Académique Documents
Professionnel Documents
Culture Documents
I. INTRODUCTION
1563
Fig. 2. Application of switched and fixed capacitors for a time varying kvar
demand condition.
Fig. 3. Conventional strategy for power factor correction through switched capacitor banks.
kvar
1564
The parallel resonance order of 4.83 is too close to the 5th harmonic order and if any magnitude of 5th harmonic current flows
from the harmonic-producing loads into the power system at the
capacitor bus, the capacitor may not be able to withstand the resonance voltage, leading to fuse blowing or capacitor damage.
TABLE I
CAPACITOR LOADING LIMITS ESTABLISHED
THE IEEE STANDARD 1036-1992
1565
1566
1) Record the steady-state waveforms of the capacitor voltages and currents. If the capacitor is not connected, its currents are treated as zero.
2) Changes are then made to the status of the capacitor. For
example, a capacitor unit can be switched on or off to meet
the power factor requirement.
3) The postdisturbance steady-state voltage and current
waveforms are recorded.
4) Discrete Fourier transform (DFT) is applied to the pre- and
postdisturbance waveforms. For each harmonic, the following system equations can be developed:
(5)
(6)
where
and
are the predisturbance hth harmonic current and voltage, and
and
are the
post-disturbance hth harmonic current and voltage.
and
are the internal system voltage and system impedance,
respectively.
5) The system harmonic impedances can be determined from
the above two equations as follows:
(7)
The impedance does not include the switched capacitor
impedance. Practical implementation and field experiences
regarding this method to calculate
can be found on [16].
B. Detection of Resonance Condition
As mentioned before, from the system impedance and the existing capacitor impedance, the resonance frequency can be calculated through (3). For a certain system impedance (or system
fault level,
), the number of capacitor units
that
lead to a harmonic resonance frequency
equal or close
to the dominant harmonic frequencies. Fig. 6 illustrates, for a
particular system impedance, how the harmonic resonance frequency changes as more and more capacitor units are switched
on. For the figure below, the system is represented by a transformer of 1600 kVA with reactance of 6.0% and each capacitor
unit has a capacity of 50 kvar. From this figure, it is clear that the
resonance frequency can be shifted from a harmonic frequency
by changing the number of switched capacitor units.
A practical way to verify if
is too close to any harmonic
frequency
is to apply (4). In the example of Fig. 6, if 11
capacitors are switched ON, the resonance frequency
is too
close to the 7th harmonic order (point A in the figure), therefore, the bank should be increased or decreased. If two more
capacitor are switched (13 in total),
is around 6.4 (point B
in the figure), which is further away from 5th and 7th harmonic
orders. However, it is also necessary to evaluate for the current
combination of capacitor units if its loading conditions meet the
limits specified by Table I.
One can also observe from Fig. 6 that more than one combination of capacitor units can be considered to avoid resonance.
In the following subsections, it will be shown the criteria to select the most appropriate combination. In this paper, each combination refers to a particular number of capacitor units to be
switched on to the circuit.
C. Determination of Capacitor Units
The final step is to determine the number of capacitor units
that can be switched without violating power factor and resonance constraints. From the previous subsection, it is possible
to estimate, from the current system impedance, the combinations of capacitor units that can be switched so that the resonance frequency
is further away from the harmonic frequencies. This can be done through the following steps:
1) The system impedance
calculated from the last
capacitor switching is used as input.
2) Substituting (3) in (4) yields (8), from which it is possible
to determine the combinations of capacitors
that
can be switched. Normally, the dominant harmonic frequencies
are the odd harmonic orders from 3 to 29
(8)
3) Among the combinations found in step 2), it is possible
to determine which combinations (kvar) lead to a power
between utility lower
and upper
factor
limits. This verification can be done as follows:
(9)
4) From the combinations found in step 3), select the combination that lead to minimum switching relative to the current capacitor bank configuration.
5) Calculate the anticipated loading for this combination this
using the indices presented in Table I.
6) If loading indices meet the standard limits, switch the combination, otherwise discard this option from the combinations obtained in step 3) and go back to step 4) to select a
suboptimal solution.
