Fig. 1
6MB5515 station control unit
Fig. 2
6MB5515 with expansion unit and fibreoptic isolation installed in the cubicle
In addition to the powerful 80386 processor and memory required for the program
code and parameters, the FP telecontrol
processor module implemented in the
basic unit contains six interfaces which
are used by two separate and very powerful 68302 communications processors:
One 2 kV isolated system interface
V.24/V.28 (RS232C)
One 8-fold multiplex interface for connecting 8 digital input/output units and
numerical protection equipment via
fibre-optic cable which can also be
used as a system interface
One interface for loading parameters
and for testing and diagnostics functions
Three system interfaces.
Siemens AG 19971
Telecontrol channel
Telephone channel
Telecontrol channel
Standard time
FP/LPII
6MB5515 station control unit
BF
BA
DE
AE, AR
SC
Stationsleitgert
Terminal block 6MB5515
Fibre-optic cable
Switchg.interlocking
8TK bay unit
6MB52
input/output unit
Switchg. interlocking
8TK bay unit
7S/7U
selective protection
Switchyard expansion
Switchyard
Serial link
Parallel link
Fig. 3
The 6MB5515 station control unit in the 6MB telecontrol system
Telecontrol channel
Telephone channel
Standard time
6MB52
input/output units
6MB5515 station
control unit
Switchyard
Station control
centre
1 ... ... n
6MB55300
mini compact unit
Terminal block
Terminal block
Terminal block
Switchyard
Switchyard
Switchyard
Fig. 4
The 6MB5515 station control unit with node function option in the 6MB telecontrol system
Parameterization
The entire plant-specific parameterization
of the station control unit is stored as a
parameter set in a non-volatile memory
of the FP or LPII processor module during
commissioning. The station control unit is
adapted to the special conditions and
requirements of the switchyard in
question by entry of the data. The
parameter set is created with the
LSATOOLS programming package for PC.
The loading process is efficiently
supported by the CB communication
module. The CB module is a
communication board in the PC.
After system startup with autonomous
distribution of the parameters to all the
components and units in the switchyard,
the system is ready for operation.
Changes and expansions can be made at
any time using LSATOOLS.
The parameterization data include:
Plant configuration and topology
Equipment configuration of the station
control unit
Connection to the primary equipment:
acquisition, processing and output parameters for each item of information
from and command to the switchyard
Specification of the serially connected
numerical relays
Configuration of the telecontrol connections to and from the unit
Complete telecontrol frame assignments and transmission protocols
Function tree for the station control
unit
Design and appearance of display,
mimic and control diagrams
Plaintext for logs and displays
Archiving and logging conventions
Sequential and logic functions, e.g.
network synchronization, switching
operations
All interlocks.
The parameter lists are function oriented
and contain the associated setting options and the catalog sheets User functions.
Telecontrol protocol
Interface type
Transmission speed
Telecontrol protocols
V.24/V.28 (RS232C)
max. 64 kBd
to IEC 8705, parts 1 and 2
Archiving
8 MB
LSAPROCESS
(archive evaluation)
Interface type
Transmission speed
Telecontrol protocols
V.24/V.28 (RS232C)
max. 64 kBd
to IEC 8705101
Inputs
Number
Time resolution for indication acquisition
Indication voltage
Input current
Outputs
Number
Switching voltage
max. break power (ohmic load)
Interface type
Transmission rate
Input current
BA command output module
Number of command outputs (with enable via BF)
Switching voltage
max. break power (ohmic load)
max. break power (inductive load, L/R <20 ms)
Contact lifetime at maximum (minimum ohmic load)
AE analog output module
Number of inputs
Measuring ranges
Resolution
Maximum measuring error
Analog value refresh time (50 Hz)
Interference suppression for
8 single indications
1 ms
19.2 to 75 V, 88 to 275 V DC
0.4 to 1.56 mA
8 changeover contacts
19.2 to 75 V, 88 to 275 V DC
100 to 55 W (for 19.2 to 75 V DC)
50 W (for 88 to 275 V DC)
60 to 20 W (for 19.2 to 75 V DC)
25 W (for 88 to 275 V DC)
>105 (107) operating cycles
32, groups of 8 with common potential
1 ms
4 to 64 ms
19.2 to 75 V, 88 to 275 V DC
For voltages of >110 V module 2 SPS
required
0.4 to 1.56 mA
32 x 1pole (2pole A) or
16 x 2pole (2pole B)
19.2 to 75 V, 88 to 275 V DC
145 to 85 W (for 19.2 to 75 V DC)
50 W (for 88 to 275 V DC)
75 to 60 W (for 19.2 to 75 V DC)
25 W (for 88 to 275 V DC)
>105 (107) operating cycles
32, connected to common potential
0 to 1.5; 2.5; 3; 5; 6; 10; 12; 20; 24 mA DC
0 to 1; 1.25; 1.5; 2.5; 3; 5; 6; 10 V DC
11 significant bits + sign
0.325 % of the measuring range
960 ms for 32 analog values
50, 60, 16 2/3 Hz
16 inputs, isolated
0 to "1.5; 2.5; 3; 5; 6; 10; 12; 20; 24 mA DC
0 to "1; 1.25; 1.5; 2.5; 3; 5; 6; 10 V DC
11 significant bits + sign
0.275 % of the measuring range
650 ms for 16 analog values
50, 60, 162/3 Hz
>109 operating cycles
Transmission frequency
Maximum length of data cable
Connection system
on terminal blocks
Power supply
Back-up time
DIN 19 244 part 21, class V12
optional
DIN VDE 0435 part 303
Residual ripple of the input voltage
24 V DC
48 to 60 V DC
110 to 125 V DC
220 to 250 V DC
115 to 230 V AC , 50/60 Hz
min. 5 ms,
50 ms with external backup capacitor
v12 %
CEconformity, standards
Insulation tests
IEC 2555, VDE 0435 part 303
IP 00 B for subracks
IP 40 for cubicle, others on request
Heat reliability
Climatic stress
(DIN 19 244 part 21)
Operating conditions:
Emission only via front and rear as well
as top
Battery voltage 120 %
Inputs connected as required for operation
50 % of indications active
0 to +40 C
25 to +70 C
5 to 95 % rel. humidity,
max. 28 g/m3 water in air
Annual average of v75 % relative humidity
on 30 days a year up to 95% relative humidity, condensation not permissible
80 to 110 kPa
Order No.
