Vous êtes sur la page 1sur 13

ANALISIS HIDRAULICO CALDERAS 1 Y 2

Fire Sprinkler Reports

for

HARINERA DE MEXICO
MEXICO

Prepared By:
ING. HOMERO JARAMILLO CATEMAXCA
HERJIM S.A de C.V.

25/11/2016

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 2

General Project Data Report


General Data
Project Title:
Designed By:
Code Reference:

Client Name:
Address:
Company Name:
Company Address:
Phone:
Building Name:
Contact at Building:
Address Of Building:

ANALISIS HIDRAULICO
Project File Name:
AH-MSC001-S-001_A1..fiw
CALDERAS 1 Y 2
ING. HOMERO JARAMILLO
Date:
25/11/2016
CATEMAXCA
NFPA-15
Approving Agency:
NFPA-15
INGENIERA BASICA PARA EL DESARROLLO DE UN SISTEMA DE PROTECCION
CONTRAINCENDIO
HARINERA DE MEXICO
Phone:
MEXICO
City, State Zip Code:
HERJIM S.A de C.V.
Representative:
ING. ARIANA AYALA
City And State:
HARINERA DE MEXICO

Building Owner:
Phone at Building:
City, State Zip Code:

MEXICO

Project Data
Description Of Hazard:
Ex. Haz. Gp. 2
Design Area Of Water Application:
50 ft
Default Sprinkler K-Factor:
4.00 K
Inside Hose Stream Allowance:
In Rack Sprinkler Allowance:

0.00 gpm
750.00 gpm

Sprinkler Specifications
Make:
Size:

Sprinkler System Type:


Maximum Area Per Sprinkler:

Dry
50 ft
SCHED 80 CARBON
Default Pipe Material:
STEEL
Outside Hose Stream Allowance:
0.00 gpm

Model:
Temperature Rating:

NTL-C
68 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID:
Hydrant Elevation:
Test Flow Rate:
Calculated System Flow Rate:

Date Of Test:
0 ft
0.00 gpm
771.96 gpm

Static Pressure:
Test Residual Pressure:
Calculated Inflow Residual Pressure:

0.00 psi
0.00 psi
85.16 psi

Calculation Project Data


Calculation Mode:
HMD Minimum Residual Pressure:
Number Of Active Nodes:
Number Of Active Pipes:
Number Of Active Sprinklers:

C:\ ...\AH-MSC001-S-001_A1.fiw

Demand
40.00 psi
23
24
16

Minimum Desired Flow Density:


Number Of Inactive Pipes:
Number Of Inactive Sprinklers:

0.50 gpm/ft
0
0

jueves, 01 de diciembre de 2016, 8:59 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 3

Fire Sprinkler Input Data


Node Input Data
Area Group
Branch Dia.
(in)

Sprinkler
KFactor (K)
Branch Len.
(ft)

Pressure
Estimate (psi)
Branch Stnd
Fittings

Node Elev (ft)


Branch NonStnd Fittings
(ft)

Non-Sprinkler
Flow (gpm)
Branch Sprk
KFactor (K)

