P

ELECTRICAL SYMBOLS
CL

ABBREVIATIONS

KEYED NOTE (APPLIES ONLY TO THE DRAWING ON WHICH IT IS SEEN),


NUMBER IDENTIFIES NOTE

LIGHTING FIXTURE CEILING OR PENDANT


MOUNTED

O
a

PC

CEILING MOUNTED PHOTO SENSOR

ST

SHUNT TRIP COIL

WC

WALL MOUNTED LIGHTING CONTROLLER

E - INDICATES EMERGENCY BATTERY


BALLAST SEE LIGHTING FIXTURE SCHEDULES

F1E

A
ACT
AFF
AFG
AHU
AIC
ASYM
ATS
AWG
BLDG
C
CB
CFCI
CFGI
CKT
CLG
CR
CT
CU
DWG
EF
ELEC
EMT
EPO
EQUIP
ETR
EWC
EX,EXIST
F
FACP
FO
FLA
FSD/FD/SD
FSS
GFCI

RACEWAY AND CONDUCTORS (2) 4mm + 4mm GND IN 21mm EMT OR


FLEXIBLE RACEWAY PER SPECIFICATIONS, UON OR SCHEDULED.
PROVIDE SWITCH CONDUCTORS AS REQUIRED.

UPPER CASE - FIXTURE TYPE (TYPICAL FOR ALL LIGHTING


FIXTURES) SEE LIGHTING FIXTURE SCHEDULES
LOWER CASE - INDICATES CONTROLLING
SWITCHES (TYPICAL FOR ALL LIGHTING FIXTURES)

XX

ARROW INDICATES HOME RUN, XX INDICATES PANEL AND CIRCUITS


NUMBER(S)
CONDUIT TURNING UP

LIGHTING FIXTURE, WALL MOUNTED - SEE LIGHTING FIXTURE SCHEDULE

CONDUIT TURNING DOWN


EX

EXIT SIGN - DARKENED SECTION INDICATES FACE WITH DIRECTIONAL


ARROWS AS INDICATED - SEE LIGHTING FIXTURE SCHEDULE

UNDERGROUND NEW WORK

S1

UNDERGROUND BARE COPPER GROUND CONDUCTOR, SIZE AS NOTED

SELF-CONTAINED, BATTERY POWERED EMERGENCY LIGHT WITH TWIN


LAMPHEAD - SEE LIGHTING FIXTURE SCHEDULE

UGL

UNDERGROUND LIGHTING CIRCUIT

EXTERIOR LIGHT POLE AND CONCRETE BASE WITH SINGLE MOUNTED FIXTURE OF TYPE
NOTED

E45

MANHOLE, UNDERGROUND WITH LOCKABLE STEEL COVER, REFER


TO DIV. 2.

S4
EXTERIOR LIGHT POLE AND CONCRETE BASE WITH TWIN MOUNTED FIXTURES OF TYPE
NOTED

HH

S5

HANDHOLE, UNDERGROUND WITH LOCKABLE STEEL


COVER (GROUND TEST WELL), MINIMUM AREA - 0.3 m,
REFER TO DIV. 2

EXTERIOR LIGHT POLE AND CONCRETE BASE WITH YOKE MOUNTED FIXTURE OF TYPE NOTED
E

Sa

TRANSFORMER - VOLTAGE, POWER, ISOLATION AND "K" RATINGS AS


NOTED.

THREE WAY TOGGLE SWITCH, 1200mm AFF, 250VAC RATED


V

SD

DIMMER SWITCH, 1200mm AFF, 250VAC, 50 HZ RATED

CEILING MOUNTED OCCUPANCY DETECTOR - DUAL TECHNOLOGY (NON-CAA AREAS)

ELECTRICAL HANDHOLE, UNDERGROUND WITH LOCKABLE STEEL


COVER, REFER TO DIV. 2.

