DESCRIPTION OF OPTIONS

Gen-set Controller, GC-1F


Option H2, Modbus communication

Description of option
Parameter list
Data tables
Parameter table

Document no.: 4189340483F

GC-1F

Option H2, Modbus communication

This description of options covers the following products:


GC-1F
GC-1F/2

DEIF A/S

SW version 1.2x.x
SW version 2.0x.x or later

Page 2 of 64

GC-1F

Option H2, Modbus communication

Table of contents
1.

WARNINGS AND LEGAL INFORMATION ........................................................................... 4


LEGAL INFORMATION AND RESPONSIBILITY ..................................................................................... 4
ELECTROSTATIC DISCHARGE AWARENESS ..................................................................................... 4
SAFETY ISSUES ............................................................................................................................ 4
DEFINITIONS ................................................................................................................................ 4

2.

DESCRIPTION OF OPTION .................................................................................................. 5


H2 OPTION ................................................................................................................................... 5
TERMINAL DESCRIPTION................................................................................................................ 5
COMMUNICATION SETTINGS .......................................................................................................... 5
W IRING ........................................................................................................................................ 5

3.

PARAMETERS ....................................................................................................................... 6

4.

DATA TABLES....................................................................................................................... 7
CONFIGURABLE AREA (READ ONLY) (FUNCTION CODE 04H) ............................................................. 7
MEASUREMENT TABLE (READ ONLY) (FUNCTION CODE 04H) .......................................................... 13
ALARM AND STATUS TABLE (READ ONLY) (FUNCTION CODE 04H) ................................................... 17
CONTROL REGISTER TABLE READ(03H)/WRITE(10H) .................................................................... 26
COMMAND FLAGS TABLE (WRITE ONLY) (FUNCTION CODE 0FH) ..................................................... 27
STATUS FLAGS TABLE (READ ONLY) (FUNCTION CODE 02H)........................................................... 29

5.

PARAMETER TABLE .......................................................................................................... 30


PARAMETER TABLE READING AND WRITING .................................................................................. 30
PARAMETER TABLE ..................................................................................................................... 33
DIGITAL INPUT TABLE (READ ONLY 02H) ....................................................................................... 60
DIGITAL OUTPUT TABLE (READ ONLY 02H) .................................................................................... 63

DEIF A/S

Page 3 of 64

GC-1F

Option H2, Modbus communication

1. Warnings and legal information


Legal information and responsibility
DEIF takes no responsibility for installation or operation of the gen-set. If there is any doubt
about how to install or operate the gen-set controlled by the unit, the company responsible for
the installation or the operation of the set must be contacted.

The units are not to be opened by unauthorised personnel. If opened anyway, the
warranty will be lost.

Electrostatic discharge awareness


Sufficient care must be taken to protect the terminals against static discharges during the
installation. Once the unit is installed and connected, these precautions are no longer necessary.

Safety issues
Installing the unit implies work with dangerous currents and voltages. Therefore, the installation
should only be carried out by authorised personnel who understand the risks involved in working
with live electrical equipment.

Be aware of the hazardous live currents and voltages. Do not touch any AC
measurement inputs as this could lead to injury or death.

Definitions
Throughout this document a number of notes and warnings will be presented. To ensure that these
are noticed, they will be highlighted in order to separate them from the general text.
Notes
The notes provide general information which will be helpful for the reader to
bear in mind.

Warnings
The warnings indicate a potentially dangerous situation which could result in
death, personal injury or damaged equipment, if certain guidelines are not
followed.

DEIF A/S

Page 4 of 64

GC-1F

Option H2, Modbus communication

2. Description of option
H2 option
The option H2 allows other systems to read all values in GC-1F and to send different commands. H2 is a hardware option.

Terminal description
Term.
49
50
51
52

Function
DATA - (B)
GND
DATA + (A)
Not used

Description
Modbus RTU, RS485

Communication settings
These are the GC-1F RS485 communication settings:
a.
b.
c.
d.

9600 or 19200 bps


8 data bits
None parity
1 stop bit

Wiring
See the chapter Communication in the Installation Instructions and Reference
Handbook.

DEIF A/S

Page 5 of 64

GC-1F

Option H2, Modbus communication

3. Parameters
The option H2 relates to the parameters 7510 and 7520.
For further information, please see the Installation Instructions and Reference Handbook,
document number 4189340472.

DEIF A/S

Page 6 of 64

GC-1F

Option H2, Modbus communication

4. Data tables
Configurable area (read only) (function code 04h)
Address

Content

0
1
2
3
4
5
6
7
8
9
10

UL1-L2
UL2-L3
UL3-L1
UL1-N
UL2-N
UL3-N
fL1
IL1
IL2
IL3
PGEN

11

QGEN

12
13

SGEN
Cos-phi

14 [HI]
15 [LO]
16 [HI]
17 [LO]
18
19
20
21
22
23
24
25
26
27
28
29
30 [HI]
31 [LO]
32
33
34
35
36
37
DEIF A/S

EGEN
UMainsL1-L2
UMainsL2-L3
UMainsL3-L1
UMainsL1-N
UMainsL2-N
UMainsL3-N
fMains

Alarms
Alarms
Start attempts
Abs. run. hours
GBoperation
MBoperation
USUPPLY
RPM

Type
ML-2
Generator voltage. Measured in [V]
Generator voltage. Measured in [V]
Generator voltage. Measured in [V]
Generator voltage. Measured in [V]
Generator voltage. Measured in [V]
Generator voltage. Measured in [V]
Generator freq. Measured in [Hz/100]
Generator current. Measured in [A]
Generator current. Measured in [A]
Generator current. Measured in [A]
Generator active power. Measured in [kW]. Negative
value means reverse power
Generator reactive power. Measured in [kVAr]. Positive
value means generated inductive reactive power
Generator apparent power. Measured in [kVA]
-99...0...100 generator cosinus-phi. Measured in cosphi:100. Negative value means capacitive cos-phi

Energy counter. Measured in [kWh]. Max. 300000


MWh
Mains voltage. Measured in [V]
Mains voltage. Measured in [V]
Mains voltage. Measured in [V]
Mains voltage. Measured in [V]
Mains voltage. Measured in [V]
Mains voltage. Measured in [V]
Mains frequency L1. Measured in [Hz/100]
Reserved
Reserved
Number of alarms
Number of unack. alarms
Start attempts
Hour
GB operations counter
MB operations counter
Supply voltage. Measured in [V/10]
Reserved
RPM
Multi-input 1, unscaled
Page 7 of 64

GC-1F

Address
38
39
40
41
42
43
44
45
46
47
48

Option H2, Modbus communication

Content

Protection
alarms

49

Protection
alarms

50

Protection
alarms

DEIF A/S

Type
Multi-input 2, unscaled
Multi-input 3, unscaled
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Bit
Menu
no.
Bit 0
1000
Bit 1
Bit 2
Bit 3
1030
Bit 4
1040
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
1150
Bit 12
1160
Bit 13
1170
Bit 14
1180
Bit 15
Bit 0
1210
Bit 1
1220
Bit 2
Bit 3
1240
Bit 4
1250
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2

Alarm
G -P> 1
Reserved
Reserved
G I> 1
G I> 2
Reserved
Reserved
Reserved
Reserved
G U> 1
G U> 2
G U< 1
G U< 2
Reserved
G f> 1
G f> 2
Reserved
G f< 1
G f< 2
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

