow rate [l/h]

The pressure drops in the charts above refer to an average water temperature of 10 C. The following table shows the corrections
to apply to the pressure drops with a variation in average water temperature.
Temperatura media dellacqua
Correction factor

5
1,03

10
1

15
0,96

20
0,91

50
0,78

60
0,75

70
0,72

1-ROW COILPRESSURE DROP (accessory BV)

Coil pressure drop (kPa]

50
40

FCX 62

FCX 22-32
FCX 42-50

30

FCX 17

FCX 82-102

20
10
0
0

100

200

300

400

500

600

700

800

900

Water flow rate [l/h]

The pressure drops in the charts above refer to an average water temperature of 65 C. The following table shows the corrections
to apply to the pressure drops with a variation in average water temperature.
Average water temperature
Correction factor

5
1,4

10
1,36

15
1,31

20
1,24

50
1,06

60
1,02

70
0,98

33

English

Coil pressure drop [kPa]

60

CORRECTION FACTORS IN COOLING OPERATION WITH GLYCOL WATER


Reading Key:
Pressure drops
Water flow
Capacity

IN COOLING

IN HEATING

1,4

1,2

1,1

Correction factor

Correction factor

1,3

1,0

0,9

0,8

10

11

12

13

14

15

16

1,2
1,1
1,0
0,9
0,8

17 C

30

Average temperature of the glycol water

40

50

60

70

80

90 C

Average temperature of the glycol water

1,2

1,4

1,1

1,3

FCorrection factor

Correction factor

GLYCOL WATER AT 20%

1,0
0,9
0,8
0,7
0,6

10

11

12

13

14

15

16

1,2
1,1
1,0
0,9
0,8

17 C

30

Average temperature of the glycol water

40

50

60

70

80

90 C

Average temperature of the glycol water

GLYCOL WATER AT 35%


1,6

1,4

1,5
1,3

1,4
1,3

Correction factor

Correction factor

English

GLYCOL WATER AT 10%

1,2
1,1
1,0
0,9
0,8
0,7
0,6
0,5

10

11

12

13

14

15

16

17

Average temperature of the glycol water

34

18 C

1,2
1,1
1,0
0,9
0,8
30

40

50

60

70

80

Average temperature of the glycol water

90 C

Speed

FCX17

Max
Med.
Min

125
40,4
34,1
26,1

250
45,8
40,2
33,0

Band middle frequency [Hz]


500
1000
2000
43,4
39,7
36,2
36,7
32,6
26,9
29,2
26,1
19,7

4000
28,3
21,1
16,2

8000
14,8
4,0
4,1

Global
dB
49,3
43,0
35,8

dB (A)
45 (E)
38 (E)
31 (E)

FCX22

Max.
Med.
Min.

45,6
39,2
25,8

50,6
44,9
33,0

48,4
41,7
29,1

44,7
37,6
26,2

41,3
31,9
19,9

33,3
25,8
16,2

19,7
7,5
2,6

54,2
47,9
35,7

50 (E)
43 (E)
31 (E)

FCX32

Max.
Med.
Min.

43,6
37,0
28,9

48,8
43,0
36,1

46,4
39,7
32,2

42,7
35,7
29,0

39,0
29,9
22,9

31,3
24,0
19,2

17,7
5,4
3,1

52,3
45,9
38,8

48 (E)
41 (E)
34 (E)

FCX42

Max.
Med.
Min.

46,6
39,6
31,9

51,8
44,8
39,1

49,4
42,4
35,2

45,7
38,7
32,0

42,0
35,0
25,9

34,3
27,3
22,2

20,7
13,7
6,1

55,3
48,3
41,8

51 (E)
44 (E)
37 (E)

FCX50

Max.
Med.
Min.

51,6
46,6
37,6

56,8
51,8
42,8

54,4
49,4
40,4

50,7
45,7
36,7

47,0
42,0
33,0

39,3
34,3
25,3

25,7
20,7
11,7

60,3
55,3
46,3

56 (E)
51 (E)
42 (E)

FCX62

Max.
Med.
Min.

52,6
46,4
37,7

57,5
51,8
42,6

55,4
49,6
40,4

51,7
45,7
36,8

48,3
41,9
33,0

40,3
34,3
25,3

26,7
20,8
11,7

61,2
55,3
46,3

57 (E)
51 (E)
42 (E)

FCX82

Max.
Med.
Min.

57,6
52,4
45,6

62,8
57,8
51,0

60,5
55,5
48,4

56,7
51,7
44,6

53,2
48,2
41,1

45,0
40,1
33,2

31,8
26,7
19,8

66,3
61,3
54,4

62 (E)
57 (E)
50 (E)

FCX102

Max.
Med.
Min.

61,5
56,6
51,7

66,7
61,8
56,8

64,4
59,4
54,4

60,7
55,7
50,7

57,1
52,0
46,9

49,3
44,3
39,3

35,8
30,7
25,7

70,3
65,3
60,3

66 (E)
61 (E)
56 (E)

Mod.

(E) =

EUROVENT certified performance.

SOUND PRESSURE LEVEL RATED IN DB (A)


Speed
Max
Med.
Min

Mod. FCX

17
36,5
29,5
22,5

22
41,5
34,5
22,5

32
39,5
32,5
25,5

42
42,5
35,5
28,5

50
47,5
42,5
33,5

62
48,5
42,5
33,5

82
53,5
48,5
41,5

102
57,5
52,5
47,5

Sound pressure level (weighted A) measured in a room with 85 m3 volume , reverberation time t= 0,5 s , direction.factor Q= 2 ,
distance r= 2,5m .

35

English

SOUND POWER LEVEL RATED IN dB (A)

SOUND POWER LEVEL RATED IN DB (A)


Speed

FCX24

Max.
Med.
Min.

125
46,5
42,0
29,8

250
51,6
47,9
37,2

Band middle frequency [Hz]


500
1000
2000
49,3
45,7
42,3
44,8
40,6
34,8
33,1
30,0
23,8

4000
34,3
28,8
20,2

8000
20,8
10,5
5,1

Global
dB
54,2
47,9
35,7

dB (A)
51
46
35

FCX34

Max.
Med.
Min.

43,7
37,2
30,8

48,8
42,5
38,0

46,5
40,0
34,2

42,7
35,7
31,1

39,1
29,9
24,9

31,3
24,2
21,2

17,6
6,1
5,7

52,3
45,9
38,8

48
41
36

FCX44

Max.
Med.
Min.

50,4
45,9
36,2

55,8
50,6
42,5

53,7
48,4
39,4

49,3
44,6
36,2

46,0
41,3
29,8

38,5
33,3
26,2

24,7
20,0
9,9

55,3
48,3
41,8

55
50
41

FCX54

Max.
Med.
Min.

51,8
48,5
40,0

56,8
53,8
44,8

54,2
51,2
42,3

50,7
47,7
38,7

47,3
44,3
35,2

39,2
36,4
27,3

25,5
22,8
13,9

60,3
55,3
46,3

56
53
44

FCX64

Max.
Med.
Min.

52,3
46,5
39,6

57,6
52,0
44,5

55,4
49,6
42,4

51,7
45,7
39,1

48,3
41,7
34,8

41,1
34,3
27,9

26,5
20,6
13,7

61,2
55,3
46,3

57
51
44

FCX84

Max.
Med.
Min.

56,8
52,5
46,7

61,8
57,7
52,3

59,4
55,5
49,6

55,7
51,7
45,2

52,0
48,2
42,1

44,3
40,3
34,5

30,9
26,6
21,2

66,3
61,3
54,4

61
57
51

English

Mod.

SOUND PRESSURE LEVEL RATED IN dB (A)


Velocit
Max.
Med.
Min.

Mod. FCX

24
42,5
37,5
26,5

34
39,5
32,5
27,5

44
46,5
41,5
32,5

54
47,5
44,5
35,5

64
48,5
42,5
35,5

84
52,5
48,5
42,5

Sound pressure level (weighted A) measured in a room with 85 m3 volume , reverberation time t= 0,5 s , direction.factor Q= 2 ,
distance r= 2,5m .

36

FCX-PO SOUND POWER LEVELS OF DUCTED HANGING VERSIONS in dB


The sound power level generated by ducted fancoils (FCX -PO)
depends on fan speed and on the point of operation reached
according to pressure drop.

The following diagrams can be used to obtain the sound power


level (weighted A), expressed in dB (A) in relation to the relevant curve, according to air flow and available static pressure
values.

The overall sound power level expressed in dB(A) are given for each curve.