No Discharge
----

---0.000

N/A
0.0

85.16
----

15.70
0.0

0.00
0.00

No Discharge
----

---0.000

N/A
0.0

68.60
----

15.70
0.0

0.00
0.00

No Discharge
----

---0.000

N/A
0.0

63.42
----

2.30
0.0

0.00
0.00

No Discharge
----

---0.000

N/A
0.0

53.98
----

11.00
0.0

0.00
0.00

No Discharge
----

---0.000

N/A
0.0

62.30
----

15.70
0.0

0.00
0.00

No Discharge
----

---0.000

N/A
0.0

57.80
----

2.30
0.0

0.00
0.00

No Discharge
----

---0.000

N/A
0.0

49.62
----

11.00
0.0

0.00
0.00

101

Sprinkler
----

A
0.000

4.00
0.0

45.71
----

11.00
0.0

0.00
0.00

102

Sprinkler
----

A
0.000

4.00
0.0

45.56
----

11.00
0.0

0.00
0.00

103

Sprinkler
----

A
0.000

4.00
0.0

41.39
----

11.00
0.0

0.00
0.00

104

Sprinkler
----

A
0.000

4.00
0.0

40.26
----

11.00
0.0

0.00
0.00

105

Sprinkler
----

A
0.000

4.00
0.0

40.00
----

11.00
0.0

0.00
0.00

106

Sprinkler
----

A
0.000

4.00
0.0

40.03
----

11.00
0.0

0.00
0.00

107

Sprinkler
----

A
0.000

4.00
0.0

40.85
----

11.00
0.0

0.00
0.00

108

Sprinkler
----

A
0.000

4.00
0.0

42.45
----

11.00
0.0

0.00
0.00

201

Sprinkler
----

B
0.000

4.00
0.0

48.39
----

11.00
0.0

0.00
0.00

202

Sprinkler
----

B
0.000

4.00
0.0

49.29
----

11.00
0.0

0.00
0.00

Node
No.

Node Description
Branch Description

C:\ ...\AH-MSC001-S-001_A1.fiw

jueves, 01 de diciembre de 2016, 8:59 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 4

Fire Sprinkler Input Data


Node Input Data (cont'd)
Area Group
Branch Dia.
(in)

Sprinkler
KFactor (K)
Branch Len.
(ft)

Pressure
Estimate (psi)
Branch Stnd
Fittings

Node Elev (ft)


Branch NonStnd Fittings
(ft)

Non-Sprinkler
Flow (gpm)
Branch Sprk
KFactor (K)

Sprinkler
----

B
0.000

4.00
0.0

44.57
----

11.00
0.0

0.00
0.00

204

Sprinkler
----

B
0.000

4.00
0.0

43.22
----

11.00
0.0

0.00
0.00

205

Sprinkler
----

B
0.000

4.00
0.0

42.87
----

11.00
0.0

0.00
0.00

206

Sprinkler
----

B
0.000

4.00
0.0

42.88
----

11.00
0.0

0.00
0.00

207

Sprinkler
----

B
0.000

4.00
0.0

43.60
----

11.00
0.0

0.00
0.00

208

Sprinkler
----

B
0.000

4.00
0.0

45.14
----

11.00
0.0

0.00
0.00

Node
No.

Node Description
Branch Description

203

C:\ ...\AH-MSC001-S-001_A1.fiw

jueves, 01 de diciembre de 2016, 8:59 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 5

Fire Sprinkler Input Data


Pipe Input Data
Nominal
Diameter
(inch)

Type
Group

Fitting
Data

Nominal
Length
(feet)

Fitting
Length
(feet)

SCHED 80 CARBON
STEEL

3.000

2T

54.04

30.00

84.04

120

SCHED 80 CARBON
STEEL

2.500

E3G

18.54

49.00

67.54

120

SCHED 80 CARBON
STEEL

2.500

2ET

10.94

24.00

34.94

120

201

SCHED 80 CARBON
STEEL

1.500

6.99

8.00

14.99

120

201

208

SCHED 80 CARBON
STEEL

1.500

6.99

8.00

14.99

120

208

207

SCHED 80 CARBON
STEEL

1.500

6.99

8.00

14.99

120

207

206

SCHED 80 CARBON
STEEL

1.500

ET

11.86

12.00

23.86

120

206

205

SCHED 80 CARBON
STEEL

1.500

ET

11.86

12.00

23.86

120

205

204

SCHED 80 CARBON
STEEL

1.500

6.99

8.00

14.99

120

204

203

SCHED 80 CARBON
STEEL

1.500

6.99

8.00

14.99

120

203

202

SCHED 80 CARBON
STEEL

1.500

ET

11.86

12.00

23.86

120

202

SCHED 80 CARBON
STEEL

1.500

9.40

4.00

13.40

120

SCHED 80 CARBON
STEEL

2.500

29.27

12.00

41.27

120

SCHED 80 CARBON
STEEL

2.500

E3G

18.54

49.00

67.54

120

SCHED 80 CARBON
STEEL

2.500

ET

10.94

18.00

28.94

120

101

SCHED 80 CARBON
STEEL

1.500

2.58

8.00

10.58

120

101

108

SCHED 80 CARBON
STEEL

1.500

6.99

8.00

14.99

120

Beg.
Node

End.
Node

Pipe Description

C:\ ...\AH-MSC001-S-001_A1.fiw

Total
CFactor
Length (gpm/inch(feet)
psi)

jueves, 01 de diciembre de 2016, 8:59 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 6

