These are Robust Detail constructions that utilise British Gypsum products where appropriate. All Robust
Details have been approved as capable of meeting or exceeding the E1 performance criteria, providing they
are built correctly. Following these specifications means you can be exempt from undertaking Pre-Completion
Testing on a 10% (by type) sample of units built. The Robust Detail scheme applies to new-build houses and
apartments only. Plots must be registered with Robust Details Limited prior to construction.
- NEW-BUILD
These constructions are British Gypsum Approved Systems, which, provided they are built correctly, have
the potential to achieve or exceed E1 performance criteria required for new-build houses and apartment
separating floor constructions and new-build rooms for residential purposes. Pre-Completion Testing must
be executed on a 10% sample (by type) to demonstrate compliance.
32 - 37
These constructions are British Gypsum Approved Systems which, provided they are built correctly, have the
potential to achieve or exceed E1 performance criteria required for separating floor constructions created by
material change of use or conversion. Pre-Completion Testing must be executed on a 10% sample (by type) to
demonstrate compliance. They also include constructions for Test and Declare scenario.
GUIDANCE CONSTRUCTIONS
20 - 31
Separating walls
ROBUST DETAILS
38 - 41
These constructions are British Gypsum versions of Approved Document E Guidance Constructions, which,
provided they are built correctly, are deemed to achieve the new E1 performance criteria.
Pre-Completion Testing must be executed on a 10% sample (by type) to demonstrate compliance.
42 - 45
Within category 7 of the Code for Sustainable Homes, Health and Wellbeing,
section Hea 2 states that up to four credits are available for achieving higher
standards of sound insulation than those given in Building Regulations
Approved Document E and demonstrating it by using either Pre-Completion
Testing or Robust Details. British Gypsum separating wall solutions can be
specified to achieve enhanced sound insulating performance. This stamp
highlights construction details which have the potential to achieve the number
of credits stated, provided they are built correctly.
19
Page
Detail
No.
Page
12
27
13
28
14
28
21
21
23
23
24
15
29
24
16
29
25
25
17
30
26
18
30
10
26
19
31
11
27
20
31
Timber
Detail
No.
Page
Steel
Detail
No.
Page
Key points
Specifying Robust Details avoids the need for Pre-Completion Testing.
Check compatibility of the separating floor with the separating wall. Please refer to page 15 for further information.
Register each plot with Robust Details Limited prior to construction.
www.british-gypsum.com/residential
20
SOUND
RD
GREEN
GUIDE
SOUND
RD
GREEN
GUIDE
email: bgtechnical.enquiries@bpb.com
www.british-gypsum.com/residential
21
Undercoat plasters
Background suction
Pre-treatment
Background
High
Aircrete blocks
Thistle
Bonding Coat
Thistle
Browning
Thistle
Hardwall
Thistle
Tough Coat
For smooth,
low suction
or flexible
backgrounds.
For bricks
and blocks
with moderate
suction.
backgrounds. Can be
Thistle GypPrime in
extreme cases
needed
Lightweight
blocks, e.g. E-WM-2
Dense blocks,
Medium
e.g. E-WM-1
If ThistleBond-it
If ThistleBond-it
If ThistleBond-it
is used
is not used
is not used
Keyed
Smooth
ThistleBond-it needed
(e.g. paint-grade)
if low suction
Metal lathing
Normal ballast
pre-cast concrete
ThistleBond-it usually
required (unless keyed)
Other aggregates
ThistleBond-it
Low
Normal thickness
Thickness recommendations
When using a bonding agent, do not
exceed the thickness given. For other
systems used on walls, if thicknesses in
excess of the recommendation is
Setting time
Coverage
1.5 - 2hrs
2.75m at 11mm
3.5m at 11mm
1.5 - 2hrs
2
sprayed
sprayed
Approx. water
requirement
1.5 - 2hrs
2
12.1kg/m2 at
8.4kg/m2 at
9.3kg/m2 at
8.5kg/m2 at
11mm plus
11mm plus
11mm plus
11mm plus
3.4kg/m2
3.4kg/m2
3.4kg/m2
3.4kg/m2
finish plaster
finish plaster
finish plaster
finish plaster
Thistle Durafinish is a gypsum finish plaster that may be used on a wide range of backgrounds,
Finish plasters
including most undercoat plasters, and to enhance the surface damage resistance of any
British Gypsum partition or wall lining system. It is particularly suited to social housing
applications where occupancy turnover is high. Thistle Durafinish has excellent resistance to
glancing impacts and repeated abrasion, typical of the accidental damage which causes scratching,
gouging or chipping of other wall finishes. This can extend the intervals between maintenance,
helping to reduce costs and maximise the occupiers use of the building. Thistle Durafinish has
Thistle Multi-Finish
Thistle Durafinish
A versatile final
coat plaster for
a wide range of
backgrounds
For improved
resistance to
accidental
damage
similar working characteristics, setting time and suction resistance to Thistle Multi-Finish.