FCX 32
52

54

90

58

56

50

75

48

60

46

45

44
42

30

40

15

38

0
140 155 170 185 200 215 230 245 260 275 290

Available static pressure [Pa]

Available static pressure [Pa]

90

48

46

60

44

45

42

30

40

15

38

0
260 275 290 305 320 335 350 365 380 395 410 425 440 455

Air flow rate [m3/h]

FCX 42
56

90

58

54

120
105

Available static pressure [Pa]

Available static pressure [Pa ]

Air flow rate [m3/h]

FCX 50

135

52

90
75

50

60

48

45

46

30

44

15

42

75

59

50

60
48

45
46

30
44

15
0

330 355 380 405 430 455 480 505 530 555 580 605

400 430 460 490 520 550 580 610 640 670 700 730

Air flow rate [m3/h]

FCX 82

140
120
100

54

56

58

60

62

64

52
50

80
60

48

40

46

20

44

0
520 560 600 640 680 720 760 800 840 880 920
Air flow rate [m3/h]

120

Available static pressure [Pa]

FCX 62

58

56

54

52

Air flow rate [m3/h]

Available static pressure [Pa]

54

52

50

75

English

FCX 22

100

60

62

64

58

80
60

56

40

54

20

52

0
700 740 780 820 860 900 940 980 1020 1060 1100 1140

Air flow rate [m3/h]

37

English

ACCESSORIES
AMP BRACKETS FOR HANGING UNITS
Kit includes brackets and bolts for ceiling
installation..
BC AUXILIARY CONDENSATE DRIP
TRAY
Made of thermoplastic material, collects
the condensate forming in summer
operation in the region of the noninsulated hydraulic connections and
conveys it to the outside. In particular,
the BC4 drip tray must be used on all the
sizes with vertical installation of the unit.
Attention: The valve VCF and the
driptray BC4 can be installed at the
same time on the fan coil.
Attention: BC8 and BC9 are not
applicable to fan coils with cabinet case
The BC5 drip tray must be installed on
sizes FCX 17, 22, 32, 42, 50 and 24, 34,
44, 54 with horizontal installation.
The BC6 drip tray must be installed
on sizes 62, 82, 102 e 64, 84 with
horizontal installation.
The BC8 drip tray must be installed on
sizes FCX 17, 22, 32, 42, 50 and 24, 34,
44, 54 in version P - PE - PO - POE with
horizontal installation.
The BC9 drip tray must be installed on
sizesFCX 62, 82, 102 and 64, 84 in
version P - PE - PO - POE with horizontal
installation.
BV WATER HEATING COIL
The single-row heating coil can be
installed in four-tube fancoils above the
standard coil.Coil operation is regulated
by a control panel, that actuates a twin
valve
CHF VENTILCASSAFORMA
A galvanised template that makes it
possible to space to the house fan coils
in the wall (FCX P). The template will
make masonary work easy during the
construction of a niche where the fan
coils will be intalled. When work is
finished the fan coil will be completely
hidden from view.
DSC
C O N D E N S AT E D R A I NAG E
DEVICE
A pump drains condensate from the
unit when natural runoff is not possible.
Installed on the exterior of the unit
GA INTAKE LOUVRE
Fixed slat sheet metal louvre with stoved
polyurethane powder paint finish. The
sub-frame is supplied as standard
GAF INTAKE LOUVRE WITH FRAME
AND FILTER
Fixed slat louvre with stoved
polyurethane powder paint finish; rear
side features frame for the filter. The subframe and filter are supplied as standard.
GM DELIVERY LOUVRE
Louvre with high-resistance enamel
finish; comes with adjustable heatmoulded plastic slats for air diffusion.
The subframe is supplied as standard.
MA HIGH COVER CABINET
Consisting of the cover cabinet, fixed
louver and air filter for fan coil in
vertical, floor-standing version. The
FCX for ceiling installation with the MA
cabinet assume the characteristics of the

38

FCX-AS and can only be fitted with the


accessories reserved for this model. BC8
and BC9 are not applicable to fan coils
with cabinet case.
MU UNIVERSAL COVER CABINET
Consisting of the cover cabinet, tiltable
(in sizes 17, 22, 32, 42 and 50) or
fixed louver (in sizes 62, 82 and 102)
and air filter for universal version fan
coil (FCX - U). The FCX for ceiling
installation with the MU cabinet assume
the characteristics of the FCX-US and
can only be fitted with the accessories
reserved for this model. BC8 and BC9
are not applicable to fan coils with
cabinet case..
PA INTAKE PLENUM
In galvanized steel, complete with
connections for circular section ducts of
diameter 200 mm.
There are two assembly positions for the
plenum, for intake parallel to the fan coil
or intake at 90.
PA FRONT INTAKE PLENUM
In galvanized steel, complete with
connections for circular section ducts of
diameter 200 mm. The plenum can be
used with a front intake coupling parallel
to the fan coil delivery or, in sizes PA 32
- 42 - 62 F, also with lateral intake.
PC REAR COVER PANEL
Conveniently covers exposed rear fancoil
sections.
The panel is required by current safety
standards for units installed away from
the room wall.
PCR CONTROL PANEL COVER
Galvanised sheet metal cover designed
to protect unit controls and electrical
terminals of ducted installations with
electrical resistance.
PM DELIVERY PLENUM
Galvanised sheet metal plenum,
externally insulated, complete with
plastic delivery unions for circular
section ducting.
RD STRAIGHT CONNECTION FOR
AIR DELIVERY
Galvanised sheet metal used to convey
air in case of installation of vertical or
horizontal recessed fan coil.
RDA STRAIGHT CONNECTION FOR
AIR INTAKE
Galvanised sheet metal used to convey
intake air in case of installation of
vertical or horizontal recessed fan coil.
RP CONNECTION AT 90 FOR AIR
DELIVERY
Galvanised sheet metal used to convey
air in case of installation of vertical or
horizontal recessed fan coil.
RPA CONNECTION AT 90 FOR AIR
INTAKE
Galvanised sheet metal used to convey
intake air in case of installation of
vertical or horizontal recessed fan coil.
RX ELECTRIC RESISTANCE
Armoured electric resistance, complete
with safet thermostat. It is available as an
accessory for all versions.

SE FRESH AIR DAMPER


Foreseen for versions A, AS, ACB, ACT,
APC, P, PPC, PO and PE with skirting
and allows the changing of air in the
room. It is mounted at the base of the fan
coil, between the skirting. The manual
control is loacted on the right skirting.
SIT 3
Each fan coil has a SIT3 card that
becomes Slave and can be controlled
by a central control panel with
electromechanic selector or with SIT5.
Up to 10 fan coils can be applied with
SIT 3 and one central control unit. The
electronic control panels and those
equipped with valve controls must be
interfaced with a SIT 5. The electronic
control panels with speed control only
can be connected directlt to the SIT 3
without interface SIT 5.
SIT 5
The SIT 5 accessory, interface master
card Master, is connected to electronic
control panels or electromechanic
control panels with valave controls
and /or electric resistances. The SIT 5
interface card connected (up to 10) are
all equipped with interface Slave SIT3.
SW3 MINIMUM WATER TEMPERATURE
PROBE
The SW3 accessory is a probe for
detecting the water temperature of the
heating coil to prevent functioning when
the temperature is less than 39C. The
SW3 probes are powered by a 230V
single phase voltage. The probes are
equipped with cables 2500mm long.
VCF 3 WAY VALVE KIT
The SW3 probe must be combined to
this accessory.
Kit complete with copper
connections and 3 way valves all
or nothing type, to be powered by a
230 V ~ 50Hz voltage supply.
They are available for fan coils :
- with 3 row coil 4 (VCF41, VCF42,
VCF43),
- with 4 row coil(VCF42, VCF43),
- with 1 row additional coil (BV) (VCF44,
VCF45).
* Attention: The VCF valve and the drip
tray BC4 can be installed at the same
time as the fan coil.
ZX5 - ZX6 SKIRTING FOR HIGH
CABINET
In plastic, mounted at the base of the
cabinet when the appliance is placed on
the floor.
ZX7 - ZX8 SKIRTING FOR WALL
VERSION
In galvanised steel, mounted at the base
of the cabinet when the appliance is
placed on the floor and recessed into the
wall.

CONTROL PANEL
F M T 1 0 C O N T R O L PA N E L W I T H
ELECTRONIC THERMOSTAT FOR WALL
RECESSING
Electronic thermostat for fan coils installed on plants with 4 pipes, 2 pipes and 2
pipes with resistance, with the possibility of connecting 2 On - Off valves for
the interception of coil feeding water.
Simplified controls with only 2 selector switches for temperature control and
fan control (3 speed). External air probe
(cable length 6 metres, supplied with
the probe-holder) to be positioned inside
the fan coil. Recess installation (module
503).
For further information refer to the accessory instructions.
F M T 2 0 C O N T R O L PA N E L W I T H
ELECTRONIC THERMOSTAT AND LCD
FOR WALL RECESSING
Electronic thermostat with LCD for fan
coils installed on plants with 4 pipes, 2
pipes and 2 pipes with resistance with
the possibility of connecting 2 On - Off
valves for the interception of coil feeding water. Air temperature probe inside
panel.
Recess installation (module 503).
KTL M REMOTE CONTROL KIT WITH
THERMOSTAT
Kit with adjustment thermostat made up
from an I.R. remote control, an I.R receiver, a circuit board with air temperature
probe, the connection cable, brackets
and fixing equipment. KTLM can be
applied to a fan coil installed in a plant
with 2 pipes with or without water valve
or with 4 pipes with water valve. For fan
coils with cabinet in the FCX series.
For further information refer to the accessory instructions.
KTL P REMOTE CONTROL KIT WITH
THERMOSTAT
Kit with adjustment thermostat made up
from an I.R. remote control, an I.R receiver, a circuit board with air temperature
probe, the connection cable, brackets
and fixing equipment. can be applied
to a fan coil installed in a plant with 2
pipes with or without water valve or with
4 pipes with water valve. For fan coils
with cabinet in the FCX series.
For further information refer to the accessory instructions.
P C T 2 C O N T R O L PA N E L W I T H
THERMOSTAT
Control panel with electro-mechanical
thermostat for plants with 2 pipes with
ventilation thermostating.
PTI MULTI-FUNCTION CONTROL
PANEL WITH THERMOSTAT
Electronic control panel for plants with
two pipes, with electronic multi-function
thermostat; it has the same functions as
the electronic multi-function thermostat
installed in the ACT version. Installation
on board and on wall.
For further information refer to the accessory instructions.