Page 8 of 64

GC-1F

Address

51

52

DEIF A/S

Option H2, Modbus communication

Content

Synchronisation
alarms

Digital inputs

Type
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

Reserved
Reserved
Reserved
Reserved
1450
1460

G P> 1
G P> 2
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

2150
2160
2170

Phase sequence error


GB open failure
GB close failure
GB pos. failure
MB open failure
MB close failure
MB pos. failure
Reserved
Not used
Not used
Not used
Not used
Not used

2200
2210

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Not used
Page 9 of 64

GC-1F

Address
53

54

55

DEIF A/S

Option H2, Modbus communication

Content
Digital inputs

Digital inputs

Analogue inputs

Type
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11

3000
3010
3020
3030
3040
3050

Dig. input 1
Dig. input 2
Dig. input 3
Dig. input 4
Dig. input 5
Dig. input 6
Not used
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Not used

3400
3410
3420

3490

Dig. multi-input 1
Dig. multi-input 2
Dig. multi-input 3
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Dig. input 19-20, emergency
stop
Not used
Not used
Not used
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Not used
Not used
Not used

Page 10 of 64

GC-1F

Address

56

57

58

DEIF A/S

Option H2, Modbus communication

Content

Analogue inputs

Type
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8

Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used

4510
4520
4620
4610
4600
4550
4570
5000
5010
5020
5030
5040

Multi-input 1.1
Multi-input 1.2
W. failure, multi-input 1
Multi-input 2.1
Multi-input 2.2
W. failure, multi-input 2
Multi-input 3.1
Multi-input 3.2
W. failure, multi-input 3
Overspeed 1
Overspeed 2
VDO fuel level 1.3
Charger gen.
V-Belt
Generator Hz/V failure
Start failure
Relay 21
Relay 22
Relay 23
Relay 24
Relay 26
Not used
Not used
Not used
Not used
Page 11 of 64

GC-1F

Address

Option H2, Modbus communication

Content

59

60

61- 499

DEIF A/S

Communication

Configurable

Type
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Reserved

5110

7570
7580
7590
7600
7610
7620
7630
7640
7650
7660

Not used
Not used
Relay 3
Not used
Not used
Not used
Not used
OFF
Manual
Reserved
Auto
Test
Island
AMF
Not used
Not used
Not used
Load take over
Not used
Not used
Not used
Not used
AMF active
EIC comm. error
EIC warning
EIC shutdown
EIC overspeed
EIC coolant temp. 1
EIC coolant temp. 2
EIC oil pressure 1
EIC oil pressure 2
EIC oil temperature 1
EIC oil temperature 2
Not used
Not used
Not used
Not used
Not used
Not used

Page 12 of 64

GC-1F

Option H2, Modbus communication

Measurement table (read only) (function code 04h)


Address
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522

Content
UL1-L2
UL2-L3
UL3-L1
UL1-N
UL2-N
UL3-N
fGEN

IL1
IL2
IL3
PL1
PL2
PL3
PGEN
QL1
QL2
QL3
QGEN

523
SL1
524
SL2
525
SL3
526
SGEN
527
528 [HI]
529 [LO]
530
531
532
533

DEIF A/S

Type
Application version
Generator voltage. Measured in [V]
Generator voltage. Measured in [V]
Generator voltage. Measured in [V]
Generator voltage. Measured in [V]
Generator voltage. Measured in [V]
Generator voltage. Measured in [V]
Generator freq.
Measured in [Hz/100]
Reserved
Reserved
Reserved
Reserved
Reserved
Generator current. Measured in [A]
Generator current. Measured in [A]
Generator current. Measured in [A]
Generator active power. Measured in [kW]. Negative value
means reverse power
Generator active power. Measured in [kW]. Negative value
means reverse power
Generator active power. Measured in [kW]. Negative value
means reverse power
Generator total active power. Measured in [kW]. Negative
value means reverse power.
Generator reactive power. Measured in [kVAr]. Positive
value means generated inductive reactive power
Generator reactive power. Measured in [kVAr]. Positive
value means generated inductive reactive power
Generator reactive power. Measured in [kVAr]. Positive
value means generated inductive reactive power
Generator total reactive power. Measured in [kVAr].
Positive value means generated inductive reactive power
Generator apparent power. Measured in [kVA]. Positive
value means generated inductive reactive power
Generator apparent power. Measured in [kVA]. Positive
value means generated inductive reactive power
Generator apparent power. Measured in [kVA]. Positive
value means generated inductive reactive power
Generator total apparent power. Measured in [kVA].
Positive value means generated inductive reactive power
Reserved
Reserved
Reserved

Page 13 of 64

GC-1F

Address
534
535
536 [HI]
537 [LO]

Option H2, Modbus communication

Content

Type
Reserved

EGEN

Total energy counter. Measured in [kWh]. Max.


300000MWh
-99...0...100 Generator cos . Measured in cos x 100.
Negative value means capacitive cos
Mains voltage. Measured in [V]
Mains voltage. Measured in [V]
Mains voltage. Measured in [V]
Mains voltage. Measured in [V]
Mains voltage. Measured in [V]
Mains voltage. Measured in [V]
Mains freq. Measured in [Hz/100]
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Absolute running hour counter

Cos
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554 [HI]
555[LO]
556
567
558
559
560
561
562
563
564
566
567
568
569
570
571
572
576
580
581
582
583
584
585
DEIF A/S

UL1-L2
UL2-L3
UL3-L1
UL1-N
UL2-N
UL3-N
fMains

Running time

Reserved

GBoperation
MBoperation
Start attempts
USUPPLY
Service timer
Service timer
Service timer
Service timer
RPM
Multi-input
Multi-input
Multi-input
Multi-input
Multi-input
Multi-input

Number of alarms
Number of unacknowledged alarms
Number of acknowledged active alarms
Reserved
Reserved
Generator/circuit breaker
operations counter
Mains breaker operation counter
Number of start attempts
Supply voltage. Measured in [V/10]
Reserved
Service timer 1 (running hours)
Service timer 1 (days)
Service timer 2 (running hours)
Service timer 2 (days)
Running feedback RPM
Multi-input 2, unscaled
Multi-input 3, unscaled
Multi-input 1, unscaled
Multi-input 2, scaled
Multi-input 3, scaled
Multi-input 1, scaled
Page 14 of 64

GC-1F

Address

Option H2, Modbus communication

Content

586
587
588
589
592
593
594
595
596
597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
642
643
644
645
646
647
648
649
660
661
662
663
664
665
DEIF A/S

Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication
Engine communication

Extern IO
Extern IO
Extern IO
Extern IO
Extern IO
Extern IO

Type
Reserved
Reserved
Reserved
Reserved
Reserved
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Refer to option H5 manual
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Analogue input 1
Analogue input 2
Analogue input 3
Analogue input 4
Analogue input 5
Analogue input 6
Page 15 of 64

GC-1F

Address
666
667
668-999
900-908

DEIF A/S

Option H2, Modbus communication

Content
Extern IO
Extern IO
Engine communication

Type
Analogue input 7
Analogue input 8
Not used
Refer to option H5 manual

Page 16 of 64

GC-1F

Option H2, Modbus communication

Alarm and status table (read only) (function code 04h)


