Académique Documents
Professionnel Documents
Culture Documents
Fire Alarm Devices - Intelligent Four, Six, Eight Loop Control Panel
Features
8 x Loops (242) capacity (1936) addressable points
Max 10 Loops Standalone
Comply with EN54 and UL864
Modular constructed for future expansion
40 x15 lines Colour Graphical LCD Display.
Up to 999 programmable zones and 140 Zone indication
Networked with all SHIELD Intelligent Fire panels up to 64
Nodes, Optional Fiber Optic and LAN Network Interface.
RS 485 mimic and repeater output up 64
RS 232-USB CRT interface, including P-CGS graphic
Online/Offline Programmable form PC
History record-999 fire incident only and 999 event capacity in
non-volatile memory
Walk Test Function with optional silent mode
Fully simulation of Cause and Effect
Advanced user friendly programming software including
Fuzzy Logic.
Built in Fire Alarm, FPE, Fault and Alarm Router output
Auto Programming Day and Night Mode
Enable and Disable function
Pre-Alarm and Acknowledge Function
Duplicate address checking
Device mismatch
Dirty Detector Reporting
Panel Printer included
Description
The P-A8M is an intelligent fire alarm control panel. Flush-mounted type housing it provides the perfect
solution for all medium to large system by utilizing advance SHIELD Protocol. The system is compatible with
the complete range of SHIELD Intelligent detectors, Sounders, Call Points, and Interfaces, including
intrinsically safe and gaseous extinguishing control. P-A8M is manufactured and certified to EN54 parts 2 and
4 and to BS5839 Part 4. The SHIELD programming facilities enables advanced and complex cause and
effects to be programmed with ease, including phased and cascade evacuation scenarios. The SHIELD zone
indication and control facilities allow the operator to manually intervene, with evacuation and control of each
zone including control of all plant equipment under an alarm condition. Gas release control monitoring are
built in as standard.
By utilizing the SHIELD protocol the P-A8M can be networked with up to 99 panels, making this the perfect
solution for large decentralized systems such as Shopping Centers Military campus industrial complexes, Holiday
villages etc. With up to 1936 two-wire fire alarm linkage control points that can also be intelligent be connected
with many serial products (ex. digital detector, analogue detector, intelligent detector, control module and multiwire control panel)
Ordering Information
Part No
P-A8M
LC-A8M
DB-A8M
NB-A8M
NB-A8MA
RB-A8M
Description
Intelligent Modular 8 Loops Fire Alarm Control Panel
Dual Loop Card
Compatible with USB and Serial Port, RS 232 Communication Card for System
Commissioning and GMC connection
RS 485 Network Card, Serial Connection (Class B) 1.2 Km Range
RS 485 Network Card, Serial Connection (Class A) 1.2 Km between Panels
RS 485 Repeater Board
Pack Qty
per Box
1
1
1
1
1
1
WWW.SHIELDGLOBAL.COM
Board Diagram
24V
GND 24V
B
A
EOL
4.7Kohms
EOL
4.7Kohms
O/P
Sounder with
built-in diode
EOL
4.7Kohms
O/P
Sounder with
built-in diode
EOL
4.7Kohms
FPE
FPE with
fitted diode
I+
I-
B2
A
I-
I+
XT10
O+
LOOP 10
O-
XT10
O+
LOOP 10
O-
A1
B1
A2
O-
I+
XT1
O+
LOOP 01
FPE
+
REPEATER
FEED
BACK
F2 F1
Output to Repeater or
Mimic Panel
I-
GND 5V TX RX
XT1
LOOP BOARD
A
Fitted
470 ohms
XT18
XS7
XT2
XS14
XT3
XT4
LOOP BOARD
ALARM
XT14
XS6
XT5
XS13
XT6
LOOP BOARD
XT19
XT9
XT8
XS5
XT7
+5V GND
LOOP BOARD
XS12
XT13
XS4
XT10
XS11
XT12
XT11
LOOP BOARD
LOOP 01 LOOP 02 LOOP 03 LOOP 04 LOOP 05 LOOP 06 LOOP 07 LOOP 08 LOOP 09 LOOP 10
O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ OI+ II+ II+ II+ II+ II+ II+ II+ II+ II+ I-
TO MAINBOARD
XS3
SOUNDER ROUTING
XS15
COM BOARD
XS10
OUTPUT TO
XS2
XS9
COM BOARD
FAULT
OUTPUT
NO COM NC
XS1
OUTPUT
F7.820.1238V2
TO FPE
XS8
Loop In
In from last device
Dimension
WWW.SHIELDGLOBAL.COM
Technical Specifications