Title:
AIC:
Document Nr-Rev:
50021275 -0.0
Table of contents
1
Introduction .............................................................................................................3
1.1
1.2
1.3
2.1
2.2
2.3
2.4
2.5
2.6
2.7
Labelling plates.......................................................................................................8
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
Fuses ......................................................................................................................10
Current transformers............................................................................................... 10
Voltage transformers............................................................................................... 11
Protection relays .....................................................................................................11
Circuit breakers.......................................................................................................11
Selector switches ....................................................................................................11
Panels.....................................................................................................................11
Anti-condensation heaters ......................................................................................11
Page 2 of 11
Title:
AIC:
Document Nr-Rev:
Introduction
1.1
The purpose of this specification is to define the marking of electrical, instrumentation, and
control components including: connecting boxes, cables, cubicles, wiring inside cubicle,
measurements, and control and regulation components.
This specification is based on "Kraftwerk-Kennzeichensystem (KKS)" system which shall be
complied with. The application of the KKS system is defined in the following sections.
The KKS of the main equipment shall be obtained from HZI P&IDs and single line diagram.
All labels shall be in English.
Note: Notwithstanding the above, the wiring and labelling of internal components of
switchboards and control boards must be in accordance with BS EN 61439. Furthermore,
all safety signage shall be in accordance with the norms, standards, and regulations,
specified in the TSD.
The labels shall be approved by HZI and shall match the designations in the mechanical
and electrical schematic diagrams.
Equipment shall have only one designation unless specific permission is obtained from the
employer.
When a wire numbering system is used it should be in accordance with a recognised
marking system or with a functional marking system or as specified elsewhere
1.2
Long term
HZI
Supplier
HZI's contractor
Sub-contractor
TII
TSD
PED
DIN
EN
European Norm
BS
British Standards
IEC
Numerical character
Alphabetical character
SLD
Page 3 of 11
Title:
AIC:
1.3
Document Nr-Rev:
50021275 -0.0
Page 4 of 11
Title:
AIC:
Document Nr-Rev:
KKS marking
2.1
General rules
All components shall be labeled according to KKS-manual for the plant based on the KKS
standard.
One marking system is defined for the process. It organises the different systems and
groups of equipment in relation with their function in different categories such as
mechanicals, civil works, electricity, control command and instrumentation.
The marking in relation with the process is composed of two categories:
2.2
System label
Component label
AK
10 - 15 kV components
AQ
AR
AS
AU
Example:
0 AEA01
2.3
11 kV/400 V transformer
BH
BR
BT
Batteries
BU
DC power
BV
UPS 1
BW
UPS 2
BX
The number of the main electrical components shall be found on the Single Line Diagram
(Doc. No. DEI-HZI-50021335).
Page 5 of 11
Title:
AIC:
2.4
Document Nr-Rev:
Controller cabinet
2.5
BBA01
Hyphen
01
Level
Destination
Voltage >1 kV
see Table 1
1 digit
Sequential cable
number
2 digit
The number of the main electrical components shall be found on the Single Line Diagram
(Doc. No. 50021335).
Level: 0 for commons, 1 for line 1, 2 for line 2.
Cables shall be labelled on either side of wall or panel penetration.
2.6
HJY20 GH501
Hyphen
01
Level
Destination
Voltage <1 kV
see Table 1
1 digit
Sequential cable
number
2 digit
Main KKS number for motors, local cabinet of package unit, instruments are to be found on
the PID, consumers and instruments list.
Page 6 of 11
Title:
AIC:
Document Nr-Rev:
Reserved
Power cable > 1 kV AC
Power cable < 1 kV AC
Power cable < 1 kV DC
Control cable
Instrumentation signal cable
Building installations, light etc.
Special cables; e.g. phone, fibre optic, etc.
Reserved
Reserved
2.7
Cables between the measurement device and the junction box are to be labelled as follows:
Each end of every core shall be identified using plastic interlocking cable ferrules or printed
sleeve type, cable labels.
Spare cable cores shall be labelled as spares and terminated with enough length to move
anywhere in the panel.