Fire Sprinkler Input Data


Pipe Input Data (cont'd)
Nominal
Diameter
(inch)

Type
Group

Fitting
Data

Nominal
Length
(feet)

Fitting
Length
(feet)

SCHED 80 CARBON
STEEL

1.500

6.99

8.00

14.99

120

106

SCHED 80 CARBON
STEEL

1.500

ET

12.19

12.00

24.19

120

106

105

SCHED 80 CARBON
STEEL

1.500

ET

12.19

12.00

24.19

120

105

104

SCHED 80 CARBON
STEEL

1.500

6.99

8.00

14.99

120

104

103

SCHED 80 CARBON
STEEL

1.500

6.99

8.00

14.99

120

103

102

SCHED 80 CARBON
STEEL

1.500

ET

12.19

12.00

24.19

120

102

SCHED 80 CARBON
STEEL

1.500

9.06

4.00

13.06

120

Beg.
Node

End.
Node

Pipe Description

108

107

107

C:\ ...\AH-MSC001-S-001_A1.fiw

Total
CFactor
Length (gpm/inch(feet)
psi)

jueves, 01 de diciembre de 2016, 8:59 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 7

Fire Sprinkler Output Data


Overall Node Groupings Output Data
Pipe Segment
Beg.
End.
Node
Node

Pipe
Type
Group

Pipe
Flow Rate
(gpm)

Sprinkler Flow
At Beg. Node
(gpm)

Non-Sprinkler Flow
Out (+)
In (-)
(gpm)
(gpm)

Beg. Node
Residual
Pressure (psi)

Imbalance
Flow At Beg.
Node (gpm)

421.96

0.00

0.00

-421.96

85.16

2
2
2

1
3
5

0
0
0

-421.96
214.58
207.39

0.00

0.00

0.00

68.60

0.00000

3
3

2
4

0
0

-214.58
214.58

0.00

0.00

0.00

63.42

0.00000

4
4
4

3
201
202

0
0
0

-214.58
109.13
105.45

0.00

0.00

0.00

53.98

0.00000

5
5

2
6

0
0

-207.39
207.39

0.00

0.00

0.00

62.30

0.00000

6
6

5
7

0
0

-207.39
207.39

0.00

0.00

0.00

57.80

0.00000

7
7
7

6
101
102

0
0
0

-207.39
108.55
98.83

0.00

0.00

0.00

49.62

0.00000

101
101

7
108

0
0

-108.55
81.51

27.04

0.00

0.00

45.71

0.00000

102
102

7
103

0
0

-98.83
71.83

27.00

0.00

0.00

45.56

0.00000

103
103

102
104

0
0

-71.83
46.10

25.74

0.00

0.00

41.39

0.00000

104
104

103
105

0
0

-46.10
20.72

25.38

0.00

0.00

40.26

0.00000

105
105

104
106

0
0

-20.72
-4.58

25.30

0.00

0.00

40.00

0.00000

106
106

105
107

0
0

4.58
-29.89

25.31

0.00

0.00

40.03

0.00000

107
107

106
108

0
0

29.89
-55.45

25.56

0.00

0.00

40.85

0.00000

108
108

101
107

0
0

-81.51
55.45

26.06

0.00

0.00

42.45

0.00000

201
201

4
208

0
0

-109.13
81.30

27.82

0.00

0.00

48.39

0.00000

202

-105.45

28.08

0.00

0.00

49.29

0.00000

C:\ ...\AH-MSC001-S-001_A1.fiw

jueves, 01 de diciembre de 2016, 8:59 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 8

Fire Sprinkler Output Data


Overall Node Groupings Output Data (cont'd)
Pipe Segment
Beg.
End.
Node
Node
202
203

Pipe
Type
Group
0

Pipe
Flow Rate
(gpm)
77.37

Sprinkler Flow
At Beg. Node
(gpm)

Non-Sprinkler Flow
Out (+)
In (-)
(gpm)
(gpm)

Beg. Node
Residual
Pressure (psi)

Imbalance
Flow At Beg.
Node (gpm)

