Vous êtes sur la page 1sur 17

ELECTRICAL EQUIPMENT LIST

Job#: 10-01525-0006
Date: 16-08-2016
Unit#: A61
Doc#: A61-P-DOC-VE-746157
Rev#: 00
Index: P

Rev.

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

SubstationNo.
SS-161
SS-161
SS-161
SS-161

EquipmentTagNo.
A61-229-XFR(T)-601
A61-229-XFR(T)-602
A61-229-GR(Y)-301
A61-229-GR(Y)-302

TRANSFORMER, 50/66.5 MVA, 132


TRANSFORMER, 50/66.5 MVA, 132
NEUTRAL GROUNDING RESISTANCE,
NEUTRAL GROUNDING RESISTANCE,

LARGE (>=10 MVA) TRANSFORMERS & GROUNDING RESISTOR


Primary Secondary
Description
Voltage
Voltage
KV-13.8 KV, 60 Hz, 3Ph, Z=10%, DELTA-WYE, ONAN/ONAF, 6 132 KV
13.8 KV
KV-13.8 KV, 60 Hz, 3Ph, Z=10%, DELTA-WYE, ONAN/ONAF, 6 132 KV
13.8 KV
13.8 KV
400 A, 10 S
400 A, 10 S
13.8 KV

Page 2 of 14

Rating

Impedance

50/66.5 MVA
50/66.5 MVA
400 A, 10 S
400 A, 10 S

10%
10%

FaultCurrentRating
(IfApplicable)

Remarks
DWG.
DWG.
DWG.
DWG.

A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001

ELECTRICAL EQUIPMENT LIST


Job#: 10-01525-0006
Date: 16-08-2016
Unit#: A61
Doc#: A61-P-DOC-VE-746157
Rev#: 00
Index: P

Rev.

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

SubstationNo.
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161

EquipmentTagNo.
A61-161-XFR(T)-301 TRANSFORMER,
A61-161-XFR(T)-302 TRANSFORMER,
A61-161-XFR(T)-307 TRANSFORMER,
A61-329-XFR(T)-301 TRANSFORMER,
A61-161-XFR(T)-201 TRANSFORMER,
A61-161-XFR(T)-202 TRANSFORMER,
A61-161-XFR(T)-203 TRANSFORMER,

Description

SMALL (<=10 MVA) TRANSFORMERS


Primary
Voltage

2.5/3.125 MVA, 13.8 KV-480 V, Z=5.75%, DELTA-WYE, ONAN/ONAF, 65C/6


2.5/3.125 MVA, 13.8 KV-480 V, Z=5.75%, DELTA-WYE, ONAN/ONAF, 65C/6
150 KVA, 13.8 KV-480 V, DELTA-WYE, PAD MOUNTED WITH SWITCH, ONAN, 65
1000 KVA, 13.8 KV-480 V, Z=5.75%, DELTA-WYE, ONAN, 65C
ELECTRO-CHLORINATION PACKAGE #1 (By EC Vendor)
ELECTRO-CHLORINATION PACKAGE #2 (By EC Vendor)
ELECTRO-CHLORINATION PACKAGE #3 (By EC Vendor)

Page 3 of 14

13.8
13.8
13.8
13.8
13.8
13.8
13.8

KV
KV
KV
KV
KV
KV
KV

Secondary
Voltage
480
480
480
480
350
350
350

V
V
V
V
V
V
V

Rating

Impedance

2.5/3.125 MVA
2.5/3.125 MVA
150 KVA
1000 KVA
3860 KVA
3860 KVA
3860 KVA

5.75%
5.75%
5.75%
5.75%
7.00%
7.00%
7.00%

FaultCurrentRating
(IfApplicable)

Remarks
DWG.
DWG.
DWG.
DWG.
DWG.
DWG.
DWG.

A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001

Rev.

