Module 33D - Closed loop proportional-integral pressure control

Components List
MODULE 33D

MODULE 33 - Unit 1

MODULE 33 - Unit 8

R1 = 100k- 1/4W - 1%
R2 = 100k- 1/4W - 1%
R3 = 2.2M- 1/4W - 1%
R4 = 2.2M- 1/4W - 1%
R5 = 1k- Trimmer
R6 = 2.2M- 1/4W - 1%
R7 = 20k- Trimmer
R8 = 1k- 1/4W - 1%
R9 = 100k- 1/4W - 1%
N1 = LM358
BP = Pressure sensor MPX2200DP
M = Pump 12V

R1 = 2.7k- 1/4W - 1%
R2 = 5k- Trimmer
R3 = 47k- 1/4W - 1%
R4 = 47k- 1/4W - 1%
R5 = 47k- 1/4W - 1%
R6 = 47k- 1/4W - 1%
C1 = 0.33F - Polyester
N1 = A741

R1 = 30k- 1/4W - 1%
R2 = 1.5k- 1/4W - 1%
R3 = 10k- Trimmer
R4 = 1M- 1/4W - 1%
R5 = 5k- Trimmer
R6 = 10k- 1/4W -1%
R7 = 10k- 1/4W - 1%
C1 = 1nF - Polyester
C2 = 0.01F - Polyester
C3 = 100nF - Polyester
C4 = 0.01F - Polyester
N1 = TL082
N2 = 555

MODULE 33 - Unit 2

MODULE 33 - Unit 5

R1 = 82k- 1/4W - 1%
R2 = 1M- Trimmer
R3 = 22k- 1/4W - 1%
R4 = 22k- 1/4W - 1%
C1 = 0.1F - Polyester
N1 = A741

R1 = 82k- 1/4W - 1%
R2 = 1M- Trimmer
R3 = 47k- 1/4W - 1%
R4 = 100- 1/4W - 1%
C1 = 220F - Electrolitic
C2 = 220F - Electrolitic
N1 = A741

MODULE 33 - Unit 6

MODULE 33 - Unit 7

R1 = 10k- 1/4W - 1%
R2 = 10k- 1/4W - 1%
R3 = 10k- 1/4W - 1%
R4 = 10k- 1/4W - 1%
N1 = A741

R1 = 1.2k- 1/4W - 5 %
R2 = 1.2k- 1/4W - 5%
V1 = TIP122 with dissipator
V2 = 1N4007
V3 = LED red
V4 = UF5406

Topographical diagram

Fig. 4.2.1

EXPERIMENTATION
perform the Operative Unit 10;
carry out the connections as in Fig.4.2.1;
disconnect for a moment the cable that connects jack 4 (Module 33 Unit 6) to jack 7 (Module
33 Unit 8);
insert a terminal of the digital voltmeter, set to direct current, in jack 1 Uref (SET POINT) and
the other one in ground jack;
adjust the SET POINT voltage to 4V (0.8bar);
move the terminal of the digital voltmeter in jack 3 of the pressure sensor (Module 33D);
close the DRAIN VALVE;
turn the knob Kp of the PROPORTIONAL CONTROLLER to 75% and the knob Ki of the
INTEGRAL CONTROLLER to 25%;

restore the connection between jack 4 (Module 33 Unit 6) and jack 7 (Module 33 Unit 8): the
pump starts and operates until when it reaches the SET-POINT value set with the Uref;
adjust the DRAIN VALVE so to make the pressure decrease in the tank: the pump starts again
to keep constant the pressure value in the tank;
observe what happens: after a series of oscillations the systems establishes itself;
repeat the previous operations for the different values of Ki, Kp, Uref and DRAIN VALVE so
to determine the best balance conditions of the system.

QUESTIONS
The output OFFSET represents:
The value assumed by the output quantity when the input quantity is null
The value assumed by the output quantity when the input quantity is
maximum

Answer:

The minimum variation of the input variation


Can the pressure transducers be used to measure the force ?
Yes

Answer:

No
In a proportional regulator (P):
The output signal is proportional to the integral of the input signal
The output signal is proportional to the input signal

Answer:

The output signal is proportional to the speed with which the input signal
varies
In its use field, does the operation of the regulator P depend on the time ?
Yes

Answer:

No