INCOMING LINE A : NA80 +MID16 PROTECTIONS

INPUTS

FROM DESCRIZIONE USE REF NOTS

Q152A CIRCUIT BREAKER CLOSED X BASE/IN1

Q152A CIRCUIT BREAKER OPEN X BASE/IN2

Q152A CIRCUIT BREAKER CONNECTED X MDI1/IN1

Q152A CIRCUIT BREAKER DRAWOUT X MDI1/IN2

S1 S1 SELECTOR TRIP X MID1/IN3

Q252A UPSTREAM SWITCHGEAR PERMISSION TO CLOSE X MID1/IN4

TCS TRIP COIL CIRCUIT OK (TCS) X MID1/IN5

VCA VOLTMETER CIRCUITS AVAILABLES X MID1/IN6

ACA AUXILIARY CIRCUITS AVAILABLES X MID1/IN7

SC SPRING CHARGED X MID1/IN8

S1 S1 NORMAL OPERATION X MID1/IN9

REMOTE CLOSING CMD REMOTE CLOSING COMMMAND (DCS) X MID1/IN10

K86 LOCKED PROTECTIONS TRIP X MID1/IN11

REMOTE OPENING CMD REMOTE OPENING COMMMAND (DCS) X MID1/IN12

AVAILABLE X MID1/IN13

AVAILABLE X MID1/IN14

AVAILABLE X MID1/IN15

AVAILABLE X MID1/IN16

OUTPUT

FROM DESCRIPTION USE REF NOTES

NA80 CONSENT TO CLOSE X BASE/K1

NA80 CLOSE CIRCUIT BREACKER X BASE/K2

NA80 OPEN CIRCUIT BREAKER X BASE/K3

NA80 K86 LOCKED (PROTECTIONS TRIP) X BASE/K4

NA80 AVAILABLE X BASE/K5

NA80 AVAILABLE X BASE/K6


90975-03-IMESA - IRAQ-ATS-I-O LIST REV 0 QMT-NGP 2 of 7

IMESA-IRAQ CONTRATTO

M.V. SWITCHGEAR
DOCUMENTO N
AUTOMATIC CHANGE-OVER & TRANSFER SYSTEM 90975-03-IMESA/IRAQ/ATS

SIGNALS

FROM DESCRIPTION USE REF NOTES

MMI-PLC C.B. CLOSED X BASE/L1

MMI-PLC C.B. AVAILABLE X BASE/L2

MMI-PLC K86 LOCKED X BASE/L3

MMI-PLC C.B. DRAWOUT X BASE/L4

MMI-PLC AVAILABLE X BASE/L5

PROTECTIONS

DESCRIZIONE USO RIF NOTE

NA80 OVERCURRENT 1^ STAGE I> X 51.S1

NA80 OVERCURRENT 2^ STAGE I> X 51.S2

NA80 SHORT CIRCUITS I>>> X 50

NA80 EARTH FAULT 1^STAGE Io> X 51N.S1

NA80 EARTH FAULT 2^STAGE Io>> X 51N.S2

NA80 EARTH FAULT 3^STAGE Io>>> X 50N

NA80 MIN. VOLTAGE X 27.S1

NA80 MIN. RESIDUAL VOLTAGE X 27.S2

NA80 OPERATING VOLTAGE X 59.S1


90975-03-IMESA - IRAQ-ATS-I-O LIST REV 0 QMT-NGP 3 of 7

IMESA-IRAQ CONTRATTO

M.V. SWITCHGEAR
DOCUMENTO N
AUTOMATIC CHANGE-OVER & TRANSFER SYSTEM 90975-03-IMESA/IRAQ/ATS

INCOMING LINE B : NA80 +MID16 PROTECTIONS

INPUTS

FROM DESCRIZIONE USE REF NOTS

Q152B CIRCUIT BREAKER CLOSED X BASE/IN1

Q152B CIRCUIT BREAKER OPEN X BASE/IN2

Q152B CIRCUIT BREAKER CONNECTED X MDI1/IN1

Q152B CIRCUIT BREAKER DRAWOUT X MDI1/IN2

S1 S1 SELECTOR TRIP X MID1/IN3

Q252B UPSTREAM SWITCHGEAR PERMISSION TO CLOSE X MID1/IN4

TCS TRIP COIL CIRCUIT OK (TCS) X MID1/IN5