ELECTRICAL EQUIPMENT LIST


Job#: 10-01525-0006
Date: 16-08-2016
Unit#: A61
Doc#: A61-P-DOC-VE-746157
Rev#: 00
Index: P

SubstationNo.
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161

EquipmentTagNo.
A61-161-XFR-001
A61-161-XFR-002
A61-161-XFR-003
A61-161-XFR-004
A61-161-XFR-005
A61-161-XFR-006
A61-161-XFR-007
A61-161-XFR-008
A61-161-XFR-011
A61-161-XFR-012
A61-161-XFR-013
A61-161-XFR-014
A61-161-XFR-015
A61-161-XFR-016
A61-161-XFR-017
A61-161-XFR-018
A61-161-XFR-019
A61-161-XFR-020
A61-161-XFR-021
A61-161-XFR-022
A61-161-XFR-023
A61-161-XFR-024

Description

DRY TRANSFORMERS
Primary
Secondary
Voltage
Voltage

SUBSTATION SS-161 INTERNAL LIGHTING XFMR


480V
SUBSTATION SS-161 EXTERNAL LIGHTING XFMR
480V
SUBSTATION SS-161 ESSENTIAL LIGHTING XFMR
480V
SUBSTATION SS-161 OUTLET XFMR
480V
SUBSTATION SS-161 (PIR) AC UPS SYSTEM A BY PASS TRANSFO 480V
SUBSTATION SS-161 (PIR) AC UPS SYSTEM B BY PASS TRANSFO 480V
MOTOR SPACE HEATER XFMR
480V
INSTRUMENTATION POWER XFMR
480V
CHLORINATION BUILDING NORMAL LIGHTING XFMR
480V
CHLORINATION BUILDING OUTLET XFMR
480V
CHLORINATION BUILDING ESSENTIAL LIGHTING XFMR
480V
INLET PUMP STATION NORMAL LIGHTING XFMR
480V
INLET PUMP STATION ROADWAY LIGHTING XFMR
480V
INLET PUMP STATION ESSENTIAL LIGHTING XFMR
480V
INLET PUMP STATION OUTLET XFMR
480V
SCREEN STATION NORMAL LIGHTING XFMR
480V
SCREEN STATION ESSENTIAL LIGHTING XFMR
480V
SCREEN STATION OUTLET XFMR
480V
INLET CANAL NORTH ROADWAY LIGHTING XFMR
480V
INLET CANAL SOUTH ROADWAY LIGHTING XFMR
480V
INTAKE CHANNEL WEST ROADWAY LIGHTING XFMR
480V
INTAKE CHANNEL EAST ROADWAY LIGHTING XFMR
480V

Page 4 of 14

400(230)
400(230)
400(230)
400(230)
208(120)
208(120)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
(
)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)

Rating
30
15
15
15
45
45
45
45
30
15
15
30
30
30
15
30
15
15
45
45
45
45

Impedance

FaultCurrentRating
(IfApplicable)

Remarks

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

Job#:
Date:
Unit#:
Doc#:
Rev#:
Index:

ELECTRICAL EQUIPMENT LIST


10-01525-0006
16-08-2016
A61
A61-P-DOC-VE-746157
00
P

Rev.

AC PANELS (POWER & LIGHTING)


SubstationNo. EquipmentTagNo.
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS 161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161

A61-161-LP-001
A61-161-LP-002
A61-161-ELP-003
A61-161-PP-004
A61-161-PP-007
A61-161-PP-008
A61-161-PP-011
A61-161-LP-012
A61-161-ELP-013
A61-161-LP-014
A61-161-LP-015
A61-161-ELP-016
A61-161-PP-017
A61-161-LP-018
A61-161-ELP-019
A61 161 PP 020
A61-161-PP-020
A61-161-LP-021
A61-161-LP-022
A61-161-LP-023
A61-161-LP-024
A61-161-LP-025

