Content
Standard: Northern Ireland Electricity (NIE), 6/025 ENA
Code: Indian Electricity Rules / Central Electricity Authority
1. Right of Way Clearance (As per GETCO Standard)
2. Minimum clearances between Electrical Lines crossing each other
3. Permissible Min ground Clearance of Electrical Line
4. Clearance for Telephone line Crossings Power Line
5. Vertical Clearance between Electrical Line and railway tracks
6. Clearance from Buildings to low, medium & high voltage lines
Min ROW
66 KV
18 Meter
132 KV
27 Meter
220 KV
35 Meter
400KV
400 KV
Go to Content
66 KV
132 KV
220 KV
400 KV
66 KV
2.4 Meter
3 Meter
4.5 Meter
5.4 Meter
132 KV
3 Meter
3 Meter
4.5 Meter
5.4 Meter
220 KV
4.5 Meter
4.5 Meter
4.5 Meter
5.4 Meter
400 KV
4.5 Meter
5.4 Meter
5.4 Meter
5.4 Meter
Go to Content
Ground Clearance
66 KV
6.1 Meter
8.0 Meter
132 KV
6.1 Meter
8.6 Meter
220 KV
7.0 Meter
9.8 Meter
400KV
8.8 Meter
10.8 Meter
Go to Content
Clearance (Min)
66 KV
2.4 Meter
132 KV
2.7 Meter
220 KV
3.0 Meter
Go to Content
Clearance (Min)
66 KV
14 Meter
132 KV
14.6 Meter
220 KV
15.4 Meter
400 KV
17.9 Meter
Go to Content
Description
Distance
Low &
Medium
Voltage
Flat roof, open balcony, verandah roof ,When the line passes above the
building a vertical clearance from the highest point
2.5 Meter
Low &
Medium
Voltage
1.2 Meter
Low &
Medium
Voltage
2.5 Meter
Low &
Medium
Voltage
1.2 Meter
11 KV to 33
KV
3.7 Meter
Above 33
KV
Up to 11 KV
The horizontal clearance between the nearer conductor and any part of
such building
1.2 Meter
11 KV to 33
KV
The horizontal clearance between the nearer conductor and any part of
such building
2.0 Meter
Above 33
KV
The horizontal clearance between the nearer conductor and any part
ofsuch building
Go to Content
Description
Distance
Across a street
5.8 Meter
High Voltage
Across a street
6.1 Meter
Along a street
5.5 Meter
High Voltage
Along a street
5.8 Meter
4.0 Meter
High Voltage
5.2 Meter
33 KV & EHV
Min 6.1
Meter
Go to Content
200 Meter
4.0 Meter
300 Meter
5.5 Meter
400 Meter
7.0 Meter
500 Meter
8.5 Meter
Go to Content
12 KV
2.6 Meter
36 KV
2.8 Meter
72.5 KV
3.1 Meter
145 KV
3.7 Meter
220 KV
4.3 Meter
400KV
6.4 Meter
800 KV
10.3 Meter
Go to Content
Min. Distance
Go to Content
214V to 415
KV
11KV
33KV
66KV
132KV
275KV
1.3 Meter
2.0
Meter
3.0
Meter
4.0
Meter
5.0 Meter
6.0 Meter
3.0 Meter
3.0
Meter
3.0
Meter
4.0
Meter
5.0 Meter
6.0 Meter
Go to Content