Vous êtes sur la page 1sur 190

Distribution Business

Overhead Line Manual Vol.2

Version Prepared by Approved by Issue Date


3 Tony Haggis Pat Booth July 2006
East Midlands Electricity Overhead Line Manual Vol.2

Revision Log For Overhead Line Manual Vol.2


Changes made in version 3 July 2006

Title Notes about the change


Documents
Removed

New
Documents

Amended OHL Vol 2 Section 2-2 Surge Arrestor holes resized from 14mm – 17mm to
Documents Steelwork E247A accept 33kV Surge Arrestor

Changes made in version 2 January 2002 (Significant changes shown bold)

Title Notes about the change


Documents
Removed

New
Documents

Amended OHL Vol 2 Section 2-2 E 223 33kV Double Circuit Botton Section Angle
Documents Steelwork E200-E299 Crossarm Commodity code corrected
OHL Vol 2 Section 2-3 E361 Ball ended hook added
Insulator & Fittings E300 -
E399
OHL Vol 2 section 2-4 Drawings E413, E413A, E415 & E416 added –
Staying Materials E400 – Screw-in anchors
E499
OHL Vol 2 Section 2-6 E615 Drawing /Photo of clamp added
Earthing E600 – E699
OHL Vol 2 Section 2-7 E704 Withdrawn - cleats for under-eaves wiring
Cable Saddles, Cleats, E714 Cleats for 33kV & 11kV XPLE cable added
Guards E700 - E799

Changes made in version 1 February 2001

Title Notes about the change


Documents
Removed

New
Documents

Version: 3 July 2006 2 of 3


Distribution Business

Drawings and Reference Information

Database Ref: 62 File Ref: CONTENTS FEB Manual Name: OHL Vol 2
2001.doc

Version Prepared by Approved by Issue Date


FEB 2001 T Haggis See Database Feb 2001
East Midlands Electricity Drawings and Reference Information
Overhead Line Manual Vol.2

Revision Log For Drawings & Reference Information


Changes made in version 1

Section Notes about the change

File Ref: Contents Feb 2001.doc Page 2 of 4 Version: 1


East Midlands Electricity Drawings and Reference Information
Overhead Line Manual Vol.2

INTRODUCTION.

1.1 Preface
1.2 References
1.3 Metric/Imperial Conversions

CURRENT 'E' DRAWINGS AND JOINTING CHARTS.

2.1. Pole Fabrication details E100 - E199


2.2. Steelwork E200 - E299
2.3. Insulators and Fittings E300 - E399
2.4. Staying Materials E400 - E499
2.5. Information Plates E500 - E599
2.6. Earthing E600 - E699
2.7. Cable Saddles, Cleats, Guards E700 - E799
2.8. Jointing charts

APPENDICES

1. Superseded 'E' Drawings.


2. Drawings and Tables held at Head Office.
3. Miscellaneous Tower Drawings.
4. Guide to Commodity Codes.

File Ref: Contents Feb 2001.doc Page 3 of 4 Version: 1


East Midlands Electricity Drawings and Reference Information
Overhead Line Manual Vol.2

This Page Is Intentionally Blank

File Ref: Contents Feb 2001.doc Page 4 of 4 Version: 1


Distribution Business

Introduction

Database Ref: 63 File Ref: INTRO FEB 2001.doc Manual Name: Overhead Line Manual
Vol.2

Version Prepared by Approved by Issue Date


FEB 2001 T Haggis See Database Feb 2001
East Midlands Electricity Introduction
Overhead Line Manual Vol.2

Revision Log For Introduction


Changes made in version 1

Section Notes about the change

File Ref: Intro Feb 2001.doc Page 2 of 6 Version: 1


East Midlands Electricity Introduction
Overhead Line Manual Vol.2

1. PREFACE

This Volume contains the current 'E Drawings and Jointing Charts for LV, llkV and 33kV
Overhead Lines. In some instances these may refer to items which have been superseded.

The 'E' Drawings in Appendix 1 are for equipment, which is not to current specification but
still exists on the.

Appendix 2 has been deleted.

Appendix 3 contains miscellaneous tower drawings, and Appendix 4 is a general guide to


Commodity Codes.

Occasional reference may be made to National Specifications, or other Volumes of the


Overhead Line Manual, and in such instances, these must be used to obtain further
information as required.

All activities must be performed in accordance with the Powergen Safety Rules (Distribution)
and other Regulations and Safety Precautions contained in the East Midlands Electricity
Safety Manual. Attention must be paid to advice given by supervisors or during training
courses and also to Safety Rules and literature that are distributed periodically.

NOTE:Where any part of the Overhead Line System has to be replaced, the new part must
conform to the current Overhead Line Specifications and Regulations contained in the
Overhead Line Manual.

IF IN DOUBT OR YOU REQUIRE FURTHER INFORMATION, CONSULT Network


Performance & Standards

The complete range of Volumes, which form the Overhead Line Manual, is as follows:

VOL 1. LV to 33kV Specifications


VOL 2. Drawings and Reference Information
VOL 3. Code of Practice
VOL 4. Superseded Systems
VOL 5. Live Line
VOL 6. Work Specifications

File Ref: Intro Feb 2001.doc Page 3 of 6 Version: 1


East Midlands Electricity Introduction
Overhead Line Manual Vol.2

2. REFERENCES

This Volume occasionally makes reference to some of the following


BS and EATS documents:

BS 125 Hard-drawn Copper and Copper-Cadmium conductors for Overhead Power


Transmission purposes.

BS 137 Insulators of Ceramic Material or Glass for Overhead Lines with a Nominal Voltage
greater than 1000 V.

BS 183 General Purpose Galvanised Steel Wire Strand.

BS 215 Aluminium Conductors and Aluminium Conductors, steel reinforced, for Overhead
PowerTransmission.

BS 729 Hot Dip Galvanised Coatings on Iron and Steel Articles.

BS 913 Wood Preservation by means of Pressure Creosoting.

BS 970 Specification for Wrought Steels for Mechanical and Allied Engineering Purposes

BS 1320 High Voltage Overhead Lines on Wood Poles, llkV Conductor Size 0.05 incheS2.

BS 1990 Wood Poles for Overhead Lines (Power and Telecommunication Lines).

BS 3242 Aluminium Alloy Stranded Conductors for Overhead Power Transmission.

BS 3288 Insulator and Conductor Fittings for Overhead Power Lines.

BS 3452 Copper/Chrome Water-borne Wood Preservatives and their Application.

BS 3643 ISO Metric Screw Threads

BS 4072 Wood Preservation by means of Water-borne Copper/Chrome/Arsenic Compositions.

BS 4190 ISO Metric Black Hexagon Bolts, Screws and Nuts.

BS 4320 Specification for Metal Washers for General Engineering Purposes. Metric Series.

BS 4360 Specification for Weldable Structural Steels

BS 4848 Specification for Hot Rolled Structural Steel Sections

BS 4921 Specification for Sherardized Coatings on Iron or Steel

BS 6004 PVC Insulated Cables (Non-Armoured) for Electric Power and Lighting.

File Ref: Intro Feb 2001.doc Page 4 of 6 Version: 1


East Midlands Electricity Introduction
Overhead Line Manual Vol.2

BS 6485 PVC Covered Conductors for Overhead Power Lines.

BES – Ll British Electricity Specification for Medium and Low


Voltage Overhead Lines on wood Poles.

EATS Standard 09.7 PVC Insulated Concentric Service Cables with Stranded
Copper or Solid Aluminium Phase Conductors and Copper
Concentric Conductors.

EATS Standard 43-6 Overhead Line Clearances.

EATS Standard 43-10 llkV Single Circuit Overhead Lines of Light Construction on
Wood Poles.

EATS Standard 43-12 Insulated Aerial Bundled Conductor Erection Requirements


for LV Overhead. . Distribution Systems.

EATS Standard 43-13 Aerial Bundled Conductors (ABC) Insulated with Cross-
Linked Polythene for Low Voltage Overhead Distribution.

EATS Standard 43-14 Conductor Fittings and Associated Apparatus for use with
LV Aerial Bundled Conductor.

EATS Standard 43-15 Insulator Binds and Equivalent Helical Fittings for Overhead
Lines

EATS Standard 43-20 llkV and 33kV Single Circuit Overhead Lines of Heavy
Construction on Wood Poles.

EATS Standard 43-40 High Voltage Single Circuit Overhead Lines on Wood Poles

EATS Standard 43-88 Treatment of Wood Poles and Associated Timber for
Overhead Lines

EATS Standard 43-89* Bonding and Earthing.

EATS Standard 43-90 Anti-Climbing Devices for HV Lines up to and including


132kVESI Standard 43-91 Stay Strands and Stay Fittings for
Overhead Lines.

EATS Standard 43-92 Conductor Terminations, Joints and Insulation Binds for
Overhead Lines up to and including 132 kV.

EATS Standard 43-93 Line Insulators.

EATS Standard 43-95 Steelwork for Overhead Lines.

EATS Standard 43-96 Fasteners and Washers for Wood Pole Overhead Lines.

File Ref: Intro Feb 2001.doc Page 5 of 6 Version: 1


East Midlands Electricity Introduction
Overhead Line Manual Vol.2

EATS Standard 43-97* Notices and Marker Posts for HV Lines up to and including
132kV.

EATS Standard 43-98* Sundries

EATS Standard 43-100* Auxiliary Equipment Erected on Overhead Line Supports.

EATS and British Standards are revised when necessary by the issue either of revised pages
or complete new editions. It is important that users of these Standards should ascertain that
they are in possession of the latest issue.

NOTE:Certain Standards quoted may have been superseded. * In course of preparation.

3. RELATIONSHIPS WITH OTHER BODIES


Where lines are erected over or alongside the plant of British Telecom or British Rail, the
provisions agreed shall be complied with. Additionally, the requirements of the following
bodies should be noted.

• The British Waterways Board.


• The Ministry of Transport and Local Authorities for Motorway and 'A' classified road
crossings.

File Ref: Intro Feb 2001.doc Page 6 of 6 Version: 1


Distribution Business

Section 2
Contents

Database Ref: 64 File Ref: Contents FEB 2001.doc Manual Name: Overhead Line Manual
Vol.2

Version Prepared by Approved by Issue Date


1 Tony Haggis See Database 02/2001
East Midlands Electricity Contents List
Overhead Line Manual Vol.2

Revision Log For Contents List


Changes made in version 1

Section Notes about the change

File Ref: Contents Feb 2001.doc Page 2 of 4 Version: 1


East Midlands Electricity Contents List
Overhead Line Manual Vol.2

SECTION 2 - 'E' DRAWINGS AND JOINTING CHARTS.

2.1. POLE FABRICATION DETAILS E100 - E199

2.2. STEELWORK E200 - E299

2.3. INSULATORS AND FITTINGS E300 - E399

2.4. STAYING MATERIALS E400 - E499

2.5. INFORMATION PLATES E500 - E599

2.6. EARTHING E600 - E699

2.7. CABLE SADDLES, CLEATS, GUARDS E700 - E799

File Ref: Contents Feb 2001.doc Page 3 of 4 Version: 1


East Midlands Electricity Contents List
Overhead Line Manual Vol.2

This Page Is Intentionally Blank

File Ref: Contents Feb 2001.doc Page 4 of 4 Version: 1


Distribution Business

Section 2.1
Pole Fabrication Details
E100 – E199

Database Ref: 65 File Ref: 2-1 FEB 2001.doc Manual Name: Overhead Line Manual
Vol.2

Version Prepared by Approved by Issue Date


1 Tony Haggis See Database 02/2001
East Midlands Electricity Pole Fabrications E100 -E199
Overhead Line Manual Vol.2

Revision Log For Pole Fabrications E100 - E199


Changes made in version 1

Section Notes about the change

File Ref: 2-1 Feb 2001.doc Page 2 of 10 Version: 1


East Midlands Electricity Pole Fabrications E100 -E199
Overhead Line Manual Vol.2

CONTENTS

E101 LV Overhead Lines 4

E106 33kV Double Circuit Intermediate Pole 5

E107 33kV Double Circuit Section Pole 6

E111 Brace / Kicking Block 7

E112 Trefoil Cable Support 8

E113 Standard Universal Pole 9

E114 H Pole 10

File Ref: 2-1 Feb 2001.doc Page 3 of 10 Version: 1


East Midlands Electricity Pole Fabrications E100 -E199
Overhead Line Manual Vol.2

E101 LV overhead lines

150

°
0
3
18 DIA HOLE

11 M LENGTH & CLASS

GOUGE MARK

CF GB SPECIES & COUNTRY OF ORIGIN

C
88 YEAR OF PRESERVATION

CSAD TYPE OF PRESERVATION

AB
WN R CG SUPPLIER

A FO
DR ED
OVERALL LENGTH AND DIA AS SPECIFICATION

ITH US TYPICAL MARKINGS

W OW
N
GOUGE

3
MARK 11 M

1
CF

88
GB

SPECIES CODE COUNTRY OF ORIGIN

1
CSAD
CG

E
CORSICAN PINE CF UNITED KINGDOM GB

DOUGLAS FIR DF CANADA CA

LODGEPOLE PINE LP FINLAND FI

LARCH, DUNKELD NORWAY NO

LARCH, EUROPEAN LX SWEDEN SE

LARCH, JAPANESE
3000

NORWAY SPRUCE NS

REDWOOD OR SCOTS PINE SP

SITKA SPRUCE SS

WESTERN RED CEDAR WC

INSPECTOR'S MARK THUS

INSPECTOR'S MARK + OR
LENGTH & CLASS + MONTH OF
TREATMENT (1=JANUARY) JS MR

C MODIFIED DRILLINGS
FOR A B C
EAST MIDLANDS
8-10-90 ELECTRICITY
B REVISED TO SHOW SAP
DISPLACED MARKINGS DRILLINGS AND MARKINGS FOR WOOD
11-4-88
POLES FOR LV OVERHEAD LINES
A REDRAWN SHOWING
DRAWN BY GR DEC 1985 Scale N.T.S. Class-
CAD INPUT RKP JAN 1994
REVISED MARKING TO
5-12-85 ESI 43-88 CHECKED BY
APPROVED BY
GR
H.H
DEC 1985
DEC 1985 E101

File Ref: 2-1 Feb 2001.doc Page 4 of 10 Version: 1


East Midlands Electricity Pole Fabrications E100 -E199
Overhead Line Manual Vol.2

E106 33kV Double Circuit Intermediate Pole

75 (3 POSITIONS)
30°

150 m
50 75

SCARFED AT RIGHT ANGLES


TO DRILLING TO LEAVE
75mm OF TIMBER SYMETRICAL 1220
ON POLE CENTRE LINE
(3 POSITIONS)

125 (3 POSITIONS)

NOTE ALL HOLES TO BE 1220


DRILLED 22mm DIAMETER
UNLESS OTHERWISE STATED
AND AT RIGHT ANGLES TO
VERTICAL CENTRE LINE
OVERALL LENGTH AND DIAMETER AS SPECIFIED

OF POLE

GOUGE MARK

DETAILS OF POLE MARKINGS


AS EATS 43-88 issue 4 Part 1
Appendix C

THIS SCARFING ON
OUTER FACE ONLY
m m

254 m

3000 m
127127

1250 UP TO AND INCLUDING 12M POLE


1550 UP TO AND INCLUDING 17M POLE
SEE NOTE

SCARFED TO GIVE
75MM FACE
m m

254 m
127127
460 m

POLE LENGTH AND CLASS


TO BE IMPRESSED ON
POLE BUTT

C GOUGE MARK
18-8-98 REFERENCE AND
EAST MIDLANDS
DH BUTT MARKINGS
AMENDED
ELECTRICITY
B
190MM DIM DELETED 33KV DOUBLE CIRCUIT
25-1-94
UNEARTHED CONSTRUCTION
RKP
INTERMEDIATE POLE

A DRAWN BY Scale N.T.S. Class-


POLE MARKINGS
5-12-85 REVISED CAD INPUT RKP JAN 1994
CHECKED BY
APPROVED BY
ASIE DEC 1977
E106

File Ref: 2-1 Feb 2001.doc Page 5 of 10 Version: 1


East Midlands Electricity Pole Fabrications E100 -E199
Overhead Line Manual Vol.2

E107 33kV Double Circuit Section Pole

190 (3 POSITIONS)
75 (3 POSITIONS) 150
30°

50 75

SCARFED AT RIGHT ANGLES 1220


TO DRILLING TO LEAVE
190mm OF TIMBER SYMETRICAL
ON POLE CENTRE LINE.
(3 POSITIONS)

125 (3 POSITIONS)

1220
OVERALL LENGTH AND DIAMETER AS SPECIFIED

NOTE ALL HOLES TO BE


DRILLED 22mm DIAMETER
UNLESS OTHERWISE STATED
AND AT RIGHT ANGLES TO
VERTICAL CENTRE LINE
OF POLE

GOUGE MARK

DETAILS OF POLE MARKINGS


AS EATS 43-88 issue 4 Part 1
Appendix C

3000

SCARFED TO GIVE
75MM FACE
127
254

460 127

POLE LENGTH AND CLASS


TO BE IMPRESSED
ON POLE BUTT
C GOUGE MARK
18-8-98 REFERENCE,BUTT
MARKINGS AND
EAST MIDLANDS
DH NOTES AMENDED ELECTRICITY
B
25-1-94
190 DIM REPOSITIONED 33KV DOUBLE CIRCUIT
RKP
UNEARTHED CONSTRUCTION
SECTION POLE
D TOP SCARF TO A DRAWN BY Scale N.T.S. Class-
POLE MARKINGS
DH TOP OF POLE 5-12-85 REVISED CAD INPUT RKP JAN 1994
JUN 99 CHECKED BY
APPROVED BY
ASIE DEC 1977
E107

File Ref: 2-1 Feb 2001.doc Page 6 of 10 Version: 1


East Midlands Electricity Pole Fabrications E100 -E199
Overhead Line Manual Vol.2

E111 Brace / Kicking Block

250
ø22 HOLE

333
425
ø22 HOLE
ø26 HOLE

850
ø22 HOLE

205
762
250
125
125

ø24 HOLE

2600
TYPE 1

2500

3000
CC 231554

ø22 HOLE

ø22 HOLE
205
650

333

ø24 HOLE
ø22 HOLE
1300

250
125

TYPE 1 300
150
CC 231580
250
125

125
125

TYPE 2
CC 231586
TYPE 2

CC 231555

STAY OR KICKING BLOCK "H" POLE BRACE BLOCK

MATERIAL: CREOSOTED TIMBER MATERIAL: CREOSOTED TIMBER

EAST MIDLANDS
ELECTRICITY
B
MHM
TYPE 1 BRACE BLOCK
STAY OR SINGLE POLE KICKING BLOCK
18-11-92
HOLE DRILL MOD AND "H" POLE BRACING BLOCK
TP
A DRAWN BY AE JUL 1991 Scale N.T.S. Class-
REDRAWN
AE CAD INPUT RKP JAN 1994
18-7-91
ADB
CHECKED BY
APPROVED BY
E111

File Ref: 2-1 Feb 2001.doc Page 7 of 10 Version: 1


East Midlands Electricity Pole Fabrications E100 -E199
Overhead Line Manual Vol.2

E112 Trefoil Cable Support

N
3500 AW
R
D
H
IT
W

MATERIAL:- 200 x 50
CREOSOTED SOFTWOOD
50

200
COMM. CODE 237595
EAST MIDLANDS
ELECTRICITY
TREFOIL CABLE SUPPORT

DRAWN BY Scale N.T.S. Class-


CAD INPUT RKP JAN 1994
CHECKED BY
APPROVED BY
ASIE DEC 1977
E112

File Ref: 2-1 Feb 2001.doc Page 8 of 10 Version: 1


East Midlands Electricity Pole Fabrications E100 -E199
Overhead Line Manual Vol.2

E113 Standard Universal Pole

125 125
MAX MAX
175 120
30° 160
= =

500
175 120
SEE DETAIL 'A' 160
500
SCARFING TO BE CUT TO
GIVE A 50mm WIDE FLAT
ON BOTH FACES OF
50 MEDIUM AND STOUT POLES.
THE ENDS CHAMFERED
AS SHOWN

45° CHAMFER

DETAIL 'A'

DETAILS OF POLE
MARKINGS AS
EATS 43-88 issue 4
Part 1 Appendix C GOUGE MARK
3000

NOTES

1 CLASS OF POLE TO BE MEDIUM , STOUT


OR EXTRA STOUT AS SPECIFIED

2 ALL HOLES TO BE 22MM DIA DRILLED AT


RIGHT ANGLES TO VERTICAL CENTRE LINE
OF POLE. ALL DRILLING AND CUTTING TO BE
DONE STRICTLY TO TEMPLATE PRIOR TO
PRESERVATION TREATMENT.

3 POLE BUTT TO BE CUT AT RIGHT ANGLES


POLE LENGTH AND CLASS TO AXIS OF POLE.
TO BE SHOWN ON POLE BUTT
4 IF BAULK IS REQUIRED, POLE IS TO BE
NOTCHED AND AND DRILLED ON SITE.