PX2 CONTROL PANEL WITH SWITCHOVER


Control panel for the manual control of
fan speed, made up of an on/off switchover with 3 positions for the selection of
fan speed. Installation on board and on
wall.
For further information refer to the accessory instructions.
P X A E C O N T R O L PA N E L W I T H
E L E C T R O N I C M U LT I - F U N C T I O N
THERMOSTAT
Eltronic multi-function room thermostat in plants with two or four pipes.
Simplified controls with only two selector switched for control of the temperature and ventilation, 3 speed + automatic
speed, on-off and automatic summer/
winter switch-over, depending on the
temperature of the water. The SW minimum water temperature probe is available as an accessory, which prevents
functioning in central heating mode with
water temperature below 35C. Wall
installation.
For further information refer to the accessory instructions.
P X A I C O N T R O L PA N E L W I T H
E L E C T R O N I C M U LT I - F U N C T I O N
THERMOSTAT
Electronic multi-function room thermostat for fan coils in plants with two or
four pipes. Simplified controls with only
two selector switched for control of the
temperature and ventilation, 3 speed +
automatic speed, on-off and automatic summer/winter switch-over, depending on the temperature of the water.
Complete with minimum water temperature probe, which prevents functioning
in central heating mode with water temperature below 35C.
Installation on board.
For further information refer to the accessory instructions.
P X A R C O N T R O L PA N E L W I T H
E L E C T R O N I C M U LT I - F U N C T I O N
THERMOSTAT
Electronic multi-function room thermostat for fan coils in plants with two pipes
and electric resistance. Simplified controls with only two selector switched for
control of the temperature and ventilation, 3 speed + automatic speed, on-off,
activation of the electric resistance when
desired and automatic summer/winter
switch-over, depending on the temperature of the water. Complete with minimum water temperature probe, which
prevents functioning in central heating
mode with water temperature below
35C. By means of appropriate configuration of the board dip-it can also be
used in plants without electric resistance,
with two or four pipes. For installation
on the machine or wall installation.
For further information refer to the accessory instructions.
PXBI ELECTRONIC CONTROL PANEL
Control panel with electronic room thermostat with simplified functions. It has
the same functions as the Thermostat
installed on the ACB version. The room

temperature probe is positioned inside


the thermostat.
The thermostat cannot be coupled with
a water temperature probe. Installation
on board.
For further information refer to the accessory instructions.
PXLM MULTIFUNCTION CONTROL
PANEL
Kit for motorization of the fins and control with a control panel. Consists of a
control panel with electronic thermostat,
a motor to be fitted to the delivery fins, a
feed card and probes for detecting water
and air temperature.
The PXLM controls the operation of a
fan coil inserted in a two-pipe hydraulic
plant.
The control parameters of the electronic
panel may be programmed even after
installation, simply be pressing the two
buttons.
Ideally the panel is for wall installation,
but can also be fitted on board the unit
provided that the ambient probe used
is external to the fan coil (excluding
that inside the panel) and that suitable
corrections are made to the probe calibration. For further information, see the
instructions coming with the accessory.
WMT05 CONTROL PANEL WITH
THERMOSTAT
Electronic thermostat for fan coils installed in plants with 2 pipes. The panel is
protected electrically by an internal fuse.
Wall installation. For further information
refer to the accessory instructions.
WMT10 CONTROL PANEL WITH
THERMOSTAT
Electro-mechanical thermostat for fan
coils installed in plants with 4 pipes, 2
pipes and 2 pipes with resistance, with
the possibility to connect two On - Off
valves for the interception of coil feeding
water.
The panel is protected electrically by an
internal fuse. Continuous or thermostated ventilation. Wall installation.

39

English

ACCESSORIES

ACCESSORIES
Consult the table of compatibility for the selection.

Accessory

Fan Coil FCX


Size
17

English

AMP
4
5
BC 6
8 (*)
9 (*)
117 (**)
122 (**)
BV 132 (**)
142 (**)
162 (**)
17
22
CHF 32
42
62
DSC 4
17
22
GA 32
42
62
17
22
GAF 32
42
62
17
22
GM 32
42
62
17 (*)
22 (*)
MA 32 (*)
42 (*)
62 (*)
17 (*)
22 (*)
MU 32 (*)
42 (*)
62 (*)
17
22
PA 32
42
62
17
22
PA F 32
42
62
17
18
22
23
PC 32
33
42
43
62
PCR 1
2
17
22
PM 32
42
62

40

22 - 24

32 - 34

42 - 44

Version

50 - 54

62 - 64

82 - 84

102

P-PPC-PO-PE-U-UE
all
P-PPC-PO-PE-U-UE
P-PPC-PO-PE-U-UE
P-PPC-PO-PE
P-PPC-PO-PE
A-AS-ACT-ACB-P-U
A-AS-ACT-ACB-P-PO-U
A-AS-ACT-ACB-P-PO-U
A-AS-ACT-ACB-P-PO-U
A-AS-ACT-ACB-P-PO-U
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
all
P-PPC-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
A-AS-ACT-ACB-APC
U
A-AS-ACT-ACB-APC
U-UE
A-AS-ACT-ACB-APC
U-UE
A-AS-ACT-ACB-APC
U-UE
A-AS-ACT-ACB-APC-U-UE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE

ACCESSORIES
Accessory

FCX Fan coil


Size

17
22
RD 32
42
62
17
22
RDA 32
42
62
17
22
RP 32
42
62
17
22
RPA 32
42
62
17 (**)
22 (**)
32 (**)
RX 42 (**)
52 (**)
62 (**)
15X (***)
20X (***)
SE 30X (***)
40X (***)
80X (***)
SIT3
SIT5
SW3
41 (****)
42 (****)
VCF 43 (****)
44 (****)
45 (****)
5
ZX 6
7
8

22 - 24

32 - 34

42 - 44

Version

50 - 54

The 4-row models are only available in the P and PO versions


(*) BC8 and BC9 are not applicable to fan coils with cover cabinets.(**)
For the 4-row model, accessories RX and BV are not available..
(***) SE accessories are matched with ZX feet

COMBINATION OF PANELS/ FAN COILS


Mod.
IN OUT
FCX - AS
FMT10
FMT20
KTLM
KTLP
PCT2
PTI
PX2
PXAE
PXAI
PXAR
PXBI
PXLM
WMT05
WMT10

IN = control panel installed on machine

62 - 64

82 - 84

VCF42 (FCX 24-34-44-54) e VCF43 (FCX 64-84).

FCX 62-102 U

P-PPC-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
P-PPC-PO-PE
A-AS-P-PPC-U
A-AS-P-PO-PE-U-UE
A-AS-P-PO-PE-U-UE
A-AS-P-PO-PE-U-UE
A-AS-P-PO-PE-U-UE
A-AS-P-PO-PE-U-UE
A-AS-ACT-ACB-P
A-AS-ACT-ACB-P-PO-PE
A-AS-ACT-ACB-P-PO-PE
A-AS-ACT-ACB-P-PO-PE
A-AS-ACT-ACB-P-PO-PE
AS-P-PO-U
AS-P-PO-U
AS-P-PO-U
A-AS-ACT-ACB-P-PPC-PO-U
A-AS-ACT-ACB-P-PPC-PO-U
A-AS-ACT-ACB-P-PPC-PO-U
A-AS-P-PPC-PO-U
A-AS-P-PPC-PO-U
A-AS-ACT-ACB
A-AS-ACT-ACB
P-PPC-PO-PE
P-PPC-PO-PE

(****) The 4-row models may only be used in combination with valves

FCX 17-50 U

102

FCX - P

FCX - PO

OUT = wall-mounted control panel

41

English

17

ACCESSORIES

English

AMP SUPPORTS FOR WALL/CEILING MOUNTING VERSION

BC4 DRIP TRAY

BC5-6 DRIP TRAY

VCF valve and BC4


drip tray can not be
contemporary installed on the same fan
coil.