VCA VOLTMETER CIRCUITS AVAILABLES X MID1/IN6

ACA AUXILIARY CIRCUITS AVAILABLES X MID1/IN7

SC SPRING CHARGED X MID1/IN8

S1 S1 NORMAL OPERATION X MID1/IN9

REMOTE CLOSING CMD REMOTE CLOSING COMMMAND (DCS) X MID1/IN10

K86 LOCKED PROTECTIONS TRIP X MID1/IN11

REMOTE OPENING CMD REMOTE OPENING COMMMAND (DCS) X MID1/IN12

AVAILABLE X MID1/IN13

AVAILABLE X MID1/IN14

AVAILABLE X MID1/IN15

AVAILABLE X MID1/IN16

OUTPUT

FROM DESCRIPTION USE REF NOTES

NA80 CONSENT TO CLOSE X BASE/K1

NA80 CLOSE CIRCUIT BREACKER X BASE/K2

NA80 OPEN CIRCUIT BREAKER X BASE/K3

NA80 K86 LOCKED (PROTECTIONS TRIP) X BASE/K4

NA80 AVAILABLE X BASE/K5

NA80 AVAILABLE X BASE/K6


90975-03-IMESA - IRAQ-ATS-I-O LIST REV 0 QMT-NGP 4 of 7

IMESA-IRAQ CONTRATTO

M.V. SWITCHGEAR
DOCUMENTO N
AUTOMATIC CHANGE-OVER & TRANSFER SYSTEM 90975-03-IMESA/IRAQ/ATS

SIGNALS

FROM DESCRIPTION USE REF NOTES

MMI-PLC C.B. CLOSED X BASE/L1

MMI-PLC C.B. AVAILABLE X BASE/L2

MMI-PLC K86 LOCKED X BASE/L3

MMI-PLC C.B. DRAWOUT X BASE/L4

MMI-PLC AVAILABLE X BASE/L5

PROTECTIONS

DESCRIZIONE USO RIF NOTE

NA80 OVERCURRENT 1^ STAGE I> X 51.S1

NA80 OVERCURRENT 2^ STAGE I> X 51.S2

NA80 SHORT CIRCUITS I>>> X 50

NA80 EARTH FAULT 1^STAGE Io> X 51N.S1

NA80 EARTH FAULT 2^STAGE Io>> X 51N.S2

NA80 EARTH FAULT 3^STAGE Io>>> X 50N

NA80 MIN. VOLTAGE X 27.S1

NA80 MIN. RESIDUAL VOLTAGE X 27.S2

NA80 OPERATING VOLTAGE X 59.S1


90975-03-IMESA - IRAQ-ATS-I-O LIST REV 0 QMT-NGP 5 of 7

IMESA-IRAQ CONTRATTO

M.V. SWITCHGEAR
DOCUMENTO N
AUTOMATIC CHANGE-OVER & TRANSFER SYSTEM 90975-03-IMESA/IRAQ/ATS

BUS-TIE NA21 PROTECTION + MID16

INPUTS

FROM DESCRIPTION USE REF NOTES

Q152C BUS-TIE CLOSED X BASE/IN1

Q152C BUS-TIE OPEN X BASE/IN2

Q152C BUS-TIE CONNECTED X MID1/IN1

Q152C BUS-TIE DRAWOUT X MID1/IN2

S1 S1 SELECTOR TRIP X MID1/IN3

TCS OK TRIP COIL CIRCUIT OK (TCS) X MID1/IN4

ACA AUXILIARY CIRCUITS AVAILABLE X MID1/IN5

SC SPRING CHARGED X MID1/IN6

F25 OK EXTERNAL SYNCROCHECK F25 OK X MID1/IN7

S43L/R S43 L/R IN LOCAL POSITION X MID1/IN8

S43T S43 T TRANSFER AUTORIZED X MID1/IN9

S43 AC S43 AC CHANGE-OVER AUTORIZED X MID1/IN10

S43L/R S43 L/R IN REMOTE POSITION X MID1/IN11

S10-A S10 SELECTOR TRANSFER A X MID1/IN12

S10-B S10 SELECTOR TRANSFER B X MID1/IN13

S10-C S10 SELECTOR TRANSFER C X MID1/IN14