C
13-5-92 POSITION OF
CROSSARM
EAST MIDLANDS
MHM
TP
MOVED UP 25MM ELECTRICITY
B
E GOUGE MARK 14-10-91 NOTE 4 AMENDED
AUG 98
REFERENCE AND BUTT
MARKINGS AMENDED
ADB SINGLE POLE FABRICATION
DH
D REF. TO 'LIGHT' POLES, A DRAWN BY Scale N.T.S. Class-
APR 98 STANDARD NOTCHINGS ADDITIONAL NOTES
17-7-91 CAD INPUT RKP JAN 1994
AND DRILLINGS,
MR
TABLE FOR DIM 'X'
ALL REMOVED
ADB CHECKED BY ADB APR 1991
APPROVED BY HBH APR 1991 E113

File Ref: 2-1 Feb 2001.doc Page 9 of 10 Version: 1


East Midlands Electricity Pole Fabrications E100 -E199
Overhead Line Manual Vol.2

E114 H Pole

MINIMUM TOP
DIA. SEE NOTE 2

125 MAX 125 MAX


30°

160 120
= =

N
120
200
SEE DETAIL 'A'

160
AW
550

's
45° CHAMFER 45° CHAMFER

13
D

E1
H
DETAIL 'A'
IT

NOTES
1. CLASS OF POLES TO BE 'MEDIUM' OR 'STOUT' AS SPECIFIED

o 2. 'MEDIUM' CLASS POLES TO HAVE A MINIMUM DIA. OF 175 AT TOP


'STOUT' CLASS POLES TO HAVE A MINIMUM DIA. OF 210 AT TOP
W

tw
3. POLES TO BE MATCHED

4. ALL HOLES TO BE 22mm DIA DRILLED AT RIGHT ANGLES TO VERTICAL


CENTRE LINE OF POLE. ALL DRILLING AND CUTTING TO BE DONE
DEATAILS OF POLE STRICTLY TO TEMPLATE PRIOR TO PRESERVATION TREATMENT
MARKINGS AS
EATS 43-88 issue 4 GOUGE MARK 5. POLE BUTT TO BE CUT AT RIGHT ANGLES TO AXIS OF POLE
Part 1 Appendix C ON OPPOSITE SIDE
6. POLE TO BE DRILLED FOR DUPLICATE 250 X 125 BAULKS
se

POLE LENGTH (m) DIM "X"

8.5-11 INCLUSIVE 1900


11.5-12 " 1700
U

13-15 " 1400


16-18 " 1100
20- " 500
DIM 'X'

3000

190
380

600

SEE NOTE 6
SEE NOTE 7

POLE LENGTH AND CLASS


TO BE IMPRESSED
ON POLE BUTT

DEC 98
C NOTE 7 DELETED
NOTE 6AMENDED
HOLE AT 750 FROM
EAST MIDLANDS
TOP REMOVED
DH

B
GOUGE MARK
ELECTRICITY
REFERENCE AND

H POLE FABRICATION
AUG 98
BUTT MARKINGS
DH AMENDED

D A DRAWN BY Scale N.T.S. Class-


NOTCHES FOR BAULKS
REMOVED ADDITIONAL NOTES
D.H. 16-7-91 CAD INPUT RKP JAN 1994

E114
JUN 99 ADB CHECKED BY ADB APR 1991

APPROVED BY HBH APR 1991

File Ref: 2-1 Feb 2001.doc Page 10 of 10 Version: 1


Distribution Business

Section 2.2
STEELWORK
E200-E299

Version Prepared by Approved by Issue Date


2 Tony Haggis See Database July 2006
East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

Revision Log For Steelwork E200 - E299


Changes made in version 2 July 2006

Section Notes about the change


E247A Surge Arrestor holes resized from 14mm – 17mm to
accept 33kV Surge Arrestor

Changes made in version 1

Section Notes about the change

Version: 2 July 2006 2 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

CONTENTS

E200 Rawlbolt Hook Anchor for ABC Services 5

E208 Coach Screw 6

E213 Crossarm 2.9m 7

E219 Crossarm 2.6m 8

E220 33kV Double Circuit Intermediate Crossarms 9

E221 33kV Double Circuit Section Crossarm 10

E222 33kV Double Circuit Middle Crossarm 11

E223 33kV Double Circuit Botton Section Angle Crossarm 12

E224 Crossarm Strap 11H, 33S & 33D SUPERSEDED 13

E226 Steady Insulator Support Channel SUPERSEDED 14

E228 Intermediate Crossarm 50 ACSR 15

E229 Intermediate Crossarm General Application 16

E230 Crossarm Strut (Tie-strap) 17

E231 Fuse Mount / Pilot Insulator Crossarm 18

E233 Fuse Crossarm Struts (Short) 19

E234 Transformer Platform 1000kg / Fuse Crossarm Struts (Long) 20

E235 Pilot Insulator Crossarm ‘H’ Pole 21

E 238 Strap for Section Pole Crossarm 22

E 239 Strap for Terminal Pole Crossarm 23

E240 Cable Support Channel 24

E241 Cable Support Bracket WITHDRAWN 25

E242 Trefoil Cable Support Channel WITHDRAWN 26

E243 Insulator Bracket 27

E244 H Pole U/G Brace 1.9m Centres 28

Version: 2 July 2006 3 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E247A Surge Arrester Mounting Bracket / Cable Termination 29

E248 H Pole U/G Brace 2.5m Centres 30

E249 Tie Rod 31

E250 33kV Sealing End Mount WITHDRAWN 32

E254 Universal ABSD Steelwork 33

E257 33kV Surge Arrester Mount WITHDRAWN 34

E258 Triggered Gap Mount WITHDRAWN 35

E260 Curved Square Washer 36

E261 Flat Square Washer 37

E262 ‘J’ Bolt 38

E263 Anti-Climbing Guards 39

E266 Tapered Curved Square Washer 40

E267 ‘J’ Bolt for Tower Anti-climbing Guard Gate 41

E268 Humped Back Split Pin 42

E269 ‘R’ Type Retaining Pin 43

Version: 2 July 2006 4 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E200 Rawlbolt Hook Anchor for ABC Services

15
ø10 GAP

ø25

70

90 THREADED M10
ISO METRIC

FULL NUT

LARGE DIAMETER BLACK


WASHER (24MM) TO BS4320

PLATED RAWLBOLT SHIELD


CAT. NO. 44-100
MATERIAL:
MILD STEEL TO BS4360 GRADE 43A
FINISH:
NUT, BOLT & WASHER - HOT DIP
GALVANISE TO BS729
RAWLBOLT - PLATED

ASSEMBLY:
TO BE SUPPLIED ASSEMBLED WITH
THREAD WELL OILED

COMMODITY CODE-234691

EAST MIDLANDS
ELECTRICITY
RAWLBOLT HOOK ANCHOR
FOR A.B.C. SERVICES
B DRAWN BY MHM SEP 1990 Scale N.T.S. Class-
MODIFIED AND CAD INPUT RKP JAN 1994
REDRAWN
SEPT 90 CHECKED BY
APPROVED BY
ADB
HBH
OCT 1990
OCT 1990 E 200

Version: 2 July 2006 5 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E208 Coach Screw

GIMLET POINT

75

ø10
10 COACH SCREW
TO BS1494 PART 2

COMMODITY CODE 235804

GIMLET POINT
31

ø10
10 COACH SCREW
FOR WOOD FIXING TO BS1494 PART 2

COMMODITY CODE 235800

MATERIAL

MILD STEEL 28/33 TON QUALITY, GALVANISED


TO MEET REQUIREMENTS OF BS729

EAST MIDLANDS
ELECTRICITY

COACH SCREW
A DRAWN BY Scale N.T.S. Class-
MHM REDRAWN. CAD INPUT RKP JAN 1994
TITLE CHANGE
SEPT 90 CHECKED BY ADB OCT 1990
APPROVED BY HBH OCT 1990 E 208

Version: 2 July 2006 6 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E213 Crossarm 2.9m

75
100
50 50 43

483

1200
467

24 DIA
500
155
2900 400
90
500
24 DIA

467
1200

483

50
HOLES TO BE 22 DIA UNLESS
OTHERWISE SHOWN COMM. CODE 233148
TOLERANCES BEFORE GALVANISING
(UNLESS OTHERWISE STATED)
MATERIAL: 100*75*12 ROLLED STEEL ANGLE
DIMENSIONS UP TO AND INCLUDING 50mm ± 1mm
MILD STEEL TO B.S. 4360
DIMENSIONS OVER 50mm ± 2mm
GRADE 43A
HOLE DIAMETERS UP TO AND INCL 10mm + 0.5mm
AFTER FABRICATION HOT DIP GALVANISE TO B.S. 729
HOLE DIAMETERS OVER 10mm + 1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE
BASED UPON EATS DRG NO 439520

EAST MIDLANDS
ELECTRICITY
B TOLERANCES
D.H. CORRECTED
NOV 99 Crossarm 2.9m
A DRAWN BY Scale N.T.S. Class-
RETRACED. JAN 1994
MHM CAD INPUT RKP
HOLE POSITION MOD
NOV 92 CHECKED BY
APPROVED BY E 213

Version: 2 July 2006 7 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E219 Crossarm 2.6m

125

75 70
100 55
43

90
233
260

467

850

500
90

2600

500

850

467

260
233
90

100 55

ALL HOLES TO BE 22 DIA


COMM. CODE 233180
TOLERANCES BEFORE GALVANISING
(UNLESS OTHERWISE STATED)
MATERIAL: 125x75x12 ROLLED STEEL ANGLE DIMENSIONS UP TO AND INCLUDING 50mm ± 1mm
MILD STEEL TO B.S. 4360 GRADE 43A
AFTER FACBRICATION HOT DIP GALVANISE DIMENSIONS OVER 50mm ± 2mm
TO B.S. 729 HOLE DIAMETERS UP TO AND INCL 10mm + 0.5mm
HOLE DIAMETERS OVER 10mm + 1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


BASED UPON EATS DRG NO 439522 0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
B TOLERANCES
D.H. CORRECTED
NOV 99 CROSSARM - 2.6M
A DRAWN BY MHM NOV 1992 Scale N.T.S. Class-
REDRAWN CAD INPUT RKP JAN 1994
MHM
20-11-92
TP
HOLE POSITION MOD
CHECKED BY
APPROVED BY
TP
TP
E 219

Version: 2 July 2006 8 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E220 33kV Double Circuit Intermediate Crossarms

125 75 125 75
75 37.5 75 37.5
75 75

ø24
ø24
610
ø22
1220

150
ø14
ø22 EARTH
STRIP
150

HOLES
2894 1524
EARTH
ø14 STRIP
EARTH HOLES
STRIP ø14
HOLES
4114 1524

150
EARTH
STRIP
HOLES
ø22
ø14 610
ø24
150

75
ø22
ITEM B
TOP OR BOTTOM CROSSARM
1220
COMMODITY CODE 233200
ø24

75
TOLERANCES BEFORE GALVANISING
ITEM A MIDDLE CROSSARM (UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50mm ± 1mm
COMMODITY CODE 233210 DIMENSIONS OVER 50mm ± 2mm
HOLE DIAMETERS UP TO AND INCL 10mm + 0.5mm
HOLE DIAMETERS OVER 10mm + 1mm
MATERIAL: 125x75x12 ROLLED STEEL ANGLE AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE
MILD STEEL TO B.S. 4360 GRADE 43A
AFTER FACBRICATION HOT DIP GALVANISE 0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE
TO B.S. 729

EAST MIDLANDS
ELECTRICITY
TOP OR BOTTOM AND MIDDLE
INTERMEDIATE CROSSARMS
FOR 33KV DOUBLE CIRCUIT LINES
A TOLERANCES DRAWN BY YMP JUL 1977 Scale N.T.S. Class-
CORRECTED
D.H. CAD INPUT RKP JAN 1994
NOV 99 CHECKED BY
APPROVED BY
ASIE JUL 1977
E 220

Version: 2 July 2006 9 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E221 33kV Double Circuit Section Crossarm

125 75 75

75 44 44
10

50
50
ø22 E238

M20*254 TIE BOLT

610
ø22

150
ø14
BONDING HOLES
2844

1524

BONDING HOLES
ø14
150

ø22
610

M20*254 TIE BOLT

ø22 E238
COMMODITY
CODE
233215
50
50

Tolerances before galvanising


COMPLETE ASSEMBLY (unless otherwise stated)
TO BE SUPPLIED ASSEMBLED WITH GALVANISED Dimensions up to and including 50mm ± 1 mm
M20*50 BOLTS, NUTS AND FLAT WASHERS over 50mm ± 2 mm
Hole diameters up to and including 10mm + 0.5 mm
over 10mm + 1 mm

MATERIAL: 125*75*10 ROLLED STEEL ANGLE MILD


STEEL TO B.S. 4360 GRADE 434A AFTER FABRICATION After galvanising holes must pass a plug gauge
HOT DIP GALVANISE TO B.S. 729 0.5mm smaller than nominal diameter of hole

C ITEM E238
DH WAS E224 EAST MIDLANDS
JUN 99
ELECTRICITY
B
IMINOR MOD.
33kV DOUBLE CIRCUIT CROSSARMS
10/01/92
TOP / BOTTOM SECTION
D TOLERANCES A DRAWN BY YMP JUL 1977 Scale N.T.S. Class-
D.H. DIM 75 ADDED CAD INPUT
CORRECTED
NOV 99 28-11-78 CHECKED BY
APPROVED BY
ASIE JUL 1977
30/10/78 E 221

Version: 2 July 2006 10 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E222 33kV Double Circuit Middle Crossarm

125 190
76 76
75 22 22

50
10
ø22

50
ø22 E238

M20*254 TIE BOLT

610
M20*254 TIE BOLT

610
ø22

150
ø14
BONDING HOLES
4064

1524

BONDING HOLES
ø14
150

ø22
610

M20*254 TIE BOLT

COMMODITY
610

M20*254 TIE BOLT


CODE ø22 E238 ø22
233220
50
50

Tolerances before galvanising


COMPLETE ASSEMBLY (unless otherwise stated)
TO BE SUPPLIED ASSEMBLED WITH GALVANISED Dimensions up to and including 50mm ± 1 mm
over 50mm ± 2 mm
M20*50 BOLTS, NUTS AND FLAT WASHERS
Hole diameters up to and including 10mm + 0.5 mm
over 10mm + 1 mm

MATERIAL: 125*75*10 ROLLED STEEL ANGLE MILD


STEEL TO B.S. 4360 GRADE 434A AFTER FABRICATION After galvanising holes must pass a plug gauge
0.5mm smaller than nominal diameter of hole
HOT DIP GALVANISE TO B.S. 729

C
DH
REDRAWN
ITEM E238
EAST MIDLANDS
JUN 99 WAS E224 ELECTRICITY
B
MINOR MOD.
33kV DOUBLE CIRCUIT CROSSARM
10-1-92
MIDDLE SECTION
D A TIE BOLT SIZE DRAWN BY YMP JUL 1977 Scale N.T.S. Class-
TOLERANCES ADDED
D.H. CORRECTED CAD INPUT
NOV 99 28-1-80 CHECKED BY
APPROVED BY
ASIE JUL 1977
OCT 78
E 222

Version: 2 July 2006 11 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E223 33kV Double Circuit Botton Section Angle Crossarm

76 190 76
125 125
75 75 44 44
10

50
50
50

E238

M20*254 TIE BOLT

610

150
4 No. ø14
1524

BONDING HOLES
3554

150
610

M20*254 TIE BOLT

E238

ALL HOLES 22 DIA UNLESS


OTHERWISE STATED

COMMODITY
722

CODE
233215
ø24 STEEL FLAT
340*75*10
38

38

38
38

44 190 44
COMPLETE ASSEMBLY
TO BE SUPPLIED ASSEMBLED WITH GALVANISED 340 Tolerances before galvanising
M20*50 BOLTS, NUTS AND FLAT WASHERS (unless otherwise stated)
Dimensions up to and including 50mm ± 1 mm
over 50mm ± 2 mm
Hole diameters up to and including 10mm + 0.5 mm
over 10mm + 1 mm
MATERIAL: 125*75*10 ROLLED STEEL ANGLE MILD
STEEL TO B.S. 4360 GRADE 434A AFTER FABRICATION After galvanising holes must pass
HOT DIP GALVANISE TO B.S. 729 a plug gauge 0.5mm smaller
than nominal diameter of hole

C REDRAWN
DH E238 WAS
EAST MIDLANDS
JUN 99 E224 ELECTRICITY
B
MINOR 33KV DOUBLE CIRCUIT CROSSARM
10.1.92 MOD BOTTOM ANGLE SECTION
D A MODS TO DRAWN BY YMP JUL 1977 Scale N.T.S. Class-
TOLERANCES CAD INPUT RKP JAN 1994
D.H. CORRECTED MATERIAL
NOV 99 28-1-80 DETAILS CHECKED BY ASIE JUL 1977
APPROVED BY E 223

Version: 2 July 2006 12 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E224 Crossarm Strap 11H, 33S & 33D SUPERSEDED

75 mm

= =

37.5
ø18
84 mm

ED
28 mm

22 WIDE SLOT

D
126 mm

SE
495 mm

ø24
D
140 mm

R
PE

ø22
70 mm

ø18
SU
37.5

10 mm

75 mm

COMM. CODE 236682


TOLERANCES BEFORE GALVANISING
(UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50mm ± 1mm MATERIAL: 75*10 MILD STEEL FLAT
DIMENSIONS OVER 50mm ± 2mm MILD STEEL TO B.S. 4360 GRADE 43A
HOLE DIAMETERS UP TO AND INCL 10mm ± 0.5mm AFTER FABRICATION HOT DIP GALVANISE
HOLE DIAMETERS OVER 10mm ± 1mm TO B.S. 729

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
CROSSARM TENSION STRAP FOR
11, 33S & 33D "H" TERMINAL POLES
DRAWN BY YMP JULY 1978 Scale N.T.S. Class-
A TITLE AMENDED
CAD INPUT RKP JAN 1994
11-9-91 CHECKED BY
APPROVED BY
ASIE JULY 1978
E 224

Version: 2 July 2006 13 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E226 Steady Insulator Support Channel SUPERSEDED

76
38 38

50
24 DIA

508
22 DIA

50 50

100
ED
1425
100*100*6 PLATES WELDED ACROSS UPRIGHTS

D
SE
OF CHANNEL. 22 DIA HOLES THROUGH
BOTH CHANNEL AND PLATE
R

24 DIA
1934

2950
PE
SU

1425

MATERIAL: 76*38 ROLLED STEEL CHANNEL


MILD STEEL TO B.S. 4360 GRADE 43A
AFTER FABRICATION HOT DIP GALVANISE 22 DIA
TO B.S. 729

COMM. CODE 233226


TOLERANCES BEFORE GALVANISING
508

(UNLESS OTHERWISE STATED)

DIMENSIONS UP TO AND INCLUDING 50MM ±1MM


DIMENSIONS OVER 50MM. . . . . ±2MM 24 DIA
HOLE DIAMETERS UP TO AND INCL 10MM ±0.5MM
HOLE DIAMETERS OVER 10MM . . . ±1MM
50

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
SUPPORT CHANNEL
FOR STEADY INSULATORS
DRAWN BY MHM FEB 1982 Scale N.T.S. Class-
CAD INPUT RKP JAN 1994
CHECKED BY
APPROVED BY
GHJ FEB 1982
E 226

Version: 2 July 2006 14 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E228 Intermediate Crossarm 50 ACSR

100 75

50 43
50

24 DIA

550

885

22 DIA
500
22 DIA
115 115

2100 230 24 DIA


22 DIA
22 DIA
500

22 DIA 885

550 24 DIA

50

COMM. CODE 233240


TOLERANCES BEFORE GALVANISING
MATERIAL: 100x75x12 ROLLED STEEL ANGLE (UNLESS OTHERWISE STATED)
MILD STEEL TO B.S. 4360 GRADE 43A DIMENSIONS UP TO AND INCLUDING 50mm ± 1mm
AFTER FACBRICATION HOT DIP GALVANISE DIMENSIONS OVER 50mm ± 2mm
TO B.S. 729
HOLE DIAMETERS UP TO AND INCL 10mm + 0.5mm
HOLE DIAMETERS OVER 10mm + 1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


BASED UPON ESI DRG NO 439556 0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

C
D.H. TOLERANCES
CORRECTED
EAST MIDLANDS
NOV 99
ELECTRICITY
B TITLE AMENDED
D.H. CROSSARM FOR SINGLE POLE
OCT 99
11kV - 50mm² ACSR
A DRAWN BY Scale N.T.S. Class-
NEW TITLE
MHM REDUNDANT HOLES CAD INPUT RKP JAN 1994
19-11-92
TP
REMOVED CHECKED BY
APPROVED BY
ADB
ADB
JUL 1991
JUL 1991 E 228

Version: 2 July 2006 15 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E229 Intermediate Crossarm General Application

100 75

50 43
50

24 DIA

750

1085

22 DIA
500
22 DIA

2500 230

22 DIA
500

22 DIA
1085

750
24 DIA

50
COMM. CODE 233242
MATERIAL: 100x75x10 ROLLED STEEL ANGLE TOLERANCES BEFORE GALVANISING
MILD STEEL TO B.S. 4360 GRADE 43A (UNLESS OTHERWISE STATED)
AFTER FACBRICATION HOT DIP GALVANISE DIMENSIONS UP TO AND INCLUDING 50mm ± 1mm
TO B.S. 729 DIMENSIONS OVER 50mm ± 2mm
HOLE DIAMETERS UP TO AND INCL 10mm + 0.5mm
HOLE DIAMETERS OVER 10mm + 1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE

BASED UPON EATS DRG NO 439557 0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
B TOLERANCES
D.H. CORRECTED CROSSARM FOR SINGLE POLE
NOV 99
(APPLICATION GENERAL)
A DRAWN BY Scale N.T.S. Class-
REDUNDANT
MHM CAD INPUT RKP JAN 1994
19-11-92
TP
OLES
REMOVED
CHECKED BY
APPROVED BY
ADB
ADB
JUL 1991
JUL 1991
E 229

Version: 2 July 2006 16 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E230 Crossarm Strut (Tie-strap)

65

15 35

15 22

22 DIA

750

COMM. CODE 233510

MATERIAL: 65x50x8 ROLLED STEEL ANGLE


MILD STEEL TO B.S. 4360 GRADE 43A
AFTER FACBRICATION HOT DIP GALVANISE
TO B.S. 729

BASED ON EATS DRG. NO.439526


TOLERANCES BEFORE GALVANISING
(UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50mm ± 1mm
DIMENSIONS OVER 50mm ± 2mm
HOLE DIAMETERS UP TO AND INCL 10mm + 0.5mm
+ 1mm 22 DIA
HOLE DIAMETERS OVER 10mm
AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE
22
0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
STRUT - CROSSARM
(TIE-STRAP)
A DRAWN BY Scale N.T.S. Class-
TOLERANCES CAD INPUT RKP JAN 1994
E 230
D.H.
CORRECTED
NOV 99 CHECKED BY ADB JUL 1991
APPROVED BY

Version: 2 July 2006 17 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E231 Fuse Mount / Pilot Insulator Crossarm

SIDE A SIDE B
70 70
40 40

18 DIA
50

50 50 50
14 DIA

22 DIA

673
875

25
18 DIA
50

1750 304
14 DIA
50

22 DIA

875
673

22 DIA
50 50 50

18 DIA
50

14 DIA
SIDE A 4 SLOTS 50*22 WIDE
COMM. CODE 233050
TOLERANCES BEFORE GALVANISING
(UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50mm ± 1mm
DIMENSIONS OVER 50mm ± 2mm
HOLE DIAMETERS UP TO AND INCL 10mm + 0.5mm MATERIAL: 70x70x10 ROLLED STEEL ANGLE
HOLE DIAMETERS OVER 10mm + 1mm MILD STEEL TO B.S. 4360 GRADE 43A
AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE
AFTER FACBRICATION HOT DIP GALVANISE
TO B.S. 729
0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
D TOLERANCES B
D.H.
NOV 99
CORRECTED 27-11-79
MINOR MOD AND TITLE
AMENDED Fuse Mount /
C
Pilot Insulator Crossarm
A LENGTHENED FROM 1675 DRAWN BY MHM JULY 1977 Scale N.T.S. Class-
HOLES AMENDED
12-7-83 9-3-79 CAD INPUT RKP JAN 1994
TO 1750
CHECKED BY
APPROVED BY
ASIE
JL
AUG 1977
NOV 1977 E 231

Version: 2 July 2006 18 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E233 Fuse Crossarm Struts (Short)

480
50
305

50
30

50
30
CROSSARM SUPPORT ITEM "A" 40
MATERIAL: 50x50x8 ROLLED STEEL ANGLE

CROSSARM SUPPORT ITEM "B"


MATERIAL: 50x50x8 ROLLED STEEL ANGLE

30 30

30 22

40
30
35
430

500
40
6

SUPPORT STRUT ITEM "C"

MATERIAL: 40x40x6 ROLLED STEEL ANGLE

COMM. CODE 233053.0


TOLERANCES BEFORE GALVANISING TO BE SUPPLIED AS A SET COMPRISING:
(UNLESS OTHERWISE STATED) 1 - ITEM A
1 - ITEM B
DIMENSIONS UP TO AND INCLUDING 50mm ± 1mm 2 - ITEM C
DIMENSIONS OVER 50mm ± 2mm BUNDLE WITH ZINC PLATED OR OTHER
HOLE DIAMETERS UP TO AND INCL 10mm + 0.5mm NONE RUSTING BANDING
HOLE DIAMETERS OVER 10mm + 1mm ALL HOLES 22MM DIA
AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE MILD STEEL TO B.S. 4360 GRADE 43A
0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE AFTER FABRICATION HOT DIP GALVANISE
TO B.S. 729

EAST MIDLANDS
ELECTRICITY
B TOLERANCES
D.H. CORRECTED FUSE CROSSARM SUPPORT
NOV 99
(SHORT)
A NOTES ADDED DIMS. DRAWN BY MHM AUG 1977 Scale N.T.S. Class-
CAD INPUT RKP JAN 1994

E 233
13.5.80 AND COMM. CODE NO.
CHECKED BY ASIE AUG 1977
AMENDED
APPROVED BY JL NOV 1977

Version: 2 July 2006 19 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E234 Transformer Platform 1000kg / Fuse Crossarm Struts (Long)

1000
500

34
60
45 45
12 DIA HOLE

34
60
50 70 70 50

ITEM "A" 60x60x6 RSA

1225
15 50
15

30
25 25
2 HOLES 22 DIA
ITEM "B" 50*50*6 RSA

330
ITEM "A" 120 90 120

M20 THREAD
M20 POLE ITEM "C" TIE ROD
830 Hole Centrers

BOLT (E249) CC 235785


NOTES
1 ALL DIMENSIONS IN MM
2 UNLESS OTHERWISE STATED, ALL HOLES
ITEM "B" 22 DIA.