The next subsection combines the previously discussed functionalities into a single flowchart.
1567
TABLE II
PARAMETERS OF A TYPICAL DISTRIBUTION POWER TRANSFORMER
TABLE III
ACTIVE AND REACTIVE POWER DEMAND OF THE CASE STUDY FACILITY
1568
TABLE IV
HARMONIC CURRENT LIMITS OF THE INVESTIGATED SYSTEM
ACCORDING TO IEEE 519-1992 [20]
TABLE V
COMBINATIONS OF SWITCHED ON CAPACITORS LEADING TO HARMONIC
RESONANCE FREQUENCY CLOSE TO TYPICAL HARMONIC ORDERS
From the parameters of the power transformer, the secondaryside short-circuit current at the PCC is
The facility is equipped with a PF correction scheme composed of units of shunt capacitor of 20 kVAR each one. The demand of active and reactive power from the facility is provided
in Table III. In this table, the maximum demand load current
(fundamental frequency) is
1569
Fig. 13. Number of the switched on capacitors and corresponding power factors before and after compensation using proposed control strategy.
Fig. 12. Number of the switched on capacitors and corresponding power factor
before and after compensation using conventional control strategy.
It is observed that the working voltage of the capacitors exceed the 110% when the number of the switch-on capacitors is
equal to 6, 8, 12, or 20.
For the first sample point given in Table III, the number of
switched on capacitors
can be firstly determined as 6 to meet
. From the system impedance
, the
resonance frequency is calculated as
, which does
not respect the requirement defined by (8) and means that
cannot be selected as 6. Instead, if
, the new PF can be
estimated as
, which is acceptable. Similarly
for other cases, the corrected PF can be calculated for all the
sample points given in Table III, as shown in Fig. 13.
One can observe from both Figs. 13 and 11 that the new control strategy avoids the harmonic resonance problem, which, in
turn, it can prevent damage to the capacitor bank of the facility.
VI. CONCLUSION
This paper presents a new control strategy for power factor
compensation on distorted low voltage power systems. The proposed strategy can perform power factor correction without exciting harmonic resonance under varying demand conditions.
Practical and robust control algorithms are proposed for the purpose of easy implementation in a microcontroller. In addition,
the controller relies on common low cost sensing devices and
does not require additional hardware circuits. As a result, the
proposed controller can be constructed as a retrofitting device
to replace existing power factor correction controllers with little
effort and low cost. Analysis of representative case studies validates the proposed strategy and illustrates how the proposed
controller performs.
REFERENCES
[1] IEEE Recommended Practice for Electric Power Systems in Commercial Buildings, ANSI/IEEE Std. 241-1990, Gray Book.
[2] T. M. Blooming and D. J. Carnovale, Capacitor application issues,
IEEE Trans. Ind. Appl., vol. 44, no. 4, pp. 10131026, Jul. 2008.
1570
[3] A. Novitskiy and H. Schau, Energy saving effect due to the voltage reduction in industrial electrical networks, in Proc. Elec. Power Quality
Supply Rel. Conf. (PQ), Jun. 2010, pp. 6772.
[4] T. A. Short, Electric Power Distribution Handbook. Boca Raton, FL:
CRC, 2004.
[5] IEEE Guide for Application of Shunt Power Capacitors, IEEE Std.
1036-1992, 1992.
[6] J. Arrillaga and N. R. Watson, Power System Harmonics, 2nd ed.
Hoboken, NJ: Wiley, 2003.
[7] A. F. Zobaa, Capacitive compensation at nonsinusoidal buses based
on IEEE Std. 18-1992, IEEE Trans. Power Del., vol. 18, no. 4, pp.
15621563, Oct. 2003.
[8] M. M. Abdel Aziz, E. E. Abou Elzahab, and A. M. Ibrahim, Sizing of
capacitors to optimize the power factor at non-sinusoidal frequencies,
Elec. Power Syst. Res., vol. 64, no. 1, pp. 8185, Jan. 2003.