6MB5515 0
A
B
Fibre-optic (FO) interface module (pairs) for connecting bay control unit
8 x FO integrated (no 6MB5512 required)
up to 32 x FO prepared (1 x 6MB5512) incl. 1 x SC module
up to 64 x FO prepared (2 x 6MB5512 incl. 2 x SC module
without
A
D
H
Y
0
5
6
1
3
4
5
6
Expansions
Without expansion rack
1 prepared expansion rack incl. 2 m cable and 1 RK module
2 prepared expansion racks incl. 1 x 2 m, 1 x 10 m cable and 2 RK modules
3 prepared expansion racks incl. 1 x 2 m, 2 x 10 m cable and 3 RK modules
4 prepared expansion racks incl. 1 x 2 m, 3 x 10 m cable and 4 RK modules
5 prepared expansion racks incl. 1 x 2 m, 4 x 10 m cable and 5 RK modules
0
1
2
3
4
5
Radio clock
with DCF77/MSF (Diem), without aerial
without
A
Y
B
D
F
H
Software version
Software V9.1
Software V9.2
0
1
Documentation
Order No.
Deutsch:
Stationsleitgert 6MB5515
Stationsleittechnik SINAUT LSA/Stationsleitgert (V9)
E50001K5701A261A1
C53000G1800C141
English:
E50001K5701A261A17600
C53000G1875C141
Order No.
6MB5511 0 A A 0 j 0 A A 0
1
3
4
5
6
6MB5512 0 A j 0 j 0 A A 0
A
B
C
D
Y
1
3
4
5
6
6MA5210 2 j E j 4
D
E
0
1
6MA5210 3 j j j j
D
E
B
C
0
1
1
2
1
2
3
Order No.
6MA5220 1 j j j j
E
F
G
H
LED display
without
with
A
B
Metal frontplate
with frontplate 1 SPS = 3 HP
with frontplate 2 SPS = 6 HP
1
2
0
1
2
6MA5250 1 j j j j
D
E
A
B
1
0
1
Order No.
6MC5001
Software registration provides the legal right to use the 6MB system software in the telecontrol system or in
the SINAUT LSA substation control and protection system as well as a claim to the EV S after-sales service.
Software registration must be purchased for each individual 6MB551 or 6MB554 or 6MB513 or 6MB514.
In the case of software updates, the diskettes with the system software are ordered separately
(6MC50000BB**).
Human-machine interface
without
1 operator station (1 VDU, 1 printer)
2 operator station (2 VDUs, 2 printers)
0
1
2
A
B
C
Connection of substations
No substations connected
up to 2 substations
up to 4 substations
up to 6 substations
up to 8 substations
A
B
C
D
E
0
1
Archiving
Fault recording and indications from protective devices
Fault recording, analog values, metered values, events
0
1
Synchronization check
without
with
0
1
A
B
A
B
C
D
E
F
G
H
Order No.