3 ALL STEEL TO BS 4360 GRADE 43A.


AFTER FABRICATION HOT DIP GALVANISE
TO BS 729
4 TO BE SUPPLIED & STOCKED AS BUNDLED
M20 POLE BOLT SET COMPRISING: 2xITEM "A"
2XITEM "B"
5 ITEM "C" MUST BE ORDERED SEPARATELY

COMM. CODE 235448


TIE ROD (E249)
TOLERANCES BEFORE GALVANISING
(UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50mm ± 1mm
DIMENSIONS OVER 50mm ± 2mm
HOLE DIAMETERS UP TO AND INCL 10mm ± 0.5mm
HOLE DIAMETERS OVER 10mm ± 1mm

AFTER GALVANISING HOLES MUST PASS A


PLUG GAUGE 0.5mm SMALLER THAN NOMINAL
DIAMETER OF HOLE
F C
COMM. CODE AMENDED
HBH
M20*40 BOLTS
DELETED NO. WAS 235575 EAST MIDLANDS
31-7-84 RATING ADDED 28-4-80
ELECTRICITY
TOLERANCES E B
H
CORRECTED TIE ROD ADDED REDRAWN WITH MODS
PLATFORM FOR POLE TRANSFORMER
D.H.
NOV 99 16-8-83 9-3-79
Up To 1000KG
OR FUSE MOUNTING CROSSARM
G D A DRAWN BY MHM MAR 1979 Scale N.T.S. Class-
TITLE MOD NOW TO ESI DRG NO. CAD INPUT RKP JAN 1994
MHM
ITEM "A" MOD
1-9-92
TP
ITEM "C" MOD 20-5-83 439523 CHECKED BY
APPROVED BY
GR APR 1979
PDB APR 1979 E 234

Version: 2 July 2006 20 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E235 Pilot Insulator Crossarm ‘H’ Pole

(INTERIM EDITION)

125
65 75

22 DIA
433

22 DIA
384

18 DIA 150
2034
150
22 DIA

18 DIA
384

22 DIA
433

22 DIA
50

COMM. CODE 233300 NOTE


1. FOR PILOT INSULATORS OR CABLE
TOLERANCES BEFORE GALVANISING TERMINATION ONE PIECE REQUIRED
(UNLESS OTHERWISE STATED) 2. FOR TRANSFORMER SUPPORT TWO
PIECES REQUIRED
DIMENSIONS UP TO AND INCLUDING 50mm ± 1mm
DIMENSIONS OVER 50mm ± 2mm
HOLE DIAMETERS UP TO AND INCL 10mm + 0.5mm
MATERIAL: 125x75x10 ROLLED STEEL ANGLE
HOLE DIAMETERS OVER 10mm + 1mm
MILD STEEL TO B.S. 4360 GRADE 43A
AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE AFTER FACBRICATION HOT DIP GALVANISE
TO B.S. 729
0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

C TOLERANCES
D.H. CORRECTED EAST MIDLANDS
NOV 99
ELECTRICITY
B
18MM DIA HOLES
ADDED FOR USE AS
PILOT INSULATOR CROSSARM
13.5.88
E218 FOR 'H' POLES
A NOTES ADDED DRAWN BY MHM AUG 1977 Scale N.T.S. Class-
CAD INPUT RKP JAN 1994

E 235
19.5.80 TITLE AMENDED
CHECKED BY ASIE AUG 1977
APPROVED BY JL NOV 1977

Version: 2 July 2006 21 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E 238 Strap for Section Pole Crossarm

120°

40

60
50mm Radius

65

110

550
Hole 24mm Dia.

110

65 2 Slots 22mm Wide

60 2 Holes 38mm Dia.


(Edges to be chamfered
3mm each side through
40 120°)
120°

100 15

COMMODITY CODE 233540


Tolerances before galvanising
(unless otherwise stated)
Dimensions up to and including 50mm ± 1 mm MATERIAL: 130*12 MILD STEEL FLAT TO
over 50mm ± 2 mm B.S. 4360 GRADE 43A
Hole diameters up to and including 10mm + 0.5 mm HOT DIP GALVANISED TO B.S. 729
over 10mm + 1 mm AFTER FABRICATION

After galvanising holes must pass a plug gauge


0.5mm smaller than nominal diameter of hole BASED UPON EATS DRG. 439525
EAST MIDLANDS
ELECTRICITY
B
TOLERANCES
D.H.
NOV 99
CORRECTED
STRAP - SECTION
DRAWN BY AE MAY 1991 Scale N.T.S. Class-
A REDRAWN

E 238
DH 38mm HOLES WERE 18mm CAD INPUT
JUN 99 CHECKED BY ADB JULY 1991
APPROVED BY ADB JULY 1991

Version: 2 July 2006 22 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E 239 Strap for Terminal Pole Crossarm

20 45 45 20
2 HOLES 22 DIA

30

80 150

D
RA
m
m
65

40

1 HOLE 38mm DIA


(EDGES TO BE CHAMFERED
3mm EACH SIDE THROUGH
120°) 120°

12

130

COMMODITY CODE 233550


Tolerances before galvanising
(unless otherwise stated)
Dimensions up to and including 50mm ± 1 mm MATERIAL: 130*12 MILD STEEL FLAT TO
over 50mm ± 2 mm B.S. 4360 GRADE 43A
Hole diameters up to and including 10mm + 0.5 mm HOT DIP GALVANISED TO B.S. 729
over 10mm + 1 mm AFTER FABRICATION

After galvanising holes must pass a plug gauge


0.5mm smaller than nominal diameter of hole BASED UPON EATS DRG. 439528
EAST MIDLANDS
ELECTRICITY
B TOLERANCES
D.H.
NOV 99
CORRECTED
STRAP - TERMINAL
DRAWN BY Scale N.T.S. Class-
A REDRAWN
CAD INPUT RKP

E 239
DH 38mm HOLE WAS 18mm JAN 1994
JUN 99 CHECKED BY ADB JULY 1991
APPROVED BY ADB JULY 1991

Version: 2 July 2006 23 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E240 Cable Support Channel

76

38

HOLE "A"
FOR HEATSHRINK

40
22 DIA HOLE
POLE TERMINATION
(M20 BOLT)

115
MOUNTING BRACKET
DRAWING E247A

190
14 DIA HOLE CC2325830
(M12 BOLT)

22 DIA HOLE
(M20 BOLT)

FOR USE WITH POLE


MOUNTED DISTRIBUTION
240

CABINET.
SEE DRG A026
USE HOLES AT A & B

22 WIDE SLOT
20

(M20 BOLT)
950
1150

HOLE "B"
22 DIA HOLE
(M20 BOLT)
+0.5mm
+1mm
±1mm
±2mm

18 DIA HOLE FOR CABLE CLEAT:


AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE

95mm² CC533201
0.5mm SMALLER THAN NOMINAL DIAMETER OF HOLE

185mm² C533204
300mm² C533207
DIMENSIONS UP TO AND INCLUDING 50mm

HOLE DIAMETERS UP TO AND INCL 10mm


TOLERANCES BEFORE GALVANISING
(UNLESS OTHERWISE STATED)

38
HOLE DIAMETERS OVER 10mm
DIMENSIONS OVER 50mm

14 DIA HOLE FOR


EARTH CONNECTION
(M12 BOLT)
25

"X"
50

20

VIEW ON ARROW "X"


MATERIAL: 76*38 ROLLED STEEL CHANNEL
MILD STEEL TO B.S. 4360 GRADE 43A
AFTER FABRICATION HOT DIP GALVANISE
TO B.S. 729
COMM. CODE 2325810
C MODS. & APPLICATIONS
4.85 EAST MIDLANDS
ELECTRICITY
E E247A WAS E247. B
MODS. TO MATERIALS
D.H. TOLEARANCES AND 28.1.80
NOV 99
TITLE AMENDED DETAILS Cable Support Channel
D REDRAWN ON A DRAWN BY YMP AUG 1977 Scale N.T.S. Class-
SIDE VIEW ADDED
PIB AUTOCAD CAD INPUT RKP JAN 1994
12.1.79
17.4.98 CHECKED BY
APPROVED BY
ASIE AUG 1977
JL NOV 1977 E 240

Version: 2 July 2006 24 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E241 Cable Support Bracket WITHDRAWN

E 218

ITEM "A" ITEM "A"

PROVISION FOR SILICON ALUMINIUM CABLE


CLEAT STOCKED SEPARATELY AS:
CC 533201 (95M 2
M )
CC 533204 (185M 2 M )

CC 533207 (300M 2 M )

CABLE

M12*30 SPUN GALVANISED


BOLT, NUT & WASHERS
(AT 2 POSITIONS)
ITEM "B"

FRONT ELEVATION

N
W
870 mm
40 mm 790 mm 40 mm

50*6 FLAT MILD STEEL


50 mm

25 mm

1 HOLE 18 DIA 1 HOLE 14 DIA


R

ITEM " A"


2 REQUIRED
D

152 mm
H

75*9 FLAT MILD STEEL 26 mm 50 mm


50 mm 26 mm

2 HOLES 14 DIA
75 mm

38 mm
IT

1 HOLE DIA 18

ITEM " B"


W

1 REQUIRED

COMM. CODE 232460 (STEELWORK)


ASSEMBLY: TO BE SUPPLIED ASSEMBLED

TOLERANCES BEFORE GALVANISING


(UNLESS OTHERWISE STATED)

DIMENSIONS UP TO AND INCLUDING 50MM E 1MM MATERIAL:


DIMENSIONS OVER 50MM. . E
. . . 2MM MILD STEEL TO B.S.GRADE
4360 43A
HOLE DIAMETERS UP TO AND INCL
E 10MM 0.5MM
AFTER FABRICATION HOT DIP GALVANISE
HOLE DIAMETERS OVER 10MM E . . . 1MM TO B.S. 729
AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE FASTENERS TO BE SUPPLIED SPUN
0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE GALVANISED TO BS 729

F C
27.6.85 MINOR MODS 25.7.80
COMM. CODE ADDED EAST MIDLANDS
ELECTRICITY
H E B
11.9.91
TITLE AMENDED
13.1.84
WOOD CLEAT
28.1.80
MODS TO MATERIAL CABLE SUPPORRT BRACKET FOR USE
REPLACED BY DETAILS
SILICON ALUMINIUM
ON H" POLE 11KV CONSTRUCTION
G MINOR MOD
D WOOD BLOCK A M16 STUDS REPLACED
DRAWN BY YMP AUG 1977 Scal e N. T. S. Cl ass-
23.3.88 16.3.82 14.6.79 CAD I NPUT RKP JAN 1994
MATERIAL WAS BY BOLTS
TEAK CHECKED BY ASIE AUG 1977 E 241
APPROVED BY JL NOV 1977

Version: 2 July 2006 25 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E242 Trefoil Cable Support Channel WITHDRAWN

99
2034 mm

1017 mm 1017 mm

V
50 mm
150 mm 150 mm
50 mm
40 mm
70 mm

O
N
14 DIA 18 DIA 14 DIA

22 DIA 22 DIA

N E 708

70*70*8 RSA
W
A

TOP FLANGE CUT AWAY AT


EACH END AT 30°
R

967 mm 967 mm
D
H
IT
W

NOTE 2 BRACKETS REQUIRED PER INSTALLATION


COMM. CODE 232455

TOLERANCES BEFORE GALVANISING


(UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50MM E 1MM MATERIAL: 70*70*8 ROLLED STEEL ANGLE
DIMENSIONS OVER 50MM. . . . . E 2MM MILD STEEL TO B.S. 4360 GRADE 43A
HOLE DIAMETERS UP TO AND INCL 10MM E 0.5MM AFTER FABRICATION HOT DIP GALVANISE
HOLE DIAMETERS OVER 10MM . . E . 1MM TO B.S. 729
AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE
0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
B NOTE AMENDED
19.5.80 MOUNTING BRACKET FOR
TREFOIL CABLE SUPPORT
A MATERIAL DESCRIPT.DRAWN BY YMP AUG 1977Scale N.T.S. Class-
28.1.80 ADDED CAD INPUT RKP JAN 1994
CHECKED BYAISE AUG 1977
APPROVED BY E242

Version: 2 July 2006 26 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E243 Insulator Bracket

270

50 170 50
= =

80
12

R12 (INTERNAL)
4 POSITIONS

20 20
1 HOLE 24 DIA

43
75

2 HOLES 22 DIA

COMM. CODE 233560


TOLERANCES BEFORE GALVANISING
(UNLESS OTHERWISE STATED) MATERIAL: 75x12 FLAT MILD STEEL
DIMENSIONS UP TO AND INCLUDING 50mm ±1mm MILD STEEL TO B.S. 4360 GRADE 43A
DIMENSIONS OVER 50mm ± 2mm AFTER FABRICATION HOT DIP GALVANISE
HOLE DIAMETERS UP TO AND INCL 10mm +0.5mm TO B.S. 729
HOLE DIAMETERS OVER 10mm +1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE BASED ON EATSI


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE
DRG. NO.439518
EAST MIDLANDS ELECTRICITY

B
TOLERANCES
D.H.
NOV 99
CORRECTED BRACKET-INSULATOR (H.V.)
A REDRAWN DRAWN BY Scale N.T.S. Class-
RKP CAD INPUT RKP JAN 1994
JAN 94 CHECKED BY
APPROVED BY
ADB
ADB
JULY 1991
JULY 1991
E 243

Version: 2 July 2006 27 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E244 H Pole U/G Brace 1.9m Centres

100
100
55
30

1470

1934
2085

91

30
55 12

COMM. CODE 235720 ALL HOLES DRILL 22 DIA


TOLERANCES BEFORE GALVANISING
(UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50mm ±1mm MATERIAL: 100 x 100 x 12 ROLLED STEEL ANGLE
DIMENSIONS OVER 50mm ± 2mm
MILD STEEL TO B.S. 4360 GRADE 43A
HOLE DIAMETERS UP TO AND INCL 10mm ±0.5mm
AFTER FABRICATION HOT DIP GALVANISE
HOLE DIAMETERS OVER 10mm ±1mm
TO B.S. 729
AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE
0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE
BASED UPON EATS DRG NO 439558
EAST MIDLANDS
ELECTRICITY
B TOLERANCES
D.H. CORRECTED BRACE, FOUNDATION
NOV 99
1934 CENTRE H POLES
A SIZE AND DRILLING MOD DRAWN BY Scale N.T.S. Class-
CAD INPUT RKP JAN 1994
CHECKED BY
APPROVED BY
ADB JUL 1991
ADB JUL 1991
E 244

Version: 2 July 2006 28 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E247A Surge Arrester Mounting Bracket / Cable Termination

17 DIA 17 DIA
17 DIA

50 mm
25 mm
40 mm
18 DIA

190 mm
18 DIA

22 DIA

14 DIA

15 mm
FRONT ELEVATION

Y
25 mm 150 mm 150 mm 25 mm

30 mm 30 mm
X

40 mm
40 mm
80 mm

25 mm
25 mm

50 g 50 g
m
m

10
m
X

m
8

0m
0
10

75
11
0

m
mm
m
75

m
m

50 mm 128 g
m

6 mm

139 g
Y
50 mm

PLAN VIEW

64 mm 6 mm

SECTION ON X-X
75 mm 6 mm

SECTION ON Y-Y
WELDS TO BE CONTIUOUS 4MM FILLET oR
CONT. BUTT. WELDS TO BE ON ALL 4 SIDES

WELD SLAG, FLUX ETC. TO BE REMOVED


BEFORE GALVANISING
COMM. CODE 232583-0
MATERIAL: 50*6 MILD STEEL FLAT
TOLERANCES BEFORE GALVANISING
MILD STEEL TO B.S. 4360
GRADE 43A (UNLESS OTHERWISE STATED)
AFTER FABRICATION HOT DIP GALVANISE E
DIMENSIONS UP TO AND INCLUDING 50MM 1MM
TO B.S. 729 DIMENSIONS OVER 50MM. . . . . E
2MM
HOLE DIAMETERS UP TO AND INCL 10MM
E 0.5MM
HOLE DIAMETERS OVER 10MM . . . E1MM

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

C
2-80 WELDED EDGES ADDED EAST MIDLANDS
ELECTRICITY
E B
Renumbered E247A MODS TO MATL DTLS
10-11-99 Surge arrester holes 28-1-80 SURGE ARRESTER MOUNTING BRACKET
changed from 14mm
to 17mm to accept / CABLE TERMINATION
33kV
D TITLE AMENDED A 18 DIA HOLES WERE
DRAWN BY CAH MAR 1975 Scale N.T.S. Class-
11-9-91 9-7-79 CAD INPUT RKP JAN 1994
19 DIAS
CHECKED BY
APPROVED BY PDB MAR 1975
LNB MAR 1975
E 247A

Version: 2 July 2006 29 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E248 H Pole U/G Brace 2.5m Centres

100 100
55
30

2000

2470
2630

ALL HOLES DRILL 22 DIA

COMM. CODE 235730

BASED UPON EATS DRG NO 439599

MATERIAL: 100 x 100 x 12 ROLLED STEEL ANGLE


MILD STEEL TO B.S. 4360 GRADE 43A
AFTER FABRICATION HOT DIP GALVANISE
TO B.S. 729

100 TOLERANCES BEFORE GALVANISING


(UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50mm ±1mm
30 DIMENSIONS OVER 50mm ± 2mm
55 12 HOLE DIAMETERS UP TO AND INCL 10mm +0.5mm
HOLE DIAMETERS OVER 10mm +1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
BRACE, FOUNDATION 2500
CENTRE H POLE
A TOLERANCES DRAWN BY Scale N.T.S. Class-
CORRECTED
D.H. CAD INPUT RKP JAN 1994
NOV 99 CHECKED BY
APPROVED BY
ADB
ADB
JUL 1991
JUL 1991 E 248

Version: 2 July 2006 30 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E249 Tie Rod

C B C

M20 THREAD

DIMENSIONS IN MILLIMETRES
COMMODITY
TYPE
DIA A B C D CODE

1 20 2100 1000 750 350 -

2 20 450 130 160 160 -

3 20 330 90 120 120 235785

COMM. CODE 2357850


TOLERANCES BEFORE GALVANISING
MATERIAL: STEEL TO BS4190, GRADE 4.6 (UNLESS OTHERWISE STATED)
NUTS TO BE GRADE 4
DIMENSIONS UP TO AND INCLUDING 50mm ±1mm
ROD AND NUTS TO BE SPUN GALVANISED TO DIMENSIONS OVER 50mm ± 2mm
BS727. AFTER GALANISING NUTS THREADS TO
BE CUT OVER SIZE AND COATED WITH CORROSION HOLE DIAMETERS UP TO AND INCL 10mm +0.5mm
INHIBITOR BEFORE ASSEMBLY. HOLE DIAMETERS OVER 10mm +1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE
BASED UPON EATS DRG NO 439608
EAST MIDLANDS
ELECTRICITY

TIE ROD
B DRAWN BY Scale N.T.S. Class-
D.H. TOLERANCES CAD INPUT RKP JAN 1994
NOV 99 CORRECTED CHECKED BY
APPROVED BY
ADB
ADB
JUL 1991
JUL 1991
E 249

Version: 2 July 2006 31 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E250 33kV Sealing End Mount WITHDRAWN

102
= = 733 51

51
25 254 102 152 175 25 30
30

9 HOLES 14 DIA 3 HOLES 12 DIA

102
TO THIS FLANGE ON CENTRE LINE 102*51*10.42KG/M RSC
51

251
200

10 HOLES 18 DIA

CHANNEL (2 OFF)
200

3 HOLES
18 DIA

304 75
587

76 152 76 38 2 HOLES DIA 18

76
100
DETAIL "A"

152

304
2 HOLES
1304

DIA 22

N
76
AW 152 50 10
1117

100

PLATES (2 OFF)

89
R

50
200

18 DIA
D
3910

= =

75
200

H
IT

56 50

18
6
21

18 DIA
1117

12
W

420
25

STRAPS (3 OFF)
1304

R9
DETAIL "A"

MATERIAL: STEEL TO BS4360 GRADE 43A

AFTER FABRICATION HOT DIP GALVANISE TO BS729


TO BE SUPPLIED AS BUNDLED SET OF 10 PIECES,
DETAIL "A" COMPLETE WITH SPUN GALVANISED BOLTS, NUTS,
FLAT & TAPER WASHERS FOR ASSEMBLY AS DRG
NO. A028
587

COMM. CODE 2352000


200

TOLERANCES BEFORE GALVANISING


(UNLESS OTHERWISE STATED)