DIMENSIONS [mm]
Mod.
FCX 2250
A [mm]
109

FCX 6282
126

DIMENSIONS [mm]
Mod.
BC 5
A [mm]
375
B [mm]
69

BC 6
476
72

BC8-9 DRIP TRAY FOR HORIZONTALLY INSTALLATION

DIMENSIONS [mm]
Mod.
BC 8
A [mm]
420
B [mm]
146
C [mm]
25
B

42

BC 9
524
146
25

ACCESSORIES
BV 1-ROW HEATING COIL
FCX 62 102

OUT

OUT
OUT

OUT

96

96
IN

IN

155

IN

156

194

170

153

167 mm

378

194

323

e 1

519

408

e 17,5

IN

88

108

49

65 mm
For FCX - U versions do not consider the foot - For all model the hydraulic attack are the following: 1/2 (female)

CHF VENTILCASSAFORMA

DSC CONDENSATE DISCHARGE DEVICE

FC

X
DS

C4

DS

C4

FC

43

English

FCX 17 50

ACCESSORIES
GA AIR SUCTION GRILL

English

GAF AIR SUCTION GRILL

DIMENSIONS [mm]
Mod.
A
B
C
D
E
GA 17
396 214 440 258 390
GA 22
506 214 550 258 500
GA 32
737 214 781 258 731
GA 42
957 214 1001 258 951
GA 62
1078 244 1122 288 1072

F
208
208
208
208
238

DIMENSIONS [mm]
Mod.
A
B
GAF 17
451 270
GAF 22
561 270
GAF 32
792 270
GAF 42 1012 270
GAF 62 1133 300

C
495
605
836
1056
1177

D
E
F
G
314 444 262 390
314 554 262 500
314 785 262 731
314 1005 262 951
344 1126 292 1072

H
208
208
208
208
238

GM AIR DELIVERY GRILL

DIMENSIONS [mm]
Mod.
GM 17
GM 22
GM 32
GM 42
GM 62

60

6
48

A
347
457
688
908
1029

B
C
134 392
134 502
134 733
134 953
134 1074

PCR RESISTANCE COVER PANEL


B

44

DIMENSIONS [mm]
Mod.
PCR 1
A [mm]
340
B [mm]
170
C [mm]
93

PC42
445
170
93

D
E
178 342
178 452
178 683
178 903
178 1024

F
128
128
128
128
128

ACCESSORIES
MA HIGH COVER CABINET
B

22

MA 17

MA 22

MA 32

MA 42

MA 62

A [mm]

458

458

458

458

563

B [mm]

640

750

980

1200

1320

English

Mod.

BC8 and BC9 are not compatible with MA accessories

MU UNIVERSAL COVER CABINET

MU 17 - 22 - 32 - 42 - 50
Mod.

MU 62 - 82 - 102

MU 17

MU 22

MU 32

MU 42

MU 62

A [mm]

520

520

520

520

590

B [mm]

640

750

980

1200

1320

BC8 and BC9 are not compatible with MU accessories

PC REAR CLOSING PANEL

DIMENSIONS [mm]
Mod. PC 22
PC 32
A [mm] 740
971
B [mm] 437
437

PC42
1191
437

PC62
1312
542

45

ACCESSORIES

215

PA INTAKE PLENUM

200

English

216

Mod.
A [mm]
No. of intake blocks

PA 17
390
1

PA 22
500
2

PA 32
731
2

PA 42
951
3

PA 62
1072
4

PA-F FRONT INTAKE PLENUM

245
L

216

A
8

200

A
Mod.
L [mm]
No. of intake blocks

PA 17 F
658
1 (A)

200

40

14

PA 22 F
768
1 (A)

40 1
4

216

216

245

216

PA 32 F
1039
2 (A+B*)

PA 42 F
1259
2 (A+B*)

PA 62 F
1381
2 (A+B)

B* = Closed intake mouth, to use it, remove the cut-out panel,in the plenum PA 42F used in combination with FCX
50/54 P - PO, the cut-out panel must be removed and the two intake mouths used.

46

ACCESSORIES
PM DELIVERY PLENUM
C
B

200
180
150

DIMENSIONS [mm]
PM

Mod.
PM 22
A [mm]
522
B [mm]
250
C [mm]
136
No. delivery outlet blocks 2

42

PM 42
973
320
166
3

PM 62
1094
270
142
4

English

140

PM 32
753
370
191
2

210

RDA STRAIGHT INTAKE CONNECTION

RPA 90 INTAKE CONNECTION

C
C

DIMENSIONS [mm]
Mod.
A
RDA 17
345
RDA 22
455
RDA 32
686
RDA 42
906
RDA 62
1027

B
180
180
180
180
180

C
60
60
60
60
60

DIMENSIONS [mm]
Mod.
A
RPA 17
345
RPA 22
455
RPA 32
686
RPA 42
906
RPA 62
1027

D
389
499
730
950
1071

RD STRAIGHT DELIVERED CONNECTION

B
150
150
150
150
150

C
389
499
730
950
1071

D
132
132
132
132
132

E
226
226
226
226
226

RP 90 DELIVERED CONNECTION

B
A

B
C

DIMENSIONS [mm]
Mod.
A
RD 17
345
RD 22
455
RD 32
686
RD 42
906
RD 62
1027

B
132
132
132
132
132

C
60
60
60
60
60

D
412
522
753
973
1094

E
149
149
149
149
149

DIMENSIONS [mm]
Mod.
A
RP 17
345
RP 22
455
RP 32
686
RP 42
906
RP 62
1027

B
156
156
156
156
156

C
412
522
753
973
1094

D
132
132
132
132
132

E
161
161
161
161
161

47

ACCESSORIES
SW3 MINIMUM WATER TEMPERATURE PROBE

English

RX ELECTRIC HEATER

2500 mm

Resistance heating power [W]


RX 17
700

RX 22
950

RX 32
1300

RX 42
1650

RX 50
1950

RX 62
2200

Current absorbed by the electric resistance[A]


RX 17
3,04

RX 22
4,13

RX 32
5,65

RX 42
7,17

RX 50
8,48

RX 62
9,57

SE FRESH AIR LOUVER

B
90

15

DIMENSIONS [mm]
Mod.

SE 15 X

SE 20 X

SE 30 X

SE 40 X

SE 80 X

436

546

777

997

1118

65

65

65

65

85

HANDLED FRESH AIR


Mod.
max
Air flow
med
min.

48

[m3/h]
[m3/h]
[m3/h]

FCX 17
40
35
30

FCX 22
60
50
40

FCX 32
80
70
50

FCX 42
100
80
65

FCX 50
140
115
90

FCX 62
180
160
120

FCX 82 FCX 102


220
250
190
210
150
170

ACCESSORIES
SIT3 - SIT5 INTERFACE CARDS
52

65

15

V1 V2 V3
OUTPUT

DIN

English

90

SIT 3
SIT 5

INPUT
V3 V2 V1 N N
PH L

SIT
3

SIT
3

Fan coil 1

Fan coil 1

SIT
5

SIT
3
Fan coil 2

SIT
3
Fan coil 3

SIT
3
Fan coil 2

SIT
3
Fan coil 3

SIT
3

SIT
3

Fan coil 4-10

Fan coil 4-10

Fan coils

49

TECHNICAL SPECIFICATIONS:
Power supply:
Start-up input power:
Operation input power:
Water temperature range:
Liquids
Operation time:
Maximum differential pressure:
Maximum work pressure applied to fan coil:
Environmental working condition
temperature:
relative humidity:
without condensation
Storaging environmental condition
temperature:
relative humidity:
without condensation
Actuator water protection degree:

230V (10%) ~ 50Hz


46VA
2,5W
4C 80C
acqua (con glicole 50%)
2 min 4min
30kPa
800kPa
0C 40C
10% 90%
-18C 60C
10% 90%

Flow direction

IP44 acc.to EN 60529

Actuator electrical protection degree:


Classe II
Flow direction in the valve (see fig.)
with fed valve
with not fed valve

A - AB
B - AB

Valve attack [mm]


Mod.
A - AB - B

VCF 41
3/4

VCF 42
3/4

VCF 43
3/4

VCF 44
1/2

VCF 45
1/2

Pressure drop
Mod.
Kvs AB-A
Kvs AB-B (by-pass)

VCF 41
2,5
1,6

VCF 42
2,5
1,6

VCF 43
2,5
1,6

VCF 44
1,7
1,2

VCF 45
1,7
1,2

Dp =

( (
10 q
Kvs

AB

OUT
IN

p [kPa] = Pressure drop


3
q [m /h] = Water flow rate

FAN COIL

VCF41
VCF42
for
FCX, FCS, FHX
VCF44
for
BV

VCF 44 (1/2)

VCF 41 (3/4)
VCF 42 (3/4)

31

3/4

166

1/2

FAN COIL

100
46

54

38

37
102

40

VCF43
for
FCX, FCS, FHX
VCF45
for
BV

VCF 45 (1/2)

VCF 43 (3/4)

3/4

179

1/2

155

English

ACCESSORIES

VCF valve and BC4 drip tray can not be contemporary installed
on the same fan coil.

50

46

58

38

37
109

40

ACCESSORIES

167 mm

ZX 5-6 BASE SUPPORTS FOR HIGH CABINET

65 mm

[mm]
ZX 5
ZX 6

English

49

B
88
108

C
105
125

ZX 7-8 BASE SUPPORTS FOR HANGING VERSION

B
A
[mm]
ZX 7
ZX 8

A
20
20

B
88
108

C
199
199

51

ACCESSORIES
CONTROL PANELS WITH THERMOSTAT
PXAR

PXAE

English

PCT2

FMT20

FMT10
20 2

10

WARMER

COOLER
START/
STOP

WMT05

WMT10

CONTROL PANEL WITH SPEED SELECTOR SWITCH


PX2

52

ON OFF

C
30

15

WARNING: check that the power supply is disconnected before performing


operations on the unit.
WARNING: before carrying out any
interventions be prepared with suitable
I.P.D.
WARNING: The appliance must be
installed in compliance with national
system regulations.
WARNING: wiring connections installation of the fancoil and relevant accessories should be performed by a technician
who has the necessary technical and
professional expertise to install, modify,

extend and maintain plants and who is


able to check the plants for the purposes of safety and correct operation.
WARNING: Install a device, master
switch or plug that allows to completely
interrupt the appliances electric power
supply.
Here, find the indications essential for
correct installation of the appliances.
Leave processing of all operations to the
experience of the installer, according to
specific requirements.
The fan coil must be installed in a position such that the air can be distributed

throughout the entire room and there are


no obstacles (curtains or objects) to the
passage of the air from the intake grills.
The fan coil must be installed in a position such to allow easy routine (cleaning
the filter) and extraordinary maintenance, as well as access to the air vent valve
on the side of the frame (connections
side).
The installation must not constitute a
danger for persons.