S43RS S43RS SELECTOR RESET LOCKOUT X MID1/IN6

OUTPUT

FROM DESCRIPTIION USE REF NOTES

NA21 BUS TIE CLOSING COMMAND X BASE/K1

NA21 BUS-TIE CONSENT TO CLOSE X BASE/K2

NA21 BUS TIE OPENING COMMAND X BASE/K3

NA21 K86 LOCKED (PROTECTIONS TRIP) X BASE/K4

NA21 AVAILABLE X BASE/K5

NA21 AVAILABLE X BASE/K6


90975-03-IMESA - IRAQ-ATS-I-O LIST REV 0 QMT-NGP 6 of 7

IMESA-IRAQ CONTRATTO

M.V. SWITCHGEAR
DOCUMENTO N
AUTOMATIC CHANGE-OVER & TRANSFER SYSTEM 90975-03-IMESA/IRAQ/ATS

SIGNALS

FROM DESCRIPTION USE REF NOTES

MMI-PLC AUTOMATIC CHANGE-OVER READY X BASE/L1

MMI-PLC BUS-TIE AVAILABLE X BASE/L2

MMI-PLC AUTOMATIC CHANGE-OVER LOCKOUT X BASE/L3

MMI-PLC BUS-TIE DRAWOUT X BASE/L4

MMI-PLC AUTOMATIC CHANGE-OVER NOT AVSILABLE X BASE/L5

PROTECTIONS

FROM DESCRIPTION USE REF NOTES

NA21 OVERCURRENT 1^ STAGE I> X 51.S1

NA21 OVERCURRENT 2^ STAGE I> X 51.S2

NA21 SHORT CIRCUITS I>>> X 50

BUS-BAR VOLTAGE PROTECTION NV11B

INPUTS

FROM DESCRIPTION USE REF NOTES

BB-A TV BUS-BAR A / VOLTMETRICAL CIRCUITS AVAILABLE X BASE/IN1

BB-B TV BUS-BAR B / VOLTMETRICAL CIRCUITS AVAILABLE X BASE/IN2

OUTPUT

FROM DESCRIPTIION USE REF NOTES

NV11B ABSENCE VOLTAGE BUSBAR A X BASE/K1

NV11B ABSENCE RESIDUAL VOLTAGE BUSBAR A X BASE/K2

NV11B PRESENCE VOLTAGE BUSBAR A (OPERATIVE VOLTAGE) X BASE/K3

NV11B ABSENCE VOLTAGE BUSBAR B X BASE/K4

NV11B ABSENCE RESIDUAL VOLTAGE BUSBAR B X BASE/K5

NV11B PRESENCE VOLTAGE BUSBAR B (OPERATIVE VOLTAGE) X BASE/K6

SIGNALS

FROM DESCRIPTION USE REF NOTES

MMI-PLC ABSENCE VOLTAGE BUSBAR A X BASE/L1

MMI-PLC PRESENCE VOLTAGE BUSBAR A (OPERATIVE VOLTAGE) X BASE/L2

MMI-PLC ABSENCE VOLTAGE BUSBAR B X BASE/L3

MMI-PLC PRESENCE VOLTAGE BUSBAR B (OPERATIVE VOLTAGE) X BASE/L4

MMI-PLC AVAILABLE X BASE/L5


90975-03-IMESA - IRAQ-ATS-I-O LIST REV 0 QMT-NGP 7 of 7

IMESA-IRAQ CONTRATTO

M.V. SWITCHGEAR
DOCUMENTO N
AUTOMATIC CHANGE-OVER & TRANSFER SYSTEM 90975-03-IMESA/IRAQ/ATS

PROTECTIONS

FROM DESCRIPTION USE REF NOTES

NV11B ABSENCE VOLTAGE BUSBAR A 27.1/A < (75%) X 27.1/A

NV11B ABSENCE RESIDUAL VOLTAGE BUSBAR A 27.2/A < (75%) X 27.2/A

NV11B PRESENCE VOLTAGE BUSBAR A 59.1/A> (90%) X 59.1/A

NV11B ABSENCE VOLTAGE BUSBAR B 27.1/B < (75%) X 27.1/B

NV11B ABSENCE RESIDUAL VOLTAGE BUSBAR B 27.2/B < (75%) X 27.2/B

NV11B PRESENCE VOLTAGE BUSBAR B 59.1/B> (90%) X 59.1/B