Address
1000

1001

1002

1003

DEIF A/S

Content
Protection
alarms

Protection
alarms

Protection
alarms

Protection
alarms

Type
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2

1000
1020
1030
1040

1090
1120
1130
1140
1150
1160
1170
1180
1210
1220
1240
1250

1450
1460

G -P> 1
Reserved
Reserved
G I> 1
G I> 2
Reserved
Reserved
Reserved
Reserved
G I>> 1
G I>> 2
G U> 1
G U> 2
G U< 1
G U< 2
Reserved
G f> 1
G f> 2
Reserved
G f< 1
G f< 2
Reserved
BB U> 1
BB U> 2
Reserved
BB U< 1
BB U< 2
Reserved
Reserved
BB f> 1
BB f> 2
Reserved
BB f< 1
BB f< 2
Reserved
Reserved
Reserved
Reserved
Reserved
G P> 1
G P> 2
Reserved
Reserved
Reserved
Reserved
Reserved
-Q>
Q>
Reserved
Reserved
Reserved
Page 17 of 64

GC-1F

Address

1004
1005

Option H2, Modbus communication

Content

Protection
alarms
Synchronisation
alarms

1006

Regulation
alarms

1007

Digital inputs

DEIF A/S

Type
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5

1620

2150
2160
2170
2200
2210

3000
3010
3020
3030
3040
3050

Reserved
Not used
Not used
Not used
Mains unbalanced voltage
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Reserved
Reserved
Reserved
Reserved
Phase seq error
GB open failure
GB close failure
GB pos failure
MB open failure
MB close failure
MB pos failure
Reserved
Not used
Not used
Not used
Not used
Not used
Reserved
Reserved
Reserved
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Dig. input 1
Dig. input 2
Dig. input 3
Dig. input 4
Dig. input 5
Dig. input 6
Page 18 of 64

GC-1F

Address

Option H2, Modbus communication

Content

1008

Digital inputs

1009

Digital inputs

1010

Protection
alarms

DEIF A/S

Type
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10

3400
3410
3420
3404
3404
3424

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Not used
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Not used
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Dig. multi-input 1
Dig. multi-input 2
Dig. multi-input 3
Wire failure, dig. multi-input 1
Wire failure, dig. multi-input 2
Wire failure, dig. multi-input 3
Reserved
Reserved
Reserved
Reserved
Reserved
Page 19 of 64

GC-1F

Address

Option H2, Modbus communication

Content

1011

Protection
alarms

1012

Analogue inputs

1013

Analogue inputs

DEIF A/S

Type
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

3490

4510
4520
4620
4610
4600
4560

Reserved
Dig. input 19-20/Emergency STOP
Not used
Not used
Not used
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Multi-input 1.1
Multi-input 1.2
W. failure, multi-input 1
Multi-input 2.1
Multi-input 2.2
W. failure, multi-input 2
Multi-input 3.1
Multi-input 3.2
W. failure, multi-input 3
Overspeed 1
Overspeed 2
VDO fuel level 1.3
Charger gen
V-Belt
Generator Hz/V failure
Start failure
Page 20 of 64

GC-1F

Address
1014

Option H2, Modbus communication

Content
Analogue inputs

1015

System/general
alarms

1016

Relay outputs

1017

DEIF A/S

Relay outputs

Type
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4

4580
4960
4970

4610

6110
6120

5000
5010
5020
5030
5040

5110

Stop failure
U< aux. supply term. 1
U> aux. supply term. 1
Reserved
Reserved
Charger Gen
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Service timer 1
Service timer 2
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Fuel fill check
Not used
Not used
Relay 21
Relay 22
Relay 23
Relay 24
Relay 26
GB On
MB On
Not used
Not used
Not used
Not used
Relay 3
Reserved
Reserved
Reserved
Not used
Reserved
Reserved
Reserved
Reserved
Reserved
Page 21 of 64

GC-1F

Address

1018

Option H2, Modbus communication

Content

Status

1019

1020

DEIF A/S

Engine
communication

Type
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Mains failure
MB pos ON
Reserved
Reserved
GB pos ON
Reserved
Engine running
Running detection, timer expired
DG Hz/V OK, timer expired
Reserved
Reserved
Not used
Not used
Not used
Not used
Not used
OFF
Manual
Reserved
Auto
Test
Island
AMF
Reserved
Reserved
Reserved
Load take over
Not used
Not used
Not used
Not used
AMF active
EIC comm. error
EIC warning
EIC shutdown
EIC overspeed
EIC coolant temp. 1
EIC coolant temp. 2
EIC oil pressure 1
EIC oil pressure 2
EIC oil temperature 1
EIC oil temperature 2
Page 22 of 64

GC-1F

Address

1021-1023
1024

1025
1026

1027

DEIF A/S

Option H2, Modbus communication

Content

Engine
communication
Engine
communication

KW2000,
Scania

KW2000,
Scania

Type
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11

Not used
Not used
Not used
Not used
Not used
Not used
Refer to option H5 manual for bit 1649

Refer to option H5 manual for bit 0-15

Reserved
Overreving
Speed sensor 1
Speed sensor 2
Water temp. sensor
Charge air temp. sensor
Charge air pressure sensor
Oil temp. sensor
Oil pressure sensor
Fault in cor.
Throttle pedal
Emergency stop override
Oil pressure prot.
Wrong parameter
Battery voltage
Oil pressure prot.
Emergency stop cor.
CAN cir. defect
CAN mess. DLN1
Wrong CAN version
Un. inj. cyl. 1
Un. inj. cyl. 2
Un. inj. cyl. 3
Un. inj. cyl. 4
Un. inj. cyl. 5
Un. inj. cyl. 6
Un. inj. cyl. 7
Un. inj. cyl. 8
Extra ana. inp.
Page 23 of 64

GC-1F

Address

1028

1029-1030
1031- 1035
1036

Option H2, Modbus communication

Content

KW2000,
Scania

Extern IO
analogue in

1037

Extern IO
analogue in

1038

Extern IO digital
in

DEIF A/S

Type
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8

System shutdown
Coola. L. prot.
HW watchdog
Fault in RAM
Seal
Coola. shut OFF
Overheat prot.
Fault in TPU
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Reserved for KW2000
Not used
External analogue 1.1
External analogue 1.2
Reserved
External analogue 2.1
External analogue 2.2
Reserved
External analogue 3.1
External analogue 3.2
Reserved
External analogue 4.1
External analogue 4.2
Reserved
External analogue 5.1
External analogue 5.2
External analogue 6.1
External analogue 6.2
Reserved
External analogue 7.1
External analogue 7.2
Reserved
External analogue 8.1
External analogue 8.2
External digital input 1
External digital input 2
External digital input 3
External digital input 4
External digital input 5
External digital input 6
External digital input 7
External digital input 8
External digital input 9
Page 24 of 64

GC-1F

Address

Option H2, Modbus communication

Content

1039

Extern IO digital
out

1040 - 1054
1055

Not used
Alarm LEDs

DEIF A/S

Type
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

External digital input 10


External digital input 11
External digital input 12
External digital input 13
External digital input 14
External digital input 15
External digital input 16
External digital output 1
External digital output 2
External digital output 3
External digital output 4
External digital output 5
External digital output 6
External digital output 7
External digital output 8
External digital output 9
External digital output 10
External digital output 11
External digital output 12
External digital output 13
External digital output 14
External digital output 15
External digital output 16

