Académique Documents
Professionnel Documents
Culture Documents
43.75 TYP
12.00
19.3 2X 9.50
2X 19.00 26.4
12.00
.69
CABLE ENTRY PLATE TYP
6.25 X 8.5 CUTOUT 15.3
15.3 E
E
SECTION A-A
ISOMETRIC VIEW
D D
28.50 45.50
VENTILATION
LOUVERS
C
C 72.00
B
B
A FRONT VIEW A SIDE VIEW REAR VIEW
RACK NOTES:
5. CUSTOM DESIGNED PALLETS FOR SHIPPING ANYWHERE LOCALLY AND GLOBALLY (UPON REQUEST).
TWO PLACE DECIMAL .02
THREE PLACE DECIMAL .01
NAME DATE TITLE:
RNA 3-5-13 BATTERY RACK, 12V, 384V,
6. BATTERY RACK CAN BE MOVED WITH A NORMAL PALLET JACK FROM FRONT AND REAR.
DRAWN
Q.A.
D EFR42-SPEC A
PROHIBITED. DO NOT SCALE DRAWING SCALE: 1:12 WEIGHT: SHEET 1 OF 2
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1
BATTERYRACKPARTNUMBERGUIDE
BREAKER DETAIL RACKPARTNUMBER DESCRIPTION
EFR42 P A
OUTPUT TO UPS
BASEPARTNUMBER
F
F + -
RACKHEIGHT
BATTERYCONFIGURATIONTABLE
MAXIMUMNUMBEROF
FROM BATTERY NEG. BATTERYMANUFACTURER
BATTERIESPERRACK
EASTPENN C&D FIAMM
GND HR3500ET UPS12355MFR
BATTERYMODEL
UPS12615MRF 12FLX700F 32
NUMBER HR5500ET
E TO BREAKER OR UPS12700MRF
E
FUSE PANEL
BREAKER
+ - BRACKET HEIGHTLEGEND COLORLEGEND
HEIGHT(INCHES) AVAILABILITY **A=BLACK
A=84.00 N/A B=BEIGE
FROM BREAKER OPTIONS
B=82.00 N/A C=LIEBERTGRAY
- + - + - + - + + - + - + - + C=80.00 46WEEKS D=MITSUBISHIBEIGE
-
TO
FUSE OPTION D=79.0 46WEEKS E=MGEWHITE
32 31 30 29 28 27 26 25 24/48/120 VDC E=78.7 46WEEKS
SOUCE
F=TOSHIBABLACK
BLUE/YELLOW
BLUE/YELLOW
F=78.4 46WEEKS G=GEWHITE
D D
TIER 4 FUSE PANEL G=78.0 46WEEKS H=LIEBERTBLACK
YELLOW
YELLOW
H=77.3 46WEEKS J=EATONBLACK
BLACK
BLACK
BLUE
BLUE
J=76.8 46WEEKS K=TBD
- + - + - + - + - + - + - + - + K=75.3 46WEEKS
FROM BATTERY POS. FUSE TERMINAL + OUTPUT
L=75.0 46WEEKS **BLACKISESSSTANDARDCOLOR
24 23 22 21 20 19 18 17 FROM BATTERY NEG. BLOCK - TO UPS M=74.8 46WEEKS ANDWILLBEINSTOCK**
LETTERSSTATING"TBD"AREOPEN
N=73.5 46WEEKS
FORCUSTOMCOLORSNOTLISTED.
TIER 3 GND. **P=72.0 INSTOCK PLEASECONSULTWITHSALES
Q=71.7 46WEEKS STAFFFORFURTHERINFO.
R=70.9 46WEEKS
- + - + - + - + - + - + - + - + S=TBD N/A C
C
T=TBD N/A
16 15 14 13 12 11 10 9
NO
COMMON
NO
FROM UPS
NC
NC
COMMON
TO UPS
**72.0ISTHESTANDARDHEIGHTFORTHEEFR42
TIER 2 RACK.SHORTERHEIGHTSARENOTAVAILABLE**
PLEASECONSULTWITHSALESSTAFFFORFURTHER
INFO.
- + - + - + - + - + - + - + - +
8 7 6 5 4 3 2 1
TO UPS
B TIER 1
AUXILLARY CONTACTS LISTED APPLICABLE WHEN B
1. REFERENCE THE BATTERY PART NUMBER GUIDE TABLE WHEN ORDERING A RACK.
2. THE BASE NUMBER WILL ALWAYS BE THE SAME. HOWEVER, 2 ALPHA DIGITS WILL
FOLLOW THE BASE NUMBER INDICATING THE HEIGHT AND COLOR OF THE RACK.
3. REFERENCE THE "HEIGHT LEGEND" TABLE AND THE "COLOR LEGEND" TABLE IN ORDER
TO DETERMINE THE 2 ALPHA DIGITS NEEDED TO COMPLETE YOUR ORDER.
4. EXAMPLE: EFR42PA - THIS REPRESENTS A STANDARD EFR42 RACK, 72.0 INCH HEIGHT
ELECTRICAL NOTES: WITH A POWDER COAT FINISH OF STANDARD BLACK.
5. THE EFR42 RACK IS NOT AVAILABLE IN OTHER HEIGHTS OTHER THAT 72.0 INCHES.
1. ALL CABLES ARE UL LISTED.
2. ALL BREAKERS ARE UL RECOGNIZED.
A
3. ALL FUSES ARE UL RECOGNIZED, TYPE A50P, A70P OR EQUIVALENT. UNLESS OTHERWISE SPECIFIED:
5. RACKS ARE SHIPPED WITH THE BREAKER IN THE TRIPPED POSITION. THREE PLACE DECIMAL .01
DRAWN RNA 3-5-13 BATTERY RACK, 12V, 384V,
6. RACK GROUND CONNECTION IS A 5/16-18 THREADED STUD.
PROJECTION:
PROPRIETARY AND CONFIDENTIAL CHECKED 4 TIER, TOP BRKR.
THE INFORMATION CONTAINED IN THIS MATERIAL
7. CABLES BETWEEN BATTERY RACK TO UNINTERRUPTIBLE POWER SUPPLY ARE OPTIONAL. SIZE DWG. NO. REV
DRAWING IS THE SOLE PROPERTY OF
ENG APPR.
SEE NOTE 1
ELECTRONIC SYSTEMS SUPPORT. ANY
REPRODUCTION IN PART OR AS A WHOLE
WITHOUT THE WRITTEN PERMISSION OF
ELECTRONIC SYSTMES SUPPORT IS USED ON
FINISH
SEE NOTE 2
MFG APPR.
Q.A.
D EFR42-SPEC A
PROHIBITED. DO NOT SCALE DRAWING SCALE: 1:12 WEIGHT: SHEET 2 OF 2
8 7 6 5 4 3 2 1