If the 3-way VCF valve is installed, the


water probe SW must be replaced with
accessory SW3, whose bulb will be
applied on the delivery pipe upstream
from the valve.
The VCF valve and the basin BC4 cannot be installed at the same time on
the same fan coil.
Make the electric connections according to that stated in the wiring diagrams and in the Electric connections chapter.
To modify the settings of the electronic
thermostat act on the Dip-Switches
positioned inside the panel (see installation manual).
Re-mount the cover, without forgetting, that for models that have one,
to connect the room probe that must
project outwards by about 3mm from
the probe-holder and must be wellfixed using the relevant probe-block.
Re-position the air filter.
Check the correct functioning of the
fan and any accessories.
Some models with electronic thermostat, by means of the Autotest procedure, allow to check correct functioning. The function is described in the
manuals supplied with the unit.

Electric connections
The electric circuits are connected to the
mains voltage of 230V ~ 50Hz; all connections and components must therefore
be isolated for this voltage.

167 mm

UNIT INSTALLATION
The place of assembly must be selected
in a way that the maximum and minimum room temperature limit is respected 045C (<85% U.R.).
Follow the precautions given below
when installing the unit:
- In wall installation, maintain a minimum distance from the floor of 80
mm. In the case of floor installation
using skirting, refer to the instructions
supplied with the accessory.
- For wall fixing, use expansion plugs
(not supplied)
- Make the hydraulic connections.
The position and diameter of the
hydraulic connections are stated in the
dimensional data.
It is advised to suitably insulate the
water pipes or to install an auxiliary
condensate collection basin, available
as an accessory, in order to prevent
dropping during functioning in cooling
mode.
The condensate drain network must
be appropriately dimensioned and the
piping positioned in a way to maintain an adequate slope along the route
(min.1%). In case of draining into the
sewer system, it is recommended to
realise a siphon that prevents nasty
smells from returning towards the
rooms.
- Apply any accessories.

FEATURES OF THE CONNECTION


CABLES
Use cable type H05V-K or N07V-K with
300/500 V insulation recessed in a pipe or
channel. All cables must be recessed in a pipe
or channel until they reach the fan coil. The
cables exiting the pipe or channel must be
positioned in a way as not to undergo stress
from traction or twisting and, however, protected from external agents
For all connections, follow the wiring diagrams supplied with the appliance and stated
in this documentation.
To protect the unit against short circuits,
mount a magnet omnipolar switch 2A
250V (IG) on the power supply line with
a minimum opening distance of the contacts of 3mm.
Every control panel can control just one
fan coil.
WARNING: the probes have double
insulation as they are exposed to a voltage of 230Vac.

ZX
49

65 mm

B
B
A

A
A

53

English

INFORMATION FOR THE INSTALLATION

DIMENSIONS [mm]
FCX - A - ACB - ACT - AS
B

50

English

100

167 mm

50

100

49

65 mm

Mod.

FCX 17 FCX 22 FCX 32 FCX 42 FCX 50 FCX 62 FCX 82 FCX 102

563

563

563

563

563

688

688

688

640

750

980

1200

1200

1320

1320

1320

220

220

220

220

220

220

220

220

105

105

105

105

105

125

125

125

Peso * [kg]

13

15

20

24

24

34

34

34

* Fan coil weight without feet

FCX - U

Mod. 17 - 22 - 32 - 42 - 50

50

Mod. 62 - 82 - 102

50
100

Mod.

54

FCX 17 FCX 22 FCX 32 FCX 42 FCX 50 FCX 62 FCX 82 FCX 102

520

520

520

520

520

590

590

590

640

220

750

980

1200

1200

1320

1320

1320

220

220

220

220

220

220

220

Weight [kg] 13

15

20

24

24

34

34

34

DIMENSIONS [mm]

3R

A
B
30

96

216
60

85

388
e 17,5

453

453

144

197

49

25

30

216
41 101

45

9 x 20

3R+1R

50

50

FCX 62 - 82 - 102
64 - 84

3R
A (FCX-P)

216
41 107

B
14

216
60

96

350
e 17,5

141
558

558

253

248

32

110

14

39

9 x 20

3R+1R

FCX P - PO
Mod.

FCX 17

FCX 22
FCX 24

FCX 32
FCX 34

FCX 42
FCX 44

FCX 50
FCX 54

FCX 62
FCX 64

FCX 82
FCX 84

FCX 102

[mm] 452

562

793

1013

1013

1147

1147

1147

[mm] 412

522

753

973

973

1122

1122

1122

[mm] 330

440

671

891

891

1102

1102

1102

COIL CONNECTIONS

Mod.

FCX 17

FCX 22

FCX 32

FCX 42

FCX 50

FCX 62

FCX 82

FCX 102

3R

1/2

1/2

1/2

3/4

3/4

3/4

3/4

3/4

1R

1/2

1/2

1/2

1/2

1/2

1/2

1/2

1/2

FCX 24

FCX 34

FCX 44

FCX 54

FCX 64

FCX 84

3/4

3/4

3/4

3/4

3/4

3/4

Mod.
4R

55

English

FCX 17 - 22 - 32 - 42 - 50
24 - 34 - 44 - 54

DIMENSIONS [mm]

Installation with AMP supports (accessories)


FCX-U 17 - 22 - 32 - 42 - 50
258

117

258

English

48

FCX-U 62 - 82 -102

FCX-P 17 - 22 - 32 - 42 - 50
24 - 34 - 44 - 54

105

258

36

100
min.

FCX-U 62 - 82 -102
64 - 84

100
min.

258

FCX A - U - P

A
C

E
24x9

Mod. FCX 17 FCX 22 FCX 32 FCX 42 FCX 50 FCX 62 FCX 82 FCX 102
FCX 24 FCX 34 FCX 44 FCX 54 FCX 64 FCX 84
A

640

750

981

1201

1201

1322

1322

1322

445

555

786

1006

1006

1127

1127

1127

490

600

831

1051

1051

1172

1172

1172

95,5

95,5

95,5

95,5

95,5

95,5

95,5

95,5

54,5

54,5

54,5

54,5

54,5

54,5

54,5

54,5

144,5

144,5

144,5

144,5

144,5

144,5

144,5

144,5

103,5

103,5

103,5

103,5

103,5

103,5

103,5

103,5

In case of inversion hydraulic connections, invert D with E, F with G

56

DIMENSIONS [mm]

3 AND 4- ROW COILS


FCX 62 102
64 84

OUT

OUT

41

41

142

IN

148

194

108

88

49

170

273

167 mm

153

260

194

e 17,5

526

404

e 17,5

IN

English

FCX 17 50
24 54

65 mm
Mod.
Coil connections (female)
Mod.
Coil connections (female)

FCX 17

FCX 22

FCX 32

FCX 42

FCX 50

FCX 62

FCX 82

1/2

1/2

1/2

3/4

3/4

3/4

3/4

FCX 24

FCX 34

FCX 44

FCX 54

FCX 64

FCX 84

3/4

3/4

3/4

3/4

3/4

FCX 102
3/4

3/4

For FCX - U versions do not consider the foot

DIRECT EXPANSION COIL

DIMENSIONS [mm]

Mod.
A

FCX 2250

FCX 62-102

400

522

408

530

9,52

9,52

12

16

Cooling connections on all FCX models fitted with


direct expansion coil (FCX - UE, FCX - PE) are located
on the right side of the unit; the control panel must
therefore be positioned on the left side. The coil cannot be rotated on these models..