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

LED 1
LED 1
LED 1
LED 1
LED 2
LED 2
LED 2
LED 2
LED 3
LED 3
LED 3
LED 3
LED 4
LED 4
LED 4
LED 4

Red colour
Yellow colour
Green colour
Flash
Red colour
Yellow colour
Green colour
Flash
Red colour
Yellow colour
Green colour
Flash
Red colour
Yellow colour
Green colour
Flash

Page 25 of 64

GC-1F

Option H2, Modbus communication

Control register table read(03h)/write(10h)


Address
0
1
2
3
4
5

Content

Control
command

Description
Not used
Not used
Not used
Not used
Not used
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10

7
8-13

DEIF A/S

Control
command

Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Reserved
Not used

This bit must be 1 when writing the


command word. If the bit is 0, the
control command is ignored
Start
GB ON
GB OFF
Stop

Alarm ack. This bit is automatically


reset.
Nominal setting 1
Nominal setting 2
Nominal setting 3
Nominal setting 4
This bit must be 1 when writing the
command word. If the bit is 0, the
control command is ignored
Island
Automatic mains failure (AMF)

Load take over (LTO)


MB ON
MB OFF
OFF mode
Manual mode
Auto mode
Test

Page 26 of 64

GC-1F

Option H2, Modbus communication

Command flags table (write only) (function code 0Fh)

DEIF A/S

Address
0
1

Content
Not used
Start

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41

GB ON
GB OFF
Stop
Reserved
Not used
Reserved
Reserved
Reserved
Alarm ack.
Nominal setting 1
Nominal setting 2
Nominal setting 3
Nominal setting 4
Start and GB ON
GB Off and stop
Island
Automatic mains failure (AMF)
Reserved
Reserved
Reserved
Load take over (LTO)
ATS mode
Neutral pos.
MB ON
MB OFF
OFF
Manual mode
Reserved
Auto mode
Test
Not used
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Not used
Not used

Description
These bits are
automatically reset.

Page 27 of 64

GC-1F

Option H2, Modbus communication

Address
42
43
44
45
46
47
48

DEIF A/S

Content
Not used
Not used
Not used
Not used
Reserved
Reserved
Reserved

Description

Page 28 of 64

GC-1F

Option H2, Modbus communication

Status flags table (read only) (function code 02h)


Address
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38

DEIF A/S

Content
GB position ON
MB position ON
Not used
Running
Generator voltage/frequency OK
Mains failure
OFF
Manual mode
Reserved
Auto mode
Test
Reserved
Reserved
Island
Automatic mains failure (AMF)
ATS mode
Reserved
Reserved
Load take over (LTO)
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

Description

Page 29 of 64

GC-1F

Option H2, Modbus communication

5. Parameter table
Parameter table reading and writing
The entire setting of parameters can be made using the Modbus. The combination of function
and address areas used is described below:
Function 01(01hex) read/write flag status
Reads the ON/OFF status of discrete flags in the slave unit.
Address area for reading of status flags
Multi-line 2
Data to request

Multi-line 2
Table

Address area

Command
Enable

Parameter table
Parameter table

0-1999
2000-3999

The maximum number of data query is limited by the length of the actual table.

Function 02(02hex) read flag status


Reads the ON/OFF status of discrete flags in the slave unit.
Address area for reading of status flags
Multi-line 2
Data to request

Multi-line 2
Table

Address area

Status
Alarm active
Alarm acknowledge
Timer output
Timer running
Digital output
Digital input

Status table
Parameter table
Parameter table
Parameter table
Parameter table
Digital output table
Digital input table

0-1999
4000-5999
6000-7999
8000-9999
10000-11999
22500-22999
23000-23499

The maximum number of data query is limited by the length of the actual table.

DEIF A/S

Page 30 of 64

GC-1F

Option H2, Modbus communication

Function 03(03hex) read/write registers


Reads the binary of registers in the slave unit.
Address area for reading of registers
Multi-line 2
Data to request

Multi-line 2
Table

Address area

Control register
Timers used
Values used
Values minimum
Values maximum
Output a
Output b
Fail class used
Enable
Inhibit

Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table

0-1999
2000-3999
4000-4999
6000-7999
8000-9999
10000-11999
12000-13999
14000-15999
16000-17999
18000-19999

The maximum number of data query is limited by the length of the actual table.

Function 04(04hex) read registers


Reads the binary of registers in the slave unit.
Address area for reading of registers
Multi-line 2
Data to request

Multi-line 2
Table

Address area

Measuring values

Measuring values table


Not used
Measurements
Status/Alarms
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table

0-1999
0 499
500 999
1000 1699
2000-3999
4000-3999
6000-7999
8000-9999
10000-11999
12000-13999
14000-15999
16000-17999

Timers minimum
Timers maximum
Output a minimum
Output a maximum
Output b minimum
Output b maximum
Fail class minimum
Fail class maximum

The maximum number of data query is limited by the length of the actual table.

DEIF A/S

Page 31 of 64

GC-1F

Option H2, Modbus communication

Function 15(0Fhex) write multiple flags


Writes each flag (0 x reference) in a sequence of flags to either ON or OFF.
Address area for writing of status flags
Multi-line 2
Data to request

Multi-line 2
Table

Address area

Command
Enable

Parameter table
Parameter table

0-1999
2000-3999

Function 16(10hex) write register


Writes values into a sequence of registers.
Address area for writing of registers
Multi-line 2
Data to request

Multi-line 2
Table

Address area

Control register
Measure values
Alarms
Not used
Timers used
Values used
Output a
Output b
Fail class used
Enable
Inhibit

Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table
Parameter table

0-499
500-999
1000-1499
1500-1999
2000-3999
4000-4999
10000-11999
12000-13999
14000-15999
16000-17999
18000-19999

The maximum number of data query is limited by the length of the actual table.

DEIF A/S

Page 32 of 64

GC-1F

Option H2, Modbus communication

Parameter table
Address and channel number overview
Offset
address

Ch. no.

Content

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39

DEIF A/S

1000

1030
1040

1130
1140
1150
1160
1170
1180

G -P> 1
Reserved
Reserved
G I> 1
G I> 2
Reserved
Reserved
Not used
Not used
G I >> 1
G I >> 2
G U> 1
G U> 2
G U< 1
G U< 2
Reserved
Reserved

Comment

Value
unit
%/10

Delay
unit
1/10s

%/10
%/10

1/10s
1/10s

%/10
%/10
%/10
%/10

1/10s
1/10s
1/10s
1/10s

1210
1220

G f> 1
G f> 2

%/10
%/10

1/10s
1/10s

1240
1250

G f< 1
G f< 2
Reserved
BB U> 1
BB U> 2
Reserved
BB U< 1
BB U< 2
Reserved
Reserved
Reserved
BB F> 1
BB F> 2
Reserved
BB f< 1
BB f< 2
Reserved
Reserved
Reserved

%/10
%/10

1/10s
1/10s

%/10
%/10

1/10s
1/10s

%/10
%/10

1/10s
1/10s

%/10
%/10

1/10s
1/10s

%/10
%/10

1/10s
1/10s

Page 33 of 64

GC-1F

Offset
address
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
DEIF A/S

Option H2, Modbus communication

Ch. no.