203
203

202
204

0
0

-77.37
50.66

26.71

0.00

0.00

44.57

0.00000

204
204

203
205

0
0

-50.66
24.37

26.30

0.00

0.00

43.22

0.00000

205
205

204
206

0
0

-24.37
-1.82

26.19

0.00

0.00

42.87

0.00000

206
206

205
207

0
0

1.82
-28.02

26.19

0.00

0.00

42.88

0.00000

207
207

206
208

0
0

28.02
-54.43

26.41

0.00

0.00

43.60

0.00000

208
208

201
207

0
0

-81.30
54.43

26.87

0.00

0.00

45.14

0.00000

C:\ ...\AH-MSC001-S-001_A1.fiw

jueves, 01 de diciembre de 2016, 8:59 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 9

Fire Sprinkler Output Data


Overall Pipe Output Data
Beg.
End.
Node

Nodal
KFactor
(K)

Elevation
(feet)

Spk/Hose
Discharge
(gpm)

Residual Nom. Dia.


Pressure Inside Dia.
(psi)
C-Value

q (gpm)
Q (gpm)
Velocity
(fps)

F. L./ft
(psi/ft)
Fittings
Type-Grp

Pipe-Len.
Fit-Len.
Tot-Len.
(ft)

PF-(psi)
PE-(psi)
PT-(psi)

1
2

0.00
15.70
0.00
0.00
15.70
0.00
SCHED 80 CARBON STEEL

85.16
68.60

3.00
3.068
120

0.00
421.96
18.31

0.19715
2T
0

54.04
30.00
84.04

16.568
0.000
16.568

2
3

0.00
15.70
0.00
0.00
2.30
0.00
SCHED 80 CARBON STEEL

68.60
63.42

2.50
2.469
120

0.00
214.58
14.38

0.16249
E3G
0

18.54
49.00
67.54

10.975
-5.802
5.172

2
5

0.00
15.70
0.00
0.00
15.70
0.00
SCHED 80 CARBON STEEL

68.60
62.30

2.50
2.469
120

0.00
207.39
13.90

0.15256
T
0

29.27
12.00
41.27

6.296
0.000
6.296

3
4

0.00
2.30
0.00
0.00
11.00
0.00
SCHED 80 CARBON STEEL

63.42
53.98

2.50
2.469
120

0.00
214.58
14.38

0.16249
2ET
0

10.94
24.00
34.94

5.677
3.767
9.444

4
201

0.00
11.00
0.00
4.00
11.00
27.82
SCHED 80 CARBON STEEL

53.98
48.39

1.50
1.610
120

27.82
109.13
17.20

0.37313
T
0

6.99
8.00
14.99

5.593
0.000
5.593

202
4

4.00
11.00
28.08
0.00
11.00
0.00
SCHED 80 CARBON STEEL

49.29
53.98

1.50
1.610
120

28.08
105.45
16.62

0.35021
E
0

9.40
4.00
13.40

4.693
0.000
4.693

5
6

0.00
15.70
0.00
0.00
2.30
0.00
SCHED 80 CARBON STEEL

62.30
57.80

2.50
2.469
120

0.00
207.39
13.90

0.15256
E3G
0

18.54
49.00
67.54

10.304
-5.802
4.502

6
7

0.00
2.30
0.00
0.00
11.00
0.00
SCHED 80 CARBON STEEL

57.80
49.62

2.50
2.469
120

0.00
207.39
13.90

0.15256
ET
0

10.94
18.00
28.94

4.415
3.767
8.182

7
101

0.00
11.00
0.00
4.00
11.00
27.04
SCHED 80 CARBON STEEL

49.62
45.71

1.50
1.610
120

27.04
108.55
17.11

0.36951
T
0

2.58
8.00
10.58

3.909
0.000
3.909

102
7

4.00
11.00
27.00
0.00
11.00
0.00
SCHED 80 CARBON STEEL

45.56
49.62

1.50
1.610
120

27.00
98.83
15.58

0.31064
E
0

9.06
4.00
13.06

4.057
0.000
4.057

101
108

4.00
11.00
27.04
4.00
11.00
26.06
SCHED 80 CARBON STEEL

45.71
42.45

1.50
1.610
120

26.06
81.51
12.85

0.21748
T
0

6.99
8.00
14.99

3.260
0.000
3.260

103
102

4.00
11.00
25.74
4.00
11.00
27.00
SCHED 80 CARBON STEEL

41.39
45.56

1.50
1.610
120

25.74
71.83
11.32

0.17214
ET
0

12.19
12.00
24.19

4.164
0.000
4.164

C:\ ...\AH-MSC001-S-001_A1.fiw

jueves, 01 de diciembre de 2016, 8:59 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 10

Fire Sprinkler Output Data


Overall Pipe Output Data (cont'd)
Beg.
End.
Node

Nodal
KFactor
(K)

Elevation
(feet)

Spk/Hose
Discharge
(gpm)

Residual Nom. Dia.