Description

RatedVoltage Rating FaultCurrentRating

SUBSTATION SS-161 INTERNAL LIGHTING PANEL


SUBSTATION SS-161 EXTERNAL LIGHTING PANEL
SUBSTATION SS-161 ESSENTIAL LIGHTING PANEL
SUBSTATION SS-161 OUTLET PANEL
MOTOR SPACE HEATER POWER PANEL
INSTRUMENTATION POWER PANEL
CHLORINATION BUILDING INDOOR POWER PANEL
CHLORINATION BUILDING OUTDOOR LIGHTING PANEL
CHLORINATION BUILDING ESSENTIAL LIGHTING PANEL
INLET PUMP STATION NORMAL LIGHTING PANEL
INLET PUMP STATION ROADWAY LIGHTING PANEL
INLET PUMP STATION ESSENTIAL LIGHTING PANEL
INLET PUMP STATION OUTLET PANEL
SCREEN STATION NORMAL LIGHTING PANEL
SCREEN STATION ESSENTIAL LIGHTING PANEL
SCREEN STATION OUTLET PANEL
INLET CANAL NORTH ROADWAY LIGHTING PANEL
INLET CANAL SOUTH ROADWAY LIGHTING PANEL
INTAKE CHANNEL WEST ROADWAY LIGHTING PANEL
INTAKE CHANNEL EAST ROADWAY LIGHTING PANEL
OUTFALL LIGHTING PANEL

400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)
400(230)

Page 5 of 14

100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
225

Remarks

ELECTRICAL EQUIPMENT LIST


Job#: 10-01525-0006
Date: 16-08-2016
Unit#: A61
Doc#: A61-P-DOC-VE-746157
Rev#: 00
Index: P

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

Rev.

13.8 KV SWITCHGEAR
SubstationNo. EquipmentTagNo.
SS-161

A61-161-SG-301

Description

RatedVoltage Rating FaultCurrentRating

SWITCHGEAR, 13.8 KV, 3Ph, 3W, 60 Hz, 3000 A, 50 KA, M-T-M w/ ATS

Page 6 of 14

13.8 KV

3000 A

50 KA

Remarks
DWG. A61-P-E1L-VA-383360-001

Job#:
Date:
Unit#:
Doc#:
Rev#:
Index:

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

ELECTRICAL EQUIPMENT LIST


10-01525-0006
16-08-2016
A61
A61-P-DOC-VE-746157
00
P

Rev.

480 V SWITCHGEAR
SubstationNo.
SS-161

EquipmentTagNo.
A61-161-SG-001

Description
SWITCHGEAR, 480 V, 3Ph, 3W, 60 Hz, 4000 A, 85 KA, M-T-M w/ ATS

Page 7 of 14

RatedVoltage

Rating

FaultCurrentRating

Remarks

480 V

4000 A

85 KA

DWG. A61-P-E1L-VA-383362-001

Job#:
Date:
Unit#:
Doc#:
Rev#:
Index:

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

ELECTRICAL EQUIPMENT LIST


10-01525-0006
16-08-2016
A61
A61-P-DOC-VE-746157
00
P

Rev.

480 V MOTOR CONTROL CENTERS


Description

SubstationNo. EquipmentTagNo.
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161

