Useful info for Cooling Tower:

I.D. of make-up tank = 73 mm


To calculate the make-up rate

Experiment 1:
Mass balance for System A and B:
Make up rate = Dry air flow rate x (humidity ratioout humidity ratioin)
Humidity ratio is obtained from psychrometric chart provided in the lab manual by
specifying the dry bulb and wet bulb temperature
Energy balance for System A:
Refer to Equation 2.5
Energy balance for System B:
Refer to Equation 2.8