DIMENSIONS UP TO AND INCLUDING 50mm ±1mm


200

DIMENSIONS OVER 50mm ± 2mm


251

HOLE DIAMETERS UP TO AND INCL 10mm ±0.5mm


51

HOLE DIAMETERS OVER 10mm ±1mm

CHANNEL (3 OFF) AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


102*51*10.42KG/M RSC 0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

C
CHANNEL DRILLINGS
& SIZE MOD EAST MIDLANDS ELECTRICITY
MAY 82 HEAD OFFICE
B
EXTRA CHANNEL SEALING END MOUNTING FOR 33KV
EXTRA HOLES FOR UNEARTHERED CONSTRUCTION
12-10-81 SURGE DIV
TERMINAL POLE
D A DRAWN BY YMP AUG 1977 Scale N.T.S. Class-
REFER TO DRG NO. 420 DIM WAS 710 CAD INPUT RKP JAN 1994
33/A4 NOW A028
JAN 92 FEB 80 CHECKED BY
APPROVED BY
ASIE
JL
AUG 1977
NOV 1977 E 250

Version: 2 July 2006 32 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E254 Universal ABSD Steelwork

50 845 120 535


6
30
51

645 620

2 SLOTS 18 2 HOLES SLOT 18 WIDE*75


SLOT 18 WIDE*75 WIDE*114 18 DIA
1600

10
102*51 RSC 2

4 HOLES 18 DIA
** *

51
30

50 500 250 750 50

* :-ISOLATOR CENTRE PHASE FIXING-POLE-


ITEM 1 TOP
** :-ISOLATOR CENTRE PHASE FIXING
UNDERSLUNG
2 HOLES DIA 18 75
2 HOLES
18 DIA 40 = =
ANGLE TO BE WELDED
CHANNEL ALONG ALL
TO 20
SEAMS
370

25 320 25
ASSEMBLY BOLTS
ESI STANDARD 43-
TO 27 31
50 M16 x 70 (2 OFF)
96 0 0

20
185 50*50*6 RSA

102*51 RSC HOOK STICK MECHANISM BASE &


3 HOLES
22 DIA (SUPPLIED WITH ISOLATOR BY
BOLTS
MANUFACTURER)
12
0
95
MATERIAL: STEEL TO BS4360 GRADE
0
43A
AFTER FABRICATION HOT DIP GALVANISE TO
2 HOLES BS729
18 DIA FASTENERS:
M16*35 BLACK BOLTS TO BS 4190
46 TO BS729. EACH BOLT TO BE FITTED
GALVANISED
1 BLACK NUT TO BS4190, GALVANISED TO
WITH
0
27 5 DEGREE D SHAPED TAPER
BS729
0 (TO ESI 439606) TO FIT INNER CHANNEL
WASHER
FLANGES
ASSEMBLY:
25 TO BE SUPPLIED AS BUNDLED SET FASTENED
70 ZINC PLATED
WITH
BANDING
COMM. CODE NO. 235167 2 OFF ITEM
40 1 2 OFF ITEM 2
4 FASTENERS
= =

TOLERANCES BEFORE
102 GALVANISING
(UNLESS OTHERWISE
STATED)
DIMENSIONS UP TO AND INCLUDING 50mm
±1mm
DIMENSIONS OVER 50mm ±
ITEM 2 CROSSARM 2mm
HOLE DIAMETERS UP TO AND INCL 10mm
+0 5mm
HOLE DIAMETERS OVER 10mm
+1mm
AFTER GALVANISING HOLES MUST PASS A PLUG
Based on ESI Drg. GAUGE
0.5mm SMALLER THAN NOMINAL DIAMETER OF
HOLE
F C
ASSEMBLY ITEM 1 SLOT
NOTE
ADDE ALTERED
* TO 2 EAST MIDLANDS
20-5- 25-5- 117*1
S O S NETWORK
H RSC E B
were100*5 COMM. CODE TOLERANCES
D.H. N S
23312 AND DIMS UNIVERSAL STEELWORK FOR AIR
0 ow as
OCT ESI 439527 Dec 28-4- APR O ISOLATOR SINGLE & H
99
G D A DRAWN Scale N.T.S. Class-
ITEM 1 2 SLOTS DRG NOTE ADDED CAD RKP JAN

E 254
117*1
WERE RE
O MANUAL
C G CENTRE
27-10- 8 6-6-78 AUG CHECKED FAD APR
FIXIN
S
82 G APPROVED PDB APR
BY

Version: 2 July 2006 33 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E257 33kV Surge Arrester Mount WITHDRAWN

113 330 2 HOLES


DIA 22
75 25 280 25

10

124
222

2 FIXING HOLES
DIA 18
86 158 86

ITEM "A" - OUTER PHASE

100 200

56 22 DIA

19
105
2 HOLES 18
DIA 222

10 21 79 79 21

ITEM "B" - CENTRE PHASE

MATERIAL:
10 THICK MS TO BS4360 GRADE 43A
AFTER FABRICATION GALVANISE TO BS729

ASSEMBLY:
TO BE SUPPLIED AS A SET COMPRISING:-
2 OFF ITEM "A"
1 OFF ITEM "B"
FASTEN WITH GALVANISED BANDING

COMM. CODE 235210 (SET)

TOLERANCES BEFORE GALVANISING


(UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50mm ±1mm
DIMENSIONS OVER 50mm ± 2mm
HOLE DIAMETERS UP TO AND INCL 10mm +0.5mm
HOLE DIAMETERS OVER 10mm +1mm

ITEM "A" ITEM "B" AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE
0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

C TOLERANCES
D.H. CORRECTED EAST MIDLANDS ELECTRICITY
NOV 99
NETWORK DEVELOPMENT
B
NOTES AMENDED
MOUNTING FOR 37KV BRACKET -
APR 78
TYPE SURGE DIVERTER (GEC X6894)
A DRAWN BY Scale N.T.S. Class-
DIMENSION CORRECTED CAD INPUT RKP JAN 1994
AUG 77 CHECKED BY
APPROVED BY
ASIE AUG 1977
JL NOV 1977 E 257

Version: 2 July 2006 34 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E258 Triggered Gap Mount WITHDRAWN

(INTERIM EDITION)

81 50

24 DIA
HOLE
25
40

6
100

125
250

14 DIA HOLE
FOR EARTHING
BRACKET

150

14 DIA HOLES FOR


112*12 COACH SCREWS
C.C. 235816
40

10
0
20
0

60

MATERIAL:
6mm THICK MS TO BS4360 GRADE 43A
AFTER FABRICATION GALVANISE TO BS729

COMM. CODE 232593-0

TOLERANCES BEFORE GALVANISING


(UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50mm ±1mm
DIMENSIONS OVER 50mm ± 2mm
HOLE DIAMETERS UP TO AND INCL 10mm +0.5mm
HOLE DIAMETERS OVER 10mm +1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

C
TOLERANCES
D.H. CORRECTED EAST MIDLANDS ELECTRICITY
NOV 99 NETWORK DEVELOPMENT
B
HOLE MADE 24 DIA SUPPORT BRACKET FOR TRIGGERED GAP
31-5-83 INSULATOR ASSEMBLY

A DRAWN BY MHM MAY 1978 Scale N.T.S. Class-


DIMENSIONS CAD INPUT RKP JAN 1994
18-12-80 METRICATED
CHECKED BY
APPROVED BY
GS MAY 1978
E 258

Version: 2 July 2006 35 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E260 Curved Square Washer

65

= =

=
65

=
22 DIA HOLE

35 FLAT
6

R 100

MATERIAL:
6 THICK MS TO BS4360 GRADE 43A
AFTER FABRICATION GALVANISE TO BS729

COMM. CODE 238800


AS EATSI DRAWING 439605
TOLERANCES BEFORE GALVANISING
(UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50mm ±1mm
DIMENSIONS OVER 50mm ± 2mm
HOLE DIAMETERS UP TO AND INCL 10mm +0.5mm
HOLE DIAMETERS OVER 10mm +1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

C
D.H.
TOLERANCES
CORRECTED
EAST MIDLANDS
NOV 99
ELECTRICITY
B
COMM. CODE WAS

28-4-80
238808 CURVED SQUARE WASHER
A DRAWN BY YMP AUG 1977 Scale N.T.S. Class-
REDRAWN CAD INPUT RKP JAN 1994

E 260
5-4-78 MILD STEEL
CHECKED BY ASIE AUG 1977
APPROVED BY JL NOV 1977

Version: 2 July 2006 36 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E261 Flat Square Washer

3 32 32

32

32

22 DIA HOLE

ITEM "A"
COMMODITY CODE 238885

3 25 25

25

25

18 DIA HOLE

ITEM "B"
COMMODITY CODE 238890
TOLERANCES BEFORE GALVANISING
MATERIAL: (UNLESS OTHERWISE STATED)
MATERIALS DIMENSIONS UP TO AND INCLUDING 50mm ±1mm
3 THICK MS TO BS4360 GRADE 43A
DIMENSIONS OVER 50mm ± 2mm
AFTER FABRICATION GALVANISE TO BS729
HOLE DIAMETERS UP TO AND INCL 10mm +0.5mm
HOLE DIAMETERS OVER 10mm +1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
B TOLERANCES
D.H. CORRECTED
NOV 99 SQUARE FLAT WASHERS
A DRAWN BY YMP AUG 1977 Scale N.T.S. Class-
ITEM "B" ADDED CAD INPUT RKP JAN 1994
SEP 87 CHECKED BY
APPROVED BY
ASIE AUG 1977
E 261

Version: 2 July 2006 37 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E262 ‘J’ Bolt

34 DIA

M16

LARGE FLAT WASHER


95 FORM F TO BS4320

125

155

RADIUS OF BEND TO BE AS SMALL


AS POSSIBLE MINIMUM 6MM

COMM. CODE: 232370


MATERIAL: TOLERANCES BEFORE GALVANISING
STEEL TO BS4190 GRADES 4.6 (BOLT), 4 (NUT) (UNLESS OTHERWISE STATED)
BOLT TO BE HOT BENT DIMENSIONS UP TO AND INCLUDING 50mm ±1mm
ALL COMPONENTS TO BE GALVANISED TO BS729 DIMENSIONS OVER 50mm ± 2mm
TO BE SUPPPLIED ASSSEMBLED WITH THREADS
HOLE DIAMETERS UP TO AND INCL 10mm +0.5mm
WELL OILED
HOLE DIAMETERS OVER 10mm +1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

F TOLERANCES C
D.H. CORRECTED
HOT BENDING
SPECIFIED
EAST MIDLANDS
NOV 99 18-2-83 ELECTRICITY
E B
LENGTHENED 140 TO ASSEMBLY NOTE

22-5-84
150
20-5-80
ADDED
"J" BOLT
D A DRAWN BY YMP AUG 1977 Scale N.T.S. Class-
DIMS ALTERED FOR MODS TO MATERIAL CAD INPUT RKP JAN 1994
ESI TRANS PLATFORM

E 262
26-1-80 DETAILS
20-5-83 CHECKED BY ASIE AUG 1977
APPROVED BY FAD DEC 1988

Version: 2 July 2006 38 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E263 Anti-Climbing Guards

40
10

6
50 12
10

10
140

390
140

2 HOLES 14 DIA FOR 12DIA*75 DETAIL OF SLOT


LONG COACH SCREWS
10
0
90MM

R115

390

SINGLE POLE
ARRANGEMENTS

H POLE

COMMODITY CODE: 234500


TOLERANCES BEFORE GALVANISING
MATERIAL: (UNLESS OTHERWISE STATED)
40 x 10 MILD STEEL FLAT TO BS4360 GRADE 43A
HOT DIP GALVANISED TO BS729 DIMENSIONS UP TO AND INCLUDING 50mm ±1mm
DIMENSIONS OVER 50mm ± 2mm
NOTE HOLE DIAMETERS UP TO AND INCL 10mm +0.5mm
1 BARBED WIRE 2 OR 3 PLY 12.5 SWG 4 POINT LONG
HOLE DIAMETERS OVER 10mm +1mm
BARBED BARBS AT 3 SPACING. GALVANISED TO BS443
2 TWO BRACKETS REQUIRED PER INSTALLATION AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE
0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
B TOLERANCES
CORRECTED
D.H.
NOV 99 ANTI-CLIMBING GUARDS
A DRAWN BY Scale N.T.S. Class-
NOTE 2 ADDED CAD INPUT RKP JAN 1994
20-5-80 CHECKED BY
APPROVED BY
ASIE AUG 1977
JL NOV 1977 E 263

Version: 2 July 2006 39 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E266 Tapered Curved Square Washer

65 6
= =

30°
=

65 22 DIA
=

R 100

COMM. CODE: 238895


TOLERANCES BEFORE GALVANISING
MATERIAL: (UNLESS OTHERWISE STATED)
MALLEABLE IRON DIMENSIONS UP TO AND INCLUDING 50mm ±1mm
GALVANISE TO BS729 DIMENSIONS OVER 50mm ± 2mm
HOLE DIAMETERS UP TO AND INCL 10mm +0.5mm
HOLE DIAMETERS OVER 10mm +1mm

AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE


0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
TAPERED CURVED
SQUARE WASHER
A TOLERANCES DRAWN BY GR APR 1983 Scale N.T.S. Class-
CORRECTED

E 266
D.H. CAD INPUT RKP JAN 1994
NOV 99 CHECKED BY GR JUN 1983
APPROVED BY HBH JUN 1983

Version: 2 July 2006 40 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E267 ‘J’ Bolt for Tower Anti-climbing Guard Gate

28 DIA
M12

65 LARGE FLAT WASHER


75 FORM F TO BS4320

100

RADIUS OF BEND TO BE AS SMALL


AS POSSIBLE MINIMUM 6mm

EXISTING UNUSED
HOLE IN FIXED ANGLE

GATE
HOLE AT PRESENT
USED FOR LOCK

COMM. CODE: 2504500


TOLERANCES BEFORE GALVANISING
(UNLESS OTHERWISE STATED)
DIMENSIONS UP TO AND INCLUDING 50mm ±1mm
MATERIAL: DIMENSIONS OVER 50mm ± 2mm
STEEL TO BS4190 GRADES 4.6 (BOLT), 4 (NUT)
HOLE DIAMETERS UP TO AND INCL 10mm +0.5mm
BOLT TO BE HOT BENT
ALL COMPONENTS TO BE GALVANISED TO BS729 HOLE DIAMETERS OVER 10mm +1mm
TO BE SUPPPLIED ASSSEMBLED WITH THREADS AFTER GALVANISING HOLES MUST PASS A PLUG GAUGE
WELL OILED
0.5MM SMALLER THAN NOMINAL DIAMETER OF HOLE

EAST MIDLANDS
ELECTRICITY
B TOLERANCES
D.H. CORRECTED "J" BOLT FOR LOCKING OF
NOV 99
ANTI-CLIMB GATES
A DRAWN BY YMP SEP 1983 Scale N.T.S. Class-
AEB DIMENSIONS ADDED CAD INPUT RKP JAN 1994
3-5-89 CHECKED BY
APPROVED BY
GRB SEP 1983
HBH NOV 1983
E 267

Version: 2 July 2006 41 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E268 Humped Back Split Pin

6.5

9.5
LA T
17.5 F
27

THIS SIDE OF HUMP


TO BE AS STEEP AS
31

POSSIBLE

2
A A
4

MAX 5.4
MIN 4.9

3.175
10° SECTION A-A
APPX.

WHEN CLOSED THIS DIMENSION MUST BE AS


STATED AND THE LEGS ADJACENT TO THE LOOP
MUST NOT BE OPEN MORE THAN 1mm

MATERIAL:
AUSTINITIC STAINLESS STEEL, EN58B, 321GRADE,
SPRING TEMPER CAPABLE OF MEETING THE
INTERCRYSTALLINE CORROSION TEST OF BS970
PART 4

EAST MIDLANDS
ELECTRICITY
4MM HUMP-BACK SPLIT PIN
DRAWN BY GR APR 1984 Scale N.T.S. Class-
CAD INPUT RKP JAN 1994
CHECKED BY
APPROVED BY
GR
HBH
APR 1984
MAY 1984
E268

Version: 2 July 2006 42 of 44


East Midlands Electricity Steelwork E200 - E299
Overhead Line Manual Vol.2

E269 ‘R’ Type Retaining Pin

ø 16

R3 R6.3

58
ø16
R6.3
30

R3
6

35°
2

MATERIAL:
AUSTINITIC STAINLESS STEEL, 4MM DIA
302 S 26 GRADE (EN58A) SPRING TEMPER CAPABLE
OF MEETING THE INTERCRYSTALLINE CORROSION
TEST OF BS 970

EAST MIDLANDS
ELECTRICITY
4MM "R" TYPE
RETAINING PIN
DRAWN BY Scale N.T.S. Class-
MATERIAL NOTE CAD INPUT RKP JAN 1994

E269
30-5-86
GR AMENDED CHECKED BY GR APR 1984
2-6-86 APPROVED BY HBH APRIL 1984

Version: 2 July 2006 43 of 44


Distribution Business

Section 2.3
Insulator & Fittings
E300 - E399

Database Ref: 67 File Ref: OHL Vol 2 Section 2-3 Manual Name: Overhead Line Manual
Insulator & Fittings E300 _ E399 Vol. 2
Jan 2002

Version Prepared by Approved by Issue Date


Jan 2002 Tony Haggis Tony Haggis Jan 2002
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

Revision Log For Insulators & Fittings E300 - E399


Changes made in version Jan 2002

Section Notes about the change


E361 Ball ended hook added

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 2 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

CONTENTS

E303 11kV pin insulator 4

E305 33kV line post insulator 5

E306 Disc insulator 6

E307 11kV triggered spark gap assembly 7

E308 Cranked Pilot Insulator pin 8

E310 11kV insulator pins, line and pilot 9

E311 Pilot insulator spindle, timber fixing 10

E312 Clevis ended socket adaptor 11

E313 11kV and 33kV tension insulator steelwork 12

E314 Eye bot and eye nut 13

E317 Socket tongue 14

E318 Stand off insulator 15

E319 11kV gap type surge arrester 16

E325 General arrangement showing stand off insulator and surge arrester mountings17

E326 Bolted Anchor Clamp 18

E327 Coach screw hook M14 19

E328 M16 hook bolt with keeper plate 20

E329 Heavy duty pig tail hook bolt and nut hook 21

E330 ABC face wall bracket 22

E331 ABC corner bracket 23

E332 ABC corner wall bracket 24

E333 ABC off set bracket 25

E334 Twisted weak link for ABC suspension fitting 26

E361 Ball Ended Hook 27

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 3 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E303 11kV pin insulator

SEMI-CONDUCTING
GLAZE
(WHEN SPECIFIED)
78 + 2

1.5
R 11

9.5
R 11

16

125 MIN

165 MAX

1 INSULATOR TO CONFORM WITH REQUIREMENTS OF BS137


2 FITTTED WITH THIMBLE COFORMING WITH THE REQUIREMENTS
OF BS 137 AND SUITABLE TO FIT THE LARGE STEEL HEAD (REF 16)
BS 137
3 THE FIRING DATE, MONTH AND YEAR, TO BE INDELIBLY MARKED
ON INSULATOR
4 PORCELAIN TO BE GLAZED BROWN OR GREY

COMMODITY CODE: 234813


EAST MIDLANDS
ELECTRICITY
B
GJ/DC
FIG 16 REMOVED
11 kV
JUNE 94
PIN INSULATOR
A DRAWN BY Scale N.T.S. Class-
COMMODITY CODE CAD INPUT DC JUNE 94
APR 80
AMENDED
NO. WAS 521301 CHECKED BY
APPROVED BY
ASIE
?
DEC 77
OCT 78 E303

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 4 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E305 33kV line post insulator

120 +/- 4

R16

24 11
5 mm
R16

178 MIN
430 MIN

OR AS SPECIFIED
50 mm

COMMODITY CODE:
234822 M22
NOTES
1 DIMENSIONS AND CHARACTERISTICS TO COMPLY WITH BS 137 1960 FOR A
NORMAL SYSTEM VOLTAGE (THREE PHASE) OF 33KV MINIMUM TRANSVERSE
FAILING LOAD TO BE 2400 LBS
2 TOLERANCE EXCEPT WHERE SPECIFIED ON DRAWING ARE TO COMPLY WITH
BS 137 1960
3 OVERALL DIMENSION OF PORCELAIN COMPONENT TO BE IN ACCORDANCE
WITH ESI DRAWING NO. 439303
4 PORCELAIN COMPONENT TO BE SOLID CONSTRUCTION
5 BASE CAP INTERNAL THREAD AND NUT THREAD
TO BE PROTECTED BY GREASE

EAST MIDLANDS
ELECTRICITY
B
11-11-85
NOTE 5 ADDED
33KV
LINE POST INSULATOR
A COMM. CODE DRAWN BY Scale N.T.S. Class-

28-4-80 NO. ADDED CAD INPUT RKP JAN 1994


CHECKED BY
APPROVED BY
ASIE DEC 1977
E305

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 5 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E306 Disc insulator

140

254

MATERIAL: BROWN OR GREY GLAZED PORCELAIN INSULATOR TO CONFORM WITH THE


REQUIREMENTS OF BS 137 AND EATS 43-93. MINIMUM FAILING LOAD 70KN
DESIGNATION OF PIN BALL AND SOCKET DIMENSION 16B OF B.S.3288

COMMODITY CODE: 2348300


C REDRAWN
D.H. GLASS INSULATOR EAST MIDLANDS
OCT 99 WITHDRAWN
ELECTRICITY
B
COMM. CODES
28-4-80
AMENDED NO.S WERE
521450 & 521600 DISC INSULATOR
A DRAWN BY YMP DEC 1977 Scale N.T.S. Class-
GLASS COMM. CAD INPUT RKP JAN 1994

E306
27-11-79
CODE ADDED ASIE DEC 1977
CHECKED BY
APPROVED BY

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 6 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E307 11kV triggered spark gap assembly

1/2" BSW INSERT


GALVANISED MILD STEEL

48
A

176
3mm

JUBILEE CLIPS

BROWN GLAZED PORCEL

A
48

7/8" BSW INSERT


GALVANISED MILD STEEL

ARCING HORN

SECTION A-A
25
25

COMMODITY CODE 234847


FOR SUPPORT STEELWORK SEE DRG. E

EAST MIDLANDS ELECTRICITY

11 kV TRIGGERED SPARK
GAP ASSEMBLY
DRAWN BY YMP AUG 80 Scale N.T.S. Class-
CAD INPUT DC JUNE 94
CHECKED BY
APPROVED BY
HBH NOV 80
EHA NOV 80 E307

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 7 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E308 Cranked Pilot Insulator pin

LARGE STEEL HEAD


REF NO. 16 TO BS3288

150
20 Dia 20 Dia
MIN R25

45.00°

400
M20

50

NOTES :
MATERIAL: MILD STEEL. HOT DIP GALVANISE TO BS729
MINIMUM FAIL LOAD: 0.7KN (APPROX 157LBS)
BASED ON BS3288 PART 2 REF NO. 54

COMM. CODE 2354240


EAST MIDLANDS
ELECTRICITY
CRANKED PILOT
INSULATOR PIN
DRAWN BY MHM MAR 1979 Scale N.T.S. Class-
CAD INPUT RKP JAN 1994
CHECKED BY
APPROVED BY
CR APR 1979
E308

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 8 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E310 11kV insulator pins, line and pilot

LARGE STEEL HEAD


(REF. 16 BS3288)

A
A
C

B
D
G

M22 F
X

M20 X

E
E
LINE PIN PILOT PIN
(ITEM B) (ITEM C&D)
MATERIAL: MILD STEEL. GALVANISE TO BS729
MINIMUM BS3288
ITEM COMM. CODE FAIL PART 2 A B C D E F G X
LOAD PIN REF NO.

