Vous êtes sur la page 1sur 12

Document title

Security level

Scenario 1: TP48600A Power Cabinet and FMS11-G1057


(ITS1000M) Battery Cabinet

Figure 1 Cabinet layout

2015-4-2

Huawei Confidential

Page 1 of 12

Document title

Security level

Table 1 Cable mapping in scenario 1


No.

Function

One End

The Other End

G1

ECC500
PGND cable

Ground point on the


left mounting ear of
the ECC500

Nearest ground point


in the TP48600A
rack

G2

Main ground
cable for
battery
supports

Ground point of the


battery support on
the bottom layer

Main ground bar in


the lower left corner
of the ITS1000M

G3

Equipotential
ground cable
between
battery
supports

Ground point of the


battery support on
the upper layer

Ground point of the


battery support on
the lower layer

1 PCS x 2

G4

ESM battery
ground cable

Battery ground point

Ground point on the


left of the support

1 PCS x 6

S1

CAN
communicatio
ns cable
between ESMs

COM_IN on ESM1

COM_OUT on
ESM2

COM_IN on ESM2

COM_OUT on
ESM3

COM_IN on ESM3

COM_OUT on
ESM4

COM_IN on ESM4

COM_OUT on
ESM5

COM_IN on ESM5

COM_OUT on
ESM6

S2

CAN
communicatio
ns cable from
the ECC to
ESM

COM2 on MUS01A

COM_IN on ESM6

S3

Communicatio
ns cable from
the ECC to
SMU-02B

COM1 on the
SMU03A

RS485/232 on the
SMU02B

S4

Communicatio
ns cable from
the ECC to
BBU

RS485/232 on the
SMU03A

MON1 on the BBU

D1

ECC500
power cable

Power port on the


MUS01A:

M4 screw on the
RTN+ bar of the
TP48600A DCDU

RTN+

2015-4-2

Huawei Confidential

Remarks

Optional

Page 2 of 12

Document title

No.

Function

Security level

One End

The Other End

Power port on the


MUS01A:

F6 circuit breaker on
the
TP48600A DCDU

NEGD2

D3

ESM positive
and negative
power cables

Power cables
to ESM PWR
ports

ESM positive
terminal

M6 screw on the
RTN+ bar of the
BSU

ESM negative
terminal

M6 screw on the
48V2 bar of the
BSU

ESM PWR+

M4 screw on the
RTN+ bar of the
BSU

ESM PWR-

M4 screw on the
48V1 bar of the
BSU

Remarks

2 PCS x 6

2 PCS x 6

D4

Negative
power cable
between the
battery cabinet
and power
cabinet

M6 screw on the
48V2 bar of the
BSU

BAT- circuit breaker


on the
TP48600A DCDU

1 PCS x 3 (connect
to BAT1, BAT2, and
BAT3)

D5

Positive power
cable between
the battery
cabinet and
power cabinet

M6 screw on the
RTN+ bar of the
BSU

BAT on the RTN+


bar of the
TP48600A DCDU

1 PCS x 3 (connect
to BAT1, BAT2, and
BAT3)

D6

BSU
cascading
cable

M4 screw on the
48V1 bar of the
BSU

M4 screw on the
48V1 bar of the
BSU

1 PCS x 2

D7

BSU power
cable

M4 screw on the
48V1 bar of the
BSU

Load circuit breaker


F11 (or a circuit
breaker greater than
40 A) in the power
cabinet

2015-4-2

Huawei Confidential

Page 3 of 12

Document title

Security level

Scenario 2: TP48600A-D12A3 Power Cabinet and


TP48600A Battery Cabinet

Figure 2 Cabinet layout

Table 2 Cable mapping in scenario 2


No.

Function

One End

The Other End

G1

ECC500
PGND cable

Ground point on the


left mounting ear of
the ECC500

Nearest ground point


in the TP48600A
power cabinet

2015-4-2

Huawei Confidential

Remarks

Page 4 of 12

Document title

Security level

No.