A61-161-MCC-001
A61-161-MCC-002
A61-161-MCC-003
A61-161-MCC-005
A61-261-MCC-006
A61-261-MCC-007
A61-261-MCC-008

MCC,
MCC,
MCC,
MCC,
MCC,
MCC,
MCC,

480
480
480
480
480
480
480

V,
V,
V,
V,
V,
V,
V,

1200
1200
1200
1200
1200
1200
1200

A,
A,
A,
A,
A,
A,
A,

3Ph,
3Ph,
3Ph,
3Ph,
3Ph,
3Ph,
3Ph,

3W,
3W,
3W,
3W,
3W,
3W,
3W,

60
60
60
60
60
60
60

Hz,
Hz,
Hz,
Hz,
Hz,
Hz,
Hz,

85
85
85
85
85
85
85

RatedVoltage

KA
KA
KA
KA
KABy EC Vendor)
KA
KA

Page 8 of 14

480
480
480
480
480
480
480

V
V
V
V
V
V
V

Rating
1200
1200
1200
1200
1200
1200
1200

A
A
A
A
A
A
A

FaultCurrentRating
85
85
85
85
85
85
85

KA
KA
KA
KA
KA
KA
KA

Remarks
DWG. A61-P-E1L-VA-383362-002
DWG. A61-P-E1L-VA-383362-003
DWG. A61-P-E1L-VA-383362-004
DWG. A61-P-E1L-VA-383362-006
DWG. A61-004-P-007 (Vendor Drawing)
DWG. A61-P-E1L-VA-383362-007
DWG. A61-P-E1L-VA-383362-007

Job#:
Date:
Unit#:
Doc#:
Rev#:
Index:

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

ELECTRICAL EQUIPMENT LIST


10-01525-0006
16-08-2016
A61
A61-P-DOC-VE-746157
00
P

Rev.

480 V AUTO TRANSFER SWITCHES


SubstationNo. EquipmentTagNo.
SS-161

A61-161-ATS-001

Description
ATS, 480 V, 1200 A, 3Ph, 3W, 60 Hz, 85 KA

Page 9 of 14

RatedVoltage

Rating

FaultCurrentRating

Remarks

480 V

1200 A

85 KA

DWG. A61-P-E1L-VA-746200-001

Job#:
Date:
Unit#:
Doc#:
Rev#:
Index:

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

ELECTRICAL EQUIPMENT LIST


10-01525-0006
16-08-2016
A61
A61-P-DOC-VE-746157
00
P

Rev.

CONTROL AND RELAY PANELS


Description

SubstationNo. EquipmentTagNo.
PANEL, CONTROL,
PANEL, CONTROL,
PANEL, CONTROL,
PANEL, CONTROL,
PANEL, CONTROL,
PANEL, CONTROL,
PANEL, CONTROL,
PANEL, CONTROL,
PANEL, CONTROL,
PANEL, CONTROL,
PANEL, CONTROL,
PANEL, CONTROL,
229-XFR(T)-601
PANEL, CONTROL,
229-XFR(T)-602
PANEL CONTROL,
PANEL,
CONTROL
TRANSFORMER
PANEL, CONTROL,
TRANSFORMER

RatedVoltage

PSA PANEL 1(POWER SYSTEM AUTOMATION)


PSA PANEL 2(POWER SYSTEM AUTOMATION)
PSA PANEL 3(POWER SYSTEM AUTOMATION)
LIGHTING CONTROL PANEL SS-161
LOCAL FIRE ALARM CONTROL PANEL SS-161
SUBSTATION SS-161 HVAC CONTROL SYSTEM
TRANSFORMER A61-229-XFR(T)-601(MARSHALLING BOX)
TRANSFORMER A61-229-XFR(T)-602(MARSHALLING BOX)
TRANSFORMER A61-161-XFR(T)-301(MARSHALLING BOX)
TRANSFORMER A61-161-XFR(T)-302(MARSHALLING BOX)
TRANSFORMER A61-329-XFR(T)-301(MARSHALLING BOX)
LOCAL OLTC MOTOR DRIVE UNIT(MDU) OF TRANSFORMER A61-

SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161

A61-161-CP-001
A61-161-CP-002
A61-161-CP-003
A61-161-CP-004
A61-161-CP-005
A61-161-CP-006
A61-161-CP-007
A61-161-CP-008
A61-161-CP-009
A61-161-CP-010
A61-161-CP-011