Content

Comment

Value
unit

Delay
unit

%/10
%/10

1/10s
1/10s

%/10
%/10

1/10s
1/10s

Reserved
Reserved
Reserved
1450
1460

G P> 1
G P> 2
Reserved
Reserved
Reserved
Reserved
Reserved
-Q>
Q>
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

Page 34 of 64

GC-1F

Offset
address
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
DEIF A/S

Option H2, Modbus communication

Ch. no.

Content

Comment

Value
unit

Delay
unit

Phase seq. error


GB open failure
GB close failure
GB position failure
Reserved
Neutral failure
Reserved

n
n
n
n

1/10s
1/10s
1/10s
1/10s

1/10s

MB open failure
MB close failure
MB position failure
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

n
n
n

1/10s
1/10s
1/10s

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
2150
2160
2170
2180

2200
2210
2220

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

Page 35 of 64

GC-1F

Offset
address
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
DEIF A/S

Option H2, Modbus communication

Ch. no.

Content

Comment

Value
unit

Delay
unit

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

Page 36 of 64

GC-1F

Offset
address

Option H2, Modbus communication

Ch. no.

Content

Delay
unit

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

181

2771

SCANIA EMS2, droop

182

2772

SCANIA EMS2, speed

DEIF A/S

Value
unit

Reserved

172
173
174
175
176
177
178
179
180

183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214

Comment

%/10
n
0: User, 1: 1500RPM, 2: 1800RPM, 3:
Low idle

Reserved
Reserved
3000
3010
3020
3030
3040
3060

Dig. input 1
Dig. input 2
Dig. input 3
Dig. input 4
Dig. input 5
Dig. input 6
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

n
n
n
n
n
n

1/10s
1/10s
1/10s
1/10s
1/10s
1/10s

Reserved
Reserved
Reserved
Reserved
Reserved

Page 37 of 64

GC-1F

Offset
address

Option H2, Modbus communication

Ch. no.

Comment

Value
unit

Delay
unit

Dig. multi-input 1
Dig. multi-input 2
Dig. multi-input 3
Wire failure, dig. multiinput 1
Wire failure, dig. multiinput 2
Wire failure, dig. multiinput 3
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

n
n
n
n

1/10s
1/10s
1/10s
n

Emergency stop
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

1/10s

mA

1/10s

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

215
216
217
218
219
220
221
222
223
224
225
226

3400
3410
3420

227

3401

228

3411

229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256

3421

DEIF A/S

Content

3490

4250

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
0-20/4-20mA no. 2.1

Page 38 of 64

GC-1F

Option H2, Modbus communication

Offset
address

Ch. no.

257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280-306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326

4260
4380
4390
4120
4130

0-20/4-20mA no. 2.2


0-20/4-20mA no. 3.1
0-20/4-20mA no. 3.2
0-20/4-20mA no.1.1
0-20/4-20mA no.1.2
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

4310
4460
4220

DEIF A/S

Value
unit
mA
mA
mA
mA
mA

Delay
unit
1/10s
1/10s
1/10s
1/10s
1/10s

VDO Oil 2.1


VDO Water temp. 3.1
VDO Fuel level 1.1
Reserved
Reserved
Reserved

Press.
Deg.
%

1/10s
1/10s

4320
4470
4230

VDO Oil 2.2


VDO Water temp. 3.2
VDO Fuel level 1.2
Reserved

Press.
Deg.
%

1/10s
1/10s

4510
4520

Overspeed 1
Overspeed 2
Reserved
V-Belt
Reserved
Hz/V failure
Reserved
Reserved

%/10
%/10

1/10s
1/10s

1/10s

1/10s

4960
4970

U< aux. supply term. 1


U> aux. supply term. 1
Reserved
Reserved

V/10
V/10

1/10s
1/10s

5000
5010
5020
5030
5040
5050
5060
6950

Relay 21
Relay 22
Relay 23
Relay 24
Relay 26
Relay 45
Relay 46
Parameter group 1

0: Alarm
1: Limit

1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s

4600
4550

Content

Comment

Page 39 of 64

GC-1F

Option H2, Modbus communication

Offset
address

Ch. no.

327
328
329
330-389
390
391-406
407
408
409
410
411
412

6960
6970
4610

413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429

6011
6012
6013
6014
6015
6021
6022
6023
6024
6025
6031
6032
6033
6034
6035
6041
6042

430
431

6043
6044

432

6051

433

6052

434
435

6070

Nom. frequency 2
Nom. power 2
Nom. current 2
Nom. voltage 2
Nom. RPM 2
Nom. frequency 3
Nom. power 3
Nom. current 3
Nom. voltage 3
Nom. RPM 3
Nom. frequency 4
Nom. power 4
Nom. current 4
Nom. voltage 4
Nom. RPM 4
G transformer, U primary
G transformer, U
secondary
G transformer, I primary
G transformer, I
secondary
BB transformer, U
primary
BB transformer, U
secondary
Reserved
Gen-set mode

436
437
438
439

6080
6103
6104
6101

Language
GB operations
MB operations
Running hours offset

DEIF A/S

4620
6001
6002
6003
6004
6005
6006

Content
Parameter group 2
Parameter group 3
Charger gen
Reserved
Fuel level 1.3
Reserved
Nom. frequency 1
Nom. power 1
Nom. current 1
Nom. voltage 1
Nom. RPM 1
Parameter set

Comment

Value
unit

Delay
unit

1/10s

Hz/10
kW
A
V
RPM

n
n
n
n
n
n

Hz/10
kW
A
V
RPM
Hz/10
kW
A
V
RPM
Hz/10
kW
A
V
RPM
V
V

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

A
A

n
n

0: Nom. set 1,
1: Nom. set 2,
2: Nom. set 3,
3: Nom. set 4

0: Island, 1: AMF, 2: Load


take over
n
n
n
hrs

n
n
n
n
n
Page 40 of 64

GC-1F

Offset
address
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
DEIF A/S

Option H2, Modbus communication

Ch. no.

6105
6112
6113
6116
6122
6123
6126
6130
6111
6112
6160
6171
6173
6570
6181
6183
6184
6191
7090
7040
6211
6212
6220
6231
6360
6350

Content
Reserved
Reset kWh counter
Reserved
Service timer 1, hours
Service timer 1, days
Service timer 1, reset
Service timer 2, hours
Service timer 2, days
Service timer 2, reset
Alarm horn
Service timer 1 type
Service timer 2 type
Run status
No. of teeth (flywheel)
Reserved
RPM run detection
Reserved
Oil pressure run
detection
Start prepare
Reserved
Start ON time (crank)
Start OFF time (pause)
Start attempts
Reserved
Island test
AMF test
Cooling down
Extended stop time
Hz/V OK
GB close delay
Reserved
GB on Temp settings
Reserved
D+
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

Comment

Value
unit

Delay
unit

Hrs
Days
n
Hrs
Days
n
n

n
n
n
n
n
n
1/10s

n
n

1/10s
n

RPM

Press
n

1/10s

n
n
n

1/10s
1/10s
n

n
n
n
n
n
n

1/10s
1/10s
1/10s
1/10s

Deg.
n

1/10s

Page 41 of 64

GC-1F

Offset
address
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
524
525
526
527
DEIF A/S

Option H2, Modbus communication

Ch. no.