B 235412 10KN 29 230 50 25 37 22 6 13 50


235413 10KN 31 305 63 27 40 22 6 16 50
C 235422 0.7KN 45 400 -
-
20 -
-
20 - - 50
235423 0.7KN 50 500 20 20 - - 50
D 235425 0.7KN 45 400 - 20 - 20 - - 150

F C
18-11-92 ITEM A DELETED 22-7-82
ITEM A COMM CODE EAST MIDLANDS
DELETED
ELECTRICITY
E
10-1-92
MATERIAL NOTE ADDED
B
10-10-80
MFL'S FOR ITEMS C & D
ADDED
11KV INSULATOR PINS
LINE AND PILOT
D A COMM. CODE DRAWN BY Scale N.T.S. Class-
ADDITIONAL PINS ADDED CAD INPUT RKP JAN 1994
E310
21-6-91 25-7-80 (235426) CANCELLED
CHECKED BY DWG NOV 1977
APPROVED BY JL NOV 1977

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 9 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E311 Pilot insulator spindle, timber fixing

LARGE STEEL HEAD


REF NO. 16 TO
BS3288 1977

ALTERNATIVE POSITION
OF FLATS

325 20 DIA

40
10 20

20
40
14 DIA HOLE
75 WELD ALL ROUND

FLATS TO SUIT M16


SPANNER (24 A/F)

100 20 DIA COACH SCREW

COMM. CODE: 235430

NOTES:
MATERIAL - MILD STEEL. HOT DIP GALVANISE
TO B.S. 729
MINIMUM FAILING LOAD - 0.70 kN (APPROX.157lbs)

*SPANNER FLATS CAN BE LOCATED ADJACENT


TOSCREW OR HEAD AT MANUFACTURERS CHOICE
EAST MIDLANDS
ELECTRICITY
B
NOTE "WELDED ALL
7-10-82 ROUND" WAS PILOT INSULATOR SPINDLE
"WELDED BOTH SIDES"
TIMBER FIXING
A REDRAWN WITH DRAWN BY MHM MAR 1979 Scale N.T.S. Class-
15-3-79 EARTHING FLAG CAD INPUT RKP JAN 1994
CHECKED BY
APPROVED BY
GR APR 1979
E311

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 10 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E312 Clevis ended socket adaptor

16B SOCKET

SECURITY

59
R5 CLIP

38
22.5
50 X 16mm
MS PIN 45
WITH WASHER HOLE STAINLESS STEEL
'R' CLIP (E269)
DIA 17.5
IN DIA 6.5 HOLE

COMMODITY CODE: 236100


BS 3288 (REF 15/84)
EAST MIDLANDS
ELECTRICITY
CLEVIS ENDED
SOCKET ADAPTER
A DRAWN BY AE SEPT 91 Scale N.T.S. Class-
REDRAWN

E312
ADB CAD INPUT DC JUNE 94
ITEMS A AND B REMOVED
SEPT 91 CHECKED BY
APPROVED BY

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 11 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E313 11kV and 33kV tension insulator steelwork

ø4 STAINLESS STEEL "R"


CLIP AS DRG E269
124 22.5
ø17.5 HOLE 16MM BALL
AND SHANK ø17.5
8
R1.6 MAX

45 mm
R5

18

38
8
50
16 mm

6
57 19 10
38
50*16 DIA PIN COMM. CODE 232860

ITEM A - BALL END CLEVIS BS3288 REF 15/25

3 mm
146 mm
16MM BALL
& SOCKET
19 mm 45 mm 19 mm 57 mm
34 mm

R22
16 mm

R11
6 mm

34 mm

MAX. 1.6 RAD ø17.5 HOLE

COMM. CODE 235100


ITEM B - BALL ENDED EYE LINK BS3288 REF 15/30

60*ø16 COTTER PIN

STAINLESS STEEL "R" CLIP


AS DRG. E269
ø17.5 HOLE
mm
-0
+3

ø35

R16
199.5

70 mm
9.5

ø16

COMM. CODE 236004


6 mm

ø6 HOLE

ITEM C- SHACKLE BS3288 REF 15/29

ALL TOLERANCES AS STATED IN BS 3288

C
29-4-85 BS REF NO. ADDED EAST MIDLANDS
ELECTRICITY
B
29-4-84
ITEM C "R" CLIP
REPLACES SPLIT PIN
11kV & 33kV TENSION
INSULATOR STEELWORK
D A DRAWN BY Scale N.T.S. Class-
ITEM A POSITION OF SHACKLE PIN WAS
11-11-88 5-3-79 CAD INPUT RKP JAN 1994
"R" CLIP CORRECTED

E 313
55*16 CHECKED BY ASIE JUL 1977
APPROVED BY FAD DEC 1976

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 12 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E314 Eye bot and eye nut

60 20 DIA
300

20
150
40 DIA M20

40 DIA 2 NUTS (OILED THREADS)


ITEM A EYE BOLT
COMM CODE: 232059

100

20
40

EYE ON BOLT AND NUT TO BE


TAPPED M20
60 IN LETTERS NOT LESS THAN 3MM
HIGH

40 DIA
20 DIA

ITEM B EYE NUT


COMM: CODE 235300
NOTE
MATERIAL: STEEL TO BS 4190 STRENGHT GRADE 4.6 TO MEET
THE REQUIREMENTS FOR MECHANICAL PROPERTIES
DETAILED IN BS 4190 TABLE 14 (BOLT) & 16 (NUT)
HOT DIP GALVANISE TO BS 729

EAST MIDLANDS
ELECTRICITY
B
ADDITION TO NOTE
20-5-80
EYE BOLT AND EYE NUT
A DRAWN BY Scale N.T.S. Class-
EYE NUT C.C. CHANGED
CAD INPUT RKP JAN 1994
7-12-78 CHECKED BY
APPROVED BY
AR
RKP
FEB 1994
FEB 1994 E314

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 13 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E317 Socket tongue

22.5 130
44 86

R17.5

16MM B SOCKET
45

R1.6 MAX 19 3
SLOT FOR
SECURITY CLIP
16

COMM. CODE 236171 0

TO BS3288 PART 2 REF 15/35

EAST MIDLANDS
ELECTRICITY
SOCKET TONGUE
A REDRAWN DRAWN BY Scale N.T.S. Class-
D.H. CAD INPUT RKP JAN 1994
NOV 99 CHECKED BY
APPROVED BY
DM
HBH
FEB 1983
FEB 1983 E317

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 14 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E318 Stand off insulator

STUD LENGTH
40 - 50mm

370 290

25

STUD LENGTH 40 - 50mm

M12

COMM. CODE 550230


EAST MIDLANDS
ELECTRICITY

STAND OFF INSULATOR


DRAWN BY PN JAN 89 Scale N.T.S. Class-
CAD INPUT DC JUNE 94
CHECKED BY PN FEB 89
APPROVED BYHBH NOV 89 E318

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 15 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E319 11kV gap type surge arrester

STEEL
TERMINAL
SCREW
31
TERMINAL
PALM

GLAZED
PORCELAIN
HOUSING
218

315

MOUNTING BRACKET

EARTH CONNECTION

C.C. 234320
EAST MIDLANDS
ELECTRICITY
11KV GAP-TYPE
SURGE ARRESTER
DRAWN BY PN JAN 1998 Scale N.T.S. Class-
CAD INPUT RKP JAN 1994
CHECKED BY
APPROVED BY
PN FEB 1989
HBH NOV 1989
E319

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 16 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E325 General arrangement showing stand off insulator and surge arrester mountings

MOUNTING BRACKET

N
E247

AW
R
D
E319
H
IT

SURGE ARRESTER
W

E318

STAND OFF INSULATOR

EAST MIDLANDS
ELECTRICITY
GENERAL ARRANGEMENT SHOWING
SURGE ARRESTER AND STAND OFF
INSULATOR MOUNTINGS
DRAWN BY MHM APR 89 Scale N.T.S. Class-
CAD INPUT DC JUNE 94
CHECKED BY PN JUN 89
APPROVED BY HBH NOV 1989 E325

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 17 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E326 Bolted Anchor Clamp

252 21 min

195

D C A B
NOTE:
CONDUCTOR RANGE DIA 13 TO DIA 20
RECOMMENDED 'U' BOLT TORQUE 60 Nm (45 Ib/ft)
GALVANISING TO BS729
COMMODITY CODE :
APPROX WEIGHT 1.9 KG 2325960
TIGHTENING SEQUENCE:
A-B-C-D 4 BOLT FITTING
100 / 150 ACSR

190 19 min

190

A B C

NOTE:
CONDUCTOR RANGE DIA 7 TO DIA 14
RECOMMENDED 'U' BOLT TORQUE 60 Nm (45 Ib/ft) COMMODITY CODE :
GALVANISING TO BS 729
APPROX WEIGHT 1.2 KG
2325950
TIGHTENING SEQUENCE
B-C-A
3 BOLT FITTING
40 / 50 ACSR

EAST MIDLANDS
ELECTRICITY
B
D.H.
REDRAWN
BOLTED ANCHOR
D.H.
CLAMPS
A BOLT DRAWN BY MHM SEPT 1990 Scale N.T.S. Class-
P.B. TIGHTNING CAD INPUT DC FEB 1994
SEQUENCE
22-1-97
ADDED
CHECKED BY
APPROVED BY
ADB OCT 1990
E 326

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 18 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E327 Coach screw hook M14

20
D

40

80

85 MIN

D=14

NOTE: FABRICATION DIMENSIONS ARE


NOMINAL AND SHALL BE WITHIN 5%

COMMODITY CODE: 2347150


EAST MIDLANDS
ELECTRICITY
COACH SCREW HOOK
(14MM DIA)
A REDRAWN DRAWN BY MHM SEP 1990 Scale N.T.S. Class-

E327
D.H. CAD INPUT RKP JAN 1994
NOV 99 CHECKED BY ADB OCT 1990
APPROVED BY HBH OCT 1990

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 19 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E328 M16 hook bolt with keeper plate

R12 KEEPER PLATE


28 31

57 16

30
2.5
R20
20 2 HOLES
DIA 17
3

150
335
16
FLAT WASHER

25 25 1 HOLE
DIA 18

50
100

MI6 NUT TO BS 4190


13 MM NOMINAL THICKNESS

CC No. 290841
NOTES
1. ALL COMPONENTS HOT DIP GAVANISED TO BS729
2. FLAT WASHER TO BE LOOSE FIT.
3. KEEPER TO BE HAND FIT.
4. ALL COMPONENTS TO BE SUPPLIED ASSEMBLED.
5. ULTIMATE FAIL LOAD 29 kN.

EAST MIDLANDS
ELECTRICITY
B DRG. NO. WAS
MHM EMEB LV 221 M16 HOOK BOLT
SEPT 90
WITH KEEPER PLATE
A DRAWN BY SFB FEB 84 Scale N.T.S. Class-
DRG. NO. WAS
SS CAD INPUT DC FEB 94

E 328
E/C&M/100/2469
OCT 85 AND CC NO. ADDED CHECKED BY SFB MAR 84
APPROVED BY

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 20 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E329 Heavy duty pig tail hook bolt and nut hook

0
2
0
2
D D

40 40

80 76

D
2D
3 MIN D

150 D=16 OR 20
NUT TO BS4190

NOTE:
1 FABRICATION DIMENSIONS ARE
NOMINAL AND SHALL BE
WITHIN ±5%
2 DIMENSION "L" IS THE PREFERED
LENGTH IN ACCORDANCE WITH
EATS 43 96
COMMODITY CODE: 234708
EAST MIDLANDS
ELECTRICITY
HEAVY DUTY PIG TAIL HOOK
BOLT AND NUT HOOK
A REDRAWN DRAWN BY MHM SEP 1990 Scale N.T.S. Class-
ADB
D.H. CAD INPUT RKP JAN 1994
NOV 99 CHECKED BY
APPROVED BY
ADB OCT 1990
HBH OCT 1990 E329

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 21 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E330 ABC face wall bracket

90
50 10
WELD

R20
40 DIA 10
200 MS ROD
30

6
170
30 30

460
6 mm

170

MATERIAL:
40 X 6 MM STRIP HOT DIP
30

GALVANISED TO BS 729

CC NO. 2902030
C
D.H.
REDRAWN
EAST MIDLANDS
NOV 99 ELECTRICITY
B
MHM
DRG. NO. WAS
EMEB LV 220 A.B.C.
SEPT 90
FACE WALL BRACKET
A DRAWN BY MHM DEC 84 Scale N.T.S. Class-
CAD INPUT

E 330
SS DC FEB 94
OCT 85 CC NO. ADDED CHECKED BY SS DEC 84
APPROVED BY HBH DEC 84

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 22 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E331 ABC corner bracket

40
10

50
30
230 170 mm
135°

m
m
5
6

17
170 FILLET WELD

230
30

4 HOLES DIA 14 mm WELD


40

R20
DIA 10 mm
MATERIAL: MS ROD
40 X 6MM MS STRIP HOT DIP
GALVANISED TO BS 729
CC NO. 2902020
C REDRAWN
D.H. EAST MIDLANDS
NOV 99
ELECTRICITY
B
MHM
DRG. NO. WAS
EMEB LV 219 A.B.C.
SEPT 90
CORNER BRACKET
A DRAWN BY MHM DEC 84 Scale N.T.S. Class-
SS CAD INPUT DC FEB 94
OCT 85 CC NO. ADDED CHECKED BY
APPROVED BY
SS
HBH
DEC 84
DEC 84 E 331

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 23 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E332 ABC corner wall bracket

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 24 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E333 ABC off set bracket

35
17

HOLES :
SEE NOTE.
70

530

2 HOLES
230 DIA 14
30

6
40
MATERIAL:
40 X 6 MM STRIP HOT DIP
GALVANISED TO BS 729

CC NO. 290200
C
MHM
DRG. NO WAS
EMEB LV 217
EAST MIDLANDS
SEPT 90 ELECTRICITY
B DIA 7 H0LE ADDED
A.B.C.
MAY 87
OFFSET BRACKET
A DRAWN BY MHM DEC 84 Scale N.T.S. Class-
CAD INPUT

E 333
SS DC FEB 94
OCT 85 CC NO. ADDED CHECKED BY SS DEC 84
APPROVED BY HBH DEC 84

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 25 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E334 Twisted weak link for ABC suspension fitting

20

55

10
20

NOMINAL FAILING LOAD : 7.5 kN. MATERIAL:


HOT DIPPED GALVANISED
STEEL TO BS729

CC NO.2903600
EAST MIDLANDS
ELECTRICITY
TWISTED WEAK LINK FOR
ABC SUSPENSION FITTING
A REDRAWN DRAWN BY MHM SEPT 90 Scale N.T.S. Class-
CAD INPUT DC FEB 94

E 334
D.H.
NOV 99 CHECKED BY ADB OCT 90
APPROVED BY HBH

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 26 of 27 Version Jan 2002:
East Midlands Electricity Insulator & Fittings E300 - E399
Overhead Line Manual Vol.2

E361 Ball Ended Hook

45mm 50mm 32mm

27mm

R14 37mm
mm

102mm

16mm ball
and shank
BS 3288 : Part 2 : Reference No. 15/81

COMMODITY CODE 2351200

EAST MIDLANDS ELECTRICITY

BALL-ENDED HOOK
A DRAWN BY DH 15/06/99 Scale N.T.S. Class-

E361
BS Ref added
D.H. CAD INPUT
SEP 99 CHECKED BY
APPROVED BY

File Ref: OHL Vol 2 Section 2-3 Insulator


& Fittings E300 – E399 Jan 2002
Page 27 of 27 Version Jan 2002:
Distribution Business

Section 2.4
STAYING MATERIALS
E400 – E499

Database Ref: 68 File Ref: OHL Vol 2 section 2-4 Manual Name: Overhead Line Manual
Staying Materials E400 _ E499 Vol.2
JAN 2002

Version Prepared by Approved by Issue Date


2 Tony Haggis Tony Haggis JAN 2002
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

Revision Log For Staying Materials E400 - E499


Changes made in version 1

Section Notes about the change

Changes made in version 2 Jan 2002

Section Notes about the change


2 Drawings E413, E413A, E415 & E416 added – Screw-in
anchors

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 2 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

CONTENTS

E401 Stay rods 4

E402 Concrete Stay Block 5

E403 Porcelain stay insulators 6

E406 Preformed helical fittings for stays 7

E407 Stay outrigger bracket 8

E408 Stay strap and thimble (maximum working tention 28kN 9

E410 Tie rod for strut pole 10

E412 Manual screw-in stay anchor 11

E413 Anchor Rod 3m for Screw-in Stay 12

E413A Anchor Rod 2m for Screw-in Stay 13

E415 Single blade screw-in stay anchor 14

E416 Twin blade screw-in stay anchor 15

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 3 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E401 Stay rods

HEXAGON HEAD OF
TUBE AND LOCKNUTS
j
MUST BE THE SAME THIMBLE TO ESI 43 91
COMPONENT REF 439109

RIGHT
HAND e e: EYE Diameter
THREAD
LEFT
HAND
THREAD b

300
15
40
a

230
SIZE AND SUITABLE FOR
SPANNERS FOR M18 OR
7/8'' BSW THREAD
(27 OR 32 AF) ACCORDING
h

TO ROD DIAMETER.

b
400
END OF ROD
FORGED SQUARE
TO FIT SQUARE
HOLE IN PLATE.

g g: NOMINAL BORE
d
10

c
40 mm

HOLE
f DIA 10
RIGHT HAND THREAD
100

0
2

100

MATERIAL AND FINISH


STEEL TO BS 4360, GRADE 43A. HOT DIP
GALVANISED IN ACCORDANCE WITH BS729
SCREW THREADS
TO BE HAND FREE OVER LENGTH OF THREAD.

STAY ROD MIN FAILING COMMODITY a b c d e f g h j


LOAD (kN) CODE NO.

TYPE 1 18 X 1800 65.0 235717 230 18 35 15 25 20 20 1800 20


TYPE 2 22 X 2400 110.0 235718 230 22 40 20 30 25 25 2400 20

RODS GENERALLY CONFORM TO EATS 43 - 91

D C
TYPE 2 ROD THREADS
AMENDED TO 7/8'' BSW
MIN FAILING
LOADS AMENDED EAST MIDLANDS
(AS SUPPLIED)
AUG 97 SEPT 91
ELECTRICITY
B ESI STANDARD WAS

STAY RODS
ISSUE 1

SEPT 88

A DRAWN BY Scale N.T.S. Class-


THIMBLE DETAILS ALTERED
CAD INPUT DC FEB 94
JAN 79 CHECKED BY
APPROVED BY
GS
HAD
NOV 78
NOV 78 E 401

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 4 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E402 Concrete Stay Block

6
50 40
460

160 460
30

110

MINIMUM FAILING LOAD : 65 kN

REINFORCEMENT 6 mm MS BARS

CC NO. 2315000

EAST MIDLANDS
ELECTRICITY
B 20mm square hole
D.H. to 30mm square
05/01/98 CONCRETE STAY BLOCK
A DRAWN BY MHM JAN 78 Scale N.T.S. Class-
TITLE AMENDED
CAD INPUT DC FEB 94
SEPT 91 CHECKED BY
APPROVED BY
GS
FAD
OCT 78
OCT 78 E 402

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 5 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E403 Porcelain stay insulators

TYPE 1 : STAY INSULATOR.


FOR L.V. AND 11 kV LINES AND EARTHED 33 kV STRUCTURES.

115 - 145 mm APPROX.

75 - 80 mm
APPROX.
DIAMETER OF HOLES 20 mm APPROX.

MATERIAL : GLAZED PORCELAIN.


MIN. FAILING LOAD : 110kN
C.C. NO. : 2348420

TYPE 2 : STAY INSULATORS AND INSULATOR LINK ASSEMBLY


FOR UNEARTHED 33 kV STRUCTURES.

533 mm APPROX

DIAMETER OF HOLES
20 mm APPROX.
APPROX.
120 mm

220 mm APPROX.
LINK ASSEMBLY

LINK ASSEMBLY :
MATERIAL : GLAZED PORCELAIN. C.C. NO. : 2355410
MIN. FAILING LOAD : 110kN
C.C. NO. : 2348430

F REDRAWN C VARIOUS MODS


D.H. EAST MIDLANDS
OCT 99 MAR 85 ELECTRICITY
E
D.H.
CATALOGUE NUMBERS
REMOVED
B COMMODITY CODES
CHANGED
PORCELAIN
NOV 97 JULY 80 STAY INSULATORS
D CHANGES TO TYPE 1 A DRAWN BY MM NOV 76 Scale N.T.S. Class-
L.V. INS. DELETED
INSULATOR L.V. / 11 kV INS CAD INPUT DC FEB 94
FEB 89 MAY 80 SUBSTITUTED CHECKED BY
APPROVED BY
GS
PDB
NOV 76
FEB 77
E 403

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 6 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E406 Preformed helical fittings for stays

1. POLE TOP MAKE OFF

LEGS OF FITTING ASSEMBLE TO


FORM STAY STRAND EQUIVALENT

2. STAY GRIP (DEAD END)

LEGS OF FITTING WRTAP AROUND STAY STRAND

3. STAY SPLICE

JOINS TWO LENGTHS OF STAY STRAND TOGETHER


OR STAY STRAND TO POLE TOP MAKE OFF

7/3.25 STAY STRAND

COMMODITY
ITEM NAME CODE

1 POLE TOP MAKE OFF 2355720


2 STAY GRIP (DEAD END) 2355110
3 STSAY SPLICE 2355810

7/4.00 STAY STRAND

COMMODITY
ITEM NAME CODE

1 POLE TOP MAKE OFF 2355710


2 STAY GRIP (DEAD END) 2355120
3 STSAY SPLICE 2355820

E REDRAWN
D.H. POLE TOP STAY GRIP
(DEAD END) DELETED
EAST MIDLANDS
OCT 99 ELECTRICITY
D

CATALOGUE NOS
PREFORMED HELICAL
DELETED
FITTINGS FOR STAYS
DRAWN BY RKP APRIL'85
C Scale N.T.S. Class-
NEW DRG.
CAD INPUT

E 406
YMP PREPPARED
APRIL'85 CHECKED BY GRB APRIL'85
APPROVED BY HBH MAY 85

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 7 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E407 Stay outrigger bracket

610

20
R 10
25

418
20
100

20 40

10
20

DIA 20
R 90
20
HOLES
DIA 12 50

MATERIAL : STEEL TO BS 4360 GRADE 43A


HOT DIP GALVANISED TO BS729 AFTER FABRICATION

CC NO. : 2325900
C CLAW RADIUSED
EAST MIDLANDS
JAN 89
ELECTRICITY
B APPLICATION NOTE ADDED
STAY
MAR 85
OUTRIGGER BRACKET
D A DRAWN BY YMP JAN 78 Scale N.T.S. Class-
REDRAWN 12 DIA HOLES WERE 11
D.H. CAD INPUT DC FEB 94
NOV 99 JAN 80 CHECKED BY
APPROVED BY
GS
FAC
OCT 78
OCT 78 E 407

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 8 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E408 Stay strap and thimble (maximum working tention 28kN

60

30 15

30

53
22
45

R 16

60 25

SMOOTH RADIUS

30

STAY STRAP

37 20
STRAPHEAD MUST BE FITTED
UNDER HEAD OF BOLT AND
A SQUARE CURVED WASHER SQUARE
FITTED UNDER NUT. CURVED R 18
25

WASHER
90

R 55
M20 BOLT

THIMBLE
ASSEMBLY SKETCH FOR 7 / 3 25 mm WIDE
(STAY STRAP SUPPLIED MATERIAL :
WITH THIMBLE CLOSED ON) STRAP AND THIMBLE - MILD STEEL
BS 4360 GRADE 43 A
GALVANISED TO BS 729.