Process Controllers
Main Switch Board0 BHA00
0CJ00
1CJ01
0 BG001 GS001 2 xx
GS001
GS002
GS003
0 ETN11 AP001 2 xx
Junction Box
(Digital I/O)
0CJ00 GDxxx
0 ETN11 AP001 4 xx
Junction Box
(Analog I/O)
1CJ01 GCxxx
0 ETN10 CL001 5 xx
230V
UPS
0 ETN11 AP001
0 ETN10 CL001
1 HFA10 CL301 2 xx
1 HFA10 CL301
xxx from 00 to 99
Page 7 of 11
Title:
AIC:
Document Nr-Rev:
Labelling plates
The final labelling plates shall be non-corrodible material such as stainless steel, Trafolite,
Gravoply, or rigid plastic (Dilophane) which is weather proof, and can withstand the
maximum temperatures in the surrounding environment. Plastic strip type labels are not
allowed.
The labels shall be indelibly stamped or engraved with the equipment number and
description as described in this document, which shall correspond to the contractors
drawings and documentation. The labels shall be secured in position with stainless steel
plated, machined, self-tapping screws or stainless steel rivets.
If not positioned on the equipment the labels shall be positioned in close proximity to the
equipment, and in all cases the labels shall be positioned so as to leave no doubt as to the
item it refers to.
In electrical panels the labels shall not be fixed to the component, but to the backplane or to
a fixed part in close proximity to the component, where it can be clearly seen.
Labelling shall be black letters on white background.
Each cabinet will be identified by its KKS and the functional description of the cabinet.
All switchgear shall identified by a label in front on the door, drawer, or module; and at rear
of the switchboard.
3.1
Text dimensions:
Colour:
Example:
LV cabinet
Example:
package unit
BURNER 2
1 HJY20 GH501
Page 8 of 11
Title:
AIC:
3.2
Document Nr-Rev:
minimum 60 mm x 10 mm x 3.2 mm
Text dimensions:
Colour:
Example:
0 ETN11 AP001
3.3
Text dimensions:
Colour:
Example:
AMMONIA FILLING STATION
0 QCA10 GH001
3.4
Instrumentation
In addition to the marking on the instrument itself (sample on the instrument itself, letter
high 3 mm minimum) a label must be fitted on a visible position of the holding part of the
instrument.
Label dimensions:
minimum 80 mm x 20 mm x 3.2 mm
Text dimensions:
Colour:
Example:
WATER LEVEL
FEED WATER TANK
0 LAA11 CL001
Page 9 of 11
Title:
AIC:
Document Nr-Rev:
50021275 -0.0
4.1
Fuses
The labelling of fuses, carriers, and bases shall comply with the applicable standard.
Identification labels fixed to panels, boards and desks for fuses and links shall describe
their duty, voltage and rating.
4.2
Current transformers
When multiple ratio secondary windings are specified, a label shall be provided at the
secondary terminals of the current transformer, indicating clearly the connections required
for each tap.
Page 10 of 11
Title:
AIC:
4.3
Document Nr-Rev:
50021275 -0.0
Voltage transformers
Secondary main protection fuses or miniature circuit breakers (MCBS) shall be provided as
close as possible to, and preferably mounted on, each voltage transformer and labelled to
show their function and phase colour.
4.4
Protection relays
Any relay mounted on a panel associated with a particular circuit breaker and which
initiates tripping of any other circuit breaker shall in addition to the required trip isolation link
bear a distinctively coloured warning label.
4.5
Circuit breakers
Circuit breakers shall have control switches which shall be labelled open/N/close for MCBs
or (O/N/I) for MCCBs and Motor Protection.
4.6
Selector switches
Each position of selector switches shall be suitably labelled to signify the functions in
accordance with the approved wiring diagrams.
4.7
Panels
Panel sections accommodating equipment at voltages higher than 125 V (nominal) shall be
partitioned off and the voltage clearly labelled.
4.8
Anti-condensation heaters
Labels shall be provided on the power supply circuit breaker stating "Heater supply".
Heater terminals shall be shrouded and labelled as "Heater.
Page 11 of 11