6290
6980
6222
6223

Content

Comment

Value
unit

Delay
unit

Reserved
Idle mode
Sleep mode
Hz/V OK voltage
Hz/V OK frequency
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

Page 42 of 64

GC-1F

Offset
address
528
529
530
531
532
533
534
535
536
537
538

539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556

Option H2, Modbus communication

Ch. no.

7040

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
AMF Test function

Comment

Value
unit

Delay
unit

0=button,
1=digital
input
2=button or
digital input

%n

min/101/10s

Reserved
Reserved
Reserved
Reserved
Reserved
7062
7063
7064
7065

7072
7073
7074
7081
7082

557
558
559
560
561
562

7511

563

7512

564
565
566

7513
7520

DEIF A/S

Content

Mains OK delay U
Mains low voltage
Mains high voltage
Mains fail ctrl
Reserved
Mains OK delay freq
Low frequency
High frequency
Mode shift
MB close delay
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Ext. comm. ID
Baud rate 0=9600,
1=19200
Comm. mode (ASCII,
RTU)
Ext. comm. error
Reserved

n
%
%
0: Start eng. + open MB
1: Start eng.
n
%
%

1/10s
n
n
n

1/10s
n
n
n
1/10s

n
n

n
n

0: Off, 1: On

0: RTU, 1: ASCII
n

n
1/10s

Page 43 of 64

GC-1F

Offset
address
567

Option H2, Modbus communication

Ch. no.

568
569
570
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600
601
602
603
604
605
606
607
608
609
610
DEIF A/S

7562
7570
7580
7590
7600
7610
7620
7630
7640
7650
7660
6320
6330

Content

Comment

Value
unit

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
EIC, J1939
Reserved
EI comm. error
EIC warning
EIC shutdown
EIC overspeed
EIC cooling w. temp. 1
EIC cooling w. temp. 2
EIC oil pressure 1
EIC oil pressure 2
EIC oil temperature 1
EIC oil temperature 2
Engine heater on
Engine heater off
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

Delay
unit

n
n
n
n
RPM
Deg.
Deg.
Press./10
Press./10
Deg.
Deg.
Deg.
Deg.

1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s

Page 44 of 64

GC-1F

Offset
address
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
631
632
633
634
635
636
637
638
639
640
641
642
643
644
645
646
647
648
649
650
651
652
653
654
DEIF A/S

Option H2, Modbus communication

Ch. no.

Content

Comment

Value
unit

Delay
unit

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used

Page 45 of 64

GC-1F

Offset
address
655
656
657
658
659
660
661
662
663
664
665
666
667
668
669
670
671
672
673
674
675
676
677
678
679
680
681
682
683
684
685
686
687
688
689
690
691
692
693
694
695
696
697
698
DEIF A/S

Option H2, Modbus communication

Ch. no.

Content
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Reserved
Setup norms
GB pulse ON
MB pulse ON
Neut pulse ON
Reserved
Auto mode shift
Startup mode
Source prio
Reserved
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used

9116
9117

Customer password
Service password
Reserved
Reserved

Comment

Value
unit

Delay
unit

n
1/10s
1/10s
1/10s

n
1/10s
1/10s
1/10s

n
n
n

n
n
n

n
n

n
n

Page 46 of 64

GC-1F

Offset
address
699
700
701
702
703
704
705
706
707
708
709
710
711
712
713
714
715
716
717
718
719
720
721
722
723
724
725
726
727
728
729
730
731
732
733
734
735
736
737
738
739
740
741
742
DEIF A/S

Option H2, Modbus communication

Ch. no.

10000
10010
10020
10030
10040
10050
10060
10070
10080
10090
10100
10110
10120
10130
10140
10150
10160
10170
10180
10190
10200
10210
10220
10230
10240
10250
10260
10270
10280
10290
10300
10310
10320
10330
10340
10350
10360
10370

Content
Reserved
Cmd timer function 1
Cmd timer day 1
Cmd timer hour 1
Cmd timer minute 1
Cmd timer function 2
Cmd timer day 2
Cmd timer hour 2
Cmd timer minute 2
Cmd timer function 3
Cmd timer day 3
Cmd timer hour 3
Cmd timer minute 3
Cmd timer function 4
Cmd timer day 4
Cmd timer hour 4
Cmd timer minute 4
Cmd timer function 5
Cmd timer day 5
Cmd timer hour 5
Cmd timer minute 5
Cmd timer function 6
Cmd timer day 6
Cmd timer hour 6
Cmd timer minute 6
Cmd timer function 7
Cmd timer day 7
Cmd timer hour 7
Cmd timer minute 7
Cmd timer function 8
Cmd timer day 8
Cmd timer hour 8
Cmd timer minute 8
Pin code GSM
SMS phone no. 1 GSM
SMS phone no. 2 GSM
SMS phone no. 3 GSM
SMS phone no. 4 GSM
SMS phone no. 5 GSM
Reserved
Not used
Not used
Not used
Reserved

Comment

Value
unit

Delay
unit

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

Page 47 of 64

GC-1F

Offset
address

Option H2, Modbus communication

Ch. no.

Content

743
744
745
746

10460

Reserved
Reserved
Reserved
VDO 1 type

747
748
749
750
751
752
753
754
755
756
757
758
759
760
761
762
763

10470
10490
10510
10530
10550
10570
10590
10610
10480
10500
10520
10540
10560
10580
10600
10620
10630

VDO 1 value 1
VDO 1 value 2
VDO 1 value 3
VDO 1 value 4
VDO 1 value 5
VDO 1 value 6
VDO 1 value 7
VDO 1 value 8
VDO 1 output 1
VDO 1 output 2
VDO 1 output 3
VDO 1 output 4
VDO 1 output 5
VDO 1 output 6
VDO 1 output 7
VDO 1 output 8
VDO 2 type

764
765
766
767
768
769
770
771
772
773
774
775
776
777
778
779
780

10640
10660
10680
10700
10720
10740
10760
10780
10650
10670
10690
10710
10730
10750
10770
10790
10800

VDO 2 value 1
VDO 2 value 2
VDO 2 value 3
VDO 2 value 4
VDO 2 value 5
VDO 2 value 6
VDO 2 value 7
VDO 2 value 8
VDO 2 output 1
VDO 2 output 2
VDO 2 output 3
VDO 2 output 4
VDO 2 output 5
VDO 2 output 6
VDO 2 output 7
VDO 2 output 8
VDO 2 type

781
782
783
784

10810
10830
10850
10870

VDO 3 value 1
VDO 3 value 2
VDO 3 value 3
VDO 3 value 4

DEIF A/S

Comment

Value
unit

0: Type 1, 1: Type 2, 2:
Type 3: Config.
Ohm/10
Ohm/10
Ohm/10
Ohm/10
Ohm/10
Ohm/10
Ohm/10
Ohm/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
0: Type 1, 1: Type 2, 2:
Type 3: Config.
Ohm/10
Ohm/10
Ohm/10
Ohm/10
Ohm/10
Ohm/10
Ohm/10
Ohm/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
0: Type 1, 1: Type 2, 2:
Type 3: Config.
Ohm/10
Ohm/10
Ohm/10
Ohm/10

Delay
unit

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

Page 48 of 64

GC-1F

Option H2, Modbus communication

Offset
address

Ch. no.