COMMODITY CODE : 2366670


C
D.H.
REDRAWN EAST MIDLANDS
NOV 99 ELECTRICITY
B
B STAY STRAND
DELETED
STAY STRAP
JUN 97
AND THIMBLE
A DRAWN BY MHM APR 77 Scale N.T.S. Class-
DIM CHANGES
CAD INPUT DC MAR 94

E 408
STRAP : 30 WAS 38
MAR 85 THIMBLE : 55 WAS 53 CHECKED BY GS JAN 78
APPROVED BY FAC OCT 78

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 9 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E410 Tie rod for strut pole

GENERAL ARRANGEMENT

E260.
URVED WASHERS

MIN 4.2M
E 266. ABOVE GROUND.
STRUT TAPERED
POLE CURVED
WASHERS
LINE
POLE
TIE ROD
AS EATS DRG 439608.
M20 THREAD

5 750 350
2100

MATERIAL : ROD : STEEL TO BS 4190 STRENGTH GRADE 4 / 6


NUTS : STEEL TO BS 4190 GRADE 4.
FINISH : HOT DIP GALVANISED TO BS 729.
ASSEMBLY : 4 FULL NUTS THREADED TO EACH ROD WITH THREADS WELL OILED.

CC NO. 2357800
EAST MIDLANDS
ELECTRICITY
TIE ROD FOR
STRUT POLE
A REDAWN DRAWN BY GR APR 83 Scale N.T.S. Class-
CAD INPUT

E 410
D.H. DC FEB 94
NOV 99 CHECKED BY GR JUN 83
APPROVED BY HBH JUN 83

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 10 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E412 Manual screw-in stay anchor

THIMBLE TO ESI
DRG. NO. 439109 TYPE 1

EYE NUT IN ACCORDANCE WITH


ESI STANDARD 43 - 96 OR
ALTERNATIVE FORGED EYE AS IN 760 mm
ESI DRG. NO. 439101

NOM. BORE 10 SWG.


75

LOCK NUT

M16

NOM. BORE 8 SWG

1600
DIA 16

25 SQUARE
1700

WELD
75

WELD
70

75

CUTTING EDGE
100

75 x 5 STEEL STRIP
REINFORCEMENT WELDED
OVER TUBE END
SWAGED SQUARE.
DIA 16
27

DISC DIA 150, 5 THICK


WELDED TO STAT ROD.
SOCKET WRENCH
STAY ANCHOR TO ESI 43 - 91
CC NO. 2310500 CC NO. 5880000
EAST MIDLANDS
ELECTRICITY

MANUAL SCREW IN STAY ANCHOR


AND SOCKET WRENCH
A REDRAWN DRAWN BY MHM SEPT 90 Scale N.T.S. Class-
CAD INPUT

E 412
D.H. DC MAR 94
NOV 99 CHECKED BY ADB OCT 90
APPROVED BY HBH OCT 90

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 11 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E413 Anchor Rod 3m for Screw-in Stay

3200

10 MM LOCKNUT SUPPLIED LOOSE


BOTH ENDS THREADED 22mm
(LOOSE FIT)

40 240
0 22 MM
TOLERANCE +1 -0 MM

10 MM LOCKNUT
WELDED AT BASE
OF THREAD WITH
10 MM MIN. RUN
AT 180°

NOTES:

1. MAY BE MADE FROM STOCK BAR 22mm

2. COMPONENT WILL BE SUBJECTED


TO PROOF LOADING OF 15 T AXIALLY

3. THREADS TO BE CUT NOT ROLL FORMED

4. FINISH HOT DIP GALVANISED

COMMODITY CODE: 231055 MATL. MILD STEEL BS 970 080A15

MOD A
THREADS NOW 22MM LENGTH INCREASED
DEC 93
GHJ
TO 3.2 M
EAST MIDLANDS ELECTRICITY

MOD B TOLERANCE ON ROD


FEB 94
GHJ
DIAMETER CHANGED.
CUT THREAD NOT
Anchor Rod 3m
ROLLED
for Screw-in Stay
MOD C COMMODITY CODE ADDED DRAWN BY GHJ Sept. 93 Scale N.T.S. Class-
WELD RUN SPECIFIED
AUG 97 BS CHANGED FROM TRACED BY

E413
4360 43A TO
DH BS 970 080A15 CHECKED BY
APPROVED BY GHJ Sept. 93

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 12 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E413A Anchor Rod 2m for Screw-in Stay

2140

10 MM LOCKNUT SUPPLIED LOOSE


BOTH ENDS THREADED 22MM
(LOOSE FIT)

40 240
0 22 MM
NOM.

10 MM LOCKNUT
WELDED AT BASE
OF THREAD

NOTES:

1. MAY BE MADE FROM STOCK BAR 22mm

2. COMPONENT WILL BE SUBJECTED


TO PROOF LOADING OF 15 T AXIALLY

3. THREADS TO BE CUT NOT ROLL FORMED

4. FINISH HOT DIP GALVANISED

COMMODITY CODE: 231054 MATL. MILD STEEL BS 970 080A15

MOD A LENGTH INCREASED


DEC 93 TO 2140

GHJ EAST MIDLANDS ELECTRICITY


MOD B
MAY 94
THREADS NOW CUT
Anchor Rod 2m
GHJ
for Screw-in Stay
MOD C THREADS NOW 22MM DRAWN BY GHJ AUGUST 93 Scale N.T.S. Class-
JUL 97 TRACED BY
DH CHECKED BY
APPROVED BY GHJ AUGUST 93 E413A

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 13 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E415 Single blade screw-in stay anchor

COUNTERBORE 25 DIA. x 5 DEEP

A TAPPED 22mm LOOSE FIT

270.0

45.0 SQUARE

35.0
125.0

R40.0 R40.0
75.0 PITCH
325.0

270.0
R20.0

R90.0
125.0

R40.0 R40.0

VIEW ON ARROW A

NOTES:

1. CENTRAL ROD MADE FROM


45 MM SQUARE BAR

2. BLADE MADE FROM


10 mm THICK PLATE

3. DISCS MUST BE WELDED


TO BODY BOTH SIDES

4. BLACK PAINT FINISH

MATERIALS.
DISCS - MILD STEEL BS 970 080A15
BODY - MILD STEEL BS 970 080A15

COMMODITY CODE 231053

EAST MIDLANDS ELECTRICITY


B
DH
OCT 97
COMMODITY CODE NO
ADDED Single blade screw-in
A DRAWN BY
stay anchor
GHJ MAY 94 Scale N.T.S. Class-
RENUMBERED TO E415
DH WAS E404 -HAS ALREADY
TRACED BY

E415
BEEN USED
AUG 97 CHECKED BY
APPROVED BY GHJ MAY 94

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 14 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

E416 Twin blade screw-in stay anchor

COUNTERBORE 25 DIA. x 5 DEEP

TAPPED 22mm LOOSE FIT


A

270.0

35.0
45.0 SQUARE

R40.0 R40.0

270.0
R20.0

R90.0

R40.0 R40.0

VIEW ON ARROW A
675.0
950.0

NOTES:

1. CENTRAL ROD MADE FROM


75.0 PITCH

45 MM SQUARE BAR

2. BLADE MADE FROM


10 mm THICK PLATE

3. DISCS MUST BE WELDED


125.0

TO BODY BOTH SIDES

4. BLACK PAINT FINISH

MATERIALS.
DISCS - MILD STEEL BS 970 080A15
COMMODITY CODE 231052
BODY - MILD STEEL BS 970 080A15

MOD.D Body size increased MOD. A Galvanised finish omitted.


to 40 mm but now
GHJ mild steel. Point GHJ Internal thread depth
reduced to 30 mm
EAST MIDLANDS
April 94 removed. Sept 93
ELECTRICITY
MOD.E Body size now MOD. B BODY MATERIAL NOW
GHJ
May 94
45 mm
GHJ
DEC 93
HIGH TENSILE STEEL
TO RESIST TORQUE
LOADS
Twin blade screw-in
MOD.G MOD.F NUMBER NOW E416 MOD. C DIMS. CHANGED DRAWN BY
stay anchor
GHJ AUGUST 93 Scale N.T.S. Class-
COMMODITY CODE
DH NO. ADDED (WAS E405 WHICH POINT ADDED TRACED BY
DH GHJ
OCT 97 AUG 97
ALREADY EXISTS)
APL 94 CHECKED BY
APPROVED BY GHJ AUGUST 93
E416

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 15 of 16 Version: 2
East Midlands Electricity Staying Materials E400 - E499
Overhead Line Manual Vol.2

This Page Is Intentionally Blank

File Ref: OHL Vol 2 Section 2-4


Staying Materials E400-E499 Jan 2002
Page 16 of 16 Version: 2
Distribution Business

Section 2.5

INFORMATION PLATES

E500 – E599

Database Ref: 69 File Ref: 2-5 FEB 2001.doc Manual Name: Overhead Line Manual
Vol. 2

Version Prepared by Approved by Issue Date


1 Tony Haggis See Database 02/2001
East Midlands Electricity Information Plates E500 - E599
Overhead Line Manual Vol.2

Revision Log For Information Plates E500 - E599


Changes made in version 1

Section Notes about the change

File Ref: 2-5 Feb 2001.doc Page 2 of 10 Version: 1


East Midlands Electricity Information Plates E500 - E599
Overhead Line Manual Vol.2

CONTENTS

E501 Label for use on wood poles on PME systems 4

E503 Pole number plate 5

E504 Identification plates for 33kV circuits 6

E505 Operational earth plate 7

E507 Concrete post and plate details for railway JIB safety clearance notice 8

E508 Statutory safety sign for overhead line poles 9

E509 Property label and statutory safety sign for poles carry HV equipment 10

File Ref: 2-5 Feb 2001.doc Page 3 of 10 Version: 1


East Midlands Electricity Information Plates E500 - E599
Overhead Line Manual Vol.2

E501 Label for use on wood poles on PME systems

75
66

4 X 4mm DIA.
FIXING HOLES P.M.E.
SYSTEM 41 50
DO NOT DISCONNECT NEUTRAL

MATERIAL : ALUMINIUM PLASTIC COATED


1.22 mm THICK

BLACK LETTERS ON WHITE BACKGROUND

COMMODITY CODE NO. : 513856

EAST MIDLANDS
ELECTRICITY
LABEL FOR USE ON WOOD
POLES ON PME SYSTEMS.
A DRAWN BY YMP SEPT 77 Scale N.T.S. Class-
REDRAWN.
DH DIMENSION BETWEEN HOLES CAD INPUT DC MAR 94
Aug 99 CORRECTED TO 41 FROM 31 CHECKED BY
APPROVED BY
ASIE DEC 77
OCT 78 E 501

File Ref: 2-5 Feb 2001.doc Page 4 of 10 Version: 1


East Midlands Electricity Information Plates E500 - E599
Overhead Line Manual Vol.2

E503 Pole number plate

EMBOSSED NUMBER
AS SPECIFIED

19 6 38

MATERIALS :
WHITE PLASTIC WITH EMBOSSED NUMERAL
COLOURED BLACK.
FIXING :
25 x 2 mm HOT DIP GALVANISED ROUND
HEAD NAILS. (CC NO. 515202.8)

COMMODITY CODE : 5149500 - 5149580

EAST MIDLANDS
ELECTRICITY
B REDRAWN
D.H.
NOV 99
POLE NUMBER PLATE
A DRAWN BY CLT OCT 77 Scale N.T.S. Class-
NOW ROUND
CLT AND PLASTIC CAD INPUT DC FEB 94
AUG 83 CHECKED BY
APPROVED BY
ASIE
HBH
DEC 77
OCT 78 E 503

File Ref: 2-5 Feb 2001.doc Page 5 of 10 Version: 1


East Midlands Electricity Information Plates E500 - E599
Overhead Line Manual Vol.2

E504 Identification plates for 33kV circuits

14 14
AREA AREA
COLOUR COLOUR
6

5
69

99

28
SIZE 2

28
SIZE 1

MATERIAL :

ALUMINIUM PLASTIC COATED


BLACK LETTERS 30 mm HIGH ON YELLOW BASE
SUITABLE FOR BENDING TO POLE CIRCUMFERENCE ON SITE.

COMMODITY CODE : 5135470

EAST MIDLANDS
ELECTRICITY
IDENTIFICATION PLATES
FOR 33 kV CIRCUITS
A REDRAWN DRAWN BY YMP AUG 77 Scale N.T.S. Class-
D.H. CAD INPUT DC FEB 94
NOV 99 CHECKED BY
APPROVED BY
ASIE DEC 77
OCT 78 E 504

File Ref: 2-5 Feb 2001.doc Page 6 of 10 Version: 1


East Midlands Electricity Information Plates E500 - E599
Overhead Line Manual Vol.2

E505 Operational earth plate

MATERIAL :
ALUMINIUM - PLASTIC COATED 1.22 GUAGE
100 mm DIAMETER
WITH 18 mm FIXING HOLE.
BLACK ON WHITE BACKGROUND.

COMMODITY CODE : 5138330


EAST MIDLANDS
ELECTRICITY
OPERATIONAL
EARTH PLATE
A DRAWN BY YMP NOV 77 Scale N.T.S. Class-
REDRAWN
D.H. CAD INPUT DC MAR 94
NOV 99 CHECKED BY
APPROVED BY
ASIE DEC 77
OCT 78 E 505

File Ref: 2-5 Feb 2001.doc Page 7 of 10 Version: 1


East Midlands Electricity Information Plates E500 - E599
Overhead Line Manual Vol.2

E507 Concrete post and plate details for railway JIB safety clearance notice

187 75 187

95 DANGER
30 OVERHEAD ELECTRIC LINE
20 15

CRANES
JIB HEIGHT FROM RAIL LEVEL 300
150 NOT TO EXCEED:- 6.5 M 18

18
EMERGENCY 20

15 TELEPHONE 20
12
55 0800 ????????

450
150
N

6.5 M
b e IO

75
Separate Plate with
Ye to y S
k/ ed a VI

actual clearance for


ac g s m E

each loaction
Bl an ur R

150
ch olo ER

w
C ND

llo
U

15 Holes
1350

Ground Level

600

EAST MIDLANDS
ELECTRICITY

Railway Jib Safety Clearance Notice


DRAWN BY TH Jan 2001 Scale N.T.S.
CAD INPUT
CHECKED BY
APPROVED BY E 507

File Ref: 2-5 Feb 2001.doc Page 8 of 10 Version: 1


East Midlands Electricity Information Plates E500 - E599
Overhead Line Manual Vol.2

E508 Statutory safety sign for overhead line poles

CORNER
200 RAD 4mm

4 FIXING HOLES
DIA 5mm

290

DANGER OF DEATH
ELECTRICITY
LIVE WIRES

18
KEEP AWAY
STATUTORY SAFETY SIGN
SYMBOL AND TEXT (BLACK) 18
BACKGROUND (YELLOW)

SIZE 290 X 200mm


MATERIAL - MATERIAL TO BE IMPACT RESISTANT
PLASTIC 1.5mm THICKNESS AND MUST
BE CREOSOTE RESISTANT.
FINISH TO BE SMOOTH FACE WITH
INSCRIPTION INTERLAMINATED INTO
PLASTIC SURFACE.
LABEL TO BE CURVED ACROSS MINOR
L AXIS TO 150mm RADIUS.

COLOURS -BLACK ON A YELLOW BACKGROUND


BLACK - REF 9103 OF BS381C
YELLOW - REF 309 OF BS 381C

0.06 x L

DANGER OF DEATH
0.12 x L (MAX)
0.87 x L
COMMODITY CODE
513640.0
C
MINOR AXIS
JULY 97 RADIUS INCREASED
TO 150mm
EAST MIDLANDS
MAR
ELECTRICITY
B REDRAWN

SEPT 90
STATUTORY SAFETY SIGN
FOR OVERHEAD LINE POLES
DRAWN BY Scale N.T.S. Class-
CAD INPUT DC JUNE 94
CHECKED BY
APPROVED BY
EAC
RAK
SEPT 90
SEPT 90
E 508

File Ref: 2-5 Feb 2001.doc Page 9 of 10 Version: 1


East Midlands Electricity Information Plates E500 - E599
Overhead Line Manual Vol.2

E509 Property label and statutory safety sign for poles carry HV equipment

200 CORNER RAD 4mm

4 FIXING HOLES
DIA 5mm

290
STATUTORY SAFETY SIGN
380 SYMBOL AND TEXT (BLACK)
DANGER OF DEATH BACKGROUND (YELLOW)
ELECTRICITY
LIVE WIRES
KEEP AWAY

IN EMERGENCY PROPERTY LABEL


Phone 0800 626555 TEXT (BLACK)
90

BACKGROUND (WHITE)
EAST MIDLANDS

18
ELECTRICITY

18
SIZE 290 X 200mm
MATERIAL - MATERIAL TO BE IMPACT RESISTANT
PLASTIC 1.5mm THICKNESS AND MUST
BE CREOSOTE RESISTANT.
FINISH TO BE SMOOTH FACE WITH
INSCRIPTION INTERLAMINATED INTO
PLASTIC SURFACE.
LABEL TO BE CURVED ACROSS MINOR
L AXIS TO 150mm RADIUS.

COLOURS -BLACK ON A YELLOW BACKGROUND


BLACK - REF 9103 OF BS381C
YELLOW - REF 309 OF BS 381C

0.06 x L

DANGER OF DEATH
COMMODITY CODE
0.87 x L 0.12 x L (MAX) 513643.0
EAST MIDLANDS
ELECTRICITY
B REDRAWN
PROPERTY LABEL AND STATUTORY
SAFETY SIGN FOR OVERHEAD LINE
SEPT 90
POLES CARRYING HV EQUIPMENT
DRAWN BY Scale N.T.S. Class-
CAD INPUT DC JUNE 94
CHECKED BY
APPROVED BY
EAC
RAK
SEPT 90
SEPT 90 E 509

File Ref: 2-5 Feb 2001.doc Page 10 of 10 Version: 1


Distribution Business

Section 2.6

EARTHING

E600 – E699

Database Ref: 70 File Ref: OHL Vol 2 Section 2-6 Manual Name: Overhead Line Manual
Earthing E600 _ E699 Jan 2002 Vol.2

Version Prepared by Approved by Issue Date


2 Tony Haggis Tony Haggis Jan 2002
East Midlands Electricity Earthing E600 - E699
Overhead Line Manual Vol.2

Revision Log For Earthing E600 - E699


Changes made in version 1

Section Notes about the change

Changes made in version 2 Jan 2002

Section Notes about the change


E615 Drawing /Photo of clamp added

File Ref: OHL Vol 2 Section 2-6


Earthing E600 – E699 Jan 2002
Page 2 of 9 Version: 2
East Midlands Electricity Earthing E600 - E699
Overhead Line Manual Vol.2

CONTENTS

E610 Crossarm bonding strap for 33kV double circuit lines 4

E611 Driving stud 5

E612 Coupling for copperbond rods 6

E613 Copperbond Earth Rod 7

E614 Non-extensible earth rod 8

E615 Steel Block Earth Clamp 9

File Ref: OHL Vol 2 Section 2-6


Earthing E600 – E699 Jan 2002
Page 3 of 9 Version: 2
East Midlands Electricity Earthing E600 - E699
Overhead Line Manual Vol.2

E610 Crossarm bonding strap for 33kV double circuit lines

40
50

1220

2540

3 HOLES
DIA 14
1220

40 x 8 ALUMINIUM
COMMERCIALLY PURE
HARDNESS AS MANUFACTURED 50
(ALCAN GB 2 SN)

COMMODITY CODE : 2366040


EAST MIDLANDS
ELECTRICITY
CROSSARM BONDING STRAP
FOR 33 kV DOUBLE CIRCUIT LINES
DRAWN BY GR OCT 80 Scale N.T.S. Class-
CAD INPUT DC MAR 94
CHECKED BY
APPROVED BY
MBK
EHA
OCT 80
OCT 80 E 610

File Ref: OHL Vol 2 Section 2-6


Earthing E600 – E699 Jan 2002
Page 4 of 9 Version: 2
East Midlands Electricity Earthing E600 - E699
Overhead Line Manual Vol.2

E611 Driving stud

D d

H L

D d H L ROD DIA
22 5/8" 16 38 5/8"

MATERIAL : HIGH TENSILE STEEL

FINISH : BLACK ADIZE

EAST MIDLANDS
ELECTRICITY

DRIVING STUD
DRAWN BY Scale N.T.S. Class-
CAD INPUT DC MAR 94
CHECKED BY
APPROVED BY
ES DEC 92
E 611

File Ref: OHL Vol 2 Section 2-6


Earthing E600 – E699 Jan 2002
Page 5 of 9 Version: 2
East Midlands Electricity Earthing E600 - E699
Overhead Line Manual Vol.2

E612 Coupling for copperbond rods

D L

D d UNC L

20.6 5/8" 70

MATERIAL : ALUM BRONZE BS 2871


GRADE CA 102

FINISH : SELF COLOUR.