Function

One End

The Other End

G2

Main ground
cable for
battery
supports

Ground point of the


battery support on
the bottom layer

Main ground bar at


the bottom of the
TP48600A battery
cabinet

G3

Equipotential
ground cable
between
battery
supports

Ground point of the


battery support on
the upper layer

Ground point of the


battery support on
the lower layer

1 PCS x 2

G4

ESM battery
ground cable

Battery ground point

Ground point on the


left of the support

1 PCS x 6

S1

CAN
communicati
ons cable
between
ESMs

COM_IN on ESM1

COM_OUT on
ESM2

COM_IN on ESM2

COM_OUT on
ESM3

COM_IN on ESM3

COM_OUT on
ESM4

COM_IN on ESM4

COM_OUT on
ESM5

COM_IN on ESM5

COM_OUT on
ESM6

S2

CAN
communicati
ons cable
from the ECC
to ESM

COM2 on MUS01A

COM_IN on ESM6

S3

Communicati
ons cable
from the ECC
to SMU-02B

COM1 on the
SMU03A

RS485/232 on the
SMU02B

S4

Communicati
ons cable
from the ECC
to the BBU

RS485/232 on the
SMU03A

MON1 on the BBU

D1

ECC500
power cable

Power port on the


MUS01A:

M4 screw on the
RTN+ bar of the
TP48600A DCDU

RTN+
Power port on the
MUS01A:
NEGD2

ESM positive
and negative
power cables

2015-4-2

ESM positive
terminal

Remarks

Optional

F6 circuit breaker on
the
TP48600A DCDU
M6 screw on the
RTN+ bar of the
BSU

Huawei Confidential

2 PCS x 6

Page 5 of 12

Document title

No.

D3

Function

Power cables
to ESM PWR
ports

Security level

One End

The Other End

ESM negative
terminal

M6 screw on the
48V2 bar of the
BSU

ESM PWR+

M4 screw on the
RTN+ bar of the
BSU

Remarks

2 PCS x 6

ESM PWR-

M4 screw on the
48V1 bar of the
BSU

Cable from
the BSU to
the battery
cabinet
negative
circuit
breaker

M6 screw on the
48V2 bar of the
BSU

Wiring terminal of
the negative circuit
breaker in the left of
the battery cabinet

D5

Negative
power cable
between the
battery
cabinet and
power cabinet

Negative circuit
breaker in the left of
the battery cabinet

BAT- circuit breaker


on the
TP48600A DCDU

1 PCS x 3 (connect
to BAT1, BAT2, and
BAT3)

D6

Positive
power cable
between the
battery
cabinet and
power cabinet

M6 screw on the
RTN+ bar of the
BSU

BAT on the RTN+


bar of the
TP48600A DCDU

1 PCS x 3 (connect
to BAT1, BAT2, and
BAT3)

D7

BSU
cascading
cable

M4 screw on the
48V1 bar of the
BSU

M4 screw on the
48V1 bar of the
BSU

1 PCS x 2

D8

BSU power
cable

M4 screw on the
48V1 bar of the
BSU

Load circuit breaker


F11 (or a circuit
breaker greater than
40 A) in the power
cabinet

D4

2015-4-2

Huawei Confidential

1 PCS x 3

Page 6 of 12

Document title

Security level

Scenario 3: TP48600A-D12A3 Power Cabinet and


ESC350 Battery Cabinet

Figure 3 Cabinet layout

Table 3 Cable mapping in scenario 3


No.

Function

One End

The Other End

G1

ECC500
PGND cable

Ground point on the


left mounting ear of
the ECC500

Nearest ground point


in the TP48600A
power cabinet

G2

ESM battery
ground cable

Battery ground point

ESC350 ground bar

G3

Main ground
cable of the
ESC350

M8 screw on the
main ground bar of
the ESC350

Outdoor ground bar

S1

CAN
communicati

COM_IN on ESM1

COM_OUT on
ESM2

2015-4-2

Huawei Confidential

Remarks

1 PCS x 6

Page 7 of 12

Document title

No.

Security level

Function

One End

The Other End

Remarks

ons cable
between
ESMs

COM_IN on ESM2

COM_OUT on
ESM3

COM_IN on ESM3

COM_OUT on
ESM4

COM_IN on ESM4

COM_OUT on
ESM5

COM_IN on ESM5

COM_OUT on
ESM6

S2

CAN
communicati
ons cable
from the ECC
to ESM

COM2 on MUS01A

COM_IN on ESM6

S3

Communicati
ons cable
from the ECC
to SMU-02B

COM1 on the
SMU03A

RS485/232 on the
SMU02B

S4

Communicati
ons cable
from the ECC
to the BBU

RS485/232 on the
SMU03A

MON1 on the BBU

Optional

S5

Door signal
cable of the
ESC350
battery
cabinet

Door status sensor

GATE port on the


MUS01A

2 PCS x 1

S6

PC500D
communicati
ons cable

COM_IN on
PC500D

COM1 on the
MUS01A panel

D1

ECC500
power cable

Power port on the


MUS01A:

M4 screw on the
RTN+ bar of the
TP48600A DCDU

RTN+
Power port on the
MUS01A:
NEGD2

ESM positive
and negative
power cables

2015-4-2

F6 circuit breaker on
the
TP48600A DCDU

ESM positive
terminal

M6 screw on the
RTN+ bar in the
right of the ESC350

ESM negative
terminal

M6 screw on the
BAT- bar in the right
of the ESC350

Huawei Confidential

2 PCS x 6

Page 8 of 12

Document title

Security level

No.

