Académique Documents
Professionnel Documents
Culture Documents
networks
electrical-engineering-portal.com/distribution-transformers-lv-networks
Google+
1/4/2017
Selection of distribution transformers for supplying power to LV networks (photo credit: gelexcambodia.com)
Transformer losses are made up of no-load losses and short circuit losses . The no-load losses are caused by the
continuous reversal of magnetization of the iron core and are practically constant and independent of loading. The
short circuit losses are made up of the ohmic losses in the windings and losses due to leakage elds. They are
proportional to the square of the loading.
Oil-lled transformers and cast resin dry-type transformers are preferred. The use of askarel transformers is
forbidden!
In this technical article, the most important criteria for the selection of distribution transformers in the power range
1/8
from 50 to 2500 kVA for supplying power to low voltage networks will be discussed.
1. Requirement of operational safety:
1. Routine tests (losses, u k, voltage test)
2. Type testing (heating, surge voltage)
3. Special tests (short circuit strength, noise)
2. Electrical conditions:
1. Short circuit voltage
2. Connection symbol / vector group (learn more)
3. Transformation ratio
3. Installation conditions:
1. Interior and outside installation
2. Special local conditions
3. Environmental protection conditions
4. Designs: oil-lled or cast resin dry-type transformer
4. Operating conditions:
1. Loading capacity (oil-lled transformers or cast resin dry-type transformers)
2. Load uctuations
3. Number of hours in operation
4. Eiciency (oil-lled transformers or cast resin dry-type transformers)
5. Voltage regulation
6. Parallel transformer operation (learn more)
2/8
3/8
Where:
1. Cable conduit
2. Zinc-plated at steel grate
3. Exhaust opening with protective grate
4. Unscrewed conduit with pump
5. Ramp
6. Air intake opening with protective grave
7. Gravel or crushed rock layer
8. Ledge
The installation of transformers should be free of underground water and ooding. The cooling must be protected
against sunlight. Fire protection measures and environmental compatibility must also be ensured. Figure 1 illustrates
a transformer with oil lling < 1000 liters. Here, an impermeable oor is suicient.
For oil lling > 1000 liters, oil collecting troughs or oil sumps are mandatory.
The heat losses of transformers must be properly dissipated! This requires air intake and exhaust openings. The
air intake must ow in underneath the transformer close to the oor and the exhaust must be led upwards.
The size of the exhaust opening is shown without grate in Figure 2 for a room heating of 15 K.
4/8
Pv = P0 + k Pk75 [kW]
The meanings of the symbols are:
A Air exaust opening and intake opening
Pv Transformer power loss
k = 1.06 for oil-lled transformers
k = 1.2 for cast resin transformers
Po No-load losses
Pk75 Short circuit losses at 75 in kW
h Dierence in height in meters
Figure 3 gives the permissible overload capacity of cast resin transformers in the power range from 400 to 2500
kVA. The determination of the loading capacity of oil-lled transformers can be made on the basis of IEC 60076-1.
The heating losses which arise while operating a transformer (Figure 4) must be dissipated. If it is not possible owing
to the conditions for installation to utilize natural ventilation, it is necessary to install a fan. The overall temperature of
the transformer must not exceed 40C.
5/8
6/8
The acoustical power (Figure 6) is a measure of the noise level produced by an acoustical source .
7/8
8/8