Content

785
786
787
788
789
790
791
792
793
794
795
796
797

10890
10910
10930
10950
10820
10840
10860
10880
10900
10920
10940
10960
10970

VDO 3 value 5
VDO 3 value 6
VDO 3 value 7
VDO 3 value 8
VDO 3 output 1
VDO 3 output 2
VDO 3 output 3
VDO 3 output 4
VDO 3 output 5
VDO 3 output 6
VDO 3 output 7
VDO 3 output 8
Engineering units

798
799
800

10980
10990
11000

Multi-input 1, config.
Multi-input 2, config.
Multi-input 3, config.
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used

801
802
803
804
805
806
807
808
809
810
811
812
813
814
815
816
817
818
819
820
821
822
823
824
825
826
827

DEIF A/S

Comment

Value
unit
Ohm/10
Ohm/10
Ohm/10
Ohm/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10

0: Bar/Celsius,
1: Psi/Fahrenheit
0= VDO 1= 4-20mA 2= 020mA 3= Binary

Delay
unit
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

Page 49 of 64

GC-1F

Offset
address
828
829
830
831
832
833
834
835
836
837
838
839
840
841
842
843
844
845
846
847
848
849
850
851
852
853
854
855
856
857
858
859
860
861
862
863
864
865
866
867
868
869
870
871
DEIF A/S

Option H2, Modbus communication

Ch. no.

Content

Comment

Value
unit

Delay
unit

n
n

n
n

Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
4140
4270

0-20mA 1 units
0-20mA 2 units

Page 50 of 64

GC-1F

Offset
address

Option H2, Modbus communication

Ch. no.

872
873

4400
1620

874
875
876

7110
6940
4630

877
878

6213
6560

879

7111

880

7112

881
882

7114

883
884
885
886
887
888
889
890
891
892
893
894
895
896
897
898
899
900
901
902
903
904
905
906
907
908
909
910
911

6214
6700

DEIF A/S

Content
0-20mA 3 units
Mains U unbalanced
Mains failure unbalance
enable
Alarm LED
Low coolant temperature
Temperature controlled
cooldown.
Cooldown timeout
Mains failure unbalance
fail delay
Mains failure unbalance
ok delay
Mains failure unbalance
setpoint
Reserved
Cooldown input/reference
Diode compensation
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

Comment

Value
unit
n
1/10%
n

Delay
unit
n
1/10s
n

n
Deg
Deg

n
1/10s
n

n
1/10%

S
1/10s

1/10%

1/10s

1/10%

1/10s

1/10V

Page 51 of 64

GC-1F

Offset
address
912
913
914
915
916
917
918
919
920
921
922
923
924
925
926
927
928
929
930
931
932
933
934
935
936
937
938
939
940
941
942
943
944
945
946
947
948
949
950
951
952
953
954
955
DEIF A/S

Option H2, Modbus communication

Ch. no.

7930
7973

7951
7952
7953
7954

Content
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
External IO comm. error
Reserved
External IO Comm. ID
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
External IO KL320x nbr 1
External IO KL320x nbr 2
External IO KL320x nbr 3
External IO KL320x nbr 4
Reserved
Reserved
Reserved

Comment

Value
unit

Delay
unit

1/10s

Page 52 of 64

GC-1F

Offset
address

Option H2, Modbus communication

Ch. no.

956
957
958
959
960
961
962
963
964
965
966

12950
12951
12952
12953
12954
12955
12956
12957
12958
12959

967

12960

968

12961

969

12962

970

12963

971

12964

972

12965

973

12966

974

12967

975

12968

976

12969

977

12970

978

12971

979

12972

980

12973

981

12974

982

12975

983

12976

984

12977

985

12978

986

12979

DEIF A/S

Content

Comment

Value
unit

Delay
unit

Reserved
External IO module 0 info
External IO module 1 info
External IO module 2 info
External IO module 3 info
External IO module 4 info
External IO module 5 info
External IO module 6 info
External IO module 7 info
External IO module 8 info
External IO module 9 info
External IO module 10
info
External IO module 11
info
External IO module 12
info
External IO module 13
info
External IO module 14
info
External IO module 15
info
External IO module 16
info
External IO module 17
info
External IO module 18
info
External IO module 19
info
External IO module 20
info
External IO module 21
info
External IO module 22
info
External IO module 23
info
External IO module 24
info
External IO module 25
info
External IO module 26
info
External IO module 27
info
External IO module 28
info
External IO module 29
info
Page 53 of 64

GC-1F

Offset
address

Option H2, Modbus communication

Ch. no.

987

12980

988

12981

989

12982

990
991
992
993
994
995
996
997
998

12983

999

12000

1000

12010

1001

12030

1002

12040

1003

12060

1004

12070

1005

12090

1006

12100

1007

12120

1008

12130

1009

12150

1010

12160

1011

12180

1012

12190

1013

12210

1014
1015
1016
1017

12220

DEIF A/S

Content
External IO module 30
info
External IO module 31
info
External IO module 32
info
External IO module 33
info
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
External IO analogue in
1.1
External IO analogue in
1.2
External IO analogue in
2.1
External IO analogue in
2.2
External IO analogue in
3.1
External IO analogue in
3.2
External IO analogue in
4.1
External IO analogue in
4.2
External IO analogue in
5.1
External IO analogue in
5.2
External IO analogue in
6.1
External IO analogue in
6.2
External IO analogue in
7.1
External IO analogue in
7.2
External IO analogue in
8.1
External IO analogue in
8.2
Reserved
Reserved
Reserved

Comment

Value
unit

Delay
unit

1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s

Page 54 of 64

GC-1F

Offset
address

Option H2, Modbus communication

Ch. no.

1018
1019
1020
1021
1022
1023
1024
1025
1026
1027
1028
1029
1030
1031
1032
1033
1034
1035
1036
1037
1038
1039
1040
1041
1042
1043
1044
1045
1046
1047
1048
1049
1050
1051
1052
1053
1054
1055

12540
12550
12560
12570
12580
12590
12600
12610
12620

1056

12630

1057

12640

1058

12650

1059

12660

DEIF A/S

Content
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
External IO digital input 1
External IO digital input 2
External IO digital input 3
External IO digital input 4
External IO digital input 5
External IO digital input 6
External IO digital input 7
External IO digital input 8
External IO digital input 9
External IO digital input
10
External IO digital input
11
External IO digital input
12
External IO digital input
13

Comment

Value
unit

Delay
unit

1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s

Page 55 of 64

GC-1F

Offset
address

Option H2, Modbus communication

Ch. no.

1060

12670

1061

12680

1062

12690

1063

12790

1064

12800

1065

12810

1066

12820

1067

12830

1068

12840

1069

12850

1070

12860

1071

12870

1072

12880

1073

12890

1074

12900

1075

12910

1076

12920

1077

12930

1078
1079
1080
1081
1082
1083
1084
1085
1086
1087
1088
1089
1090
1091

12940

DEIF A/S

Content
External IO digital input
14
External IO digital input
15
External IO digital input
16
External lO digital output
1
External lO digital output
2
External lO digital output
3
External lO digital output
4
External lO digital output
5
External lO digital output
6
External lO digital output
7
External lO digital output
8
External lO digital output
9
External lO digital output
10
External lO digital output
11
External lO digital output
12
External lO digital output
13
External lO digital output
14
External lO digital output
15
External lO digital output
16
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

Comment

Value
unit

Delay
unit
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s

Page 56 of 64

GC-1F

Offset
address
1092
1093
1094
1095
1096
1097
1098
1099
1100
1101
1102
1103
1104
1105
1106
1107
1108
1109
1110
1111
1112
1113
1114
1115
1116
1117
1118
1119
1120
1121
1122
1123
1124
1125
1126
1127
1128
1129
1130
1131
1132
1134
1135
1136
DEIF A/S

Option H2, Modbus communication

Ch. no.