Function

One End

The Other End

Remarks

D3

Power cables
to ESM PWR
ports

ESM PWR+

M4 screw on the
RTN+ bar in the left
of the ESC350

ESM PWR-

M4 screw on the
48V bar in the left
of the ESC350

2 PCS x 6

D4

Negative
power cable
between the
battery
cabinet and
power cabinet

BAT- bar in the right


of the ESC350
battery cabinet

BAT- circuit breaker


on the
TP48600A DCDU

1 PCS x 3 (connect
to BAT1, BAT2, and
BAT3)

D5

Positive
power cable
between the
battery
cabinet and
power cabinet

RTN+ bar in the right


of the ESC350
battery cabinet

BAT screw on the


RTN+ bar of the
TP48600A DCDU

1 PCS x 3 (connect
to BAT1, BAT2, and
BAT3)

D6

48V bar
battery power
cable

48V bar in the left


of the ESC350
battery cabinet

Load circuit breaker


F11 (or a circuit
breaker greater than
40 A) in the
TP48600A power
cabinet

2015-4-2

Huawei Confidential

Page 9 of 12

Document title

Security level

Scenario 4: TP48200A-H15D9 Integrated Cabinet

Figure 4 Cabinet layout

2015-4-2

Huawei Confidential

Page 10 of 12

Document title

Security level

Table 4 Cable mapping in scenario 4


No.

Function

One End

The Other End

G1

ECC500
PGND cable

Ground point on the


left mounting ear of
the ECC500

Ground bar in the


left of the integrated
cabinet

G2

Main ground
cable for
battery
supports

Ground point of the


battery support on
the top layer

Main ground bar of


the integrated cabinet

G3

Equipotential
ground cable
between
battery
supports

Ground point of the


battery support on
the upper layer

Ground point of the


battery support on
the lower layer

G4

ESM battery
ground cable

Battery ground point

Ground point on the


left of the support

1 PCS x 4

S1

CAN
communicati
ons cable
between
ESMs

COM_OUT on
ESM1

COM_IN on ESM2

COM_OUT on
ESM2

COM_IN on ESM3

COM_OUT on
ESM3

COM_IN on ESM4

S2

CAN
communicati
ons cable
from the ECC
to ESM

COM2 on MUS01A

COM_IN on ESM1

S3

Communicati
ons cable
from the ECC
to SMU-02B

COM1 on the
SMU03A

RS485/232 on the
SMU02B

S4

Communicati
ons cable
from the ECC
to BBU

RS485/232 on the
SMU03A

MON1 on the BBU

D1

ECC500
power cable

Power port on the


MUS01A:

M4 screw on the
RTN+ bar of the
BSU on the upper
layer

RTN+
Power port on the
MUS01A:
NEG-

2015-4-2

Remarks

Optional

M4 screw on the
48V1 bar of the
BSU on the upper
layer

Huawei Confidential

Page 11 of 12

Document title

Security level

No.

Function

One End

The Other End

Remarks

D2

ESM positive
and negative
power cables

ESM positive
terminal

M6 screw on the
RTN+ bar of the
BSU

2 PCS x 4

ESM negative
terminal

M6 screw on the
48V2 bar of the
BSU

ESM PWR+

M4 screw on the
RTN+ bar of the
BSU

D3

Power cables
to ESM PWR
ports

ESM PWR-

M4 screw on the
48V1 bar of the
BSU

2 PCS x 4

D4

Negative
power cable
of the BSU

48V2 bar of the


BSU

Negative battery
circuit breaker
(BAT1-, BAT2-) in
the integrated cabinet

1 PCS x 2

D5

Positive
power cable
of the BSU

RTN+ bar of the


BSU

Positive busbar
(BAT1+, BAT2+) in
the integrated cabinet

1 PCS x 2

D6

BSU
cascading
cable

M4 screw on the
48V1 bar of the
BSU

M4 screw on the
48V1 bar of the
BSU

D7

48V bar
battery power
cable

M4 screw on the
48V1 bar of the
BSU

BLVD load circuit


breaker (at least 40
A)

2015-4-2

Huawei Confidential

Page 12 of 12