SS-161

A61-161-CP-012

SS-161

A61-161-CP-013

SS-161

A61-161-CP-014

SS-161

A61-161-CP-015

SS-161

A61-161-CP-016

SS-161

A61-161-CP-017

SS-161

A61-161-CP-018

PANEL, CONTROL,DESOLVE GAS ANALYZER (DGA) PANEL TRANSFORMER A61-229XFR(T)-601


PANEL, CONTROL,DESOLVE GAS ANALYZER (DGA) PANEL TRANSFORMER A61-229XFR(T)-602
PANEL, CONTROL, SPACE HEATER CONTACTOR PANEL

EC BUILDING

A61-EC-CP-001

PANEL, CONTROL, LOCAL FIRE ALARM CONTROL PANEL ELECTRO-CHLORINATOR BUIL

125VDC
125VDC
125VDC
120VAC
120VAC
120VAC
480VAC
480VAC
480VAC
480VAC
480VAC
125VDC

LOCAL OLTC MOTOR DRIVE UNIT(MDU) OF TRANSFORMER A61125VDC


REMOTE TAPCHANGER CONTROL CUBICLE (RTCC) OF
A61-229-XFR(T)-601
REMOTE TAPCHANGER CONTROL CUBICLE (RTCC) OF
A61-229-XFR(T)-602

Page 10 of 14

125VDC
125VDC
230VAC
230VAC
480VAC
120VAC

Rating

FaultCurrentRating

Remarks
DWG. A61-010-P-007
DWG. A61-010-P-007
DWG. A61-010-P-007
DWG. A61-P-ECD-VA-014463
DWG. A61-B-FPS-VA-308768
DWG. A61-016-P-003
DWG. A61-P-ECD-VA-000620
DWG. A61-P-ECD-VA-000621
DWG. A61-P-ECD-VA-000622
DWG. A61-P-ECD-VA-000623
DWG. A61-P-ECD-VA-000624
DWG. A61-P-ECD-VA-000625
DWG. A61-P-ECD-VA-000626
DWG. A61-P-ECD-VA-000625
DWG. A61-P-ECD-VA-000626
DWG. A61-P-ECD-VA-000620
DWG. A61-P-ECD-VA-000621
DWG. A61-P-ECD-VA-721691
DWG. A61-B-FPS-VA-308769

ELECTRICAL EQUIPMENT LIST


Job#: 10-01525-0006
Date: 16-08-2016
Unit#: A61
Doc#: A61-P-DOC-VE-746157
Rev#: 00
Index: P

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

Rev.

UPS AND BATTERIES


SubstationNo.

EquipmentTagNo.

Description

FaultCurrentRating
(IfApplicable)

Remarks

RatedVoltage

Rating

480 V
480 V
240 VDC
240 VDC
240 VDC
240 VDC
208/120 VAC
208/120 VAC

40 KVA
40 KVA
215Ah
215Ah
200A
200A
150A
150A

DWG. A61-P-E1L-VA-746229-001
DWG. A61-P-E1L-VA-746229-001
DWG. A61-P-E1L-VA-746229-001
DWG. A61-P-E1L-VA-746229-001
DWG. A61-P-E1L-VA-746229-001
DWG. A61-P-E1L-VA-746229-001
DWG. A61-P-ECD-VA-721682
DWG. A61-P-ECD-VA-721683

SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161

A61-161-UPS-001A
A61-161-UPS-001B
A61-161-SB-001A
A61-161-SB-001B
A61-161-BCB-001A
A61-161-BCB-001B
A61-161-PP-001A
A61-161-PP-001B

UPS, AC, SYSTEM A, SUBSTATION SS-161 PIR (mainly supplying the PCS system)
UPS, AC, SYSTEM B, SUBSTATION SS-161 PIR
BATTERY, SYSTEM A, SUBSTATION SS-161 PIR UPS
BATTERY, SYSTEM B, SUBSTATION SS-161 PIR UPS
CIRCUIT BREAKER BOX, BATTERY SYSTEM A, SUBSTATION SS-161 PIR UPS
CIRCUIT BREAKER BOX, BATTERY SYSTEM B, SUBSTATION SS-161 PIR UPS
PANEL, POWER, AC, UPS SYSTEM A, SUBSTATION SS-161 PIR
PANEL, POWER, AC, UPS SYSTEM B, SUBSTATION SS-161 PIR

