SPECIFICATIONS

1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE
PHILIPPINE ELECTRICAL CODE (RA 7920) AND SHALL COMPLY THE RULES AND REGULATIONS OF THE
LOCAL GOVERNMENT AUTHORITIES CONCERNED IN THE ENFORCEMENT OF THE ELECTRICAL LAWS
AND ORDINANCE AND WITH THE REQUIREMENTS OF THE LOCAL ELECTRIC UTILITY COMPANY.
S1
2.ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE FOR PURPOSE AND LOCATIONS.
3.SERVICE ENTRANCES TO THE BUILDING SHALL BE 220V, SINGLE PHASE,60HZ, 2 WIRES
S1

S2
4.ALL WIRING INSTALLATIONS SHALL BE IN RIGID STEEL CONDUITS AND PVC CONDUITS
S1
5.ALL SPECIAL PURPOSE OUTLETS SHALL BE OF PROPER RATING, GROUNDING TYPE AND READILY
S2
1PB
2 ACCESSIBLE
S2 6.ADEQUATE AND EFFECTIVE EQUIPMENT GROUND SHALL BE PROVIDED
7.MINIMUM WIRING SIZE SHALL BE NO.14 THW FOR LIGHTING AND NO.12 THW FOR GENERAL POWER

B
AND CONVENIENCE OUTLETS

1P
1
S4
8.BRANCH CONDUITS SHALL NOT BE LOADED MORE THAN 80% OF RATING
9.MOUNTING HEIGHT SHALL BE:
CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . 0.60 ABOVE FLOOR
LIGHTING CONTROL SWITCHES . . . . . . . . . . 1.50 ABOVE FLOOR
PANEL BOARD . . . . . . . . . . . . . . . . . . . . . . . . . 1.50 ABOVE FLOOR
10. ALL FEEDERS AND BRANCH CIRCUITS SHALL BE INSTALLED AS INDICATED ON THE PLANS. INDIVIDUAL
S3 BRANCH CIRCUIT HOMERUNS SHALL NOT COMBINED IN THE SAME RACEWAY UNLESS NOTED OTHERWISE.
11. ALL WORKS HERE IN SHALL BE IN ACCORDANCE WITH STANDARD ENGINEERING PRACTICES

LEGEND:
POWER SERVICE ENTRANCE
2 LOWER GROUND FLOOR LIGHTING LAYOUT 1 GROUND FLOOR LIGHTING LAYOUT CABLE SERVICE ENTRANCE
E-01 SCALE 1 : 100 MTS E-01 SCALE 1 : 100 MTS
M ELECTRIC METER
SERVICE
CONVINIENCE OUTLET ENTRANCE
M
CO

LIGHTING OUTLET

S3 THREE(3) -WAY SWITCH


40AT/60AF
S2 TWO GANG SWITCH
S1 SINGLE SWITCH 1 2
20 AT 20 AT

1PB
3
1PB
LIGHT/POWER PANEL BOARD 3 4
4 20 AT 20 AT
# CIRCUIT HOMERUN
5 6
SPARE SPARE

2
22mm TW GROUND WIRE

LOAD SCHEDULE
PROTECTIVE DEVICES
CKT # LOAD DESCRIPTION TOTAL NOMINAL COMPUTED SIZE AND TYPE SIZE AND TYPE OF ELECTRODE GROUNDING SYSTEM
WATT VOLTAGE CURRENT OF CONDUCTOR CONDUIT
AT AF KAIC POLE
20 10 2 2-3.5 mm sq. THW 15mm PVC
1 LIGHTING OUTLET 700 230 3.04 A 20 RISER DIAGRAM
2 LIGHTING OUTLET 700 230 3.04 A 20 20 10 2 2-3.5 mm sq. THW 15mm PVC
800 20 2 2-3.5 mm sq. THHN
3 CONVENIENCE OUTLET 230 3.50 A 20 10 1-2.5 mm sq. THHN GRND 15mm PVC
700 20 2 2-3.5 mm sq. THHN
4 CONVENIENCE OUTLET 230 3.04 A 20 10 1-2.5 mm sq. THHN GRND 15mm PVC
5 SPARE 1000 230 4.35 A
6 SPARE 1000 230 4.35 A

TOTAL 4,800 W 20.88 A

COMPUTATION:
D.F. (DEMAND FACTOR) = 80% FIRST 3000 VOLT- AMPERE @100 D.F = 3000W
REMAINDER @35 % D.F. (1800VA x 35 %) = 630W
I
T = (20.88 x 0.8) + (8.00 x 0.25)
TOTAL = 3,630 W
= 24.95 AMPERE
I
T = 3,630 W + 8.0 (0.25)
USE : 220V
240 VOLT MOLDED CIRCUIT BREAKER = 18.50 AMPERE

USE :
SERVICE ENTRANCE 240
V, 60 HZ
SECONDARY RACK

LOCAL TELEPHONE ENTRANCE


SERVICE ENTRANCE CAP

LOCAL CABLE SERVICE


ENTRANCE

4 LOWER GROUND FLOOR POWER LAYOUT 2 COND-22.0mm SQ THW


E-01 SCALE 1 : 100 MTS
GROUND FLOOR POWER LAYOUT
IN 32mm dia uPVC PNS14
PIPE
3 PVC STRAP

E-01 SCALE 1 : 100 MTS


KWH METER

PB
TELEPHONE
TERMINAL BOX

PRIVATE POLE

NATURAL GROUND LINE

ARCHITECTURAL ENGINEERING Drawings and specifications and other contract documents PROJECT TITLE SHEET CONTENT Cadd/Drawn By: cta APPROVED BY: SHEET NO.
duly signed, stamped or sealed as instruments of service, are
the intellectual property and documents of the Architect, Date:
whether the object for which they are made is executed or Revised By:
not. It shall be unlawful for any person, to duplicate or to AS-BUILT COMMERCIAL & 3-BEDROOM
ARCHITECT
make copies of said documents for use in the repetition of
and for other projects or buildings, whether executed partly
or in whole, without the written consent of Architect or
RESIDENTIAL BUILDING AS ASHOWN Date:
Checked By:
MR.&MRS. NELSON ALIGUYON
OWNER
E-01
REG. NO. TIN NO. REG. NO. TIN NO.
PTR NO. PLACE PTR NO. PLACE author of said documents.
R.A. 9266 LOCATION: POTIA, ALFONSO LISTA, IFUGAO