Detectors: V-PS, V-PHS, V-HFD, V-HRD
Bases: B4U, RB4U, IB4U, SB4U
Overview
Edwards Vigilant brand intelligent analog detectors are meticulously engineered to deliver high-performance features, superb
reliability, and unbeatable quality. With their highly stable design,
these detectors resist air movement caused by heating and air
conditioning, making them reliable performers ideally suited to
modern building interiors.
Standard Features
M85001-0592
D ATA S H E E T
Not to be used for installation purposes. Issue 1
Wire size
Base diameter
Height from box
(including detector)
Maximum distance
from ceiling (wall
mount)
32 to 120F (0 to 49C)
0 to 93% RH, noncondensing at 90F (32C)
-4 to 140F (-20 to 60C)
V-PS, V-PHS, V-HRD, and V-HFD detectors
North American 2-1/2 in. (64 mm) deep 2 gang
box
Standard 4" square box 1-1/2 in. (38 mm) deep
box
European 100 mm square box
12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0,
or 0.75 sq. mm) (Sizes 16 and 18 AWG are
preferred)
6.0 in. (152 mm)
2.58 in. (66 mm)
12 in. (305 mm)
High dBA
28
41
52
48
60
66
Low dBA
High dBA
71.3
75.0
77.7
75.8
79.2
82.0
77.2
79.8
81.5
80.5
84.1
86.0
77.3
81.0
83.7
81.8
85.2
88.0
83.2
85.8
87.5
86.5
90.1
92.0
Specifications, Detectors
Air velocity
Smoke sensitivity range
ULI fixed-temp alarm rating
ULC fixed-temp alarm rating
Maximum Spacing
Rate-of-Rise
Operating voltage
Normal operating current
Alarm current
Environmental compensation
Compatible bases
Maximum distance from ceiling
wall-mounted
Storage temperature
Operating environment
Agency listings
Page 4 of 6
V-PHS
V-PS
V-HRD
0 to 5,000 ft/min (0 to 25.39 m/s)
N/A
0.67% - 3.66%
135F (57C)
N/A
140F (60C)
30 ft (9.1 m)
N/A
15F (8C)/min.
15.2 to 19.95 VDC
45 A, average
45 A, average
Automatic
B4U Standard, RB4U Relay, IB4U Isolator, SB4U Audible
V-HFD
135F (57C)
140F (60C)
50 ft (15 m) centers
N/A
12 in (305 mm)
-4 to 140F (-20 to 60C)
Temperature: 32 to 120F (0 to 49C); Humidity: 0 to 93% RH, noncondensing at 90F (32C)
Meets UL 268,
Meets UL 268,
ULC-S529-02, UL 521,
Meets UL 521, ULC-S530-M91, NFPA 72, and
ULC-S529-02, NFPA 72,
ULC-S530-M91, NFPA 72,
CAN/ULC S524-01
and CAN/ULC S524-01
and CAN/ULC S524-01
M85001-0592
D ATA S H E E T
Not to be used for installation purposes. Issue 1
Specifications, Bases
B4U Standard Base
Operating environment
Temperature
Humidity
Storage temperature range
Compatible detectors
Compatible electrical boxes
Wire size
Base diameter
Height from box (including detector)
Maximum distance from ceiling (wall
mount)
32 to 120F (0 to 49C)
0 to 93% RH, noncondensing at 90F ( 32C)
-4 to 140F (-20 to 60C)
V-PS, V-PHS, V-HRD, and V-HFD detectors
North American 2-1/2 in. (64 mm) deep 2 gang box
Standard 4 in. square box 1-1/2 in. (38 mm) deep box
European 100 mm square box
12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq. mm) (Sizes 16 and 18 AWG are preferred)
6.0 in. (152 mm)
2.08 in. (53 mm)
2.57 in. (65 mm)
12 in. (305 mm)
Ordering Information
Model
V-PHS
V-PS
V-HRD
V-HFD
B4U
RB4U
IB4U
SB4U
AB4G-SB
RLED
Page 5 of 6
Description
Intelligent Analog Optical/Fixed Temperature Detector
Intelligent Analog Optical Smoke Detector
Intelligent Analog Rate-of-Rise Heat Detector
Intelligent Analog Fixed Temperature Heat Detector
Standard Base
Relay Detector Base
Isolator Detector Base
Audible (Sounder) Detector Base
Surface Box for Audible Base
Remote alarm LED, use with standard base only
M85001-0592
D ATA S H E E T
Not to be used for installation purposes. Issue 1
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
2010 UTC Fire & Security.
All rights reserved.
M85001-0592
D ATA S H E E T
Not to be used for installation purposes. Issue 1
07-09-10
Page 6 of 6