EAST MIDLANDS
ELECTRICITY
COUPLING FOR
COPPERBOND RODS
DRAWN BY Scale N.T.S. Class-
CAD INPUT DC MAR 94
CHECKED BY
APPROVED BY
ES DEC 92
E 612

File Ref: OHL Vol 2 Section 2-6


Earthing E600 – E699 Jan 2002
Page 6 of 9 Version: 2
East Midlands Electricity Earthing E600 - E699
Overhead Line Manual Vol.2

E613 Copperbond Earth Rod

14.2

MINIMUM COPPER
THICKNESS 0.25 mm

L
THREAD THREAD
DIA (d) LENGTH (l)
1220 5/8" 32 MATERIAL : HIGH TENSILE STEEL
650 - 770 N/mm^2
99.9% PURE COPPER
FINISH : SELF COLOUR.

EAST MIDLANDS
ELECTRICITY

COPPERBOND EARTH ROD


DRAWN BY Scale N.T.S. Class-
CAD INPUT DC FEB 94
CHECKED BY
APPROVED BY
ES DEC 92
E 613

File Ref: OHL Vol 2 Section 2-6


Earthing E600 – E699 Jan 2002
Page 7 of 9 Version: 2
East Midlands Electricity Earthing E600 - E699
Overhead Line Manual Vol.2

E614 Non-extensible earth rod

14.2 +/-0.1
°
60 4

1524 +/- 5
0.3 +/- 0.05

45
°
3

MATERIAL : CARBON STEEL


60.77 kG / mm^2
COPPER 99.9% PURITY
FINISH : SELF COLOUR

EAST MIDLANDS
ELECTRICITY
NON EXTENSIBLE
EARTH ROD
DRAWN BY Scale N.T.S. Class-
CAD INPUT DC MAR 94
CHECKED BY
APPROVED BY
ES DEC 92 E 614

File Ref: OHL Vol 2 Section 2-6


Earthing E600 – E699 Jan 2002
Page 8 of 9 Version: 2
East Midlands Electricity Earthing E600 - E699
Overhead Line Manual Vol.2

E615 Steel Block Earth Clamp OHJ 144

Commodity Code 512 261

MATERIAL : STAINLESS STEEL

EAST MIDLANDS
ELECTRICITY

Steel Block Earth Clamp


DRAWN BY TH JAN 2002 Scale N.T.S. Class-
CAD INPUT TH JAN 2002

CHECKED BY
APPROVED BY
TH JAN 2002

JAN 2002
E 615
TH

File Ref: OHL Vol 2 Section 2-6


Earthing E600 – E699 Jan 2002
Page 9 of 9 Version: 2
Distribution Business

Section 2.7

Cable Saddles, Cleats, Guards

E700 - E799

Database Ref: 71 File Ref: Jan 2002 Manual Name: Overhead Line Manual
Vol.2

Version Prepared by Approved by Issue Date


2 Tony Haggis Tony Haggis Jan 2002
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

Revision Log For Cable Saddles, Cleats & Guards E700 - E799

Changes made in version 2 Jan 2002

Section Notes about the change


E704 Withdrawn - cleats for under-eaves wiring
E 714 Cleats for 33kV & 11kV XPLE cable added

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 2 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

CONTENTS

E701 Small Single Way Sadles 4

E702 Sadles for Pole Mounting 5

E703 Single Way Snap On Large Saddles 6

E706 PVC Cable Saddle 7

E707 Service Lead In Tube 8

E708 Cable Guards for 33kV 11kV& LV Cables. 9

E709 Pole Earth Wire Cover 10

E710 90° PVC Lead In Tube for Services 11

E712 Plastic Cable Cleat for A.B.C. 12

E713 Cable Tie Cradle 13

E714 Cable Cleats for 33kV & 11kV Cables 14

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 3 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

E701 Small Single Way Sadles

CABLE APPLICATION (mm²)


ELLIS PATENTS COMMODITY INTERNAL FIXING
PART NUMBER CODE DIAMETER HOLE
HYBRID COPPER Cu split PVC / PVC BLACK PVC (mm) (mm)
CONCENTRIC 1 CORE* Cu 1 CORE
CONCENTRIC CONCENTRIC
10 - 34 232697 4 16 8.6 3
10 - 46 232700 16 35 11.7 4
10 - 53 232703 25 70 13.5 4
10 - 56 232706 35 25 16 50 14.2 4
10 - 65 232709 70 16.5 4
10 - 72 232710 35 95 18.2 4
EP2W -53FR 232737 2 x 25/35 25 70 13.5 4
TWIN CLEAT

MATERIAL : GREY FLAME RETARDANT POLYPROPYLENE.


* ALUMINIUM OR COPPER.

C REVISED AND REDRAWN


EAST MIDLANDS ELECTRICITY
JUN 88 HEAD OFFICE

SMALL SINGLE WAY SADDLES

D TWIN CLEAT ADDED DRAWN BY GRB MAY 88 Scale N.T.S. Class-


CAD INPUT

E 701
D C MAR 94
SEPT 90 CHECKED BY GRB JUN 88
APPROVED BY HBH JUN 88

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 4 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

E702 Sadles for Pole Mounting

LARGE SINGLE WAY SADDLE.

MATERIAL : BLACK POLYPROPYLENE GP GRADE.

CABLE APPLICATION (mm²) INTERNAL FIXING


ELLIS PATENTS COMMODITY HOLE
PART NUMBER DIAMETER
CODE (mm) (mm)
LV WAVEFORM 11 kV PIAS

35 - 22 232765 95 49.2 8
35 - 34 232767 300 185 61.6 11
35 - 42 232769 300 72.5 11

THREE WAY SADDLE.

MATERIAL : BLACK POLYPROPYLENE GP GRADE.

CABLE APPLICATION (mm²) INTERNAL FIXING


ELLIS PATENTS COMMODITY PVC / PVC COPPER HOLE
PART NUMBER DIAMETER
CODE (PT LV TAILS) (mm) (mm)

3 W P 10 232672 70 16.5 6.35


3 W P 20 232674 120 21.7 6.35

EAST MIDLANDS ELECTRICITY


HEAD OFFICE
B
REVISED INCORPORATES
OLD DRG. E706 SADDLES FOR POLE
JUN 88
MOUNTINGS
DRAWN BY GRB MAY 88 Scale N.T.S. Class-
CAD INPUT DC

E 702
MAR 94
CHECKED BY GRB JUN 88
APPROVED BY HBH JUN 88

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 5 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

E703 Single Way Snap On Large Saddles

MATERIAL : GREY FLAME RETARDANT


POLYPROPYLENE

ELLIS PATENTS COMMODITY CABLE APPLICATION (mm²) INTERNAL


PART NUMBER CODE DIAMETER
3 CORE
LV WAVEFORM 11 kV PIAS (mm)

90 - 6 232741 25 27.5
90 - 7 232742 35 31.7
90 - 8 232743 34.0
90 - 9 232744 70 38.1
90 - 11 232746 42.6
90 - 12 232747 120 44.4
90 - 13 232748 95 48.7
90 - 14 232749 185 53.9
90 - 15 232750 300 185 60.5

C
REVISED AND EAST MIDLANDS ELECTRICITY
REDRAWN
JUN 88

SINGLE WAY SNAP ON


LARGE SADDLES
DRAWN BY GRB MAY 88 Scale N.T.S. Class-
CAD INPUT DC MAR 94
CHECKED BY
APPROVED BY
GRB JUN 88
HBH JUN 88 E 703

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 6 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

E706 PVC Cable Saddle

CLEARANCE / HOLE FOR


10 COACHSCREW
OR 3.17 NAIL

50
154

d
3.17

d COMMODITY
CODE

50 232765

61 232767

73 232769

SUPPLIER : B & H (LEICS)

C
d - DIMENSIONS
AMENDED EAST MIDLANDS ELECTRICITY
JAN 84

B
COMM. CODE 549460
JULY 80
CANCELLED PVC CABLE SADDLE
D COACHSCREW A COMM. CODES DRAWN BY YMP NOV 77 Scale N.T.S. Class-
D.H. DIA WAS 9.52 AMENDED. CAD INPUT DC FEB 94

E 706
NO.S WERE
NOV 99 APRIL 80 CHECKED BY ASIE DEC 77
549454.6-8
APPROVED BY OCT 78

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 7 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

E707 Service Lead In Tube

R75
305

MINIMUM INTERNAL DIAMETER :


34 ON STRAGHT
30 ON BEND

MATERIAL :
HIGH IMPACT PVC COLOUR BLACK

38 o/d
COMMODITY CODE : 551602 - 0

EAST MIDLANDS ELECTRICITY

SERVICE LEAD IN TUBE


DRAWN BY Scale N.T.S. Class-
CAD INPUT DC

E 707
MAR 94
CHECKED BY ASIE DEC 77
APPROVED BY OCT 78

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 8 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

E708 Cable Guards for 33kV 11kV& LV Cables.

100
12 MIN
FLAT

6
700

10 HOLES
DIA 6

WOOD
3000 ± 25

POLE
R 115

12 MIN A
FLAT
700

33kV 11kV LV
CABLE CABLE CABLE
UP TO
50 ITEM B
120mm² 234602-0
UP TO 95mm² 185mm² ITEM C
400mm² 300mm² 300mm² 100 234604-0

MATERIAL : HIGH IMPACT PVC (COLOUR BLACK)


3.0 + 0.25mm THICK
ALL DIMENSIONS IN mm.

F STEEL GUARD FOR C RETRACED WITH


DH 33kV CABLE MINOR MODS. EAST MIDLANDS ELECTRICITY
NOV 99 REMOVED PVC OCT 82
GUARD ADDED
E LIFTING HOLE B
DEC 98 REMOVED -NOW DIMENSIONS CABLE GUARDS FOR 33kV ,
MODIFIED
DH AT ONE END ONLY JAN 81 11 kV & LV CABLES.
D DIA 18 LIFTING A DRAWN BY Scale N.T.S. Class-
AUG 98 HOLES ADDED ITEMS A, B & C CAD INPUT DC MAR 94
DH JULY 80
ADDED
CHECKED BY
APPROVED BY
MR
DH
DEC 98
DEC 98
E 708

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 9 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

E709 Pole Earth Wire Cover

100
700

DIA
18

55
700
3000

10 HOLES
DIA 3.5
700

MATERIAL :
700

2.0 mm HIGH IMPACT PVC


COLOUR BLACK

COMMODITY CODE : 2329850


100

EAST MIDLANDS ELECTRICITY

B COVER PROFILE
CLT
JAN 82
MODIFIED
POLE EARTH WIRE COVER
A DRAWN BY Scale N.T.S. Class-
DIMENSIONS MODIFIED CAD INPUT DC

E 709
SS MAR 94
JAN 81 CHECKED BY ASIE DEC 77
APPROVED BY PDB OCT 78

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 10 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

E710 90° PVC Lead In Tube for Services

40

90°
R 90
40

28* * MINIMUM INTERNAL ON BEND

32
36

MATERIAL :

HIGH IMPACT RIGID PVC


(COLOUR BLACK)
THICKNESS : 2mm

COMMODITY CODE : 5340840

EAST MIDLANDS ELECTRICITY

90° PVC LEAD IN TUBE


FOR SERVICES
A DRAWN BY MHM NOV 82 Scale N.T.S. Class-
NO. WAS E204 CAD INPUT DC

E 710
MAR 94
JULY 83 CHECKED BY DAS DEC 82
APPROVED BY HBH DEC 82

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 11 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

E712 Plastic Cable Cleat for A.B.C.

10 mm STAND OFF COMMODITY CODE 290290 (ELLIS PATENT)


50 mm STAND OFF COMMODITY CODE 290289 (ELLIS PATENT)
100 mm STAND OFF COMMODITY CODE 290291 (ELLIS PATENT)

RANGE : 2 CORE 25 mm²


4 CORE 95 mm² ABC

EAST MIDLANDS ELECTRICITY

PLASTIC CABLE CLEAT


FOR A.B.C.
DRAWN BY MHM SEPT 90 Scale N.T.S. Class-
CAD INPUT DC MAR 94
CHECKED BY
APPROVED BY
ADB
HBH
OCT 90
OCT 90 E 712

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 12 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

E713 Cable Tie Cradle

12.5 12.5

9.5

R 24

HOLE DIA 4.8


17.0

25.4

CC NO. 2327050

EAST MIDLANDS ELECTRICITY

CABLE TIE CRADLE


DRAWN BY MHM NOV 92 Scale N.T.S. Class-

E 713
CAD INPUT DC MAR 94
CHECKED BY TJP DEC 92
APPROVED BY TJP DEC 92

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 13 of 14 Version: 2
East Midlands Electricity Cable Saddles, Cleats & Guards E700 - E799
Overhead Line Manual Vol.2

E714 Cable Cleats for 33kV & 11kV Cables

Cable Commodity Code


70 & 150 mm2 triplex 11kV XPLE cable 5332100

185 & 300 mm2 triplex 11kV XLPE cable 5332110

150 & 400 mm2 triplex 33kV XLPE cable 5332120

400 mm2 single 33kV XLPE cable 5332130

EAST MIDLANDS ELECTRICITY

Cleats for 33kV & 11kV


XLPE Cables
DRAWN BY TH Jan 2002 Scale N.T.S. Class-
CAD INPUT Jan 2002

E 714
TH
CHECKED BY TH Jan 2002
APPROVED BY TH Jan 2002

File Ref: OHL Vol 2 Section 2-7 Cable Saddles,


Cleats, Guards E700_E799 Jan 2002
Page 14 of 14 Version: 2
APPENDIX 1 SUPERSEDED 'E' DRAWINGS.

DRG TITLE

El02 FABRICATION DETAILS OF POLES FOR 1lkV LIGHT


CONSTRUCTION.

El03 FABRICATION DETAILS FOR SINGLE INTERMEDIATE POLE


33kV & 1lkV HEAVY CONSTRUCTION.

El04 FABRICATION DETAILS FOR SINGLE ANGLE POLE 33kV &


1lkV HEAVY CONSTRUCTION.

El05 FABRICATION DETAILS 33kV AND 1lkV UNEARTHED


CONSTRUCTION TERMINAL, 'H' POLES.

El08 FABRICATION DETAILS FOR 11H SECTION POLE WITH


ISOLATOR.

El09 FABRICATION DETAILS OF UNI-POLE FOR 11L & LV


CONSTRUCTION.

E201 SERVICES - WALL BRACKETS.

E202 SERVICES - CORNER WALL BRACKETS.

E203 HOUSE SERVICE BRACKET (CONCENTRIC).

E206 LV D-IRON ASSEMBLY COMPLETE.

E207 LV SHACKLE STRAP.

E210 llL, 3 PHASE, CROSSARM INTERMEDIATE & TIESTRAP.

E211 llL, 3 PHASE, CROSSARMS SECTION ANGLE & TERMINAL.


E212 1lkV 3 PHASE, CROSSARM 2.5m INTERMEDIATE.

E215 LINE CROSSARM 33kV & 1lkV HEAVY CONSTRUCTION.


(SINGLE INTERMEDIATE POLE).
E216 1lkV AND 33kV CROSSARM 'H' POLE TERMINAL.
E217 LINE CROSSARM AND LINE DEVIATIONS OVER 30' 33kV &
1lkV HEAVY CONSTRUCTION. ('H' ANGLE SECTION).

E225 11H AND 33s CROSSARM TIE STRAP.

E227 EXTENSION BRACKETS FOR 11L INTERMEDIATE CROSSARM.

E232 FUSE MOUNTING CROSSARM AND SUPPORT STRUT FOR


TRANSFORMER POLE.

OHL MANUAL - VOLUME 2


APPENDICES - PRINTED 10/12/92
DRG TITLE

E236 LIGHT CONSTRUCTION RENOVATION CROSSARM STRUTS FOR


HV OVERHEAD LINES

E245 POLE BOX BRACKET FOR SINGLE POLE MOUNTING.

E251 SHEAR PIN AND CARRIER FOR FAILURE CONTAINMENT


DEVICE

E252 FLATS FOR FAILURE CONTAINMENT DEVICE

E255 SURGE DIVERTER MOUNTINGS FOR 1lkV OVERHEAD LINES.

E264 SUPPORT BRACKET PILOT INSULATOR.

E301 BOBBIN INSULATOR FOR LV O/H LINES.

E302 COACHSCREW SERVICE INSULATOR.

E315 TWO DISC SPACER FOR TENSION INSULATOR.

E316 LONG INSULATOR HOOK FOR 11L REFURBISHING.

E320 33kV POST INSULATOR STIRRUP.


E321 1lkV PIN INSULATOR STIRRUPS FOR ALUMINIUM
CONDUCTORS.

E322 STIRRUP FOR ANGLE POSITIONS FOR SCA OR SILMALEC


CONDUCTORS.
E323 33kV POST INSULATOR STIRRUP (FOR TAYLOR
TUNNICLIFFE INSULATORS).
E324 1lkV PIN INSULATOR STIRRUP FOR COPPER CONDUCTORS.

E335 TERMINATING STRAP AND INSULATOR HOOK.

OHL HANUAL - VOLUME 2


APPENDICES - PRINTED 10/12/92
,” 7
/

I -.- -. .:t
SCARFING TO BE CUTTO
I GIVE A 50 FACE AND THE
END CHAMFERED OFF
BEYOND THE LENGTH SHOWN

POLE SCARFED ON ONE


SIDE ONLY.

&---. -- f
DRILLINGS 22DIA.

.-. J
\

GOUGE
MARK
-r-

r-
-- -.

BOLT HOLE 22OlA AN0 SCARFI NC


:q FOR BLOCK WHERE REQUIRED.
SCARFING TO BE CUT TO GIVE A
100 FACE (THIS DRILLING AND
I_.!- L-J SCARFING TO BE PROVIDED WHEN
SPECIFIED 1

POLE SIZE AND INSPECTORS MARK


IMPRESSED ON POLE BUTT

A Redrawn
5 12 85 snowlngrcvls em HEAD OFFICE
marklngs to ,
ES1 43-88
FABRICATION DETAILS OF POLES
I
FOR 1lkV LIGHT CONSTRUCTION
iir

OUGE
IARK

ALL DRILLINGS 22mm OIA

SCA?FIYG TC GIVE
A 75mm FACE

/ t 1 25m ON PC-ES C,‘JEi( 12m


POLE SIZE 6 INSPECTOdS HARK
IMPRESSED ON POLE BUTT
,
I I \ AIS 12 85 1
I/ HEAD OFFICE
I POLE
MARKINGS
1 REVISED
1 FABRICAT!CN ~ETLI?S -33 Slr\;GLE SCALE
8 I I t
tbiTERME3N;TE pp1-L- c 2 3 K ?’ 3 ’ : K ‘J DRG No

I HEAVY :SNSTR!JCTIC:. E. 103


OI.LID IU I, LID 9lOirE
DETAILS OF POLE
MARKINGS ARE

r SHOWN ON DRG. El01

ALL DRILLINGS 22mm’ DIP

;:

r -- -

7
N

4i
011
II
I
.--2-I

POLE
---
SIZE 6 lNSPECTOd5
-“_tmi
--.I ::
MARK ‘II 125m ON POLES OVER 1Zm
IMPRESSED ON BUTT

ANGLE SECTION POLES 33KV 8 1!KV


HEAVY CONSTRUCTION
SCARFED AT RIGHT ANGLES
TO DRILLING TO LEAVE 190mm.
OF TIMBER SYMMETRICAL ON
POLE CENTRE LINE

NOTES :-
ALL HCLES TO BE !JRIiLED
22mm 0 IA UNLESS OTHERWISE
STATED AN0 DRILLED AT
RIGHT ANGLES TO VERTICAL
CENTRE LINE CF POLE.

-_
--I---
SCARFED TO GIVE
A 75mm FACE

-t
“1
izI
POLE SIZE a INSPECTOR’S
- - MARK

JI.w* IV
I I A 5 12 8E
HE&C OFFICE TR.CEO I” EL’ 22 :: --
MINOK
Moor
I I SCALE -
FABRICATION 3ETAICS C;? ‘:H
I I I DRG NO.
SECTION PCLE WlTh ISGLATZ,R
E.108
01.LIO
IU.I LVD 91Obi
SCARFING TC BE CUT TO GIVE
A 50 FACE 8 THE END CHAMFERED
OUT
POLE SCAfiFED GN ONE SIDE ONLY

GRILLINGS 22mm DIAMETER

SPECIES COOE COUNTRY OF ORIGIN

Corslcon ptnc ICF Unltcd Kingdom (GB

Larch. Europcon U Sweden SE

Larch. Joponcse

Norwoy spruce NS

Redwood or Scats pm SP

Sltko spruce ss

Western red cedar WC

GOUGE
UPRK--.
I-

11M LENGTH 6 CLASS

GOUGE MARK

SP FI SPECIES & COUNTRY OF ORIGIN


(See Toblc Above 1
--- 86 YEAR OF PRESERVATION

\- CG SUPPLIER

TYPICAL MARKINGS

__.--_-- .--
l-----

\ ;~C$gF~WKX~l;~ ;$m;;:;C:EE ,

L IF REPLIRE~,
-- .-
TyP’C4L MARKINGS ON BUTT LENGTH OF POLEm! CIt.‘ENS,ON A’ ,
-s--p-. -- ..-----i
a SL- LENGTH 6 CLASS OF POLE B 5-10 5 : c
--. -------*
11 - 1L 1 3
3 - MONTH OF IMPREGNATION. MARCH --_-
EC OR ,J : INSPECTORS MARK 3’/ER 1; 1 6
; -_--_- .- -. J
OlMENSlUNS IN MILLIMETRES
I A POLE MARKINGS
HEAD OFFICE
3 12. ec REVISED TC
t ”
ES1 L3-88
H
FABRICATION DETAILS OF UNI-
POLE FOR llL& L.LI CONSTRUCTION
2 HOLE

18 BORE SOLID
DRAWN PIPE
TO BS 980
CDS-2
MIN. WALL
THICKNESS 3 I
2 BOLT FIXING ITEM “A”
COMM CODE 232500

300 ,

25 55 70
Q 70 55
.
I

/ I
HOLES 14 DIA / / I
I
I 1, 7 I
I I I /

18 BORE SOL I
DRAWN PIPE
TO 0s 980
CDS-2
MIN WALL
THICKNESS 3

WALL BRACKETS
2-l& DIA

18 BORE SOLID
DRAWN PIPE
TO BS 900 CDS 2
MIN WALL THICKNESS 3

CORNER WALL (STRAIGHT)


COMM CODE 232520

FILLET

MATERIAL

MILD STEEL TO BS L360


GRADE L3A.
HOT DIP GALVANISED TO
B.5 729 AFTER FABRICATION

14 DIA
STRIP

t 365

LOm8 MS STRIP

CORNER WALL (DIAGONAL I 1


COMM CODE 232525 I

I I 3Ri vo
WALL BRACKETS
I
I I I E. 202
2 SLGTS 1Lx 75,

2 HOLES 1L DIA
/,-- .
I
MATERIAL
‘D’IRON PIN. MILD STEEL HOT DIP GALVANISED TO ES.729
HUMP PIN - STAINLESS STEEL

HOLE -
DEBURRE

116 DIAJ f

22 DIA

16 DIA

FOR DETAIL
SEE DRG
E 268

70 LO I
- 3
6

I TE M ‘8’
ITEM-A'
PIN 8 HUMP PIN
‘D’ IRON BRACKET
COMM CODE 23klOO
COMM CODE 23LOO5

LV D-IRON
-- -

‘186

- --
-o--
-_ -18 0
- -4.-

3
l-w

-- . -- +

LV L”
i
- -.- --_ _ _ .- _--
I’ -

MATERIAL
LtJx6 MILD STEEL FLAT BS L360 GRADE
L3A, HOT DIP GALVANISED TO BS 729
AFTER FABRICATION.

i E 207
22 DIA HOLE
I EARTH)
f
I
I -1.