[9] R. H. Simpson, Misapplication of power capacitors in distribution systems with nonlinear loads-three case histories, IEEE Trans. Ind. Appl.,
vol. 41, no. 1, pp. 134143, Jan. 2005.
[10] L. Herman and I. Papic, Hybrid active filter for power factor correction and harmonics elimination in industrial networks, in Proc. IEEE
Electr. Power Energy Conf. (EPEC), Oct. 2011, pp. 302308.
[11] J.-C. Wu, H.-L. Jou, K.-D. Wu, and N. C. Shen, Power converter-based method for protecting three-phase power capacitor from
harmonic destruction, IEEE Trans. Power Del., vol. 19, no. 3, pp.
14341441, Jul. 2004.
[12] M. M. Abdel Aziz, E. E. Abou El-Zahab, A. M. Ibrahim, and A. F.
Zobaa, LC compensators for power factor correction of nonlinear
loads, IEEE Trans. Power Del., vol. 19, no. 1, pp. 331336, Feb.
2004.
[13] P. Jintakosonwit, S. Srianthumrong, and P. Jintakosonwit, Implementation and performance of an anti-resonance hybrid delta-connected capacitor bank for power factor correction, IEEE Trans. Power Del., vol.
22, no. 6, pp. 25432551, Nov. 2007.
[14] A. Robert and T. Deflandre, Guide for assessing the network harmonic
impedances, , CIGRE 36.05, Working Group CC02 Rep., Mar. 1993.
[15] A. de Oliveira, J. C. de Oliveira, J. W. Resende, and M. S. Miskulin,
Practical approaches for AC system harmonic impedance measurements, IEEE Trans. Power Del., vol. 6, pp. 17211726, Oct. 1991.
[16] W. Xu, E. E. Ahmed, X. Zhang, and X. Liu, Measurement of network
harmonic impedances: Practical implementation issues and their solutions, IEEE Trans. Power Del., vol. 17, no. 1, pp. 210216, Jan. 2002.
[17] J. C. Whitaker, AC Power Systems Handbook, 2nd ed. Boca Raton,
FL: CRC, 1999.
[18] R. C. Dugan, M. F. McGranaghan, and H. W. Beaty, Electrical Power
System Quality. New York: McGraw-Hill, 1996.
[19] R. Tinggren, Y. Hu, L. Tang, H. Mathews, R. Tyner, R. Heinemeyer, H.
Breder, and C. Cereda, Power factor controllerAn integrated power
quality device, in Proc. IEEE Transm. Power Distrib. Conf., 1999.
[20] Task force on harmonics modeling and simulation, modeling and simulation of the propagation of harmonics in electric power networks, part
I: Concepts, models, and simulation techniques, IEEE Trans. Power
Del., vol. 11, no. 1, pp. 452465, Jan. 1996.
[21] IEEE Standard for Shunt Power Capacitors, IEEE Std. 182002, 2002.
[22] IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Std 5191992, 1993.
Shunfu Lin (M12) received the B.S. degree in applied physics and the Ph.D.
degree in nuclear technology and application from the University of Science
and Technology of China in 2002 and 2007, respectively.
He worked for the Corporate Technology of Siemens Limited China as a Research Scientist in power monitoring and control of low-voltage distribution
system from July 2007 to September 2009. He was a Postdoctoral Fellow at the
Department of Electrical and Computer Engineering of University of Alberta,
Canada from October 2009 to October 2010. He is currently a Distinguished
Professor at the Shanghai University of Electric Power, China. His research interests include power quality and power measurement.
Diogo Salles (S04) received the B.Sc. and M.Sc. degrees in electrical engineering from the University of Campinas, Campinas, Brazil in 2006 and 2008,
respectively, where currently he is working toward the Ph.D. degree.
From 2010 to 2011, he was a visiting Ph.D. student at the University of Alberta, Edmonton, Canada. His research interests are power quality and analysis
of distribution systems.
Walmir Freitas (M02) received the Ph.D. degree in electrical engineering from
the University of Campinas, Campinas, Brazil in 2001.
He is currently an Associate Professor, University of Campinas. His areas of
research interest are analysis of distribution systems and distributed generation.