1.5hrs
1.5hrs
2C
2C
10m2
10m2
3.4kg/m2 at 2mm
3.4kg/m2 at 2mm
www.british-gypsum.com/residential
22
SOUND
GREEN
GUIDE
RD
SOUND
RD
GREEN
GUIDE
email: bgtechnical.enquiries@bpb.com
www.british-gypsum.com/residential
23
RD
GREEN
GUIDE
SOUND
RD
GREEN
GUIDE
C1
www.british-gypsum.com/residential
24
SOUND
RD
GREEN
GUIDE
SOUND
GREEN
GUIDE
RD
1 Sand / cement render may shrink on drying, usually with some cracking,
which can appear several days after application. Therefore, care must be taken
to ensure full drying is complete before drylining.
email: bgtechnical.enquiries@bpb.com
www.british-gypsum.com/residential
25
SOUND
RD
10
GREEN
GUIDE
SOUND
B1
RD
GREEN
GUIDE
www.british-gypsum.com/residential
26
SOUND
RD
12
GREEN
GUIDE
SOUND
RD
GREEN
GUIDE
B1
11
email: bgtechnical.enquiries@bpb.com
www.british-gypsum.com/residential
27
13
RD
GREEN
GUIDE
SOUND
RD
GREEN
GUIDE
www.british-gypsum.com/residential
28
14
SOUND
RD
FIRE
Min.
60 mins BS
GREEN
GUIDE
A+
16
SOUND
RD
FIRE
Min.
60 mins BS
GREEN
GUIDE
A+ or A1
Board options:
Inner layer of 19mm Gyproc Plank,
outer layer of 12.5mm Gyproc WallBoard each side,
or Double layer of 15mm Gyproc SoundBloc each side,
or Double layer of 15mm Gyproc FireLine each side,
or Inner layer of 19mm Gyproc Plank,
outer layer of 12.5mm Gyproc FireLine each side
15
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used and the companys fixing
recommendations are strictly observed. Any variation in the specifications should be
checked with Robust Details Limited.Based on 80% Load Ratio.
Refer to flanking details pages 163 - 166
email: bgtechnical.enquiries@bpb.com
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used and the companys fixing
recommendations are strictly observed. Any variation in the specifications should be
checked with Robust Details Limited.Based on 80% Load Ratio.
Refer to flanking details pages 163 - 166
www.british-gypsum.com/residential
29
17
18
SOUND
RD
FIRE
Min.
60 mins BS1
GREEN
GUIDE
SOUND
RD
FIRE
Min.
90 mins BS
GREEN
GUIDE
HEIGHTS
Max. 3900mm at 600mm
centres using Gypframe
60 I 70 I Studs
PSR A216007
Board options:
Double layer of 15mm Gyproc SoundBloc each side
(for 90 minutes BS and EN fire resistance)
or
Double layer of 15mm Gyproc SoundBloc each
side overboarded with one layer of 12.5mm
Gyproc FireLine each side (for 120 minutes BS and EN
fire resistance)
Board options:
Inner layer of 19mm Gyproc Plank,
outer layer of 12.5mm Gyproc WallBoard each side,
or
Double layer of 15mm Gyproc SoundBloc each side.
www.british-gypsum.com/residential
30
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used , and the companys fixing
recommendations are strictly observed. Any variation in the specifications should be
checked with Robust Details Limited.
Refer to flanking details pages 172 - 176
SOUND
RD
FIRE
60 mins
1
BS
GREEN
GUIDE
B or C2
20
SOUND
RD
FIRE
GREEN
GUIDE
60 mins
1
BS
19
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used , and the companys fixing
recommendations are strictly observed. Any variation in the specifications should be
checked with Robust Details Limited.
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used , and the companys fixing
recommendations are strictly observed. Any variation in the specifications should be
checked with Robust Details Limited.
email: bgtechnical.enquiries@bpb.com
www.british-gypsum.com/residential
31
Page
Detail
No.
Page
21
33
27
GypWall QUIET SF
36
22
33
28
36
23
GypWall QUIET
34
29
37
24
GypWall QUIET
34
Masonry
Detail
No.
25
GypWall QUIET SF
35
26
35
30
Page
37
Key points
Specification tips
www.british-gypsum.com/residential
32
22
PRE-COMPLETION TESTING
PRE-COMPLETION TESTING
- NEW-BUILD
56 dB
Rw + Ctr
FIRE
90 mins BS
- NEW-BUILD
SOUND
HEIGHTS
SOUND
FIRE
57 dB
Rw + Ctr
Max. 8100mm at
600mm centres
90 mins BS
HEIGHTS
Max. 8100mm at
600mm centres
PSR A206A255
PSR A206A243
Alternatively:
Alternatively:
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used throughout, and the companys
fixing recommendations are strictly observed. Any variation in the specifications should
be checked with British Gypsum.