ITEM x TIE STRAP lc0~~00lT~ cooE 236678)

2100
\
.--- IL30
--.--___---- .~__ _ - ..~~-___ -
_. _ _.- 1050 __._ --.- --.. --
~~.. -----

4 670
_ __ - --- -. ---. -
I I I

I ::
---. _ .-_

<3 iz

\-3 HOLES 22 DIA

-w-M
---.- +EzL - ti

~__.._ _..-
!
_ _-- .--- - -. ..-. -__-
_ _ _ ___. --.
-. __ __- ~-~ .~ -- -. ---- -- -__ --I
ITEM ‘ti ~~JTERMEDIATE (c0Mt4001Ty CODE 2331351 AS ESI DRG b3gsOl
7 HOLES 22 DIA.-
5 IIOLES 22 OIA -
1 1 I __-
L.-III - -IiL ________ -__--- \ --- -- _----T------------ ----- -- ts

-- -.820
100x 75xtO BS U A STEEL TO BS 4360
J GRAOE L3A HOT LliP GALVANISEOTOBS 72g
,yIo

ITEM ii SECTION ANGLE (COMMODITY CODE 2331LOl AS ES1 DR6 139502

ALL HOLES 22 OIA ALL HOLES 22 MA-/


I 1 I
___------- ---------- ______--_------

- _-_ ----- -.+ .+-.

9uJ d
.,@jo- ..-
- -7;b&..- .v
_ .___ _ I__ 1950 -- ~. -.-
.~. 2050 _- .- ..--: 2 - -7 -9
150r75x 10 BSUA SrEEL I.360 folrronos bdorr galvonlsmg (unlrrs
GRADE L3A HOI DIP GALVANISED l thwwrr stotod I -
ITEM’B’TERMINAL i COMMODITY CODE 2331451 Dlmrnsions up to and mcludlng 5Onm
ro 85 723 2 trim
AS ES1 DRG. 439503 ,I over SOmm ? znm
Hole d~omelrrs up to and lncludlng lOawn ? 0 h
” ovtr tomm : lmm
Atter golvontslng holes must pars o pt~g 90~4
0 5 1m01lrr than nom~nol dnamttrr at halt
-T-

III
1630

IInI
L3 HOLES 22 DIA

IIIII
--L

n
0
3
I
0

n
0
0
m

-al--
W
b
L
l-

3 Ne 22 DIA. HOLE
/-

4 No* 24 DIAHOLE
/-

1
I-I
1.

I
.
I- r f’
!U .
.
I
.
I e
U I
I
, c

.
c
1
/I I
/ IIII ’
I
I

Iy I I

L l-i.:
P. ;

104
1

4,,A.
MATERIAL: 125x75~10 ANGLE. BS4360 GRADE 43A
COMMODITY CODE 233150
l

ALL STEEL TO BE HOT DIP GALVANISED


TO B.S.729 AFTER FABRICATION.

33 kV b 11 kV. HEAVY CONSTRUCTION.


(SINGLE INTERMEDIATE POLE)
1
2134
t-.. --- -- ---. - - ._- ._-.. 1713 _. .-I-. ___ .___ _. -- -- .-. --__--.- _ .-- 1
lb59
- __-_.-~--- --
.x.qi.q I !
IO
I ! !
ODln
Im n-4
I.. -4m
mm
af-
N

l-l-
m
75 190 75
r 24 DIA. HOLE

+-cl E226

24 DIA. HOLE
/--

3 No- MZOX 270 LDNG TIE BOLTS’


%T E224

THREADED 75 EACH END


L EACH WITH 4 NUTS
AND TWO WASHERS.

24 DIA. HOLE 1

MATERIAL: ROLLED STEEL ANGLE - BSb360 GRADE A3A


SECTION -125~75x10
CDMMDDITY CODE - 233160 - ( COMPLETE itSSEMBLY 1
NOTFS 1 ALL HOLES 22 DIA. EXCEPT WHERE OTHERWISE SPECIFIED.
2 TO BE SUPPLIED ASSEMBLED WITH GALVANISED WZOr 50
BOLTSNUTS AND FLAT WASHERS AS NECESSARY.
3 ALL STEEL TO BE’HOT DIP’ GALVANISED TO WITHSTAND
TESTS TO LS.729 AFTER FABRICATION.

I I I ‘;I”:yc;; ~p”1~7-”
LINE CROSSARM AND A?-OYLD Iy

I 1 I LINE DEVIATIONS OVER 30’ SCALE : N.T. 5.


’ 33 kV. L 11 kV. HEAVY CONSTRUCTION. DRG No.
(‘H’ ANGLE SECTION)
E217
*owaL SCM74
I
WEB REMOVED FOR WEB REMOVED FOR

540

loltrancts hfort 9ol”onlrln9 IunIts


othtrwlst slottd I -
Dlmtnrlonr up to and mcludlng 5Omn 2 Imm
8, ovtr SOmm ! 2mm
Holt d~omtltrr up to and includq 1Omm : 3 km
u ovtr 1omll t lm

*fttr 9olvonls~ng holts must pass o pug gougt


0 5 smolltr than nomlnal d8omtftr of hoIt
Crossarm ’
Llf t 1ng Hole
.

\ To be Cut and
Welded.

ITEM ITEM B

I 22mm Dia-
Hole

I 22 x 50mm
i

/iQ, Slot. i

Lo 30
A
VIEW A-,
NOTES--
YTTENSI~NS IN MM. NOT TO SCALE.
2 70 x 70 ~10 BSEA. MILD STEEL TO
BS L360, GRADE 13A. HOT DIP
GALVANISED TO 85.729.
3 TO BE SUPPLIED AS A SET COMPRISING
l- ITEM A, l-ITEM B. TO BE BUNDLED
WITH NON- RUSTING BANDING.
L COMMODITY CODE: 233020.0
5 SEE SECTION 2, O/H LINE MANUAL.

DETAIL OF SLOTS

FORllL INTERMEDIATE CROSSARM.


/
ITEM ‘A’ i 1
?50 686 - 178

_-_-----------_-_---__________( “,-------- .o
ITEM’& L

MATERIAL ROLLED STEEL ANGLE 50x50~8


TO BS L360 GRADE L3A

CROSSARM SUPPORT

~--~~--~-------------~----~~~-~~-~~-~-------~~----- urr:.+
ITEM ‘c’
!
1OLO
I- I

Totrroncrr brtorr 9olvonlstn9 lunlrss


othwrlsr stotrd I -
Dtnrns~ons up to one includlnp 5Grm : 1nm
MATERIAL ROLLED STEEL ANGLE LOxLOx .* ovrr samal ? 2nm
TO BS C360 GRADE L3 A Wolr daamrtrrs uo to and mludmg 1Orm : 9 Snn
u ovrr 1oem :1mh
SUPPORT STRUT I
Attrr golron~slng
ID 5 gmillrr
holrs
then-nomtnol
musr
diomrtrr
Doss 0
ot
mug
hotr
goupl ‘II

TO BE SUPPLIED AS A SET NOTES: 1 ALL KJIMENSIONS IN MILLIMETRES.


COMPRISING : 1 - ITEM A, 2. AU STEEL TO BE’HOT DIP’GALVANISED
I-ITEM 6 AND 2-ITEM C TO BS 729 AFTER FABRICATION
BUNDLED WITH ZINC PLATED 3. AU HOLES 22 mm DIA
OR OTHER NON-RUSTING BANDING.
COMMODITY CODE : 233052.0

D SUPPORT STRUT
\
.-___.-.--.-.-.- 40

2HOLES 22DIA.DRlLLEDTOTEMPLATE

MATERIAL:-
COMM.CODE 233520 40 x 40x 6 B.S.U.A.
:olcrancrs betorr palranlslnp (unless MILO STEEL TO B.S.4360
othwrbse slate4 1 - GRADE 43A HOT DIP
Dimensions up to and mclud1n9 SoIlm GALVANISED TO B.S.729
over 50mm AFTER FABRICATION
m
0
m

.-

!
HOLES.

MATERIAL:
6mm STEEL TO BS L360 GRADE L3A
HOT DIP GALVANISED To B 5 729

COMMODITY COOE : 232580

POLE BOX BRACKET FOR


SINGLE POLE MOUNTING.
Ml6 x 30mm Hexagonal head stainless
steel screw modified as follows -
a. Head machined 7mm thick
ed and reamed to suit b. Centre drilled 8mm. dla.clearance
% .dla.p~n toleranced Complete wtth full nut
fine series to B.S. 4186 OR
Stainless steel hexagon stock bar
to B.S.6105

-Screwed Ml6 2mm pitch


(Coarse pitch series)

COMM.CODE 233610

ITEM 1. SHEAR PIN CARRIER MATERIAL:- STAINLESS STEEL


TO 8.5 6105. 20FF THUS
SCALE.-FULL SIZE

- 80--.--- . - -. - - 10

375
!_
,r--L r-r
-_- i- 1 -- _ ZI’ 0,
/.
\, /
\
‘\ T,3
~
3x 45' Chamfer
See enlarged detail'\ 5 Radius

ITEM 2. SHEAR PIN


60'
SCALE -FULL SIZE
‘H------Y

MATERIAL:-STAINLESS STEEL 303 GRAB


1
10 TO B.S.6105. 1OFF THUS
jo
- In
12!
0
I"

ENLARGED DETAIL
At root of waist SCALE-FOUR TIMES ACTUAL SIZE
0.5 mm radius COMM. CODE 233612
I I I I

AND CARRIER FOR


NTAINMENT DEVICE
490 O/A I
I
35 65 250 I 100 I

'18 dia. \ 22dla ‘24dla. ’ 2Gdia.

ITEM 1 - TOP FLAT


Material. 80 x 10 x 490 long

L25 O/A

_-..--- -- - -
- 9
4
22 dla " 24d Ia “j 2 4 d I a

ITEM 2 -BOTTOM FLAT


Material 80 xijx L25 long

Notes
1 SteelworK to B 5 L360 Grade A

2 Flar sectlons shall conform to B 5 6722

3 Material to be Hot Gapped galvanised In


accordance wlrh B 5 729 after fabrlcatton

CCIMM. COGE 233600

I \
I ,

1 1 ! FLATS FOR FAILURE I


I 4 6
, CONTAINMENT DEVICE
/
I ::.\ j " A.EI 2L-6-91 --.: I -
.“-I,‘E;. 0” ,, .
--F--E3 Qr A.Q@ 17-7-91
--$ .-- - .- I Ei-ii A
i,,,; ,?'-.'.? A4
I
ITEM ‘A’ - I -=lL DIA. SLOT

-------- -:- II 7 ----- - -1

+ lg i 60 j 16 kd 19 c
1 , 152

NOTE
3 REWIRED FOR EACH
INSTALLATION.

76 76
MATERIAL.
152 75~50x6 R.S. ANGir HO’
. DIP GALVANISED TO BS 729
I--

SURGE DIVERTER MOU tJTI NG BRACKET

COMMODITY CODE : 235215


-. . . . e . e .-

i I

I
22 DIA.
HOLE
1 22 DIA.

CENTRE PHASE STAND OFF BRACKET FOR 11L TERMINAL POLE

MATERIAL 125 s 75 ~8 R S ANGLE TO B S.


L360 GRADE 43A. HOT DIF
GALVANISED TO BS 729
COMMODITY CODE :235220

I 3B 16-E-79 THE EAST MIDLANDS ELECTRICITY BOARD DRAWN


n74CED
BV jYMPj
CY I .. 1
18-U-77
‘I
28mm tlm HEADQUARTERS
CHECKED BY bs1E.j 30. 8. 77
Was 26mm APPROVED SV] JL 1 I& -f/-f;
On ltrm ‘d
19.5-8i Al !I-5-79 SURGE DIVERTER MOUNTINGS ,SCALE: NTS
ORG. No.
NOTES 1TEM.B. R S FOR 1lkV OVERHEAD LINES.
AFIENLED ANGLE SIZE
E 255
ADUEL 50674
tmrnrlons up to and mciualng 5Omn :lmm 1

50
4 httrr golvontsmg holrs must POSS o Lug 9oupr
I
I
/

=.
n /

--- -
- -*_-_ -
.- __-.- --- -
_ _-.. -- ._-
__ _ -- .- - -
--
_---~ - -- ._
-- ___- -
--.-. -.

13

,----1L @

Ia- /,;
\\.s-/ - .- -. ---22 rj

MATERIAL
STEEL TO BS L360 GRADE WA
HOT DIP GALVANISED TO 95729
!

COMM CODE 232591 ALL DIMENSIONS IN MILLIMETRES

I I

I
SUPPORT BRACKET
PILOT INSULATOR
MATERIAL - BROWN GLAZED PORCELAIN

,SCALE DRG rue


, , 1 I ’ l----I BCBBIN ‘.- ! ATr;, ccc ;y
c, I w ,iNES
E. 301
SECTION ON “A-A-

I’----. 4
,

0:
I
r-1 i-s

LEAD FIXING
,

m,
m, COACH SCREW
W1
1

! -- -1
L -‘A- GlHLET POINT

C
\

L I
\
\ I
I
I I
I \
I \

TYPICAL
PLAN COACHSCREW HEAD
MATERIAL : BROWN GLAZED PORCELAIN
METAL FIXING SCREWS: SCREW To
BE OF MILD STEEL 28 33 TON OUALITY MINIMUM To BE
COMPLETELY GALVANISED TO BS 5 29 SHAPE OF THE HEAD POkTlON IS LEFT
TO MANUFACTURER, PROVIDED THE COUPLETED SERVICE INSULATOR WILL
COMPLY WITH THE MECHANICAL TESTS SPECIFIED BELOW. EXPOSED
PORTION To BE A CLEAN CUT ‘WOOD SCREW’ THROUGHOUT ITS LENGTH
WITH GIMLET POINT. SCREW To BE FIXED INTO PORCELAIN BY POURING
MOLTEN LEAD ALLOY INTO THE PRE-HEATED PORCELAIN.
TESTS-MECHANICAL TEST. MINIMUM FAILING LOAD ON COMPLETE INSULATOR MOUNTED AS IN
SERVICE DIRECT PULL IN LINE WITH SCREW - 4 KN
LATERAL PULL AT RIGHT ANGLES - 2.5 KN
NOTE : FOR WOOD FIXING DRILL 6 DIA. PILOT HOLE
COMMODITY CODE : 234806

COACHSCREW SERVICE INSULATOR

Ol.Llo
,".‘,,ID I E.302
91061
25 RADIUS 18 DIP, HOLE

AS DUG E269

16 DIA COTTER PIN


8 WASHER

---_
-
-L -
-
11 RAOIUS -
& --\ \ 25 RADIUS

A SSEHBLY TO BE SlIPPLIED ASSEHBLEC

MATERIAL MILD STEEL BS L360 GRAOE L3A HOT DIP GALkANISED TO BS 729

COMM COOE - 236200

91061
500
-!
16mm BALL t SHANK

22 DIA

III
NOTES
1. ALL DIMENSIONS ARE GIVEN IN mm. NOT TO SCALE
2. STEEL TO BS 4360. GRADE 43A. HOT DIP GALVANISED TO B.S.729
3. IN ACCORDANCE WfTH FIGURE 7. B.S. 3288: PART 2: 1977 EXCEPT
FOR LENGTH DIMENSION CHANGE FROM 235 TO 500 mm

COMMODITY CODE : 23L705.0


27

-t

,+ 8 RAD.
x \

- .-.. --• --.. --


INSIDE DIA. 123

MATERIAL :- No- 1 SW.G HARD DRAWN ALUMINIUM ( CONDITION H-6 I

COMM CODE 236L,63 - 0 = 1 PAIR

RE-DRAWN HEADQUARTERS CWECKEDBV 0 WI 1- 3-78


.-ROVED 8Y JML 1 1 .3

I I I 33 kV POST INSULATOR SCALE 1 : 2


DRG No.
STIRRUP E 320
31.LW
,u.I LID 9106
:3MM CODE 236L30 >

SD PLAN
ELEVATION

MATERIAL - No 3 SWG HARD DRAWN ALUMINIUM i CONDITION HB)

- ------ __ ,” yy
L
A-OVLD mr PDBjlL 1 .80

’ 11 KV PIN INSULATOR STIRRUP mSCALE


nRT
. lun
FOR ALUMINIUM CONDUCTORS j E 321
MATERIAL,-No 3 SWG HARD DRA\hlN
ALUMINIUM ( CONDITION H8 )

COMM CODE 236LOO


- OI).Wk
1 I I BV
!/ LhGBkxk Electricity
‘,E HEADQUARTERS
TRACEDBY

4wROVED
AEB
i"ECrEO8r

erpDB
ss
9.1-w
10 1-8c

lL.1.80

I I 1 ’ STIRRUP FOR ANGLE POSITIONS .SCALE 3Rci ho.

FOR S.C.A OR SILMALEC CONDUCTORS E 322


i01.‘ID
I” K,L,D 9106
.

1
6’ I

MATERIAL - No 1 SWG HARD DRAWN ALUMINIUM ( CONDITION H8 )

COMM CODE 236L66


on***IV
,, LZkatdGm EIectricim TRACEDBY AEB 9. 1.80 ,
‘, r HEADOUARTERS C*LcKEDB~ s s 13-1-83

. 33 kV POST INSULATOR STIRRUP ::L:D’vPDB ‘L-1.8o


I DRG.No.
I ‘- (FOR TAYLOR TUNNICLIFFE
INSULATORS) E 323
01.,IB
,“.‘,LTB 9106L
Lightly

MATERIAL--
Smm or Sswg (5.38)
Hard Drawn Copper

I
:OMM CODE .- 236470
l-’

,, /SSQ 122tiM Electricity


,E Headquarters

-11 I& PIN INSULATOR STIRRUP


, I 7
=I I
I
t=l
I I I FOR COPPER
DRAWBYJH M 12 .6 8~
CONDUCTORS
SCALE- 1 2 ICLASS-

3 APPROVEDBY]
CmocEDlWlGR
TTWXDBY -I-
HBH 13
--- 6 SL
8~. E 32TM
AF63ov79
160 i MATERIALS :
STEEL TO 6.5. L360
110 25 . GRADE L3A HOT DIP
I GALVANISED TO B.S.729

’ EDGE CHAMFERED
ON BOTH SIDES

I 12
I
1 I
0 I ! I I
JIIT I I , ; (7 1
I I

ITEM ‘A’ TERMINATING STRAP


(COMMODITY COOE 2366701

16mm BALL AND SHANK

235

ITEM ‘B’ INSULATOR HOOK 8.5 3288 REF. L/88


COMMODITY CODE 23L701

hEA OFFICE
APPENDIX 3 MISCELLANEOUS TOWER DRAWINGS

DRG TITLE

E270 TEE PLATE (FOR 132kV TOWERS).

E510 STATUTORY SAFETY NOTICE FOR STEEL TOWERS.

E511 DETAILS OF CiRCUIT IDENTIFICATION, PHASE 6. TOWER


NUMBER PLATES. FOR TOWERS WITH KEYED FLAG
BRACKETS.

OHL RANUAL - VOLUME 2


APPENDICES - PRINTED 17/10/90
ERED %RAD.

MATERI AL -
2 NO ~16 )‘I(:4 STRENGTH BOLTS, - STEEL TO %.S L360 GRADE L3L
5Omm LONi r:UTS. LOCKNUTS 8 HOT DIP GALVANISED T3
WASHERS .EL,JIRED B.S. 729 AFTER FABRICATION

REFER TO BLAW KNOX


-I l/i’ l- DRG. Nqs XM 1631-L9
XM 1217-Ll
SECTION X,-X'

---.- DIG N” WAS E316 \pUt’i ljzl<V. IUWtK3)


EXTENDED EZ?O
TO ! ‘/*’ tHAMFLKA&
0;O’,’s
OI.LID
I"EL
,10 911 16E
3
NGEd OF DEATH
.I.
-::
.:
-.
-
._
LIVE WIRES
KEEP AWAY
IN EMERGENCY
Phone 0800 626 555
EAST MIDLANDS
ELECTRICITY
11 ( /,PXB, 45FA j

DETAILS OF CIRCUIT IDENTIFICATION.


PHASE L TOWER NUMBER PLATES

1, -- _ -.. r -- I
-“,
f.7 II i j
-1 !
Distribution Business

APPENDIX 4 GUIDE TO
COMMODITY CODE

Database Ref: 59 File Ref: Commidit Feb Manual Name: Overhead Line Manual
2001V2.doc Vol.2

Version Prepared by Approved by Issue Date


1 Tony Haggis See Database 02/2001
East Midlands Electricity Appendix 4 Guide To Commodity Code
Overhead Line Manual Vol.2

Revision Log For Appendix 4 Guide To Commodity Code

Changes made in version 1

Section Notes about the change

File Ref: Commidit Feb 2001V2.doc Page 2 of 4 Version: 1


East Midlands Electricity Appendix 4 Guide To Commodity Code
Overhead Line Manual Vol.2

APPENDIX 4 GUIDE TO COMMODITY CODES

The table below may be of help to staff trying to locate a particular Commodity Code for an
item of Overhead Line plant or equipment, it denotes the first two digits of the Commodity
Code together with a brief description of the area covered.

07 Aluminium Based Conductors ACSR HDA Stranded Bunched Flexible


08 Copper Conductors ABC
14 LV Service Cut-Outs, LV Pole Mounted Fuse Mounts, LV Contact Shrouds
15 LV Fuse Carriers and Fuses
16 llkV Fuses and Links 19 Fusewires
22 Wood Poles
23 Overhead Line Pole Hardware
25 Tower Hardware
26 26 Overhead Line Joints and Connectors
28 132kV Joints and Connectors
29 ABC Fittings
38 HV Switches
39 Cabinets, Switchgear Oils and Greases
49 Seals
50 Substation Security Locks Etc Fencing
51 General Hardware
53 Meter Boards, Cable Jointing Materials
54 Cable Connectors
55 Shrink Kits and Tapes
57 Clothing
58 Tooling

File Ref: Commidit Feb 2001V2.doc Page 3 of 4 Version: 1


East Midlands Electricity Appendix 4 Guide To Commodity Code
Overhead Line Manual Vol.2

This Page Is Intentionally Blank

File Ref: Commidit Feb 2001V2.doc Page 4 of 4 Version: 1

Vous aimerez peut-être aussi