Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
accept any compensations for personal injury, material damage or capital disadvantages.
PROGRAMMABLE INDICATOR
SET
ENDA
EI141
1 - Supply Voltage
230VAC...230V AC
24VAC.....24V AC
SM...........9-30V DC / 7-24V AC
TECHNICAL SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature 0 ... +50C/-25 ... +70C (with no icing)
80% up to 31C decreasing linearly 50% at 40C.
Max. relative humidity
According to EN 60529
Front panel : IP65
Rated pollution degree
Rare panel : IP20
Height
Max. 2000m
Do not use the device in locations subject to corrosive and flammable gases.
up to date: 03072010, modification reserved and can be change any time previous notice !
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Wiring
Date retention
EMC
Safety requirements
Input type
0-1V DC voltage
0-10V DC voltage
0-20mA DC current
4-20mA DC current
1.1V
14V
25mA
25mA
Input empedance
Approx. 11kW (terminal voltage limits: min. = -2V, max. = 30V)
Approx. 11kW (terminal voltage limits: min. = -2V, max. = 30V)
Approx. 5W (applicable terminal voltage is max. 50mA.)
Approx. 5W (applicable terminal voltage is max. 50mA.)
In the current measurement mode input impedance is 5W. Therefore, in the current measurement mode, any voltage input
should not be connected to the input terminals. Otherwise, the device will be broken down. To change the input type from
voltage to a current measurement mode while the device is operating, first, leave out the voltage inputs. Then, change
input type to one of the current measurement modes.
HOUSING
Housing type
Dimensions
Weight
Enclosure material
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
1./3
EI141-E
TERMS
1) Measurement value, measurement unit, the minimum or the maximum measured values are
displayed in the run mode.
Parameter name, parameter value or a user defined unit is displayed in the programming mode.
PROGRAMMABLE INDICATOR
SET
ENDA
EI141
4) Used for selecting run and programming modes, adjusting parameters, displaying
measurement unit or making the minimum and the maximum measured values equal.
( 1 ) Digital display
Character height
( 2 ),( 3 ),( 4 ),( 5 ) Keypad
Micro switch
DIMENSIONS
Panel
77mm
35mm
PROGRAMMABLE INDICATOR
SET
ENDA
71mm
EI141
5mm
2
Flush mounting
clamp
Rubber
packing
Flush mounting
clamp
9 10 11 12
230V AC +10%-20%
50/60Hz 7VA
GND
+
INPUT
Panel
Panel cut-out
71mm
EI141-230VAC
PROGRAMMABLE INDICATOR
SN: XXXXXXXXX
29mm
CONNECTION DIAGRAM
ENDA EI141 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The shielding must be
grounded on the instrument side. During an installation, all of the cables that are connected to the device must be free of energy. The device
must be protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation temperature is not exceeded. All
input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. These cables should not be
close to the power cables or components. The installation and electrical connections must be carried on by a qualified staff and must be
according to the relevant locally applicable regulations.
NOTE :
SUPPLY :
184-253V AC 1
50/60Hz 7VA 2
Line
Neutral
Fuse
F 100 mA
250V AC
Switch
230V AC
Supply
Fuse should
be connected
Holding screw
0.4-0.5Nm
GND
+
INPUT
9 10 11 12
GND
9 10 11 12
24V DC 10%
7VA
GND
+
INPUT
SN: XXXXXXXXX
+
INPUT
SN: XXXXXXXXX
SN: XXXXXXXXX
9 10 11 12
Note : 1) Mains supply cords shall meet the requirements of IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument and it should be
easily accessible by the operator.
2./3
EI141-E
Bar.
&
SET
then,
then, by using
H.inp.
l.inp.
The minumum
measured value
then
SET
SET
Programming Mode
870
CAL.
NOTE 2
SET
SET
SET
C.err.
3./3
EI141-E
If the reference voltage or current applied to the input for calibration is too high or too low, this error message appears.
No
C.err.
C.end
Yes
CAL okey?
S.err.
ERROR MESSAGES
s.err.
CAL.
NOTE 3
D.Ca.s.
Uo.sc.
d.C.sc.
S.Cod.
SeCU.
If the difference between the reference voltages or currents applied for the calibration of H.inP. and L.inP. is lower than one
half of the full scale, this error message appears on the display.
For example: Assume that the selected input type is 0-1V. In this case, if the difference between the reference voltages
applied for calibration of H.inP.and L.inP. is lower than 0.5V, this error message appears.
C.end
then
SET
10.CA.
1.CA.
a.CAL.
Yes
Res.
SET
If first
and then
keys are
pressed together, the maximum and
the minumum measurement values
become equal to the measured value at
that time and the message res.
appears on display.
If no key is pressed within 20 seconds during programming mode data is stored automatically and the run
mode is entered. Alternatively the same function occurs by pressing
key and holding for 5 seconds
S.Cod.
CAL
CALokey?
okey?
The maximum
measured value
SET
1453
d.Cal.
Running Mode
SET
Evet
CAL.t.=U.nP.
H.sCl.
l.sCl.
d.pnt.
Cal.t.
U.opt.
NOTE 1
Unit
Hold
rate
dsp.C.
i.typ.
No
Measurement unit
If
key is pressed and held for 5
seconds programming mode is entered
SET
Measurement
value
SET
If first
and then
keys are
pressed together , measurement
unit appears. See Unit
parameter
For programming.
d.Cnf.
SET
1000
SET