8 7 6 5 4 3 2 1

43.75 TYP
CABINET FRONT 21.88 TYP
5.8
CABLE ENTRY PLATES
F
8.0 X 3.0 CUTOUT, 2X F

18.3 2X 10.25 12.00

2X 20.50 28.4
12.00

CABLE ENTRY PLATE .69


6.25 X 8.5 CUTOUT TYP
15.3 15.3 E
E
BOTTOM VENTILATION
TOP VIEW
SECTION A-A
BOTTOM VIEW

ISOMETRIC VIEW
D D
30.50 45.50

VENTILATION
LOUVERS

C
C 72.00

B
FRONT VIEW SIDE VIEW REAR VIEW B
A A

RACK NOTES:

1. EMPTY RACK WEIGHT: 600 LBS.


A 2. FULLY WELDED FRAME. MANUFACTURED FROM HEAVY GAUGE STEEL. UNLESS OTHERWISE SPECIFIED: 3233 W. Kingsley Rd.
Ste. 200 A
3. POWDER COATED WITH A CORROSION RESISTANT POWDER USING A DIMENSIONS ARE IN INCHES
TOLERANCES:
ESS ELECTRONIC SYSTEM SUPPORT
888-475-9292 www.ess.to
Garland, Texas 75041
PH. 972-272-2468
FIVE STAGE EMERSION PRETREATMENT PROCESS. ANGULAR: MACH .5 BEND 1
FAX 972-276-9844

4. BATTERIES CAN BE ACCESSED FROM FRONT, REAR, AND BOTH SIDES.


TWO PLACE DECIMAL .02
THREE PLACE DECIMAL .01
NAME DATE TITLE:
RNA 3-5-13 BATTERY RACK, 12V, FT,
5. CUSTOM DESIGNED PALLETS FOR SHIPPING ANYWHERE LOCALLY AND GLOBALLY (UPON REQUEST).
DRAWN

PROPRIETARY AND CONFIDENTIAL


PROJECTION:
CHECKED
384V, 4 TIER, TOP BRKR.
6. BATTERY RACK CAN BE MOVED WITH A NORMAL PALLET JACK FROM FRONT AND REAR. THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
MATERIAL
SEE NOTE 1
ENG APPR. SIZE DWG. NO. REV
7. STANDARD AND CUSTOM SPILL CONTAINMENT OPTIONS ARE AVAILABLE. ELECTRONIC SYSTEMS SUPPORT. ANY
REPRODUCTION IN PART OR AS A WHOLE
WITHOUT THE WRITTEN PERMISSION OF
ELECTRONIC SYSTMES SUPPORT IS USED ON
FINISH
SEE NOTE 2
MFG APPR.

Q.A.
D EFR44-SPEC A
PROHIBITED. DO NOT SCALE DRAWING SCALE: 1:12 WEIGHT: SHEET 1 OF 2
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1

BREAKER DETAIL CABINETPARTNUMBER


BATTERYRACKPARTNUMBERGUIDE
DESCRIPTION
EFR44 P A
OUTPUT TO UPS
BASEPARTNUMBER F
F + -
RACKHEIGHT

FROM BATTERY POS. RACKCOLOR

FROM BATTERY NEG.


BATTERYCONFIGURATIONTABLE
MAXIMUMNUMBEROF
BATTERYMANUFACTURER
GND BATTERIESPERRACK
E
E
TO BREAKER OR BREAKER EASTPENN
FUSE PANEL
BRACKET BATTERYMODEL HR5500ET
+ - 32
NUMBER HR7500ET

HEIGHTLEGEND COLORLEGEND
FROM BREAKER OPTIONS
- + - + - + - + + - + - + - +
FUSE OPTION HEIGHT(INCHES) AVAILABILITY **A=BLACK
- A=84.00 N/A B=BEIGE
TO B=82.00 N/A C=LIEBERTGRAY
32 31 30 29 28 27 26 25
24/48/120 VDC C=80.00 46WEEKS
SOUCE
D=MITSUBISHIBEIGE
FUSE PANEL