2773
7561
4950
2774
7974

Content
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Cummins Gain
ADEC Node ID
Reserved
< Battery 2
Volvo rpm
External IO reset
S1 I> 1
S1 I> 2
S1 I>> 1
S1 I>> 2
S1 U> 1
S1 U> 2
S1 U< 1
S1 U< 2
S1 f> 1
S1 f> 2
S1 f< 1
S1 f< 2
CB1 open failure
CB1 close failure
CB1 pos. failure
CB2 open failure
CB2 close failure
CB2 pos. Failure
Reserved
S1 U pri
S1 U sec
S1 I pri
S1 I sec
S2 U pri
S2 U sec

Comment

Value
unit

Delay
unit

1/10V
rpm

1/10s

1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s
1/10s

Page 57 of 64

GC-1F

Offset
address
1137
1138
1139
1140
1141
1142
1143
1144
1145
1146
1147
1148
1149
1150
1151
1152
1153
1154
1155
1156
1157
1158
1159
1160
1161
1162
1163
1164
1165
1166
1167
1168
1169
1170
1171
1172
1173
1174
1175
1176
1177
1178
1179
1180
DEIF A/S

Option H2, Modbus communication

Ch. no.

Content

Comment

Value
unit

Delay
unit

CB1 counter
CB2 counter
ATS test
Prio2 Hz/V OK delay
CB1 close delay
Prio2 U OK
Prio2 f OK
Prio1 U OK delay
Prio1 U< fail
Prio1 U> fail
Prio1 f OK delay
Prio1 f< fail
Prio1 f> fail
CB2 close delay
CB1 pulse ON
CB2 pulse ON
S2 U unbl.
Prio1 U unbl enable
Prio1 U unbl fail delay
Prio1 U unbl OK delay
Prio1 U unbl lvl
S2 U> 1
S2 U> 2
S2 U< 1
S2 U< 2
S2 f> 1
S2 f> 2
S2 f< 1
S2 f< 2
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Page 58 of 64

GC-1F

Option H2, Modbus communication

Offset
address
1181
1182
1183
1184
1185
1186
1187
1188
1189
1190
1191
1192
1193
11941562

Ch. no.

2280

Content

Comment

Value
unit

Delay
unit

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Phase direction
Reserved
EIC speed ramp
(in/decrease)

1563

Please refer to the Installation Instructions and Reference Handbook for


information about:

Availability of channels
Min./max. settings
Factory settings

Note that several channels also depend on the options.


Limitations
It is possible to write to channels, where the option is not activated. It is not possible to enable
the channel. E.g. if an attempt is made to write a 1 to the enable flag, then the 1 will be
discarded, and the enable flag remains 0. It is not possible to write to offset address 0. These
values are used for DEIF internal version control.
Abbreviations
These abbreviations are used in the tables:

y means that the channel is writeable.


n means that a 0 can be written to the channel only.

Examples
Write nominal frequency (6011), offset 258, 60Hz
ID = 1, 60Hz = 600Hz/10 = 0258h
Address 4000 + 258 = 4258d = 10A2h
Tx:
01h 10h 10h A2h 00h 01h 02h 02h 58h AEh 49h
Rx:
01h 10h 10h A2h 00h 01h A4h EBh
Read nominal frequency (6011) offset 258, 60Hz
Tx:
01h 03h 10h A2h 00h 01h 21h 28h
Rx:
01h 03h 02h 02h 58h B8h DEh
Read 0258h = 600d
DEIF A/S

Page 59 of 64

GC-1F

Option H2, Modbus communication

Digital input table (read only 02h)


Address
22501
22502
22503
22504
22505
22506
22507
22508
22509
22510
22511
22512
22513
22514
22515
22516
22517
22518
22519
22520
22521
22522
22523
22524
22525
22526
22527
22528
22529
22530
22531
22532
22533
22534
22535
22536
22537
22538
22539
22540
22541
22542
22543
DEIF A/S

Description
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Page 60 of 64

GC-1F

Option H2, Modbus communication

Address
22544
22545
22546
22547
22548
22549
22550
22551
22552
22553
22554
22555
22556
22557
22558
22559
22560
22561
22562
22563
22564
22565
22566
22567
22568
22569
22570
22571
22572
22573
22574
22575
22576
22577
22578
22579
22580
22581
22582
22583
22584
22585
22586
22587
22588
DEIF A/S

Description
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Terminal 19-20 Emergency stop
Terminal 10
Terminal 11
Terminal 12
Terminal 13

Standard

Standard

Page 61 of 64

GC-1F

Option H2, Modbus communication

Address
22589
22590
22591
22592
22593
22594
22595
22596
22597
22598
22599
22600
22601
22602
22603
22604
22605
22606

DEIF A/S

Description
Terminal 14
Terminal 15
External IO digital input 1
External IO digital input 2
External IO digital input 3
External IO digital input 4
External IO digital input 5
External IO digital input 6
External IO digital input 7
External IO digital input 8
External IO digital input 9
External IO digital input 10
External IO digital input 11
External IO digital input 12
External IO digital input 13
External IO digital input 14
External IO digital input 15
External IO digital input 16

External IO

Page 62 of 64

GC-1F

Option H2, Modbus communication

Digital output table (read only 02h)


Address
23000
23001
23002
23003
23004
23005
23006
23007
23008
23009
23010
23011
23012
23013
23014
23015
23016
23017
23018
23019
23020
23021
23022
23023
23024
23025
23026
23027
23028
23029
23030
23031
23032
23033
23034
23035
23036
23037
23038
23039
23040
23041
23042
23043
DEIF A/S

Terminal
20/21
20/22
20/23
24/25

26/27
47/48
45/46

LED 1
LED 2
LED 3
LED 4

Description
Relay 21
Relay 22
Relay 23
Relay 24
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Not used
Relay 3
Not used
Not used
Reserved
Reserved
Reserved
Reserved
Not used
Not used
Not used
Not used
Not used
Reserved
Relay 26
Relay 47
Reserved
Relay 45
Reserved
Reserved
Alarm LED 1
Alarm LED 2
Alarm LED 3
Alarm LED 4
External IO output 1
External IO output 2
External IO output 3
External IO output 4
External IO output 5
External IO output 6
External IO output 7
External IO output 8

Standard

Standard

External IO

Page 63 of 64

GC-1F

Address
23044
23045
23046
23047
23048
23049
23050
23051
23052
23053
23054
23055

Option H2, Modbus communication

Terminal

Description
External IO output 9
External IO output 10
External IO output 11
External IO output 12
External IO output 13
External IO output 14
External IO output 15
External IO output 16
Reserved
Reserved
Reserved
Reserved

DEIF A/S reserves the right to change any of the above.