Pressure Inside Dia.
(psi)
C-Value

q (gpm)
Q (gpm)
Velocity
(fps)

F. L./ft
(psi/ft)
Fittings
Type-Grp

Pipe-Len.
Fit-Len.
Tot-Len.
(ft)

PF-(psi)
PE-(psi)
PT-(psi)

104
103

4.00
11.00
25.38
4.00
11.00
25.74
SCHED 80 CARBON STEEL

40.26
41.39

1.50
1.610
120

25.38
46.10
7.26

0.07577
T
0

6.99
8.00
14.99

1.136
0.000
1.136

105
104

4.00
11.00
25.30
4.00
11.00
25.38
SCHED 80 CARBON STEEL

40.00
40.26

1.50
1.610
120

20.72
20.72
3.27

0.01725
T
0

6.99
8.00
14.99

0.259
0.000
0.259

106
105

4.00
11.00
25.31
4.00
11.00
25.30
SCHED 80 CARBON STEEL

40.03
40.00

1.50
1.610
120

4.58
4.58
0.72

0.00106
ET
0

12.19
12.00
24.19

0.026
0.000
0.026

107
106

4.00
11.00
25.56
4.00
11.00
25.31
SCHED 80 CARBON STEEL

40.85
40.03

1.50
1.610
120

25.31
29.89
4.71

0.03398
ET
0

12.19
12.00
24.19

0.822
0.000
0.822

108
107

4.00
11.00
26.06
4.00
11.00
25.56
SCHED 80 CARBON STEEL

42.45
40.85

1.50
1.610
120

25.56
55.45
8.74

0.10663
T
0

6.99
8.00
14.99

1.598
0.000
1.598

201
208

4.00
11.00
27.82
4.00
11.00
26.87
SCHED 80 CARBON STEEL

48.39
45.14

1.50
1.610
120

26.87
81.30
12.81

0.21646
T
0

6.99
8.00
14.99

3.245
0.000
3.245

203
202

4.00
11.00
26.71
4.00
11.00
28.08
SCHED 80 CARBON STEEL

44.57
49.29

1.50
1.610
120

26.71
77.37
12.19

0.19748
ET
0

11.86
12.00
23.86

4.712
0.000
4.712

204
203

4.00
11.00
26.30
4.00
11.00
26.71
SCHED 80 CARBON STEEL

43.22
44.57

1.50
1.610
120

26.30
50.66
7.98

0.09023
T
0

6.99
8.00
14.99

1.352
0.000
1.352

205
204

4.00
11.00
26.19
4.00
11.00
26.30
SCHED 80 CARBON STEEL

42.87
43.22

1.50
1.610
120

24.37
24.37
3.84

0.02329
T
0

6.99
8.00
14.99

0.349
0.000
0.349

206
205

4.00
11.00
26.19
4.00
11.00
26.19
SCHED 80 CARBON STEEL

42.88
42.87

1.50
1.610
120

1.82
1.82
0.29

0.00019
ET
0

11.86
12.00
23.86

0.005
0.000
0.005

207
206

4.00
11.00
26.41
4.00
11.00
26.19
SCHED 80 CARBON STEEL

43.60
42.88

1.50
1.610
120

26.19
28.02
4.42

0.03015
ET
0

11.86
12.00
23.86

0.719
0.000
0.719

208
207

4.00
11.00
26.87
4.00
11.00
26.41
SCHED 80 CARBON STEEL

45.14
43.60

1.50
1.610
120

26.41
54.43
8.58

0.10302
T
0

6.99
8.00
14.99

1.544
0.000
1.544

C:\ ...\AH-MSC001-S-001_A1.fiw

jueves, 01 de diciembre de 2016, 8:59 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 11

Fire Sprinkler Output Data


Overall Sprinkler Output Data
Flowing
Sprinkler
Node No.