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used throughout, and the companys
fixing recommendations are strictly observed. Any variation in the specifications should
be checked with British Gypsum.
email: bgtechnical.enquiries@bpb.com
21
www.british-gypsum.com/residential
33
23
24
GypWall QUIET
PRE-COMPLETION TESTING
- NEW-BUILD
PRE-COMPLETION TESTING
SOUND
53 dB
Rw + Ctr
FIRE
90 mins BS
GypWall QUIET
- NEW-BUILD
HEIGHTS
SOUND
57 dB
Rw + Ctr
PSR A216009
PSR A216010
FIRE
90 mins BS
HEIGHTS
Max. 7500mm at 600mm
centres, cross-braced at
1200mm centres
PSR A216011
Alternatively:
Lined with a double layer of 15mm Gyproc FireLine
for 120 minutes fire resistance
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used throughout, and the companys
fixing recommendations are strictly observed. Any variation in the specifications should
be checked with British Gypsum.
www.british-gypsum.com/residential
34
Alternatively:
Lined with a double layer of 15mm Gyproc DuraLine
for 120 minutes fire resistance
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used throughout, and the companys
fixing recommendations are strictly observed. Any variation in the specifications should
be checked with British Gypsum.
26
PRE-COMPLETION TESTING
PRE-COMPLETION TESTING
- NEW-BUILD
FIRE
54 dB
Rw + Ctr
90 mins BS
- NEW-BUILD
SOUND
GypWall QUIET SF
with additional
service zone created with
GypLyner UNIVERSAL
HEIGHTS
Max. 4200mm at
600mm centres
FIRE
SOUND
54 dB
Rw + Ctr
90 mins BS
HEIGHTS
Max. 4200mm at
600mm centres
PSR A316009
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used throughout, and the companys
fixing recommendations are strictly observed. Any variation in the specifications should
be checked with British Gypsum.
Refer to flanking details pages 177 - 179
email: bgtechnical.enquiries@bpb.com
25
GypWall QUIET SF
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used throughout, and the companys
fixing recommendations are strictly observed. Any variation in the specifications should
be checked with British Gypsum.
Refer to flanking details pages 177 - 179
www.british-gypsum.com/residential
35
27
28
GypWall QUIET SF
PRE-COMPLETION TESTING
PRE-COMPLETION TESTING
- NEW-BUILD
53 dB
Rw + Ctr
FIRE
120 mins BS
HEIGHTS
Max. 4200mm at
600mm centres
PSR Q606040
SOUND
58 dB
Rw + Ctr
FIRE
90 mins BS
HEIGHTS
Max. 2800mm at
600mm centres
PSR A216014
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used throughout, and the companys
fixing recommendations are strictly observed. Any variation in the specifications should
be checked with British Gypsum.
www.british-gypsum.com/residential
36
- NEW-BUILD
SOUND
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled, or
skimmed according to British Gypsums recommendations. The quoted performances
are achieved only if British Gypsum components are used throughout, and the companys
fixing recommendations are strictly observed. Any variation in the specifications should
be checked with British Gypsum.
Refer to flanking details pages 172 - 176
30
PRE-COMPLETION TESTING
- NEW-BUILD
PRE-COMPLETION TESTING
SOUND
62 dB
Rw + Ctr
FIRE
90 mins BS
- NEW-BUILD
SOUND
HEIGHTS
59 dB
Rw + Ctr
Max. 3300mm at
600mm centres
PSR B226005
PSR A216013
29
email: bgtechnical.enquiries@bpb.com
www.british-gypsum.com/residential
37
Steel
Detail
No.
Timber
Page
Detail
No.
34
31
GypWall CLASSIC
39
32
GypWall QUIET SF
39
Page
Timber stud and Gypframe RB1
Resillient Bar
Masonry
Detail
No.
33
40
40
Page
35
41
36
41
Specification tips
When using systems incorporating Gypframe RB1 Resilient Bar, ensure lining board fixings are suitably
positioned and of the appropriate length to avoid contact with the framing sections behind the Gypframe
RB1 Resilient Bars.
When installing Isover insulation, ensure that the insulation covers the whole wall area without gaps. Particular
care should be taken to ensure correct installation.
Where service penetrations are unavoidable, including light switches and socket box installations, ensure
the correct detailing is followed to prevent loss of acoustic, fire and air leakage performance.
Always stagger joints in wall linings to avoid air paths which will allow the transmission of sound.