57

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS


LEGENDA READING KEY LEGENDE LEGENDE LEYENDA
AL = Alimentatore 12V
Power supply 12V
Alimentation electrique 12V
Spannung 12V
Alimentador

MV = Motore ventilatore Fan motor


Moteur ventilateur Ventilatormotor
Motor del ventilador
PE = Collegamento a terra
GND Earth connection
Mise terre
Erdanschluss
Toma de tierra
RE = Resistenza elettrica Electric heater
RX = Rsistance lectrique Elt. Heizregister
Resistencia elctrica

CN = Connettore
Connector
Connecteur
Schtz
Conector

SA = Sonda ambiente Room sensor


Sonde ambiante Raumtemperaturfuhler
Sonda ambiente
SC = Scheda di controllo
Electronic control board
Platine de contrle Steuerschaltkreis
Tarjeta electrnica de control

CRE= Contattore resistenza elettrica


Electric heater contactor
Contacteur rsistance elctrique
El. Heizregister-Schutz
Contactor de la resistencia elctrica
F

SW = Sonda minima temperatura acqua


Water low temperature sensor
Sonde minimum temp. eau
Wasserfhler
Sonda temperatura mnima del agua

= Fusibile Fuse Fusible


Sicherung Fusible

IG = Interruttore generale Main switch


Interupteur gnral Hauptschalter
Interruptor general

TR = Trasformatore Transformer
Transformateur
Transformator Transformador

M = Morsettiera Terminal board


Boitier Klemmleiste
Placa de bornes

TSR = Termostato a riarmo automatico


Automatic resetting thermostat
Thermostat rarmement automatique
Thermostat automatischer Entriegelung
Termostato de rearme automtico

ML = Motore aletta
Louvre motor
Moteur deflecteur
Motor- Umlenkklappe
Lamas motorizadas

TSRM= Termostato a riarmo manuale


Manual resetting thermostat
Thermostat rarmement manuel
Thermostat manueller Entriegelung
Termostato de rearme manual

MS = Microinterruttore griglia
(Solo per i modelli che ne sono provvisti)
Louvre microswitch
(Only for the appropriate models)
Micro-interrupteur grille
(Uniquement pour les modles qui en sont fournis)
Mikroschalter Gitter
(Nur bei Modellen, die damit ausgestattet sind)
Microinterruptor de la rejilla de impulsin
(Slo para los modelos que lo incluyen)

= Componenti non forniti


Components not supplied
Composants non fournis
Nicht lieferbare Teile
Componentes no suministrados
= Componenti forniti optional
Optional components
Composants en option
Optionsteile
Componentes opcionales
= Collegamenti da eseguire in loco
On-site wiring
Raccordements effectuer in situ
Vor Ort auszufhrende Anschlsse
Cableado in situ

AR = Arancio Orange Orange Orange Naranja


BI = Bianco White Blanc Weiss Blanco
BL = Blu Blue Bleu Blau Azul
GR = Grigio Grey Gris Gray Gris
MA = Marrone Brown Marron Braun Marrn
NE = Nero Black Noir Schwarz Negro
RO = Rosso Red Rouge Rot Rojo
VE = Verde Green Vert Grn Verde
VI = Viola Violet Violet Violet Violeta

VCF=Valvola solenoide Solenoid valve


Vanne solenoide Magnetventil
Vlvula solenoide
VC = Valvola solenoide caldo
Solenoid valve hot
Vanne magntique chaud
Magnetventil Heizbetrieb
Vlvula solenoide para calor

MIN. VEL. - RO

MED. VEL. - MA

COMUNE - BL

MAX. VEL. - NE

SCHEMA DI COLLEGAMENTO MOTORE FCX - PO FCX - PO MOTOR CONNECTION DIAGRAM


SCHEMA DE RACCORDEMENT MOTEUR FCX - PO ANSCHLUSSPLAN MOTOR FCX - PO
ESQUEMA DE CONEXIONADO ELCTRICO DEL MOTOR FCX - PO

RO

AR

VE

BL

GI

GR

NE

BI

L 1 2 3 4 5 6 7

BL

English

CE = Contatto esterno
EX External contact
Contact extrieur
Externer Kontakt
Contacto externo

VF = Valvola solenoide freddo


Solenoid valve cold
Vanne magntique froid
Magnetventil Khlbetrieb
Vlvula solenoide para fro

MA

Le velocit disponibili sono numerate da 1 a 7 in ordine decrescente di velocit


Available speeds are numbered from 1 to 7 following a speed decreasing order
Les vitesses disponibles sont numerates de 1 7 en ordre de vitesse dcroissante
Die verfgbaren Drehzahlen sind von 1 zu 7 mit abnehmender Drehzahlstufe numeriert
Las velocidades disponibles se numeran, en orden decreciente, de 1 a 7.
Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

58

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

SC

T C

SA

V1
V2
V3
Y1
Y2
L
PE
N
SW

ON/VEL

GR
ROS

AR AR

SA

10k

BI

GR

BL

MA

NE

RO

English

FCX - APC

10

NE

BL NE MA RO

ROS

BL

MV

1 3 5 6 7

PE
N
L

C L U S T E R

IG

230V ~ 50Hz

BL

Y N

MAX

VCF

10k

MIN

SW

MED

BL NE MA RO

FCX - ACT

SC
V1
V2
V3
Y1

L
PE
N

SA

GR

SW

BL

AR

MA

NE

BI

RO

PE

AR

M
4

SA
SW

BL

VC/F

NE MA RO

MV
~1

Sez. 1,5 mm2

IG 2A L

9 10
MIN

MED

MAX

230V ~ 50Hz

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

59

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX - A

SC

BL

NE

MA

RO

MIN

MAX

M 1
FCX

MED

English

1
2
3
4
5
6

NE

BL

10

MA

RO

M
MV

PE

Sez. 1,5 mm2

N
L
IG
230V ~ 50Hz

FCX - ACB
SC
N
N
PE
L
Y1
V3
V2
V1

M1

M2

DL1

BL

NE

MA

RO

MIN

MAX

MED

PT1

BL

VCF

NE

10

MA

INT

EXT
JP1

SA

SA

RO

M
MV

PE

Sez. 1,5 mm2

N
L
IG
230V ~ 50Hz

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

60

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX - AS
FCX - P
FCX - U

FCX - U
(escluso 62 - 82 - 102) Universale senza comandi
(except 62 - 82 - 102) Universal, without controls
(esclus 62 - 82 - 102) Universel sans commandes
(ohne 62 - 82 - 102) Universalgert ohne Steuerungen
(excluidos 62 - 82 - 102) Universal sin panel de
mandos

(solo 62 - 82 - 102) Universale senza comandi


(62 - 82 - 102 only) Universal, without controls
(seulement 62 - 82 - 102) Universel sans commandes
(nur 62 - 82 - 102) Universalgert ohne Steuerungen
(slo 62 - 82 - 102) Universal sin panel de mandos

M 1
FCX

BL

NE

MA

RO

NE

BL

Sez. 1,5 mm2

10

MA

BL

NE

MA

RO

MIN

MED

MAX

MIN

MED

MAX

M
FCX

RO

BL

NE

Sez. 1,5 mm2

English

MS

MV

10

MA

RO

M
MV

IG

IG
PE
L N
230V ~ 50Hz

L N PE
230V ~ 50Hz

FCX U*
PXLM

2 tubi pannello PXLM a muro


2 tubes PXLM wall-mounted panel
2 tuyaux panneau PXLM inst. murale
2 Rhren Platte PXLM an Wand
2 tubos panel PXLM mural
NE

BI

BL

GI

RO

EX

AL
M2 12Vdc

Sez. 1,5 mm2

L
N

M1

1
2
3
4
5

CN1

EX
EX
M3
12V
GND

NE

MA

RO

BL

NE

IG
PE
L N
230V ~ 50Hz

10

MA

M4

SA

SW

7
BL

MIN

MAX

M
FCX

230

BL

MED

M1

M2

SA
SA
SW
SW

GND
GR

V1
V2
V3

* termostato elettronico ed alette motorizzate


con FCX - U (escluso 62 - 82 - 102)

* electronic thermostat and motorized fins


with FCX - U (62 - 82 - 102 excluded)

RO

* thermostat lectronique et ailettes motorisees

avec FCX - U (esclus 62 - 82 - 102)

MV

12345

ML

* elektronischer Thermostat mit Motorbetriebenen Lamellen


mit FCX - U (ohne 62 - 82 - 102)

* termostato electrnico y lamas motorizadas


con FCX - U (excluidos 62 - 82 - 102)

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

61

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX

FCX

PX2

PXBI + VCF

commutatore a distanza
remote switch
commutateur distance
Fernumschalter
conmutador remoto

2 tubi pannello PXBI a bordo macchina


2 tubes PXBI panel on board machine
2 tuyaux panneau PXBI sur l'appareil
2 Rhren Platte PXBI am Gert
2 tubos panel PXBI en el equipo
PXBI

MS*

MS*

N
N
PE
L
Y1
V3
V2
V1

MS*

1
2
3
4
5
6

MS*
M1

M 1
FCX

BL

NE

MA

RO

BL

NE

10

MA

BL

NE

MA

RO

MIN

MAX

MIN

MED

M 1
FCX

MED

M2

MAX

NE

BL

VCF

MA

RO

DL1 EXT

SA
M

RO

MV

PE

Sez. 1,5 mm2

MV

PE

Sez. 1,5 mm2

INT
JP1

10

N
L

IG

230V ~ 50Hz

IG
230V ~ 50Hz

FCX

PTI + VCF

MS*

2 tubi pannello PTI a bordo macchina


2 tubes PTI panel on board machine
2 tuyaux panneau PTI sur l'appareil
2 Rhren Platte PTI am Gert
2 tubos panel PTI en el equipo

PTI
V1
V2
V3
Y1

L
PE
N

SA

MS*
SW
GR

BL

NE

MA

RO

BI

10

BL

NE

MA

RO

MIN

M
FCX

AR

MED

AR

SA
SW

MAX

English

PX2

VCF
Sez. 1,5 mm2

BL

NE

MA

RO

M
MV

IG 2A
PE
L N
230V ~ 50Hz
Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

62

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX

PXAE + VC + VF
4 tubi pannello PXAE a muro
4 tubes PXAE wall-mounted panel
4 tuyaux panneau PXAE inst. murale
4 Rhren Platte PXAE an Wand
4 tubos panel PXAE mural