Sprinkler
KFactor (K)

Sprinkler
Elevation
(feet)

101
A
102
A
103
A
104
A
105
A
106
A
107
A
108
A
Sub Totals For Group A

4.00
4.00
4.00
4.00
4.00
4.00
4.00
4.00

11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00

45.71
45.56
41.39
40.26
40.00
40.03
40.85
42.45

201
B
202
B
203
B
204
B
205
B
206
B
207
B
208
B
Sub Totals For Group B

4.00
4.00
4.00
4.00
4.00
4.00
4.00
4.00

11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00

48.39
49.29
44.57
43.22
42.87
42.88
43.60
45.14

Area Group
Code

Totals For All Groups

C:\ ...\AH-MSC001-S-001_A1.fiw

Residual
Flowing Area
Pressure
(ft)
(psi)

Flowing
Density
(gpm/ft)

Sprinkler
Discharge
(gpm)

50.00
50.00
50.00
50.00
50.00
50.00
50.00
50.00
400.00

0.541
0.540
0.515
0.508
0.506
0.506
0.511
0.521
0.518

27.04
27.00
25.74
25.38
25.30
25.31
25.56
26.06
207.39

50.00
50.00
50.00
50.00
50.00
50.00
50.00
50.00
400.00

0.556
0.562
0.534
0.526
0.524
0.524
0.528
0.537
0.536

27.82
28.08
26.71
26.30
26.19
26.19
26.41
26.87
214.58

800.00

0.527

421.96

jueves, 01 de diciembre de 2016, 8:59 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 12

Fire Sprinkler Output Summary


Hydraulically Most Demanding Sprinkler Node
HMD Sprinkler Node Number:
HMD Actual Residual Pressure:
HMD Actual GPM:

105
40.00 psi
25.30 gpm

Sprinkler Summary
Sprinkler System Type:
Specified Area Of Application:
Adjusted Area Of Application:
Minimum Desired Density:
Application Average Density:
Application Adjusted Density (not required by NFPA 13):
Application Average Area Per Sprinkler:
Adjusted Area Per Sprinkler (not required by NFPA 13):
Sprinkler Flow:
Average Sprinkler Flow:

Dry
50.00
65.00
0.500
8.439
6.492
3.13
4.06
421.96
26.37

ft
ft
gpm/ft
gpm/ft
gpm/ft
ft
ft
gpm
gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 2 - 1 )
Maximum Velocity Pressure ( In Pipe 2 - 1 )
Allowable Maximum Nodal Pressure Imbalance:
Actual Maximum Nodal Pressure Imbalance:
Actual Average Nodal Pressure Imbalance:
Actual Maximum Nodal Flow Imbalance:
Actual Average Nodal Flow Imbalance:

18.31 ft/sec
2.26 psi
0.0100
0.0000
0.0000
0.0000
0.0000

psi
psi
psi
gpm
gpm

Overall Network Summary


Number Of Unique Pipe Sections:
Number Of Flowing Sprinklers:
Pipe System Water Volume:
Sprinkler Flow:
Non-Sprinkler Flow:
Demand Flow Excluding Exterior Hose Flow:
Exterior Hose Flow:
Minimum Required Residual Pressure At System Inflow
Node:
Demand Flow At System Inflow Node:

C:\ ...\AH-MSC001-S-001_A1.fiw

24
16
59.21 gal
421.96
0.00
421.96
350.00

gpm
gpm
gpm
gpm

85.16 psi
771.96 gpm

jueves, 01 de diciembre de 2016, 8:59 p.m.

Fire - Fire Sprinkler Hydraulics Calculation Program


Gpo Prof Planeacion y Proyectos
Naucalpan, MEX 53390

Elite Software Development, Inc.


ANALISIS HIDRAULICO CALDERAS 1 Y 2
Page 13

Fire Sprinkler Output Data


Hydraulic Supply/Demand Graph

100
90

85

80

P re ssu re p si

70
60
50
40
30
20
10
0

10

Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 85.16 psi
Calculated Flow Rate: 771.96 gpm
Exterior Hose Flow: 350.00 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 0.00 psi

C:\ ...\AH-MSC001-S-001_A1.fiw

jueves, 01 de diciembre de 2016, 8:59 p.m.

Vous aimerez peut-être aussi