BLUE/YELLOW
BLUE/YELLOW
D
D=79.0 46WEEKS E=MGEWHITE D
TIER 4
E=78.7 46WEEKS F=TOSHIBABLACK

YELLOW
YELLOW
BLACK
F=78.4 46WEEKS
BLACK
G=GEWHITE
FROM BATTERY POS. + OUTPUT

BLUE
FUSE

BLUE
TERMINAL
- + - + - + - + - + - + - + - + G=78.0 46WEEKS H=LIEBERTBLACK
FROM BATTERY NEG. BLOCK - TO UPS H=77.3 46WEEKS J=EATONBLACK
24 23 22 21 20 19 18 17 J=76.8 46WEEKS K=TBD
GND. K=75.3 46WEEKS
TIER 3 L=75.0 46WEEKS **BLACKISESSSTANDARDCOLOR
M=74.8 46WEEKS ANDWILLBEINSTOCK**
N=73.5 46WEEKS LETTERSSTATING"TBD"AREOPEN
FORCUSTOMCOLORSNOTLISTED.
- + - + - + - + - + - + - + - + **P=72.0 INSTOCK C
C PLEASECONSULTWITHSALES
Q=71.7 46WEEKS STAFFFORFURTHERINFO.
16 15 14 13 12 11 10 9 R=70.9 46WEEKS
S=TBD N/A
NO
COMMON
NO
FROM UPS

NC

NC
COMMON
TO UPS

TIER 2 T=TBD N/A

**72.0ISTHESTANDARDHEIGHTFORTHEEFR54
- + - + - + - + - + - + - + - + RACKS.SHORTERHEIGHTSARENOTAVAILABLE**
PLEASECONSULTWITHSALESSTAFFFORFURTHER
INFO.
8 7 6 5 4 3 2 1

B TIER 1 TO UPS PART NUMBER GUIDE:


B

AUXILLARY CONTACTS LISTED APPLICABLE WHEN


BREAKER IS IN THE CLOSED (ON) POSITION 1. REFERENCE THE BATTERY PART NUMBER GUIDE TABLE WHEN ORDERING A RACK.
2. THE BASE NUMBER WILL ALWAYS BE THE SAME. HOWEVER, 2 ALPHA DIGITS WILL
FOLLOW THE BASE NUMBER INDICATING THE HEIGHT AND COLOR OF THE RACK.
3. REFERENCE THE "HEIGHT LEGEND" TABLE AND THE "COLOR LEGEND" TABLE IN ORDER
TO DETERMINE THE 2 ALPHA DIGITS NEEDED TO COMPLETE YOUR ORDER.
4. EXAMPLE: EFR44PA - THIS REPRESENTS A STANDARD EFR4 RACK, 72.0 INCH HEIGHT
WITH A POWDER COAT FINISH OF STANDARD BLACK.
ELECTRICAL NOTES:
1. ALL CABLES ARE UL LISTED.
2. ALL BREAKERS ARE UL RECOGNIZED.
A 3. ALL FUSES ARE UL RECOGNIZED, TYPE A50P, A70P OR EQUIVALENT. UNLESS OTHERWISE SPECIFIED: 3233 W. Kingsley Rd.
A
ALWAYS REPLACE WITH SAME TYPE OR ITS EQUIVALENT.
Ste. 200
ELECTRONIC SYSTEM SUPPORT
DIMENSIONS ARE IN INCHES
TOLERANCES:
ESS 888-475-9292 www.ess.to
Garland, Texas 75041
PH. 972-272-2468
4. TERMINAL BLOCKS ARE UL RECOGNIZED, 600V RATED. ANGULAR: MACH .5 BEND 1 FAX 972-276-9844

5. RACKS ARE SHIPPED WITH THE BREAKER IN THE TRIPPED POSITION.


TWO PLACE DECIMAL .02 NAME DATE TITLE:
THREE PLACE DECIMAL .01
DRAWN RNA 3-5-13
BATTERY RACK, 12V, FT,
6. RACK GROUND CONNECTION IS A 5/16-18 THREADED STUD. PROPRIETARY AND CONFIDENTIAL
PROJECTION:
CHECKED
384V, 4 TIER, TOP BRKR.

7. CABLES BETWEEN BATTERY RACK TO UNINTERRUPTIBLE POWER SUPPLY ARE OPTIONAL. THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
MATERIAL
SEE NOTE 1
ENG APPR. SIZE DWG. NO. REV
ELECTRONIC SYSTEMS SUPPORT. ANY
REPRODUCTION IN PART OR AS A WHOLE
WITHOUT THE WRITTEN PERMISSION OF
ELECTRONIC SYSTMES SUPPORT IS USED ON
FINISH
SEE NOTE 2
MFG APPR.

Q.A.
D EFR44-SPEC A
PROHIBITED. DO NOT SCALE DRAWING SCALE: 1:12 WEIGHT: SHEET 2 OF 2
8 7 6 5 4 3 2 1