SINGLE POLE TOGGLE SWITCH - SUBSCRIPT INDICATES FIXTURES CONTROLLED BY THE SWITCH (TYPICAL FOR
ALL LIGHTING SWITCHES), 1200mm AFF, 250VAC RATED

S3

GFE
GFGI
GND
GW
HH
HOA
HP
HZ
JB
KCMIL
KVA
KVAR
KVARH
KW
KWH
LTG
MCB
MCP
MDP
MECH
MIN
MH
MLO
MOV
MT HT
MTS
NEC
NEMA
NFSS
NIC
NTS
PH
P
PF
PNL
PT
PVC
RECEPT
RFCP
RGS
RM
SEC
SC
SPD
ST
SYM
TEL
TR
TTB
TYP
UON
USG
V
VA
VFD
W
W/
WIU
WP
XFMR

VOLTAGE REGULATOR, TYPE AND RATINGS AS NOTED

GENERATOR, SIZE AND RATINGS AS NOTED

CEILING MOUNTED OCCUPANCY DETECTOR - PASSIVE INFRARED ONLY (CAA AREAS)


SURGE SUPPRESSOR/LIGHTNING ARRESTER

WALL MOUNTED OCCUPANCY DETECTOR, 1200mm AFF


CURRENT TRANSFORMER
PHOTOELECTRIC CONTROL FOR SITE LIGHTING

POTENTIAL TRANSFORMER
J

JUNCTION BOX, WALL,CEILING OR FLUSH-FLOOR MOUNTED (MOUNTING


HEIGHT AS SHOWN ON PLANS)
DUPLEX RECEPTACLE - 2P, 3W, 20A, 250V, NEMA 6-20R, WP - WEATHERPROOF, 450mm AFF
UON

ENCLOSED CIRCUIT BREAKER

QUADRUPLEX RECEPTACLE - 2P, 3W, 20A (AS NOTED), NEMA 6-20R, 250V,
FLOOR MOUNTED IN RECESSED FLOOR BOX PER SPECIFICATIONS

MOLDED CASE CIRCUIT BREAKER


DRAW OUT, POWER TYPE CIRCUIT BREAKER

DUPLEX RECEPTACLE - 2P, 3W, 20A (AS NOTED), NEMA 6-20R,


250V, CEILING MOUNTED (FASTENED TO STRUCTURE ABOVE)

DRAWOUT POWER TYPE CIRCUIT BREAKER WITH SOLID STATE


TRIP UNIT 'L'- LONG TIME 'S'- SHORT TIME 'I'- INSTANTANEOUS
'G'- GROUND FAULT

L
S
I
G

QUADRUPLEX RECEPTACLE - 2P, 3W, 250V, NEMA 6-20R, 450 mm AFF UON
SINGLE RECEPTACLE - 2P, 3W, 250V, NEMA 6-20R, 450 mm AFF UON, D-DEDICATED CIRCUIT

MEDIUM VOLTAGE FUSED SWITCH

ABOVE COUNTER DUPLEX RECEPTACLE - 2P, 3W, 20A, 250V, NEMA 6-20R, GFCI - GROUND
FAULT CIRCUIT INTERRUPTER, MOUNT AT HEIGHT SHOWN ON ARCHITECTURAL ELEVATIONS

MEDIUM VOLTAGE CIRCUIT BREAKER

DUPLEX RECEPTACLE - 2P, 3W, 20A, 250V, NEMA 6-20R, GFCI - GROUND FAULT CIRCUIT
INTERRUPTER, 450mm AFF UON
2 COMPARTMENT SURFACE RACEWAY, SIZE AND MOUNTING HEIGHT AS INDIDCATED.
NUMBER OF RECEPTACLES AS SHOWN.