MAX 15m

PXAE
M1

N
L

CE
MS*
MAX 100m

M
FCX

BL

NE

MA

RO

SW
SW

NE

MA

EXT

MAX 15m

MIN

MED

MAX
BL

VC

10

SW

VF

English

V1
V2
V3
Y1
Y2
CE
CE
MS
MS

SA (INT)

JP1
INT

RO

M
MV

PE

Sez. 1,5 mm2

230V ~ 50Hz

L
IG

FCX

PXAE + VCF
2 tubi pannello PXAE a muro
2 tubes PXAE wall-mounted panel
2 tuyaux panneau PXAE inst. murale
2 Rhren Platte PXAE an Wand
2 tubos panel PXAE mural

MAX 15m

PXAE
M1

N
L
V1
V2
V3
Y1
Y2
CE
CE
MS
MS

CE
MAX 100m
3

BL

NE

MA

RO

SW
5

BL

VCF

NE

SW
SW

EXT

MAX 15

MIN

MA

10

MED

MAX

M 1
FCX

MS*

JP1

SA (INT)

INT

RO

M
MV

PE

Sez. 1,5 mm2

N
L

230V ~ 50Hz

IG

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

63

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX

PXAI + VC + VF
4 tubi pannello PXAI a bordo macchina
4 tube PXAI panel on board machine
4 tuyaux panneau PXAI sur l'appareil
4 Rhren Platte PXAI am Gert
4 tubos panel PXAI en el equipo

PXAI
M1

N
L
V1
V2
V3
Y1
Y2
CE
CE
MS
MS

English

CE

BL

NE

MA

RO

MIN

M
FCX

MED

MS*
6

10

MAX
NE

BL

VC

MA

SA
SW

VF

SW
SW

SA (INT)

RO

M
MV

PE

Sez. 1,5 mm

N
L
IG
230V ~ 50Hz

FCX

PXAI + VCF
4 tubi pannello PXAI a bordo macchina
4 tube PXAI panel on board machine
4 tuyaux panneau PXAI sur l'appareil
4 Rhren Platte PXAI am Gert
4 tubos panel PXAI en el equipo

PXAI
M1

N
L

CE

BL

NE

MA

RO

MIN

10

SA
SW

MAX

M
FCX

MED

MS*

VCF

BL

NE

MA

V1
V2
V3
Y1
Y2
CE
CE
MS
MS

SA
SA
SW
SW

SA (INT)

RO

M
MV

PE

Sez. 1,5 mm2

N
L
IG
230V ~ 50Hz

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

64

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX

PXAR + VF + RX
2 tubi pannello PXAR a muro
2 tubes PXAR wall-mounted panel
2 tuyaux panneau PXAR inst. murale
2 Rhren Platte PXAR an Wand
2 tubos panel PXAR mural

MAX 15m

PXAR
M1

N
L

CE
MS*
1

BL

NE

MA

RO

BL

NE

MA

RE

10

MED

MAX

VF

EXT

SA (INT)

JP1
INT

RO

M
MV

SA (EXT)

PE

TSR

CRE

SW
230V ~ 50Hz

IG

Sez. 1,5 mm2

TSRM

SA
SA
SW
SW

SW

MIN

M
FCX

English

V1
V2
V3
Y1
Y2
CE
CE
MS
MS

RX

FCX

PXAR + VCF + RX
2 tubi pannello PXAR a bordo macchina
2 tube PXAR panel on board machine
2 tuyaux panneau PXAR sur l'appareil
2 Rhren Platte PXAR am Gert
2 tubos panel PXAR en el equipo

PXAR
M1

N
L

CE
MS*
2

BL

NE

MA

RO

MAX

VF

BL

RE

10

NE

MA

SA
SW

SA
SA
SW
SW
JP1

SA (INT)

INT

RO

M
MV

SA (EXT)

PE

TSR

CRE

SW

TSRM
RX

EXT

MIN

MED

M
FCX

V1
V2
V3
Y1
Y2
CE
CE
MS
MS

Sez. 1,5 mm2

IG
230V ~ 50Hz

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

65

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX

FCX

2 tubi
2 tube
2 tuyaux
2 Rhren
2 tubos

4 tubi
4 tube
4 tuyaux
4 Rhren
4 tubos

KTLM/KTLP + VC + VF

OWE

C
O
O
L

KTLM/KTLP + VCF
H
E
A
T

IR receiver

UT

KTLM / KTLP

C
O
O
L

H
E
A
T

IR receiver

KTLM / KTLP

SC
TR

Room
Sensor

L1

Room
Sensor

L1

SC
TR
SA

L2 - N

GND
HEAT

GND
HEAT

F
10 A

L2 - N

F
10 A

COOL

COOL

FAN LOW

FAN LOW
VI
GR

Receiver

BI

FAN MED

BL

BI

VI
GR

FAN MED

BL

FAN HIGH

FAN HIGH

NE

NE

MA

MA

VCF

10

BL

NE

MA

RO

M
FCX

VC

N
MV

MA

230V ~ 50Hz

NE

MIN

MED

MAX

230V ~ 50Hz

VF

10

BL

NE

MA

RO

IG 2A

BL

PE

IG 2A

MIN

MED

RO

RO

RO

MAX

M
FCX

Receiver

English

SA

BL

NE

MV

MA

RO

PE

FCX

WMT05

NE

MA

RO

BL

NE

Sez. 1,5 mm2

IG

10

MA

RO

1234N

MV

PE

WMT05

7
BL

MIN

MS*

MAX

M 1
FCX

MS*

MED

2 tubi
2 tube
2 tuyaux
2 Rhren
2 tubos

230V ~ 50Hz

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

66

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX

WMT10 + VCF
MS*

NE

MA

RO

MAX

VCF

7
BL

MIN

M 1
FCX

MED

MS*

NE

BL

MA

English

HIGH

MED

LOW

HEAT

COOL

L2 - N

MV

IG

RO

Sez. 1,5 mm

PE

WMT10

Fan coil

L1~

2 1

10

2 tubi
2 tube
2 tuyaux
2 Rhren
2 tubos

230V ~ 50Hz

FCX

WMT10 + VF + VC
MS*

NE

MA

RO

NE

BL

4 tubi
4 tube
4 tuyaux
4 Rhren
4 tubos

RO

HIGH

MED

LOW

HEAT

COOL

L2 - N

L1~

Sez. 1,5 mm2

MV

IG

MA

WMT10

Fan coil

BL

VC

PE

10

MAX

VF

MIN

M
FCX

MED

MS*

230V ~ 50Hz

FCX

WMT10 + VF + RX

MS*

MS*

NE
NE

TSRM

HIGH

MED

NE

MV

PE

Sez. 1,5 mm2

F 2A

NE

RO

LOW

MA

HEAT

NE

Fan coil

COOL

BL

NE

RX

BL

RO

10

L2 - N

CRE

RO

BL
RO

9
MA

L1~

RO

8
NE

MAX

VF

7
BL

N
L

IG

230V ~ 50Hz

MIN

MED

WMT10
M
FCX

2 tubi
2 tube
2 tuyaux
2 Rhren
2 tubos

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

67

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX

FMT10 + VCF
MS*

MS*

NE

English

BL

Sez. 1,5 mm2

MA

EXT. SENSOR

RO

HIGH

MED

LOW

HEAT

RO

COOL

MA

L2 - N

NE

L1~

BL

FMT10

(6m)

AIR

10

MAX

VCF

MIN

MED

M
MV

WARMER

C650 FS - 1C - 1H

M 1
FCX

2 tubi
2 tube
2 tuyaux
2 Rhren
2 tubos

OFF

ON

LOW MED HIGH


COOLER

PE

IG

230V ~ 50Hz

FCX

FMT10 + VF + VC

MS*
MS*

10

BL

VC

NE

MA

Sez. 1,5 mm2

EXT. SENSOR

RO

HIGH

MED

LOW

HEAT

RO

COOL

MA

L2 - N

NE

L1~

BL

FMT10

(6m)

AIR

MAX

VF

MIN

MED

M
MV

WARMER

C650 FS - 1C - 1H

M
FCX

4 tubi
4 tube
4 tuyaux
4 Rhren
4 tubos

OFF

ON

LOW MED HIGH


COOLER

IG
PE

230V ~ 50Hz

FCX

FMT10 + VF + RX

MS*

2 tubi
2 tube
2 tuyaux
2 Rhren
2 tubos

MS*

BL

NE

MA

F 2A
8

NE

NE
NE

TSRM

EXT. SENSOR

RO

M
MV

Sez. 1,5 mm

NE

HIGH

MED

LOW

HEAT

COOL

NE

RX

BL

RO

10

L2 - N

CRE

RO

BL
RO

9
MA

L1~

RO

8
NE

MAX

VF

7
BL

PE

N
L

IG

230V ~ 50Hz

MIN

MED

FMT10

(6m)

