Académique Documents
Professionnel Documents
Culture Documents
Volume V
AG2010-04
INTRODUCTION
A common power transformer configuration for industrial plants supplying radial mediumvoltage distribution systems uses delta-wye power transformers that are low-resistance grounded
to reduce the single-line-to-ground fault current magnitude. Typically, the single-line-to-ground
fault current magnitude is limited to 400 A by sizing the neutral grounding resistor accordingly.
The differential elements (87R and 87U) in the SEL-387A Current Differential and Overcurrent
Relay may not be sensitive enough to detect internal single-line-to-ground faults in the wye
winding. To improve sensitivity, apply one of the two optional restricted earth fault (REF)
protection elements. Also known as directional ground (67G) or zero-sequence neutral
differential protection (87N), REF uses ground current in the transformer neutral as a polarizing
reference and zero-sequence current derived from the calculated residual current (IG or 3I0) as its
operating quantity to detect single-line-to-ground faults in the transformer wye winding. Tripping
is supervised by zero-sequence current thresholds and a positive-sequence current restraint
setting.
As shown in Figure 1, the REF element should be used to provide sensitive protection for
winding-to-ground faults in the wye-connected, low-side transformer winding. The element is
restricted in the sense that protection is restricted to ground faults within a zone defined by
neutral CTs (current transformers) and low-side phase CTs. This application guide provides two
REF application examples that can be used to develop REF settings for the SEL-387A.
Figure 1
The 50GPn setting must be greater than any natural 3I0 unbalance caused by load
conditions.
The 50GPn setting must be greater than a minimum value determined by the relationship
of the CTRn values used in the REF function. Use (1) to determine the second criterion
for 50GPn.
50GPn = 0.05 Inom
CTRn
CTRN
(1)
Figure 2, Figure 3, and Figure 4 show the REF logic using the second REF element available in
the relay. Thresholds a0|I1W1| and a0|I1W2| in Figure 2 are fixed positive-sequence current restraint
factors used to ensure that the ratio of zero-sequence to positive-sequence current is above a
threshold (a01 setting, in this example) for REF element security (e.g., CT saturation during a
three-phase fault) [2].
Figure 2
In Figure 3, we see that the relay enables the 32I directional element (forward or reverse) by
calculating a torque product (real part of the operating current [Iop] product and polarizing
current conjugate [Ipol*]). The 32In element calculates the real part of IOP times IPOL* (IPOL
complex conjugate). This equates to |IOP| times |IPOL| times the cosine of the angle between
them. The result is positive if the angle is within 90 degrees, indicating a forward or internal
fault. The result is negative if the angle is greater than +90 degrees or less than 90 degrees,
indicating a reverse or external fault. The relay compares the output of the 32I element to positive
and negative thresholds to ensure security for very small currents or for an angle very near
+90 or 90 degrees. If the 32I output exceeds the threshold test, it must persist for at least
1.5 cycles before the Relay Word bit 32IF2 (forward) or 32IR2 (reverse) asserts. Assertion of
32IF2 constitutes a decision to trip by the REF function [3]. This calculation is allowed if the two
Relay Word bits 32IE and 50GC2 assert (AND2).
A second path for assertion of the 32IF2 Relay Word bit is shown in Figure 3. This bypass of the
normal REF logic is used for situations where the line-end breaker is open and the wye-side
transformer terminals are isolated from the power system, but a fault to ground on the wye
transformer winding is fed from another energized transformer winding. The AND1 gate asserts
if 32IE2 is asserted but 50GC2 (residual current pickup) is not. This assertion indicates that the
neutral current is above pickup but 50GCn is not asserted, indicating no line-end current flow.
This logic covers the situation of an internal wye-winding fault with the line-end breaker open.
Figure 3
Figure 4
APPLICATION EXAMPLES
This section covers two application examples with SEL-387A REF protection settings and logic
settings.
Settings
Table 1 and Table 2 show the SEL-387A REF protection settings and logic settings for
Applications 1 and 2. The dc schematic from which the logic settings were derived is shown in
Figure 5.
Table 1 87T and REF Protection Settings for Applications 1 and 2
Protection Settings
Description
Application 1
Application 2
!CTS21
E32I
!CTS2
32IOP2
a02
0.02
0.02
2.5
2.5
50GP2
TR1
51P1T
TR2
51P2T + 51NN2T
TR3
OUT101
TRIP1 + TRIP3
OUT102
TRIP2 + TRIP3
OUT103
TRIP3
The CTSn Relay Word bit is the result of a CT saturation detection algorithm in the relay. The inverted
CTS output (!CTSn) is used to enable the 32I2 element and block the REF function on false I0 during CT
saturation.
Note that a setting of 50GP2:= 2.5 A secondary = 2.5 40 = 100 A primary provides REF protection for
75 percent of the secondary winding.
+DC
+DC
+DC
SEL-387A
(Partial)
A17
IN101
A19
IN102
A18
A20
52 1
a
52 2
a
A05
A09
OUT103
A15
A06
A16
Alarm
A10
86T
b Trip
ANN
+ Z25
Power
Supply
Z26
A01
GND
Z27
A03
OUT101
OUT102
A02
A04
52 1
a
Fail
ANN
86T
a
52 2
a
52 2
TC
52 1
TC
86T
OP
DC
DC
86T
a
DC
Remaining:
4 Inputs (IN103IN106)
3 Outputs (OUT104, OUT106, OUT107)
Figure 5
General DC Schematic
INFERENCE
Typically, the ground overcurrent pickup on a 400 A grounded system is set less than or equal to
200 A primary to ensure that the element will pick up for most single-line-to-ground faults.
Therefore, a 100 A primary REF pickup is acceptable for most applications. In the previous
examples, the REF element provides protection for 75 percent of the transformer winding
(assume fault resistance Rf = 0). This is shown in Figure 6, which is a linear relation between the
fault current in A primary and the percentage of secondary winding [1].
450
400
350
300
250
200
REF Pickup
150
100
50
0
0
20
25
40
60
80
100
120
Figure 6
(2)
where:
VLL = line-to-line system voltage
R = neutral ground resistance
Therefore, for the Application 1 and Application 2 examples, the minimum fault current is the
following:
4160
I F = 0.25 3 = 100 A
6
(3)
CONCLUSION
Applying the REF (67G or 87N) element in an SEL-387A for a low-resistance-grounded power
transformer is relatively straightforward. This application improves detection of low-side
transformer single-line-to-ground faults without the need to set a reverse ground directional
element in the relay for a low-side main breaker.
REFERENCES
[1]
C. Labuschagne and I. van der Merwe, A Comparison Between High-Impedance and LowImpedance Restricted Earth-Fault Transformer Protection, proceedings of the Minnesota
Power Systems Conference, St. Paul, MN, November 2005. Available:
http://www.selinc.com.
[2]
[3]
FACTORY ASSISTANCE
We appreciate your interest in SEL products and services. If you have questions or comments,
please contact us at:
Schweitzer Engineering Laboratories, Inc.
2350 NE Hopkins Court
Pullman, WA 99163-5603 USA
Telephone: +1.509.332.1890
Fax: +1.509.332.7990
www.selinc.com info@selinc.com
*AG2010-04*
Date Code 20100512