Key points
All conversion specifications are suitable for rooms designed for residential purpose, for example, hotels
and student accommodation.
Pre-Completion Testing is required when specifying British Gypsum Approved Systems.
Flanking details should be fully considered during the design and construction process.
www.british-gypsum.com/residential
38
32
PRE-COMPLETION TESTING
PRE-COMPLETION TESTING
- CONVERSIONS
53 dB
Rw + Ctr
FIRE
90 mins BS
- CONVERSIONS
SOUND
GypWall QUIET SF
HEIGHTS
SOUND
53 dB
Rw + Ctr
Max. 4000mm at
600mm centres
FIRE
60 mins BS
HEIGHTS
Max. 4000mm at
600mm centres
PSR A316008
PSR A206243
31
GypWall CLASSIC
Alternatively:
Lined with a double layer of 15mm
Gyproc DuraLine for 120 minutes fire resistance
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled,
or skimmed according to British Gypsums recommendations. The quoted
performances are achieved only if British Gypsum components are used throughout,
and the companys fixing recommendations are strictly observed. Any variation in the
specifications should be checked with British Gypsum.
email: bgtechnical.enquiries@bpb.com
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled,
or skimmed according to British Gypsums recommendations. The quoted
performances are achieved only if British Gypsum components are used throughout,
and the companys fixing recommendations are strictly observed. Any variation in the
specifications should be checked with British Gypsum.
Refer to flanking details pages 177 - 179
www.british-gypsum.com/residential
39
33
34
PRE-COMPLETION TESTING
- CONVERSIONS
PRE-COMPLETION TESTING
SOUND
52 dB
Rw + Ctr
FIRE
120 mins
- CONVERSIONS
SOUND
HEIGHTS
2800mm at 600mm
centres using 48mm
Gypframe I Studs1
51 dB
Rw + Ctr
FIRE
90 mins BS
PSR A046007
PSR A216006
1 For other stud sizes / maximum heights, contact the British Gypsum
Drywall Academy.
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled,
or skimmed according to British Gypsums recommendations. The quoted
performances are achieved only if British Gypsum components are used throughout,
and the companys fixing recommendations are strictly observed. Any variation in the
specifications should be checked with British Gypsum.
Refer to flanking details pages 172 - 176
www.british-gypsum.com/residential
40
NB For existing timber stud, partitions lined with lath and plaster, this specification
could be used after complete removal of the lath and plaster. If the lath and plaster is
in good condition then it could remain in place on the non-resilient bar side, with the
double layer 15mm Gyproc SoundBloc screw-fixed through the lath and plaster into
the timber framing.
NB The fire resistance and sound insulation performance are for imperforate
partitions, walls and ceilings incorporating boards with all joints taped and filled,
or skimmed according to British Gypsums recommendations. The quoted
performances are achieved only if British Gypsum components are used throughout,
and the companys fixing recommendations are strictly observed. Any variation in the
specifications should be checked with British Gypsum.
Refer to flanking details pages 177 - 179
36
PRE-COMPLETION TESTING
- CONVERSIONS
PRE-COMPLETION TESTING
- CONVERSIONS
SOUND
SOUND
53 dB
Rw + Ctr
PSR B160018
55 dB
Rw + Ctr
PSR B226003
email: bgtechnical.enquiries@bpb.com
35
www.british-gypsum.com/residential
41
Masonry
Detail
No.
Page
37
43
38
43
39
44
40
44
41
45
Key points
Flanking details should be fully considered during the design and construction process.
Pre-Completion Testing is required when specifying Approved Document E Guidance Constructions.
When installing Isover insulation, ensure that the insulation covers the whole wall area without gaps.
Particular care should be taken to ensure correct installation.
Where service penetrations are unavoidable, including light switches and socket boxes, etc.
Ensure the correct detailing is followed to prevent loss of acoustic, fire and air leakage performance.
Always stagger joints in wall linings to avoid air paths which will allow the transmission of sound.
For masonry constructions, ensure all blockwork joints are fully filled with mortar.
www.british-gypsum.com/residential
42
SOUND
38
Lightweight aggregate
cavity masonry
(wall type 2.2)
GREEN
GUIDE
Guidance
Construction
SOUND
GREEN
GUIDE
Guidance
Construction
email: bgtechnical.enquiries@bpb.com
37
www.british-gypsum.com/residential
43
39
40
Masonry between
independent panels
(wall type 3.1) with
GypLyner IWL
SOUND
Guidance
Construction
Solid masonry
(wall type 1)
GREEN
GUIDE
SOUND
Guidance
Construction
GREEN
GUIDE
www.british-gypsum.com/residential
44
41
SOUND
Guidance
Construction
GREEN
GUIDE
A+
email: bgtechnical.enquiries@bpb.com
1
www.british-gypsum.com/residential
45