AIR

WARMER

C650 FS - 1C - 1H

M
FCX

OFF

ON

LOW MED HIGH


COOLER

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

68

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX

FMT20 + VCF
MS*

MS*

FMT20
6

NE

Sez. 1,5 mm2

RO

M
MV

IG

MA

N/C

HIGH

MED

LOW

HEAT

RO

COOL

MA

L2 - 0

NE

L1~

BL

BL

PE

10

MAX

VCF

English

MIN

MED

C650 FS - 1C - 1H

EXT. SENSOR

M 1
FCX

2 tubi
2 tube
2 tuyaux
2 Rhren
2 tubos

230V ~ 50Hz

FCX

FMT20 + VF + VC

MS*
MS*

FMT20
4

BL

NE

Sez. 1,5 mm2

RO

M
MV

IG

MA

N/C

HIGH

MED

LOW

HEAT

RO

COOL

MA

L2 - 0

NE

L1~

BL

VC

PE

10

MAX

VF

MIN

MED

C650 FS - 1C - 1H

EXT. SENSOR

M
FCX

4 tubi
4 tube
4 tuyaux
4 Rhren
4 tubos

230V ~ 50Hz

FCX

FMT20 + VF + RX

MS*

2 tubi
2 tube
2 tuyaux
2 Rhren
2 tubos

MS*

FMT20
5

BL

NE

MA

NE

NE

NE
NE

TSRM

RO

M
MV

PE

Sez. 1,5 mm2

F 2A
8

N/C

HIGH

MED

LOW

HEAT

RO

COOL

MA

NE

RX

NE

L2 - 0

CRE

BL

BL

RO

10

BL
RO

L1~

RO

MAX

VF

N
L

IG

230V ~ 50Hz

MIN

MED

C650 FS - 1C - 1H

EXT. SENSOR

M
FCX

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

69

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX PPC
PXAE
M1

N
L
V1
V2
V3
Y1
Y2
CE
CE
MS
MS

English

CE

BL

NE

MA

10

NE

BL

NE

MA

SW
SW

EXT

JP1

SA (INT)

INT

MIN

MED

MAX

Y N

ROS

BL

BL

RO

SW
VC/F

RO

M
MV

PE

1 3 5 6 7

N
L
C L U S T E R

IG
230V ~ 50Hz

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

70

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX PPC
PXAE

English

JP1

EXT

L = 15m MAX

L = 100m MAX

SIT5

INPUT

CE

L PH N N V1 V2 V3 Y1 Y2

SW

L = 15m MAX
F 1A

INT

SW
SW

V1
V2
V3
Y1
Y2
CE
CE
MS
MS

N
L
M1

PXAE

SA (INT)

SIT3 + SIT5

OUTPUT

V1 Y1 Y2

FC/ 1

MV

RO
MA

4
3
2

IG

C L U S T E R

BL

1 3 5 6 7

NE

BL

ROS

VC/F

4
3

MS

Y N

FC/ 2

MV

RO
MA

4
3
2

BL

1
5

4
3
2

NE

10

RO

MA

NE

SIT3/ 2

C L U S T E R

BL

1 3 5 6 7

NE

BL

VC/F

ROS

5
4
3
2

MS

Y N

FC/ 2

PH L

INPUT

V3 V2 V1 N

V3

MAX

V2

OUTPUT

MED

V1

MIN

F
2A

BL

FC/ 1

PH L

L
N
230V ~ 50Hz

BL

1
5

4
3
2

NE

10

RO

MA

NE

INPUT

V3 V2 V1 N

SIT3/ 1

V3

MAX

V2

OUTPUT

MED

V1

MIN

F
2A

BL

PE

V3 V2

MAX FC/10

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

71

SCHEMI ELETTRICI WIRING DIAGRAMS SCHEMAS ELECTRIQUES SCHALTPLNE ESQUEMAS ELCTRICOS

FCX AS
PXAE

EXT

INT

JP1

SW
SW

N
L

V1
V2
V3
Y1
Y2
CE
CE
MS
MS

L = 15m MAX

English

M1
Y2 Y1 V3 V2 V1 N N PH L

PXAE

SA (INT)

SIT3 + SIT5

F 1A

SIT5

INPUT
OUTPUT

V2 V3

FCX/1

RO
MA

M
1

L
N
230V ~ 50Hz

BL

MV

NE

4
3

4
3
2

2
1
5
6

1
5
6

10

RO

MA

8
7
6

BL

SIT3/1

MAX

F
2A

INPUT

PH L

4A

IG

VCH

FCX/2

RO
MA

M
1
MV

NE

4
3

BL

4
3

2
1
5

2
1
5
6

10

RO

MA

NE

7
6

SIT3/2

F
2A

INPUT

PH L

VCH

FCX/N

RO

MV

MA

M
1

4
3

NE
BL

4
3

2
1
5

2
1
5

10

RO

MA

NE

7
6

SIT3/10

F
2A

INPUT

PH L

VCH

MS

V3 V2 V1 N

MAX

V3

MIN

V2

OUTPUT

MED

V1

BL

MS

V3 V2 V1 N

MAX

V3

MIN

V2

OUTPUT

MED

V1

BL

MS

V3 V2 V1 N

MIN

V3

MED

V2

OUTPUT

NE

PE

Y2 Y1 V1

V1

Gli schemi elettrici sono soggetti ad un continuo aggiornamento, obbligatorio quindi fare riferimento a quelli a bordo macchina.
All
wiring
diagrams
are
constantly
updated.
Please
refer
to
the
ones
supplied
with
the
unit.
Nos schmas lectriques tant constamment mis jour, il faut absolument se rfrer ceux fournis bord de nos appareils.
Die Schaltplne werden stndig aktualisiert, deswegen muss man sich stets auf das mit dem Gert gelieferte Schaltschema beziehen.
El cableado de las mquinas es sometido a actualizaciones constantes. Por favor, para cada unidad hagan referencia a los esquemas suministrados con la misma.

72

TROUBLE SHOOTING
PROBLEM
Feeble air discharge

PROBABLE CAUSE
Wrong speed setting on the control panel

SOLUTION
Select the speed on the control panel
Clean the filter

Blocked filter
Remove the obstruction
Ostruzione del flusso daria (entrata e/o uscita)
It does not heat

Control the boiler


Control the heating pump
See control panel settings

Poor hot power supply

English

Wrong setting on control panel


It does not cool

Poor chilled water supply

Control the chiller


See control panel settings

Wrong setting on control panel

Control the power supply

The fan does not turn


Check up the boiler or the chiller and/or their
setting
Check up the thermostat settings
The water has not reached operating temperature
Increase the water temperature beyond the
The water has not reached operating temperature
The limit conditions of temperature and humi- minimum limits indicated in MINIMUM
dity indicated in MINIMUM AVERAGE WATER AVERAGE WATER TEMPERATURE.
TEMPERATURE have been reached
No current

Condensation on the unit


cabinet

For anomalies dont hesitate, contact the after sales service immediately.

MAINTENANCE
ROUTINE MAINTENANCE
Routime maitenance can be performed by
the user. It consists of a series of simple
operations that allow the facncoil to
operatore at its maximum performance.

Before carrying out any intervention


be sure that electrical power supply
is disconnected. Do nor remove the
shell or the electrical or mechanical
protections.

Interventions:
- External cleaning must be carried out
weekly. Use a wet rag (with water at max,
40C temperature) and neutral detergent;
avoid other detergents or solvents. .
- Do not spray water in the external or
internal surfaces of the fancoil (short circuit coud occur) .

- Examination of the fancoil status at any maintenance intervention: any anomaly must be communicated to the After Sales dept.

EXTRAORDINARY MAINTENANCE
Only Aermec After Sales dept. or
personnel with all the technicalprofessional capacities for the
installation,transformation and
maintenance of the units and able
to verify them according to the safety
normes in force with particular reference
to electrical connections can carry out
the extraordinary maintenance. The

following verifications relating to the


above are requested:
- Measure of the electrical unit
insulatioon resistance.
- Continuity testo of the protection
conductors.
Extraordinary maintenance consists of a
series of complex operations that involve
the disassembling of the fancoil or its

Intervention:
- Internal cleaning with year frequence or before prolonged
period. In particular situation where an high level nof cleaning
is requetsed, it can be carried out more frequently. It consists in
the coil cleaning, fancoil fins, drip tray, ioniser and all the parts
in contact with the treated air. Moreover verify the status of the
filter, clean it and if necessary replace it.
For cleaning do nou use jets or water spray..

74

components. Thanks to this operation


the maximum efficency condition for the
bfan coil functioning is restored.
Before any intervention, be sure
electrical power supply is disconnected.

Use a small brush to remove possible dust deposit.


- For repairing or setting operation, consult the TROUBLE AND
SHOOTING chapter before contact the After Sales dept.

Aermec partecipa al Programma di Certificazione EUROVENT. I prodotti interessati figurano nella Guida EUROVENT dei Prodotti Certificati.
Aermec is partecipating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products.
Aermec partecipe au Programme de Certification EUROVENT. Les produits figurent dans lAnnuaire EUROVENT des Produits Certifis.
Aermec ist am Zertifikations - Programm EUROVENT beteiligt. Die entsprechend gekennzeichneten Produkte sind im EUROVENT - Jahrbuch aufgefrt.
AERMEC S.p.A. participa en el programa de certificacin EUROVENT. Sus equipos aparecen en el directorio de productos certificados EUROVENT.