SS-161
SS-161
SS-161
SS-161
SS-161

A61-161-UPS-002A
A61-161-UPS-002B
A61-161-SB-002A
A61-161-SB-002B
A61-161-PP-002

UPS, AC, SYSTEM A, SUBSTATION SS-161 FOR COMMUNICATION SYSTEM


UPS, AC, SYSTEM B, SUBSTATION SS-161 FOR COMMUNICATION SYSTEM
BATTERY, SYSTEM A, SUBSTATION SS-161 FOR COMMUNICATION SYSTEM UPS
BATTERY, SYSTEM B, SUBSTATION SS-161 FOR COMMUNICATION SYSTEM UPS
PANEL, POWER, AC, UPS SYSTEM A, SUBSTATION SS-161 FOR INSTRUMENTS

480 V
480 V
125 VDC
125 VDC
120 VAC

5 KVA
5 KVA
45Ah
45Ah
100A

DWG. A61-037-P-015
DWG. A61-037-P-015
DWG. A61-037-P-015
DWG. A61-037-P-015
DWG. A61-P-ECD-VA-721684

SS 161
SS-161
SS-161
SS-161
SS-161
SS-161

A61 161 UPS 003A


A61-161-UPS-003A
A61-161-UPS-003B
A61-161-SB-003A
A61-161-SB-003B
A61-161-PP-003

UPS, AC,
UPS
AC SYSTEM A,
A SUBSTATION SS
SS-161
161 FOR PROCESS CCTV
UPS, AC, SYSTEM B, SUBSTATION SS-161 FOR PROCESS CCTV
BATTERY, SYSTEM A, SUBSTATION SS-161 FOR PROCESS CCTV
BATTERY, SYSTEM B, SUBSTATION SS-161 FOR PROCESS CCTV
PANEL, POWER, AC, UPS SYSTEM A, SUBSTATION SS-161 FOR

& ACCESS
& ACCESS
& ACCESS
& ACCESS
IN-PLANT

CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM UPS
CONTROL SYSTEM UPS
COMMUNICATION

480 V
480 V
125 VDC
125 VDC
120 VAC

6 KVA
6 KVA
445Ah
445Ah
100A

DWG. A61
DWG
A61-037-P-016
037 P 016
DWG. A61-037-P-016
DWG. A61-037-P-016
DWG. A61-037-P-016
DWG. A61-P-ECD-VA-721685

SS-161
SS-161
SS-161
SS-161
SS-161

A61-161-UPS-004A
A61-161-UPS-004B
A61-161-SB-004A
A61-161-SB-004B
A61-161-PP-004

UPS, AC, SYSTEM A, SUBSTATION SS-161 FOR PROCESS CCTV


UPS, AC, SYSTEM B, SUBSTATION SS-161 FOR PROCESS CCTV
BATTERY, SYSTEM A, SUBSTATION SS-161 FOR PROCESS CCTV
BATTERY, SYSTEM B, SUBSTATION SS-161 FOR PROCESS CCTV
PANEL, POWER, AC, UPS SYSTEM A, SUBSTATION SS-161 FOR

& ACCESS CONTROL SYSTEM


& ACCESS CONTROL SYSTEM
& ACCESS CONTROL SYSTEM UPS
& ACCESS CONTROL SYSTEM UPS
DATA NETWORK SYSTEM &

480 V
480 V
125 VDC
125 VDC
230 VAC

3 KVA
3 KVA
245Ah
245Ah
100A

DWG. A61-037-P-017
DWG. A61-037-P-017
DWG. A61-037-P-017
DWG. A61-037-P-017
DWG. A61-P-ECD-VA-721686

Page 11 of 14

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

ELECTRICAL EQUIPMENT LIST


Job#: 10-01525-0006
Date: 16-08-2016
Unit#: A61
Doc#: A61-P-DOC-VE-746157
Rev#: 00
Index: P

Rev.