OV

OVER VOLTAGE RELAY

UV

UNDER VOLTAGE RELAY

OF

OVER FREQUENCY RELAY

UF

UNDER FREQUENCY RELAY

PL

PHASE LOSS RELAY

PR

PHASE REVERSAL/REVERSE PHASE ROTATION RELAY

PANELBOARD, SURFACE MOUNTED


PANELBOARD, RECESS MOUNTED
SINGLE PHASE ELECTRICAL MOTOR

AMPERES
ACOUSTICS TILE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ASYMMETRICAL
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAUGE
BUILDING
CONDUIT
CIRCUIT BREAKER
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CONTRACTOR FURNISHED GOVERNMENT INSTALLED
CIRCUIT
CEILING
CONTROL RELAY
CURRENT TRANSFORMER
COPPER
DRAWING
EXHAUST FAN
ELECTRIC/ ELECTRICAL
ELECTRICAL METALLIC TUBING
EMERGENCY POWER OFF
EQUIPMENT
EXISTING TO REMAIN
ELECTRIC WATER COOLER
EXISTING
FUSED OR FUSIBLE
FIRE ALARM CONTROL PANEL
FIBER OPTIC
FULL LOAD AMPERES
FIRE / SMOKE DAMPER
FUSED SAFETY SWITCH
GROUND FAULT CIRCUIT INTERRUPTER OR
GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GOVERNMENT FURNISHED EQUIPMENT
GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GROUND
GROUND WIRE
HANDHOLE
HAND-OFF-AUTOMATIC
HORSE POWER
HERTZ
JUNCTION BOX
THOUSAND CIRCULAR MILS
KILOVOLT-AMPRES
KILOVOLT AMP REACTIVE
KILOVAR HOUR
KILOWATT
KILOWATT HOUR
LIGHTING
MAIN CIRCUIT BREAKER
MOTOR CIRCUIT PROTECTOR
MAIN DISTRIBUTION PANEL
MECHANICAL
MINUTES
MANHOLE
MAIN LUGS ONLY
METAL OXIDE VARISTOR
MOUNTING HEIGHT
MANUAL TRANSFER SWITCH
NATIONAL ELECTRIC CODE
NATIONAL ELECTRICAL MANUFACTUR'S ASSOCIATION
NON-FUSED SAFETY SWITCH
NOT IN CONTRACT
NOT TO SCALE
PHASE
POLE
POWER FACTOR
PANEL
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
RECEPTACLE
REMOTE FIRE ALARM CONTROL PANEL
RIGID GALVANIZED STEEL
ROOM
SECONDS
SHUNT CLOSE
SURGE PROTECTION DEVICE
SHUNT TRIP
SYMMETRICAL
TELEPHONE
TELEPHONE ROOM
TELEPHONE TERMINAL BOARD
TYPICAL
UNLESS OTHERWISE NOTED
UNITED STATES GOVERNMENT
VOLTAGE
VOLT AMPERES
VARIABLE FREQUENCY DRIVE
WIRE
WITH
WHILE IN USE
WEATHER PROOF
TRANSFORMER

SEE NOTE 2

MAX.
2440mm

FIRE ALARM AUDIO/VISUAL DEVICES

MIN.
2032mm

United States Department of State


OVERSEAS BUILDINGS OPERATIONS
WALL SWITCHES

CL 1200mm MAX.

WALL TELEPHONE

PULL

KEYPAD

U.S. EMBASSY
CLAY ALLEE COMPOUND
BERLIN, GERMANY
TELEPHONE/DATA OUTLETS
RECEPTACLES
FINISHED FLOOR

ISSUED FOR
CONSTRUCTION

NOTES:
1.

ALL MOUNTING HEIGHTS SHALL BE MEASURED FROM FINISHED FLOOR TO OPERABLE PORTION OF DEVICE.

2.

DEVICES, NOT NECESSARILY THE ELECTRICAL BACK BOX, SHALL BE INSTALLED ON A COMMON VERTICAL CENTERLINE WHERE
LOCATED WITHIN 1000mm OF EACH OTHER HORIZONTALLY IN PLAN.

3.

ALL DEVICES SHALL BE INSTALLED AT MOUNTING HEIGHTS AS INDICATED ON THE DETAIL UNLESS OTHERWISE NOTED.

4.

REFER TO ARCHITECT'S PLANS, ELEVATION, AND DETAILS FOR HORIZONTAL ARRANGEMENT.

A
E001

GENERAL NOTES

TYPICAL DETAIL - DEVICE MOUNTING DETAIL


N.T.S.

METRIC/ENGLISH EQUIVALENT
CONVERSION TABLE

1.

PROVIDE ELECTRICAL SYSTEMS PER THE N.E.C. AND OBO


DESIGN REQUIREMENTS AND STANDARDS.

2.

DETAILS ARE SHOWN FOR REFERENCE ONLY AND MAY


NOT BE APPLICABLE OR SUITABLE IN ALL SITUATIONS.

3.

ALL EQUIPMENT AND SYSTEM DESIGNS MUST BE


APPROVED BY OBO PRIOR TO CONSTRUCTION.

4.

IF NEMA 6-20 RECEPTACLE IS MOUNTED VERTICALLY WITH


GROUND SLOT ON TOP, THE NEUTRAL CONDUCTOR SHALL
BE CONNECTED TO RIGHT SIDE TERMINAL. IF GROUND
SLOT IS AT THE BOTTOM THE NEUTRAL CONDUCTOR S
HALL BE CONNECTED TO THE LEFT SIDE TERMINAL. IF
NEMA 6-20 RECEPTACLE IS MOUNTED HORIZONTALLY WITH
GROUND SLOT TO THE LEFT, THE NEUTRAL CONDUCTOR
SHALL BE CONNECTED TO TOP SIDE TERMINAL, IF GROUND
SLOT IS AT THE RIGHT THE NEUTRAL CONDUCTOR SHALL
BE CONNECTED TO THE BOTTOM SIDE TERMINAL.

