Vous êtes sur la page 1sur 2

A brand of the

FP200 Gold Multicore

FIRE RESISTANT MULTICORE CABLE 300/500 V

Certificate No 077a
Certificate No 077b

Cable Description
Conductor

Key Applications

Plain annealed solid copper conductors to BS EN 60228 class 1.

> Control cable for circuits that require circuit integrity to BS6387 CWZ only
> Low Smoke
> Zero Halogen
> Reduced flame propogation

Insulation
High performance, damage resistant Insudite to meet
BS EN 50363-5, Type EI5.

Overall metallic screen and CPC


Polyester backed laminated aluminium tape bonded to outer sheath to
provide overall screen. In contact with 0.5mm, tinned annealed copper
drain wire and laid-up with the cores to provide automatic screen
earthing.

British Standards
> BS7629-1 Construction of screened fire resistant cables
> BS6387 CWZ Circuit integrity under fire
> EN 61034-2 Low smoke test
> BS EN 60754-1 Zero Halogen Test

Core identification
7-12-19 cores white with printed number.

Robust thermoplastic low smoke, zero halogen and reduced flame


propagation outer sheath. Standard colours white and red with bespoke
colours available to special order. For external exposure use white
sheath. For red sheath use suitable shading protection from UV.

r=6d

BS EN 60754-1

BS6387 CWZ

Ref:FP200GoldMulti/10/16

Sheath

Conductor Approximate
Mean
Approximate
Overall
Construction
overall
cable
Diameter
diameter
weight

Nominal
cross
sectional
area
2

mm

no/mm

mm

Maximum
conductor
resistance
at 20C

kg/km

Current
Current
rating DC or rating DC or
single phase single phase
AC
AC
Enclosed
Clipped direct
Amps
Amps

/km

Volt drop
DC or single
phase
AC

Recommended accessories
Colour - White or Red

LSOH
fixing
clips

mV/A/m

Nylon

LSOH
gland

Seven Core
1.0

1/1.13

12.5

200

18.1

13

15

44

AP12

252

1.5

1/1.38

13.5

250

12.1

16.5

19.5

29

AP13

252

2.5

7/0.67

16.5

380

7.41

23

27

18

AP16

254

1.5

1/1.38

17.5

395

12.1

16.5

19.5

29

AP18

254

2.5

7/0.67

22.0

630

7.41

23

27

18

AP22

255

19.5

29

AP20

255

Twelve core

Nineteen Core
1.5

1/1.38

20.5

580

12.1

16.5

Notes to table
> Recommended clip spacing 300 mm horizontal and 400mm vertical using only metallic fixings.
> Minimum recommended installation temperature 0C. Installation methods for current rating in accordance with BS7671/IET Wiring Regulations.
> The tabulated ratings are based upon a 30C ambient temperature and 70C operating temperature. For other ambient temperatures or where cables are
grouped together, appropriate rating factors should be applied.

Temperature ratings factor

Table 4B1

Ambient TemperatureC

25

30

35

40

45

50

Rating factor

1.03

1.00

0.94

0.87

0.79

0.71

Rating factors for multiple loaded cores


Table 4B5

Number of loaded cores

10

12

14

19

Rating factor

0.72

0.67

0.63

0.56

0.53

0.51

0.45

UK Sales enquiries
Tel: 0845 767 8345
Fax: 0238 029 5465

Overseas Sales enquiries


Tel: +44 (0) 23 8029 5481
Fax: +44 (0) 23 8029 5465

UK Technical helpline
Tel: 0238 029 5465
Fax: 0238 029 5002

Overseas Technical hotline


Tel: ++44 23 8029 5481
Fax: ++44 23 8029 5002

For further information please


see our dedicated FP Cables website:
www.fpcables.co.uk

Should you have any concerns about


unsafe, non-approved or counterfeit
cable, please contact the ACI
Tel: 020 8946 6978
Email: report@aci.org.uk
A brand of the

Ref: FP200GoldMulti/10/16

Prysmian Cables & Systems Limited


Chickenhall Lane
Eastleigh
Hampshire
SO50 6YU

Information hotline
Tel: ++44 (0) 23 8029 5029
Fax: ++44 (0) 23 8029 5437
cables.marketing.uk@prysmian.
com

Vous aimerez peut-être aussi