Accessories
Isolating module
0
1
ABR1)
C73207A305B401
C73207A305B451
C73207A268B102
C73207A268B100
10
SINAUT LSA
system bus
FP or LPII
32 single indications
per module
Interfaces
Command enable module
BF
RM module
DCF
77
RxD
TxD
CTS
RTS
8 local indications
8 local commands
Command enable
Switching current
check
BA
32 single commands
per module
FO module 1)
RxD
TxD
8
FO
8 x FO
AE/AR
FO module 2)
RxD
TxD
4
FO
4 x FO
ABR module 3)
RxD
TxD
CTS
RTS
RxD
TxD
CTS
RTS
RxD
DTR
CTS
RTS
ABRSK 4)
V.24
V.24
Alternatively, a
connection via FO or
and ABR-SK module is
also possible
4 x V.24
1
V.24
2
V.24
V.24
Power supply module
RxD
TxD
CTS
RTS
1)
2)
3)
4)
SV
V.24
=
=
L+
L
Fig. 5
Connection diagram showing connections and data flow for 6MB5515 (V9) station control unit, overview
11
VR
1
2
3
4
5
6
7
8
W
BF
VR
BA
V Ref
EN1
EN2
Command enable
1
2
3
4
5
6
7
8
O 1.1
O 1.2
O 2.1
O 2.2
O 3.1
O 3.2
O 4.1
O 4.2
O 2.1
O 2.2
O 2.3
O 3.1
O 3.2
O 3.3
O 4.1
O 4.2
O 4.3
O 5.1
O 5.2
O 5.3
O 6.1
O 6.2
O 6.3
O 7.1
O 7.2
O 7.3
O 8.1
O 8.2
O 8.3
...
...
O 1.1
O 1.2
O 1.3
16.1
16.2
16
V Ref
VR
VR1
1
2
3
4
5
6
7
8
W1
VR
VR4
25
26
27
28
29
30
31
32
W4
1
2
3
4
5
6
7
8
...
VC+
VC
EN+
EN
SCC1
SCC2
Command enable
or switching
current check
Switching current
check for external enable relay
V Ref
25
26
27
28
29
30
31
32
Fig. 6
Connection diagram showing connections and data flow for 6MB5515 (V9) station control unit, BF, BA, DE modules
12
EN+ EN
BF Command
enable module
O1.2
K101
O16.1 O16.2
K116
EN1
K117
K118
K119
K120
EN2
Fig. 7
Two-pole A (11/2-pole) command output via one single contact per command and one sum contact from the BF
EN+ EN
O16.1 O16.2
O1.1
O1.2
K101
O16.1 O16.2
K116
EN1
K117
K118
K119
K120
BF Command
enable module
EN2
Fig. 8
Two-pole B (2-pole) command output via two single contacts per command and one sum contact from the BF
13
AE
AE1
AE2
2
SC
a)
RxD
TxD
CTS
RTS
TTL
8 communication
channels
or
or
RxD
TxD
b)
Quad multiplexer
...
TTL
...
RxD
TxD
AE4
1
TTL
.
.
4
AE3
Channel 1
1)
a)
RxD
TxD
CTS
RTS
TTL
Channel 8
W
or
or
RxD
TxD
b)
RxD
TxD
AE32
32
1
TTL
.
.
4
Quad multiplexer
TTL
AR1
AR2+
AR2
AR3+
AR3
AR4+
AR4
...
...
AR13+
13
AR13
AR14+
14
AR14
AR15+
15
AR15
AR16+
16
AR16
Fig. 9
Connection diagram showing connections and data flow for 6MB5515 (V9) station control unit, modules SC, AE, AR
14
Dimension drawings in mm
482.6
182
30
57.15
133.35
7
57.15
SV
BA
BA
BF
AE
AR
DE
DE
FP/LPII
RK
RK
SC
6 U = 266.7
...
251
37.4
84 E = 426.72
11
465.1
Rear view
Front view
Fig. 10
6MB5515 station control unit basic rack with module complement
482.6
37.4
182
30
133.35
57.15
57.15
SV
BA
BA
AR
DE
DE
RK
AE
6 U = 266.7
...
217
84 E = 426.72
11
465.1
Rear view
Front view
Fig. 11
6MB5515 station control unit expansion rack with module complement
482.6
37.4
57.15
11
465.1
Front view
240
3 U = 133.35
84 E = 426.72
Side panel
Cover
Fibre-optic cable
bracket
Rear view
Detail X:
Detail Z:
Fig. 12
6MB5515 rack for fibre-optic cable connection (connection of max. 32 bay control units)
15
Export Regulations
In accordance with present provisions of
the German Export List and the US Commercial Control List, export licences are
not required for the products listed in this
catalog.
Trademarks
All product designations used are trademarks or product names of Siemens AG
or of other suppliers.
Relevant are the criteria stated in the delivery note and the invoice.
Subject to change without notice.
Dimensions
All dimensions in this catalog are given in
mm.
Siemens online!
The Power Transmission and Distribution
Group can also be found in the Internet:
http://www.ev.siemens.de
Responsible for
Technical contents: Jrgen Heckel,
Siemens AG, EV S V22, Nrnberg
General editing: Roland Reichel/Claudia KhnSutiono,
Siemens AG, EV S SUP22, Nrnberg/EV BK T, Erlangen
Bereich
Energiebertragung und -verteilung
Geschftsgebiet Sekundrsysteme
Postfach 48 06
D-90026 Nrnberg
16
Siemens
Aktiengesellschaft
Power
Transmission
and Distribution
Order No.: E50001-K5701A261-A17600
Siemens LSA 1.2.6 . March 1997
Printed in Germany
KGK 0397 2.0 16 En 322517 6101/U526