BATTERIES AND CHARGERS


SubstationNo. EquipmentTagNo.
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161
SS-161

A61-161-BC-005A
A61-161-BC-005B
A61-161-SB-005A
A61-161-SB-005B
A61-161-BCB-005A
A61-161-BCB-005B
A61-161-PP-005

Description
CHARGER, BATTERY, 125 VDC, SYSTEM A, SUBSTATION SS-161
CHARGER, BATTERY, 125 VDC, SYSTEM B, SUBSTATION SS-161
BATTERY, DC, SUBSTATION SS-161 DC SYSTEM A
BATTERY, DC, SUBSTATION SS-161 DC SYSTEM B
CIRCUIT BREAKER BOX, BATTERY, DC SYSTEM A, SUBSTATION SS-161
CIRCUIT BREAKER BOX, BATTERY, DC SYSTEM B, SUBSTATION SS-161
PANEL, POWER, DC, SUBSTATION SS-161 DC DISTRIBUTION PANEL

Page 12 of 14

RatedVoltage

Rating

480 V
480 V
125 VDC
125 VDC
125 VDC
125 VDC
125 VDC

80A
80A
185Ah
185Ah
160A
160A
150A

FaultCurrentRating(If
Applicable)

Remarks
DWG. A61-P-E1L-VA-746208-001
DWG. A61-P-E1L-VA-746208-001
DWG. A61-P-E1L-VA-746208-001
DWG. A61-P-E1L-VA-746208-001
DWG. A61-P-E1L-VA-746208-001
DWG. A61-P-E1L-VA-746208-001
DWG. A61-P-ECD-VA-721687

ELECTRICAL EQUIPMENT LIST


Job#: 10-01525-0006
Date: 16-08-2016
Unit#: A61
Doc#: A61-P-DOC-VE-746157
Rev#: 00
Index: P

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

Rev.

CABLE BUS
Description

SubstationNo. EquipmentTagNo.
SS-161
SS-161
SS-161
SS-161
SS-161

A61-161-CBD-301
A61-161-CBD-302
A61-161-CBD-001
A61-161-CBD-002
A61-161-CBD-003

CABLE
CABLE
CABLE
CABLE
CABLE

BUS,
BUS,
BUS,
BUS,
BUS,

RatedVoltage

13.8 KV, 3000 A, 65 KA, 3Ph, 3W


13.8 KV, 3000 A, 65 KA, 3Ph, 3W
480 V, 4000 A, 85 KA, 3Ph, 3W
480 V, 4000 A, 85 KA, 3Ph, 3W
480 V, 1200 A, 85 KA, 3Ph, 3W

13.8
13.8
480
480
480

Page 13 of 14

KV
KV
V
V
V

Rating
3000
3000
4000
4000
1200

A
A
A
A
A

FaultCurrentRating
(IfApplicable)
65 KA
65 KA
85 KA
85 KA
85 KA

Remarks
DWG.
DWG.
DWG.
DWG.
DWG.

A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001
A61-P-E1L-VA-746200-001

JAZAN INTEGRATED GASIFICATION COMBINED CYCLE (JIGCC) PROJECT


JAZAN, SAUDI ARABIA
SEA WATER SYSTEM

Job#:
Date:
Unit#:
Doc#:
Rev#:
Index:

ELECTRICAL EQUIPMENT LIST


10-01525-0006
16-08-2016
A61
A61-P-DOC-VE-746157
00
P

Rev.

JUNCTION BOX
SubstationNo.
SS-161

EquipmentTagNo.
A61-161-JB-OC101

Description
JUNCTION BOX, OVERHEAD CRANE, CHLORINATION BUILDING

Page 14 of 14

RatedVoltage
480 V

Remarks

Vous aimerez peut-être aussi