5.

REFER TO "SE" SERIES DRAWINGS, VOLUME 1, FOR


SEISMIC REQUIREMENTS.

METRIC/ENGLISH EQUIVALENT
CONVERSION TABLE
WIRE

CONDUIT
TRADE
SIZE (inches)

METRIC
SIZE (mm)

AWG
SIZE (#)

METRIC
SIZE (mm2)

1/2

16

18

3/4

21

16

1.5

27

14

2.5

1-1/4

35

12

1-1/2

41

10

53

10

2-1/2

63

16

78

25

3-1/2

91

35

103

50

129

1/0

70

155

2/0

70

3/0

95

LC

TIME DELAY RELAY

4/0

120

RC

RECLOSING RELAY

250 KCMIL

150

AMMETER

300 KCMIL

185

VOLTMETER

350 KCMIL

185

NONFUSED DISCONNECT SWITCH

400 KCMIL
MULTIFUNCTION METER, DIGITAL WITH KWH, KVARH,
KW, KVAR, KVA, 'KVAH, PF AND PEAK KVA AND KVAR
MEASUREMENTS

240

500 KCMIL

300

POWER FILTER

600 KCMIL

300

750 KCMIL

400

FUSED DISCONNECT SWITCH


F
VARIABLE SPEED DRIVE, SIZE AS NOTED

EMERGENCY POWER OFF PUSHBUTTON

E
NO.

REVISION/SUBMISSION

DATE

EYP/

EYP Inc.
NanoFab East
257 Fuller Road - 1st Floor
Albany, NY 12203
Telephone: 518.795.3800
Fax: 518.795.3998

Consultant:

TCP

TEMPERATURE CONTROL PANEL

UPS

UNINTERRUPTABLE POWER SUPPLY

Release for Construction:


OBO / PE / PM

OBO / PE / PM

Drawing Title:

ELECTRICAL LEGEND

GROUND BAR

OBO Project Number:

Drawing Scale:

XJ-A5-0163

Phase:
35% SUBMISSION

1:1

File Name:

AIR TERMINAL - LIGHTNING PROTECTION

Plot Scale:

BER CAC E001.dwg

1=1

IFC

100% SUBMISSION

CERTIFICATION

IS TE RE D

SO

EG

10

BVP

R D V. P A R

10.28.2014

11

12

13

14

15

16

17

JDW

NA

Drawn By:
Checked By:

EN GINE

No. 7493

UNCLASSIFIED
2

OCTOBER 28, 2014

AL

SWITCHBOARD OR SWITCHGEAR AS INDICATED.


SIZE AS SHOWN ON ONE-LINE DIAGRAMS.

SB

CA R O

OF E S SION
PR

IN

TH

BUILDING AUTOMATION SYSTEM


U

BAS

DRIVEN GROUND ROD

GROUND CONNECTION

BACKCHECK

65% SUBMISSION

Date:

DRIVEN GROUND ROD, COPPER CLAD, 3000 mm X 21 mm

EPO

eypae.com

COMBINATION STARTER WITH ADJUSTABLE, MAGNETIC TRIP ONLY,


CIRCUIT BREAKER DISCONNECT AND ADJUSTABLE, SOLID STATE,
OVERLOAD RELAY

OR VSD

Revisions

ENCLOSED CIRCUIT BREAKER WITH 2 FORM 'C' AUXILIARY CONTACTS, SHUNT TRIP COIL,
AND LOCKOUT/TAGOUT PROVISIONS

WARNING: This document is the property of the U.S. Government. Further reproduction and/or
distribution outside the contractor team is prohibited without the express written approval of:
U.S. Department of State
Overseas Building Operations
ATTN: Brian Mulcahy
Washington, D.C. 20520

CL 450mm

MOTOR SWITCH, HORSEPOWER RATED, 250VAC - 1HP MIN

FOR

THREE PHASE ELECTRICAL MOTOR

SM

FY14 MAJOR REHAB COMPOUND SECURITY


UPGRADE & MSGQ FIT-OUT

FIRE

FIRE ALARM PULL STATION

Washington, D.C.